| 1 | L1₹4.2 CrAccepted-AOC | ₹4.2 Cr | L1 | Accepted-AOC L1 |
| 2 | L2₹5.3 Cr+₹1.0 Cr (24.2%)Rejected-Finance 42 608A PULLOMPARAMBIL HOUSE MANDAKARA ROAD KOCHI 682 018 | ERNAKULAM | KERALA | 682018 | ₹5.3 Cr+₹1.0 Cr (24.2%) | L2 | Rejected-Finance Not lowest |
Tender Value
₹4.2 Cr
EMD Value
₹5.7 L
Closing Date
10 Jun 2024, 6:00 pmClosed
CHIEF ENGINEER RND SECUNDERABAD
CHIEF ENGINEER RND SECUNDERABAD PICKET OPP JUBILEE BUS STATION SECUNDERABAD 500003
ADDITION ALTERATION INCLUDING SPECIAL REPAIRS TO BLDG No. P-22 (TIRC) AT NPOL KOCHI
2024_MES_651576_1
86126
Open Tender
Civil Works
Lump-sum
365 days
NPOL Kochi
Class A
Category a (i)
8 documents required · 8 mandatory
₹2,000
ASSISTANT GARRISON ENGINEER RND KOCHI
₹5.7 L
Yes
16 Jul 2024
29 Apr 2024
17 Jun 2024
29 Apr 2024
10 Jun 2024
27 May 2024
Amount
Schedule 'A' Part - I (BUILDINGS AND STRUCTURES) This Schedule (contains under mentioned Sl. item No. 1.01) is not prepriced by MES and the prepriced rate indicated in Col - 5 as `0.00 indicates this fact only. The tenderer is required to quote their rates in Column 6.
Lumpsum price worked out by the contractor for "Construction of ground plus two storey building for lecture hall with RCC framed structure upto and including provision of 50m crumple joint" complete all as shown on drawings and as specified.
Lump sum price worked out by the Contractor for "ADDITION / ALTERATION INCLUDING SPECIAL REPAIRS TO BUILDING No. P-22” as listed in Schedule ‘A’ Part - II representing _________________ % _________________________________ percent Above / Below the lumpsum price of `72,22,951.17 inserted by the MES in Schedule ‘A’ Part - II
Lump sum price worked out by the Contractor for “DEMOLITION / DISMANTLING” as listed in Schedule ‘A’ Part - III representing _______ % ______________ percent Above / Below the lump sum price of `2,19,655.08 inserted by the MES in Schedule ‘A’ Part - III
Lump sum price worked out by the Contractor for “INTERNAL ELECTRIFICATION” as listed in Schedule ‘A’ Part - IV representing _________________ % ________________________________ percent Above / Below the lump sum price of `16,05,312.48 inserted by the MES in Schedule ‘A’ Part - IV
Lump sum price worked out by the Contractor for “FIRE ALARM SYSTEM” as listed in Schedule ‘A’ Part - V representing _______ % _______________ percent Above / Below the lump sum price of `0.00 inserted by the MES in Schedule ‘A’ Part - V
Lump sum price worked out by the Contractor for “LIFT” as listed in Schedule ‘A’ Part - VI representing _______ % _________________ percent Above / Below the lump sum price of `24,150.80 inserted by the MES in Schedule ‘A’ Part - VI
Lump sum price worked out by the Contractor for “AIR CONDITIONING” as listed in Schedule ‘A’ Part - VII representing _________ % ______________________ percent Above / Below the lump sum price of `22,608.92 inserted by the MES in Schedule ‘A’ Part - VII
Lump sum price worked out by the Contractor for “EXTERNAL ELECTRIC SUPPLY” as listed in Schedule ‘A’ Part - VIII representing ______ % _________________ percent Above / Below the lump sum price of `10,02,940.50 inserted by the MES in Schedule ‘A’ Part - VIII
Schedule 'A' Part - IX This Schedule is not prepriced by MES and the prepriced rate indicated in Col - 5 as `0.00 indicates this fact only.The tenderer is required to quote their rates in Column 6. This Schedule constitutes Sl. Item No. 10 to 133
ADDITION / ALTERATION INCLUDING SPECIAL REPAIRS TO BUILDING No. P-22 Supply & fixed, CP health faucet with flexible tube upto 1 metre long fitted to European type W.C. of quality and make as approved by Engineer-in-Charge.
S&F, aluminium anodised deco grill of size 150 x 150mm fitted with 'C' channel fixed to wall all as specified and directed.
Providing & fixing, false ceiling at all heights with Mineral fibre beveled regular edged ceiling tiles 595 x 595mm, 12mm thick with bio-block conforming to ISO 5 (class 100) specifications in true horizontal level suspended on interlocking metal powder coated T-Grid of hot dipped galvanised iron section of 0.40 mm thick on Silhouette profile, rotary stiched double webbed white with 6mm reveal profile white / black), comprising of main-T runners of size 15 x 42mm of length 3000mm, cross-T of size 15 x 42mm of length 1200mm and secondary intermediate cross-T of size 15 x 42mm of length 600mm to form grid module of size 600 x 600mm, suspended from ceiling using galvanised mild steel items (galvanizing @ 80 grams per sqm) i.e. 50mm long, 8mm outer dia dash fasteners, 6mm dia fully threaded hanger rod upto 1000mm length and L-shape level adjuster of size 85 x 25 x 2 mm. Galvanised iron perimeter wall angle of size 22 x 19 x 0.40 mm of length 3000 mm to be fixed on periphery wall / partition with the help of plastic rawl plugs at 450 mm center to center and 40mm long dry wall S.S screws. The work shall be carried out as per specifications, drawing and as per directions of the Engineer-in-Charge.
S&F, display / name boards of area not less than 3 Sqmm made out of brush finished stainless steel sheet including engraving and painting letters as directed and approved, fixed with stainless steel screws including drilling holes, rawl plugs etc complete all as per the direction of Engineer-in-Charge.
S&F, position in alphabetical letters in Hindi or English and signs arrows etc made of stainless steel sheet of grade SS 304 L of thickness 1mm and fixing to MS sheet cladding with necessary fixing arrangements size of each letter 45 CM in width & 60 cm in height and thickness of letter 40 mm so as give a shape of 3D complete all as specified and directed.
S&F, roller blinds for windows UV protection, waterproof of approved colour and pattren nylon, operation unit with internal gear system and other special nylon combined with acrylic fittings with integral gear adjusting system and nylon chord with double ball chain and synthetic / Dol by Jacque of choice colour fabric, with quality component for extra maintenance free operations including all fittings complete all as specified and directed.
Making hole and fixing metallic packer for injecting hydrophobic Pufoam and sealer as per manufactures instruction (Avg I metallic packer per sqm) complete all as specified and directed. Make: STP, Build core chemicals, MC bouchmie, Pidilite or equivalent.
M&L for CORESEAL 357 A / CORESEAL 357 CAT (foaming agent) for carrying out non destructive water proofing treatmentusing construction chemical methods such as 1) HYDROPHOBIC PU GROUTING including cleaning of surface with wire brush detecting the source of leakages complete all as specified and directed. Make: STP, Build core chemicals, MC bouchmie, Pidilite or equivalent.
M&L for second course injection of CORESEAL 135 A / CORESEAL 135 B (sealing agent) complete all as specified and directed. Make: STP, Build core chemicals, MC bouchmie, Pidilite or equivalent.
S&F, aluminium extruded tubular and other aluminium sections as per the architectural drawings and approved shop drawings, the aluminium quality as per grade 6063 T5 or T6 asper BS 1474, including super durable powder coating of 60-80 microns conforming to AAMA 2604 of required colour and shade as approved by the Engineer-in-Charge. (The item includes cost of material such as cleats, sleeves, screws, anchor bolts etc, necessary for fabrication of extruded aluminium frame work. Nothing extra shall be paid on this account). The weight of aluminium extruded section shall be taken for purpose of payment.
S&F, Aluminium Composite Pannels (ACP) comprising of 4mm thick protective film PVDF coating aluminium coil, adhesive film (Dupont) polyethylene core strengthened monolithical ACP sheet of approved colour and shade in the vision panels etc, all complete for the required performances as specified as per the architectural drawings / as per the approved shop drawings, as specified and as directed by the Engineer-in-Charge.
DEMOLITION / DISMANTLING Dismantling of aly brading around the FRP sheets complete all as specified and directed.
Dismantling FRP transulent sheets complete all as specified and directed.
INTERNAL ELECTRIFICATION S&F, recess mounted LED luminaire 36 watt and fixture size 2ft x 2ft complete with high performance LEDs and electronic driver with range 150-270V AC duly pre wired including fixing arrangement on ceiling and making electric connection by providing 3 core copper cable from ceiling rose to fitting, colour temperature -5700K or above, IP20 or above, power factor >0.95 complete all as specified and directed.
S&F, LED batten 20 watt surface / wall mounted type with aluminium housing and integrated electronic driver and necessary fixing arrangement and making electronic connection with 3 core copper cable from ceiling rose to fitting, high optically efficient polycarbonate diffuser, colour temperature -6000K, IP20, complete all as specified and directed.
S&F, LED batten 10 watt surface / wall mounted type batten fittings specially designed extruded thermal aluminium housing, high optically efficient polycarbonate diffuser inbuilt electronic driver and necessary fixing arrangement and making electronic connection by providing 3 core copper cable from ceiling rose to fitting complete all as specified and directed.
S&F, exhaust fan, PVC body, AC single phase, 230 V of size 250 mm sweep with blades, rated speed min 1350 RPM including frame and louvers, low wattage, minimum noise including making a hole of required size for fixing of fan and make good the disturbed surfaces to match with the existing surface complete all as specified by Engineer-in-Charge.
M&L for telephone socket RJ 11 with shutter including frame and modular cover plate with frame complete all as specified and directed.
M&L for MCCB vertical DB 8 way, with space for 125 Amps, 4 pole MCCB incomer, double door with 200 Amps copper bus bars, neutral links, blanking plates, IP 42 and provision for SP/TP out going. The DB shall be suitable for flush mounting complete all as specified and directed.
M&L for MCCB vertical DB 4 way, with space for 100 Amps, 4 pole MCCB incomer, double door with 200 Amps copper bus bars, neutral links, blanking plates, IP 42 and provision for SP/TP out going. The DB shall be suitable for flush mounting complete all as specified and directed.
S&F, MCCB 4 pole, 125 Amps, 25 KA breaking capacity suitable incomer for MCCB DB complete all as specified and directed.
S&F, MCCB 4 pole, 100 Amps, 25 KA breaking capacity suitable incomer for MCCB DB complete all as specified and directed.
S&F, LED light fitting 36 watts of fixture size 2ft x 2ft recess mounting type complete with high performance LEDs complete with all accessories and electronic driver, LEDs etc duly prewired including fixing arrangement in surface and making electric connection with suitable 3 core copper cable from ceiling rose to fitting complete all as specified and directed.
S&F, LED security light fitting 36 watts made out of die cast aluminium housing with toughened glass and high power LEDs complete with all accessories and electronic driver, LEDs etc with IP 65 protection duly pre-wired and fixing arrangement on wall surface at suitable height by providing GI bracket medium grade of suitable size and adequate length with necessary fixing clamps and making electric connection by providing 3 core copper conductor cable from ceiling rose to light fitting complete all as specified and directed.
S&F, BLDC type ceiling fan 1200mm sweep, air delivery 210 cfm complete with blades, down rod and other accessories, BEE five star rated with brushless direct current motor and making connections by providing suitable copper cable from ceiling rose to fan complete all as specified and directed.
FIRE ALARM SYSTEM Supply, installation, testing & commissioning of FACP of micro processor based 2 wire fault tolerant loop, required loop for minimum 200 addressable detectors and 200 addressable modules (each loop accessing minimum 99 detectors and 99 modules) fire alarm / detection control panel. The panel shall be able to give location of all fire / fault conditions of addressable units via the address codes. Further the panel must be able to automatically switch ON/OFF respective control module whenever any alarm is triggered. The panel shall have rectifier, loop cards, LCD unit to indicate fire fault signal with address and analog output, external / inbuilt printer to log all fire / fault events complete in all respects. The panel shall have integrated fire fighters telephone command centre and it shall annunciate 10 fire fighter telephone zones through touch / key pad. The panel shall include 10 control modules for fire fighter telephone zones. The panel shall have a built in power supply and battery charger alongwith maintenance free 7AH, 2 x 12 Volt SMF lead acid batteries capable of running for a minimum of 2 hours with battery charger complete all as specified and directed.
Supply, installation, testing & commissioning of intelligent, active, repeater panel with minimum 80 character LCD display charger. The panel shall have feature for annunciation of all alarm and fault situations & loop resetting facility alongwith maintenance free battery 7AH, 1x12V for backup up to 2 Hrs complete all as specified and directed near main gate.
Supply, installation, testing & commissioning of detectors complying with and type certified to EN - 45 Addressable type muiltisensor detectors with heat and smoke combination complete all as specified and directed by the Engineer-in-Charge.
Supply, installation, testing & commissioning of manual call point to initiate audio alarm with a breakable glass cover / resettable, intelligent addressable type complete all as specified and directed.
Supply, installation, testing & commissioning of addressable electronic sounder cum strobe complete all as specified and directed by the Engineer-in-Charge.
Supply, installation, testing & commissioning of Addressable Control Module complete all as specified and directed by the Engineer-in-Charge.
Supply, installation, testing & commissioning of Fire Alarm Sirens / sounders electronic type horizontal single stage continous normal operation for atleast 50 minutes with sound level 65 DB to 120 DB measured at 1.5 Mtr with sound output variation of +5 DB, range upto 1000m complete all as specified and directed by the Engineer-in-Charge.
Supply, installation, testing & commissioning of Response Indicator for addressable detectors which are placed in above celling area complete all as specified and directed.
Supply, installation, testing & commissioning of PVC insulated, PVC sheathed cable galvanized steel strip or wire armoured, electric control cables (heavy duty) with stranded copper conductor of size 1.5 Sqmm 2 core 1100 Volts grade red in colour and fixed on wall surface by providing saddles clamps etc complete all as specified and directed.
Supply & installation of mounting box for electronic Sounder cum Strobe and detectors complete all as specified and directed by the Engineer-in-Charge.
Supply, installation, testing & commissioning of Loop Isolator Module, isolates against short circuits, providing approx after 20 detectors complete all as specified and directed by the Engineer-in-Charge.
S&F, category 6 cable for panel networking from LAN connector to fire section at main gate with and including PVC conduit of suitable dia laid in trenches / walls etc and making connections complete all as specified and as directed by Engineer-in-Charge.
Taking down old unserviceable fire alarm cable alongwith connected accessories and fire alarm panel etc and removing from site for taking credit under relevent items of schedule complete all as specified and directed.
LIFT Design, supply, installation, testing & commissioning electrically operated microprocessor controlled passengers lift, speed 1.0/ 1.5 metre/sec, lift with single speed motor 415 volts, 3 phase, AC 50 Hz supply conforming to IS - 14665, single phase 230 Volts Auxilary supply system, suitable to carry 8 Passengers (544 Kgs) and serve 2 floor (G+2 upper floors) having SS car enclosure with Micro processor based AC Variable Voltage & Variable Frequency drive (VVVF drive), 2 speed automatic control drive, complete with all standard accessories all specified below: -
(a)Type of lift: 8 passenger (b) Load capacity: 544Kgs (c) Speed : 1/1.5m/sec with single speed motor, 415 Volts, 3 Phase. (d) Type of drive: AC Variable Voltage, Variable Frequency drive (VVVF). (e) Type of machine: Geared and directly coupled vertical traction. (f) Car size: Not less than 1.45 sqm and allowable tolerance as per IS: 14665 (g) Car door: Staineless steel door door with hairline finish (N-304) for car and landing at all floors. (h) Car enclosure: Sliding stainless steel doors, car cage and frames etc shall be made out of minimum 1 mm thick stainless steel and vandal proof (scratch free, hairline finish) as well as cage roof covered with stainless steel sheets of suitable size panelling with suitable nos of LED lights and concealed fan in stainless steel grill.
(j) Flooring: Flooring with 18mm thick granite slab over 5mm thick SS plate. (k) Door opening (Inside): Protected by centre opening stainless steel doors with hairline finish with clear opening of 800 x 2000mm telescopic heights. (l) Car and counter weight guide: Guide rails of T section mild steel. (m) Signals:- (i) Combined luminous hall butoons with digital hall postion indicators at all floors. (ii) One no car operating panel with touch screen buttons in the car.
(iii) Vaccum filled display for car position indicator of stainless steel and overload warning in car. (iv) Car direction indicator in car and landing. (v) Battery operated alarm bell and emergency light (rechargable) alongwith suitable maintenance free battery. (vi) Fire mans switch one No per lift to be installed at Ground floor near landing door. (vii) All signal fizture and car opearting panel on stainless steel face plate. (vii) 3D infra red sensor safety edge of door for entire height. (viii) Built in annnouncing system hands free. (ix) Stainless steel hand rail 40mm dia all around inside the car cabin. (x) Stops and opening all on the same side.
(m) Safety device: Automatic rescue device (ARD) system battery operated with and including maintenance free battery of suitable capacity and battery charger with optimum direction system in start operation requiring no human intervention rescues during power / system failure with latest power control devices. Make: APS / BHARAT BIJLEE / OTIS etc. (n) Operation: Simplex automatic & manual dual controlled operation with / without attendant. (o) Two separate earting complete all as specified in SSR Part-I, Plate No: 3 with GI strip of 32 x 6mm. (p) Machine room less system as per drawing.
(q) Hoist way construction: As shown in drawing. (r) AC-VVVF drive shall be of make: Yashkawa / Mistsubisshi / Fuji / Otis. (s) Control systm shall be of closed loop type. (t) Counter weight shall be cast iron or as recommended by OEM. Note: (i) The contractor shall submit the drawings at the time of sample approval of 8 passengers lift, data, design calculations, technical specification for approval of Accepting Officer. (ii) All system controls and devices as per standards codes, acts of lifts safety normsshall deemed to be included in quoted rate. The cost effect of testing and obtaining statutary certificate from lift inspector before commisioning by department shall deemed to be included in the rate contract.
(iii) The lift shall be taken over by the department only after producing the clearance from authorised lift inspector by bidder. The bidder has to consider this element while quoting the rates and no extra claim if any shall be entertained at a later stage. (iv) The contractor shall note that the defect liability period will be one year from the certified date of completion and during this period the lift shall be kept functional serviceable all the time and all consummable items shall also be provided by the contractor for satisafactory running of the lift. (v) Car and slide doors shall be made from SS 304 grade. (vi) Earthing and earth strip will be measured and paid separately.
AIR CONDITIONING Supply install, testing & commisioning of Modular type outdoor units equipped with highly efficient DC scroll compressors with all inverter type compressor(s) only, special acryl precoated heat exchanger, low noise condenser fan, auto check function for connection error, R410a Refrigerent, auto address setting and the equipment should deliver 100% capacity at 40 degree celcius ambient with out any deration. The equipment shall be flexible for operation at a voltage range of 320V-460V. Working Temperature upto 56 degree celcius.
12 HP Top Discharge Outdoor Unit.
24 HP Top Discharge Outdoor Unit.
28 HP Top Discharge Outdoor Unit.
Design, supply, install, testing & commissioning of VRF based 4-way cassette type IDU machine complete with fan & cooling coil suitable for R-410A, return air filter, insulated drain tray, drain pump complete with all necessary controls including air and refrugerant temparature sensors and electronic expansion valves providing individual, variable refrigerant flow the electronic expansion valve of IDU shall be controlled by the microprocesser control system via a control board with in the indoor unit that includes a unit address recognition system, and indoor units shall trip in case of fire signal, units for critical rooms shall work on working and stanby sequential basis complete all as specified and directed. Make: Voltas / Carrier / Blustar / Daikin. Note: The rate is inclusive of cordless remote of indoor units, remote receiver, decorative panel for casstte units.
5.0 TR Four Way Cassette Indoor - 1200cfm - 910 x 910 x 293mm.
2.8 TR Four Way Cassette Indoor - 900 cfm - 840 x 840 x 320mm.
2.3 TR Four Way Cassette Indoor - 650cfm - 840 x 840 x 240mm.
Supply, installation, testing & commissioning of VRF Cassette Hiwall Units of 2TR capacity and 650 CFM with necessary fittings.
Supply, install, testing & commisioning of wifi based central controller for entire VRF system, the scope includes the control wiring and conduiting of the same in a lot complete all as specified and directed.
Supply, install Refnet (Y/T) joints as per manufactures recommendation complete all as speicified for indoor units.
Supply, install Refnet (Y/T) joints as per manufactures recommendation complete all as speicified for outdoor units.
Design, supply, install testing & commisioning of hard drawn copper refrigerent suction and discharge pipes for VRF indoor and outdoor units with necessary copper fittings laid neatly, secured with GI clamps and wall brackets with pipe supports as per technical specification at every 2.4 mr intervel and at bends including nitrile rubber insulation, UV treatment (coating) for exposed refrigerent piping insulation complete all as specified and as required at site.
44.5 mm with 19 mm thick insulation
41.3 mm with 19 mm thick insulation
34.9 mm with 19 mm thick insulation
28.6 mm with 19 mm thick insulation
25.4 mm with 19 mm thick insulation
22.4 mm with 19 mm thick insulation
19.1 mm with 13 mm thick insulation
15.9 mm with 13 mm thick insulation
12.7 mm with 13 mm thick insulation
9.52 mm with 13mm thick insulation
6.4 mm with 13mm thick insulation
Supply, laying, testing flexible PVC insulated multistranded 1100 V grade copper conductor cable, 2 x 1.5 Sqmm aluminium shielded for communication bw IDU to IDU and ODU complete all as specified and directed. Make: Polycab / Havells / Finolex.
Supply, filling charging refrigerant gas 410A and oil required during commisioning of refrigerant piping including complete leak testing complete all as specified and directed.
Supply, installation, testing of CPVC drain pipe of 32mm dia connecting the drain lines from indoor units to nearest drain point, with U-trap, 9mm thick round nitrite rubber insulation supported on suitable size GI cable tray including chasing, drilling, concealing and making good the same complete all as specified and directed.
M&L for MS frame support for outdoor uniits with min 1 ft height on the terrace floor with anti corrosive primer painting complete all as specified and directed.
M&L for earthing with galvanised steel earth plate electrode of size 60cm x 60cm x 6mm thick buried directly in ground (earth pit not less than 2.25m deep below the ground level) with top edge of the plate not less than 1.5m below normal ground level, connected to the galvanised earth lead by means of bolts, nuts check nuts and washers of galvanised iron or steel using GI strip 32 x 6mm as earthing lead as shown in electrical plate No. 3 of SSR Part-I connected to earthing test point all as specified or indicated including testing on completion including necessary excavation and earth work in soft/loose soil, returning filling, disposal of surplus soil, earth pit in PCC 1:3:6 type C1 using 20mm graded stone aggregate pit, funnel, 20mm dia GI light grade watering pipe, 40mm dia GI medium grade earth lead protection pipe, CI frame and cover, wire, copper lugs etc mesh, chorcoal and common salt in alternate layer complete all as specified and directed by Engineer-in-Charge. Note: Cost of GI earth strip and GI protection pipe upto 7.5m length shall be deemed to be included in the rate quoted for this item.
Removing / taking down the old AC duct, small AHU including all accessories and closing the chiller in and out pipes complete in existing first floor of TIRC bldg No. P-22 including making good surface and the removal / dismantling of spares to be deposited in MES store yard.
Supply, install, test & commissioning of outdoor type double door LT feeder piller box suiatble for 3 phase, 415 Volts, 50 Hz cubicle type, floor mounted, self supported free standing, made out of 3.15 mm thick powder coated painting in 7 tank process CRCA sheet out door type totally enclosed weather dust and vermin proof as per IS-8623 and CPRI approved with front and rear opening with mechanical locking arrangement having copper bus bar of 600 Amps capacity for RYB and half for neutral and fixed on hygroscopic insulators with heat shrinkable sleeves and prewired with copper cables and protection fuses etc, including cnnecting and outgoing cables necessary PCC 1:3:6 in foundation and made out of 50 mm x 50 mm x 6 mm angle iron grouted at ground above 30 cm from ground level and IP 54 as per IS 2147 comprising of the followings. Note: Cost including necessary internal wiring to CT's and meters, control MCBs Cost -FOR VRF AC ODUs.
Incoming: (a) MCCB 320 Amps, 4 P, 36 KA, Ics =100% of Icu with adjustable thermal and magnetic setting Spreader & room - 01 No. Make: MDS Legrand / L&T / Havells / Indo Asian. (b) Indicating Lamp Red / Yellow / Blue - 03 Nos. (c) Digital MFM meter class-1 with CT - 01 No. Outgoings: (a) MCCB 63 Amps, 3 Pole, 16 KA, Ics-100% of Icu with adjustable thermal and magnetic setting spreader & room - 05 Nos. Make: MDS Legrand / L&T / Havells / Indo Asian. (b) MCCB 40 Amps, 3 Pole, 16 KA, Ics-100% of Icu with adjustable thermal and magnetic setting spreader & room - 02 Nos. Make: MDS Legrand / L&T / Havells / Indo Asian. (c) MCCB 32 Amps, 3 Pole, 16 KA, Ics-100% of Icu with adjustable thermal and magnetic setting spreader & rom - 03 Nos. Make: MDS Legrand / L&T / Havells / Indo Asian.
EXTERNAL ELECTRIC SUPPLY Supply, install, test & commissioning of outdoor type double door LT feeder pillar box suiatble for 3 phase, 415 Volts, 50 Hz cubicle type, floor mounted, self supported free standing, made out of 3.15 mm thick powder coated painting in 7 tank process CRCA sheet out door type totally enclosed weather dust and vermin proof as per IS-8623 and CPRI approved with front and rear opening with mechanical locking arrangement having copper bus bar of 600 Amps capacity for RYB and half for neutral and fixed on hygroscopic insulators with heat shrinkable sleeves and prewired with copper cables and protection fuses etc, including cnnecting and outgoing cables necessary PCC 1:3:6 in foundation and made out of 50 mm x 50 mm x 6 mm angle iron grouted at ground above 30 cm from ground level and IP 54 as per IS 2147 comprising of the followings. Note: Cost including necessary internal wiring to CT's and meters, control MCBs SP 6A, suitable lugs.
Incoming: (a) MCCB 400 Amps, 4 P, breaking cpacity-36 KA, Ics =100% of Icu with spreader & room-01 No, adjustable overload settings. Make: MDS Legrand / L&T / Havells / Indo Asian. (b) Indicating Lamp Red / Yellow / Blue - 03 Nos. (c) MFM meter class 1 with programmable CT and PT - 01 No. Outgoings: (a) MCCB 320 A, 4 Pole, 36 KA, Ics-100% of Icu with spreader & room - 01 No. Make: MDS Legrand / L&T / Havells / Indo Asian-VRF panel.
(b) MCCB 125 Amps, 4 Pole, 25 KA, Ics-100% of Icu with spreader & room - 01 No. Make: MDS Legrand / L&T / Havells / Indo Asian. (c) MCCB 100 A, 4 Pole, 16 KA, Ics-100% of Icu with spreader & rom - 01 No. Make: MDS Legrand / L&T / Havells / Indo Asian. (d) MCCB 63 A, 4 Pole, 16 KA, Ics-100% of Icu with spreader & rom - 01 No. Make: MDS Legrand / L&T / Havells / Indo Asian. (e) MCB 32 A, 4 Pole, 10 KA, Ics-100% of Icu with spreader & rom - 01 No.
S&F, LED security light fitting 40 Watts energy saving, envioronmental friendly, long life made up of pressure die cast aluminium housing with high power LEDs and polycarbonate cover as diffuser with IP 66 protection including fixing arrangement on wall by using GI bracket made out of GI pipe of size not less than 32 mm and length 1.5 m bend to shape and clamps / nut bolts and MS flat iron of 40 x 50mm shall be fixed and returning unserviceable old fitting. The bracket shall be painted with primer and two coats of aluminium paint complete all as specified and directed by Engineer-in-Charge. Make: Havells, Cat No: ENDURASUNDOWNSL40WLED765PASYBOPC or equivelent make of Crompton / Bajaj / Philips / Luker. Note: The rate is inclusive of 3 core PVC copper cable of 1.5 sqmm from light fittings to junction box and PVC conduit of size not less than 20mm.
S&F, street light junction box of size 168 mm x 253 mm x 115 mm made of high quality thermoplastic complete with electric terminals and MCB SP 6 Amps and fixing arrangement on wall surface by providing suitable clamps and making electric connectioins etc made of high quality thermoplastic type with hinges and 4 Nos, DIN mounted terminal suitable for 6 Sqmm XLPE cable, IP-66 (Dust and power jet Proof according to IEC 60529), shock proof, rust free, corrosion free acid and chemical resistant, fire retardant having high impact (IK 08) totally insulated (Class II) made of halogen and silica free recyclable material, UV resistant having high grade gasket made of polyurethane with copper bus bar 25 x 5 mm -04 strip with locking arrangement, nuts & bolt, etc, complete all as specified and directed. Make: Hensel Cat Part No. KG 9002 or its equivalent make of Syntex.
M&L for earthing with galvanised steel earth plate electrode of size 600 mm x 600 mm x 6mm thick buried directly in ground (earth pit not less than 2.25m deep below the ground level) with top edge of the plate not less than 1.5m below normal ground level, connected to the galvanised earth lead by means of bolts, nuts check nuts and washers of galvanised iron or steel using GI strip 32 x 6 mm as earthing lead as shown in electrical plate No. 3 of SSR Part-I connected to earthing test point all as specified or indicated including testing on completion including necessary excavation and earth work in soft / loose soil, returning filling, disposal of surplus soil, earth pit in PCC 1:3:6 type C1 using 20mm graded stone aggregate pit, funnel, 20mm dia GI medium grade watering pipe, 40mm dia GI light grade earth lead protection pipe, CI frame and cover, wire, copper lugs etc mesh, chorcoal and common salt in alternate layer complete aincluding removal of old unserviceable earth earth plates all as specified and directed by Engineer-in-Charge.
M&L for cable route indicator fabricated from 40 x 40 x 6mm angle iron 450mm long, rivetted or welded with 100mm dia CI or MS round disc duly engraved LT cable in letters including grouted in ground with PCC 1:4:8 type D2 complete all as specified and directed by Engineer-in-Charge.
Removing old unserviceable LT cable of any size and type from the existing location after disconnecting electrical connection complete all as speciified and directed by Engineer-in Charge.
WELTRONENGINEERINGSERVICES
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .