Loading…
Loading…
Tender Value
₹45 L
EMD Value
₹90,000
Closing Date
30 Jun 2026, 6:00 pm
Lt Col Suraj Sadasivan
Military Engineer Service Garrison Engineer (AF) No.1 Air Force Station No 1 Jamnagar 361003
REPAIR/ MAINT OF LT UG CABLES WITH CONNECTED ITEMS UNDER GE (AF) JAMNAGAR NO. 1
2026_MES_770637_1
8401/E8
Open Tender
Miscellaneous Works
270 days
JAMNAGAR
6 documents required · 6 mandatory
₹500
GE (AF) Jamnagar No 1
₹90,000
Yes
9 Jun 2026
9 Jun 2026
1 Jul 2026
9 Jun 2026
30 Jun 2026
23 Jun 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Excavation in trenches in soft/loose soil not exceeding 1.5 metre wide and not exceeding 1.5 metre deep for laying/taking out of cables and foundation of poles etc. and getting out, complete all as specified and directed. | 1,398.6 | Cum | - | - |
| 2 | Excavation trenches not exceeding 1.5m wide and not exceeding 1.5m depth for laying of cables and erectioning of poles and getting out in any Hard /Dense soil all as specified and directed. | 25 | Cum | - | - |
| 3 | Returning, filling in trenches (soil), including spreading, levelling and well ramming in layers not exceeding 25 cm thick, complete all as specified and directed. | 842.56 | Cum | - | - |
| 4 | Removal of surplus excavated soil to a distance not exceeding 50metre and depositing where directed at a level not exceeding 1.5metre above the starting point, complete all as specified and directed. | 556.04 | Cum | - | - |
| 5 | Material and labour, sand cushioning with a layer of dry river sand, 80mm thick before laying of cable and 150mm thick (punned down to 100mm thick) after laying of cables, in trenches/ducts, complete all as specified and directed. Note : Punned down thickness (overall 18cm), shall be considered for measurement and payment. | 419.58 | Cum | - | - |
| 6 | Supplying and laying un-reinforced precast concrete cable cover, classLV, Type 1, flat, size 250 mm x 150mm x 40mm complete all as specified and directed by Engineer in charge | 22,560 | Each | - | - |
| 7 | Laying only old un-reinforced precast concrete cable cover, classLV, Type 1, flat, size 250 mm x 150mm x 40mm complete all as specified and directed by Engineer in charge | 6,000 | Each | - | - |
| 8 | Taking out / down old existing LT 1100 volt grade cables of size 2x16Sqmm, aluminium conductor, XLPE, armoured, removal to store for re-use or for credit, complete all as specified and directed
Note : Excavation shall be measured and paid for separately | 950 | RM | - | - |
| 9 | All as per Serial Item No. 8 here-in-before but 16 Sqmm 4 Core size | 750 | RM | - | - |
| 10 | All as per Serial Item No. 8 here-in-before but 25 Sqmm 4 Core size | 850 | RM | - | - |