| Sl No | Description | Qty | Unit | VOLTAS LIMITED L1 | ADS ENGINEERS L3 | Shinryo Suvidha Engineers India Pvt. Ltd. L2 |
|---|---|---|---|---|---|---|
| 1.00 | WATER-COOLED SCREW CHILLING UNIT (2W+1S):
Supply, installation, testing & commissioning of AHRI Certified Water-cooled semi- hermetic horizontal twin Screw chiller units with single/multiple compressor, insulated shell and tube type flooded evaporator, water- cooled condenser, VFD starter, control panel etc. The chiller will be precharged with CFC/HCFC free R134a Refrigerant gas. The drive motor suitable for 415V +/-5%, 3 phase , drive assembly, guard, etc. The chiller should be insulated as per manufacturers standard. Microprocessor based starters shall be unit mounted with protection for under voltage, over load, earth fault and single phasing etc. The quoted price shall also include necessary vibration isolators. Micro-processor based controls with alpha-numeric display in English for all operating parameters such as supply voltage, frequency, load current, chilled water inlet, chilled water outlet, condenser inlet and outlet temperature parameters, operating pressures etc., Power and control hardware including one point start-stop, protective Main Switch for electric motors, starters, safety features for under-voltage and over voltage, single phase preventer, trip circuit with sensing elements for HP/LP/Anti-freeze, chilled water temperature sensors. Compressor shall be able to unload down upto 25%. COP and IPLV of chiller shall be as per ECBC building code.Actual cooling capacity at designed conditions indicated below : (3 Nos. Working ) | 3 | Item | 36,43,509 ₹1,09,30,527 Lowest | 42,14,464 ₹1,26,43,392 | 43,41,590 ₹1,30,24,770 |
| 1.01a) Refrigeration capacity : 215 TR (Minimum) with unit mounted Micro-Processor based VFD Starer Panel b) Refrigerant: R134a c) Chilled water leaving temperature : 7.00 Deg C d) Chilled water entering temperature : 12.00 Deg C e) Fouling Factor Evaporator : 0.0001 FPS f) Condenser water entering temperature : 32.00 Deg C g) Condenser water leaving temperature : 36.00 Deg C h) Fouling Factor condensor : 0.00025 FPS i) IKW/TR at design condition shall not exceed 0.62 j) IPLV shall be as per latest BEE circular for ECBC building. k) COP of chiller shall be as per latest BEE circular for ECBC building. l) Selection sheet both in design condition as well as AHRI condition should be submitted along with the bid for evaluation.Scan copy of original certificates of AHRI & others should be uploaded. | ||||||
| 2.00 | PRIMARY CHILLED WATER PUMP
Supply, installation, testing and commissioning of End Suction Back Pull out Type Primary chilled water pump with CI casing, Bronze Impeller, mechanical seal along with TEFC pump motor, Each comprising of Suitable HP, TEFC Squirrel Cage Induction Motor with class "B" insulation, 1450 rpm speed, suitable for operatation on 415 ± 10% volts, 3 phase, 50 Hz A.C. supply. The Pump / Motor shall confirm to IE2 Standard(minimum) and Efficiency 70% minimum and minimum 580 USGPM flow rate under suitable head 15M (Min), mounted and aligned on a common MS base and, drain assy., vibration isolators, mounted on common MS base plate, complete as per specifications etc. as required. The pump motor shall have IP55, all weather proof. (2 Nos. Working + 1 No. StandBy) | 3 | Item | 1,15,960 ₹3,47,880 Lowest | 4,56,828 ₹13,70,484 | 1,57,059 ₹4,71,177 |
| 3.00 | SECONDARY CHILLED WATER PUMP
Supply, installation, testing and commissioning of End Suction Back Pull out Type Secondary chilled water pump with CI casing, Bronze Impeller, mechanical seal along with TEFC pump motor, Each comprising of Suitable HP, TEFC Squirrel Cage Induction Motor with class "B" insulation, 1450 rpm speed, suitable for operatation on 415 ± 10% volts, 3 phase, 50 Hz A.C. supply. The Pump / Motor shall confirm to IE2 Standard(minimum) and Efficiency 70% minimum and minimum 580 USGPM flow rate under suitable head 30M (Min), mounted and aligned on a common MS base and, drain assy., vibration isolators, mounted on common MS base plate, complete as per specifications etc. as required. The pump motor shall have IP55, all weather proof. Each pump shall have Variable Frequency Drive. (2 Nos. Working + 1 No. StandBy) | 3 | Set | 2,02,908 ₹6,08,724 Lowest | 4,56,828 ₹13,70,484 | 2,09,321 ₹6,27,963 |
| 3.01 | a)Variable Frequency Drive shall be complete with necessary fitting and wiring in a enclosure including locks arrangement (wall mounted/floor mounted) with display glass for reading. | 3 | Each | 71,661 ₹2,14,983 Lowest | 6,45,614 ₹19,36,842 | 1,17,839 ₹3,53,517 |
| 3.02 | b) SITC of Logic Controller for the pumps. | 1 | Each | 8,42,103 ₹8,42,103 | 67,956 ₹67,956 Lowest | 4,08,300 ₹4,08,300 |
| 3.03 | c) SITC of DP sensor for Variable Pumping application. | 2 | Each | 29,822 ₹59,644 | 15,530 ₹31,060 Lowest | 17,012 ₹34,024 |
| 3.04 | d) S&L of Signal cabling between DP Sensor to Pump Controller complete with protection. | 150 | Mtr. | 98 ₹14,700 Lowest | 188 ₹28,200 | 143 ₹21,450 |
| 4.00 | CONDENSER WATER PUMP
Supply, installation, testing and commissioning of End Suction Back Pull Out Type Condenser Water recirculating pump with CI casing, Bronze Impeller, Mechanical Seal along with TEFC pump motor, 1450 RPM suitable for 860 USGPM flow rate under suitable head 30M (Min) of operatation on 415 ± 10% volts, 3 phase, 50 Hz A.C. supply. The Pump / Motor shall confirm to IE2 Standard (minimum) and 70% Efficiency (Min) and complete mounted and aligned on a common MS base and, drain assy., vibration isolators complete in all respects. The pump motor shall have IP55, all weather proof. (2 Nos. Working + 1 No. StandBy) (On pick time 3Nos. will be working) | 3 | Each | 2,20,995 ₹6,62,985 Lowest | 5,69,123 ₹17,07,369 | 2,38,992 ₹7,16,976 |
| 5.00 | FRP INDUCED DRAFT COOLING TOWER
Supply, installation, testing and commissioning of FRP Induced Top air flow draft Counter Flow Cooling Tower suitable for 850USGPM water Air-conditioning Plant having following heat rejection capacity with FRP water basin, PVC fillings with integral louvers, ladder and drift eliminators complete with hot water basin either filled with spray nozzles or having self rotating sprinklers, statically and dynamically balanced axial flow type fan- direct driven or driven through reduction gear box with three phase, 415 ± 10% volts, 50 Hz. TEFC induction motor IE3 Standard, suction screen, make up-quick fill arrangement, overflow and drain connections with necessary valves and suitable inspection ladder, access arrangement for cooling tower interior, steel / mesonary supporting structure, anti-vibration mountings etc. complete as per specifications and as required. Each Cooling Tower Electrical part(motor) shall have IP65, all weather proof, isolator with lockable arrangement.
i) Heat rejection capacity - Suitable for 215 Tr. water cooled Air conditioning Plant.
ii) Design Wet Bulb Temperature: 28.5 Deg C
iii) Cooling Tower Inlet Temp: 36.0 Deg C
iv) Cooling Tower Outlet Temp: 32.0 Deg C
v) water circulating capacity: 850USGPM (2 Nos. Working + 1 No. StandBy) | 3 | Each | 5,06,690 ₹15,20,070 Lowest | 15,38,143 ₹46,14,429 | 6,27,421 ₹18,82,263 |
Tender Value
Refer Docs
EMD Value
₹10 L
Closing Date
21 Jul 2025, 2:00 pmClosed
Superintending Engineer PWD Electrical
Superintending Engineer PWD North Bengal Electrical Circle P.W.D Inspection Bungalow Annex Building 1ST Floor Kutchery Road Venus More Siliguri
Construction of Cancer Care Centers at North Bengal Medical College and Hospital Siliguri under North Bengal Construction Division S.I.T.C of central Air conditioning system
2025_WBPWD_847597_1
WBPWD/SENBEC/NIT-01/2025-2026
Open Tender
ELECTRICAL WORKS ORG
Item Rate
500 days
North Bengal Medical College and Hospital Siliguri
Please refer Tender documents.
5 documents required · 5 mandatory
₹10 L
Siliguri
1 Dec 2025
16 May 2025
23 Jul 2025
16 May 2025
21 Jul 2025
30 May 2025
27 May 2025
Amount
WATER-COOLED SCREW CHILLING UNIT (2W+1S): Supply, installation, testing & commissioning of AHRI Certified Water-cooled semi- hermetic horizontal twin Screw chiller units with single/multiple compressor, insulated shell and tube type flooded evaporator, water- cooled condenser, VFD starter, control panel etc. The chiller will be precharged with CFC/HCFC free R134a Refrigerant gas. The drive motor suitable for 415V +/-5%, 3 phase , drive assembly, guard, etc. The chiller should be insulated as per manufacturers standard. Microprocessor based starters shall be unit mounted with protection for under voltage, over load, earth fault and single phasing etc. The quoted price shall also include necessary vibration isolators. Micro-processor based controls with alpha-numeric display in English for all operating parameters such as supply voltage, frequency, load current, chilled water inlet, chilled water outlet, condenser inlet and outlet temperature parameters, operating pressures etc., Power and control hardware including one point start-stop, protective Main Switch for electric motors, starters, safety features for under-voltage and over voltage, single phase preventer, trip circuit with sensing elements for HP/LP/Anti-freeze, chilled water temperature sensors. Compressor shall be able to unload down upto 25%. COP and IPLV of chiller shall be as per ECBC building code.Actual cooling capacity at designed conditions indicated below : (3 Nos. Working )
PRIMARY CHILLED WATER PUMP Supply, installation, testing and commissioning of End Suction Back Pull out Type Primary chilled water pump with CI casing, Bronze Impeller, mechanical seal along with TEFC pump motor, Each comprising of Suitable HP, TEFC Squirrel Cage Induction Motor with class "B" insulation, 1450 rpm speed, suitable for operatation on 415 ± 10% volts, 3 phase, 50 Hz A.C. supply. The Pump / Motor shall confirm to IE2 Standard(minimum) and Efficiency 70% minimum and minimum 580 USGPM flow rate under suitable head 15M (Min), mounted and aligned on a common MS base and, drain assy., vibration isolators, mounted on common MS base plate, complete as per specifications etc. as required. The pump motor shall have IP55, all weather proof. (2 Nos. Working + 1 No. StandBy)
SECONDARY CHILLED WATER PUMP Supply, installation, testing and commissioning of End Suction Back Pull out Type Secondary chilled water pump with CI casing, Bronze Impeller, mechanical seal along with TEFC pump motor, Each comprising of Suitable HP, TEFC Squirrel Cage Induction Motor with class "B" insulation, 1450 rpm speed, suitable for operatation on 415 ± 10% volts, 3 phase, 50 Hz A.C. supply. The Pump / Motor shall confirm to IE2 Standard(minimum) and Efficiency 70% minimum and minimum 580 USGPM flow rate under suitable head 30M (Min), mounted and aligned on a common MS base and, drain assy., vibration isolators, mounted on common MS base plate, complete as per specifications etc. as required. The pump motor shall have IP55, all weather proof. Each pump shall have Variable Frequency Drive. (2 Nos. Working + 1 No. StandBy)
a)Variable Frequency Drive shall be complete with necessary fitting and wiring in a enclosure including locks arrangement (wall mounted/floor mounted) with display glass for reading.
b) SITC of Logic Controller for the pumps.
c) SITC of DP sensor for Variable Pumping application.
d) S&L of Signal cabling between DP Sensor to Pump Controller complete with protection.
CONDENSER WATER PUMP Supply, installation, testing and commissioning of End Suction Back Pull Out Type Condenser Water recirculating pump with CI casing, Bronze Impeller, Mechanical Seal along with TEFC pump motor, 1450 RPM suitable for 860 USGPM flow rate under suitable head 30M (Min) of operatation on 415 ± 10% volts, 3 phase, 50 Hz A.C. supply. The Pump / Motor shall confirm to IE2 Standard (minimum) and 70% Efficiency (Min) and complete mounted and aligned on a common MS base and, drain assy., vibration isolators complete in all respects. The pump motor shall have IP55, all weather proof. (2 Nos. Working + 1 No. StandBy) (On pick time 3Nos. will be working)
FRP INDUCED DRAFT COOLING TOWER Supply, installation, testing and commissioning of FRP Induced Top air flow draft Counter Flow Cooling Tower suitable for 850USGPM water Air-conditioning Plant having following heat rejection capacity with FRP water basin, PVC fillings with integral louvers, ladder and drift eliminators complete with hot water basin either filled with spray nozzles or having self rotating sprinklers, statically and dynamically balanced axial flow type fan- direct driven or driven through reduction gear box with three phase, 415 ± 10% volts, 50 Hz. TEFC induction motor IE3 Standard, suction screen, make up-quick fill arrangement, overflow and drain connections with necessary valves and suitable inspection ladder, access arrangement for cooling tower interior, steel / mesonary supporting structure, anti-vibration mountings etc. complete as per specifications and as required. Each Cooling Tower Electrical part(motor) shall have IP65, all weather proof, isolator with lockable arrangement. i) Heat rejection capacity - Suitable for 215 Tr. water cooled Air conditioning Plant. ii) Design Wet Bulb Temperature: 28.5 Deg C iii) Cooling Tower Inlet Temp: 36.0 Deg C iv) Cooling Tower Outlet Temp: 32.0 Deg C v) water circulating capacity: 850USGPM (2 Nos. Working + 1 No. StandBy)
S & F of Expansion tank, HDPE, 2000 Ltr, with 1 no float valves & 3 nos 50 mm dia butterfly valves with 50 mm thick thermocol insulation having 16 kg/cum density. [ For Makeup chilled water line].
S & F of Make Up Water Tank, HDPE, 3000 Ltr, with 1 no float valves & 3 nos 50 mm dia butterfly valves with 50 mm thick thermocol insulation having 16 kg/cum density. [ For Makeup Cooling Tower line].
Supply, Installation, Testing and commissioning of factory built floor mounted chilled water double skin type horizontal/vertical air handling units made of 25mm thick panels consisting of pre plasticized G.I. casing of thickness 0.8mm outside layer and 0.8 mm inside layer with polyurethane foam (PUF) insulation factory injected between them by injection moulding machine, complete with blower section with blower suitable for static pressure as required, minimum 2 bend GSS/PVC eliminators,cooling coil section with aluminium finned copper tubes (tubes thickness not less than 0.5mm) cooling coil of 6 row deep, filter section with 50mm thick metal viscous/ washable synthetic type air prefilters & fine filter, belt drive package with TEFC drive motor of efficiency class IE3 suitable for 415 + 10% volts, 50Hz, 3 Phase AC supply suitably designed for varialbe frequency drive applications, drain connections, stainless steel (18G) drain pan with PUF insulation, 150 mm dia. dial type pressure gauges (2 nos.)and industrial type thermometers (2 nos.) at the inlet and outlet of coil, auto purge valve wherever required, necessary vibration isolation arrangement etc. complete as per specification and of following capacities. (As per item no- 16.26 of DSR 2022)
Cooling capacity - 20400 CMH, 65 mm static pressure (For Gr. Floor EMERGENCY WARD+NURSE STATION, DAYCARE CHEMO UNIT, CORRIDOR)
Cooling capacity - 23800 CMH, 65 mm static pressure (For Gr. Floor WAITING HALL RADIO THERAPY, PREPARATION-RECOVERY, TUMOR BOARD ROOM, RADIATION ONCO, MEDICAL PHYSICIST)
Cooling capacity - 13600 CMH, 65 mm static pressure (For Gr. Floor WAITING SEMI STERILE ZONE + CORRIDOR (BESIDE OF MRI) + OPG + USG + MAMOGRAPHY)
Cooling capacity - 15300 CMH, 65 mm static pressure (For 1st Floor OPD-9 TO 16 + WAITING AREA)
Cooling capacity - 11900 CMH, 65 mm static pressure (For 1st Floor OPD-1 TO 8 + WAITING AREA)
Cooling capacity - 15300 CMH, 65 mm static pressure (For 2nd Floor 17Beded Medical Onco - Left + 17Beded Medical Onco - Right + COUNSELING ROOM + NAVIGATION ROOM + CORRIDOR)
Cooling capacity - 15300 CMH, 65 mm static pressure (For 2nd Floor 17Beded Daycare ward - Left + 17Beded Daycare ward - Right + DOCTORS LOUNGE-3& 4 + CORRIDOR)
Cooling capacity - 17000 CMH, 65 mm static pressure (For 3rd Floor 17 BEDDED ONCOLOGY WARD-1 + 17 BEDDED ONCOLOGY WARD-2 + CORRIDOR)
Cooling capacity - 17000 CMH, 65 mm static pressure (For 3rd Floor 17 BEDDED ONCOLOGY WARD-3 + 17 BEDDED ONCOLOGY WARD-4 + CORRIDOR)
CEILING SUSPENDED AIR HANDLING UNITS SITC of following Ceiling Suspended Modular Construction Double Skinned Air Handling Units (65 mm S.P.)with recommended Fresh Air arrangement each consisting of the following and having 25mm thick PUF insulated extruded Aluminium section frame construction: a) Fan Section backward / forward curve. The AHU shall consist of 1 no. Centrifugal Blower with 2 nos TEFC Squirell cage induction motor IE3 Standard (1W+1S) b) 6 Rows deep Coil (0.41 mm thick) with washable Pre-filters with efficiency 90% down to 10 microns. c) Set of Microvee Fine Filters with efficiency of 95% down to 5 Microns. d) TEFC sq,Cage Induction Motor. e) SS Drain Pan. The AHU shall be complete with VFD.The VFD shall be of IP20 rating. f) Inner skin - 0.63 mm thick plain GI sheet g) outer skin - 0.63 mm thick pre coated GI sheet
Cooling capacity - 2500 CFM, 65 mm static pressure (For Gr. Floor SPECT CT & CONSOLE)
Cooling capacity - 2500 CFM, 65 mm static pressure (For Gr. Floor PET CT & CONSOLE)
Cooling capacity - 2500 CFM, 65 mm static pressure (For Gr. Floor BRANCHYTHERAPY & CONSOLE)
Cooling capacity - 2100 CFM, 65 mm static pressure (For Gr. Floor CT SIMULATOR)
Cooling capacity - 2100 CFM, 65 mm static pressure (For Gr. Floor MRI)
Cooling capacity - 2100 CFM, 65 mm static pressure (For Gr. Floor CT Scan)
Cooling capacity - 9000 CFM, 65 mm static pressure (For Gr. Floor CORRIDOR NEAR PET CT + AD WASTE STR+DECONT + DOSE ADMIN AREA + PHARMACY + TECH. ROOM ETC)
Cooling capacity - 11000 CFM, 65 mm static pressure (For 1st Floor BIOCHEMISTRY LAB + IHC ROOM + HISTOPATHOLOGY LAB + RIGHT CORRIDOR+WAITING(BIO) + ETC)
Cooling capacity - 7000 CFM, 65 mm static pressure (For 1st Floor HLA + NAT + SEROLOGY + BLOOD STORE + RECX./ISSUE COUNTER + WAITING)
Cooling capacity - 5500 CFM, 65 mm static pressure (For 2nd Floor PALLIATIVE CARE WARD)
Cooling capacity - 1600 CFM, 65 mm static pressure (For 2nd Floor 4 BEDED ISOLATION WARD WITH NURSE STATION-1)
Cooling capacity - 1600 CFM, 65 mm static pressure (For 2nd Floor 4 BEDED ISOLATION WARD WITH NURSE STATION-2)
Cooling capacity - 6500 CFM, 65 mm static pressure (For 2nd Floor 13 BEDED RADIATION ONCOLOGY-Left + 12 BEDED RADIATION ONCOLOGY-Right + DOCTORS LOUNGE-1&2 + CORRIDOR)
Cooling capacity - 5500 CFM, 65 mm static pressure (For 3rd Floor ENGINNERING AND MEDICAL)
Cooling capacity - 8000 CFM, 65 mm static pressure (For 3rd Floor COUNSELLING ROOM + NEVIGATION ROOM + PATIENT PARTY WAITING+CORRID)
Cooling capacity - 7500 CFM, 65 mm static pressure (For 3rd Floor ICU + TRANSPLANT RECOVERY + SURGEON LOUNGE + CSSD ROOM ETC)
Cooling capacity - 7000 CFM, 65 mm static pressure (For 3rd Floor HDU + RMO + DOCTOR LOUNGE + CORRIDOR)
Cooling capacity - 7500 CFM, 65 mm static pressure (For 3rd Floor SUB STERILIZATION-1,2,3 + SEMI STERILE CORRIDOR + ANESTHETIST ROOM + PRE POST OP WARD )
FLOOR MOUNTED AIR HANDLING UNITS ( FOR OTs ): SITC of following Floor Mounted Modular Construction Double Skinned Air Handling Units (125 mm S.P.)with recommended Fresh Air arrangement each consisting of the following and having 40mm thick PUF insulated extruded Aluminium section frame construction: a) Fan Section backward / Forward curve fan.The AHU shall consist of 1 no. Centrifugal Blower with 2 nos TEFC Squirell cage induction motor IE3 Standard. (1W+1S) b) 8 Rows deep Cooling Coil with washable Pre-filters with efficiency 90% down to 10 microns. d) Mixing Chamber with return air and fresh air dampers. e) Set of Microvee Fine Filters with efficiency of 95% down to 5 Microns. f) TEFC sq,Cage Induction Motor. g) SS Drain Pan. The AHU shall be complete with VFD.The VFD shall be of IP20 rating. h) Inner skin - 0.63 mm thick plain GI sheet i) outer skin - 0.63 mm thick precoated GI sheet j)supply and fixing of UVGI. K)Thermal Break profile
Cooling capacity - 2500 CFM, 125 mm static pressure (For 3rd Floor Major OT-1, Major OT-2, Major OT-3,Major OT-4, Major OT-5, Major OT-6)
CEILING SUSPENDED AIR HANDLING UNITS ( FOR OTs ): SITC of following Ceiling Suspended Modular Construction Double Skinned Air Handling Units (125 mm S.P.)with recommended Fresh Air arrangement each consisting of the following and having 25mm thick PUF insulated extruded Aluminium section frame construction: a) Fan Section backward / Forward curve fan.The AHU shall consist of 1 no. Centrifugal Blower with 2 nos TEFC Squirell cage induction motor IE3 Standard.(1W+1S) b) 8 Rows deep Cooling Coil with washable Pre-filters with efficiency 90% down to 10 microns. d) Mixing Chamber with return air and fresh air dampers. e) Set of Microvee Fine Filters with efficiency of 95% down to 5 Microns. f) TEFC sq,Cage Induction Motor. g) SS Drain Pan. The AHU shall be complete with VFD.The VFD shall be of IP20 rating. h) Inner skin - 0.63 mm thick plain GI sheet i) outer skin - 0.63 mm thick precoated GI sheet j)supply and fixing of UVGI.
Cooling capacity - 2500 CFM, 125 mm static pressure (For 3rd Floor BONE MARROW TRANSPLANT OT)
SITC of Aluminium laminar bench with perforated sheet cover to accommodate inside HEPA filter bank along with necessary support as per standard of minimum 6 ft X 8ft dimension for OT Area with necessary flange joints of air duct shall have to be fixed with sealant adhesive to prevent leakage.
SITC of Cabinet inline Fan shall be of DIDW, forward/ backward curved centrifugal impeller fitted with maintenance free external rotor motor, belt / direct drive type. Impeller material shall be Galvanized Steel. Motor shall be suitable for external power supply 200~220V/50Hz/Single Phase.
500 CFM, 20MM Static for OT Exhaust
FAN COIL UNITS & CASSETTE UNITS SITC of ceiling concealed Fan Coil Units/ceiling suspended Cassette /Hi-wall Units with 2/3 rows deep Chilled Water Cooling coil, AC Motor and Fan assy with medium static, pre-filter, provision for fresh air port unit mounted and price also includes valve controller station includes 2 way on/off type Motorised valve, Digital tempeature controller , Ball Valve with and without strainer, Drain Pump for FCU, all respect for following capacities and quantities :
FAN COIL UNIT 1.0 TR / 400 CFM
FAN COIL UNIT 1.5 TR / 600 CFM
FAN COIL UNIT 2.0 TR / 800 CFM
FAN COIL UNIT 2.5 TR / 1000 CFM
FAN COIL UNIT 3.0 TR / 1200 CFM
FAN COIL UNIT 3.5 TR / 1400 CFM
4 Way CASSETTE UNIT 3.5 TR / 1400 CFM
CHILLED WATER PIPING WITH THERMAL INSULATION:- Supply, laying/fixing, testing and commissioning of following normal sizes of chilled water piping inside the building (with valves, strainers, gauges etc.) duly insulated with following closed cell elastomettric nitrile of minimun 45 Kg/cu m density, thermal conductivity 0.037 W/MK or better at 20 deg mean temperature class 'O' insulation applied by suitable adhesive complete including repairing of damage to building etc. as per specifications and as required complete in all respect. Note - - The pipes of sizes 150mm & below shall be M.S. 'C' class as per IS : 1239 and pipes size above 150 mm shall be welded black steel pipe heavy class as per IS:3589, from minimum 6.35 mm thick M.S. sheet for pipes upto 350mm dia and from minimum 7mm thick MS sheet for pipes of 400mm dia and above. (As per item no- 16.2 of DSR 2022)
25 mm dia pipe (50 mm thick insulation)
32 mm dia pipe (50 mm thick insulation)
40 mm dia pipe (50 mm thick insulation)
50 mm dia pipe (50 mm thick insulation)
65 mm dia pipe (50 mm thick insulation)
80 mm dia pipe (50 mm thick insulation)
100 mm dia pipe (50 mm thick insulation)
125 mm dia pipe (50 mm thick insulation)
150 mm dia pipe (50 mm thick insulation)
200 mm dia pipe (50 mm thick insulation)
BUTTERFLY VALVE SITC of Butterfly valve (Manual) with C.I. body SS Disc, Nitrile Rubber seal & O-Ring PN-16 pressure rating for chilled water/hot eater circulation as sepcifications. (As per item no- 16.7.1 of DSR 2022)
40 mm dia
50 mm dia
65 mm dia
125 mm dia
BALL VALVE S & F of Ball Valve
25 mm dia for Drain
32 mm dia for AHU
NON-RETURN VALVE SITC of Non - Return Valve with duel plate of CI body SS plates vulcanized NBR seal flanged end & PN 16 pressure rating for chilled/hot water circulation as specified. (As per item no- 16.7.3 of DSR 2022)
125 mm dia
Y-STRAINER MS SITC of Y-Strainer of Ductile CI body flange ends with Stainless Steel strainer for chilled/hot water circulation including insulation as specified. (As per item no- 16.7.4 of DSR 2022)
125 mm dia
BALANCING VALVE SITC of Balancing valve with built in measuring facility with CI body flanged construction with EPDM coated disc with long pitch with protected out pipe insulation & PN 16 pressure rating for chilled/hot water circulation as specified. (As per item no- 16.7.2 of DSR 2022)
32 mm dia
40 mm dia
50 mm dia
65 mm dia
125 mm dia
32 mm dia
40 mm dia
50 mm dia
65 mm dia
S&F of Rubber Bellow Expansion Joints
125 mm dia pipe
S & F of Auto Air Vent with Ball Valve
S & F of water Flow Switch
DIAL TYPE PRESSURE GAUGE S & F of the following Water line PRESSURE GAUGE as per following categories, sizes and quantities complete with providing flanges, nut-bolts, gasket and welding arrangements. Bourden type pressure gauges of 100mm dial of suitable range shall be provided.The water pressure gauge shall be made of stainless steel grade SS304. All the pressure gauges shall be complete with ball valves & SS Siphon and confirming to IS:3624.
DIAL TYPE THERMOMETER S & F of the following Water line INDUSTRIAL TYPE THERMOMETER, as per following categories, sizes and quantities complete with providing all fixing accessories.
CONDENSER WATER PIPING Supply, installation, testing and commissioning of condencer water pipes of following sizes of MS "C" class along with necessary clamps, vibration isolators and fittings such as bends, tees etc. but excluding valves, strainers, gauges etc. adequeately supported on figid supports duly painted/buried in ground excavation and refilling etc. as per specification and as required complete in all respect. Note:- The pipes size 150mm & below shall be M.S. 'C' class as per IS:1239 and pipes size above 150mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35mm thick M.S. sheet for pipes of 400mm dia and above. (As per item no- 16.10 of DSR 2022)
50 mm dia pipe
200 mm dia pipe
250 mm dia pipe
BUTTERFLY VALVE SITC of Butterfly valve (Manual) with C.I. body SS Disc, Nitrile Rubber seal & O-Ring PN-16 pressure rating for chilled water/hot eater circulation as sepcifications. (As per item no- 16.7.1 of DSR 2022)
200 mm dia
250 mm dia
BALL VALVE S & F of Ball Valve
25 mm dia for Drain
NON-RETURN VALVE SITC of Non - Return Valve with duel plate of CI body SS plates vulcanized NBR seal flanged end & PN 16 pressure rating for chilled/hot water circulation as specified. (As per item no- 16.7.3 of DSR 2022)
200 mm dia
Y-STRAINER MS SITC of Y-Strainer of Ductile CI body flange ends with Stainless Steel strainer for chilled/hot water circulation including insulation as specified. (As per item no- 16.7.4 of DSR 2022)
200 mm dia
BALANCING VALVE SITC of Balancing valve with built in measuring facility with CI body flanged construction with EPDM coated disc with long pitch with protected out pipe insulation & PN 16 pressure rating for chilled/hot water circulation as specified. (As per item no- 16.7.2 of DSR 2022)
200 mm dia
POT STRAINER MS S & F of the following Water line POT-Strainer as per following categories, sizes and quantities complete with providing flanges, nut-bolts, gasket and welding arrangements. Pot-strainer shall be fabricated out of Mild Steel.. The body shall be pressure tested at 16 Kg/cm² and shall be hot dip galvanized.
250 mm dia
S&F of Rubber Bellow Expansion Joints
200 mm dia pipe
S & F of water Flow Switch
DIAL TYPE PRESSURE GAUGE S & F of the following Water line PRESSURE GAUGE as per following categories, sizes and quantities complete with providing flanges, nut-bolts, gasket and welding arrangements. Bourden type pressure gauges of 100mm dial of suitable range shall be provided.The water pressure gauge shall be made of stainless steel grade SS304. All the pressure gauges shall be complete with ball valves & SS Siphon and confirming to IS:3624.
DIAL TYPE THERMOMETER S & F of the following Water line INDUSTRIAL TYPE THERMOMETER, as per following categories, sizes and quantities complete with providing all fixing accessories.
Supply, installation, balancing and commissioning of fabricated at site GSS sheet metal rectangular/ round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes,hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required. (As per item no- 16.12.1 of DSR 2022)
Thickness 0.63 mm Sheet
Thickness 0.80 mm Sheet
Thickness 1.00 mm Sheet
Supply and fixing of Flexible double Canvas connection in between each FCU & Supply Duct
Supply, installation, testing and commissioning of Supply Air Diffusers with volume control dampers.
Supply, installation, testing and commissioning of Return Air Diffusers without volume control dampers.
Supply, installation, testing and commissioning of Supply Air Grill with volume control dampers.
Supply, installation, testing and commissioning of Return Air Grill without volume control dampers.
Supply, installation, testing and commissioning of Opposed blade GI Duct Damper of 18 G GI sheet and frame.
Supply, installation, testing and commissioning of Fire Dampers in supply air duct/main branch and return air path as and where required of required sizes i/c control wiring,the damper shall be motorized and spring return so as to close the damper in the event of power failure automatically and open the same in case of power being restored. The spring return action shall be inbuilt mechanism and not externally mounted. The damper shall also be closed in the event of fire signal complete as required and as per spefications.(As per item no- 16.20 of DSR 2022)
Fire Damper
Actuator
DUCT ACCOUSTIC INSULATION Supply and fixing of acoustic lining of supply air duct and plenum with 10 mm thick class "O" open cell nitrile rubber insulation.
DUCT THREMAL INSULATION Supply and fixing of 19mm thick thickness duly laminated aluminum foil of mat finish closed cell nitrile rubber (Class “O”) insulation on supply & Return air duct after applying suitable adhesive for nitrile rubber.
UNDERDECK INSULATION Supply & Fixing of underdeck insulation with 50mm thick TF quality Expanded polysterene slab having density 16kg per CuM.
Supply and Laying of PVC Drain Pipe (Medium Class)with respective fittings ,proper supports and duly insulated with 6 mm thick closed cell nitrile rubber insulation.
25 mm Dia
32 mm Dia
40 mm Dia
SITC of wall mounted AHU Starter panel board having rigid and self supporting structure fabricated with 14 SWG CRCA sheet with M.S. angle iron frame. The panel is to be properly gasketed to prevent the dust & vermin. The panel consist of following accessorie :. Panel drawing & design must be approved by EIC
VFD Bypass AHU Starter Panel Wall Mounted Electrical Panel Board compatible with the proposed work consisting of 1 No Main Incoming MCB , 2 nos (1 Working + 1 StandBy) Outgoing feeder consisting of MCB (ABB/Siemens/L&T)along with Ammeter, ON/OFF indicating Lamps and DOL Starter for Air Handling Units. Panel shall have necessary arrangement for control valve and motorized fire damper Actuator. Panel shall have VFD Bypass arrangement.
VFD Bypass AHU Starter Panel for OT Area Wall Mounted Electrical Panel Board compatible with the proposed work consisting of 1 No Main Incoming MCB , 2 nos (1 Working + 1 StandBy) Outgoing feeder consisting of MCB (ABB/Siemens/L&T)along with Ammeter, ON/OFF indicating Lamps and DOL Starter for Air Handling Units, 1no power supply for heater & 1no power supply feeder for exhaust fan. Panel shall have necessary arrangement for control valve and motorized fire damper Actuator. Panel shall have VFD Bypass arrangement.
Supply and laying of XLPE insulated Aluminium Armoured Power Cable of following sizes.[Make Polycab / RR /KEI/ Havells/ Gloster as approved by E.I.C]
3.5C X 240 Sqmm
3C X 25 Sqmm
3C X 16 Sqmm
3C X 10 Sqmm
3C X 6 Sqmm
Supply and laying of XLPE insulated Copper Control Cables of following sizes.[Make Polycab / RR /KEI/ Havells/ Gloster as approved by E.I.C]
7C X 1.5 sq mm
3C X 1.5 sq mm
Supply & Fixing of perforated GI cable tray with perforation not more than 17.5% suspended from ceiling incl. S&F GI connector, MS support, bolts & nuts, steel fastener etc. as required of the following size. Incl.
100x50x1.25mm (18SWG)
200x50x1.25mm (18SWG)
600x50x1.25mm (18SWG)
S&F of earthing of galvanized (Hot Dip) MS flat 25 mm x 6 mm on wall/floor
S&F of Solid GI (Hot Dip) wire of size 8 SWG
Insulation for external ducting (OT) 75mm thick TF quality expanded polyesterent slap having density of 16Kg/CuM covered with vaporbarrier with chicken wireness and finished with 12mm sand cement plaster.
Charges for cutting wall/floor for entry of different sizes duck & pipe lines including mending good the damages including painting with wall matching colour and removal ofrubbish as per direction of EIC.
TERMS & CONDITIONS a. Rate should be quoted inclusive of all applicable taxes and Duty etc. b. The Agency must procure the materials from the Manufacturer / OEM or from their authorised sales channel so that the standard warranty / support of the Manufacturer / OEM becomes applicable to the products to be delivered and installed by them. c. Documents that authenticates such procurement from the Manufacturer / OEM or from their authorized sales channel and standard warranty / support should be sent from the e-mail of the Manufacturer / OEM / authorized sales channel to the e-mail of Engineer-in-Charge and hard copy of it to be submitted during execution, of work/submission of bill. d. The Agency will have to submit detailed design & drawing to the Engineer-in-charge. It has to be designed considering the situation that all the 3 (three) units may be required to run simultaneosly, if required. Necessary aproval of the Engineer-in -Charge is mandatory for every step of design, procurement, execution etc. e. Defect Liability period 1 (One) Year f. If any refurbished material is supplied and installed, penal action will be taken as per existing rules.
Shinryo Suvidha Engineers India Pvt. Ltd. (BID ID -6563029)
ADS ENGINEERS (BID ID -6745124)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
BOQ.xls
BOQ • 0.44 MB
Tenderdocument.pdf
Tender Documents • 0.32 MB
Tenderdocument_2.pdf
Tender Documents • 0.54 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .