| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹22.9 LAccepted-AOC 43 MANAK BHAVAN FIRST FLOOR GUMANPURA KOTA 324 007 RAJASTHAN | KOTA | KOTA | RAJASTHAN | 324007 | L1 | Accepted-AOC Lowest and reasonable | |
| 2 | L2₹24.9 L+₹2.0 L (8.95%)Rejected-Finance | L2 | Rejected-Finance L2 | |
| 3 | L3₹25.1 L+₹2.3 L (9.84%)Rejected-Finance | L3 | Rejected-Finance L3 |
Tender Value
₹28 L
EMD Value
₹56,000
Closing Date
11 Nov 2023, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
CWE JAIPUR
Military Engineer Services, HQ Commander Works Engineer, Kalyan Marg, Banipark, Jaipur-06
PROVN OF HT RING MAIN CIRCUIT FROM SOUTHERN SECTOR TO CENTRAL SECTOR AND DOE AREA UNDER KOTA MIL STN
2023_MES_623482_1
CWE/KOTA/82264/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
KOTA
As per NIT
8 documents required · 8 mandatory
₹500
Yes
GE KOTA
₹56,000
Yes
17 Jan 2024
16 Oct 2023
13 Nov 2023
16 Oct 2023
11 Nov 2023
30 Oct 2023
16 Oct 2023 - 29 Oct 2023
Amount
Excavation in trenches not exceeding 1.5 metre wide and not exceeding 1.5 metre in depth for laying cables, erection of poles / struts/stays etc not exceeding 10 Sqm on plan, not exceeding 1.5 metre in depth and getting out in hard / dence soil complete all as specified and directed.
Excavation in trenches not exceeding 1.5 metre wide and exceeding 1.5 metre in depth for laying cables, erection of poles / struts/stays etc not exceeding 10 Sqm on plan, not exceeding 1.5 metre in depth and getting out in hard / dence soil complete all as specified and directed.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25cm in any type of soil complete all as specified and directed.
Removing of excavated material (soil) to a distance not exceeding 50 metre and depositing where directed at a level not exceeding 1.50metre above the starting point complete all as specified and directed
M&L for sand cushioning to PVC underground cable with tibba sand and punning to provide a required cover complete all as specified and directed. Note:- Punned thickness shall be considered for payment purpose
Supplying and laying un-reinforced precast cable covers class HV, type I, flat, size 300mm x 180mm x 40mm complete all as specified and directed.
M&L for Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of aluminium paint complete all as specified and directed
S&F Steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts, nuts and screws as specified type 410 SP-55 (11.0 metres long) etc complete all as specified and directed.
M&L for PCC 1:2:4 type B1 (using 20 mm graded stone aggregate) as in coping to the poles etc complete all as specified and directed.
M&L for PCC (1:3:6) type C-2 using 40mm graded stone aggregate as in foundation, filing and mass concrete etc complete all as specified and directed.
M&L earthing complete as per electrical plate No 3 of MES SSR Part-I with galvanised steel earth plate electrode 600 mmx600mmx6.3mm, buried directly vertically in ground in a pit depth not less than 2.25 metres below ground level with top edge of earth plate at a depth not less than 1.5 metre below normal ground level connected to and including galvanised iron or steel earth strip 32mm x 6mm by means of bolts, nuts check nuts and washers of galvanised iron or steel. Earthing strip shall be protected by galvanised iron or steel pipe 40 mm bore light grade and connected to continuous earth wire on pole / test point. Watering pipe shall be 20 mm bore GI medium grade. The earthing shall be of inclusive of excavation & earth work in any type of soil, charcoal, salt, funnel PCC pit and RCC cover complete all as specified & tested complete. NOTE:- (i)The concrete pit shall be made in PCC 1:3:6 type C-1, using 12.5mm graded crushed stone aggregate 40mm thick precast cover slab of RCC (1:2:4), type B-1, using 20mm graded crushed stone aggregate with suitable MS handle in lieu of CI cover shown in electrical plate No 3 of MES SSR Part-I shall be provided. Reinforcement in RCC cover shall be of 8mm dia TMT bars laid @150mm c/c both ways (ii) Quoted shall include the cost of 7.5 metre GI pipe for protection of earth wire. (iii) Quoted shall include cost of 7.5 metre earth lead wire. (iv) Earth electrode shall be surrounded by adequate quantity of charcoal dust and salt to a packed thickness of 15 cm on all sides.
M&L earthing complete as per electrical plate No 3 of MES SSR Part-I with galvanised steel earth plate electrode 600 mmx600mmx6.3mm, buried directly vertically in ground in a pit depth not less than 2.25 metres below ground level with top edge of earth plate at a depth not less than 1.5 metre below normal ground level connected to and including connected to galvanised earth lead wire 4.0mm dia by means of bolts, nuts check nuts and washers of galvanised iron or steel. Earthing strip shall be protected by galvanised iron or steel pipe 40 mm bore light grade and connected to continuous earth wire on pole / test point. Watering pipe shall be 20 mm bore GI medium grade. The earthing shall be of inclusive of excavation & earth work in any type of soil, charcoal, salt, funnel PCC pit and RCC cover complete all as specified & tested complete. NOTE:- (i) The concrete pit shall be made in PCC 1:2:4 type B-0, using 12.00 mm graded crushed stone aggregate 40mm thick precast cover slab of RCC (1:2:4), type B-1, using 20mm graded crushed stone aggregate with suitable MS handle in lieu of CI cover. Reinforcement in cover shall be of 8mm dia TMT bars laid @150mm c/c both ways. (ii) Quoted shall include the cost of 7.5 metre GI pipe for protection of earth wire. (iii) Quoted shall include cost of 7.5 metre earth lead wire. (iv) Earth electrode shall be surrounded by adequate quantity of charcoal dust and salt to a packed thickness of 15 cm on all sides
Supply, installing, testing and commissioning of gang operated Air-break, triple pole disconnecting switch, outdoor, vertical mounting type (ISI marked), mechanically operated, mounted on insulators 15 Nos including 11 kV, 400 amp rating complete with (DO Fuse unit) fuse mounts, fuse carriers and HT fuse elements and frame work with operating mechanism and including adequate length of GI Pipes for operation from ground level, with locking arrangements including Godrej pattern 65mm pad locks with two keys, complete suitable for HT 11 KV, 50 Hz AC supply including necessary electric connections and taking down old U/S complete all as specified and directed
Supply, laying and commissioning XLPE insulated screened, PVC bedded galvanised steel strip or wire armoured electric power cables (heavy duty) with aluminium conductor 11000 volts grade earthed IS-7098 marked for HT 11 KV (E) System laid in trenches/ ducts/ encased in GI pipe/ fixed to poles including jointing & testing complete all as specified and directed of following cross sectional area :-
(a) 95 Sqmm, 3 core cable
(b) 185 Sqmm, 3 core cable
M&L for cable end termination, jointing kit for HT 11 KV (Earthed) grade cable for outdoor termination heat shrinkable type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor complete all as specified and directed of following sizes :-
(a) 95 Sqmm x 3 core
(b) 120 to 185 Sqmm x 3 core
S&F for HT cables route indicator cast iron of suitable size along HT cable trench including painting and grouted in ground in PCC etc complete all as specified and directed.
S&F HT lightning arresters expulsion type complete with all fittings, transmission class, discharge capacity 30 KA Amp suitable for 11000 volts complete all as specified an directed
M&L for Anti-climbing device; spikes type fabricated out of M.S. bars (round, square and flat) including nuts, bolts, washers and welding in two halves made to shape to suit the cross section of the pole etc complete all as specified and directed.
M&L for trenchless technology boring for laying of HT cable including supply and inserting HDPE pipe of 100mm dia for cable protection etc complete all as specified and directed
RAGHAV ENTERPRISES
K B Enterprises
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .