Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹25.8 LAccepted-AOC COLABA MUMBAI | YAVATMAL | MAHARASHTRA | 445001 | L1 | Accepted-AOC LOWEST BIDDER WITH REASONABLE RATES | |
| 2 | L2₹26.5 L+₹41,800 (1.60%)Rejected-Finance NO 23 SECOND MAIN ROAD RAJAMMAL NAGAR MADAMBAKKAM CHENNAI 600 126 | CHENNAI | CHENGALPATTU | TAMIL NADU | 600126 | L2 | Rejected-Finance OTHER THAN LOWEST BIDDER | |
| 3 | L3₹27.3 L+₹1.2 L (4.70%)Rejected-AOC 11 SANJIV BAUG SOCIETY NEW SHARDA MANDIR ROAD PALDI AHMEDABAD GUJARAT 380007 | AHMADABAD | GUJARAT | 380007 | L3 | Rejected-AOC REJECTED DUE TO OTHER THAN LOWEST BIDDER |
Tender Value
Refer Docs
EMD Value
₹56,000
Closing Date
22 Apr 2021, 6:00 pmClosed
CWE (NW) Kochi
CWE (NW) Kochi PIN-682004
SPECIAL REPAIR/REPLACEMENT TO EXISTING GOODS LIFT 1000 KG CAPACITY AT OLD NPOL BUILDING (BLDG NO P-14 AND 14A) INCLUDING 03 YEARS COMPREHENSIVE MAINTENANCE NAVAL BASE KOCHI
2021_MES_432676_1
CWE(NW)KOCHI/81189
Open Tender
Civil Works
Item Rate
180 days
Kochi
Please refer Tender documents.
6 documents required · 6 mandatory
₹500
GE (NS) Kochi
₹56,000
Yes
7 May 2021
24 Mar 2021
24 Apr 2021
24 Mar 2021
22 Apr 2021
7 Apr 2021
24 Mar 2021 - 15 Apr 2021
Amount
SCHEDULE 'A' PART I
Dismantling existing old lift of capacity 1000 kg serving G+3 floors at old NPOL Building complete including car guide rail counterweight depositing drive machine with motor, control panels etc and depositing to MES store yard including making good the disturbed surfaces all as directed by Engineer-in-Charge
(d) FIXTURES/SIGNALS INSIDE CAR (Stainless steel car operating panel with following buttons and indications) : - Door open/door close buttons with symbol markings. Door hold button for service lifts, ARD operation audio/Visual indication in car,Emergency alarm button with bell symbol and the same should be at distinct distance from the call buttons. Emergency alarm button to be located along-with door open and close buttons at a height of 900 + 10 mm from floor level. Yellow pictogram to be provided, Alarm sound shall be siren type audible from at least 50 meters from the ground floor landing, Ventilation fan ON/OFF switch with auto switch off feature after 120 seconds lift at idle condition, Two position key operated attendant switch for with/without attendant operation, LED illuminated tactile braille buttons of micro motion type corresponding to the floors served. The push buttons to be of robust SS vandal resistant type, Three-way built in press and speak type with 1 master and 2 slave units in security room/control room. Additionally, wiring provision for connecting building EPABX with car phone with rechargeable batteries,16 segment, LED/Dot matrix car direction display and digital position indicators located at a conspicuous height above car door for passenger Lift (Bidder to provide inputs on car displays),
Emergency light with rechargeable sealed maintenance free battery with 30minute backup, Emergency alarm with rechargeable sealed maintenance free batteries rated for 30minute backup, Audio/visual over load warning indicator, Floor position voice announcement with back ground music. (e) LANDING INDICATORS : - Two landing buttons with position indicator in all floor,Chime on car (f) Voice announcements to announce the floor position, Multi beam infrared protection device to reverse the closing door in case of slight obstruction in the door way. (g) SAFETY FEATURES AND OTHER INCLUSIONS : - Fire man’s switch for the lifts at ground floor level. The lifts to have fire man mode – stage 1 and fire lift to be with stage 1 and 2, Multi beam infrared protection device to reverse the closing door in case of slight obstruction in the door way, Automatic phase reversal device, Overload, non-start and overload protection device, Spring buffers, Electro mechanical type safety governor for car, DO’s and Don’ts with emergency contact numbers engraved on a SS face plate displayed in the car as for safety instructions, Terminal and final limit switch provn for Over travel protection, Controller/driver/motor protection
Trip device for over current, under voltage and over voltage than the rated capacity +/- 10%, Motor over load/over torque, Instantaneous over current, Ground fault, Under voltage, Over voltage – 3 phase, Output & input phase loss, Phase reversal, Output short circuit , Over speed, Spike and surges. ARD battery operated with and including of any maintenance free batteries of suitable capacity and battery charger with optimum direction in start operation and requiring no human intervention, rescue clearing, power/system failure with latest IGBT power devices, Landing door to have 2 hour fire resistance rating. Car doors as per requirements, Intercum connection in Car and control room and also in security room., Provision of suitable cables along the travelling cable for fire detector and music inside the car, Provn of one car blower to be connected through power supply, Full height fascia plates and sill angles to be provided. Apron of min height 750 m to be provided at car side, epoxy coated MS pit ladder of height more than lift pit to be provided and securely fastened inside the pit, System memory should be retained in the event of power failure or disturbance. Lifts should not go in to correction mode or correction run to the lowest floor/highest floor to update its position and memory,Safe landing feature- If a car has stopped between floors due to some equipment malfunction, the controller checks the cause, and if it is considered safe to move the car, the car will move to the nearest floor at low speed and the door will open. Ascending over speed protection device, Unintended car movement protection device,Earth quake operation if required under lift act for Kochi region- Seismic sensors and auto isolation arrangement for safety & Counter weight derailment device or displacement switches to be provided. Other functions – anti nuisance, car call cancellation, next landing, bye pass, self levelling, door time adjustment, independent operation and return operation
Sl item No. 2 Contd/…. (m) Provision of hoist way and governors rope and governor. (n) Provision of new buffer spring as per manufacturers design. (o) Provision of battery operated alarm and emergency light through inverter of suitable capacity having power pack up for a period of minimum 30 minutes. (p) Drive- Geared with machine frame fixed in the machien room. (q) Over speed governor monitors the speed and triggers safety gears etc shall be installed in the machine room. Safety measures:- (i) Overload relays,(ii) Contactors and fuses (iii) Electrical terminals high quality,(iv) Limit switch with accessories on each doors/ cage (v) Gravity/ counter weight limit switches for top most position (vi) Break motor of suitable size with manned released arrangements (vii) Phase sequence corrected (viii) Lift should be fire resistance as specified in IS- 14665 Note: 1. The lifts are to be installed in existing lift shaft/lift-well of size 2660 mm(W) x2100 mm (D) and opening width of lift car shall be as per IS specifications or as directed by Engineer-in-charge . 2. Any addition/alteration cost required for the execution of new lift is deemed to be included in quoted rate. 3. The contractor shall note that this work shall be executed in pre occupied condition building and shall take care of all safety measures and avoid disturbance to occupants while carrying out the work. The contractor shall not dump any materials in the premises which may cause hindrance to user. 4. The work of lift design, supply installation testing and commissioning will be executed by the lift manufacturers as per the makes mentioned above in BOQ.The manufacturers of these lifts be (a) M/s Kone India (b) M/s Schindier India Pvt Ltd (c) M/s Kinetic Hyundai Elevator & Movement Technologies Ltd (d) M/s Hitachi Lifts India Pvt Ltd (e) M/s Mistubishi Elevator India Pvt Ltd (f) M/s Otis Elevators Company India Ltd (g) M/s Fujitech India Pvt Ltd (h) M/s Johnson Lifts Pvt Ltd (j) M/s Thyssenkrup Elevator India Pvt Ltd (k) M/s Omega elevators (l) M/s Hitachi Lifts India Pvt Ltd (m) M/s Escon Elevators Pvt Ltd (n) M/s LT Elevators Pvt Ltd (o) M/s IES Elevators 5. The OEM or the agency authorised to carry out maintenance of lifts by OEM as per Sch 'A' provisions and relevant items of BOQ will be permitted to undertake maintenance of lifts.
Supply and fixing for bulk head light fitting in lift shaft at each landing for maintenance in lift and controlled by single phase 06 Amps MCB complete with loop point wiring with 20mm MS conduit for light fitting including 15 watt LED buld for fittings all as specified and directed.
Materials and labour for earthing complete with galvanised iron earth plate electrode of size 600 mm x 600 mm x 6 mm thick, burried directly and vertically in ground, earth pit not less than 2.25 Mtr deep below ground level with top edge of the plate not less than 1.5 m below ground level connetced with and including galvanised strip of size 32 x 6 mm (Upto length of 7.5Mtr including) by means of nuts, bolts, check nuts and washers made of galvanised iron or steel earthing lead to be protected by galvanised iron pipe 40 mm bore (light grade) and other end connected to earthing test point or lightening arrestor or main controlling switch as directed including providing funnel with 20mm bore galvanised iron pipe (light grade), wire mesh, charcoal or coke and common salt in alternate layer of 15cm (compacted thickness) all round the earth electrode, concrete earth pit in PCC (1:3:6) type C-1 (with 20mm graded aggregate), 50mm thick precast RCC (1:2:4) cover slab (re-inforced with 8mm dia)including necessary earth work excavation complete all as specifed and directed.
Supply and fixing earth continuity GI strip 32mm x 6mm all as specified and as directed.
Supply and lay XLPE insulated,screened,PVC bedded,galvanised steel strip or wire armoud electrical cable 1100 volts of size along the wall/trench/roof having cross sectonal size of 3.5 core,35 sqmm with necessary supports with clamps and PVC pipes complete all as specified and drected.
Design, fabricate, erecting, testing commissioning LT panel board indoor type suitable for 3 phase 415 volts grade 4 wire, 50 Hz and type tested by CPRI, factory made and with latest fabrication and testing process comprising of power coating with suitable gasket to make it dust, vermin proof and general construction confirming to IS- 8623/ 93. The panel shall be made out of 2 mm thick CRCA sheet with front operated double door with industrial type locking arrangement and with sufficient ventilation and the enclosure shall be confirm to IP- 54. The panel shall be mounted on angle iron frame fabricated of angle iron or size 45x 45x 6mm thick of suitable shape and size and grouted on floor. The panel shall have sufficient space all around the accessories being accommodated the panel should have aluminium bus bar of appropriate size duly sleeved with colour code mounted on epoxy cylindrical type insulators with and including following accessories. (a) MCCB 160 Amps, 4 pole 35 KA, 50 Hz 415 V with ICU = 100% ICS- 01 No (As incomer) (b) MCCB 100 Amps, 4 pole 25 KA, 50 Hz 415 Volts- 01 No (As outgoing) (c) MCB SPN 63 Amps 240 Volts- 01 No (Out going for building light) (d) Digital type multi function meters to measure current voltage, frequency,Amp (e) Phase indicating lamps LED type, 230 Volts AC (make L&T or seimens) at the incomer of the unit to show the availability of three phase.
Total of Schedule 'A' Part I
Schedule 'A' Part II
All as per item No.2.01 above, but for Second year after expiry of defects liability period (ie for one year after completion of first year maintenance period vide item No.2.01 above)
All as per item No.2.01 above, but for Third year after expiry of defects liability period (ie for one year after completion of second year maintenance period vide item No.2.02 above)
Total of Part II
PREMIER ENGINEERING SYSTEMS
Omega Elevators
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .