Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L-1₹1.3 CrAccepted-AOC | ₹1.3 Cr | L-1 | Accepted-AOC AOC |
| 2 | L-2₹1.4 Cr+₹1.7 L (1.23%)Rejected-Finance H NO 787 22 JHANG COLONY ROHTAK 124001 | ROHTAK | HARYANA | 124001 | ₹1.4 Cr+₹1.7 L (1.23%) | L-2 | Rejected-Finance Highest |
| 3 | L-3₹1.4 Cr+₹5.5 L (4.07%)Rejected-Finance H NO 861 12 SALARA MOHALLA ROHTAK 124001 HARYANA INDIA | ROHTAK | HARYANA | 124001 | ₹1.4 Cr+₹5.5 L (4.07%) | L-3 | Rejected-Finance Highest |
| 4 | Rejected-Technical | - | - | Rejected-Technical Rejected |
| 5 | Rejected-Technical SCF 15 HUDA COMPLEX 184 NEW IDC 124001 | ROHTAK | HARYANA | 124001 | - | - | Rejected-Technical Rejected |
Tender Value
Refer Docs
EMD Value
₹2.5 L
Closing Date
8 Apr 2021, 5:00 pmClosed
Ritesh Nandal
Executive Engineer, Elect. Divn. PWD B and R Br. Ambala Cantt.
Up-gradation of Civil Hospital from 200 Bedded to 300 Bedded at Ambala City in Ambala Distt. (Pdg. 11 KV Compact Sub-Station).
2021_HRY_155499_1
PWD/Elect-KNL/Elect-AMB/110138
Open Tender
Construction Works
Works
300 days
Ambala Cantt
Please refer Tender documents.
3 documents required · 3 mandatory
₹15,000
₹2.5 L
12 Oct 2021
6 Jan 2021
9 Apr 2021
6 Jan 2021
8 Apr 2021
6 Jan 2021
Amount
( c ) Moulded case Circuit breakers. S/E of moulded case circuit breakers on wall or on existing pedestal i/c bonding to earth and necessary connections. (Make:-Schenider, L&T, ABB) 15 amp.to 60 amp. 415 V ,10 KA 3-phase. HRS No. 31.12 c (i)
100 amp.to 220 amp.415 V,10 KA 3-phase. HRS No. 31.12 c (ii)
250 amp to 300 amp 415 V 35 KA 3 Phase HRS No. 31.12.c (iii)
300 amp. to 400 amp. 415 V , 35 KA 3-phase. HRS No. 31.12 c (iv)
(L) Miniature Circuit Breaker and Isolator. Supply and erection of miniature circuit breaker / isolator 240 /415 V in the existing distribution board including making necessary connections. (Make:-Schenider,L&T,ABB) SP MCB of 9 KA breaking capacity 6 amp. to 32 amp. HRS No. 31.17a) (ii)
TP MCB of 9 KA breaking capacity 40 amp. to 63 amp. HRS No. 31.17(a)(iii
(P) Pipe Laying. Supply and erection of pipe for wiring purposes including bends inspection boxes etc. where necessary and painting as required. Galvanised iron pipe 65 mm dia on surface.(Make:-Jindal, Ravindra,TATA) HRS No. 31.21 (vii)
PVC pipe 120 mm dia. HRS No. 31.21(xxx) (a)
(Q) Earthing Earthing with GI earth pipe 4.5 m long and 40 mm dia with masonry enclosure on the top etc. as required . HRS No. 31.22 (i)
Extra for charcoal or coke and salt for G.I. Pipe earth electrode. HRS No. 31.22 (ii)
Earthing with GI earth plate 600 mm x 600 mm x 6 mm thick including accessories and providing masonry enclosures with cover plate having locking arrangement and watering pipe etc. ( but without charcoal or coke and salt ) complete as required. HRS No. 31.22 (iii)
Earthing with tinned copper earth plate 600 mm x 600 mm x 3 mm thick including accessories and providing masonry enclosures with cover plate having locking arrangement and watering pipe etc. ( but without charcoal or coke and salt ) comlete as required. HRS No. 31.22 (iv)
Extra for charcoal or coke and salt for G.I. Plate or copper plate earth electrode. HRS No. 31.22 (v)
Pdg. and fixing 25 mm x 5 mm copper strip in 40 mm dia G.I. pipe from earth electrode as required . HRS No. 31.22 (x)
Pdg. and fixing 25 mm x 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode as required . HRS No. 31.22 (xi)
Pdg. and laying earth connections from earth electrode with 4.00 mm dia G.I. wire in 15 mm dia G.I. pipe from earth electrode as required . HRS No. 31.22 (xii)
Pdg. and fixing 25 mm x 5 mm copper strip on surface or in recess for connections etc. as required with all labour and material. HRS No. 31.22 (xiv)
Pdg. and fixing 25 mm x 5 mm G.I. Strip on surface or in recess for connections etc. as required with all labour and material. HRS No. 31.22 (xv)
Pdg. and fixing 4.00 mm dia G.I.wire on surface or in recess for loop earthing as required . HRS No. 31.22 (xvi)
(R) Lightning conductor (a) Copper. Supply and erection of copper tape 32 mm x 6 mm thick from earth electrode directly in ground and surface , fixed with suitable copper stapples of same size. HRS No. 31.23 (vii)
Supply and erection of under ground cable ,loose in existing pipe or trenches complete with necessary connections . (Make:-Polycab,Havell,Plaza) 35 Sq. mm 3.5 Core Armoured Cable. HRS No. 31.26 (xxvi)
50 Sq. mm 3.5 Core Armoured Cable. HRS No. 31.26 (xxvii)
95 Sq. mm 3.5 Core Armoured Cable. HRS No. 31.26 (xxix)
150 Sq. mm 3.5 Core Armoured Cable. HRS No. 31.26 (xxxi)
185 Sq. mm 3.5 Core Armoured Cable. HRS No. 31.26 (xxxii)
240 Sq. mm 3.5 Core Armoured Cable. HRS No. 31.26 (xxxiii)
300 Sq. mm 3.5 Core Armoured Cable. HRS No. 31.26 (xxxiv)
400 Sq. mm 3.5 Core Armoured Cable. HRS No. 31.26 (xxxv)
16 Sq. mm 4 Core Armoured Cable. HRS No. 31.26 (xI)
25 Sq. mm 4 Core Cable . HRS No. 31.26 (xIi) Ard.
Supply and erection of suitable compression type brass cable glands for underground Cable. 25 Sqmm to 50 Sqmm Cable 2 to 4 Core. HRS No. 31.28 (iii)
70 Sqmm to 95 Sqmm Cable 3 to 3.5 Core . HRS No. 31.28(iv)
120 Sqmm to 185 Sqmm Cable 3 to 3.5 Core HRS No. 31.28 (v)
300 Sq mm to 400 Sqmm Cable 3 to 3.5 Core . HRS No. 31.28 (vii)
Street Light Supply and erection of prestressed cement concrete pole as per IS : 1678-1960. 11 metres long 152 mm x 203 mm at top and 152 mm x 368 mm at bottom with working load of 360 Kg. burried 2.20 m in ground. HRS No. 31.30 (VI) (iii)
(X) Miscellaneous . Supply and erection of caution notice plate in three languages. HRS No. 31.35 (iii)
Supply and erection of shock restoration chart in glass frame HRS No. 31.35 (iv)
Supply and erection of aluminium lugs heavy duty including crimping etc. upto the entire satisfaction of the Engineer-in-charge of the work. 16 sqmm . HRS No. 31.35 (ix) (d)
25 sqmm . HRS No. 31.35 (ix) (e)
35 sqmm . HRS No. 31.35 (ix) (f)
50 sqmm . HRS No. 31.35 (ix) (g)
95 sqmm . HRS No. 31.35 (ix) (I)
150 sqmm . HRS No. 31.35 (ix) (k)
185 sqmm . HRS No. 31.35 (ix) (l)
300 sqmm . HRS No. 31.35 (ix) (n)
400 sqmm . HRS No. 31.35 (ix) (o)
Supply and Fixing of rotary handle for ON / OFF operation of existing MCCB in the LT panel including fixing the same in position with all labour and material to required to complete the job in all respect. Rotary Handle up to 125 Amp., MCCB HRS No. 31.66 ( i )
Rotary Handle above 125 Amp., MCCB HRS No. 31.66 ( ii )
S/E of mark double walled corrugated (DWC) HDPE pipe laid 1 Mtr. Below ground level including digging and refilling of earth including cost of suitable size socket / cuppler for HDPE pipe including cost of labour and material required to complete the job in all respect upto the entire satisfaction of Engineer in charge of work. HDPE 63/50 mm outer dia / inner dia HRS No. 31.67 ( i )
HDPE 90/75 mm outer dia / inner dia HRS No. 31.67 ( ii )
S/E of XLPE (E)11 KV HT aluminum conductor armoured cable ISI mark laid in existing pipe /trenches/surface with all labour and material required to complete the job in all respect upto the entire satisfaction of the Engineer-in-charge of the work. HRS No. 31.71
Supply and erection of heat shrinkage type end termination joinnting kit indoor type of suitable to accommodate 3 core 11 KV XLPE aluminum cable / ABC cable complete wityh all the kit comtent including earth continuing connection along with 3 nos.crimpling type aluminum lugs of suitable capacity including making joining etc complete in all respect. Suitable for 70 to 120 sqmm 3core XLPE Cable HRS No. 31.72 II
Supply and erection of heat shrinkage type end termination joinnting kit Outdoor type of suitable to accommodate 3 core 11 KV XLPE aluminum cable / ABC cable complete with all the kit comtent including earth continuing connection along with 3 nos.crimplin type aluminum lugs of suitab;le capacity including making joining etc com[plete in all respect. Suitable for 70 to 120 sqmm 3core XLPE Cable HRS No. 31.73 ii
Supply & erection of cable tray made out of 2 mm thick galavanised perforated sheet steel including erection of the same on wall or ceiling with necessary fixture and other material required to complete the Job in all respect upto the Entire statisfaction of Engineer-in-Charge of the work. 50 x 300 mm HRS No. 31.81 iii
Supply & erection of factory manufactureed cable tray cover made of 16g GI Sheet complete with Fastoner Nuts bots and in position including all petty material required to complete the Job in all respect upto the Entire statisfaction of Engineer in Charge of the work 50 x 300 mm HRS No. 31.82 iii
Supply, installation, testing and commissioning of distribution net work, 11 kv outdoor compact Sub Station totally factory assembled (non walk in type) consisting of 3 way RMU type, 1 No. 11KV/433V, 1000 KVA Mineral Oil type transformer, 1 set of LT device as under. Approved Makes- Siemens/ Schneider/ ABB MV COMPARTMENT 11 KV, 630A, 21KA/3Sec indoor type non-extensible, SF6 gas insulated Ring Main unit with sealed pressure system criterion in accordance with the IEC: 60298,62271 - 202.IAC of 20 kA for 1 s for tank and cable box category IAC-AFL. The Switchgear includes the following HV cubicles The indoor non -extensible SF6 insulated RMU fully motorised consist of 2 No. incomer Isolator and 1 no. outgoing Vacuum Breakers with self powered relay for protection of transformer . Rated for Voltage 12kV, 630A, 21 KA for 3 sec. Rated voltage should be - 12 KV Rated power frequenecy voltage - 28 KV Rated lightening withstand voltage - 75 KV Rated current for Ring main feeder - 630 amps Rated current for VCB feeder - 630 amps Vacuum Circuit Breaker of RMU should clear minimum 50 nos. of dead short circuit operations Rated short time current - 21 KA / 3sec Rated short time making current -50 KA Ambient temp ( 0 deg C to +40 deg C) Rated internal arc rating - 20 KA for 1 sec for tank and cable box category IAC-AFL RMU shall be provided with protection CTs rated for 30 / 1amps, class - 10P10 accuracy , 2.5 VA burdan for circuit breaker The circuit breaker feeder shall be self powered/powered by external source and shall be provided with OC+EF protection for transformer and shall have serial port for communication on modbus protocol. RMU manufacturere shall have in house NABL accredited testing lab. Transformer (Mineral Oil Type) Three phase, Oil type transformer. Make of transformer shall be ABB, Siemens, Schneider, BHEL, CG Standard: IS : 2026, IS 1180 Level 2 Vector group : Dyn11 Rating : 1000 KVA Cooling System: ONAN Winding: Copper Magnetic Core: Prime grade of M4 or better High voltage : 11KV - 50 Hz System highest voltage : 12kV at the HV side H.V. Power Frequency (KV rms): 28 kV H.V. Impulse withstand voltage (KV peak): 75 kVp The Losses of Transformer shall be as per IS 1180 Level 2 Transformers shall be designed for 110% continuous overfluxing withstand capability Temperature rise as per IS1180 LV COMPARTMENT The LV compartment with Degree of protection-IP54 designed for a 50 degree C ambient temperature. The panel is modular, dead front, freestanding, floor mounted and comprises the following equipment 433 V air insulated Aluminium busbar having capacity 1600A, 50Hz,50KA withstand fault level capacity, MFM - EM6400NG, with necessary CT in incommer Incommer Cum Outgoing - 1no. 4 Pole, 1600A, Manual Operated ACB with inbuilt Microporcessor based release, fixed typeACB with S/C , O/C & earthfault release. The fault system of 50kA, Ics=Icu=Icw for 1 sec. Make- Schneider/ ABB/ Siemens Outdoor Enclosure :- The enclosure shall be made of 2.0 mm thickness Galvanized Sheet Steel tropicalised to meet Indian weather conditions including all the partition sheets & doors.The base of the enclosure shall be of 4.0 mm thickness Hot Dip Galvanized Sheet Steel to ensure rigidity for easy transport & installation. The entire Package Substation shall be Factory Assembled & Factory Fitted. The enclosure shall have IP54 degree of protection for HT & LT switchgear compatment IP23 degree of protection for Transformer compartment. The Enclosure to be tested for Internal Arc fault test to the tune of atleast 20 KA for 1 second adhering to as per latest IEC 62271-202.The temperature rise test on enclosure for K10class.The enclosure exterior shall be pure polyester powder coated (RAL 7032). Each compartment will be provided with door and pad locking arrangement. The compartment illumination lamp with door operated switch shall be provided for MV & LV compartment. HRS No. NS-1
Design, Engineering, Manufacturing, Testing at Works and Supply of 11 kv 630A 21KA 4 way Outdoor Non-Extensible Fixed (IP 54), Ring Main Unit Consisting of 2nos. motor operated Load Break Switch (Both Incomers) and 2nos. Motor Operated SF6 insulated Vaccum circuit Breaker as outgoing having following feature: All live parts Cu bus bar, VCB will be enclosed in a manually/TIG welded, of suitable thickness, stainless steel tank enclosure filled with SF6 gas at suitable pressure. Make ABB,Schneider, SIEMENS, The Unit Shall include the following with all necessary standard fittings required at site: 11KV, 630A, 21KA for 1Sec, Outdoor type, Motorized, Non-Extensible, SF6 gas insulated Ring Main unit with sealed pressure system criterion in accordance with the IEC: 60298. The complete switchgear shall be tested for internal arc of 21kA AFLR for 1 sec. for both cable box and tank.Rated Voltage - 12KV Power frequency withstand voltage - 28KV Impulse witstand voltage - 75kVP (an altitude <1000 m above msl) Rated Current Amp - 630A. Ambient mp ( -5 deg C to +40 deg C) SF6 Insulated Vacuum Circuit Breaker (RMU) consisting of 4 modules having:- Two (2) nos. Load Break Switch as incomer and Two (2) nos. Vaccum Circuit Breaker as outgoing:- Each Incomer (LBS) should consist of following: - Operation of Load Break Switch should be Motorized - The switching-unit is designed as a three-position-switch. This three-position-switch combines the functions of switch-disconnector and earthing-switch. The switch-disconnector as well as the earthing-switch is equipped with a separate drive-unit. 1 Cable switch 12 kV, 630 A, 21 kA. 1 Stored Energy mechanism for Motorized Operation – with integrated manual operated earth-switch. 1 Cable bushing 630 A, standard C bushings. 1 Cable cover standard. 1 Capacitive voltage indication fixed type - LED display. 1 ON, OFF, EARTH indication on the front mimic of the panel. 1 Cable box for termination of cable up to 1 No. X 3C X 300 sq. mm. 1 Cable entry bottom, front. 1 Set of 12kV Right Angled Cable Boots Each Outgoing Vaccum Circuit Breaker shall consist of following: This function-unit consists of a vacuum-circuit breaker in combination with a three-position-switch. The three-position-switch fulfils the operation of the disconnector-function and the earthing-function. The circuit-breaker-unit T2 is equipped with an over current-time-release for the protection of distribution transformers. No. of Dead Short circuit operations of vaccum bottle shall be 50nos. 1 Vacuum circuit breaker 12 kV, 630 A, 21kA 1 Stored Energy mechanism for motorized operation with integrated earthing switch. 1 Self powered Numerical protection relay providing over-current & earth fault protection – Schneider Electric make DPX-V5. 3 Tap Wound Ring core current transformers for Protection ratio 60/1/1 A, AC. Class 1.0/5P10, Burden 2.5VA 1 Capacitive voltage indication fixed type - LED display 1 ON, OFF, EARTH indication on the front mimic of the panel 1 Cable box for termination of cable up to 1 No. x 3C X 300 sq. mm. 1 Cable cover standard. 1 Shunt Trip Coil – 24V DC. 1 Emergency Trip Push Button. 1 Set of 12 kV Right Angled Cable Boots Additional equipment delivered separately or mounted separately or mounted in resp. of each panel / RMU 1 Standard Manometer w/o remote contact 1 Operating Handle 1 Cable clamping provision (standard) 1 Operation and Installation Manual 1 Installation & Commissioning Manual RMU shall be fully manually and motorized. RMU shall be provided with battery and battery charger rated for 24 V DC for motorisation. RMU cable box shall be front accesible type to have easy access to protection. Cable box should be arc proof with bolted door and interlocked with respective earthing switchs. Doors should be removable for the ease aceess to terminate cables. RMU Enclosure shall be made up of CRCA having minimum thick ness of 2mm for load bearing and minimum 1.6mm for non load bearing members. RMU tanks shall be 2 mm thick of stainless steel material welded by using robotic weling or manual tig welding. Both Incomer of RMU should be interlocked in such a way that only one incomer shall be in operation at a single time HRS No. NS-2
AUTOMATIC POWER FACTOR CORRRECTION PANEL Supply, fixing, connecting and testing of OEM Manufactured APFC Panel with 7% Aluminium reactor of capacity 350 KVAR (Output) @ 440Vac with VarplusCan Heavy Duty Capacitors . The stage ratings shall be 2x12.5 KVAR +1x25kvar + 6 x 50 KVAR . The APFC Panel shall be fully type tested at an Independent Laboratory and shall comply with IEC 61439-1&2 and IEC 61921, IS-16636-2017.The degree of protection of enclosures system of the APFC Panel shall be min. IP41 in accordance with IEC 60529.The capacitor bank shall be Internet of things (IoT) enabled and communicable/ integrable with BMS The APFC Panel shall be (Indoor) type conforming to IS13341:1992 & IS 13440:1993 floor mounted design, weather, dust and vermin proof suitable for humidity up to 95%. Average daily temperature: +35°C max, Ambient temperature: -5°C to 40°C, Maximum altitude: 2000 m. Approved Makes- ABB / Schneider / Siemens / L&T make only. The OEM's specified cannot authorize any other partners / sub vendors to manufacture APFC Panels on their behalf. The APFC Panel manufactured by OEM's only will be accepted & factory acceptance test ( FAT ) will be carried out at OEM's plant only. As equipment shall be comprising of the following:- (A) Insulated bus bar pan assembly made from aluminium and rated of 800 Amps capacity. The short circuit withstand capacity shall be 50 KA / 1 Sec (Icw) for the main bus bar and the rated impulse withstand voltage shall be 6 KV. ( B) The incomer of the APFC Panel shall be a 800 Amp, MCCB, 3P, 50kA TMD type with O/L & S/C protection, Ics = 100% Icu, MCCB shall have standard extended rotary handle, spreaders, phase barrier. MCCB shall be of certified design confirming to IEC 60947-1,2 & 3. (C) Capacitor Units: The capacitor unit shall be metalized polypropylene film with Zn / Al alloy. The capacitors shall be encapsulated in an aluminium can. The capacitor unit shall have a rated voltage of 525V and shall have a maximum over current capacity of: 2.5 In. The capacitor unit shall have a built in 3 phase over pressure protection and shall have discharge resistors (50V in 1min) factory fitted and shall be tamper proof. Capacitance Tolerance -5%, +10%. Maximum permissible over voltage 1.1 x Un, 8 h every 24 h. The capacitor unit shall be of certified design confirming to IS-13340-1993, 13341-1992 & IEC -60831-1&2. ((D) Short-circuit and Overload Protection: Each stage of the APFC Panel shall have a suitably rated MCCB for short-circuit and overload protection. The over-current setting shall be adjustable & Breaking capacity Ics=> 36kA. The MCCB shall be of certified design confirming to IEC 60947-1, 2 & 3. The Detuned Reactor (Al Wound) should be equipped with Thermal Switch inside the Winding which should cut-off the respective contactor in case of Over-temperature. Tolerance of reactors shall not exceed +/-3% of rated value. (E) PF Regulator/ APFC Relay: Advanced Range PF Regulator / micro-processor based APFC relay having 12 steps with a LCD Display, Voltage Range: 90V - 550V, 50 / 60Hz, CT Input: 1A/5A with a built in RS 485 communication port. The PF Regulator shall be of certified design confirming to IEC 61326. (F) Stage Contactor: The capacitor duty contactors shall be rated for 230 Volts AC and shall be 3-pole type and shall be employed for switching 'on' and switching 'off' operations in capacitor banks. The contactor shall be AC- 3 duty type. The contactor shall be of certified design confirming to IEC 60947-1 & 4-1. (G) Reactor: - Harmonic block reactors Al wound with 7 % filtering factor shall be connected in series with each capacitor stage and shall be of iron cored type. The Reactor should be equipped with Thermal Switch inside the Winding which should cut-off the respective contactor in case of Over-temperature. Tolerance of reactors shall not exceed +/-3% of rated value. The reactors shall be of certified design confirming to IEC-60076 - 6. (H) Ventilating fans of required size shall be sued to dissipate the heat produced by the capacitor bank components like the capacitor units, reactors, contactors, breakers etc. The capacitor banks should be of type tested design and temperature rise test report of the capacitor bank performed at an independent laboratory should be submitted along with the offer. Note:-The APFC Panel described as above complete in all respect as per specification enclosed, up to the entire satisfaction of engineer In Charge.To ensure safety, reliability and accountability of component co ordination, all the major capacitor bank components such as capacitor units, de tuning reactors, PF controllers, circuit breakers, contactors and the enclosure system called for in this specification should preferably be from a single manufacturer. The OEM shall preferably manufacturer PFC components and switchgear. HRS No. NS-3
LIFT PANEL Supply, installation, testing and commissioning of powder coated of Siemens grey or of approved colour compartmentalized cubicle Panel fabricated out of 14 SWG thick CRCA sheet steel with chemical wash after 7 tank process and suitable for operation on 415 volts, 50Hz, 3 Phase 4 wire AC supply . The panel shalll be indoor free standing, floor mounting, dust and vermin proof type, adeqate size cable alley with front operated rotary handles for MCCB's complete with gland plates, lifting hooks, ventillating louvers, busbars, Inter connections, earthing, labelling as per specification and drawings, suitable for termination of cables as per single line diagram including. supply and fixing of following switchgear and accessories complete as required.Detailed specifications and material list attatched. Make Kalyani,Vrindavan,Sudhir. Panel should be with breaking capacity of 50 kA as approved by CPRI Bhopal. INCOMER FEEDER MCCB 250Amps. FP 36 KA, Ics=100% Icu, Suitable for Isolation,Class II front Face, Overload setting .7-1xIn , Protection Settings MCCB with thermal magnetic type release with Double break Roto mechanism. Minimum elec. Operation should be 10000. Make L&T (DNX)/ GE(record plus)/ Schneider (Easy Pact CVS) Siemens (3VL). 01 No. Spreader links. 01 No. Extended Rotary Handle. 01 No. MFM Multifunction meters should be EM6400 with RS485 Port or Equivalent in Make : Schneider / Conzerv / Secure / Siemens (Class 0.1, with RS485 Port, with Paramenters V, Amp, PF, % THD, F,W,WH,VA,VAH, VAR,VARH, Runhrs, ON hrs, Interupts, 01 No. RYB Indication Lamp LED. 01 No. 250/5Amp. 15 VA CL-1 Current Transformer. 03 No. 06Amp. Control SP MCB. 03 No. CT Short Link. 03 No. All MCCB's should be Thermal Magnetic / Microprocessor Adjustable as per BOQ type ICS=100% ICU, Class II Front Facia with cross bolt terminals, Frame Size - Single Frame from MCCB Rating 32Amp to 250Amp, MCCB 400Amp / 630Amp as Single Frame. All MCCB's should have aux. contact for ON /Trip Indication on Panel. The Electrical Life of MCCB should be as follows : Upto 250Amp Rating MCCB's as 10000no. Electricals operations & 400Amp Rating - 6000no. Electrical operations & 630Amp - 4000no. Electrical operations. OUTGOING FEEDER MCCB 63Amps. FP 25KA. Ics=100% Icu, Suitable for Isolation,Class II front Face, Overload setting .7-1xIn , Protection Settings MCCB with thermal magnetic type release with Double break Roto mechanism. Minimum elec. Operation should be 10000. Make L&T (DNX)/ GE(record plus)/ Schneider (Easy Pact CVS) Siemens (3VL). 06 Nos. Spreader links. 06 Nos. Extended Rotary Handle. 06 Nos. MCCB 63Amps. FP 25KA. Ics=100% Icu, Suitable for Isolation,Class II front Face, Overload setting .7-1xIn , Protection Settings MCCB with thermal magnetic type release with Double break Roto mechanism. Minimum elec. Operation should be 10000. Make L&T (DNX)/ GE(record plus)/ Schneider (Easy Pact CVS) Siemens (3VL)For Spare. 01 No. Spreader links. 01 No. Extended Rotary Handle. 01 No. FABRICATION & POWDER COATING Fabrication in 1.6/2MM.CRCA Sheet Powder Coating in Siemens Gray Shade, 75x40mm.Channel Base Frame, Cable Entry will be Top & Bottom Suitable for Cable ,Lock, Rubber Gasket, hardware etc. 01 Set BUS BAR & HARDWARE 250A.Copper .Bus Bar,Load wise Sub Feeder Bus Bar Colour Coated Heat Shrink Bus Bar sleave Nut-Bolt,Washer ,Hardware etc. 01 Set WIRING & ACCESSORIES Power & Control Wiring will be (ISI 1100V) flamc smoke FRLS PVC Single Core Copper Wire,Copper Lugs, PVC Sleeve, Ferruels Numbers, Hardware & Labour etc. HRS No. NS-6
S/E of 11KV gang operated switch ‘Jayshree make’conforming to IS with latest amendment including suitable size of copper blade erection of same on the existing ‘H’ pole with the help of 3 No. channels of size 75mm×40mm×6mm,1.8m long fixed with suitable size of MS clamp, nuts & bolts including cost of 6 No. 11 KV insulator with GI pin, RD fuses and painting with 2 coat of approved paint and one coat of red oxide material required to complete the job in all respect upto the entire satisfaction of Engineer-in-Charge of work. HRS No. NS-7
Supply & erection of lightening Arrestor model SDU ALPRO make suitable for11KV 3 phase 50 HZ grounded neutral system comprising of Speek gap type (Quench gap type) in series with non liner resister element housesd in horizontally Scale porcelain bushing with line and ground terminal along with mounting clamps Conforming to ISS 3070 (Part-I) of 1985 with latest amendment with all labour and Material required to complete the job in all respect upto the entire satisfaction of Engineer-in-Charge of work HRS No. NS-8
Supply and erection of MS angle 50x50x6mm including cutting bending to the required shape drilling hole carriage Painting loading unloading complete in all respect upto the entire satisfaction of Engineer-in-charge of work. HRS No. NS-9
Supply and erection of MS flat 50x6mm including cutting bending to the required shape drilling hole carriage Painting loading unloading complete in all respect upto the entire satisfaction of Engineer-in-charge of work HRS No. NS-10
Supply and erection of MS channel 100x50x6mm including cutting bending to the required shape drilling hole carriage Painting loading unloading complete in all respect upto the entire satisfaction of Engineer-in-charge of work. HRS No. NS-11
Supply, Commissioning , Testing of Stey Set complete with stey wire & disc insulator as per specification complete in all respect upto the entire satisfaction of Engineer -in - charge of work. HRS No. NS-12
Supply and erection of Pin insulator Rashtriya / Jayshree / BHEL make with Disc fitting T&C type complete in all respect with erection of the same upto the entire satisfaction of the Engineer in Charge of work HRS No. NS-13
Supply & Erection of Rubber mat of size 2mX1m & 12 mm thick suitable for 11 KV complete in all respect upto the entire satisfaction of the Engineer in Charge of work HRS No. NS-14
Supply & Erection MS bucket stand including cost of 6 nos. buckets of 9 liter capacity each with sand filling including cost of welding & painting of complete stand & buckets with one coat of red oxide and two coats of approved paint of red colour with all labour & petty material to complete the job in all respect upto the entire satisfaction of Engineer-in-charge of work. HRS No. NS-15
Supply & eraction of fire extingusher ISI marked Co2 type 4.5 Kg. Capacity as per ISI 7285 duly erected on wall with hook including the cost of hook, Screw etc. with all the labur and material required to complete the job in all respect upto the entire satisfaction of Engineer-in-Charge work. Make- Ajay, Zenith, Minimax. HRS No. NS-16
Supply, Erection, Testing, commissioning of 11 Kv outdoor type HT Metering Panel complete with CT 's,PT cubical and Electronic meter with accuracy class0.5 as per required/approved by UHBVN required to complete the job in all respect upto the entire satisfaction of Engineer-in-Charge of work. HRS No. NS-17
Janta Electric Store
Vijender Kumar Contractor
stage.html
html • 0.05 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .