Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹13.2 CrAccepted-AOC 102 SUBHASH ROAD HERITAGE HEIGHTS DEHRADUN | DEHRADUN | UTTARAKHAND | 248001 | ₹13.2 Cr | L1 | Accepted-AOC Due to Lowest Quoted Rates |
| 2 | L2₹13.6 CrRejected-Finance 245 2 RAJPUR ROAD OPPOSITE HOTEL MADHUBAN DEHRADUN | ₹13.6 Cr | L2 | Rejected-Finance Higher than L1 quoted financial Bid |
| Sl No | Description | Qty | Unit | Modern Electric Company L2 | M/S Shiv Kumar Agarwal L1 |
|---|---|---|---|---|---|
| 1.00 | Internal Electrical wiring
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.
Group C | 1,500 | Nos | 1,537 ₹23.1 L | 1,410 ₹21.1 L |
| 2.00 | Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point (without independent switch etc.) with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed PVC conduit, and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc. as required.
Group C | 100 | Nos | 788 ₹78,800 | 902 ₹90,200 |
| 3.00 | Wiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface /recessed medium class PVC conduit, 2 way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. | 20 | Nos | 1,732 ₹34,640 | 1,502 ₹30,040 |
| 4.00Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. | |||||
| 4.01 | Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. | 12,000 | Mtr. | 212 ₹25.4 L | 223 ₹26.8 L |
| 4.02 | 2x2.5 sq. mm + 1x2.5 sq. mm earth wire | 15,000 | Mtr. | 268 ₹40.2 L | 264 ₹39.6 L |
| 4.03 | 2x4 sq. mm + 1x4 sq. mm earth wire | 12,000 | Mtr. | 374 ₹44.9 L | 321 ₹38.5 L |
| 4.04 | 2x6 sq. mm + 1x6 sq. mm earth wire | 2,500 | Mtr. | 536 ₹13.4 L | 421 ₹10.5 L |
| 4.05 | 2x10 sq. mm + 1x6 sq. mm earth wire | 1,200 | Mtr. | 724 ₹8.7 L | 548 ₹6.6 L |
| 4.06 | 4x10 sq. mm + 2x6 sq. mm earth wire | 1,000 | Mtr. | 1,363 ₹13.6 L | 966 ₹9.7 L |
Tender Value
Refer Docs
EMD Value
₹29.3 L
Closing Date
25 Nov 2025, 5:00 pmClosed
Superintending Engineer
Office of The Superintending Engineer, 11th Circle P.W.D., 107-Nehru colony, Phase-II,Dharampur,Dehradun
Electrification of Vaikalpik Bhawan at Secretariat Campus Dehradun.
2025_pwd_88855_1
1941/7CB(I)-11/2025-26 Dated 07.11.2025
Open Tender
Electrical Works
450 days
Secretariat Building
Please refer tender documents
2 documents required · 2 mandatory
₹5,900
Executive Engineer, E/M Division, PWD, Dehradun
₹29.3 L
Dehradun
23 Feb 2026
12 Nov 2025
26 Nov 2025
12 Nov 2025
25 Nov 2025
12 Nov 2025
12 Nov 2025 - 17 Nov 2025
18 Nov 2025
Amount
Internal Electrical wiring Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. Group C
Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point (without independent switch etc.) with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed PVC conduit, and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc. as required. Group C
Wiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface /recessed medium class PVC conduit, 2 way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.
Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.
Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.
2x2.5 sq. mm + 1x2.5 sq. mm earth wire
2x4 sq. mm + 1x4 sq. mm earth wire
2x6 sq. mm + 1x6 sq. mm earth wire
2x10 sq. mm + 1x6 sq. mm earth wire
4x10 sq. mm + 2x6 sq. mm earth wire
4x16 sq. mm + 2x6 sq. mm earth wire
Supply and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.
20 mm dia ISI mark.
25 mm dia ISI mark.
32 mm dia ISI mark.
40 mm dia ISI mark.
Sujpply and fixing of follwing modular switch/socket on the existing moudalr plate & switch box inculiding connections but excluding modular plate etc. as required.
5/6 amps switch
15/16 A switch
3 pin 5/6 amp socket outlet
6 pin 15/16 A socket outlet
Telephone socket outlet
TV antenna socket outlet
Bell push
S/F two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required.
Supply and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required.
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required.
Supply and fixing following size / modules, GI box along with modular base & cover plate for modular switches in recess etc as required.
6 Module (200mmX75mm)
8 Module (200mmX125mm)
Supply and fixing 3 pin, 5 amp ceiling rose on the existing junction box/wooden block including connection etc as required.
Supplying and fixing call bell/ buzzer suitable for single phase, 230 V, complete as required.
Installation, testing and commissioning of ceiling fan, including wiring the down rods of standard length (upto 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable, including providing and fixing phenolic laminated sheet cover on the fan box etc. as required.
Numbering of ceiling fan/ fluorescent fittings as required.
Installation of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required.
Upto 450 mm sweep
Extra for fixing the louvers / shutters complete with frame for a exhaust fan of all sizes.
Supply of 300mm diameter single phase, 230 V AC, 50 Hz Industrial exhaust fan for toilets complete with motor, capacitor, fan assembly mounting frame & louvers.
Supply of 48/56 inch diameter, three blade, single phase, 230 volt AC, 50 Hz, ceiling fan complete with the motor, starting capacitor, fan assembly, hang pipe, top bottom domes, required hardwares etc.
MCCB, MCB & DBs
Supplying and fixing 12 way , Double door, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)
Supplying and fixing 8 way (4 + 24), Double door, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB / RCCB / Isolator)
Supply, installation, testing and commissioning of wall mounted, vermin proof, dust proof, indoor duty, front door for access SDB's will have FOUR TIER PPI type 12 Ways TPN DB metal casing with double door and shall be of fabricated with minimum 1.2 mm thick CRCA sheet and powder coated, as mentioned in this document and shall have lockable front door and this lock shall be flushed with main door with common key for all SDB. (This item excludes MCBs and incomer).
Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.)
4 way (4 + 12 ), Double door
8 way (4 + 24), Double door
12 way (4 + 36), Double door
Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Single pole
Triple pole
Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.
Supplying and fixing 40 amps, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Supplying and fixing 63 amps, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Supplying and fixing 63 amps, double pole, (single phase and neutral), 240 V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Supplying and fixing 20 A, 240 V, SPN Industrial type socket outlet, with 2 pole and earth, metal enclosed plug top alongwith 20 A, “C” curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required.
Supplying, installation, testing and commissioning of 100A 4P MCCB 18 KA/16KA
Supplying, installation, testing and commissioning of 63A 4P MCCB
Cable Supply & Termination Supply of multi core/ single core, stranded /solid aluminium/ copper conductor, XLPE/PVC, inner sheath of PVC compound ST2 as per IS 5831, armoured/unarmoured, outer sheath of extruded FRLS. PVC compound ST2 1100V grade cables of the following sizes confirming to IS 7098 part I.
3.5c x 300 sq.mm Al, XLPE, arm
3.5c x 240 sq.mm Al, XLPE, arm
3.5c x 120sqmm Al, XLPE, arm
3.5c x 95sqmm Al, XLPE, arm
3.5c x 35sqmm Al, XLPE, arm
3.5c x 25sqmm Al, XLPE, arm
4c x 16sqmm Al, XLPE, arm
1c x 50sqmm Cu, XLPE, unarm
4c x 16 sq.mm multistranded copper, XLPE, arm
4c x 6 sq.mm multistranded copper, XLPE, arm
4c x 2.5 sq.mm multistranded copper, XLPE, arm
3c x 6 sq.mm multistranded copper, XLPE, arm
Cable Terminations Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade as required. For single core polyamide glands shall be used. One set will comprise of four cores in three phase system.
3½ X 25 sq. mm (28mm)
3½ X 35 sq. mm (32mm)
3½ X 95 sq. mm (45mm)
3½ X 120 sq. mm (45mm)
3½ X 240 sq. mm (62mm)
3½ X 300 sq. mm (70mm)
Cable Tray. Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc. as required.
100 mm width X 50 mm depth X 1.6 mm thickness
150 mm width X 50 mm depth X 1.6 mm thickness
300 mm width X 50 mm depth X 1.6 mm thickness
450 mm width X 62.5 mm depth X 2.0 mm thickness
CABLE TRAY BENDS Supplying and installing following size of perforated painted with powder coating M.S. cable trays bends with perforation not more than 17.5%,, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.
100 mm width X 50 mm depth X 1.6 mm thickness
150 mm width X 50 mm depth X 1.6 mm thickness
300 mm width X 50 mm depth X 1.6 mm thickness
450 mm width X 62.5 mm depth X 2.0 mm thickness
CABLE TRAY TEE Supplying and installing following size of perforated painted with powder coating M.S. cable trays Tee with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.
100 mm width X 50 mm depth X 1.6 mm thickness
150 mm width X 50 mm depth X 1.6 mm thickness
300 mm width X 50 mm depth X 1.6 mm thickness
450 mm width X 62.5 mm depth X 2.0 mm thickness
CABLE TRAY REDUCER Supplying and installing following size of perforated painted with powder coating M.S. cable trays Reducer with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required
100 mm width X 50 mm depth X 1.6 mm thickness
150 mm width X 50 mm depth X 1.6 mm thickness
300 mm width X 50 mm depth X 1.6 mm thickness
450 mm width X 62.5 mm depth X 2.0 mm thickness
LADDER TYPE CABLE TRAY Supply, installation of M.S. powder coated (min 65 - 70 micron) factory built in ladder type cable trays of various width in single tier/two tier fashion either on one side of the wall or on two sides of the wall or at other places and paint with one coat of red oxide primer and two coats of synthetic enamel paint afterward. Paint colour shall be same as that of machines / truss. All cable trays complete shall have spring washers.
450 mm tray, main channel:20x75x20x2.0 mm thick, rungs 20x35x20x2.0 mm thick @ 250 mm c/c
600 mm tray, main channel:20x75x20x2.0 mm thick, rungs 20x35x20x2.0 mm thick @ 250 mm c/c
750 mm tray, main channel:20x75x20x2.0 mm thick, rungs 20x35x20x2.0 mm thick @ 250 mm c/c
1000 mm tray, main channel:20x100x20x2.0 mm thick, rungs 20x35x20x2.0 mm thick @ 250 mm c/c
CABLE TRAY SUPPORTS Supply, installation of hangers and supports for cable tray, cable tray of various width in one/two/three or five tier fashion either on one side of the wall or on two sides of the wall/column/truss or at other places as required as per drawing. The work involve fabrication of clamps, hooks, suspension rod or strip painted with two coats of red oxide and one coat afterward with paint as per the approved colour. Before fabricating, the contractor has to get the design approved. In this, item shall be inclusive of square section, channel, angle etc.
S/L of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required.
63 mm dia (OD-63 mm & ID-51 mm nominal)
90 mm dia (OD-90 mm & ID-76 mm nominal)
120 mm dia (OD-120 mm & ID-103 mm nominal)
160 mm dia (OD-160 mm & ID-135 mm nominal)
200 mm dia (OD-200 mm & ID-175 mm nominal)
INTERNEL LIGHTING FIXTURES Supply, Installation, testing and commissioning of following type of light fixtures as per drawings and specifications with all other accessories such as supporting rods /frames, anchor fasteners, necessary hardware etc.
Supplying, installation, testing & Commissioning of recessed type Back-Lit LED Round Downlight of 15W with White powder coated, Aluminum housing of Fixture cutout size 158mm Dia (Nominal) Surge Voltage Protection min 3KV. Total system Lumen not less than 1500 in Cool day Light(5700K), THD(%)<10, Power factor>0.95, CRI>80, LED Lamp Efficacy>140 Lm/W with Average life L70B50: 50000 hours. Complete with all accessories as required with connections. All above mentioned Specs will be verified through NABL Certified LM79 & LM80 Report before supply of LED Fixture onsite.
Supplying, installation, testing & Commissioning of recessed Type Full window opal Diffuser LED Panel of 36W, size 595X595mm (Nominal) suitable for Existing false ceiling with CRCA powder coated White Housing with Surge Voltage protection min 2 KV. Total system Lumen not less than 3600 in Cool day Light(5700K), System lumen efficacy>100 LM/W, Power factor>0.95, CRI (Ra) >80, with Average life L70B50: 35000 hours. Complete with all accessories as required with connections. All above mentioned Specs will be verified through NABL Certified LM79 & LM80 Report before supply of LED Fixture onsite.
Supply, Installation, testing and commissioning of 20 watt Surface mounted LED batten made of CRCA housing with high efficiency polycarbonate diffuser, LED Used shall be SMD type and fixture should have minimum efficacy at System level >=110 lumens/watt with Minimum system Lumens 4000, Life of fixture: 50000 burning Hrs. @ L70 B50 Lumen maintenance, CCT of 4000K (SDCM<5) , CRI >80, PF >0.95 & THD<10%, an operating Voltage Range of 140 - 270 VAC. Minimum Internal Surge Protection 2.5KV. The fixture design should comply with EMC / EMI compliance with flicker free operations ripple <5%, BIS certification is required for LED Driver & Luminaries. 20 Watt
Supply, Installation, testing and commissioning of 10 Watt LED Mirror Light.
9 METER LONG DOUBLE ARM STEEL TUBULAR POLE Supply, installation, wiring, connection, testing and commissioning of external boundary lighting system conforming to the technical specifications & drawings forming part of this document. The work for each light point comprises of: - of 9.0 meter long MS tubular pole. Weighing 125Kgs (as per IS 2713 1980 of pole code 410 SP 29) + 2 nos. end bracket wt.5Kg. /mtr. + base plate 300 x 300 x 6mm plate Wt 4.3Kg. + Nipple Wt. 800gm. Fixture will come at top of the pole along with reducer. Providing weather proof Electrical Junction Box on surface. Digging for making foundation of the pole. Erecting the pole by grouting in concrete foundation (The civil construction materials are the part of the supply against this assignment) made out of 1:3:6: mixture of cement concrete. Weather proof junction box with 6A MCB and arrangement for terminating incoming and outgoing three phases cable Mounting the street light fixture or approved equal on the pole top. Connecting the fixture by using 3c* 2.5mm PVC flexible copper wires of colour green, red and black to the junction box. Testing the connections and completing the installation. Providing two numbers 38 mm GI Pipe for incoming and outgoing cables from cable laying depth to outside foundation. Painting the pole with two coats of red oxide and two coats of aluminium paint. The incoming cable work, outgoing cable work and the earthing of poles are covered under the cabling and earthing.
SITC of 100W LED Street Light fixtures IP66 with integral electronic driver complete in everyway with accessories & LED lamps. The specification are as follows: Lumen efficacy of > 100 Lm/W, System Lumen = 10000 CCT- 5700K CRI>= 70, Drivers life - 50000 Hrs, THD<10% PF>0.95 IP 66, IK 08 Life class - 50000 hrs @ L70.
CABLE SUPPLY FOR OUTDOOR ILLUMINATION Supplying multi-core, stranded aluminum or copper conductor, PVC/ XLPE insulated aluminium conductor armoured, extruded outer PVC/ FRLS sheathed 1100V, grade cables. The work involves the following sizes. 4c * 10sqmm stranded "Al" XLPE arm cable
METERING UNIT Supply, installation of indoor metering cubicle unit (without CT, PT) as per the approved make of Electricity Board only. HT meter supply & installation shall be in scope of State Electricity Board.
Providing & fixing 11kV CT & PT in above metering indoor unit and getting them calibrated from Electricty Board before fixing.
All interconnected control wiring.
11 KV H.T. PANEL BOARDS 11KV SINGLE VCB (ICOG) PANEL BOARD (OUTDOOR) (1 HT Panel 11 KV H.T. Panel VCB Board) (ICOG type) (Outdoor type,Location:Near Substation area) Supply, installation, testing & commissioning of 11 KV 1 HT Panel Board (Outdoor). VCB panel board shall comprise of following items: (Single Panel H.T. Board VCB circuit breaker of 630 amps, one common incoming & outgoing. Suitable cable termination box shall be provided for both inlet and outlet cables). The breaker shall withstand 18.4 kA for 3 seconds. Note: All spare contacts of breaker or any other equipment inside the breaker shall be wired upto the outgoing terminal strip with appropriate ferrules / coding. The terminal strip rating shall be suitable for connecting two wires of 2.5sqmm subjected to providing minimum size strip suitable for 4/6 sqmm. The bidder shall indicate battery Ah for both static and transient load with supportive calculation for each panel separately. Minimum battery size shall be 17AH in power pack suitable for 8 to 10 operations. 1 no. VCB circuit breaker common incoming & outgoing panel of 11 KV. Feeder breaker comprises of following: 1 number 630 Amps 18.4 kA for 3 second VCB circuit breaker horizontally insulated horizontal drawout, electrical motor operated, spring charged with facility of manual closing. 3 number combined 11kV cast resin 75/5A current transformer 5P20 and class 1.0 accuracy. CT burden shall be minimum 10 VA for metering and protection. The CT shall be manufactured and tested as per IEC standard for partial discharge with fault level of 18.4 kA for 1 sec and shall have short links. Test certificate for IEC testing shall be submitted.
Detailed testing of HT panel (item 2.1 ) including relay calibration as per discrimination, setting of relay along with LT incomer transformer and system fault level complete in all respect along with meggaring of earthing complete in all respect. The vendor has to give necessary graph coordinating all relays in one graph with tripping timing.
H.T. CABLES & SUBSTATION EQUIPMENTS
H.T. CABLES Supply, laying, testing and commissioning of 11kV 3C x 240 sq.mm (E) XLPE armoured cable conforming to IS 7098 II below ground, digging 1.0 meter deep and back filling the trench with excavated earth, covering it with sand and brick with HT route marker at every 15-20mtr distance. (Excavation providing sand & brick will be part of this item).
HT CABLE TERMINATIONS Supplying and making indoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for 240 Sq.mm. size of 3 core, XLPE aluminum conductor cable of 11 kV grade as required.
SUB STATION EQUIPMENTS Supply and erection of the following equipment at suitable place in the sub-station building as required and as per detailed specifications.
G.I buckets of followings capacity paint and written with white paint Fire and mounted on M.S. angle iron bracket of sizes 50mm x 50mm x 6mm thick and 500 mm long including grouting in wall or shall be supported from floor by providing heavy size angle iron from floor.etc. as required including filling with dry sand 9.0 ltr capacity. (2 Nos. buckets will be in one set)
First aid box as approved by St. John Ambulance Brigade/Indian Red Cross Conforming to IS:2217 - 1963
Shock treatment chart at least in three languages duly mounted on a wooden frame with glass as required.
Elastomeric mat 914.4 mm wide and 2.0 mm thick to withstand 1.1 KV dielectric strength as per latest amended IS 15652 and it shall also follow latest guidelines of State Electricity inspectorate division.
Medium Voltage Danger Notice Plate 200mm x 150mm made of M.S. Steel at least 2mm thick and vitreous enamelled white on both sides and with inscription in single red colour on front side as required.
High Voltage Danger Notice Plate 250mm x 200mm made of M.S. Steel at least 2mm thick and vireous enameled white on both sides and with inscription in single red colour on front side as required.
Hand Glove withstand 11 KV dielectric strength as per latest amended IS and it shall.
S.I.T.C of 1250KVA Compact Substation- The CSS should be NQube model as should be designed in line with IEC 62271-202. Should provide maintenance-free operation throughout its life span. fully factory assembled & tested by OEM at its premises. The make of LV switchgear, MV Switchgear and CSS should be the same. Should have modular & compartmentalized type construction and to be reinforced with a specially designed ventilation system. CSS dimensions should be 3650 x 2100 x 2600 (WxDxH in mm). The Ingress protection level should be 1P54 for MV, IP34D for Transformer & IP 54 for LV. Make: L&T/Schnider/ Siemens/ABB Following should be installed in CSS along with all accessories required as per OEM standard. Gas Insulated Ring Main Unit: FRI VI — 12, 12kV,630A, 21 kA, 1 LBS + Fixed type 1 No VCB. The RMU should comply IEC62271-200; 102,103,100. Qty. 1 Nos Make : L&T, Schneider, Siemens. 11/0.415 KV Oil Cooled TRANSFORMER, OFFLOAD Tap changer OCTC, Tapping = +5% to -5% @ 2.5% in HV side, AN cooling, L2 Losses. The transformer rating should be 1250 KVA. The make of the Transformer should be as recommended by OEM & PWD. LT Outgoing comprising of ACB 2000 A, four-pole, 50 KA, ACB with microprocessor release with LSING Protection, 1 Nos. 630A four Pole 36KA MCCB Variable thermal and variable magnetic and 1 Nos. 400A four Pole 36KA MCCB Variable thermal and variable magnetic.
Incomer-2 from DG set 625 KVA. One incomer with 1x1250A 4P EDO ACB with microprocessor based over current, short circuit & earth fault release with 200A TP neutral contactor. ACB releases shall have over current different time settings, short ckt. release with variable setting, short time delay, instantaneous current setting, earth fault release, earth fault time delay. Suitable links shall be provided for min 4Rx300 Sq.mm Aluminum XLPE Arm cables. This DG will be synchronised with another DG and all necessary hardwares shall be included. Each incomer shall have following. 1 No. microprocessor based releases in breaker for over current, short circuit, earth fault and separate indication for over current, short ckt & earth fault. This shall have one no. micro processor based standbye earth fault relay in the neutral circuit with suitable CT, 1 no. micro processor based REF relay with 5 nos PS Class CTs (4 nos. in panel and 1 no in neutral contactor output), 1 no reverse power relay, combined under voltage and over voltage with under and over frequency relay, 1 no. field failure relay & 1 no. Engine Cranking relay. Please note that these relays will be common in manual as well as auto operation. Please note that ralays having features covered in controller shall not be repeated. 3 nos. indicating lights for ACB ON/ OFF/ TRIP position. 1 No. kW / phase angle transducer dedicated for each DG along with PLC, auto load management, power failure sensing, operation of all breakers in Main LT panel etc. Each DG controller will carryout basic function like AMF start, auto synchronising, load sharing and auto load management. 1 No. digital multifunction meter with harmonics communicating on modbus & RS 485 port with matching cast resin CT's of class 0.5.
Outgoings from Bus Bar -1 2 Nos. 800A feeders each having 1 no. 800A TP MDO ACB with microprocessor based release, protections for over current, short circuit and earth fault. 1 No. 630A TPN feeder having one no. 630A TP MCCB's with isolable neutral. 3 Nos. 400A TPN feeders each having one no. 400A TP MCCB's with isolable neutral. 1 No. 250A TPN feeder having one no. 250A TP MCCB's with isolable neutral 1 No. 160A TPN feeder having one no. 160A TP MCCB's with isolable neutral. 1 No. Fabrication Compartment space for 400A MCCB. 1 no. type I+II SPD 4 Mode for lightning impluse current 100kA per pole (10/350 micro second), as per specification to meet 440 TOV withstand for 2 hrs. Voltage protection (VP) level will be less than 1.5kV. Outgoings from Bus Bar -2 1 No. 400A TPN feeder having one no. 400A TP MCCB's with isolable neutral. 3 Nos. 250A TPN feeders each having one no. 250A TP MCCB's with isolable neutral. 1 No. 200A TPN feeder having one no. 200A TP MCCB's with isolable neutral. 1 No. 160A TPN feeder having one no. 160A TP MCCB's with isolable neutral. 1 No Fabrication Compartment space for 400A MCCB. Other items such as Interlocking logic electrical & mechanical between 4 incomers & 1 no. Bus coupler through PLC complete in everyway in all respect. 1 Lot of control wiring . 1 Set of designation plates
FIRE TRACE TUBE FOR MAIN LT PANEL Supply, Installation, testing & Commissioning of fire trace tube along with Clean Gas NOVAC-1230 or any green gas in suitable cylinder for flooding in case of fire condition for all LT Panel feeders complete in everyway.
1 No. Fabrication Compartment space for 160A MCB. 1 No. Type II SPD 4 Mode Din mounted for nominal current 20kA per pole (8/20 micro-second) with HRC Fuses as per specification to meet 440V TOV withstand for 2 hrs. Voltage protection (VP) level will be less than 1.5kV. 1 set of complete wiring
CAPACITOR PANEL- (415V AC, 3 Phase, 4 Wire, 50 Hz) COMMON NOTES FOR CAPACITOR PANEL: Switchgear , Capacitor & Reactor should be in Almirah Design. There will be separate exhaust fan for switchgear side & Capacitor / Reactor side. Fan shall be of minimum 800 CFM subjected to maintain Air velocity of 2 meter /second. APCR relay swithcing on each capacitor bank time shall be min 60 sec. We should be able to operate each bank individually in auto & manual mode. Tapping for APCR relay shall be taken from HT feeder. Each capacitor bank shall have 1 no. Magentic type MCCB (setting from 8-12 times), 1 no. TP capacitor duty contactor which should be suitable for 50 degree C as per A6b duty. There will be 1 no. 7% harmonic block copper wound reactor rated 440V AC with 200% linearity class H and thermistors, 1 set ON/OFF indication lights, 1 no. Auto/manual switch, 1 set of ON/OFF push buttons and 1 no. START/STOP push button in each capacitor bank. Each Capacitor bank shall also have 1 no. CT operated ammeter with 1 no. matching cast resin CT. All Capacitors should be super heavy duty type. Each capacitor bank shall be able to operate in either manual or auto mode individually through APCR relay and separately in auto mode. (Harmonic reactor shall reduce harmonic current considerably and reduction of hamonic figure shall be given at the time of manufacturing of harmonic reactor).
4 nos. x 25 KVAR capacitor banks. Each 25KVAR (33KVAR at 525V) section will have 1 no. 100A TP MCCB Magneitc type (setting from 8-12 times) as incomer with 1 no. CT operated ammeter 0-100A with matching cast resin CT, 1 no. TP capacitor duty contactor suitable for 50 degree C as per A6b duty, 1no. 7% harmonic block copper wound reactor rated 440V AC with 200% linearity class H and thermistors, 1 no. super heavy duty 33KVAR capacitor at 525V. The complete heat should come out of Panel, air dynamics shall be designed accordingly so that heat is not trapped. We should be able to operate each bank individually in auto & manual mode. Other items such as: 1 Lot of control wiring. 1 Set of designation plates.
Earthing
Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required.
Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 meter long etc. with charcoal/ coke and salt as required.
Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosurewith cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
Supplying and laying 6 SWG G.I. wire at 0.50 meter below ground level for conductor earth electrode, including connection / termination with GI thimble etc. as required.
EARTHING CONDUCTORS Supply, straightening, shaping, laying under ground/ laying on a cable tray/ laying in cement concrete trench the following sizes of hot dipped galvanised iron conductor. The work is inclusive of providing clamping with the trays/ on the sides of the trenches, making joints where ever required and providing the hardwares and the terminating the hardwares and the termination to the equipment/ earthing station/ etc.
65 mm x 6 mm GI flat
50 mm x 10 mm GI flat
50 mm x 12 mm GI flat
50 mm x 6 mm GI flat
40 mm x 5 mm GI flat
25 mm x 6 mm GI flat
25 mm x 3 mm GI flat
40 mm x 5 mm Cu flat
8 guage GI wire
MAINTENANCE FREE CHEMICAL EARTHING Supply, installation, testing & commissioning of maintenance free chemical earthing system sets comprises of UL listed copper bonded earthing steel roads of 17.2 mm dia 3000mm long with 250 micron copper molecular bonding, KEMA certified and tested as per IEC EN 62561-2:2012 alongwith minimum 2 bags each 11.2kgs of ground enhancement material (GEM) having resistivity less than 0.02ΩM, one no. stainless steel universal clamp for connecting earth electrode to equipment and one no. inspection pit of polymide/ FRP. (Only Erico make ) with poly amide cover. (For UPS System)
UPS System 20 KVA Online UPS system. With inbuilt isolation transformer and automaticstatic bypass switch and Mannual Bypass Switch, 3 phase input 1 Phase output
12Volt, 42AH SMF Battery – 30 Nos For 30 Min back up time in 20KVA Load Make Exide (EP 42-12) Including battery stand & Loopping Cables.
Air Termination grid at Terrace Level
SITC of 8 mm Aluminum Round Conductor & Meets the requirements of DIN EN 50164-2 (VDE 0185 part 202) & VDE 0185-305 (IS/IEC 62305). Cross Section 50 Sq mm, Semi hard Al Mg Si 0.5 corresponds to DIN 48801
SITC of Roof conductor holder for sheet, Bottom section & Conductor holder made of stainless steel (V2A) with Ø 8.5 mm slot at bottom @ every 1 mtr distance.
SITC of Stainless Steel Cross connector (At every crossing of conductor) BET Tested conforms to the requirement according to DIN VDE 0185-305 (IS/IEC 62305)
SITC of Expansion Piece for equalizing temperature related length changes (necessary on conductor lengths over 20 m) 8mm Aluminum round conductor along with Hot dip galvanized Connector BET Tested conforms to the requirement according to IS/IEC 62305
SITC of Bridging cable to connect horizontal air terminal with metal column conforms to the requirement according to IS/IEC 62305
SITC of 10/16 mm dia 2000 mm long Al. vertical interception rod along with stand of 16 kg stone with base and clamp lightning current tested with 100 KA (10/350) to connect 8 mm round Al. conductor
SITC of 10/16 mm dia 4000 mm long Al. vertical interception rod along with stand of 16 kg stone with base and clamp Lightning current tested with 100 KA (10/350) to connect 8 mm round Al. conductor
Down Conductor
SITC of 8 mm Aluminum Round Conductor & Meets the requirements of DIN EN 50164-2 (VDE 0185 part 202) & VDE 0185-305 (IS/IEC 62305). Cross Section 50 Sq mm, Semi hard Al Mg Si 0.5 corresponds to DIN 48801
SITC of Universal cable bracket for Parapet wall having hole Ø 7 mm, made of polyamide, weather and temperature resistant from -35°C to +90°C
SITC of stainless steel test joint to connect 8/10 mmm round conductor fixed in polycarbonate enclosure on all down conductor above 1 metre from the ground level according to IS/IEC 62305
SITC of Lightning Counter which should automatically detects the number as well as time and date in the event of a lightning or overvoltage impulse and conforms to IEC/EN 62305-3.
Earthing
SITC of 8 mm copper bonded round steel solid conductor having 250 micron copper coating for ring earthing and conforms to IEC/EN 62305-3.
SITC of cable bracket with cross bar and 2 hexagonal bolts (VA)
SITC of chemical earthing included maintenance free Copper coated earth rod of 3 meter long 17.2 mm dia and clamping system with vertical conductor and earth enhancing mineral compound 25 kg and providing of earth electrode chamber including excavation and refilling with cover as per specification as per TAC minimum coper coating 250micron on earth rod.
500 KVA DG Set
S.I.T.C of 500 KVA, 3 Phase, 415 V, 50 HZ, CPCB IV Silient Type Diesel Generator Set Complete with AMF Panel suitable for 500KVA D.G. Set with ATS bypass panel arrangement. Complete with two years standard warranty. Self excited and self regulated rated 500 KVA, 0.80 Power Fector alternator provided with self excitation, runing at 1500 RPM, driven by suitable 608 BHP or Near by BHP naturally aspirated electric Start water cooled configuration to IS:3046 complete with all other standerd and electric accessories and saftey device with heavy duty fly wheel 24 Volts electric start oil pressure gauge exhaust silencer with exhaust Pipe lines as required, 12 Volt 25 Plate 150 AH heavy duty battery, AVM pads and power coated control panel 14/16 dust vermin and corresion proof C.R.C.A. sheet, wall/floor mounted with MCCB switch of sutaible rating, fuel tank integrated with base frame and operated through Digital Genset Controller as per direction of Engineer 1ncharge with commissioning, Testing at site F.O.R Dehradun including cost of fuel for 1 hour testing and lubricant oil.
Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 meter long etc. with charcoal/ coke and salt as required.
Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 meter long etc. with charcoal/ coke and salt as required
Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.
Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required.
S/F of control cable 2.5sqmm x 12 core armoured between DG set and Synchrozing panel for automation of DG Set.
S/F of aluminium Conductor PVC insulated armoured, seved, sheathed cable 1100 V grade at a depth of 750mm below ground level over a cushion of 75mm thick sand around and protected with burnt bricks on sides and on top, on surface the cable run shall be fixed on M.S. clamps etc. of suitable size or as directed by the engineer incharge, complete in all respects. The armouring of the cable shall be properly connected with the earth conductor by clamps etc.size 3 x 3.5 x 240 output of DG Set).
S/F of cable lugs for size 240 sqmm.
S/F of DWC PVC pipe 63 mm
S/F of busbar chamber 1000 Amp.4 way. 415V.Make- Havells/ equivalent.
Supply and fixing of 70 Sq.mm single core copper cable from altanator to earth terminal.
S/F of main switch 320 Amp. Sides handle type fixing on angle Iron. Make- Havells/ Equivalent.
Supply and Installation, testing, commising, of powder coated compartmetalized board made from 2mm thick CRCA sheet suitable for Floor mounting provides with 1000 Amp strip Al. bus bar Al. inter connections including making provision for earth bar seperate netural and connector for making outgoing and incoming cable/wires. The panel shall be fabricated so that there is shall be separate segregation of each face. Incoming :- 800 Amp, 415 V FP ACB - 1 No. breaking capacity 65 KA, Indication Lamp R/Y/B with back up-fuse- 1 set of three(Make Siemens, Schneidder, L & T) Outgoing :- 800 Amp 415V FP on load Change over switch – 2 Nos.
Servo Voltage Stabilizer S.I.T.C. of 500 KVA SERVO VOLTAGE CONTROLLER with Following- TYPE - DIMMER TYPE. FREQUENCY - 50 Hz +/-3 Hz NO. OF PHASES - 3 phase COOLING - ONAN DESIGN & TESTING STANDARDS - IS 9815 / IS 2026 TERMINATIONS - Porcelain Bushings (IS 3347) OVERLOAD CAPACITY - Tested to withstand overloading of 200% for momentarily. DUTY CYCLE - Continuous FIRST FILL OF TRANSFORMER OIL - Apar / Equivalent make oil conforming to IS 335, so as to achieve high insulation level. CLASS OF INSULATION - F TEMP. RISE PERMISSIBLE IN OIL - 55 degree C CORE ARCHITECTURE - For attaining high efficiency of the stabilizer we use stepped and mitered core architecture. WINDINGS. Using Super-Enamalled Copper Winding Wire. SERVO VOLTAGE STABILIZER INCLUDES FOLLOWING FEATURES: Digital voltage display for three phases independently. input voltage 300-460 volts High accuracy of output voltage within +/- 1%. Lamp for input voltage beyond limits on each phase. Auto/Manual Switch. The control panel and display units . Suitable for unbalanced current load & for unbalanced input voltage supply.
(A) Supply, installation, testing and commissioning of electric driven pressurisation pump suitable for automatic operation and consisting of following, complete in all respects, as required : (Jockey Pump) (B) Horizontal type, multistage, centrifugal pump of cast iron body and bronze impeller with stainless steel shaft, mechanical seal conforming to IS : 1520. (C) Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase 50 Hz AC supply with IP 55 class of protection for enclosure, horizontal foot mounted type with Class-'F' insulation,conforming to IS : 325. (D) M.S.fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required. (E) Suitable cement concrete foundation duly plastered and with anti vibration pads. 180 lpm at 70 m Head
Supply and fixing of fire brigade connection of cast iron body with gun metal male instantaneous inlet couplings complete with cap and chain as reqd. for suitable dia MS pipe connection conforming to IS 904 as required :
2 way - 100 mm dia M.S. Pipe (for Ring Main)
4 way-150 mm dia M.S. Pipe (For Fire Water Tank)
Providing and fixing fire brigade suction hose coupling (draw out connection) with nut for female coupling as per IS-902 complete with 100mm dia. Suction pipe and foot valve (to be connected to static tank) complete as required and as per enclosed specification. (For Fire Water Tank)
Providing & fixing of pressure switch in M.S. pipe line including connection etc. as required.
Supplying and fixing single headed internal hydrant valve with instantaneous Gunmetal/Stainless Steel coupling of 63 mm dia with cast iron wheel ISI marked conforming to IS 5290 (Type -A) with blank Gunmetal/Stainless Steel cap and chain as required : Single headed Stainless steel
Supplying and fixing Single headed external yard hydrant valve with 1 No. 63 mm dia instantaneous FM Gunmetal/Stainless Steel coupling and cast iron wheel, ISI marked, conforming to IS 5290 (type A) with blank Gunmetal/Stainless Steel cap and chain as required Single headed Stainless steel
Supplying & fixing 63 mm dia gun metal short branch pipe with 20 mm nominal internal diameter size nozzle conforming to IS 903 suitable for instantaneous connection to interconnect hose pipe coupling as required. Stainless Steel (Grade 304)
S/F of 63 mm dia, 15 m long RRL hose pipe with 63 mm dia male and female couplings duly bound with GI wire, rivets etc. conforming to IS 636 (type-A) as required : Stainless Steel (Grade 304)
Supplying and fixing first-aid Hose Reel with MS construction spray painted in post office red, conforming to IS 884 complete with the following as required. 20 mm nominal internal dia water hose thermoplastic (Textile reinforced) type -2 as per IS: 12585 20 mm nominal internal dia gun metal globe valve & nozzle. Drum and brackets for fixing the equipmets on wall. Connections from riser with 25 mm dia stop gun metal valve & M.S. Pipe and socket. 30 m
Providing and fixing angle iron (40mmx40mmx5mm) door frame and MS sheet (6mm thick) cum glass shutter of size 2.1mtrx0.9mtr(N.S.) with 25mmx25mmx3mm angle frame all around and stiffened in between i/c hinges, handle, locking arrangement, painting with approved synthetic enamel paint i/c sign writing on glass at internal hydrant including providing & fixing S.S. sheet 2mm thick on remaining portion above door to close opening i/c painting etc. as required. Glass shall be 6 mm thick.
Providing & fixing of MS fire Hose cabinet outdoor type of size 0.90 Mx 0.60 Mx 0.50 M made of 6mm thick MS sheet with 6mm thick glazed glass doors i/c necessary locking arrangement suitable to accomodate 2nos 15m long hoses, one no branch pipe, etc. and mounted on 400 mm height agle . The cabinet shall be painted with red colour shade No. 536 of IS: 5 externally & white internally complete in all respects for internal hydrant and as per enclosed specification.
Providing and fixing stainless steel standard fireman's axe with heavy insulated rubber handle tested to 20000 volts as per IS : 926 complete.
PIPES & VALVES Providing laying, testing & commissioning of 'C' class heavy duty MS Pipe conforming to IS 1239/3589 i/c fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. in ground including welding, excavation & providing cement concrete blocks as supports, anticorrosive treatment with coaltar/asphalt tape as per IS 10221, refilling the trench etc. of following sizes complete as required. 150 mm. Dia
Supply and fixing of fire brigade connection of cast iron body with gun metal male instantaneous inlet couplings complete with cap and chain as reqd. for suitable dia MS pipe connection conforming to IS 904 as required :
250 mm dia.
200 mm dia.
150 mm dia.
100 mm dia.
80 mm dia.
65 mm dia.
50mm dia.
40 mm dia.
32 mm dia.
25 mm dia.
Supply and fixing of fire brigade connection of cast iron body with gun metal male instantaneous inlet couplings complete with cap and chain as reqd. for suitable dia MS pipe connection conforming to IS 904 as required :
200mm dia. (Gear Operated)
150mm dia.
100mm dia.
80mm dia.
Supplying, fixing, testing & commissioning of double flanged sluice valve of rating PN 1.6 with non rising spindle, bronze/gun metal seat, ISI marked complete with nuts, bolts, washers, gaskets and conforming to IS 780 of following sizes as required : 150 mm dia.
Supply and fixing of fire brigade connection of cast iron body with gun metal male instantaneous inlet couplings complete with cap and chain as reqd. for suitable dia MS pipe connection conforming to IS 904 as required :
200 mm dia.
150 mm dia.
100 mm dia.
80 mm dia.
Providing, installation, testing and commissioning of stainless steel Y-strainer fabricated out of 1.6 mm thick stainless steel, Grade 304, sheet with 3 mm dia holes with stainless steel flange.
150 mm dia.
80 mm dia.
Providing & fixing of 25mm dia. gunmetal air release valve with all fittings and forged ball valve on header complete as required and as per enclosed specification.
Providing and fixing following size Pressure gauge (0-15 Kg/Cm2) complete with shut off valve duly calibrated before installation complete as required & as per enclosed specification. 150mm dia.
Supply and fixing air vessel made of 250 mm dia, 8 mm thick MS sheet, 1200 mm in height with air release valve on top and flanged connection to riser, drain arrangement with 25 mm dia gun metal wheel valve with required accessories, pressure gauge and paintingwith synthetic enamel paint of approved shade as required.
Providing and fixing reinforced neoprene rubber vibration eliminators/expansion joints (to provide relief from stresses at pipe flanges) suitable for upto 20 kg/cm2 pressure, complete as per specification.
150mm dia.
80mm dia.
Providing, fixing, testing & commissioning of Air Vessel fabricated from 8 mm thick MS plate, 450 mm in diameter and 2 m in height with dished ends fabricated from 8mm thick MS plate with Air release valve with stop cock, flanged inlet connection and drain arrangement with 25mm dia valve, pressure gauge with gun metal stop cock complete with all accessories as required and conforming to IS 4736-1968. (FOR FIRE PUMP ROOM) Recommended dia. : 450 mm Height of shell : 2000 mm Working pressure : 7 Kg/Sq.cm Test Pressure : 10 Kg/Sq.cm
Supply and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ PVC conduit as required. 2 x 1.5 sq. mm
Providing and fixing heavy duty copper armored cables 1.1 KVA grade including necessary support clamps at ceiling level and connection legs complete in all respects.
Power cable 3 core 16 Sq.mm
Power cable 3 core 95 Sq.mm
Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as requried.
Supply and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required..
150mm width x 50mm depth x 1.6 mm thickness.
300mm width x 50mm depth x 1.6 mm thickness.
Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm)
Providing, fixing, testing & commissioning of installation control valve of cast iron body, brass/bronze working parts comprising of water motor alarm, bronze seat clapper, clapper arm and hydraulically driven mechanical gong bell to sound continuous alarm when the wet riser/sprinkler system activates, pressure gauges, emergency releases, strainer, pressure switch, cock valve complete with drain valve and bypass, test control box, ball valves, MS pipe of required size, flanges, orifice plate, gasket etc of follwing sizes as required : 150 mm dia.
Providing & fixing flow switch in following sizes M.S. pipe including connection etc as required.
100mm dia
150mm dia
Providing, fixing, inspecting, testing of built in drain assembly with sight glass for installation on Sprinkler System, in brass body consisting of steel single lever ball valve for multiple test and drain functions, including inlet connection of specified size, sight glass, connections to the main header and line drain complete as per requirements. Product shall suitable for min. 10 kg/cm2 working pressure and shall be UL Listed / FM Approved. 50mm Drain size and 15mm (5.6K) Testing Orifice
AUTOMATIC SPRINKLER SYSTEM
Providing, fixing, testing & commissioning of 15mm dia quartzoid bulb type sprinklers of rating 68 degree centigrade with required accessories : Pendent Sprinkler
Supplying, installation, testing & commissioning of sprinkler flexible pipe (UL Listed) of stainless steel complete with 15 NPT on reducer thread with maximum working pressure of 175 PSI test pressure of 875 PSI (Burst) with branch line (Inlet) 25mm NPT male thread to sprinkler head (Outlet) 15mm NPT female thread with reducer, nipple, 2 side brackets, center bracket, stockbar of following sizes complete as required. 1000 mm
Providing, installation, testing & commissioning of adjustable rosette plate for 15mm dia in white finish UL Listed or FM approved complete as required.
Supplying, installation, testing & commissioning of deluge valve (to be used for water curtains) UL listed with wet pilot basic trim assembly for DVA with test and alarm, drip and drain valve with water motor gong complete as required. 100mm dia
Providing, installation, testing & commissioning of water curtain nozzle 15mm dia nickel chrome plated brass, BSPT, K-factor as per design consideration complete as required.
Fire Extinguishers
Supply,installation,testingand commissioning ISI marked (IS:15683) Fire Extinguisher,Carbon-di-oxide type capacity 4.5 Kg. Flat base including valve, discharge hose of not less than 10 mm dia,1M long and complete in all respects including initial fill with CO2 gas conforming to IS:307-1966 and walll suspension braket. Make- CeaseFire/Minimax/Kanex.
Supply,installation,testingand commissioning ISI marked (IS:15683) Fire Extinguisher,Carbon-di-oxide type capacity 2 Kg. Flat base including valve, discharge hose of not less than 10 mm dia,1M long and complete in all respects including initial fill with CO2 gas conforming to IS:307-1966 and walll suspension braket.Make- CeaseFire/Minimax/Kanex.
Supply, installation, testing and commissioning of 6 kg ABC (Powder Type) Fire Extinguisher. Mild Steel Cylinders ISI marked fitted with pressure indicating gauge, internal tube, squeeze lever type valve fully charged with ABC 90 powder (Mono Ammonium Phosphate) pressured by Nitrogen complete in all respects including wall suspension bracket and conforming to IS:15683 as required as per specifications. Make- CeaseFire/Minimax/Kanex.
Supply,installation,testingand commissioning ISI marked (IS:15683) Fire Extinguisher,Carbon-di-oxide type capacity 9 Kg. Flat base including valve, discharge hose of not less than 10 mm dia,1M long and complete in all respects including initial fill with CO2 gas conforming to IS:307-1966 and walll suspension braket. Make- CeaseFire/Minimax/Kanex.
Providing and fixing CO2 type fire extinguishers consisting of welded M.S.cylindrical body automatic modular CO2 type extinguisher actuated through a sprinkler head mounted on. The extinguisher body finished externally with red enamel with trolly mounted complete with internal charge.(Capacity 22.5 Kg.) Make- CeaseFire/Minimax/Kanex.
Intellgent Addressable Fire Detection and Alarm System
Supply, installation, testing & commissioning of repeater panel wih 320 character/ Touch screen LCD display with inbuilt reset, acknowledge and silence switches complete as required.
Supplying, installation, testing & commissioning of intelligent analog addressable photothermal detector complete with mounting base complete as required.
Supplying, installation, testing & commissioning of intelligent addressable thermal detector with rate of rise cum fixed tempreature thermistor complete with base as required.
Supplying, installation, testing & commissioning of addressable fire control module complete as required.
Supplying, installation, testing & commissioning of fault isolator complete with base as required.
Supplying, installation, testing & commissioning of addressable manual call point complete as required.
Supplying, installation, testing & commissioning of addressable horn cum strobe complete as required.
Supply and fixing of 25 mm sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.
Supply, laying including termination with proper connection & temination of 2 core, 1.5.0 sq. mm. stranded copper conductor, PVC insulated PVC sheathed, FRLS wire in existing conduit.Make: Polycab/KEI/Havalls
Supplying, installation, testing & commissioning of response indicator on surface/recessed MS Box having two LED, metallic cover complete with all connections etc as required.
Providing and installation of Siren Single Phase, 3 Kms range complete in all respects
Supply,Installation , testing and commissioning of Exit Sign Boards with flouracent light complete in all respects
Supply and laying of 1sqmm 4core networking data cable from Main panel to repeater panel. Make Polycab/KEI
HVAC Outdoor Unit Supply, Installation, Testing & Commissioning of modular type Variable Refrigerant Flow / Variable Refrigerant Volume air cooled outdoor units suitable for cooling and heating, having all hermitically sealed inverter type scroll compressor(s), minimum two compressor for above 14 HP modules, microprocessor based controller, top discharge type condensing unit(s), with R 410 A Refrigerant, vibration isolators, with suitable foundation etc. complete as required, The unit shall deliver the rated capacity at AHRI conditions and work even at 500C ambient temperature without tripping. The unit shall be suitable to wok on 400V +/- 10%, 3 Phase, 50Hz AC power supply. The unit shall be filled with first charge of the refrigerant and ready for use as required. The COP at AHRI conditions shall not be less than 3.1 and IEER not less than 6.5. (Make- Daikin/Mitsubishi/Toshiba)
Indoor Unit Ductable Type Supply, Installation, Testing & Commissioning of following minimum capacity and external static pressure VRF/VRV ceiling mounted ductable type indoor unit equipped with washable synthetic media pre-filter, fan section with low noise fan/dynamically balanced blower, multispeed motor, coil section with DX copper coil, electronic expansion valve, corded remote control, outer cabinet, vibration isolators, drain pan, other necessary supports etc., suitable for operation on single phase AC supply 230 V + 10%, 50Hz, complete as required. The unit shall have automatic force shut down provision in case of fire on receiving signal from BMS system or fire panel of the building. The cooling capacity of indoor unit will be at air inlet conditions of 27 Degree C DB and 19 Degree C WB temperature. (Make- Daikin/Mitsubishi/Toshiba) High Static Ductable Units (Minimum 110 Pascal External Static Pressure)
Mid Static Ductable Units (Minimum 45 Pascal External Static Pressure) 4 TR
Indoor Unit Cassette Type Supply, Installation, Testing & Commissioning of following minimum capacity 4-way flow VRF/VRF Cassette type indoor ceiling mounted unit equipped with synthetic washable media pre filter, fan section with low noise fan/dynamically balanced blower, multispeed motor, coil section with DX Copper coil, electronic expansion valve, outer cabinet, drain pump, grill, necessary supports, vibration isolator, cordess
2.8 TR 4 Way VRV/VRF Cassette Unit
1.6 TR 4 Way VRV/VRF Cassette Unit
1.2 TR 4 Way VRV/VRF Cassette Unit
1.0 TR 4 Way VRV/VRF Cassette Unit
Indoor Unit High Wall Type Supply, installation, testing and commissioning of following minimum capacity VRV/VRF High wall type Indoor unit equipped with washable synthetic media pre-filter, fan section with low noise fan/dynamically balanced blower, multi speed motor, coil section with DX copper coil, electronic expansion valve, outer cabinet, drain pump, cordless remote control, drain pan, necessary accessories etc., suitable for operation on 230V±10%, 50Hz, single phase AC supply, complete as required. The unit shall have automatic force shut down provision in case of fire on receiving signal from BMS System. The cooling capacity of indoor unit will be at air inlet conditions of 27 Degree C DB and 19 Degree C WB temperature. (Make- Daikin/Mitsubishi/Toshiba)
Supply Installation, testing & commissioning of Y-joints for various size of Refrigerant pipe including insulation.
Centralized controller Supply Installation, testing & commissioning of Main Intelligent touch screen central controller system including all the accessories suitable to operate, monitor, on/off, temperature setting of all the indoor units individually complete as required and as specified.
Heat Recovery Ventilation Unit Supply, installation, testing and commissioning of heat reclaim ventilation unit with inlet and exhaust blower with fan (Inlet & exhaust) desiccant absorption material non contact seal, modular design with Aluminum supports of extruded section, galvanized steel plate casing, self-extinguishable polyurethane foam insulation, multi-directional fibrous fleeces air filter complete with electric panel with cabling & earthing complete as per requirements.
2000 CMH, 20mmwg ESP
1500 CMH, 20mmwg ESP
Exhaust Air Fans - Axial Flow Type (Fire rated : 250 deg for 2 Hrs. ) Supply, installation, testing and commissioning of normal & smoke extract fans as per specifications. Fan shall be direct driven type with long casing (motor should completely accommodated in fan casing). AMCA Certified (For Air and Sound) tube/vane axial flow fan of different capacity as mentioned below in standard M.S./G.I. construction. Entire fan model & AMCA Seal shall apear in technical submittal of fan. All the fans are synthetic enameled painted/hot dip galvanized with minimum 220 GSM Zinc Coating and complete with bird screen at inlet, along with backdraft dampe at outlet. Fan shall be with flexible fire proof connections at inlet and outlet. The electric motor shall be suitable for 415+/- 10% volts, 50 cycles, 3 phase AC supply with high efficiency, IE-3 type with class `H' insulation. Motor shall be of high temperature resistance "Class H Smoke Spill" 250° C for 2 hour as per (BS-7346 Part 2:1090).Fan shall be CE or UL certified for high temperature. Fan Total Efficiency should be min 70%, noise level should not be more than 75 dba when measured in hemispherical reverberant room conditions at a distance of 3 mtrs from the fan.Cost of spring isolators & back draft damper for the installation of the fans needs to be included. Fan shall be activated receiving signal from fire alarm system. Fans should be as per specification. Motor make shall be same as mentioned on the fire certificate.
Air Quantity : 23000 CFM Static Pressure : 20 mm wg
Air Quantity : 6500 CFM Static Pressure : 20 mm wg
Air Quantity : 4500 CFM Static Pressure : 20 mm wg
Air Quantity : 4000 CFM Static Pressure : 20 mm wg
Air Quantity : 3500 CFM Static Pressure : 20 mm wg
Air Quantity : 3000 CFM Static Pressure : 20 mm wg
Air Quantity : 2000 CFM Static Pressure : 20 mm wg
Air Quantity : 1000 CFM Static Pressure : 20 mm wg
Air Quantity : 500 CFM Static Pressure : 20 mm wg
Fresh Air Fans - Axial Flow Type : ( Non Fire Rated ) Supply, installation, testing and commissioning of AMCA Certified (For Air and Sound) vane/tube axial flow fan of different capacity as mentioned below in standard M.S./G.I. construction with long casing (motor should completely accommodated in fan casing). Entire fan model & AMCA Seal shall apear in techncial submittal of fan. All the fans are synthetic enamelled panited/hot dip galvanized with minimum 220 GSM Zinc Coating and complete with bird screen at inlet, along with backdraft damper. Fan shall be with flexible fire proof connections at inlet and outlet. The electric motor shall be suitable for 415+/- 10% volts, 50 cycles, 3 phase AC supply with high efficiency, IE-3 type with class `F' insulation.Fan shall be CE or UL certified for high temprature. Fan Total Efficiency should be 70%, noise level should not be more than 75 dba when measured in hemisperical reverberant room conditions at a distance of 3 mtrs from the fan.Cost of spring isolators & back draft damper for the installation of the fans needs to be included. Fan shall be activated receiving signal from fire alarm system. Fans should be as per specification.
Air Quantity : 23000 CFM Static Pressure : 20 mm wg
Air Quantity : 12000 CFM Static Pressure : 20 mm wg
Air Quantity : 1000 CFM Static Pressure : 20 mm wg
Air Quantity : 6500 CFM Static Pressure : 20 mm wg
Air Quantity : 4500 CFM Static Pressure : 20 mm wg
Air Quantity : 4000 CFM Static Pressure : 20 mm wg
Air Quantity : 3500 CFM Static Pressure : 20 mm wg
Air Quantity : 3000 CFM
Air Quantity : 2000 CFM Static Pressure : 20 mm wg
Air Quantity : 1000 CFM Static Pressure : 20 mm wg
Air Quantity : 500 CFM Static Pressure : 20 mm wg
Inline Fans Supply, Installation, testing and commissioning inline fans of G.I. construction complete with centrifugal fan with motor, canvass connection at inlet and outlet complete with electric panel with MCB and relays, with 5 Rm cabling and earthing complete as per standards, requirement and drawings.
800 cfm 15 mm wg S.P
100 cfm 15 mm wg S.P
CO Sensor Supply and installation of CO sensors with online, continuous monitoring of CO & CO radicals concentration in ambient air, measuring range: 0-300 ppm CO with electro-chemical (Gel electrolyte) technology, sensor should be UL2075 certified, response time t90 < 30 sec, capable of providing multiple threshold to identify normal mode, invisible smoke mode and fire mode. It should provide both analog output and digital communication via RS485 serial interface with Modbus RTU protocol. It should be uniquely addressable and suitable for connection in digital communication BUS. Enclosure should have minimum fire retardant UL94: V0 rated with IP65 protection. Sensor cell should be plug-in, field replaceable, sensor life expectancy > 7 years, replaceable sensor cell, CE certified. It Should confirm to EMC- Directive 2014/30/EU
Combined MCC + PLC Panel for Fan operation: Supply, installation, testing and commissioning of combined single panel for control logic and fan starter modules, with self diagnostic feature of overload, cable heating, over temperature, inbuilt smoke detection and alarm. Control system should based on programmable logic controller (PLC) with RS485 serial interface over ModBus RTU open protocol digital communication, with Master-Slave architecture connected in Bus – sensor values, fan status, alarm status, error & fault log, alarm location etc. topology. Sensors should be connected in Bus and addressed, with bi-directional communication, capable of configuring multiple threshold for each sensor to identify and trigger normal ventilation, fire mode etc. It should work in closed loop, feedback mode with sensors, with auxilliary power supply to the sensor transmitters. It should be easily integrated with BMS (from Master PLC Module if required) providing all parameter values including fan status, sensor values, threshold status, fire command etc. It should accept and offer command to & from fire alarm system. Master Panel should have colored touch-screen based HMI LCD display for System should be configurable via touch-screen with easy English driven menu. It should have password protection against unauthorized access. Programmable to run and control fan (Jet Fans, Axial Fans) operation in normal, early fire, ventilation and fire mode based on sensor values or fire alarm signal or BMS signal or Manual operation. Configurable to control fan operation of any zone based on trigger of sensor of any same or other zone.It should have automated logic controlled fan Starter for Jet fans, Axial fans start / stop. It should have closed feedback signals for fan status, fan error etc. It should have overvoltage, over current, phase protection features. Manual / Auto fan mode should be accessed by LCD Display.
2 x 2-core 1.00 sq mm, twisted, shielded cable (PLC to Sensor).
2-core 1.00 sq mm, twisted, shielded cable (PLC to PLC).
Copper Refrigerant Piping Supply, Installation, Testing & Commissioning including vaccumiazation and Nitrogen testing of following nominal sizes of soft/hard drawn copper refrigerant piping for VRV/VRF system, complete with fittings, with suitable adjustable ring type hanger supports, jointing/brazing including accessories, insulated with with Class-O closed cell elastometric nitrile rubber insulation of specified thickness as given below for Suction and Liquid lines, all accessories as per specifications etc. as required:
6.4 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm with 19 mm thick insulation
9.5 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm with 19 mm thick insulation
12.7 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm with 19 mm thick insulation
15.86 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm with 19 mm thick insulation
19 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm with 19 mm thick insulation
22.2 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm with 19 mm thick insulation
28.58 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm with 19 mm thick insulation
34.9 mm dia (OD) (Hard drawn) with tube thickness 1.62 mm with 19 mm thick insulation
41.27 mm dia (OD) (Hard drawn) with tube thickness 1.62 mm with 19 mm thick insulation
Drain Piping Supply, Installation, Testing & Commissioning including vaccumiazation and Nitrogen testing of following nominal sizes of soft/hard drawn copper refrigerant piping for VRV/VRF system, complete with fittings, with suitable adjustable ring type hanger supports, jointing/brazing including accessories, insulated with with Class-O closed cell elastometric nitrile rubber insulation of specified thickness as given below for Suction and Liquid lines, all accessories as per specifications etc. as required:
50 mm dia
40 mm dia
32 mm dia
25 mm dia
Ducting Supply, installation, balancing and commissioning of factory fabricated GSS sheet metal rectangular ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required. G.I. Sheet Metal Ducting (Rectangular)
Thickness 0.63 mm sheet (750 mm & below)
Thickness 0.80 mm sheet (751 mm - 1500 mm)
Thickness 1.00 mm sheet(1501 mm - 2250 mm)
Thickness 1.25 mm sheet (2251 mm & above)
Insulation Supplying and fixing of following thickness duly laminated aluminum foil of mat finish closed cell Nitrile rubber (class "O") insulation on duct after applying adhesive for nitrile rubber . The joints shall sealed with 50 mm wide and 3 mm thick self adhesive nitrile rubber tape insulation complete as per specifications and as required. 19 mm thick
Duct Acoustic Lining Supply and fixing of accoustic lining of supply air duct and plenum with 25 mm thick resin bonded glass wool having density of 32 kg/m3, with 25 mm x 25 mm GI section of 1.25 mm thick, at 600 mm centre to centre covered with Reinforced Plastic tissue paper and 0.5 mm thick perforated aluminum sheet fixed to inside surface of ducts with cadmium plated nuts, bolts, stick pins, CPRX compound etc. complete as required and as per specifications. 25 mm thick, 32 kg/m3 density
Grilles / Diffuser Supply, installation, testing and commissioning of Aluminium extruted powder coated supply and return air grilles/ diffusers as per specifications and drawings (Approval of colour shall be taken from Architects/Consultants).
Supplying & fixing of powder coated extruded aluminium Supply Air Grills with aluminium volume control dampers as per specifications.
Supplying & fixing of powder coated extruded aluminium Return Air Grills with louvers but without volume control dampers complete as required.
Supply, fixing, testing & commissioning of exhaust air diffuser of powder coated aluminium with volume control damper with anti smudge ring & removable core.
Louvers Supply and fixing of Fresh / Exhaust air Aluminium extruded with bird screen, damper adjustable louvers as per specifications and drawings.
Flexible Duct Connection Supplying and fixing Fire retardant non porous double layer flexible connection between ductable, ahu, fresh air unit & PAC indoor unit and duct.
Isolator Supplying & installation of weather proof isolator with suitable rating near each outdoor unit the prices should be inclusive of copper cabling from isolators to outdoor units and complete as required.
1 No. 25 Amps MCCB outgoing along with 1 No. star delta starter for axial fan motor (1 No. spare).
1 No. 25 Amps MCB outgoing along with 1 No. DOL starter for axial fan motor (1 No. spare).
1 No. 16 Amps MCB outgoing along with 1 No. DOL starter for axial fan motor (1 No. spare).
Power Cabling Supply & fixing of PVC sheathed Aluminum / Copper cables for various equipment’s through walls/ceiling with appropriate clamps & fixing arrangement as per specifications and drawings.
3C - 4 sq. mm (Aluminum)
2C - 1.5 sq. mm (Copper) For HRV Units
Control & Transmission Wiring Supply and installation of control cum transmission wiring of 2 core x 1.5 sq. mm Aluminum in suitable conduits between indoor and outdoor unit.
Cable Tray Supplying and installation of following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc. as required.
450 mm width X 50 mm depth X 2.0 mm thickness
300 mm width X 50 mm depth X 1.6 mm thickness
150 mm width X 50 mm depth X 1.6 mm thickness
Earthing Supply and laying of double earthing continuity conductors of G.I. between panel boards and equipments as drawings.
Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.
Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required.
Modern Electric Company (BID ID -407112)
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.58 MB
SBD.pdf
Tender Documents • 1.41 MB
BOQ_105414.xls
BOQ • 0.60 MB
Download all tender documents and submit your bid