Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹9.2 CrAccepted-AOC | ₹9.2 Cr | L1 | Accepted-AOC Lowest bidder |
| 2 | L2₹10.2 Cr+₹1.0 Cr (11.2%)Rejected-Finance | ₹10.2 Cr+₹1.0 Cr (11.2%) | L2 | Rejected-Finance other than Lowest Bidder |
| 3 | L3₹10.2 Cr+₹1.1 Cr (11.6%)Rejected-Finance | ₹10.2 Cr+₹1.1 Cr (11.6%) | L3 | Rejected-Finance other than Lowest Bidder |
| 4 | L4₹10.3 Cr+₹1.1 Cr (12.0%)Rejected-Finance | ₹10.3 Cr+₹1.1 Cr (12.0%) | L4 | Rejected-Finance other than Lowest Bidder |
| 5 | L5₹10.7 Cr+₹1.6 Cr (17.4%)Rejected-Finance | ₹10.7 Cr+₹1.6 Cr (17.4%) | L5 | Rejected-Finance other than Lowest Bidder |
Tender Value
₹10 Cr
EMD Value
₹8.3 L
Closing Date
30 Jul 2020, 6:00 pmClosed
Chief Engineer Navy Visakhapatnam
HQ Chief Engineer Navy, MES, Station Road, Visakhapatnam - PIN 530 004
Demolition/Reconstruction of Dock Yard Apprentice Hostel Building including Galley, Dining Hall and Hostel Superintendent MD Accn at Visakhapatnam
2020_MES_322375_1
CE Navy / VIZ / Token / 21 of 2019-2020
Open Tender
Civil Works
Lump-sum
730 days
Visakhapatnam
As per NIT criteria
8 documents required · 8 mandatory
₹3,000
Yes
Garrison Engineer (P) (N)
₹8.3 L
Yes
2 Sept 2020
11 Apr 2020
31 Jul 2020
11 Apr 2020
30 Jul 2020
24 Jul 2020
15 Apr 2020 - 25 Apr 2020
Amount
Schedule "A" Part – I to Schedule "A" Part – XV: NOTE: Schedule "A" Part – I to Part – XV are prepriced by MES. Bidders shall insert their Lumpsum amount in Green coloured field under Column - 6 only
Lumpsum price worked out by the contractor for "BUILDINGS & STRUCTURES", as listed in Schedule "A" Part – I
Lumpsum price worked out by the contractor for "SITE CLEARANCE / AREA DEVELOPMENT/EARTH WORK/EXCAVATION", as listed in Schedule "A" Part – II
Lumpsum price worked out by the contractor for "ROAD /PATH", as listed in Schedule "A" Part – III
Lumpsum price worked out by the contractor for "AREA DRAINAGE", as listed in Schedule "A" Part – IV
Lumpsum price worked out by the contractor for "SEWAGE DISPOSAL", as listed in Schedule "A" Part – V
Lumpsum price worked out by the contractor for "RAIN WATER HARVESTING", as listed in Schedule "A" Part – VI
Lumpsum price worked out by the contractor for "INTERNAL WATER SUPPLY", as listed in Schedule "A" Part – VII
Lumpsum price worked out by the contractor for "INTERNAL ELECTRIFICATION", as listed in Schedule "A" Part – VIII
Lumpsum price worked out by the contractor for "EXTERNAL WATER SUPPLY", as listed in Schedule "A" Part – IX
Lumpsum price worked out by the contractor for "EXTERNAL ELECTRIFICATION", as listed in Schedule "A" Part – X
Lumpsum price worked out by the contractor for "SOLAR WATER HEATER/COOLING APPLIANCES", as listed in Schedule "A" Part – XI
Lumpsum price worked out by the contractor for "PILE FOUNDATION", as listed in Schedule "A" Part – XII
Lumpsum price worked out by the contractor for "LIGHTENING PROTECTION", as listed in Schedule "A" Part – XIII
Lumpsum price worked out by the contractor for "FIRE FIGHTING SYSTEM", as listed in Schedule "A" Part – XIV
Lumpsum price worked out by the contractor for "DEMOLITION & DISMANTLING", as listed in Schedule "A" Part – XV
Schedule "A" Part - XVI [Miscellaneous Items] [Internal Water Supply,Internal Electrification, External Water Supply, External Electrification,Solar water heater/Cooling appliances,Pile foundation, Lightening protection, Fire Fighting System, Demolition and dismantling, Arboriculture, DG Set, Air Conditioning, Electric chimney]:
INTERNAL WATER SUPPLY
Supply and Fixing 15 mm bore fancy type chromium plated bib tap cast copper alloy with two ways bib taps with wall flanfe scewed for iron pipe or for brass ferrule complete all as specified and as directed.
Supply and Fixing fancy type health faucet 15 mm dia up to 1 mtr long (hand wash for EWC) 1st quality incl CP bracket to hold the faucet in wall all as per manufacturer instruction complete all as specified and as directed.
INTERNAL ELECTRIFICATION
Point wiring with 1.5 sqmm FRLS PVC insulated and unsheathed copper conductor multistranded 1100 volts grade, ISI marked drawn through and inculding non metallic PVC rigid concealed conduit and conduit accessories, medium grade ISI marked, concealed including provn of pressed steel terminal box of suitable size fabricated out of 1.5 mm thick GI sheet suitable for modular brackets as required at site for fixing Moduler switches, sockets, inculding one run of 1.5 sqmm PVC insulated unsheathed copper cable for earth continuity, connected to earth dolly complete all as specified and directed for one light/bell point controlled by one switch
Point wiring with 1.5 sqmm FRLS PVC insulated and unsheathed copper conductor multistranded 1100 volts grade, ISI marked drawn through and inculding non metallic PVC rigid concealed conduit and conduit accessories, medium grade, ISI marked, concaled including provn of pressed steel terminal box of suitable size fabricated out of 1.5 mm thick GI sheet of suitable for modular brackets as required at site for fixing Moduler switches, sockets, inculding one run of 1.5 sqmm PVC insulated unsheathed copper cable for earth continuity, connected to earth dolly complete all as specified and directed for one fan (ceiling/Wall/Ex.fan) point controlled by one switch.B38
Point wiring with 1.5 sqmm FRLS PVC insulated and unsheathed copper conductor multistranded 1100 volts grade, ISI marked drawn through and inculding non metallic PVC rigid concealed conduit and conduit accessories, medium grade, ISI marking, concaled including provn of pressed steel terminal box of suitable size fabricated out of 1.5 mm thick GI sheet of suitable for modular brackets as required at site for fixing Moduler switches, sockets, inculding one run of 1.5 sqmm PVC insulated unsheathed copper cable for earth continuity, connected to earth duly complete all as specified and directed for one 3 Pin socket outlet 5 amps socket on independent board.
Point wiring with 1.5 sqmm FRLS PVC insulated and unsheathed copper conductor multistranded 1100 volts grade, ISI marked drawn thorugh and inculding non metallic PVC rigid concealed conduit and conduit accessories, medium grade, ISI marked, concealed including provn of pressed steel terminal box of suitable size fabricated out of 1.5 mm thick GI sheet of suitable for modular brackets as required at site for fixing Moduler switches, sockets, inculding one run of 1.5 sqmm PVC insulated unsheathed copper cable for earth continuity, connected to earth dolly complete all as specified and directed for one 3 pin socket outlet 15 amps socket on independent board with 2.5 sqmm FRLS PVC wire and one run of 2.5 sqmm copper cable for earth continuty.
All as per above item here-in-before but controlled by two, two way switches complete all as specified and as directed.
S & F Energy efficient LED light fitting with tube minimum 1x 20 watt ,230V surface mounted LED batten type with extruded aluminium/CRCA housing and robust constrution with necessary acrylic cover as diffuser complete with mounting bracket etc including connecting up with twin core twisted flexible copper conductor cable with suitable size complete all as specified and as directed.
S & F Energy efficient LED light fitting with tube minimum 1 x 40 watt ,230V for trunking based solution for large open area with high ceiling with extruded aluminium/CRCA housing and robust constrution with necessary acrylic cover as diffuser complete with mounting bracket etc including connecting up with twin core twisted flexible copper conductor cable with suitable size complete all as specified
S & F Energy efficient LED ceiling light fitting minimum 08 watt , integral round shape , 230V surface mounted with necessary diffuser complete with mounting bracket etc including connecting up with twin core twisted flexible copper conductor cable with suitable size complete all as specified and as directed.
S & F Energy efficient LED light fitting with tube minimum 2'x2' ,36 watt ,230V ceiling light recessed mounting type including connecting up with twin core twisted flexible copper conductor cable with suitable size,(False ceiling light) complete all as specified and as directed.
S & F Energy efficient LED light fitting with tube minimum 1'x1' ,24 watt ,230V ceiling light recessed mounting type including connecting up with twin core twisted flexible copper conductor cable with suitable size,(False ceiling light) complete all as specified and as directed.
S & F LED Security light fitting with tube minimum 20 W New generation Energy saving &environmental friendly long life versatile pressure die cast aluminium luminiare with mid power LEDs as source and HF electronic driver pre wired with 1.5 Sq mm copper conductor cable upto connector including 2 Mtr long GI Tubing Med grade 32 mm dia bend to shape fixing on wall with suitable MS brackets complete all as specified and as directed.
S & F Flame proof LED tube light fitting 2x16 Watt or minimum lumen output not less than 3200 lumens, 240volts with complete drive complete all as specified and as directed.
Point wiring for flame proof fixtures/fittings with 1.5 sqmm FRLS PVC insulated and unsheathed copper conductor multistranded 1100 volts grade, ISI marking drawn through and including concealed stove enamelled steel metallic conduit and metal conduit accessories, medium grade, ISI marking, concealed , inculding one run of 1.5 sqmm PVC insulated unsheathed copper cable for earth continuity, connected to earth dolly complete all as specified and directed for one light /fan point controlled by one switch (for POL Store)
S & F ceiling fans AC single phase 230 V of size 1200 mm sweep with complete set with fixtures, 5 Star rating, metallic body complete all as specefied and directed.
S & F Exhaust fan 300 mm sweep or nearest size, metal body(Heavy duty), complete with louvers suitable for operation on 230 V AC, 50 Hz AC supply fixed on wall making opening,fixing and making good the disturbed surfaces etc complete all as spcified and as directed.
S & F Vertical on load MCCB TPN DB double 4 way 415V, 50Hz double door, IP 43 protection for incommer in and including 100 Amps MCCB with 200A rated bus bar for provision of MCCB as incommer and MCBc for outgoing circuits complete, fill empty with blanks, making good the disturbed area as per existing surface complete all as specefied and directed.
S & F Vertical on load MCCB TPN DB double 4 way 415V, 50Hz double door, IP 43 protection for incommer up to 125 amp with 200A rated bus bar for provision of MCCB as incommer and MCBc for outgoing circuits complete, fill empty with blanks, making good the disturbed area as per existing surface complete all as specefied and directed.
S & F Telephone jack with shutter glossy white RJ45 complete all as specefied and directed.
M&L for earthing complete with GI earth plate electrode 60cmX60cmX6mm thick, burried directly in ground (earth pit not less than 2.25 metres deep below ground level)with top edge of the plate not less than 1.5 metres below normal groundlevel, connected to GI earth lead wire 4.0mm dia by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No-3 of SSR Part-I connected to earthing test point all as specified or indicated including excavation and connected earth work in any type of soill, PCC 1:3:6 type C-1 as in pit, 20mm dia GI pipe medium grade for watering pipe, 15 mm bore GI medium grade earth lead protection pipe connected upto DBs, and suitable C.I top cover with handle, funnel, strainer,charcoal and testing on completion all as specified and directed. Note- Rate quoted deemed to be include excavation and earth work in any type of soil complete all as specefied and directed.
EXTERNAL WATER SUPPLY
M&L for valve chamber of internal size 750x750x750mm comprising of 50mm thick PCC 1:5:10 type E2 foundation, 200mm thick brick wall in CM 1:6, 15mm thick plastering in CM 1:4 internally and externally up to 50mm below GL,100mm thick PCC 1:3:6 type B1 as in copings,3mm thick MS sheet cover with suitable hinges and locking arrangement, painting steel surfaces with two coats of synthetic enamel paint over a coat of primerincluding necessary earth work and excavation in any type of soil complete all as specified and as directed.
Cutting existing steel tubing for necessary additions or alterations to be done in position without taking down and inserting T of 80 x 80 x 80 mm and Tee of 80 x 80 x 80 mm for tapping complete all as specified and as directed.
EXTERNAL ELECTRIFICATION
LT Panel board made out of CRCA sheet 3.15 mm thick Outdoor Pedestal type totally enclosed with front and rear opening, hinged doors with projected an raised platform of suitable size weather and water proof with necessary locking arrangements along with lugs, cable glands of various sizes for cables, danger notice plate, strickering of Switcher gear about termination of switch gear, and the nuts/ bolts etc used are to be made of rust proof material incl as per IS: 8623 Aluminium bus bar with heat proof colour code, insulators suitable for three phase and neutral four, wire LT AC, 50 Hz 415 V 800 A capacity complete with powder coating, necessary internal electric connection as required and provision of the following: Incoming: a) MCCB AC 3 Phase 415 V, 50Hz 4 pole 400 A capactiy 35kA with adjustable microprocessing released display type relays - 01 Nos Outgoing: b) MCCB AC 3 Phase 415 V, 50Hz 4 pole 315 A capactiy 35kA with adjustable type thermal and magnetic setting relays - 02 Nos( for bldg panel) c) MCCB AC 3 Phase 415 V, 50Hz 4 pole 63 A capactiy 25 kA with adjustable type thermal and magnetic setting relays - 02 Nos ( for STP) d) MCCB AC 3 Phase 415 V, 50Hz 4 pole 32 A capactiy 25kA with adjustable, microprocessing released display type relays - 02 Nos(for street light) e) LED Indicating Lamps for each phase with colour coed Red Yellow Blue for R, Y and B Phases f) Multifunctional Intelligent Panel Meter digital type for measuring Volts, Current, Hz, pf, power, energy, THD along with connected CTs
Supply & Fix and testing of Integral LED street light Luminaire 72 Watts, comprising of epoxy powder coated, Pressure die cast aluminium housing enclosed with glass cover in frame, with suitable size of bracket, nut and bolts, PVC insulated three core flexible cable of suitable size and length duly connected to light fitting complete including installation and testing complete all as specified and as directed.
Supply fix and testing of Loop in loop out box of FRP made with IP 65 protection of thermoplasic circuit breaker boxes with metric knockouts for cable entry and exit, Combi climate Cable Glands of IP 66/ IP 67 for cable entry and Grommets IP 65 for conduit for cable exit with MCB 6 Amps, 10 kA, C Curve Overload and Short Circuit protection, terminals as bus terminals for cable with necessary fixing arrangemets and with cable glands, etc complete all as specified and as directed.
Earthing complete with galvanized earth plate electrode 600x600x6 mm thick buried directly in ground (earth pit not less than 2.25 m deep below normal ground level) with top edge of the plate not less than 1.5 m below normal ground level connected to galvanized iron strip of 32x 6 mm (up to 7.5m in length from earth plate) by means of brass bolts and nuts checknuts and washers of brass all as specified and shown in electrical plate no 3 of SSR part 1 including Charcoal and rock salt with necessary excavation and earth work in any type of soil PCC 1:3:6 type C1 chamber with CI Cover 10mm thick Hinged to CI frame with MS bar 6mm dia 150mm c/c reinforcement, watering funnel, 50 mm dia light grade pipe for protection of earth electrode and 20mm dia pipe for watering complete all as specified and as directed and tested on completion. NOTE: This item is meant for external electrification,Lightening protection,fire Fighting system and DG set.
SOLAR WATER HEATER/COOLING APPLIANCES
Supply fix and testing refrigerator, electric driven (single phase), capacity more than 260 Liters BEE 5 star rated,double door,all as specified and directed.
S&F and testing Voltage stabilizer for automatic operation, single phase naturally air cooled indoor type & designed for input variation between 170 V to 250 V with output voltage stabilized at 230 V with accuracy of ± 2.5% and of capacity 3.0 kVA ,all as specified and directed.
PILE FOUNDATION
Boring for bored cast-in-situ piles 600 mm dia in any type of soil / clay / soft rock except hard rock by Hydraulic system of boring method and getting out and disposal of spoil to a distance not exc 10KM out side MD land complete all as specified and directed.
Boring for bored cast-in-situ piles 450 mm dia in any type of soil / clay / soft rock except hard rock by Hydraulic system of boring method and getting out and disposal of spoil to a distance not exc 10KM out side MD land complete all as specified and directed.
Boring for bored cast-in-situ piles 600 mm dia in hard rock & Factured rock by Hydraulic system of boring method and getting out and disposal of spoil to a distance not exc 10KM out side MD land complete all as specified and directed.
Boring for bored cast-in-situ piles 450 mm dia in hard rock & Factured rock by Hydraulic system of boring method and getting out and disposal of spoil to a distance not exc 10KM out side MD land complete all as specified and directed.
MS pipe liner fabricated out of 6mm thick plain MS plate conforming to Fe-410S by welding the joints lengthening wherever required,providing stiffner,lifting hooks including all T&P as required,shifting the same from position to position required,driving in true vertical alignment in positions to the reqd level for piles complete all as specified and directed Note: MS pipe liner shall be casted as mentioned in drawing.However for payment purpose the depth of pile liner shall be measured up to cutoff level only irrespective of the depth provided for retaining concrete/Bentonite slurry.The unit rate quoted shall be deemed to include for the same.
Chipping out pile up to cutoff level including disposal up to distance of 50m all as specified and directed.
Carrying out initial load test on 600 mm dia pile as per IS 2911 Part IV,complete all as specified and directed.
Carrying out initial load test on 450 mm dia pile as per IS 2911 Part IV,complete all as specified and directed.
Carrying out routine load test on 600 mm dia pile as per IS 2911 Part IV,complete all as specified and directed.
Carrying out routine load test on 450 mm dia pile as per IS 2911 Part IV,complete all as specified and directed.
Carrying out pull out test on cast in situ piles 600mm dia pile as per specified in IS complete all and as specified and as directed.
Carrying out pull out test on cast in situ piles 450mm dia pile as per specified in IS complete all and as specified and as directed.
Carrying out low strain integrity test on cast in situ piles including analysing the result as per ASTM D 5882 complete all and as specified and as directed.
Carrying out lateral load test on cast in situ piles 600mm dia piles as specified in IS and as directed.
Carrying out lateral load test on cast in situ piles 450mm dia piles as specified in IS and as directed.
FIRE FIGHTING SYSTEM
Supply and fix DOL starter for Booster pump set upto capacity of 7.5 HP with steel sheet enclosure complete all as specified and directed.
DEMOLITION AND DISMANTLING
Taking down PVC cistern low level/ high leval including all fittings any size and pattern complete all as specified and directed.
Taking down bib taps/stop cock of any dia complete all as specified and directed.
Taking down carefully sub main wiring including batten/ conduit by unscrewing from wall, celling and making good surfaces to match with original status complete all as specified and directed.
Taking down carefully light fittings any type any light complete all as specified and directed.
Taking down carefully switch piano 5 amps, switch socket 5/15 amp, celling rose and switch piano complete all as specified and directed.
Taking down MCB DB any type with MCB SP, MCB SPN complete all as specified and directed.
ARBORICULTURE
Supply & Planting Korean Carpet Grass by piece turfing including preparation of ground deep and filling soft soil,cow dung and watering etc complete all as specified and directed. Note:-loose soil and cow dung will measured separately.
Supply only approved loose/soft soil best quality for plantation complete all as specified and directed.
Supply only approved vermi compost of the best quality complete all as specified and directed.
Supply & Planting Ashoka Plant including preparation of ground upto 30 cm deep and filling soft soil, cow dung and watering etc., complete all as specified and directed. Note:- loose/soft soil and cow dung will be measured and paid separately under relevent items of BoQ.
Supply & Planting Gulmohar (Hybrid) including preparation of ground upto 30 cm deep and filling soft soil, cow dung and watering etc complete all as specified and directed. Note:- loose/soft soil and cow dung will be measured and paid separately under relevent items of BoQ
Supply & Planting Bougainvillea including preparation of ground upto 30 cm deep and filling soft soil, cow dung and watering etc complete all as specified and directed. Note:- loose/soft soil and cow dung will be measured and paid separately under relevent items of BoQ
Supply & Planting Royal palm tree including preparation of ground upto 30 cm deep and filling soft soil, cow dung and watering etc complete all as specified and directed. Note:- loose/soft soil and cow dung will be measured and paid separately under relevent items of BoQ
Supply & Plantation of crotons and hedges (height 30 cm c/c) including preparation of ground to required depth and filling of good earth including watering etc complete all as specified and directed. Notes For Item Nos 67,70 to 74 : (a) The Contrctor shall maintain the grass and plants for a period of 06 Months from the certified date of completion of the work covered under the scope of the work and the rates quoted against the respective item of the BOQ shall be demed to be inclusive of the same.Nothing extra will be paid for the maintenance of the grass and pants for a said maintenance period of six months. (b) Maintenance of arboriculture comprises of weeding, hosing, saucer melding once in every 15 days, planting new plants / grass in place of dead plants / grass of same species and height with out any extra cost to the department and as directed complete for the period of maintenance period of 06(Six) Months all as specified and as directed. (c) Rate quoted shall be deemed to include for all labour, materials, tools & plants, including supply and spreading / spraying organic manure, chemical fertilizers, pesticides to the required extent complete all as specified. (d) Supply of water and watering of plants and grass is responsibility of user's and not the responsibilty of the contractor
M&L 3-layer 20 mm dia PP-R Polypropylene random copolymer concealed pipes SDR 7.4 (PN 16) UV stabilized and antimicrobial fusion welded having thermal stability for hot & cold water supply including all PP-R plain & brass treaded polypropylene random fittings laid in trenches complete all as specified and directed.
M&L 3-layer 32 mm dia PP-R Polypropylene random copolymer concealed pipes SDR 7.4 (PN 16) UV stabilized and antimicrobial fusion welded having thermal stability for hot & cold water supply including all PP-R plain & brass treaded polypropylene random fittings laid in trenches complete all as specified and directed.
S&F of PP-R gate valves (brass insert) 20 mm dia complete all as specified and directed.
S&F of PP-R gate valves (brass insert) 32 mm dia complete all as specified and directed.
M & L for Sprinklers 15 mm dia fixed in pipe line , complete all as specified and directed.
DG SET
Silent engine generating set with accoustic enclosure as per CPCB norms 415 volts 20 KVA 3 phase 0.8 power factor 50 Hz, 1500 RPM self excited self regulated brushless AC generator including accoustic enclosure suitable for ambient condition and conforming to condition under IS 4722, BS 5514/ 2613 /5000 with and including the following:- (i) The capacity of Generator set shall be net after all due de-rating factors as per relevant ISI design (ii) Rate quoted shall be deemed to be inclusive of cable and terminations from Generator to the AMF Panel, with necessary holes to wall including making good to disturbed surfaces so as to match with the existing finishes all as specified and directed. (iii) The quoted rate shall be deemed to be inclusive of first fill of oil and final successful acceptance test+B106
(A) Alternator :- Standard design alternator rated at 20 KVA net output at site after considering de-rating as per site conditions at 0.8 (lag) power factor AC, 3 - phase 4 - wire 415 volts 50 Hz, 1500 RPM, self excited self regulated screen protected drip proof IP 23 enclosure brushless design with winding in pole faces, insulating class 'H' and voltage regulation of +/- 1% at rated voltage from no load to full load. The alternator shall be conforming to BS 2613/5000 and shall be imposition to generate supply with frequency regulation with in +/- 1% tolerance. The alternator will be suitable for tropical climate and shall generally conform to BS - 2613/5000/ IS – 4722 i) Insualation class - 'H‘ ii) Temparature rise Class - 'H‘ iii) Excitation : Self Excited iv) Regulation performance: The voltage is kept constant with +/- 1%, manual voltage adjustment within +/- 5% v) Frequency regulation +/- 1%
(B) Diesel Engine: - Adequate capacity of Diesel engine as approved by the GE basing on manufacturers technical details water cooled to drive independently above alternator and after considering de-rating as per site conditions after generating and reducing power consumed by accessories directly coupled through flexible coupling multi cylinder multi stroke direct injection, cold starting 1500 RPM, as per relevant ISI/BS - 5514 with an overload capacity of 10% for half an hour in 12 hours continuous running complete with standard accessories all as specified and required for safe handling and operation. Salient features of accessories shall be as under i)Fly wheel with housing ii) Cooling system :- Moulded radiator with fan & belts iii) Cooling Water pump : - Centrifugal type belt driven iv) Exhaust System :- Exhaust System complete with exhaust piping of suitable dia with MS pipe light grade upto & outside and 1meter away from the enclosure, covered with asbestos rope and aluminium foil of 28 SWG complete with in the enclosure for safe exhaust without transforming vibration to the wall of the enclosure. Exhaust gas turbo charger type. Exhaust manifold Silencer : Residual type Bellows v) Fuel System :- Fuel injection system with fuel injectors, fuel injection solenoid switch controlled by electronic governor for 1% speed /frequency regulation, Fuel filters, Fuel hoses. vi) Lub oil System : Lubricating oil filter Lubricating oil pump
vii) Air Intake System : Air intake Manifold Air cleaner dry type viii) Governor :- Electronic Governor ix) Starting System :- Electric Self starter with maintenance free battery including battery charging alternator x) Batteries :- Batteries of maintenance free of capacity as recommended by the manufacturer complete with copper conductor multi stranded leads of suitable length from self starter to the battery terminals complete with initial charge and initial fill of electrolyte all as specified and Starter gear ring Start and stop push button, Ignition key / Switch Handling and operation : Salient features of accessories shall be as under: Radiator with blower fan Corrosion inhibitor coolant Paper element filters for fuel, lub oil and by pass Electronic governor controlled direct fuel injection system Fly wheel housing and fly wheel xi) Generator Monitoring Panel : - Comprising of all standard items as mentioned under this schedule or asper standard practice iginiton key switch and start / stop arrangement, indications for Engine parametes, hour run meter, RPM meter, Engine oil pressure indicator, water/coolent temparature indicator, Battary volt display.
xii) Safety Controls : - Engine low lube oil pressure high water temparature and over speeding of engine xiii) Coupling arrangement : - Flexible coupling, fly wheel to suit flexible coupling+B109 xiii) Accessories :- AVM Pads built in enclosure and for entire unit on platform. xiv) Base Frame : - Should be provided as OEM norms xv) Fuel Tank :- Fuel Tank of capcaity to suit Daily service fuel tank made out of 3mm thick (10G) HR sheet top and bottom with caliberated level indicating arrangement, stop cock, drain plug, fuel pump of suitable capacity complete on a common base out side the accoustic enclosure. xvi) MS pipe line to and from the fuel tank to the DG Set
D) Accoustic Enclosure:- Manufactured by OEM suitable for 20 KVA DG Set (i) NAL approved as per CPCB (ii) It Should be as per latest rules and regulations of Ministry of Environment and Forest and Pollution control board (iii) The generating set battaries and control panel should be inside the enclosure. (iv) Fuel tank should be out side the enclosure in the sub station building. (v) Construction Details/specification are as follows: a) Outer body :- CRCA Sheet of 1.6mm thick b) Doors :- CRCA sheet of 1.6 mm thick c) Sound Insulation :- As per OEM Norms vi) The accoustic should be composite in construction and fully assembled integral unit vii) The batteries should be placed inside the enclosure beside the DG Set on a suitable insulated plat form viii) The fuel tank is to be located in Sub Station Building and cost of the fuel lines is deemed to be included in the offer.
ix) The DG Set should be provided with external Emergency stop push button x) The enclosure should be suitably illuminated by CFL/FTL Lamp fittings. xi) The noise level should be 75 dba at 1m under free field conditions. xii) The acoustic enclosure parts shall be of powder coated after pre treatment process. The powder coating shade should be Gen set Green. The base frame should be painted with epoxy based black shade
E) The quoted rate includes excavation, removing of soft soil and PCC, Cement Concrete foundation, filling and mass concrete type B2 (1:2:4) using 40 mm graded aggregate of size not less than 2.6 x 2. 0 x 0.8 m for placing of DG Set complete all as specified and directed.
AIR CONDITIONING
Supply and install,testing wall mounted split units Indoor/outdoor complete with cordless remote control unit and with in built air ioniser and Plasma filter for better indoor air quality with latest Inverter Technology of capacity 1.5 TR all as specified and directed.
Sub-main wiring with 2 runs of 6 Sqmm PVC insulated FRLS copper conductor cable including PVC conduit 20mm dia along with one run of 4 sqmm FR copper cable for earth continuity conductor as earth lead for sub-main wireing and connecting to common earth dolly all as specified and directed. Note: Two runs of 6 Sqmm PVC insulated FRLS grade cable one run of 4 Sqmm FRLS earth wire and one run of PVC condute will be measured and paid as one length.
Supply and fix Metal clad 20 Amps 2P+E all as specified and as directed.
ELECTRIC CHIMNEY
Design, installation, testing, commissioning of electric operated chimney for cook house of approx size of platform 2m x 2.2 m with chimney hood made of galvanised steel sheet with oil filter of minimum gauge 22 including GI ducting of 22 gauge for exhaust upto 15 mtr height of suitable size fixed on the wall with clamps angle iron frame ,threading rod,nut boltsalong with controlling dampers 04 Nos with suitable blower motor of capacity 3 HP with starter,controlling/display panel with auto clean system all as specified and as directed. NOTE: (a) The Contractor shall submit the drawing of chimney for approval of Engineer in charge before placing the order.
S & F Cable PVC insulated sheathed LT 1100 V grade with copper conductor of size 3 core 10 Sq mm multi stranded conductor laid in ground/ fixed to wall/roof etc., with suitable clamps, spacers, bolts and nuts all as specified and directed.
K KUMAR RAJA PROJECTS P LIMITED
Venkateswara Electricals
jd constructions
S V S ENTERPRISES
MURALI KRISHNA ASSOCIATES
B DURGA REDDY INFRASTRUCTURES PRIVATE LIMITED
SVS PROJECTS
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .