Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹18.9 LAccepted-AOC 50 SARASWATI VIHAR SINGHAWALA AMBALA CITY | AMBALA CITY | L1 | Accepted-AOC ACCEPTED L1 | |
| 2 | L2₹21.9 L+₹1.1 L (5.20%)Rejected-Finance | L2 | Rejected-Finance Being rejected L2 | |
| 3 | L3₹22.2 L+₹1.3 L (6.42%)Rejected-Finance | L3 | Rejected-Finance Being rejected L3 | |
| 4 | L4₹22.5 L+₹1.7 L (8.08%)Rejected-Finance | L4 | Rejected-Finance Being rejected L4 | |
| 5 | L5₹23.1 L+₹2.2 L (10.6%)Rejected-Finance | L5 | Rejected-Finance Being rejected L5 |
Tender Value
₹25.7 L
EMD Value
₹51,320
Closing Date
18 Jan 2021, 6:00 pmClosed
SHRI N N LANGHE EE GE SOUTH AMBALA
GE SOUTH AMBALA CANTT
CERTAIN MISC REPAIR REPLACEMENT OF MAIN DISTRIBUTION BOARDS SUB MAIN WIRING SERVICE CONNECTIONS AND ALLIED WORKS IN CERTAIN OFFICERS JCOs ORs MARRIED ACCN IN NORTHERN ZONE UNDER GE SOUTH AMBALA
2020_MES_403412_1
GE (SOUTH) / AMB - 45 / 2020 - 2021
Open Tender
Civil Works
Item Rate
180 days
GE SOUTH AMBALA CANTT
AS PER NIT
9 documents required · 9 mandatory
₹500
GE SOUTH AMBALA CANTT
₹51,320
Yes
26 Feb 2021
14 Dec 2020
20 Jan 2021
14 Dec 2020
18 Jan 2021
4 Jan 2021
14 Dec 2020 - 30 Dec 2020
Amount
Material and labour for disconnecting from main electric supply and dismantling and taking out single phase energy meter and refixing same in location as shown with and including enclosure for single phase energy meter wall mounted , single front , single door , fixed type, suitable for outdoor application polycarbonate transperant hinged type box of size suitable for mounting single / three phase energy meter with sealing arrangement as recommended by OEM and fixing arrangement such as fastnerers, screws etc., complete all as specified and directed. All incoming & outgoing cable shall be directly terminated on meter, outgoing cable shall be directly terminated on DBs complete all as specified and directed.
Material and labour for disconnecting from main electric supply and dismantling and taking out three phase energy meter and refixing same in location as shown with and including enclosure for three phase wall mounted , single front , single door , fixed type, suitable for outdoor application polycarbonate transperant hinged type box of size suitable for mounting single / three phase energy meter with sealing arrangement as recommended by OEM and fixing arrangement such as fastnerers, screws etc., complete all as specified and directed. All incoming & outgoing cable shall be directly terminated on meter, outgoing cable shall be directly terminated on DBs complete all as specified and directed.
Material and labour supply and fixing two compartment wall mounted sheet metal enclouser indoor application made from 1.6m CRCA sheet of size 900mm X 900mmx 450mm for load bearing members / non load bearing members painted with powder coating with and including angle iron brackets fixing with separate compartment for cable termination complete all as specified and directed.
Material and labour supply and fixing four compartment wall mounted sheet metal enclouser indoor application made from 1.6m CRCA sheet of size 1000mm x 1000mm x 450mm for load bearing members / non load bearing members painted with powder coating with and including angle iron brackets fixing with separate compartment for cable termination complete all as specified and directed.
Material and labour supply and fixing six compartment wall mounted sheet metal enclouser indoor application made from 1.6m CRCA sheet of size 1250mm x 1250mm x 450mm for load bearing members / non load bearing members painted with powder coating with and including angle iron brackets fixing with separate compartment complete all as specified and directed.
Material and labour for sub main wiring with two single core FRLSH PVC insulated unsheathed copper conductor cable 6 sqmm drawn in and including rigid non metallic PVC medium grade 25 mm dia new concealed conduit with accessories on wall or ceiling with one additional PVC insulated , stranded copper conductor FRLSH of 6sqmm,green colour for earth continuity conductor complete all as specified and directed. NOTE : - 3 run of 6.0 sqmm cable with concealed conduct shall be measured as 1 unit
Material and labour for sub main wiring with two single core FRLSH PVC insulated unsheathed copper conductor cable 4 sqmm drawn in and including rigid non metallic PVC medium grade 25 mm dia new concealed conduit with accessories on wall or ceiling with one additional PVC insulated , stranded copper conductor FRLSH of 4 sqmm,green colour for earth continuity conductor complete all as specified and directed. NOTE : - 3 run of 4.0 sqmm cable with concealed conduct shall be measured as 1 unit
Material and labour for sub main wiring with two single core FRLSH PVC insulated unsheathed copper conductor cable 2.5 sqmm drawn in and including rigid non metallic PVC medium grade 25 mm dia new concealed conduit with accessories on wall or ceiling with one additional PVC insulated , stranded copper conductor FRLSH of 2.5 sqmm,green colour for earth continuity conductor complete all as specified and directed. NOTE : - 3 run of 2.5 sqmm cable with concealed conduct shall be measured as 1 unit
Material and labour for sub main wiring with Four single core FRLSH PVC insulated unsheathed copper conductor cable 10 sqmm drawn in and including rigid non metallic PVC medium grade 32 mm dia new concealed conduit with accessories on wall or ceiling with two additional PVC insulated , stranded copper conductor FRLSH of 10 sqmm,green colour for earth continuity conductor including including taking down old unserviceable sub main wiring and making good the disturbed surface complete all as specified and directed. NOTE : - 3 run of 10 sqmm cable with concealed conduct shall be measured as 1 unit.
Material and labour Earthing complete with galvanized steel earth plate electrode 60cm x 60cm x 6 mm thick buried directly in ground( earth pit not less than 2.25 mtrs deep below normal ground level )with the top edges of plate not less than 1.5 mtrs below normal ground level connected to GI earth strip 32x6mm by means of GI nuts, bolts check nuts and washers earth lead protected by 40mm dia GI pipe light grade and connected to main distribution board/earthing test point all as shown in electrical plate No 3 of SSR part 1 and all as specified including testing on completion. Notes:-The unit rate also including for excavation, earth work in any type of strata, plain cement concrete 1:3:6 mix, Type C1 pit, 40mm thick RCC 1:2:4 mix , type B1 cover reinforced with 8mm dia TMT bars @150mm C/C both ways ,GI funnel with GI watering pipe 20mm dia med gde ,wire mesh, protection pipe 40mm dia GI pipe light gde for earth lead upto 7.50m long complete all as specified and directed.
Material and labour Earthing complete with galvanized steel earth plate electrode 60cm x 60cm x 6 mm thick buried directly in ground( earth pit not less than 2.25 mtrs deep below normal ground level )with the top edges of plate not less than 1.5 mtrs below normal ground level connected to GI wire 4mm by means of GI nuts, bolts check nuts and washers earth lead protected by 15 mm dia GI pipe light grade and connected to main distribution board/earthing test point all as shown in electrical plate No 3 of SSR part 1 and all as specified including testing on completion. NOTE: - The unit rate also including for excavation, earth work in any type of strata, plain cement concrete 1:3:6 mix, Type C1 pit, 40mm thick RCC 1:2:4 mix , type B1 cover reinforced with 8mm dia TMT bars @150mm C/C both ways ,GI funnel with GI watering pipe 20mm dia med gde ,wire mesh, protection pipe 15 mm dia GI pipe light gde for earth lead upto 7.50m long complete all as specified and directed.
Material and labour in replacement of GI funnel , wire mesh, earth cover Precast RCC 1:2:4 nominal mix using 12.5 mm aggregate cover 25 mm thick reincorced with 8 mm dia TMT bars @ 10 cm C/C on both sides and handle made to shape of size 300 mm x 300 mm, 10 mm dia bar handle with CI frame not less than 25x4 mm of size for earthing complete all as specified and directed.
Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 4mm dia galvanised iron or steel wire complete all as specified and directed.
Excavation in trenches not exceeding 1.5 mtr wide and not exceeding 1.5 mtr deep for taking out/laying of under ground cable and getting out in Soft soil complete all as specified and directed.
Returning filling in including spreading leveling watering and well ramming in layers not exceeding 25cms spread any type of soil complete all as specified and directed.
Removing excavated materials not exceeding 50 mtr and depositing where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified and directed.
Supply and fixing House service bracket (hook type) complete with 3.0m long G.I. pipe 40mm dia Med. grade, two nos 900 bends. M.S. hook and stay or guy including dismantling and taking out old unsv service brackets complete all as specified and directed.
Supply and fixing 1100 volts grade heavy duty cable PVC insulated aluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 1 metre apart including 4mm suspension wire, one twin core cable circular of size 10 Sqmm including all incoming and outgoing connection with proper size of thimble complete all as specified and directed.
Supply and fixing 1100 volts grade heavy duty cable PVC insulated aluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 1 metre apart including 4mm suspension wire, one twin core cable circular of size 16 Sqmm including all incoming and outgoing connection with proper size of thimble complete all as specified and directed.
Supply and laying, connecting, testing and commissioning of LT under ground cable PVC insulated PVC sheathed armoured with multistranded aluminium conductor heavy duty 1100 Volts grade in trenches/on wall/poles laid in ducts/inside protection pipe of the following sizes including cable glands,lugs and suitable size of MS saddle clips(where ever cable laid in ceilings/walls without cable duct) complete all as specified and directed and Engineer-in-Charge for the following :- Note:- (I) Excavation,sand cushioning,brick will be measured and paid separtely (a) 2 Core 10 sqmm
All as per item No 20.00 here-in-above but 4 core 10 sqmm.
All as per item No 20.00 here-in-above but 4 core 16sqmm.
All as per item No 20.00 here-in-above but 4 core 25 sqmm.
Supply and spreading sand of approved quality for cushioning of UG cable laid in trenches complete all as specified and directed.
Supply and lay in trenches old size bricks for cable protection complete all as specified and directed.
Supply and fixing in replacement for GI protection pipe light grade for cable protection incl all fittings laid in trenches or fixed on pole/wall all as specified for 40mm dia including making good to the disturbed surfaces complete all as specified and directed.
Supply and fixing in replacement for GI protection pipe light grade for cable protection incl all fittings laid in trenches or fixed on pole all as specified for 50mm dia including good to the disturbed surfaces complete all as specified and directed.
Cutting of road/hard standing to a size suitable for passing GI protection pipe of 50mm dia in width and not exceeding 90 cm in depth for laying of protection pipe/water line/Cable including returining filling , spreading levelling watering and well ramming in layers and providing PCC in 1:2:4 type B1 for the top 100mm layer using 20mm graded stone aggregate after the pipes /cables are laid complete all as specified and directed.
Supply and fixing in replacement bracket for security light made up of 25mm dia, 0.9m long GI pipe, light grade, bent to required length, fixed to wall with two clamps made of 20 x 3 mm mild steel flat minimum 15cm long, 4 nos 8mm dia bolts with nuts complete all as specified and directed.
Disconnecting and taking down old unserviceable security light fitting of any description and in any position and Supply and fixing LED security light luminaire 30 watt , pressure die cast aluminum housing, toughened heat resistant glass, IP65 protection, better optics for uniform distribtion with multiplte LEDs not less than 2 W eachand having optical grade polycarbonate lens with all accessories internally pre wired and including connecting up with t core 1.5 sq mm copper conductor cable from connector to ceiling rose to connection of light complete all as specified and directed.
Disconnecting and taking down old unserviceable security light fitting of any description and in any position and Supply and fixing LED security light luminaire 45 watt, pressure die cast aluminum housing, toughened heat resistant glass, IP65 protection, better optics for uniform distribtion with multiplte LEDs not less than 2 W eachand having optical grade polycarbonate lens with all accessories internally pre wired and including connecting up with twin core 1.5 sq mm copper conductor cable from connector to ceiling rose to connection of light complete all as specified and directed.
Disconnecting and taking down old existing Bollard light fitting of any description and in any position and Supply and fix LED bollard light fittings surface mounting LED round/ square 10 W adjusable with high Efficiency low glare diffuser with pressure die casted housing with efficient high outpuLED IP 65 Protection including base frame made up of sheet metal and connecting up with three core 1.5 sqmm flexible copper conductor cable complete all as specified and directed.
Supply and fixing highway lighting energy saving, 80 watt,environment friendly & robust LED fitting IP65 luminarie with high efficacy, cast aluminium spigot with poly carbonate diffuser including accessories internally pre wired and including connecting up with three core 1.5 sqmm flexible copper conductor cable including disconnecting and taking down existing unsv light fitting and removal complete all as specified and directed.
Disconnecting and taking down old fitting of any description and in any position and Supply and fix in repair recess mounting type/ surface mounting LED round/ square down lighter12 W adjusable with high efficiency & clear diffuser with IP 20 Protection including connecting up with three core 1.5 sqmm flexible copper conductor cable complete all as specified and directed.
Disconnecting and taking down old existing down lighter fitting of any description and in any position and Supply and fix surface mounting type LED bed side lamp with cover round/ square down lighter 10 W adjusable with high efficiency & clear diffuser with IP 20 Protection including connecting up with three core 1.5 sqmm flexible copper conductor cable complete all as specified and directed.
Disconnecting and taking down old existing wall fitting of any description and in any position and Supply and fix in repair surface mounting type / recess mounting type LED round/ square type ceiling downlighters with high efficiency LED 6W capacity & clear diffuser Oval/ roubd / square type with IP 20 Protection including connecting up with three core 1.5 sqmm flexible copper conductor cable complete all as specified and directed.
Taking down old unserviceable MCB DBs any type including MCB SP/SPN and removing materials to stores for keeping in safe custody for taking credit and making good the disturbed surfaces of walls.Serviceable MCBs will be re- fixed under serial item No. 69.00 here-in- after.
Supply and fixing sheet metal enclosures distribution board Vertical type TPN,(MCCB DB) 4 ways, double door , 415 volts with 200 amps rated bus bar IP 42 protection, with shrouded neutral bar and insulated bus bar and earth link, suitable for MCCB 4 pole 250A as incomer and MCB s as out going complete with making suitable size of MS cabinet 2 mm thick dully grouted on the wall (flush) with opening arrangement making connections with suitable size of lugs and making good the disturbed surface matching with existing surface complete all as specified and directed.
Supply and fixing sheet metal enclosures distribution board Vertical type TPN,(MCCB DB) 4 ways, double door , 415 volts with 200 amps rated bus bar IP 42 protection, with shrouded neutral bar and insulated bus bar and earth link, suitable for MCCB 4 pole 125A as incomer and MCB s as out going complete with making suitable size of MS cabinet 2 mm thick dully grouted on the wall (flush) with opening arrangement making connections with suitable size of lugs and making good the disturbed surface matching with existing surface complete all as specified and directed.
Supply and fixing sheet metal enclosures distribution board TPN, (MCB DB) 4 ways, double door , 415 volts with 200 amps rated bus bar IP 42 protection, with shrouded neutral bar and insulated bus bar and earth link, suitable for MCB 4 pole as incomer and MCB s as out going complete with making suitable size of MS cabinet 2 mm thick dully grouted on the wall (flush) with opening arrangement including taking down the existing DB and MCBs any type making connections with suitable size of lugs and making good the disturbed surface matching with existing surface complete all as specified and directed.
Supply , insatallation, testing SPN distibution board 12 way,double door , IP 43 , as per IS 8623 including 100 amps fully insulated copper bus bar, insulated neutral bar, earth bar, door earthing, reversible doors, PAN assembly for easy installation and also incoming and outgoing connections with suitable size of lugs/thimbles complete all as specified and directed. NOTE : - Unserviceable MCBs will be taken in credit and serviceable will be reused under item Sl NO here in before
Supply , insatallation, testing of SPN distibution board 8 way,double door , IP 43 , as per IS 8623 including 100 amps fully insulated copper bus bar, insulated neutral bar, earth bar, door earthing, reversible doors, PAN assembly for easy installation and also incoming and outgoing connections with suitable size of lugs/thimbles complete all as specified and directed.
Supply , insatallation, testing of SPN distibution board 4 way,double door , IP 43 , as per IS 8623 including 100 amps fully insulated copper bus bar, insulated neutral bar, earth bar, door earthing, reversible doors, PAN assembly for easy installation and also incoming and outgoing connections with suitable size of lugs/thimbles complete all as specified and directed.
Supply and fixing thermal release type MCCB four pole, 415 volts, 50Hz , breaking capacity 25KA, 125 Amps, complete all as specified and directed.
Supply and fixing thermal release type MCCB four pole, 415 volts, 50Hz , breaking capacity 25KA, 160 Amps, complete all as specified and directed.
Supply and fixing MCB four pole, 240 volts, 50Hz , breaking capacity 10KA, 100 Amps, 'C' Curve, complete all as specified and directed.
Supply and fixing MCB four pole, 240 volts, 50Hz , breaking capacity 10KA, 63 Amps, 'C' Curve, complete all as specified and directed.
Supply and fixing MCB single pole, with neutral 240 Volts 50 Hz, 40A to 63 Amps (`B’ series ) having current rating 10 KA complete all as specified and directed.
Supply and fixing MCB single pole, with neutral 240 Volts 50 Hz, 16A to 32 Amps (`B’ series ) having current rating 10 KA complete all as specified and directed.
Supply and fixing for MCB SP, 6 to 32 Amps (`B’ series) having current rating 10 KA complete all as specified and directed.
Repair/replacement of unserviceable electrical fitting and fixture and emergent fault rectification in elctrical circuit incl no light , earth leakage, short cicuit, neutral break I mains /sub mains/internal circuits of existing system of main building / block ,making continious electric supply including carrying out minour repairs etc as required to make system in order / functional by replacing, copper cable , copper thimbles, glands, earthing wire complete all as specified and directed as required at site by Engineer-in-Charge. NOTE : - (a) Items reqd for replacemen such as switchs, sockets for power/light/ fan/ bell/geyser points including security lights complete will be measured and paid under respective items of Sch 'A, (b) Contractor rep/supervisor will report to MES Service Centre alongwith reqd sufficient skilled/unskilled manpower between 930 Hrs to 1030 Hrs on all working days. for carrying out necessary execution. (c) Contractor will attend emergent nature of work i.e. no light, short circuit after working hours/holiday. The rate of the is deemed to be included in above quoted rates.
Supply only switch piano 5 Amps, flush type, single pole, one way, 230 volt , AC supply, ISI Marked, complete all as specified and directed.
Supply only switch, single pole two way 6 Amps, 230 volts AC circuit complete all as specified and directed.
Supply only switch piano 15 Amps flush type one way 230 Volts, 50 Hz , AC supply, complete all as specified and directed.
Supply only bell push 5 Amps, flush type, single pole, one way, 230 volt , AC supply, complete all as specified and directed.
Supply only socket outlet 3 pin 6 amps, 230 volt. flush type, ISI Marked, complete all as speciied and directed.
Supply only socket outlet 2 in 1, 6 pin 5 /16 Amp and multi pin flush type, complete all as specified and directed.
Supply only ceiling rose surface bakelite 65x50mm, 3 terminal complete all as specified and directed.
Supply only fan regulator/ Dimmer electronic step type ,230 Volts, AC supply, suitable for ceiling fan any type/make/sweep, complete all as specified and directed.
Supply only door bell electric ,ding dong /musical| type, single phase 230 volts, complete all as specified and directed.
Supply and fixing in repair lamp holder, PVC/polycarbonate type with back plate suitable for batten fittings, complete all as specified and directed.
Material and labour for Preparing Old surfaces plastered or unplastered on wall surface and applying two coats of white wash including finishing complete all as specified and directed.
Material and labour for Preparing Old surfaces plastered or unplastered on wall surface and applying two coats of applying two coats with cement base paint in patches on walls surface with including finishing and matching with existing complete all as specified and directed.
Material and labour for replacement Fan condenser 2.5 mfd complete all as specified and directed.
Material and labour for replacement PVC insulated, unsheathed cable 4.00 Sqmm three core 1100 volt grade with multi stranded copper conductor complete all as specified and directed.
Material and labour for replacement PVC insulated, unsheathed cable 2.5 Sqmm single core 1100 volt grade with multi stranded copper conductor complete all as specified and directed.
Material and labour for replacement of Cable PVC copper conductor flexible twin core 0.75mm complete all as specified and directed.
Supply and fix in repair sheet metal enclosure SP with two pin and earth plug and socket with one single pole, MCB 32 Amps, 'C' curve, 240 volts complete all as specified and directed.
Material and labour for PCC for pole foundation of 1:3:6 type C2 40mm graded stone aggregate complete all as specified and directed.
Material and labour for PCC for bollard light mounting / post top lantern base frame mounting with 1:2:4 type B1 20mm graded stone aggregate, with necessary form work complete all as specified and directed.
Supply and fixing enclosure for single phase energy meter wall mounted, single front, single door, fixed type, non compartmentalized for indoor application made from 1.6mm CRCA sheet of size 600 mm x 600 mm x 300 mm painted with powder coating including provision for mounting MCB SPN complete all as specified and directed.
Supply and fixing enclosure for single phase energy meter wall mounted, single front, single door, fixed type, non compartmentalized for indoor application made from 1.6mm CRCA sheet of size 750 mm x 750 mm x 300 mm painted with powder coating including provision for mounting MCB TPN complete all as specified and directed.
Supply only switch modular 6A, 1 way single module with and including necessary frame and cover i.e. inner and outer plate as per existing make and type complete all as specified and directed.
Supply only switch modular 16A, 1 way single module with and including necessary frame and cover i.e. inner and outer plate as per existing make and type complete all as specified and directed.
Supply only socket modular 6A, 2/3 pin combined universal socket 2 module with and including necessary frame and cover i.e. inner and outer plate as per existing make and type complete all as specified and directed.
Supply only socket modular 6A / 16A-2/3 pin combined universal socket 2 module with and including necessary frame and cover i.e. inner and outer plate as per existing make and type complete all as specified and directed.
Supply only fan regulator/ Dimmer step type one module / 2 module, 120W, 230 Volts, 50 Hz, AC complete with and including necessary frame and cover i.e. inner and outer plate as per existing make and type complete all as specified and directed.
V K Constructive Builders
unique power & control system
Ashwani Kumar
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .