Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹14.4 LAccepted-Finance | L1 | Accepted-Finance OK | |
| 2 | L2₹14.7 L+₹30,276 (2.10%)Accepted-Finance 1008 A PREMIER ENGINEERING COMPANY PURVI RITHANI MEERUT DELHI ROAD MEERUT UTTAR PRADESH 250103 INDIA | MEERUT | UTTAR PRADESH | 250103 | L2 | Accepted-Finance OK | |
| 3 | L3₹14.8 L+₹39,922.80 (2.77%)Accepted-Finance PROP NO A 80 FIRST FLOOR FLAT NO 3 CHATTAR PUR ENCLAVE PHASE 2 NEW DELHI SOUTH WEST DELHI DELHI 110074 | SOUTH DELHI | DELHI | 110074 | L3 | Accepted-Finance OK | |
| 4 | Rejected-Technical | - | Rejected-Technical not fulfil technical criteria | |
| 5 | Rejected-Technical | - | Rejected-Technical not fulfil techincal criteria |
Tender Value
Refer Docs
EMD Value
₹29,500
Closing Date
12 Dec 2023, 1:15 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Er. Yogesh Lohchab
WAZIRABAD WATER WORKS TIMARPUR DELHI
Renovation and upgradation of electric feeder system of clarifier no 1 and 2 at Ist 40 MGD plant at Wazirabad water works. .
2023_DJB_250890_2
NIT No. 13(2023-24)
Open Tender
Miscellaneous Works
Item Rate
60 days
WAZIRABAD WATER WORKS TIMARPUR DELHI
Please refer Tender documents.
3 documents required · 3 mandatory
₹500
DJBEMD A/c No-50448339804
₹29,500
12 Jan 2024
6 Dec 2023
12 Dec 2023
6 Dec 2023
12 Dec 2023
6 Dec 2023
6 Dec 2023 - 12 Dec 2023
Excavation of well near the entry point of main feeder cable of clarifier of about the size of 6X6'X18' by hydraulic/manual means by taking all the precautions for the working personals and other structures nearby. This includes getting out the excavated earth and refilling after execution of the cable replacement work. Making arrangement of ballies, planks, steel plates and other supporting items in such a manner that no harm occurs to the workers during execution of work in the deep well.
Dismantling of G.I. Pipe of size of 80 mm dia. carrying the feeder cable, from the bend in the bottom of the excavated well and making of new G.I. bend arrangement for fixing of new G.I. Pipe in the bend. The lenght of the G.I. Pipe to be replaced is approximately 6 meters. Making arrangement of G.I. end cap on the top of the pipe so as to make it sound against entry of any foreign objects. making arrangement of cable exit of the pipe to the MCB box.
Arrangement of all safety equipment for the protection of staff to work at height of clarifier and in the deep well outside the clarifier such as Safety belts, safety shoes, gloves, helmets etc as per site requirement.
Cleaning of existing M.S. Pipe, under the clarifier structure with the help of rust removal chemicals and with heavy water pressure. Removal of old cable from the G.I. pipe, below the clarifier's bottom surface with the help of heavy manual labour/Chain pulley block. The work is to be carried out in the 20 fit deep excavated well, hence must be done taking all the precautions.
Supply of 4 X 10 sq. mm PVC insulated & PVC sheathed/XLPE aluminium armoured conductor 650/1100 voltage grade cable confirming to 1S: 7098. Make:- Grandly/Gloster/ DJB Approved.
Supply of 25sq. mmx4 core pvc/xlpe insulated (heavy duty) electrical cables for working voltage upto and including 1100 volts to is:1554 (part-i) 1988/7098 (part – i) wth aluminium conductor – isi marked power cable- aluminium conductor Make:- Grandly/Gloster/DJB approved
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 x 10 sq. mm (25 mm). (i) 4X 10 sq. mm (25 mm)
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 x 10 sq. mm (25 mm). (i) 4X25 sq. mm (28 mm)
Drawing of new 4 X 10 sq. mm PVC cable in the existing G.1. underground pipe, below the clarifier's bottom surface with the help of Heavy manual labour/Chain pulley block etc in very cautionary manner to prevent the cable of any damage/harm.
Supplying and laying 6 SWG G.I. wire in double running (80mtrs approx.) in the existing 100 mm dia. G.I. pipe below the clarifier structure along with new feeder cable for supporting the cable at the time of drawing and for earthing purpose, including connection/termination with GI thimble etc. as required
Supplying and fixing of Polyester IP66 Enclosure Plain Door of size 300 X 250 X 140 mm (BRES-325, Cape India) with 63 A FP MCB (L&T) installed inside the box and the same to installed on angle Iron frame of size 250 X 1000 mm long made out of MS angle of size 35 X 35 X 5 mm duly hot dip galvanized and installation of MS frame in ground by excavation of ground making CC (1:2:4) foundation of size 350 (W) X 200 (H) X 200 (D) and refilling the balace space etc. as required.
Providing & fixing of slipring with complete carbon bush set by using of nut bolts (as per existing). Making of connection of the cable on the new slipring and from slipring to the control panel of the flocculator and Bridge.
Earthing with copper earth plate 600 mm x 600 mm x 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
Supplying and laying 25 mm x 5 mm G.1 strip at 0.50 metre below ground as strip earth electrode, including connection/terminating with G.1, nut, bolt, spring, washer etc. as required (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm).
Supplying and fixing of 63 amp 6 way Bus Bar Chamber Box made out of 1.6mm thick Sheet steel duly painted with powder coating. Including making connections of 1 No. Incoming and 2no. outgoing cables to starters of the flocculator and Bridge.
SITC of modular/ combinable polycarbonate insulated outdoor type feeder panel housing, shock proof, weather proof, rust proof, UV resistant, halogen free, silicone free, corrosion proof, protection class: Il safe, IP 65 according to IEC 61 439-2, IEC 60 999, DIN EN 50 262, DIN 43 880, IEC 60 529/ DIN VDE 0470 Teil 1 totally insulated, having internal embedded gasket with provision of cable entry through glands. The panel board should have following control panel MCB and accessories etc complete with connections& Interconnections etc as required. Note 1: For mounting of meters, indicating lights & push button only box with hinged door with triangular lid to be used. Note 2: For mounting of 5 HP DOL starter MS angle frame should be hot dipped galvanized and made out of MS angle of size 35 x 35 x 5 mm with all required material/arrangement as per site requirement. The Panel should consist of the followings: (a) 18 A, TP, power contactor (MNX 18, L&T)-1 No (b) 1 NO +1 NC side mounting add-on aux. contact block(L&T)-1No. (c) 6-10 A thermal over load relay (L&T)-1 No. (d) Single phasing preventer (L&T)-1 No. (e) 16 A, FP, 10 kA, MCB (L&T) - 1 No (e)16 A , FP, 10 KA MCB (L&T)-1 No. (f) LED indicating lights red, Yellow, Blue & green (L&T) - 6nos. (g) Push Button with element (L&T)-2 Nos. (h) 6 A SP MCB (L&T) - 1 No. (i) 32 A, 3 way open connector - 1 No. (Digital 3 phase VAF meter (L&T) 1 No. (j)Digital 3 phase VAF meter (L&T)- 1 No. (k) 50/5A, 5 VA, 5.0 class current transformer (AE)-3 No
Laying of 4 X 10 sq. mm cable upto both the starter panels of flocculator and bridge with the help of M.S. Clamps under the Clarifier bridge structure by following all the precautions and safety manual as the work is to be carried out at height about 20 feet.
Laying of 25sq. mmx4 core cable from main panel upto outer junction box of clarifier by digging of ground upto 1.5 fit depth with the help of electric hammer machine and manual labour by following all the precautions and safety manual as the work is to be carried out at site.
Testing and Commissioning of the complete system for satisfactory operation.
Premier Engineering Company
M G Traders and Engineers
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .