| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹6.3 LAccepted-AOC D NO 9 947 66 DOCTORS COLONY SHIVAJI PLEM VISAKHAPATNAM 530017 | VISAKHAPATANAM | ANDHRA PRADESH | 530017 | L1 | Accepted-AOC Being L1 | |
| 2 | L2₹6.9 L+₹51,915 (8.16%)Rejected-Finance | L2 | Rejected-Finance Being not L1 | |
| 3 | L3₹7.6 L+₹1.2 L (18.9%)Rejected-Finance 121 MADHAV SQUAR OPP AVANTIKA COMPLEX LIMDA LANE JAMNAGAR 361001 | JAMNAGAR | GUJARAT | 361001 | L3 | Rejected-Finance Being not L1 |
Tender Value
₹8.7 L
EMD Value
₹17,400
Closing Date
22 Feb 2022, 6:00 pmClosed
Shri Nitesh K Singh, IDSE AEE AGE (I) R and D NSTL
AGE (I) R and D, NSTL Complex, Visakhapatnam 530027
8363 OUTSOURCING OF SERVICES FOR OPERATION AND ROUTINE MAINTENANCE OF 3X70 TR WATER COOLED SCREW BASED CHILLED WATER A/C PACKAGE UNIT FOR MCC AND VIB I BLDGS AT DRDL KALINGA UNDER AGE (I) RnD NSTL, VISAKHAPATNAM.
2022_MES_503662_1
AGE I R AND D NSTL VIZAG 8363
Open Tender
Civil Works
Item Rate
335 days
Visakhapatnam
Class E Category c (i) , d (v)
7 documents required · 7 mandatory
₹500
Yes
₹17,400
Yes
10 Mar 2022
25 Jan 2022
24 Feb 2022
25 Jan 2022
22 Feb 2022
8 Feb 2022
Amount
Outsourcing of services for operation and routine maintenance of 3x70 TR central water cooled screw based chilled water air conditioning package type (2 working & 1 Standby) plant [Blue Star make] for VIB-I and MCC Building consisting of Semi hermetic twin screw based type compressors, Chiller water pumps - 03 Nos, Condenser Pump-03 Nos, chiller AHUs in different locations (18000CFM -02 Nos in MCC and VIB I Building and 10000 CFM - 02 Nos in VIB-I Building), cooling towers, electrical control panel boards complete including daily maintenance of plants log sheets for each plant, cleaning of plant rooms, machines, control panels and area cleaning all around the plant room including cutting of vegetation, grass etc. complete all as specified and as directed by the Engineer-in-Charge. Manpower:- Contractor shall employ One Semi Skilled Refrigeration Mechanic in General shift of 08 hours per day on all days including Sundays & Public Holidays.
Outsourcing of services for operation and routine maintenance of 3x70 TR central water cooled screw based chilled water air conditioning package type (2 working & 1 Standby) plant [Blue Star make] for VIB-I and MCC Building consisting of Semi hermetic twin screw based type compressors, Chiller water pumps - 03 Nos, Condenser Pump-03 Nos, chiller AHUs in different locations (18000CFM -02 Nos in MCC and VIB I Building and 10000 CFM - 02 Nos in VIB-I Building), cooling towers, electrical control panel boards complete daily maintenance of plants log sheets for each plant, cleaning of plant rooms, machines, control panels and area cleaning all around the plant room including cutting of vegetation, grass etc. complete all as specified and as directed by the Engineer-in-Charge. Manpower:- Contractor shall employ One Semi Skilled Refrigeration Mechanic per shift of 08 hours in 3 shifts (round the clock) per day on all days including Sundays & Public Holidays.
Supply and replace Wedge (V) Belts B - 72A for compressor & motor/ AHU & motor. [Make: Fenner/ Yule/ ContiTech]
Supply and replace Wedge (V) Belts B - 95 for compressor & motor/ AHU & motor. [Make: Fenner/ Yule/ ContiTech]
Supply and replace Wedge (V) Belts B-2253 LP /B87 for compressor & motor/ AHU & motor. [Make: Fenner/ Yule/ ContiTech]
S&F in repairs Starter Push Button switch with 1 NO + 1 NC complete working on DC/ AC supply up to 16 Amps capacity all as specified and as directed [Make: L&T ESBEE/ Siemens]
M&L for complete leak testing the entire central AC plant of capacity 70 TR capacity/ chiller unit consisting of compressors, condensers, chillers, AHUs with connected chilled piping, expansion valves and all accessories by flushing out the refrigerant gas present in the system, pumping Nitrogen gas at requisite pressure, locating leak positions, rectifying the leaks, including pressure testing and holding the pressure for 48 Hrs for observation for any pressure drop in the system and flushing out the complete system on rectification of leaks if any, vacuumising & de-hydration the complete system with heavy duty vacuum pump and removal of moisture and other foreign particles from the system complete including checking of all safety controls and parameters, testing & commissioning of the AC plant after charging the refrigerant gas all as directed by the Engineer-in-Charge. [Note: Supply & charging refrigerant gas will be measured and paid separately]
Supply only Nitrogen gas in manufacturer's sealed cylinder.
Supply only Refrigerant gas 'R- 134a' in manufacturer's sealed cylinder. Note for Sl. item No 8 & 9 - (i) Empty cylinder will be returned to contractor on completion of work (ii) Net weight of refrigerant gas shall be measured and paid under these items.
M&L for carrying out repairs to PCB boars/cards by replacing the damaged/ worn-out electronic components/ ICs with heat sinks complete for Central AC plants of various capacities from 70 TR to 160 TR complete including testing and commissioning all as directed.
S&F in repairs pneumatic safety valve for condensers of central AC plants of capacity 35/ 40/ 60/ 80/ 120/ 140 TR. [Make: Castle/ Brassolite/ Henry]
S&F in repairs flow control limit switch/ sensor as per the existing make/ model complete all as specified and as directed. [Make: Castle/ Rapid controls/ Honeywell]
S&F in repairs HP cutout on compressed/ pressurized gas lines complete all as directed. [Make: Danfoss / Indfos]
S&F in repairs LP cutout on compressed/ pressurized gas lines complete all as directed. [Make: Danfoss / Indfos]
LAKSHMI SAI CONSTRUCTIONS
suresh electricals
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .