| Sl No | Description | Qty | Unit | MAHAVEER TECHNO ENGINEERS L1 | MAYANK ELECTRICAL WORK L2 |
|---|---|---|---|---|---|
| 1.00 | Following work to be carried out for preventive maintenance of 2 No. 160 MVA(220/132KV), 2 No. 80 MVA T/F(132/33KV), 1 No. 50 MVA(220/33KV) & 1 No. 25 MVA T/F (220/33KV) (Two times in a year 6 x 2 times = 12).
(1) Checking of Oil level in main & OLTC conservator tank & bushings. (2) Attending minor Oil leakage/ seepage from main body/conservator tank/radiator of transformer by tightening. (3) Tightening of all bushing clamps & replacement of damage/defected clamps & connectors. (4) Rectification of electrical fault of auto/ mannual operation of cooling fans by replacement of electrical equipment like contactor, MCB, relay etc. (5) Tightening of neutral & main body earthing. (6) Cleaning & washing of trnasformer main tank/ radiator etc. (7) Tightening of all electrical connections in Transformer Marshalling Box & apply CRC on all connections/connectors/relays etc. (8) Testing of WTI & OTI and Buccholze relay & PRV. (9) Checking of earth resistance. (10) Replacement of jumpers including cutting/drilling in hole in clamps.
(11) Work of special maintenance on breakdown/crisis basis/fault tracing & removal or any other work as per site requirement or as per direction of site incharge. | 12 | Job | 9,650 ₹1,15,800 Lowest | 9,650 ₹1,15,800 Lowest |
| 2.00 | Following work to be carried out for Preventive maintenance of 220 KV, 132 KV, 220/132 KV & 220/33 KV Isolators (Two times in a year 22 x 2 times = 44). (1) Tightening of clamps and connectors & replace if found damage/defective. (2) Cleaning of porcelain insulators by CTC and checking of damage. (3) Replacement of rusted nut/bolts of Isolator/ hardware fiitings. (4) Tightening of male and female contacts and replace if found damage/defective. (5) Apply petroleum jelly between male/female contacts. (6) Tightening of earth link and its jaws. (7) Alignment of isolator and earth link. (8) Lubrication of all moving parts. (9) Testing of drive motor in cubical. (10) Tightening of all connections in Bay Marshalling Box. (11) Apply CRC on all connections in cubical. (12) Replacement of jumpers including cutting/drilling in hole in clamps.(13) Work of special maintenance on breakdown/crisis basis/fault tracing & removal or any other work as per site requirement or as per direction of site incharge. | 44 | Job | 5,600 ₹2,46,400 Lowest | 5,700 ₹2,50,800 |
| 3.00 | Following work to be carried out for Preventive maintenance of 220 KV Bay, 132 KV Bay, 220/132 KV Bay & 220/33 KV Bay equipments. i.e. CT/PT/CVT/LA/CB/Wave Trap (if installed) (Two times in a year 78 x 2 times = 156). Following work to be carried out for Preventive maintenance of 132 KV CT/PT/CVT/LA/Wave Trap. (1) Top up of oil after checking of oil level in CT/PT/CVT. (2) Checking of oil leakage and rectification if found. (3) Checking and tightening of clamps & Connectors etc. (4) Replacement of rusted nut/bolts if found damage in hardware fitting. (5) Checking and tightening of equipments earthing. (6) Checking the healtiness of surge arrester. (7) Filling of SF-6 gas in circiut breaker under breakdown/ preventive maintenance including shifting of SF-6 gas cylinder. (8) Replacement of jumpers including cutting/drilling in hole in clamps.(9) Work of special maintenance on breakdown/crisis basis/fault tracing & removal or any other work as per site requirement or as per direction of site incharge. | 156 | Job | 2,825 ₹4,40,700 Lowest | 2,950 ₹4,60,200 |
| 4.00 | Taking Specific gravity of individual cell (220 Cells) of each battery set and record it in battery register & Checking level of electrolyte in the cells and filling of distill water by making of distill water in distill water plant as per requirement. | 48 | Job | 3,370 ₹1,61,760 Lowest | 3,700 ₹1,77,600 |
| 5.00 | Cleaning of battery terminals and apply petrolium jelly on the terminals & Cleaning of battery set rack. | 12 | Job | 975 ₹11,700 | 900 ₹10,800 Lowest |
| 6.00 | Cleaning & maintenance of distill water plant by replacement of heating element, Switches & cabling etc. | 12 | Job | 975 ₹11,700 | 900 ₹10,800 Lowest |
| 8.00 | Checking of voltage of individual cell after turning off the batttery charger of each battery set. | 12 | Job | 975 ₹11,700 Lowest | 1,300 ₹15,600 |
Tender Value
Refer Docs
EMD Value
₹3 L
Closing Date
3 Jan 2025, 1:00 pmClosed
Superintending Engineer
SE O and M Circle PTCUL 26- Civil Lines Roorkee.
Preventive maintenance (AMC) of 220 KV and 132 KV equipments installed at 220 kv Substation SIDCUL Haridwar.
2024_PTCUX_78435_1
T-16/SE(OandM)CR/2024-25
Open Tender
Electrical Works
Item Rate
365 days
SIDCUL Haridwar
Please refer Tender documents.
3 documents required · 3 mandatory
₹590
Yes
SE O and M PTCUL Roorkee
₹3 L
Yes
27 Oct 2025
4 Dec 2024
4 Jan 2025
4 Dec 2024
3 Jan 2025
4 Dec 2024
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .