| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹6.3 LAccepted-AOC HOUSE NO 102 LANE NO 4 C ANAND NAGAR BOHRI JAMMU 180002 J K | JAMMU | JAMMU AND KASHMIR | 180002 | ₹6.3 L Quoted ₹6.6 L | L1 | Accepted-AOC lowest bidder |
| 2 | L2₹8.0 L+₹1.3 L (19.7%)Rejected-Finance | ₹8.0 L+₹1.3 L (19.7%) | L2 | Rejected-Finance OTHER THAN LOWEST BIDDER |
| 3 | L3₹8.9 L+₹2.2 L (33.4%)Rejected-Finance | ₹8.9 L+₹2.2 L (33.4%) | L3 | Rejected-Finance OTHER THAN LOWEST BIDDER |
| 4 | L4₹9.2 L+₹2.5 L (38.0%)Rejected-Finance 361 BEHIND DAV SCHOOL JAWAHAR NAGAR SRINAGAR 190008 | SRINAGAR | JAMMU AND KASHMIR | 190008 | ₹9.2 L+₹2.5 L (38.0%) | L4 | Rejected-Finance OTHER THAN LOWEST BIDDER |
| 5 | L5₹12.8 L+₹6.1 L (92.1%)Rejected-Finance BIAMATHANG BAROO KARGIL J K | KARGIL | KARGIL | J K | ₹12.8 L+₹6.1 L (92.1%) | L5 | Rejected-Finance OTHER THAN LOWEST BIDDER |
Tender Value
₹15 L
EMD Value
₹30,000
Closing Date
14 Jan 2023, 6:00 pmClosed
GE KARGIL
MES OFFICE KARGIL
REPAIR AND MAINT OF INTERNAL ELECTRIFICATION AND ALLIED WORKS IN VARIOUS UNITS AT KARGIL UNDER GE KARGIL
2022_MES_569646_1
GE/K-48/2022-23
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
KARGIL
Please refer Tender documents.
7 documents required · 7 mandatory
₹500
GE KARGIL
₹30,000
Yes
10 Mar 2023
17 Dec 2022
16 Jan 2023
17 Dec 2022
14 Jan 2023
1 Jan 2023
Amount
Taking down carefully copper or aluminium point wiring (light, fan, socket or power) complete, including fixture and fittings such as switches ceiling roses, pendants, sockets bulk, head fitting, tube light fitting by unscrewing carefully from boards etc and making good, distrubed surface of walls floors etc.
Point wiring with multi-stranded copper conductor PVC insulated and unsheathed cable in PVC casing and capping, 1.5 Sqmm with all fittings/accessories and including 1.5 Sqmm PVC insulated copper earth wire connected to common earth including closed recessed wooden terminal Boxes of suitable size made of 2nd class hard wood for mounting switches, sockets etc with 3mm thick laminated sheet cover for one light point or bell/buzzer point controlled by one switch, complete.
All as per Srl item No 02 here in before but for one 3 pin 5 Amps switch socket on same board.
All as per Srl item No 02 here in before but for one 3 pin socket outlet 5 Amps on independent board.
Description all as per item No 02 here-in-before but using 4 Sq mm single core copper conductor cable of multistranded PVC insulated unsheathed 1100 Volts grade for industrial plug socket. point including running of 2.5 Sq mm copper conductor PVC wire as earth continuity conductor along with wiring and connecting to the common earth dully.
Switch piano flush type 5 Amps, single pole one way.
Switch socket combination 2 in 1, and 3 and 2 pin, 5 Amps flush type.
Switch socket combination 2 in 1, 5 and 15 Amps flush type.
S&F in repair Ceiling rose surface bakelite 65x50mm, two to three terminals.
S&F in repair Sheet metal enclosure for DB's Single door, single pole and neutral, 240V, 8 way with 200 Amp rated bus bar including blanking plates where required. Complete all as specified and directed.
S&F in repair Sheet metal enclosure for DB's Single door, single pole and neutral, 240V, 6 way with 200 Amp rated bus bar including blanking plates where required. Complete all as specified and directed.
S&F in repair Sheet metal enclosure for DB's single door, single pole and neutral, 240V, 4 way with 200 Amp rated bus bar including blanking plates where required, complete all as specified and directed.
S&F in repair MCB, single pole and neutral, 63 Amp, 240V, 10KA.
S&F in repair MCB, single pole, 5 to 32 Amp, 240V, 10KA.
S&F in repair Sub main wiring with two single core 4 sqmm multistranded copper conductor cable, PVC insulated cable 1100 volts grade and 2.5 Sqmm as continous earthing drawing and including PVC casing and caping of suitable size with all acessories, complete all as specified.
S&F in repair Sub main wiring with two single core 6 sqmm multistranded copper conductor cable, PVC insulated cable 1100 volts grade and 4 Sqmm as continous earthing drawing and including PVC casing and caping of suitable size with all acessories, complete all as specified.
M&L in repair for Earthing complete with galvanised steel earth plate electrode 600mm x 600mm and 6mm thick buried directly in ground not less than 2.25 mtr deep below normal ground level with top edge of plate not less than 1.5 metres below normal ground level, connected to the Galvanized iron earth wire 4.0mm dia by means of bolts, nuts, check nuts and washers of galvanized iron protected by provision of G I light grade pipe 40mm bore including provision of concrete pit in PCC 1:2:4 type B1 using 20mm grade stone aggregate with 40mm thick cover of RCC 1:2:4 reinforced with XPM (weight not less than 4Kg/Sqm) and frame of angle iron 25x25x6mm with lugs two number and with 6mm dia MS bar handle made to shape and GI medium grade 20mm bore pipe for watering perforated at bottom 1.75m long placed on top edge of earth plate, common salt and charcoal filling, test point made out of 40mmx8mm flat iron with fixing arrangement funnel wire mesh and earth work in hard/dense soil, returing filling in and removal of surplus soil to a distance not exceeding 50M all as per electric plate No 5 of SSR Part-I conected to earth test point as specified or indicated including testing on completion.
S&F in repairLED building security light 45 watt energy efficient with bracket,suitable dia pipe for fixing the street light in wall all as directed.Make Havells Cat part No.ENDURAPERLINEOSL60WLED75PASYTOPC or equivalent in PHILIPS/WIPRO
S&F in repair 1100 volts grade heavy duty 6 sqmm 2 core flat cable PVC insulated aluminium stranded conductor, served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 01 metre apart including 4 mm suspension complete all as specified.
S&F in repair 1100 volts grade heavy duty 16 sqmm 2 core flat cableb PVC insulated aluminium stranded conductor,served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 1 meter apart including 4mm suspension wire withtwo single core cable complete all as specified.
S&F in repair LED 18 Watt Tubelight fitting decorative ultra slim square profile linear with extruded polycarbonate environment friendly Make Havells Cat part LHEXBTP7INW018/ LHEXBTP71N1W018
Note :Deduction for amount of Rs 30,882.00 as listed in Schedule A Part - II ( Schedule of Credit) shall be made while awarding of contract.
osho traders
Ms Salaria Builders
M/S TRADE LINK
M/S MOHD KHAN
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .