| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹75.2 LAccepted-AOC TUPKHANA PART 1 PO ARUNACHAL PS SILCHAR DIST CACHAR ASSAM 788025 | CACHAR | ASSAM | 788025 | L1 | Accepted-AOC AOC | |
| 2 | L2₹80.7 L+₹5.5 L (7.33%)Rejected-AOC HENGRABAI LICHUBAGAN BYE LANE 2 HOUSE NO 2 GUWAHATI 781036 ASSAM | KAMRUP METRO | ASSAM | 781036 | L2 | Rejected-AOC AOC | |
| 3 | L3₹81.7 L+₹6.5 L (8.60%)Rejected-AOC H M APARTMENT 4C S J ROAD ATHGAON GUWAHATI 781001 | GUWAHATI | KAMRUP METRO | ASSAM | 781001 | L3 | Rejected-AOC AOC | |
| 4 | L4₹82.9 L+₹7.7 L (10.2%)Rejected-AOC 11 GURU NANAK MARKET AMBALA ROAD SAHARANPUR 247001 | SAHARANPUR | UTTAR PRADESH | 247001 | L4 | Rejected-AOC AOC | |
| 5 | L5₹84.1 L+₹8.9 L (11.8%)Rejected-AOC V P O SAROTARI TEHSIL BAROH DISTRICT KANGRA PIN 176037 HP | KANGRA | HIMACHAL PRADESH | 176037 | L5 | Rejected-AOC AOC |
Tender Value
Refer Docs
EMD Value
₹1.8 L
Closing Date
9 Apr 2024, 6:00 pmClosed
CWE (AF) Borjhar
HQ CWE AF Borjhar Military Engineer Services PO Borjhar Airport Guwahati Assam 781015
SPECIAL REPAIRS REPLACEMENT TO BER EM EQUIPMENT PH-II AND PROVN OF 200 KVA TROLLEY MOUNTED DG SET AT AFS KUMBHIRGRAM UNDER AGE I AF KUMBHIRGRAM
2024_MES_646054_1
CWE(AF)/KUM/TOKEN- 38 OF 2023-24
Open Tender
Electrical and Maintenance Works
Item Rate
120 days
KUMBHIRGRAM
Refer to as per tender document
8 documents required · 8 mandatory
₹1,000
AGE (I) (AF) KUMBHIRGRAM
₹1.8 L
Yes
21 Jun 2024
12 Mar 2024
11 Apr 2024
12 Mar 2024
9 Apr 2024
26 Mar 2024
Amount
Supply and install hi wall split units indoor/outdoor complete with cordless remote control unit and with in built air ioniser and Plasma filter for better indoor air quality with minimum 3 star rating with ISEER as per latest Ministery of Power notification dt 10 Nov 2023 of cooling capacity 4500 K Cal per hour (1.5 TR ) complete all as specified and directed. Make: LG / Bluestar / Daiken Note : 1.Cost for provision of making holes for necessary connections through the existing walls, PVC pipe 15 mm bore dia for draining out condensated water, copper tube with insulated material for complete Job and to place outdoor unit on brickwork platform of minimum size (0.8 x 0.3 x 0.3) with sub class 'B' brick with cement mortar 1:4 and randering with 15 mm on fair face of brick work for complete job or factory made MS bracket inclusive of quoted rate . 2. Extra copper tube with insulated material required will be measured saperately.
Supply and install hi wall split units indoor/outdoor complete with cordless remote control unit and with in built air ioniser and Plasma filter for better indoor air quality with minimum 3 star rating with ISEER as per latest Ministery of Power notification dt 10 Nov 2023 of cooling capacity 6000 K Cal per hour (2 TR ) complete all as specified and directed. Make: LG / Bluestar / Daiken Note : 1.Cost for provision of making holes for necessary connections through the existing walls, PVC pipe 15 mm bore dia for draining out condensated water, copper tube with insulated material for complete Job and to place outdoor unit on brickwork platform of minimum size (0.8 x 0.3 x 0.3) with sub class 'B' brick with cement mortar 1:4 and randering with 15 mm on fair face of brick work for complete job or factory made MS bracket inclusive of quoted rate . 2. Extra copper tube with insulated material required will be measured saperately.
Supply, installation,commissioning of storage Water cooler with in built UV Purification fully stainless steel, electric driven single phase having approx storage capacity of 80 litre and nominal cooling capacity of 60 Litres per hour complete all as specified and directed. Make Blue Star (Model SWCSDLX6080UVE), Aquagard Pro (AG Pure chill 80 SS UV Commercial Water Purifier) or Equivalent
Supply and fix refrigerator, electric driven (single phase), suitable to working on AC 220 volts (+/-) 12%, 50Hz, CFC free refrigerant gas, single door type with minimum 3 star rating with ISEER as per latest Ministery of Power notification dt 10 Nov 2023 capacity more than or equal to 230 ltrs, auto defrost system complete all as specified and directed. Make: LG / Bluestar / Godraj
Supply and fix refrigerator, electric driven (single phase), suitable to working on AC 220 volts (+/-) 12%, 50Hz, CFC free refrigerant gas, double door type with minimum 3 star rating with ISEER as per latest Ministery of Power notification dt 10 Nov 2023 capacity more than or equal to 310 ltrs, auto defrost system complete all as specified and directed. Make: LG / Bluestar / Godraj
Supply, installation,commissioning of Hard top single lid, Deep Freezer single phase 230 volt, 50 Hz of capacity more than or equal to 200 ltr, PUF insulation minimum thickness 60 mm complete all as specified and directed. Make: Bluestar / Godraj / Voltas
Supply, installation,commissioning of Hard top single lid, Deep Freezer single phase 230 volt, 50 Hz of capacity more than or equal to 300 ltr, PUF insulation minimum thickness 60 mm complete all as specified and directed. Make: Bluestar / Godraj / Voltas
Supply and fix 1.0 KVA wall/floor mounted type Electronic Voltage stabilizer for automatic operation, single phase naturally air colled indoor type & designed for input variation between 120 V to 280V with output voltage stabilized at 230 V with accuracy of (+/-)2.5% complete all as specified and as directed. Make: Bluestar / V Guard / Microtech
Supply and fix 5.0 KVA wall/floor mounted type Electronic Voltage stabilizer for automatic operation, single phase naturally air colled indoor type & designed for input variation between 120 V to 280V with output voltage stabilized at 230 V with accuracy of (+/-) 2.5% complete all as specified and as directed. Make: Bluestar / V Guard / Microtech
Copper tube (extra if required) for fixing of split Air conditioning of size 1/2 inch with insulating material all as specified and directed
Copper tube (extra if required) for fixing of split Air conditioning of size 1/4 inch with insulating material all as specified and directed
Supply, Installation testing and commissioning of electrically driven horizontal six stages centrifugal pump, CI impeller having suction x delivery nozzle size 65 x 50 mm shaft and shaft sleeves coupled with 37KW / 50HP fan cooled squirrel cage induction motor foot mounted, 415 volts, 50Hz, 3phase, 2900 rpm mounted on a common base plate with coupling guard suitable for discharge of 37.85 CMH at a total head of 175 Mtr complete all as specified and directed. Make: Kirloskar model RKB 50 / 15E or equivalent in CG / Havells
Supply, Installation testing and commissioning of electrically driven horizontal monoblock centrifugal pump,SS impeller having suction x delivery nozzle size 65 x 50 mm shaft and shaft sleeves coupled with 11 KW / 15 HP squirrel cage induction motor , 415 volts, 50 Hz, 3 phase, 300 rpm mounted on a common base plate with coupling guard suitable for discharge of 8.1 - 4.9 LPS at a total head of 52 - 76 Mtr complete all as specified and directed. Make: Kirloskar model KDS - 1575+ or equivalent in CG / Havells
Supply, Installation testing and commissioning of electrically driven horizontal monoblock centrifugal pump,SS impeller having suction x delivery nozzle size 65 x 50 mm shaft and shaft sleeves coupled with 7.5 KW / 10 HP squirrel cage induction motor , 415 volts, 50 Hz, 3 phase, 3000 rpm mounted on a common base plate with coupling guard suitable for discharge of 28.3 - 10.8 CMH at a total head of 40 - 68 Mtr complete all as specified and directed. Note for item No 1, 2 and 3 : (i) The quoted unit rates shall deemed to be included the Base Plate, coupling and coupling guard, gland packing etc. (ii) Necessary PCC in filling and foundation and plastering work shall be measured and paid separately under respectiv item of BoQ. Make: Kirloskar model KDS - 1065++ / 15E equivalent in CG / Havells
M&L for PCC 1:2:4 (B1) with 20 mm grade stone aggregate for foundation filling, mass concrete for foundation / basement of pump set as per manufacturer design complete all as specified and directed
M&L for rendering 10mm thick cement plaster 1:3 on fair faces of concrete surfaces (pump set basement) complete all as specified and directed
S&F PVC insulated, PVC round sheathed copper conductor (flexible) cable industrial, multicore, 1100 volts grade single core of 25 sqmm for connection of Pump Sets to starter panel cutting to required length with copper lug complete all as specified and directed. Make - Havells/Finolex/Polycab
S&F PVC insulated, PVC round sheathed copper conductor (flexible) cable industrial, multicore, 1100 volts grade 3 core of 6 sqmm for connection of Pump Sets to starter panel cutting to required length with copper lug complete all as specified and directed. Make - Havells/Finolex/Polycab
S&F DOL starter in SS enclosure 15 HP capacity, 11 KW, over load range 14 – 23 Amps suitable for 15 HP Centrifugal pumping set including taking down old star delta starter. (Make – L&T cat part No – SS94352 or equivalent of BCH / Siemens / Havells)
S&F DOL starter in SS enclosure 10 HP capacity, 7.5 KW, over load range 9 – 15 Amps suitable for 10 HP Centrifugal pumping set including taking down old star delta starter. (Make – L&T cat part No – SS94351 or equivalent of BCH / Siemens / Havells)
S&F star delta starter in SS enclosure 50 HP capacity, 37 KW, over load range 30 – 50 Amps suitable for 50 HP Centrifugal pumping set including taking down old star delta starter. (Make – L&T cat part No – SS94021 or equivalent of BCH / Siemens / Havells)
Earthing complete with galvanised steel earth plate electrode 600×600×6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less'than 1.5 metres below normal ground level, connected to galvanised iron wire 4 mm as earthing lead by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No. 3 connected to earthing test point all as specified or indicated including testing on completion
Earthing complete with galvanised steel earth plate electrode 600×600×6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less'than 1.5 metres below normal ground level, connected to galvanised iron strip 32x6 mm as earthing lead by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No. 3 connected to earthing test point all as specified or indicated including testing on completion
Supplying, installing, commissioning and testing complete of manufacturer of OEM (Original Eqpt Manufacturer) manufactured and tested static Silent Diesel Engine Driven Generating Set CPCB 4 Plus including inbuilt manual panel capable of delivering 200 KVA, 415 volts (AC 3 Phase, 4 wire system of supply) 50 Hz at power factor 0.8 minimum. The DG set shall consist of a diesel engine coupled through flexible coupling to a matching alternatore and mounted on a common MS channel base frame and threafter intalled in the CPCB 4 Plus approved acoustic enclosure with control panel standardised by manufacturer, fix exhaust pipe including four wheel trolly of suitable size as per manufacturer reccomendation complete all as specified and directed. Note : Trolly will be measured and paid saperatelly. Make of DG: Cummins / Kirloskar / Greavs Cotton (a) ENGINE (PRIME MOVER). Diesel Engine 1500 RPM of suitbale BHP as recommended by manufacturer but not less than 249.1 BHP (at NTP) Liquid cooled, Turbocharged, 2 x 12 Volts electric battery start, complete with fly wheel and all standard fittings / fixtures as per manufacturing practice including manual engine control panel with tachometer, lub oil temp & pressure gauge, water temp guage and frequency meter including safety shutdown etc. (b) ALTERNATOR. AC alternator, self excited, self regulated, self ventilated, brushless design, conforming to BS 2613/IS 4722, 3 Phase, 415 volts, 50 Hz, 4 wire system output 200 KVA PF 0.8 1500 RPM insulation class `H' enclosure IP 23 / TEFC complete with AVR with + 1% voltage regulation directly coupled to and match the above engine. (c ) BASE FRAME. Made out of structural steel as per Manufacturer's recommended design/specefications. (d) ACCOUSTIC ENCLOSURE. Provn of an integral type approved/certified acoustic enclosure as per CPCB norms for the DG sets restricted the noise level to 75 db at one meter along and temp rise within canopy shall not exceed 5° to 7° Celsius. It shall be made of 16 SWG CRCA MS sheet with powder coated finish on outside and provided with non igniting fire retardant foam as accustic material. There shall be four hinged doors out of which one shall be with a glass window. The base frame shall be ISM section. It shall also include the followings:- (i) Internal wiring with PVC copper conductor cables, IS 694 marked, FRLS in conduit and LED light fittings. (e) Battery 2 Nos 12 V DC charged/sealed maint free of suitable cap all inclusive of engine/alternator protective foundation with LCD display. Make : EXIDE/AMCO (f) Control Panel (g) CATALOGUES. Operation and Maintenance manual, spare parts list, overhauling manual (h) Diesel Exhaust Fluid (DEF) Tank : lDEF / Aqueous urea to sets off the chemical reaction with Exhaust gas DOC & SCR system sets off the reaction to meet the latest CPCB norms to reduction in PM, Nox & HC etc. Note :- 1. Consumption of FOL in testing inclusive of quotes rate. Note : - 2. Emission control conforming as per latest CPCB norms as circulated vide E-in-C's Branch latter No 62888/Gen-Misc-2/E4 (U-4) dt 21 Aug 2021
Provision of Trolley of DG Set comprising of 4 wheel double axle trolley with 10/20 tyres, leef spring suspension, Suitable to hold DG Set canopy Size (LxWxH) 4050 mm x 1350 mm x 1850 mm (Size of DG canopy may vary) and can take a approx weight 4000 kg, along with turn Table, Parking brakes and 2 Nos Screw Jack assembly, 8 mm thick top plate, and providing minimum 600 mm platform all round DG Set with 40 mm MS pipe ralling for operation and maintenance of DG set. The Mobile unit Set will bolted on frame on trolley complete with all the following specifications. MAIN BEAM - Size 200 X150 MB MAIN BEAM CROSS NUMBERS - Size 125 X 125 MB SIDE BOUNDRY BEAMS - Size 125X75MC TYRES - BRILLA ULTRA MILLER - Size 10/20 WHEEL RIM WITH HUB - Size 10 HOLES SPRINGS - Size 15 NOS X 13/75 THK LANDING GEAR - MECHANICAL SIDE CROSS NUMBERS - Size 125X75 MB REBAR - Size 100X50 MC TURNING PLATE WITH FRAME - Size 125 X 75 MC - 12 MM PLATE TRAILER AXLE - Size 125 MM ROUND BED - Size 16 MM PLATE REBAR HOOK - Size 50 MM ROUND PLATFORM PLATE - Size 8 MM THICK RALLING PIPE - 40 MM ROUND
Supply, fixing & testing of 1100 volts grade, XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured LT electric power under, heavy duty with aluminium conductor of cross sectional area 150 sqmm 3.5 core with all fixing & connecting accessories such as Aluminium cable lugs, nut, bolts, washer etc complete as specified and as directed. Make: Havells / Polycab / KEI
Supply and fix ON LOAD change over switch as per IS / EC-60947-3 415 V in sheet metal enclosures 4 pole of capacity 320 Amps complete all as specified and directed. Make: Havells / L&T / C&S
Supply single core 16 Sqmm HRFR PVC insulated industrial grade copper conductor - 30 mtr (unsheated) flexible cable, 1100 volts conforming to IS-694 and spike for copper earthing SS 14 mm Size 1 mtr length 04 Nos, including required size lug, nuts, bolts and washers (For portable earthing purpose).
S and B Electricals
M/S. SUBHAS CONSTRUCTION CO.
Rajan Traders
Electromech Engineers
INDO CONSTRUCTION
M/s JK Jangid and Company
RS COOLING APPLIANCES
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .