Executive Engineer
PWD Electrical Division, Thrissur
GENERAL Home Department Judiciary work recommended in the security audit report in NIA Special Court Ernakulam Standardization of existing EI Installation of DG set and fire protection arrangements General Electrical Work
2023_PWD_595869_2
PWD/BLDG/7052/2023-2024
Open Tender
Electrical Works
Item Rate
180 days
Ernakulam
Please refer Tender documents.
10 documents required · 10 mandatory
₹2,760
₹47,908
21 Nov 2023
20 Sept 2023
29 Sept 2023
20 Sept 2023
27 Sept 2023
20 Sept 2023
Amount
Providing 50 KVA DG Set
OD233875/2022-2023:Supply,Conveyance, Installation and Testing of 50 KVA Diesel Generator set and integral acoustic enclosure as per CPCB norms and as per technical details given below. 1. Engine. a) Make of Engine - Leyland / Greaves / Kirloskar Green b.Type of Engine - Diesel Engine. c. No. of Cylinders - As per manufactures standards. d. Method of cooling - Water cooled with radiator e. Aspiration - Turbo charged after cooled f. Design - Suitable for generating set operation. g. Out put -32 BHP at 1500 rpm under NTP condition,. 2. Standard accessories with Diesel Engine. a. Fly wheel to suit flexible coupling b. Close Coupling. c. Air cleaner. d. Radiator with fan provided with fan guard e. Fuel Pump. f. Mechanical governor. g. Fuel filter. h. Lubricating oil filter. i. Exhaust silencer. j. Exhaust Muffler k. Battery Charger/Generator 3. Engine Instrument Panel with the following items. a. Starting switch with key or button b. Lubricating oil pressure gauge. c. Water temperature gauge. d. RPM Indicator with hour meter. e. Battery charging ammeter. 4. Safety Controls for Engine a. Trip for low lubricating oil pressure. b. Trip for high water temperature. 5. Brushless Alternator a. Make - Stamord/ crompton b. Type - Self exited and self regulated. c. Capacity - 25KVA/ 20kW @ 0.8 PF d. System of Voltage - 3 Phase, 415 V, 4 wire system e. Speed - 1500 rpm. f. Voltage regulation band - +/- 1% of rated voltage g. Frequency : 50 Hz h. Insulation - Class - H. The alternator should confirm to IS 4722. Operation and service manual , spares and tools shall be provided. 6. Fuel Tank Suitable size built in type integrated with the acoustic enclosure Fuel connection shall be done as per standards 7. Battery. Suitable capacity fully charged battery with leads and terminals of appropriate AH capacity as per Manufactures requirement. Automatic Battery charger. 8. Comprising of Gen-Set Controller-model KG934, which has indication / LCD displays available for Lube oil pressure, Battery voltage, Engine RPM, fuel level in the day tank, Engine Running hours, AC Current, AC Voltage,AC Frequency, AC Power metering with Safety trips for high engine temperature, low lube oil pressure, low radiator water level, low fuel level, under/over speed and high canopy temperature . The D.G set should have a warranty of three years
14.1:Excavation for foundation in soft soil including dressing of sides and ramming of bottoms, lift upto 1.5 m including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 metres.
14.7:Providing and laying in position cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) in foundation of pump, DG set etc including form work etc as required.
14.10:Providing and laying in position reinforced cement concrete 1 :2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) in foundation of pump, DG set etc. including form work etc. as required (excluding reinforcement).
14.12:Providing 15mm thick cement plaster of mix 1:4(1 cement: 4 fine sand) at all levels
OD233885/2022-2023:Supply and providing 80 mm/equivalent size M. S. pipe -5mm thickness B class complete with suitable size 12mm flange coupling with minimum 4/5mtr using allied packing with MS bolt with washer and rising the same on the wall/ parapet using chain pulley, scaffolding's, supports with M.S angles/channels etc. including painting the pipe with one coat of zinc chromate primer over a coat of high temperature resistance aluminum paint etc. for extending the exhaust pipe of the newly erected 50 KVA D. G. sets.
5.8:Supplying and laying 25 mm X 5 mm copper strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm)
90.16.1.5:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required4.75 mm copper conductor (6 SWG)
90.16.5.3:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.3.15 mm (10 SWG)
90.16.5.5:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.4.75 mm (6 SWG)
5.4:Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
90.16.2.1:Supply and laying of the following sizes of B class GI pipe laid 0.6 m below ground level including excavating trench of suitable size and refilling etc, as required.15.mm dia. G.I pipe ( medium class)
90.12.7.28:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 35 sq mm with factory made clamp
9.1.21:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 35 sq. mm (32mm)
OD234045/2022-2023:Supply and providing and fixing 100A, 4 pole On-Load Change Over Switches In Sheet Steel Enclosure with ISI marked HRC fuses on wall/angle iron frame including drilling holes in frame, making connections, etc. as required
2.1.3:Providing and fixing following capacity TP&N disconnector fuse switch unit inside the existing panel board with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required.100 Amp TP&N
OD108870/2023-2024:Charges for preparation of Electrical/Fire drawing A3 sheet-additional copy
OD108871/2023-2024:Charges for preparation of Electrical/Fire drawing per A3 sheet-first copy
Providing High mast Light
90.15.4.9:Supply Conveyance, installation, testing and commissioning of 150W LED Flood light output greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminium pressure die-cast Powder coated housing, acrylic cover complete with THD less than 10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer)
90.15.2.3:Supply installation testing and commissioning of High Mast using Octogaonal Pole made single/two sections of hot dip galvanised GI sheet 100mm top diameter, 360mm bottom diameter thickness 3mm mm suitable for wind speed as per IS 875 Part III with head frame assembly two point suspension system with steel wire rope 5mm dia double drum winching system w and including round arm galvanized luminary carriage suitable to install 6/8 nos luminaries in symmetrical arrangement control gear box and lighting spikes with single phase operation power tool installed inside the base compartment including connector foundation bolt 4 nos fixed in existing RCC foundation and junction box etc, complete 12 Meters
OD235624/2022-2023:Supply and installation of Twin unit aviation LED Obstruction light with stand yellow - painted die cast aluminium alloy housing, red coloured polycarbonate dome and BC/EC lamp holders sutable for LED lamp
90.14.5:Supply and fabrication conveyance and installation of angle iron frame work for wall mounting panel board
OD235672/2022-2023:Supplying and fixing 40A, double pole, 240 volts,center OFF COS in the existing MCB DB complete with connections, testing and commissioning etc. as required.
OD235684/2022-2023:Supply and fixing 24Hr Time Switch 240V AC DIN/BASE mounting (L&T make) giving connections etc as required
OD235687/2022-2023:Supply and fixing 25A AC1, power contactor (L&T make MNX 9) conforming to IS in the existing enclosure and giving connection as required
2.14.1:Supplying and fixing following rating, double pole, (single phase and neutral), 240 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.25 amps
2.12.1:Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.10.1:Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole
90.6.5.19:Supply and drawing the following sizes of multi-core PVC insulated & FRLS PVC sheathed 650/1100 V grade copper conductor round flexible cables conforming to IS 694 part I 1960 in the existing surface / recess conduit as required including giving necessary connections of the following sizes.4 core 2.50 sq mm
1.17.1:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.1 x 1.5 sq. mm
1.17.12:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 2.5 sq. mm
1.17.20:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.2 x 4 sq. mm
90.12.5.3:Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.2 core 10 sq mm
9.1.2:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.2 X 10 sq. mm (19mm)
90.12.10.2:Supply & laying of DWC pipe in ordinary soil 0.75m below ground level including excavation50/38 mm or nearest size
90.16.1.2:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required2.65 mm copper conductor (12 SWG)
90.16.1.3:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required3.15 mm copper conductor ( 10 SWG)
90.16.5.2:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.2.65 mm (12 SWG)
90.16.5.3:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.3.15 mm (10 SWG)
OD235735/2022-2023:Supply & installation of dust and vermin proof, HENSEL make Mi 0800 - With Transparent hinged lid & meter fixing rails of size600x600x170mm and to fix KSEB meters, fuse units, CT etc as required including fixing it on wall, making good the damages colour washing etc. as required.
OD235738/2022-2023:Supply and fixing the following accessories in the existing meter board and giving connections etc.(32, HRC Fuse Base with HRC Fuse link)
OD235741/2022-2023:Supply and fixing the following accessories in the existing meter board and giving connections etc.(32 A, 2 Way neutral links mounted on DMC/SMC base)
14.1:Excavation for foundation in soft soil including dressing of sides and ramming of bottoms, lift upto 1.5 m including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 metres.
14.8:Providing and laying in position cement concrete 1 :3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size) in foundation of pump, DG set etc. including form work etc. as required.
14.10:Providing and laying in position reinforced cement concrete 1 :2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) in foundation of pump, DG set etc. including form work etc. as required (excluding reinforcement).
5.4:Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
OD235963/2022-2023:Steel reinforcement for RCC work including straightening, cutting, bending and placing in position and binding all complete
OD235990/2022-2023:Supply and providing 25x6mm brass nut and bolt etc. as required.
OD235993/2022-2023:Supply and providing 25x3mm brass nut and bolt etc. as required.
STANDADISATION OF EI
90.14.1.2:Fabrication, supply, conveyance, installation testing and commissioning of floor or wall mounting, dust and vermin proof, cubicle type MV panel board comprising of the following components/ devices & complying to IS 8623.<br> Fabrication of fully partitioned, dust and vermin proof enclosure for panel assembly as per form 4 of IS 8623 (with latest amendments) using CRCA sheet as per approved design and requirement, with front and rear access facility, bus bar chambers, hinged doors for all switch gear compartments, earthing the doors using 4 sq mm braided copper conductor, providing necessary cut-outs for mounting meters, relays, indication lamps, bus bar interconnection etc, detachable covers for bus bar chamber and cable alley, powder coating the assembly after subjecting to 7 tank process etc as required. CRCA sheet alone be used for the fabrication. Angles/ flats/ slotted angles etc shall not be used for the fabrication of panel assembly. The measurments will be taken the area of the complete sheets used for panel board including partitions, folding, shrouding etc.Supply and fabrication of MV panel board using 1.6mm CRCA sheet, powder coated (excluding base frame)
90.14.2.1:Supply and providing 2mm SMC sheet as shrouding for bus interconnection / terminations etc. including required nut & bolt etc.
90.14.3.1:Supply and providing heavy duty 'A' section neoprene gasket in the panel boardA' section neoprene beeding suitable for 1.60/ 2.00 mm sheet
90.14.4:Supply and fabrication conveyance and installation of base frame of panel board using 75 x 40 mm rolled steel channel (ISMC)
90.14.6:Supply and providing copper bus bars including finger type SMC bus bar supports in the bus chamber, suitable size nut & bolt, providng heat shrink sleeves etc. as required.
90.14.7:Supply and providing copper earth bus in the panel board
2.1.1:Providing and fixing following capacity TP&N disconnector fuse switch unit inside the existing panel board with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required.32 Amp TP & N
2.1.2:Providing and fixing following capacity TP&N disconnector fuse switch unit inside the existing panel board with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required.63 Amp TP & N
2.2.13:Providing and fixing following rating and breaking capacity and pole MCCB in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required.100 Amp, 30 KA 4 Pole
90.14.11.5:MCCB AccessoriesSupply and fixing 100 - 200A earth fault module of MCCB with builtin CBCT.
90.14.11.12:MCCB AccessoriesSupply and fixing shunt release for all voltage range up to 630A.
90.14.11.13:MCCB AccessoriesSupply and fixing rotary handle, External type (including BUC handle with door interlock ) in the existing MCCB of rating up to 250 A
OD77444/2023-2024:Supply and Fixing of Red, Green, Black, Yellow, Orange colours LED indicator, AC/DC, 22.5 mm cut out dia
2.10.2:Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole and netural
2.16:Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32amps 240 volts "C" curve DP MCB complete with connections, testing and commissioning etc. as required.
2.1.5:Providing and fixing following capacity TP&N disconnector fuse switch unit inside the existing panel board with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required.160 Amp TP&N
90.12.7.29:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 50 sq mm with factory made clamp
90.12.5.29:Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.3.5 core 50 sq mm
90.12.10.3:Supply & laying of DWC pipe in ordinary soil 0.75m below ground level including excavation63/50 mm or nearest size
90.12.7.40:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 10 sq mm with factory made clamp
9.1.22:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2 X 50 sq. mm (35mm)
9.1.32:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 10 sq. mm (25mm)
90.11.1.18:Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required4 way (8+12) - double cover TPN vertical DB with provision for fixing MCCB as incomer and SP/ TP MCB as outgoing (IP 42/43)
2.3.3:Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCBIRCCB/Isolator12 way, Double door
5.4:Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
OD14843/2023-2024:Supply and providing and fixing 100A, 4 pole On-Load Change Over Switches In Sheet Steel Enclosure with ISI marked HRC fuses on wall/angle iron frame including drilling holes in frame, making connections, etc. as required...
OD20480/2023-2024:Carrying out control wiring for panel with normal meters and indication lamps alone with 650/1100 V grade PVC insulated stranded single core copper conductor cables 1.50 sq mm single run with required sockets.conforming to IS 694 part I 1990 for interconnecting the control devices/ equipments including providing suitable size insulated sockets at the termination points or soldered properly, providing numbering ferrules for the proper identification of the wiring, keeping the wiring firm by suitable tie/ tie mounts/ PVC duct etc as required.
OD20510/2023-2024:Supplying and fixing 32 A, 2 Way neutral links mounted on DMC/SMC base with connections, in existing meter board
OD20511/2023-2024:Supplying and fixing 32, HRC Fuse with HRC Fuse link with connections, in existing meter board
OD20513/2023-2024:Supply and Fixing of Red, Green, Black, Yellow, Orange colours LED indicator, AC/DC, 22.5 mm cut out dia
OD20554/2023-2024:Supply and Fixing of Blue colour LED indicator, AC/DC, 22.5 mm cut out dia
OD20555/2023-2024:supply and fixing Digital Multifunction meter to read: V, A, F, PF-3 phase accuracy class 1 LED
OD20556/2023-2024:Supply and fixing 100/5 A, 5 VA, accuracy class 1, Tape wound Metering CT
OD20566/2023-2024:Supply and providing ABC type fire extinguisher 6kg capacity with installation brackets conforming to IS 15222 as required
OD80005/2023-2024:Supply and installation of Clean agent Fire Extinguisher 6 Kgs. Capacity ceiling mounted type suitable for below ceiling built in 1 piece with body and bottom. Mild Steel Body owith pressure gauge, refillable device and safety release device, Brass valve suitable for B and C Classes of Fire complete with Charge of HFC Blend A, It is a blend of Hydro Fluoro carbon and organic detossificant essence P 26. The Extinguisher shall have pressure gauge for indicating inside pressure with opening and closing lever of squeeze grip type with tamper proof seal. The Extinguisher as per IS:15683-2006 with ISI Mark.
OD20706/2023-2024:Supply and providing First Aid Chart duly framed and placed in a conspicuous location for clear vision.
OD79771/2023-2024:Painting letters or figures of the following sizes with enamel paint as identification mark to SB, DB, panel board etc as required
90.16.1.1:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required2.00 mm copper conductor ( 14 SWG)
90.16.1.5:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required4.75 mm copper conductor (6 SWG)
90.16.5.1:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.2.00 mm (14 SWG)
90.16.5.5:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.4.75 mm (6 SWG)
OD20691/2023-2024:Supply and providing 2.5mm thick Elastomeric fire retardent insulating mat as per IS 15652/2006 to withstand 11 KV dielectric strength including fixing with suitable synthetic adhesive,
OD20563/2023-2024:Supply and providing 9L capacity GI Fire Bucket painted in post office red with primer coat of red oxide and written with white paint FIRE mounted on MS angle frame work/wall bracket filled with fine sand,painted the bracket/floor stand including making good the damages,colour washing etc.as required.as per IS 2546
EI Maintenance
1.10.3:Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.Group C
90.3.10:Supplying and providing extra H.G conduit down rod of 19 mm dia 2 x 1.00 m long with 16/0.20 mm 3 core copper conductor flex wire conforming to relevant ISS or with the extended original wiring and giving connection etc. as required.
90.3.24.3:Supply & installation of light fittings suspended on ball & socket arrangement with 19 mm down rod <br> Supply, conveyance, installation, testing and commissioning the light fittings of following types made of .5mm thick CRCA sheet accessories and lamps etc. including supplying and fixing ball and socket arrangements on PVC round block, suspension down rod of 19mm dia MS conduit up to 2x30cm length including painting and wiring the down rod with 16/0.20mm 3 core round copper conductor flex wire conforming to relevant ISS or extending the original wiring and giving connections etc. a required.1200 mm 1X20W LED Lamp with box type fixture
90.3.18.2:Supply, fabrication, conveyance and fixing the following sizes of B class GI pipe bent to shape / cut and welded to shape and fixing the same to wall / parapet using clamps as noted along with each size, painting with 2 coats of synthetic enamel paint over a coat of zinc chromate primer, making good the damages, colour washing etc as required.32 mm dia with HG company fabricated clamps
90.4.1:Supply and installation of suitable size MS rod type fan clamp in the RCC slab as per IS 732 as required.
90.4.2:Supply and installation of suitable size MS belt type fan clamp fabricated from flat iron 40 x 6 mm, 150mm long x 2 Nos with M.S. rod bent to shape, neatly painted with 2 coats of enamel paint over a coat of red oxide primer as per IS 732 as required.
90.4.5.4:Supply, Installation, testing and commissioning of ceiling fan of following sizes including wiring the down rods of standard length (up to 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable etc. as required. 1200mm sweep - ceiling fan complete with service value minimum 4.0(cub meter/minute/Watt), Air delivery minimum 210(cubic meter/minute), Copper winding suitable for 230V/240V single phase AC supply
OD18091/2023-2024:Supply, conveyance installation testing and commissioning of 40W LED Flood light output > 105lumen/W 4000-6000 K with IP 66protection LED Chip make Cree/Lumilled/Nichea with power factor>0.95 at full load, internal surge protection up to 8 KV,and Aluminiumpressure die-cast Powder coated housing, acrylic cover complete withTHD <10%, power factor >0.98, RoHS compliant, duly wired up for useon 230 V AC supply. Driver compartment should be seperatly accessiblefor maintenance (LM 79&80 certificates from NABL accredited Thirdparty lab to be produced mentioning chip manufacturer in the existing GI pipe and giving connection as required.
OD18095/2023-2024:Supply, conveyance installation testing and commissioning of 70W LED Flood light output > 105lumen/W 4000-6000 K with IP 66protection LED Chip make Cree/Lumilled/Nichea with power factor>0.95 at full load, internal surge protection up to 8 KV,and Aluminiumpressure die-cast Powder coated housing, acrylic cover complete withTHD <10%, power factor >0.98, RoHS compliant, duly wired up for useon 230 V AC supply. Driver compartment should be seperatly accessiblefor maintenance (LM 79&80 certificates from NABL accredited Thirdparty lab to be produced mentioning chip manufacturer in the existing GI pipe and giving connection as required.
1.58:Supplying and fixing PVC batten/ angle holder including connection etc. as required.
90.5.1.3:Supply and fixing the following types of superior quality 250V A.C call bell on existing M.S. box and giving connections with required length of 3 core, 16 / 0.20mm 650/1100V grade PVC insulated and PVC sheathed round copper conductor flex wire conforming to relevant ISS or with the extended original wiring, earthing the MS box and making good the surface as required.Ding dong bell
1.21.1:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm
1.21.2:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm
OD18114/2023-2024:Supply and providing every additional length of down rod of suitable size heavy gauge GI / WI pipe with 16/0.20mm PVC insulated and PVC sheathed 3 core round copper conductor flex wire conforming in relevant ISS or with original wiring extended including painting as required.
1.22.3:Supplying and fixing metal box of following sizes (nominal size) on surface or in recess with suitable size of phenolic laminated sheet cover in front including painting etc as required.150 mm X 75 mm X 60 mm deep
OD18337/2023-2024:Supply and providing the following types and power rated lamps in the existing fittings as required. B22 LED bulb 9W
OD18270/2023-2024:Supply, conveyance, installation , testing and commissioning of 300/305 mm sweep Light Duty Exhaust fan in metal frame working on 230 V A/C in the existing opening, fixing necessary anchor bolts / bolt and nuts etc., as required including giving connections with the supplied wire along with the exhaust fan.
1.22.4:Supplying and fixing metal box of following sizes (nominal size) on surface or in recess with suitable size of phenolic laminated sheet cover in front including painting etc as required.150 mm X 150 mm X 60 mm deep
1.27.2:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.3 Module (100mmX75mm)
1.27.5:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.8 Module (125mmX125mm)
1.17.3:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 X 1.5 sq.mm
1.17.4:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.4 x 1.5 sq. mm
1.17.5:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.5 X 1.5 Sq. mm
1.17.6:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.6 x 1.5 sq. mm
1.17.12:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 2.5 sq. mm
1.17.13:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.4 x 2.5 sq. mm
1.17.14:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.5 x 2.5 sq. mm
1.17.15:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.6 x 2.5 sq. mm
1.24.1:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 amps switch
1.24.3:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.15/16 amp switch
1.24.4:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.3 pin 5/6 amp socket outlet
1.24.5:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.6 pin 15/16 amp socket outlet
2.16:Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32amps 240 volts "C" curve DP MCB complete with connections, testing and commissioning etc. as required.
1.25:Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required.
OD79809/2023-2024:Painting letters or figures of the following sizes with enamel paint as identification mark to SB, DB, panel board etc as required
OD18262/2023-2024:Supply and fixing the following deep PVC accessories conforming to IS 3419/1988 along with the PVC conduits. 20 mm one way terminal junction box
OD18139/2023-2024:Supply and renewing fan condenser of ceiling fan in place of faulty one and giving connection.
1.33:Supplying and fixing 3 pin, 5 amp ceiling rose on the existing junction box/ wooden block including connection etc as required.
OD18263/2023-2024:Supply and fixing the following PVC accessories conforming to IS 3419/1988 along with the PVC conduits . 20 mm two way through junction box
OD18220/2023-2024:Supply and fixing the following PVC accessories conforming to IS 3419/1988 along with the PVC conduits. 20 mm three way tee junction box
OD18398/2023-2024:Supply and fixing the following deep PVC accessories conforming to IS 3419/1988 along with the PVC conduits. 20 mm one way terminal junction box
OD18261/2023-2024:Charges for dismantling the existing EI, complete, making good the damages of walls and conveying the dismantled materials to section store.
OD26922/2023-2024:Supply, installation, and commissioning of 2kva UPS Single phase in and out. with indoor (IP20) with 1 hours backup battery @ 2kva with min VAH of 4230 (Tubular battery of reputed approved make exide/quanta including rack and interconnecting cables), Input pf >0.99, Inernal Isolation transformers at Input, double conversion technology with input voltage range 160-300 @ full load, 50Hz Single Phase, output 230V, 50Hz Single phase, It shall be 100% generator compatible, with Efficiency > 87% and output power factor unity ( 2kVA=2kW), Eco mode Efficiency 98% and including all accessories etc as required. The acoustic noise at 1m of the system should be <50dB.The system shall comply to IEC /EN 62040-1, EN/IEC 62040-2, EN/IEC 62040-3, CE, BIS, ROHS, and relevant IS standards. The system shall be true online double - conversion DSP based UPS system and also UPS shall be with automatic bypass builtin. The system shall have IGBT rectifier and inverter. warranty 3 years for UPS and batteries. APC/GE/Zebronics/Riello/Numeric
Bidder Name
Kittu Electricals private limited
stage.html
html • 0.04 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_901284.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .