Area manager (EnM), Lodna Area
Office of General Manager, Lodna Area.
Diversion of the part of Lodna- I, Lodna- II, Lodna- III, Jealgora-I and Jealgora-II feeders, under OB dump area of Patch-D, of Amalgamated Joyrampur Colliery, Lodna Area.
2026_BCCL_351469_1
BCCL/LA/ENM/F-19/25-26/140
Open Tender
Electrical and Maintenance Works
Percentage
45 days
Lodna Area
Please refer Tender documents.
7 documents required · 7 mandatory
₹2.0 L
11 Feb 2026
19 Jan 2026
5 Feb 2026
20 Jan 2026
4 Feb 2026
20 Jan 2026
20 Jan 2026 - 27 Jan 2026
Supply of Rail pole of 60/52 Kg 13 Meter length
Erection of Rail pole of 60/52 Kg 13 Meter length in cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size) foundation including excavation and refilling etc. as required.
Supplying and erection of 11 KV pin insulator complete with large steel head G.I. pin, nuts, washers etc. as required.
Supplying and erection of 11 KV disc insulator for 11 KV over head lines with galvanised insulator fittings, ball and socket type and complete with galvanised strain clamps, bolts, nuts, washers etc. as required
Supply and erection of G.I wire 8 SWG
Erection of G.I wire 8 SWG
Supply of AB switch Nominal Voltage 11 KV grade, Rated Voltage 12 KV, 1240 A, 3- Phase Outdoor Type offload disconnection in horizontal plane with earthing switch
Erection of AB switch Nominal Voltage 11 KV grade, Rated Voltage 12 KV, 1240 A, 3- Phase Outdoor Type offload disconnection in horizontal plane with earthing switch
Supplying of channel iron 75 mm X 40 mm X 6 mm (7.14 kg per metre) V shape cross arm for two 11 KV over head line conductors complete with 50 mm X 6mm M.S. flat iron clamps, bolts and nuts including drilling holes for insulator pins, bolts, nuts and washers etc (as per drawing) and painting with primer and finish paint as required
Supplying of two lengths of channel iron 75 mm X 40 mm X 6 mm (7.14 kg per metre) double pole cross arm for three wire 11KV over head line conductors complete with through bolts and nuts for clamping to the poles, 50 mm X 6 mm M.S. flats welded on one side to the channel iron and with bolts and nuts on the other side for tying the cross arms together, including drilling holes for insulator pins/ fittings, bolts, nuts and washers etc (as per drawing) and painting with primer and finish paint as required
Supplying of channel iron 75 mm X 40 mm X 6 mm (7.14 kg per metre) pole top bracket/ cross arm for single 11 KV over head line conductor complete with 50 mm X 6mm flat iron clamp, bolts, nuts and washers including drilling holes for insulator pins, bolts and nuts etc and painting with primer and finish paint as required
Supplying of 50 mm X 8 mm M.S. flat iron pole top bracket/ cross arm for single 11/22/33 KV over head line conductor complete with fixing clamps, bolts, nuts and washers drilling holes for insulator pins, bolts and nuts etc and painting with primer and finish paint as required
Erection of pole top/ straight two wire/ V shape two wire, angle iron/ channel iron, cross arm on steel tubular/ rail/ PCC pole for 11/22/33 KV as required
Erection of double pole 3 wire cross arm for 11KV/ 22KV/ 33 KV over head lines as required
Providing and fixing H.T. danger notice plate of 250 mm X 200 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required.
Supply of ACSR dog conductor
Erection of ACSR dog conductor including binding as required 1.2 KM+10% Sag= 3.96 KM = 1560.24 KG.
Supplying and erection of galvanised stay set for 11 KV over head lines complete with 19/ 20 mm dia X 1.8 metres long stay rod, anchor plate of size 45 cm X 45 cm X 7.5 mm thick, thimble, stay clamps, turn buckle ( 20 mm X 600 mm ), 7/ 4.00 mm dia G.I. stay wire and 11 KV strain insulator etc in cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size) foundation including excavation and refilling etc. as required.
Supply & Fitting of Craddle Guard
Total impact of GST for the purpose of CTC
stage.html
html • 0.02 MB
tech_bid_open.pdf
cancelled_1.pdf
pdf • 0.40 MB
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.05 MB
Tendernotice_1.pdf
PDF • 3.20 MB
BOQ_364230.xls
BOQ • 0.25 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .