Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹401.3 CrAccepted-Finance | ₹401.3 Cr | L1 | Accepted-Finance L1 Accepted |
| 2 | L2₹402.6 CrRejected-Finance NCC HOUSE MADHAPUR HYDERABAD 500081 TELANGANA INDIA TELEPHONE 040 23268730 | ₹402.6 Cr | L2 | Rejected-Finance L2 Rejected |
| 3 | L3₹404.3 CrRejected-Finance S 2 TECHNOCRAT INDUSTRIAL ESTATE BALANAGAR HYDERABAD 500 037 TELANGANA INDIA | HYDERABAD | HYDERABAD | TELANGANA | 500037 | ₹404.3 Cr | L3 | Rejected-Finance L3 Rejected |
| 4 | L4₹405.1 CrRejected-Finance JINDAL ITF CENTRE 28 SHIVAJI MARG MOTI NAGAR NEW DELHI 110015 INDIA | NEW DELHI | WEST DELHI | DELHI | 110015 | ₹405.1 Cr | L4 | Rejected-Finance L4 Rejected |
| Sl No | Description | Qty | Unit | JWIL INFRA LIMITED L4 | NCC LIMITED L2 | MEGHA ENGINEERING AND INFRASTRUCTURES LIMITED L3 | Civet Projects Private Limited L1 |
|---|---|---|---|---|---|---|---|
| 1.00KOVVUR MUNICIPALITY | |||||||
| 2.00Construction of Raw Water Intake Well in River Godavari down stream side of 4th bridge | |||||||
| 3.00 | Well sinking for construction of 8.0m dia Raw Water Intake well in sandy and other loose soils under water either by manual sinkers and labour, divers, or dredgers, weighing the top of steining to assist sinking etc.,. This rate including cost of all labour charges, dewatering, hiring of machinery, fuel charges, wages of driver ,transportaions of machinary and other incidental charges etc., complete for finished item of work and as per ss and as adirected by the departmental officer in charge of work. For the following the depths a) Up to 2.00m depth | 2 | Rmt | 31,826 ₹63,652 | 36,282 ₹72,564 | 28,643 ₹57,286 | 29,791 ₹59,582 |
| 4.00 | Well sinking for construction of 8.0m dia Raw Water Intake well in sandy and other loose soils under water either by manual sinkers and labour, divers, or dredgers, weighing the top of steining to assist sinking etc.,. This rate including cost of all labour charges, dewatering, hiring of machinery, fuel charges, wages of driver ,transportaions of machinary and other incidental charges etc., complete for finished item of work and as per ss and as adirected by the departmental officer in charge of work. For the following the depths b) 2.00m to 4.00m depth | 2 | Rmt | 94,903.13 ₹1.9 L | 1,08,190 ₹2.2 L | 1,02,495 ₹2.0 L | 87,711 ₹1.8 L |
| 5.00 | Well sinking for construction of 8.0m dia Raw Water Intake well in sandy and other loose soils under water either by manual sinkers and labour, divers, or dredgers, weighing the top of steining to assist sinking etc.,. This rate including cost of all labour charges, dewatering, hiring of machinery, fuel charges, wages of driver ,transportaions of machinary and other incidental charges etc., complete for finished item of work and as per ss and as adirected by the departmental officer in charge of work. For the following the depths c) 4.00m to 6.00m depth | 2 | Rmt | 1,53,621.58 ₹3.1 L | 1,75,129 ₹3.5 L | 1,65,911 ₹3.3 L | 1,40,338 ₹2.8 L |
| 6.00 | Well sinking for construction of 8.0m dia Raw Water Intake well in sandy and other loose soils under water either by manual sinkers and labour, divers, or dredgers, weighing the top of steining to assist sinking etc.,. This rate including cost of all labour charges, dewatering, hiring of machinery, fuel charges, wages of driver ,transportaions of machinary and other incidental charges etc., complete for finished item of work and as per ss and as adirected by the departmental officer in charge of work. For the following the depths d) 6.00m to 8.00m depth | 2 | Rmt | 2,04,451.48 ₹4.1 L | 2,33,075 ₹4.7 L | 2,20,808 ₹4.4 L | 1,86,840 ₹3.7 L |
| 7.00 | Well sinking for construction of 8.0m dia Raw Water Intake well in sandy and other loose soils under water either by manual sinkers and labour, divers, or dredgers, weighing the top of steining to assist sinking etc.,. This rate including cost of all labour charges, dewatering, hiring of machinery, fuel charges, wages of driver ,transportaions of machinary and other incidental charges etc., complete for finished item of work and as per ss and as adirected by the departmental officer in charge of work. For the following the depths e) 8.00m to 10.00m depth | 2 | Rmt | 2,45,852.1 ₹4.9 L | 2,80,272 ₹5.6 L | 2,65,520 ₹5.3 L | 2,22,028 ₹4.4 L |
| 8.00 | Well sinking for construction of 8.0m dia Raw Water Intake well in sandy and other loose soils under water either by manual sinkers and labour, divers, or dredgers, weighing the top of steining to assist sinking etc.,. This rate including cost of all labour charges, dewatering, hiring of machinery, fuel charges, wages of driver ,transportaions of machinary and other incidental charges etc., complete for finished item of work and as per ss and as adirected by the departmental officer in charge of work. For the following the depths f) 10.00m to 12.85m depth | 2.85 | Rmt | 3,47,848.38 ₹9.9 L | 3,96,548 ₹11.3 L | 3,75,676 ₹10.7 L | 3,14,203 ₹9.0 L |
| 9.00 | Well sinking for construction of 8.0m dia Raw Water Intake well in sandy and other loose soils under water either by manual sinkers and labour, divers, or dredgers, weighing the top of steining to assist sinking etc.,. This rate including cost of all labour charges, dewatering, hiring of machinery, fuel charges, wages of driver ,transportaions of machinary and other incidental charges etc., complete for finished item of work and as per ss and as adirected by the departmental officer in charge of work. For the following the depths g) 12.85.00m to 13.85m depth | 1 | Rmt | 3,65,240.8 ₹3.7 L | 4,16,375 ₹4.2 L | 3,94,460 ₹3.9 L | 3,26,140 ₹3.3 L |
| 10.00 | Well sinking for construction of 8.0m dia Raw Water Intake well in sandy and other loose soils under water either by manual sinkers and labour, divers, or dredgers, weighing the top of steining to assist sinking etc.,. This rate including cost of all labour charges, dewatering, hiring of machinery, fuel charges, wages of driver ,transportaions of machinary and other incidental charges etc., complete for finished item of work and as per ss and as adirected by the departmental officer in charge of work. For the following the depths h) 13.85m to 14.85m depth | 1 | Rmt | 3,83,502.84 ₹3.8 L | 4,37,194 ₹4.4 L | 4,14,183 ₹4.1 L | 3,42,436 ₹3.4 L |
Updated dates
Tender Value
Refer Docs
EMD Value
₹3.9 Cr
Closing Date
23 Oct 2025, 5:00 pmClosed
Superintending Engineer
Superintending Engineer, Public Health circle, Reservoirs Compound, Gorakshana Peta,
Andhra Pradesh Urban Water Supply and Septage Management Improvement Project
2025_MAUD_877316_2
IFB (SPN)No,665/AIIB/TS-ATO/2025 Dated 10.09.2025
Open Tender
Civil Works - Water Works
730 days
East and West Godavari Districts
Please refer Tender documents.
8 documents required · 8 mandatory
₹0
₹3.9 Cr
Yes
O/O Engineer-in-Chief, PH
30 Jan 2026
13 Sept 2025
27 Oct 2025
13 Sept 2025
23 Oct 2025
13 Sept 2025
19 Sept 2025
KOVVUR MUNICIPALITY
Construction of Raw Water Intake Well in River Godavari down stream side of 4th bridge
Well sinking for construction of 8.0m dia Raw Water Intake well in sandy and other loose soils under water either by manual sinkers and labour, divers, or dredgers, weighing the top of steining to assist sinking etc.,. This rate including cost of all labour charges, dewatering, hiring of machinery, fuel charges, wages of driver ,transportaions of machinary and other incidental charges etc., complete for finished item of work and as per ss and as adirected by the departmental officer in charge of work. For the following the depths a) Up to 2.00m depth
Well sinking for construction of 8.0m dia Raw Water Intake well in sandy and other loose soils under water either by manual sinkers and labour, divers, or dredgers, weighing the top of steining to assist sinking etc.,. This rate including cost of all labour charges, dewatering, hiring of machinery, fuel charges, wages of driver ,transportaions of machinary and other incidental charges etc., complete for finished item of work and as per ss and as adirected by the departmental officer in charge of work. For the following the depths b) 2.00m to 4.00m depth
Well sinking for construction of 8.0m dia Raw Water Intake well in sandy and other loose soils under water either by manual sinkers and labour, divers, or dredgers, weighing the top of steining to assist sinking etc.,. This rate including cost of all labour charges, dewatering, hiring of machinery, fuel charges, wages of driver ,transportaions of machinary and other incidental charges etc., complete for finished item of work and as per ss and as adirected by the departmental officer in charge of work. For the following the depths c) 4.00m to 6.00m depth
Well sinking for construction of 8.0m dia Raw Water Intake well in sandy and other loose soils under water either by manual sinkers and labour, divers, or dredgers, weighing the top of steining to assist sinking etc.,. This rate including cost of all labour charges, dewatering, hiring of machinery, fuel charges, wages of driver ,transportaions of machinary and other incidental charges etc., complete for finished item of work and as per ss and as adirected by the departmental officer in charge of work. For the following the depths d) 6.00m to 8.00m depth
Well sinking for construction of 8.0m dia Raw Water Intake well in sandy and other loose soils under water either by manual sinkers and labour, divers, or dredgers, weighing the top of steining to assist sinking etc.,. This rate including cost of all labour charges, dewatering, hiring of machinery, fuel charges, wages of driver ,transportaions of machinary and other incidental charges etc., complete for finished item of work and as per ss and as adirected by the departmental officer in charge of work. For the following the depths e) 8.00m to 10.00m depth
Well sinking for construction of 8.0m dia Raw Water Intake well in sandy and other loose soils under water either by manual sinkers and labour, divers, or dredgers, weighing the top of steining to assist sinking etc.,. This rate including cost of all labour charges, dewatering, hiring of machinery, fuel charges, wages of driver ,transportaions of machinary and other incidental charges etc., complete for finished item of work and as per ss and as adirected by the departmental officer in charge of work. For the following the depths f) 10.00m to 12.85m depth
Well sinking for construction of 8.0m dia Raw Water Intake well in sandy and other loose soils under water either by manual sinkers and labour, divers, or dredgers, weighing the top of steining to assist sinking etc.,. This rate including cost of all labour charges, dewatering, hiring of machinery, fuel charges, wages of driver ,transportaions of machinary and other incidental charges etc., complete for finished item of work and as per ss and as adirected by the departmental officer in charge of work. For the following the depths g) 12.85.00m to 13.85m depth
Well sinking for construction of 8.0m dia Raw Water Intake well in sandy and other loose soils under water either by manual sinkers and labour, divers, or dredgers, weighing the top of steining to assist sinking etc.,. This rate including cost of all labour charges, dewatering, hiring of machinery, fuel charges, wages of driver ,transportaions of machinary and other incidental charges etc., complete for finished item of work and as per ss and as adirected by the departmental officer in charge of work. For the following the depths h) 13.85m to 14.85m depth
Well sinking for construction of 8.0m dia Raw Water Intake well in sandy and other loose soils under water either by manual sinkers and labour, divers, or dredgers, weighing the top of steining to assist sinking etc.,. This rate including cost of all labour charges, dewatering, hiring of machinery, fuel charges, wages of driver ,transportaions of machinary and other incidental charges etc., complete for finished item of work and as per ss and as adirected by the departmental officer in charge of work. For the following the depths i) 14.85m to 15.85m depth
Well sinking for construction of 8.0m dia Raw Water Intake well in sandy and other loose soils under water either by manual sinkers and labour, divers, or dredgers, weighing the top of steining to assist sinking etc.,. This rate including cost of all labour charges, dewatering, hiring of machinery, fuel charges, wages of driver ,transportaions of machinary and other incidental charges etc., complete for finished item of work and as per ss and as adirected by the departmental officer in charge of work. For the following the depths j) 15.85m to 16.85m depth
Well sinking for construction of 8.0m dia Raw Water Intake well in sandy and other loose soils under water either by manual sinkers and labour, divers, or dredgers, weighing the top of steining to assist sinking etc.,. This rate including cost of all labour charges, dewatering, hiring of machinery, fuel charges, wages of driver ,transportaions of machinary and other incidental charges etc., complete for finished item of work and as per ss and as adirected by the departmental officer in charge of work. For the following the depths k) 16.85m to 17.85m depth
Well sinking for construction of 8.0m dia Raw Water Intake well in sandy and other loose soils under water either by manual sinkers and labour, divers, or dredgers, weighing the top of steining to assist sinking etc.,. This rate including cost of all labour charges, dewatering, hiring of machinery, fuel charges, wages of driver ,transportaions of machinary and other incidental charges etc., complete for finished item of work and as per ss and as adirected by the departmental officer in charge of work. For the following the depths l) 17.85m to 18.85m depth
Well sinking for construction of 8.0m dia Raw Water Intake well in sandy and other loose soils under water either by manual sinkers and labour, divers, or dredgers, weighing the top of steining to assist sinking etc.,. This rate including cost of all labour charges, dewatering, hiring of machinery, fuel charges, wages of driver ,transportaions of machinary and other incidental charges etc., complete for finished item of work and as per ss and as adirected by the departmental officer in charge of work. For the following the depths m) 18.85m to 19.85m depth
Well sinking for construction of 8.0m dia Raw Water Intake well in sandy and other loose soils under water either by manual sinkers and labour, divers, or dredgers, weighing the top of steining to assist sinking etc.,. This rate including cost of all labour charges, dewatering, hiring of machinery, fuel charges, wages of driver ,transportaions of machinary and other incidental charges etc., complete for finished item of work and as per ss and as adirected by the departmental officer in charge of work. For the following the depths n) 19.85m to 20.85m depth
Well sinking for construction of 8.0m dia Raw Water Intake well in sandy and other loose soils under water either by manual sinkers and labour, divers, or dredgers, weighing the top of steining to assist sinking etc.,. This rate including cost of all labour charges, dewatering, hiring of machinery, fuel charges, wages of driver ,transportaions of machinary and other incidental charges etc., complete for finished item of work and as per ss and as adirected by the departmental officer in charge of work. For the following the depths o) 20.85m to 21.70m depth
Providing C.C.mix (M15 grade) for well bottam Plugging from approved quarries by using 20mm graded HBG machine crushed metal. This rate including cost & conveyance of all materials, all labour charges for machine mixing, laying, vibrating, centering, tamping delifting upto 26 mts depth under water and curing including all delifts other incidental charges etc., complete as per S.S and as directed by the departmental officer in charges of work. For 8..00m dia Intake well
Providing VRCC M30 Grade Design Concrete Mix corresponding to IS 456 using MIXER with 20mm size graded machine crushed hard granite metal (coarse aggregate) from approved quarry. including cost and conveyance of all materials like cement, fine aggregate (sand) coarse aggregate, water etc., to site including all operational, incidental and labour charges such as , machine mixing, laying concrete, curing with cement content 400Kgs/Cum as per I.S code from standard suppliers approved by the department including centering, shuttering, seaffolding laying concrete, vibrating, curing etc. complete with all de-lift for 8.00mm dia intake wall in river godavari charges but excluding cost of steel and its fabrication charges for finished item of work (APSS No. 402)and as directed the departmental officer in charge of work as follows a) for Base slab & Plugging
Providing VRCC M30 Grade Design Concrete Mix corresponding to IS 456 using MIXER with 20mm size graded machine crushed hard granite metal (coarse aggregate) from approved quarry. including cost and conveyance of all materials like cement, fine aggregate (sand) coarse aggregate, water etc., to site including all operational, incidental and labour charges such as , machine mixing, laying concrete, curing with cement content 400Kgs/Cum as per I.S code from standard suppliers approved by the department including centering, shuttering, laying concrete, vibrating, curing etc. complete with all de-lift charges but excluding cost of steel and its fabrication charges for finished item of work (APSS No. 402)and as directed the departmental officer in charge of work b) for Well Curb 0.30m thick
Providing VRCC M30 Grade Design Concrete Mix corresponding to IS 456 using MIXER with 20mm size graded machine crushed hard granite metal (coarse aggregate) from approved quarry. including cost and conveyance of all materials like cement, fine aggregate (sand) coarse aggregate, water etc., to site including all operational, incidental and labour charges such as , machine mixing, laying concrete, curing with cement content 400Kgs/Cum as per I.S code from standard suppliers approved by the department including centering, shuttering, laying concrete, vibrating, curing etc. complete with all de-lift charges but excluding cost of steel and its fabrication charges for finished item of work (APSS No. 402)and as directed the departmental officer in charge of work c) for Side walls (Well Steining) (Side Wall of the Well of 0.75m thick upto Normal water level+0.50m +19.70m(-)+0.00m)
Providing VRCC M30 Grade Design Concrete Mix corresponding to IS 456 using MIXER with 20mm size graded machine crushed hard granite metal (coarse aggregate) from approved quarry. including cost and conveyance of all materials like cement, fine aggregate (sand) coarse aggregate, water etc., to site including all operational, incidental and labour charges such as , machine mixing, laying concrete, curing with cement content 400Kgs/Cum as per I.S code from standard suppliers approved by the department including centering, shuttering, laying concrete, vibrating, curing etc. complete with all de-lift charges but excluding cost of steel and its fabrication charges for finished item of work (APSS No. 402)and as directed the departmental officer in charge of work c) for Side walls (Well Steining) Side Wall of the Well of 0.50m thick upto bottom of floor slab to Normal water level + 22.70m to +19.70m=3.00m
Providing VRCC M30 Grade Design Concrete Mix corresponding to IS 456 using MIXER with 20mm size graded machine crushed hard granite metal (coarse aggregate) from approved quarry. including cost and conveyance of all materials like cement, fine aggregate (sand) coarse aggregate, water etc., to site including all operational, incidental and labour charges such as , machine mixing, laying concrete, curing with cement content 400Kgs/Cum as per I.S code from standard suppliers approved by the department including centering, shuttering, laying concrete, vibrating, curing etc. complete with all de-lift charges but excluding cost of steel and its fabrication charges for finished item of work (APSS No. 402)and as directed the departmental officer in charge of work c) for Side walls (Well Steining) Side Wall of the Well of 0.50m thick upto bottom of floor slab to Normal water level + 23.70m to +22.70m=1.00m
Providing VRCC M30 Grade Design Concrete Mix corresponding to IS 456 using MIXER with 20mm size graded machine crushed hard granite metal (coarse aggregate) from approved quarry. including cost and conveyance of all materials like cement, fine aggregate (sand) coarse aggregate, water etc., to site including all operational, incidental and labour charges such as , machine mixing, laying concrete, curing with cement content 400Kgs/Cum as per I.S code from standard suppliers approved by the department including centering, shuttering, laying concrete, vibrating, curing etc. complete with all de-lift charges but excluding cost of steel and its fabrication charges for finished item of work (APSS No. 402)and as directed the departmental officer in charge of work c) for Side walls (Well Steining) Side Wall of the Well of 0.50m thick upto bottom of floor slab to Normal water level + 24.70m to +23.70m=1.00m
Providing VRCC M30 Grade Design Concrete Mix corresponding to IS 456 using MIXER with 20mm size graded machine crushed hard granite metal (coarse aggregate) from approved quarry. including cost and conveyance of all materials like cement, fine aggregate (sand) coarse aggregate, water etc., to site including all operational, incidental and labour charges such as , machine mixing, laying concrete, curing with cement content 400Kgs/Cum as per I.S code from standard suppliers approved by the department including centering, shuttering, laying concrete, vibrating, curing etc. complete with all de-lift charges but excluding cost of steel and its fabrication charges for finished item of work (APSS No. 402)and as directed the departmental officer in charge of work c) for Side walls (Well Steining) Side Wall of the Well of 0.50m thick upto bottom of floor slab to Normal water level + 25.685m to +24.70m=0.985m
Providing VRCC M30 Grade Design Concrete Mix corresponding to IS 456 using MIXER with 20mm size graded machine crushed hard granite metal (coarse aggregate) from approved quarry. including cost and conveyance of all materials like cement, fine aggregate (sand) coarse aggregate, water etc., to site including all operational, incidental and labour charges such as , machine mixing, laying concrete, curing with cement content 400Kgs/Cum as per I.S code from standard suppliers approved by the department including centering, shuttering, laying concrete, vibrating, curing etc. complete with all de-lift charges but excluding cost of steel and its fabrication charges for finished item of work (APSS No. 402)and as directed the departmental officer in charge of work platform for placing Sluice Valves
Providing VRCC M30 Grade Design Concrete Mix corresponding to IS 456 using MIXER with 20mm size graded machine crushed hard granite metal (coarse aggregate) from approved quarry including cost and conveyance of all materials like cement, fine aggregate (sand) coarse aggregate, water etc., to site and including all operational, incidental and labour charges such as weigh batching, machine mixing, laying concrete, curing with cement content 400Kgs/Cum as per I.S code from standard suppliers approved by the department including centering, shuttering, Seaffolding, other incidental charges laying concrete, vibrating, curing etc. complete but excluding cost of steel and its fabrication charges for finished item of work (APSS No. 402) as directed by the departmental officer in charge of work as follows a) for Pump house Columns
Providing VRCC M30 Grade Design Concrete Mix corresponding to IS 456 using MIXER with 20mm size graded machine crushed hard granite metal (coarse aggregate) from approved quarry including cost and conveyance of all materials like cement, fine aggregate (sand) coarse aggregate, water etc., to site and including all operational, incidental and labour charges such as weigh batching, machine mixing, laying concrete, curing with cement content 400Kgs/Cum as per I.S code from standard suppliers approved by the department including centering, shuttering, laying concrete, vibrating, curing etc. complete but excluding cost of steel and its fabrication charges for finished item of work (APSS No. 402) as directed by the departmental officer in charge of work b) for floor beams
Providing VRCC M30 Grade Design Concrete Mix corresponding to IS 456 using MIXER with 20mm size graded machine crushed hard granite metal (coarse aggregate) from approved quarry including cost and conveyance of all materials like cement, fine aggregate (sand) coarse aggregate, water etc., to site and including all operational, incidental and labour charges such as weigh batching, machine mixing, laying concrete, curing with cement content 400Kgs/Cum as per I.S code from standard suppliers approved by the department including centering, shuttering, laying concrete, vibrating, curing etc. complete but excluding cost of steel and its fabrication charges for finished item of work (APSS No. 402) as directed by the departmental officer in charge of work c) for Floor Slab 0.30m thick with allrouns walk way
Providing VRCC M30 Grade Design Concrete Mix corresponding to IS 456 using MIXER with 20mm size graded machine crushed hard granite metal (coarse aggregate) from approved quarry including cost and conveyance of all materials like cement, fine aggregate (sand) coarse aggregate, water etc., to site and including all operational, incidental and labour charges such as weigh batching, machine mixing, laying concrete, curing with cement content 400Kgs/Cum as per I.S code from standard suppliers approved by the department including centering, shuttering, laying concrete, vibrating, curing etc. complete but excluding cost of steel and its fabrication charges for finished item of work (APSS No. 402) as directed by the departmental officer in charge of work d) ring Beams at lintel level
Providing VRCC M30 Grade Design Concrete Mix corresponding to IS 456 using MIXER with 20mm size graded machine crushed hard granite metal (coarse aggregate) from approved quarry including cost and conveyance of all materials like cement, fine aggregate (sand) coarse aggregate, water etc., to site and including all operational, incidental and labour charges such as weigh batching, machine mixing, laying concrete, curing with cement content 400Kgs/Cum as per I.S code from standard suppliers approved by the department including centering, shuttering, laying concrete, vibrating, curing etc. complete but excluding cost of steel and its fabrication charges for finished item of work (APSS No. 402) as directed by the departmental officer in charge of work e) for Roof Beams
Providing VRCC M30 Grade Design Concrete Mix corresponding to IS 456 using MIXER with 20mm size graded machine crushed hard granite metal (coarse aggregate) from approved quarry including cost and conveyance of all materials like cement, fine aggregate (sand) coarse aggregate, water etc., to site and including all operational, incidental and labour charges such as weigh batching, machine mixing, laying concrete, curing with cement content 400Kgs/Cum as per I.S code from standard suppliers approved by the department including centering, shuttering, laying concrete, vibrating, curing etc. complete but excluding cost of steel and its fabrication charges for finished item of work (APSS No. 402) as directed by the departmental officer in charge of work f) for Roof slab 0.15m thick with slab extension 0.30m
Providing VRCC M30 Grade Design Concrete Mix corresponding to IS 456 using MIXER with 20mm size graded machine crushed hard granite metal (coarse aggregate) from approved quarry including cost and conveyance of all materials like cement, fine aggregate (sand) coarse aggregate, water etc., to site and including all operational, incidental and labour charges such as weigh batching, machine mixing, laying concrete, curing with cement content 400Kgs/Cum as per I.S code from standard suppliers approved by the department including centering, shuttering, laying concrete, vibrating, curing etc. complete but excluding cost of steel and its fabrication charges for finished item of work (APSS No. 402) as directed by the departmental officer in charge of work g) for Sunshade
Brick masonary in CM (1:6) using 2nd class bricks of size 23 x 11 x 7cms. Cost including cost and conveyance of all materials at site, labour charges for curing , scaffolding, all lifts, seaffolding other incidental charges etc.,Complete as per SS and as directed by the departmental officer incharge of work.For Construction of Pumphouse. Suerstructure.
Brick masonary in CM (1:6) using 2nd class bricks of size 23 x 11 x 7cms. Cost including cost and conveyance of all materials at site, labour charges for curing , scaffolding, all lifts, seaffolding other incidental charges etc.,Complete as per SS and as directed by the departmental officer incharge of work.For Construction of Pumphouse. parapet wall and supporting pilled
Supply and fixing of 50mm thick pre-cast Cement Jollys of approved design including cost and conveyance to work spot and all labour charges for fixing in position etc.complete as per S.S and as directed by the departmental officer in charge of work for pump house
Plastering with CM (1:4) 12mm thick including cost and conveyance of all materials at site labour charges for finishing and curing scaffolding, lifting, smooth,finishing,other incidental charges etc., complete as per S.S as per ss and as directed by the departmental officer in charge of work. For the Pump house inside.and outside
Plastering with CM (1:4) 12mm thick including cost and conveyance of all materials at site labour charges for finishing and curing scafoolding, lifting, smooth,finishing,other incidental charges etc., complete as per S.S as per ss and as directed by the departmental officer in charge of work. For the Pump house inside.paropet wall and supporting pillers
Providing impervious coat to exposed RCC roof slab surface with CM(1:3), 20mm thick with 1kg of water proof compound per bag of cement laid over roof when it is green including cost of all materials, including conveyance charges of materials and including all operational, incidental and labour charges for mixing mortar, laying, rendering smooth and thread lining, curing, rounding off junctions of wall and slab etc,, complete for finished item of work for pumphouse
Plastering with CM (1:3) 12mm thick for ceiling including cost and conveyance of all materials at site, and labour charges for mixing of mortar, plastering and curing scaffolding , lifting,smooth finishings etc., complete as per S.S and as directed by the departmental departmental officer incharge of work. For pump house ceiling
Painting Walls with Snowcem or other equal and approved Water Proof Cement Paint 2 Coats (All Colours) over a base coat of aproved cement primer making 3 coats in total including cost of all materials all labour charges, conveyance charges of materials and other incidental charges, scaffolding, lifting and as directed by the departmental officer in charge of work. For Pump house
Manufacture,supply,delivery of MS grill gates,window ornamental safety grill ,made with MS flats,MS angles,MS squares etc including welding,finishing, transportation , site finish,fabrication and erection charges, and other incidental charge etc., complete as per ss and as directed by the departmental officer in charge of work.for pumphouse windows
Painting two coats with synthetic enamel paint 1st quality over a base coat of red oxide. The rate includeds cost and conveyance of all materilas at site, labour charges, scaffolding charges lifting,cost of brushes, other incidental charges etc., complete as directed by the departmental authorities (APDSS No:1201) For Rolling shuttering in pump house.
Supply & fixing of Rolling shutter made of 80 x 1.25 mm machine rolled CRCA laths, interlocked together through their entire length and jointed together at the ends by end-locks, mounted on specially designed pipe shaft of 50mm dia nominal bore MS B class pipe with brackets, plates, guide channels, stoppers, bottom locking plates and arrangements for inside & outside locking with push-pull operations including cost of hood cover and springs complete, painted with one coat of approved steel primer, locks, ball bearings, all accessories etc complete for finished item of work as per special spn: 1108 and other incidental charges etc., complete as directed by the departmental offincer in charge of work
Supply and fixing Aluminium Anodised Two/ Three Track Sliding Windows of size 1.35 mts x 1.20 mts as per approved drawing with aluminium anodised sections of Series C Jindal sections and outer frame top horizontals & both verticals of 8774 of size 62 x 29.5 mm and bottom horizontal - two track frame of 8773 of size 62 x 29.5 mm, Shutter frame top, bottom and verticals of 8304 of size 50 mm x 20 mm and Weather interlocking frame of 8306 of size 50 x 20 with plain clear float glass 5 mm thick fixed including supply and fixing aluminium handles of 100 mm for each shutter, nylon rollers assembly and all labour charges for fixing the fixtures with required no.of screws, bolts and nuts and including labour charges for fixing the frame in position, fixing shutter to frame other incidental charge and etc. completed for finished item of work
Supply, delivery, fabrication and erection of Cutting toe for Well curb with ISA 150x150x12mm including cost and conveyance to work spot including all labour charges for fabrication and erection hire charges of machine, sitewelding charges, and other incidental charge etc.,complete etc.,complete as directed by the departmental authorities.For well curb.
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 500/500D grade) of different diameters for RCC works, including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying including and other all materials etc., complete for finished item of work in all floors. as per SS and as directed by the departmental office incharge of work.
Supply and delivery of 350mm dia PN 1.6 "Resilient Seated Soft Sealing" Gate Valves (Sluice Valves) with Body and Bonnet of Ductile Iron GGG-40/SG-400/15 or GGG-50/SG-500/7 or Equivalent as per IS1865,IS:3896-2 and Wedge fully Rubber Lined with food grade quality grade W270 grade EPDM, Replaceable Spindle Nut without gland packing with 3-O ring protection system on the Shaft and Seals of NBR. The Valves should be Vacuum tight and 100% leak proof with face to face dimensions as BS:5163 Type A/IS:14846. All the valves should be with fusion bonded Electrostatic Powder coating both inside and outside (Min 250 Microns)- RAL 5005 with Pocket Less Straight through body Passage conforming to Design standards of DIN-3202F4/BS:5163 Type A Flange drilling as per IS - 1538 including and transportation. PN1.6. other incidental charges as per ss and as dirceted by the departmental officer in charge of work.
Labour charges for lowering and keeping in position of 350mm dia D.I. Sluice valves(with cap/with hand wheel), reflux valves and scour valves. This rate including cost of all labour charges , cost of bolts , nuts.rubber packing ,and other incidental charge s etc., complete per ss and as directed by the departmental officer in charge of work.
Centrifugally cast (Spun) Ductile Iron 350mm dia 2.00 m long DI D/F pressure pipes with flanged (welded) ends for water, gas, sewage conforming to IS: 8329/2000 in standard working lengths of 1,2,3, 4, 5 mts for classification K9 with cement mortar lining inside the pipes with outside zinc coating, including transportation other incidental charge etc., complete per ss and as directed by the departmental officer in charge of work.
Supply and delivery of Centrifugally cast (spun) up to 350mm dia Ductile Iron Fittings of DI double socket branch flange Tee, DI All Socket Tees, DI Double socket Tapers (Reducer), DI Flanged Socket, DI Flanged Spigot, DI Double Socket Duck Foot Bend, DI Double Flange Duck/Foot bend, DI All socket Cross, DI All Flange Tee, DI All Flange Cross, DI Double Flange Reducer, Blank Flange, Mechanical Joints, DI Double Socket Bends, DI Double Flanged Bends and DI Manhole Frame & cover conforming to IS:9523/2000 having dimensions Up to 500 x 500 mm dia. The rates mentioned here under are for fittings, zinc coated externally with inside mortar lining (with finishing as per class 13/IS 9523/2000) including Transportation and . as directed by the departmental officer incharge of work.
Lowering the 350mm dia D.I. Pipes of all classes and fittings with flanged ends carefully into the trenches and laying them true to alignment and gradient including all sundries,conveyance from source of supply as per BIS No.3114/94.This rate including all labour charges hiring of machinary , fuel charges and other incidental charge as per ss and as directed by the departmental officer in charge of work
Jointing the 350 mm dia D.I. Pipes, fittings and valves with flanged ends including cost of jointing materials such as bolts, nuts, rubber insertion, white lead and including filling with water with a water lead upto 500 m and testing to required pressure etc., comp as per BIS No.3114/85 and as directed by the departmental officer in charge of work.
Supply and delivery ss 304 grade operating handle with rod & wheel for operatn at site of work ion of D.I. Sluice valve inside the intake well as per the actuals and this rate including cost of ss 304 , fabrication charges, erection at site of work cost of welding charges and other incidental charges etc., complete as per ss and as directed by the departmental officer in charge of work.
Supply, delivery and erection of 5 tonnes capacity double girder gantry arrangements to move and lift the installations of the pump house one way with required MS ISMB of best quality 250 x 100 mm of standard make, including the required MS ISMC, MS angular iron, 5 tonne capacity travelling trolley and 5 tonne capacity chain pulley block with chains of suitable capacity for lifting and moving arrangements to length of 10.00 m rate is inclusive of the cost of materials, labour charges, site welding etc.,complete as per ss and as direceted by the departmental officer incharge of work
Supply and delivery ss 304 grade operating Steel Ladder inside the intake well as per the actuals and this rate including cost of ss 304 , fabrication charges, erection at site of work cost of welding charges and other incidental charges etc., complete as per ss and as directed by the departmental officer in charge of work.
Supply and fixing of 25 mm dia 2.00 mm thick PVC pipe concealed in roof slab with all required accessories including masonary work all labour chages complete with as per approved makes as per IE Rules and as directed by the departmental officer incharge of work
Supply and fixing of 20 mm dia 1.50 mm thick PVC pipe concealed in walls with all required accessories including masonary work for light , fan and plug point with metal deep box including all labour chages complete as per IE Rules and approved makes and as directed by the departmental officer incharge of work
Wiring with 2 runs 14/0.3 mm. (1.0. sq.mm) Fire retardant PVC insulated Flexible copper cable in existing pipe with 6A siwtch, ceiling rose and 3 mm thick hyla sheet covering to switch control box including all labour charges etc,., complet for light, bell , fan and exhaust fan points in non - residential building complete as per IE Rules and as directed by the departmental officer incharge of work
Wiring with 2 runs 14/0.3 mm. (1.0. sq.mm) Fire retardant PVC insulated Flexible copper cable in existing pipe with 6A modular siwtch control and 3/2 pin sockets fixing on board including all labour charges complete and approved makes as per IE Rules and as directed by the departmental officer incharge of work
supply and run of 2 of 36/0.3 mm. (1.5. sq.mm) Fire retardant PVC insulated Flexible copper cable in existing pipe for mains including all labour charges complete as per IE Rules and as per approved brands as directed by the departmental officer incharge of work
supply and run of 1 of 14/0.3 mm. (1.0. sq.mm) Fire retardant PVC insulated Flexible copper cable in existing pipe for earth continuity including all labour charges cost of materials, other incidental charges etc complete as per apprved brand and as directed by the departmental officer incharge of work.
supply and run of 2 of 6 sq.mm (7/18) WPSC alluminium cable along with No.10 SWG G.I barer wire through PVC cleats with all accessories including all labour charges cost of all aterials other incidetal charge etc.,complete as per IE Rules and as directed by the departmental officer incharge of work
Providing independent earthing by excavating a trench to a depth of 2.10m in all soils, as per size specied in data ,using 40 mm dia B class GI pipe 2.50m long with necessary accessories with hume pipe ring duly providing staggered holes including filling with equal proportion of salt and charcoal in layers and all labour charges etc complete as per IE Rules and as directed by the departmental officer incharge of work
Supply and fixing SPN Distribution board with IP-20 protection suitable for single phase Earth Leakage Circute Braker (ELCB) / Residual Current Circute Braker (RCCB) / Double Pole (DP) Isolator as incomer and 10kA SP MCBs as out going including internal connections and labour charges for surface / flush mounting etc., complete as per IE Rules approved brand and as directed by the departmental officer incharge of work
Supply of 48" (1200mm) Sweep 5 star rated Ceiling Fan , with double ball bearings, air delivery more than 200 cubic meter/min but without Regulator.Makes : Crompton HS Plus / Havells ES Neo/Orient Energy Star/ Halonix(Zephyr)/Polycab(Synergy Star) unit each complete as per IE Rules and as directed by the departmental officer incharge of work
Supply of stepped type Electronic Regulator of Makes: GM G Home / Gold Medal Olive / Million Zoom / Great white Omega/Koncept/Vimal opel/ Anchor/Vihan/CPL complete as per IE Rules and as directed by the departmental officer incharge of work
Supply of 9" (225mm), Light duty exhaust fan with double ball bearing and wire guard etc complete. Makes: Crompton / Bajaj Bahar WG / Havells Ventil Air-DS / Orient hill air / MIIT complete as per IE Rules and as directed by the departmental officer incharge of work
Supply of 20 W Box type tube light luminaire powder coated CRCA sheet steel housing with Electronic Ballast Chokes and all standard accessoriesof makes Wipro / G.E. / Phillips / Crompton / Bajaj. complete as per IE Rules and as directed by the departmental officer incharge of work
Providing temporory Island for preparation platform for sinking of Intake well of 20m dia island and 6.50m height
Providing and construction of Temporary island of 20.00m. Diameter and 11 metres height for preparation of platform etc.with laying of sand bags in the stipulated places including cost of empty cement bag, sand thread, stiching charges and labour charges . During the emergency conditions such as floods .and other natural calamities, the above rate is allowed to enhance by 25% for 1st warning level and above, keeping in view of the difficulty in availability of labour and vehicles for ring bund by using crane with grap, consumbles, wooden ballies shutable dia and shutable height and braceings, for construction of 8.00m dia Raw water intake well in River in Godavari near Bridge. This rate including cost of all materials,all labour charges conveyance charges and all operational, incidental and labour charges etc., complete for finished item of work and as per ss and as adirected by the departmental officer in charge of work.
Formation of bund/approach ramp for Temporary Island with Gravel from approved quarry including cost of gravel and conveyance of all materials and labour charges for formation of filling, raming,sectining,including supporting the sides for water flow etc., Complegte for approch ram from bund to intake well at bridge to Godavari river .This rate including cost of all materials,all labour charges conveyance charges and all operational,other incidental and labour charges etc., complete for finished item of work and as per ss and as adirected by the departmental officer in charge of work.
Construction of Approch Bridge for Intake well in Godavari River
Earthwork in excavation for Bridge as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH and as directed by the departmental officer in charge of work. Service Bridge as follows - Manual Means upto 3 metres depth in ordinary soil
Earthwork in excavation for Bridge as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH and as directed by the departmental officer in charge of work. Service Bridge as follows - Mechanical Means above 3 metres depth in Ordinary Soil
Filling Sand for foundation for service bridge as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH.This rate including cost of sand ,filling charges,watering,ramming,and other incidental charges etc., complete as per ss and directed by the departmental officer incharge of work for column footing
Plain Cement Concrete (1:4:8) (cement: fine aggregate: Coarse aggregate) using coarse aggregate 40mm size hard, machine crushed granite from approved quarry using concrete Mixer 10 / 7 cft (0.2 / 0.8 cum) capacity including cost and conveyance of all materials like cement, sand, coarse aggregate, water etc. to site including all charges for machine mixing and hire charges of concrete mixer, laying concrete finishing top surface to the required level curing etc., and complete for finished item of work as per SS and as directed by the departmental officer incharge of work. (APSS No. 402)for Piles caps bed
Providing VRCC M30 Grade Design Concrete Mix corresponding to IS 456 using MIXER with 20mm size graded machine crushed hard granite metal (coarse aggregate) from approved quarry including cost and conveyance of all materials like cement, fine aggregate (sand) coarse aggregate, water etc., to site and including including all operational, incidental and labour charges such as, machine mixing, laying concrete, seaffolding, curing with cement content 400Kgs/Cum as per I.S code from standard suppliers approved by the department including concreting of piles by tremie concrete method etc. complete with all de-lift charges but excluding cost of steel and its fabrication charges for finished item of work (APSS No. 402) as directed by the departmental officer in charge of work as follows. For pile concrete. (For Footings)
Providing VRCC M30 Grade Design Concrete Mix corresponding to IS 456 using MIXER with 20mm size graded machine crushed hard granite metal (coarse aggregate) from approved quarry including cost and conveyance of all materials like cement, fine aggregate (sand) coarse aggregate, water etc., to site and including including all operational, incidental and labour charges such as, machine mixing, laying concrete, curing with cement content 400Kgs/Cum as per I.S code from standard suppliers approved by the department including concreting of piles by tremie concrete method etc. complete with all de-lift charges but excluding cost of steel and its fabrication charges for finished item of work (APSS No. 402) as directed by the departmental officer in charge of work. For pile concrete. (For Columns)
Providing VRCC M30 Grade Design Concrete Mix corresponding to IS 456 using MIXER with 20mm size graded machine crushed hard granite metal (coarse aggregate) from approved quarry including cost and conveyance of all materials like cement, fine aggregate (sand) coarse aggregate, water etc., to site and including including all operational, incidental and labour charges such as, machine mixing, laying concrete, curing with cement content 400Kgs/Cum as per I.S code from standard suppliers approved by the department including concreting of piles by tremie concrete method etc. complete with all de-lift charges but excluding cost of steel and its fabrication charges for finished item of work (APSS No. 402) as directed by the departmental officer in charge of work. For pile concrete. (For Carriage Slab Beams)
Providing VRCC M30 Grade Design Concrete Mix corresponding to IS 456 using MIXER with 20mm size graded machine crushed hard granite metal (coarse aggregate) from approved quarry including cost and conveyance of all materials like cement, fine aggregate (sand) coarse aggregate, water etc., to site and including including all operational, incidental and labour charges such as, machine mixing, laying concrete, curing with cement content 400Kgs/Cum as per I.S code from standard suppliers approved by the department including concreting of piles by tremie concrete method etc. complete with all de-lift charges but excluding cost of steel and its fabrication charges for finished item of work (APSS No. 402) as directed by the departmental officer in charge of work. For pile concrete. (For Carriage Slab 0.30m thick)
Construction of R.C.C. railing of M 25 grade in cast-in-situ with 20 mm nominal size aggregate, true to line and grade, tolerance of vertical railing post not to exceed 1 in 500, centre-to-centre spacing between vertical posts not to exceed 2000 mm as per drawing and technical specifications Clauses 800, 900 and 1208.3 MORD. This rate including cost of material, all lanbour charges, scaffolding charge , vibrating, watering, centering, transporations, hand rail in 3stires as per approved secification including HYSD bar reinforcement as par ss and as directed by the departmental officer in charge of work.
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 500/500D grade) of different diameters for RCC works, including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying including and other all materials etc., complete for finished item of work in all floors. as per SS and as directed by the departmental office incharge of work.
Painting Walls with Snowcem or other equal and approved Water Proof Cement Paint 2 Coats (All Colours) over a base coat of aproved cement primer making 3 coats in total including cost of all , conveyance charges of materials and other incidental charges, scaffolding, lifting all labour charges, cost of materials and as directed by the departmental officer in charge of work. For Pump house
Supply and erection of 2#of 29.84 Kw(40 HP) of VT Pumpsets Each with a duty of 98 LPS and a total head of 21 m (one working and one stand bye) for pumping Raw water from intake well to Aerator of Proposed WTP
Supply and erection of 2#of 29.84 Kw(40 HP) of VT Pumpsets Each with a duty of 98 LPS and a total head of 21 m (one working and one stand bye) for pumping Raw water from intake well to Aerator of Proposed WTP
Supply, delivery and erection of Raw Water Vertical Turbine Pump sets including all Suction, Delivery Connections, Panel Board etc., Complete Supply, delivery, erection and commissioning of reputed make Energy Efficiency as per BEE Vertical Turbine Pumpsets 3 No Capable of Discharging 5340 LPM gainst a head of 20.00 Mts, with 50% standby and suitable capacity Vertical squirrel cage induction motor suitable for operation on 415 V +/- 10%, 50Hz +/- 5%, (Vertical solid shaft) of reputed make.(15% Overloading on BKW) including all taxes but excluding GST.Suitbale size Columns & Colum assembly length including bowl assemble, MOC for VT pump, Bell Mouth / Bowl CI - IS 210, Impeller / CF8M - Shafts - SS 410, Pipe / M tool - MS IS 2062 as approved by DepartmentSupply, delivery, erection and commissioning of control panel board with suitable capacity bus bar suitable to operate above 3 Nos of pump sets. The panel board is made of 16 gauge MS sheet metal cubical/industrial indoor type and duly painted with 2 coats of enamel paint. a. Incoming MCCB – 1 nob. FCMA Soft Starters.- 3 nosc. Shunt capacitor with MCB - 3 nosd. 315 A TPN SFU for starter o/g – 3 nosf. ASS – 1 noe. VSS – 1 nog. Ammeters for motors – 3 nosh. Spare TPN SFU – 1 noi. Phase indicating lamps – 3 nosj. ON/OFF push buttons with bulbs - 6nos Supply, delivery, erection and commissioning of Incoming Alluminium armoured cable from transformer to Control panel board.
Supply, delivery, erection and commissioning of alluminium armoured cable from panel board to starters and to motor.Supply and errection of suitable diamer and length 10 mm thick MS Manifold as approved by the Department (Dia should not be less than 1.5 times the dia of the pumping main)Supply and errection of suitable suction and delivery DI pipes and connections upto ManifoldCable Joints with jointing material such as lugs, glands, adhesive tapes etc to join the above cables.Supply, laying and fixing of 40 x 6 mm GI flat patti double earthing for electrical protection for motor, pump panel board efficiently earthing duly providing earth pits and filling with coal and salt and GI pipes 1 ½ x 6” long and bottom 2’ x 2’ GI plate welded as per IE rules and specifications with 1 ½ ‘ x 1 ½ ‘ earth pit chambers with brick masonary and top cover.Fire Extinguisher buckets and other safety measures accessoriesa. CO2 Fire extinguishers of 5 kgs each – 2 nosb. First aid kits – 2 nosc. 4 fire buckets with stand – 2 nos d. Rubber mats – 2 nose. Rubber hand gloves – 3 pairsf. Danger boards – 5 nos All Civil Works Such as anchor Blocks ,Thrust Blocks, Platform for Pannel Board and Cable trench etc Complete as directed by the Field Engineer
Providing 400mm dia. D.I. K9 Raw Water Pumping main from Intake well in Godavari River to Aerator of WTP (150m MS pipe+650m DI K9 pipe)
Cutting and open of B.T. Road surface (as well as asphalt concrete upto 75mm thick) including water bound macadam including stacking of excavated materials including cost of all labour charges, hireing of machinery, fuil charges, wages of driver and other incidetal charges for lying of pipe lines as per the ditections of the departmental authorities. For Pipe line trenches.
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH and as directed by the departmental officer incharge of work For Pipe line trenches - Mechanical Means
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH and as directed by the departmental officer incharge of work For Pipe line trenches - Manual Means
Manufacture supply delivery,of 400mm dia k9 ductile iron centrifugally cast (spun) pipes for water with SOCKET SPIGOT ENDS CONFIRMING TO IS NO 8329/2000 in standard lengths of 4.00,5.00,5.50,6.00m for classification k9 suitable for push-on-joint (rubber gasket D jointing) with cement mortor lining inside and zinc coating out side (K9) including transportation to site ,loading,unloading, stacking etc complete other incidental charge as per ss and as directed by the departmental officer in charge of work for pumping main
Supply and delivery of Centrifugally cast (spun) up to 500mm dia Ductile Iron Fittings of DI double socket branch flange Tee, DI All Socket Tees, DI Double socket Tapers (Reducer), DI Flanged Socket, DI Flanged Spigot, DI Double Socket Duck Foot Bend, DI Double Flange Duck/Foot bend, DI All socket Cross, DI All Flange Tee, DI All Flange Cross, DI Double Flange Reducer, Blank Flange, Mechanical Joints, DI Double Socket Bends, DI Double Flanged Bends and DI Manhole Frame & cover conforming to IS:9523/2000 having dimensions Up to 500 x 500 mm dia. The rates mentioned here under are for fittings, zinc coated externally with inside mortar lining (with finishing as per class 13/IS 9523/2000) ( ex-works) including Transportation and . as directed by the departmental officer incharge of work.
Centrifugally cast (Spun) Ductile Iron DI D/F pressure pies with flanged (welded) ends for water, gas, sewage conforming to IS: 8329/2000 in standard working lengths of 1,2,3, 4, 5 mts for classification K9 with cement mortar lining inside the pipes with outside zinc coating, including transportation other incidental charge etc., complete per ss and as directed by the departmental officer in charge of work. (250mm dia. 2.00m. Long pipe for scours)
Centrifugally cast (Spun) Ductile Iron DI D/F pressure pies with flanged (welded) ends for water, gas, sewage conforming to IS: 8329/2000 in standard working lengths of 1,2,3, 4, 5 mts for classification K9 with cement mortar lining inside the pipes with outside zinc coating, including transportation other incidental charge etc., complete per ss and as directed by the departmental officer in charge of work. (400mm dia. 1.00m. Long pipe for sluice and non return valves and flow meter)
Centrifugally cast (Spun) Ductile Iron DI D/F pressure pies with flanged (welded) ends for water, gas, sewage conforming to IS: 8329/2000 in standard working lengths of 1,2,3, 4, 5 mts for classification K9 with cement mortar lining inside the pipes with outside zinc coating, including transportation other incidental charge etc., complete per ss and as directed by the departmental officer in charge of work. (400mm dia. 2.00m. Long pipe at intake well )
Lowering the of 400mm dia , D.I. K9 Pipes pumping main and fittings with S/S (Plain)ends carefully into the trenches and laying them true to alignment and gradient including all sundries. This rate including cost of all labour charges, fixing of machinary fuil charges other incidental charge etc., complete and as per ss and as directed by the departmental officer in charge of work.
Jointing the 400mm dia ,D.I. K9 Pipes, fittings and valves with rubber gasket(push-on-joint) including the cost of the gasket but including all sundries, filling with water with a water lead upto 500 m and testing to required pressure etc., comp as per BIS No.3114/1994/12888/1987 as per ss and as directed by the departmental officer in charge of work.
Lowering the D.I. Pipes of all classes and fittings with flanged ends carefully into the trenches and laying them true to alignment and gradient including all sundries,conveyance from source of supply as per BIS No.3114/94.This rate including all labour charges hiring of machinary , fuel charges and other incidental charge as per ss and as directed by the departmental officer in charge of work - 400mm DI Specials for pumping main
Lowering the D.I. Pipes of all classes and fittings with flanged ends carefully into the trenches and laying them true to alignment and gradient including all sundries,conveyance from source of supply as per BIS No.3114/94.This rate including all labour charges hiring of machinary , fuel charges and other incidental charge as per ss and as directed by the departmental officer in charge of work - 250mm DI Specials for pumping main
Jointing the D.I. Pipes, fittings and valves with flanged ends including cost of jointing materials such as bolts, nuts, rubber insertion, white lead including all sundries,hiring of machinery ,all labour charges,and filling with water with a water lead upto 500 m and testing to required pressure and other incidental charges etc, complete as per ss and as directed by the departmental officer incharge of work as follows( BIS No.3114/85) - 400mm Dia
Jointing the D.I. Pipes, fittings and valves with flanged ends including cost of jointing materials such as bolts, nuts, rubber insertion, white lead including all sundries,hiring of machinery ,all labour charges,and filling with water with a water lead upto 500 m and testing to required pressure and other incidental charges etc, complete as per ss and as directed by the departmental officer incharge of work as follows( BIS No.3114/85) - 250mm Dia
Jointing the D.I. Pipes, fittings and valves with flanged ends including cost of jointing materials such as bolts, nuts, rubber insertion, white lead including all sundries,hiring of machinery ,all labour charges,and filling with water with a water lead upto 500 m and testing to required pressure and other incidental charges etc, complete as per ss and as directed by the departmental officer incharge of work as follows( BIS No.3114/85) - 100mm Dia
supply and delivery at work site 400mm internal dia M.S.Pipe fabricated with 10mm thick MS plates confirming to IS 2062-1992 of grade A manufactured as per IS 3589-2001 in suitable lengths painted with two coats of food grade epoxy paint inside and outside to suit the site conditions, in co-ordination with the concerned authorities as per approved drawings and directed by the Engineer-in –charge including Cost of Laying, Jointing, Hydrostatic Filed Test Pressure, Including Cost of Site Welding, Jointing Materials And Cost of Transportation of Water Including Emptying Pipe Line After Completion Of Field Testing as per ss and as directed by the departmental officer incharge of work
Supply and delivery of "Resilient Seated Soft Sealing" Gate Valves (Sluice Valves) with Body and Bonnet of Ductile Iron GGG-40/SG-400/15 or GGG-50/SG-500/7 or Equivalent as per IS1865,IS:3896-2 and Wedge fully Rubber Lined with food grade quality grade W270 grade EPDM, Replaceable Spindle Nut without gland packing with 3-O ring protection system on the Shaft and Seals of NBR. The Valves should be Vacuum tight and 100% leak proof with face to face dimensions as BS:5163 Type A/IS:14846. All the valves should be with fusion bonded Electrostatic Powder coating both inside and outside (Min 250 Microns)- RAL 5005 with Pocket Less Straight through body Passage conforming to Design standards of DIN-3202F4/BS:5163 Type A Flange drilling as per IS - 1538 including and transportation. PN1.6. as per ss and as dirceted by the departmental officer in charge of work - 400mm Ø DI D/F valve - PN16
Supply and delivery of "Resilient Seated Soft Sealing" Gate Valves (Sluice Valves) with Body and Bonnet of Ductile Iron GGG-40/SG-400/15 or GGG-50/SG-500/7 or Equivalent as per IS1865,IS:3896-2 and Wedge fully Rubber Lined with food grade quality grade W270 grade EPDM, Replaceable Spindle Nut without gland packing with 3-O ring protection system on the Shaft and Seals of NBR. The Valves should be Vacuum tight and 100% leak proof with face to face dimensions as BS:5163 Type A/IS:14846. All the valves should be with fusion bonded Electrostatic Powder coating both inside and outside (Min 250 Microns)- RAL 5005 with Pocket Less Straight through body Passage conforming to Design standards of DIN-3202F4/BS:5163 Type A Flange drilling as per IS - 1538 including and transportation. PN1.6. as per ss and as dirceted by the departmental officer in charge of work - 250mm Ø DI D/F valve - PN16 (for Scour)
Supply & Delivery of 100mm dia PN 16 on 400mm dia pipelines Tamper Proof DI Flanged Single Chamber Air Release Valves with body & cover made of Ductile Iron Grade GGG-40/SG-400/15 or GGG-50/SG-500/7 or Equivalent as per IS1865, IS:3896-2 with Food Grade Epoxy Powder Coating(EP-P) (Min:250 Micron) inside and Outside of Color Blue RAL 5005. All internal parts such as Float, shell, Cove Bolts etc. made of Austenitic alloy steel of SS AISI 304/316 and DN 50 float of and other components with ABS/PTFE/EPDM/NBR and generally conforming to DIN/BIS/AWWA standards (or) combination Flange drilling as per IS - 1538 PN 1.6 as per ss and as dirceted by the departmental officer in charge of work.
Supply, Delivery of 400mm dia PN 1.6 D.I Double Flanged Swing Check type Reflux valves (Non Return Valves) of following dia. conforming to IS- 5312 (Pts-1&2) (with amendments up to date, if any) having Body, Cover, Door, Bearing holder with D.I; Hinge pin, Door pin, Door suspension pin with Stainless Steel (IS 6603); Body seat ring , Door face ring, Bearing bushes, Plugs for hinge pin with Leaded Tin Bronze ( IS 318 ); Bolts, Nuts with Carbon steel; Gaskets with Rubber; Hinges with Cast steel; including transportation pn 1.6 andas per ss and as dirceted by the departmental officer in charge of work.
Manufacture, Supply and delivery of 100mm dia PN 1.6 Air Cushion valves / Quick Released damped Air Valves (QRDA) as per AWWA,form factory to site of work.This rate including cost of all material transit risk , other incidental charges as per ss and directed by the departmental officer in charge of work.
Labour charges for lowering and keeping in position of 400mm dia D.I. Sluice valves(with cap/with hand wheel), reflux valves and scour valves. This rate including cost of all labour charges , cost of bolts , nuts.rubber packing ,and other incidental charge s etc., complete per ss and as directed by the departmental officer in charge of work - 400mm dia
Labour charges for lowering and keeping in position of 250mm dia D.I. Sluice valves(with cap/with hand wheel), reflux valves and scour valves. This rate including cost of all labour charges , cost of bolts , nuts.rubber packing ,and other incidental charge s etc., complete per ss and as directed by the departmental officer in charge of work - 250mm dia
Labour charges for fixing Kinetic Air Valves 100mm dia PN 1.6 with isolating Sluice valves, Double Air valves/ Air Cushion valve including cost of jointing materials such as bolts, nuts and rubber insertions etc., complete. other incidental cgharges etc., complete as per ss and as directed by the departmental officer in charge of work.
RCC M-20 Nominal mix (cement,fine aggregate,coarse aggregate) corresponding to Table -9 of IS -456 using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including on all materials including all operational ,incidental and labour charges such as machine mixing ,laying concrete ,curing scaffolding , shuttering, centering etc complete but excluding cost of steel and its fabrication charges for finished item of work,as per ss and as directed by the departmental officer in charge of work.for thrust blocks
RCC M-20 Nominal mix (cement,fine aggregate,coarse aggregate) corresponding to Table -9 of IS -456 using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including on all materials including all operational ,incidental and labour charges such as machine mixing ,laying concrete ,curing scaffolding , shuttering, centering etc complete but excluding cost of steel and its fabrication charges for finished item of work,as per ss and as directed by the departmental officer in charge of work.for Anchor blocks
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 500/500D grade) of different diameters for RCC works, including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying including and other all materials etc., complete for finished item of work in all floors. as per SS and as directed by the departmental office incharge of work.
Construction Valve Chambers above 350mm dia Sluice Valve Earthwork in excavation for valve chamber as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH Note : Classifications of Earth Work Specification are as per 302.2.1(a) of MORD and 301.2.1 of MORT&H--ordinary soil--manual means upto 3m depth manual means
Filling Sand for foundation of Valve Chamber as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH.This rate including cost of sand ,filling charges,watering,ramming,and other incidental charges etc., complete as per ss and directed by the departmental officer incharge of work
Plain Cement Concrete for Vlave Chamber (1:4:8) (cement: fine aggregate: Coarse aggregate) using coarse aggregate 40mm size hard, machine crushed granite from approved quarry using concrete Mixer 10 / 7 cft (0.2 / 0.8 cum) capacity including cost and conveyance of all materials like cement, sand, coarse aggregate, water etc. to site including all charges for machine mixing and hire charges of concrete mixer, laying concrete finishing top surface to the required level curing etc., and complete for finished item of work as per SS and as directed by the departmental officer incharge of work. (APSS No. 402).for Valve Chamber bed concrete
RCC M-20 Nominal mix for Valve Chamber (cement,fine aggregate,coarse aggregate) corresponding to Table -9 of IS -456 using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and on all materials including all operational ,incidental and labour charges such as machine mixing ,laying concrete centering, curing etc complete but excluding cost of steel and its fabrication charges for finished item of work,but including centering, shuttering and as directed by the departmental officer incharge of work as follows For Bottom Slab
RCC M-20 Nominal mix for Valve Chamber (cement,fine aggregate,coarse aggregate) corresponding to Table -9 of IS -456 using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and on all materials including all operational ,incidental and labour charges such as machine mixing ,laying concrete curing centering, seaffolding other incidental charges etc complete but excluding cost of steel and its fabrication charges for finished item of work, but including centering, shuttering and as directed by the departmental officer incharge of work as follows For Side walls all round
RCC M-20 Nominal mix (cement,fine aggregate,coarse aggregate) corresponding to Table -9 of IS -456 using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and on all materials including all operational ,incidental and labour charges such as machine mixing ,laying concrete ,curing centering, seaffolding etc complete but excluding cost of steel and its fabrication charges for finished item of work,but including centering, shuttering and as directed by the departmental officer incharge of work for Pre cast slabs
Providing High Yield Strength Deformed (HYSD)/Thermo Mechanically Treated (TMT)/Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works,including labour charges for straightening, cutting,bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG,forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps,couplings,chairs,spacer bars including cost and conveyance of binding wire,cover blocks and all incidental,operational,labour charges such as cutting, bending, placing in position,tying i etc.,complete for finished item of work in all floors.( APSS No.126) for pre cast slabs of culverts
Filling crushur stone dust in pipe line trenches for cutting portion as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH.This rate including cost of stone dust ,filling charges,watering,ramming,and other incidental charges etc., complete as per ss and directed by the departmental officer incharge of work
Restoration of CC road with Construction of un-reinforced, plain cement concrete pavement, thickness as per design, over a prepared sub base, with 43 grade cement or any other type as per Clause 1501.2.2 M30 (Grade), coarse and fine aggregates conforming to IS : 383, maximum in a concrete mixer of not less than 0.2 cum capacity and spreading the concrete with sholvels, rakes, compacted using needle, scareed and plate vibrators and finished in continuous operation, curing of concrete slabs for 14- days, curing compound (where specified) and water finishing to lines and grade as per drawing and Technical Specification Clause 1501 MORD and complete as per SS and as directed by the departmental officer incharges of work
Supply, delivery of 400mm dia Electromagnetic flow meter manufacture should have ISO 9001:2008 certification anf flow meter testing confirming to ISO 17025; Flow meter tube SS 304; Flnages Carbon steel as per DIN PN 10 or higher rating as per requirement ;Liner;Hard rubber or PTFE suitsble for drinking water application; Grounding:Grounding rings SS 304/Grounding electrodes of material SS 316; Coil housing and junction box SS 304 Die cast Aluminium / Carbon steel with anticorrossive apoxy coating of minimim thickness 150 Micron /Equivalent as per EN-ISO-12944 standard as per site condition ingress protection ; IP 68 for Sensor and IP 67 for Transmitter; Flow Transmitter accuracy +/- 0.50% of measured values of velocities 0.50m/sec and above ,Display:Digital LCD/LED (backlit LCD/LED) Display instantaneous flow ,Bi-directional flow,totalised flow, Cable beween flow head and Transmitter maximum 25 m including PVC conduit,Surge arrester to be provided.Power supply and out put 230 V AC or 24V DC as appilicable to site condition and -4-20m A HART;Compatible to SCADA/WEB based data acqusition system;Flow meter test lab certification should be provided from NABL approved lab/FCRI with 5 years warrenty (make M/S krohne Marshall / Endress+Hauser / Yokagawa / siemens / Emerson / ABB / or equivalent make. This rate including cost of materials all labour charges transporation charges other incidental charge etc complete as directed by the departmental officer incharge of work.
Supply,delivery of 400mm dia strainer /dirt box of T type of the following dia suitable to respective meters of same size inclusive of costs,transportation, etc complete as per ss and as directed by the departmental officer incharge of work
Manufacture, Supply and delivery of 400mm MS. Dismantling Joints with both side flange end suitable for installation in between flange end pipes. Thickness as per IS: 7322. Thise rates is including cost of materials, transportation charges, other incidental charges etc complete as per ss and as directed by the departmental officer in charge of work
Construction of 8.00 MLD Rapid Gravity Filtration plant
Construction of 8 MLD Rapid Gravity Filtration Plant including all civil, mechanical and electrical works using sand as filter media, compatible with SCADA arrangements, duly following relevant IS codes in the design of plant components including trial running for 90 days etc., including chlorine contact tank & consumables etc., complete.
a) For Intermediate Capacities proportional rates may be adopted b) The above rates are arrived with base rate of Cement Rs.4220/- per MT and steel Rs.59000 /- f(i) For SBC below 10T/Sqm to 7.5 T/Sqm, solid raft shall be provided and for solid raft the rate shall be increased by 10% on basic rate. ii) For SBC below 7.5 T/Sqm to 5 T/Sqm, solid raft shall be provided and for solid raft the rate shall be increased by 15% on basic rate. g) For SBC value of less than 5 T/Sqm, soil improvement shall be adopted, for which additional payment shall be made as per field condition. h) For components immersed in water Stain less Steel of Grade 304L shall be used. For other components 304 Grade steel shall be used. i) Lab testing equipment of reputed make and consumables for one year. The testing equipment for conducting all laboratory tests shall be installed & training shall be imparted to the Municipal staff. The above rates of Filtration Plants shall include all the following components.
A) Civil Works,(All works of VRCC Shall be in M30 design mix),1). Stilling Chamber and Aeration cascade,3). Raw water channel with Stainless Steel Weir of SS 304 L Grade material and also with digital flow meters,4) Flash Mixer chamber with Flash mixing arrangements including SS shaft & SS Blades with gear wheel arrangements etc, using 304 L Grade Steel.,5-a) Clariflocculator / Flocculation tanks with the components of central driven circular clarifier with scrapper & bridge arrangements made with Stainless Steel Grade 304 Ltubes /angular for durability & chemical resistant with wheel arrangements etc,,6) Filter house, Chemical house, Alum store, Laboratory room, Chlorination plant room, toilet etc. (All structures shall be provided RCC roof only).Chemical house & Chlorinator rooms are to be isolated and shall be as per CPHEEO manual.7) Wash water tank of suitable capacity shall be constructed at minimum clearance of 2.00m, above the roof slab of Filter beds / any other structure, and the minimum residual head at the top of under drain system shall not be less than 8.0 meters.,8) Chlorine contact tank,9) All the Doors and Windows shall be of Best Teak wood/Aluminum / UPVC make, except entrance door. The entrance door including shutter in filter house shall be with best teak wood of minimum size of 2.40 X 2.40 mts.,a) Main Doors of all individual Buildings shall be made of Best Teak woodb) Other Internal Doors of the buildings shall be of Compressed wood/ Aluminum/ UPVC materials.,c) Ventilators shall be provided for each building/structure of suitable size as per NBC standards.,10) a) All pipes in Plant shall be of D.I., D/F materials. All Connecting pipes of the plant components such as from Flash mixer to Clariflocculator/ Clarifier/Flocculation tank, to Filter beds, sludge disposal pipes shall be of D.I., D/F material. The size of sludge disposal pipe shall be minimum of 450 mm dia. with D.I D/F pipe and minimum length of 100 meters.,b) All the Valves in Plant shall be heavy duty and as per the specification of SoR,item No.30,11) The Pipe gallery way for Clear water/ Back wash water/ pipe connections shall be,sufficiently spaced for easy operation & maintenance and inspection, as per standard norms.,12) The bottom level of the wash water control chamber must be above G.L so as to dispose the wash water and sludge from Clariflocculator by gravity to disposal point.
Additional specifications,13) Railing for all the components (Clariflocculator, Filter House, Staircase etc,.) shall be provided with Stainless Steel of grade 304 for a height of 1.00m, with 40mm dia.,pipe for top horizotals,25mm dia. for middle row and 40mm dia. verticals spaced atinterval of not more than 1.00m c/c.,14) Inspection / Path ways in filter beds: Middle pathway: Minimum of 1.50m, Side pathway: Minimum of 1.20m,15) i) Flooring in the buildings (Filter house, Chemical House, Chlorinator Room, Laboratory) shall be provided with Non-skid ceramic tiles of approved make & quality, as per standard specifications.,ii) All water Channels such as inlet, outlet channels and chambers shall be provided with tiles.,16) The basement of the Filtration plant building shall be minimum of 1.20m and pipe gallery shall be minimum 0.3m above the existing nearby Road top level.,17) Minimum head room of 2.00m shall be provided, at the alum mixing chambers in alum store for inspection & maintenance.,18) The minimum width of entrance hall for the Filter House shall be 4.50m, and Laboratory of min size of 3.30 X 4.50m.
18) b) For various components of the WTP should be designed by considering the uplift pressure also. 19) a) High efficient Air Blowers shall be installed to the design requirement with low noise pollution, environmental pollution as per PCB guide lines & Testing of blowers as per I.S Standards at site. b) The Piping from Blower to Filter Beds shall be GI and submerged pipe in water shall be HDPE.,20) UPVC pipes shall be provided for under drain system. Filter pipe manifolds shall be assembled with HDPE pipes.,21) Alum storage capacity shall be designed for minimum period of 90 days. Consumables shall be provided for 2115 Running Hours of WTP.,22) Chlorinator : Vacuum type chlorinator shall be provided with following specifications:,a) Vacuum operated solution feeding type Vacuum Regulator, Rotameter, Rate setting Valve, built-in NRV, Gas Overflow out let by man folding to mount the system with the unit. b) The unit shall consist of Ejector with necessary accessories such as Check Valve, Drain Valve and Vacuum relief Valves - for control of chlorinator dosage. c) The Accessories and manifolds shall be chlorine resistant and made of carbon steel seam less pipes, copper tube with brass fittings of suitable size & dimensions, with diaphragm sealed chlorine pressure gauge arrangements d) Water Booster Pump of pumping capacity ranging from 2 cum/hr to 12 cum/hr, with Head ranging from 16 to 35 m,e) The water & solution carrying pipes shall be made of UPVC material of suitable size incl. all specials such as Tee's , Bends, couplings & NRVs and also Pressure Gauges of suitable range. f) Chlorine Gas Leak detector with alarm indicator. The installation includes all necessary accessories, civil and mechanical works, manifold header installations, injector fixing, connection with UPVC pipes, solution piping’s, fixing of motors as per standard specifications and commissioning of Chlorination Plant to the required demand, with a defect liability period of 1 year. The chlorinator of may be of any reputed make or any make of Metito/Toshocow-Jesco Siemens Industrial Devices.,g) Life breathing apparatus.,h) Chlorine escape BA set,i) 2 to 10 MLD Plants - 1Kg/hr Chlorinator- For Post Chlorination
B) Mechanical Equipment.1) Alum dosing equipment with SS 304 material made stirrers & paddles for chemical.resistance. (Alum tanks must be bound with corrosion resistant material (HDPE Lining,. Bitumen Coating, tiles etc) 2) Flash mixer equipment with SS 304 material made stirrers & paddles for chemical resistance..3) Filtration plant equipment instrumentation and piping..4) Clarifloccualation equipment (with stainless steel blades) with rotating bridge arrangement etc.,..5) Pneumatic tyre wheel shall be provided for the bridge Clariflocculator..6) Wash water tank fittings and pump sets with 100% stand by..7) Air blower with motor of 100% stand by and pipe connections made with of SS pipes confirming to SS 304 Grade, in filter bed region..8) Chlorination equipment and pipe connections with chlorinator of 100% standby..9) Spares & Tools for 2 years..10) Gaseous Chlorination with cylinders has to be provided with protection measures.C) Electrical Equipment.1) Necessary power supply wiring to motors and switches bus bar connections as perIE Rules.2) Internal wiring and illumination and fittings and fixtures for internal and external lighting exhaust fans, ceiling fans etc..3) Erecting mechanical and electrical equipment, trial run for 90 days at 23.50 hours.per day testing the treated water as per CPHEEO standards and maintenance of records.and imparting training to staff..4) Supply of 6 - Sets of completion plans and maintenance manual and brochures..5) All cables shall be of copper material, Cable ducts shall be covered with MS / Aluminum cheque plate..6) Min LUX levels inside the treatment plant shall be maintained..7) Yard lighting shall be provided as per norms.D ) Equipment for Flow measurements.1) Equipment for measuring Conductivity, Turbidity, Ph value, Residual Chlorine with recording & data storage facility (Computer based) & Alarm by SMS or other methods..2) Off - Site Supervisory and Data Acquisition (OSSADA) system for Raw water &Clear water flows by installing Digital Flow meters to measure the flows at Raw water Channel and at each filter bed individually and combined for measuring the quantities of water treated with a facility to record and store the readings & also to sendmessages to the assigned designators about the variations/ deficiencies in the flow including alerts for back wash requirements of filter beds, and recovery of data for the past 360 days. All the Digital Flow Meters & Pressure Gauges shall be provided of standard approved make. The equipment shall have the following specifications.
Hardware:,i) Wall mounted Sensor House for measuring Raw water & Clear water flow from Filter bed out lets with accessories consists of,ii) Electrode Type: General type, Scraper type or replaceable type Electrode made with material of SS external Ultra Touch Sensors as per requirement.,iii) Customized Application Requirement : Sensors with Interface logic control board with serial interfaces, including accessories such as Add-on port, external DC Power Socket, On - sensor Board Buffer, Timer, RS485 Communication, Analog to Digital Sensing Sensor Circuit, 32 Sensors Sensing Tags, Interval Power Supply System , LCD 16c/2L, Filter Bed Working Status Indication LED, Filter Bed Wash IndicationButton and memory of Data Storage for 30Days , status of Filter Bed Level indicator, Rating, Reading on LCB Display, Menu Driven Data for sending to Onsite Big Display, operated with Battery Power of any reputed make or any equivalent make.,iv) Customized Application Requirement: Power Sensors Interface logic control board with support 8 Power Sensing tags, Central System Interfacing Communication, On - board analog to Digit Convert Integrate Circuit of any reputed make or any equivalent make.v) Customized Application Requirement: Centralized System with two serial interfaces, 3 No’s of Add-On ports, One external DC Power Socket, On - BoardBuffer, On - Board Timer, On - Board RS485 Communication, On - Board RS 232 Communication, On - Board GPRS/GSM Module, On - Board Voice Chip, On - Board,Power Sensing Module, LCD 16c/2L, Filter Bed Wash Precaution Indication with Stop Button, Memory of Data Storage for 30 Days, Total Bed Rating, Reading display onLCD Display, Menu Driven, Menu Navigate Keypad, sending data to the Web Server, Communication with GPRS , operated with Battery Power of any reputed make or any equivalent make.
Software:,The software shall be designed with Web Domain with Data Base Server and Web Name as per the directions of the Departmental Authorities. The application of Software for Web design & Desktop shall meet the following requirements: i)Onsite Display: Letters with size of 1.5’ seven Segment LED Display with Interface for each Filter Bed, for Onsite Display, by displaying the Bed Levels, Ratings,Readings in 3 Columns, for each bed of the plant in successive rows and cumulative results at the bottom of the screen.,ii) Off Site Display: Letters with size of 1.5’ seven Segment LED Display withInterface GPRS/GSM Modules Offsite Display, with Display of Bed Total Rating,,Total Cumulative Reading as specified on On-site Display Features. The system shall have also the features of Onsite Bed Wash Voice Precautions for Bed Levels, Readings, Ratings, Bed Capacity Readings and Ratings and Bed Low Level Triggering, before & after Bed wash. The software shall also have the features of sending messages to the mobiles of the Departmental designators indicating Bed Low Levels, Power Supply timings, Bed Wash timings and its status, Power Supply timings and its status Grid View Table, Motor Working time and its status Grid View Table, all trigger events and schedule information and including all Snap View Reports, all Daily, Monthly, Yearly Reports, all Power Working Reports, all Power Events Information etc,.
Supply and delivery of 300mm dia DI D/F 2.00m length Centrifugally cast (SPUN) Ductile iron K9 pressure pipes with flanged ends for water, gas and sewage conforming to I.S, 8329/2000 in standard working lengths of 4, 5, 5.5 & 6 meter for classification K9 suitable for push on joint (Rubber gasket and jointing) with cement mortar lining inside the pipes with outside zinc coating, rates are ex-factory, including transportion and as per ss and as directed by the departmental officer incharge of work as follows - 300 mm dia DI DF pipes from WTP to clear water sump (2.00m length)
Supply and delivery of 300mm dia 1.00m lengh DI D/f Centrifugally cast (SPUN) Ductile iron K9 pressure pipes with flanged ends for water, gas and sewage conforming to I.S, 8329/2000 in standard working lengths of 4, 5, 5.5 & 6 meter for classification K9 suitable for push on joint (Rubber gasket and jointing) with cement mortar lining inside the pipes with outside zinc coating, rates are ex-factory, including transportion and as per ss and as directed by the departmental officer incharge of work as follows - 300 mm dia DI DF pipes from WTP to clear water sump (1.00m length)
Supply and delivery of Centrifugally cast (spun) upto 500mm dia Ductile Iron Fittings of DI double socket branch flange Tee, DI All Socket Tees, DI Double socket Tapers (Reducer), DI Flanged Socket, DI Flanged Spigot, DI Double Socket Duck Foot Bend, DI Double Flange Duck/Foot bend, DI All socket Cross, DI All Flange Tee, DI All Flange Cross, DI Double Flange Reducer, Blank Flange, Mechanical Joints, DI Double Socket Bends, DI Double Flanged Bends and DI Manhole Frame & cover conforming to IS:9523/2000 having dimensions Up to 500 x 500 mm dia. The rates mentioned here under are for fittings, zinc coated externally with inside mortar lining (with finishing as per class 13/IS 9523/2000) ( ex-works) including Transportation and as per ss and as directed by the departmental officer incharge of work.
Supply and delivery of 300 MM DIA PN 1.6 "Resilient Seated Soft Sealing" Gate Valves (Sluice Valves) with Body and Bonnet of Ductile Iron GGG-40/SG-400/15 or GGG-50/SG-500/7 or Equivalent as per IS1865, IS:3896-2 and Wedge fully Rubber Lined with food grade quality grade W270 grade EPDM, Replaceable Spindle Nut without gland packing with 3-O ring protection system on the Shaft and Seals of NBR. The Valves should be Vacuum tight and 100% leak proof with face to face dimensions as BS:5163 Type A/IS:14846. All the valves should be with fusion bonded Electrostatic Powder coating both inside and outside (Min 250 Microns)- RAL 5005 with Pocket Less Straight through body Passage conforming to Design standards of DIN-3202F4/BS:5163 Type A Flange drilling as per IS - 1538 including transportation PN1.6 Mpa - other incidental charges etc complete as directed by the departmental officer incharges of work.
Labour charges for lowering and keeping in position of 300mm dia PN 1.6C.I./DI Sluice valves(with cap/with hand wheel), reflux valves and scour valves.This rate including cost of all labour charges,hiring of machinery and other incidental charges and complete as per ss and as directed by the departmental officer incharge of work
Lowering the 300MM D.I. Pipes K9 of all classes and fittings with flanged ends carefully into the trenches and laying them true to alignment and gradient including all sundries,hiring of machinery ,all labour charges,and other incidental charges etc, complete as per ss and as directed by the departmental officer incharge of work as follows(BIS No.3114/94)
Jointing the 300 MM DIA D.I. Pipes, fittings and valves with flanged ends including cost of jointing materials such as bolts, nuts, rubber insertion, white lead including all sundries,hiring of machinery ,all labour charges,and filling with water with a water lead upto 500 m and testing to required pressure and other incidental charges etc, complete as per ss and as directed by the departmental officer incharge of work as follows( BIS No.3114/85)
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH for pipe line trench
Construction Valve Chambers above 350mm dia Sluice Valve Earthwork in excavation for valve chamber as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH Note : Classifications of Earth Work Specification are as per 302.2.1(a) of MORD and 301.2.1 of MORT&H--ordinary soil--manual means upto 3m depth manual means
Filling Sand for foundation of Valve Chamber as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH.This rate including cost of sand ,filling charges,watering,ramming,and other incidental charges etc., complete as per ss and directed by the departmental officer incharge of work
Plain Cement Concrete for Vlave Chamber (1:4:8) (cement: fine aggregate: Coarse aggregate) using coarse aggregate 40mm size hard, machine crushed granite from approved quarry using concrete Mixer 10 / 7 cft (0.2 / 0.8 cum) capacity including cost and conveyance of all materials like cement, sand, coarse aggregate, water centering etc. to site including all charges for machine mixing and hire charges of concrete mixer, laying concrete finishing top surface to the required level curing etc., and complete for finished item of work as per SS and as directed by the departmental officer incharge of work. (APSS No. 402).for Valve Chamber bed concrete
RCC M-20 Nominal mix for Valve Chamber (cement,fine aggregate,coarse aggregate) corresponding to Table -9 of IS -456 using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and on all materials including all operational ,incidental and labour charges such as machine mixing ,laying concrete ,curing centering, seaffolding charge etc complete but excluding cost of steel and its fabrication charges for finished item of work,but including centering, shuttering and as directed by the departmental officer incharge of work as follows For Bottom Slab
RCC M-20 Nominal mix for Valve Chamber (cement,fine aggregate,coarse aggregate) corresponding to Table -9 of IS -456 using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and on all materials including all operational ,incidental and labour charges such as machine mixing ,laying concrete ,curing centering seaffolding etc complete but excluding cost of steel and its fabrication charges for finished item of work,but including centering, shuttering and as directed by the departmental officer incharge of work as follows For Side walls allround
RCC M-20 Nominal mix (cement,fine aggregate,coarse aggregate) corresponding to Table -9 of IS -456 using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and on all materials including all operational ,incidental and labour charges such as machine mixing ,laying concrete ,curing centering seaffolding etc complete but excluding cost of steel and its fabrication charges for finished item of work,but including centering, shuttering and as directed by the departmental officer incharge of work for Pre cast slabs
Providing High Yield Strength Deformed (HYSD)/Thermo Mechanically Treated (TMT)/Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works,including labour charges for straightening, cutting,bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG,forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps,couplings,chairs,spacer bars including cost and conveyance of binding wire,cover blocks and all incidental,operational,labour charges such as cutting, bending, placing in position,tying i etc.,complete for finished item of work in all floors.( APSS No.126) for pre cast slabs of culverts valve chamber
Construction of Pre Settling Tank of 345 KL capacity near water treatent plant
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH for foundations upto 3.00m depth - Mechanical Means
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH for foundations upto 3.00m depth - Manual Means
Filling Sand for foundation of PRE SETTLING TANK as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH.This rate including cost of sand ,filling charges,watering,ramming,and other incidental charges etc., complete as per ss and directed by the departmental officer incharge of work
Plain Cement Concrete for Vlave Chamber (1:4:8) (cement: fine aggregate: Coarse aggregate) using coarse aggregate 40mm size hard, machine crushed granite from approved quarry using concrete Mixer 10 / 7 cft (0.2 / 0.8 cum) capacity including cost and conveyance of all materials like cement, sand, coarse aggregate, water etc. to site including all charges for machine mixing and hire charges of concrete mixer, laying concrete finishing top surface to the required level curing etc., and complete for finished item of work as per SS and as directed by the departmental officer incharge of work. (APSS No. 402).for PRE SETTLINK TANK
Supply and placing of the M30 design mix concrete corresponding to IS -456 using /MIXER using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including , all materials including all operational ,incidental and labour charges such as ,machine mixing ,laying concrete ,curing steel centering, seaffolding charges etc complete but excluding cost of steel and its fabrication charges for finished item of work (APSS NO 402) with minimum cement content as per IS Code from standard suppliers approved by the deparment including pumping , centering,shuttering,laying concrete ,vibrating,curing etc., complete and as per ss and as directed by the departmental officer in charge of work as follows - Raft
Supply and placing of the M30 design mix concrete corresponding to IS -456 using /MIXER using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including , all materials including all operational ,incidental and labour charges such as ,machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work (APSS NO 402) with minimum cement content as per IS Code from standard suppliers approved by the deparment including pumping , centering,shuttering,laying concrete ,vibrating,curing etc., complete and as per ss and as directed by the departmental officer in charge of work - Side walls
Supply and placing of the M30 design mix concrete corresponding to IS -456 using /MIXER using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including , all materials including all operational ,incidental and labour charges such as ,machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work (APSS NO 402) with minimum cement content as per IS Code from standard suppliers approved by the deparment including pumping , centering,shuttering,laying concrete ,vibrating,curing etc., complete and as per ss and as directed by the departmental officer in charge of work - Central shaft, 8pill channel
Supply and placing of the M30 design mix concrete corresponding to IS -456 using /MIXER using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including , all materials including all operational ,incidental and labour charges such as ,machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work (APSS NO 402) with minimum cement content as per IS Code from standard suppliers approved by the deparment including pumping , centering,shuttering,laying concrete ,vibrating,curing etc., complete and as per ss and as directed by the departmental officer in charge of work - Walk Way Slab- 150mm thick slab
Painting Walls with Snowcem or other equal and approved Water Proof Cement Paint 2 Coats (All Colours) over a base coat of aproved cement primer making 3 coats in total including cost of all , conveyance charges of materials and other incidental charges, scaffolding, lifting and as directed by the departmental officer in charge of work
Supply and delivery and fixing in position Stainless Steel Hand Railing with SS 304 Grade of any design including all fabrication and all fixing charges welding charges fabrication charges and other incidental charges etc compalete as per ss and as directed by the dept authorities
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 500/500D grade) of different diameters for RCC works, including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying including and other all materials etc., complete for finished item of work in all floors. as per SS and as directed by the departmental office incharge of work.
Manufacture supply delivery,of 400mm dia K9 centrifugally cast (spun) ductile iron pipes for water with Socket spigot ends confirming to IS NO 8329/2000 in standard lengths of 4.00,5.00,5.50,6.00m suitable for push-on-joint (rubber gasket D jointing) with cement mortor lining inside and zinc coating out side (K9) including transportation ,loading,unloading,transmit risk stacking, etc complete and as directed by the departmental officer in charge of work.
Manufacture supply delivery,of 400mm dia K7 centrifugally cast (spun) ductile iron pipes for water with Socket spigot ends confirming to IS NO 8329/2000 in standard lengths of 4.00,5.00,5.50,6.00m suitable for push-on-joint (rubber gasket D jointing) with cement mortor lining inside and zinc coating out side (K9) including transportation ,loading,unloading,transmit risk stacking, etc complete and as directed by the departmental officer in charge of work for disposal of sludge.
Lowering of 400mm dia DI k9 D.I. socket and spigot Pipes and fittings carefully in to the trench and laying them true to alignment and gradient including all labour charges, sundries and other incidental charges as per BIS No. 3114/85 etc., complete as per S.S and as directed by the departmental officer in charge of work for raw water
Jointing of 400MM DIA D.I. Pipes & fittings with Rubber Gasket including all sundries filling with water with a water lead up to 500m and testing to required pressure including cost of jointing material Gasket, all labour charges other incedintal charges etc., complete as per BISNo.3114/85 and as directed by the departmental officer in charge of work.
Supply and delivery of 400mmdia DI K9 1.00m long Centrifugally cast (SPUN) ductile iron pressure pipes with flanged ends for water, gas and sewage conforming to I.S, 8329/2000 in standard working lengths of 4, 5, 5.5 & 6 meter for classification K9 suitable for push on joint (Rubber gasket and jointing) with cement mortar lining inside the pipes with outside zinc coating, rates are , including transportion and transportation ,loading,unloading,transmit risk stacking, etc complete and as directed by the departmental officer in charge of work
Lowering the 400 mm dia, D.I. Pipes of all classes and fittings with flanged ends carefully into the trenches and laying them true to alignment and gradient including all sundries,and other incidental charges etc complete as per ss and as directed by the departmental officer in charge of work.
Jointing the 400mm D.I. Pipes, fittings and valves with flanged ends including cost of jointing materials such as bolts, nuts, rubber insertion, white lead including all sundries,hiring of machinery ,all labour charges,and filling with water with a water lead upto 500 m and testing to required pressure and other incidental charges etc, complete as per ss and as directed by the departmental officer incharge of work( BIS No.3114/85)
Supply and delivery of Centrifugally cast (spun) Ductile Iron Fittings up to 500mm dia of DI double socket branch flange Tee, DI All Socket Tees, DI Double socket Tapers (Reducer), DI Flanged Socket, DI Flanged Spigot, DI Double Socket Duck Foot Bend, DI Double Flange Duck/Foot bend, DI All socket Cross, DI All Flange Tee, DI All Flange Cross, DI Double Flange Reducer, Blank Flange, Mechanical Joints, DI Double Socket Bends, DI Double Flanged Bends and DI Manhole Frame & cover conforming to IS:9523/2000 having dimensions Up to 500 The rates mentioned here under are for fittings, zinc coated externally with inside mortar lining (with finishing as per class 13/IS 9523/2000) ( ex-works) including Transportation . etc., complete as per ss and as directed by the departmental officer incharge of work.
Supply and delivery of 400MM dia "Resilient Seated Soft Sealing" Gate Valves (Sluice Valves) PN 1.6(Mpa) with Body and Bonnet of Ductile Iron GGG-40/SG-400/15 or GGG-50/SG-500/7 or Equivalent as per IS1865, IS:3896-2 and Wedge fully Rubber Lined with food grade quality grade W270 grade EPDM, Replaceable Spindle Nut without gland packing with 3-O ring protection system on the Shaft and Seals of NBR. The Valves should be Vacuum tight and 100% leak proof with face to face dimensions as BS:5163 Type A/IS:14846. All the valves should be with fusion bonded Electrostatic Powder coating both inside and outside (Min 250 Microns)- RAL 5005 with Pocket Less Straight through body Passage conforming to Design standards of DIN-3202F4/BS:5163 Type A Flange drilling as per IS - 1538 and transportation and other incidental charges etc,as per ss and as directed by the departmental officer incharge of work
Construction Valve Chambers Sluice Valve Earthwork in excavation for valve chamber as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH Note : Classifications of Earth Work Specification are as per 302.2.1(a) of MORD and 301.2.1 of MORT&H--ordinary soil--manual means upto 3m depth manual means
Filling Sand for foundation of Valve Chamber as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH.This rate including cost of sand ,filling charges,watering,ramming,and other incidental charges etc., complete as per ss and directed by the departmental officer incharge of work
Plain Cement Concrete for Vlave Chamber (1:4:8) (cement: fine aggregate: Coarse aggregate) using coarse aggregate 40mm size hard, machine crushed granite from approved quarry using concrete Mixer 10 / 7 cft (0.2 / 0.8 cum) capacity including cost and conveyance of all materials like cement, sand, coarse aggregate, water etc. to site including all charges for machine mixing and hire charges of concrete mixer, laying concrete finishing top surface to the required level curing etc., and complete for finished item of work as per SS and as directed by the departmental officer incharge of work. (APSS No. 402).for Valve Chamber bed concrete
RCC M-20 Nominal mix for Valve Chamber (cement,fine aggregate,coarse aggregate) corresponding to Table -9 of IS -456 using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and on all materials including all operational ,incidental and labour charges such as machine mixing ,laying concrete ,curing centering etc complete but excluding cost of steel and its fabrication charges for finished item of work,but including centering, shuttering and as directed by the departmental officer incharge of work as follows For Bottom Slab
RCC M-20 Nominal mix for Valve Chamber (cement,fine aggregate,coarse aggregate) corresponding to Table -9 of IS -456 using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and on all materials including all operational ,incidental and labour charges such as machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work,but including centering, shuttering and as directed by the departmental officer incharge of work as follows For Side walls allround
RCC M-20 Nominal mix (cement,fine aggregate,coarse aggregate) corresponding to Table -9 of IS -456 using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and on all materials including all operational ,incidental and labour charges such as machine mixing ,laying concrete ,curing centering etc complete but excluding cost of steel and its fabrication charges for finished item of work,but including centering, shuttering and as directed by the departmental officer incharge of work for Pre cast slabs
Construction of R.C.C. thrust blocks using RCC M- 20 Nominal mix (Cement:fine aggregate: coarse aggregate) corresponding to Table 9 of IS 456 using 20mm size graded machine crushed hard granite metal (coarse aggregate) from approved quarry including cost and conveyance of all materials like cement, fine aggregate (sand) coarse aggregate, water etc., to site and including all operational, incidental and labour charges such as machine mixing, laying concrete, centering shuterig seaffolding curing etc.,complete but excluding cost of steel and its fabrication charges for finished item of work,
Providing High Yield Strength Deformed (HYSD)/Thermo Mechanically Treated (TMT)/Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works,including labour charges for straightening, cutting,bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG,forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps,couplings,chairs,spacer bars including cost and conveyance of binding wire,cover blocks and all incidental,operational,labour charges such as cutting, bending, placing in position,tying i etc.,complete for finished item of work in all floors.( APSS No.126) for pre cast slabs of culverts - RBR-FNDN-8 & Revised Data sl.No-5
Construction of R.C.C. railing of M 25 grade in cast-in-situ with 20 mm nominal size aggregate, true to line and grade, tolerance of vertical railing post not to exceed 1 in 500, centre-to-centre spacing between vertical posts not to exceed 2000 mm as per drawing and technical specifications Clauses 800, 900 and 1208.3 MORD.complete as per ss and as directed by the departmental officer incharge of work
Construction of clear water sump at WTP
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH for foundations upto 3.00m depth Note : Classifications of Earth Work Specification are as per 302.2.1(a) of MORD and 301.2.1 of MORT&H--ordinary soil-- upto 3m depth as per ss as directed by the departmental officer in-charge of work - Mechanical means
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH for foundations upto 3.00m depth Note : Classifications of Earth Work Specification are as per 302.2.1(a) of MORD and 301.2.1 of MORT&H--ordinary soil--Mechanical means 3 to 6 metres depth in ordinary soils - Mechanical means
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH for foundations upto 3.00m depth Note : Classifications of Earth Work Specification are as per 302.2.1(a) of MORD and 301.2.1 of MORT&H--ordinary soil--Manual means 3 to 6 metres depth in ordinary soils
Filling Sand for foundation for sump as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH.This rate including cost of sand ,filling charges,watering,ramming,and other incidental charges etc., complete as per ss and directed by the departmental officer incharge of work
Plain Cement Concrete (1:4:8) (cement: fine aggregate: Coarse aggregate) using coarse aggregate 40mm size hard, machine crushed granite from approved quarry using concrete Mixer including cost and conveyance of all materials like cement, sand, coarse aggregate, water etc. to site including all charges for machine mixing and hire charges of concrete mixer, laying concrete finishing top surface to the required level curing for finished item of work as per SS and as directed by the departmental officer incharge of work. for bed concrete.of sump
Supply and placing of the Design mix M30 concrete corresponding to IS -456 using /MIXER using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and on all materials including all operational ,incidental and labour charges such as weigh batching ,machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work (APSS NO 402) with minimum cement content as per IS Code from standard suppliers approved by the deparment including pumping , centering,shuttering,laying concrete ,vibrating,curing and other incidental charges complete as per ss and as directed by the departmental officer in charge of work as follows - Raft
Supply and placing of the Design mix M30 concrete corresponding to IS -456 using /MIXER using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and on all materials including all operational ,incidental and labour charges such as weigh batching ,machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work (APSS NO 402) with minimum cement content as per IS Code from standard suppliers approved by the deparment including pumping , centering,shuttering,laying concrete ,vibrating,curing and other incidental charges complete as per ss and as directed by the departmental officer in charge of work as follows - For side walls circular 0.30m thick below GL
Supply and placing of the Design mix M30 concrete corresponding to IS -456 using /MIXER using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and on all materials including all operational ,incidental and labour charges such as weigh batching ,machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work (APSS NO 402) with minimum cement content as per IS Code from standard suppliers approved by the deparment including pumping , centering,shuttering,laying concrete ,vibrating,curing and other incidental charges complete as per ss and as directed by the departmental officer in charge of work as follows - For side walls circular 0.30m thick above GL
Supply and placing of the Design mix M30 concrete corresponding to IS -456 using /MIXER using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and on all materials including all operational ,incidental and labour charges such as weigh batching ,machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work (APSS NO 402) with minimum cement content as per IS Code from standard suppliers approved by the deparment including pumping , centering,shuttering,laying concrete ,vibrating,curing and other incidental charges complete as per ss and as directed by the departmental officer in charge of work as follows - For Columns
Supply and placing of the Design mix M30 concrete corresponding to IS -456 using /MIXER using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and on all materials including all operational ,incidental and labour charges such as weigh batching ,machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work (APSS NO 402) with minimum cement content as per IS Code from standard suppliers approved by the deparment including pumping , centering,shuttering,laying concrete ,vibrating,curing and other incidental charges complete as per ss and as directed by the departmental officer in charge of work as follows - For Roof Beams
Supply and placing of the Design mix M30 concrete corresponding to IS -456 using /MIXER using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and on all materials including all operational ,incidental and labour charges such as weigh batching ,machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work (APSS NO 402) with minimum cement content as per IS Code from standard suppliers approved by the deparment including pumping , centering,shuttering,laying concrete ,vibrating,curing and other incidental charges complete as per ss and as directed by the departmental officer in charge of work as follows - For Roof slab 0.15m thick
Supply and placing of the Design mix M30 concrete corresponding to IS -456 using /MIXER using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and on all materials including all operational ,incidental and labour charges such as weigh batching ,machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work (APSS NO 402) with minimum cement content as per IS Code from standard suppliers approved by the deparment including pumping , centering,shuttering,laying concrete ,vibrating,curing and other incidental charges complete as per ss and as directed by the departmental officer in charge of work as follows - For Roof dome slab 0.15m thick
Providing impervious coat to exposed RCC roof slab surface with CM(1:3), 20mm thick with 1kg of water proof compound per bag of cement laid over roof when it is green including cost of all materials, seigniorage charges, excluding conveyance charges of materials and including all operational, incidental and labour charges for mixing mortar, laying, rendering smooth and thread lining, curing, rounding off junctions of wall and slab etc,, complete for finished item of work
Painting Walls with Snowcem or other equal and approved Water Proof Cement Paint 2 Coats (All Colours) over a base coat of aproved cement primer making 3 coats in total including cost of all , conveyance charges of materials and other incidental charges, scaffolding, lifting and as directed by the departmental officer in charge of work.
Supply and delivery and fixing in position M S ladder and manhole cover grill of any design including all fabrication and all fixing charges and other incidental charges power charges welding rod other incidental charges etc complete as per ss and as directed by the dept authorities
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 500/500D grade) of different diameters for RCC works, including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying including and other all materials etc., complete for finished item of work in all floors. as per SS and as directed by the departmental office incharge of work.
Construction of R.C.C. railing of M 25 grade in cast-in-situ with 20 mm nominal size aggregate, true to line and grade, tolerance of vertical railing post not to exceed 1 in 500, centre-to-centre spacing between vertical posts not to exceed 2000 mm as per drawing and technical specifications Clauses 800, 900 and 1208.3 MORD. This rate including cost of material, all lanbour charges, scaffolding charge , vibrating, watering, hand rail in 3stires including HYSD bar reinforcement as par ss and as directed by the departmental officer in charge of work.
Construction of pump house for clear water pumps and motors at proposed WTP
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH Note : Classifications of Earth Work Specification are as per 302.2.1(a) of MORD and 301.2.1 of MORT&H--ordinary soil-Mechanical Means
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH Note : Classifications of Earth Work Specification are as per 302.2.1(a) of MORD and 301.2.1 of MORT&H--ordinary soil-Manual Means
Filling Sand for foundation for pump house as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH.This rate including cost of sand ,filling charges,watering,ramming,and other incidental charges etc., complete as per ss and directed by the departmental officer incharge of work
Plain Cement Concrete (1:4:8) (cement: fine aggregate: Coarse aggregate) using coarse aggregate 40mm size hard, machine crushed granite from approved quarry using concrete Mixer including cost and conveyance of all materials like cement, sand, coarse aggregate, water etc. to site including all charges for machine mixing and hire charges of concrete mixer, laying concrete finishing top surface to the required level curing for finished item of work as per SS and as directed by the departmental officer incharge of work.
Providing PCC 1:3:6 using 40 mm graded SS 5 HBG m/c metal and OPC coarse and fine aggregate confirming to IS 383 including cost and conveyance of all materials and labour charges, machine mixing , vibration,laying in position, curing centering etc., complete as per ss directed by the departmental officer incharge of work for flooring and ramp
Supply and placing of the M25 design mix concrete corresponding to IS -456 using MIXER using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including ,sales and other taxes on all materials including all operational ,incidental and labour charges such as weigh batching ,machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work (APSS NO 402) with minimum cement content as per IS Code from standard suppliers approved by the deparment including pumping , centering,shuttering,laying concrete ,vibrating,curing etc for Column footings
Supply and placing of the M25 design mix concrete corresponding to IS -456 using MIXER using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including ,sales and other taxes on all materials including all operational ,incidental and labour charges such as weigh batching ,machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work (APSS NO 402) with minimum cement content as per IS Code from standard suppliers approved by the deparment including pumping , centering,shuttering,laying concrete ,vibrating,curing etc for Pedestals
Supply and placing of the M25 design mix concrete corresponding to IS -456 using MIXER using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including ,sales and other taxes on all materials including all operational ,incidental and labour charges such as weigh batching ,machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work (APSS NO 402) with minimum cement content as per IS Code from standard suppliers approved by the deparment including pumping , centering,shuttering,laying concrete ,vibrating,curing etc for Columns
Supply and placing of the M25 design mix concrete corresponding to IS -456 using MIXER using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including ,sales and other taxes on all materials including all operational ,incidental and labour charges such as weigh batching ,machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work (APSS NO 402) with minimum cement content as per IS Code from standard suppliers approved by the deparment including pumping , centering,shuttering,laying concrete ,vibrating,curing etc for Plinth beam
Supply and placing of the M25 design mix concrete corresponding to IS -456 using MIXER using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including ,sales and other taxes on all materials including all operational ,incidental and labour charges such as weigh batching ,machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work (APSS NO 402) with minimum cement content as per IS Code from standard suppliers approved by the deparment including pumping , centering,shuttering,laying concrete ,vibrating,curing etc for Lintel beams
Supply and placing of the M25 design mix concrete corresponding to IS -456 using MIXER using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including ,sales and other taxes on all materials including all operational ,incidental and labour charges such as weigh batching ,machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work (APSS NO 402) with minimum cement content as per IS Code from standard suppliers approved by the deparment including pumping , centering,shuttering,laying concrete ,vibrating,curing etc for Roof Beams
Supply and placing of the M25 design mix concrete corresponding to IS -456 using MIXER using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including ,sales and other taxes on all materials including all operational ,incidental and labour charges such as weigh batching ,machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work (APSS NO 402) with minimum cement content as per IS Code from standard suppliers approved by the deparment including pumping , centering,shuttering,laying concrete ,vibrating,curing etc for Roof slab 0.125m thick,
Supply and placing of the M25 design mix concrete corresponding to IS -456 using MIXER using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including ,sales and other taxes on all materials including all operational ,incidental and labour charges such as weigh batching ,machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work (APSS NO 402) with minimum cement content as per IS Code from standard suppliers approved by the deparment including pumping , centering,shuttering,laying concrete ,vibrating,curing etc for Sunshades
Brick work in CM 1:6 mix using 2nd class ordinary clay bricks as per table of IS 1077-1992 Non-Modularof traditional size 23x11x7cm brought from approved kilns including cost and conveyance of all materials and all labour charges ,curing for 21 days scaffolding charges, lifting charges, other incidental charge etc., complete and as per ss and as directed by the departmental officer in charge of work.As follows - Ground Floor
Brick work in CM 1:6 mix using 2nd class ordinary clay bricks as per table of IS 1077-1992 Non-Modularof traditional size 23x11x7cm brought from approved kilns including cost and conveyance of all materials and all labour charges ,curing for 21 days scaffolding charges, lifting charges, other incidental charge etc., complete and as First Floor peropet wall
Plastering with CM (1:5) 12mm thick including cost and conveyance of all materials at site, seignorage charges and labour charges for mixing of mortar, plastering and curing scaffolding , lifting,other incidental charges etc., complete as per S.S as per ss and as directed by the departmental officer in charge of work - Ground Floor
Plastering with CM (1:5) 12mm thick including cost and conveyance of all materials at site, seignorage charges and labour charges for mixing of mortar, plastering and curing scaffolding , lifting,other incidental charges etc., complete as per S.S as per ss and as directed by the departmental officer in charge of work - First Floor
Plastering with CM (1:3) 12mm thick including cost and conveyance of all materials at site, seignorage charges and labour charges for mixing of mortar, plastering and curing scaffolding , lifting,other incidental charges etc., complete as per S.S as per ss and as directed by the departmental officer in charge of work for ceiling
Plastering with CM (1:3) 20mm thick including cost and conveyance of all materials at site, seignorage charges and labour charges for mixing of mortar, plastering and curing scaffolding , lifting,other incidental charges etc., complete as per S.S as per ss and as directed by the departmental officer in charge of work flooring
Painting Walls with Snowcem or other equal and approved Water Proof Cement Paint 2 Coats (All Colours) over a base coat of aproved cement primer making 3 coats in total including cost of all , conveyance charges of materials and other incidental charges, scaffolding, lifting and as directed by the departmental officer in charge of work
Supply & fixing of Rolling shutter made of 80 x 1.25 mm machine rolled CRCA laths, interlocked together through their entire length and jointed together at the ends by end-locks, mounted on specially designed pipe shaft of 50mm dia nominal bore MS B class pipe with brackets, plates, guide channels, stoppers, bottom locking plates and arrangements for inside & outside locking with push-pull operations including cost of hood cover and springs complete, painted with one coat of approved steel primer, locks, ball bearings, all accessories etc complete for finished item of work as per special spn: 1108 and other incidental charges etc., complete as directed by the departmental offincer in charge of work
Supply and fixing Aluminium Anodised Two/ Three Track Sliding Windows AS SIZE 1.50m X 1.20m as per approved drawing with aluminium anodised sections of Series C Jindal sections and outer frame top horizontals & both verticals of 8774 of size 62 x 29.5 mm and bottom horizontal - two track frame of 8773 of size 62 x 29.5 mm, Shutter frame top, bottom and verticals of 8304 of size 50 mm x 20 mm and Weather interlocking frame of 8306 of size 50 x 20 with plain clear float glass 5 mm thick fixed including supply and fixing aluminium handles of 100 mm for each shutter, nylon rollers assembly and all labour charges for fixing the fixtures with required no.of screws, bolts and nuts and including labour charges for fixing the frame in position, fixing shutter to frame other incidental charge and etc. completed for finished item of work
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 500/500D grade) of different diameters for RCC works, including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying including and other all materials etc., complete for finished item of work in all floors. as per SS and as directed by the departmental office incharge of work.
Supply and delivery and fixing in position M S grill of any design including all fabrication and all fixing charges and other incidental charges power charges welding rod etc complete as per ss and as directed by the dept authorities
Painting two coats with synthetic enamel paint 1st quality over a base coat of red oxide. The rate includeds cost and conveyance of all materilas at site, labour charges, scaffolding charges lifting,cost of brushes, other incidental charges etc., complete as directed by the departmental authorities (APDSS No:1201) For Rolling shuttering in pump house.
Supply and fixing of 50mm thick pre-cast Cement Jollys of approved design including cost and conveyance to work spot and all labour charges for fixing in position etc.complete as per S.S and as directed by the departmental officer in charge of work.
Manufacture, Supply and Delivery of 110mm dia 6 kg/cm Unplasticised PVCs Pipes for potable water supplies conforming to IS : 4985/2000 (3rd revision) with bell ends (Socket) as per specification in light Grey/Natural Ivory Grey/ Any other Color (except White) inclusive of transportation to the sub-divisional stores anywhere in AP in cluding all taxes. - 110 mm dia.This rate including cost of material , all labour charges,necessary fixing, other incidental charge. etc.complete as per S.S and as directed by the departmental officer in charge of work
Supply and fixing of 25 mm dia 2.00 mm thick PVC pipe concealed in roof slab with all required accessories including masonary work all labour chages complete as per IE Rules and as directed by the departmental officer incharge of work
Supply and fixing of 20 mm dia 1.50 mm thick PVC pipe concealed in walls with all required accessories including masonary work for light , fan and plug point with metal deep box including all labour chages complete as per IE Rules and as directed by the departmental officer incharge of work
Wiring with 2 runs 14/0.3 mm. (1.0. sq.mm) Fire retardant PVC insulated Flexible copper cable in existing pipe with 6A siwtch, ceiling rose and 3 mm thick hyla sheet covering to switch control box including all labour charges etc,., complete for light, bell , fan and exhaust fan points in non - residential building as per IE Rules and as directed by the departmental officer incharge of work
Wiring with 2 runs 14/0.3 mm. (1.0. sq.mm) Fire retardant PVC insulated Flexible copper cable in existing pipe with 6A modular siwtch control and 3/2 pin sockets fixing on board including all labour charges complete as per IE Rules and as directed by the departmental officer incharge of work
supply and run of 2 of 36/0.3 mm. (1.5. sq.mm) Fire retardant PVC insulated Flexible copper cable in existing pipe for mains including all labour charges complete as per IE Rules and as directed by the departmental officer incharge of work
supply and run of 1 of 14/0.3 mm. (1.0. sq.mm) Fire retardant PVC insulated Flexible copper cable in existing pipe for earth continuity including all labour charges etc. complete as per IE Rules and as directed by the departmental officer incharge of work
supply and run of 2 of 6 sq.mm (7/18) WPSC alluminium cable along with No.10 SWG G.I barer wire through PVC cleats with all accessories including all labour charges etc., complete as per IE Rules and as directed by the departmental officer incharge of work
Providing independent earthing by excavating a trench to a depth of 2.10m in all soils, as per size specied in data ,using 40 mm dia B class GI pipe 2.50m long with necessary accessories with hume pipe ring duly providing staggered holes including filling with equal proportion of salt and charcoal in layers and all labour charges etc complete complete as per IE Rules and as directed by the departmental officer incharge of work
S&F of SPN distrubution board with IP 42 protection (metal door) suitable for 3 phase ELCB-RCCB-FP isolator as incomer and 10 KA SP MCBS as out going including internal connection and labour charges for surface-flush mounting etc -- 63 A FP isolator-1 no for incomer,6-32A SP MCBS -18 Nos for out going complete as per IE Rules and as directed by the departmental officer incharge of work
Supply of 48" (1200mm) Sweep 5 star rated Ceiling Fan , with double ball bearings, air delivery more than 200 cubic meter/min but without Regulator.Makes : Crompton HS Plus / Havells ES Neo/Orient Energy Star/ Halonix(Zephyr)/Polycab(Synergy Star) unit each complete as per IE Rules and as directed by the departmental officer incharge of work
Supply of stepped type Electronic Regulator of Makes: GM G Home / Gold Medal Olive / Million Zoom / Great white Omega/Koncept/Vimal opel/ Anchor/Vihan/CPL complete as per IE Rules and as directed by the departmental officer incharge of work
Supply of 9" (225mm), Light duty exhaust fan with double ball bearing and wire guard etc complete. Makes: Crompton / Bajaj Bahar WG / Havells Ventil Air-DS / Orient hill air / MIIT complete as per IE Rules and as directed by the departmental officer incharge of work
Supply of 20 W Box type tube light luminaire powder coated CRCA sheet steel housing with Electronic Ballast Chokes and all standard accessoriesof makes Wipro / G.E. / Phillips / Crompton / Bajaj. complete as per IE Rules and as directed by the departmental officer incharge of work
Supply, delivery and erection of 5 tonnes capacity double girder gantry arrangements to move and lift the installations of the pump house one way with required MS ISMB of best quality 250 x 100 mm of standard make, including the required MS ISMC, MS angular iron, 5 tonne capacity travelling trolley and 5 tonne capacity chain pulley block with chains of suitable capacity for lifting and moving arrangements to length of 10.00 m rate is inclusive of the cost of materials, labour charges, site welding etc.,complete as per ss and as direceted by the departmental officer incharge of work
Supply and erection of 3# X 26.11 KW of CF Pumpsets Each with a duty of 50 LPS and a total head of 38m ( Two simultaneous working ane stand bye) to various proposed and existing ELSRs
Supply and erection of 3# CF Pumpsets Each with a duty of 50 LPS and a total head of 38m ( Two simultaneous working ane stand bye) to various proposed and existing ELSRs
Supply, delivery and erection of 3# of 26.11Kw electrically driven horizontal foot mounted heavy duty ball bearing type C.F clear water pump sets. The pump should be fitted with S.S / Bronze impiller, S.S shaft as per IS spesification with casing of heavy duty and gland packing capable of discharging of 35 LPS at total head of 38.00m. operated at required RPM coupled for operation on combined variation of +/-10% AC Supply. Motor with Class ‘F” insulation and suitable for ambient tempareture up to 500 C S1 duty continuous rated and performance in general conform to IS325. The rate including all taxes and duties etc.complete with suction, delivery arrengements,DI valves,DI and MS specials,gauges,panel board for motors, capacitors, startes, earthening arrengements, change over switch,bed blocks under pumps,valves,suitable cables etc complete for finished item of work..
Supply, delivery and erection of 5 tonnes capacity double girder gantry arrangements to move and lift the installations of the pump house one way with required MS ISMB of best quality 250 x 100 mm of standard make, including the required MS ISMC, MS angular iron, 5 tonne capacity travelling trolley and 5 tonne capacity chain pulley block with chains of suitable capacity for lifting and moving arrangements to length of 10.00 m rate is inclusive of the cost of materials, labour charges, site welding etc., (Mandatory if required) All Civil Works Such as anchor Blocks ,Thrust Blocks, Platform for Pannel Board and Cable trench etc Complete as directed by the Field Engineer Testing and maintanance of the complete equipment covered and trial run for 30 days at 8 hours per day after completion of errection
Construction wash water recirculation sump at WTP
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH for foundations upto 3.00m depth Note : Classifications of Earth Work Specification are as per 302.2.1(a) of MORD and 301.2.1 of MORT&H--ordinary soil-- upto 3m depth_ Mechanical means up to 3 metres depth in ordinary soils
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH for foundations upto 3.00m depth Note : Classifications of Earth Work Specification are as per 302.2.1(a) of MORD and 301.2.1 of MORT&H--ordinary soil-- upto 3m depth_ Mechanical means 3 to 6 metres depth in ordinary soils
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH for foundations upto 3.00m depth Note : Classifications of Earth Work Specification are as per 302.2.1(a) of MORD and 301.2.1 of MORT&H--ordinary soil-- upto 3m depth_ Manual means 3 to 6 metres depth in ordinary soils
Filling Sand for foundation for recirculation sump house as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH.This rate including cost of sand ,filling charges,watering,ramming,and other incidental charges etc., complete as per ss and directed by the departmental officer incharge of work
Plain Cement Concrete (1:4:8) (cement: fine aggregate: Coarse aggregate) using coarse aggregate 40mm size hard, machine crushed granite from approved quarry using concrete Mixer 10 / 7 cft (0.2 / 0.8 cum) capacity including cost and conveyance of all materials like cement, sand, coarse aggregate, water etc. to site including all charges for machine mixing and hire charges of concrete mixer, laying concrete finishing top surface to the required level curing etc., and complete for finished item of work as per SS and as directed by the departmental officer incharge of work. (APSS No. 402).for recirculation sump
Supply and placing of the M30 design mix concrete corresponding to IS -456 using /MIXER using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including , all materials including all operational ,incidental and labour charges such as ,machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work (APSS NO 402) with minimum cement content as per IS Code from standard suppliers approved by the deparment including pumping , centering,shuttering,laying concrete ,vibrating,curing etc., complete and as per ss and as directed by the departmental officer in charge of work - Raft
Supply and placing of the M30 design mix concrete corresponding to IS -456 using /MIXER using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including , all materials including all operational ,incidental and labour charges such as ,machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work (APSS NO 402) with minimum cement content as per IS Code from standard suppliers approved by the deparment including pumping , centering,shuttering,laying concrete ,vibrating,curing etc., complete and as per ss and as directed by the departmental officer in charge of work - For side walls circular 0.30m thick below GL
Supply and placing of the M30 design mix concrete corresponding to IS -456 using /MIXER using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including , all materials including all operational ,incidental and labour charges such as ,machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work (APSS NO 402) with minimum cement content as per IS Code from standard suppliers approved by the deparment including pumping , centering,shuttering,laying concrete ,vibrating,curing etc., complete and as per ss and as directed by the departmental officer in charge of work - For side walls circular 0.30m thick above GL
Supply and placing of the M30 design mix concrete corresponding to IS -456 using /MIXER using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including , all materials including all operational ,incidental and labour charges such as ,machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work (APSS NO 402) with minimum cement content as per IS Code from standard suppliers approved by the deparment including pumping , centering,shuttering,laying concrete ,vibrating,curing etc., complete and as per ss and as directed by the departmental officer in charge of work - For Columns
Supply and placing of the M30 design mix concrete corresponding to IS -456 using /MIXER using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including , all materials including all operational ,incidental and labour charges such as ,machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work (APSS NO 402) with minimum cement content as per IS Code from standard suppliers approved by the deparment including pumping , centering,shuttering,laying concrete ,vibrating,curing etc., complete and as per ss and as directed by the departmental officer in charge of work - For Roof beams
Supply and placing of the M30 design mix concrete corresponding to IS -456 using /MIXER using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including , all materials including all operational ,incidental and labour charges such as ,machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work (APSS NO 402) with minimum cement content as per IS Code from standard suppliers approved by the deparment including pumping , centering,shuttering,laying concrete ,vibrating,curing etc., complete and as per ss and as directed by the departmental officer in charge of work - For Roof slab 0.15m thick
Supply and placing of the M30 design mix concrete corresponding to IS -456 using /MIXER using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including , all materials including all operational ,incidental and labour charges such as ,machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work (APSS NO 402) with minimum cement content as per IS Code from standard suppliers approved by the deparment including pumping , centering,shuttering,laying concrete ,vibrating,curing etc., complete and as per ss and as directed by the departmental officer in charge of work - For Roof dome slab 0.15m thick
Providing impervious coat to exposed RCC roof slab surface with CM(1:3), 20mm thick with 1kg of water proof compound per bag of cement laid over roof when it is green including cost of all materials, seigniorage charges, including conveyance charges of materials and including all operational, incidental and labour charges for mixing mortar, laying, rendering smooth and thread lining, curing, rounding off junctions of wall and slab etc,, complete as per ss and as directed by the departmntal officer in charge of work.
Painting Walls with Snowcem or other equal and approved Water Proof Cement Paint 2 Coats (All Colours) over a base coat of aproved cement primer making 3 coats in total including cost of all , conveyance charges of materials and other incidental charges, scaffolding, lifting and as directed by the departmental officer in charge of work
Supply and delivery and fixing in position M S ladder and manhole cover of any design including all fabrication and all fixing charges and other incidental charges power charges welding rod etc complete as per ss and as directed by the dept authorities
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 500/500D grade) of different diameters for RCC works, including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying including and other all materials etc., complete for finished item of work in all floors. as per SS and as directed by the departmental office incharge of work.
Construction of R.C.C. railing of M 25 grade in cast-in-situ with 20 mm nominal size aggregate, true to line and grade, tolerance of vertical railing post not to exceed 1 in 500, centre-to-centre spacing between vertical posts not to exceed 2000 mm as per drawing and technical specifications Clauses 800, 900 and 1208.3 MORD. This rate including cost of material, all lanbour charges, scaffolding charge , vibrating, watering, hand rail in 3stires including HYSD bar reinforcement as par ss and as directed by the departmental officer in charge of work.
Laying of 100 mm dia . DI K9 Pumping mains from wash water sump at HWW to Areator
Earth work excavation in all soils up to SDR & stone matrix by machinery for Pipe lines as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and back filling in trenches with excavated suitable material as per Technical Specification No.305 MORD/304 MORTH up to initial lift of 3.00m. For Pipe line trenches - Mechanical Means
Earth work excavation in all soils up to SDR & stone matrix by machinery for Pipe lines as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and back filling in trenches with excavated suitable material as per Technical Specification No.305 MORD/304 MORTH up to initial lift of 3.00m. For Pipe line trenches - Manual Means
Manufacture supply delivery,of 100mm dia K9 centrifugally cast (spun) ductile iron pipes for water with Socket spigot ends confirming to IS NO 8329/2000 in standard lengths of 4.00,5.00,5.50,6.00m suitable for push-on-joint (rubber gasket D jointing) with cement mortor lining inside and zinc coating out side (K9) including transportation ,loading,unloading,transmit risk stacking, etc complete and as directed by the departmental officer in charge of work.
Supply and delivery of 100mmdia DI K9 1.00m long Centrifugally cast (SPUN) ductile iron pressure pipes with flanged ends for water, gas and sewage conforming to I.S, 8329/2000 in standard working lengths of 4, 5, 5.5 & 6 meter for classification K9 suitable for push on joint (Rubber gasket and jointing) with cement mortar lining inside the pipes with outside zinc coating, rates are , including transportion and transportation ,loading,unloading,transmit risk stacking, etc complete and as directed by the departmental officer in charge of work
Supply and delivery of Centrifugally cast (spun) Ductile Iron Fittings up to 500mm dia of DI double socket branch flange Tee, DI All Socket Tees, DI Double socket Tapers (Reducer), DI Flanged Socket, DI Flanged Spigot, DI Double Socket Duck Foot Bend, DI Double Flange Duck/Foot bend, DI All socket Cross, DI All Flange Tee, DI All Flange Cross, DI Double Flange Reducer, Blank Flange, Mechanical Joints, DI Double Socket Bends, DI Double Flanged Bends and DI Manhole Frame & cover conforming to IS:9523/2000 having dimensions Up to 500 The rates mentioned here under are for fittings, zinc coated externally with inside mortar lining (with finishing as per class 13/IS 9523/2000) ( ex-works) including Transportation . etc., complete as per ss and as directed by the departmental officer incharge of work.
Lowering of 100mm dia DI k9 D.I. socket and spigot Pipes and fittings carefully in to the trench and laying them true to alignment and gradient including all labour charges, sundries and other incidental charges as per BIS No. 3114/85 etc., complete as per S.S and as directed by the departmental officer in charge of work.
Jointing of 100mm dia D.I. Pipes & fittings with Rubber Gasket including all sundries filling with water with a water lead up to 500m and testing to required pressure including cost of jointing material Gasket, all labour charges other incedintal charges etc., complete as per BISNo.3114/85 and as directed by the departmental officer in charge of work.
Supply and delivery of 100 mm dia "Resilient Seated Soft Sealing" Gate Valves (Sluice Valves) PN 1.6(Mpa) with Body and Bonnet of Ductile Iron GGG-40/SG-400/15 or GGG-50/SG-500/7 or Equivalent as per IS1865, IS:3896-2 and Wedge fully Rubber Lined with food grade quality grade W270 grade EPDM, Replaceable Spindle Nut without gland packing with 3-O ring protection system on the Shaft and Seals of NBR. The Valves should be Vacuum tight and 100% leak proof with face to face dimensions as BS:5163 Type A/IS:14846. All the valves should be with fusion bonded Electrostatic Powder coating both inside and outside (Min 250 Microns)- RAL 5005 with Pocket Less Straight through body Passage conforming to Design standards of DIN-3202F4/BS:5163 Type A Flange drilling as per IS - 1538 and transportation and other incidental charges etc,as per ss and as directed by the departmental officer incharge of work
Supply, Delivery of 100mm dia D.I Double Flanged Swing Check type Reflux valves 100mm dia PN1.6(Mpa) (Non Return Valves) of following dia. conforming to IS- 5312 (Pts-1&2) (with amendments up to date, if any) having Body, Cover, Door, Bearing holder with D.I; Hinge pin, Door pin, Door suspension pin with Stainless Steel (IS 6603); Body seat ring , Door face ring, Bearing bushes, Plugs for hinge pin with Leaded Tin Bronze ( IS 318 ); Bolts, Nuts with Carbon steel; Gaskets with Rubber; Hinges with Cast steel; including transportation etc., complete as per ss and as directed by the departmental officer in charge of work.
Labour charges for lowering and keeping in position of100mm dia DI Sluice valves(with cap/with hand wheel), reflux valves and scour valves.This rate including cost of all labour charges, other incidental charges etc complete and as directed by the departmental officer in charge of work.
Lowering the 500 mm dia, D.I. Pipes of all classes and fittings with flanged ends carefully into the trenches and laying them true to alignment and gradient including all sundries,and other incidental charges etc complete as per ss and as directed by the departmental officer in charge of work.
Lowering the 100 mm dia, D.I. Pipes of all classes and fittings with flanged ends carefully into the trenches and laying them true to alignment and gradient including all sundries,and other incidental charges etc complete as per ss and as directed by the departmental officer in charge of work.
Jointing of 500mm dia the D.I. Pipes, fittings and valves with flanged ends including cost of jointing materials such as bolts, nuts, rubber insertion, white lead including all sundries,hiring of machinery ,all labour charges,and filling with water with a water lead upto 500 m and testing to required pressure and other incidental charges etc, complete as per ss and as directed by the departmental officer incharge of work( BIS No.3114/85) - 500mm dia
Jointing of 250mm dia the D.I. Pipes, fittings and valves with flanged ends including cost of jointing materials such as bolts, nuts, rubber insertion, white lead including all sundries,hiring of machinery ,all labour charges,and filling with water with a water lead upto 500 m and testing to required pressure and other incidental charges etc, complete as per ss and as directed by the departmental officer incharge of work( BIS No.3114/85) - 250mm dia
Jointing of 100mm dia the D.I. Pipes, fittings and valves with flanged ends including cost of jointing materials such as bolts, nuts, rubber insertion, white lead including all sundries,hiring of machinery ,all labour charges,and filling with water with a water lead upto 500 m and testing to required pressure and other incidental charges etc, complete as per ss and as directed by the departmental officer incharge of work( BIS No.3114/85) - 100mm dia
RCC M-20 Nominal mix (cement,fine aggregate,coarse aggregate) corresponding to Table -9 of IS -456 using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including on all materials including all operational ,incidental and labour charges such as machine mixing ,laying concrete ,curing scaffolding , shuttering etc complete but excluding cost of steel and its fabrication charges for finished item of work,as per ss and as directed by the departmental officer in charge of work.for thrust blocks
Construction Valve Chambers above 350mm dia Sluice Valve Earthwork in excavation for valve chamber as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH Note : Classifications of Earth Work Specification are as per 302.2.1(a) of MORD and 301.2.1 of MORT&H--ordinary soil--manual means upto 3m depth manual means
Filling Sand for foundation of Valve Chamber as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH.This rate including cost of sand ,filling charges,watering,ramming,and other incidental charges etc., complete as per ss and directed by the departmental officer incharge of work
Plain Cement Concrete for Vlave Chamber (1:4:8) (cement: fine aggregate: Coarse aggregate) using coarse aggregate 40mm size hard, machine crushed granite from approved quarry using concrete Mixer 10 / 7 cft (0.2 / 0.8 cum) capacity including cost and conveyance of all materials like cement, sand, coarse aggregate, water etc. to site including all charges for machine mixing and hire charges of concrete mixer, laying concrete finishing top surface to the required level curing etc., and complete for finished item of work as per SS and as directed by the departmental officer incharge of work. (APSS No. 402).for Valve Chamber bed concrete
RCC M-20 Nominal mix for Valve Chamber (cement,fine aggregate,coarse aggregate) corresponding to Table -9 of IS -456 using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and on all materials including all operational ,incidental and labour charges such as machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work,but including centering, shuttering and as directed by the departmental officer incharge of work as follows For Bottom Slab
RCC M-20 Nominal mix for Valve Chamber (cement,fine aggregate,coarse aggregate) corresponding to Table -9 of IS -456 using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and on all materials including all operational ,incidental and labour charges such as machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work,but including centering, shuttering and as directed by the departmental officer incharge of work as follows For Side walls allround
RCC M-20 Nominal mix (cement,fine aggregate,coarse aggregate) corresponding to Table -9 of IS -456 using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and on all materials including all operational ,incidental and labour charges such as machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work,but including centering, shuttering and as directed by the departmental officer incharge of work for Pre cast slabs
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying etc., complete for finished item of work in all floors.( APSS No.126) for pre cast slabs of culverts - RBR-FNDN-8 & Revised Data sl.No-5
Manufacture, Supply and delivery of 100mm CI. Dismantling Joints with both side flange end suitable for installation in between flange end pipes. Thickness as per IS: 7322. Thise rates is including cost of materials, transportation charges, other incidental charges etc complete as per ss and as directed by the departmental officer in charge of work
Supply and erection of 2# of 1.87KW(2.50HP) CF Pumpsets each with a duty of 12 LPS and a total head of 11m ( one working and one stand bye) for pumping wash waterto Areatorm for recirculation
Supply and erection of 2# of CF Pumpsets each with a duty of 7 LPS and a total hed of 11m ( one working and one stand bye) for pumping wash waterto Areatorm for recurculation
Supply, delivery and erection of 2# of 1.87Kw electrically driven horizontal foot mounted heavy duty ball bearing type C.F clear water pump sets. The pump should be fitted with S.S / Bronze impiller, S.S shaft as per IS spesification with casing of heavy duty and gland packing capable of discharging of 35 LPS at total head of 38.00m. operated at required RPM coupled for operation on combined variation of +/-10% AC Supply. Motor with Class ‘F” insulation and suitable for ambient tempareture up to 500 C S1 duty continuous rated and performance in general conform to IS325. The rate including all taxes and duties etc.complete with suction, delivery arrengements,DI valves,DI and MS specials,gauges,panel board for motors, capacitors, startes, earthening arrengements, change over switch,bed blocks under pumps,valves,suitable cables etc complete for finished item of work..
Supply, delivery and erection of 5 tonnes capacity double girder gantry arrangements to move and lift the installations of the pump house one way with required MS ISMB of best quality 250 x 100 mm of standard make, including the required MS ISMC, MS angular iron, 5 tonne capacity travelling trolley and 5 tonne capacity chain pulley block with chains of suitable capacity for lifting and moving arrangements to length of 10.00 m rate is inclusive of the cost of materials, labour charges, site welding etc., (Mandatory if required) All Civil Works Such as anchor Blocks ,Thrust Blocks, Platform for Pannel Board and Cable trench etc Complete as directed by the Field Engineer Testing and maintanance of the complete equipment covered and trial run for 30 days at 8 hours per day after completion of errection
Construction of electrician / operator/watchman quarters at HWW - 2 Nos
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD - Mechanical means up to 3 metres depth in ordinary soil
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD - Manual means up to 3 metres depth in ordinary soil
Filling Sand in foundation of the building as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH This rate including cost of material all labour charges etc complete and as per ss and as direacted by the departmental officer incharge of work.
Plain Cement Concrete (1:4:8) (cement: fine aggregate: Coarse aggregate) using coarse aggregate 40mm size hard, machine crushed granite from approved quarry using concrete Mixer including cost and conveyance of all materials like cement, sand, coarse aggregate, water etc. to site including all charges for machine mixing and hire charges of concrete mixer, laying concrete finishing top surface to the required level curing for finished item of work as per SS and as directed by the departmental officer incharge of work.
RCC M- 25 Design mix corresponding to Table 9 of IS 456 using 20mm size graded machine crushed hard granite metal (coarse aggregate) from approved quarry including cost and conveyance of all materials like cement, fine aggregate (sand) coarse aggregate, water etc., to site and including on all materials including all operational, incidental and labour charges such as machine mixing, laying concrete, curing centering,scaffolding , vibrating etc.,complete but excluding cost of steel and its fabrication charges for finished item of work, and other incidental charges etc., complete and as per ss and as direacted by the departmental officer incharge of work. for Column Footings
RCC M- 25 Design mix corresponding to Table 9 of IS 456 using 20mm size graded machine crushed hard granite metal (coarse aggregate) from approved quarry including cost and conveyance of all materials like cement, fine aggregate (sand) coarse aggregate, water etc., to site and including on all materials including all operational, incidental and labour charges such as machine mixing, laying concrete, curing centering,scaffolding , vibrating etc.,complete but excluding cost of steel and its fabrication charges for finished item of work, and other incidental charges etc., complete and as per ss and as direacted by the departmental officer incharge of work. for Columns
RCC M- 25 Design mix corresponding to Table 9 of IS 456 using 20mm size graded machine crushed hard granite metal (coarse aggregate) from approved quarry including cost and conveyance of all materials like cement, fine aggregate (sand) coarse aggregate, water etc., to site and including on all materials including all operational, incidental and labour charges such as machine mixing, laying concrete, curing centering,scaffolding , vibrating etc.,complete but excluding cost of steel and its fabrication charges for finished item of work, and other incidental charges etc., complete and as per ss and as direacted by the departmental officer incharge of work. As follows for Plinth beam
RCC M- 25 Design mix corresponding to Table 9 of IS 456 using 20mm size graded machine crushed hard granite metal (coarse aggregate) from approved quarry including cost and conveyance of all materials like cement, fine aggregate (sand) coarse aggregate, water etc., to site and including on all materials including all operational, incidental and labour charges such as machine mixing, laying concrete, curing centering,scaffolding , vibrating etc.,complete but excluding cost of steel and its fabrication charges for finished item of work, and other incidental charges etc., complete and as per ss and as direacted by the departmental officer incharge of work. As follows for Lintel Beam
RCC M- 25 Design mix corresponding to Table 9 of IS 456 using 20mm size graded machine crushed hard granite metal (coarse aggregate) from approved quarry including cost and conveyance of all materials like cement, fine aggregate (sand) coarse aggregate, water etc., to site and including on all materials including all operational, incidental and labour charges such as machine mixing, laying concrete, curing centering,scaffolding , vibrating etc.,complete but excluding cost of steel and its fabrication charges for finished item of work, and other incidental charges etc., complete and as per ss and as direacted by the departmental officer incharge of work. As follows for Roof Beam
RCC M- 25 Design mix corresponding to Table 9 of IS 456 using 20mm size graded machine crushed hard granite metal (coarse aggregate) from approved quarry including cost and conveyance of all materials like cement, fine aggregate (sand) coarse aggregate, water etc., to site and including on all materials including all operational, incidental and labour charges such as machine mixing, laying concrete, curing centering,scaffolding , vibrating etc.,complete but excluding cost of steel and its fabrication charges for finished item of work, and other incidental charges etc., complete and as per ss and as direacted by the departmental officer incharge of work. As follows for Roof slab 0.125m thick with 0.30m cxtension all sides
RCC M- 25 Design mix corresponding to Table 9 of IS 456 using 20mm size graded machine crushed hard granite metal (coarse aggregate) from approved quarry including cost and conveyance of all materials like cement, fine aggregate (sand) coarse aggregate, water etc., to site and including on all materials including all operational, incidental and labour charges such as machine mixing, laying concrete, curing centering,scaffolding , vibrating etc.,complete but excluding cost of steel and its fabrication charges for finished item of work, and other incidental charges etc., complete and as per ss and as direacted by the departmental officer incharge of work. for Sunshade
RCC M- 25 Design mix corresponding to Table 9 of IS 456 using 20mm size graded machine crushed hard granite metal (coarse aggregate) from approved quarry including cost and conveyance of all materials like cement, fine aggregate (sand) coarse aggregate, water etc., to site and including on all materials including all operational, incidental and labour charges such as machine mixing, laying concrete, curing centering,scaffolding , vibrating etc.,complete but excluding cost of steel and its fabrication charges for finished item of work, and other incidental charges etc., complete and as per ss and as direacted by the departmental officer incharge of work. for Loft slab 0.075m thick kitchen
Brick masonary in CM (1:6) using 2nd class bricks of size 23 x 11 x 7cms. Cost including cost and conveyance of all materials at site, labour charges for curing , scaffolding, all lifts, other incidental charges etc.,Complete as per SS and as directed by the departmental officer incharge of work.
Plastering with CM (1:5) 12mm thick including cost and conveyance of all materials at site, and labour charges for mixing of mortar, plastering and curing scaffolding , lifting,smooth finishings etc., complete as per S.S and as directed by the departmental departmental officer incharge of work. out side & inside of the two quarters
Plastering with CM (1:3) 12mm thick including cost and conveyance of all materials at site labour charges for finishing and curing scafoolding, lifting, smooth,finishing,other incidental charges etc., complete as per S.S as per ss and as directed by the departmental officer in charge of work for walls out side & inside above 3.5 m Height
Painting Walls with Snowcem or other equal and approved Water Proof Cement Paint 2 Coats (All Colours) over a base coat of aproved cement primer making 3 coats in total including cost of all , conveyance charges of materials and other incidental charges, scaffolding, lifting and as directed by the departmental officer in charge of work
Supply and fixing of 50mm thick pre-cast Cement Jollys of approved design including cost and conveyance to work spot and all labour charges for fixing in position etc.complete as per S.S and as directed by the departmental officer in charge of work.
Supply and fixing Aluminium Anodized Doors - Single Shutter of size 1.20 x2.10m as per approved drawing with aluminium anodized sections of Jindal or approved equivalent make sections and outer frame top horizontals & both verticals of 2408 of size 101.6 x 44.75 of specified thickness Shutter frame top, bottom and verticals of 4504 of size 44.45 mm x 47.62 mm of specified thickness and Middle lock rail of 4621 of size 49.91 x 44.45 x 3 mm with plain clear float glass 5 mm thick fixed including supply and fixing aluminium handles of 100 mm for each shutter, floor springs/ hydraulic door closure assembly and all labour charges for fixing the fixtures with required no. of screws, bolts and nuts and including labour charges for fixing the frame in position, fixing shutter to frame etc. completed for finished item of work - Door -D - 1.20X2.10 m
Supply and fixing Aluminium Anodized Doors - Single Shutter of size 1.00 x 2.10as per approved drawing with aluminium anodized sections of Jindal or approved equivalent make sections and outer frame top horizontals & both verticals of 2408 of size 101.6 x 44.75 of specified thickness Shutter frame top, bottom and verticals of 4504 of size 44.45 mm x 47.62 mm of specified thickness and Middle lock rail of 4621 of size 49.91 x 44.45 x 3 mm with plain clear float glass 5 mm thick fixed including supply and fixing aluminium handles of 100 mm for each shutter, floor springs/ hydraulic door closure assembly and all labour charges for fixing the fixtures with required no. of screws, bolts and nuts and including labour charges for fixing the frame in position, fixing shutter to frame etc. completed for finished item of work - doors D1 - 1.0X2.10m
Supply and fixing Aluminium Anodized Two/ Three Track Sliding Windows of size 1.20 x 1.20m as per approved drawing with aluminium anodized sections of Series C Jindal or approved equivalent make sections and outer frame top horizontals & both verticals of 8774 of size 62 x 29.5 mm and bottom horizontal - two track frame of 8773 of size 62 x 29.5 mm, Shutter frame top, bottom and verticals of 8304 of size 50 mm x 20 mm and Weather interlocking frame of 8306 of size 50 x 20 with plain clear float glass 5 mm thick fixed including supply and fixing aluminium handles of 100 mm for each shutter, nylon rollers assembly and all labour charges for fixing the fixtures with required no. of screws, bolts and nuts and including labour charges for fixing the frame in position, fixing shutter to frame etc. completed for finished item of work
Providing and fixing factory made polyvinyl chloride (PVC) Door Frame of the size 50 x 47mm with a wall thickness of 5mm, made out of extruded 5mm rigid PVC foam sheet, mitre cut at two corners and joined with 2nos. of 150mm long brackets of 15x15mm M.S. square tube. The two vertical door profiles are to be reinforced with 19x19mm M.S. Square tube of 19 gauge. The door frame shall be fixed to the wall using 65/100mm long M.S. Screws through the frame by using PVC fasteners. A minimum of 4nos. of screws to be provided for each vertical member & minimum 2nos. for horizontal member etc. complete as per manufacturers specification and direction of Engineer-in-Charge for finished item of work. This rate including cost of material , all labour charges,necessary fixing, other incidental charge. etc.complete as per S.S and as directed by the departmental officer in charge of work
Providing and fixing 30mm thick Solid panel PVC door shutter consisting of frame made out of M.S. tubes of 19 gauge thickness and size of 19mm x 19mm for stiles, & 15mm x 15mm for top & bottom rails. M.S. frame shall have a coat of steel primers of approved make and manufacture. M.S. frame shall be covered with 5mm thick heat moulded PVC ‘C’ channel of size 30 x 50mm forming stiles, and 5mm thick, 75mm wide PVC sheets for top rail, lock rail & bottom rail on either side, and 10mm (5mm x 2) thick, 20mm wide cross PVC sheet as gap insert for top rail & bottom rail. Panelling of 5mm thick PVC sheet to be fitted in the M.S. frame welded / sealed to the stiles & rails with 30mm wide x 5mm thick PVC sheet beading on either side, and joined together with solvent cement adhesive etc. An additional 5mm thick PVC strip of 20mm width is to be stuck on the interior side of the ‘C’ Channel using PVC solvent adhesive. Complete as per direction of Engineer-in-charge, manufacturer’s specification & drawing for finished item of work . This rate including cost of material , all labour charges,necessary fixing, other incidental charge. etc.complete as per S.S and as directed by the departmental officer in charge of work
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 500/500D grade) of different diameters for RCC works, including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying including and other all materials etc., complete for finished item of work in all floors. as per SS and as directed by the departmental office incharge of work.
Cement plastering using opc in cm(1:3) prop 20 mm thick including cost of all materials, conveyance charges of materials and all operational, incidental and labour charges etc., complete for finished item of work as per S.Sfor floorring
Manufacture,supply,delivery of MS grill gates,window ornamental safety grill ,made with MS flats,MS angles,MS squares etc including welding,finishing,applying red oxide paint as primary coat etc complete.This rate including cost of material , all labour charges, other incidental charge. etc.complete as per S.S and as directed by the departmental officer in charge of work
Painting two coats with synthetic enamel paint over a base coat of red led. The rate includeds cost and conveyance of all materilas at site, labour charges, scaffolding charges etc., complete as directed by the departmental authorities (APDSS No:1201) This rate including cost of material , all labour charges,necessary fixing, other incidental charge. etc.complete as per S.S and as directed by the departmental officer in charge of work
Manufacture, Supply and Delivery of Unplasticised 110mm dia 6kg/cm PVCs Pipes for potable water supplies conforming to IS : 4985/2000 (3rd revision) with bell ends (Socket) as per specification in light Grey/Natural Ivory Grey/ Any other Color (except White) inclusive of transportation to the sub-divisional stores anywhere in AP in cluding all taxes. - 110 mm dia.This rate including cost of material , all labour charges,necessary fixing, other incidental charge. etc.complete as per S.S and as directed by the departmental officer in charge of work
Supply and fixing of 25 mm dia 2.00 mm thick PVC pipe concealed in roof slab with all required accessories with approved brand and makes including masonary work all labour chages complete as per IE rules and as directed by the departmental officer incharge of work
Supply and fixing of 20 mm dia 1.50 mm thick PVC pipe concealed in walls with all required accessories including masonary work for light , fan and plug point with metal deep box of approved brand including all labour chages complete as per IE rules and as directed by the departmental officer incharge of work
Wiring with 2 runs 14/0.3 mm. (1.0. sq.mm) Fire retardant PVC insulated Flexible copper cable in existing pipe with 6A siwtch, ceiling rose and 3 mm thick hyla sheet covering to switch control box including all labour charges etc,., complet for light, bell , fan and exhaust fan points in non - residential building complete as per IE rules and as directed by the departmental officer incharge of work
Wiring with 2 runs 14/0.3 mm. (1.0. sq.mm) Fire retardant PVC insulated Flexible copper cable in existing pipe with 6A modular siwtch control and 3/2 pin sockets fixing on board with approved brands including all labour charges complete as per IE rules and as directed by the departmental officer incharge of work
supply and run of 2 of 36/0.3 mm. (1.5. sq.mm) Fire retardant PVC insulated Flexible copper cable in existing pipe for mains of with approved brands including all labour charges complete as per IE rules and as directed by the departmental officer incharge of work
supply and run of 1 of 14/0.3 mm. (1.0. sq.mm) Fire retardant PVC insulated Flexible copper cable in existing pipe approved makes for earth continuity including all labour charges etc. complete as per IE rules and as directed by the departmental officer incharge of work
supply and run of 2 of 6 sq.mm (7/18) WPSC alluminium cable along with No.10 SWG G.I barer wire through PVC cleats with all accessories with approved makes including all labour charges etc., complete as per IE rules and as directed by the departmental officer incharge of work
Providing independent earthing by excavating a trench to a depth of 2.10m in all soils, as per size specied in data ,using 40 mm dia B class GI pipe 2.50m long with necessary accessories with hume pipe ring duly providing staggered holes including filling with equal proportion of salt and charcoal in layers and all labour charges etc complete complete as per IE rules and as directed by the departmental officer incharge of work
Supply and fixing SPN Distribution board with IP-20 protection suitable for single phase Earth Leakage Circute Braker (ELCB) / Residual Current Circute Braker (RCCB) / Double Pole (DP) Isolator as incomer and 10kA SP MCBs as out going including internal connections and labour charges for surface / flush mounting etc. complete as per IE rules and as directed by the departmental officer incharge of work
Supply of 48" (1200mm) Sweep 5 star rated Ceiling Fan , with double ball bearings, air delivery more than 200 cubic meter/min but without Regulator.Makes : Crompton HS Plus / Havells ES Neo/Orient Energy Star/ Halonix(Zephyr)/Polycab(Synergy Star) unit each complete as per IE Rules and as directed by the departmental officer incharge of work
Supply of stepped type Electronic Regulator of Makes: GM G Home / Gold Medal Olive / Million Zoom / Great white Omega/Koncept/Vimal opel/ Anchor/Vihan/CPL complete as per IE Rules and as directed by the departmental officer incharge of work
Supply of 20 W Box type tube light luminaire powder coated CRCA sheet steel housing with Electronic Ballast Chokes and all standard accessoriesof makes Wipro / G.E. / Phillips / Crompton / Bajaj. complete as per IE Rules and as directed by the departmental officer incharge of work
Providing & Placing on Terrace (at all floor levels) polyethylene water storage tank with Double layer approved brand & manufacture with cover and suitable locking arrangement & making necessary holes for inlet & outlets and over flow pipes but without fittings & base support for tanks complete as per ss rules and as directed by the departmental officer incharge of work
Supplying and fixing 580mm x 440mm long Orissa pan white glazed Water Closet 1st quality ISI marked confirming to IS:2556-Part-3-1981 with "P" or "S" trap, ISI marked and providing masonry seat, CC squatting plate and 10 litres capacity single flush PVC low level cistern with internal components fixed on 2 Nos. of teak wood blocks of size 76.20mm x 101.60mm using required size of nails, screws as approved by Engineer-in-charge, 15 mm nominal size CP finish brass angled stop valve screw type with internal /external threaded conforming to IS 8931, 12.70mm PVC connection with brass union nuts CP coated , 31.75mm brass plumber union, P trap or S trap of Indian W.C. shall be encased on CC (1:2:4) 150mm alround well above the joint to stop leakage at the joint etc., complete including cost and conveyance of all materials to site, cost of CC bed, labour charges and seigniorage charges, overheads & contractors profit etc., complete as per ss rules and as directed by the departmental officer incharge of work
Supplying and fixing Indian make Flat Back Wash Hand Basin 1st quality conforming to IS:2556-Part-4:1972 of size 550mm x 400mm with 32 mm nominal size C.P. Fitting with parallel pipe thread conforming to IS:2963-1979 and fitted with 15 mm nominal bore Chromium Plated Pillar Tap of 1st quality Indian make heavy duty complete with standard CI brackets including wooden blocks ,1 No.12.70mm PVC connection with brass union nuts CP coated , angle stop cock 12.70mm dia. first quality Indian make heavy duty, 30mm dia. PVC flexible waste pipe 914.4mm length of 1st quality including cost and conveyance of all materials to site, labour charges complete as per ss rules and as directed by the departmental officer incharge of work
Supply of 110 mm dia 3 m single Socket PVC/SWR pipe - 6 Kg/sq.cm - Prince/Sudhakar/Kisan/Supreme or any ISI Brand. complete as per ss rules and as directed by the departmental officer incharge of work
Supply of 110 mm dia - Plain Bend 87.5 Degree - UPVC/SWR Pipe fittings (Prince/Sudhakar/Kisan/Supreme or any ISI Brand) complete as per ss rules and as directed by the departmental officer incharge of work
Supply of 110 mm dia - Coupler - UPVC/SWR Pipe fittings (Prince/Sudhakar/Kisan/Supreme or any ISI Brand complete as per ss rules and as directed by the departmental officer incharge of work
Labour charges for laying, fixing and commissioning the PVC pipes of 110mm dia including Supplying & fixing 76.2 mm W.I clamps/ couplers/ bends/ tees etc any diameter including fixing necessary fittings like bends, plugs, couplers, junctions, tees, etc with solvent jointing as per standard practice complete as per ss rules and as directed by the departmental officer incharge of work
Constructing 457.2 mm x 457.2 mm (1'6"x1'6") brick in CM 1:6 prop. Masonry. Inspection chamber up to 914.4 mm (3'0") and fitted with light weight 457.2 mm x 457.2 mm (1'6"x1'6") C.I frame and cover of 20 Kg complete as per ss rules and as directed by the departmental officer incharge of work
S& F GI pipe Medium Grade 25mm dia properties & weight as per IS 1239 ISI mark with GI fittings including the cost of pipe & its fittings & labour charges complete as per ss rules and as directed by the departmental officer incharge of work - 25 mm dia nominal bore -from tank to jn for of individual lines
S& F GI pipe Medium Grade 20mm dia properties & weight as per IS 1239 ISI mark with GI fittings including the cost of pipe & its fittings & labour charges complete as per ss rules and as directed by the departmental officer incharge of work - 20 mm dia nominal bore -from jn for of individual lines to toilets & Kitchen
S& F GI pipe Medium Grade 15mm dia properties & weight as per IS 1239 ISI mark with GI fittings including the cost of pipe & its fittings & labour charges complete as per ss rules and as directed by the departmental officer incharge of work - 15 mm dia nominal bore -for internal
GM Ball valve with SS Ball and SS Spindle as per IS - Class - I, Indian make heavy type - 25 mm NB Size. This rate including cost of materials labour charges, other incidental charge etc complete as per SS and as directed by the departmental officer incharge of work.
GM Ball valve with SS Ball and SS Spindle as per IS - Class - I, Indian make heavy type - 20 mm NB Size. This rate including cost of materials labour charges, other incidental charge etc complete as per SS and as directed by the departmental officer incharge of work.
GM Ball valve with SS Ball and SS Spindle as per IS - Class - I, Indian make heavy type - 15 mm NB Size. This rate including cost of materials labour charges, other incidental charge etc complete as per SS and as directed by the departmental officer incharge of work.
S&F 12.7 mm N.P bib tap Indian make heavy dutys Seiko/ Senior/ Nice or equivalent. This rate including cost of materials labour charges, other incidental charge etc complete as per SS and as directed by the departmental officer incharge of work.
S& F following GI union Ist Quality. This rate including cost of materials all labour charges, other incidental charge etc complete as per SS and as directed by the departmental officer incharge of work. 12.70mm
S& F following GI union Ist Quality. This rate including cost of materials all labour charges, other incidental charge etc complete as per SS and as directed by the departmental officer incharge of work. 19.05mm
S& F following GI union Ist Quality. This rate including cost of materials all labour charges, other incidental charge etc complete as per SS and as directed by the departmental officer incharge of work. 25.40mm
For septic Tank Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD. Note : Classifications of Earth Work Specification are as per 302.2.1(a) of MORD and 301.2.1 of MORT&H--ordinary soil--manual means upto 3m depth by manual means upto 3.00m depth
Filling Sand in foundation of the building as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH This rate including cost of material all labour charges etc complete and as per ss and as direacted by the departmental officer incharge of work.
Plain Cement Concrete (1:4:8) (cement: fine aggregate: Coarse aggregate) using coarse aggregate 40mm size hard, machine crushed granite from approved quarry using concrete Mixer including cost and conveyance of all materials like cement, sand, coarse aggregate, water etc. to site including all charges for machine mixing and hire charges of concrete mixer, laying concrete finishing top surface to the required level curing for finished item of work as per SS and as directed by the departmental officer incharge of work.
Brick masonary in CM (1:6) using 2nd class bricks of size 23 x 11 x 7cms. Cost including cost and conveyance of all materials at site, labour charges for curing , scaffolding, all lifts, other incidental charges etc.,Complete as per SS and as directed by the departmental officer incharge of work.
Cement plastering using opc in cm(1:3) prop 20 mm thick including cost of all materials, conveyance charges of materials and all operational, incidental and labour charges etc., complete for finished item of work as per S.S SS out side & inside and as directed by the departmental officer incharge of work.
RCC M-25 Nominal mix (cement,fine aggregate,coarse aggregate) corresponding to Table -9 of IS -456 using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including all operational ,incidental and labour charges such as machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work,but including centering,shuttering for culvert slabs 150mm thick as directed by the departmental officer incharge of work.
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying etc., complete for finished item of work in all floors.( APSS No.126)
Erection of 500 KVA Transformer at Head Water Works Kovvur with Transformer yard 15.00x12.00m
Supply and erection of 7.50m long double pole structure fabricated with 150x75mm RS Joists,100x50mm MS channels, iron cross armstor fuse set and Lighting arrestrors etc.,including one coat of red oxide primer and two coats of bright Supply. This rate including cost of all materials, and all labour charges other incidental charges etc complete as directed by the departmental officer incharge of work.
Supply and fixing of 11 KV ,400 A 3 phase central post rotating double break type AB switch(isolator) as per IS 9921) without earth blade, gang operated, Horizontal type, operating mechanism with GI spring loaded reverse loop type fixed contact, solid HD electrolytic copper tubular moving contact with silver/Nickel plated at end points,9 Nos post insulators of 12 KV (IS 2594 and IS 5350) ,Hot Dip galvanizing hardware, GI pipe, Nuts and bolts etc., complete., as per IE Rules and as directed by the departmental officer incharge of work.
Supply and fixing of 100 A 11 KV Horn Gap fuse set as per IS 9385 on existing DP structure with 6 no of 24 KV /22 KV post Insulators (IS 5350, Hot dipped Hardware, fuse wire of required size etc., complete as per IE Rules and as directed by the departmental officer incharge of work
Supply and fixing of distribution type lightning arrester 11 KV 5 kA as per IS 3070 with mounting base on the existing DP structure as per IE Rules. This rate incluidng cost of materials, all labour charges, other incidental charges etc complete as per IE Rules and as directed by the departmental officer incharge of work.
Supply and erection of 11KV Strain disc. Insulators with GI pins and top clamps. This rate incluidng cost of materials, all labour charges, other incidental charges etc complete as per IE Rules and as directed by the departmental officer incharge of work.
Supply and fixing of 11 KV pin Insulator (IS 731/1971) with minimum creepage distance of 300 mm on existing cross arm including all accessories like Hot dip GI spindle and nuts etc., This rate incluidng cost of materials, all labour charges, other incidental charges etc complete as per IE Rules and as directed by the departmental officer incharge of work.
Providing jumper connections with I/O' SWG HDBC wire between the 11 KV equipment on the outdoor structures. This rate incluidng cost of materials, all labour charges, other incidental charges etc complete as per IE Rules and as directed by the departmental officer incharge of work.
Supply and erection of GI stay set of dia 16mm,1.8 mtr long stay rod and anchor plate 380mmx380mmx6.4mm. including stay clamps, turn buckle and GI stay wire tight end through strain insulator including excavation of pit and cc work etc., complete This rate incluidng cost of materials, all labour charges, other incidental charges etc complete as per IE Rules and as directed by the departmental officer incharge of work.
Providing efficient earthing arrangement forthe DP structure lighting arresters and the HV equipment. Transformer body and neutral etc., with 25 x 3 mm copper flats and connecting them to the Earth Electrodes fabricated and buried accroding to standard specifications. This rate incluidng cost of materials, all labour charges, other incidental charges etc complete as per IE Rules and as directed by the departmental officer incharge of work. and as per the details given below:
A) Earth Electrodes
B) 20mm x 3mm Copper Flat(0.529Kgs/1Mtr) MAT 04146
C) Epoxy insulators
D) No.'8' SWG Copper wire. MAT 04141
Supply and erection of 500 KVA, 11KV/433 V, DY-11 Vectro group, out door type, plinth mounting type, Hint /make transformer with bushings on HT side and cable entry box on L V side to received 1.1 KV grade cable with all standard accessories transformer oil. tansformer having copper wound natural cooled with all standard accessories . This rate incluidng cost of materials, all labour charges, other incidental charges etc complete as per IE Rules and as directed by the departmental officer incharge of work.
Supply and laying of 400Sq mm X 3.5 core XLPE insulated, 1100V grade armoured aluminum cable as per specification confirming to IS:7098 (Part- I)./1554-I. This rate incluidng cost of materials, all labour charges, other incidental charges etc complete as per IE Rules and as directed by the departmental officer incharge of work. Makes: Makes: Torent / Universal / Unicab / Havells / Finecab/ KEI / Gloster/ Polycab /RR Kabel/ Fortune Arrt ELEC-4.1.1q MAT-03431
MAIN PANEL, BOARD.LT Sheet steelclad, free standing, floor mounting unitized, Duat and vermin proof Indoor, Cubicle powder coated panel board made out of 16 SWG CRCA sheet sheetable for use 3 ph, 440v, 50 Hz. System and comprising, complete with busbars of adeeequate capacity, interconnections,control wiring etc..as required. This rate incluidng cost of materials, all labour charges, other incidental charges etc complete as per IE Rules and as directed by the departmental officer incharge of work.
Incoming Supply, delivery transporation, other incidental charges etc complete as per IE Rules and as directed by the departmental officer incharge of work as follows
a) . 630A TPN SFU for main switch
b) . 630 A pole change over switch
c) one set Metering Panel Comprisinga). 1( 0-500V) 96mm.SQ.flush type Digital Voltmeter.
e). ( 0-250A) 96mm SQ.flush type digital Ammeter
g).3RYB Phase indication lamps with leds
h).Supply and Fixing of Current Transformer, with all necessary support in existing panel including connection etc. as required from 200 / 5 to 400/5 Ratio, 10 VA, class 1 accuracy: Make: Kappa/L&T/Seimens/C&S/Schneider MAT 03986
Out-going Supply, delivery transporation, other incidental charges etc complete as per IE Rules and as directed by the departmental officer incharge of work as follows
630A TPN SDFU forCW pump house motors Makes:LauritzKnudsen(FormerlyL&T)/Schneider/ C&S/ ABB / SIEMENS MAT 02885
630A TPN SDFU for compressor/mechanical equipments Makes:LauritzKnudsen(FormerlyL&T)/Schneider/ C&S/ ABB / SIEMENS MAT 02885
630A TPN SDFU for low lift sump Raw water motors Makes:LauritzKnudsen(FormerlyL&T)/Schneider/ C&S/ ABB / SIEMENS MAT 02885
630A TPN SDFU for Space Makes:LauritzKnudsen(FormerlyL&T)/Schneider/ C&S/ ABB / SIEMENS MAT 02885
630A TPN SDFU for lighting section Makes:LauritzKnudsen(FormerlyL&T)/Schneider/ C&S/ ABB / SIEMENS MAT 02885
630A 4pole change over switch for lighting section Makes:Socomec/LauritzKnudsen(FormerlyL&T)/HPL / Havells/ C&SMAT MAT 02898
.KWH digital meter fro lighting section
Supply of 32 Amp………ISI marked TPN Switch Disconnector Fuse Unit, Cubical type without fuses as per IS: 13947/IEC 60947-3 Makes: As per list of recommended brands as category I.MAT-02879
Supply of 6A to 35 A……ISI marked HRC Fuse Links as per IS 13703-Part 2/IEC 60269- Part 2 Makes: As per list of recommended brands as category I MAT-02938
Standard duty Single phase 250 V / Three phase 440 V, 50 Hz capacitor (Bank) MAT-03998
500KV.LT/Transformer Errection.testing Commensing and Supply of drawing layout plans of installed transformer in tracing cloth and duly get approved from electrical inspector APEPDCL and leaflets for various equipments and opearation manuals etc., complete. This rate incluidng cost of materials, all labour charges, other incidental charges etc complete as per IE Rules and as directed by the departmental officer incharge of work.
Transformer Yard at proposed SS Tank
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH Note : Classifications of Earth Work Specification are as per 302.2.1(a) of MORD and 301.2.1 of MORT&H--ordinary soil--manual means upto 3m depth for foundations of buildings in restricted places By manual means
Providing river sand filling brought from approved quarry including cost and conveyance of all material and all labour charges such as filling in layers watering ramming etc complete as per ss and as directed by the departmental officer incharge of work.
Providing PCC 1:4:8 using 40 mm graded SS 5 HBG m/c metal and OPC coarse and fine aggregate confirming to IS 383 including cost and conveyance of all materials and labour charges, machine mixing , vibration,laying in position, curing centering etc., complete as per SS and as directed by the departmental officer incharge of work.
Supply and placing of the 25 design mix concrete corresponding to IS -456 using /MIXER using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including ,sales and other taxes on all materials all operational ,incidental and labour charges such as ,machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work (APSS NO 402) with minimum cement content as per IS Code from standard suppliers approved by the deparment including pumping , centering,shuttering,laying concrete, vibrating,curing .This rate including cost of material , all labour charges, other incidental charge. etc.complete as per ss and as directed by the departmental officer in charge of work M25 design mix - column footings
Supply and placing of the 25 design mix concrete corresponding to IS -456 using /MIXER using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including ,sales and other taxes on all materials all operational ,incidental and labour charges such as ,machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work (APSS NO 402) with minimum cement content as per IS Code from standard suppliers approved by the deparment including pumping , centering,shuttering,laying concrete, vibrating,curing .This rate including cost of material , all labour charges, other incidental charge. etc.complete as per ss and as directed by the departmental officer in charge of work M25 design mix - Columns
Supply and placing of the 25 design mix concrete corresponding to IS -456 using /MIXER using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including ,sales and other taxes on all materials all operational ,incidental and labour charges such as ,machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work (APSS NO 402) with minimum cement content as per IS Code from standard suppliers approved by the deparment including pumping , centering,shuttering,laying concrete, vibrating,curing .This rate including cost of material , all labour charges, other incidental charge. etc.complete as per ss and as directed by the departmental officer in charge of work M25 design mix - Plinth beam
Painting Walls with Snowcem or other equal and approved Water Proof Cement Paint 2 Coats (All Colours) over a base coat of aproved cement primer making 3 coats in total including cost of all , conveyance charges of materials and other incidental charges, scaffolding, lifting and as directed by the departmental officer in charge of work
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 500/500D grade) of different diameters for RCC works, including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying including and other all materials etc., complete for finished item of work in all floors. as per SS and as directed by the departmental office incharge of work.
Supplying and fixing galvanised steel barbed wire (IS : 278-1962 Type I) weighing 9.38 Kg per 100 metres (min.), Straining and fixing to any type of standard, rails, straining bolts, including securing with and provision of galvanised mild steel wire, stapples or steel pins, etc., as directed (Posts and struts of wood, concrete, steel, etc.) and straining bolts shall be paid for separately).
Manufacture,supply,delivery of MS grill gates,window ornamental safety grill ,made with MS flats,MS angles,MS squares etc including welding, finishing, applying red oxide paint as primary coat etc complete This rate including cost of material , all labour charges,fabrication charges , other incidental charges etc., complete as per ss and as directed by the departmental officer in charge of work.
Painting two coats with synthetic enamel paint over a base coat of red led. The rate includes cost and conveyance of all materials at site, labour charges, scaffolding charges other incidental charges etc., complete as directed by the departmental officer in charges of work
supply and filling the transformer yard with 40mm HBG metal m/c.This rate including cost of metal,filling charges,Spreading,and other incidental charges etc., complete as per ss and directed by the departmental officer incharge of work
Providing 800mm dia.(10 mm thick plate) at National High way at kovvur for Raw water pumping main 400 mm dia DIK9 for NH crossings and clear water pumping main 150 mm dia RLY crossing
Railway crossing/Road crossing/Canal crossing by adopting trenchless technology tunneling work through specialized pipe jacking method by erecting the equipment to true to the alignment and gradient, by hydraulic pipe jacking technique complete including tunneling, excavation in all types of soils including hard rock and construction of RCC chambers suitable to casing pipe pits, and conveyance charges of machinery and other required materials including Manufacture, supply and delivery at work site 800mm internal dia M.S.Pipe fabricated with 10mm thick MS plates confirming to IS 2062-1992 of grade A manufactured as per IS 3589-2001 in suitable lengths painted with two coats of food grade epoxy paint inside and outside to suit the site conditions, in co-ordination with the concerned authorities as per approved drawings and directed by the Engineer-in –charge including Cost of Laying, Jointing, Hydrostatic Filed Test Pressure, Including Cost of Site Welding, Jointing Materials And Cost of Transportation of Water Including Emptying Pipe Line After Completion Of Field Testing as per SS and as directed by the departmental officer incharge of work.
Construction of 600 mm size CC disposal drain from proposed WTP
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD - Mechanical Means
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD - Manual Means
Filling Sand for foundation as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH.This rate including cost of sand ,filling charges,watering,ramming,and other incidental charges etc., complete as per ss and directed by the departmental officer incharge of work
Providing PCC 1:4:8 using 40 mm graded SS 5 HBG m/c metal and OPC coarse and fine aggregate confirming to IS 383 including cost and conveyance of all materials and labour charges, machine mixing , vibration,laying in position, curing centering charges , scaffolding charges, other incidental charge etc., complete.as per SS and as directed by the departmental officer incharge of work
Reinforced Cement Concrete M-15 Nominal mix (cement,fine aggregate,coarse aggregate) corresponding to Table -9 of IS -456 using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including seigniorage charges ,sales and other taxes on all materials including all operational ,incidental and labour charges such as machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work,but including centering,shuttering for CC drains bottom layer
Reinforced Cement Concrete M-15 Nominal mix (cement,fine aggregate,coarse aggregate) corresponding to Table -9 of IS -456 using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including seigniorage charges ,sales and other taxes on all materials including all operational ,incidental and labour charges such as machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work,but including centering,shuttering for CC drains side Walls
Construction of 600 KL ELSR with 18m staging at Achayamma Colony zone -II
Construction of ELSR With the following specification 600 kl capacity with a staging of 18 m, with Seismic analysis.
All concrete components shall be designed with M30 Design Mix proportion. The rate are arrived with base rate of cement Rs 4220/- per MT and steel Rs 600001. 1.The foundations shall be designed for solid raft; 2.Rate inclusive of three coats of epoxy paint Food Grade of best quality to inner surface of the Reservoir including roof .3.The above rates are adopted for preparation of estimate for construction of ELSRs/OHSRs for finished work including 2 coats of weather proof emulsion painting for external surfaces, lettering, all required fixtures, Pipes,Pipe specials, valves of DI material, Valve chambers etc., for pipe connections including cost of pipes,specials and valves as per departmental designs and drawings. 4.The above rates adopted for a wind pressure upto "250 kg/sq m". For every 100 kg/sqm decrease in wind pressure, the rate shall be decreased by 5% 5.The Basic rate is adopted by considering the design for Seismic forces for Zone-I & II only of seismic zones 6.The basic rates shall be increased by 15% for Zone-III of seismic zones 7.The ELSR/OHSR shall be designed with minimum of two rows of columns for capacities above 500 KL & upto 1000KL 8.The ELSR/OHSR shall be designed with minimum of three rows of columns for capacities above 1000KL.
i) Pipe connections & Specials with D.I materials (a) All pipe connections for Inlet, Out let, Over Flow, Scour pipes shall be provided with D/F DI material. (b) The Valves for above pipe connections also shall be of DI material of PN 16 duty confirming to the specification of SoR item No.28 (c) All specials such as Bends, Tees, Reducers, Duck foot Bends, Bell mouths etc,. Shall be of DI material. II) The sizes of the verticals for ELSR/OHSR shall be: Above 1000KL three rows columns shall be provided a) For 500 KL to 750 Kl ELSRs Inlet Pipe - 300mm dia. Out let Pipe - 350mm dia. DI valves – 2 No’s Over Flow pipe - 350m dia. Scour Pipe - 200mm dia All Manholes Frames & covers
b) For 800 KL to 1500 Kl ELSRs Inlet Pipe - 400mm dia. Out let Pipe - 450mm dia. DI valves – 2 No’s Over Flow pipe - 450m dia. Scour Pipe - 200mm dia. c) For above 1500 KL to 2500 Kl ELSRs Inlet Pipe - 400mm dia. Out let Pipe - 500mm dia. DI valves – 2 No’s Over Flow pipe - 500m dia. Scour Pipe - 200mm dia. Note: Any deviation from the above sizes as per design, shall be paid or recovered. (iii) Manhole Frames & Covers All man hole Frames & Covers shall be made of CI/DI materials with min. size of 0.60mX 0.60m - For Roof & Valve Chambers. CI/D.I Double Swan neck ventilators (min. of 150mm dia.) shall be provided in top dome and slab with mosquito/fly proof nets - 4Nos. RCC Finial ventilator with fly/bird protection with GI mesh - 1 No. RCC precast ladders of 0.60 m width - 2 Nos. RCC dog legged stair case of 1.00 m flight width and 1.20 m landing width R.C.C hand railing of 1.0 m height – 1 No
The staircase shall be enclosed with brick masonary walls on three side and collapsible MS gate on front side up to 1st brace level, to prevent unauthorized entry Construction of R.C.C valve chambers as per Standard Drawings with RCC cover slab fixed with CI/DI manhole Frame & Cover with lock and Key arrangement. The Mix shall not be less than VRCC M 20 grade with 150mm thick side walls, 150mm thick top slab, 150mm thick base slab over base course of 100mm thick (1:4:8) prop. ) Balcony of 1.00 m width at floor slab level / middle ring beam level by using Stainless Steel pipe of grade 304 hand railing up to 1.20 m height, with top railing of 40mm dia. pipe & middle railing of 25mm dia. and verticals with 40mm dia. at an interval not more than of 1.00m c/c. Lightening Arrestor with all its accessories complete including earthing,with relevant IS Codes - 1 No.
Compound wall: Construction of compound wall including ornamentalM.S.Gate of size 3.0 X 2.40m is included in the basic rate of ELSRs. Length of compound wall hall be minimum of 150m. Min. height of the compound wall shall be 1.80m above plinth and thickness 230mm in brick masonry in CM(1:6).The compound wall shall be constructed including earth work excavation in all types of soils for plinth beam of 230mm X 300mm and 0.75X0.75X1.20m size for column footing portions. The footings shall be of0.75X0.75X0.25m in VRCC M20 grade and constructed over a C.C(1:4:8)prop bed of 100mm thick. The columns shall be of 230X230 mm in size with VRCC M20 grade at 3.00m c/c spacing, having depth of 1.20m below ground level and height of 2.00m above GL. The plinth beam of size of 230X300 mm shall be constructed in VRCC M20 grade at Gound level over a bed of CC(1:4:8)-100mmthick. 450X450mm size columns in M20 grade shall be constructed for gate pillars. All the materials shall be followed as per the standards grade shall be constructed for gate pillars. All the materials shall be followed as per the standards. Tie beam shall be provided above the brick work with 230X200mm size,fixed with MS angulars of 25mm X 25mm X 4mm in "Y" shape to hieght of 0.60m, with embedded length of 150mm in concrete. The barbed wire fencing with 3 ply of 18 gauge shall be streched in 4 rows (2x2). Plastering shall be done with 16mm thick in two coats i.e., base coat 12mm thick in CM(1:6)prop and 4mm thick 2nd coat CM(1:4) prop on both sides of brickwork.
Snowcem paint in two coats shall be provided for both sides of wall. The M.S ornamental gate as per the approved drawings shall be provided with minimum of 3.60mts width and 2.40mts height with enamel paint. Yard lighting shall be arranged on four corners of compound wall. If the length of the wall is increased/ decreased Note:-For every 1m increase/decrease in length of compound wall the increase/decrease in basic rates of ELSRs of the capacities from 500KL to 2500KL shall be as follows.: i) 500 KL : 0.086% ii) 1000 KL : 0.047% iii) 1500 KL : 0.034% iv) 2000 KL : 0.026% v) 2500 KL : 0.022 % For intermediate capacities, interpolated percentages shall be adopted Staff Quarter shall be constructed for a minimum plinth area of 40 sqm with the following specification: RCC framed structure withconcrete grade not less than M20 design mix at the locations specified by the department at the time of execution with verandah, hall, bed room, kitchen and bath &W/C with floor area of 40.00sqmts excluding balconies and staircases
MS hollow door frame with cold rolled processed steel sheet 1.25mm thick bright CRCA conforming to IS 4351/76, Flush door shutters with solid bond wood bond board doors shall be provided. N.C.L. Windows centre fixed both sides openable shutter window 1.35 X 1.35mts outer frame section 48x50mm shutter frame section with a size of 48 X20 mm mullion section of size 48 X 50mm fixed beading section of 12 X 12 mm shall be provided.Flooring with polished Kadapa stone shall be provided. Walls shall be provided with snowcem paint in two coats over primary coat. Electrical and water supply arrangement shall be provided as directed by dept officer.Water Storage tank made with plastic/polymer material of reputed makewith necessary out let and inlet connection pipes shall provided. Septic tank for 5 users shall be provided.
Construction of 500 KL ELSR with 18m staging at Bridge peta zone -III
Construction of ELSR With the following specification 500 kl capacity with a staging of 18 m, with Seismic analysis.
All concrete components shall be designed with M30 Design Mix proportion. The rate are arrived with base rate of cement Rs 4220/- per MT and steel Rs 600001. 1.The foundations shall be designed for solid raft; 2.Rate inclusive of three coats of epoxy paint Food Grade of best quality to inner surface of the Reservoir including roof .3.The above rates are adopted for preparation of estimate for construction of ELSRs/OHSRs for finished work including 2 coats of weather proof emulsion painting for external surfaces, lettering, all required fixtures, Pipes,Pipe specials, valves of DI material, Valve chambers etc., for pipe connections including cost of pipes,specials and valves as per departmental designs and drawings. 4.The above rates adopted for a wind pressure upto "250 kg/sq m". For every 100 kg/sqm decrease in wind pressure, the rate shall be decreased by 5% 5.The Basic rate is adopted by considering the design for Seismic forces for Zone-I & II only of seismic zones 6.The basic rates shall be increased by 15% for Zone-III of seismic zones 7.The ELSR/OHSR shall be designed with minimum of two rows of columns for capacities above 500 KL & upto 1000KL 8.The ELSR/OHSR shall be designed with minimum of three rows of columns for capacities above 1000KL.
i) Pipe connections & Specials with D.I materials (a) All pipe connections for Inlet, Out let, Over Flow, Scour pipes shall be provided with D/F DI material. (b) The Valves for above pipe connections also shall be of DI material of PN 16 duty confirming to the specification of SoR item No.28 (c) All specials such as Bends, Tees, Reducers, Duck foot Bends, Bell mouths etc,. Shall be of DI material. II) The sizes of the verticals for ELSR/OHSR shall be: Above 1000KL three rows columns shall be provided a) For 500 KL to 750 Kl ELSRs Inlet Pipe - 300mm dia. Out let Pipe - 350mm dia. DI valves – 2 No’s Over Flow pipe - 350m dia. Scour Pipe - 200mm dia All Manholes Frames & covers
b) For 800 KL to 1500 Kl ELSRs Inlet Pipe - 400mm dia. Out let Pipe - 450mm dia. DI valves – 2 No’s Over Flow pipe - 450m dia. Scour Pipe - 200mm dia. c) For above 1500 KL to 2500 Kl ELSRs Inlet Pipe - 400mm dia. Out let Pipe - 500mm dia. DI valves – 2 No’s Over Flow pipe - 500m dia. Scour Pipe - 200mm dia. Note: Any deviation from the above sizes as per design, shall be paid or recovered. (iii) Manhole Frames & Covers All man hole Frames & Covers shall be made of CI/DI materials with min. size of 0.60mX 0.60m - For Roof & Valve Chambers. CI/D.I Double Swan neck ventilators (min. of 150mm dia.) shall be provided in top dome and slab with mosquito/fly proof nets - 4Nos. RCC Finial ventilator with fly/bird protection with GI mesh - 1 No. RCC precast ladders of 0.60 m width - 2 Nos. RCC dog legged stair case of 1.00 m flight width and 1.20 m landing width R.C.C hand railing of 1.0 m height – 1 No
The staircase shall be enclosed with brick masonary walls on three side and collapsible MS gate on front side up to 1st brace level, to prevent unauthorized entry Construction of R.C.C valve chambers as per Standard Drawings with RCC cover slab fixed with CI/DI manhole Frame & Cover with lock and Key arrangement. The Mix shall not be less than VRCC M 20 grade with 150mm thick side walls, 150mm thick top slab, 150mm thick base slab over base course of 100mm thick (1:4:8) prop. ) Balcony of 1.00 m width at floor slab level / middle ring beam level by using Stainless Steel pipe of grade 304 hand railing up to 1.20 m height, with top railing of 40mm dia. pipe & middle railing of 25mm dia. and verticals with 40mm dia. at an interval not more than of 1.00m c/c. Lightening Arrestor with all its accessories complete including earthing,with relevant IS Codes - 1 No.
Compound wall: Construction of compound wall including ornamentalM.S.Gate of size 3.0 X 2.40m is included in the basic rate of ELSRs. Length of compound wall hall be minimum of 150m. Min. height of the compound wall shall be 1.80m above plinth and thickness 230mm in brick masonry in CM(1:6).The compound wall shall be constructed including earth work excavation in all types of soils for plinth beam of 230mm X 300mm and 0.75X0.75X1.20m size for column footing portions. The footings shall be of0.75X0.75X0.25m in VRCC M20 grade and constructed over a C.C(1:4:8)prop bed of 100mm thick. The columns shall be of 230X230 mm in size with VRCC M20 grade at 3.00m c/c spacing, having depth of 1.20m below ground level and height of 2.00m above GL. The plinth beam of size of 230X300 mm shall be constructed in VRCC M20 grade at Gound level over a bed of CC(1:4:8)-100mmthick. 450X450mm size columns in M20 grade shall be constructed for gate pillars. All the materials shall be followed as per the standards grade shall be constructed for gate pillars. All the materials shall be followed as per the standards. Tie beam shall be provided above the brick work with 230X200mm size,fixed with MS angulars of 25mm X 25mm X 4mm in "Y" shape to hieght of 0.60m, with embedded length of 150mm in concrete. The barbed wire fencing with 3 ply of 18 gauge shall be streched in 4 rows (2x2). Plastering shall be done with 16mm thick in two coats i.e., base coat 12mm thick in CM(1:6)prop and 4mm thick 2nd coat CM(1:4) prop on both sides of brickwork.
Snowcem paint in two coats shall be provided for both sides of wall. The M.S ornamental gate as per the approved drawings shall be provided with minimum of 3.60mts width and 2.40mts height with enamel paint. Yard lighting shall be arranged on four corners of compound wall. If the length of the wall is increased/ decreased Note:-For every 1m increase/decrease in length of compound wall the increase/decrease in basic rates of ELSRs of the capacities from 500KL to 2500KL shall be as follows.: i) 500 KL : 0.086% ii) 1000 KL : 0.047% iii) 1500 KL : 0.034% iv) 2000 KL : 0.026% v) 2500 KL : 0.022 % For intermediate capacities, interpolated percentages shall be adopted Staff Quarter shall be constructed for a minimum plinth area of 40 sqm with the following specification: RCC framed structure withconcrete grade not less than M20 design mix at the locations specified by the department at the time of execution with verandah, hall, bed room, kitchen and bath &W/C with floor area of 40.00sqmts excluding balconies and staircases
MS hollow door frame with cold rolled processed steel sheet 1.25mm thick bright CRCA conforming to IS 4351/76, Flush door shutters with solid bond wood bond board doors shall be provided. N.C.L. Windows centre fixed both sides openable shutter window 1.35 X 1.35mts outer frame section 48x50mm shutter frame section with a size of 48 X20 mm mullion section of size 48 X 50mm fixed beading section of 12 X 12 mm shall be provided.Flooring with polished Kadapa stone shall be provided. Walls shall be provided with snowcem paint in two coats over primary coat. Electrical and water supply arrangement shall be provided as directed by dept officer.Water Storage tank made with plastic/polymer material of reputed makewith necessary out let and inlet connection pipes shall provided. Septic tank for 5 users shall be provided.
Laying of 400mm,300 mm 250mm and 200 mm dia . DI K9 Pumping mains from clear water sump at HWW to Proposed and existing ELSRs
Cutting of existing B.T.road surface (aswell as asphalt concrete up to 75mm thick) including water bound macadam including all labour charges for cutting, stacking of materials etc.including cost of all labour charges ,hiring of machinery fuel charges ,wages of driver etc., complete as per the directions of departmental authorities. For pipe line trenches.
Cutting and open of C.C. Road surface including stacking of excavated materials for lying of pipe lines etc.including cost of all labour charges ,hiring of machinery fuel charges ,wages of driver etc., complete as per the directions of departmental authorities. For pipe line trenches.
Cutting and open of Water bound macadam surface including stacking of excavated materials etc.including cost of all labour charges ,hiring of machinery fuel charges ,wages of driver etc., complete as per the directions of departmental authorities. For pipe line trenches.
Earth work excavation in all soils up to SDR & stone matrix by machinery for Pipe lines as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and back filling in trenches with excavated suitable material as per Technical Specification No.305 MORD/304 MORTH up to initial lift of 3.0m. For Pipe line trenches. as per ss and as directed by the departmental officer incharge of work as follows - Mechanical Means up to 3 metres depth in ordinary soil
Earth work excavation in all soils up to SDR & stone matrix by machinery for Pipe lines as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and back filling in trenches with excavated suitable material as per Technical Specification No.305 MORD/304 MORTH up to initial lift of 3.0m. For Pipe line trenches. as per ss and as directed by the departmental officer incharge of work as follows - Manual means up to 3 metres depth in ordinary soil
Manufacture supply delivery,of 400mm dia centrifugally cast (spun) Ductile iron K9 pipes for water with Socket spigot ends confirming to IS NO 8329/2000 in standard lengths of 4.00,5.00,5.50,6.00m suitable for push-on-joint (rubber gasket D jointing) with cement mortor lining inside and zinc coating out side (K9) including transportation ,loading,unloading, stacking, etc complete as per ss and as directed by the departmental officer incharge of work - 400mm dia
Manufacture supply delivery,of 300mm dia centrifugally cast (spun) Ductile iron K9 pipes for water with Socket spigot ends confirming to IS NO 8329/2000 in standard lengths of 4.00,5.00,5.50,6.00m suitable for push-on-joint (rubber gasket D jointing) with cement mortor lining inside and zinc coating out side (K9) including transportation ,loading,unloading, stacking, etc complete as per ss and as directed by the departmental officer incharge of work - 300mm dia
Manufacture supply delivery,of centrifugally cast (spun) Ductile iron K9 pipes for water with Socket spigot ends confirming to IS NO 8329/2000 in standard lengths of 4.00,5.00,5.50,6.00m suitable for push-on-joint (rubber gasket D jointing) with cement mortor lining inside and zinc coating out side (K9) including transportation ,loading,unloading, stacking, etc complete as per ss and as directed by the departmental officer incharge of work as follows - 250mm dia
Manufacture supply delivery,of 200mm dia centrifugally cast (spun) Ductile iron K9 pipes for water with Socket spigot ends confirming to IS NO 8329/2000 in standard lengths of 4.00,5.00,5.50,6.00m suitable for push-on-joint (rubber gasket D jointing) with cement mortor lining inside and zinc coating out side (K9) including transportation ,loading,unloading, stacking, etc complete as per ss and as directed by the departmental officer incharge of work - 200mm dia
Supply and delivery of 200mm dia 2.00 m long Centrifugally cast (SPUN) Ductile iron K9 pressure pipes with flanged ends for water, gas and sewage conforming to I.S, 8329/2000 in standard working lengths of 4, 5, 5.5 & 6 meter for classification K9 suitable for push on joint (Rubber gasket and jointing) with cement mortar lining inside the pipes with outside zinc coating, rates are ex-factory, including transportion and as per ss and as directed by the departmental officer incharge of work - 200 mm dia 2.00 m long for scours on 300 mm line
Supply and delivery of 100mm dia 2.00 m long Centrifugally cast (SPUN) Ductile iron K9 pressure pipes with flanged ends for water, gas and sewage conforming to I.S, 8329/2000 in standard working lengths of 4, 5, 5.5 & 6 meter for classification K9 suitable for push on joint (Rubber gasket and jointing) with cement mortar lining inside the pipes with outside zinc coating, rates are ex-factory, including transportion and as per ss and as directed by the departmental officer incharge of work- 100 mm dia 2.00 m long for scours on 150 mm line
Supply and delivery of 400mm dia 1.00m long Centrifugally cast (SPUN) Ductile iron K9 pressure pipes with flanged ends for water, gas and sewage conforming to I.S, 8329/2000 in standard working lengths of 4, 5, 5.5 & 6 meter for classification K9 suitable for push on joint (Rubber gasket and jointing) with cement mortar lining inside the pipes with outside zinc coating, rates are ex-factory, including transportion and as per ss and as directed by the departmental officer incharge of work - 400 mm dia 1.00m long DI DF pipes for sluice and non return valves and flow meter
Supply and delivery of 300mm dia 1.00m long Centrifugally cast (SPUN) Ductile iron K9 pressure pipes with flanged ends for water, gas and sewage conforming to I.S, 8329/2000 in standard working lengths of 4, 5, 5.5 & 6 meter for classification K9 suitable for push on joint (Rubber gasket and jointing) with cement mortar lining inside the pipes with outside zinc coating, rates are ex-factory, including transportion and as per ss and as directed by the departmental officer incharge of work - 300 mm dia 1.00m long DI DF pipes for sluice and non return valves
Supply and delivery of 250mm dia 1.00m long Centrifugally cast (SPUN) Ductile iron K9 pressure pipes with flanged ends for water, gas and sewage conforming to I.S, 8329/2000 in standard working lengths of 4, 5, 5.5 & 6 meter for classification K9 suitable for push on joint (Rubber gasket and jointing) with cement mortar lining inside the pipes with outside zinc coating, rates are ex-factory, including transportion and as per ss and as directed by the departmental officer incharge of work - 250 mm dia 1.00m long DI DF pipes for sluice and non return valves
Supply and delivery of 200mm dia 1.00m long Centrifugally cast (SPUN) Ductile iron K9 pressure pipes with flanged ends for water, gas and sewage conforming to I.S, 8329/2000 in standard working lengths of 4, 5, 5.5 & 6 meter for classification K9 suitable for push on joint (Rubber gasket and jointing) with cement mortar lining inside the pipes with outside zinc coating, rates are ex-factory, including transportion and as per ss and as directed by the departmental officer incharge of work - 200 mm dia 1.00m long DI DF pipes for sluice and non return valves
Supply and delivery of Centrifugally cast (spun) Ductile Iron Fittings upto 500mm dia of DI double socket branch flange Tee, DI All Socket Tees, DI Double socket Tapers (Reducer), DI Flanged Socket, DI Flanged Spigot, DI Double Socket Duck Foot Bend, DI Double Flange Duck/Foot bend, DI All socket Cross, DI All Flange Tee, DI All Flange Cross, DI Double Flange Reducer, Blank Flange, Mechanical Joints, DI Double Socket Bends, DI Double Flanged Bends and DI Manhole Frame & cover conforming to IS:9523/2000 having dimensions Up to 500 x 500 mm dia. The rates mentioned here under are for fittings, zinc coated externally with inside mortar lining (with finishing as per class 13/IS 9523/2000) ( ex-works) including Transportation and as per ss and as directed by the departmental officer incharge of work
Lowering of 400mm Dia D.I. socket and spigot Pipes and fittings carefully in to the trench and laying them true to alignment and gradient including all labour charges, sundries as per BIS No. 3114/85 etc., complete as per ss and as directed by the departmental officer incharge of work
Lowering of 300mm Dia D.I. socket and spigot Pipes and fittings carefully in to the trench and laying them true to alignment and gradient including all labour charges, sundries as per BIS No. 3114/85 etc., complete as per ss and as directed by the departmental officer incharge of work
Lowering of D.I. socket and spigot Pipes and fittings carefully in to the trench and laying them true to alignment and gradient including all labour charges, sundries as per BIS No. 3114/85 etc., complete as per ss and as directed by the departmental officer incharge of work as follows - 250mm Dia
Lowering of 200mm Dia D.I. socket and spigot Pipes and fittings carefully in to the trench and laying them true to alignment and gradient including all labour charges, sundries as per BIS No. 3114/85 etc., complete as per ss and as directed by the departmental officer incharge of work
Jointing of 400mm Dia K9 D.I. Pipes & fittings with Rubber Gasket including all sundries filling with water with a water lead up to 500m and testing to required pressure etc., complete as per BISNo.3114/85 and as per ss and as directed by the departmental officer incharge of work
Jointing of 300mm Dia K9 D.I. Pipes & fittings with Rubber Gasket including all sundries filling with water with a water lead up to 500m and testing to required pressure etc., complete as per BISNo.3114/85 and as per ss and as directed by the departmental officer incharge of work
Jointing of 250mm Dia K9 D.I. Pipes & fittings with Rubber Gasket including all sundries filling with water with a water lead up to 500m and testing to required pressure etc., complete as per BISNo.3114/85 and as per ss and as directed by the departmental officer incharge of work
Jointing of 200mm Dia K9 D.I. Pipes & fittings with Rubber Gasket including all sundries filling with water with a water lead up to 500m and testing to required pressure etc., complete as per BISNo.3114/85 and as per ss and as directed by the departmental officer incharge of work
Supply and delivery of 400mm dia "Resilient Seated Soft Sealing" Gate Valves (Sluice Valves) PN 1.6(Mpa) with Body and Bonnet of Ductile Iron GGG-40/SG-400/15 or GGG-50/SG-500/7 or Equivalent as per IS1865, IS:3896-2 and Wedge fully Rubber Lined with food grade quality grade W270 grade EPDM, Replaceable Spindle Nut without gland packing with 3-O ring protection system on the Shaft and Seals of NBR. The Valves should be Vacuum tight and 100% leak proof with face to face dimensions as BS:5163 Type A/IS:14846. All the valves should be with fusion bonded Electrostatic Powder coating both inside and outside (Min 250 Microns)- RAL 5005 with Pocket Less Straight through body Passage conforming to Design standards of DIN-3202F4/BS:5163 Type A Flange drilling as per IS - 1538 and transportation and other incidental charges etc,as per ss and as directed by the departmental officer incharge of work 400 mm dia sluice valves
Supply and delivery of 300 mm dia "Resilient Seated Soft Sealing" Gate Valves (Sluice Valves) PN 1.6(Mpa) with Body and Bonnet of Ductile Iron GGG-40/SG-400/15 or GGG-50/SG-500/7 or Equivalent as per IS1865, IS:3896-2 and Wedge fully Rubber Lined with food grade quality grade W270 grade EPDM, Replaceable Spindle Nut without gland packing with 3-O ring protection system on the Shaft and Seals of NBR. The Valves should be Vacuum tight and 100% leak proof with face to face dimensions as BS:5163 Type A/IS:14846. All the valves should be with fusion bonded Electrostatic Powder coating both inside and outside (Min 250 Microns)- RAL 5005 with Pocket Less Straight through body Passage conforming to Design standards of DIN-3202F4/BS:5163 Type A Flange drilling as per IS - 1538 and transportation and other incidental charges etc,as per ss and as directed by the departmental officer incharge of work sluice valves
Supply and delivery of 250mm dia "Resilient Seated Soft Sealing" Gate Valves (Sluice Valves) PN 1.6(Mpa) with Body and Bonnet of Ductile Iron GGG-40/SG-400/15 or GGG-50/SG-500/7 or Equivalent as per IS1865, IS:3896-2 and Wedge fully Rubber Lined with food grade quality grade W270 grade EPDM, Replaceable Spindle Nut without gland packing with 3-O ring protection system on the Shaft and Seals of NBR. The Valves should be Vacuum tight and 100% leak proof with face to face dimensions as BS:5163 Type A/IS:14846. All the valves should be with fusion bonded Electrostatic Powder coating both inside and outside (Min 250 Microns)- RAL 5005 with Pocket Less Straight through body Passage conforming to Design standards of DIN-3202F4/BS:5163 Type A Flange drilling as per IS - 1538 and transportation and other incidental charges etc,as per ss and as directed by the departmental officer incharge of work - 250 mm dia sluice valves
Supply and delivery of 200mm dia "Resilient Seated Soft Sealing" Gate Valves (Sluice Valves) PN 1.6(Mpa) with Body and Bonnet of Ductile Iron GGG-40/SG-400/15 or GGG-50/SG-500/7 or Equivalent as per IS1865, IS:3896-2 and Wedge fully Rubber Lined with food grade quality grade W270 grade EPDM, Replaceable Spindle Nut without gland packing with 3-O ring protection system on the Shaft and Seals of NBR. The Valves should be Vacuum tight and 100% leak proof with face to face dimensions as BS:5163 Type A/IS:14846. All the valves should be with fusion bonded Electrostatic Powder coating both inside and outside (Min 250 Microns)- RAL 5005 with Pocket Less Straight through body Passage conforming to Design standards of DIN-3202F4/BS:5163 Type A Flange drilling as per IS - 1538 and transportation and other incidental charges etc,as per ss and as directed by the departmental officer incharge of work - 200 mm dia sluice valves
Supply and delivery of 200mm dia "Resilient Seated Soft Sealing" Gate Valves (Sluice Valves) PN 1.6(Mpa) with Body and Bonnet of Ductile Iron GGG-40/SG-400/15 or GGG-50/SG-500/7 or Equivalent as per IS1865, IS:3896-2 and Wedge fully Rubber Lined with food grade quality grade W270 grade EPDM, Replaceable Spindle Nut without gland packing with 3-O ring protection system on the Shaft and Seals of NBR. The Valves should be Vacuum tight and 100% leak proof with face to face dimensions as BS:5163 Type A/IS:14846. All the valves should be with fusion bonded Electrostatic Powder coating both inside and outside (Min 250 Microns)- RAL 5005 with Pocket Less Straight through body Passage conforming to Design standards of DIN-3202F4/BS:5163 Type A Flange drilling as per IS - 1538 and transportation and other incidental charges etc,as per ss and as directed by the departmental officer incharge of work - 200 mm dia sluice valves for scour
Supply and delivery of 100mm dia "Resilient Seated Soft Sealing" Gate Valves (Sluice Valves) PN 1.6(Mpa) with Body and Bonnet of Ductile Iron GGG-40/SG-400/15 or GGG-50/SG-500/7 or Equivalent as per IS1865, IS:3896-2 and Wedge fully Rubber Lined with food grade quality grade W270 grade EPDM, Replaceable Spindle Nut without gland packing with 3-O ring protection system on the Shaft and Seals of NBR. The Valves should be Vacuum tight and 100% leak proof with face to face dimensions as BS:5163 Type A/IS:14846. All the valves should be with fusion bonded Electrostatic Powder coating both inside and outside (Min 250 Microns)- RAL 5005 with Pocket Less Straight through body Passage conforming to Design standards of DIN-3202F4/BS:5163 Type A Flange drilling as per IS - 1538 and transportation and other incidental charges etc,as per ss and as directed by the departmental officer incharge of work - 100 mm dia sluice valves for scour
Supply & Delivery of 100mm dia Tamper Proof DI Flanged Single Chamber Air Release Valves PN1.6(Mpa) with body & cover made of Ductile Iron Grade GGG-40/SG-400/15 or GGG-50/SG-500/7 or Equivalent as per IS1865, IS:3896-2 with Food Grade Epoxy Powder Coating(EP-P) (Min:250 Micron) inside and Outside of Color Blue RAL 5005. All internal parts such as Float, shell, Cove Bolts etc. made of Austenitic alloy steel of SS AISI 304/316 and DN 50 float of and other components with ABS/PTFE/EPDM/NBR and generally conforming to DIN/BIS/AWWA standards (or) combination Flange drilling as per IS - 1538 and transportation and other incidental charges etc,as per ss and as directed by the departmental officer incharge of work 100mm dia. PN 16 on 400 mm dia
Supply & Delivery of 80mm dia Tamper Proof DI Flanged Single Chamber Air Release Valves PN1.6(Mpa) with body & cover made of Ductile Iron Grade GGG-40/SG-400/15 or GGG-50/SG-500/7 or Equivalent as per IS1865, IS:3896-2 with Food Grade Epoxy Powder Coating(EP-P) (Min:250 Micron) inside and Outside of Color Blue RAL 5005. All internal parts such as Float, shell, Cove Bolts etc. made of Austenitic alloy steel of SS AISI 304/316 and DN 50 float of and other components with ABS/PTFE/EPDM/NBR and generally conforming to DIN/BIS/AWWA standards (or) combination Flange drilling as per IS - 1538 and transportation and other incidental charges etc,as per ss and as directed by the departmental officer incharge of work 80mm dia. PN 16 on 300 mm dia
Supply & Delivery of 80mm dia Tamper Proof DI Flanged Single Chamber Air Release Valves PN1.6(Mpa) with body & cover made of Ductile Iron Grade GGG-40/SG-400/15 or GGG-50/SG-500/7 or Equivalent as per IS1865, IS:3896-2 with Food Grade Epoxy Powder Coating(EP-P) (Min:250 Micron) inside and Outside of Color Blue RAL 5005. All internal parts such as Float, shell, Cove Bolts etc. made of Austenitic alloy steel of SS AISI 304/316 and DN 50 float of and other components with ABS/PTFE/EPDM/NBR and generally conforming to DIN/BIS/AWWA standards (or) combination Flange drilling as per IS - 1538 and transportation and other incidental charges etc,as per ss and as directed by the departmental officer incharge of work 80mm dia. PN 16 on 250 mm dia
Manufacture, Supply and delivery of 100mm dia PN 1.6 on 400mm dia line Air Cushion valves / Quick Released damped Air Valves (QRDA) as per AWWA, Ex-factory including transportation complete other incidental charges etc complete as per ss and as directed by the departmental officer incharge of work
Supply, Delivery of 400mm dia D.I Double Flanged Swing Check type Reflux valves (Non Retum Valves) PN 1.6(Mpa) of following dia. conforming to IS-5312 (Pts-1&2) (with amendments up to date. if any) having Body, Cover, Door, Bearing holder with D.I, Hinge pin, Door pin, Door suspension pin with Stainless Steel (IS 6603); Body seat ring. Door face ring, Bearing bushes, Plugs for hinge pin with Leaded Tin Bronze (IS 318), Bolts, Nuts with Carbon steel; Gaskets with Rubber; Hinges with Cast steel and transportation as per ss and as directed by the departmental officer incharge of work 400mm Dia
Supply, Delivery of 300mm dia D.I Double Flanged Swing Check type Reflux valves (Non Retum Valves) PN 1.6(Mpa) of following dia. conforming to IS-5312 (Pts-1&2) (with amendments up to date. if any) having Body, Cover, Door, Bearing holder with D.I, Hinge pin, Door pin, Door suspension pin with Stainless Steel (IS 6603); Body seat ring. Door face ring, Bearing bushes, Plugs for hinge pin with Leaded Tin Bronze (IS 318), Bolts, Nuts with Carbon steel; Gaskets with Rubber; Hinges with Cast steel and transportation as per ss and as directed by the departmental officer incharge of work 300mm Dia
Supply, Delivery of 250mm dia D.I Double Flanged Swing Check type Reflux valves (Non Retum Valves) PN 1.6(Mpa) of following dia. conforming to IS-5312 (Pts-1&2) (with amendments up to date. if any) having Body, Cover, Door, Bearing holder with D.I, Hinge pin, Door pin, Door suspension pin with Stainless Steel (IS 6603); Body seat ring. Door face ring, Bearing bushes, Plugs for hinge pin with Leaded Tin Bronze (IS 318), Bolts, Nuts with Carbon steel; Gaskets with Rubber; Hinges with Cast steel and transportation as per ss and as directed by the departmental officer incharge of work 250mm Dia
Supply, Delivery of 200mm dia D.I Double Flanged Swing Check type Reflux valves (Non Retum Valves) PN 1.6(Mpa) of following dia. conforming to IS-5312 (Pts-1&2) (with amendments up to date. if any) having Body, Cover, Door, Bearing holder with D.I, Hinge pin, Door pin, Door suspension pin with Stainless Steel (IS 6603); Body seat ring. Door face ring, Bearing bushes, Plugs for hinge pin with Leaded Tin Bronze (IS 318), Bolts, Nuts with Carbon steel; Gaskets with Rubber; Hinges with Cast steel and transportation as per ss and as directed by the departmental officer incharge of work - 200mm Dia
Supply, delivery of 400mm Electromagnetic flow meter manufacture should have ISO 9001:2008 certification anf flow meter testing confirming to ISO 17025; Flow meter tube SS 304; Flnages Carbon steel as per DIN PN 10 or higher rating as per requirement ;Liner;Hard rubber or PTFE suitsble for drinking water application; Grounding:Grounding rings SS 304/Grounding electrodes of material SS 316; Coil housing and junction box SS 304 Die cast Aluminium / Carbon steel with anticorrossive apoxy coating of minimim thickness 150 Micron /Equivalent as per EN-ISO-12944 standard as per site condition ingress protection ; IP 68 for Sensor and IP 67 for Transmitter; Flow Transmitter accuracy +/- 0.50% of measured values of velocities 0.50m/sec and above ,Display:Digital LCD/LED (backlit LCD/LED) Display instantaneous flow ,Bi-directional flow,totalised flow, Cable beween flow head and Transmitter maximum 25 m including PVC conduit,Surge arrester to be provided.Power supply and out put 230 V AC or 24V DC as appilicable to site condition and -4-20m A HART;Compatible to SCADA/WEB based data acqusition system;Flow meter test lab certification should be provided from NABL approved lab/FCRI Excluding taxes and duties with 5 years warrenty (make M/S krohne Marshall / Endress+Hauser / Yokagawa / siemens / Emerson / ABB / or equivalent make as directed by the departmental officer incharge of work
Supply,delivery of 400mm dia strainer /dirt box of T type of the following dia suitable to respective meters of same size inclusive of costs,transportation, etc complete as per SS and as directed by the departmental officer incharges of work (rate as per quatation)
Labour charges for lowering and keeping in position of 400mm dia C.I./DI Sluice valves(with cap/with hand wheel), reflux valves and scour valves.This rate including cost of all labour charges,hiring of machinery and other incidental charges and complete as per ss and as directed by the departmental officer incharge of work 400mm
Labour charges for lowering and keeping in position of 300mm dia C.I./DI Sluice valves(with cap/with hand wheel), reflux valves and scour valves.This rate including cost of all labour charges,hiring of machinery and other incidental charges and complete as per ss and as directed by the departmental officer incharge of work
Labour charges for lowering and keeping in position of 250mm dia C.I./DI Sluice valves(with cap/with hand wheel), reflux valves and scour valves.This rate including cost of all labour charges,hiring of machinery and other incidental charges and complete as per ss and as directed by the departmental officer incharge of work
Labour charges for lowering and keeping in position of 200 mm dia C.I./DI Sluice valves(with cap/with hand wheel), reflux valves and scour valves.This rate including cost of all labour charges,hiring of machinery and other incidental charges and complete as per ss and as directed by the departmental officer incharge of work
Labour charges for lowering and keeping in position of C.I./DI Sluice valves(with cap/with hand wheel), reflux valves and scour valves.This rate including cost of all labour charges,hiring of machinery and other incidental charges and complete as per ss and as directed by the departmental officer incharge of work as follows - 200mm
Labour charges for lowering and keeping in position of 100mm dia C.I./DI Sluice valves(with cap/with hand wheel), reflux valves and scour valves.This rate including cost of all labour charges,hiring of machinery and other incidental charges and complete as per ss and as directed by the departmental officer incharge of work
Labour charges for fixing Kinetic Air Valves 100mm dia PN 1.6 (Mpa)with isolating Sluice valves, Double Air valves/ Air Cushion valve excluding cost of jointing materials such as bolts, nuts and rubber insertions etc.,and complete as per ss and as directed by the departmental officer incharge of work
Labour charges for fixing Kinetic Air Valves 80mm dia PN 1.6 (Mpa)with isolating Sluice valves, Double Air valves/ Air Cushion valve excluding cost of jointing materials such as bolts, nuts and rubber insertions etc.,and complete as per ss and as directed by the departmental officer incharge of work
Lowering the D.I. Pipes K9 of 400mm dia all classes and fittings with flanged ends carefully into the trenches and laying them true to alignment and gradient including all sundries,hiring of machinery ,all labour charges,and other incidental charges etc, complete as per ss and as directed by the departmental officer incharge of work as follows(BIS No.3114/94) - 400mm dia
Lowering the D.I. Pipes K9 of 300mm dia all classes and fittings with flanged ends carefully into the trenches and laying them true to alignment and gradient including all sundries,hiring of machinery ,all labour charges,and other incidental charges etc, complete as per ss and as directed by the departmental officer incharge of work as follows(BIS No.3114/94) - 300mm dia
Lowering the D.I. Pipes K9 of 200mm dia all classes and fittings with langed ends carefully into the trenches and laying them true to alignment and gradient including all sundries,hiring of machinery ,all labour charges,and other incidental charges etc, complete as per ss and as directed by the departmental officer incharge of work as follows(BIS No.3114/94) - 200mm dia
Lowering the D.I. Pipes K9 of 150mm dia all classes and fittings with flanged ends carefully into the trenches and laying them true to alignment and gradient including all sundries,hiring of machinery ,all labour charges,and other incidental charges etc, complete as per ss and as directed by the departmental officer incharge of work as follows(BIS No.3114/94) - 150mm dia
Jointing the 400mm dia D.I. Pipes, fittings and valves with flanged ends including cost of jointing materials such as bolts, nuts, rubber insertion, white lead including all sundries,hiring of machinery ,all labour charges,and filling with water with a water lead upto 500 m and testing to required pressure and other incidental charges etc, complete as per ss and as directed by the departmental officer incharge of work as follows( BIS No.3114/85) - 400mm dia
Jointing the 300mm dia D.I. Pipes, fittings and valves with flanged ends including cost of jointing materials such as bolts, nuts, rubber insertion, white lead including all sundries,hiring of machinery ,all labour charges,and filling with water with a water lead upto 500 m and testing to required pressure and other incidental charges etc, complete as per ss and as directed by the departmental officer incharge of work ( BIS No.3114/85) - 300mm dia
Jointing the 200mm dia D.I. Pipes, fittings and valves with flanged ends including cost of jointing materials such as bolts, nuts, rubber insertion, white lead including all sundries,hiring of machinery ,all labour charges,and filling with water with a water lead upto 500 m and testing to required pressure and other incidental charges etc, complete as per ss and as directed by the departmental officer incharge of work as follows( BIS No.3114/85) - 200mm dia
Jointing the 150mm dia D.I. Pipes, fittings and valves with flanged ends including cost of jointing materials such as bolts, nuts, rubber insertion, white lead including all sundries,hiring of machinery ,all labour charges,and filling with water with a water lead upto 500 m and testing to required pressure and other incidental charges etc, complete as per ss and as directed by the departmental officer incharge of work ( BIS No.3114/85) - 150mm dia
Jointing the 100mm dia D.I. Pipes, fittings and valves with flanged ends including cost of jointing materials such as bolts, nuts, rubber insertion, white lead including all sundries,hiring of machinery ,all labour charges,and filling with water with a water lead upto 500 m and testing to required pressure and other incidental charges etc, complete as per ss and as directed by the departmental officer incharge of work ( BIS No.3114/85) - 100mm dia
Jointing the 80mm dia D.I. Pipes, fittings and valves with flanged ends including cost of jointing materials such as bolts, nuts, rubber insertion, white lead including all sundries,hiring of machinery ,all labour charges,and filling with water with a water lead upto 500 m and testing to required pressure and other incidental charges etc, complete as per ss and as directed by the departmental officer incharge of work ( BIS No.3114/85) - 80mm dia
RCC M-20 Nominal mix (cement,fine aggregate,coarse aggregate) corresponding to Table -9 of IS -456 using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and on all materials including all operational ,incidental and labour charges such as machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work,but including centering, shuttering and as directed by the departmental officer incharge of work.for Thrust Blocks ,Bends and Tees
RCC M-20 Nominal mix (cement,fine aggregate,coarse aggregate) corresponding to Table -9 of IS -456 using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and on all materials including all operational ,incidental and labour charges such as machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work,but including centering, shuttering and as directed by the departmental officer incharge of work.For Anchor Blocks
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 500/500D grade) of different diameters for RCC works, including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying including and other all materials etc., complete for finished item of work in all floors. as per SS and as directed by the departmental office incharge of work.
Construction Valve Chambers for Sluice Valve Earthwork in excavation for valve chamber as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH Note : Classifications of Earth Work Specification are as per 302.2.1(a) of MORD and 301.2.1 of MORT&H--ordinary soil--manual means upto 3m depth manual means
Filling Sand for foundation of Valve Chamber as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH.This rate including cost of sand ,filling charges,watering,ramming,and other incidental charges etc., complete as per ss and directed by the departmental officer incharge of work
Plain Cement Concrete for Vlave Chamber (1:4:8) (cement: fine aggregate: Coarse aggregate) using coarse aggregate 40mm size hard, machine crushed granite from approved quarry using concrete Mixer 10 / 7 cft (0.2 / 0.8 cum) capacity including cost and conveyance of all materials like cement, sand, coarse aggregate, water etc. to site including all charges for machine mixing and hire charges of concrete mixer, laying concrete finishing top surface to the required level curing etc., and complete for finished item of work as per SS and as directed by the departmental officer incharge of work. (APSS No. 402).for Valve Chamber bed concrete
RCC M-20 Nominal mix for Valve Chamber (cement,fine aggregate,coarse aggregate) corresponding to Table -9 of IS -456 using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and on all materials including all operational ,incidental and labour charges such as machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work,but including centering, shuttering and as directed by the departmental officer incharge of work as follows For Bottom Slab
RCC M-20 Nominal mix for Valve Chamber (cement,fine aggregate,coarse aggregate) corresponding to Table -9 of IS -456 using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and on all materials including all operational ,incidental and labour charges such as machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work,but including centering, shuttering and as directed by the departmental officer incharge of work as follows For Side walls allround
RCC M-20 Nominal mix (cement,fine aggregate,coarse aggregate) corresponding to Table -9 of IS -456 using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and on all materials including all operational ,incidental and labour charges such as machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work,but including centering, shuttering and as directed by the departmental officer incharge of work for Pre cast slabs
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying etc., complete for finished item of work in all floors.( APSS No.126) for pre cast slabs of culverts - RBR-FNDN-8 & Revised Data sl.No-5
Filling crushur stone dust in pipe line trenches for cutting portion as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH.This rate including cost of stone dust ,filling charges,watering,ramming,and other incidental charges etc., complete as per ss and directed by the departmental officer incharge of work
Restoration of CC road with Construction of un-reinforced, plain cement concrete pavement, thickness as per design, over a prepared sub base, with 43 grade cement or any other type as per Clause 1501.2.2 M30 (Grade), coarse and fine aggregates conforming to IS : 383, maximum in a concrete mixer of not less than 0.2 cum capacity and spreading the concrete with sholvels, rakes, compacted using needle, scareed and plate vibrators and finished in continuous operation, curing of concrete slabs for 14- days, curing compound (where specified) and water finishing to lines and grade as per drawing and Technical Specification Clause 1501 MORD and complete as per SS and as directed by the departmental officer incharges of work
Manufacture, Supply and Delivery of 450mm dia M.S. Dismantling Joints with both side flange end suitable for installation in between flange end pipes. Thickness as per IS: 7322. These rates including cost of materials, all labour charge other incidental charge etc complete
Manufacture, Supply and Delivery of 300mm dia C.I Dismantling Joints with both side flange end suitable for installation in between flange end pipes. These rates are and including transportation - 300mm dia as per SS and as directed by the departmental officer incharge of work.
Manufacture, Supply and Delivery of 250mm dia C.I Dismantling Joints with both side flange end suitable for installation in between flange end pipes. These rates are and including transportation - 250mm dia as per SS and as directed by the departmental officer incharge of work.
Manufacture, Supply and Delivery of 200mm dia C.I Dismantling Joints with both side flange end suitable for installation in between flange end pipes. These rates are and including transportation - 200mm dia as per SS and as directed by the departmental officer incharge of work.
Shifting of existing Electrical Pole and transformers for lying on the Pipe line alignment including shifting charges payble to AP Transco and other incidental charges etc.,complete and as per IE Rules and as directed by the departmental officer incharge of work
supply and delivery at work site 150mm internal dia M.S.Pipe fabricated with 8 mm thick MS plates confirming to IS 2062-1992 of grade A manufactured as per IS 3589-2001 in suitable lengths painted with two coats of food grade epoxy paint inside and outside to suit the site conditions, in co-ordination with the concerned authorities as per approved drawings and directed by the Engineer-in –charge including Cost of Laying, Jointing, Hydrostatic Filed Test Pressure, Including Cost of Site Welding, Jointing Materials And Cost of Transportation of Water Including Emptying Pipe Line After Completion Of Field Testing and as directed by the departmental officer incharge of work
Implementation of Environmental Management plan
Air Quality Monitoring (5 Monitoring station) once in a month for three seasons during the construction period at Coffer dam/Intake well and pumping main, Filtration Plant/WTP, Sump, ELSR's, Pumping main & Distribution network as directed by the departmental officer incharge of work
Noise level (5 Monitoring station) once in a month for three seasons during the construction period at Coffer dam/Intake well and pumping main, Filtration Plant/WTP, Sump, ELSR's, Pumping main & Distribution network as directed by the departmental officer incharge of work
Water Quality Monitoring surface / ground(5 Monitoring station) once in a month for three seasons during the construction period at Coffer dam/Intake well and pumping main, Filtration Plant/WTP, Sump, ELSR's, Pumping main & Distribution network as directed by the departmental officer incharge of work
Air Quality Monitoring (5 Monitoring station) once in a month for three seasons during the construction period at Coffer dam/Intake well and pumping main, Filtration Plant/WTP, Sump, ELSR's, Pumping main & Distribution network as directed by the departmental officer incharge of work
Noise level (5 Monitoring station) once in a month for three seasons during the construction period at Coffer dam/Intake well and pumping main, Filtration Plant/WTP, Sump, ELSR's, Pumping main & Distribution network as directed by the departmental officer incharge of work
Water Quality Monitoring surface / ground(5 Monitoring station) once in a month for three seasons during the construction periodat Coffer dam/Intake well and pumping main, Filtration Plant/WTP, Sump, ELSR's, Pumping main & Distribution network as directed by the departmental officer incharge of work
Compensatory plantation and three years maintenance (Compensatory afforestation ratio is 1:5) plants & tree guards as directed by the departmental officer incharge of work
Greenbelt development and maintenance in the surroundings / Buffer zone
Health checkups and free medical distribution (6 Camps)
Awareness program/training (every Six Months - 4 Camps)
Sprinkling of water once in a day for two years (excluding rainy days): 500 days @ Rs.800/trip
Hiring for 1 Nos. Vehicle during execution period including hire charges of vehicle, diesel, lubrication, driver charges, repairs and all incidental charges etc.,
Construction of Central SCADA Room and Construction of Central SCADA Room (G+1 Building)
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH - Manual Means upto 3 metres depth in ordinary soil
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH - Mechanical Means up to 3 metres depth in Ordinary Soil
Filling Sand in foundation of the building as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH This rate including cost of material all labour charges etc complete and as per ss and as direacted by the departmental officer incharge of work.
Plain Cement Concrete (1:4:8) (cement: fine aggregate: Coarse aggregate) using coarse aggregate 40mm size hard, machine crushed granite from approved quarry using concrete Mixer including cost and conveyance of all materials like cement, sand, coarse aggregate, water etc. to site including all charges for machine mixing and hire charges of concrete mixer, laying concrete finishing top surface to the required level curing for finished item of work as per SS and as directed by the departmental officer incharge of work.
Construction of RR Masonary in C.M (1: 6) prop. Using hard granite stone including cost and conveyance of all materials like cement, sand, water, Granite stone etc. including cost of all materials, including labour for cutting stones to required size and shape, mixing of cement mortar construction, Scaffolding charges etc. complete for finished item of work.
RCC M- 25 Design mix corresponding to Table 9 of IS 456 using 20mm size graded machine crushed hard granite metal (coarse aggregate) from approved quarry including cost and conveyance of all materials like cement, fine aggregate (sand) coarse aggregate, water etc., to site and including on all materials including all operational, incidental and labour charges such as machine mixing, laying concrete, curing centering,scaffolding , vibrating etc.,complete but excluding cost of steel and its fabrication charges for finished item of work, and other incidental charges etc., complete and as per ss and as direacted by the departmental officer incharge of work. As follows.
RCC M- 25 Design mix corresponding to Table 9 of IS 456 using 20mm size graded machine crushed hard granite metal (coarse aggregate) from approved quarry including cost and conveyance of all materials like cement, fine aggregate (sand) coarse aggregate, water etc., to site and including on all materials including all operational, incidental and labour charges such as machine mixing, laying concrete, curing centering,scaffolding , vibrating etc.,complete but excluding cost of steel and its fabrication charges for finished item of work, and other incidental charges etc., complete and as per ss and as direacted by the departmental officer incharge of work.for septic tank walls
RCC M- 25 Design mix corresponding to Table 9 of IS 456 using 20mm size graded machine crushed hard granite metal (coarse aggregate) from approved quarry including cost and conveyance of all materials like cement, fine aggregate (sand) coarse aggregate, water etc., to site and including on all materials including all operational, incidental and labour charges such as machine mixing, laying concrete, curing centering,scaffolding , vibrating etc.,complete but excluding cost of steel and its fabrication charges for finished item of work, and other incidental charges etc., complete and as per ss and as direacted by the departmental officer incharge of work. Footings
RCC M- 25 Design mix corresponding to Table 9 of IS 456 using 20mm size graded machine crushed hard granite metal (coarse aggregate) from approved quarry including cost and conveyance of all materials like cement, fine aggregate (sand) coarse aggregate, water etc., to site and including on all materials including all operational, incidental and labour charges such as machine mixing, laying concrete, curing centering,scaffolding , vibrating etc.,complete but excluding cost of steel and its fabrication charges for finished item of work, and other incidental charges etc., complete and as per ss and as direacted by the departmental officer incharge of work.- Pedastals around Columns
RCC M- 25 Design mix corresponding to Table 9 of IS 456 using 20mm size graded machine crushed hard granite metal (coarse aggregate) from approved quarry including cost and conveyance of all materials like cement, fine aggregate (sand) coarse aggregate, water etc., to site and including on all materials including all operational, incidental and labour charges such as machine mixing, laying concrete, curing centering,scaffolding , vibrating etc.,complete but excluding cost of steel and its fabrication charges for finished item of work, and other incidental charges etc., complete and as per ss and as direacted by the departmental officer incharge of work. Columns Up to plinth
RCC M- 25 Design mix corresponding to Table 9 of IS 456 using 20mm size graded machine crushed hard granite metal (coarse aggregate) from approved quarry including cost and conveyance of all materials like cement, fine aggregate (sand) coarse aggregate, water etc., to site and including on all materials including all operational, incidental and labour charges such as machine mixing, laying concrete, curing centering,scaffolding , vibrating etc.,complete but excluding cost of steel and its fabrication charges for finished item of work, and other incidental charges etc., complete and as per ss and as direacted by the departmental officer incharge of work. -Plinth Beams 300 x 400
RCC M- 25 Design mix corresponding to Table 9 of IS 456 using 20mm size graded machine crushed hard granite metal (coarse aggregate) from approved quarry including cost and conveyance of all materials like cement, fine aggregate (sand) coarse aggregate, water etc., to site and including on all materials including all operational, incidental and labour charges such as machine mixing, laying concrete, curing centering,scaffolding , vibrating etc.,complete but excluding cost of steel and its fabrication charges for finished item of work, and other incidental charges etc., complete and as per ss and as direacted by the departmental officer incharge of work. Columns
RCC M- 25 Design mix corresponding to Table 9 of IS 456 using 20mm size graded machine crushed hard granite metal (coarse aggregate) from approved quarry including cost and conveyance of all materials like cement, fine aggregate (sand) coarse aggregate, water etc., to site and including on all materials including all operational, incidental and labour charges such as machine mixing, laying concrete, curing centering,scaffolding , vibrating etc.,complete but excluding cost of steel and its fabrication charges for finished item of work, and other incidental charges etc., complete and as per ss and as direacted by the departmental officer incharge of work. Up to First Floor Roof Level
RCC M- 25 Design mix corresponding to Table 9 of IS 456 using 20mm size graded machine crushed hard granite metal (coarse aggregate) from approved quarry including cost and conveyance of all materials like cement, fine aggregate (sand) coarse aggregate, water etc., to site and including on all materials including all operational, incidental and labour charges such as machine mixing, laying concrete, curing centering,scaffolding , vibrating etc.,complete but excluding cost of steel and its fabrication charges for finished item of work, and other incidental charges etc., complete and as per ss and as direacted by the departmental officer incharge of work. Beams 230 x 500
RCC M- 25 Design mix corresponding to Table 9 of IS 456 using 20mm size graded machine crushed hard granite metal (coarse aggregate) from approved quarry including cost and conveyance of all materials like cement, fine aggregate (sand) coarse aggregate, water etc., to site and including on all materials including all operational, incidental and labour charges such as machine mixing, laying concrete, curing centering,scaffolding , vibrating etc.,complete but excluding cost of steel and its fabrication charges for finished item of work, and other incidental charges etc., complete and as per ss and as direacted by the departmental officer incharge of work. Lintels
RCC M- 25 Design mix corresponding to Table 9 of IS 456 using 20mm size graded machine crushed hard granite metal (coarse aggregate) from approved quarry including cost and conveyance of all materials like cement, fine aggregate (sand) coarse aggregate, water etc., to site and including on all materials including all operational, incidental and labour charges such as machine mixing, laying concrete, curing centering,scaffolding , vibrating etc.,complete but excluding cost of steel and its fabrication charges for finished item of work, and other incidental charges etc., complete and as per ss and as direacted by the departmental officer incharge of work. Sunshades avarre thick ness 100mm width 0.60m wid
RCC M- 25 Design mix corresponding to Table 9 of IS 456 using 20mm size graded machine crushed hard granite metal (coarse aggregate) from approved quarry including cost and conveyance of all materials like cement, fine aggregate (sand) coarse aggregate, water etc., to site and including on all materials including all operational, incidental and labour charges such as machine mixing, laying concrete, curing centering,scaffolding , vibrating etc.,complete but excluding cost of steel and its fabrication charges for finished item of work, and other incidental charges etc., complete and as per ss and as direacted by the departmental officer incharge of work. - Staircase slab 0.15 m thick upto 2nd floor
RCC M- 25 Design mix corresponding to Table 9 of IS 456 using 20mm size graded machine crushed hard granite metal (coarse aggregate) from approved quarry including cost and conveyance of all materials like cement, fine aggregate (sand) coarse aggregate, water etc., to site and including on all materials including all operational, incidental and labour charges such as machine mixing, laying concrete, curing centering,scaffolding , vibrating etc.,complete but excluding cost of steel and its fabrication charges for finished item of work, and other incidental charges etc., complete and as per ss and as direacted by the departmental officer incharge of work. RCC Slab 150mm thick Grand flow and Ist floor slabs
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 500/500D grade) of different diameters for RCC works, including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying including and other all materials etc., complete for finished item of work in all floors. as per SS and as directed by the departmental office incharge of work.
Brick masonary in CM (1:6) using 2nd class bricks of size 23 x 11 x 7cms. Cost including cost and conveyance of all materials at site, labour charges for curing , scaffolding, all lifts, other incidental charges etc.,Complete as per SS and as directed by the departmental officer incharge of work. - Ground floor
Brick masonary in CM (1:6) using 2nd class bricks of size 23 x 11 x 7cms. Cost including cost and conveyance of all materials at site, labour charges for curing , scaffolding, all lifts, other incidental charges etc.,Complete as per SS and as directed by the departmental officer incharge of work. - First floor
11.5 cm wide Brick masonry for super-structure on ground floor in cm (1:3) using second class traditional size bricks including cost of all materials, seigniorage charges, labour and all operations for constructing half brick masonry, mixing cement mortar, curing etc., complete for finished item of work, for toilets walls
Plastering with CM (1:4), 20 mm thick including cost and conveyance of all materials and water to work site and all operational incidental, labour charges such as scaffolding, mixing mortar lift charges curing etc., complete for finished item of work. for ground floor and 1st floor walls
Plastering with CM (1:3), 12 mm thick including cost and conveyance of all materials and water to work site and all operational incidental, labour charges such as scaffolding, mixing mortar lift charges curing etc., complete for finished item of work.for Ground floor and 1st floor
Plastering with CM (1:3), 12 mm thick including cost and conveyance of all materials and water to work site and all operational incidental, labour charges such as scaffolding, mixing mortar lift charges curing etc., complete for finished item of work.for ceiling
Flooring with Nano polished /stain free soluble salt porcelain vitrified tiles screen printed of size 600 x 600 mm and thickness between 8-10 mm 1st quality conforming to IS:13711, IS:13712, IS:13630 (Parts 1 to 15) of any colour and finish in all shades and designs, set over base coat of cement mortar (1:8), 12 mm thick over CC bed already laid or RCC roof slab, including neat cement slurry of honey like consistency spread @ 3.3.kgs per sqm & jointed neatly with white cement paste to full depth mixed with pigment of matching shade, including cost of all materials like cement, sand water and tiles etc., complete for finished item of work
Flooring with non-skid ceramic tiles of size (600X 600, set over base coat of cement mortar (1:8), 12 mm thick over CC bed already laid or RCC roof slab, including neat cement slurry of honey like consistency spread @ 3.3.kgs per sqm & jointed neatly with white cement paste to full depth mixed with pigment of matching shade, including cost of all materials like cement, sand water and tiles etc., complete, including seigniorage charges, etc., complete for finished item of work, including the cost of conveyance of all materials.
Dadooing to walls with first quality glazed coloured tiles approved colour of any size set over base coat of C.M(1:3)prop. 12mm thick and neat grey cement slurry of honey like consistency spread at the rate of 3.3Kg of cement per sqm and jointed with neat white cement paste at 0.20 kg per sqm mixed with pigment of matching shade to match the shade of tiles including cost and conveyance of all materials labour charges, water to work site,seignourage and all operational .incidental , mixing mortar , fixing in position ,lift charges, curing etc., complete as per SS or as directed by the departmental authorities for finished item of work.
Painting Walls with Snowcem or other equal and approved Water Proof Cement Paint 2 Coats (All Colours) over a base coat of aproved cement primer making 3 coats in total including cost of all materials, conveyance charges of materials and including all operational, incidental and labour charges etc,, complete for finished item of work as directed by the departmental authorities for extenal walls in GF & FF
Painting Walls with Snowcem or other equal and approved Water Proof Cement Paint 2 Coats (All Colours) over a base coat of aproved cement primer making 3 coats in total including cost of all materials, conveyance charges of materials and including all operational, incidental and labour charges etc,, complete for finished item of work as directed by the departmental authorities.for internal wall GF&Ff
Painting Walls with Snowcem or other equal and approved Water Proof Cement Paint 2 Coats (All Colours) over a base coat of aproved cement primer making 3 coats in total including cost of all materials, conveyance charges of materials and including all operational, incidental and labour charges etc,, complete for finished item of work as directed by the departmental authorities.fr seada room in GF&Ff
Providing & Fixing of Scientific Doors with metal door frames and door shutters made of galvanize steel (base steel as per IS 513 of 0.58 mm thick D quality, galvanized as per IS 277 with Zinc of 120 GSM) pure polyester powder upto 50-60 microns thick, outer frame section of 100 x 58 mm x 1.2 mm thick, shutter section of 0.80 mm thick galvanized steel sheet pressed (roll formed) for 46mm thick fully flush, double skin door shell seam joints at stile edges, in-fill of honeycomb kraft paper used to give the equired rigidity and effective acoustic insulation with 6” Tower bolt – 1 No., 6” D handles – 2 Nos., 10” Aldrop – 1 No., Butt Hinges – 3 Nos, Mortise Lock of approved quality – 1 No, frames fixed to the concrete/masonry wall by means of self expanding screws complete for finished item of work for Single leaf Door
Supply and fixing of pre-painted steel openable windows base steel as per IS 513 of -0.58 mm thick 'D" quality, galvanized as per IS 277 , finish painted with a polyester paint of 12-16 microns thick and back coated with 5-7 microns thick alkyd backer, section for outer frame of 46 x 52 mm section and for shutter of 46 x 46 mm section for mullion 46 x 70 mm, and section for beading should be 18 x 25 mm with 5 mm thick plain float glass fitted with Ethyl propylene Diamine monomer Gasket (EPDM) and handle made of high grade aluminium powder coated with frames fixed to the concrete /masonry wall by means of self expanding screws including 10 mm square guard bars with 6" pitch double shutter 914.4mm x 1219.20 out from sectiin size 46x52mm shutter from section size 46x46 muliion section size 46x70mm complete for finished item of work
Providing & fixing 30 mm thick solid panel PVC door shutter consisting of frame made out of 19 guage M.S tube of 19 x 19 mm for stiles, top & bottom rail, with a coat of primer of approved make. M.S. Frame covered with 5 mm thick heat moulded PVC “C” channel of size of 30 x 50 mm forming stiles, 5 mm thick 75 mm wide PVC sheet for top, lock & bottom rail on either side 20 mm wide cross PVC sheet as gap insert for top & bottom rail, panelling of 10mm(+/-)( 5mm+5mm)” thick PVC sheet fitted in the M.S. frame welded /sealed to the stiles, on either side joined together with solvent cement adhesive etc., additional 5 mm thick PVC strip of 20 mm width stuck on the interior side of the C channel using solvent cement, complete as per direction of Engineer–in–charge, manufacturers specification.
Supplying and fixing of Top Hung Ventilators made of pre - painted steel (base steel as per IS 513 of -0.58 mm thick 'D" quality, galvanized as per IS 277 with zinc of 120 GSM) primer coated with epoxy primer of 5-7 microns thick, finish painted with a polyester paint of 12-16 microns thick and back coated with 5-7 microns thick alkyd backer, section for outer frame of 46 x 52 mm section and for shutter of 46 x 46 mm section for mullion 46 x 70 mm, The Ventilator to be panelled 4 mm pinhead glass with Ethyl propylene Diamine monomer Gasket (EPDM) and the sections cut to length mitre joined with corner brocket mullions fixed using mullion cap and with handle made of high grade aluminium powder coated and nylon receiver, corner brackets made of CRCA with Zinc Phosphate, Mullion caps made of glass filled nylon, frames fixed to the concrete /masonry wall by means of self expanding screws including 10 mm square guard bars with 6" pitch complete for finished item of work.
Providing and fixing Thermocole False ceiling in true horizontal level 600 mm x 600 mm using 15 mm/ 19 mm thick Thermocole sheet anodized Aluminium Tee sections of size 24.50 mm x 24.0 mm x 2.4 mm in grid with cross tee of size 24 x 24.5 mm at every 600 mm c/c and anodized aluminium wall angle of size 24 x 24 mm fixed to periphery of the wall and the above grid is suspended at every 1200 mm c/c in both directions using 2.0 mm thick GI Wire for finished of size 600 x 600 mm including Cost &conveyance of all materials and labour charges such as cutting , fixing of standing of frame work exposing roof making complete for finished item of work for Ground Floor and 1st Floor
Supply and fixing of 25 mm dia 2.00 mm thick PVC pipe concealed in roof slab with all required accessories including masonary work all labour chages complete as per IE Rules and as directed by the departmental officer incharge of work
Supply and fixing of 20 mm dia 1.50 mm thick PVC pipe concealed in walls with all required accessories including masonary work for light , fan and plug point with metal deep box including all labour chages complete as per IE Rules and as directed by the departmental officer incharge of work
Wiring with 2 runs 14/0.3 mm. (1.0. sq.mm) Fire retardant PVC insulated Flexible copper cable in existing pipe with 6A siwtch, ceiling rose and 3 mm thick hyla sheet covering to switch control box including all labour charges etc,., complet for light, bell , fan and exhaust fan points in non - residential building complete as per IE Rules and as directed by the departmental officer incharge of work
Wiring with 2 runs 14/0.3 mm. (1.0. sq.mm) Fire retardant PVC insulated Flexible copper cable in existing pipe with 6A modular siwtch control and 3/2 pin sockets fixing on board including all labour charges complete as per IE Rules and as directed by the departmental officer incharge of work
supply and run of 2 of 36/0.3 mm. (1.5. sq.mm) Fire retardant PVC insulated Flexible copper cable in existing pipe for mains including all labour charges complete as per IE Rules and as directed by the departmental officer incharge of work
supply and run of 1 of 14/0.3 mm. (1.0. sq.mm) Fire retardant PVC insulated Flexible copper cable in existing pipe for earth continuity including all labour charges etc.
supply and run of 2 of 6 sq.mm (7/18) WPSC alluminium cable along with No.10 SWG G.I barer wire through PVC cleats with all accessories including all labour charges etc.,complete as per IE Rules and as directed by the departmental officer incharge of work
Providing independent earthing by excavating a trench to a depth of 2.10m in all soils, as per size specied in data ,using 40 mm dia B class GI pipe 2.50m long with necessary accessories with hume pipe ring duly providing staggered holes including filling with equal proportion of salt and charcoal in layers and all labour charges etc complete as per IE Rules and as directed by the departmental officer incharge of work
Supply and fixing SPN Distribution board with IP-20 protection suitable for single phase Earth Leakage Circute Braker (ELCB) / Residual Current Circute Braker (RCCB) / Double Pole (DP) Isolator as incomer and 10kA SP MCBs as out going including internal connections and labour charges for surface / flush mounting etc., complete as per IE Rules and as directed by the departmental officer incharge of work
Supply of 48" (1200mm) Sweep 5 star rated Ceiling Fan , with double ball bearings, air delivery more than 200 cubic meter/min but without Regulator.Makes : Crompton HS Plus / Havells ES Neo/Orient Energy Star/ Halonix(Zephyr)/Polycab(Synergy Star) unit each complete as per IE Rules and as directed by the departmental officer incharge of work
Supply of stepped type Electronic Regulator of Makes: GM G Home / Gold Medal Olive / Million Zoom / Great white Omega/Koncept/Vimal opel/ Anchor/Vihan/CPL complete as per IE Rules and as directed by the departmental officer incharge of work
Supply of 20 W Box type tube light luminaire powder coated CRCA sheet steel housing with Electronic Ballast Chokes and all standard accessoriesof makes Wipro / G.E. / Phillips / Crompton / Bajaj. complete as per IE Rules and as directed by the departmental officer incharge of work
Supply of 2.0 TR 5 Star capable of delivering 24000 BTU/ hr and above with operating on refrigerant R-32 / R-410A AC unit with high wall mounted indoor unit and outdoor condencing unit Hermetically sealed compressor suitable for operation on 230V, 50Hz, 1Phase AC supply capable of performing cooling dehumidifying air circulating and filtering with cooling and condensing units with 3 mts of copper piping, insulation kit and 4 mts of 3 core copper flexible cable including cordless remote control etc.ELEC-5.5.1k complet as per IE rules and as directed by the departmental officer inharge of work
Providing & Placing on Terrace (at all floor levels) polyethylene water storage tank with Double layer approved brand & manufacture with cover and suitable locking arrangement & making necessary holes for inlet & outlets and over flow pipes but without fittings & base support for tanks complet as per ss rules and as directed by the departmental officer inharge of work
Supplying and fixing 580mm x 440mm long Orissa pan white glazed Water Closet 1st quality ISI marked confirming to IS:2556-Part-3-1981 with "P" or "S" trap, ISI marked and providing masonry seat, CC squatting plate and 10 litres capacity single flush PVC low level cistern with internal components fixed on 2 Nos. of teak wood blocks of size 76.20mm x 101.60mm using required size of nails, screws as approved by Engineer-in-charge, 15 mm nominal size CP finish brass angled stop valve screw type with internal /external threaded conforming to IS 8931, 12.70mm PVC connection with brass union nuts CP coated , 31.75mm brass plumber union, P trap or S trap of Indian W.C. shall be encased on CC (1:2:4) 150mm alround well above the joint to stop leakage at the joint etc., complete including cost and conveyance of all materials to site, cost of CC bed, labour charges and seigniorage charges, overheads & contractors profit etc., complete for finished item of work for toilets
Supplying and fixing Indian make Flat Back Wash Hand Basin 1st quality conforming to IS:2556-Part-4:1972 with waste fittings like rubber plug, chain,32 mm nominal size C.P. Fitting with parallel pipe thread conforming to IS:2963-1979 and fitted with 15 mm nominal bore Chromium Plated Pillar Tap of 1st quality Indian make 400 grams Seiko/ Senior/ Nice/ Esso or equivalent complete with standard CI brackets including wooden block: 550 x 400 mm - Single C.P. Pillar cock ,1 No.12.70mm PVC connection with brass union nuts CP coated , angle stop cock 12.70mm dia. first quality Indian make heavy duty, 31.75mm brass plumber union, 31.75mm dia PVC flexible waste pipe of 914.4mm length of Ist quality including cost and conveyance of all materials to site, labour charges , overheads & contractors profit for finished item of work
Supplying and fixing white glazed flat back Bowl urinals of size 440 mm x 265 mm x 315 mm with integral flushing rim fixed with screws complete Indian make conforming to IS:2556-1995 as approved by Engineer-in-charge, including supply and fixing 31.75 mm brass plumber Union best Indian first quality, 12.7mm PVC connection with brass plumber union nuts CP coated, 12.70mm push cock 1st quality of approved make , 31.75mm dia PVC flexible waste pipe of 914.4 mm length of Ist quality including cost and conveyance of all materials to site, labour charges , overheads & contractors profit complete for finished item of work for all floors.
Supply of 110 mm dia 3 m single Socket PVC/SWR pipe - 6 Kg/sq.cm - Prince/Sudhakar/Kisan/Supreme or any ISI Brand. complet as per ss rules and as directed by the departmental officer inharge of work
Supply of 110 mm dia - Plain Bend 87.5 Degree - UPVC/SWR Pipe fittings (Prince/Sudhakar/Kisan/Supreme or any ISI Brand) complet as per ss rules and as directed by the departmental officer inharge of work
Supply of 110 mm dia - 3.00mts long pipe Coupler - UPVC/SWR Pipe fittings (Prince/Sudhakar/Kisan/Supreme or any ISI Brand complet as per ss rules and as directed by the departmental officer inharge of work
Labour charges for 100mm dia laying, fixing and commissioning the PVC pipes including Supplying & fixing 76.2 mm W.I clamps/ couplers/ bends/ tees etc any diameter including fixing necessary fittings like bends, plugs, couplers, junctions, tees, etc with solvent jointing as per standard practice complet as per ss rules and as directed by the departmental officer inharge of work
Constructing 457.2 mm x 457.2 mm (1'6"x1'6") brick in CM 1:6 prop. Masonry. Inspection chamber up to 914.4 mm (3'0") and fitted with light weight 457.2 mm x 457.2 mm (1'6"x1'6") C.I frame and cover of 20 Kg complet as per ss rules and as directed by the departmental officer inharge of work
S& F GI pipe Medium Grade properties & weight as per IS 1239 ISI mark with GI fittings including the cost of pipe & its fittings & labour charges complet as per ss rules and as directed by the departmental officer inharge of work as follows
25 mm dia nominal bore -from tank to jn for of individual lines and inlet
20 mm dia nominal bore -from jn for of individual lines to toilets
15 mm dia nominal bore -for internal
S&F of GI & GM fittings
supply, delivery and fixing of the GM Ball valve with SS Ball and SS Spindle as per IS - Class - I, Indian make heavy type - 25 mm NB Size including cost of materials all labour charges, other incidental charge etc complete as per directed by the departmental officer incharge of work
supply, delivery and fixing of the GM Ball valve with SS Ball and SS Spindle as per IS - Class - I, Indian make heavy type - 20 mm NB Size including cost of materials all labour charges, other incidental charge etc complete as per directed by the departmental officer incharge of work
supply, delivery and fixing of the GM Ball valve with SS Ball and SS Spindle as per IS - Class - I, Indian make heavy type - 15 mm NB Size including cost of materials all labour charges, other incidental charge etc complete as per directed by the departmental officer incharge of work
supply, delivery and fixing of the S&F 12.7 mm N.P bib tap Indian make heavy dutys Seiko/ Senior/ Nice or equivalent including cost of materials all labour charges, other incidental charge etc complete as per directed by the departmental officer incharge of work
S& F GI union Ist Quality Supply, Delivery and fixing of the following GI union 1st quality including cost of Materials all labour charges other incidental charges etc complete as directed by the departmental officer incharge of work.
Laying new Distribution lines zone-I
Earthwork in excavation for Pipe Line Trenche by Mechanical/Manual Means as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH as per ss and as directed by the departmental officer in-charge of work as follows Manual Means
Earthwork in excavation for Pipe Line Trenche by Mechanical/Manual Means as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH as per ss and as directed by the departmental officer in-charge of work as follows Mechanica Means
Manufacture, supply and delivery of the following HDPE Pipes PE 100-Grade PN-6Kg/Sqcm confirming to IS 4984-2016 including transportation to anywhere in ap from factory to work site , stacking ,other incidental charges and Transit Risk etc complete and as directed by the departmental officer in charge of the work
110mm dia.
160mm dia.
200mm dia.
250mm dia.
315 mm dia.
Manufacture, supply and delivery of the following HDPE Specials PE 100-Grade confirming to IS 4984-2016 including transportation to anywhere in ap from factory to work site , stacking ,other incidental charges and Transit Risk etc complete and as directed by the departmental officer in charge of the work
a) Pipe ends - long neck
110mm dia.
160mm dia.
160 mm dia for Air TEEs
200mm dia.
200 mm dia for Air TEEs
250mm dia.
250 mm dia for Air TEEs
355 mm dia
355 mm dia for Air TEEs
355 mm dia for bulk flow meter
b) MS Flanges
110mm dia.
160mm dia.
160 mm dia for Air TEEs
200mm dia.
200 mm dia for Air TEEs
250mm dia.
250 mm dia for Air TEEs
355 mm dia
355 mm dia for Air TEEs
355 mm dia for bulk flow meter
c) End Caps
110mm dia.
160mm dia.
200mm dia.
d) Reducers
110X125 mm dia
125x140 mm dia
140x160 mm dia
e) TEES
110mm dia.
160mm dia.
200mm dia.
250mm dia.
355mm dia
F)Bends
110mm dia.
160mm dia.
200mm dia.
250mm dia.
355mm dia
Laying and jointing of the following HDPE pipes by butt fusion welding as per IS 7634-part-II/1975 as amended from time to time to the alignment and gradient and testing the pipeline to required pressure etc.complete.Thi rate including cost of all labour charges,testing the pipe line,hiring of machinery,fuel charges,wages of drivers and other incidental charges etc.complete as per ss and as directed by the departmental officer incharge of work
110mm dia.
160mm dia.
200mm dia.
250mm dia.
315mm dia
Supply and delivery of Centrifugally cast (spun) Ductile Iron Fittings of DI double socket branch flange Tee, DI All Socket Tees, DI Double socket Tapers (Reducer), DI Flanged Socket, DI Flanged Spigot, DI Double Socket Duck Foot Bend, DI Double Flange Duck/Foot bend, DI All socket Cross, DI All Flange Tee, DI All Flange Cross, DI Double Flange Reducer, Blank Flange, Mechanical Joints, DI Double Socket Bends, DI Double Flanged Bends and DI Manhole Frame & cover conforming to IS:9523/2000 having dimensions Up to 500 x 500 mm dia. The rates mentioned here under are for fittings, zinc coated externally with inside mortar lining (with finishing as per class 13/IS 9523/2000) ( ex-works) including Transportation and as directed by the departmental officer incharge of work.
100X2.00m on 110 dia mains for scours
100X2.00m on 160 dia mains for scours
100x1.00m long DF pipes for sluice valves
150X2.00m on 200 mm dia mains for scours
150x1.00m long DF pipes for sluice valves
200x1.00m long DF pipes for sluice valves
250x1.00m long DF pipes for sluice valves
350x1.00m long DF pipes for sluice valves
350x1.00m long DF pipes for bulk flow meter
deck foot bends, semicircular bends, air valves
Supply and delivery of "Resilient Seated Soft Sealing" Gate Valves (Sluice Valves) PN 1.6(Mpa) with Body and Bonnet of Ductile Iron GGG-40/SG-400/15 or GGG-50/SG-500/7 or Equivalent as per IS1865, IS:3896-2 and Wedge fully Rubber Lined with food grade quality grade W270 grade EPDM, Replaceable Spindle Nut without gland packing with 3-O ring protection system on the Shaft and Seals of NBR. The Valves should be Vacuum tight and 100% leak proof with face to face dimensions as BS:5163 Type A/IS:14846. All the valves should be with fusion bonded Electrostatic Powder coating both inside and outside (Min 250 Microns)- RAL 5005 with Pocket Less Straight through body Passage conforming to Design standards of DIN-3202F4/BS:5163 Type A Flange drilling as per IS - 1538 and transportation and other incidental charges etc,as per ss and as directed by the departmental officer incharge of work as follows
100 mm distrubution
150mm dia for distrubution
200mm dia for distrubution
250mm dia for distrubution
350mm dia for distrubution
100mm dia on 110 mm dia mains
100mm dia on 160 mm dia mains
150 mm dia on 200 mm dia lines
Manufacture, supply and delivery of 80mm dia Single Chamber DI Air Valve with Body and cover in Ductile Iron of grade SG 400/12 or equivalent grade as per I.S.3896-part2-1985 and subsequent revisions. All internal parts such as float, shell etc., all cover bolts, of stainless steel, and Gaskets and seals of EPDM food grade quality Epoxy powder coating (EP-P) inside and outside colour blue. Drilled as per IS:1538. PN1.6 complete as per ss and as direceted by the departmental officer incharge of work
Labour charges for lowering and keeping in position of C.I./DI Sluice valves(with cap/with hand wheel), reflux valves and scour valves.This rate including cost of all labour charges,hiring of machinery and other incidental charges and complete as per ss and as directed by the departmental officer incharge of work as follows
100 mm distrubution
150mm dia for distrubution
200mm dia for distrubution
250mm dia for distrubution
350mm dia for distrubution
350 mm dia for bulk flow meter
100mm dia on 110 mm dia mains
100mm dia on 160 mm dia mains
150 mm dia on 200 mm dia lines
Labour charges for fixing Kinetic Air Valves with isolating Sluice valves, Double Air valves/ Air Cushion valve excluding cost of jointing materials such as bolts, nuts and rubber insertions etc., complete.as per as ss and as directed by the departmental officer incharge of work
Construction Valve Chambers for Sluice Valve Earthwork in excavation for valve chamber as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH Note : Classifications of Earth Work Specification are as per 302.2.1(a) of MORD and 301.2.1 of MORT&H--ordinary soil--manual means upto 3m depth manual means
Filling Sand for foundation of Valve Chamber as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH.This rate including cost of sand ,filling charges,watering,ramming,and other incidental charges etc., complete as per ss and directed by the departmental officer incharge of work
Plain Cement Concrete for Vlave Chamber (1:4:8) (cement: fine aggregate: Coarse aggregate) using coarse aggregate 40mm size hard, machine crushed granite from approved quarry using concrete Mixer 10 / 7 cft (0.2 / 0.8 cum) capacity including cost and conveyance of all materials like cement, sand, coarse aggregate, water etc. to site including all charges for machine mixing and hire charges of concrete mixer, laying concrete finishing top surface to the required level curing etc., and complete for finished item of work as per SS and as directed by the departmental officer incharge of work. (APSS No. 402).for Valve Chamber bed concrete
RCC M-20 Nominal mix for Valve Chamber (cement,fine aggregate,coarse aggregate) corresponding to Table -9 of IS -456 using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and on all materials including all operational ,incidental and labour charges such as machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work,but including centering, shuttering and as directed by the departmental officer incharge of work as follows - For Botom slab
RCC M-20 Nominal mix for Valve Chamber (cement,fine aggregate,coarse aggregate) corresponding to Table -9 of IS -456 using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and on all materials including all operational ,incidental and labour charges such as machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work,but including centering, shuttering and as directed by the departmental officer incharge of work as follows - For Side walls around
RCC M-20 Nominal mix (cement,fine aggregate,coarse aggregate) corresponding to Table -9 of IS -456 using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and on all materials including all operational ,incidental and labour charges such as machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work,but including centering, shuttering and as directed by the departmental officer incharge of work for Pre cast slabs
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying etc., complete for finished item of work in all floors.( APSS No.126) for pre cast slabs of culverts - RBR-FNDN-8 & Revised Data sl.No-5
Lowering the 100mm dia D.I. Pipes K9 of all classes and fittings with flanged ends carefully into the trenches and laying them true to alignment and gradient including all sundries,hiring of machinery ,all labour charges,and other incidental charges etc, complete as per ss and as directed by the departmental officer incharge of work BIS No.3114/94) - 100mm
Lowering the 150mm dia D.I. Pipes K9 of all classes and fittings with flanged ends carefully into the trenches and laying them true to alignment and gradient including all sundries,hiring of machinery ,all labour charges,and other incidental charges etc, complete as per ss and as directed by the departmental officer incharge of work (BIS No.3114/94) - 150mm
Lowering the 200mm dia D.I. Pipes K9 of all classes and fittings with flanged ends carefully into the trenches and laying them true to alignment and gradient including all sundries,hiring of machinery ,all labour charges,and other incidental charges etc, complete as per ss and as directed by the departmental officer incharge of work (BIS No.3114/94) - 200mm
Lowering the 250mm D.I. Pipes K9 of all classes and fittings with flanged ends carefully into the trenches and laying them true to alignment and gradient including all sundries,hiring of machinery ,all labour charges,and other incidental charges etc, complete as per ss and as directed by the departmental officer incharge of work as follows(BIS No.3114/94) - 250mm
Lowering the 350mm dia D.I. Pipes K9 of all classes and fittings with flanged ends carefully into the trenches and laying them true to alignment and gradient including all sundries,hiring of machinery ,all labour charges,and other incidental charges etc, complete as per ss and as directed by the departmental officer incharge of work (BIS No.3114/94) - 350mm
Jointing the D.I. Pipes, fittings and valves with flanged ends including cost of jointing materials such as bolts, nuts, rubber insertion, white lead including all sundries,hiring of machinery ,all labour charges,and filling with water with a water lead upto 500 m and testing to required pressure and other incidental charges etc, complete as per ss and as directed by the departmental officer incharge of work as follows( BIS No.3114/85)
80 mm dia
100 mm dia
150 mm dia
200 mm dia
250 mm dia
300 mm dia
350 mm dia
Cutting of existing B.T.road surface (aswell as asphalt concrete up to 75mm thick) including water bound macadam including all labour charges for cutting, stacking of materials etc.including cost of all labour charges ,hiring of machinery fuel charges ,wages of driver etc., complete as per the directions of departmental authorities. For pipe line trenches.
Cutting and open of C.C. Road surface including stacking of excavated materials for lying of pipe lines etc.including cost of all labour charges ,hiring of machinery fuel charges ,wages of driver etc., complete as per the directions of departmental authorities. For pipe line trenches.
Cutting and open of Water bound macadam surface including stacking of excavated materials etc.including cost of all labour charges ,hiring of machinery fuel charges ,wages of driver etc., complete as per the directions of departmental authorities. For pipe line trenches.
Filling crushur stone dust in pipe line trenches for cutting portion as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH.This rate including cost of stone dust ,filling charges,watering,ramming,and other incidental charges etc., complete as per ss and directed by the departmental officer incharge of work
Restoration of CC road with Construction of un-reinforced, plain cement concrete pavement, thickness as per design, over a prepared sub base, with 43 grade cement or any other type as per Clause 1501.2.2 M30 (Grade), coarse and fine aggregates conforming to IS : 383, maximum in a concrete mixer of not less than 0.2 cum capacity and spreading the concrete with sholvels, rakes, compacted using needle, scareed and plate vibrators and finished in continuous operation, curing of concrete slabs for 14- days, curing compound (where specified) and water finishing to lines and grade as per drawing and Technical Specification Clause 1501 MORD and complete as per SS and as directed by the departmental officer incharges of work
Laying new Distribution lines zone-II
Earthwork in excavation for Pipe Line Trenche by Mechanical/Manual Means as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH as per ss and as directed by the departmental officer in-charge of work as follows Manual Means
Earthwork in excavation for Pipe Line Trenche by Mechanical/Manual Means as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH as per ss and as directed by the departmental officer in-charge of work as follows Mechanica Means
Manufacture, supply and delivery of the following HDPE Pipes PE 100-Grade PN-6Kg/Sqcm confirming to IS 4984-2016 including transportation to anywhere in ap from factory to work site , stacking ,other incidental charges and Transit Risk etc complete and as directed by the departmental officer in charge of the work
110mm dia.
160mm dia.
200mm dia
250mm dia
315mm dia
Manufacture, supply and delivery of the following HDPE Specials PE 100-Grade confirming to IS 4984-2016 including transportation to anywhere in ap from factory to work site , stacking ,other incidental charges and Transit Risk etc complete and as directed by the departmental officer in charge of the work
a) Pipe ends - long neck
110mm dia.
160mm dia.
160 mm dia for Air TEEs
200mm dia.
200 mm dia for Air TEEs
250mm dia.
250 mm dia for Air TEEs
315mm dia
315 mm dia for Air TEEs
355 mm dia
355 mm dia for Air TEEs
355 mm dia for bulk flow meter
b) MS Flanges
110mm dia.
160mm dia.
160 mm dia for Air TEEs
200mm dia.
200 mm dia for Air TEEs
250mm dia.
250 mm dia for Air TEEs
315mm dia
315 mm dia for Air TEEs
355 mm dia
355 mm dia for Air TEEs
355 mm dia for bulk flow meter
c) End Caps
110mm dia.
160mm dia.
200mm dia.
d) Reducers
110X125 mm dia
125x140 mm dia
140x160 mm dia
160x180 mm dia
180x200 mm dia
200x225 mm dia
225x250 mm dia
250x280 mm dia
280x315 mm dia
e) TEES
110mm dia.
160mm dia.
200mm dia.
250mm dia.
315mm dia
355mm dia
F)Bends
110mm dia.
160mm dia.
200mm dia.
250mm dia.
315mm dia
355mm dia
Laying and jointing of the following HDPE pipes by butt fusion welding as per IS 7634-part-II/1975 as amended from time to time to the alignment and gradient and testing the pipeline to required pressure etc.complete.Thi rate including cost of all labour charges,testing the pipe line,hiring of machinery,fuel charges,wages of drivers and other incidental charges etc.complete as per ss and as directed by the departmental officer incharge of work
110mm dia.
160mm dia.
200mm dia.
250mm dia.
315mm dia
Supply and delivery of Centrifugally cast (spun) Ductile Iron Fittings of DI double socket branch flange Tee, DI All Socket Tees, DI Double socket Tapers (Reducer), DI Flanged Socket, DI Flanged Spigot, DI Double Socket Duck Foot Bend, DI Double Flange Duck/Foot bend, DI All socket Cross, DI All Flange Tee, DI All Flange Cross, DI Double Flange Reducer, Blank Flange, Mechanical Joints, DI Double Socket Bends, DI Double Flanged Bends and DI Manhole Frame & cover conforming to IS:9523/2000 having dimensions Up to 500 x 500 mm dia. The rates mentioned here under are for fittings, zinc coated externally with inside mortar lining (with finishing as per class 13/IS 9523/2000) ( ex-works) including Transportation and as directed by the departmental officer incharge of work.
100X2.00m on 110 dia mains for scours
100X2.00m on 160 dia mains for scours
100x1.00m long DF pipes for sluice valves
150X2.00m on 200 mm dia mains for scours
150X2.00m on 250 mm dia mains for scours
150x1.00m long DF pipes for sluice valves
200x1.00m long DF pipes for sluice valves
250x1.00m long DF pipes for sluice valves
300x1.00m long DF pipes for sluice valves
350x1.00m long DF pipes for sluice valves
350x1.00m long DF pipes for bulk flow meter
deck foot bends, semicircular bends, air valves
Supply and delivery of "Resilient Seated Soft Sealing" Gate Valves (Sluice Valves) PN 1.6(Mpa) with Body and Bonnet of Ductile Iron GGG-40/SG-400/15 or GGG-50/SG-500/7 or Equivalent as per IS1865, IS:3896-2 and Wedge fully Rubber Lined with food grade quality grade W270 grade EPDM, Replaceable Spindle Nut without gland packing with 3-O ring protection system on the Shaft and Seals of NBR. The Valves should be Vacuum tight and 100% leak proof with face to face dimensions as BS:5163 Type A/IS:14846. All the valves should be with fusion bonded Electrostatic Powder coating both inside and outside (Min 250 Microns)- RAL 5005 with Pocket Less Straight through body Passage conforming to Design standards of DIN-3202F4/BS:5163 Type A Flange drilling as per IS - 1538 and transportation and other incidental charges etc,as per ss and as directed by the departmental officer incharge of work as follows
100 mm distrubution
150mm dia for distrubution
200mm dia for distrubution
250mm dia for distrubution
300mm dia for distrubution
350mm dia for distrubution
for scour
100mm dia on 110 mm dia mains
100mm dia on 160 mm dia mains
150 mm dia on 200 mm dia lines
150 mm dia on 250 mm dia lines
Manufacture, supply and delivery of 80mm dia Single Chamber DI Air Valve with Body and cover in Ductile Iron of grade SG 400/12 or equivalent grade as per I.S.3896-part2-1985 and subsequent revisions. All internal parts such as float, shell etc., all cover bolts, of stainless steel, and Gaskets and seals of EPDM food grade quality Epoxy powder coating (EP-P) inside and outside colour blue. Drilled as per IS:1538. PN1.6 complete as per ss and as direceted by the departmental officer incharge of work
Labour charges for lowering and keeping in position of C.I./DI Sluice valves(with cap/with hand wheel), reflux valves and scour valves.This rate including cost of all labour charges,hiring of machinery and other incidental charges and complete as per ss and as directed by the departmental officer incharge of work as follows
100 mm distrubution
150mm dia for distrubution
200mm dia for distrubution
250mm dia for distrubution
300mm dia for distrubution
350mm dia for distrubution
350 mm dia for bulk flow meter
100mm dia on 110 mm dia mains
100mm dia on 160 mm dia mains
150 mm dia on 200 mm dia lines
151 mm dia on 250 mm dia lines
Labour charges for 80mm dia fixing Kinetic Air Valves with isolating Sluice valves, Double Air valves/ Air Cushion valve excluding cost of jointing materials such as bolts, nuts and rubber insertions etc., complete.as per as ss and as directed by the departmental officer incharge of work
Construction Valve Chambers for Sluice Valve Earthwork in excavation for valve chamber as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH Note : Classifications of Earth Work Specification are as per 302.2.1(a) of MORD and 301.2.1 of MORT&H--ordinary soil--manual means upto 3m depth manual means
Filling Sand for foundation of Valve Chamber as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH.This rate including cost of sand ,filling charges,watering,ramming,and other incidental charges etc., complete as per ss and directed by the departmental officer incharge of work
Plain Cement Concrete for Vlave Chamber (1:4:8) (cement: fine aggregate: Coarse aggregate) using coarse aggregate 40mm size hard, machine crushed granite from approved quarry using concrete Mixer 10 / 7 cft (0.2 / 0.8 cum) capacity including cost and conveyance of all materials like cement, sand, coarse aggregate, water etc. to site including all charges for machine mixing and hire charges of concrete mixer, laying concrete finishing top surface to the required level curing etc., and complete for finished item of work as per SS and as directed by the departmental officer incharge of work. (APSS No. 402).for Valve Chamber bed concrete
RCC M-20 Nominal mix for Valve Chamber (cement,fine aggregate,coarse aggregate) corresponding to Table -9 of IS -456 using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and on all materials including all operational ,incidental and labour charges such as machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work,but including centering, shuttering and as directed by the departmental officer incharge of work as follows - For Botom slab
RCC M-20 Nominal mix for Valve Chamber (cement,fine aggregate,coarse aggregate) corresponding to Table -9 of IS -456 using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and on all materials including all operational ,incidental and labour charges such as machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work,but including centering, shuttering and as directed by the departmental officer incharge of work as follows - For Side walls around
RCC M-20 Nominal mix (cement,fine aggregate,coarse aggregate) corresponding to Table -9 of IS -456 using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and on all materials including all operational ,incidental and labour charges such as machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work,but including centering, shuttering and as directed by the departmental officer incharge of work for Pre cast slabs
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying etc., complete for finished item of work in all floors.( APSS No.126) for pre cast slabs of culverts
Lowering the 100mm dia D.I. Pipes K9 of all classes and fittings with flanged ends carefully into the trenches and laying them true to alignment and gradient including all sundries,hiring of machinery ,all labour charges,and other incidental charges etc, complete as per ss and as directed by the departmental officer incharge of work (BIS No.3114/94) - 100mm
Lowering the 150mm dia D.I. Pipes K9 of all classes and fittings with flanged ends carefully into the trenches and laying them true to alignment and gradient including all sundries,hiring of machinery ,all labour charges,and other incidental charges etc, complete as per ss and as directed by the departmental officer incharge of work (BIS No.3114/94) - 150mm
Lowering the 200mm dia D.I. Pipes K9 of all classes and fittings with flanged ends carefully into the trenches and laying them true to alignment and gradient including all sundries,hiring of machinery ,all labour charges,and other incidental charges etc, complete as per ss and as directed by the departmental officer incharge of work (BIS No.3114/94) - 200mm
Lowering the 250mm dia D.I. Pipes K9 of all classes and fittings with flanged ends carefully into the trenches and laying them true to alignment and gradient including all sundries,hiring of machinery ,all labour charges,and other incidental charges etc, complete as per ss and as directed by the departmental officer incharge of work (BIS No.3114/94) - 250mm
Lowering the 200mm dia D.I. Pipes K9 of all classes and fittings with flanged ends carefully into the trenches and laying them true to alignment and gradient including all sundries,hiring of machinery ,all labour charges,and other incidental charges etc, complete as per ss and as directed by the departmental officer incharge of work (BIS No.3114/94) - 300mm
Lowering the 350mm dia D.I. Pipes K9 of all classes and fittings with flanged ends carefully into the trenches and laying them true to alignment and gradient including all sundries,hiring of machinery ,all labour charges,and other incidental charges etc, complete as per ss and as directed by the departmental officer incharge of work (BIS No.3114/94) - 350mm
Jointing the D.I. Pipes, fittings and valves with flanged ends including cost of jointing materials such as bolts, nuts, rubber insertion, white lead including all sundries,hiring of machinery ,all labour charges,and filling with water with a water lead upto 500 m and testing to required pressure and other incidental charges etc, complete as per ss and as directed by the departmental officer incharge of work as follows( BIS No.3114/85)
80 mm dia
100 mm dia
150 mm dia
200 mm dia
250 mm dia
300 mm dia
350 mm dia
Cutting of existing B.T.road surface (aswell as asphalt concrete up to 75mm thick) including water bound macadam including all labour charges for cutting, stacking of materials etc.including cost of all labour charges ,hiring of machinery fuel charges ,wages of driver etc., complete as per the directions of departmental authorities. For pipe line trenches.
Cutting and open of C.C. Road surface including stacking of excavated materials for lying of pipe lines etc.including cost of all labour charges ,hiring of machinery fuel charges ,wages of driver etc., complete as per the directions of departmental authorities. For pipe line trenches.
Cutting and open of Water bound macadam surface including stacking of excavated materials etc.including cost of all labour charges ,hiring of machinery fuel charges ,wages of driver etc., complete as per the directions of departmental authorities. For pipe line trenches.
Filling crushur stone dust in pipe line trenches for cutting portion as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH.This rate including cost of stone dust ,filling charges,watering,ramming,and other incidental charges etc., complete as per ss and directed by the departmental officer incharge of work
Restoration of CC road with Construction of un-reinforced, plain cement concrete pavement, thickness as per design, over a prepared sub base, with 43 grade cement or any other type as per Clause 1501.2.2 M30 (Grade), coarse and fine aggregates conforming to IS : 383, maximum in a concrete mixer of not less than 0.2 cum capacity and spreading the concrete with sholvels, rakes, compacted using needle, scareed and plate vibrators and finished in continuous operation, curing of concrete slabs for 14- days, curing compound (where specified) and water finishing to lines and grade as per drawing and Technical Specification Clause 1501 MORD and complete as per SS and as directed by the departmental officer incharges of work
Laying new Distribution lines zone-IIA
Earthwork in excavation for Pipe Line Trenche by Mechanical/Manual Means as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH as per ss and as directed by the departmental officer in-charge of work as follows Manual Means
Earthwork in excavation for Pipe Line Trenche by Mechanical/Manual Means as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH as per ss and as directed by the departmental officer in-charge of work as follows Mechanica Means
Manufacture, supply and delivery of the following HDPE Pipes PE 100-Grade PN-6Kg/Sqcm confirming to IS 4984-2016 including transportation to anywhere in ap from factory to work site , stacking ,other incidental charges and Transit Risk etc complete and as directed by the departmental officer in charge of the work
110mm dia.
160mm dia.
200mm dia
250mm dia
315mm dia
Manufacture, supply and delivery of the following HDPE Specials PE 100-Grade confirming to IS 4984-2016 including transportation to anywhere in ap from factory to work site , stacking ,other incidental charges and Transit Risk etc complete and as directed by the departmental officer in charge of the work
a) Pipe ends - long neck
110mm dia.
160mm dia.
160 mm dia for Air TEEs
200mm dia.
200 mm dia for Air TEEs
250mm dia.
250 mm dia for Air TEEs
315mm dia
315 mm dia for Air TEEs
355 mm dia
355 mm dia for Air TEEs
355 mm dia for bulk flow meter
b) MS Flanges
110mm dia.
160mm dia.
160 mm dia for Air TEEs
200mm dia.
200 mm dia for Air TEEs
250mm dia.
250 mm dia for Air TEEs
315mm dia
315 mm dia for Air TEEs
355 mm dia
355 mm dia for Air TEEs
355 mm dia for bulk flow meter
c) End Caps
110mm dia.
160mm dia.
200mm dia.
d) Reducers
110X125 mm dia
125x140 mm dia
140x160 mm dia
160x180 mm dia
180x200 mm dia
200x225 mm dia
225x250 mm dia
250x280 mm dia
280x315 mm dia
e) TEES
110mm dia.
160mm dia.
200mm dia.
250mm dia.
315mm dia
355mm dia
F)Bends
110mm dia.
160mm dia.
200mm dia.
250mm dia.
315mm dia
355mm dia
Laying and jointing of the following HDPE pipes by butt fusion welding as per IS 7634-part-II/1975 as amended from time to time to the alignment and gradient and testing the pipeline to required pressure etc.complete.Thi rate including cost of all labour charges,testing the pipe line,hiring of machinery,fuel charges,wages of drivers and other incidental charges etc.complete as per ss and as directed by the departmental officer incharge of work
110mm dia.
160mm dia.
200mm dia.
250mm dia.
315mm dia
Supply and delivery of Centrifugally cast (spun) Ductile Iron Fittings of DI double socket branch flange Tee, DI All Socket Tees, DI Double socket Tapers (Reducer), DI Flanged Socket, DI Flanged Spigot, DI Double Socket Duck Foot Bend, DI Double Flange Duck/Foot bend, DI All socket Cross, DI All Flange Tee, DI All Flange Cross, DI Double Flange Reducer, Blank Flange, Mechanical Joints, DI Double Socket Bends, DI Double Flanged Bends and DI Manhole Frame & cover conforming to IS:9523/2000 having dimensions Up to 500 x 500 mm dia. The rates mentioned here under are for fittings, zinc coated externally with inside mortar lining (with finishing as per class 13/IS 9523/2000) ( ex-works) including Transportation and as directed by the departmental officer incharge of work.
100X2.00m on 110 dia mains for scours
100X2.00m on 160 dia mains for scours
100x1.00m long DF pipes for sluice valves
150X2.00m on 200 mm dia mains for scours
150X2.00m on 250 mm dia mains for scours
150x1.00m long DF pipes for sluice valves
200x1.00m long DF pipes for sluice valves
250x1.00m long DF pipes for sluice valves
300x1.00m long DF pipes for sluice valves
350x1.00m long DF pipes for sluice valves
350x1.00m long DF pipes for bulk flow meter
deck foot bends, semicircular bends, air valves
Supply and delivery of "Resilient Seated Soft Sealing" Gate Valves (Sluice Valves) PN 1.6(Mpa) with Body and Bonnet of Ductile Iron GGG-40/SG-400/15 or GGG-50/SG-500/7 or Equivalent as per IS1865, IS:3896-2 and Wedge fully Rubber Lined with food grade quality grade W270 grade EPDM, Replaceable Spindle Nut without gland packing with 3-O ring protection system on the Shaft and Seals of NBR. The Valves should be Vacuum tight and 100% leak proof with face to face dimensions as BS:5163 Type A/IS:14846. All the valves should be with fusion bonded Electrostatic Powder coating both inside and outside (Min 250 Microns)- RAL 5005 with Pocket Less Straight through body Passage conforming to Design standards of DIN-3202F4/BS:5163 Type A Flange drilling as per IS - 1538 and transportation and other incidental charges etc,as per ss and as directed by the departmental officer incharge of work as follows
100 mm distrubution
150mm dia for distrubution
200mm dia for distrubution
250mm dia for distrubution
300mm dia for distrubution
350mm dia for distrubution
for scour
100mm dia on 110 mm dia mains
100mm dia on 160 mm dia mains
150 mm dia on 200 mm dia lines
150 mm dia on 250 mm dia lines
Manufacture, supply and delivery of Single Chamber DI Air Valve with Body and cover in Ductile Iron of grade SG 400/12 or equivalent grade as per I.S.3896-part2-1985 and subsequent revisions. All internal parts such as float, shell etc., all cover bolts, of stainless steel, and Gaskets and seals of EPDM food grade quality Epoxy powder coating (EP-P) inside and outside colour blue. Drilled as per IS:1538. PN1.6 complete as per ss and as direceted by the departmental officer incharge of work
Labour charges for lowering and keeping in position of C.I./DI Sluice valves(with cap/with hand wheel), reflux valves and scour valves.This rate including cost of all labour charges,hiring of machinery and other incidental charges and complete as per ss and as directed by the departmental officer incharge of work as follows
100 mm distrubution
150mm dia for distrubution
200mm dia for distrubution
250mm dia for distrubution
300mm dia for distrubution
350mm dia for distrubution
350 mm dia for bulk flow meter
100mm dia on 110 mm dia mains
100mm dia on 160 mm dia mains
150 mm dia on 200 mm dia lines
Labour charges for fixing Kinetic Air Valves of 80mm dia on varions pipelines with isolating Sluice valves, Double Air valves/ Air Cushion valve excluding cost of jointing materials such as bolts, nuts and rubber insertions etc., complete.as per as ss and as directed by the departmental officer incharge of work
Construction Valve Chambers for Sluice Valve Earthwork in excavation for valve chamber as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH Note : Classifications of Earth Work Specification are as per 302.2.1(a) of MORD and 301.2.1 of MORT&H--ordinary soil--manual means upto 3m depth manual means
Filling Sand for foundation of Valve Chamber as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH.This rate including cost of sand ,filling charges,watering,ramming,and other incidental charges etc., complete as per ss and directed by the departmental officer incharge of work
Plain Cement Concrete for Vlave Chamber (1:4:8) (cement: fine aggregate: Coarse aggregate) using coarse aggregate 40mm size hard, machine crushed granite from approved quarry using concrete Mixer 10 / 7 cft (0.2 / 0.8 cum) capacity including cost and conveyance of all materials like cement, sand, coarse aggregate, water etc. to site including all charges for machine mixing and hire charges of concrete mixer, laying concrete finishing top surface to the required level curing etc., and complete for finished item of work as per SS and as directed by the departmental officer incharge of work. (APSS No. 402).for Valve Chamber bed concrete
RCC M-20 Nominal mix for Valve Chamber (cement,fine aggregate,coarse aggregate) corresponding to Table -9 of IS -456 using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and on all materials including all operational ,incidental and labour charges such as machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work,but including centering, shuttering and as directed by the departmental officer incharge of work as follows - For Botom slab
RCC M-20 Nominal mix for Valve Chamber (cement,fine aggregate,coarse aggregate) corresponding to Table -9 of IS -456 using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and on all materials including all operational ,incidental and labour charges such as machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work,but including centering, shuttering and as directed by the departmental officer incharge of work as follows - For Side walls around
RCC M-20 Nominal mix (cement,fine aggregate,coarse aggregate) corresponding to Table -9 of IS -456 using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and on all materials including all operational ,incidental and labour charges such as machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work,but including centering, shuttering and as directed by the departmental officer incharge of work for Pre cast slabs
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying etc., complete for finished item of work in all floors.( APSS No.126) for pre cast slabs of culverts
Lowering the 100mm dia D.I. Pipes K9 of all classes and fittings with flanged ends carefully into the trenches and laying them true to alignment and gradient including all sundries,hiring of machinery ,all labour charges,and other incidental charges etc, complete as per ss and as directed by the departmental officer incharge of work (BIS No.3114/94) - 100mm
Lowering the 150mm dia D.I. Pipes K9 of all classes and fittings with flanged ends carefully into the trenches and laying them true to alignment and gradient including all sundries,hiring of machinery ,all labour charges,and other incidental charges etc, complete as per ss and as directed by the departmental officer incharge of work (BIS No.3114/94) - 150mm
Lowering the 200mm dia D.I. Pipes K9 of all classes and fittings with flanged ends carefully into the trenches and laying them true to alignment and gradient including all sundries,hiring of machinery ,all labour charges,and other incidental charges etc, complete as per ss and as directed by the departmental officer incharge of work (BIS No.3114/94) - 200mm
Lowering the 250mm dia D.I. Pipes K9 of all classes and fittings with flanged ends carefully into the trenches and laying them true to alignment and gradient including all sundries,hiring of machinery ,all labour charges,and other incidental charges etc, complete as per ss and as directed by the departmental officer incharge of work (BIS No.3114/94) - 250mm
Lowering the 300mm dia D.I. Pipes K9 of all classes and fittings with flanged ends carefully into the trenches and laying them true to alignment and gradient including all sundries,hiring of machinery ,all labour charges,and other incidental charges etc, complete as per ss and as directed by the departmental officer incharge of work (BIS No.3114/94) - 300mm
Lowering the 350mm dia D.I. Pipes K9 of all classes and fittings with flanged ends carefully into the trenches and laying them true to alignment and gradient including all sundries,hiring of machinery ,all labour charges,and other incidental charges etc, complete as per ss and as directed by the departmental officer incharge of work (BIS No.3114/94) - 350mm
Jointing the D.I. Pipes, fittings and valves with flanged ends including cost of jointing materials such as bolts, nuts, rubber insertion, white lead including all sundries,hiring of machinery ,all labour charges,and filling with water with a water lead upto 500 m and testing to required pressure and other incidental charges etc, complete as per ss and as directed by the departmental officer incharge of work as follows( BIS No.3114/85)
80 mm dia
100 mm dia
150 mm dia
200 mm dia
250 mm dia
300 mm dia
350 mm dia
Cutting of existing B.T.road surface (aswell as asphalt concrete up to 75mm thick) including water bound macadam including all labour charges for cutting, stacking of materials etc.including cost of all labour charges ,hiring of machinery fuel charges ,wages of driver etc., complete as per the directions of departmental authorities. For pipe line trenches.
Cutting and open of C.C. Road surface including stacking of excavated materials for lying of pipe lines etc.including cost of all labour charges ,hiring of machinery fuel charges ,wages of driver etc., complete as per the directions of departmental authorities. For pipe line trenches.
Cutting and open of Water bound macadam surface including stacking of excavated materials etc.including cost of all labour charges ,hiring of machinery fuel charges ,wages of driver etc., complete as per the directions of departmental authorities. For pipe line trenches.
Filling crushur stone dust in pipe line trenches for cutting portion as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH.This rate including cost of stone dust ,filling charges,watering,ramming,and other incidental charges etc., complete as per ss and directed by the departmental officer incharge of work
Restoration of CC road with Construction of un-reinforced, plain cement concrete pavement, thickness as per design, over a prepared sub base, with 43 grade cement or any other type as per Clause 1501.2.2 M30 (Grade), coarse and fine aggregates conforming to IS : 383, maximum in a concrete mixer of not less than 0.2 cum capacity and spreading the concrete with sholvels, rakes, compacted using needle, scareed and plate vibrators and finished in continuous operation, curing of concrete slabs for 14- days, curing compound (where specified) and water finishing to lines and grade as per drawing and Technical Specification Clause 1501 MORD and complete as per SS and as directed by the departmental officer incharges of work
Laying new Distribution lines zone-III
Earthwork in excavation for Pipe Line Trenche by Mechanical/Manual Means as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH as per ss and as directed by the departmental officer in-charge of work as follows Manual Means
Earthwork in excavation for Pipe Line Trenche by Mechanical/Manual Means as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH as per ss and as directed by the departmental officer in-charge of work as follows Mechanica Means
Manufacture, supply and delivery of the following HDPE Pipes PE 100-Grade PN-6Kg/Sqcm confirming to IS 4984-2016 including transportation to anywhere in ap from factory to work site , stacking ,other incidental charges and Transit Risk etc complete and as directed by the departmental officer in charge of the work
110mm dia.
160mm dia.
200mm dia
Manufacture, supply and delivery of the following HDPE Specials PE 100-Grade confirming to IS 4984-2016 including transportation to anywhere in ap from factory to work site , stacking ,other incidental charges and Transit Risk etc complete and as directed by the departmental officer in charge of the work
a) Pipe ends - long neck
110mm dia.
160mm dia.
160 mm dia for Air TEEs
355 mm dia
355 mm dia for Air TEEs
355 mm dia for bulk flow meter
b) MS Flanges
110mm dia.
160mm dia.
160 mm dia for Air TEEs
355 mm dia
355 mm dia for Air TEEs
355 mm dia for bulk flow meter
c) End Caps
110mm dia.
160mm dia.
d) Reducers
110X125 mm dia
125x140 mm dia
140x160 mm dia
e) TEES
110mm dia.
160mm dia.
200mm dia.
355mm dia
F)Bends
110mm dia.
160mm dia.
200mm dia.
355mm dia
Laying and jointing of the following HDPE pipes by butt fusion welding as per IS 7634-part-II/1975 as amended from time to time to the alignment and gradient and testing the pipeline to required pressure etc.complete.Thi rate including cost of all labour charges,testing the pipe line,hiring of machinery,fuel charges,wages of drivers and other incidental charges etc.complete as per ss and as directed by the departmental officer incharge of work
110mm dia.
160mm dia.
200mm dia.
Supply and delivery of Centrifugally cast (spun) Ductile Iron Fittings of DI double socket branch flange Tee, DI All Socket Tees, DI Double socket Tapers (Reducer), DI Flanged Socket, DI Flanged Spigot, DI Double Socket Duck Foot Bend, DI Double Flange Duck/Foot bend, DI All socket Cross, DI All Flange Tee, DI All Flange Cross, DI Double Flange Reducer, Blank Flange, Mechanical Joints, DI Double Socket Bends, DI Double Flanged Bends and DI Manhole Frame & cover conforming to IS:9523/2000 having dimensions Up to 500 x 500 mm dia. The rates mentioned here under are for fittings, zinc coated externally with inside mortar lining (with finishing as per class 13/IS 9523/2000) ( ex-works) including Transportation and as directed by the departmental officer incharge of work as follows.
100X2.00m on 110 dia mains for scours
100X2.00m on 160 dia mains for scours
100x1.00m long DF pipes for sluice valves
150x1.00m long DF pipes for sluice valves
350x1.00m long DF pipes for sluice valves
350x1.00m long DF pipes for bulk flow meter
deck foot bends, semicircular bends, air valves
Supply and delivery of "Resilient Seated Soft Sealing" Gate Valves (Sluice Valves) PN 1.6(Mpa) with Body and Bonnet of Ductile Iron GGG-40/SG-400/15 or GGG-50/SG-500/7 or Equivalent as per IS1865, IS:3896-2 and Wedge fully Rubber Lined with food grade quality grade W270 grade EPDM, Replaceable Spindle Nut without gland packing with 3-O ring protection system on the Shaft and Seals of NBR. The Valves should be Vacuum tight and 100% leak proof with face to face dimensions as BS:5163 Type A/IS:14846. All the valves should be with fusion bonded Electrostatic Powder coating both inside and outside (Min 250 Microns)- RAL 5005 with Pocket Less Straight through body Passage conforming to Design standards of DIN-3202F4/BS:5163 Type A Flange drilling as per IS - 1538 and transportation and other incidental charges etc,as per ss and as directed by the departmental officer incharge of work as follows
100 mm distrubution
150mm dia for distrubution
350mm dia for distrubution
for scour
100mm dia on 110 mm dia mains
100mm dia on 160 mm dia mains
Manufacture, supply and delivery of 80mm dia Single Chamber DI Air Valve with Body and cover in Ductile Iron of grade SG 400/12 or equivalent grade as per I.S.3896-part2-1985 and subsequent revisions. All internal parts such as float, shell etc., all cover bolts, of stainless steel, and Gaskets and seals of EPDM food grade quality Epoxy powder coating (EP-P) inside and outside colour blue. Drilled as per IS:1538. PN1.6 complete as per ss and as direceted by the departmental officer incharge of work
Labour charges for lowering and keeping in position of C.I./DI Sluice valves(with cap/with hand wheel), reflux valves and scour valves.This rate including cost of all labour charges,hiring of machinery and other incidental charges and complete as per ss and as directed by the departmental officer incharge of work as follows
100 mm distrubution
150mm dia for distrubution
350mm dia for distrubution
350 mm dia for bulk flow meter
100mm dia on 110 mm dia mains
100mm dia on 160 mm dia mains
Labour charges for fixing Kinetic Air Valves 80mm dia with isolating Sluice valves, Double Air valves/ Air Cushion valve excluding cost of jointing materials such as bolts, nuts and rubber insertions etc., complete.as per as ss and as directed by the departmental officer incharge of work
Construction Valve Chambers for Sluice Valve Earthwork in excavation for valve chamber as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH Note : Classifications of Earth Work Specification are as per 302.2.1(a) of MORD and 301.2.1 of MORT&H--ordinary soil--manual means upto 3m depth manual means
Filling Sand for foundation of Valve Chamber as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH.This rate including cost of sand ,filling charges,watering,ramming,and other incidental charges etc., complete as per ss and directed by the departmental officer incharge of work
Plain Cement Concrete for Vlave Chamber (1:4:8) (cement: fine aggregate: Coarse aggregate) using coarse aggregate 40mm size hard, machine crushed granite from approved quarry using concrete Mixer 10 / 7 cft (0.2 / 0.8 cum) capacity including cost and conveyance of all materials like cement, sand, coarse aggregate, water etc. to site including all charges for machine mixing and hire charges of concrete mixer, laying concrete finishing top surface to the required level curing etc., and complete for finished item of work as per SS and as directed by the departmental officer incharge of work. (APSS No. 402).for Valve Chamber bed concrete
RCC M-20 Nominal mix for Valve Chamber (cement,fine aggregate,coarse aggregate) corresponding to Table -9 of IS -456 using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and on all materials including all operational ,incidental and labour charges such as machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work,but including centering, shuttering and as directed by the departmental officer incharge of work as follows - For Botom slab
RCC M-20 Nominal mix for Valve Chamber (cement,fine aggregate,coarse aggregate) corresponding to Table -9 of IS -456 using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and on all materials including all operational ,incidental and labour charges such as machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work,but including centering, shuttering and as directed by the departmental officer incharge of work as follows - For Side walls around
RCC M-20 Nominal mix (cement,fine aggregate,coarse aggregate) corresponding to Table -9 of IS -456 using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and on all materials including all operational ,incidental and labour charges such as machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work,but including centering, shuttering and as directed by the departmental officer incharge of work for Pre cast slabs
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying etc., complete for finished item of work in all floors.( APSS No.126) for pre cast slabs of culverts for valve chamber
Lowering the 100mm dia D.I. Pipes K9 of all classes and fittings with flanged ends carefully into the trenches and laying them true to alignment and gradient including all sundries,hiring of machinery ,all labour charges,and other incidental charges etc, complete as per ss and as directed by the departmental officer incharge of work (BIS No.3114/94) - 100mm
Lowering the 150mm dia D.I. Pipes K9 of all classes and fittings with flanged ends carefully into the trenches and laying them true to alignment and gradient including all sundries,hiring of machinery ,all labour charges,and other incidental charges etc, complete as per ss and as directed by the departmental officer incharge of work (BIS No.3114/94) - 150mm
Lowering the 350mm dia D.I. Pipes K9 of all classes and fittings with flanged ends carefully into the trenches and laying them true to alignment and gradient including all sundries,hiring of machinery ,all labour charges,and other incidental charges etc, complete as per ss and as directed by the departmental officer incharge of work (BIS No.3114/94) - 350mm
Jointing the D.I. Pipes, fittings and valves with flanged ends including cost of jointing materials such as bolts, nuts, rubber insertion, white lead including all sundries,hiring of machinery ,all labour charges,and filling with water with a water lead upto 500 m and testing to required pressure and other incidental charges etc, complete as per ss and as directed by the departmental officer incharge of work as follows( BIS No.3114/85)
80 mm dia
100 mm dia
150 mm dia
300 mm dia
350 mm dia
Cutting of existing B.T.road surface (aswell as asphalt concrete up to 75mm thick) including water bound macadam including all labour charges for cutting, stacking of materials etc.including cost of all labour charges ,hiring of machinery fuel charges ,wages of driver etc., complete as per the directions of departmental authorities. For pipe line trenches.
Cutting and open of C.C. Road surface including stacking of excavated materials for lying of pipe lines etc.including cost of all labour charges ,hiring of machinery fuel charges ,wages of driver etc., complete as per the directions of departmental authorities. For pipe line trenches.
Cutting and open of Water bound macadam surface including stacking of excavated materials etc.including cost of all labour charges ,hiring of machinery fuel charges ,wages of driver etc., complete as per the directions of departmental authorities. For pipe line trenches.
Filling crushur stone dust in pipe line trenches for cutting portion as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH.This rate including cost of stone dust ,filling charges,watering,ramming,and other incidental charges etc., complete as per ss and directed by the departmental officer incharge of work
Restoration of CC road with Construction of un-reinforced, plain cement concrete pavement, thickness as per design, over a prepared sub base, with 43 grade cement or any other type as per Clause 1501.2.2 M30 (Grade), coarse and fine aggregates conforming to IS : 383, maximum in a concrete mixer of not less than 0.2 cum capacity and spreading the concrete with sholvels, rakes, compacted using needle, scareed and plate vibrators and finished in continuous operation, curing of concrete slabs for 14- days, curing compound (where specified) and water finishing to lines and grade as per drawing and Technical Specification Clause 1501 MORD and complete as per SS and as directed by the departmental officer incharges of work
Providing house service connections on HDPE mains at House hold side in Earthen Roads with Earthwork Excavation in all type of soils fixing PP Saddle,PP Clamp Saddle shall be manufactured by injection moulding using virigin Polypropylene,Mechanical tapping saddles for water works purposes and designed for use with PVC/PE pipe as per IS 4985/IS 4984 respectively. These saddles should be contoured to fit around the pipe. PP saddles shall be Blue/Black moulded-in with Nickel plated Brass / SS 304 metal female threaded outlets. Seal shall be thermoplastic elastomer rubber suitable for drinking water and nut-bolt-washer with SS. The PP Clamp saddle fittings shall be mouldedwith SS 304/Nickel plated Brass female threaded outlet inserted to connect necessary fittings. Thread dimension shall conform to IS-554/ISO-7. Adequate thickness of PP shall be provided to hold brass insert in place and avoid leakage while pressure applications. Fasteners shall be threaded type, with SS. Fasteners of size 125mm and above. The grade of raw material used must be certified by WRAS, UK for type test as per BS 6920 from their certified laboratories like NSF International Ltd. UK and certificate of Compliance to be produced for the following parameters: i) Odour&Flavour of water ii) Appearance of water iii) Growth of Micro Organismaxes etc,FOR main pipes Hdpe /PVC of 110mm dia .flow control valve SS 316 NRV 10 LPM ,Compression adaptor with one side compression end to suit 1/2 "to1''(15mmOD to25 mm OD) MDPE pipe and other side with female threaded with SS-304 material inserts of sizes 1/2" BSP threads,body,nut, and cap of poly propylene,clip ring PP Compression Metal insert female Threaded Adaptorcompression adaptor with one side compression end to suit 1/2'' to 1'' mdpe pipe and other side with female thread with ss-304 material inserts of sizes 1/2'' BSP thread,PP compression elbow to suit 1/2 " to 1'' (15mm OD to 25 mm OD) MDPE pipe body, nuts, and caps of polypropelene, clip ring of POM(Acetylic resin) and and "O" ring of NBR material,as per ISO 14236 standardsDouble compression elbow to suit 20mm OD for 100mm, MDPE PE80 Blue pipe as per ISO 4427 up to date 1. for conveyance of potable water ,MDPE 20mm OD pipe (2.00 m avg length for each of 1/2'' HSC) of SDR 9-PN-16 for pipes side,Premium make UPVC Pipes with Fittings.(IS 4985/2000)(PH SSR :20) UPVC pipe for 40 mm (Casing for drain crossing)fixing of 12.7 mm brass bib cock indian make heavy duty long bodyFixing of House service connections,including fixing of ferrule, MDPE/GI pipes and specials and connecting newly laid pipe (For HDPE / PVC Pipes)Making Holes upto 18 mm Dia in RCC/any Stones up to 50 mm Thick( BMS-W78)Fixing of 25.4 mm Holder Back Clamps at Drain Crossing this rate cost of above all materials ,Including all Labour Charges ,other incidental charges etc for finished item of work and as directed by the departmental officer in charge of work
Providing house service connections on HDPE mains at other side in Earthen Roads with Earthwork Excavation in all type of soils fixing PP Saddle,PP Clamp Saddle shall be manufactured by injection moulding using virigin Polypropylene,Mechanical tapping saddles for water works purposes and designed for use with PVC/PE pipe as per IS 4985/IS 4984 respectively. These saddles should be contoured to fit around the pipe. PP saddles shall be Blue/Black moulded-in with Nickel plated Brass / SS 304 metal female threaded outlets. Seal shall be thermoplastic elastomer rubber suitable for drinking water and nut-bolt-washer with SS. The PP Clamp saddle fittings shall be mouldedwith SS 304/Nickel plated Brass female threaded outlet inserted to connect necessary fittings. Thread dimension shall conform to IS-554/ISO-7. Adequate thickness of PP shall be provided to hold brass insert in place and avoid leakage while pressure applications. Fasteners shall be threaded type, with SS. Fasteners of size 125mm and above. The grade of raw material used must be certified by WRAS, UK for type test as per BS 6920 from their certified laboratories like NSF International Ltd. UK and certificate of Compliance to be produced for the following parameters: i) Odour&Flavour of water ii) Appearance of water iii) Growth of Micro Organismaxes etc,FOR main pipes Hdpe /PVC of 110mm dia .flow control valve SS 316 NRV 10 LPM ,Compression adaptor with one side compression end to suit 1/2 "to1''(15mmOD to25 mm OD) MDPE pipe and other side with female threaded with SS-304 material inserts of sizes 1/2" BSP threads,body,nut, and cap of poly propylene,clip ring PP Compression Metal insert female Threaded Adaptorcompression adaptor with one side compression end to suit 1/2'' to 1'' mdpe pipe and other side with female thread with ss-304 material inserts of sizes 1/2'' BSP thread,PP compression elbow to suit 1/2 " to 1'' (15mm OD to 25 mm OD) MDPE pipe body, nuts, and caps of polypropelene, clip ring of POM(Acetylic resin) and and "O" ring of NBR material,as per ISO 14236 standardsDouble compression elbow to suit 20mm OD for 100mm, MDPE PE80 Blue pipe as per ISO 4427 up to date 1. for conveyance of potable water ,MDPE 20mm OD pipe (2.00 m avg length for each of 1/2'' HSC) of SDR 9-PN-16 for pipes side,Premium make UPVC Pipes with Fittings.(IS 4985/2000)(PH SSR :20) UPVC pipe for 40 mm (Casing for drain crossing)fixing of 12.7 mm brass bib cock indian make heavy duty long bodyFixing of House service connections,including fixing of ferrule, MDPE/GI pipes and specials and connecting newly laid pipe (For HDPE / PVC Pipes)Making Holes upto 18 mm Dia in RCC/any Stones up to 50 mm Thick( BMS-W78)Fixing of 25.4 mm Holder Back Clamps at Drain Crossing this rate cost of above all materials ,Including all Labour Charges ,other incidental charges etc for finished item of work and as directed by the departmental officer in charge of work
Providing house service connections on HDPE mains at House hold side in B.T & CC Roads with Earthwork Excavation in all type of soils fixing PP Saddle,PP Clamp Saddle shall be manufactured by injection moulding using virigin Polypropylene,Mechanical tapping saddles for water works purposes and designed for use with PVC/PE pipe as per IS 4985/IS 4984 respectively. These saddles should be contoured to fit around the pipe. PP saddles shall be Blue/Black moulded-in with Nickel plated Brass / SS 304 metal female threaded outlets. Seal shall be thermoplastic elastomer rubber suitable for drinking water and nut-bolt-washer with SS. The PP Clamp saddle fittings shall be mouldedwith SS 304/Nickel plated Brass female threaded outlet inserted to connect necessary fittings. Thread dimension shall conform to IS-554/ISO-7. Adequate thickness of PP shall be provided to hold brass insert in place and avoid leakage while pressure applications. Fasteners shall be threaded type, with SS. Fasteners of size 125mm and above. The grade of raw material used must be certified by WRAS, UK for type test as per BS 6920 from their certified laboratories like NSF International Ltd. UK and certificate of Compliance to be produced for the following parameters: i) Odour&Flavour of water ii) Appearance of water iii) Growth of Micro Organismaxes etc,FOR main pipes Hdpe /PVC of 110mm dia .flow control valve SS 316 NRV 10 LPM ,Compression adaptor with one side compression end to suit 1/2 "to1''(15mmOD to25 mm OD) MDPE pipe and other side with female threaded with SS-304 material inserts of sizes 1/2" BSP threads,body,nut, and cap of poly propylene,clip ring PP Compression Metal insert female Threaded Adaptorcompression adaptor with one side compression end to suit 1/2'' to 1'' mdpe pipe and other side with female thread with ss-304 material inserts of sizes 1/2'' BSP thread,PP compression elbow to suit 1/2 " to 1'' (15mm OD to 25 mm OD) MDPE pipe body, nuts, and caps of polypropelene, clip ring of POM(Acetylic resin) and and "O" ring of NBR material,as per ISO 14236 standardsDouble compression elbow to suit 20mm OD for 100mm, MDPE PE80 Blue pipe as per ISO 4427 up to date 1. for conveyance of potable water ,MDPE 20mm OD pipe (2.00 m avg length for each of 1/2'' HSC) of SDR 9-PN-16 for pipes side,Premium make UPVC Pipes with Fittings.(IS 4985/2000)(PH SSR :20) UPVC pipe for 40 mm (Casing for drain crossing)fixing of 12.7 mm brass bib cock indian make heavy duty long bodyFixing of House service connections,including fixing of ferrule, MDPE/GI pipes and specials and connecting newly laid pipe (For HDPE / PVC Pipes)Making Holes upto 18 mm Dia in RCC/any Stones up to 50 mm Thick( BMS-W78)Fixing of 25.4 mm Holder Back Clamps at Drain Crossing this rate cost of above all materials ,Including all Labour Charges ,other incidental charges etc for finished item of work and as directed by the departmental officer in charge of work
Providing house service connections on HDPE mains at other side in B.T & CC Roads with Earthwork Excavation in all type of soils fixing PP Saddle,PP Clamp Saddle shall be manufactured by injection moulding using virigin Polypropylene,Mechanical tapping saddles for water works purposes and designed for use with PVC/PE pipe as per IS 4985/IS 4984 respectively. These saddles should be contoured to fit around the pipe. PP saddles shall be Blue/Black moulded-in with Nickel plated Brass / SS 304 metal female threaded outlets. Seal shall be thermoplastic elastomer rubber suitable for drinking water and nut-bolt-washer with SS. The PP Clamp saddle fittings shall be mouldedwith SS 304/Nickel plated Brass female threaded outlet inserted to connect necessary fittings. Thread dimension shall conform to IS-554/ISO-7. Adequate thickness of PP shall be provided to hold brass insert in place and avoid leakage while pressure applications. Fasteners shall be threaded type, with SS. Fasteners of size 125mm and above. The grade of raw material used must be certified by WRAS, UK for type test as per BS 6920 from their certified laboratories like NSF International Ltd. UK and certificate of Compliance to be produced for the following parameters: i) Odour&Flavour of water ii) Appearance of water iii) Growth of Micro Organismaxes etc,FOR main pipes Hdpe /PVC of 110mm dia .flow control valve SS 316 NRV 10 LPM ,Compression adaptor with one side compression end to suit 1/2 "to1''(15mmOD to25 mm OD) MDPE pipe and other side with female threaded with SS-304 material inserts of sizes 1/2" BSP threads,body,nut, and cap of poly propylene,clip ring PP Compression Metal insert female Threaded Adaptorcompression adaptor with one side compression end to suit 1/2'' to 1'' mdpe pipe and other side with female thread with ss-304 material inserts of sizes 1/2'' BSP thread,PP compression elbow to suit 1/2 " to 1'' (15mm OD to 25 mm OD) MDPE pipe body, nuts, and caps of polypropelene, clip ring of POM(Acetylic resin) and and "O" ring of NBR material,as per ISO 14236 standardsDouble compression elbow to suit 20mm OD for 100mm, MDPE PE80 Blue pipe as per ISO 4427 up to date 1. for conveyance of potable water ,MDPE 20mm OD pipe (2.00 m avg length for each of 1/2'' HSC) of SDR 9-PN-16 for pipes side,Premium make UPVC Pipes with Fittings.(IS 4985/2000)(PH SSR :20) UPVC pipe for 40 mm (Casing for drain crossing)fixing of 12.7 mm brass bib cock indian make heavy duty long bodyFixing of House service connections,including fixing of ferrule, MDPE/GI pipes and specials and connecting newly laid pipe (For HDPE / PVC Pipes)Making Holes upto 18 mm Dia in RCC/any Stones up to 50 mm Thick( BMS-W78)Fixing of 25.4 mm Holder Back Clamps at Drain Crossing this rate cost of above all materials ,Including all Labour Charges ,other incidental charges etc for finished item of work and as directed by the departmental officer in charge of work
Providing Instrumentation and Automation of the Pumping System, Supervisory Control and Data Acuasation System (SCADA) & Providing 24x7 water supply system at 200 KL ELSR at Bus stand area
Providing, Installation, Testing and Commissioning of PRESSURE TRANSMITTER for suction, Delivery and common Header with specifications of Water Application: Range: 0-16 Bar / Power Supply: 24 V DC / Output: 4-20 mA / Diaphragm: SS316L / Process Connection: 1/2 "NPT (M) / Accuracy: 0.15% Protection: IP67 . The cost also includes the calibration of all the sensors manifold etc., complete including cost and conveyance of all material and labor charges other incidental charges etc complete and as per SS and as directed by the department officer for raw water pumping station and clear waater pumping station
Supply, errection, testing and commissioning of Ultra sonic/ Altitude Level sensors make of SIEMENS/ ABB/ BAUMER/ DANFOSS with specifications of body construction with standard construction, measuring upto 6.00 Mtr depth, protection clause of IP 65, accuracy is +/- 5%, input power supply is 24 V.. DC, remote communication protocol of 4 to 20 ma, temperature safety is in-built to comprehensive over temperature range with in the -40 Deg to +80 Deg, installed in both conditions i.e., indoor and outdoor, charges including cost and conveyance of all material including transport and labor etc., complete and as directed by the dept., officer. for raw water pumping station and clear waater pumping station
Supply and delivery of 25 MM Dia electrical actuated valves for Vaccume operation for each pump with specification of Thread end, 24 V.. DC and required limit switches and manual override facility complete charges including cost and convayance of all the material, labor etc., complete and cost of materials all labour charges, other incidental charges etc complete as per SS and as directed by the departmental officer incharge of work for clear water pumping main.
Supply and delivery of DI D/F hydraulic and self-medium operated double chamber diaphragm control valve for the functions of pump control i.e. to ensure smooth startup and shutdown of pumps. Valve shall be activated by line pressure and 24V DC solenoid for its operation. Non-return function in built to prevent surges due to pump trip events. Valve closure started as soon as solenoids are deenergized and limit switch of valve position indicator triggered. The valve can be manually overridden to check function. The main valve body internals shall consist of three basic parts i.e. body, diaphragm assembly and top cover with a spring inside main body. The nylon reinforced natural rubber diaphragm of the valve shall close on a seating arrangement. The control tubing shall include inline filter unit. The coating shall be of epoxy BLUE. Charges including cost and conveyance of all material and labor excluding cost of taxes and duties per SS and as directed by the department officer as follow
a)DN 250 - PN 16 pump control valve for Raw Water Pumping Station as per the above specification
b)DN 200 - PN 16 pump control valve for Clear Water Pumping Station as per the above specification
Supply and delivery of 350mm dia separate version Electro Magnetic Flow Meter MAG 5100 model or equilant with the specification of flow body as per company standards, electrodes of SS316, accuracy of +/- 2%, cable length of 20 Mtrs, end connection of ANSI flanges as IS/DIN standards, flow bore protection is IP68, earth rings of SS ( If required as per site condition) flow transmitter body as per company standard and two line display, transmitter having 4-20mA, RS485 and modbus communication for data transfer through any network, power supply of 24 volts DC , and submittion of manufacturer test and calbrationreports charges and all charges including cost and conveyance of all material , freight, transport and labour etc and complete, and as directed by the dept., officer for raw water and clear water pumping station.
Supply and testing of panel mounted 96 mmx 48 mm size on line mounted pH Analyser with Display (4 Digit) make of FM/ JUMO / ABB/ SIEMENS/ HACH with the technical specifications of Measuring Range: 0-14 pH, Process pressure range : 1 bar @ 50 Deg C, Measuring method : Reference, Solution ground : Graphite, electrode body: Glass body (tip), Wetted Parts : Glass tip plastic shaft protection Operating Temp: 0 to 50 Deg C, Protection Class : IP 65 (front) & IP 20 (rear), Communication : RS485, Voltage : 24 V.. DC Cable : 10 mtrs of Poly made the charges are including test and calibration certificate, cost and conveyance of all material, labor cost materials other incidental charges etc complete as per SS and as directed by the departmental officer incharge of work for raw water inlet and clear water outlet treatement plant.
Supply and testing of wall mounted 120(w), 140(H), 77(D) Turbidity analyser with display(4 digit) make of FM/ JUMO / ABB/ SIEMENS/ HACH with the technical specifications of Measuring range: 1-4000 Ntu, Process pressure range : 2 bar @ 50 deg c, Measuring method : Infrared light 90 deg scatter light method, Max. sampling rate for measured values: 1 Hz, Resolution : 0.01 to 1 depending on measuring range , Measurands : Turbidity & Temperature Operating temp: 0 to 50 deg c, Protection class : IP 67, Communication : RS 485/4-20 mA, Voltage : 24 v.. DC, Sensor case : PVC/POM-C, Optical window: PMMA, Cable : 10 mtrs of Poly made the charges are including test and calibration certificate, cost and conveyance of all material, labor andcost and conveyance of all material, labor cost materials other incidental charges etc complete as per SS and as directed by the departmental officer incharge of work for raw water inlet and clear water outlet treatement plant.
Supply and testing of panel mounted 96 mm x 48 mm size on line mounted Conductivity/ TDS sensor with display (4 digit) make of FM/ JUMO / ABB/ SIEMENS/ HACH with the technical specifications of Measuring range: .1 to approx. 1000 μS/cm, Cell constant : 0.1, Process pressure range : 5 bar @ 50 deg c, Measuring method : Conductive 2 electrode, Sampling : 500 msec, Measurands : Conductivity / TDS, Operating temp : -5 to +80 °C, Protection class : IP 67, Communication : RS 485, Voltage : 24 v.. DC, Sensor case: Stainless Steel 1.4571, Body material: PEI, Cable : 10 Mtrs of Polyimide and the charges are including test and calibration certificate, cost and conveyance of all material, labor and cost and conveyance of all material, labor cost materials other incidental charges etc complete as per SS and as directed by the departmental officer incharge of work for raw water inlet and clear water outlet treatement plant.
Supply and testing of panel mounted 96 mm x 48 mm size on line mounted Chlorine Analyzer with display (4 digit) make of FM/ JUMO / ABB/ SIEMENS/ HACH with the technical specifications of Measuring range: 0-10 PPM, Cell constant : 0.1, Process pressure range : 1 bar @ 50 deg c, Measuring method : 2 and 3 Electrode principle, Response time : Approx. 2 min, pH Dependency (loss of slope) : In the range from pH 5 to 7: no loss of slope, at pH 8 about 10%, at pH 9 about 20%, (starting from pH 7), Operating temp : 0 to 50°C, Protection class : IP 67, Communication : RS 485, Voltage : 24 v.. DC, Sensor Case: PVC, Body material : PEI, Cable : 10 Mtrs of Polyimide and the charges are including test and calibration certificate, cost and conveyance of all material, labor and cost and conveyance of all material, labor cost materials other incidental charges etc complete as per SS and as directed by the departmental officer incharge of work for clear water outlet of WTP
Supply laying and fixing of tubing for Inlet and out let of raw water and clear water to the analyzers with necessary pipes with compressed fittings charges excluding cost of taxes and duties including cost and conveyance of all material including transport and labor etc., complete and as directed by the dept., officer. for Raw Water inlet and clear water outlet WTP
Supply, errection, Testing & Commissioning of Out door type PLC/Controller based Automation and communication Panel fabricating with 16 SWG CR sheet, internal and external surface coating with Epoxy powder coating, making internal wiring with suitable wires including nomenclature. The panel is suitable for the Control & Monitoring the Level, Flow & Pressure and Quality Parameters and Comunicating with Central SCADA for Auto logic, Local and Remote operation of the valves with specifications of fabricating with 16 SWG CR sheet, internal and external surface coating with powder coating, making internal wiring with suitable wires including nomenclature. The panel is suitable for the above operations with PLC/Controller, communication modules, HMI, Power back up and necessary modules and as per site conditions etc., complete charges including all material and labor and and as per SS and as directed by the department officer. for raw water inlet and clear water outlet at WTP
Supply, errection, Testing & Commissioning of In door type Scada based RTU control panel for Opearating and monitoring of the Raw Water and Clear Water Pumping stations in auto logic and manual operations including synchornize with SCADA and the specifications of fabricating with 16 SWG CR sheet, internal and external surface coating with Epoxy powder coating, arrangement of required PLC/ Controller, Ethernet Switch, Required I/O Modules and DI, DO modules, all components powered by 24 V. DC with necesssary control MCB's, Relay cards, fixing of all termination with FTB's, Internal wiring by all power cables with suitable guage of Single core copper PVC sheated cables and all communication cables with SS Brided cables, and the panel having logic for the following and erection with required civil works as per site conditions etc., complete charges including all materials and labour and as per SS and as directed by the department officer. for raw water and clear water pumping station
supply and delivery of 150mm dia "Resilient Seated Soft Sealing" Gate Valves (Sluice Valves) with Body and Bonnet of Ductile Iron GGG-40/SG-400/15 or GGG-50/SG-500/7 or Equivalent as per IS1865, IS:3896-2 and Wedge fully Rubber Lined with food grade quality grade W270 grade EPDM, Replaceable Spindle Nut without gland packing with 3-O ring protection system on the Shaft and Seals of NBR. The Valves should be Vacuum tight and 100% leak proof with face to face dimensions as BS:5163 Type A/IS:14846. All the valves should be with fusion bonded Electrostatic Powder coating both inside and outside (Min 250 Microns)- RAL 5005 with Pocket Less Straight through body Passage conforming to Design standards of DIN-3202F4/BS:5163 Type A Flange drilling as per IS - 1538 and including transportation. and other incidental charges etc complete as per SS and as directed by the departmental officer incharges of work.
supply and delivery of 250mm dia "Resilient Seated Soft Sealing" Gate Valves (Sluice Valves) with Body and Bonnet of Ductile Iron GGG-40/SG-400/15 or GGG-50/SG-500/7 or Equivalent as per IS1865, IS:3896-2 and Wedge fully Rubber Lined with food grade quality grade W270 grade EPDM, Replaceable Spindle Nut without gland packing with 3-O ring protection system on the Shaft and Seals of NBR. The Valves should be Vacuum tight and 100% leak proof with face to face dimensions as BS:5163 Type A/IS:14846. All the valves should be with fusion bonded Electrostatic Powder coating both inside and outside (Min 250 Microns)- RAL 5005 with Pocket Less Straight through body Passage conforming to Design standards of DIN-3202F4/BS:5163 Type A Flange drilling as per IS - 1538 and including transportation and other incidental charges etc complete as per SS and as directed by the departmental officer incharge of work.
Supply and delivery of 150mm dia separate version Electro Magnetic Flow Meter MAG 5100 model or equilant with the specification of flow body as per company standards, electrodes of SS316, accuracy of +/- 2%, cable length of 20 Mtrs, end connection of ANSI flanges as IS/DIN standards, flow bore protection is IP68, earth rings of SS ( If required as per site condition) flow transmitter body as per company standard and two line display, transmitter having 4-20mA, RS485 and modbus communication for data transfer through any network, power supply of 24 volts DC , and submittion of manufacturer test and calbrationreports charges and all charges including cost and conveyance of all material , freight, transport and labour etc and other incidental charges etc., complete, and as directed by the dept., officer.150MM Dia.
Supply and delivery of 250mm dia separate version Electro Magnetic Flow Meter MAG 5100 model or equilant with the specification of flow body as per company standards, electrodes of SS316, accuracy of +/- 2%, cable length of 20 Mtrs, end connection of ANSI flanges as IS/DIN standards, flow bore protection is IP68, earth rings of SS ( If required as per site condition) flow transmitter body as per company standard and two line display, transmitter having 4-20mA, RS485 and modbus communication for data transfer through any network, power supply of 24 volts DC , and submittion of manufacturer test and calbrationreports charges and all charges including cost and conveyance of all material , freight, transport and labour etc and other incidental charges etc., complete, and as directed by the dept., officer.250MM Dia.
Supply and delivery of 150mm dia Electrically switched, DI D/F hydraulic and self-medium operated diaphragm Control valve for the functions of Pressure & Flow control at Tank inlet with the function to maintain a constant downstream flow and pressure by controlling the differential pressure between the inlet and outlet of an orifice plate, regardless of pressure variations. The valve shall be of globe pattern inline or angular pattern with a main valve body of full or reduced bore designed for full differential pressure. The seat shall be of stainless steel which is replaceable.The valve can use manually and electrically with 24 V.. AC/DC for operation. The control tubing with self cleaning filter unit to functions as per customer requirement. The internal & external coating with liquid/Powder form epoxy coating, all fastners with SS including cost and convayance of all material and labor and other incidental charges etc complete and as per SS and as directed by the department officer - 150mm
Supply and delivery of 250mm dia Electrically switched, DI D/F hydraulic and self-medium operated diaphragm Control valve for the functions of Pressure & Flow control at Tank inlet with the function to maintain a constant downstream flow and pressure by controlling the differential pressure between the inlet and outlet of an orifice plate, regardless of pressure variations. The valve shall be of globe pattern inline or angular pattern with a main valve body of full or reduced bore designed for full differential pressure. The seat shall be of stainless steel which is replaceable.The valve can use manually and electrically with 24 V.. AC/DC for operation. The control tubing with self cleaning filter unit to functions as per customer requirement. The internal & external coating with liquid/Powder form epoxy coating, all fastners with SS including cost and convayance of all material and labor other incidental charges and as per SS and as directed by the department officer - 250mm
Supply ad delivery of M.S. Dismantling Joints /SS, D/F expansion bellows with specifications of bellow with SS ASTM A 240 TP 304 grade, tie rods with EN8/IS-2062 Grade, End connection flanges with IS 2062 Gr.B Sorf plate, Drilling and dimensions as per approved drawing as required by customer at the time of order confirmation charges excluding cost of taxes and duties including cost and conveyance of all material including transport and labor etc., complete as per specification of SOR and as directed by the dept., officer. as follows
Supply, errection, testing and commissioning of Ultra sonic/ Altitude Level sensors make of SIEMENS/ ABB/ BAUMER/ DANFOSS / KELLER with specifications of body construction with standard construction, mesuring upto 6.00 Mtr depth, protection clause of IP 65, accuracy is +/- 5%, input power supply is 24 V.. DC, remote comunication protocol of 4 to 20 ma, temperature safety is in-built to comperhencive over temprature range with in the -40 Deg to +80 Deg, installed in both conditions i.e., indoor and outdoor, charges other incidental charges including cost and conveyance of all material including transport and labor etc., complete and as directed by the dept., officer. for firms at various ELSR's
Providing, Installation, Testing and Commissioning of PRESSURE TRANSMITTER for Water Application: Range: 0-10 Bar / Power Supply: 24 V DC / Output: 4-20 mA / Diaphragm: SS316L / Process Connection: 1/2 "NPT (M) / Accuracy: 0.15% Protection: IP67 . The cost also includes the calibration of all the sensors manifold etc., complete including cost and convayance of all material and labor other incidental charges and as per SS and as directed by the department officer for fixing at various ELSR's
Supply and testing of panel mounted 96 mm x 48 mm size on line mounted Chlorine Analyzer with display (4 digit) make of FM/ JUMO / ABB/ SIEMENS/ HACH with the technical specifications of Measuring range: 0-10 PPM, Cell constant : 0.1, Process pressure range : 1 bar @ 50 deg c, Measuring method : 2 and 3 Electrode principle, Response time : Approx. 2 min, pH Dependency (loss of slope) : In the range from pH 5 to 7: no loss of slope, at pH 8 about 10%, at pH 9 about 20%, (starting from pH 7), Operating temp : 0 to 50°C, Protection class : IP 67, Communication : RS 485, Voltage : 24 v.. DC, Sensor Case: PVC, Body material : PEI, Cable : 10 Mtrs of Polyimide and the charges are including test and calibration certificate, cost and conveyance of all material, labor and other incidental charges etc complete as per SS and as directed by the departmental officer incharge of work for fixing of various ELSR's.
Supply laying and fixing of tubing for Inlet and out let of raw water and clear water to the analyzers with necessary pipes with compressed fittings charges as per technical specifications including cost and conveyance of all material including transport and labor other incidental charges etc., complete and as directed by the dept., officer. for fixing at various ELSR's.
Supply, errection, Testing & Commissioning of Out door type PLC/Controller based Automation and communication Panel fabricating with 16 SWG CR sheet, internal and external surface coating with Epoxy powder coating, making internal wiring with suitable wires including nomenclature. The panel is suitable for the Control & Monitoring the Level, Flow,Pressure and Quality Parameters and Comunicating with Central SCADA for Auto logic, Local and Remote operation of the valves with specifications of fabricating with 16 SWG CR sheet, internal and external surface coating with powder coating, making internal wiring with suitable wires including nomenclature. The panel is suitable for the above operations with PLC/Controller, communication modules, HMI, Power back up and necessary modules and as per site conditions etc., complete charges including all material and labor and as per SS and as directed by the department officer.
Supply laying and jointing of 4 Sq.MM - 2 core PVC sheeted cable make of LAPP/Orbit/Polycab/Finolex for solar / Raw power for the instrumantation and automation at Raw water and clear water pumping with in the Head works compound/ pumping stations/Individual OHSR's and laying with necessary cable trays/Condutes/ Civil works from each and every panel through side walls/cealing / floorings etc., where ever is necessary with all related civil works etc., charges including cost and conveyance of all material including transport and labor etc., complete and as directed by the dept., officer.
Supply laying and jointing of 0.75 Sq.MM - 4 core SS Brided and PVC sheeted cable make of LAPP/Orbit/Polycab/Finolex for solar / Raw power for the instrumantation and automation at Raw water and clear water pumping/ with in the Head works compound/ pumping stations/ Individual OHSR,s and laying with necessary cable trays/Condutes/ Civil works from each and every panel through side walls/cealing / floorings etc., where ever is necessary with all related civil works etc., charges excluding cost of including cost and conveyance of all material including transport and labor etc., complete and as directed by the dept., officer.
Erection, testing and commissioning of Reservoir Management unit including dejointing of existing pipeline / flange joints, taking out already laid DI/MS or any kind of pipe barrel piece, lifting the said pipe, cleaning & returning to the departmental store as per direction of the Engineer-in-charge and lowering, aligning & placing the flow Meter unit, jointing the same with fabricating of fittings, reducers, flanges with necessary MS material as per flow meter manufacturer standards and as per the site conditions with necessary lifting equiment, fabrication works, fixing with new Nuts , bolts and Rubber insertion with arrangment of necessary earth work excavations, MS clamp brackets, lifting equipment, retrofit works to complete the job as per site condition (Excluding cost of Meter, Valve& Expansion bellow etc.,) charges other incidental charges including cost and conveyance of all material including transport and labor etc., complete and as directed by the dept., officer. for various ELSR's
Integration of PLC panels with Developing necessary softwares and programming as per field condition and user interface, communicated from each panel and intigrated with central SCADA station charges including cost and conveyance of all material including transport and labor etc., complete and as directed by the dept., officer.
supply and delivery of 200mm dia "Resilient Seated Soft Sealing" Gate Valves (Sluice Valves) with Body and Bonnet of Ductile Iron GGG-40/SG-400/15 or GGG-50/SG-500/7 or Equivalent as per IS1865, IS:3896-2 and Wedge fully Rubber Lined with food grade quality grade W270 grade EPDM, Replaceable Spindle Nut without gland packing with 3-O ring protection system on the Shaft and Seals of NBR. The Valves should be Vacuum tight and 100% leak proof with face to face dimensions as BS:5163 Type A/IS:14846. All the valves should be with fusion bonded Electrostatic Powder coating both inside and outside (Min 250 Microns)- RAL 5005 with Pocket Less Straight through body Passage conforming to Design standards of DIN-3202F4/BS:5163 Type A Flange drilling as per IS - 1538 other incidental charge and including transportation and as directed by the departmental officer incharge of work.
Supply and delivery of 200mm dia Separate Version Electro Magnetic Flow Meter MAG 5100 model or equilant with the specification of flow body as per company standards, electrodes of SS316, accuracy of +/- 2%, cable length of 20 Mtrs, end connection of ANSI flanges as IS/DIN standards, flow bore protection is IP68, earth rings of SS ( If required as per site condition) flow transmitter body as per company standard and two line display, transmitter having 4-20mA, RS485 and modbus communication for data transfer through any network, power supply of 24 volts DC , and submittion of manufacturer test and calbrationreports charges and all charges including cost and conveyance of all material , freight, transport and labour and then incidental charges etc., complete, and as directed by the dept., officer.
Supply and delivery of 200mm Dia Electrically switched, DI D/F hydraulic and self-medium operated diaphragm Control valve for the functions of Pressure & Flow control at Tank inlet with the function to maintain a constant downstream flow and pressure by controlling the differential pressure between the inlet and outlet of an orifice plate, regardless of pressure variations. The valve shall be of globe pattern inline or angular pattern with a main valve body of full or reduced bore designed for full differential pressure. The seat shall be of stainless steel which is replaceable.The valve can use manually and electrically with 24 V.. AC/DC for operation. The control tubing with self cleaning filter unit to functions as per customer requirement. The internal & external coating with liquid/Powder form epoxy coating, all fastners with SS including cost and convayance of all material and labor other incidental charges and as per SS and as directed by the department officer
Supply ad delivery of 200mm dia M.S. Dismantling Joints /SS, D/F expansion bellows with specifications of bellow with SS ASTM A 240 TP 304 grade, tie rods with EN8/IS-2062 Grade, End connection flanges with IS 2062 Gr.B Sorf plate, Drilling and dimensions as per approved drawing as required by customer at the time of order confirmation charges other incidental charges including cost and conveyance of all material including transport and labor etc., complete and as directed by the dept., officer.
Providing, Installation, Testing and Commissioning of PRESSURE TRANSMITTER for Water Application: Range: 0-10 Bar / Power Supply: 24 V DC / Output: 4-20 mA / Diaphragm: SS316L / Process Connection: 1/2 "NPT (M) / Accuracy: 0.15% Protection: IP67 . The cost also includes the calibration of all the sensors manifold etc., complete including cost and convayance of all material and labor and other incidental charges and as per SS and as directed by the department officers incharges of work for inlet of DMA under 500 KL ELSRs at bridge peta
Supply, errection, Testing & Commissioning of Out door type PLC/Controller based Automation and communication Panel fabricating with 16 SWG CR sheet, internal and external surface coating with Epoxy powder coating, making internal wiring with suitable wires including nomenclature. The panel is suitable for the Control & Monitoring the Level, Flow, Pressure and Qaulity Parameters and Comunicating with Central SCADA for Auto logic, Local and Remote operation of the valves with specifications of fabricating with 16 SWG CR sheet, internal and external surface coating with powder coating, making internal wiring with suitable wires including nomenclature. The panel is suitable for the above operations with PLC/Controller, communication modules, HMI, Power back up and necessary modules and as per site conditions etc., complete charges including all material and labor and other incidental charges and as per SS and as directed by the department officer for Inlet of DMA-1 under 500 KL ELSR at Bridge peta
Supply laying and jointing of 4 Sq.MM - 2 core PVC sheeted cable make of LAPP/Orbit/Polycab/Finolex for solar / Raw power for the instrumantation and automation at Raw water and clear water pumping with in the Head works compound/ pumping stations/Individual OHSR's and laying with necessary cable trays/Condutes/ Civil works from each and every panel through side walls/cealing / floorings etc., where ever is necessary with all related civil works etc., charges other incidental charges including cost and conveyance of all material including transport and labor etc., complete and as directed by the dept., officer for inlet of DMA under varion ELSR's
Supply laying and jointing of 0.75 Sq.MM - 4 core SS Brided and PVC sheeted cable make of LAPP/Orbit/Polycab/Finolex for solar / Raw power for the instrumantation and automation at Raw water and clear water pumping/ with in the Head works compound/ pumping stations/ Individual OHSR,s and laying with necessary cable trays/Condutes/ Civil works from each and every panel through side walls/cealing / floorings etc., where ever is necessary with all related civil works etc., charges and other incidental charge including cost and conveyance of all material including transport and labor etc., complete and as directed by the dept., officer for Inlet of DMA under 500 KL ELSR at Bridge peta.
Erection, testing and commissioning of DMA management unit including dejointing of existing pipeline / flange joints, taking out already laid DI/MS or any kind of pipe barrel piece, lifting the said pipe, cleaning & returning to the departmental store as per direction of the Engineer-in-charge and lowering, aligning & placing the flow Meter unit, jointing the same with fabricating of fittings, reducers, flanges with necessary MS material as per flow meter manufacturer standards and as per the site conditions with necessary lifting equiment, fabrication works, fixing with new Nuts , bolts and Rubber insertion with arrangment of necessary earth work excavations, MS clamp brackets, lifting equipment, retrofit works to complete the job as per site condition (Excluding cost of Meter, Valve& Expansion bellow etc.,) charges and other incidental charges including cost and conveyance of all material including transport and labor etc., complete and as directed by the dept., officer. incharges of work for inlet of DMA-1 under 500KL ELSRs at Bridge peta.
Integration of PLC panels with Developing necessary softwares and programming as per field condition and user interface, communicated from each panel and intigrated with central SCADA station charges and other incidental charges including cost and conveyance of all material including transport and labor etc., complete and as directed by the dept., officer for Inlet of DMA of 500 KL ELSR at Bridge peta.
Providing, Installing and satisfactory field testing of domestic Water Meter with AMR Compatible Mechanical Water Meters with the specifications of minimum Dynamic ratio (Q3/Q1) of 160:1, fully body made up of composite material/ Brass/ Bronze, the metal Material that come in contact with the water supply shall withstand 2 ppm (Parts per million) of chlorine residual in the water supply and shall be resistant to corrosion, mechanical inferential type, multi jet, magnetically coupled, having dry dial, protection class of IP-68, Class ’B’ confirming to IS-779: 1994 with up to date amendments or ISO 4064:2014 standard with ISI/EEC/OIML/MID/CE certification mark shall be with meter and offer 5 years warranty and submittion of manufacturer test and calbrationreports charges and all charges including cost and conveyance of all material , freight, transport and labour etc and etc., complete, and as directed by the dept., officer. for DN 15 - PN 16 AMR Compatible Mechanical Water Meter as per above specification for all reservoirs comman area
Supply, Delivery, Installing and satisfactory field testing of AMR Unit for domestic Water Meters from 15 mm to 40 mm with the specifications of fully body made up of composite material, magnetically coupled in between meter and AMR module, protection class of IP-68, In built battery with 3.60 V... Lithium Battery for life of 10 Years based on one communication /Day, Communication interface in between meter and AMR unit with Pulse/ Photo Electric, AMR unit can fetch the data from meter on hourly basis and store the data for 48 Hours on FIFO basis and send the data through NB IoT in every 24 Hours without fail through the provider registered in DOT, India, if the communication fails due to bad communication the AMR module can try for a maximum six times in different time intervals to ensure the data to reach to server. The AMR unit have option of Bluetooth for remote configurations at field. In the special event and field testing the data sending interval of AMR unit can be configurable and minimum time interval span is one Hour (The battery life can be calculated based on the time intervals of data communication) The data storage should be kept in Indian data centres for the data security, AMR unit can be registered the abnormalities like Reverse flow, Leak detection, Tampering and send to the server via reading data packet, Every communication from the AMR module to server should be in JSON format with real time stamping, The AMR can suitable for all the Mechanical Water meters supplied by the agency in this contract. The AMR Module offered with 5 years warranties and submittion of manufacturer test and calbrationreports charges and all charges including cost and conveyance of all material , freight, transport and labour etc and etc., complete, and as directed by the dept., officer.under DMA under 500 KL ELSR at Bridge peta
Supplying and Fixing water meter BOX- with Weather resistant FRP box, press fitted Lid fixing & locking and locked with built-in or external lock. Charges including breather, NBR bushes for pipe entry, SS Grouting screws other incidental charges etc., complete and as directed by the departmment officer.
Supply, erection, testing, commissioning of Hard ware for the SCADA system for Local control station where the SCADA room will be developed by the local ULB for operting & View from Service Reservoirs, DMA and AMI meter management where the instrumantation and automation developed under this project and synchornization by deploying the following components including cost and convayance of all material, user licences, communication networks, etc., complete and as directed by the department officer. Desktop PC Station with specification of I7 Processor, 8 GB Ram, ,512 GB SSD, Licensed OS, 21" Screen with Mouse, keyboard, and relevant accessories make of LENOVO/ HP/ DELL 55" LED Display make of Sony/Samsung/ LG or equilant with ethernet/HDMI/VGA supported for front end view by connecting with PC in dual mode operation and View the SCADA screens with required cables and connectors etc., complete. Modem with specifications of Fibre Port having ILL, PON & Network Features, Speed 100/1000, LAN Ports, Fibre port x 1 N0 make of CISCO/ HP/ FF/ONV/PHOENIX/Dlink/ Suggested by the telecom provider
3 KVA Stabilizer with specifications of 220 V.AC Input/ 220 V.AC output, necessary terminal wires etc., complete complete 3 KVA online ups with specifications of 220 V.AC Input/ 220 V.AC output, Static By pass with isoltion transformer, Required Battery bank, make of Vertex/EATON/ BPE/ NUMERIC /RIELLO / ENERTECH complete 3 in one on line B/W A4 Lazer Jet printer Network for all local control stations and central station with registration with any communication provider and payment of minimum one year subscription and establishment of communication Establishment of Local SCADA station at Kovvuru Municipality with the above specifications.
Design, Development, Deploy, testing & commissioning of Firmware for the WEB based SCADA system for Local control station where the SCADA room will be developed by the local ULB for operting & View from Service Reservoirs, DMA and AMI meter management and where the instrumantation and automation developed under this project by synchornization with the field instruments, configuration with the following features including cost and convayance of all material, user licences, communication networks, etc., complete and as directed by the department officer. Development and providing the WEB based SCADA for Operation and Monitoring by the individual ULB where implemented the Reservoir management to AMI management. (Expandable upto Source to end user) Development of front end view monitoring and operating application in Digital Twin Mode with 3D & 2D model including designing, animation, drawings and integration of SCADA with field devices through MQTT/ MODBUS/ TCPIP protocol etc., complete. Develop, Supply, install and commissioning of customized WEB applications for Data analytics, Visulation, Trends, Data auditing, generating the reports as required by the customer at the time of commissioning Develop, Supply, install and commissioning of Anroid & IO's application for data monitoring by through Mobi-APP as required by the customer at the time of commissioning complete Establishment of Local SCADA station at Kovvuru Municipality with the above specifications.
Providing Technical Graduate for co-ordinating the process of interconnections of the existing and proposed systems, preparation of documents related to inter departmental permissions and liaison with line departments to obtain permissions including preparation of build drawings as instructed by the Engineer in charge.
Providing the services such as consumer survey and mapping, asset mapping, ground validation, component wise structural and hydraulic designs as per site condition, GIS based hydraulic modelling of all components of both existing and proposed water supply infrastructure and any other documentation/ plan/ designs related to the whole scheme as per the instructions of the Engineer incharge and CPHEEO Manual
Engaging of Man Mazdoor (Skilled / Semi Skilled) Like Electrician, pump Operator, Mechanic, Helpers, watch man, Filter bed operator, Diploma Engineer, Lab Technician, Technical work inspector etc, as per the requirment. The rate includes wages along with Municipal allowance, conveyancer charges for transporation to the work site including statutory provisions as per norms etc complete for sucessful by Maintainace of the entire scheme as directed by the departmental officer incharge of the work (for 10 years + 2 years Defect liablity period as follows
i)Personal required for operating Intake/Offtake well/Pump housesPersonal required for operating Intake/Offtake well/Pump houses
a)Operator
b)Fitter/Helper
c)Watch man
ii)Personal required at operating Raw water rising mains
Fitter/Helper
iii)Personal required at operating Water treatment plants & Sump
Operator
Fitter/Helper
Lab Technician
Electrician/Mechanic
Watch man
iv)Personal required at operating Clear water rising mains
Fitter/Helper
v)Personal required at operating Gravity mains
Watchman
vi)Personal required at operating Service reservoirs
Watchman
vii)Personal required at operating distribution system
Fitter/Helper
Supply, delivery and stacking of Chorine gas for disinfection 3mg/Lt as per relevant indian standards in cylinders including cost of material, coveyance, stacking at the location specified by the Department and., complete to be used as a disinfectant in accordance with CPHEEO manual guidelines.
Supply and delivery of Alumino -Ferric (Alum) as per IS standards including the cost of material, conveyance, stacking at the location specified by the Dept., ., complete.rement at 20 mg/lit
Repairs to pumpsets & Water pipe lines (2 years after execution period) complete as per ss and as directed by the departmental officer incharge of work
iv)Replacement of glands of sluice valves
v) Replacements of balls of Air valves
vi) Greease
vii) Gland Packing
Provision towards purchase pipe jointing materials, etc
LEAKAGES
Earth work Excavation,Bailing out water from Pipe Line Trench and replacement damaged HDPE Pipe for 1 M length including the Cost of Pipe Collar M/F Joint and refilling etc complete
315 mm HDPE Pipes
280 mm HDPE Pipes
250 mm HDPE Pipes
225 mm HDPE Pipes
200 mm HDPE Pipes
160 mm HDPE Pipes
110 mm HDPE Pipes
To asist to attend the service calls by the seniour service engineer
With assistance of the DBA, preparation of daily reports, monthly billing, correspondence with consumers and also co-ordinate with the GVMC Officials for obtaining of required information when ever asks.
To assist the entire team, dispatches and also maintain SCADA station clean and neat
Replacement of necessary servicable materials(Reagents) for Chlorine Analysers * Each Reagent bottle will work for 90 days (Self life) as per the Caluculation based on the Sampling interval in every 10 Minuets.
Replacement of necessary tranducers for PH analysers
Replacement of necessary tranducers for Turbidity analysers
Interconnection for Data receive station from all Local Contol RTU panels.
Data transfer from RTU control panels
Charges for maintainance of PC's, Hardware consumables, Minor repair & Servers ,servomax Stabliser, UPS, maintainance of entire system including cost and convayance of all material and labor and attending minor repairs to instrumantation and automation equipment etc., complete
To monitor all issues related to both operation & service
To monitor all meters location through SCADA station and give feedback to the service engineers.
With assistance of the DBA, preparation of daily reports, monthly billing, correspondence with consumers and also co-ordinate with the Officials for obtaining of required information when ever asks.
To assist the entire team, dispatches and also maintain SCADA station clean and neat
Interconnection for Data receive station from all Local Contol RTU panels.
Data storage and reporting system for view through WEB and Mobile networks
for day to day Operations & Reporting
JANGAREDDYGUDEM MUNICIPALITY
Construction of 8.00m dia.(201.22 KL) Raw Water Intake Well in Yerra Kalvuva Reservior
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH Note : Classifications of Earth Work Specification are as per 302.2.1(a) of MORD and 301.2.1 of MORT&H--ordinary soil--manual means upto 3m depth for foundations of buildings in restricted places By mechanical means
a) Upto Initial Lift of 3.00m 0.00-3.00m
b) 3.00 to 6.00m depth
Filling sand in foundation trenches of Intake well bed as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH etc., complete. This rate including cost of all materials, all labour charges, watering, ranning other incidental charge etc complete as per SS and as directed by the Departmental officer in charge of the work. But excluding seigniorage charge.
Plain Cement Concrete (1:4:8) (cement: fine aggregate: Coarse aggregate) for foundations and under drain bed using 162.0 kgs of cement, coarse aggregate 40mm size hard , machine crushed granite from approved quarry including cost and conveyance of all materials like cement, sand, coarse aggregate, water etc. to site, includingall materials and all charges for machine mixing, laying concrete in foundations and under drain bed, ramming in 15 cm layers finishing top surface to the required level curing etc., and complete for finished item of workas per SS and as directed by the departmental officer incharge of the work but excluding seigniorage charges for bed concrete of Intake well.
Supply and placing of the M30 grade Design Mix Concrete corresponding to IS 456 using Concrete Mixer with 20mm size graded machine crushed hard granite metal (coarse aggregate) from approved quarry including cost and conveyance of all materials like cement, fine aggregate (sand) coarse aggregate, water etc., to site and including Seigniorage charges, sales & other taxes on all materials including all operational, incidental and labour charges such as weigh batching, machine mixing, laying concrete, curing etc.,complete but excluding cost of steel and its fabrication charges for finished item of work (APSS No. 402)with minimum cement content as per IS code from standard suppliers approved by the department including pumping, centering, shuttering, laying concrete, vibrating, lifting, delifting curing etc. complete but excluding cost of steel and its fabrication charges for finished item of work.But excluding seigniorage Charges. as follows
a) for Base slab
b) for Side walls 85.75-72=13.75 upto 3.00mts
Side Wall of the Well of 0.50m thick 1st d lift i.e 1.00mts
Side Wall of the Well of 0.50m thick 2nd d lift i.e 0.50mts
Side Wall of the Well of 0.50m thick above BL i.e 3.00mts
Side Wall of the Well of 0.50m thick 1st lift i.e 1.00mts
Side Wall of the Well of 0.50m thick 2 nd lift i.e 1.00mts
Side Wall of the Well of 0.50m thick 3 rd lift i.e 1.00mts
Side Wall of the Well of 0.50m thick 4 th lift i.e 1.00mts
Side Wall of the Well of 0.50m thick 5th lift i.e 1.00mts
Side Wall of the Well of 0.50m thick 6th lift i.e 1.00mts
Side Wall of the Well of 0.50m thick 7th lift i.e 1.00mts
Side Wall of the Well of 0.50m thick 8th lift i.e 1.00mts
Supply and placing of the M30 grade Design Mix Concrete corresponding to IS 456 using Concrete Mixer with 20mm size graded machine crushed hard granite metal (coarse aggregate) from approved quarry including cost and conveyance of all materials like cement, fine aggregate (sand) coarse aggregate, water etc., to site and including Seigniorage charges, sales & other taxes on all materials including all operational, incidental and labour charges such as weigh batching, machine mixing, laying concrete, curing etc.,complete but excluding cost of steel and its fabrication charges for finished item of work (APSS No. 402)with minimum cement content as per IS code from standard suppliers approved by the department including pumping, centering, shuttering, laying concrete, vibrating, lifting, delifting curing etc. complete but excluding cost of steel and its fabrication charges for finished item of work.But excluding seigniorage Charges as follows
a) for Pump house Columns
b) for floor beams - Ring Beam
c) for Floor Slab 0.30 m thick
d) for Lintel Beams alround
e) for Roof Beams
f) for Roof slab 0.125m thick
g) for Sunshade of 0.60mts wide and thickness of .075mts at fixed end and 0.05mts.at free end
Brick Masonry in CM (1:6) with 2nd class clay Bricks traditional size 23 x 11 x 7 cms including cost and conveyance of all materials and labour charges,watering, lifting , scoffoliding other incidental charges etc.,complete as per ss and directed by the departmental authorities of the work as per site conditions.But excluding seigniorage Charges. As follows.
for Super structure of Pump house
for Pump house Parapet wall
Plastering with CM (1:4), 12 mm thick including cost and conveyance of all materials and labour charges, watering , smooth finishing cost material, scoffoliding other incidental charges etc.,complete as per ss and directed by the departmental authorities of the work as per site conditions.But excluding seigniorage Charges.As follows.
for Pump house inside
for Parapet wall
Plastering with CM (1:3), 12 mm thick including cost and conveyance of all materials and labour charges, watering , smooth finishing cost material, scoffoliding other incidental charges etc.,complete as per ss and directed by the departmental authorities of the work as per site conditions.But excluding seigniorage Charges.for ceiling
Plastering with CM (1:3), 20 mm thick including cost and conveyance of all materials and labour charges, watering , smooth finishing cost material, scoffoliding other incidental charges etc.,complete as per ss and directed by the departmental authorities of the work as per site conditions.But excluding seigniorage Charges
Painting Walls with Snowcem or other equal and approved Water Proof Cement Paint 2 Coats (All Colours) over a base coat of aproved cement primer making 3 coats in total including cost of all , conveyance charges of materials and other incidental charges, scaffolding, lifting and as directed by the departmental officer in charge of work
Painting two coats with synthetic enamel paint over a base coat of red oxide led. The rate includeds cost and conveyance of all materilas at site, labour charges, scaffolding charges etc., complete as ss and as directed by the departmental authorities (APDSS No:1201)
Supply & fixing of Rolling shutter made of 80 x 1.25 mm machine rolled CRCA laths, interlocked together through their entire length and jointed together at the ends by end-locks, mounted on specially designed pipe shaft of 50mm dia nominal bore MS B class pipe with brackets, plates, guide channels, stoppers, bottom locking plates and arrangements for inside & outside locking with push-pull operations including cost of hood cover and springs complete, painted with one coat of approved steel primer, locks, ball bearings, all accessories etc complete for finished item of work as per SS 1108 and as directed by the departmental officer in charge of work.
Supply and fixing Aluminium Anodised Two/ Three Track Sliding Windows of size 1.50Mx1.20M as per approved drawing with aluminium anodised sections of Series C Jindal sections and outer frame top horizontals & both verticals of 8774 of size 62 x 29.5 mm and bottom horizontal - two track frame of 8773 of size 62 x 29.5 mm, Shutter frame top, bottom and verticals of 8304 of size 50 mm x 20 mm and Weather interlocking frame of 8306 of size 50 x 20 with plain clear float glass 5 mm thick fixed including supply and fixing aluminium handles of 100 mm for each shutter, nylon rollers assembly and all labour charges for fixing the fixtures with required no.of screws, bolts and nuts and including labour charges for fixing the frame in position, fixing shutter to frame etc. completedand as directed by the departmental officer in charge of work.For Pump house 1.50x1.20m size
Bailing out of water with oil engine, driven pumpset including hire charges, fuel charges and wages of driver and helper and other incidental charges etc., complete as per the directions of departmental authorities payment shall be made a per log book and certifyed by the Engineer in charge
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying including sales and other taxes on all materials etc., complete for finished item of work in all floors.( APSS No.126)
Supply and delivery of 300mm dia "Resilient Seated Soft Sealing" Gate Valves (Sluice Valves) with Body and Bonnet of Ductile Iron GGG-40/SG-400/15 or GGG-50/SG-500/7 or Equivalent as per IS1865, IS:3896-2 and Wedge fully Rubber Lined with food grade quality grade W270 grade EPDM, Replaceable Spindle Nut without gland packing with 3-O ring protection system on the Shaft and Seals of NBR. The Valves should be Vacuum tight and 100% leak proof with face to face dimensions as BS:5163 Type A/IS:14846. All the valves should be with fusion bonded Electrostatic Powder coating both inside and outside (Min 250 Microns)- RAL 5005 with Pocket Less Straight through body Passage conforming to Design standards of DIN-3202F4/BS:5163 Type A Flange drilling as per IS - 1538 including conveyance to work spot and stacking care fully at site etc.complete as per S.S and as directed by the departmental officer in charge of work
Centrifugally cast (Spun) Ductile Iron pressure pies with flanged (welded) ends for water, gas, sewage conforming to IS: 8329/2000 in standard working lengths of 1,2,3, 4, 5 mts for classification K9 with cement mortar lining inside the pipes with outside zinc coating. Rates are ex-factory, the rate including transportation and conveyance to work spot and stacking at site etc., complete as per S.S and as directed by the departmental authorities.
Centrifugally cast (spun) Ductile Iron Fittings upto 500mm dia conforming to IS:9523/2000 having dimensions as per table. The rates mentioned here under are for fittings, zinc coated externally with inside mortar lining (with finishing as per class 13/IS 9523/2000) (ex-works) including Transportation and other incidental charges etc.complete as per S.S and as directed by the departmental officer in charge of work
Lowering, keeping in position and fixing 300mm dia D.I. sluice valves (with cap / with hand wheel & Reflex valves) excluding cost of bolts, nuts, rubber insertion, sluice valve and tail pieces . For 300mm dia. for fixing to Intake well Inlet Pipes other incidental charges etc.complete as per S.S and as directed by the departmental officer in charge of work
Lowering the C.I. Pipes, D.I. Pipes of 300mm dia all classes and fittings with flanged ends carefully into the trenches and laying them true to alignment and gradient including all sundries, but including conveyance from source of supply as per BIS No.3114/94. For 300mm dia. DI 90 deg bend other incidental charges etc.complete as per S.S and as directed by the departmental officer in charge of work
Jointing the 300mm dia D.I. Pipes, fittings and valves with flanged ends including cost of jointing materials such as bolts, nuts, rubber insertion, white lead and including filling with water with a water lead upto 500 m and testing to required pressure etc., comp as per BIS No.3114/85 other incidental charges etc.complete as per S.S and as directed by the departmental officer in charge of work for ladders.
Supply and delivery of S.S 304 grade operating handle with rod & wheel for operation of D.I. Sluice valve inside the intake well as per the actuals and as directed by the departmental authorities. Including fabrication and erection other incidental charges etc.complete as per S.S and as directed by the departmental officer in charge of work
Supply and delivery of S.S 304 grade for hand Railing 1.2 m height around the walk way the intake well as per the actuals and as directed by the departmental authorities. Including fabrication and erection other incidental charges etc.complete as per S.S and as directed by the departmental officer in charge of work
Supply and fixing of Stain less steel ladder made out of suitable sections for access from floor slab to Base slab 304 grade.This rate including cost of material all labour charges incidental charges etc.complete as per S.S and as directed by the departmental officer in charge of work
Supply and fixing of 25 mm dia 2.00 mm thick PVC pipe concealed in roof slab with all required accessories including masonary work all labour chages. This rate including cost of material all labour charges incidental charges etc.complete as per IE rule and as directed by the departmental officer in charge of work
Supply and fixing of 20 mm dia 1.50 mm thick PVC pipe concealed in walls with all required accessories including masonary work for light , fan and plug point with metal deep box including all labour chages. This rate including cost of material all labour charges incidental charges etc.complete as per IE rule and as directed by the departmental officer in charge of work .
Wiring with 2 runs 14/0.3 mm. (1.0. sq.mm) Fire retardant PVC insulated Flexible copper cable in existing pipe with 6A siwtch, ceiling rose and 3 mm thick hyla sheet covering to switch control box including all labour charges etc,., complet for light, bell , fan and exhaust fan points in non - residential building- for 6 points unit each Makes: Finolex / RR kabel / Havells /APAR E-beam for cable Makes: Legrand Arteor / Schneider Zen celo / Crabtree Murano/ GM-Zenova. for Modular switches Makes: Vimal opel / Starex Smile / CPL for Jumbo celling rose.This rate including cost of material all labour charges incidental charges etc.complete as per IE rule and as directed by the departmental officer in charge of work .
Wiring with 2 runs 14/0.3 mm. (1.0. sq.mm) Fire retardant PVC insulated Flexible copper cable in existing pipe with 6A modular siwtch control and 3/2 pin sockets fixing on board including all labour charges unit each Makes: Finolex / RR kabel / Havells /APAR E-beam for cable Makes: Legrand Arteor / Schneider Zen celo / Crabtree Murano/ GM-Zenova. for Modular swithes Makes: GM G Home / Gold Medal Olive / Million Zoom / Anchor Penta Cherry / Great white Omega for Jumbo Celling rose .This rate including cost of material all labour charges incidental charges etc.complete as per IE rule and as directed by the departmental officer in charge of work .
Supply and run of 2 of 36/0.3 mm. (1.5. sq.mm) Fire retardant PVC insulated Flexible copper cable in existing pipe for mains including all labour charges etc.,unit 1.00 Rmt Makes: KEI / Polycab / Bonton / V-Guard / GM / Million / HPL / Goldmedal / Finecab / Vimal / Fortune Art / Gloster / Kundan cab/Sudhakar. .This rate including cost of material all labour charges incidental charges etc.complete as per IE rule and as directed by the departmental officer in charge of work .
supply and run of 1 of 14/0.3 mm. (1.0. sq.mm) Fire retardant PVC insulated Flexible copper cable in existing pipe for earth continuity including all labour charges etc. unit 1.00 Rmt Makes: Finolex / RR kabel / Havells /APAR E-beam . This rate including cost of material all labour charges incidental charges etc.complete as per IE rule and as directed by the departmental officer in charge of work
supply and run of 2 of 6 sq.mm (7/18) WPSC alluminium cable along with No.10 SWG G.I barer wire through PVC cleats with all accessories including all labour charges etc.,unit 1.00 rmt Makes: Gold Medal / Million / GM / Vimal / Finecab / Nakoda / Nanadicab / Payal / Kundan cab/Sudhakar.This rate including cost of material all labour charges incidental charges etc.complete as per IE rule and as directed by the departmental officer in charge of work
Providing independent earthing by excavating a trench to a depth of 2.10m in all soils, as per size specied in data ,using 40 mm dia B class GI pipe 2.50m long with necessary accessories with hume pipe ring duly providing staggered holes including filling with equal proportion of salt and charcoal in layers and all labour charges etc complete.This rate including cost of material all labour charges incidental charges etc.complete as per IE rule and as directed by the departmental officer in charge of work
Supply and fixing SPN Distribution board with IP-30 protection suitable for single phase Earth Leakage Circute Braker (ELCB) / Residual Current Circute Braker (RCCB) / Double Pole (DP) Isolator as incomer and 10kA SP MCBs as out going including internal connections and labour charges for surface / flush mounting etc., complete.This rate including cost of material all labour charges incidental charges etc.complete as per IE rule and as directed by the departmental officer in charge of work
Supply and fixing of 48" (1200mm) Sweep Ceiling Fan including Regulator.of makes Crompton High Speed / Bajaj Ultima / Havells Velocity / Usha Astra / Orient Summer Pride. This rate including cost of material incidental charges etc.complete as per IE rule and as directed by the departmental officer in charge of work. But excluding labour charges.
Supply of stepped type Electronic Regulator of makes GM G Home / Gold Medal Olive / Million Zoom / Anchor Penta Cherry / Great white Omega.This rate including cost of material all labour charges incidental charges etc.complete as per IE rule and as directed by the departmental officer in charge of work
Supply of 9" (225mm), Light duty exhaust fan with double ball bearing and wire guard etc complete. Makes: Crompton / Bajaj Bahar WG / Havells Ventil Air-DS / Orient hill air / MIIT. This rate including cost of material all labour charges incidental charges etc.complete as per IE rule and as directed by the departmental officer in charge of work
Supply and fixing of 20W, 2400 lumens, T8 not lessthan 1100 mm length LED retrofit tube light with aluminum anodized body, input voltage AC 220 - 260 Volts, having luminous efficacy >=100 lumens/watt, with PF>0.9, surge protection: 2KV, THD<10%, with inbuilt driver and frosted cover CCT: 3000K- 5700K, minimum CRI>70, etc., as per IS 10322 (Part5/ Sec 1), 2012, complete with earth connection and not less than two years warranty. Makes: As per list of recommended brands as category
Labour charges for Fixing of Ceiling fan and regulator including transportation and giving connections with twin core wire etc., complete .This rate including cost of all labour charges incidental charges etc.complete as per IE rule and as directed by the departmental officer in charge of work
Labour charges for fixing of Exhaust fan in wall with necessary connections and masonary work of making hole, finishing etc., complete . .This rate including cost of all labour charges incidental charges etc.complete as per IE rule and as directed by the departmental officer in charge of work
Providing temporory Island for preparation platform for sinking of Intake well of 30m dia island and 6.00m height
Providing and construction of temporary island of 30.00m. diameter for preparation of platform with a height of 6.00mts for temporay Island for preparation platform top width 30.00mts minium height 6.00mts and formation temparay road of worksite etc. for construction of well foundation for 8.00m. internal dia. Intake well as per Tech. Specification 1203 MORTH.Sand bags for Crane with grab 1 cum capacity for Wooden ballies 8" Dia and 6 m long for Wooden ballies 2" Dia and 6 m long 3" to 4".This rate including cost of material all labour charges cost of sand bages,filling chrges ,hiring of machinery ,fuil chares , wages of driver , consumbkl, cost of wooden bullies, and other incidental charges etc.complete as per SS and as directed by the departmental officer in charge of work
Gravel filling infor tempory island approach road as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH etc., complete. This rate including cost of all materials, all labour charges, watering, ranning other incidental charge etc complete as per SS and as directed by the Departmental officer in charge of the work. But excluding seigniorage charge. for approach ramp payment mode a per level payment.
Construction of Approch Bridge 200.00m long for Intake well in Yerra Kalvuva Reservior
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH as per SS and as directed by the departmental officer incharge of the work for foundations of approach bridge in restricted places. As follows
Mechanical Means up to 3 metres depth in ordinary soils
manual means up to 3 metres depth in ordinary soils
Mechanical Means up to 3 metres depth in ordinary rock not requiring blasting
Filling sand in foundation trenches of column footing bed as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH etc., complete. This rate including cost of all materials, all labour charges, watering, ranning other incidental charge etc complete as per SS and as directed by the Departmental officer in charge of the work. But excluding seigniorage charge.
Plain Cement Concrete (1:4:8) (cement: fine aggregate: Coarse aggregate) for foundations and under column footing bed using 162.0 kgs of cement, coarse aggregate 40mm size hard , machine crushed granite from approved quarry including cost and conveyance of all materials like cement, sand, coarse aggregate, water etc. to site, includingall materials and all charges for machine mixing, laying concrete in foundations and under drain bed, ramming in 15 cm layers finishing top surface to the required level curing etc., and complete for finished item of workas per SS and as directed by the departmental officer in charge of work.
Supply and placing of the M30 grade Design Mix Concrete corresponding to IS 456 using Concrete Mixer with 20mm size graded machine crushed hard granite metal (coarse aggregate) from approved quarry including cost and conveyance of all materials like cement, fine aggregate (sand) coarse aggregate, water etc., to site and including Seigniorage charges, sales & other taxes on all materials including all operational, incidental and labour charges such as weigh batching, machine mixing, laying concrete, curing etc.,complete but excluding cost of steel and its fabrication charges for finished item of work (APSS No. 402)with minimum cement content as per IS code from standard suppliers approved by the department including pumping, centering, shuttering, laying concrete, vibrating, lifting, delifting curing etc. complete but excluding cost of steel and its fabrication charges for finished item of work.But excluding seigniorage Charge.As follows
column footings
For columns
For Intermediate Braces
For Carriage Slab Beams
For Carriage Slab 0.30m thick
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying including sales and other taxes on all materials etc., complete for finished item of work as per ss and as directed by the departmental officer in charge of work in all floors.( APSS No.126)
Construction of R.C.C. railing of M 25 grade in cast-in-situ with 20 mm nominal size aggregate, true to line and grade, tolerance of vertical railing post not to exceed 1 in 500, centre-to-centre spacing between vertical posts not to exceed 2000 mm as per drawing and technical specifications Clauses 800, 900 and 1208.3 MORD including cost of necessary reinforcement etc.complete as per S.S and as dorected by the departmental officer in charge of work
Supply and erection of 3# of 29.84 KW (35 HP)VTPumpsets each with a duty of 80 LPS and a total head of 25m( Two working and one stand bye) for pumping Raw water from intake well to Aerator of Proposed WTP for intermediate requirement 2033
Supply and erection of 3# of 29.84 KW (35 HP)VTPumpsets each with a duty of 80 LPS and a total head of 25m( Two working and one stand bye) for pumping Raw water from intake well to Aerator of Proposed WTP for intermediate requirement 2033 Supply, delivery, erection and commissioning of reputed make Energy Efficiency as per BEE VT Pumpset Capable of Discharging 80 LPS and a total head of 25m , directly coupled by pin and rubber bush type couplings to a squirrel cage induction motor having a duty of suitable capacity, with standard CI construction with bronze impeller of reputed/standard make alongwith all pressure guages and vaccum guages siphon and cock including cost of base frame including cost and conveyance of all materials, errection and commissioning charges and dismantling the existing pumpsets carefully if any and all taxes, duties, labour and transportation charges to site and all other incidental and operational charges etc; complete including all taxes but excluding GST. Supply, delivery, errection and commissioning of Motors with a speed of 1500 RPM 50 Hz TEFC horizontal foot mounted squirrel cage induction motor of reputed standard make suitable to operate 440volts to suit above pump sets fitted on a common base plate including cost and conveyance of all materials including errection and commissioning charges and
dismantling the existing motors carefully if any and all taxes , duties, labour and transportation charges to site and all other incidental and operational chrages etc; complete including all taxes but excluding GST. Supply, delivery and errection of suitable capacity vaccum pumpsets with all necessary Electrical connections, GI pipe connections & other accessories for self priming with 100 % Stand bye including cost and conveyance of all materials, errection and commissioning charges and dismantling the existing pumpsets carefully if any and all taxes, duties, labour and transportation charges to site and all other incidental and operational charges etc; complete including all taxes but excluding GST. Supply and fixing of control Pannel Board with suitable capacity bus bar suitable to operate above 3 Nos Pump Sets. The accessories all are internally wired with necessary earthing terminations. The Panel Board is made of 16 guage MS sheet metal cubical/industrial indoor type and duty painted with 2 coats enamel paint with cost of material as follows. conveyance, all taxes, duties, labour charges and all other incidents etc; complete for finished item of work Soft Starter i.e; FCMA ( flux compensated magnetic amplifier) standard reputed make - 3 Nos) Suitable capacity MCCB for incoming supplystandard reputed make - 1 No
Supply and errection of suitable suction and delivery DI/MS pipes and connections upto manfold including heavy duty Sluice Valves on suction side per stipulations of water supply mannual and I.S.Codes Supply,delivery,errection and commissioning of suitable capacity vaccum pump to operate ablve pumpsets including connecting or pumpsets with required G.I Pipes, Specials and fixing in concrete bed etc; Supply, laying and fixing of 40x6mm G.I flat patti double earthing for electrical protection for motor, pump and panel board efficiently earthing duly providing earth pits and filling with coal and salt and G.I pipe 1 1/2 x 6" long and bottom 2'x2' G.I.Plate welded as per I.E.Rules and Specifications with cost of materialss, conveyance, taxes,duties, labour charges and all other incidental charges and providing 1 1/2' x 1 1/2' earth pit chamber with brick masonary with top cover Supply and delivery of necessary suitable errection tools of reputed make mounted on polished teak wood board including cost of materials and all taxes and duties etc; Ring Spanner 3/16 to 1" - 1No Double end spanner set 3/16" to 1" - 1 No Pipe Wrench 18" & 4" - 2Nos Screw drivers 6", 10" & 12" - 3 Nos
Cutting Plier 12" - 1No 2 Kgs Hammer with Handle - 1 No Nose Plier - 1 No Flat and Half round smooth file - 2 Nos Adjustable Spanner 6" Column pipe Clamps - 2 pairs Line Shaft Clamps - 1 Pair Line rope and clamps double the weight of pump - 2 sets Gland thghtening Spanner - 1 No Spitter removing Spanner - 1 No Supply and delivery of necessary safety equipments as per IE Rules including cost of materials and all taxes and duties etc; complete Fire extiguisher 3Kg capacity - 2 Nos Rubber Mat 6" x 4" - 2Nos Fire Buckets with stand and three buckets - 1 No Rubber Hand Gloves - 1 Sets Danger Board Plates - 4 Nos First aid kit with chart - 1No Shock Treatment Chart - 1No Portable rechargeble torch light - 1 No Supply and delivery of indigeneous make 500V insulation tested a portable type technometer and megger etc;
Supply, delivery and erection of 5 tonnes capacity double girder gantry arrangements to move and lift the installations of the pump house one way with required MS ISMB of best quality 250 x 100 mm of standard make, including the required MS ISMC, MS angular iron, 5 tonne capacity travelling trolley and 5 tonne capacity chain pulley block with chains of suitable capacity for lifting and moving arrangements to length of 10.00 m rate is inclusive of the cost of materials, labour charges, site welding etc., All Civil Works Such as anchor Blocks ,Thrust Blocks, Platform for Pannel Board and Cable trench etc Complete as directed by the Field Engineer Testing and maintanance of the complete equipment covered and trial run for 30 days at 8 hours per day after completion of errection . This rate including cost of all labour charges incidental charges etc.complete as per IE rule and as directed by the departmental officer in charge of work Supply, delivery and erection of VFD Control Panels for Pump sets with the following specifications as below and the charges including all cost, convayance, tools, tackles, labor etc., complete and excluding cost of GST and as per the SS and as directed by the department officer.
Errection of 630 KVA Transformer at Head water works with Transformer yard 15.00x12.00m
Supply and erection of 7.50m long double pole structure fabricated with 150x75mm RS Joists,100x50mm MS channels, iron cross armstor fuse set and Lighting arrestrors etc.,including one coat of red oxide primer and two coats of bright Supply as per IE Rules and as directed by the departmental officer incharge of work.
Supply and fixing of 11 KV ,400 A 3 phase central post rotating double break type AB switch(isolator) as per IS 9921) without earth blade, gang operated, Horizontal type, operating mechanism with GI spring loaded reverse loop type fixed contact, solid HD electrolytic copper tubular moving contact with silver/Nickel plated at end points,9 Nos post insulators of 12 KV (IS 2594 and IS 5350) ,Hot Dip galvanizing hardware, GI pipe, Nuts and bolts etc., complete., as per IE Rules and as directed by the departmental officer incharge of work.
Supply and fixing of 100 A 11 KV Horn Gap fuse set as per IS 9385 on existing DP structure with 6 no of 24 KV /22 KV post Insulators (IS 5350, Hot dipped Hardware, fuse wire of required size etc., complete as per IE Rules and as directed by the departmental officer incharge of work.
Supply and fixing of distribution type lightning arrester 11 KV 5 kA as per IS 3070 with mounting base on the existing DP structure as per IE Rules and as directed by the departmental officer incharge of work.
Supply and erection of 11KV Strain disc. Insulators with GI pins and top clamps as per IE Rules and as directed by the departmental officer incharge of work.
Supply and fixing of 11 KV pin Insulator (IS 731/1971) with minimum creepage distance of 300 mm on existing cross arm including all accessories like Hot dip GI spindle and nuts etc., as per IE Rules and as directed by the departmental officer incharge of work.
Providing jumper connections with I/O' SWG HDBC wire between the 11 KV equipment on the outdoor structures as per IE Rules and as directed by the departmental officer incharge of work.
Supply and erection of GI stay set of dia 16mm,1.8 mtr long stay rod and anchor plate 380mmx380mmx6.4mm. including stay clamps, turn buckle and GI stay wire tight end through strain insulator including excavation of pit and cc work etc., complete as per IE Rules and as directed by the departmental officer incharge of work.
Providing efficient earthing arrangement forthe DP structure lighting arresters and the HV equipment. Transformer body and neutral etc., with 25 x 3 mm copper flats and connecting them to the Earth Electrodes fabricated and buried accroding to standard specifications as per IE Rules and other incidental charges etc., complete as directed by the departmental officer incharge of work.and as per the details given below:
A) Earth Electrodes
B) 20mm x 3mm Copper Flat(0.529Kgs/1Mtr) MAT 04146
C) Epoxy insulators
D) No.'8' SWG Copper wire. MAT 04141
Supply and Transportation of ISI marked copper wound Transformers 11/0.433 KV, Three Phase, 50 Hz, DYN 11, ONAN type , Standard accessories, winding temperature rise of 45°C/40°C first fill oil, having permissible total loss values not exceeding 7.5%of the maximum total loss values for 11 KV as per Energy Efficiency Level - 2 at basic Insulation level conforming to ISS 2026 (Part- I to Part - II), latest ammended and IS 1180 Part-I : 2014 described as above with Cable box on HV side and Bus duct on LV Side , ON load Tap changer(OLTC)+10% to -10%, with RTCC etc., with initial filling of oil as per IS 335-1993 complete and as per the following continuous rating.This rate including cost of transformer, other required items and as directed by the departmental officer incharge of work for the following items. Makes : As per list of recommended brands as category I. MAT-08780a 630KVA 1. Quantity : 1 2. Rated KVA : 630 KVA 3. Service & Location: Continuous Outdoor Distribution Transformer 4. Mounting : Plinth. 5. Wound : Copper Double wound 6. Type : Core type oil immersed 7. Cooling : ONAN
7. Cooling : ONAN 8. Temp Rise : 40⁰C in oil 45⁰C by resistance 9. Vector Group: Dyn 11 10. Primary Connection : Delta 11. Nominal Voltage / Current : ______ 12. Highest system Voltage: 12000V 13. Primary Frequency :50 HZ +/- 3% 14. Number of Phases : 3 15. Primary wires: 3 16. Secondary connection : Star 17. Secondary Volts / Current : 433V 18. Secondary phases : 3 19. Secondary wires: 4 20. Taps on primary winding for primary voltage variation : +5% to - 10% in steps of 2.5% of 7 position (6 Steps) 21. Terminal arrangement. a.HV: HT terminal box as per the site condition. b. LV: Cable box suitable to receive ------------Sq.mm XLPE cable 22. LV:One separate terminal for earthing. 23. Total Losses at 50% Loading [Watts] [Max] : 955 Wats 24. Total Losses at 100% Loading [Watts] [Max] : 2750 Wats 25. Percentage Impedance at 75 deg C AT 4.5 26. No load Current Less than 2% of full load Current
27. Standrad Fittings & Accessories. a. Rating and terminal marking plate: One b. Lifting Lugs:Two c. Off-circuit tap switch :One d. Earthing Terminals :Two e. Radiators ( Attachable) :Adequate f. Explosion vent with Diaphragm :One g. Conservator with Drain plug:one h. Oil filling hole with cap :One i. Oil level indicator : One j. Dehydrating Silicagel Breather : One k. Terminal Arrangement: HV With Treminal Box l. Terminal Arrangement : LV Cable Box m. Separate Neutral Bushing : One n. Filter valve with blanking plate : One o. Drain cum filter valve with blanking plate : One p. Air release device : One q. Thermometer Pocket : One r. Four :Unidirectional flat rollers s. One :10Cm dial thermometer(Rigid stem type)
Supply and laying of 400Sq mm X 3.5 core XLPE insulated, 1100V grade armoured aluminum cable as per specification confirming to IS:7098 (Part- I)./1554-I. This rate including cost of material and alabour charges, transporttion other incidental charges etc., complete as per IR Rules and as directed by the departmental officer incharge of work . Makes: Makes: Torent / Universal / Unicab / Havells / Finecab/ KEI / Gloster/ Polycab /RR Kabel/ Fortune Arrt ELEC-4.1.1q MAT-03431
LT panel
Supply Installation Testing and commissioning of free-standing floor mounted dust and vermin proof compartmentalized cubical panel made out of CRCA sheet, required hardware, cleaning with 7 tank process duly painted by two coats of zinc/red oxide primer followed by Powder coated / epoxy / PU painted with phosphatisation in grey or required shade after rinsing. The panel having PU/ Neoprene rubber gasket of not less than 3mm thickness, separate detachable, gland plate M.S. base channel, hinged door with locking arrangement for equipment/switchgear. The thickness of sheet shall not be less than 1.6mm up to 600mm length/ width of any compartment and be 2.0mm above 600mm. The load bearing structure shall be of 2.0mm thick sheet supported by base M.S. channel if required. Side walls and cable alley compartments having bolted type doors with detachable extension type structure (only outer area on all sides shall be measured and panel to be fabricated from CPRI approved fabricator) MAT 03976 This rate including cost of material and alabour charges, transporttion other incidental charges etc., complete as per IR Rules and as directed by the departmental officer incharge of work .
Supply and fixing of Electrolytic grade copper bus bar bus bar by means of SMC / DMC type insulator, high tensile nuts and bolts spring washers in existing panel including bending , cutting in required shape and size and colour coding with heat shrinkable PVC sleeves MAT 03978. This rate including cost of material and alabour charges, transporttion other incidental charges etc., complete as per IR Rules and as directed by the departmental officer incharge of work .
Incoming
a) 630A TPN SDFU for main switch. This rate including cost of material and alabour charges, transporttion other incidental charges etc., complete as per IR Rules and as directed by the departmental officer incharge of work . Makes:LauritzKnudsen(FormerlyL&T)/Schneider/ C&S/ ABB / SIEMENS MAT 02885
b) 630A 4pole change over switch. This rate including cost of material and alabour charges, transporttion other incidental charges etc., complete as per IR Rules and as directed by the departmental officer incharge of work . Makes:Socomec/LauritzKnudsen(FormerlyL&T)/HPL / Havells/ C&SMAT MAT 02898
c) Supply and fixing of (0-500) V range Voltmeter on existing panel, making connection by PVC insulated copper conductor with PVC sleeves /channel etc. as required Digital type. This rate including cost of material and alabour charges, transporttion other incidental charges etc., complete as per IR Rules and as directed by the departmental officer incharge of work . Make: Conzerve/Elmeasure/Meco/HPL/L&T/socomec MAT 03980
e). Supply and fixing of CT operated direct reading type Ammeter on existing panel, making connection by PVC insulated copper conductor with PVC sleeves / channel etc. as required. Digital type Below 500 A. This rate including cost of material and alabour charges, transporttion other incidental charges etc., complete as per IR Rules and as directed by the departmental officer incharge of work . Make: Conzerve/Elmeasure/Meco/HPL/L&T/Schneider/AE/Socomec MAT 03983
g).3RYB Phase indication lamps with leds Quotation This rate including cost of material and alabour charges, transporttion other incidental charges etc., complete as per IR Rules and as directed by the departmental officer incharge of work .
h).Supply and Fixing of Current Transformer, with all necessary support in existing panel including connection etc. as required from 200 / 5 to 400/5 Ratio, 10 VA, class 1 accuracy: This rate including cost of material and alabour charges, transporttion other incidental charges etc., complete as per IR Rules and as directed by the departmental officer incharge of work . Make: Kappa/L&T/Seimens/C&S/Schneider MAT 03986
Out-Going
630A TPN SDFU forCW pump house motors This rate including cost of material and alabour charges, transporttion other incidental charges etc., complete as per IR Rules and as directed by the departmental officer incharge of work . Makes:LauritzKnudsen(FormerlyL&T)/Schneider/ C&S/ ABB / SIEMENS MAT 02885
630A TPN SDFU for compressor/mechanical equipments. This rate including cost of material and alabour charges, transporttion other incidental charges etc., complete as per IR Rules and as directed by the departmental officer incharge of work . Makes:LauritzKnudsen(FormerlyL&T)/Schneider/ C&S/ ABB / SIEMENS MAT 02885
630A TPN SDFU for low lift sump Raw water motors This rate including cost of material and alabour charges, transporttion other incidental charges etc., complete as per IR Rules and as directed by the departmental officer incharge of work . Makes:LauritzKnudsen(FormerlyL&T)/Schneider/ C&S/ ABB / SIEMENS MAT 02885
630A TPN SDFU for Space . This rate including cost of material and alabour charges, transporttion other incidental charges etc., complete as per IR Rules and as directed by the departmental officer incharge of work . Makes:LauritzKnudsen(FormerlyL&T)/Schneider/ C&S/ ABB / SIEMENS MAT 02885
630A TPN SDFU for lighting section. This rate including cost of material and alabour charges, transporttion other incidental charges etc., complete as per IR Rules and as directed by the departmental officer incharge of work . Makes:LauritzKnudsen(FormerlyL&T)/Schneider/ C&S/ ABB / SIEMENS MAT 02885
630A 4pole change over switch for lighting section. This rate including cost of material and alabour charges, transporttion other incidental charges etc., complete as per IR Rules and as directed by the departmental officer incharge of work . Makes:Socomec/LauritzKnudsen(FormerlyL&T)/HPL / Havells/ C&SMAT MAT 02898
.KWH digital meter fro lighting section Quotation This rate including cost of material and alabour charges, transporttion other incidental charges etc., complete as per IR Rules and as directed by the departmental officer incharge of work .
Supply of 32 Amp………ISI marked TPN Switch Disconnector Fuse Unit, Cubical type without fuses as per IS: 13947/IEC 60947-3.This rate including cost of material and alabour charges, transporttion other incidental charges etc., complete as per IR Rules and as directed by the departmental officer incharge of work . Makes: As per list of recommended brands as category I.MAT-02879
Supply of 6A to 35 A……ISI marked HRC Fuse Links as per IS 13703-Part 2/IEC 60269- Part 2. This rate including cost of material and alabour charges, transporttion other incidental charges etc., complete as per IR Rules and as directed by the departmental officer incharge of work . Makes: As per list of recommended brands as category I MAT-02938
Standard duty Single phase 250 V / Three phase 440 V, 50 Hz capacitor (Bank) MAT-03998 This rate including cost of material and alabour charges, transporttion other incidental charges etc., complete as per IR Rules and as directed by the departmental officer incharge of work .
1000KV LT/Transformer Errection.testing Commensing and Supply of drawing layout plans of installed transformer in tracing cloth and duly get approved from electrical inspector APEPDCL and leaflets for various equipments and opearation manuals etc., complete.This rate including cost of material and alabour charges, transporttion other incidental charges etc., complete as per IR Rules and as directed by the departmental officer incharge of work .
Supply and Laying of 3C X 95 Sq mm XLPE insulated IS:7098/II/85 H.T. cable for working voltage 11 KV Earthed with Stranded Compacted Circular Aluminium Conductor Screened with Extruded Semi-conducting compound, XLPE Insulated Screened with extruded semi-conducting compound in combination with Copper Tape, cores laid up, inner sheath of Thermoplastic tape, galvanized flat steel strip armoured and overall Extruded PVC Type ST- 2 Outer Sheathed cable etc., complete.This rate including cost of material and alabour charges, transporttion other incidental charges etc., complete as per IR Rules and as directed by the departmental officer incharge of work . Make: Torrent / Universal / Unicab / Havells / KEI/Polycab/Gloster/RR Kabel/RPG MAT 03459
Transformer yard at HWW
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH as per SS and as directed by the departmental officer incharge of the work Note : Classifications of Earth Work Specification are as per 302.2.1(a) of MORD and 301.2.1 of MORT&H--ordinary soil--manual means upto 3m depth for foundations of buildings in restricted places By manual means For Column footings
Filling for River sand in foundation Column footing bed as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH etc., complete. This rate including cost of all materials, all labour charges, watering, ranning other incidental charge etc complete as per SS and as directed by the Departmental officer in charge of the work. But excluding seigniorage charge.
Plain Cement Concrete (1:4:8) (cement: fine aggregate: Coarse aggregate) for foundations and under Column footing bed using 162.0 kgs of cement, coarse aggregate 40mm size hard , machine crushed granite from approved quarry including cost and conveyance of all materials like cement, sand, coarse aggregate, water etc. to site, includingall materials and all charges for machine mixing, laying concrete in foundations and under drain bed, ramming in 15 cm layers finishing top surface to the required level curing etc., and complete for finished item of workas per SS and as directed by the departmental officer incharge of the work but excluding seigniorage charges
Supply and placing of the design mix concrete corresponding to IS -456 using WEIGH BATCHER/MIXER using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including seigniorage charges ,sales and other taxes on all materials including all operational ,incidental and labour charges such as weigh batching ,machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work (APSS NO 402) with minimum cement content as per IS Code from standard suppliers approved by the deparment including pumping , centering,shuttering,laying concrete, vibrating,curing etc M25 design mix concrete
column footings
Columns 1.20-0.10-0.10-0.30+1.80
Plinth beam 2(15+12)=54-gate3.00=51.00
Painting Walls with Snowcem or other equal and approved Water Proof Cement Paint 2 Coats (All Colours) over a base coat of aproved cement primer making 3 coats in total including cost of all , conveyance charges of materials and other incidental charges, scaffolding, lifting and other incidental charges as directed by the departmental officer in charge of work
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying including sales and other taxes on all materials etc., complete for finished item of work in all floors.( APSS No.126)
Supplying and fixing galvanised steel barbed wire (IS : 278-1962 Type I) weighing 9.38 Kg per 100 metres (min.), Straining and fixing to any type of standard, rails, straining bolts, including securing with and provision of galvanised mild steel wire, stapples or steel pins, etc., as directed (Posts and struts of wood, concrete, steel, etc.) and straining bolts shall be paid for separately).
Manufacture,supply,delivery of MS grill gates,window ornamental safety grill ,made with MS flats,MS angles,MS squares etc including welding, transportation to site finishing, applying red oxide paint as primary coat etc complete as per SS and as directed by the departmental officer in charge of work
Providind Synthic enamil paint two coats over the primery coat including cost of primer including cost and conveyance of all matrial and all labour charges etc complete as per ss and as directed by the departmental officer in charge of work
supply and filling the transformer yard with 40mm HBG metal m/c. This rate including cost of material, spreading charges, sectionng, other incidental charges etc., as directed by the departmental officer in charge of work
Providing 500mm dia. D.I. K9 Raw Water Pumping main from Intake well in Yerra Kalvuva Reservior to Aerator of WTP ( 100m MS pipe+600m DI K9 pipe))
Cutting and open of B.T. Road surface (as well as asphalt concrete upto 75mm thick) including water bound macadam . This rate including cost of hire of electrical and other incidental charge of work and all labour charges etc., Complete as per ss and as directed by the departmental stacking of excavated materials for lying of pipe lines as per the ditections of the departmental authorities. For Pipe line trenches.
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH as per SS and as directed by the departmental officer incharge of the work . For Pipe line trenches as follows.:
Mechanical Means up to 3 metres depth in ordinary soil
Manual means upto 3 metres depth in ordinary soils
Mechanical means up to 3 metres depth in ordinary rock not requiring blasting
Filling sand bedding in pipe line bed as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH etc., complete. This rate including cost of all materials, all labour charges, watering, ranning other incidental charge etc complete as per SS and as directed by the Departmental officer in charge of the work. But excluding seigniorage charge.
Supply and delivery of 500mm dia D.I K9 Socket and spigot centrigually cast (spun) Ductile Iron pressure pipes of K-9 Class confirming to specification No.IS 8329/2000 of standard lengths suitable for push-on joint (Rubber gasket D jointing) with cement lining inside the pipe, out side Zinc Coating including cost of Pipe, excluding GST and other duties. The rate including transportation and conveyance to work spot and stacking at site etc., complete as per S.S and as directed by the departmental authorities.
Supply and delivery of Centrifugally cast (spun) Ductile Iron fittings upto 500mm dia conforming to is:9523/2000 having dimentions as per table. The rate including zinc coated externally with inside mortar lining (with finishing as per class 13/is 9523/2000) including transportation, to site and other incidentl charges etc., complete as per S.S and as directed by the departmental authorities.
Supply and delivery of centrifugally cast (spun) Ductile Iron pressure pies with flanged (welded) ends for water, gas, sewage conforming to I.S.: 8329/2000 in standard working lengths of1,2,3, 4, 5 mts for classification K9 with cement mortar lining inside the pipes with outside zinc coating including transportation to site and other incidentl charges etc., complete as per S.S as follows:
500mm dia. 1.00m. Long for sluice and non return valves and flow meter
500mm dia. 2.00m. Long at intake well
Lowering of 500mm dia D.I K9 DI socket and spigot Pipes and fittings carefully in to the trench and laying them true to alignment and gradient including all labour charges, sundries as per BIS No. 3114/85 etc., complete as per S.S and as directed by the departmental authorities.
Jointing of 500mm dia D.I K9 D.I Pipes & fittings with Rubber Gasket including all sundries filling with water with a water lead up to 500m and testing to required pressure etc., complete as per BISNo.3114/85 and as directed by the departmental authorities.
Lowering D.I. Pipes of all classes and fittings with flanged ends carefully into the trenches and laying them true to alignment and gradient including all sundries,other incidental charges from source of supply as per BIS No.3114/94 other incidental charges.
Jointing the C.I. Pipes, fittings and valves with flanged ends including cost of jointing materials such as bolts, nuts, rubber insertion, white lead and including filling with water with a water lead upto 500 m and testing to required pressure etc., comp as per BIS No.3114/85 other incidental charges etc., complete
500mm dia.
150mm dia.
Manufacture, supply and delivery at work site 500mm dia internal dia M.S.Pipe fabricated with 10mm thick MS plates confirming to IS 2062-1992 of grade A manufactured as per IS 3589-2001 with cement lining in suitable lengths to suit the sit conditionse , in co-ordination with the concerned authorities as per approved drawings and directed by the Engineer-in –charge. This rate including cost of material and alabour charges, transporttion charges, hiring of machinary, welding charges and other incidental charges etc., complete as per IR Rules and as directed by the departmental officer incharge of work .
Supply and delivery of 500mm dia "Resilient Seated Soft Sealing" Gate Valves (Sluice Valves) with Bodyand Bonnet of Ductile Iron GGG-40/SG-400/15 or GGG-50/SG-500/7 or Equivalent as per IS1865, IS:3896-2 and Wedge fully Rubber Lined with food grade quality grade W270 grade EPDM, Replaceable Spindle Nut without gland packing with 3-O ring protection system on the Shaft and Seals of NBR. The Valves should be Vacuum tight and 100% leak proof with face to face dimensions as BS:5163 Type A/IS:14846. All the valves should be with fusion bonded Electrostatic Powder coating both inside and outside (Min 250 Microns)- RAL 5005 with Pocket Less Straight through body Passage conforming to Design standards of DIN- 3202F4/BS:5163 Type A Flange drilling as per IS - 1538 excluding all taxes, duties and per IS:1538 other incidental charges etc., complete as directed by the departmental officer incharge of work . PN16 including transportation PN 1.6
Supply & Delivery of 500mm dia Tamper Proof DI Flanged Single Chamber Air Release Valves with body & cover made of Ductile Iron Grade GGG-40/SG- 400/15 or GGG-50/SG-500/7 or Equivalent as per IS1865, IS:3896-2 with Food Grade Epoxy Powder Coating(EP-P) (Min:250 Micron) inside and Outside of Color Blue RAL 5005. All internal parts such as Float, shell, Cove Bolts etc. made of Austenitic alloy steel of SS AISI 304/316 and DN 50 float of and other components with ABS/ PTFE/ EPDM/ NBR and generally conforming to DIN/BIS/AWWA standards (or) combination Flange drilling as per IS - 1538 and other incidental charges etc., complete as directed by the departmental officer incharge of work .
Supply, Delivery of 500mm dia D.I Double Flanged Swing Check type Reflux valves (Non Return Valves) of following dia. conforming to IS- 5312 (Pts-1&2) (with amendments up to date, if any) having Body, Cover, Door, Bearing holder with D.I; Hinge pin, Door pin, Door suspension pin with Stainless Steel (IS 6603);Body seat ring , Door face ring, Bearing bushes, Plugs for hinge pin with Leaded Tin Bronze ( IS 318 ); Bolts, Nuts with Carbon steel; Gaskets with Rubber; Hinges with Cast steel; including transportation and other incidental charges as directed by the departmental officer incharge of work .
Labour charges for 500mm dia lowering and keeping in position of C.I./DI Sluice valves(with cap/with hand wheel), reflux valves and scour valves and flow meter and other incidental charges
Labour charges for 150mm dia fixing Kinetic Air Valves with isolating Sluice valves, Double Air valves/ Air Cushion valve excluding cost of jointing materials such as bolts, nuts and rubber insertions etc., complete. dia. of Air Valve and other incidental charges as directed by the departmental officer incharge of work .
Construction of R.C.C. thrust blocks using using VRCC M25 Gr. nominal mix using 20mm HBG metal from approved quarry including cost and conveyance of all materials at site, labour charges for machine mixing, laying, vibrating including centering charges but excluding cost of steel for reinforcement and its fabrication including curing etc., complete as directed by the departmental officer incharge of work .
Construction of Anchor blocks with P.C.C. M25 nominal mix using 20mm HBG crushed metal from approved quarry including cost and conveyance of all materials and all labour charges for machine mixing, laying, vibrating and curing including centering charges etc.,complete as per S.S and as directed by the departmental authorities.
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying including sales and other taxes on all materials etc., complete for finished item of work in all floors.( APSS No.126)
Construction of 500mm dia RCC Sluice Valve chambers suitable to the sluice valves including cost and conveyance of all materials and all labour charges, Cost of material, Earthwork excavation , sand bedding, VCC 1:4:8 , RCC Bed and side wll, RCC Slab duly providing suitable opening for operation of valves, cost of steel and other incidenal chagrges etc., complete., as per approved type design as approved by the department. etc.complete as per S.S finished item of work and as directed by the dpartmental office incharge of work.
Construction of 150mm dia RCC Air Valve chambers suitable to the Air Valve including cost and conveyance of all materials and all labour charges cost of steel and other incidenal chagrges etc., complete., as per approved type design as approved by the department. etc.complete as per S.S finished item of work and as directed by the dpartmental office incharge of work.
Collection ,supply and spreading of crusher stone dust from approved quarries for road restoration including compaction and watering etc., complete ramming, all labour charge and other incidental charges
Using Concrete mixture up to Plinth : Plain Cement concrete nominal mix M-30 (Cement : fine aggregate: coarse aggregate ) using 20mm size Hard Granite Machine Crushed Graded Metal including cost and conveyance of all materials like cement, sand, coarse aggregate water etc., to site , seigniorage charges on all materials, labour charges , for mixing , laying, concrete , ramming in 15 cm layers, finishing top surface to the required level curing etc., complete for finished item of work with nomonal reinforcement for Road restoration.M30 as directed by the dpartmental office incharge of work.
Manufacture, Supply and delivery of 500mm di MS. Dismantling Joints with both side flange end suitable for installation in between flange end pipes. Thickness as per IS: 7322. These rates are transportation charges, all labour charges, other incidental charges, cost of material as per SS and as directed by the dpartmental office incharge of work.
Construction of 13.00 MLD Rapid Gravity Filtration plant
Construction of 13.00 MLD Rapid Gravity Filtration plant Construction of Rapid Gravity Filtration Plant including all civil,mechanical and electrical works using sand as filter media, compatible with SCADA arrangements, duly following relavant IS codes in the design of plant components including trial running for 90 days etc., complete CivilWorks(All works of VRCC Shall be in M30 design mix) 1). Stilling Chamber and Areation cascade 2). Raw water channel with Stainless Steel Weir of SS304L Grade material and also with digital flow meters 3) Flash Mixer chamber with Flash mixing arrangements including SS shaft & SS Blades with gear wheel arrangements etc, Using 304L Grade Steel 4) Clariflucculator / Flocculation tanks with the components of central driven circular clarifier with scrapper & bridge arrangements made with Stainless Steel Grade 304 L tubes /angulars for durability & chemical resistant with wheel arrangements etc,. 5) Filter house, Chemical house, Alum store, Laboratory room , Chlorination plant room, toilet etc. (All structures shall be provided RCC roof only).Chemical house & Chlorinator rooms are to be isolated.
6) Wash water tank of suitable capacity shall be constructed at minimum clearance of 2.00m, above the roof slab of Filter beds / any other structure. Chlorine contact tank 7) All the Doors and Windows shall be of Best Teak wood/Aluminium /UPVC make, except entrance door. The entrance door including shutter in filter house shall be with best teak wood of size of 2.40 X 2.40 mts. a) Main Doors of the individual Buidings shall be made of Best Teak wood b) Other Internal Doors of the buildings shall be of Compreesed wood/Aluminium/ UPVC materials. c) Ventilators shall be provided for each building/structure of suitable size as per NBC statndards. 8) All pipes and valves in Plant shall be of D.I. materials. All theConnecting pipes of the plant coponents such as from Flash mixer to Clarifloculator/ Clarifier/Flocculation tank, to Filter beds, sludge disposal pipes shall be of D.I. material. The size of sludge disposal pipe shall be minimum of 450 mm dia with D.I D/F pipe. 8) All pipes and valves in Plant shall be of D.I. materials. All theConnecting pipes of the plant coponents such as from Flash mixer to Clarifloculator/ Clarifier/Flocculation tank, to Filter beds, sludge disposal pipes shall be of D.I. material. The size of sludge disposal pipe shall be minimum of 450 mm dia with D.I D/F pipe.
9) The Pipe gallery way for Clear water/ Back wash water/ pipe connections shall be suffuiciently spaced for easy operation & maintenance and inspection. 10)The bottom level of the wash water control chamber must be above G.Lso as to dispose the wash water and sludge from Clariflocculator by gravity to disposal point. Additional specificaions 11) Railing for all the components (Clarifloculator, Filter House, Staircas eetc,.) shall be provided with Stainless Steel of grade 304 for a height of 1.00m, with 40mm dia pipe for top horizotals,25mm dia for middle row and 40mm dia verticals spaced at interval of not more than 1.00m c/c. 12) Inspection / Path ways in filter beds : Middle pathway: Minimum of 1.50m,Side pathway: Minimum of 1.20m 13) Flooring in the buildings (Filter house, Chemical House, Chlorinator Room, Laboratory) shall be provided with Non-skid tiles of approved make 14 ) The basement of Filtriatiion plant building shall be minimum of 1.20m above the existing nearby Road top level. 15) Minimum head room of 2.00m shall be provided , at the alum mixing chambers in alum store for inspection & maintenance 16) The minimum width of entrance hall for the Filter House shall be 4.50m and Laboratory, of min size .of 3.30 X 4.50m.
17) High efficient Air Blowers shall be installed to the design requirement with low noise pollution , environmental pollution as per PCB guide lines &Testing of blowers as per I.S norms at site. 18) UPVC pipes shall be provided for water drain.Filter pipe manifolds shall be assembled with HDPE pipes 19) Alum storage capacity shall be designed for minimum period of 90 days. Consumables shall be provided for 2115 Running Hours of WTP. 22) Chlorinator : Vacuum type chlorinator shall be provided with following specifications: a) Vacuum operated solution feeding type Vacuum Regulator, Rotameter, Rate setting Valve, built-in NRV, Gas Overflow out let by man folding to mount the system with the unit. b) The unit shall consist of Ejector with necessary accessories such as Check Valve, Drain Valve and Vacuum relief Valves - for control of chlorinator dosage. c) The Accessories and manifolds shall be chlorine resistant and made of carbon steel seam less pipes, copper tube with brass fittings of suitable size & dimensions, with diaphragm sealed chlorine pressure gauge arrangements b) The unit shall consists of Ejector with necessary accessories such as Check Valve, Drain Valve and Vacum relief Valves - for control of chlorinator dosage. c) The Accessories and manifolds shall be chlorine resistant and made of corbon steel seam less pipes, copper tube with brass fittings of suitable size & dimensions, with diaphram sealed chlorine pressure gauge arrangements
d) Water Booster Pump of pumping capacity ranging from 2 cum/hr to 12 cum/hr, with Head ranging from 16 to 35 m e) The water & solution carrying pipes shall be made of UPVC material of suitable size incl. all specials such as Tee's , Bends, couplings & NRVs and also Pressure Gauges of suitable range. f) Chlorine Gas Leak detector with alarm indicator. The installation includes all necessary accessories, civil and mechanical works, manifold header installations, injector fixing, connection with UPVC pipes, solution piping’s, fixing of motors as per standard specifications and commissioning of Chlorination Plant to the required demand, with a defect liability period of 1 year. The chlorinator of may be of any reputed make or any make of Metito/Toshocow-Jesco Siemens Industrial Devices. g) Life breathing apparatus. f) Chlorine Gas detector with alarm indicator. The installation includes all necessary accssories, civil and mechanical works,manifold header installations, injector fixing, connection with UPVC pipes, solution pipings, fixing of motors as per standard speicfications and commissioning of Cholirnation Plant to the required demand, with a deffect liability period of 1 year. The cholrinator of may be of any reupted make or any make of Metito/Toshocow-Jesco/ Industrial devices. g)Life breathing operators. h)Chlorine escape BA Set. i) 2 to 10 MLD Plants - 1Kg/hr Chlorinator for Post Chlorination
ii) 10 MLD to 20 MLD Plants - 2 Kg/hr Chlorinator for Post Chlorination iii) 20 MLD to 50 MLD Plants - 5 Kg/hr Chlorinator for Post Chlorination Mechnical Equipment 1) Alum dosing equipment with SS 304 material made stirrers & paddles for chemical resistance. (Alam tanks must be bound with corrosion resistant material (HDPE Lining, Bitumen Coating, tiles etc) 2) Flash mixer equipment with SS 304 material made stirrers & paddles for chemical resistance 3) Filtration plant euqipment instrumentation and piping 4) Clarifloccualation equipment (with stainless steel blades) with rotating bridge arrangeemnt etc., 5) Pneumatic tyre wheel shall be provided for the bridge clariflocculator 6) Wash water tank fittings and pumpsets with 100% stand by. 7)Air blower with motor 100% stand by and pipe connections made with of SS Pipes Confirming to SS304 Grade, in filter bed region. 8)Spares & Tools for 2 years 9) Gaseous Chlorination with cylinders has to provided with protection measures. Electrical Equipment 1)Necessary power supply wiring to motors and switches bus bar connections as per I.E. Rules 2)Internal wiring and illumination and fittings and fixtures for internal and external lighting exhaust fans, ceiling fans etc.
3) Erecting mechanical & Electrical equipment, trial run for 90 days 23.50 hours per day testing the treated water for efficient standards and maintenance of records and imparting training to staff. 4)Supply of 6 - sets of completion plans and maintenance manual and brochures 5) All cables shall be with of copper material, Cable ducts shall be covered with MS / Aluminum chequed plate. 6) Min LUX levels inside the treatment plant shall be maintained 7) Yard lighting shall be provided as per norms Automation for flow measurements 1) Equipment for Flow of Conductivity, Turbidity, Ph value, Residual Chlorine with recording & data storage facility (Computer based) & Alarm by SMS or other methods 2) Off - Site Supervisory and Data Acquisition (OSSADA) system for Raw water & Clear water flows by installing Digital Flow meters to measure the flows at Raw water Channel and at each filter bed individually and combined for measuring the quantities of water treated with a facility to record and store the readings & also to send messages to the assigned designatories about the variations/ defficiencies in the flow including alerts for back wash requirements of filter beds, and recovery of data for the past 360 days.
All the Digital Flow Meters & Pressure Gauges shall be provided of standard approved make. The equipment shall have the following specifications, but not limited to: Hardware: i) Wall mounted Sensor House for measuring Raw water & Clear water flow from Filter bed out lets with accessories consists of ii)Electrode Type: General type, Scraper type or replaceable type Electorde made with material of SS external Ultra Touch Sensors as per requirement iii)Customised Application Requirement : Sensors with Interface logic control board with serial interfaces, including accessories such as Add-on port, external DC Power Socket, On - sensor Board Buffer, Timer, RS485 Communication, Analog to Digital Sensing Sensor Circuit, 32 Sensors Sensing Tags, Interval Power Supply System , LCD 16c/2L, Filter Bed Working Status Indication LED, Filter Bed Wash Indication Button and memory of Data Storage for 30Days , status of Filter Bed Level indicator,Rating, Reading on LCB Display, Menu Driven Data for sending to Onsite Big Display, operated with Battery Power of any reputed make or any equalent make. iv)Customised Application Requirement: Power Sensors Interface logic control board with support 8 Power Sensing tags, Central System Interfacing Communication,
On - board analog to Digit Convert Integrate Circuit of any reputed make or any equalent make. v)Customised Application Requirement: Centralized System with two serial interfaces, 3 Nos of Add-On ports, One external DC Power Socket,On - Board Buffer, On - Board Timer, On - Board RS485 Communication,On - Board RS 232 Communication, On - Board GPRS/GSM Module, On -Board Voice Chip, On - Board Power Sensing Module, LCD 16c/2L, Filter Bed Wash Precaution Indication with Stop Button, Memory of Data Storage for 30 Days, Total Bed Rating, Reading display on LCD Display, Menu Driven, Menu Navigate Keypad, sendind data to the Web Server,Communication with GPRS , operated with Battery Power of any reputed make or any equalent make The software shall be designed with Web Domain with Data Base Server and Web Name as per the directions of the Departmental Authorities The application of Software for Web design & Desktop shall meet the following requirements: Onsite Display: Letters with size of 1.5’ seven Sigment LED Display with Interface for each Filter Bed, for Onsite Display, by displaying the Bed Leves, Ratings, Readings in 3 Columns , for each bed of the plant in succesive rows and cumulative results at the bottom of the screen Off Site Display: Letters with size of 1.5’ seven Sigment LED Display with Interface GPRS/GSM Modules Offsite Display, with Display of Bed Total Rating, Total Cumulative Reading as specified on On-site Display Features
The system shall have also the features of Onsite Bed Wash Voice Precautions for Bed Levels, Readings, Ratings, Bed Capacity Readings and Ratings and Bed Low Level Triggering, before & after Bed wash. The software shall also have the features of sending messages to the mobiles of the Departmental designatories indicating Bed Low Levels,Power Supply timings, Bed Wash timings and its status, Power Supply timings and its status Grid View Table, Motor Working time and its status Grid View Table, all trigger events and schedule information and including all Snap View Reports, all Daily, Monthly, Yearly Reports, all Power Working Reports, all Power Events Information etc,, and other incidental charges etc., complete as per SS and as directed by the departmental officer incharge of work .
Centrifugally cast(spun) Ductile iron pressure pipes with flanges welded ends for water gas,sewage confirming to IS 8329/2000 in standard lengths of 1,2,3,4,5m for clasification K9 with cement mortor lining inside the pipes with out side zinc coating ,rates are ex factory including transportation and other incidental charges etc., complete as per SS and as directed by the departmental officer incharge of work as follows:
400 mm dia DI 2.00 m Long DF pipes from WTP to clear water sump
400mm dia1.00 mtr long 1.00 length vertical from WTP
Supply, delivery of 400mm dia D.I. fittings confirming to I.S.No.9523/2000 having dimensions as per table with Zinc coated externally and inside Cement Mortar lining (With finishing as per Class 13/IS 9523/2000) including cost of fittings, transportation, stacking carefully at site. The rate including VAT and other duties etc.,complete as per S.S. and as directed by the departmental authorities.
Manufacture, Supply and delivery of 400mm dia DI D/F Gate Valves (Soft Seated) Resilient seated soft sealing gate valves (Sluice valves) with body bonnet of ductile cast iron of grade GGG40/ SG 400/12 or equivalent grade as per I.S.3896-part2-1985 and subsequent revisions, wedge fully rubber lined with EPDM food grade quality and seals of NBR and the valves should be of vacuum tight and 100% leak proof with face to face dimensions as per BS5163-89/IS14846-2000/DIN 3202 F 4. All the valves should be with Electrostatic powder coating both inside and outside pocket less body passage. Drilled as per IS:1538. PN16 as per S.S. and as directed by the departmental officer incharge of the work.
Labour charges for 400mm dia lowering and keeping in position of C.I./DI Sluice valves(with cap/with hand wheel), reflux valves and scour valves as per IS:1538. PN16 as per S.S. and as directed by the departmental officer incharge of the work.
Lowering the 400mm da C.I. Pipes, D.I. Pipes of all classes and fittings with flanged ends carefully into the trenches and laying them true to alignment and gradient including all sundries, but excluding conveyance from source of supply as per BIS No.3114/94.PHE-LCIF-2
Jointing the 400mm dia C.I. Pipes, fittings and valves with flanged ends including cost of jointing materials such as bolts, nuts, rubber insertion, white lead and including filling with water with a water lead upto 500 m and testing to required pressure etc., comp as per BIS No.3114/85.
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH as per SS and as directed by the departmental officer incharge of the work for Valve chmber
Filling sand in foundation of Valve chamber trenches of drain bed as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH etc., complete. This rate including cost of all materials, all labour charges, watering, ranning other incidental charge etc complete as per SS and as directed by the Departmental officer in charge of the work. But excluding seigniorage charge.
Plain Cement Concrete (1:4:8) (cement: fine aggregate: Coarse aggregate) using coarse aggregate 40mm size hard, machine crushed granite from approved quarry using concrete Mixer 10 / 7 cft (0.2 / 0.8 cum) capacity including cost and conveyance of all materials like cement, sand, coarse aggregate, water etc. to site including all charges for machine mixing and hire charges of concrete mixer, laying concrete finishing top surface to the required level curing etc., and overheads & contractors profit etc complete for finished item of work as per SS and as directed by the departmental officer incharge of work. (APSS No. 402).
RCC M-20 Nominal mix (cement,fine aggregate,coarse aggregate) corresponding to Table -9 of IS -456 using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including seigniorage charges ,sales and other taxes on all materials including all operational ,incidental and labour charges such as machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work,but including centering, shuttering and other incidental charges etc., complete as directed by the departmental officer incharge of work as follows:
For Bottom Slab of Valve Chmaber
For Side walls allround of Valve Chmaber
RCC M-20 Nominal mix (cement,fine aggregate,coarse aggregate) corresponding to Table -9 of IS -456 using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including seigniorage charges ,sales and other taxes on all materials including all operational ,incidental and labour charges such as machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work,but including centering, shuttering for cover slabs
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 500/500D grade) of different diameters for RCC works, including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying including and other all materials etc., complete for finished item of work in all floors. as per SS and as directed by the departmental office incharge of work.
Construction 14.50m dia m dia (396.62 KL) clear water sump at WTP
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH as per SS and as directed by the departmental officer incharge of the work Note : Classifications of Earth Work Specification are as per 302.2.1(a) of MORD and 301.2.1 of MORT&H--ordinary soil-- upto 3m depth as follows:
for clear water sump foundations 0-3.00m Machanical means
for clear water sump foundations 3.00-6.00m Machanical means
Filling sand in foundation trenches of drain bed as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH etc., complete. This rate including cost of all materials, all labour charges, watering, ranning other incidental charge etc complete as per SS and as directed by the Departmental officer in charge of the work. But excluding seigniorage charge.
Plain Cement Concrete (1:4:8) (cement: fine aggregate: Coarse aggregate) for foundations and under drain bed using 162.0 kgs of cement, coarse aggregate 40mm size hard , machine crushed granite from approved quarry including cost and conveyance of all materials like cement, sand, coarse aggregate, water etc. to site, includingall materials and all charges for machine mixing, laying concrete in foundations and under drain bed, ramming in 15 cm layers finishing top surface to the required level curing etc., and complete for finished item of workas per SS and as directed by the departmental officer incharge of the work but excluding seigniorage charges
Supply and placing of the M30 grade Design Mix Concrete corresponding to IS 456 using Concrete Mixer with 20mm size graded machine crushed hard granite metal (coarse aggregate) from approved quarry including cost and conveyance of all materials like cement, fine aggregate (sand) coarse aggregate, water etc., to site and including Seigniorage charges, sales & other taxes on all materials including all operational, incidental and labour charges such as weigh batching, machine mixing, laying concrete, curing etc.,complete (APSS No. 402)with minimum cement content as per IS code from standard suppliers approved by the department including pumping, centering, shuttering, laying concrete, vibrating, curing etc. complete but excluding cost of steel and its fabrication charges for finished item of work.But excluding seigniorage Charges.
For side walls circular 0.30m thick below GL
For side walls circular 0.30m thick above GL
Columns 0.30 x 0.30m 3.60-0.30
Roof beams
Roof slab 0.15m thick 0.786x(15.10^2-6.00^2)
Roof dome slab 0.15m thick
Providing impervious coat to exposed RCC roof slab surface with CM(1:3), 20mm thick with 1kg of water proof compound per bag of cement laid over roof when it is green including cost of all materials, seigniorage charges, excluding conveyance charges of materials and including all operational, incidental and labour charges for mixing mortar, laying, rendering smooth and thread lining, curing, rounding off junctions of wall and slab etc,, complete for finished item of work
Providing Painting walls with snowcern or equivalent paint two coats by using approved water proof paint grade-1 over one coat prime coat by using cement primary coat by using cement primer making 3 coats including cost of Colour washing two coats Using snowcem including cost cost of material and all bour charges, transporttion other incidental charges etc., complete as directed by the departmental officer incharge of work .
Supply and delivery and fixing in position M S grill of any design including all fabrication and all fixing charges etc compalete as per ss and as directed by the dept authorities
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying including sales and other taxes on all materials etc., complete for finished item of work in all floors.( APSS No.126)
Construction of R.C.C. railing of M 25 grade in cast-in-situ with 20 mm nominal size aggregate, true to line and grade, tolerance of vertical railing post not to exceed 1 in 500, centre-to-centre spacing between vertical posts not to exceed 2000 mm as per drawing and technical specifications Clauses 800, 900 and 1208.3 MORD as per approved design by the department and as per direction of the deparment.
Construction of 10.50x7.50m pump house for clear water pumps and motors at proposed WTP
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH Note : Classifications of Earth Work Specification are as per 302.2.1(a) of MORD and 301.2.1 of MORT&H--ordinary soil--manual means upto 3m depth for foundations of buildings in restricted places By manual means as follows:
Mechanical Means up to 3 metres depth in ordinary soil
Manual Means up to 3 metres depth in ordinary soil
Filling in foundation trenches as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH-sand filling. This rate including cost of material and all lbour charges, watering, ramming and other incidental charges etc., complete as directed by the departmental officer incharge of work .
Providing PCC 1:4:8 using 40 mm graded SS 5 HBG m/c metal and OPC coarse and fine aggregate confirming to IS 383 including cost and conveyance of all materials and labour charges, machine mixing , vibration,laying in position, curing etc., complete This rate including cost of material and all lbour charges, watering, ramming and other incidental charges etc., complete as directed by the departmental officer incharge of work .
Providing PCC 1:3:6 using 40 mm graded SS 5 HBG m/c metal and OPC coarse and fine aggregate confirming to IS 383 including cost and conveyance of all materials and labour charges, machine mixing , vibration,laying in position, curing etc., complete This rate including cost of material and all lbour charges, watering, ramming and other incidental charges etc., complete as directed by the departmental officer incharge of work .
Supply and placing of the M25 design mix concrete corresponding to IS -456 using WEIGH BATCHER/MIXER using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including seigniorage charges ,sales and other taxes on all materials including all operational ,incidental and labour charges such as weigh batching ,machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work (APSS NO 402) with minimum cement content as per IS Code from standard suppliers approved by the deparment including pumping , centering,shuttering,laying concrete ,vibrating,curing etc M25 design mix concrete as follows:
Column footings
Pedestals
Columns
Plinth beam 3.50-0.30
Lintel beams
Roof Beams
Roof slab 0.125m thick,
Sunshades 0.60m wide, 0.10m at fixed end and 0.05m at free end
Brick work in CM 1:6 mix using 2nd class bricks brought from approved kilns including cost and conveyance of all materials and all labour charges ,curing for 21 days and conveyance of maerials, all labour charges, scaffolding, watering etc complete as per ss and as directed by the departmental officer incharge of work .
Ground floor
1st floor Parapet wall 2(11.70+8.63)=40.66
Cement plastering using opc in cm(1:5) prop 12 mm thick including cost of material, labour ,curing etc and conveyance of maerials, all labour charges, scaffolding, watering etc complete as per ss and as directed by the departmental officer incharge of work. out side & inside
Ground floor
1st floor Parapet wall
Cement plastering using opc in cm(1:3) prop 12 mm thick including cost of material, labour ,curing and conveyance of maerials, all labour charges, scaffolding, watering etc complete as per ss and as directed by the departmental officer incharge of work for ceiling
Cement plastering using opc in cm(1:3) prop 20 mm thick including cost of material, labour ,curing etc.and conveyance of maerials, all labour charges, scaffolding, watering etc complete as per ss and as directed by the departmental officer incharge of work for flooring
Colour washing two coats using snowcem over the primery coat conveyance of all labour charges etc., and conveyance of maerials, all labour charges, scaffolding, watering etc complete as per ss and as directed by the departmental officer incharge of work (in and out side)
Supply & fixing of Rolling shutter made of 80 x 1.25 mm machine rolled CRCA laths, interlocked together through their entire length and jointed together at the ends by end-locks, mounted on specially designed pipe shaft of 50mm dia nominal bore MS B class pipe with brackets, plates, guide channels, stoppers, bottom locking plates and arrangements for inside & outside locking with push-pull operations including cost of hood cover and springs complete, painted with one coat of approved steel primer, locks, ball bearings, all accessories etc and conveyance of maerials, all labour charges, scaffolding and other ncidental charges etc complete as per ss and as directed by the departmental officer incharge of work. for finished item of work as per special spn: 1108
Supply and fixing Aluminium Anodised Two/ Three Track Sliding Windows of size 1.5m X 1.20m as per approved drawing with aluminium anodised sections of Series C Jindal sections and outer frame top horizontals & both verticals of 8774 of size 62 x 29.5 mm and bottom horizontal - two track frame of 8773 of size 62 x 29.5 mm, Shutter frame top, bottom and verticals of 8304 of size 50 mm x 20 mm and Weather interlocking frame of 8306 of size 50 x 20 with plain clear float glass 5 mm thick fixed including supply and fixing aluminium handles of 100 mm for each shutter, nylon rollers assembly and all labour charges for fixing the fixtures with required no.of screws, bolts and nuts and including labour charges for fixing the frame in position, fixing shutter to frame etc. completed for finished item of work
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying including sales and other taxes on all materials etc., complete for finished item of work in all floors.( APSS No.126)
Manufacture,supply,delivery of MS grill gates,window ornamental safety grill ,made with MS flats,MS angles,MS squares etc including welding,finishing,applying red oxide paint as primary coat etc complete
Providing Synthic enamil paint two coats over the primery coat excluding cost of one coat primer including cost and conveyance of all matrial and all labour charges etc complete as per ss and as directed by the departmental officer incharge of work .
Supply delivary and fixing RCC Jollys includnig cost and conveyance of all material and all labour charges for fixing etc complete as ss and as directed by the departmental officer incharge of work .
Supply, delivery and fixing of 110mm dia single socket PVC pipes 4 kg/sqcm prince/Sudhakar or any ISI brand for rain water pipes with clamps. This rate is including cost of material and all labour charges and other incidental charges etc., complete as per IE Rules and as directed by the departmental officer incharge of work .
Supply and fixing of 25 mm dia 2.00 mm thick PVC pipe concealed in roof slab with all required accessories including masonary work all labour chages. This rate is including cost of material and all labour charges and other incidental charges etc., complete as per IE Rules and as directed by the departmental officer incharge of work .
Supply and fixing of 20 mm dia 1.50 mm thick PVC pipe concealed in walls with all required accessories including masonary work for light , fan and plug point with metal deep box including all labour chages. This rate is including cost of material and all labour charges and other incidental charges etc., complete as per IE Rules and as directed by the departmental officer incharge of work .
Wiring with 2 runs 14/0.3 mm. (1.0. sq.mm) Fire retardant PVC insulated Flexible copper cable in existing pipe with 6A siwtch, ceiling rose and 3 mm thick hyla sheet covering to switch control box including all labour charges etc,., complete for light, bell , fan and exhaust fan points in non - residential building. This rate is including cost of material and all labour charges and other incidental charges etc., complete as per IE Rules and as directed by the departmental officer incharge of work .
Wiring with 2 runs 14/0.3 mm. (1.0. sq.mm) Fire retardant PVC insulated Flexible copper cable in existing pipe with 6A modular siwtch control and 3/2 pin sockets fixing on board including all labour charges. This rate is including cost of material and all labour charges and other incidental charges etc., complete as per IE Rules and as directed by the departmental officer incharge of work .
supply and run of 2 of 36/0.3 mm. (1.5. sq.mm) Fire retardant PVC insulated Flexible copper cable in existing pipe for mains including all labour charges. This rate is including cost of material and all labour charges and other incidental charges etc., complete as per IE Rules and as directed by the departmental officer incharge of work .
supply and run of 1 of 14/0.3 mm. (1.0. sq.mm) Fire retardant PVC insulated Flexible copper cable in existing pipe for earth continuity including all labour charges etc. This rate is including cost of material and all labour charges and other incidental charges etc., complete as per IE Rules and as directed by the departmental officer incharge of work .
supply and run of 2 of 6 sq.mm (7/18) WPSC alluminium cable along with No.10 SWG G.I barer wire through PVC cleats with all accessories including all labour charges etc.,This rate is including cost of material and all labour charges and other incidental charges etc., complete as per IE Rules and as directed by the departmental officer incharge of work .
Providing independent earthing by excavating a trench to a depth of 2.10m in all soils, as per size specied in data ,using 40 mm dia B class GI pipe 2.50m long with necessary accessories with hume pipe ring duly providing staggered holes including filling with equal proportion of salt and charcoal in layers and all labour charges etc complete. This rate is including cost of material and all labour charges and other incidental charges etc., complete as per IE Rules and as directed by the departmental officer incharge of work .
S&F of SPN distrubution board with IP 42 protection (metal door) suitable for 3 phase ELCB-RCCB-FP isolator as incomer and 10 KA SP MCBS as out going including internal connection and labour charges for surface-flush mounting etc -- 63 A FP isolator-1 no for incomer,6-32A SP MCBS -18 Nos for out going. This rate is including cost of material and all labour charges and other incidental charges etc., complete as per IE Rules and as directed by the departmental officer incharge of work .
Supply and fixing of 48" (1200mm) Sweep Ceiling Fan with double ball bearings, air delivery more than 00 cubic meter/min but without Regulator.Makes: Crompton HS Plus/ Havells ES Neo/ Orient/ Energy Star/Halonix(Zephyr)/ Polycab(ynergy Star) unit each complete as per IE Rules and as directed by the departmental officer incharge of work.
Supply of stepped type Electronic Regulator of makes GM G Home / Gold Medal Olive / Million Zoom / Anchor Penta Cherry / Great white Omega as per IE Rules and as directed by the departmental officer incharge of work.
Supply of 9" (225mm), Light duty exhaust fan with double ball bearing and wire guard etc complete. Makes: Crompton / Bajaj Bahar WG / Havells Ventil Air-DS / Orient hill air / MIIT as per IE Rules and as directed by the departmental officer incharge of work.
Supply and transportation of 20W, 2000 lumens, T8,1200mm length LED retro tube light,wide operating voltage with double side connection, PF≥0.9,Surge protection: > 2KV, THD<15%, with inbuilt driver and frosted cover CCT: 3000K - 6500K as desired by the department and as per IS specifications, minimum CRI≥80,.etc complete with 5 years warranty.LUMINAIRE MAKE: Phillips / OSRAM / GE / Crompton /VIN / Bajaj / Havells / Halonix / HPL. LED MAKE : PHILIPS LUMILEDS / CREE / NICHIA /OSRAM / SAMSUNG / LG LEDs. as per IE Rules and as directed by the departmental officer incharge of work.
Labour charges for Fixing of Ceiling fan and regulator including transportation and giving connections with twin core wire etc., complete as per IE Rules and as directed by the departmental officer incharge of work.
Labour charges for fixing of Exhaust fan in wall with necessary connections and masonary work of making hole, finishing etc., complete as per IE Rules and as directed by the departmental officer incharge of work.
Labour charges Fixing of 40W tube light luminaire on wall / Ceiling with / TW round blocks with all accessories including giving connections and all labour charges etc., complete. as per IE Rules and as directed by the departmental officer incharge of work.
Supply, delivery and erection of 3 tonnes capacity double girder gantry arrangements to move and lift the installations of the pump house one way with required MS ISMB of best quality 250 x 100 mm of standard make, including the required MS ISMC, MS angular iron, 5 tonne capacity travelling trolley and 5 tonne capacity chain pulley block with chains of suitable capacity for lifting and moving arrangements to length of 10.00 m rate is inclusive of the cost of materials, labour charges, site welding etc.,
Construction of 10.50x7.50m pump house for clear water pumps and motors at proposed intermediate sump
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH Note : Classifications of Earth Work Specification are as per 302.2.1(a) of MORD and 301.2.1 of MORT&H--ordinary soil--manual means upto 3m depth for foundations of buildings in restricted places By manual means as follows
Mechanical Means up to 3 metres depth in ordinary soil
Manual Means up to 3 metres depth in ordinary soil
Filling Sand for foundation for pump house as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH.This rate including cost of sand ,filling charges,watering,ramming,and other incidental charges etc., complete as per ss and directed by the departmental officer incharge of work
Providing PCC 1:4:8 using 40 mm graded SS 5 HBG m/c metal and OPC coarse and fine aggregate confirming to IS 383 including cost and conveyance of all materials and labour charges, machine mixing , vibration,laying in position, curing etc., complete as directed by the departmental officer incharge of work .
Providing PCC 1:3:6 using 40 mm graded SS 5 HBG m/c metal and OPC coarse and fine aggregate confirming to IS 383 including cost and conveyance of all materials and labour charges, machine mixing , vibration,laying in position, curing etc., complete as directed by the departmental officer incharge of work .
Supply and placing of the design mix concrete corresponding to IS -456 using WEIGH BATCHER/MIXER using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site,sales and other taxes on all materials including all operational ,incidental and labour charges such as weigh batching ,machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work (APSS NO 402) with minimum cement content as per IS Code from standard suppliers approved by the deparment including pumping , centering,shuttering,laying concrete ,vibrating,curing etc M25 design mix concrete as follows:
Column footings
Pedestals
Columns
Plinth beam 3.50-0.30
For brakets (0.5+0.3)/2 =0.40
Roof Beams
Roof slab 0.125m thick,
Sunshades 0.60m wide, 0.10m at fixed end and 0.05m at free end
Brick work in CM 1:6 mix using 2nd class bricks brought from approved kilns including cost and conveyance of all materials and all labour charges ,curing for 21 days etc complete as per ss as directed by the departmental officer incharge of work .
Ground floor
1st floor Parapet wall 2(11.70+8.63)=40.66
Cement plastering using opc in cm(1:5) prop 12 mm thick including cost of all materials, conveyance charges of materials and all operational, incidental and labour charges etc., complete for finished item of work as per S.S out side & inside
Ground floor
1st floor Parapet wall
Cement plastering using opc in cm(1:3) prop 12 mm thick including cost of all materials, conveyance charges of materials and all operational, incidental and labour charges etc., complete for finished item of work as per S.S for ceiling
Cement plastering using opc in cm(1:3) prop 20 mm thick including cost of all materials, conveyance charges of materials and all operational, incidental and labour charges etc., complete for finished item of work as per S.S for flooring
Colour washing two coats using snowcem over the primery coat including cost of all materials, conveyance charges of materials and all operational, incidental and labour charges etc., complete for finished item of work as per S.S out side & inside
Supply & fixing of Rolling shutter made of 80 x 1.25 mm machine rolled CRCA laths, interlocked together through their entire length and jointed together at the ends by end-locks, mounted on specially designed pipe shaft of 50mm dia nominal bore MS B class pipe with brackets, plates, guide channels, stoppers, bottom locking plates and arrangements for inside & outside locking with push-pull operations including cost of hood cover and springs complete, painted with one coat of approved steel primer, locks, ball bearings, all accessories etc complete for finished item of work as per special spn: 1108
Supply and fixing Aluminium Anodised Two/ Three Track Sliding Windows of size 1.50m X 1.20m as per approved drawing with aluminium anodised sections of Series C Jindal sections and outer frame top horizontals & both verticals of 8774 of size 62 x 29.5 mm and bottom horizontal - two track frame of 8773 of size 62 x 29.5 mm, Shutter frame top, bottom and verticals of 8304 of size 50 mm x 20 mm and Weather interlocking frame of 8306 of size 50 x 20 with plain clear float glass 5 mm thick fixed including supply and fixing aluminium handles of 100 mm for each shutter, nylon rollers assembly and all labour charges for fixing the fixtures with required no.of screws, bolts and nuts and including labour charges for fixing the frame in position, fixing shutter to frame etc. completed for finished item of work
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying including sales and other taxes on all materials etc., complete for finished item of work in all floors.( APSS No.126)
Manufacture,supply,delivery of MS grill gates,window ornamental safety grill ,made with MS flats,MS angles,MS squares etc including welding,finishing,applying red oxide paint as primary coat etc complete
Providind Synthic enamil paint two coats over the primery coat including cost of primer including cost and conveyance of all matrial and all labour charges etc complete as per ss as directed by the departmental officer incharge of work .
Supply delivary and fixing RCC Jollys includnig cost and conveyance of all material and all labour charges for fixing etc complete as ss
Supply, delivery and fixing of 110mm dia single socket PVC pipes 4 kg/sqcm prince/Sudhakar or any ISI brand for rain water pipes with clamps as per IE Rules and as directed by the departmental officer incharge of work .
Supply and fixing of 25 mm dia 2.00 mm thick PVC pipe concealed in roof slab with all required accessories including masonary work all labour chages as per IE Rules and as directed by the departmental officer incharge of work .
Supply and fixing of 20 mm dia 1.50 mm thick PVC pipe concealed in walls with all required accessories including masonary work for light , fan and plug point with metal deep box including all labour chages as per IE Rules and as directed by the departmental officer incharge of work .
Wiring with 2 runs 14/0.3 mm. (1.0. sq.mm) Fire retardant PVC insulated Flexible copper cable in existing pipe with 6A siwtch, ceiling rose and 3 mm thick hyla sheet covering to switch control box including all labour charges etc,., complete for light, bell , fan and exhaust fan points in non - residential building as per IE Rules and as directed by the departmental officer incharge of work .
Wiring with 2 runs 14/0.3 mm. (1.0. sq.mm) Fire retardant PVC insulated Flexible copper cable in existing pipe with 6A modular siwtch control and 3/2 pin sockets fixing on board including all labour charges as per IE Rules and as directed by the departmental officer incharge of work .
supply and run of 2 of 36/0.3 mm. (1.5. sq.mm) Fire retardant PVC insulated Flexible copper cable in existing pipe for mains including all labour charges as per IE Rules and as directed by the departmental officer incharge of work .
supply and run of 1 of 14/0.3 mm. (1.0. sq.mm) Fire retardant PVC insulated Flexible copper cable in existing pipe for earth continuity including all labour charges etc. as per IE Rules and as directed by the departmental officer incharge of work .
supply and run of 2 of 6 sq.mm (7/18) WPSC alluminium cable along with No.10 SWG G.I barer wire through PVC cleats with all accessories including all labour charges etc.,as per IE Rules and as directed by the departmental officer incharge of work .
Providing independent earthing by excavating a trench to a depth of 2.10m in all soils, as per size specied in data ,using 40 mm dia B class GI pipe 2.50m long with necessary accessories with hume pipe ring duly providing staggered holes including filling with equal proportion of salt and charcoal in layers and all labour charges etc complete as per IE Rules and as directed by the departmental officer incharge of work .
S&F of SPN distrubution board with IP 42 protection (metal door) suitable for 3 phase ELCB-RCCB-FP isolator as incomer and 10 KA SP MCBS as out going including internal connection and labour charges for surface-flush mounting etc -- 63 A FP isolator-1 no for incomer,6-32A SP MCBS -18 Nos for out going as per IE Rules and as directed by the departmental officer incharge of work .
Supply of 48" (1200mm) Sweep 5 star rated Ceiling Fan , with double ball bearings, air delivery more than 200 cubic meter/min but without Regulator.Makes : Crompton HS Plus / Havells ES Neo/Orient Energy Star/ Halonix(Zephyr)/Polycab(Synergy Star) unit each complete as per IE Rules and as directed by the departmental officer incharge of work
Supply of stepped type Electronic Regulator of Makes: GM G Home / Gold Medal Olive / Million Zoom / Great white Omega/Koncept/Vimal opel/ Anchor/Vihan/CPL complete as per IE Rules and as directed by the departmental officer incharge of work
Supply of 9" (225mm), Light duty exhaust fan with double ball bearing and wire guard etc complete. Makes: Crompton / Bajaj Bahar WG / Havells Ventil Air-DS / Orient hill air / MIIT complete as per IE Rules and as directed by the departmental officer incharge of work
Supply and transportation of 20W, 2000 lumens, T8,1200mm length LED retro tube light,wide operating voltage with double side connection, PF≥0.9,Surge protection: > 2KV, THD<15%, with inbuilt driver and frosted cover CCT: 3000K - 6500K as desired by the department and as per IS specifications, minimum CRI≥80,.etc complete with 5 years warranty.LUMINAIRE MAKE: Phillips / OSRAM / GE / Crompton /VIN / Bajaj / Havells / Halonix / HPL. LED MAKE : PHILIPS LUMILEDS / CREE / NICHIA /OSRAM / SAMSUNG / LG LEDs.as per IE Rules and as directed by the departmental officer incharge of work
Labour charges for Fixing of Ceiling fan and regulator including transportation and giving connections with twin core wire etc., complete
Labour charges for fixing of Exhaust fan in wall with necessary connections and masonary work of making hole, finishing etc., complete
Labour charges Fixing of 40W tube light luminaire on wall / Ceiling with / TW round blocks with all accessories including giving connections and all labour charges etc., complete.
Supply ,Erection and Commissioning of Crane Gantry Girder of Capacity of 3.00 T including cost and conveyance of all material and all labour charges etc complete as per ISI and as directed by the dept . Including all taxes & Labour cess s follows:
Construction 11.00m dia m dia (285.32 KL) clear water intermediate sump
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH for foundations upto 3.00m depth Note : Classifications of Earth Work Specification are as per 302.2.1(a) of MORD and 301.2.1 of MORT&H--ordinary soil-- upto 3m depth
for clear water sump foundations 0-3.00m Machanical means
Mechanical Means 3 metres to 6 metres depth in ordinary soil
Manual means 3 metres to 6 metres depth in ordinary soil
Filling Sand in foundation trenches as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH . The rate including cost and conveyance of all material, labour charges for filling, watering, ramming, etc., complete as per SS and as directed by the departmental officer in charge of the work but excluding seigniroage charges.
Plain Cement concrete (1:4:8) using 40 mm metal with concrete mixer. All work upto plinth level including cost of all materials and labour charges etc., complete as per SS and as directed by the departmental officer in charge of the work but excluding seigniorage charges
Supply and placing of the design mix concrete corresponding to IS -456 using WEIGH BATCHER/MIXER using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including seigniorage charges ,sales and other taxes on all materials including all operational ,incidental and labour charges such as weigh batching ,machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work (APSS NO 402) with minimum cement content as per IS Code from standard suppliers approved by the deparment including pumping , centering,shuttering,laying concrete ,vibrating,curing etc M30 design mix concrete with concrete mixer as follows:
For side walls circular 0.30m thick below GL
For side walls circular 0.30m thick above GL
Columns 0.30 x 0.30m 3.60-0.30
Roof beams
Roof slab 0.15m thick 0.786x(11.60^2-5.00^2)
Roof dome slab 0.15m thick
Providing impervious coat to exposed RCC roof slab surface with CM(1:3), 20mm thick with 1kg of water proof compound per bag of cement laid over roof when it is green including cost of all materials, seigniorage charges, excluding conveyance charges of materials and including all operational, incidental and labour charges for mixing mortar, laying, rendering smooth and thread lining, curing, rounding off junctions of wall and slab etc,, complete for finished item of work
Colour washing two coats using snowcem over the primery coat conveyance of all labour charges etc., and conveyance of maerials, all labour charges, scaffolding, watering etc complete as per ss and as directed by the departmental officer incharge of work (in and out side)
Supply and delivery and fixing in position M S grill of any design including all fabrication and all fixing charges etc compalete as per ss and as directed by the departmental officer incharge of work .
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying including sales and other taxes on all materials etc., complete for finished item of work in all floors.( APSS No.126)
Construction of R.C.C. railing of M 25 grade in cast-in-situ with 20 mm nominal size aggregate, true to line and grade, tolerance of vertical railing post not to exceed 1 in 500, centre-to-centre spacing between vertical posts not to exceed 2000 mm as per drawing and technical specifications Clauses 800, 900 and 1208.3 MORD.as directed by the departmental officer incharge of work .
Errection of 3 # of 55.95 KW (80 HP)CF Pumpsets each with a duty of 80 LPS and a total head of 50.00 m( two working and one stand bye) for pumping clear water from clear water sump at Head water works to ELSRs at Junction near JRG Community hall(for filling intermediate sump at Uppalameta and ELSRs at Santha market and sai balaji layout for intermediate requirements 2033
Errection of 3 # of 55.95 KW (80 HP)CF Pumpsets each with a duty of 80 LPS and a total head of 50.00 m( two working and one stand bye) for pumping clear water from clear water sump at Head water works to ELSRs at Junction near JRG Community hall(for filling intermediate sump at Uppalameta and ELSRs at Santha market and sai balaji layout for intermediate requirements 2033 Supply, delivery, erection and commissioning of reputed make Energy Efficiency as per BEE Horizontal Split case Pumpset Capable of Discharging 80 LPS and a total head of 50m , directly coupled by pin and rubber bush type couplings to a squirrel cage induction motor having a duty of suitable capacity, with standard CI construction with bronze impeller of reputed/standard make alongwith all pressure guages and vaccum guages siphon and cock including cost of base frame including cost and conveyance of all materials, errection and commissioning charges and dismantling the existing pumpsets carefully if any and all taxes, duties, labour and transportation charges to site and all other incidental and operational charges etc; complete including all taxes but excluding GST.Supply, delivery, errection and commissioning of Motors with a speed of 1500 RPM 50 Hz TEFC
horizontal foot mounted squirrel cage induction motor of reputed standard make suitable to operate 440volts to suit above pump sets fitted on a common base plate including cost and conveyance of all materials including errection and commissioning charges and dismantling the existing motors carefully if any and all taxes , duties, labour and transportation charges to site and all other incidental and operational chrages etc; complete including all taxes but excluding GST. Supply, delivery and errection of suitable capacity vaccum pumpsets with all necessary Electrical connections, GI pipe connections & other accessories for self priming with 100 % Stand bye including cost and conveyance of all materials, errection and commissioning charges and dismantling the existing pumpsets carefully if any and all taxes, duties, labour and transportation charges to site and all other incidental and operational charges etc; complete including all taxes but excluding GST. Supply and fixing of control Pannel Board with suitable capacity bus bar suitable to operate above 3 Nos Pump Sets. The accessories all are internally wired with necessary earthing terminations. The Panel Board is made of 16 guage MS sheet metal cubical/industrial indoor type and duty painted with 2 coats enamel paint with cost of material as follows. conveyance, all taxes, duties, labour charges and all other incidents etc; complete for finished item of work
Out-going cable of suitable size of Alluminium armoured cable of 3.50core of standard make from Panel Board to Starter and to Motor Cable Joints with jointing materials such as lugs glands, adhesive taps etc; to join the above cables a per I.E Rules Supply and errection of suitable suction and delivery DI/MS pipes and connections upto manfold including heavy duty Sluice Valves on suction side per stipulations of water supply mannual and I.S.Codes Supply,delivery,errection and commissioning of suitable capacity vaccum pump to operate ablve pumpsets including connecting or pumpsets with required G.I Pipes, Specials and fixing in concrete bed etc; Supply, laying and fixing of 40x6mm G.I flat patti double earthing for electrical protection for motor, pump and panel board efficiently earthing duly providing earth pits and filling with coal and salt and G.I pipe 1 1/2 x 6" long and bottom 2'x2' G.I.Plate welded as per I.E.Rules and Specifications with cost of materialss, conveyance, taxes,duties, labour charges and all other incidental charges and providing 1 1/2' x 1 1/2' earth pit chamber with brick masonary with top cover Supply and delivery of necessary suitable errection tools of reputed make mounted on polished teak wood board including cost of materials and all taxes and duties etc;
Ring Spanner 3/16 to 1" - 1No Double end spanner set 3/16" to 1" - 1 No Pipe Wrench 18" & 4" - 2Nos Screw drivers 6", 10" & 12" - 3 Nos Cutting Plier 12" - 1No 2 Kgs Hammer with Handle - 1 No Nose Plier - 1 No Flat and Half round smooth file - 2 Nos Adjustable Spanner 6" Column pipe Clamps - 2 pairs Line Shaft Clamps - 1 Pair Line rope and clamps double the weight of pump - 2 sets Gland thghtening Spanner - 1 No Spitter removing Spanner - 1 No Supply and delivery of necessary safety equipments as per IE Rules including cost of materials and all taxes and duties etc; complete Fire extiguisher 3Kg capacity - 2 Nos Rubber Mat 6" x 4" - 2Nos Fire Buckets with stand and three buckets - 1 No Rubber Hand Gloves - 1 Sets Danger Board Plates - 4 Nos
First aid kit with chart - 1No Shock Treatment Chart - 1No Portable rechargeble torch light - 1 No Supply and delivery of indigeneous make 500V insulation tested a portable type technometer and megger etc; Supply, delivery and erection of 5 tonnes capacity double girder gantry arrangements to move and lift the installations of the pump house one way with required MS ISMB of best quality 250 x 100 mm of standard make, including the required MS ISMC, MS angular iron, 5 tonne capacity travelling trolley and 5 tonne capacity chain pulley block with chains of suitable capacity for lifting and moving arrangements to length of 10.00 m rate is inclusive of the cost of materials, labour charges, site welding etc., All Civil Works Such as anchor Blocks ,Thrust Blocks, Platform for Pannel Board and Cable trench etc Complete as directed by the Field Engineer Testing and maintanance of the complete equipment covered and trial run for 30 days at 8 hours per day after completion of errection
Errection of 2 # of 14.92 KW (20 HP)CF Pumpsets each with a duty of 27 LPS and a total head of 40.00 m( one working and one stand bye) for pumping clear water from proposed Intermediate Sump at Uppalametta to proposed 800 KL ELSR Gov. Junior College
Errection of 2 # of 14.92 KW (20 HP)CF Pumpsets each with a duty of 27 LPS and a total head of 40.00 m( one working and one stand bye) for pumping clear water from proposed Intermediate Sump at Uppalametta to proposed 800 KL ELSR Gov. Junior College Supply, delivery, erection and commissioning of reputed make Energy Efficiency as per BEE Horizontal Split case Pumpset Capable of Discharging 27 LPS and a total head of 40m , directly coupled by pin and rubber bush type couplings to a squirrel cage induction motor having a duty of suitable capacity, with standard CI construction with bronze impeller of reputed/standard make alongwith all pressure guages and vaccum guages siphon and cock including cost of base frame including cost and conveyance of all materials, errection and commissioning charges and dismantling the existing pumpsets carefully if any and all taxes, duties, labour and transportation charges to site and all other incidental and operational charges etc; complete including all taxes but excluding GST. Supply, delivery, errection and commissioning of Motors with a speed of 1500 RPM 50 Hz TEFC horizontal foot mounted squirrel cage induction motor of reputed standard make suitable to operate 440volts to suit above pump sets fitted on a common base plate
including cost and conveyance of all materials including errection and commissioning charges and dismantling the existing motors carefully if any and all taxes , duties, labour and transportation charges to site and all other incidental and operational chrages etc; complete including all taxes but excluding GST. Supply, delivery and errection of suitable capacity vaccum pumpsets with all necessary Electrical connections, GI pipe connections & other accessories for self priming with 100 % Stand bye including cost and conveyance of all materials, errection and commissioning charges and dismantling the existing pumpsets carefully if any and all taxes, duties, labour and transportation charges to site and all other incidental and operational charges etc; complete including all taxes but excluding GST. Supply and fixing of control Pannel Board with suitable capacity bus bar suitable to operate above 3 Nos Pump Sets. The accessories all are internally wired with necessary earthing terminations. The Panel Board is made of 16 guage MS sheet metal cubical/industrial indoor type and duty painted with 2 coats enamel paint with cost of material as follows. conveyance, all taxes, duties, labour charges and all other incidents etc; complete for finished item of work
Incoming cable of suitable size of alluminium armoured cable 3.50 core of standard make from transformer to Panel Board Out-going cable of suitable size of Alluminium armoured cable of 3.50core of standard make from Panel Board to Starter and to Motor Cable Joints with jointing materials such as lugs glands, adhesive taps etc; to join the above cables a per I.E Rules Supply and errection of suitable suction and delivery DI/MS pipes and connections upto manfold including heavy duty Sluice Valves on suction side per stipulations of water supply mannual and I.S.Codes Supply,delivery,errection and commissioning of suitable capacity vaccum pump to operate ablve pumpsets including connecting or pumpsets with required G.I Pipes, Specials and fixing in concrete bed etc; Supply, laying and fixing of 40x6mm G.I flat patti double earthing for electrical protection for motor, pump and panel board efficiently earthing duly providing earth pits and filling with coal and salt and G.I pipe 1 1/2 x 6" long and bottom 2'x2' G.I.Plate welded as per I.E.Rules and Specifications with cost of materialss, conveyance, taxes,duties, labour charges and all other incidental charges and providing 1 1/2' x 1 1/2' earth pit chamber with brick masonary with top cover
Supply and delivery of necessary suitable errection tools of reputed make mounted on polished teak wood board including cost of materials and all taxes and duties etc; Ring Spanner 3/16 to 1" - 1No Double end spanner set 3/16" to 1" - 1 No Pipe Wrench 18" & 4" - 2Nos Screw drivers 6", 10" & 12" - 3 Nos Cutting Plier 12" - 1No 2 Kgs Hammer with Handle - 1 No Nose Plier - 1 No Flat and Half round smooth file - 2 Nos Adjustable Spanner 6" Column pipe Clamps - 2 pairs Line Shaft Clamps - 1 Pair Line rope and clamps double the weight of pump - 2 sets Gland thghtening Spanner - 1 No Spitter removing Spanner - 1 No Supply and delivery of necessary safety equipments as per IE Rules including cost of materials and all taxes and duties etc; complete Fire extiguisher 3Kg capacity - 2 Nos Rubber Mat 6" x 4" - 2Nos Fire Buckets with stand and three buckets - 1 No Rubber Hand Gloves - 1 Sets
Danger Board Plates - 4 Nos First aid kit with chart - 1No Shock Treatment Chart - 1No Portable rechargeble torch light - 1 No Supply and delivery of indigeneous make 500V insulation tested a portable type technometer and megger etc; Supply, delivery and erection of 5 tonnes capacity double girder gantry arrangements to move and lift the installations of the pump house one way with required MS ISMB of best quality 250 x 100 mm of standard make, including the required MS ISMC, MS angular iron, 5 tonne capacity travelling trolley and 5 tonne capacity chain pulley block with chains of suitable capacity for lifting and moving arrangements to length of 10.00 m rate is inclusive of the cost of materials, labour charges, site welding etc., All Civil Works Such as anchor Blocks ,Thrust Blocks, Platform for Pannel Board and Cable trench etc Complete as directed by the Field Engineer Testing and maintanance of the complete equipment covered and trial run for 30 days at 8 hours per day after completion of errection
(Deducting the SCADA Valves on Delivery Side. The following valves rates are deducted in the above pumpsets 150 mm dia sluice valves 150 mm dia non return valves loweing of valves 150 mm dia jointing of valves 150 mm dia
Errection of 2 # of 11.19 KW (15.00 HP)CF Pumpsets each with a duty of 30 LPS and a total head of 28.00 m( one working and one stand bye) for pumping clear water from proposed Intermediate Sump at Uppalametta to proposed 800 KL ELSRs Uppalametta zone-IV
Errection of 2 # of 11.19 KW (15.00 HP)CF Pumpsets each with a duty of 30 LPS and a total head of 28.00 m( one working and one stand bye) for pumping clear water from proposed Intermediate Sump at Uppalametta to proposed 800 KL ELSRs Uppalametta zone-IV Supply, delivery, erection and commissioning of reputed make Energy Efficiency as per BEE Horizontal Split case Pumpset Capable of Discharging 30 LPS and a total head of 28m , directly coupled by pin and rubber bush type couplings to a squirrel cage induction motor having a duty of suitable capacity, with standard CI construction with bronze impeller of reputed/standard make alongwith all pressure guages and vaccum guages siphon and cock including cost of base frame including cost and conveyance of all materials, errection and commissioning charges and dismantling the existing pumpsets carefully if any and all taxes, duties, labour and transportation charges to site and all other incidental and operational charges etc; complete including all taxes but excluding GST. Supply, delivery, errection and commissioning of Motors with a speed of 1500 RPM 50 Hz TEFC horizontal foot mounted squirrel cage induction motor of reputed standard make suitable to operate 440volts to suit above pump sets fitted on a common base plate including cost and conveyance of all materials
including errection and commissioning charges and dismantling the existing motors carefully if any and all taxes , duties, labour and transportation charges to site and all other incidental and operational chrages etc; complete including all taxes but excluding GST.Supply, delivery and errection of suitable capacity vaccum pumpsets with all necessary Electrical connections, GI pipe connections & other accessories for self priming with 100 % Stand bye including cost and conveyance of all materials, errection and commissioning charges and dismantling the existing pumpsets carefully if any and all taxes, duties, labour and transportation charges to site and all other incidental and operational charges etc; complete including all taxes but excluding GST. Supply and fixing of control Pannel Board with suitable capacity bus bar suitable to operate above 3 Nos Pump Sets. The accessories all are internally wired with necessary earthing terminations. The Panel Board is made of 16 guage MS sheet metal cubical/industrial indoor type and duty painted with 2 coats enamel paint with cost of material as follows. conveyance, all taxes, duties, labour charges and all other incidents etc; complete for finished item of work
Out-going cable of suitable size of Alluminium armoured cable of 3.50core of standard make from Panel Board to Starter and to Motor Cable Joints with jointing materials such as lugs glands, adhesive taps etc; to join the above cables a per I.E Rules
Supply and errection of suitable suction and delivery DI/MS pipes and connections upto manfold including heavy duty Sluice Valves on suction side per stipulations of water supply mannual and I.S.Codes
Supply,delivery,errection and commissioning of suitable capacity vaccum pump to operate ablve pumpsets including connecting or pumpsets with required G.I Pipes, Specials and fixing in concrete bed etc;
Supply, laying and fixing of 40x6mm G.I flat patti double earthing for electrical protection for motor, pump and panel board efficiently earthing duly providing earth pits and filling with coal and salt and G.I pipe 1 1/2 x 6" long and bottom 2'x2' G.I.Plate welded as per I.E.Rules and Specifications with cost of materialss, conveyance, taxes,duties, labour charges and all other incidental charges and providing 1 1/2' x 1 1/2' earth pit chamber with brick masonary with top cover
Supply and delivery of necessary suitable errection tools of reputed make mounted on polished teak wood board including cost of materials and all taxes and duties etc;
Ring Spanner 3/16 to 1" - 1No
Double end spanner set 3/16" to 1" - 1 No
Pipe Wrench 18" & 4" - 2Nos
Screw drivers 6", 10" & 12" - 3 Nos
Cutting Plier 12" - 1No
2 Kgs Hammer with Handle - 1 No
Nose Plier - 1 No
Flat and Half round smooth file - 2 Nos
Adjustable Spanner 6"
Column pipe Clamps - 2 pairs
Line Shaft Clamps - 1 Pair
Line rope and clamps double the weight of pump - 2 sets
Gland thghtening Spanner - 1 No
Spitter removing Spanner - 1 No
Supply and delivery of necessary safety equipments as per IE Rules including cost of materials and all taxes and duties etc; complete
Fire extiguisher 3Kg capacity - 2 Nos
Rubber Mat 6" x 4" - 2Nos
Fire Buckets with stand and three buckets - 1 No
Rubber Hand Gloves - 1 Sets
Danger Board Plates - 4 Nos
First aid kit with chart - 1No
Shock Treatment Chart - 1No
Portable rechargeble torch light - 1 No
Supply and delivery of indigeneous make 500V insulation tested a portable type technometer and megger etc;
Supply, delivery and erection of 5 tonnes capacity double girder gantry arrangements to move and lift the installations of the pump house one way with required MS ISMB of best quality 250 x 100 mm of standard make, including the required MS ISMC, MS angular iron, 5 tonne capacity travelling trolley and 5 tonne capacity chain pulley block with chains of suitable capacity for lifting and moving arrangements to length of 10.00 m rate is inclusive of the cost of materials, labour charges, site welding etc.,
All Civil Works Such as anchor Blocks ,Thrust Blocks, Platform for Pannel Board and Cable trench etc Complete as directed by the Field Engineer
Testing and maintanance of the complete equipment covered and trial run for 30 days at 8 hours per day after completion of errection
(Deducting the SCADA Valves on Delivery Side. The following valves rates are deducted in the above pumpsets
150 mm dia sluice valves
150 mm dia non return valves
loweing of valves 150 mm dia
jointing of valves 150 mm dia
Errection of 3 # of 14.92 KW (20.00 HP)CF Pumpsets each with a duty of 18 LPS and a total head of 50.00 m( two working and one stand bye) for pumping clear water from proposed Intermediate Sump at Uppalametta to proposed 1000 KL GLSR at Rajivi Nagar zone-I
Errection of 3 # of 14.92 KW (20.00 HP)CF Pumpsets each with a duty of 18 LPS and a total head of 50.00 m( two working and one stand bye) for pumping clear water from proposed Intermediate Sump at Uppalametta to proposed 1000 KL GLSR at Rajivi Nagar zone-I
Supply, delivery, erection and commissioning of reputed make Energy Efficiency as per BEE Horizontal Split case Pumpset Capable of Discharging 18 LPS and a total head of 50m , directly coupled by pin and rubber bush type couplings to a squirrel cage induction motor having a duty of suitable capacity, with standard CI construction with bronze impeller of reputed/standard make alongwith all pressure guages and vaccum guages siphon and cock including cost of base frame including cost and conveyance of all materials, errection and commissioning charges and dismantling the existing pumpsets carefully if any and all taxes, duties, labour and transportation charges to site and all other incidental and operational charges etc; complete including all taxes but excluding GST.
Supply, delivery, errection and commissioning of Motors with a speed of 1500 RPM 50 Hz TEFC horizontal foot mounted squirrel cage induction motor of reputed standard make suitable to operate 440volts to suit above pump sets fitted on a common base plate including cost and conveyance of all materials including errection and commissioning charges and dismantling the existing motors carefully if any and all taxes , duties, labour and transportation charges to site and all other incidental and operational chrages etc; complete including all taxes but excluding GST.
Supply, delivery and errection of suitable capacity vaccum pumpsets with all necessary Electrical connections, GI pipe connections & other accessories for self priming with 100 % Stand bye including cost and conveyance of all materials, errection and commissioning charges and dismantling the existing pumpsets carefully if any and all taxes, duties, labour and transportation charges to site and all other incidental and operational charges etc; complete including all taxes but excluding GST.
Supply and fixing of control Pannel Board with suitable capacity bus bar suitable to operate above 3 Nos Pump Sets. The accessories all are internally wired with necessary earthing terminations. The Panel Board is made of 16 guage MS sheet metal cubical/industrial indoor type and duty painted with 2 coats enamel paint with cost of material as follows. conveyance, all taxes, duties, labour charges and all other incidents etc; complete for finished item of work
Soft Starter i.e; FCMA ( flux compensated magnetic amplifier) standard reputed make - 3 Nos)
Suitable capacity MCCB for incoming supplystandard reputed make - 1 No
Suitable capacity TPN switch fuse unit HRC type to control starters standard reputed make- 3 Nos
Suitable KVAR Capacitors bank with controlling MCB switch for improving power factor standard reputed make - 1No
Suitable Amps Ammeter for individual reading of motor load standard reputed make - 3 Nos
Suitable Amps TPN switch fuse unit with HRC fuse for spare - 1 No
Suitable Phase indicating lamps reputed make - 3 Nos
Suitable ON/OFF green and red push buttons with indicating bulbs of any reputed make - 6 Nos
Supply, delivery and errection and jointing of suitable cable connection
Incoming cable of suitable size of alluminium armoured cable 3.50 core of standard make from transformer to Panel Board
Out-going cable of suitable size of Alluminium armoured cable of 3.50core of standard make from Panel Board to Starter and to Motor
Cable Joints with jointing materials such as lugs glands, adhesive taps etc; to join the above cables a per I.E Rules
Supply and errection of suitable suction and delivery DI/MS pipes and connections upto manfold including heavy duty Sluice Valves on suction side per stipulations of water supply mannual and I.S.Codes
Supply,delivery,errection and commissioning of suitable capacity vaccum pump to operate ablve pumpsets including connecting or pumpsets with required G.I Pipes, Specials and fixing in concrete bed etc;
Supply, laying and fixing of 40x6mm G.I flat patti double earthing for electrical protection for motor, pump and panel board efficiently earthing duly providing earth pits and filling with coal and salt and G.I pipe 1 1/2 x 6" long and bottom 2'x2' G.I.Plate welded as per I.E.Rules and Specifications with cost of materialss, conveyance, taxes,duties, labour charges and all other incidental charges and providing 1 1/2' x 1 1/2' earth pit chamber with brick masonary with top cover
Supply and delivery of necessary suitable errection tools of reputed make mounted on polished teak wood board including cost of materials and all taxes and duties etc;
Ring Spanner 3/16 to 1" - 1No
Double end spanner set 3/16" to 1" - 1 No
Pipe Wrench 18" & 4" - 2Nos
Screw drivers 6", 10" & 12" - 3 Nos
Cutting Plier 12" - 1No
2 Kgs Hammer with Handle - 1 No
Nose Plier - 1 No
Flat and Half round smooth file - 2 Nos
Adjustable Spanner 6"
Column pipe Clamps - 2 pairs
Line Shaft Clamps - 1 Pair
Line rope and clamps double the weight of pump - 2 sets
Gland thghtening Spanner - 1 No
Spitter removing Spanner - 1 No
Supply and delivery of necessary safety equipments as per IE Rules including cost of materials and all taxes and duties etc; complete
Fire extiguisher 3Kg capacity - 2 Nos
Rubber Mat 6" x 4" - 2Nos
Fire Buckets with stand and three buckets - 1 No
Rubber Hand Gloves - 1 Sets
Danger Board Plates - 4 Nos
First aid kit with chart - 1No
Shock Treatment Chart - 1No
Portable rechargeble torch light - 1 No
Supply and delivery of indigeneous make 500V insulation tested a portable type technometer and megger etc;
Supply, delivery and erection of 5 tonnes capacity double girder gantry arrangements to move and lift the installations of the pump house one way with required MS ISMB of best quality 250 x 100 mm of standard make, including the required MS ISMC, MS angular iron, 5 tonne capacity travelling trolley and 5 tonne capacity chain pulley block with chains of suitable capacity for lifting and moving arrangements to length of 10.00 m rate is inclusive of the cost of materials, labour charges, site welding etc.,
All Civil Works Such as anchor Blocks ,Thrust Blocks, Platform for Pannel Board and Cable trench etc Complete as directed by the Field Engineer
Testing and maintanance of the complete equipment covered and trial run for 30 days at 8 hours per day after completion of errection
(Deducting the SCADA Valves on Delivery Side. The following valves rates are deducted in the above pumpsets
150 mm dia sluice valves
150 mm dia non return valves
loweing of valves 150 mm dia
jointing of valves 150 mm dia
Construction wash water recirculation of 7.00m dia sump(92.43 KL) at WTP
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH for foundations upto 3.00m depth Note : Classifications of Earth Work Specification are as per 302.2.1(a) of MORD and 301.2.1 of MORT&H--ordinary soil-- upto 3m depth as follows
for wash water recirculation sump foundations 0-3.00m Machanical means
for wash water recirculation sump foundations 3.00-6.00m Machanical means
Filling Sand for foundation as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH.This rate including cost of sand ,filling charges,watering,ramming,and other incidental charges etc., complete as per ss and directed by the departmental officer incharge of work
Plain Cement concrete (1:4:8) using 40 mm metal with concrete mixer. All work upto plinth level including cost of all materials and labour charges etc., complete as per SS and as directed by the departmental officer in charge of the work but excluding seigniorage charges
Supply and placing of the design mix concrete corresponding to IS -456 using WEIGH BATCHER/MIXER using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including seigniorage charges ,sales and other taxes on all materials including all operational ,incidental and labour charges such as weigh batching ,machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work (APSS NO 402) with minimum cement content as per IS Code from standard suppliers approved by the deparment including pumping , centering,shuttering,laying concrete ,vibrating,curing etc M30 design mix concrete with concrete mixer as directed by the departmental officer incharge of work .
For side walls circular 0.30m thick below GL
For side walls circular 0.30m thick above GL
Columns 0.30 x 0.30m 3.60-0.30
Roof beams
Roof slab 0.15m thick 0.786x(7.60^2-3.00^2)
Roof dome slab 0.15m thick
Providing impervious coat to exposed RCC roof slab surface with CM(1:3), 20mm thick with 1kg of water proof compound per bag of cement laid over roof when it is green including cost of all materials, seigniorage charges, excluding conveyance charges of materials and including all operational, incidental and labour charges for mixing mortar, laying, rendering smooth and thread lining, curing, rounding off junctions of wall and slab etc,, complete for finished item of work
Providing Painting walls with snowcern or equivalent paint two coats by using approved water proof paint grade-1 over one coat prime coat by using cement primary coat by using cement primer making 3 coats including cost of Colour washing two coats Using snowcem including cost cost of material and all bour charges, transporttion other incidental charges etc., complete as directed by the departmental officer incharge of work .
Supply and delivery and fixing in position M S grill of any design including all fabrication and all fixing charges and other incidental charges power charges welding rod etc complete as per ss and as directed by the dept authorities
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying including sales and other taxes on all materials etc., complete for finished item of work in all floors.( APSS No.126)
Construction of R.C.C. railing of M 25 grade in cast-in-situ with 20 mm nominal size aggregate, true to line and grade-3 size, tolerance of vertical railing post not to exceed 1 in 500, centre-to-centre spacing between vertical posts not to exceed 2000 mm as per drawing and technical specifications Clauses 800, 900 and 1208.3 MORD.
Laying of 100 mm dia . DI K9 Pumping mains from wash water sump at HWW to Areator
Earth work excavation in all soils up to SDR & stone matrix by machinery for Pipe lines as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and back filling in trenches with excavated suitable material as per Technical Specification No.305 MORD/304 MORTH up to initial lift of 3.00m. For Pipe line trenches.
Filling in foundation trenches as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH-sand filling. This rate including cost of material and all lbour charges, watering, ramming and other incidental charges etc., complete as directed by the departmental officer incharge of work . for Pipe line sand bedding
Manufacture supply delivery,of 100mm dia centrifugally cast (spun) ductile iron pipes for water with Socket spigot ends confirming to IS NO 8329/2000 in standard lengths of 4.00,5.00,5.50,6.00m suitable for push-on-joint (rubber gasket D jointing) with cement mortor lining inside and zinc coating out side (K9) including transportation ,loading,unloading, stacking, etc complete as directed by the departmental officer incharge of work .
Supply and delivery of 100mm dia Centrifugally cast (SPUN) ductile iron pressure pipes with flanged ends for water, gas and sewage conforming to I.S, 8329/2000 in standard working lengths of 4, 5, 5.5 & 6 meter for classification K9 suitable for push on joint (Rubber gasket and jointing) with cement mortar lining inside the pipes with outside zinc coating, rates are ex-factory, including transportion and other incidental charges etc., complete as directed by the departmental officer incharge of work .
Supply, delivery of D.I. fittings confirming to I.S.No.9523/2000 having dimensions upto 500mm dia as per table with Zinc coated externally and inside Cement Mortar lining (With finishing as per Class 13/IS 9523/2000) including cost of fittings, transportation, stacking carefully at site. The rate etc.,complete as per S.S. and as directed by the departmental authorities.
Lowering of 100mm dia D.I. socket and spigot Pipes and fittings carefully in to the trench and laying them true to alignment and gradient including all labour charges, sundries as per BIS No. 3114/85 etc., complete as per S.S and as directed by the departmental authorities.
Jointing of 100mm da D.I. Pipes & fittings with Rubber Gasket including all sundries filling with water with a water lead up to 500m and testing to required pressure etc., complete as per BISNo.3114/85 and as directed by the departmental authorities.
Manufacture, Supply and delivery of 100mm dia DI D/F Gate Valves (Soft Seated) Resilient seated soft sealing gate valves (Sluice valves) with body bonnet of ductile cast iron of grade GGG40/ SG 400/12 or equivalent grade as per I.S.3896-part2-1985 and subsequent revisions, wedge fully rubber lined with EPDM food grade quality and seals of NBR and the valves should be of vacuum tight and 100% leak proof with face to face dimensions as per BS5163-89/IS14846-2000/DIN 3202 F 4. All the valves should be with Electrostatic powder coating both inside and outside pocket less body passage. Drilled as per IS:1538. PN16
Manufacture, Supply and delivery of 100mm dia DI D/F Swing Check Valves Slanted/Straight seated with metallic, corrosion proof and wear resistant seat faces resilient seat, Body and Disc of ductile cast iron GGG 40/SG Iron 420/12 or equivalent grade as per IS 3896(part2)-1985 and subsequent revisions. All the inside and outside of the body is to be coated with double coating of epoxy liquid. Drilled as per IS:1538. Specification and Dimensions as per I.S 5312 or equivalent codes. PN 16
Labour charges for 100mm dia lowering and keeping in position of C.I./DI Sluice valves(with cap/with hand wheel), reflux valves and scour valves.
Lowering the C.I. Pipes, D.I. Pipes of all classes and fittings with flanged ends carefully into the trenches and laying them true to alignment and gradient including all sundries, but excluding conveyance from source of supply as per BIS No.3114/94.and other incidental charges etc., complete as directed by the departmental officer incharge of work . as follows
500mm dia
100 mm dia
Jointing the D.I. Pipes, fittings and valves with flanged ends including cost of jointing materials such as bolts, nuts, rubber insertion, white lead and including filling with water with a water lead upto 500 m and testing to required pressure etc., comp as per BIS No.3114/85 and other incidental charges etc., complete as directed by the departmental officer incharge of work .
500 mm dia
250 mm dia
100 mm dia
Construction of M20 concrete thrust blocks using 20mm HBG metal from approved quarry including cost and conveyance of all materials at site, seignorage charges, labour charges for machine mixing, laying, vibrating including centering charges but excluding cost of steel for reinforcement and its fabrication including curing etc., complete.as per SS and as directed by the departmental officer incharge of work .
Construction of 150mm dia Sluice Valve chambers with CC M20 mix suitable to the sluice valves including cost and conveyance of all materials and all labour charges etc.complete as per S.S and for finished item of work. This rate is including cost of material and all labour charges with Earthwork, asand bedding, VCC 1:4:8, RCC bedding and side wall, cover slab with suitble opening, cast stell as per type design approved by the department.
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying including sales and other taxes on all materials etc., complete for finished item of work in all floors.( APSS No.126) for pre cast slabs of culverts - RBR-FNDN-8 & Revised Data sl.No-5
Supply and erection of 2# of 1.87KW(2.50HP) CF Pumpsets each with a duty of 12 LPS and a total hed of 11m ( one working and one stand bye) for pumping wash waterto Areator for recirculation
Supply and erection of 2# of 1.87KW(2.50HP) CF Pumpsets each with a duty of 12 LPS and a total hed of 11m ( one working and one stand bye) for pumping wash waterto Areatorm for recirculation
Construction of electrician / operator/watchman quarters at HWW
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD. Note : Classifications of Earth Work Specification are as per 302.2.1(a) of MORD and 301.2.1 of MORT&H--ordinary soil--manual means upto 3m depth for foundations of buildings in restricted places as follows:
Mechanical means up to 3 metres depth in ordinary soil
Manual Means up to 3 metres depth in ordinary soil
Providing river sand filling brought from approved quarry including cost and conveyance of all material and all labour charges such as filling in layers watering ramming etc complete as per ss as directed by the departmental officer incharge of work for Foundaion bedding
Providing PCC 1:4:8 using 40 mm graded SS 5 HBG m/c metal and OPC coarse and fine aggregate confirming to IS 383 including cost and conveyance of all materials and labour charges, machine mixing , vibration,laying in position, Centering curing etc., complete as directed by the departmental officer incharge of work.
Supply and placing of the design mix concrete corresponding to IS -456 using WEIGH BATCHER/MIXER using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including seigniorage charges ,sales and other taxes on all materials including all operational ,incidental and labour charges such as weigh batching ,machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work (APSS NO 402) with minimum cement content as per IS Code from standard suppliers approved by the deparment including pumping , centering,shuttering,laying concrete ,vibrating,curing etc M20 design mix as follows
column footings
Columns 1.50-0.15-0.15-0.20-0.25 =0.75 + basement 0.75m+superstructure 3.35m=4.85m
Plinth beam
Lintle beams Windows
Roof Beams
Roof slab 0.125m thick with 0.30m extension all sides
Sunshades 0.60m wide, 0.10m at fixed end and 0.05m at free end Windows
Loft slab 0.075m thick kitchen
Brick work in CM 1:6 mix using 2nd class bricks brought from approved kilns including cost and conveyance of all materials and all labour charges ,Scaffolding liftngcuring for 21 days etc complete as per ss as directed by the departmental officer incharge of work as follows
Ground floor
1st floor
Cement plastering using opc in cm(1:5) prop 12 mm thick including cost of material, labour ,curing, scaffolding, etc. complete as per SS as directed by the departmental officer incharge of work. out side & inside
Ground floor
1st floor Parpet wall
Cement plastering for Ceiling using opc in cm(1:3) prop 12 mm thick including cost of material, labour ,curing etc. complete as per SS for inside above 3.5 m Height This rate is including cost of material and all labour charges, scaffolding charges etc., complete as per IE Rules and as directed by the departmental officer incharge of work .
Providing Painting walls with snowcern or equivalent paint two coats by using approved water proof paint grade-1 over one coat prime coat by using cement primary coat by using cement primer making 3 coats including cost of Colour washing two coats Using snowcem including cost cost of material and all bour charges, transporttion other incidental charges etc., complete as directed by the departmental officer incharge of work .
Supply delivary and fixing RCC Jollys includnig cost and conveyance of all material and all labour charges for fixing etc complete as ss as directed by the departmental officer incharge of work .
Supply and fixing Aluminium Anodised Doors - Single Shutter as per approved drawing with aluminium anodised sections of Jindal sections and outer frame top horizontals & both verticals of 2408 of size 101.6 x 44.75 x 3.18 mm Shutter frame top, bottom and verticals of 4504 of size 44.45 mm x 47.62 mm x 3.18 and Middle lock rail of 4621 of size 49.91 x 44.45 x 3 mm with tinted-bronze/green glass 5 mm thick(middle to top),MDF Board-exterior both sides laminaed 12mm thick(middle to bottom) fixed including supply and fixing aluminium handles of 150 mm for each shutter and all labour charges for fixing the fixtures with required no.of screws, bolts and nuts and including labour charges for fixing the frame in position, fixing shutter to frame etc. completed for finished item of work as follows
Door -D - 1.20X2.10 m
doors D1 - 1.0X2.10m
Supply and fixing Aluminium Anodised Two/ Three Track Sliding Windows of size 1.50m X 1.20 m as per approved drawing with aluminium anodised sections of Series C Jindal sections and outer frame top horizontals & both verticals of 8774 of size 62 x 29.5 mm and bottom horizontal - two track frame of 8773 of size 62 x 29.5 mm, Shutter frame top, bottom and verticals of 8304 of size 50 mm x 20 mm and Weather interlocking frame of 8306 of size 50 x 20 with plain clear float glass 5 mm thick fixed including supply and fixing aluminium handles of 100 mm for each shutter, nylon rollers assembly and all labour charges for fixing the fixtures with required no.of screws, bolts and nuts and including labour charges for fixing the frame in position, fixing shutter to frame etc. completed for finished item of work
Providing and fixing factory made polyvinyl chloride (PVC) Door Frame of the size 50 x 47mm with a wall thickness of 5mm, made out of extruded 5mm rigid PVC foam sheet, mitre cut at two corners and joined with 2nos. of 150mm long brackets of 15x15mm M.S. square tube. The two vertical door profiles are to be reinforced with 19x19mm M.S. Square tube of 19 gauge. The door frame shall be fixed to the wall using 65/100mm long M.S. Screws through the frame by using PVC fasteners. A minimum of 4nos. of screws to be provided for each vertical member & minimum 2nos. for horizontal member etc. complete as per manufacturers specification and direction of Engineer-in-Charge for finished item of work
Providing and fixing 30mm thick Solid panel PVC door shutter consisting of frame made out of M.S. tubes of 19 gauge thickness and size of 19mm x 19mm for stiles, & 15mm x 15mm for top & bottom rails. M.S. frame shall have a coat of steel primers of approved make and manufacture. M.S. frame shall be covered with 5mm thick heat moulded PVC ‘C’ channel of size 30 x 50mm forming stiles, and 5mm thick, 75mm wide PVC sheets for top rail, lock rail & bottom rail on either side, and 10mm (5mm x 2) thick, 20mm wide cross PVC sheet as gap insert for top rail & bottom rail. Panelling of 5mm thick PVC sheet to be fitted in the M.S. frame welded / sealed to the stiles & rails with 30mm wide x 5mm thick PVC sheet beading on either side, and joined together with solvent cement adhesive etc. An additional 5mm thick PVC strip of 20mm width is to be stuck on the interior side of the ‘C’ Channel using PVC solvent adhesive. Complete as per direction of Engineer-in-charge, manufacturer’s specification & drawing for finished item of work
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying including sales and other taxes on all materials etc., complete for finished item of work in all floors.( APSS No.126)
Cement plastering using opc in cm(1:3) prop 20 mm thick including cost of material, labour ,curing, scffolding, smooth finish etc. complete as per SS as directed by the departmental officer incharge of work for floorring
Manufacture,supply,delivery of MS grill gates,window ornamental safety grill ,made with MS flats,MS angles,MS squares etc including welding,finishing,applying red oxide paint as primary coat etc complete
Providing two coats of Synthic enamil paint over new Iron works including one coat red oxide paint cost and conveyance of all material and all labour charges etc complete as per ss for Grills as directed by the departmental officer incharge of work .
Supply, delivery and fixing of 110mm dia single socket PVC pipes 4 kg/sqcm prince/Sudhakar or any ISI brand for rain water pipes with clamps as per IE Rules and as directed by the departmental officer incharge of work.
Supply and fixing of 25 mm dia 2.00 mm thick PVC pipe concealed in roof slab with all required accessories including masonary work all labour chages as directed by the departmental officer incharge of work .
Supply and fixing of 20 mm dia 1.50 mm thick PVC pipe concealed in walls with all required accessories including masonary work for light , fan and plug point with metal deep box including all labour chages as per IE Rules and as directed by the departmental officer incharge of work.
Wiring with 2 runs 14/0.3 mm. (1.0. sq.mm) Fire retardant PVC insulated Flexible copper cable in existing pipe with 6A siwtch, ceiling rose and 3 mm thick hyla sheet covering to switch control box including all labour charges etc,., complet for light, bell , fan and exhaust fan points in non - residential building This rate is including cost of material and all labour charges and other incidental charges etc., complete as per IE Rules and as directed by the departmental officer incharge of work .
Wiring with 2 runs 14/0.3 mm. (1.0. sq.mm) Fire retardant PVC insulated Flexible copper cable in existing pipe with 6A modular siwtch control and 3/2 pin sockets fixing on board including all labour charges This rate is including cost of material and all labour charges and other incidental charges etc., complete as per IE Rules and as directed by the departmental officer incharge of work .
supply and run of 2 of 36/0.3 mm. (1.5. sq.mm) Fire retardant PVC insulated Flexible copper cable in existing pipe for mains including all labour charges This rate is including cost of material and all labour charges and other incidental charges etc., complete as per IE Rules and as directed by the departmental officer incharge of work .
supply and run of 1 of 14/0.3 mm. (1.0. sq.mm) Fire retardant PVC insulated Flexible copper cable in existing pipe for earth continuity including all labour charges etc. This rate is including cost of material and all labour charges and other incidental charges etc., complete as per IE Rules and as directed by the departmental officer incharge of work .
supply and run of 2 of 6 sq.mm (7/18) WPSC alluminium cable along with No.10 SWG G.I barer wire through PVC cleats with all accessories including all labour charges etc.,This rate is including cost of material and all labour charges and other incidental charges etc., complete as per IE Rules and as directed by the departmental officer incharge of work .
Providing independent earthing by excavating a trench to a depth of 2.10m in all soils, as per size specied in data ,using 40 mm dia B class GI pipe 2.50m long with necessary accessories with hume pipe ring duly providing staggered holes including filling with equal proportion of salt and charcoal in layers and all labour charges etc complete This rate is including cost of material and all labour charges and other incidental charges etc., complete as per IE Rules and as directed by the departmental officer incharge of work .
Supply and fixing SPN Distribution board with IP-20 protection suitable for single phase Earth Leakage Circute Braker (ELCB) / Residual Current Circute Braker (RCCB) / Double Pole (DP) Isolator as incomer and 10kA SP MCBs as out going including internal connections and labour charges for surface / flush mounting etc., complete This rate is including cost of material and all labour charges and other incidental charges etc., complete as per IE Rules and as directed by the departmental officer incharge of work .
Supply of 48" (1200mm) Sweep 5 star rated Ceiling Fan , with double ball bearings, air delivery more than 200 cubic meter/min but without Regulator.Makes : Crompton HS Plus / Havells ES Neo/Orient Energy Star/ Halonix(Zephyr)/Polycab(Synergy Star) unit each complete as per IE Rules and as directed by the departmental officer incharge of work
Supply of stepped type Electronic Regulator of Makes: GM G Home / Gold Medal Olive / Million Zoom / Great white Omega/Koncept/Vimal opel/ Anchor/Vihan/CPL complete as per IE Rules and as directed by the departmental officer incharge of work
Supply of 9" (225mm), Light duty exhaust fan with double ball bearing and wire guard etc complete. Makes: Crompton / Bajaj Bahar WG / Havells Ventil Air-DS / Orient hill air / MIIT complete as per IE Rules and as directed by the departmental officer incharge of work
Supply and transportation of 20W, 2000 lumens, T8,1200mm length LED retro tube light,wide operating voltage with double side connection, PF≥0.9,Surge protection: > 2KV, THD<15%, with inbuilt driver and frosted cover CCT: 3000K - 6500K as desired by the department and as per IS specifications, minimum CRI≥80,.etc complete with 5 years warranty.LUMINAIRE MAKE: Phillips / OSRAM / GE / Crompton /VIN / Bajaj / Havells / Halonix / HPL. LED MAKE : PHILIPS LUMILEDS / CREE / NICHIA /OSRAM / SAMSUNG / LG LEDs.as per IE Rules and as directed by the departmental officer incharge of work
Labour charges for Fixing of Ceiling fan and regulator including transportation and giving connections with twin core wire etc., complete
Labour charges for fixing of Exhaust fan in wall with necessary connections and masonary work of making hole, finishing etc., complete
Labour charges Fixing of 40W tube light luminaire on wall / Ceiling with / TW round blocks with all accessories including giving connections and all labour charges etc., complete.
Providing & Placing on Terrace (at all floor levels) polyethylene water storage tank with Double layer approved brand & manufacture with cover and suitable locking arrangement & making necessary holes for inlet & outlets and over flow pipes but without fittings & base support for tanks as per SS and as directed by the departmental officer incharge of work .
Supplying and fixing 580mm x 440mm long Orissa pan white glazed Water Closet 1st quality ISI marked confirming to IS:2556-Part-3-1981 with "P" or "S" trap, ISI marked and providing masonry seat, CC squatting plate and 10 litres capacity single flush PVC low level cistern with internal components fixed on 2 Nos. of teak wood blocks of size 76.20mm x 101.60mm using required size of nails, screws as approved by Engineer-in-charge, 15 mm nominal size CP finish brass angled stop valve screw type with internal /external threaded conforming to IS 8931, 12.70mm PVC connection with brass union nuts CP coated , 31.75mm brass plumber union, P trap or S trap of Indian W.C. shall be encased on CC (1:2:4) 150mm alround well above the joint to stop leakage at the joint etc., complete including cost and conveyance of all materials to site, cost of CC bed, labour charges and seigniorage charges, overheads & contractors profit etc., complete for finished item of worke
Supplying and fixing Indian make Flat Back Wash Hand Basin 1st quality conforming to IS:2556-Part-4:1972 of size 550mm x 400mm with 32 mm nominal size C.P. Fitting with parallel pipe thread conforming to IS:2963-1979 and fitted with 15 mm nominal bore Chromium Plated Pillar Tap of 1st quality Indian make heavy duty complete with standard CI brackets including wooden blocks ,1 No.12.70mm PVC connection with brass union nuts CP coated , angle stop cock 12.70mm dia. first quality Indian make heavy duty, 30mm dia. PVC flexible waste pipe 914.4mm length of 1st quality including cost and conveyance of all materials to site, labour charges , overheads & contractors profit for finished item of work
Supplying and fixing CP finish brass soap dish of approved make ISI quality including cost and conveyance of all materials, labour charges for fixing , overheads & contractors profit for finished item of work in all floors
Supplying and fixing TV shape mirror with plastic frame of size 609.6mm x 457.2mm , plywood back with NP screws 1st quality including cost and conveyance of all materials, labour charges , overheads & contractors profit for finished item of work in all floors.
Supplying and fixing of 25.4mm dia , 609.6mm long aluminium anodized towel rods with brackets and aluminium screws including cost and conveyance of all materials, labour charges , overheads & contractors profit for finished item of work.
Supply of 110 mm dia 3 m single Socket PVC/SWR pipe - 6 Kg/sq.cm - Prince/Sudhakar/Kisan/Supreme or any ISI Brand.
Supply of 110 mm dia - Plain Bend 87.5 Degree - UPVC/SWR Pipe fittings (Prince/Sudhakar/Kisan/Supreme or any ISI Brand)
Supply of 110 mm dia - Coupler - UPVC/SWR Pipe fittings (Prince/Sudhakar/Kisan/Supreme or any ISI Brand
Labour charges for laying, fixing and commissioning the PVC pipes including couplers/ bends/ tees etc any diameter including fixing necessary fittings like bends, plugs, couplers, junctions, tees, etc with solvent jointing as per standard practice
Constructing 457.2 mm x 457.2 mm (1'6"x1'6") brick in CM 1:6 prop. Masonry. Inspection chamber up to 914.4 mm (3'0") and fitted with light weight 457.2 mm x 457.2 mm (1'6"x1'6") C.I frame and cover of 20 Kg
S& F GI pipe Medium Grade properties & weight as per IS 1239 ISI mark with GI fittings including the cost of pipe & its fittings & labour charges complete
25 mm dia nominal bore -from tank to jn for of individual lines
20 mm dia nominal bore -from jn for of individual lines to toilets & Kitchen
15 mm dia nominal bore -for internal
S&F of GI &GM fittings
GM Ball valve with SS Ball and SS Spindle as per IS - Class - I, Indian make heavy type - 25 mm NB Size
GM Ball valve with SS Ball and SS Spindle as per IS - Class - I, Indian make heavy type - 20 mm NB Size
GM Ball valve with SS Ball and SS Spindle as per IS - Class - I, Indian make heavy type - 15 mm NB Size
S&F 12.7 mm N.P bib tap Indian make heavy dutys Seiko/ Senior/ Nice or equivalent
S& F GI union Ist Quality
12.70mm GI union
19.05mm GI union
25.40mm GI union
For septic Tank
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD. Note : Classifications of Earth Work Specification are as per 302.2.1(a) of MORD and 301.2.1 of MORT&H--ordinary soil--manual means upto 3m depth by manual means upto 3.00m depth
Filling in foundation trenches as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH-sand filling. This rate including cost of material and all lbour charges, watering, ramming and other incidental charges etc., complete as directed by the departmental officer incharge of work .
Providing PCC 1:4:8 using 40 mm graded SS 5 HBG m/c metal and OPC coarse and fine aggregate confirming to IS 383 including cost and conveyance of all materials and labour charges, machine mixing , vibration,laying in position, curing etc., complete This rate including cost of material and all lbour charges, watering, ramming and other incidental charges etc., complete as directed by the departmental officer incharge of work .
Brick work in CM 1:5 mix using 2nd class bricks brought from approved kilns including cost and conveyance of all materials and all labour charges ,curing for 21 days etc complete as per ss for Septic tank walls as directed by the departmental officer incharge of work .
Cement plastering using opc in cm(1:3) prop 20 mm thick including cost of material, labour ,curing etc. complete as per SS out side & inside for Septic tank walls as directed by the departmental officer incharge
RCC M-20 Nominal mix (cement,fine aggregate,coarse aggregate) corresponding to Table -9 of IS -456 using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including seigniorage charges ,sales and other taxes on all materials including all operational ,incidental and labour charges such as machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work,but including centering,shuttering for Septic tank as directed by the departmental officer incharge
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying including sales and other taxes on all materials etc., complete for finished item of work in all floors.( APSS No.126)
Construction of electrician / operator/watchman quarters at HWW
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD. Note : Classifications of Earth Work Specification are as per 302.2.1(a) of MORD and 301.2.1 of MORT&H--ordinary soil--manual means upto 3m depth for foundations of buildings in restricted places as follows
Mechanical means up to 3 metres depth in ordinary soil
Manual Means up to 3 metres depth in ordinary soil
Filling sand in foundation trenches of column footing bed as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH etc., complete. This rate including cost of all materials, all labour charges, watering, ranning other incidental charge etc complete as per SS and as directed by the Departmental officer in charge of the work. But excluding seigniorage charge.
Plain Cement Concrete (1:4:8) (cement: fine aggregate: Coarse aggregate) for foundations and under column footing bed using 162.0 kgs of cement, coarse aggregate 40mm size hard , machine crushed granite from approved quarry including cost and conveyance of all materials like cement, sand, coarse aggregate, water etc. to site, includingall materials and all charges for machine mixing, laying concrete in foundations and under drain bed, ramming in 15 cm layers finishing top surface to the required level curing etc., and complete for finished item of workas per SS and as directed by the departmental officer in charge of work.
Supply and placing of the design mix concrete corresponding to IS -456 using WEIGH BATCHER/MIXER using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including seigniorage charges ,sales and other taxes on all materials including all operational ,incidental and labour charges such as weigh batching ,machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work (APSS NO 402) with minimum cement content as per IS Code from standard suppliers approved by the deparment including pumping , centering,shuttering,laying concrete ,vibrating,curing etc M20 design mix s follows
column footings
Columns 1.50-0.15-0.15-0.20-0.25 =0.75 + basement 0.75m+superstructure 3.35m=4.85m
Plinth beam
Lintle beams Windows
Roof Beams
Roof slab 0.125m thick with 0.30m extension all sides
Sunshades 0.60m wide, 0.10m at fixed end and 0.05m at free end Windows
Loft slab 0.075m thick kitchen
Brick work in CM 1:6 mix using 2nd class bricks brought from approved kilns including cost and conveyance of all materials and all labour charges ,curing for 21 days etc complete as per ss as directed by the departmental officer incharge of work .
Ground floor
1st floor
Cement plastering using opc in cm(1:5) prop 12 mm thick including cost of material, labour ,curing, scaffolding etc. complete as per SS out side & inside as directed by the departmental officer incharge of work .
Ground floor
1st floor
Cement plastering using opc in cm(1:3) prop 12 mm thick including cost of material, labour ,curing etc. complete as per SS for inside above 3.5 m Height as directed by the departmental officer incharge of work .
Providing Painting walls with snowcern or equivalent paint two coats by using approved water proof paint grade-1 over one coat prime coat by using cement primary coat by using cement primer making 3 coats including cost of Colour washing two coats Using snowcem including cost cost of material and all bour charges, transporttion other incidental charges etc., complete as directed by the departmental officer incharge of work .
Supply delivary and fixing RCC Jollys includnig cost and conveyance of all material and all labour charges for fixing etc complete as ss as directed by the departmental officer incharge of work .
Supply and fixing Aluminium Anodised Doors - Single Shutter as per approved drawing with aluminium anodised sections of Jindal sections and outer frame top horizontals & both verticals of 2408 of size 101.6 x 44.75 x 3.18 mm Shutter frame top, bottom and verticals of 4504 of size 44.45 mm x 47.62 mm x 3.18 and Middle lock rail of 4621 of size 49.91 x 44.45 x 3 mm with tinted-bronze/green glass 5 mm thick(middle to top),MDF Board-exterior both sides laminaed 12mm thick(middle to bottom) fixed including supply and fixing aluminium handles of 150 mm for each shutter and all labour charges for fixing the fixtures with required no.of screws, bolts and nuts and including labour charges for fixing the frame in position, fixing shutter to frame etc. completed for finished item of work as follows
Door -D - 1.20X2.10 m
doors D1 - 1.0X2.10m
Supply and fixing Aluminium Anodised Two/ Three Track Sliding Windows of size 1.5X1.2m as per approved drawing with aluminium anodised sections of Series C Jindal sections and outer frame top horizontals & both verticals of 8774 of size 62 x 29.5 mm and bottom horizontal - two track frame of 8773 of size 62 x 29.5 mm, Shutter frame top, bottom and verticals of 8304 of size 50 mm x 20 mm and Weather interlocking frame of 8306 of size 50 x 20 with plain clear float glass 5 mm thick fixed including supply and fixing aluminium handles of 100 mm for each shutter, nylon rollers assembly and all labour charges for fixing the fixtures with required no.of screws, bolts and nuts and including labour charges for fixing the frame in position, fixing shutter to frame etc. completed for finished item of work
Providing and fixing factory made polyvinyl chloride (PVC) Door Frame of the size 50 x 47mm with a wall thickness of 5mm, made out of extruded 5mm rigid PVC foam sheet, mitre cut at two corners and joined with 2nos. of 150mm long brackets of 15x15mm M.S. square tube. The two vertical door profiles are to be reinforced with 19x19mm M.S. Square tube of 19 gauge. The door frame shall be fixed to the wall using 65/100mm long M.S. Screws through the frame by using PVC fasteners. A minimum of 4nos. of screws to be provided for each vertical member & minimum 2nos. for horizontal member etc. complete as per manufacturers specification and direction of Engineer-in-Charge for finished item of work
Providing and fixing 30mm thick Solid panel PVC door shutter consisting of frame made out of M.S. tubes of 19 gauge thickness and size of 19mm x 19mm for stiles, & 15mm x 15mm for top & bottom rails. M.S. frame shall have a coat of steel primers of approved make and manufacture. M.S. frame shall be covered with 5mm thick heat moulded PVC ‘C’ channel of size 30 x 50mm forming stiles, and 5mm thick, 75mm wide PVC sheets for top rail, lock rail & bottom rail on either side, and 10mm (5mm x 2) thick, 20mm wide cross PVC sheet as gap insert for top rail & bottom rail. Panelling of 5mm thick PVC sheet to be fitted in the M.S. frame welded / sealed to the stiles & rails with 30mm wide x 5mm thick PVC sheet beading on either side, and joined together with solvent cement adhesive etc. An additional 5mm thick PVC strip of 20mm width is to be stuck on the interior side of the ‘C’ Channel using PVC solvent adhesive. Complete as per direction of Engineer-in-charge, manufacturer’s specification & drawing for finished item of work
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying including sales and other taxes on all materials etc., complete for finished item of work in all floors.( APSS No.126)
Cement plastering using opc in cm(1:3) prop 20 mm thick including cost of material, labour ,curing, scaffolding, sommth fnishing etc. complete as per SS for floorring as directed by the departmental officer incharge of work .
Manufacture,supply,delivery of MS grill gates,window ornamental safety grill ,made with MS flats,MS angles,MS squares etc including welding,finishing,applying red oxide paint as primary coat etc complete
Providing two coats of Synthic enamil paint over new Iron works including one coat of red oxide paint cost and conveyance of all material and all labour charges etc complete as per ss for Grills as directed by the departmental officer incharge of work .
Supply, delivery and fixing of 110mm dia single socket PVC pipes 4 kg/sqcm prince/Sudhakar or any ISI brand for rain water pipes with clamps
Supply and fixing of 25 mm dia 2.00 mm thick PVC pipe concealed in roof slab with all required accessories including masonary work all labour chages
Supply and fixing of 20 mm dia 1.50 mm thick PVC pipe concealed in walls with all required accessories including masonary work for light , fan and plug point with metal deep box including all labour chages
Wiring with 2 runs 14/0.3 mm. (1.0. sq.mm) Fire retardant PVC insulated Flexible copper cable in existing pipe with 6A siwtch, ceiling rose and 3 mm thick hyla sheet covering to switch control box including all labour charges etc,., complet for light, bell , fan and exhaust fan points in non - residential building This rate is including cost of material and all labour charges and other incidental charges etc., complete as per IE Rules and as directed by the departmental officer incharge of work .
Wiring with 2 runs 14/0.3 mm. (1.0. sq.mm) Fire retardant PVC insulated Flexible copper cable in existing pipe with 6A modular siwtch control and 3/2 pin sockets fixing on board including all labour charges This rate is including cost of material and all labour charges and other incidental charges etc., complete as per IE Rules and as directed by the departmental officer incharge of work .
supply and run of 2 of 36/0.3 mm. (1.5. sq.mm) Fire retardant PVC insulated Flexible copper cable in existing pipe for mains including all labour charges This rate is including cost of material and all labour charges and other incidental charges etc., complete as per IE Rules and as directed by the departmental officer incharge of work .
supply and run of 1 of 14/0.3 mm. (1.0. sq.mm) Fire retardant PVC insulated Flexible copper cable in existing pipe for earth continuity including all labour charges etc. This rate is including cost of material and all labour charges and other incidental charges etc., complete as per IE Rules and as directed by the departmental officer incharge of work .
supply and run of 2 of 6 sq.mm (7/18) WPSC alluminium cable along with No.10 SWG G.I barer wire through PVC cleats with all accessories including all labour charges etc.,This rate is including cost of material and all labour charges and other incidental charges etc., complete as per IE Rules and as directed by the departmental officer incharge of work .
Providing independent earthing by excavating a trench to a depth of 2.10m in all soils, as per size specied in data ,using 40 mm dia B class GI pipe 2.50m long with necessary accessories with hume pipe ring duly providing staggered holes including filling with equal proportion of salt and charcoal in layers and all labour charges etc complete This rate is including cost of material and all labour charges and other incidental charges etc., complete as per IE Rules and as directed by the departmental officer incharge of work .
Supply and fixing SPN Distribution board with IP-20 protection suitable for single phase Earth Leakage Circute Braker (ELCB) / Residual Current Circute Braker (RCCB) / Double Pole (DP) Isolator as incomer and 10kA SP MCBs as out going including internal connections and labour charges for surface / flush mounting etc., complete This rate is including cost of material and all labour charges and other incidental charges etc., complete as per IE Rules and as directed by the departmental officer incharge of work .
Supply and fixing of 48" (1200mm) Sweep Ceiling Fan including Regulator.of makes Crompton High Speed / Bajaj Ultima / Havells Velocity / Usha Astra / Orient Summer Pride. This rate including cost of material incidental charges etc.complete as per IE rule and as directed by the departmental officer in charge of work. But excluding labour charges.
Supply of stepped type Electronic Regulator of makes GM G Home / Gold Medal Olive / Million Zoom / Anchor Penta Cherry / Great white Omega.This rate including cost of material all labour charges incidental charges etc.complete as per IE rule and as directed by the departmental officer in charge of work
Supply of 9" (225mm), Light duty exhaust fan with double ball bearing and wire guard etc complete. Makes: Crompton / Bajaj Bahar WG / Havells Ventil Air-DS / Orient hill air / MIIT. This rate including cost of material all labour charges incidental charges etc.complete as per IE rule and as directed by the departmental officer in charge of work
Supply and fixing of 20W, 2400 lumens, T8 not lessthan 1100 mm length LED retrofit tube light with aluminum anodized body, input voltage AC 220 - 260 Volts, having luminous efficacy >=100 lumens/watt, with PF>0.9, surge protection: 2KV, THD<10%, with inbuilt driver and frosted cover CCT: 3000K- 5700K, minimum CRI>70, etc., as per IS 10322 (Part5/ Sec 1), 2012, complete with earth connection and not less than two years warranty. Makes: As per list of recommended brands as category
Labour charges for Fixing of Ceiling fan and regulator including transportation and giving connections with twin core wire etc., complete
Labour charges for fixing of Exhaust fan in wall with necessary connections and masonary work of making hole, finishing etc., complete
Labour charges Fixing of 40W tube light luminaire on wall / Ceiling with / TW round blocks with all accessories including giving connections and all labour charges etc., complete.
Providing & Placing on Terrace (at all floor levels) polyethylene water storage tank with Double layer approved brand & manufacture with cover and suitable locking arrangement & making necessary holes for inlet & outlets and over flow pipes but without fittings & base support for tanks as per SS and as directed by the departmental officer incharge of work .
Supplying and fixing 580mm x 440mm long Orissa pan white glazed Water Closet 1st quality ISI marked confirming to IS:2556-Part-3-1981 with "P" or "S" trap, ISI marked and providing masonry seat, CC squatting plate and 10 litres capacity single flush PVC low level cistern with internal components fixed on 2 Nos. of teak wood blocks of size 76.20mm x 101.60mm using required size of nails, screws as approved by Engineer-in-charge, 15 mm nominal size CP finish brass angled stop valve screw type with internal /external threaded conforming to IS 8931, 12.70mm PVC connection with brass union nuts CP coated , 31.75mm brass plumber union, P trap or S trap of Indian W.C. shall be encased on CC (1:2:4) 150mm alround well above the joint to stop leakage at the joint etc., complete including cost and conveyance of all materials to site, cost of CC bed, labour charges and seigniorage charges, overheads & contractors profit etc., complete for finished item of worke
Supplying and fixing Indian make Flat Back Wash Hand Basin 1st quality conforming to IS:2556-Part-4:1972 of size 550mm x 400mm with 32 mm nominal size C.P. Fitting with parallel pipe thread conforming to IS:2963-1979 and fitted with 15 mm nominal bore Chromium Plated Pillar Tap of 1st quality Indian make heavy duty complete with standard CI brackets including wooden blocks ,1 No.12.70mm PVC connection with brass union nuts CP coated , angle stop cock 12.70mm dia. first quality Indian make heavy duty, 30mm dia. PVC flexible waste pipe 914.4mm length of 1st quality including cost and conveyance of all materials to site, labour charges , overheads & contractors profit for finished item of work
Supplying and fixing CP finish brass soap dish of approved make ISI quality including cost and conveyance of all materials, labour charges for fixing , overheads & contractors profit for finished item of work in all floors
Supplying and fixing TV shape mirror with plastic frame of size 609.6mm x 457.2mm , plywood back with NP screws 1st quality including cost and conveyance of all materials, labour charges , overheads & contractors profit for finished item of work in all floors.
Supplying and fixing of 25.4mm dia , 609.6mm long aluminium anodized towel rods with brackets and aluminium screws including cost and conveyance of all materials, labour charges , overheads & contractors profit for finished item of work.
Supply of 110 mm dia 3 m single Socket PVC/SWR pipe - 6 Kg/sq.cm - Prince/Sudhakar/Kisan/Supreme or any ISI Brand.
Supply of 110 mm dia - Plain Bend 87.5 Degree - UPVC/SWR Pipe fittings (Prince/Sudhakar/Kisan/Supreme or any ISI Brand)
Supply of 110 mm dia - Coupler - UPVC/SWR Pipe fittings (Prince/Sudhakar/Kisan/Supreme or any ISI Brand
Labour charges for laying, fixing and commissioning the PVC pipes including couplers/ bends/ tees etc any diameter including fixing necessary fittings like bends, plugs, couplers, junctions, tees, etc with solvent jointing as per standard practice
Constructing 457.2 mm x 457.2 mm (1'6"x1'6") brick in CM 1:6 prop. Masonry. Inspection chamber up to 914.4 mm (3'0") and fitted with light weight 457.2 mm x 457.2 mm (1'6"x1'6") C.I frame and cover of 20 Kg
S& F GI pipe Medium Grade properties & weight as per IS 1239 ISI mark with GI fittings including the cost of pipe & its fittings & labour charges complete
25 mm dia nominal bore -from tank to jn for of individual lines
20 mm dia nominal bore -from jn for of individual lines to toilets & Kitchen
15 mm dia nominal bore -for internal
S&F of GI &GM fittings
GM Ball valve with SS Ball and SS Spindle as per IS - Class - I, Indian make heavy type - 25 mm NB Size
GM Ball valve with SS Ball and SS Spindle as per IS - Class - I, Indian make heavy type - 20 mm NB Size
GM Ball valve with SS Ball and SS Spindle as per IS - Class - I, Indian make heavy type - 15 mm NB Size
S&F 12.7 mm N.P bib tap Indian make heavy dutys Seiko/ Senior/ Nice or equivalent
S& F GI union Ist Quality
12.70mm GI union
19.05mm GI union
25.40mm GI union
For septic Tank
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD. Note : Classifications of Earth Work Specification are as per 302.2.1(a) of MORD and 301.2.1 of MORT&H--ordinary soil--manual means upto 3m depth by manual means upto 3.00m depth
Filling in foundation trenches as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH-sand filling. This rate including cost of material and all lbour charges, watering, ramming and other incidental charges etc., complete as directed by the departmental officer incharge of work .
Providing PCC 1:4:8 using 40 mm graded SS 5 HBG m/c metal and OPC coarse and fine aggregate confirming to IS 383 including cost and conveyance of all materials and labour charges, machine mixing , vibration,laying in position, curing etc., complete This rate including cost of material and all lbour charges, watering, ramming and other incidental charges etc., complete as directed by the departmental officer incharge of work .
Brick work in CM 1:5 mix using 2nd class bricks brought from approved kilns including cost and conveyance of all materials and all labour charges ,curing for 21 days etc complete as per ss for Septic tank walls as directed by the departmental officer incharge of work .
Cement plastering using opc in cm(1:3) prop 20 mm thick including cost of material, labour ,curing etc. complete as per SS out side & inside for Septic tank walls as directed by the departmental officer incharge
RCC M-20 Nominal mix (cement,fine aggregate,coarse aggregate) corresponding to Table -9 of IS -456 using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including seigniorage charges ,sales and other taxes on all materials including all operational ,incidental and labour charges such as machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work,but including centering,shuttering for Septic tank as directed by the departmental officer incharge
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying including sales and other taxes on all materials etc., complete for finished item of work in all floors.( APSS No.126)
Errection of 250 KVA Transformer at intermediate sump with Transformer yard 15.00x12.00m
Supply and erection of 7.5m long double pole structure fabricated with 150x75mm RS Joists,100x50mm MS channels, iron cross armstor fuse set and Lighting arrestrors etc.,including one coat of red oxide primer and two coats of bright Supply.This rate including cost of material and all bour charges, transporttion other incidental charges etc., complete as per IE Rules and as directed by the departmental officer incharge of work .
Supply of 11 KV 200A Gang operated Air break disconnecting switch complete with tandom bar, operating pipe, handle with badlock arrangements, 11 KV insulators etc This rate including cost of material and all bour charges, transporttion other incidental charges etc., complete as per IE Rules and as directed by the departmental officer incharge of work .
Supply and erection of 11 KV Horn gap fuse units complete with insulators, arcing horn etc.,This rate including cost of material and all bour charges, transporttion other incidental charges etc., complete as per IE Rules and as directed by the departmental officer incharge of work .
Supply and erection of 9 KV 5 KA auto valve distribution class lighting arresters suitable for use on 3 Ph. 11 KV 50 Hz system.This rate including cost of material and all bour charges, transporttion other incidental charges etc., complete as per IE Rules and as directed by the departmental officer incharge of work .
Supply and erection of 11KV Strain disc. Insulators with GI pins and top clamps This rate including cost of material and all bour charges, transporttion other incidental charges etc., complete as per IE Rules and as directed by the departmental officer incharge of work .
Supply and erection of 11 KV Pin Inuslators complete with GI pins and top clamps This rate including cost of material and all bour charges, transporttion other incidental charges etc., complete as per IE Rules and as directed by the departmental officer incharge of work .
Providing jumper connections with I/O' SWG HDBC wire between the 11 KV equipment on the outdoor structures This rate including cost of material and all bour charges, transporttion other incidental charges etc., complete as per IE Rules and as directed by the departmental officer incharge of work .
Providing stay sets for the structures complete with stay wire 11 KV guy insulators. Stay rod bow, thimble etx., This rate including cost of material and all bour charges, transporttion other incidental charges etc., complete as per IE Rules and as directed by the departmental officer incharge of work .
Providing efficient earthing arrangement forthe DP structure lighting arresters and the HV equipment. Transformer body and neutral etc., with 25 x 3 mm copper flats and connecting them to the Earth Electrodes fabricated and buried accroding to standard specifications and as per the details given below:This rate including cost of material and all bour charges, transporttion other incidental charges etc., complete as per IE Rules and as directed by the departmental officer incharge of work .
A) Earth Electrodes
B) 25 x 3 mm HDB copper flat
C) Epoxy insulators
D) No.'8' SWG Copper wire.
Supply and erection of 250 KVA, 11KV/433 V, DY-11 Vectro group, out door type, plinth mounting type, Hint /make transformer with bushings on HT side and cable entry box on L V side to received 1.1 KV grade cable with all standard accessories transformer oil. tansformer having copper wound natural cooled with all standard accessories This rate including cost of material and all bour charges, transporttion other incidental charges etc., complete as per IE Rules and as directed by the departmental officer incharge of work .
Supply and laying of 3.5 core x 400 sq.mm, 1.10 KV grade PVC insulated and armoured cable with alminium conductors This rate including cost of material and all bour charges, transporttion other incidental charges etc., complete as per IE Rules and as directed by the departmental officer incharge of work .
MAIN PANEL, BOARD.LT Sheet steelclad, free standing, floor mounting unitized, Duat and vermin proof Indoor, Cubicle powder coated panel board made out of 16 SWG CRCA sheet sheetable for use 3 ph, 440v, 50 Hz. System and comprising, complete with busbars of adeeequate capacity, interconnections,control wiring etc..as required.This rate including cost of material and all bour charges, transporttion other incidental charges etc., complete as per IE Rules and as directed by the departmental officer incharge of work .
Iicoming
a) . 630A TPN SFU for main switch This rate including cost of material and all bour charges, transporttion other incidental charges etc., complete as per IE Rules and as directed by the departmental officer incharge of work .
b) . 630 A pole change over switch This rate including cost of material and all bour charges, transporttion other incidental charges etc., complete as per IE Rules and as directed by the departmental officer incharge of work .
c) one set Metering Panel Comprisinga). 1( 0-500V) 96mm.SQ.flush type Digital Voltmeter.This rate including cost of material and all bour charges, transporttion other incidental charges etc., complete as per IE Rules and as directed by the departmental officer incharge of work .
e). ( 0-250A) 96mm SQ.flush type digital Ammeter This rate including cost of material and all bour charges, transporttion other incidental charges etc., complete as per IE Rules and as directed by the departmental officer incharge of work .
g).3RYB Phase indication lamps with leds This rate including cost of material and all bour charges, transporttion other incidental charges etc., complete as per IE Rules and as directed by the departmental officer incharge of work .
h).3-200/5A ration bar primary type current tranformers. (Alluminium busbar) This rate including cost of material and all bour charges, transporttion other incidental charges etc., complete as per IE Rules and as directed by the departmental officer incharge of work .
Out-Going
250 A TPN SFUs for CW pump house motors.This rate including cost of material and all bour charges, transporttion other incidental charges etc., complete as per IE Rules and as directed by the departmental officer incharge of work .
250 A TPN SFUs for compressor/mechanical equipments This rate including cost of material and all bour charges, transporttion other incidental charges etc., complete as per IE Rules and as directed by the departmental officer incharge of work .
250 A TPN SFUs for low lift sump Raw water motors.This rate including cost of material and all bour charges, transporttion other incidental charges etc., complete as per IE Rules and as directed by the departmental officer incharge of work .
160 A TPN SFUs for Space This rate including cost of material and all bour charges, transporttion other incidental charges etc., complete as per IE Rules and as directed by the departmental officer incharge of work .
160 a TPN SFUs fir lighting section This rate including cost of material and all bour charges, transporttion other incidental charges etc., complete as per IE Rules and as directed by the departmental officer incharge of work .
160 A 4 poles change over switch for lighting section This rate including cost of material and all bour charges, transporttion other incidental charges etc., complete as per IE Rules and as directed by the departmental officer incharge of work .
.KWH digital meter fro lighting section This rate including cost of material and all bour charges, transporttion other incidental charges etc., complete as per IE Rules and as directed by the departmental officer incharge of work .
4 nos-32 amps TPN Switch with HRC fuses and 1 No.10 KVAR capacitor bank total KVAR-40 This rate including cost of material and all bour charges, transporttion other incidental charges etc., complete as per IE Rules and as directed by the departmental officer incharge of work .
250KV.LT/Transformer transportation, Errection.testing Commensing and Supply of drawing layout plans of installed transformer in tracing cloth and duly get approved from electrical inspector APEPDCL and leaflets for various equipments and opearation manuals etc., complete.
Transformer yard at proposed intermediate sump Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH Note : Classifications of Earth Work Specification are as per 302.2.1(a) of MORD and 301.2.1 of MORT&H--ordinary soil--manual means upto 3m depth for foundations of buildings in restricted places By manual means
Providing river sand filling brought from approved quarry including cost and conveyance of all material and all labour charges such as filling in layers watering ramming etc complete as per ss and as directed by the departmental officer incharge of work .
Providing PCC 1:4:8 using 40 mm graded SS 5 HBG m/c metal and OPC coarse and fine aggregate confirming to IS 383 including cost and conveyance of all materials and labour charges, machine mixing , vibration,laying in position, curing etc., complete and as directed by the departmental officer incharge of work .
Supply and placing of the design mix concrete corresponding to IS -456 using WEIGH BATCHER/MIXER using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including seigniorage charges ,sales and other taxes on all materials including all operational ,incidental and labour charges such as weigh batching ,machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work (APSS NO 402) with minimum cement content as per IS Code from standard suppliers approved by the deparment including pumping , centering,shuttering,laying concrete, vibrating,curing etc M25 design mix concrete as follosws
column footings
Columns 1.20-0.10-0.10-0.30+1.80
Plinth beam 2(15+12)=54-gate3.00=51.00
Colour washing two coats using snowcem over the primery coat conveyance of all labour charges etc., and conveyance of maerials, all labour charges, scaffolding, watering etc complete as per ss and as directed by the departmental officer incharge of work (in and out side)
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying including sales and other taxes on all materials etc., complete for finished item of work in all floors.( APSS No.126)
Supplying and fixing galvanised steel barbed wire (IS : 278-1962 Type I) weighing 9.38 Kg per 100 metres (min.), Straining and fixing to any type of standard, rails, straining bolts, including securing with and provision of galvanised mild steel wire, stapples or steel pins, etc., as directed (Posts and struts of wood, concrete, steel, etc.) and straining bolts shall be paid for separately).
Manufacture,supply,delivery of MS grill gates,window ornamental safety grill ,made with MS flats,MS angles,MS squares etc including welding, finishing, applying red oxide paint as primary coat etc complete
Providind Synthic enamil paint two coats over the primery coat excluding cost of primer including cost and conveyance of all matrial and all labour charges etc complete as per ss
supply and filling the transformer yard with 40mm HBG metal m/c. This rate including cost of material, spreading charges, sectionng, other incidental charges etc., as directed by the departmental officer in charge of work
Filling site of proposed 13.00 MLD site 60x50m
Granular sub-base/base/surface course with local materials (Table 400.13) by mix in place method normal Construction of granular sub-base by providing local material spreading in uniform layers with motor grader on prepared surface, mixing by mix in place method with rotavator at once and compacting with smooth wheel roller to achieve the desired density complete as per Clause 401.4 as per Technical Specification Clause 408 MORD. using gravel payment made as per level payment Note : Classifications of Earth Work Specification are as per 302.2.1(a) of MORD and 301.2.1 of MORT&H--ordinary soil-- upto 3m depth
Providing LT electrical power line from WTP to intake well pumps
Cost data per KM of LT 3 Ph 4 wire line horizantal formation with 3x55 sqmm +1x34 sq mm AAAC conductor over 8.00m PSCC poles at 65m span,75 kg/sqm wind pressure working load 140 kgs 8.00m PSCC Poles LT 3 Phase cross arms Back clamp Stay set complete 55 sqmm conductor 34 sqmm conductor shackle insulator with metal parts LT pin insulator with pin CI kerb nob Concreting of poles, stay sets and base concreting Mis .items like coil earthing,pipe earthing,danger,bolts and nuts etc Amount Paybale AP Transco on Receipt of Invoice from the APTRANSCO are as directed by the depaartmental officer incharge of work
Construction of Compound wall and fencing to Head water works 100m compound wall ,200m fencing
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH
Crusher Stone Dust Filling of foundation trenches of Compound wall as per drawing and technical specification watering, ramming in Clause 305.3.9 MORD & 304 MORTH as per SS and as directed by the departmental officer incharge of work .
Plain Cement concrete (1:4:8) using 40 mm metal with concrete mixture including cost and conveyance of all materials, labour charges, machine mixing charges, curing charges etc., complete as per S.S.and other incidental charges etc., complete as per IE Rules and as directed by the departmental officer incharge of work .
VRCC M-25 Design l mix (Cement: fineaggregate: coarse aggregate) corresponding to Table 9 of IS 456 using 20mm size graded machine crushed hard granite metal (coarse aggregate) from approved quarry including cost and conveyance of all materials like cement, fine aggregate (sand) coarse aggregate, water etc., to site and including Seigniorage charges, sales & other taxes on all materials including all operational, incidental and labour charges such as machine mixing, laying concrete, curing etc., complete but excluding cost of steel and its fabrication charges for finished item of work, including centering, shutteing for RAFT. ( with Skin reinforcement)
VRCC M-25 Design l mix (Cement: fineaggregate: coarse aggregate) corresponding to Table 9 of IS 456 using 20mm size graded machine crushed hard granite metal (coarse aggregate) from approved quarry including cost and conveyance of all materials like cement, fine aggregate (sand) coarse aggregate, water etc., to site and including Seigniorage charges, sales & other taxes on all materials including all operational, incidental and labour charges such as machine mixing, laying concrete, curing etc., complete but excluding cost of steel and its fabrication charges for finished item of work, including centering, shutteing for Retaing Walls ( with Skin reinforcement)
Supplying, Fitting and placing HYSD bar reinforcement in foundation complete as per drawings and technical specifications for Bars below 36mm dia including over laps and wastage, where they are not welded.
Bailing out water from the trenches with oil engine driven pump sets, including hire charges, fuel charges and wages for Driver and Helper upto 5HP capacity pumps as per SS and as directed by the departmental officer incharge of work .
Construction of 800 KL ELSR with 18m staging at Govt college zone -II
Construction of ELSR With the following specification 800 kl capacity with a staging of 18 m, with Seismic analysis.
All concrete components shall be designed with M30 Design Mix proportion
The foundations shall be designed for Annular Raft Footings.
Rate inclusive of three coats of epoxy paint Food Grade of best quality to inner surface of the Reservoir including roof.
The above rates are adopted for preparation of estimate for construction of ELSRs/OHSRs for finished work including 2 coats of weather proof emulsion painting for external surfaces, lettering, all required fixtures, Pipes,Pipe specials, valves of DI material, Valve chambers etc., for pipe connections including cost of pipes,specials and valves as per departmental designs and drawings.
The above rates adopted for a wind pressure upto "350 kg/sq m". For every 100 kg/sqm decrease in wind pressure, the rate shall be decreased by 5%
The Basic rate is adopted by considering the design for Seismic forces for Zone-I & II only of seismic zones
The basic rates shall be increased by 33 1/3% for Zone-III of seismic zones
The ELSR/OHSR shall be designed with minimum of two rows of columns for capacities above 500 KL & upto 1000KL The ELSR/OHSR shall be designed with minimum of three rows of columns for capacities above 1000KL.
i) Pipe connections & Specials with D.I materials
All pipe conections for Inlet, Out let, Over Flow, Scour pipes shall be provided with D/F DI material. The Valves for above pipe connections also shall be of DI material of PN16 All specials such as Bends,Tees, Reducers, Duckfoot Bends,Bell mouths etc,. shall be of DI material
The sizes of the verticals for ELSR/OHSR shall be:
Above 1000KL three rows columns shall be provided
For 500 KL to 750 Kl ELSRs Inlet Pipe - 300mm dia. Out let Pipe - 350mm dia Over Flow pipe - 350m dia Scour Pipe - 200mm dia
For 800 KL to 1500 Kl ELSRs Inlet Pipe - 400mm dia. Out let Pipe - 450mm dia Over Flow pipe - 450m dia Scour Pipe - 200mm dia
For above 1500 KL to 2500 Kl ELSRs Inlet Pipe - 400mm dia. Out let Pipe - 500mm dia Over Flow pipe - 500m dia Scour Pipe - 200mm dia
Manhole Frames & Covers
All man hole Frames & Covers shall be made of CI/DI materials with min. size of 0.60mX 0.60m - For Roof & Valve Chambers
CI/D.I Double Swan neck ventilators (min.of 150mm dia) shall be provided in top dome and slab with mosquito/fly proof nets - 4Nos
RCC Finial ventilator with fly/bird protection with GI mesh - 1 No.
RCC precast ladders of 0.60 m width - 2 Nos.
RCC dog legged stair case of 1.00 m flight width and 1.20 m landing width R.C.C hand railing of 1.0 m height – 1 No
The staircase shall be enclosed with brick masonary walls on three side and collapsible MS gate on front side up to 1st brace level, to prevent unauthorized entry
Construction of R.C.C valve chambers as per Standard Drawings with RCC cover slab fixed with CI/DI manhole Frame & Cover with lock and Key arrangement.The Mix shall not be less than VRCC M 20 grade with 150mm thick side walls, 150mm thick top slab, 150mm thick base slab over base course of 100mm thick (1:4:8) prop.
Balcony of 1.00 m width at floor slab level / middle ring beam level by using Stainless Steel pipe of grade 304 hand railing up to 1.20 m height,with top railing of 40mm dia pipe & middle railing of 25mm dia and verticals with 40mm dia at an interval not more than of 1.00m c/c.
Water Level Indicator of reputed make – Digital type (1 No) and Conventional type (1 No).
Lightening Arrestor with all its accessories complete including earthing,with relevant IS Codes - 1 No.
Compound wall: Construction of compound wall including ornamentalM.S.Gate of size 3.0 X 2.40m is included in the basic rate of ELSRs. Length of compound wall hall be minimum of 150m. Min. height of the compound wall shall be 1.80m above plinth and thickness 230mm in brick masonry in CM(1:6).The compound wall shall be constructed including earth work excavation in all types of soils for plinth beam of 230mm X 300mm and 0.75X0.75X1.20m size for column footing portions. The footings shall be of0.75X0.75X0.25m in VRCC M20 grade and constructed over a C.C(1:4:8)prop bed of 100mm thick. The columns shall be of 230X230 mm in size with VRCC M20 grade at 3.00m c/c spacing, having depth of 1.20m below ground level and height of 2.00m above GL. The plinth beam of size of 230X300 mm shall be constructed in VRCC M20 grade at Gound level over a bed of CC(1:4:8)-100mmthick. 450X450mm size columns in M20 grade shall be constructed for gate pillars. All the materials shall be followed as per the standards grade shall be constructed for gate pillars. All the materials shall be followed as per the standards.
Tie beam shall be provided above the brick work with 230X200mm size,fixed with MS angulars of 25mm X 25mm X 4mm in "Y" shape to hieght of 0.60m, with embedded length of 150mm in concrete. The barbed wire fencing with 3 ply of 18 gauge shall be streched in 4 rows (2x2). Plastering shall be done with 16mm thick in two coats i.e., base coat 12mm thick in CM(1:6)prop and 4mm thick 2nd coat CM(1:4) prop on both sides of brickwork.
Snowcem paint in two coats shall be provided for both sides of wall. The M.S ornamental gate as per the approved drawings shall be provided with minimum of 3.60mts width and 2.40mts height with enamel paint. Yard lighting shall be arranged on four corners of compound wall. If the length of the wall is increased/decreased
Note:-For every 1m increase/decrease in length of compound wall the increase/decrease in basic rates of ELSRs of the capacities from 500KL to 2500KL shall be as follows.: i) 500 KL : 0.086% ii) 1000 KL : 0.047% iii) 1500 KL : 0.034% iv) 2000 KL : 0.026% v) 2500 KL : 0.022 % For intermediate capacities, interpolated percentages shall be adopted
Staff Quarter shall be constructed for a minimum plinth area of 40 sqm with the following specification: RCC framed structure withconcrete grade not less than M20 design mix at the locations specified by the department at the time of execution with verandah, hall, bed room, kitchen and bath &W/C with floor area of 40.00sqmts excluding balconies and staircases
MS hollow door frame with cold rolled processed steel sheet 1.25mm thick bright CRCA conforming to IS 4351/76, Flush door shutters with solid bond wood bond board doors shall be provided. N.C.L. Windows centre fixed both sides openable shutter window 1.35 X 1.35mts outer frame section 48x50mm shutter frame section with a size of 48 X20 mm mullion section of size 48 X 50mm fixed beading section of 12 X 12 mm shall be provided.Flooring with polished Kadapa stone shall be provided. Walls shall be provided with snowcem paint in two coats over primary coat. Electrical and water supply arrangement shall be provided as directed by dept officer.Water Storage tank made with plastic/polymer material of reputed makewith necessary out let and inlet connection pipes shall provided. Septic tank for 5 users shall be provided.
800 KL ELSR
deduct items covered under SCADA
inlet sluice valve 250mm
out let sluice valve 350mm
inlet non return valve 250mm
lowering of valves 250 mm dia
lowering of valves 350 mm dia
jointing of valves 250 mm dia
jointing of valves350 mm dia
Construction of 1000 KL ELSR with 18m staging at santha market zone -III
Construction of ELSR With the following specification 1000 kl capacity with a staging of 18 m, with Seismic analysis.
All concrete components shall be designed with M30 Design Mix proportion
The foundations shall be designed for Annular Raft Footings.
Rate inclusive of three coats of epoxy paint Food Grade of best quality to inner surface of the Reservoir including roof.
The above rates are adopted for preparation of estimate for construction of ELSRs/OHSRs for finished work including 2 coats of weather proof emulsion painting for external surfaces, lettering, all required fixtures, Pipes,Pipe specials, valves of DI material, Valve chambers etc., for pipe connections including cost of pipes,specials and valves as per departmental designs and drawings.
The above rates adopted for a wind pressure upto "350 kg/sq m". For every 100 kg/sqm decrease in wind pressure, the rate shall be decreased by 5%
The Basic rate is adopted by considering the design for Seismic forces for Zone-I & II only of seismic zones
The basic rates shall be increased by 33 1/3% for Zone-III of seismic zones
The ELSR/OHSR shall be designed with minimum of two rows of columns for capacities above 500 KL & upto 1000KL The ELSR/OHSR shall be designed with minimum of three rows of columns for capacities above 1000KL.
i) Pipe connections & Specials with D.I materials
All pipe conections for Inlet, Out let, Over Flow, Scour pipes shall be provided with D/F DI material. The Valves for above pipe connections also shall be of DI material of PN16 All specials such as Bends,Tees, Reducers, Duckfoot Bends,Bell mouths etc,. shall be of DI material
The sizes of the verticals for ELSR/OHSR shall be:
Above 1000KL three rows columns shall be provided
For 500 KL to 750 Kl ELSRs Inlet Pipe - 300mm dia. Out let Pipe - 350mm dia Over Flow pipe - 350m dia Scour Pipe - 200mm dia
For 800 KL to 1500 Kl ELSRs Inlet Pipe - 400mm dia. Out let Pipe - 450mm dia Over Flow pipe - 450m dia Scour Pipe - 200mm dia
For above 1500 KL to 2500 Kl ELSRs Inlet Pipe - 400mm dia. Out let Pipe - 500mm dia Over Flow pipe - 500m dia Scour Pipe - 200mm dia
Manhole Frames & Covers
All man hole Frames & Covers shall be made of CI/DI materials with min. size of 0.60mX 0.60m - For Roof & Valve Chambers
CI/D.I Double Swan neck ventilators (min.of 150mm dia) shall be provided in top dome and slab with mosquito/fly proof nets - 4Nos
RCC Finial ventilator with fly/bird protection with GI mesh - 1 No.
RCC precast ladders of 0.60 m width - 2 Nos.
RCC dog legged stair case of 1.00 m flight width and 1.20 m landing width R.C.C hand railing of 1.0 m height – 1 No
The staircase shall be enclosed with brick masonary walls on three side and collapsible MS gate on front side up to 1st brace level, to prevent unauthorized entry
Construction of R.C.C valve chambers as per Standard Drawings with RCC cover slab fixed with CI/DI manhole Frame & Cover with lock and Key arrangement.The Mix shall not be less than VRCC M 20 grade with 150mm thick side walls, 150mm thick top slab, 150mm thick base slab over base course of 100mm thick (1:4:8) prop.
Balcony of 1.00 m width at floor slab level / middle ring beam level by using Stainless Steel pipe of grade 304 hand railing up to 1.20 m height,with top railing of 40mm dia pipe & middle railing of 25mm dia and verticals with 40mm dia at an interval not more than of 1.00m c/c.
Water Level Indicator of reputed make – Digital type (1 No) and Conventional type (1 No).
Lightening Arrestor with all its accessories complete including earthing,with relevant IS Codes - 1 No.
Compound wall: Construction of compound wall including ornamentalM.S.Gate of size 3.0 X 2.40m is included in the basic rate of ELSRs. Length of compound wall hall be minimum of 150m. Min. height of the compound wall shall be 1.80m above plinth and thickness 230mm in brick masonry in CM(1:6).The compound wall shall be constructed including earth work excavation in all types of soils for plinth beam of 230mm X 300mm and 0.75X0.75X1.20m size for column footing portions. The footings shall be of0.75X0.75X0.25m in VRCC M20 grade and constructed over a C.C(1:4:8)prop bed of 100mm thick. The columns shall be of 230X230 mm in size with VRCC M20 grade at 3.00m c/c spacing, having depth of 1.20m below ground level and height of 2.00m above GL. The plinth beam of size of 230X300 mm shall be constructed in VRCC M20 grade at Gound level over a bed of CC(1:4:8)-100mmthick. 450X450mm size columns in M20 grade shall be constructed for gate pillars. All the materials shall be followed as per the standards grade shall be constructed for gate pillars. All the materials shall be followed as per the standards.
Tie beam shall be provided above the brick work with 230X200mm size,fixed with MS angulars of 25mm X 25mm X 4mm in "Y" shape to hieght of 0.60m, with embedded length of 150mm in concrete. The barbed wire fencing with 3 ply of 18 gauge shall be streched in 4 rows (2x2). Plastering shall be done with 16mm thick in two coats i.e., base coat 12mm thick in CM(1:6)prop and 4mm thick 2nd coat CM(1:4) prop on both sides of brickwork.
Snowcem paint in two coats shall be provided for both sides of wall. The M.S ornamental gate as per the approved drawings shall be provided with minimum of 3.60mts width and 2.40mts height with enamel paint. Yard lighting shall be arranged on four corners of compound wall. If the length of the wall is increased/decreased
Note:-For every 1m increase/decrease in length of compound wall the increase/decrease in basic rates of ELSRs of the capacities from 500KL to 2500KL shall be as follows.: i) 500 KL : 0.086% ii) 1000 KL : 0.047% iii) 1500 KL : 0.034% iv) 2000 KL : 0.026% v) 2500 KL : 0.022 % For intermediate capacities, interpolated percentages shall be adopted
Staff Quarter shall be constructed for a minimum plinth area of 40 sqm with the following specification: RCC framed structure withconcrete grade not less than M20 design mix at the locations specified by the department at the time of execution with verandah, hall, bed room, kitchen and bath &W/C with floor area of 40.00sqmts excluding balconies and staircases
MS hollow door frame with cold rolled processed steel sheet 1.25mm thick bright CRCA conforming to IS 4351/76, Flush door shutters with solid bond wood bond board doors shall be provided. N.C.L. Windows centre fixed both sides openable shutter window 1.35 X 1.35mts outer frame section 48x50mm shutter frame section with a size of 48 X20 mm mullion section of size 48 X 50mm fixed beading section of 12 X 12 mm shall be provided.Flooring with polished Kadapa stone shall be provided. Walls shall be provided with snowcem paint in two coats over primary coat. Electrical and water supply arrangement shall be provided as directed by dept officer.Water Storage tank made with plastic/polymer material of reputed makewith necessary out let and inlet connection pipes shall provided. Septic tank for 5 users shall be provided.
1000 KL ELSR
deduct items covered under SCADA
inlet sluice valve 350mm
out let sluice valve 350mm
inlet non return valve350mm
lowering of valves 350 mm dia
lowering of valves 350 mm dia
jointing of valves 250 mm dia
jointing of valves350 mm dia
Construction of 900 KL ELSR with 18m staging at Balaji Town ship zone -IV
Construction of ELSR With the following specification 900 kl capacity with a staging of 18 m, with Seismic analysis.
All concrete components shall be designed with M30 Design Mix proportion
The foundations shall be designed for Annular Raft Footings.
Rate inclusive of three coats of epoxy paint Food Grade of best quality to inner surface of the Reservoir including roof.
The above rates are adopted for preparation of estimate for construction of ELSRs/OHSRs for finished work including 2 coats of weather proof emulsion painting for external surfaces, lettering, all required fixtures, Pipes,Pipe specials, valves of DI material, Valve chambers etc., for pipe connections including cost of pipes,specials and valves as per departmental designs and drawings.
The above rates adopted for a wind pressure upto "350 kg/sq m". For every 100 kg/sqm decrease in wind pressure, the rate shall be decreased by 5%
The Basic rate is adopted by considering the design for Seismic forces for Zone-I & II only of seismic zones
The basic rates shall be increased by 33 1/3% for Zone-III of seismic zones
The ELSR/OHSR shall be designed with minimum of two rows of columns for capacities above 500 KL & upto 1000KL The ELSR/OHSR shall be designed with minimum of three rows of columns for capacities above 1000KL.
i) Pipe connections & Specials with D.I materials
All pipe conections for Inlet, Out let, Over Flow, Scour pipes shall be provided with D/F DI material. The Valves for above pipe connections also shall be of DI material of PN16 All specials such as Bends,Tees, Reducers, Duckfoot Bends,Bell mouths etc,. shall be of DI material
The sizes of the verticals for ELSR/OHSR shall be:
Above 1000KL three rows columns shall be provided
For 500 KL to 750 Kl ELSRs Inlet Pipe - 300mm dia. Out let Pipe - 350mm dia Over Flow pipe - 350m dia Scour Pipe - 200mm dia
For 800 KL to 1500 Kl ELSRs Inlet Pipe - 400mm dia. Out let Pipe - 450mm dia Over Flow pipe - 450m dia Scour Pipe - 200mm dia
For above 1500 KL to 2500 Kl ELSRs Inlet Pipe - 400mm dia. Out let Pipe - 500mm dia Over Flow pipe - 500m dia Scour Pipe - 200mm dia
Manhole Frames & Covers
All man hole Frames & Covers shall be made of CI/DI materials with min. size of 0.60mX 0.60m - For Roof & Valve Chambers
CI/D.I Double Swan neck ventilators (min.of 150mm dia) shall be provided in top dome and slab with mosquito/fly proof nets - 4Nos
RCC Finial ventilator with fly/bird protection with GI mesh - 1 No.
RCC precast ladders of 0.60 m width - 2 Nos.
RCC dog legged stair case of 1.00 m flight width and 1.20 m landing width R.C.C hand railing of 1.0 m height – 1 No
The staircase shall be enclosed with brick masonary walls on three side and collapsible MS gate on front side up to 1st brace level, to prevent unauthorized entry
Construction of R.C.C valve chambers as per Standard Drawings with RCC cover slab fixed with CI/DI manhole Frame & Cover with lock and Key arrangement.The Mix shall not be less than VRCC M 20 grade with 150mm thick side walls, 150mm thick top slab, 150mm thick base slab over base course of 100mm thick (1:4:8) prop.
Balcony of 1.00 m width at floor slab level / middle ring beam level by using Stainless Steel pipe of grade 304 hand railing up to 1.20 m height,with top railing of 40mm dia pipe & middle railing of 25mm dia and verticals with 40mm dia at an interval not more than of 1.00m c/c.
Water Level Indicator of reputed make – Digital type (1 No) and Conventional type (1 No).
Lightening Arrestor with all its accessories complete including earthing,with relevant IS Codes - 1 No.
Compound wall: Construction of compound wall including ornamentalM.S.Gate of size 3.0 X 2.40m is included in the basic rate of ELSRs. Length of compound wall hall be minimum of 150m. Min. height of the compound wall shall be 1.80m above plinth and thickness 230mm in brick masonry in CM(1:6).The compound wall shall be constructed including earth work excavation in all types of soils for plinth beam of 230mm X 300mm and 0.75X0.75X1.20m size for column footing portions. The footings shall be of0.75X0.75X0.25m in VRCC M20 grade and constructed over a C.C(1:4:8)prop bed of 100mm thick. The columns shall be of 230X230 mm in size with VRCC M20 grade at 3.00m c/c spacing, having depth of 1.20m below ground level and height of 2.00m above GL. The plinth beam of size of 230X300 mm shall be constructed in VRCC M20 grade at Gound level over a bed of CC(1:4:8)-100mmthick. 450X450mm size columns in M20 grade shall be constructed for gate pillars. All the materials shall be followed as per the standards grade shall be constructed for gate pillars. All the materials shall be followed as per the standards.
Tie beam shall be provided above the brick work with 230X200mm size,fixed with MS angulars of 25mm X 25mm X 4mm in "Y" shape to hieght of 0.60m, with embedded length of 150mm in concrete. The barbed wire fencing with 3 ply of 18 gauge shall be streched in 4 rows (2x2). Plastering shall be done with 16mm thick in two coats i.e., base coat 12mm thick in CM(1:6)prop and 4mm thick 2nd coat CM(1:4) prop on both sides of brickwork.
Snowcem paint in two coats shall be provided for both sides of wall. The M.S ornamental gate as per the approved drawings shall be provided with minimum of 3.60mts width and 2.40mts height with enamel paint. Yard lighting shall be arranged on four corners of compound wall. If the length of the wall is increased/decreased
Note:-For every 1m increase/decrease in length of compound wall the increase/decrease in basic rates of ELSRs of the capacities from 500KL to 2500KL shall be as follows.: i) 500 KL : 0.086% ii) 1000 KL : 0.047% iii) 1500 KL : 0.034% iv) 2000 KL : 0.026% v) 2500 KL : 0.022 % For intermediate capacities, interpolated percentages shall be adopted
Staff Quarter shall be constructed for a minimum plinth area of 40 sqm with the following specification: RCC framed structure withconcrete grade not less than M20 design mix at the locations specified by the department at the time of execution with verandah, hall, bed room, kitchen and bath &W/C with floor area of 40.00sqmts excluding balconies and staircases
MS hollow door frame with cold rolled processed steel sheet 1.25mm thick bright CRCA conforming to IS 4351/76, Flush door shutters with solid bond wood bond board doors shall be provided. N.C.L. Windows centre fixed both sides openable shutter window 1.35 X 1.35mts outer frame section 48x50mm shutter frame section with a size of 48 X20 mm mullion section of size 48 X 50mm fixed beading section of 12 X 12 mm shall be provided.Flooring with polished Kadapa stone shall be provided. Walls shall be provided with snowcem paint in two coats over primary coat. Electrical and water supply arrangement shall be provided as directed by dept officer.Water Storage tank made with plastic/polymer material of reputed makewith necessary out let and inlet connection pipes shall provided. Septic tank for 5 users shall be provided.
900 KL ELSR
deduct items covered under SCADA
inlet sluice valve 250mm
out let sluice valve 350mm
inlet non return valve 250mm
lowering of valves 250 mm dia
lowering of valves 350 mm dia
jointing of valves 250 mm dia
jointing of valves350 mm dia
Construction of 800 KL ELSR with 18m staging at Upperametta zone -V with Seismic analysis.
Construction of ELSR With the following specification 800 kl capacity with a staging of 18 m, with Seismic analysis.
All concrete components shall be designed with M30 Design Mix proportion
The foundations shall be designed for Annular Raft Footings.
Rate inclusive of three coats of epoxy paint Food Grade of best quality to inner surface of the Reservoir including roof.
The above rates are adopted for preparation of estimate for construction of ELSRs/OHSRs for finished work including 2 coats of weather proof emulsion painting for external surfaces, lettering, all required fixtures, Pipes,Pipe specials, valves of DI material, Valve chambers etc., for pipe connections including cost of pipes,specials and valves as per departmental designs and drawings.
The above rates adopted for a wind pressure upto "350 kg/sq m". For every 100 kg/sqm decrease in wind pressure, the rate shall be decreased by 5%
The Basic rate is adopted by considering the design for Seismic forces for Zone-I & II only of seismic zones
The basic rates shall be increased by 33 1/3% for Zone-III of seismic zones
The ELSR/OHSR shall be designed with minimum of two rows of columns for capacities above 500 KL & upto 1000KL The ELSR/OHSR shall be designed with minimum of three rows of columns for capacities above 1000KL.
i) Pipe connections & Specials with D.I materials
All pipe conections for Inlet, Out let, Over Flow, Scour pipes shall be provided with D/F DI material. The Valves for above pipe connections also shall be of DI material of PN16 All specials such as Bends,Tees, Reducers, Duckfoot Bends,Bell mouths etc,. shall be of DI material
The sizes of the verticals for ELSR/OHSR shall be:
Above 1000KL three rows columns shall be provided
For 500 KL to 750 Kl ELSRs Inlet Pipe - 300mm dia. Out let Pipe - 350mm dia Over Flow pipe - 350m dia Scour Pipe - 200mm dia
For 800 KL to 1500 Kl ELSRs Inlet Pipe - 400mm dia. Out let Pipe - 450mm dia Over Flow pipe - 450m dia Scour Pipe - 200mm dia
For above 1500 KL to 2500 Kl ELSRs Inlet Pipe - 400mm dia. Out let Pipe - 500mm dia Over Flow pipe - 500m dia Scour Pipe - 200mm dia
Manhole Frames & Covers
All man hole Frames & Covers shall be made of CI/DI materials with min. size of 0.60mX 0.60m - For Roof & Valve Chambers
CI/D.I Double Swan neck ventilators (min.of 150mm dia) shall be provided in top dome and slab with mosquito/fly proof nets - 4Nos
RCC Finial ventilator with fly/bird protection with GI mesh - 1 No.
RCC precast ladders of 0.60 m width - 2 Nos.
RCC dog legged stair case of 1.00 m flight width and 1.20 m landing width R.C.C hand railing of 1.0 m height – 1 No
The staircase shall be enclosed with brick masonary walls on three side and collapsible MS gate on front side up to 1st brace level, to prevent unauthorized entry
Construction of R.C.C valve chambers as per Standard Drawings with RCC cover slab fixed with CI/DI manhole Frame & Cover with lock and Key arrangement.The Mix shall not be less than VRCC M 20 grade with 150mm thick side walls, 150mm thick top slab, 150mm thick base slab over base course of 100mm thick (1:4:8) prop.
Balcony of 1.00 m width at floor slab level / middle ring beam level by using Stainless Steel pipe of grade 304 hand railing up to 1.20 m height,with top railing of 40mm dia pipe & middle railing of 25mm dia and verticals with 40mm dia at an interval not more than of 1.00m c/c.
Water Level Indicator of reputed make – Digital type (1 No) and Conventional type (1 No).
Lightening Arrestor with all its accessories complete including earthing,with relevant IS Codes - 1 No.
Compound wall: Construction of compound wall including ornamentalM.S.Gate of size 3.0 X 2.40m is included in the basic rate of ELSRs. Length of compound wall hall be minimum of 150m. Min. height of the compound wall shall be 1.80m above plinth and thickness 230mm in brick masonry in CM(1:6).The compound wall shall be constructed including earth work excavation in all types of soils for plinth beam of 230mm X 300mm and 0.75X0.75X1.20m size for column footing portions. The footings shall be of0.75X0.75X0.25m in VRCC M20 grade and constructed over a C.C(1:4:8)prop bed of 100mm thick. The columns shall be of 230X230 mm in size with VRCC M20 grade at 3.00m c/c spacing, having depth of 1.20m below ground level and height of 2.00m above GL. The plinth beam of size of 230X300 mm shall be constructed in VRCC M20 grade at Gound level over a bed of CC(1:4:8)-100mmthick. 450X450mm size columns in M20 grade shall be constructed for gate pillars. All the materials shall be followed as per the standards grade shall be constructed for gate pillars. All the materials shall be followed as per the standards.
Tie beam shall be provided above the brick work with 230X200mm size,fixed with MS angulars of 25mm X 25mm X 4mm in "Y" shape to hieght of 0.60m, with embedded length of 150mm in concrete. The barbed wire fencing with 3 ply of 18 gauge shall be streched in 4 rows (2x2). Plastering shall be done with 16mm thick in two coats i.e., base coat 12mm thick in CM(1:6)prop and 4mm thick 2nd coat CM(1:4) prop on both sides of brickwork.
Snowcem paint in two coats shall be provided for both sides of wall. The M.S ornamental gate as per the approved drawings shall be provided with minimum of 3.60mts width and 2.40mts height with enamel paint. Yard lighting shall be arranged on four corners of compound wall. If the length of the wall is increased/decreased
Note:-For every 1m increase/decrease in length of compound wall the increase/decrease in basic rates of ELSRs of the capacities from 500KL to 2500KL shall be as follows.: i) 500 KL : 0.086% ii) 1000 KL : 0.047% iii) 1500 KL : 0.034% iv) 2000 KL : 0.026% v) 2500 KL : 0.022 % For intermediate capacities, interpolated percentages shall be adopted
Staff Quarter shall be constructed for a minimum plinth area of 40 sqm with the following specification: RCC framed structure withconcrete grade not less than M20 design mix at the locations specified by the department at the time of execution with verandah, hall, bed room, kitchen and bath &W/C with floor area of 40.00sqmts excluding balconies and staircases
MS hollow door frame with cold rolled processed steel sheet 1.25mm thick bright CRCA conforming to IS 4351/76, Flush door shutters with solid bond wood bond board doors shall be provided. N.C.L. Windows centre fixed both sides openable shutter window 1.35 X 1.35mts outer frame section 48x50mm shutter frame section with a size of 48 X20 mm mullion section of size 48 X 50mm fixed beading section of 12 X 12 mm shall be provided.Flooring with polished Kadapa stone shall be provided. Walls shall be provided with snowcem paint in two coats over primary coat. Electrical and water supply arrangement shall be provided as directed by dept officer.Water Storage tank made with plastic/polymer material of reputed makewith necessary out let and inlet connection pipes shall provided. Septic tank for 5 users shall be provided.
800 KL ELSR
deduct items covered under SCADA
inlet sluice valve 250mm
out let sluice valve 350mm
inlet non return valve 250mm
lowering of valves 250 mm dia
lowering of valves 350 mm dia
jointing of valves 250 mm dia
jointing of valves350 mm dia
Construction 1000 KL GLSR Hill lock near Rajivi nagar zone-I
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH for foundations upto 3.00m depth Note : Classifications of Earth Work Specification are as per 302.2.1(a) of MORD and 301.2.1 of MORT&H--ordinary soil-- for the following depth
for GLSR foundations 0-3.00m Machanical means
for GLSR foundations 3.00-6.00m Machanical means
Mechanical means 3 to 6 metres in ordinary soils
Manual Means 3 to 6 metres in ordinary soils
Filling in foundation trenches as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH for foundations RBR-FNDN-2(1)
Plain cement concrete (1:4:8) using 40mm m/c SS5 HBG including machine mixing, laying, compacting, finishing, curing etc for foundations bed concrete as directed by the departmental officer incharge of work .
Supply and placing of the design mix concrete corresponding to IS -456 using WEIGH BATCHER/MIXER using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including seigniorage charges ,sales and other taxes on all materials including all operational ,incidental and labour charges such as weigh batching ,machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work (APSS NO 402) with minimum cement content as per IS Code from standard suppliers approved by the deparment including pumping , centering,shuttering,laying concrete ,vibrating,curing etc M30 design mix concrete with concrete mixer as follows
For side walls circular 0.30m thick below GL
For side walls circular 0.30m thick below GL
For side walls circular 0.30m thick above GL
Columns 0.30 x 0.30m 3.60-0.30
Roof beams
Roof slab 0.15m thick 0.786x(18.600^2-7.00^2)
Roof dome slab 0.15m thick
Providing impervious coat to exposed RCC roof slab surface with CM(1:3), 20mm thick with 1kg of water proof compound per bag of cement laid over roof when it is green including cost of all materials, seigniorage charges, excluding conveyance charges of materials and including all operational, incidental and labour charges for mixing mortar, laying, rendering smooth and thread lining, curing, rounding off junctions of wall and slab etc,, complete for finished item of work
Providing Painting walls with snowcern or equivalent paint two coats by using approved water proof paint grade-1 over one coat prime coat by using cement primary coat by using cement primer making 3 coats including cost of Colour washing two coats Using snowcem including cost cost of material and all bour charges, transporttion other incidental charges etc., complete as directed by the departmental officer incharge of work .
Supply and delivery and fixing in position M S grill of any design including all fabrication and all fixing charges etc compalete as per ss and as directed by the dept authorities for Man hole cover and ladder as per SS and as directed by the departmental officer incharge of work .
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying including sales and other taxes on all materials etc., complete for finished item of work in all floors.( APSS No.126)
Construction of R.C.C. railing of M 25 grade in cast-in-situ with 20 mm nominal size aggregate, true to line and grade-3 tire, tolerance of vertical railing post not to exceed 1 in 500, centre-to-centre spacing between vertical posts not to exceed 2000 mm as per drawing and technical specifications Clauses 800, 900 and 1208.3 MORD.
Inlet,out let,scour and over flow arrengements
Centrifugally cast (spun) Ductile Iron Fittings conforming to IS:9523/2000 having dimensions as per table. The rates mentioned here under are for fittings, zinc coated externally with inside mortar lining (with finishing as per class 13/IS 9523/2000) ( ex-works) including Transportation,Excluding Taxes and Duties etc and other incidental charges etc., complete as per as directed by the departmental officer incharge of work . as follows
250 mm dia 2.00m long DIDF pipes
250 mm dia 1.00m long DIDF pipes
150 mm dia 2.00m long DIDF pipes
150 mm dia 1.00m long DIDF pipes
350 mm dia 2.00m long DIDF pipes
350 mm dia 1.00m long DIDF pipes
Supply, delivery of D.I. fittings confirming to I.S.No.9523/2000 having dimensions upto 500mm dia as per table with Zinc coated externally and inside Cement Mortar lining (With finishing as per Class 13/IS 9523/2000) including cost of fittings, transportation, stacking carefully at site. etc.,complete as per S.S. and as directed by the departmental authorities.
Manufacture, Supply and delivery of 150mm dia DI D/F Gate Valves (Soft Seated) Resilient seated soft sealing gate valves (Sluice valves) with body bonnet of ductile cast iron of grade GGG40/ SG 400/12 or equivalent grade as per I.S.3896-part2-1985 and subsequent revisions, wedge fully rubber lined with EPDM food grade quality and seals of NBR and the valves should be of vacuum tight and 100% leak proof with face to face dimensions as per BS5163-89/IS14846-2000/DIN 3202 F 4. All the valves should be with Electrostatic powder coating both inside and outside pocket less body passage. Drilled as per IS:1538. PN16
Labour charges for 150mm dia lowering and keeping in position of C.I./DI Sluice valves(with cap/with hand wheel), reflux valves and scour valves.
Lowering the C.I. Pipes, D.I. Pipes of all classes and fittings with flanged ends carefully into the trenches and laying them true to alignment and gradient including all sundries, as per BIS No.3114/94.as follosws
350 mm dia
250 mm dia
150 mm dia
Jointing the D.I. Pipes, fittings and valves with flanged ends including cost of jointing materials such as bolts, nuts, rubber insertion, white lead and including filling with water with a water lead upto 500 m and testing to required pressure etc., comp as per BIS No.3114/85 as follows
350 mm dia
250 mm dia
150 mm dia
Construction of Sluice Valve chambers with CC M25 mix suitable to the sluice valves including cost and conveyance of all materials and all labour charges etc.complete as per S.S and for finished item of work. This rate is including cost of material and all labour charges with Earthwork, sand bedding, VCC 1:4:8, RCC bedding and side wall, cover slab with suitble opening, cast stell as per type design approved by the department.
350 mm dia
250 mm dia
150 mm dia
Supply and fixing of Stain less steel ladder made 304 grade steel out of suitable sections for access from floor slab to Base slab.This rate is including cost of material, transportaton and all labour charges, site welding and other incidental charges etc., complete as directed by the departmental officer incharge of work .
Laying of 500mm,400mm,350 mm,250 mm dia . DI K9 combined Pumping mains from clear water sump at HWW to intermediate sump at Uppalametta and proposed 1000 KL ELSR at Santha Market zone-III and proposed 900 KL ELSR at Saibalaji town ship zone-iv
Cutting of existing B.T.road surface (aswell as asphalt concrete up to 75mm thick) including water bound macadam including all labour charges for cutting, stacking of materials etc.,complete as per the directions of departmental authorities. For pipe line trenches.
Cutting and open of C.C. Road surface including stacking of excavated materials for lying of pipe lines by uing chissiling, compresion, hiring of machinery, fuel charges and incidentl charges as per the ditections of the departmental authorities.
Cutting and open of Water bound macadam surface including stacking of excavated materials for lying of pipe lines by uing chissiling, compresion, hiring of machinery, fuel charges and incidentl charges as per the ditections of the departmental authorities.
Earth work excavation in all soils up to SDR & stone matrix by machinery for Pipe lines as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and back filling in trenches with excavated suitable material as per Technical Specification No.305 MORD/304 MORTH up to initial lift of 3.0Mts. For Pipe line trenches. as follows
Mechanical means up to 3 metres depth in ordinary soils
Manual means up to 3 metres depth in ordinary soils
Maechanical means up to 3 metres depth in ordinary rock not requiring blasting
Filling sand bedding in pipe line bed as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH etc., complete. This rate including cost of all materials, all labour charges, watering, ranning other incidental charge etc complete as per SS and as directed by the Departmental officer in charge of the work. But excluding seigniorage charge.
Manufacture supply delivery,of D.I K9 centrifugally cast (spun) ductile iron pipes for water with Socket spigot ends confirming to IS NO 8329/2000 in standard lengths of 4.00,5.00,5.50,6.00m suitable for push-on-joint (rubber gasket D jointing) with cement mortor lining inside and zinc coating out side (K9) including transportation ,loading,unloading, stacking,CED, etc complete as per SS and as directed by the departmental officer incharge of work .
500mm dia. DI k9 combined Pumping main from Proposed Clear water sump to Juction near JRG Community hall
400mm dia. DI k9 combined Pumping main from Juction near JRG Community hall to Intermediate sump near Uppalametta
350mm dia. DI k9 combined Pumping main from Juction near JRG Community hall to jn of proposed 1000 KL ELSR at Santha Market zone-III
250mm dia. DI k9 Pumping main from jn of proposed 1000 KL ELSR at Santha Market zone-III to proposed 900 KL ELSR at Saibalaji town ship zone-iv
Supply and delivery of D.I D/F Centrifugally cast (SPUN) ductile iron pressure pipes with flanged ends for water, gas and sewage conforming to I.S, 8329/2000 in standard working lengths of 4, 5, 5.5 & 6 meter for classification K9 suitable for push on joint (Rubber gasket and jointing) with cement mortar lining inside the pipes with outside zinc coating, rates are ex-factory, including transportion and as per SS and as directed by the departmental officer incharge of work . as follows
300 mm dia on 500 mm lines
200 mm dia on 350 mm lines
150 mm dia on 250 mm lines
for sluice valves,non return valves and flow meters
500 mm dia 1.00m long DI DF pipes for sluice and non return valves and flow meter 5+1+1
400 mm dia 1.00m long DI DF pipes for sluice and non return valves 1+1+1
350 mm dia 1.00m long DI DF pipes for sluice and non return valves 3+2
250 mm dia 1.00m long DI DF pipes for sluice and non return valves 4+2
Supply, delivery of D.I. fittings confirming to I.S.No.9523/2000 having dimensions as per table with Zinc coated externally and inside Cement Mortar lining (With finishing as per Class 13/IS 9523/2000) including cost of fittings, transportation, stacking carefully at site. The rate excluding VAT and other duties etc.,complete as per S.S. and as directed by the departmental authorities. upto 500mm dia
Lowering of D.I. socket and spigot Pipes and fittings carefully in to the trench and laying them true to alignment and gradient including all labour charges, sundries as per BIS No. 3114/85 etc., complete as per S.S and as directed by the departmental authorities.as follows
500mm dia. DI k9 combined Pumping main from Proposed Clear water sump to Juction near JRG Community hall
400mm dia. DI k9 combined Pumping main from Juction near JRG Community hall to Intermediate sump near Uppalametta
350mm dia. DI k9 combined Pumping main from Juction near JRG Community hall to jn of proposed 1000 KL ELSR at Santha Market zone-III
250mm dia. DI k9 Pumping main from jn of proposed 1000 KL ELSR at Santha Market zone-III to proposed 900 KL ELSR at Saibalaji town ship zone-iv
Jointing of D.I. Pipes & fittings with Rubber Gasket including all sundries filling with water with a water lead up to 500m and testing to required pressure etc., complete as per BISNo.3114/85 and as directed by the departmental authorities. As follows
500 mm dia DI K9
400 mm dia DI K9
350 mm dia DI K9
250 mm dia DI K9
Supply, Delivery of 500mm dia D.I double flanged Sluice Valves conforming to IS- 14846 (with up to date amendments, if any) including gear arrangements for the following dia. as per test pressure having Body, Bonnet, Dome, Stool cover, Wedge, Stuffing box, Gland, Thrust plate, Cap/Hand wheel with D.I; Stem, Body seat ring, Wedge facing ring, Bushes, Bolts, Nuts, Pinion and Pinion shaft with Stainless steel (IS 6603) ; Wedge nut, Shoe, Channel with Leaded Tin Bronze ( IS 318 ); Gasket with Neoprene Rubber; Gland packing with Rubber; Gear, Gear housing with Cast Steel and including transportation, etc. complete ISI marked.PN 1.6 (MPa)
Supply and delivery of "Resilient Seated Soft Sealing" Gate Valves (Sluice Valves) with Body and Bonnet of Ductile Iron GGG-40/SG-400/15 or GGG-50/SG-500/7 or Equivalent as per IS1865, IS:3896-2 and Wedge fully Rubber Lined with food grade quality grade W270 grade EPDM, Replaceable Spindle Nut without gland packing with 3-O ring protection system on the Shaft and Seals of NBR. The Valves should be Vacuum tight and 100% leak proof with face to face dimensions as BS:5163 Type A/IS:14846. All the valves sh ould be with fusion bonded Electrostatic Powder coating both inside and outside (Min 250 Microns)-RAL 5005 with Pocket Less Straight through body Passage conforming to Design standards of DIN-3202F4/BS:5163 Type A Flange drilling as per IS - 1538, duties and including transportation. PN1.6 Mpa -as per SS and as directed by the departmental officer incharge of work .
400 mm dia sluice valves
350 mm dia sluice valves
250 mm dia sluice valves
100 mm dia for air valves
300 mm dia sluice valves for scour
200 mm dia sluice valves for scour
150 mm dia sluice valves for scour
Supply, delivery and fixing in position of Single Chamber DI Air Valve with Body and cover in Ductile Iron of grade SG 400/12 or equivalent grade as per I.S.3896-part2-1985 and subsequent revisions. All internal parts such as float, shell etc., all cover bolts, of stainless steel, and Gaskets and seals of EPDM food grade quality Epoxy powder coating (EP-P) inside and outside colour blue. Drilled as per IS:1538. The rate including all taxes and duties and labour charges for placing and fixing in position etc.complete as per S.S as follows
100mm dia. PN 16 on 500 mm dia
100mm dia. PN 16 on 400 mm dia
80mm dia. PN 16 on 350 mm dia
80mm dia. PN 16 on 250 mm dia
Manufacture, Supply and delivery of DI D/F Swing Check Valves Slanted/Straight seated with metallic, corrosion proof and wear resistant seat faces resilient seat, Body and Disc of ductile cast iron GGG 40/SG Iron 420/12 or equivalent grade as per IS 3896(part2)-1985 and subsequent revisions. All the inside and outside of the body is to be coated with double coating of epoxy liquid. Drilled as per IS:1538. Specification and Dimensions as per I.S 5312 or equivalent codes. PN 16 as follows
500mm dia DI
400 mm dia
350mm dia DI
250mm dia DI
Labour charges for lowering and keeping in position of C.I./DI Sluice valves(with cap/with hand wheel), reflux valves and scour valves. as per SS and as directed by the departmental officer incharge of work .
500 mm dia sluice valves
400 mm dia sluice valves
350 mm dia sluice valves
250 mm dia sluice valves
100 mm dia for air valves
300 mm dia sluice valves for scour
200 mm dia sluice valves for scour
150 mm dia sluice valves for scour
Labour charges for fixing Kinetic Air Valves with isolating Sluice valves, Double Air valves/ Air Cushion valve excluding cost of jointing materials such as bolts, nuts and rubber insertions etc.as per SS and as directed by the departmental officer incharge of work .
100mm dia. PN 16 on 500 mm dia
100mm dia. PN 16 on 400 mm dia
80mm dia. PN 16 on 350 mm dia
80mm dia. PN 16 on 250 mm dia
Lowering the C.I. Pipes, D.I. Pipes of all classes and fittings with flanged ends carefully into the trenches and laying them true to alignment and gradient including all sundries, but excluding conveyance from source of supply as per BIS No.3114/94.as per SS and as directed by the departmental officer incharge of work . as follos
500mm dia
400 mm dia
350 mm dia
300 mm dia
250 mm dia
200 mm dia
150mm dia
Jointing the D.I. Pipes, fittings and valves with flanged ends including cost of jointing materials such as bolts, nuts, rubber insertion, white lead and including filling with water with a water lead upto 500 m and testing to required pressure etc., comp as per BIS No.3114/85 as folows
500 mm dia
400 mm dia
300 mm dia
250 mm dia
200 mm dia
150 mm dia
100 mm dia
80 mm dia air valves
Construction of M20 concrete thrust blocks using 20mm HBG metal from approved quarry including cost and conveyance of all materials at site, seignorage charges, labour charges for machine mixing, laying, vibrating including centering charges but excluding cost of steel for reinforcement and its fabrication including curing etc., complete.
Construction of Anchor blocks with M20 concrete using 20mm HBG crushed metal from approved quarry including cost and conveyance of all materials, seignorage charges and all labour charges for machine mixing, laying, vibrating and curing including centering charges etc.,complete as per S.S and as directed by the departmental authorities.
Collection ,supply,spreading and compaction of crusher stone dust including curing as per SS for pipe line trench cutting portion .This rate including cost of material and all lbour charges, watering, ramming and other incidental charges etc., complete as directed by the departmental officer incharge of work .
Construction of Sluice Valve chambers with CC M25 mix suitable to the sluice valves including cost and conveyance of all materials and all labour charges etc.complete This rate is including cost of material and all labour charges with Earthwork, asand bedding, VCC 1:4:8, RCC bedding and side wall, cover slab with suitble opening, cast stell as per type design approved by the department.
For 500mm dia. Sluice Valves and swing check valves
For 400mm dia. Sluice Valves and swing check valves
For 350mm dia. Sluice Valves and swing check valves
For 250mm dia. Sluice Valves
Construction of Scour Valve chambers with CC M25 mix suitable to the Scour Valve including cost and conveyance of all materials and all labour charges etc.complete This rate is including cost of material and all labour charges with Earthwork, asand bedding, VCC 1:4:8, RCC bedding and side wall, cover slab with suitble opening, cast stell as per type design approved by the department.
For 300mm dia. Scour Valves
For 200mm dia. Scour Valves
For 150mm dia. Scour Valves
Construction of Air Valve chambers with RCC M30 mix suitable to the Scour Valve including cost and conveyance of all materials This rate is including cost of material and all labour charges with Earthwork, asand bedding, VCC 1:4:8, RCC bedding and side wall, cover slab with suitble opening, cast stell as per type design approved by the department.
100mm dia. PN 16 on 500 mm dia
100mm dia. PN 16 on 400 mm dia
80mm dia. PN 16 on 350 mm dia
80mm dia. PN 16 on 250 mm dia
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying including sales and other taxes on all materials etc., complete for finished item of work in all floors.( APSS No.126) for pre cast slabs of culverts
Using Concrete mixture up to Plinth Level : Plain Cement concrete nominal mix M-30 (Cement : fine aggregate: coarse aggregate ) using 20mm size Hard Granite Machine Crushed Graded Metal including cost and conveyance of all materials like cement, sand, coarse aggregate water etc., to site , seigniorage charges on all materials, labour charges , for mixing , laying, concrete , ramming in 15 cm layers, finishing top surface to the required level curing etc., complete for finished item of work with nomonal reinforcement for Road restoration.
Manufacture, Supply and delivery of MS/CI Dismantling Joints with both side flange end suitable for installation in between flange end pipes. These rates, Taxes and transportation charges etc., complete
500mm dia
400mm dia
350mm dia
250mm dia
Shifting of existing Electrical Pole and transformers for lying on the Pipe line alignment including shifting charges payble to AP Transco and other incidental charges etc.,complete as directed by the departmental officer incharge of work .
Manufacture, supply and delivery at work site 500mm dia internal dia M.S.Pipe fabricated with 10mm thick MS plates confirming to IS 2062-1992 of grade A manufactured as per IS 3589-2001 in suitable lengths to suit the sit conditionse with cement lime, in co-ordination with the concerned authorities as per approved drawings and directed by the Engineer-in –charge
Laying of ,250 mm dia . DI K9 Pumping mains from intermediate sump at Uppalametta to proposed 800 KL ELSR at Uppalametta zone-V
Earth work excavation in all soils up to SDR & stone matrix by machinery for Pipe lines as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and back filling in trenches with excavated suitable material as per Technical Specification No.305 MORD/304 MORTH up to initial lift of 3.0Mts. For Pipe line trenches with the following depth
Mechanical means up to 3 metres depth in ordinary soils
Manual means up to 3 metres depth in ordinary soils
Maechanical means up to 3 metres depth in ordinary rocknot rquiring blasting
Filling in foundation trenches as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH for pipe line trench This rate is including cost of material and all labour charges and other incidental charges etc., complete and as directed by the departmental officer incharge of work .
Manufacture supply delivery,of 250mm dia D.I K9 centrifugally cast (spun) ductile iron pipes for water with Socket spigot ends confirming to IS NO 8329/2000 in standard lengths of 4.00,5.00,5.50,6.00m suitable for push-on-joint (rubber gasket D jointing) with cement mortor lining inside and zinc coating out side (K9) including transportation ,loading,unloading, stacking,and other incidental charges etc., complete and as directed by the departmental officer incharge of work .
Supply and delivery of 250mm dia 1.0m long D.I K9 D/F Centrifugally cast (SPUN) ductile iron pressure pipes with flanged ends for water, gas and sewage conforming to I.S, 8329/2000 in standard working lengths of 4, 5, 5.5 & 6 meter for classification K9 suitable for push on joint (Rubber gasket and jointing) with cement mortar lining inside the pipes with outside zinc coating, rates are ex-factory, including transportion and other incidental charges etc., complete and as directed by the departmental officer incharge of work .
Supply, delivery of D.I. fittings confirming to I.S.No.9523/2000 having dimensions as per table with Zinc coated externally and inside Cement Mortar lining (With finishing as per Class 13/IS 9523/2000) including cost of fittings, transportation, stacking carefully at site. The rate excluding VAT and other duties etc.,complete as per S.S. and as directed by the departmental authorities. upto 500mm dia
Lowering of 250mm dia D.I. socket and spigot Pipes and fittings carefully in to the trench and laying them true to alignment and gradient including all labour charges, sundries as per BIS No. 3114/85 etc., complete as per S.S and as directed by the departmental authorities.
Jointing of 250mm dia D.I. Pipes & fittings with Rubber Gasket including all sundries filling with water with a water lead up to 500m and testing to required pressure etc., complete as per BISNo.3114/85 and as directed by the departmental authorities.
Manufacture, Supply and delivery of 250mm dia PN 1.6 DI D/F Gate Valves (Soft Seated) Resilient seated soft sealing gate valves (Sluice valves) with body bonnet of ductile cast iron of grade GGG40/ SG 400/12 or equivalent grade as per I.S.3896-part2-1985 and subsequent revisions, wedge fully rubber lined with EPDM food grade quality and seals of NBR and the valves should be of vacuum tight and 100% leak proof with face to face dimensions as per BS5163-89/IS14846-2000/DIN 3202 F 4. All the valves should be with Electrostatic powder coating both inside and outside pocket less body passage. Drilled as per IS:1538. PN16
Supply, delivery and fixing in position of 80mm dia PN 1.6 Single Chamber DI Air Valve with Body and cover in Ductile Iron of grade SG 400/12 or equivalent grade as per I.S.3896-part2-1985 and subsequent revisions. All internal parts such as float, shell etc., all cover bolts, of stainless steel, and Gaskets and seals of EPDM food grade quality Epoxy powder coating (EP-P) inside and outside colour blue. Drilled as per IS:1538. The rate including all taxes and duties and labour charges for placing and fixing in position etc.complete as per S.S
Manufacture, Supply and delivery of 250mm dia DI D/F Swing Check Valves Slanted/Straight seated with metallic, corrosion proof and wear resistant seat faces resilient seat, Body and Disc of ductile cast iron GGG 40/SG Iron 420/12 or equivalent grade as per IS 3896(part2)-1985 and subsequent revisions. All the inside and outside of the body is to be coated with double coating of epoxy liquid. Drilled as per IS:1538. Specification and Dimensions as per I.S 5312 or equivalent codes. PN 16
Labour charges for 250mm dia lowering and keeping in position of C.I./DI Sluice valves(with cap/with hand wheel), reflux valves and scour valves.
Labour charges for 80mm dia fixing Kinetic Air Valves with isolating Sluice valves, Double Air valves/ Air Cushion valve excluding cost of jointing materials such as bolts, nuts and rubber insertions etc.
Lowering the 250mm dia C.I. Pipes, D.I. Pipes of all classes and fittings with flanged ends carefully into the trenches and laying them true to alignment and gradient including all sundries, but excluding conveyance from source of supply as per SS and as directed by the departmental officer incharge of work
Jointing the D.I. Pipes, fittings and valves with flanged ends including cost of jointing materials such as bolts, nuts, rubber insertion, white lead and including filling with water with a water lead upto 500 m and testing to required pressure etc., comp as per BIS No.3114/85 as follows
250 mm dia
80 mm dia air valves
Construction of M25 concrete thrust blocks using 20mm HBG metal from approved quarry including cost and conveyance of all materials at site, seignorage charges, labour charges for machine mixing, laying, vibrating including centering charges but excluding cost of steel for reinforcement and its fabrication including curing centering, shuttering, all labour charges etc., complete.
Construction of Anchor blocks with M25 concrete using 20mm HBG crushed metal from approved quarry including cost and conveyance of all materials, seignorage charges and all labour charges for machine mixing, laying, vibrating and curing including centering charges etc.,complete as per S.S and as directed by the departmental authorities.
Construction of Sluice Valve chambers with CC M20 mix suitable to the sluice valves including cost and conveyance of all materials and all labour charges etc.complete as per S.S and for finished item of work. This rate is including cost of material and all labour charges with Earthwork, asand bedding, VCC 1:4:8, RCC bedding and side wall, cover slab with suitble opening, cast stell as per type design approved by the department.
Construction of Air Valve chambers with CC M30 mix suitable to the Scour Valve including cost and conveyance of all materials and all labour charges etc.complete as per S.S This rate is including cost of material and all labour charges with Earthwork, asand bedding, VCC 1:4:8, RCC bedding and side wall, cover slab with suitble opening, cast stell as per type design approved by the department.
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying including sales and other taxes on all materials etc., complete for finished item of work in all floors.( APSS No.126) for pre cast slabs of culverts - RBR-FNDN-8 & Revised Data sl.No-5
Manufacture, Supply and delivery of 250mm dia MS/CI Dismantling Joints with both side flange end suitable for installation in between flange end pipes complete as per SS and as directed by the departmental officer incharge of work .
Laying of ,250 mm dia . DI K9 Pumping mains from intermediate sump at Uppalametta to proposed 800 KL ELSR at Govt.college zone-II
Cutting of existing B.T.road surface (aswell as asphalt concrete up to 75mm thick) including water bound macadam including all labour charges for cutting, stacking of materials etc.,complete as per the directions of departmental authorities. For pipe line trenches.
Cutting and open of C.C. Road surface including stacking of excavated materials for lying of pipe lines etc.including cost of all labour charges ,hiring of machinery fuel charges ,wages of driver etc., complete as per the directions of departmental authorities. For pipe line trenches.
Cutting and open of Water bound macadam surface including stacking of excavated materials etc.including cost of all labour charges ,hiring of machinery fuel charges ,wages of driver etc., complete as per the directions of departmental authorities. For pipe line trenches.
Earth work excavation in all soils up to SDR & stone matrix by machinery for Pipe lines as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and back filling in trenches with excavated suitable material as per Technical Specification No.305 MORD/304 MORTH up to initial lift of 3.0Mts. For Pipe line trenches.
Filling in foundation trenches as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH for pipe line trench RBR-FNDN-2(1)
Manufacture supply delivery,of 250mm dia D.I K9 centrifugally cast (spun) ductile iron pipes for water with Socket spigot ends confirming to IS NO 8329/2000 in standard lengths of 4.00,5.00,5.50,6.00m suitable for push-on-joint (rubber gasket D jointing) with cement mortor lining inside and zinc coating out side (K9) including transportation ,loading,unloading, stacking, and other incidental charges etc., complete and as directed by the departmental officer incharge of work .
Supply and delivery of Centrifugally cast (SPUN) ductile iron pressure pipes with flanged ends for water, gas and sewage conforming to I.S, 8329/2000 in standard working lengths of 4, 5, 5.5 & 6 meter for classification K9 suitable for push on joint (Rubber gasket and jointing) with cement mortar lining inside the pipes with outside zinc coating, rates are ex-factory, including transportion and other incidental charges etc., complete and as directed by the departmental officer incharge of work .
For scours 2.00mDIDF pipes 150mm dia
250 mm dia 1.00m long DI DF pipes for sluice and non return valve
Supply, delivery of D.I. fittings confirming to I.S.No.9523/2000 having dimensions as per table with Zinc coated externally and inside Cement Mortar lining (With finishing as per Class 13/IS 9523/2000) including cost of fittings, transportation, stacking carefully at site as per S.S. and as directed by the departmental authorities. This rate including cost of material and alabour charges, transporttion charges, hiring of machinary, welding charges and other incidental charges etc., complete and as directed by the departmental officer incharge of work . upto 500mm dia
Lowering of 250mm dia D.I. K9 socket and spigot Pipes and fittings carefully in to the trench and laying them true to alignment and gradient including all labour charges, sundries as per BIS No. 3114/85 etc., complete as per S.S and as directed by the departmental authorities.
Jointing of 250mm dia D.I. K9. Pipes & fittings with Rubber Gasket including all sundries filling with water with a water lead up to 500m and testing to required pressure etc., complete as per BISNo.3114/85 and as directed by the departmental authorities.
Manufacture, Supply and delivery of DI D/F Gate Valves (Soft Seated) Resilient seated soft sealing gate valves (Sluice valves) with body bonnet of ductile cast iron of grade GGG40/ SG 400/12 or equivalent grade as per I.S.3896-part2-1985 and subsequent revisions, wedge fully rubber lined with EPDM food grade quality and seals of NBR and the valves should be of vacuum tight and 100% leak proof with face to face dimensions as per BS5163-89/IS14846-2000/DIN 3202 F 4. All the valves should be with Electrostatic powder coating both inside and outside pocket less body passage. Drilled as per IS:1538. PN16 as follows
250 mm dia sluice valves
150 mm dia sluice valves for scour
Supply, delivery and fixing in position of 80mm dia PN 1.6 Single Chamber DI Air Valve with Body and cover in Ductile Iron of grade SG 400/12 or equivalent grade as per I.S.3896-part2-1985 and subsequent revisions. All internal parts such as float, shell etc., all cover bolts, of stainless steel, and Gaskets and seals of EPDM food grade quality Epoxy powder coating (EP-P) inside and outside colour blue. Drilled as per IS:1538. The rate including all taxes and duties and labour charges for placing and fixing in position etc.complete as per S.S
Manufacture, Supply and delivery of 250mm dia PN 1.6 DI D/F Swing Check Valves Slanted/Straight seated with metallic, corrosion proof and wear resistant seat faces resilient seat, Body and Disc of ductile cast iron GGG 40/SG Iron 420/12 or equivalent grade as per IS 3896(part2)-1985 and subsequent revisions. All the inside and outside of the body is to be coated with double coating of epoxy liquid. Drilled as per IS:1538. Specification and Dimensions as per I.S 5312 or equivalent codes. PN 16
Labour charges for lowering and keeping in position of C.I./DI Sluice valves(with cap/with hand wheel), reflux valves and scour valves.as per SS and as directed by the departmental officer incharge of work . As follows
250 mm dia sluice valves
150 mm dia sluice valves for scour
Labour charges for fixing of 80mm dia Kinetic Air Valves with isolating Sluice valves, Double Air valves/ Air Cushion valve excluding cost of jointing materials such as bolts, nuts and rubber insertions etc.
Lowering the C.I. Pipes, D.I. Pipes of all classes and fittings with flanged ends carefully into the trenches and laying them true to alignment and gradient including all sundries, but excluding conveyance from source of supply as per BIS No.3114/94. as follows
250 mm dia
150mm dia
Jointing the D.I. Pipes, fittings and valves with flanged ends including cost of jointing materials such as bolts, nuts, rubber insertion, white lead and including filling with water with a water lead upto 500 m and testing to required pressure etc., comp as per BIS No.3114/85 as follows
250 mm dia
150 mm dia
80 mm dia air valves
Construction of M20 concrete thrust blocks using 20mm HBG metal from approved quarry including cost and conveyance of all materials at site, seignorage charges, labour charges for machine mixing, laying, vibrating including centering charges but excluding cost of steel for reinforcement and its fabrication including curing, centering, scaffolding etc., complete.
Construction of Anchor blocks with M20 concrete using 20mm HBG crushed metal from approved quarry including cost and conveyance of all materials, seignorage charges and all labour charges for machine mixing, laying, vibrating and curing including centering charges etc.,complete as per S.S and as directed by the departmental authorities.
Collection ,supply,spreading and compaction of crusher stone dust including curing as per SS for pipe line trench cutting portion .This rate including cost of material and all lbour charges, watering, ramming and other incidental charges etc., complete as directed by the departmental officer incharge of work .
Construction of Sluice Valve chambers with CC M25 mix suitable to the sluice valves including cost and conveyance of all materials and all labour charges etc.complete as per S.S and for finished item of work. This rate is including cost of material and all labour charges with Earthwork, asand bedding, VCC 1:4:8, RCC bedding and side wall, cover slab with suitble opening, cast stell as per type design approved by the department.
Construction of Scour Valve chambers with CC M20 mix suitable to the Scour Valve including cost and conveyance of all materials and all labour charges etc.complete as per S.S for finished item of work This rate is including cost of material and all labour charges with Earthwork, asand bedding, VCC 1:4:8, RCC bedding and side wall, cover slab with suitble opening, cast stell as per type design approved by the department.
Construction of Air Valve chambers with RCC M30 mix suitable to the Scour Valve including cost and conveyance of all materials and all labour charges etc.complete as per S.S
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying including sales and other taxes on all materials etc., complete for finished item of work in all floors.( APSS No.126) for pre cast slabs of culverts -
Using Concrete mixture Restoration of CC road by Plain Cement concrete nominal mix M-30 (Cement : fine aggregate: coarse aggregate ) using 20mm size Hard Granite Machine Crushed Graded Metal including cost and conveyance of all materials like cement, sand, coarse aggregate water etc., to site , seigniorage charges on all materials, labour charges , for mixing , laying, concrete , ramming in 15 cm layers, finishing top surface to the required level curing etc., complete for finished item of work with nomonal reinforcement for Road restoration.
Manufacture, Supply and delivery of 250mm dia MS/CI Dismantling Joints with both side flange end suitable for installation in between flange end pipes. complete
Shifting of existing Electrical Pole and transformers for lying on the Pipe line alignment including shifting charges payble to AP Transco and other incidental charges etc.,complete as per SS and as directed by the departmental officer incharge of work . as per the direction of APTRANSCO and by the departmental officer incharge of work .
Laying of ,250 mm dia . DI K9 Pumping mains from intermediate sump at Uppalametta to proposed 1000 KL GLSR at Rajivi Nagar zone-I
Cutting of existing B.T.road surface (aswell as asphalt concrete up to 75mm thick) including water bound macadam including all labour charges for cutting, stacking of materials etc.,complete as per the directions of departmental authorities. For pipe line trenches.
Cutting and open of C.C. Road surface including stacking of excavated materials for lying of pipe lines etc.including cost of all labour charges ,hiring of machinery fuel charges ,wages of driver etc., complete as per the directions of departmental authorities. For pipe line trenches.
Cutting and open of Water bound macadam surface including stacking of excavated materials etc.including cost of all labour charges ,hiring of machinery fuel charges ,wages of driver etc., complete as per the directions of departmental authorities. For pipe line trenches.
Earth work excavation in all soils up to SDR & stone matrix by machinery for Pipe lines as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and back filling in trenches with excavated suitable material as per Technical Specification No.305 MORD/304 MORTH up to initial lift of 3.0Mts. For Pipe line trenches. as follows
Mechanical means up to 3 metres depth in ordinary soils
Manual means up to 3 metres depth in ordinary soils
Maechanical means up to 3 metres depth in ordinary rock not requiring blasting
Filling in foundation trenches as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH-sand filling. This rate including cost of material and all lbour charges, watering, ramming and other incidental charges etc., complete as directed by the departmental officer incharge of work .
Manufacture supply delivery,of 250mm dia centrifugally cast (spun) ductile iron pipes for water with Socket spigot ends confirming to IS NO 8329/2000 in standard lengths of 4.00,5.00,5.50,6.00m suitable for push-on-joint (rubber gasket D jointing) with cement mortor lining inside and zinc coating out side (K9) including transportation ,loading,unloading, stacking, etc complete as per SS and as directed by the departmental officer incharge of work .
Supply and delivery of 250mm dia D.I D/F Centrifugally cast (SPUN) ductile iron pressure pipes with flanged ends for water, gas and sewage conforming to I.S, 8329/2000 in standard working lengths of 4, 5, 5.5 & 6 meter for classification K9 suitable for push on joint (Rubber gasket and jointing) with cement mortar lining inside the pipes with outside zinc coating, rates are ex-factory, including transportion as per SS and as directed by the departmental officer incharge of work . as follows
For scours 2.00mDIDF pipes
250 mm dia 1.00m long DI DF pipes for sluice and non return valves
Supply, delivery of D.I. fittings confirming to I.S.No.9523/2000 having dimensions as per table with Zinc coated externally and inside Cement Mortar lining (With finishing as per Class 13/IS 9523/2000) including cost of fittings, transportation, stacking carefully at site. The rate excluding VAT and other duties etc.,complete as per S.S. and as directed by the departmental authorities.
Lowering of D.I. socket and spigot Pipes and fittings carefully in to the trench and laying them true to alignment and gradient including all labour charges, sundries as per BIS No. 3114/85 etc., complete as per S.S and as directed by the departmental authorities.
Jointing of D.I. Pipes & fittings with Rubber Gasket including all sundries filling with water with a water lead up to 500m and testing to required pressure etc., complete as per BISNo.3114/85 and as directed by the departmental authorities.
Manufacture, Supply and delivery of DI D/F Gate Valves (Soft Seated) Resilient seated soft sealing gate valves (Sluice valves) with body bonnet of ductile cast iron of grade GGG40/ SG 400/12 or equivalent grade as per I.S.3896-part2-1985 and subsequent revisions, wedge fully rubber lined with EPDM food grade quality and seals of NBR and the valves should be of vacuum tight and 100% leak proof with face to face dimensions as per BS5163-89/IS14846-2000/DIN 3202 F 4. All the valves should be with Electrostatic powder coating both inside and outside pocket less body passage. Drilled as per IS:1538. PN16
250 mm dia sluice valves
150 mm dia sluice valves for scour
Supply, delivery and fixing in position of 80mm dia PN 1.6 Single Chamber DI Air Valve with Body and cover in Ductile Iron of grade SG 400/12 or equivalent grade as per I.S.3896-part2-1985 and subsequent revisions. All internal parts such as float, shell etc., all cover bolts, of stainless steel, and Gaskets and seals of EPDM food grade quality Epoxy powder coating (EP-P) inside and outside colour blue. Drilled as per IS:1538. The rate including and other incidentl charges labour charges for placing and fixing in position etc.complete as per S.S
Manufacture, Supply and delivery of 250mm dia PN 1.6 DI D/F Swing Check Valves Slanted/Straight seated with metallic, corrosion proof and wear resistant seat faces resilient seat, Body and Disc of ductile cast iron GGG 40/SG Iron 420/12 or equivalent grade as per IS 3896(part2)-1985 and subsequent revisions. All the inside and outside of the body is to be coated with double coating of epoxy liquid. Drilled as per IS:1538. Specification and Dimensions as per I.S 5312 or equivalent codes. PN 16
Labour charges for lowering and keeping in position of C.I./DI Sluice valves(with cap/with hand wheel), reflux valves and scour valves.as follows
250 mm dia sluice valves
150 mm dia sluice valves for scour
Labour charges for 80mm dia PN 1.6 fixing Kinetic Air Valves with isolating Sluice valves, Double Air valves/ Air Cushion valve excluding cost of jointing materials such as bolts, nuts and rubber insertions etc.as follows
Lowering the C.I. Pipes, D.I. Pipes of all classes and fittings with flanged ends carefully into the trenches and laying them true to alignment and gradient including all sundries, but excluding conveyance from source of supply as per BIS No.3114/94.
250 mm dia
150mm dia
Jointing the D.I. Pipes, fittings and valves with flanged ends including cost of jointing materials such as bolts, nuts, rubber insertion, white lead and including filling with water with a water lead upto 500 m and testing to required pressure etc., comp as per BIS No.3114/85 as foolows
250 mm dia
150 mm dia
80 mm dia air valves
Construction of M25 concrete thrust blocks using 20mm HBG metal from approved quarry including cost and conveyance of all materials at site, seignorage charges, labour charges for machine mixing, laying, vibrating including centering charges but excluding cost of steel for reinforcement and its fabrication including curing etc., complete.
Construction of Anchor blocks with M25 concrete using 20mm HBG crushed metal from approved quarry including cost and conveyance of all materials, seignorage charges and all labour charges for machine mixing, laying, vibrating and curing including centering charges etc.,complete as per S.S and as directed by the departmental authorities.
Collection ,supply and spreading of crusher stone dust from approved quarries for road restoration including compaction and watering etc., complete ramming, all labour charge and other incidental charges
Construction of Sluice Valve chambers with CC M25 mix suitable to the sluice valves including cost and conveyance of all materials and all labour charges etc.complete as per S.S and for finished item of work. This rate is including cost of material and all labour charges with Earthwork, asand bedding, VCC 1:4:8, RCC bedding and side wall, cover slab with suitble opening, cast stell as per type design approved by the department.
Construction of Scour Valve chambers with CC M25 mix suitable to the Scour Valve including cost and conveyance of all materials and all labour charges etc.complete as per S.S for finished item of work This rate is including cost of material and all labour charges with Earthwork, asand bedding, VCC 1:4:8, RCC bedding and side wall, cover slab with suitble opening, cast stell as per type design approved by the department.
Construction of Air Valve chambers with CC M25 mix suitable to the Scour Valve including cost and conveyance of all materials and all labour charges etc.complete as per S.S This rate is including cost of material and all labour charges with Earthwork, asand bedding, VCC 1:4:8, RCC bedding and side wall, cover slab with suitble opening, cast stell as per type design approved by the department.
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying including sales and other taxes on all materials etc., complete for finished item of work in all floors.( APSS No.126) for pre cast slabs of culverts - RBR-FNDN-8 & Revised Data sl.No-5
Using Concrete mixture up to Plinth Level : Plain Cement concrete nominal mix M-30 (Cement : fine aggregate: coarse aggregate ) using 20mm size Hard Granite Machine Crushed Graded Metal including cost and conveyance of all materials like cement, sand, coarse aggregate water etc., to site , seigniorage charges on all materials, labour charges , for mixing , laying, concrete , ramming in 15 cm layers, finishing top surface to the required level curing etc., complete for finished item of work with nomonal reinforcement for Road restoration.
Manufacture, Supply and delivery of 250mm dia MS/CI Dismantling Joints with both side flange end suitable for installation in between flange end pipes. These rates and transportation charges etc., completeas per SS and as directed by the departmental officer incharge of work .
Shifting of existing Electrical Pole and transformers for lying on the Pipe line alignment including shifting charges payble to AP Transco and other incidental charges etc.,complete as directed by the departmental officer incharge of work .
Manufacture, supply and delivery at work site 400mm dia internal dia M.S.Pipe fabricated with 10mm thick MS plates confirming to IS 2062-1992 of grade A manufactured as per IS 3589-2001 in suitable lengths to suit the sit conditionse including cement, linning, in co-ordination with the concerned authorities as per approved drawings and directed by the Engineer-in –charge
Laying of 800mm dia.(10 mm thick plate) at State High way for clear water pumping main 500 mm and 250 mm dia DIK9 ( for Horizantal boring)
Railway crossings / Road crossings / Canal crossings by trenchless technology tunneling work through specialized pipe jacking method in co-ordination with concerned authorities for laying of 800mm dia MS pipe line as per approved drawings, installing to correct level gradient and alignment by hydralic pipe jacking technique complete including tunneling excavation drive and receive pits ,excavation and all machines tranaportation charges and other required materials but including cost of encasing pipe as per the directon of the Highway authorities and as directed by the department authorities Engineer-in-cheif
Construction of 600 mm size CC disposal drain from proposed WTP
Earth work excavation in all soils up to SDR & stone matrix by machinery for Pipe lines as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and back filling in trenches with excavated suitable material as per Technical Specification No.305 MORD/304 MORTH up to initial lift of 3.0Mts. For Pipe line trenches. as follows
Mechanical means up to 3 metres depth in ordinary soils
Manual means up to 3 metres depth in ordinary soils
Filling in foundation trenches as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH as per SS and as directed by the departmental officer incharge of work .
Providing PCC 1:4:8 using 40 mm graded SS 5 HBG m/c metal and OPC coarse and fine aggregate confirming to IS 383 including cost and conveyance of all materials and labour charges, machine mixing , vibration,laying in position, curing etc., complete for bed concrete CC Drain
PCC M-15 Nominal mix (cement,fine aggregate,coarse aggregate) corresponding to Table -9 of IS -456 using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including seigniorage charges ,sales and other taxes on all materials including all operational ,incidental and labour charges such as machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work,but including centering,shuttering for CC drains
Providing Instrumentation and Automation of the Pumping System, Supervisory Control and Data Acuasation System (SCADA) & Providing 2x7 water supply system at 1000 KL ELSR in Santha market of Zone-III
Providing, Installation, Testing and Commissioning of PRESSURE TRANSMITTER for suction, Delivery and common Header with specifications of Water Application: Range: 0-16 Bar / Power Supply: 24 V DC / Output: 4-20 mA / Diaphragm: SS316L / Process Connection: 1/2 "NPT (M) / Accuracy: 0.15% Protection: IP67 . The cost also includes the calibration of all the sensors manifold etc., complete including cost and conveyance of all material and labor excluding cost of taxes and duties and as per SS and as directed by the department officer for Raw water and clear water pumping station
Supply, errection, testing and commissioning of Ultra sonic/ Altitude Level sensors make of SIEMENS/ ABB/ BAUMER/ DANFOSS with specifications of body construction with standard construction, measuring upto 6.00 Mtr depth, protection clause of IP 65, accuracy is +/- 5%, input power supply is 24 V.. DC, remote communication protocol of 4 to 20 ma, temperature safety is in-built to comprehensive over temperature range with in the -40 Deg to +80 Deg, installed in both conditions i.e., indoor and outdoor, charges excluding cost of taxes and duties including cost and conveyance of all material including transport and labor etc., complete and as directed by the dept., officer.for Raw water and clear water pumping station
Supply and delivery of 25 MM Dia electrical actuated valves for Vaccume operation for each pump with specification of Thread end, 24 V.. DC and required limit switches and manual override facility complete charges including cost and convayance of all the material, labor etc., complete and other incidental charges etc., complete for clear water pumping station
Supply and delivery of 250mm dia DI D/F hydraulic and self-medium operated double chamber diaphragm control valve for the functions of pump control i.e. to ensure smooth startup and shutdown of pumps. Valve shall be activated by line pressure and 24V DC solenoid for its operation. Non-return function in built to prevent surges due to pump trip events. Valve closure started as soon as solenoids are deenergized and limit switch of valve position indicator triggered. The valve can be manually overridden to check function. The main valve body internals shall consist of three basic parts i.e. body, diaphragm assembly and top cover with a spring inside main body. The nylon reinforced natural rubber diaphragm of the valve shall close on a seating arrangement. The control tubing shall include inline filter unit. The coating shall be of epoxy BLUE. Charges including cost and conveyance of all material and labor per SS and as directed by the department officer for Raw water and clear water control valve
Supply and delivery of 500mm dia separate version Electro Magnetic Flow Meter MAG 5100 model or equilant with the specification of flow body as per company standards, electrodes of SS316, accuracy of +/- 2%, cable length of 20 Mtrs, end connection of ANSI flanges as IS/DIN standards, flow bore protection is IP68, earth rings of SS ( If required as per site condition) flow transmitter body as per company standard and two line display, transmitter having 4-20mA, RS485 and modbus communication for data transfer through any network, power supply of 24 volts DC , and submittion of manufacturer test and calbrationreports charges and all charges including cost and conveyance of all material , freight, transport and labour etc and etc., complete, and as directed by the dept., officer.
Supply and testing of panel mounted 96 mmx 48 mm size on line mounted pH Analyser with Display (4 Digit) make of FM/ JUMO / ABB/ SIEMENS/ HACH with the technical specifications of Measuring Range: 0-14 pH, Process pressure range : 1 bar @ 50 Deg C, Measuring method : Reference, Solution ground : Graphite, electrode body: Glass body (tip), Wetted Parts : Glass tip plastic shaft protection Operating Temp: 0 to 50 Deg C, Protection Class : IP 65 (front) & IP 20 (rear), Communication : RS485, Voltage : 24 V.. DC Cable : 10 mtrs of Poly made the charges are including test and calibration certificate, cost and conveyance of all material, labor and other incidental charges etc., complete for clear water WTP
Supply and testing of wall mounted 120(w), 140(H), 77(D) Turbidity analyser with display(4 digit) make of FM/ JUMO / ABB/ SIEMENS/ HACH with the technical specifications of Measuring range: 1-4000 Ntu, Process pressure range : 2 bar @ 50 deg c, Measuring method : Infrared light 90 deg scatter light method, Max. sampling rate for measured values: 1 Hz, Resolution : 0.01 to 1 depending on measuring range , Measurands : Turbidity & Temperature Operating temp: 0 to 50 deg c, Protection class : IP 67, Communication : RS 485/4-20 mA, Voltage : 24 v.. DC, Sensor case : PVC/POM-C, Optical window: PMMA, Cable : 10 mtrs of Poly made the charges are including test and calibration certificate, cost and conveyance of all material, labor and other incidental charges etc., complete for clear water WTP
Supply and testing of panel mounted 96 mm x 48 mm size on line mounted Conductivity/ TDS sensor with display (4 digit) make of FM/ JUMO / ABB/ SIEMENS/ HACH with the technical specifications of Measuring range: .1 to approx. 1000 μS/cm, Cell constant : 0.1, Process pressure range : 5 bar @ 50 deg c, Measuring method : Conductive 2 electrode, Sampling : 500 msec, Measurands : Conductivity / TDS, Operating temp : -5 to +80 °C, Protection class : IP 67, Communication : RS 485, Voltage : 24 v.. DC, Sensor case: Stainless Steel 1.4571, Body material: PEI, Cable : 10 Mtrs of Polyimide and the charges are including test and calibration certificate, cost and conveyance of all material, labor and other incidental charges etc., complete for Raw water and clear water WTP
Supply and testing of panel mounted 96 mm x 48 mm size on line mounted Chlorine Analyzer with display (4 digit) make of FM/ JUMO / ABB/ SIEMENS/ HACH with the technical specifications of Measuring range: 0-10 PPM, Cell constant : 0.1, Process pressure range : 1 bar @ 50 deg c, Measuring method : 2 and 3 Electrode principle, Response time : Approx. 2 min, pH Dependency (loss of slope) : In the range from pH 5 to 7: no loss of slope, at pH 8 about 10%, at pH 9 about 20%, (starting from pH 7), Operating temp : 0 to 50°C, Protection class : IP 67, Communication : RS 485, Voltage : 24 v.. DC, Sensor Case: PVC, Body material : PEI, Cable : 10 Mtrs of Polyimide and the charges are including test and calibration certificate, cost and conveyance of all material, labor. and other incidental charges etc., complete for Raw water and clear water WTP
Supply laying and fixing of tubing for Inlet and out let of raw water and clear water to the analyzers with necessary pipes with compressed fittings charges excluding cost of taxes and duties including cost and conveyance of all material including transport and labor etc., complete and as directed by the dept., officer. and other incidental charges etc., complete for Raw water and clear water WTP
Supply, errection, Testing & Commissioning of Out door type PLC/Controller based Automation and communication Panel fabricating with 16 SWG CR sheet, internal and external surface coating with Epoxy powder coating, making internal wiring with suitable wires including nomenclature. The panel is suitable for the Control & Monitoring the Level, Flow & Pressure and Quality Parameters and Comunicating with Central SCADA for Auto logic, Local and Remote operation of the valves with specifications of fabricating with 16 SWG CR sheet, internal and external surface coating with powder coating, making internal wiring with suitable wires including nomenclature. The panel is suitable for the above operations with PLC/Controller, communication modules, HMI, Power back up and necessary modules and as per site conditions etc., complete charges including all material and as per SS and other incidental charges etc., complete for Raw water and clear water WTP
Supply, errection, Testing & Commissioning of In door type Scada based RTU control panel for Opearating and monitoring of the Raw Water and Clear Water Pumping stations in auto logic and manual operations including synchornize with SCADA and the specifications of fabricating with 16 SWG CR sheet, internal and external surface coating with Epoxy powder coating, arrangement of required PLC/ Controller, Ethernet Switch, Required I/O Modules and DI, DO modules, all components powered by 24 V. DC with necesssary control MCB's, Relay cards, fixing of all termination with FTB's, Internal wiring by all power cables with suitable guage of Single core copper PVC sheated cables and all communication cables with SS Brided cables, and the panel having logic for the following and erection with required civil works as per site conditions etc., complete charges including all materials and labour and and other incidental charges etc., complete for Raw water and clear water WTP as directed by the department officer. as follows
Logic for RTU opeartaions: 1. RTU panel for local operaion of the pumps in manual and Auto Mode. 2. All the equipment like Pumps, PCC, MCC, VFD Control panels, Pump Control Valves, Vaccume Valve, Pressure and flow sensors connected to RTU through the cabling with necessary power and communication cables. 3. The pumps can be opearte in Auto mode by the pumping sequence including monitor and opearte the Vacumization, SumpLevels, Suction, Delivery pressures, Pump Monitoting and PCV operating according to site conditions. 4. In Auto management, the pumps can be operate based on the field demand through control the VFD panels according to pump curves. 5. Monitoring the suction and delivery pressures of the pumps and operate under limits assigned. 6. Check all the reservoir demands and switch on and switch off the pumps according to demand under limits of pump curves. 7. In manual opeartion, all the equiment can be run through PLC panel by individual operations. 8.The RTU connected with SCADA for remote monitoring and operation. 9. The RTU have a adequated facility to modify any sequence at any time demanded by the department incharge.
supply and delivery of "Resilient Seated Soft Sealing" Gate Valves (Sluice Valves) with Body and Bonnet of Ductile Iron GGG-40/SG-400/15 or GGG-50/SG-500/7 or Equivalent as per IS1865, IS:3896-2 and Wedge fully Rubber Lined with food grade quality grade W270 grade EPDM, Replaceable Spindle Nut without gland packing with 3-O ring protection system on the Shaft and Seals of NBR. The Valves should be Vacuum tight and 100% leak proof with face to face dimensions as BS:5163 Type A/IS:14846. All the valves should be with fusion bonded Electrostatic Powder coating both inside and outside (Min 250 Microns)- RAL 5005 with Pocket Less Straight through body Passage conforming to Design standards of DIN-3202F4/BS:5163 Type A Flange drilling as per IS - 1538 and other incidental charges etc., complete as follows
150MM Dia Above Specification. For Reservoirs
200 MM Dia Above Specification.For Reservoirs
Supply and delivery of separate version Electro Magnetic Flow Meter MAG 5100 model or equilant with the specification of flow body as per company standards, electrodes of SS316, accuracy of +/- 2%, cable length of 20 Mtrs, end connection of ANSI flanges as IS/DIN standards, flow bore protection is IP68, earth rings of SS ( If required as per site condition) flow transmitter body as per company standard and two line display, transmitter having 4-20mA, RS485 and modbus communication for data transfer through any network, power supply of 24 volts DC , and submittion of manufacturer test and calbrationreports charges and all charges including cost and conveyance of all material , freight, transport and labour etc and other incidental charges., complete, and as directed by the dept., officer.as follows
150MM Dia Above Specification.For Reservoirs
200 MM Dia Above Specification.For Reservoirs
Supply and delivery of Electrically switched, DI D/F hydraulic and self-medium operated diaphragm Control valve for the functions of Pressure & Flow control at Tank inlet with the function to maintain a constant downstream flow and pressure by controlling the differential pressure between the inlet and outlet of an orifice plate, regardless of pressure variations. The valve shall be of globe pattern inline or angular pattern with a main valve body of full or reduced bore designed for full differential pressure. The seat shall be of stainless steel which is replaceable.The valve can use manually and electrically with 24 V.. AC/DC for operation. The control tubing with self cleaning filter unit to functions as per customer requirement. The internal & external coating with liquid/Powder form epoxy coating, all fastners with SS including cost and convayance of all material and labor and other incidental charges., complete, and as directed by the dept., officer.as follows
150MM Dia Above Specification.For Reservoirs
200 MM Dia Above Specification.For Reservoirs
Supply ad delivery of M.S. Dismantling Joints /SS, D/F expansion bellows with specifications of bellow with SS ASTM A 240 TP 304 grade, tie rods with EN8/IS-2062 Grade, End connection flanges with IS 2062 Gr.B Sorf plate, Drilling and dimensions as per approved drawing as required by customer at the time of order confirmation charges excluding cost of taxes and duties including cost and conveyance of all material including transport and labor etc., complete and as directed by the dept., officer.
150MM Dia Above Specification.For Reservoirs
200 MM Dia Above Specification.For Reservoirs
Supply, errection, testing and commissioning of Ultra sonic/ Altitude Level sensors make of SIEMENS/ ABB/ BAUMER/ DANFOSS / KELLER with specifications of body construction with standard construction, mesuring upto 6.00 Mtr depth, protection clause of IP 65, accuracy is +/- 5%, input power supply is 24 V.. DC, remote comunication protocol of 4 to 20 ma, temperature safety is in-built to comperhencive over temprature range with in the -40 Deg to +80 Deg, installed in both conditions i.e., indoor and outdoor, charges and other incidental, transportation, all labour charges.,complete, and as directed by the dept., officer.incharge of work for various ELSR's inlets
Providing, Installation, Testing and Commissioning of PRESSURE TRANSMITTER for Water Application: Range: 0-10 Bar / Power Supply: 24 V DC / Output: 4-20 mA / Diaphragm: SS316L / Process Connection: 1/2 "NPT (M) / Accuracy: 0.15% Protection: IP67 . The cost also includes the calibration of all the sensors manifold etc., complete including cost and convayance of all material and labor and other incidental, transportation, all labour charges.,complete, and as directed by the dept., officer.incharge of work for various ELSR's inlets
Supply and testing of panel mounted 96 mm x 48 mm size on line mounted Chlorine Analyzer with display (4 digit) make of FM/ JUMO / ABB/ SIEMENS/ HACH with the technical specifications of Measuring range: 0-10 PPM, Cell constant : 0.1, Process pressure range : 1 bar @ 50 deg c, Measuring method : 2 and 3 Electrode principle, Response time : Approx. 2 min, pH Dependency (loss of slope) : In the range from pH 5 to 7: no loss of slope, at pH 8 about 10%, at pH 9 about 20%, (starting from pH 7), Operating temp : 0 to 50°C, Protection class : IP 67, Communication : RS 485, Voltage : 24 v.. DC, Sensor Case: PVC, Body material : PEI, Cable : 10 Mtrs of Polyimide and the charges are including test and calibration certificate, cost and conveyance of all material, labor and other incidental, transportation, all labour charges.,complete, and as directed by the dept., officer.incharge of work for various ELSR's inlets
Supply and testing of wall mounted 120(w), 140(H), 77(D) Turbidity analyser with display(4 digit) make of FM/ JUMO / ABB/ SIEMENS/ HACH with the technical specifications of Measuring range: 1-4000 Ntu, Process pressure range : 2 bar @ 50 deg c, Measuring method : Infrared light 90 deg scatter light method, Max. sampling rate for measured values: 1 Hz, Resolution : 0.01 to 1 depending on measuring range , Measurands : Turbidity & Temperature Operating temp: 0 to 50 deg c, Protection class : IP 67, Communication : RS 485/4-20 mA, Voltage : 24 v.. DC, Sensor case : PVC/POM-C, Optical window: PMMA, Cable : 10 mtrs of Poly made the charges are including test and calibration certificate, cost and conveyance of all material, labor and and other incidental, transportation, all labour charges.,complete, and as directed by the dept., officer.incharge of work for various ELSR's inlets
Supply laying and fixing of tubing for Inlet and out let of raw water and clear water to the analyzers with necessary pipes with compressed fittings charges excluding cost of taxes and duties including cost and conveyance of all material including transport and labor etc., and other incidental, transportation, all labour charges.,complete, and as directed by the dept., officer.incharge of work for various ELSR's inlets
Supply, errection, Testing & Commissioning of Out door type PLC/Controller based Automation and communication Panel fabricating with 16 SWG CR sheet, internal and external surface coating with Epoxy powder coating, making internal wiring with suitable wires including nomenclature. The panel is suitable for the Control & Monitoring the Level, Flow,Pressure and Quality Parameters and Comunicating with Central SCADA for Auto logic, Local and Remote operation of the valves with specifications of fabricating with 16 SWG CR sheet, internal and external surface coating with powder coating, making internal wiring with suitable wires including nomenclature. The panel is suitable for the above operations with PLC/Controller, communication modules, HMI, Power back up and necessary modules and as per site conditions etc., complete charges including all material and labor and other incidental, transportation, all labour charges.,complete, and as directed by the dept., officer.incharge of work for various ELSR's inlets
Supply laying and jointing of 4 Sq.MM - 2 core PVC sheeted cable make of LAPP/Orbit/Polycab/Finolex for solar / Raw power for the instrumantation and automation at Raw water and clear water pumping with in the Head works compound/ pumping stations/Individual OHSR's and laying with necessary cable trays/Condutes/ Civil works from each and every panel through side walls/cealing / floorings etc., where ever is necessary with all related civil works etc., charges excluding cost of taxes and duties including cost and conveyance of all material including transport and labor and other incidental, transportation, all labour charges.,complete, and as directed by the dept., officer.incharge of work for various ELSR's
Supply laying and jointing of 0.75 Sq.MM - 4 core SS Brided and PVC sheeted cable make of LAPP/Orbit/Polycab/Finolex for solar / Raw power for the instrumantation and automation at Raw water and clear water pumping/ with in the Head works compound/ pumping stations/ Individual OHSR,s and laying with necessary cable trays/Condutes/ Civil works from each and every panel through side walls/cealing / floorings etc., where ever is necessary with all related civil works etc., charges and other incidental, transportation, all labour charges.,complete, and as directed by the dept., officer.incharge of work for various ELSR's
Erection, testing and commissioning of Reservoir Management unit including dejointing of existing pipeline / flange joints, taking out already laid DI/MS or any kind of pipe barrel piece, lifting the said pipe, cleaning & returning to the departmental store as per direction of the Engineer-in-charge and lowering, aligning & placing the flow Meter unit, jointing the same with fabricating of fittings, reducers, flanges with necessary MS material as per flow meter manufacturer standards and as per the site conditions with necessary lifting equiment, fabrication works, fixing with new Nuts , bolts and Rubber insertion with arrangment of necessary earth work excavations, MS clamp brackets, lifting equipment, retrofit works to complete the job as per site condition and other incidental, transportation, all labour charges.,complete, and as directed by the dept., officer.incharge of work for various ELSR's
Integration of PLC panels with Developing necessary softwares and programming as per field condition and user interface, communicated from each panel and intigrated with central SCADA station charges excluding cost of taxes and duties including cost and conveyance of all material including transport and labor etc., and other incidental, transportation, all labour charges.,complete, and as directed by the dept., officer.incharge of work for various ELSR's
supply and delivery of "Resilient Seated Soft Sealing" Gate Valves (Sluice Valves) with Body and Bonnet of Ductile Iron GGG-40/SG-400/15 or GGG-50/SG-500/7 or Equivalent as per IS1865, IS:3896-2 and Wedge fully Rubber Lined with food grade quality grade W270 grade EPDM, Replaceable Spindle Nut without gland packing with 3-O ring protection system on the Shaft and Seals of NBR. The Valves should be Vacuum tight and 100% leak proof with face to face dimensions as BS:5163 Type A/IS:14846. All the valves should be with fusion bonded Electrostatic Powder coating both inside and outside (Min 250 Microns)- RAL 5005 with Pocket Less Straight through body Passage conforming to Design standards of DIN-3202F4/BS:5163 Type A Flange drilling as per IS - 1538 and other incidental, transportation, all labour charges.,complete, and as directed by the dept., officer.incharge of work for various ELSR's
Supply and delivery of Separate Version Electro Magnetic Flow Meter MAG 5100 model or equilant with the specification of flow body as per company standards, electrodes of SS316, accuracy of +/- 2%, cable length of 20 Mtrs, end connection of ANSI flanges as IS/DIN standards, flow bore protection is IP68, earth rings of SS ( If required as per site condition) flow transmitter body as per company standard and two line display, transmitter having 4-20mA, RS485 and modbus communication for data transfer through any network, power supply of 24 volts DC , and submittion of manufacturer test and calbrationreports charges and all charges including cost and conveyance of all material , freight, transport and labour etc and excluding of GST etc., and other incidental, transportation, all labour charges.,complete, and as directed by the dept., officer.incharge of work for Inlet DMA 1 & 2 100KL ELSR's
Supply and delivery of Electrically switched, DI D/F hydraulic and self-medium operated diaphragm Control valve for the functions of Pressure & Flow control at Tank inlet with the function to maintain a constant downstream flow and pressure by controlling the differential pressure between the inlet and outlet of an orifice plate, regardless of pressure variations. The valve shall be of globe pattern inline or angular pattern with a main valve body of full or reduced bore designed for full differential pressure. The seat shall be of stainless steel which is replaceable.The valve can use manually and electrically with 24 V.. AC/DC for operation. The control tubing with self cleaning filter unit to functions as per customer requirement. The internal & external coating with liquid/Powder form epoxy coating, all fastners with SS including cost and convayance of all material and labor and other incidental, transportation, all labour charges.,complete, and as directed by the dept., officer.incharge of work for Inlet DMA 1 & 1000KL ELSR's
Supply ad delivery of 250mm dia M.S. Dismantling Joints /SS, D/F expansion bellows with specifications of bellow with SS ASTM A 240 TP 304 grade, tie rods with EN8/IS-2062 Grade, End connection flanges with IS 2062 Gr.B Sorf plate, Drilling and dimensions as per approved drawing as required by customer at the time of order confirmation charges and other incidental, transportation, all labour charges. etc., complete and as directed by the dept., officer incharge of work
Providing, Installation, Testing and Commissioning of PRESSURE TRANSMITTER for Water Application: Range: 0-10 Bar / Power Supply: 24 V DC / Output: 4-20 mA / Diaphragm: SS316L / Process Connection: 1/2 "NPT (M) / Accuracy: 0.15% Protection: IP67 . The cost also includes the calibration of all the sensors manifold etc., complete including cost and convayance of all material and labor and other incidental, transportation, all labour charges.,complete, and as directed by the dept., officer.incharge of work for Inlet DMA 1 & 2 1000KL ELSR's
Supply, errection, Testing & Commissioning of Out door type PLC/Controller based Automation and communication Panel fabricating with 16 SWG CR sheet, internal and external surface coating with Epoxy powder coating, making internal wiring with suitable wires including nomenclature. The panel is suitable for the Control & Monitoring the Level, Flow, Pressure and Qaulity Parameters and Comunicating with Central SCADA for Auto logic, Local and Remote operation of the valves with specifications of fabricating with 16 SWG CR sheet, internal and external surface coating with powder coating, making internal wiring with suitable wires including nomenclature. The panel is suitable for the above operations with PLC/Controller, communication modules, HMI, Power back up and necessary modules and as per site conditions etc., complete charges including all material and labor and other incidental, transportation, all labour charges.,complete, and as directed by the dept., officer.incharge of work for Inlet DMA 1 & 2 1000KL ELSR's
Supply laying and jointing of 4 Sq.MM - 2 core PVC sheeted cable make of LAPP/Orbit/Polycab/Finolex for solar / Raw power for the instrumantation and automation at Raw water and clear water pumping with in the Head works compound/ pumping stations/Individual OHSR's and laying with necessary cable trays/Condutes/ Civil works from each and every panel through side walls/cealing / floorings etc., where ever is necessary with all related civil works etc., charges and other incidental, transportation, all labour charges.,complete, and as directed by the dept., officer.incharge of work for Inlet DMA 1 & 2 1000KL ELSR's
Supply laying and jointing of 0.75 Sq.MM - 4 core SS Brided and PVC sheeted cable make of LAPP/Orbit/Polycab/Finolex for solar / Raw power for the instrumantation and automation at Raw water and clear water pumping/ with in the Head works compound/ pumping stations/ Individual OHSR,s and laying with necessary cable trays/Condutes/ Civil works from each and every panel through side walls/cealing / floorings etc., where ever is necessary with all related civil works etc., charges and other incidental, transportation, all labour charges.,complete, and as directed by the dept., officer.incharge of work for Inlet DMA 1 & 2 1000KL ELSR's
Erection, testing and commissioning of DMA management unit including dejointing of existing pipeline / flange joints, taking out already laid DI/MS or any kind of pipe barrel piece, lifting the said pipe, cleaning & returning to the departmental store as per direction of the Engineer-in-charge and lowering, aligning & placing the flow Meter unit, jointing the same with fabricating of fittings, reducers, flanges with necessary MS material as per flow meter manufacturer standards and as per the site conditions with necessary lifting equiment, fabrication works, fixing with new Nuts , bolts and Rubber insertion with arrangment of necessary earth work excavations, MS clamp brackets, lifting equipment, retrofit works to complete the job as per site conditionand other incidental, transportation, all labour charges.,complete, and as directed by the dept., officer.incharge of work for Inlet DMA 1 & 2 1000KL ELSR's
Integration of PLC panels with Developing necessary softwares and programming as per field condition and user interface, communicated from each panel and intigrated with central SCADA station charges including cost and conveyance of all material including transport and labor and other incidental, transportation, all labour charges.,complete, and as directed by the dept., officer.incharge of work for Inlet DMA 1 & 2 1000KL ELSR's
Providing, Installing and satisfactory field testing of domestic Water Meter with AMR Compatible Mechanical Water Meters with the specifications of minimum Dynamic ratio (Q3/Q1) of 160:1, fully body made up of composite material/ Brass/ Bronze, the metal Material that come in contact with the water supply shall withstand 2 ppm (Parts per million) of chlorine residual in the water supply and shall be resistant to corrosion, mechanical inferential type, multi jet, magnetically coupled, having dry dial, protection class of IP-68, Class ’B’ confirming to IS-779: 1994 with up to date amendments or ISO 4064:2014 standard with ISI/EEC/OIML/MID/CE certification mark shall be with meter and offer 5 years warranty and submittion of manufacturer test and calbrationreports charges and all charges including cost and conveyance of all material , freight, transport and labour etc., complete, and as directed by the dept., officer. for DN 15-PN-16 AMR compartible, Mechanical water metric Note: Detailesd technical specifications enclosed as Anexure-A.
Supply, Delivery, Installing and satisfactory field testing of AMR Unit for domestic Water Meters from 15 mm to 40 mm with the specifications of fully body made up of composite material, magnetically coupled in between meter and AMR module, protection class of IP-68, In built battery with 3.60 V... Lithium Battery for life of 10 Years based on one communication /Day, Communication interface in between meter and AMR unit with Pulse/ Photo Electric, AMR unit can fetch the data from meter on hourly basis and store the data for 48 Hours on FIFO basis and send the data through NB IoT in every 24 Hours without fail through the provider registered in DOT, India, if the communication fails due to bad communication the AMR module can try for a maximum six times in different time intervals to ensure the data to reach to server. The AMR unit have option of Bluetooth for remote configurations at field. In the special event and field testing the data sending interval of AMR unit can be configurable and minimum time interval span is one Hour (The battery life can be calculated based on the time intervals of data communication) The data storage should be kept in Indian data centres for the data security, AMR unit can be registered the abnormalities like Reverse flow, Leak detection, Tampering and send to the server via reading data packet, Every communication from the AMR module to server should be in JSON format with real time stamping, The AMR can suitable for all the Mechanical Water meters supplied by the agency in this contract. The AMR Module offered with 5 years warranties and submittion of manufacturer test and calbrationreports charges and all charges including cost and conveyance of all material , freight, transport and labour etc and excluding of GST etc., complete, and as directed by the dept., officer. Note: Detailesd technical specifications enclosed as Anexure-B
Supplying and Fixing water meter BOX- with Weather resistant FRP box, press fitted Lid fixing & locking and locked with built-in or external lock. Charges including breather, NBR bushes for pipe entry, SS Grouting screws etc., complete and as directed by the departmment officer.
Supply, erection, testing, commissioning of Hard ware for the SCADA system for Local control station where the SCADA room will be developed by the local ULB for operting & View from Service Reservoirs, DMA and AMI meter management where the instrumantation and automation developed under this project and synchornization by deploying the following components including cost and convayance of all material, user licences, communication networks, etc., complete and as directed by the department officer. a. Desktop PC Station with specification of 17 Processor, 8 GB Ram,-512 GB SSD, 1 Licensed OS, 21" Screen with Mouse, keyboard, and relevant accessories make of LENOVO/HP/DELL b. 55" LED Display make of Sony/Samsung/ LG or equilant with ethernet/HDMI/VGA 1 supported for front end view by connecting with PC in dual mode operation and View the SCADA screens with required cables and connectors etc., complete. c. Modem with specifications of Fibre Port having ILL, PON & Network Features, 1 Speed 100/1000, LAN Ports, Fibre port x 1 NO make of CISCO/HP/FF/ONV/PHOENIX/Dlink/Suggested by the telecom provider
d. 3 KVA Stabilizer with specifications of 220 V.AC Input/ 220 V.AC output, necessary 1 terminal wires etc., complete complete e. 3 KVA online ups with specifications of 220 V.AC Input/ 220 V.AC output, Static By 1 pass with isoltion transformer, Required Battery bank, make of Vertex/EATON/BPE/ NUMERIC/RIELLO/ENERTECH complete f. 3 in one on line B/W A4 Lazer Jet printer g. Network for all local control stations and central station with registration with any 1 communication provider and payment of minimum one year subscription and establishment of communication h.Establishment of Local SCADA station at Jangareddygudem Municipality with the above specifications.
Design, Development, Deploy, testing & commissioning of Firmware for the WEB based SCADA system for Local control station where the SCADA room will be developed by the local ULB for operting & View from Service Reservoirs, DMA and AMI meter management and where the instrumantation and automation developed under this project by synchornization with the field instruments, configuration with the following features including cost and convayance of all material, user licences, communication networks, etc., complete and as directed by the department officer. Development and providing the WEB based SCADA for Operation and Monitoring by 1 the Individual ULB where implemented the Reservoir management to AMI management. (Expandable upto Source to end user) Development of front end view monitoring and operating application in Digital Twin 1 Job Mode with 3D & 20 model including designing, animation, drawings and integration of SCADA with field devices through MQTT/ MODBUS/ TCPIP protocol etc., complete Develop, Supply, install and commissioning of customized WEB applications for Data 1 analytics, Visulation, Trends, Data auditing, generating the reports required by the customer at the time of commissioning
Develop, Supply, install and commissioning of Anroid & 10's application for data 1 monitoring by through Mobi-APP as required by the customer at the time of commissioning complet Establishment of Local SCADA station at langareddygudem Municipality with the above specifications
Construction of Clear Water SCADA Room 8.00 x 12.00 Size at WTP.
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH for Manual Means.as follows
Mechanical Means up to 3 Metres depth in Ordinary Soil
Manual Means up to 3 Metres depth in Ordinary Soil
Supply and filling with Sand complying with standard specifications including cost and conveyance of sand to site to work labour charges watering tamping, ramming etc complete and as directed by the Engineer-in-Charge of the work (APDSS No.101).
Laying Cement concrete (1:4:8) using 40mm nominal size HBG metal M/C including cost and conveyance of all materials from approved quarry, machine mixing, vibrating, laying, levelling, ramming, curing and labour charges etc., complete. As per APSS 402 (BLD-CSTN-2-5).
Construction of Brick Masonary in C.M (1: 6) prop. Using 2nd class country bricks of size 23 X 11 X 7 IS 1077-1992 non modular size hard granite stone including cost and conveyance of all materials like cement, sand, water, Granite stone etc. including cost of and other incidental charges including labour for mixing of cement mortar construction, Scaffolding charges etc. complete for finished item of work.
Plain Cement concrete (M 25) Nominal Mix using 20mm metal using concrete mixer including cost and conveyance of all materials like cement, fine aggregate (sand) coarse aggregate, water etc., to site and including on all materials including all operational, incidental and labour charges such as machine mixing, laying concrete, curing, centering, shuttering etc.,complete for Septic tank Bed.
Plain Cement concrete (M 25) Nominal Mix using 20mm metal using concrete mixer including cost and conveyance of all materials like cement, fine aggregate (sand) coarse aggregate, water etc., to site and including Seigniorage charges, sales & other taxes on all materials including all operational, incidental and labour charges such as machine mixing, laying concrete, curing, centering, shuttering etc.,complete for Septic tank walls
Supply and placing of the RCC M - 25 Design Mix Concrete corresponding to IS 456 using MIXER with 20mm size graded machine crushed hard granite metal (coarse aggregate) from approved quarry including cost and conveyance of all materials like cement, fine aggregate (sand) coarse aggregate, water etc., to site and including Seigniorage charges, sales & other taxes on all materials including all operational, incidental and labour charges such as weigh batching, machine mixing, laying concrete, curing etc.,complete but excluding cost of steel and its fabrication charges for finished item of work (APSS No. 402)with minimum cement content as per IS code from standard suppliers approved by the department including pumping, centering, shuttering, laying concrete, vibrating, curing etc. complete but excluding cost of steel and its fabrication charges for finished item of work.as follows
Footings
Pedastals around Columns
Columns Up to plinth
Plinth Beams 300 x 400
Columns
Up to First Floor Roof Level
Beams 230 x 500
Lintels
Sunshades
Staircase slab 0.15 m thick
RCC Slab 150mm thick
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying including sales and other taxes on all materials etc., complete for finished item of work in all floors.( APSS No.126) for SCADA Room
Brick Masonry in CM (1:6) for 230mm thick with 2nd class Bricks traditional size 23x11x7cms including cost and conveyance of materials to site, mixing of cement mortar and laying of bricks and mortar to specified thickness, watering and curing, scaffolding charges, etc complete for finished item of work as follows
For Ground Floor Level
For First Floor Level
11.5 cm wide Brick masonry for super-structure on ground floor in cm (1:3) using second class traditional size bricks including cost of all materials, seigniorage charges, labour and all operations for constructing half brick masonry, mixing cement mortar, curing etc., complete for finished item of work, but excluding conveyance charges of materials.
Plastering with CM (1:4), 20 mm thick including cost and conveyance of all materials and water to work site and all operational incidental, labour charges such as scaffolding, mixing mortar lift charges curing etc., complete for finished item of work.
Ground Floor
For First Floor
Plastering with CM (1:3), 12 mm thick including cost and conveyance of all materials and water to work site and all operational incidental, labour charges such as scaffolding, mixing mortar lift charges curing etc., complete for finished item of work.
Plastering with CM (1:3), 12 mm thick including cost and conveyance of all materials and water to work site and all operational incidental, labour charges such as scaffolding, mixing mortar lift charges curing etc., complete for finished item of work.
Flooring with 50 mm thick Rough Cuddapah/Shabad stones, set over base coat of cement mortar (1 : 8) 12 mm thick over CC bed already laid or RCC roof slab, including pointing with cement mortar 1:3 duly filling joints nearly, including cost of all materials like flooring stone, cement, sand, and water etc., complete, including seigniorage charges, labour charges for dressing of flooring stones etc., complete for finished item of work, but excluding the cost of conveyance of all materials.
Flooring with ceramic tiles, set over base coat of cement mortar (1:8), 12 mm thick over CC bed already laid or RCC roof slab, including neat cement slurry of honey like consistency spread @ 3.3.kgs per sqm & jointed neatly with white cement paste to full depth mixed with pigment of matching shade, including cost of all materials like cement, sand water and tiles etc., complete, including seigniorage charges, etc., complete for finished item of work, including the cost of conveyance of all materials.
Dadooing to walls with first quality glazed coloured tiles approved colour of any size set over base coat of C.M(1:3)prop. 12mm thick and neat grey cement slurry of honey like consistency spread at the rate of 3.3Kg of cement per sqm and jointed with neat white cement paste at 0.20 kg per sqm mixed with pigment of matching shade to match the shade of tiles including cost and conveyance of all materials labour charges, water to work site,seignourage and all operational .incidental , mixing mortar , fixing in position ,lift charges, curing etc., complete as per SS or as directed by the departmental authorities for finished item of work.
Painting Walls with Snowcem or other equal and approved Water Proof Cement Paint over Priming Coat, 2 Coats (All Colours) This rate is including cost of material and all labour charges, scaffolding charges other incidental charges etc., complete as directed by the departmental officer incharge of work .
Painting Walls with Snowcem or other equal and approved Water Proof Cement Paint over Priming Coat, 2 Coats (All Colours) This rate is including cost of material and all labour charges, scaffolding charges other incidental charges etc., complete as directed by the departmental officer incharge of work .
Painting Walls with Snowcem or other equal and approved Water Proof Cement Paint over Priming Coat, 2 Coats (All Colours) This rate is including cost of material and all labour charges, scaffolding charges other incidental charges etc., complete as directed by the departmental officer incharge of work .
Providing & Fixing of Scientific Doors with metal door frames and door shutters made of galvanize steel (base steel as per IS 513 of 0.58 mm thick D quality, galvanized as per IS 277 with Zinc of 120 GSM) pure polyester powder upto 50-60 microns thick, outer frame section of 100 x 58 mm x 1.2 mm thick, shutter section of 0.80 mm thick galvanized steel sheet pressed (roll formed) for 46mm thick fully flush, double skin door shell seam joints at stile edges, in-fill of honeycomb kraft paper used to give the equired rigidity and effective acoustic insulation with 6” Tower bolt – 1 No., 6” D handles – 2 Nos., 10” Aldrop – 1 No., Butt Hinges – 3 Nos, Mortise Lock of approved quality – 1 No, frames fixed to the concrete/masonry wall by means of self expanding screws complete for finished item of work for Single leaf Door
Supply and fixing of pre-painted steel windows & top hung and fixed louvered ventilators made of pre - painted steel (base steel as per IS 513 of -0.58 mm thick 'D" quality, galvanized as per IS 277 with zinc of 120 GSM) primer coated with epoxy primer of 5-7 microns thick, finish painted with a polyester paint of 12-16 microns thick and back coated with 5-7 microns thick alkyd backer, section for outer frame of 46 x 52 mm section and for shutter of 46 x 46 mm section for mullion 46 x 70 mm, and section for beading should be 18 x 25 mm and section for louvered ventilation of 33 x 56 mm Box section and the windows panelled with 5 mm thick plain float glass & 4 mm pinhead glass for ventilators with Ethyl propylene Diamine monomer Gasket (EPDM) and the sections cut to length mitre joined with corner brocket centre mullions fixed using mullion cap and with handle made of high grade aluminium powder coated and nylon receiver, corner brackets made of CRCA with Zinc Phosphate, Mullion caps made of glass filled nylon, frames fixed to the concrete /masonry wall by means of self expanding screws including 10 mm square guard bars with 6" pitch complete for finished item of work.
Providing & fixing 30 mm thick solid panel PVC door shutter consisting of frame made out of 19 guage M.S tube of 19 x 19 mm for stiles, top & bottom rail, with a coat of primer of approved make. M.S. Frame covered with 5 mm thick heat moulded PVC “C” channel of size of 30 x 50 mm forming stiles, 5 mm thick 75 mm wide PVC sheet for top, lock & bottom rail on either side 20 mm wide cross PVC sheet as gap insert for top & bottom rail, panelling of 10mm(+/-)( 5mm+5mm)” thick PVC sheet fitted in the M.S. frame welded /sealed to the stiles, on either side joined together with solvent cement adhesive etc., additional 5 mm thick PVC strip of 20 mm width stuck on the interior side of the C channel using solvent cement, complete as per direction of Engineer–in–charge, manufacturers specification.
Ventilators: Top Hung 2 '-0" x 2'-0" (609.6x609.6mm) outer frame section size of 46mm x 52 mm shutter frame section size of 46mm x 46 mm
Providing and fixing Thermocole False ceiling in true horizontal level 600 mm x 600 mm using 15 mm/ 19 mm thick Thermocole sheet anodised Aluminium Tee sections of size 24.50 mm x 24.0 mm x 2.4 mm in grid with cross tee of size 24 x 24.5 mm at every 600 mm c/c and anodised aluminium wall angle of size 24 x 24 mm fixed to periphery of the wall and the above grid is suspended at every 1200 mm c/c in both directions using 2.0 mm thick GI Wire for finished of size 600 x 600 mm including Cost &conveyance of all materials and labour charges such as cutting , fixing of standing of frame work exposing roof making complete for finished item of work
Supply and fixing of 25 mm dia 2.00 mm thick PVC pipe concealed in roof slab with all required accessories including masonary work all labour chages This rate including cost of material and labour charges, transporttion charges, hiring of machinary, welding charges and other incidental charges etc., complete as per IE Rules and as directed by the departmental officer incharge of work .
Supply and fixing of 20 mm dia 1.50 mm thick PVC pipe concealed in walls with all required accessories including masonary work for light , fan and plug point with metal deep box including all labour chages This rate including cost of material and labour charges, transporttion charges, hiring of machinary, welding charges and other incidental charges etc., complete as per IE Rules and as directed by the departmental officer incharge of work .
Wiring with 2 runs 14/0.3 mm. (1.0. sq.mm) Fire retardant PVC insulated Flexible copper cable in existing pipe with 6A siwtch, ceiling rose and 3 mm thick hyla sheet covering to switch control box including all labour charges etc,., complete for light, bell , fan and exhaust fan points in non - residential building This rate including cost of material and labour charges, transporttion charges, hiring of machinary, welding charges and other incidental charges etc., complete as per IE Rules and as directed by the departmental officer incharge of work .
Wiring with 2 runs 14/0.3 mm. (1.0. sq.mm) Fire retardant PVC insulated Flexible copper cable in existing pipe with 6A modular siwtch control and 3/2 pin sockets fixing on board including all labour charges This rate including cost of material and labour charges, transporttion charges, hiring of machinary, welding charges and other incidental charges etc., complete as per IE Rules and as directed by the departmental officer incharge of work .
supply and run of 2 of 36/0.3 mm. (1.5. sq.mm) Fire retardant PVC insulated Flexible copper cable in existing pipe for mains including all labour charges This rate including cost of material and labour charges, transporttion charges, hiring of machinary, welding charges and other incidental charges etc., complete as per IE Rules and as directed by the departmental officer incharge of work .
supply and run of 1 of 14/0.3 mm. (1.0. sq.mm) Fire retardant PVC insulated Flexible copper cable in existing pipe for earth continuity including all labour charges etc. This rate including cost of material and labour charges, transporttion charges, hiring of machinary, welding charges and other incidental charges etc., complete as per IE Rules and as directed by the departmental officer incharge of work .
supply and run of 4 of 6 sq.mm (7/18) WPSC alluminium cable along with No.10 SWG G.I barer wire through PVC cleats with all accessories including all labour charges etc., This rate including cost of material and labour charges, transporttion charges, hiring of machinary, welding charges and other incidental charges etc., complete as per IE Rules and as directed by the departmental officer incharge of work .
Providing independent earthing by excavating a trench to a depth of 2.10m in all soils, as per size specied in data ,using 40 mm dia B class GI pipe 2.50m long with necessary accessories with hume pipe ring duly providing staggered holes including filling with equal proportion of salt and charcoal in layers and all labour charges etc complete This rate including cost of material and labour charges, transporttion charges, hiring of machinary, welding charges and other incidental charges etc., complete as per IE Rules and as directed by the departmental officer incharge of work .
Supply and fixing TPN Distribution board with IP-20 protection suitable for 3 phase ELCB / RCCB / FP Isolator as incomer and 10kA SP MCBs as outing going including internal connection and labour charges for surface / flush mounting etc., complete. This rate including cost of material and labour charges, transporttion charges, hiring of machinary, welding charges and other incidental charges etc., complete as per IE Rules and as directed by the departmental officer incharge of work .
Supply of 48" (1200mm) Sweep 5 star rated Ceiling Fan , with double ball bearings, air delivery more than 200 cubic meter/min but without Regulator.Makes : Crompton HS Plus / Havells ES Neo/Orient Energy Star/ Halonix(Zephyr)/Polycab(Synergy Star) unit each complete as per IE Rules and as directed by the departmental officer incharge of work
Supply of stepped type Electronic Regulator of Makes: GM G Home / Gold Medal Olive / Million Zoom / Great white Omega/Koncept/Vimal opel/ Anchor/Vihan/CPL complete as per IE Rules and as directed by the departmental officer incharge of work
Supply and transportation of 20W, 2000 lumens, T8,1200mm length LED retro tube light,wide operating voltage with double side connection, PF≥0.9,Surge protection: > 2KV, THD<15%, with inbuilt driver and frosted cover CCT: 3000K - 6500K as desired by the department and as per IS specifications, minimum CRI≥80,.etc complete with 5 years warranty.LUMINAIRE MAKE: Phillips / OSRAM / GE / Crompton /VIN / Bajaj / Havells / Halonix / HPL. LED MAKE : PHILIPS LUMILEDS / CREE / NICHIA /OSRAM / SAMSUNG / LG LEDs.as per IE Rules and as directed by the departmental officer incharge of work
Labour charges for Fixing of Ceiling fan and regulator including transportation and giving connections with twin core wire etc., complete as per IE Rules and as directed by the departmental officer incharge of work
Labour charges Fixing of 40W tube light luminaire on wall / Ceiling with / TW round blocks with all accessories including giving connections and all labour charges etc., complete.as per IE Rules and as directed by the departmental officer incharge of work
Supply and fixing of 16A 3/2 pin flush type wall plug modular socket with shutter and 16A modular switche controll on a common switch board with earth continuity including wire leads, earth connections along with all labour charges etc., complete. Makes of Switches : GM G Home /Anchor Penta Cherry / Gold Madel Olive / Million Zoom / Great White as per IE Rules and as directed by the departmental officer incharge of work
Supply of 2.0 TR 5 Star capable of delivering 24000 BTU/ hr and above with operating on refrigerant R-32 / R-410A AC unit with high wall mounted indoor unit and outdoor condencing unit Hermetically sealed compressor suitable for operation on 230V, 50Hz, 1Phase AC supply capable of performing cooling dehumidifying air circulating and filtering with cooling and condensing units with 3 mts of copper piping, insulation kit and 4 mts of 3 core copper flexible cable including cordless remote control etc.as per IE Rules and as directed by the departmental officer incharge of work
Providing & Placing on Terrace (at all floor levels) polyethylene water storage tank with Double layer approved brand & manufacture with cover and suitable locking arrangement & making necessary holes for inlet & outlets and over flow pipes but without fittings & base support for tanks as per SS and as directed by the departmental officer incharge of work .
Supplying and fixing 580mm x 440mm long Orissa pan white glazed Water Closet 1st quality ISI marked confirming to IS:2556-Part-3-1981 with "P" or "S" trap, ISI marked and providing masonry seat, CC squatting plate and 10 litres capacity single flush PVC low level cistern with internal components fixed on 2 Nos. of teak wood blocks of size 76.20mm x 101.60mm using required size of nails, screws as approved by Engineer-in-charge, 15 mm nominal size CP finish brass angled stop valve screw type with internal /external threaded conforming to IS 8931, 12.70mm PVC connection with brass union nuts CP coated , 31.75mm brass plumber union, P trap or S trap of Indian W.C. shall be encased on CC (1:2:4) 150mm alround well above the joint to stop leakage at the joint etc., complete including cost and conveyance of all materials to site, cost of CC bed, labour charges and seigniorage charges, overheads & contractors profit etc., complete for finished item of work
SSupplying and fixing Indian make Flat Back Wash Hand Basin 1st quality conforming to IS:2556-Part-4:1972 of size 550mm x 400mm with 32 mm nominal size C.P. Fitting with parallel pipe thread conforming to IS:2963-1979 and fitted with 15 mm nominal bore Chromium Plated Pillar Tap of 1st quality Indian make heavy duty complete with standard CI brackets including wooden blocks ,1 No.12.70mm PVC connection with brass union nuts CP coated , angle stop cock 12.70mm dia. first quality Indian make heavy duty, 30mm dia. PVC flexible waste pipe 914.4mm length of 1st quality including cost and conveyance of all materials to site, labour charges , overheads & contractors profit for finished item of work
Supplying and fixing CP finish brass soap dish of approved make ISI quality including cost and conveyance of all materials, labour charges for fixing , overheads & contractors profit for finished item of work in all floors
Supplying and fixing TV shape mirror with plastic frame of size 609.6mm x 457.2mm , plywood back with NP screws 1st quality including cost and conveyance of all materials, labour charges , overheads & contractors profit for finished item of work in all floors.
Supplying and fixing of 25.4mm dia , 609.6mm long aluminium anodized towel rods with brackets and aluminium screws including cost and conveyance of all materials, labour charges , overheads & contractors profit for finished item of work.
Supplying and fixing white glazed flat back Bowl urinals of size 440 mm x 265 mm x 315 mm with integral flushing rim fixed with screws complete Indian make (HSW/Parry/Neycer) conforming to IS:2556-1995 as approved by Engineer-in-charge, including supply and fixing 12.7mm PVC connection with brass plumber union nuts CP coated, 12.70mm push cock 1st quality of approved make , 30mm dia PVC flexible waste pipe of 914.4 mm length of Ist quality including cost and conveyance of all materials to site, labour charges , overheads & contractors profit complete for finished item of work for all floors
Supply of 110 mm dia 3 m single Socket PVC/SWR pipe - 6 Kg/sq.cm - Prince/Sudhakar/Kisan/Supreme or any ISI Brand.
Supply of 110 mm dia - Plain Bend 87.5 Degree - UPVC/SWR Pipe fittings (Prince/Sudhakar/Kisan/Supreme or any ISI Brand)
Supply of 110 mm dia - Coupler - UPVC/SWR Pipe fittings (Prince/Sudhakar/Kisan/Supreme or any ISI Brand
Labour charges for laying, fixing and commissioning the PVC pipes including couplers/ bends/ tees etc any diameter including fixing necessary fittings like bends, plugs, couplers, junctions, tees, etc with solvent jointing as per standard practice
Constructing 457.2 mm x 457.2 mm (1'6"x1'6") brick in CM 1:6 prop. Masonry. Inspection chamber up to 914.4 mm (3'0") and fitted with light weight 457.2 mm x 457.2 mm (1'6"x1'6") C.I frame and cover of 20 Kg
S& F GI pipe Medium Grade properties & weight as per IS 1239 ISI mark with GI fittings including the cost of pipe & its fittings & labour charges complete
25 mm dia nominal bore -from tank to jn for of individual lines and inlet
20 mm dia nominal bore -from jn for of individual lines to toilets
15 mm dia nominal bore -for internal
S&F of GI & GM fittings
GM Ball valve with SS Ball and SS Spindle as per IS - Class - I, Indian make heavy type - 25 mm NB Size
GM Ball valve with SS Ball and SS Spindle as per IS - Class - I, Indian make heavy type - 20 mm NB Size
GM Ball valve with SS Ball and SS Spindle as per IS - Class - I, Indian make heavy type - 15 mm NB Size
S&F 12.7 mm N.P bib tap Indian make heavy dutys Seiko/ Senior/ Nice or equivalent
S& F GI union Ist Quality
Distribution Network Including House Service Connections and Restoration of Trenches
Laying new Distribution lines zone-I
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH for pipe line trenches
Providing bedding with sand for pipelines trencehs as per specification and drawing including cost and conveyance of materials to site with all leads, lifts including watering, tamping, ramming, labour charges, all other incidental and operational charges etc., complete as per detailed specification and directed by the Engineer - in - Charge
Manufacture, supply and delivery of PE 100-PN 6 HDPE pipes confirming to IS 4984-1995 including transportation to work spot, stacking including all taxes etc. completeas per SS and as directed by the departmental officer incharge of work . As follows
110mm dia.
160mm dia.
200mm dia.
315 mm dia.
355 mm dia.
Manufacture, supply, & delivery of HDPE fittings conforming to IS 4984 - 1995 including transportation to work spot, stacking excluding all taxes and duties etc.complete and other incidental, transportation, all labour charges.,complete, and as directed by the dept., officer.incharge of work
a) Pipe ends - long neck
110mm dia.
160mm dia.
160 mm dia for Air TEEs
200mm dia.
200 mm dia for Air TEEs
315 mm dia.
315 mm dia for Air TEEs
355 mm dia
355 mm dia for Air TEEs
355 mm dia for bulk flow meter
110mm dia.
160mm dia.
160 mm dia for Air TEEs
200mm dia.
200 mm dia for Air TEEs
315 mm dia.
315 mm dia for Air TEEs
355 mm dia
355 mm dia for Air TEEs
355 mm dia for bulk flow meter
110mm dia.
160mm dia.
200mm dia.
110X125 mm dia
125x140 mm dia
140x160 mm dia
160x180 mm dia
180x200 mm dia
200x225 mm dia
225x250 mm dia
250x280 mm dia
280x315 mm dia
315x355 mm dia
e) TEES
110mm dia.
160mm dia.
200mm dia.
315 mm dia.
355 mm dia
F)Bends
110mm dia.
160mm dia.
200mm dia.
315 mm dia.
355 mm dia
Lowering, laying and jointing of HDPE pipes and jointing by butt fusion welding as per IS 7634-part-II/1975 as amended from time to time to the alignment and gradient and testing the pipeline to required pressure etc.complete and other incidental, transportation, all labour charges.,complete, and as directed by the dept., officer.incharge of work
110mm dia.
160mm dia.
200mm dia.
315 mm dia.
355 mm dia.
Supply and delivery of DI Pipes and fittings (Specials) confirming to specification No.I.S.No. 7181/1986, 5531/1988, 3950/1979 excluding GST and other duties including transportation and conveyance to work spot and stacking etc., complete as per S.S and as directed by the departmental authorities.
DIDF pipes for scours
100X2.00m on 110 dia mains for scours
100X2.00m on 160 dia mains for scours
100x1.00m long DF pipes for sluice valves
150X2.00m on 200 mm dia mains for scours
150x1.00m long DF pipes for sluice valves
200x1.00m long DF pipes for sluice valves
300x1.00m long DF pipes for sluice valves
350x1.00m long DF pipes for sluice valves
350x1.00m long DF pipes for bulk flow meter
DI Specials up to 500mm dia including coast of material transportaion, other incdental charges etc., complete as directed by the dept., officer.incharge of work
supply and delivery of "Resilient Seated Soft Sealing" Gate Valves (Sluice Valves) with Body and Bonnet of Ductile Iron GGG-40/SG-400/15 or GGG-50/SG-500/7 or Equivalent as per IS1865, IS:3896-2 and Wedge fully Rubber Lined with food grade quality grade W270 grade EPDM, Replaceable Spindle Nut without gland packing with 3-O ring protection system on the Shaft and Seals of NBR. The Valves should be Vacuum tight and 100% leak proof with face to face dimensions as BS:5163 Type A/IS:14846. All the valves should be with fusion bonded Electrostatic Powder coating both inside and outside (Min 250 Microns)- RAL 5005 with Pocket Less Straight through body Passage conforming to Design standards of DIN-3202F4/BS:5163 Type A Flange drilling as per IS - 1538 other incidental charges, duties and including as followtransportation. PN16 -
100 mm distrubution
150mm dia for distrubution
200mm dia for distrubution
300mm dia for distrubution
350mm dia for distrubution
for scour
100mm dia on 110 mm dia mains
100mm dia on 160 mm dia mains
150 mm dia on 200 mm dia lines
Manufacture, supply and delivery of 80mm dia PN 1.6 Single Chamber DI Air Valve with Body and cover in Ductile Iron of grade SG 400/12 or equivalent grade as per I.S.3896-part2-1985 and subsequent revisions. All internal parts such as float, shell etc., all cover bolts, of stainless steel, and Gaskets and seals of EPDM food grade quality Epoxy powder coating (EP-P) inside and outside colour blue. Drilled as per IS:1538. PN16
Labour charges for lowering and keeping in position of D.I. Sluice valves, reflux valves and scour valves.
100 mm distrubution
150mm dia for distrubution
200mm dia for distrubution
300mm dia for distrubution
350mm dia for distrubution
350 mm dia for bulk flow meter
for scour
100mm dia on 110 mm dia mains
100mm dia on 160 mm dia mains
150 mm dia on 200 mm dia lines
Labour charges for 80mm da fixing Kinetic Air Valves with isolating Sluice valves, Double Air valves/ Air Cushion valve excluding cost of jointing materials such as bolts, nuts and rubber insertions etc., complete.
Construction of sluice and scour Valve Chamber as per type design drawing with RCC including, plastering, RCC cover slabs etc. including cost and conveyance of all material and all labour charges This rate is including cost of material and all labour charges with Earthwork, asand bedding, VCC 1:4:8, RCC bedding and side wall, cover slab with suitble opening, cast stell as per type design approved by the department.etc. complete as per S.S for finished item of work
100 mm distrubution
150mm dia for distrubution
200mm dia for distrubution
300mm dia for distrubution
350mm dia for distrubution
for scour
100mm dia on 110 mm dia mains
100mm dia on 160 mm dia mains
150 mm dia on 200 mm dia lines
Construction of Air Valve Chamber as per type design drawing with RCC including, plastering, RCC cover slabs etc. including cost and conveyance of all material and all labour charges This rate is including cost of material and all labour charges with Earthwork, asand bedding, VCC 1:4:8, RCC bedding and side wall, cover slab with suitble opening, cast stell as per type design approved by the department.etc. complete as per S.S for finished item of work etc. complete as per S.S for finished item of work
80 mm dia on 160 mm pipe
80 mm dia on 200 mm pipe
80mm dia 315 mm pipe
80mm dia 355 mm pipe
Lowering the C.I. Pipes, D.I. Pipes of all classes and fittings with flanged ends carefully into the trenches and laying them true to alignment and gradient including all sundries, but excluding conveyance from source of supply as per BIS No.3114/94.As follows
150 mm dia
200 mm dia
300 mm dia
350 mm dia
Jointing the C.I. Pipes, fittings and valves with flanged ends including cost of jointing materials such as bolts, nuts, rubber insertion, white lead and including filling with water with a water lead upto 500 m and testing to required pressure etc., comp as per BIS No.3114/85.
80 mm dia
100 mm dia
150 mm dia
200 mm dia
300 mm dia
350 mm dia
400 mm dia
Cutting BT road surface as well as asphalt (75mm thick) including water bound. The rate including labour charges for cutting, incidental charges etc., complete as directed by the departmental officer in charge of the work.
Cutting the CC road surface. The rate including cost of all labour cutting ,chargesincidental charges etc complete .This rate including cost of all labour charge , hiring of machinery , fuil charges, wage of driver and other incidental chargestetc complete as per ss and a directed by the departmental officer in charges of work.
Cutting the open water bound macadam. The rate including labour charges for cutting, incidental chargesThis rate including cost of all labour charge , hiring of machinery , fuil charges, wage of driver and other incidental chargestetc complete as per ss and a directed by the departmental officer in charges of work. etc., complete as directed by the departmental officer in charge of the work.
Using Concrete mixture up to Plinth Level : Plain Cement concrete nominal mix M-30 (Cement : fine aggregate: coarse aggregate ) using 20mm size Hard Granite Machine Crushed Graded Metal including cost and conveyance of all materials like cement, sand, coarse aggregate water etc., to site , seigniorage charges on all materials, labour charges , for mixing , laying, concrete , ramming in 15 cm layers, finishing top surface to the required level curing etc., complete for finished item of work with nomonal reinforcement for Road restoration. for BT&CC roads
Laying new Distribution lines zone-II
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH for pipe line trenches
Providing bedding with sand for pipelines trencehs as per specification and drawing including cost and conveyance of materials to site with all leads, lifts including watering, tamping, ramming, labour charges, all other incidental and operational charges etc., complete as per detailed specification and directed by the Engineer - in - Charge
Manufacture, supply and delivery of PE 100-PN 6 HDPE pipes confirming to IS 4984-1995 including transportation to work spot, stacking including all taxes etc. complete as per S.S and as directed by the dept., officer.incharge of work
110mm dia.
160mm dia.
200mm dia.
315 mm dia.
355 mm dia.
Manufacture, supply, & delivery of HDPE fittings conforming to IS 4984 - 1995 including transportation to work spot, stacking etc.complete Treansmit risk other incidental charges etc., complete as per ss and as directed by the departmental officer incharge of work .
a) Pipe ends - long neck
110mm dia.
160mm dia.
160 mm dia for Air TEEs
200mm dia.
200 mm dia for Air TEEs
315 mm dia.
315 mm dia for Air TEEs
355 mm dia
355 mm dia for Air TEEs
355 mm dia for bulk flow meter
110mm dia.
160mm dia.
160 mm dia for Air TEEs
200mm dia.
200 mm dia for Air TEEs
315 mm dia.
315 mm dia for Air TEEs
355 mm dia
355 mm dia for Air TEEs
355 mm dia for bulk flow meter
c) End Caps
160mm dia.
200mm dia.
110X125 mm dia
125x140 mm dia
140x160 mm dia
160x180 mm dia
180x200 mm dia
200x225 mm dia
225x250 mm dia
250x280 mm dia
280x315 mm dia
315x355 mm dia
e) TEES
200mm dia.
355 mm dia
110mm dia.
160mm dia.
200mm dia.
315 mm dia.
355 mm dia
Lowering, laying and jointing of HDPE pipes and jointing by butt fusion welding as per IS 7634-part-II/1975 as amended from time to time to the alignment and gradient and testing the pipeline to required pressure etc.complete as follows
110mm dia.
160mm dia.
200mm dia.
315 mm dia.
355 mm dia.
Supply and delivery of DI Pipes and fittings (Specials) confirming to specification No.I.S.No. 7181/1986, 5531/1988, 3950/1979 excluding GST and other duties including transportation and conveyance to work spot and stacking etc., complete as per S.S and as directed by the departmental authorities.
DIDF pipes for scours
100X2.00m on 110 dia mains for scours
100X2.00m on 160 dia mains for scours
100x1.00m long DF pipes for sluice valves
150X2.00m on 200 mm dia mains for scours
150x1.00m long DF pipes for sluice valves
200x1.00m long DF pipes for sluice valves
300x1.00m long DF pipes for sluice valves
350x1.00m long DF pipes for sluice valves
350x1.00m long DF pipes for bulk flow meter
Supply and delivery of Centrifugally Ductile Iron Fittingsconfiring to IS 9523/2000 having diamention Zinc coated externanly with incside mortor lines a per ss and as directed by the departmental officer in charges of work.
supply and delivery of "Resilient Seated Soft Sealing" Gate Valves (Sluice Valves) with Body and Bonnet of Ductile Iron GGG-40/SG-400/15 or GGG-50/SG-500/7 or Equivalent as per IS1865, IS:3896-2 and Wedge fully Rubber Lined with food grade quality grade W270 grade EPDM, Replaceable Spindle Nut without gland packing with 3-O ring protection system on the Shaft and Seals of NBR. The Valves should be Vacuum tight and 100% leak proof with face to face dimensions as BS:5163 Type A/IS:14846. All the valves should be with fusion bonded Electrostatic Powder coating both inside and outside (Min 250 Microns)- RAL 5005 with Pocket Less Straight through body Passage conforming to Design standards of DIN-3202F4/BS:5163 Type A Flange drilling as per IS - 1538 other incidental charges and including transportation. PN16 -
100 mm distrubution
150mm dia for distrubution
200mm dia for distrubution
300mm dia for distrubution
350mm dia for distrubution
for scour
100mm dia on 110 mm dia mains
100mm dia on 160 mm dia mains
150 mm dia on 200 mm dia lines
150 mm dia on 250 mm dia lines
Manufacture, supply and delivery of 80mm dia PN1.6 Single Chamber DI Air Valve with Body and cover in Ductile Iron of grade SG 400/12 or equivalent grade as per I.S.3896-part2-1985 and subsequent revisions. All internal parts such as float, shell etc., all cover bolts, of stainless steel, and Gaskets and seals of EPDM food grade quality Epoxy powder coating (EP-P) inside and outside colour blue. Drilled as per IS:1538. PN16
Labour charges for lowering and keeping in position of D.I. Sluice valves, reflux valves and scour valves. as per SS and as directed by the departmental officer incharge of work .
100 mm distrubution
150mm dia for distrubution
200mm dia for distrubution
300mm dia for distrubution
350mm dia for distrubution
350 mm dia for bulk flow meter
for scour
100mm dia on 110 mm dia mains
100mm dia on 160 mm dia mains
150 mm dia on 200 mm dia lines
Labour charges for fixing Kinetic Air Valves 80mm dia PN 1.6 with isolating Sluice valves, Double Air valves/ Air Cushion valve excluding cost of jointing materials such as bolts, nuts and rubber insertions etc., complete and as per SS and as directed by the departmental officer incharge of work .
Construction of sluice and scour Valve Chamber as per type design drawing with RCC including, plastering, RCC cover slabs etc. including cost and conveyance of all material and all labour charges This rate is including cost of material and all labour charges with Earthwork, asand bedding, VCC 1:4:8, RCC bedding and side wall, cover slab with suitble opening, cast stell as per type design approved by the department.etc. complete as per S.S for finished item of work
100 mm distrubution
150mm dia for distrubution
200mm dia for distrubution
300mm dia for distrubution
350mm dia for distrubution
for scour
100mm dia on 110 mm dia mains
100mm dia on 160 mm dia mains
150 mm dia on 200 mm dia lines
Construction of Air Valve Chamber as per type design drawing with RCC including, plastering, RCC cover slabs etc. including cost and conveyance of all material and all labour chargesThis rate is including cost of material and all labour charges with Earthwork, asand bedding, VCC 1:4:8, RCC bedding and side wall, cover slab with suitble opening, cast stell as per type design approved by the department. etc. complete as per S.S for finished item of work
80 mm dia on 160 mm pipe
80 mm dia on 200 mm pipe
80mm dia 315 mm pipe
80mm dia 355 mm pipe
Lowering the C.I. Pipes, D.I. Pipes of all classes and fittings with flanged ends carefully into the trenches and laying them true to alignment and gradient including all sundries, but excluding conveyance from source of supply as per BIS No.3114/94.as per SS and as directed by the departmental officer incharge of work . as follows
150 mm dia
200 mm dia
300 mm dia
350 mm dia
Jointing the C.I. Pipes, fittings and valves with flanged ends including cost of jointing materials such as bolts, nuts, rubber insertion, white lead and including filling with water with a water lead upto 500 m and testing to required pressure etc., comp as per BIS No.3114/85.as follows
80 mm dia
100 mm dia
150 mm dia
200 mm dia
300 mm dia
350 mm dia
400 mm dia
Cutting BT road surface as well as asphalt (75mm thick) including water bound. The rate including labour charges for cutting, incidental charges including cost of labour charges, transporttion charges, hiring of machinary,fuil charges,wages of drive other incidental charges etc., complete as per s and as directed by the departmental officer incharge of work . etc., complete as directed by the departmental officer in charge of the work.
Cutting the CC road surface. The rate including labour charges for cutting, incidental charges including cost of labour charges, transporttion charges, hiring of machinary,fuil charges,wages of drive other incidental charges etc., complete as per s and as directed by the departmental officer incharge of work . etc., complete as directed by the departmental officer in charge of the work. etc., complete as directed by the departmental officer in charge of the work.
Cutting the open water bound macadam. The rate including labour charges for cutting, incidental charges including cost of labour charges, transporttion charges, hiring of machinary,fuil charges,wages of drive other incidental charges etc., complete as per s and as directed by the departmental officer incharge of work . etc., complete as directed by the departmental officer in charge of the work. etc., complete as directed by the departmental officer in charge of the work.
Using Concrete mixture up to Plinth Level : Plain Cement concrete nominal mix M-30 (Cement : fine aggregate: coarse aggregate ) using 20mm size Hard Granite Machine Crushed Graded Metal including cost and conveyance of all materials like cement, sand, coarse aggregate water etc., to site , seigniorage charges on all materials, labour charges , for mixing , laying, concrete , ramming in 15 cm layers, finishing top surface to the required level curing etc., complete for finished item of work with nomonal reinforcement for Road restoration. for BT&CC roads
Laying new Distribution lines zone-III
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH for pipe line trenches
Manufacture, supply and delivery of PE 100-PN 6 HDPE pipes confirming to IS 4984-1995 including transportation to work spot, stacking including all taxes etc. complete as per S.S as per SS and as directed by the departmental officer incharge of work . As follkow
110mm dia.
160mm dia.
200mm dia.
315 mm dia.
355 mm dia.
Manufacture, supply, & delivery of HDPE fittings conforming to IS 4984 - 1995 including transportation to work spot, stacking etc.complete transmit risk other incidental,.,complete, as follows
a) Pipe ends - long neck
110mm dia.
160mm dia.
160 mm dia for Air TEEs
200mm dia.
200 mm dia for Air TEEs
315 mm dia.
315 mm dia for Air TEEs
355 mm dia
355 mm dia for Air TEEs
355 mm dia for bulk flow meter
b) MS Flanges
110mm dia.
160mm dia.
160 mm dia for Air TEEs
200mm dia.
200 mm dia for Air TEEs
315 mm dia.
315 mm dia for Air TEEs
315 mm dia for bulk flow meter
355 mm dia
355 mm dia for Air TEEs
355 mm dia for bulk flow meter
c) End Caps
160mm dia.
200mm dia.
110X125 mm dia
125x140 mm dia
140x160 mm dia
160x180 mm dia
180x200 mm dia
200x225 mm dia
225x250 mm dia
250x280 mm dia
280x315 mm dia
315x355 mm dia
e) TEES
110mm dia.
200mm dia.
355 mm dia
F)Bends
160mm dia.
200mm dia.
315 mm dia.
355 mm dia
Lowering, laying and jointing of HDPE pipes and jointing by butt fusion welding as per IS 7634-part-II/1975 as amended from time to time to the alignment and gradient and testing the pipe line to required pressure etc.complete as follows
110mm dia.
160mm dia.
200mm dia.
315 mm dia.
355 mm dia.
Supply and delivery of DI Pipes and fittings (Specials) confirming to specification No.I.S.No. 7181/1986, 5531/1988, 3950/1979 excluding GST and other duties including transportation and conveyance to work spot and stacking etc., complete as per S.S and as directed by the departmental authorities. a follows
DIDF pipes for scours
100X2.00m on 110 dia mains for scours
100X2.00m on 160 dia mains for scours
100x1.00m long DF pipes for sluice valves
150X2.00m on 200 mm dia mains for scours
150x1.00m long DF pipes for sluice valves
200x1.00m long DF pipes for sluice valves
300x1.00m long DF pipes for sluice valves
350x1.00m long DF pipes for sluice valves
350x1.00m long DF pipes for bulk flow meter
Supply and delivery of centrifugally cast (spun) Ductile Iron fittings of K9 Class confirming to IS:9523/2000 having dimensions as per table with cement lining inside, out side Zinc Coating with finishing as per Class 13/IS9523/2000 including cost of Pipe, VAT and other duties. The rate including transportation and conveyance to work spot and stacking at site etc., complete as per S.S and as directed by the departmental authorities.
supply and delivery of "Resilient Seated Soft Sealing" Gate Valves (Sluice Valves) with Body and Bonnet of Ductile Iron GGG-40/SG-400/15 or GGG-50/SG-500/7 or Equivalent as per IS1865, IS:3896-2 and Wedge fully Rubber Lined with food grade quality grade W270 grade EPDM, Replaceable Spindle Nut without gland packing with 3-O ring protection system on the Shaft and Seals of NBR. The Valves should be Vacuum tight and 100% leak proof with face to face dimensions as BS:5163 Type A/IS:14846. All the valves should be with fusion bonded Electrostatic Powder coating both inside and outside (Min 250 Microns)- RAL 5005 with Pocket Less Straight through body Passage conforming to Design standards of DIN-3202F4/BS:5163 Type A Flange drilling as per IS - 1538 excluding all taxes, duties and including transportation. PN16 - as per S.S and as directed by the departmental authorities.
100 mm distrubution
150mm dia for distrubution
200mm dia for distrubution
300mm dia for distrubution
350mm dia for distrubution
400mm dia for distrubution
for scour
100mm dia on 110 mm dia mains
100mm dia on 160 mm dia mains
150 mm dia on 200 mm dia lines
150 mm dia on 250 mm dia lines
Manufacture, supply and delivery of 80mm dia Single Chamber DI Air Valve with Body and cover in Ductile Iron of grade SG 400/12 or equivalent grade as per I.S.3896-part2-1985 and subsequent revisions. All internal parts such as float, shell etc., all cover bolts, of stainless steel, and Gaskets and seals of EPDM food grade quality Epoxy powder coating (EP-P) inside and outside colour blue. Drilled as per IS:1538. PN16
Labour charges for lowering and keeping in position of D.I. Sluice valves, reflux valves and scour valves. as per S.S and as directed by the departmental authorities.
100 mm distrubution
150mm dia for distrubution
200mm dia for distrubution
300mm dia for distrubution
350mm dia for distrubution
350 mm dia for bulk flow meter
for scour
100mm dia on 110 mm dia mains
100mm dia on 160 mm dia mains
150 mm dia on 200 mm dia lines
Labour charges for 80mm dai fixing Kinetic Air Valves with isolating Sluice valves, Double Air valves/ Air Cushion valve excluding cost of jointing materials such as bolts, nuts and rubber insertions etc., complete.
Construction of sluice and scour Valve Chamber as per type design drawing with RCC including, plastering, RCC cover slabs etc. including cost and conveyance of all material and all labour charges This rate is including cost of material and all labour charges with Earthwork, asand bedding, VCC 1:4:8, RCC bedding and side wall, cover slab with suitble opening, cast stell as per type design approved by the department. etc. complete as per S.S for finished item of work
100 mm distrubution
150mm dia for distrubution
200mm dia for distrubution
250mm dia for distrubution
300mm dia for distrubution
350mm dia for distrubution
for scour
100mm dia on 110 mm dia mains
100mm dia on 160 mm dia mains
150 mm dia on 200 mm dia lines
150 mm dia on 250 mm dia lines
Construction of Air Valve Chamber as per type design drawing with RCC including, plastering, RCC cover slabs etc. including cost and conveyance of all material and all labour charges This rate is including cost of material and all labour charges with Earthwork, asand bedding, VCC 1:4:8, RCC bedding and side wall, cover slab with suitble opening, cast stell as per type design approved by the department.etc. complete as per S.S for finished item of work
80 mm dia on 160 mm pipe
80 mm dia on 200 mm pipe
80mm dia 315 mm pipe
80mm dia 355 mm pipe
Lowering the C.I. Pipes, D.I. Pipes of all classes and fittings with flanged ends carefully into the trenches and laying them true to alignment and gradient including all sundries, but excluding conveyance from source of supply as per BIS No.3114/94.as per S.S for finished item of work as follows
150 mm dia
200 mm dia
300 mm dia
350 mm dia
Jointing the C.I. Pipes, fittings and valves with flanged ends including cost of jointing materials such as bolts, nuts, rubber insertion, white lead and including filling with water with a water lead upto 500 m and testing to required pressure etc., comp as per BIS No.3114/85.As follows
80 mm dia
100 mm dia
150 mm dia
200 mm dia
300 mm dia
350 mm dia
400 mm dia
Cutting BT road surface as well as asphalt (75mm thick) including water bound. The rate including labour charges for cutting, incidental charges including hire charges of machinery , dfuil charges , wages of driver and other incidental charges for pipe line cutting trench portion only etc., complete as directed by the departmental officer in charge of the work.
Cutting the CC road surface. The rate including labour charges for cutting, incidental charges including hire charges of machinery , dfuil charges , wages of driver and other incidental charges for pipe line cutting trench portion only etc., complete as directed by the departmental officer in charge of the work.
Cutting the open water bound macadam. The rate including labour charges for cutting, incidental charges including hire charges of machinery , dfuil charges , wages of driver and other incidental charges for pipe line cutting trench portion only etc., complete as directed by the departmental officer in charge of the work.
Filling crushur stone dust in pipe line trenches as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH
Using Concrete mixture up to Plinth Level : Plain Cement concrete nominal mix M-30 (Cement : fine aggregate: coarse aggregate ) using 20mm size Hard Granite Machine Crushed Graded Metal including cost and conveyance of all materials like cement, sand, coarse aggregate water etc., to site , seigniorage charges on all materials, labour charges , for mixing , laying, concrete , ramming in 15 cm layers, finishing top surface to the required level curing etc., complete for finished item of work with nomonal reinforcement for Road restoration. for BT&CC roads
Laying new Distribution lines zone-IV
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH for pipe line trenches
Providing bedding with sand for pipelines trencehs as per specification and drawing including cost and conveyance of materials to site with all leads, lifts including watering, tamping, ramming, labour charges, all other incidental and operational charges etc., complete as per detailed specification and directed by the Engineer - in - Charge
Manufacture, supply and delivery of PE 100-PN 6 HDPE pipes confirming to IS 4984-1995 including transportation to work spot, stacking including all taxes etc. complete as per S.S as follows
110mm dia.
160mm dia.
200mm dia.
Manufacture, supply, & delivery of HDPE fittings conforming to IS 4984 - 1995 including transportation to work spot, stacking excluding all taxes and duties etc.complete as per SS and as directed by the departmental officer incharge of work .
a) Pipe ends - long neck
110mm dia.
160mm dia.
160 mm dia for Air TEEs
200mm dia.
200 mm dia for Air TEEs
315 mm dia.
315 mm dia for Air TEEs
355 mm dia
355 mm dia for Air TEEs
355 mm dia for bulk flow meter
b) MS Flanges
110mm dia.
160mm dia.
160 mm dia for Air TEEs
200mm dia.
200 mm dia for Air TEEs
315 mm dia.
315 mm dia for Air TEEs
355 mm dia
355 mm dia for Air TEEs
355 mm dia for bulk flow meter
c) End Caps
160mm dia.
d) Reducers
110X125 mm dia
125x140 mm dia
140x160 mm dia
160x180 mm dia
180x200 mm dia
200x225 mm dia
225x250 mm dia
250x280 mm dia
280x315 mm dia
315x355 mm dia
F)Bends
160mm dia.
200mm dia.
315 mm dia.
355 mm dia
Lowering, laying and jointing of HDPE pipes and jointing by butt fusion welding as per IS 7634-part-II/1975 as amended from time to time to the alignment and gradient and testing the pipe line to required pressure etc.completeas per SS and as directed by the departmental officer incharge of work .
110mm dia.
160mm dia.
200mm dia.
Supply and delivery of DI Pipes and fittings (Specials) confirming to specification No.I.S.No. 7181/1986, 5531/1988, 3950/1979 excluding GST and other duties including transportation and conveyance to work spot and stacking etc., complete as per S.S and as directed by the departmental authorities. as follows
100X2.00m on 110 dia mains for scours
100X2.00m on 160 dia mains for scours
100x1.00m long DF pipes for sluice valves
150X2.00m on 200 mm dia mains for scours
150x1.00m long DF pipes for sluice valves
200x1.00m long DF pipes for sluice valves
350x1.00m long DF pipes for sluice valves
350x1.00m long DF pipes for bulk flow meter
Supply and delivery of centrifugally cast (spun) Ductile Iron fittings of K9 Class confirming to IS:9523/2000 having dimensions as per table with cement lining inside, out side Zinc Coating with finishing as per Class 13/IS9523/2000 including cost of Pipe, VAT and other duties. The rate including transportation and conveyance to work spot and stacking at site etc., complete as per S.S and as directed by the departmental authoritie
supply and delivery of "Resilient Seated Soft Sealing" Gate Valves (Sluice Valves) with Body and Bonnet of Ductile Iron GGG-40/SG-400/15 or GGG-50/SG-500/7 or Equivalent as per IS1865, IS:3896-2 and Wedge fully Rubber Lined with food grade quality grade W270 grade EPDM, Replaceable Spindle Nut without gland packing with 3-O ring protection system on the Shaft and Seals of NBR. The Valves should be Vacuum tight and 100% leak proof with face to face dimensions as BS:5163 Type A/IS:14846. All the valves should be with fusion bonded Electrostatic Powder coating both inside and outside (Min 250 Microns)- RAL 5005 with Pocket Less Straight through body Passage conforming to Design standards of DIN-3202F4/BS:5163 Type A Flange drilling as per IS - 1538 and including transportation. PN16 - as follows
100 mm distrubution
150mm dia for distrubution
200mm dia for distrubution
350mm dia for distrubution
400mm dia for distrubution
for scour
100mm dia on 110 mm dia mains
100mm dia on 160 mm dia mains
150 mm dia on 200 mm dia lines
Manufacture, supply and delivery of 80mm dia Single Chamber DI Air Valve with Body and cover in Ductile Iron of grade SG 400/12 or equivalent grade as per I.S.3896-part2-1985 and subsequent revisions. All internal parts such as float, shell etc., all cover bolts, of stainless steel, and Gaskets and seals of EPDM food grade quality Epoxy powder coating (EP-P) inside and outside colour blue. Drilled as per IS:1538. PN16
Labour charges for lowering and keeping in position of D.I. Sluice valves, reflux valves and scour valves. as per SS and as directed by the departmental officer incharge of work .
100 mm distrubution
150mm dia for distrubution
200mm dia for distrubution
350mm dia for distrubution
350 mm dia for bulk flow meter
for scour
100mm dia on 110 mm dia mains
100mm dia on 160 mm dia mains
150 mm dia on 200 mm dia lines
Labour charges for fixing Kinetic Air Valves 80mm dia with isolating Sluice valves, Double Air valves/ Air Cushion valve excluding cost of jointing materials such as bolts, nuts and rubber insertions etc., complete.
Construction of sluice and scour Valve Chamber as per type design drawing with RCC including, plastering, RCC cover slabs etc. including cost and conveyance of all material and all labour charges This rate is including cost of material and all labour charges with Earthwork, asand bedding, VCC 1:4:8, RCC bedding and side wall, cover slab with suitble opening, cast stell as per type design approved by the department. etc. complete as per S.S for finished item of work
100 mm distrubution
150mm dia for distrubution
200mm dia for distrubution
350mm dia for distrubution
for scour
100mm dia on 110 mm dia mains
100mm dia on 160 mm dia mains
150 mm dia on 200 mm dia lines
150 mm dia on 250 mm dia lines
Construction of Air Valve Chamber as per type design drawing with RCC including, plastering, RCC cover slabs etc. including cost and conveyance of all material and all labour charges This rate is including cost of material and all labour charges with Earthwork, asand bedding, VCC 1:4:8, RCC bedding and side wall, cover slab with suitble opening, cast stell as per type design approved by the department. etc. complete as per S.S for finished item of work
80 mm dia on 160 mm pipe
80 mm dia on 200 mm pipe
80mm dia 355 mm pipe
Lowering the C.I. Pipes, D.I. Pipes of all classes and fittings with flanged ends carefully into the trenches and laying them true to alignment and gradient including all sundries, but excluding conveyance from source of supply as per BIS No.3114/94.
150 mm dia
200 mm dia
350 mm dia
Jointing the C.I. Pipes, fittings and valves with flanged ends including cost of jointing materials such as bolts, nuts, rubber insertion, white lead and including filling with water with a water lead upto 500 m and testing to required pressure etc., comp as per BIS No.3114/85.
80 mm dia
100 mm dia
150 mm dia
200 mm dia
300 mm dia
350 mm dia
Cutting of existing B.T.road surface (aswell as asphalt concrete up to 75mm thick) including water bound macadam including all labour charges for cutting, stacking of materials etc.including cost of all labour charges ,hiring of machinery fuel charges ,wages of driver etc., complete as per the directions of departmental authorities. For pipe line trenches.
Cutting and open of C.C. Road surface including stacking of excavated materials for lying of pipe lines etc.including cost of all labour charges ,hiring of machinery fuel charges ,wages of driver etc., complete as per the directions of departmental authorities. For pipe line trenches.
Cutting and open of Water bound macadam surface including stacking of excavated materials etc.including cost of all labour charges ,hiring of machinery fuel charges ,wages of driver etc., complete as per the directions of departmental authorities. For pipe line trenches.
Using Concrete mixture up to Plinth Level : Plain Cement concrete nominal mix M-30 (Cement : fine aggregate: coarse aggregate ) using 20mm size Hard Granite Machine Crushed Graded Metal including cost and conveyance of all materials like cement, sand, coarse aggregate water etc., to site , seigniorage charges on all materials, labour charges , for mixing , laying, concrete , ramming in 15 cm layers, finishing top surface to the required level curing etc., complete for finished item of work with nomonal reinforcement for Road restoration. for BT&CC roads
Laying new Distribution lines zone-V
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH for pipe line trenches
Providing bedding with sand for pipelines trencehs as per specification and drawing including cost and conveyance of materials to site with all leads, lifts including watering, tamping, ramming, labour charges, all other incidental and operational charges etc., complete as per detailed specification and directed by the Engineer - in - Charge
Manufacture, supply and delivery of PE 100-PN 6 HDPE pipes confirming to IS 4984-1995 including transportation to work spot, stacking including all taxes etc. complete as per S.S
110mm dia.
200mm dia.
315 mm dia.
355 mm dia.
Manufacture, supply, & delivery of HDPE fittings conforming to IS 4984 - 1995 including transportation to work spot, stacking excluding all taxes and duties etc.complete
a) Pipe ends - long neck
110mm dia.
160mm dia.
160 mm dia for Air TEEs
200mm dia.
200 mm dia for Air TEEs
315 mm dia.
315 mm dia for Air TEEs
355 mm dia
355 mm dia for Air TEEs
355 mm dia for bulk flow meter
b) MS Flanges
110mm dia.
160mm dia.
160 mm dia for Air TEEs
200mm dia.
200 mm dia for Air TEEs
315 mm dia.
315 mm dia for Air TEEs
355 mm dia
355 mm dia for Air TEEs
355 mm dia for bulk flow meter
d) Reducers
110X125 mm dia
125x140 mm dia
140x160 mm dia
160x180 mm dia
180x200 mm dia
200x225 mm dia
225x250 mm dia
250x280 mm dia
280x315 mm dia
315x355 mm dia
F)Bends
160mm dia.
200mm dia.
315 mm dia.
355 mm dia
Lowering, laying and jointing of HDPE pipes and jointing by butt fusion welding as per IS 7634-part-II/1975 as amended from time to time to the alignment and gradient and testing the pipe line to required pressure etc.complete
110mm dia.
200mm dia.
315 mm dia.
355 mm dia.
Supply and delivery of DI Pipes and fittings (Specials) confirming to specification No.I.S.No. 7181/1986, 5531/1988, 3950/1979 excluding GST and other duties including transportation and conveyance to work spot and stacking etc., complete as per S.S and as directed by the departmental authorities.
DIDF pipes for scours
100x1.00m long DF pipes for sluice valves
150X2.00m on 200 mm dia mains for scours
200x1.00m long DF pipes for sluice valves
250x1.00m long DF pipes for sluice valves
300x1.00m long DF pipes for sluice valves
350x1.00m long DF pipes for sluice valves
350x1.00m long DF pipes for bulk flow meter
Supply and delivery of centrifugally cast (spun) Ductile Iron fittings of K9 Class confirming to IS:9523/2000 having dimensions as per table with cement lining inside, out side Zinc Coating with finishing as per Class 13/IS9523/2000 including cost of Pipe, VAT and other duties. The rate including transportation and conveyance to work spot and stacking at site etc., complete as per S.S and as directed by the departmental authoritie
supply and delivery of "Resilient Seated Soft Sealing" Gate Valves (Sluice Valves) with Body and Bonnet of Ductile Iron GGG-40/SG-400/15 or GGG-50/SG-500/7 or Equivalent as per IS1865, IS:3896-2 and Wedge fully Rubber Lined with food grade quality grade W270 grade EPDM, Replaceable Spindle Nut without gland packing with 3-O ring protection system on the Shaft and Seals of NBR. The Valves should be Vacuum tight and 100% leak proof with face to face dimensions as BS:5163 Type A/IS:14846. All the valves should be with fusion bonded Electrostatic Powder coating both inside and outside (Min 250 Microns)- RAL 5005 with Pocket Less Straight through body Passage conforming to Design standards of DIN-3202F4/BS:5163 Type A Flange drilling as per IS - 1538 excluding all taxes, duties and including transportation. PN16
100 mm distrubution
200mm dia for distrubution
350mm dia for distrubution
for scour
150 mm dia on 200 mm dia lines
Manufacture, supply and delivery of 80mm dia Single Chamber DI Air Valve with Body and cover in Ductile Iron of grade SG 400/12 or equivalent grade as per I.S.3896-part2-1985 and subsequent revisions. All internal parts such as float, shell etc., all cover bolts, of stainless steel, and Gaskets and seals of EPDM food grade quality Epoxy powder coating (EP-P) inside and outside colour blue. Drilled as per IS:1538. PN16
Labour charges for lowering and keeping in position of D.I. Sluice valves, reflux valves and scour valves. as per SS and as directed by the departmental officer incharge of work
100 mm distrubution
200mm dia for distrubution
350mm dia for distrubution
350 mm dia for bulk flow meter
for scour
150 mm dia on 200 mm dia lines
Labour charges for fixing Kinetic Air Valves with isolating Sluice valves, Double Air valves/ Air Cushion valve excluding cost of jointing materials such as bolts, nuts and rubber insertions etc., complete.
Construction of sluice and scour Valve Chamber as per type design drawing with RCC including, plastering, RCC cover slabs etc. including cost and conveyance of all material and all labour charges This rate is including cost of material and all labour charges with Earthwork, asand bedding, VCC 1:4:8, RCC bedding and side wall, cover slab with suitble opening, cast stell as per type design approved by the department. etc. complete as per S.S for finished item of work
100 mm distrubution
200mm dia for distrubution
350mm dia for distrubution
for scour
150 mm dia on 200 mm dia lines
Construction of Air Valve Chamber as per type design drawing with RCC including, plastering, RCC cover slabs etc. including cost and conveyance of all material and all labour charges This rate is including cost of material and all labour charges with Earthwork, asand bedding, VCC 1:4:8, RCC bedding and side wall, cover slab with suitble opening, cast stell as per type design approved by the department. etc. complete as per S.S for finished item of work
80 mm dia on 200 mm pipe
80mm dia 355 mm pipe
Lowering the C.I. Pipes, D.I. Pipes of all classes and fittings with flanged ends carefully into the trenches and laying them true to alignment and gradient including all sundries, but excluding conveyance from source of supply as per BIS No.3114/94. as follows
150 mm dia
200 mm dia
350 mm dia
Jointing the C.I. Pipes, fittings and valves with flanged ends including cost of jointing materials such as bolts, nuts, rubber insertion, white lead and including filling with water with a water lead upto 500 m and testing to required pressure etc., comp as per BIS No.3114/85. as follow
80 mm dia
100 mm dia
150 mm dia
200 mm dia
300 mm dia
350 mm dia
400 mm dia
Cutting of existing B.T.road surface (aswell as asphalt concrete up to 75mm thick) including water bound macadam including all labour charges for cutting, stacking of materials etc.including cost of all labour charges ,hiring of machinery fuel charges ,wages of driver etc., complete as per the directions of departmental authorities. For pipe line trenches.
Cutting and open of C.C. Road surface including stacking of excavated materials for lying of pipe lines etc.including cost of all labour charges ,hiring of machinery fuel charges ,wages of driver etc., complete as per the directions of departmental authorities. For pipe line trenches.
Cutting and open of Water bound macadam surface including stacking of excavated materials etc.including cost of all labour charges ,hiring of machinery fuel charges ,wages of driver etc., complete as per the directions of departmental authorities. For pipe line trenches.
Using Concrete mixture up to Plinth Level : Plain Cement concrete nominal mix M-30 (Cement : fine aggregate: coarse aggregate ) using 20mm size Hard Granite Machine Crushed Graded Metal including cost and conveyance of all materials like cement, sand, coarse aggregate water etc., to site , seigniorage charges on all materials, labour charges , for mixing , laying, concrete , ramming in 15 cm layers, finishing top surface to the required level curing etc., complete for finished item of work with nomonal reinforcement for Road restoration. for BT&CC roads
HSC Shifting and Provision for new HSCs
Providing house service connections on HDPE mains at House hold side in Earthen Roads with Earthwork Excavation in all type of soils fixing PP Saddle,PP Clamp Saddle shall be manufactured by injection moulding using virigin Polypropylene,Mechanical tapping saddles for water works purposes and designed for use with PVC/PE pipe as per IS 4985/IS 4984 respectively. These saddles should be contoured to fit around the pipe. PP saddles shall be Blue/Black moulded-in with Nickel plated Brass / SS 304 metal female threaded outlets. Seal shall be thermoplastic elastomer rubber suitable for drinking water and nut-bolt-washer with SS. The PP Clamp saddle fittings shall be mouldedwith SS 304/Nickel plated Brass female threaded outlet inserted to connect necessary fittings. Thread dimension shall conform to IS-554/ISO-7. Adequate thickness of PP shall be provided to hold brass insert in place and avoid leakage while pressure applications. Fasteners shall be threaded type, with SS. Fasteners of size 125mm and above. The grade of raw material used must be certified by WRAS, UK for type test as per BS 6920 from their certified laboratories like NSF International Ltd. UK and certificate of Compliance to be produced for the following parameters: i) Odour&Flavour of water ii) Appearance of water iii) Growth of Micro Organismaxes etc,FOR main pipes Hdpe /PVC of 110mm dia .flow control valve SS 316 NRV 10 LPM ,Compression adaptor with one side compression end to suit 1/2 "to1''(15mmOD to25 mm OD) MDPE pipe and other side with female threaded with SS-304 material inserts of sizes 1/2" BSP threads,body,nut, and cap of poly propylene,clip ring PP Compression Metal insert female Threaded Adaptorcompression adaptor with one side compression end to suit 1/2'' to 1'' mdpe pipe and other side with female thread with ss-304 material inserts of sizes 1/2'' BSP thread,PP compression elbow to suit 1/2 " to 1'' (15mm OD to 25 mm OD) MDPE pipe body, nuts, and caps of polypropelene, clip ring of POM(Acetylic resin) and and "O" ring of NBR material,as per ISO 14236 standardsDouble compression elbow to suit 20mm OD for 100mm, MDPE PE80 Blue pipe as per ISO 4427 up to date 1. for conveyance of potable water ,MDPE 20mm OD pipe (2.00 m avg length for each of 1/2'' HSC) of SDR 9-PN-16 for pipes side,Premium make UPVC Pipes with Fittings.(IS 4985/2000)(PH SSR :20) UPVC pipe for 40 mm (Casing for drain crossing)fixing of 12.7 mm brass bib cock indian make heavy duty long bodyFixing of House service connections,including fixing of ferrule, MDPE/GI pipes and specials and connecting newly laid pipe (For HDPE / PVC Pipes)Making Holes upto 18 mm Dia in RCC/any Stones up to 50 mm Thick( BMS-W78)Fixing of 25.4 mm Holder Back Clamps at Drain Crossing this rate cost of above all materials ,Including all Labour Charges ,other incidental charges etc for finished item of work and as directed by the departmental officer in charge of work
Providing house service connections on HDPE mains at other side in Earthen Roads with Earthwork Excavation in all type of soils fixing PP Saddle,PP Clamp Saddle shall be manufactured by injection moulding using virigin Polypropylene,Mechanical tapping saddles for water works purposes and designed for use with PVC/PE pipe as per IS 4985/IS 4984 respectively. These saddles should be contoured to fit around the pipe. PP saddles shall be Blue/Black moulded-in with Nickel plated Brass / SS 304 metal female threaded outlets. Seal shall be thermoplastic elastomer rubber suitable for drinking water and nut-bolt-washer with SS. The PP Clamp saddle fittings shall be mouldedwith SS 304/Nickel plated Brass female threaded outlet inserted to connect necessary fittings. Thread dimension shall conform to IS-554/ISO-7. Adequate thickness of PP shall be provided to hold brass insert in place and avoid leakage while pressure applications. Fasteners shall be threaded type, with SS. Fasteners of size 125mm and above. The grade of raw material used must be certified by WRAS, UK for type test as per BS 6920 from their certified laboratories like NSF International Ltd. UK and certificate of Compliance to be produced for the following parameters: i) Odour&Flavour of water ii) Appearance of water iii) Growth of Micro Organismaxes etc,FOR main pipes Hdpe /PVC of 110mm dia .flow control valve SS 316 NRV 10 LPM ,Compression adaptor with one side compression end to suit 1/2 "to1''(15mmOD to25 mm OD) MDPE pipe and other side with female threaded with SS-304 material inserts of sizes 1/2" BSP threads,body,nut, and cap of poly propylene,clip ring PP Compression Metal insert female Threaded Adaptorcompression adaptor with one side compression end to suit 1/2'' to 1'' mdpe pipe and other side with female thread with ss-304 material inserts of sizes 1/2'' BSP thread,PP compression elbow to suit 1/2 " to 1'' (15mm OD to 25 mm OD) MDPE pipe body, nuts, and caps of polypropelene, clip ring of POM(Acetylic resin) and and "O" ring of NBR material,as per ISO 14236 standardsDouble compression elbow to suit 20mm OD for 100mm, MDPE PE80 Blue pipe as per ISO 4427 up to date 1. for conveyance of potable water ,MDPE 20mm OD pipe (2.00 m avg length for each of 1/2'' HSC) of SDR 9-PN-16 for pipes side,Premium make UPVC Pipes with Fittings.(IS 4985/2000)(PH SSR :20) UPVC pipe for 40 mm (Casing for drain crossing)fixing of 12.7 mm brass bib cock indian make heavy duty long bodyFixing of House service connections,including fixing of ferrule, MDPE/GI pipes and specials and connecting newly laid pipe (For HDPE / PVC Pipes)Making Holes upto 18 mm Dia in RCC/any Stones up to 50 mm Thick( BMS-W78)Fixing of 25.4 mm Holder Back Clamps at Drain Crossing this rate cost of above all materials ,Including all Labour Charges ,other incidental charges etc for finished item of work and as directed by the departmental officer in charge of work
Providing house service connections on HDPE mains at other side in B.T & CC Roads with Earthwork Excavation in all type of soils fixing PP Saddle,PP Clamp Saddle shall be manufactured by injection moulding using virigin Polypropylene,Mechanical tapping saddles for water works purposes and designed for use with PVC/PE pipe as per IS 4985/IS 4984 respectively. These saddles should be contoured to fit around the pipe. PP saddles shall be Blue/Black moulded-in with Nickel plated Brass / SS 304 metal female threaded outlets. Seal shall be thermoplastic elastomer rubber suitable for drinking water and nut-bolt-washer with SS. The PP Clamp saddle fittings shall be mouldedwith SS 304/Nickel plated Brass female threaded outlet inserted to connect necessary fittings. Thread dimension shall conform to IS-554/ISO-7. Adequate thickness of PP shall be provided to hold brass insert in place and avoid leakage while pressure applications. Fasteners shall be threaded type, with SS. Fasteners of size 125mm and above. The grade of raw material used must be certified by WRAS, UK for type test as per BS 6920 from their certified laboratories like NSF International Ltd. UK and certificate of Compliance to be produced for the following parameters: i) Odour&Flavour of water ii) Appearance of water iii) Growth of Micro Organismaxes etc,FOR main pipes Hdpe /PVC of 110mm dia .flow control valve SS 316 NRV 10 LPM ,Compression adaptor with one side compression end to suit 1/2 "to1''(15mmOD to25 mm OD) MDPE pipe and other side with female threaded with SS-304 material inserts of sizes 1/2" BSP threads,body,nut, and cap of poly propylene,clip ring PP Compression Metal insert female Threaded Adaptorcompression adaptor with one side compression end to suit 1/2'' to 1'' mdpe pipe and other side with female thread with ss-304 material inserts of sizes 1/2'' BSP thread,PP compression elbow to suit 1/2 " to 1'' (15mm OD to 25 mm OD) MDPE pipe body, nuts, and caps of polypropelene, clip ring of POM(Acetylic resin) and and "O" ring of NBR material,as per ISO 14236 standardsDouble compression elbow to suit 20mm OD for 100mm, MDPE PE80 Blue pipe as per ISO 4427 up to date 1. for conveyance of potable water ,MDPE 20mm OD pipe (2.00 m avg length for each of 1/2'' HSC) of SDR 9-PN-16 for pipes side,Premium make UPVC Pipes with Fittings.(IS 4985/2000)(PH SSR :20) UPVC pipe for 40 mm (Casing for drain crossing)fixing of 12.7 mm brass bib cock indian make heavy duty long bodyFixing of House service connections,including fixing of ferrule, MDPE/GI pipes and specials and connecting newly laid pipe (For HDPE / PVC Pipes)Making Holes upto 18 mm Dia in RCC/any Stones up to 50 mm Thick( BMS-W78)Fixing of 25.4 mm Holder Back Clamps at Drain Crossing this rate cost of above all materials ,Including all Labour Charges ,other incidental charges etc for finished item of work and as directed by the departmental officer in charge of work
Providing house service connections on HDPE mains at House hold side in Earthen Roads with Earthwork Excavation in all type of soils fixing PP Saddle,PP Clamp Saddle shall be manufactured by injection moulding using virigin Polypropylene,Mechanical tapping saddles for water works purposes and designed for use with PVC/PE pipe as per IS 4985/IS 4984 respectively. These saddles should be contoured to fit around the pipe. PP saddles shall be Blue/Black moulded-in with Nickel plated Brass / SS 304 metal female threaded outlets. Seal shall be thermoplastic elastomer rubber suitable for drinking water and nut-bolt-washer with SS. The PP Clamp saddle fittings shall be mouldedwith SS 304/Nickel plated Brass female threaded outlet inserted to connect necessary fittings. Thread dimension shall conform to IS-554/ISO-7. Adequate thickness of PP shall be provided to hold brass insert in place and avoid leakage while pressure applications. Fasteners shall be threaded type, with SS. Fasteners of size 125mm and above. The grade of raw material used must be certified by WRAS, UK for type test as per BS 6920 from their certified laboratories like NSF International Ltd. UK and certificate of Compliance to be produced for the following parameters: i) Odour&Flavour of water ii) Appearance of water iii) Growth of Micro Organismaxes etc,FOR main pipes Hdpe /PVC of 110mm dia .flow control valve SS 316 NRV 10 LPM ,Compression adaptor with one side compression end to suit 1/2 "to1''(15mmOD to25 mm OD) MDPE pipe and other side with female threaded with SS-304 material inserts of sizes 1/2" BSP threads,body,nut, and cap of poly propylene,clip ring PP Compression Metal insert female Threaded Adaptorcompression adaptor with one side compression end to suit 1/2'' to 1'' mdpe pipe and other side with female thread with ss-304 material inserts of sizes 1/2'' BSP thread,PP compression elbow to suit 1/2 " to 1'' (15mm OD to 25 mm OD) MDPE pipe body, nuts, and caps of polypropelene, clip ring of POM(Acetylic resin) and and "O" ring of NBR material,as per ISO 14236 standardsDouble compression elbow to suit 20mm OD for 100mm, MDPE PE80 Blue pipe as per ISO 4427 up to date 1. for conveyance of potable water ,MDPE 20mm OD pipe (2.00 m avg length for each of 1/2'' HSC) of SDR 9-PN-16 for pipes side,Premium make UPVC Pipes with Fittings.(IS 4985/2000)(PH SSR :20) UPVC pipe for 40 mm (Casing for drain crossing)fixing of 12.7 mm brass bib cock indian make heavy duty long bodyFixing of House service connections,including fixing of ferrule, MDPE/GI pipes and specials and connecting newly laid pipe (For HDPE / PVC Pipes)Making Holes upto 18 mm Dia in RCC/any Stones up to 50 mm Thick( BMS-W78)Fixing of 25.4 mm Holder Back Clamps at Drain Crossing this rate cost of above all materials ,Including all Labour Charges ,other incidental charges etc for finished item of work and as directed by the departmental officer in charge of work
Implementation of Environmental Management plan
Air Quality Monitoring (5 Monitoring station) once in a month for three seasons during the construction period at Intake well and pumping main, Filtration Plant/WTP, GLSR, ELSR's, Pumping main & Distribution network
Noise level (5 Monitoring station) once in a month for three seasons during the construction period at Intake well and pumping main, Filtration Plant/WTP, GLSR, ELSR's, Pumping main & Distribution network
Water Quality Monitoring surface / ground(5 Monitoring station) once in a month for three seasons during the construction period at Intake well and pumping main, Filtration Plant/WTP, GLSR, ELSR's, Pumping main & Distribution network
Monitoring Costs : Operation Phase ( One year)
Air Quality Monitoring (5 Monitoring station) once in a month for three seasons during the construction period at Intake well and pumping main, Filtration Plant/WTP, GLSR, ELSR's, Pumping main & Distribution network
Noise level (5 Monitoring station) once in a month for three seasons during the construction period at Intake well and pumping main, Filtration Plant/WTP, GLSR, ELSR's, Pumping main & Distribution network
Water Quality Monitoring surface / ground(5 Monitoring station) once in a month for three seasons during the construction period at Intake well and pumping main, Filtration Plant/WTP, GLSR, ELSR's, Pumping main & Distribution network
Compensatory plantation and three years maintenance (Compensatory afforestation ratio is 1:5)
Greenbelt development and maintenance in the surroundings / Buffer zone
Health checkups and free medical distribution
Awareness program/training
Sprinkling of water once in a day for two years (excluding rainy days): 400 days @ Rs.1000/trip
Hiring for 1 Nos. Vehicles for 24 Months during execution period including hire charges of vehicle, diesel, lubrication, driver charges, repairs and all incidental charges etc.,
Providing Technical Graduate for co-ordinating the process of interconnections of the existing and proposed systems, preparation of documents related to inter departmental permissions and liaison with line departments to obtain permissions including preparation of build drawings as instructed by the Engineer in charge.
Providing the services such as consumer survey and mapping, asset mapping, ground validation, component wise structural and hydraulic designs as per site condition, GIS based hydraulic modelling of all components of both existing and proposed water supply infrastructure and any other documentation/ plan/ designs related to the whole scheme as per the instructions of the Engineer incharge and CPHEEO Manual
Operation and Maintenance for the Seven (7) Years including Defect Liability Period-From Source to ELSR's
Engary man power skilled/ Semiskilled like operation, Electrician., pump operation machanic, helper,watch man , filer bed peration, Diploma Engineering, lab technician technical work inspector as per requriment .This rate including wagrs along with miunicipal allowance, cinveyance charges transportion to site including statutory provisions as per norm complete for sucessful Maintenance of the entire scheme and s directed by the departmental officer in charge sof work for 7yers including 2years Defect liabiliy period as follows. including Personal required for operating Intake/Offtake well/Pump houses
Operator
Fitter/Helper
Watch man
Personal required at operating Raw water rising mains
Fitter/Helper
Personal required at operating Water treatment plants & Sump
Operator
Fitter/Helper
Lab Technician
Electrician /Mechanic
Watch man
Personal required at operating Clear water rising mains and Distribution lines
Fitter/Helper
Personal required at operating Gravity mains
Watch man
Personal required at operating Service reservoirs
Watch man
Supply, delivery and stacking of Chorine gas as per relevant indian standards in cylinders including cost of material, coveyance, stacking at the location specified by the Department and inclusive of all taxes except GST etc., complete to be used as a disinfectant in accordance with CPHEEO manual guidelines.
1st year
Supply and delivery of Alumino -Ferric (Alum) as per IS standards including the cost of material, conveyance, stacking at the location specified by the Dept., and including all taxes except GST etc., complete.rement at 15 mg/lit
1st year
Repairs to pumpsets & Water pipe lines (2 years after execution period)
i) Replacement of bearings of pumpsets
ii) Replacement of sleeves
iii) Rewinding of Motors
iv) Raw Water Motors
Clear Water Motors
iv)Replacement of glands of sluice valves
v) Replacements of balls of Air valves
vi) Greease
vii) Gland Packing
LEAKAGES
Operation and Maintenance for the Seven (7) Years including Defect Liability Period-For Distribution network
Personal required at operating distribution system
Fitter/Helper
Earth work Excavation,Bailing out water from Pipe Line Trench and replacement damaged HDPE Pipe for 1 M length including the Cost of Pipe Collar M/F Joint and refilling etc complete
110 mm Dia
160 mm Dia
200 mm Dia
250 mm Dia
Local SCADA at ULB
Jr. Service Engineer (Diploma Engineer) To asist to attend the service calls by the seniour service engineer
Data Operator With assistance of the DBA, preparation of daily reports, monthly billing, correspondence with consumers and also co-ordinate with the GVMC Officials for obtaining of required information when ever asks.
Office assistant To assist the entire team, dispatches and also maintain SCADA station clean and neat
Hiring of vehicle (4 wheeler) Rate as per G.O.MS.No.87 Dated 01-06-2017.
Replacement of necessary servicable materials(Reagents) for Chlorine Analysers * Each Reagent bottle will work for 90 days (Self life) as per the Caluculation based on the Sampling interval in every 10 Minuets.
Replacement of necessary tranducers for PH analysers
Replacement of necessary tranducers for Turbidity analysers
BSNL Charges for static IP Interconnection for Data receive station from all Local Contol RTU panels.
Data transfer from RTU control panels
Charges for maintainance of PC's, Hardware consumables, Minor repair & Servers ,servomax Stabliser, UPS, maintainance of entire system including cost and convayance of all material and labor and attending minor repairs to instrumantation and automation equipment etc., complete
Central SCADA for ULB
Application Engineer (Graduate Engineer) To monitor all issues related to both operation & service
System Engineer (Diploma Engineer) To monitor all meters location through SCADA station and give feedback to the service engineers.
Data Operator With assistance of the DBA, preparation of daily reports, monthly billing, correspondence with consumers and also co-ordinate with the Officials for obtaining of required information when ever asks.
Office assistant To assist the entire team, dispatches and also maintain SCADA station clean and neat
BSNL Charges for static IP Interconnection for Data receive station from all Local Contol RTU panels.
Data base management for WEB reporting Data storage and reporting system for view through WEB and Mobile networks
Charges for maintainance of PC's, Hardware consumables, Minor repair & Servers ,servomax Stabliser, UPS, maintainance of entire system including cost and convayance of all material and labor and attending minor repairs to instrumantation and automation equipment etc., complete for day to day Operations & Reporting
GOLLAPROLU NAGAR PANCHAYAT
Providing 800mm dia DI K7 Clear Water gravity Main from Clear Water Sump to Yeleswaram town
Earth work excavation in all soils up to SDR & stone matrix by machinery as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and back filling in trenches with excavated suitable material as per Technical Specification No.305 MORD/304 MORTH up to initial lift of 3.0ms. For Pipe line trenches.for 800 mm dia DI K7
Manufacture supply delivery,of 800 mm dia DI K7centrifugally cast (spun) ductile iron pipes for water with SOCKET SPIGOT ENDS CONFIRMING TO IS NO 8329/2000 in standard lengths of 4.00,5.00,5.50,6.00m suitable for push-on-joint (rubber gasket D jointing) with cement mortor lining inside and zinc coating out side (K9) including transportation ,loading,unloading, stacking, etc complete as per ss and as directed by the departmental officer incharge of work
Lowering the C.I. Pipes, D.I. Pipes of 800 mm dia DI K7centrifugally and fittings with S/S (Plain)ends carefully into the trenches and laying them true to alignment and gradient including all sundries, but excluding conveyance from source of supply as per BIS No.3114/94.etc complete as per ss and as directed by the departmental officer incharge of work
Jointing the C.I,D.I. Pipes,of 800 mm dia DI K7 fittings and valves with rubber gasket(push-on-joint) including the cost of the gasket but including all sundries, filling with water with a water lead upto 500 m and testing to required pressure etc., comp as per BIS No.3114/1994/12888/1987 etc complete as per ss and as directed by the departmental officer incharge of work
Supply and delivery of Centrifugally cast (spun) Ductile Iron pressure pies with flanged (welded) ends for water, gas, sewage conforming to I.S.: 8329/2000 in standard working Lengths of 1,2,3, 4, 5 mts. for classification k9 with Cement mortar lining inside the pipes with outside Zinc coating. The rates are including transportation, etc. complete as per ss and as directed by the departmental officer incharge of work as follows
800mm dia 2.00m long DI DF pipes for scour
400mm dia 2.00m long DI DF pipes at intake well cum pump house
400mm dia 1.00m long DI DF pipes for sluice and check valves 8+2
Supply, delivery of D.I. fittings of 250mm dia confirming to I.S.No.9523/2000 having dimensions as per table with Zinc coated externally and inside Cement Mortar lining (With finishing as per Class 13/IS 9523/2000) including cost of fittings, transportation, stacking carefully at site. etc.,complete as per S.S. and as directed by the departmental authorities.
Lowering the C.I. Pipes, D.I. of 800 mm diaPipes of all classes and fittings with flanged ends carefully into the trenches and laying them true to alignment and gradient including all sundries, but excluding conveyance from source of supply as per BIS No.3114/94.complete as per S.S. and as directed by the departmental authorities.
Jointing the D.I. Pipes, fittings and valves with flanged ends including cost of jointing materials such as bolts, nuts, rubber insertion, white lead and including filling with water with a water lead upto 500 m and testing to required pressure etc., comp as per BIS No.3114/85 complete as per S.S. and as directed by the departmental authorities. as follows
800 mm dia
250 mm dia
Supply, delivery, of DI D/F Gate Valve (Soft Seated) Resilient seated soft sealing gate valves (Sluice valves) with body bonnet of ductile cast iron of grade GGG40/ SG 400/12 or equivalent grade as per I.S.3896-part2-1985 and subsequent revisions, wedge fully rubber lined with EPDM food grade quality and seals of NBR and the valves should be of vacuum tight and 100% leak proof with face to face dimensions as per BS5163-89/IS14846-2000/DIN 3202 F 4. All the valves should be with Electrostatic powder coating both inside and outside pocket less body passage. Drilled as per IS:1538. The rate including cost, and conveyance to work spot and stacking care fully at site etc.complete as per S.S. and as directed by the departmental authorities. as follows
250mm Ø DI D/F valve - PN16 for scour
150mm Ø DI D/F valve - PN16 for Air valves and Air release valves
Supply, Delivery of D.I 800mm dia double flanged Sluice Valves PN1.6conforming to IS- 14846 (with up to date amendments, if any) including gear arrangements for the following dia. as per test pressure having Body, Bonnet, Dome, Stool cover,Wedge, Stuffing box, Gland, Thrust plate, Cap/Hand wheel with D.I; Stem,Body seat ring, Wedge facing ring, Bushes, Bolts, Nuts, Pinion and Pinion shaft with Stainless steel (IS 6603) ; Wedge nut, Shoe, Channel with Leaded Tin Bronze ( IS 318 ); Gasket with Neoprene Rubber; Gland packing with Rubber;Gear, Gear housing with Cast Steel and transportation, etc complete ISI marked PN 1.6 (MPa) complete as per S.S. and as directed by the departmental authorities. as follows
Supply, delivery and fixing in position of Single Chamber of 150mm dia. PN1.6 DI Air Valve with Body and cover in Ductile Iron of grade SG 400/12 or equivalent grade as per I.S.3896-part2-1985 and subsequent revisions. All internal parts such as float, shell etc., all cover bolts, of stainless steel, and Gaskets and seals of EPDM food grade quality Epoxy powder coating (EP-P) inside and outside colour blue. Drilled as per IS:1538. The rate including labour charges for placing and fixing in position etc.complete as per S.S and as directed by the departmental officer incharge of work
Manufacture, Supply and delivery of 150mm dia. PN1.6 Air Cushion valves / Quick Released damped Air Valves (QRDA) as per AWWA, Ex-factory including trasportation, etc., complete15 kg/sqcm test pressure complete as per S.S and as directed by the departmental officer incharge of work
Labour charges for lowering and keeping in position of C.I./DI Sluice valves(with cap/with hand wheel), reflux valves and scour valves.complete as per S.S and as directed by the departmental officer incharge of work as follows
250 mm dia
150 mm dia
Labour charges for fixing of 150 mm dia Kinetic Air Valves with isolating Sluice valves, Double Air valves/ Air Cushion valve excluding cost of jointing materials such as bolts, nuts and rubber insertions etc., complete.
Construction of R.C.C. thrust blocks using using VRCC M20 Gr. nominal mix using 20mm HBG metal from approved quarry including cost and conveyance of all materials at site, seignorage charges, labour charges for machine mixing, laying, vibrating including centering charges but excluding cost of steel for reinforcement and its fabrication including curing etc.,complete as per S.S and as directed by the departmental officer incharge of work For Thrust Blocks
Providing concrete for plain/reinforced concrete in open foundations using 20mm nominal size Graded hard stone aggregate, mechanically mixed, placed in foundation and compacted by vibration including curing for 14 days complete as per drawings and technical specifications Clause 802, 803, 1202 & 1203 MORD and 1500, 1700 & 2100 MORTH.Nominal mix for Anchor Blocks PCC M20 For Anchor Blocks
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, on all materials etc., complete for finished item of work for thurst blocks
Construction of PCC Sluice/scour Valve chambers suitable to the sluice/scour valves including cost and conveyance of all materials and all labour charges etc.complete as per S.S for finished item of work Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH Note : Classifications of Earth Work Specification are as per 302.2.1(a) of MORD and 301.2.1 of MORT&H--ordinary soil--manual means upto 3m depth manual means
Filling with sand in valve chambers sand bedding. This rate including cost of sand,all labour charges,watering,ramming,and other incidental charges etc as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH etc.,complete as per S.S and as directed by the departmental officer incharge of work
Providing PCC 1:4:8 using 40 mm graded SS 5 HBG m/c metal and OPC coarse and fine aggregate confirming to IS 383 including cost and conveyance of all materials and labour charges, machine mixing , vibration,laying in position, curing ,centering,etc., ,complete as per S.S and as directed by the departmental officer incharge of work
RCC M-20 Nominal mix (cement,fine aggregate,coarse aggregate) corresponding to Table -9 of IS -456 using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including seigniorage charges ,sales and other taxes on all materials including all operational ,incidental and labour charges such as machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work,but including centering,shuttering complete as per S.S and as directed by the departmental officer incharge of work as follows
Raft 0.10m thick
For side walls 0.20m thick 4x1.40=5.60
for cover slabs 0.15 m thick
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying including on all materials etc., complete for finished item of work in all floors.( APSS No.126) for pre cast slabs of valve chambers
Construction of PCC Air Valve chambers suitable to the Air Valve including cost and conveyance of all materials and all labour charges etc.complete as per S.S for finished item of work Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH Note : Classifications of Earth Work Specification are as per 302.2.1(a) of MORD and 301.2.1 of MORT&H--ordinary soil--manual means upto 3m depth manual means
Filling with sand in valve chambers sand bedding. This rate including cost of sand,all labour charges,watering,ramming,and other incidental charges etc as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH etc.,complete as per S.S and as directed by the departmental officer incharge of work
Providing PCC 1:4:8 using 40 mm graded SS 5 HBG m/c metal and OPC coarse and fine aggregate confirming to IS 383 including cost and conveyance of all materials and labour charges, machine mixing , vibration,laying in position, curing ,centering,etc., ,complete as per S.S and as directed by the departmental officer incharge of work
RCC M-20 Nominal mix (cement,fine aggregate,coarse aggregate) corresponding to Table -9 of IS -456 using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including seigniorage charges ,sales and other taxes on all materials including all operational ,incidental and labour charges such as machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work,but including centering,shuttering complete as per S.S and as directed by the departmental officer incharge of work as follows
Raft 0.10m thick
For side walls 0.20m thick 2x1.55+2*1.75=6.6
for cover slabs 0.15 m thick
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying including on all materials etc., complete for finished item of work in all floors.( APSS No.126) for pre cast slabs of valve chambers
Cutting of existing B.T.road surface for pipe line trench (aswell as asphalt concrete up to 75mm thick) including water bound macadam including all labour charges for cutting, stacking this rate including hiring of machinary,fuel charges,wages of driver, complete as per the directions of departmental authorities. complete as per the directions of departmental authorities.
Cutting and open of C.C. Road surface for pipe line trenches including stacking of excavated materials for lying of pipe lines,this rate including hiring of machinary,fuel charges,wages of driver, complete as per the directions of departmental authorities.
Cutting and open of Water bound macadam surface for pipe line trenches including stacking of excavated materials for lying of pipe lines,this rate including hiring of machinary,fuel charges,wages of driver, complete as per the directions of departmental authorities.as per the ditections of the departmental authorities.
Filling with Crusher Stone dust in valve chambers sand bedding. This rate including cost of Dust,all labour charges,watering,ramming,and other incidental charges etc as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH etc.,complete as per S.S and as directed by the departmental officer incharge of work
Restoration of CC Road by Using Concrete mixture Plain Cement concrete nominal mix M-30 (Cement : fine aggregate: coarse aggregate ) using 20mm size Hard Granite Machine Crushed Graded Metal including cost and conveyance of all materials like cement, sand, coarse aggregate water etc., to site , seigniorage charges on all materials, labour charges , for mixing , laying, concrete , ramming in 15 cm layers, finishing top surface to the required level curing etc., complete for finished item of work with nomonal reinforcement for Road restoration.
Manufacture, Supply and delivery of 500mm dia MS. Dismantling Joints with both side flange end suitable for installation in between flange end pipes. Thickness as per IS: 7322. complete as per the directions of departmental authorities.
Railway crossings / Road crossings / Canal crossings by trenchless technology tunneling work through specialized pipe jacking method for inserting 1100mm dia MS Pipe in co-ordination with concerned authorities for as per approved drawings, installing to correct level gradient and alignment by hydralic pipe jacking technique complete including tunneling excavation drive and receive pits ,excavation and all machines tranaportation charges and other required materials but excluding cost of encasing pipe for National HighWay Crossing
Manufacture, Supply and Delivery of outer 1100mm dia 10 mm thick M.S Pipes Conforming to IS 3589/2001 including in lining with Cement motor(1:2)12mm thick using 4 numbers of 6mm dia M.S.Rings at each end of the pipe and Out coating cement motor(1:3)30mm thick by shorcreting or Guniting duly providing wire mesh of size 50x50x3mm including cost of all materials,Labour charges, transportation to anywhere in AP, complete as per the directions of departmental authorities.
Providing 600mm dia DI K7 Clear Water Gravity Main from Kirlampudi junction to Tatiparthi
Earth work excavation in all soils up to SDR & stone matrix by machinery as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and back filling in trenches with excavated suitable material as per Technical Specification No.305 MORD/304 MORTH up to initial lift of 3.0ms. For 600 mm dia DI K7 Pipe line trenches.
Filling with Sand in Pipe line trenches. This rate including cost of Sand,all labour charges,watering,ramming,and other incidental charges etc as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH etc.,complete as per S.S and as directed by the departmental officer incharge of work For 600 mm dia DI K7 Pipe line trenches.
Manufacture supply delivery,of centrifugally cast (spun) of 600 mm dia DI K7 ductile iron pipes for water with SOCKET SPIGOT ENDS CONFIRMING TO IS NO 8329/2000 in standard lengths of 4.00,5.00,5.50,6.00m suitable for push-on-joint (rubber gasket D jointing) with cement mortor lining inside and zinc coating out side (K9) including transportation ,loading,unloading, stacking, etc complete as per S.S and as directed by the departmental officer incharge of work
Lowering the C.I. Pipes, D.I. Pipes of 600 mm dia DI K7 and fittings with S/S (Plain)ends carefully into the trenches and laying them true to alignment and gradient including all sundries, but excluding conveyance from source of supply as per BIS No.3114/94.complete as per S.S and as directed by the departmental officer incharge of work
Jointing the C.I,D.I. Pipes,of 600 mm dia DI K7 fittings and valves with rubber gasket(push-on-joint) including the cost of the gasket but including all sundries, filling with water with a water lead upto 500 m and testing to required pressure etc., comp as per BIS No.3114/1994/12888/1987 complete as per S.S and as directed by the departmental officer incharge of work
Supply and delivery of Centrifugally cast (spun) Ductile Iron pressure pies with flanged (welded) ends for water, gas, sewage conforming to I.S.: 8329/2000 in standard working Lengths of 1,2,3, 4, 5 mts. for classification k9 with Cement mortar lining inside the pipes with outside Zinc coating. The rates are including transportation, etc. complete as per S.S and as directed by the departmental officer incharge of work as follows
300mm dia 2.00m long DI DF pipes for scour
600mm dia 2.00m long DI DF pipes at intake well cum pump house
600mm dia 1.00m long DI DF pipes for sluice and check valves 8+2
Supply, delivery of 600mm dia D.I. fittings confirming to I.S.No.9523/2000 having dimensions as per table with Zinc coated externally and inside Cement Mortar lining (With finishing as per Class 13/IS 9523/2000) including cost of fittings, transportation, stacking carefully at site.,complete as per S.S. and as directed by the departmental authorities.
Lowering the C.I. Pipes, D.I. Pipes of 600mm dia of all classes and fittings with flanged ends carefully into the trenches and laying them true to alignment and gradient including all sundries, but excluding conveyance from source of supply as per BIS No.3114/94.,complete as per S.S. and as directed by the departmental authorities.
Jointing the D.I. Pipes, fittings and valves with flanged ends including cost of jointing materials such as bolts, nuts, rubber insertion, white lead and including filling with water with a water lead upto 500 m and testing to required pressure etc., BIS No.3114/85 complete as per S.S. and as directed by the departmental authorities. as follows
600 mm dia
250 mm dia
150 mm dia
Supply, delivery, of DI D/F Gate Valve (Soft Seated) Resilient seated soft sealing gate valves (Sluice valves) with body bonnet of ductile cast iron of grade GGG40/ SG 400/12 or equivalent grade as per I.S.3896-part2-1985 and subsequent revisions, wedge fully rubber lined with EPDM food grade quality and seals of NBR and the valves should be of vacuum tight and 100% leak proof with face to face dimensions as per BS5163-89/IS14846-2000/DIN 3202 F 4. All the valves should be with Electrostatic powder coating both inside and outside pocket less body passage. Drilled as per IS:1538. The rate including cost of conveyance to work spot and stacking care fully at site etc.complete as per S.S. and as directed by the departmental authorities. as follows
250mm Ø DI D/F valve - PN16 for scour
150mm Ø DI D/F valve - PN16 for Air valves and Air release valves
Supply, Delivery of 600mm Ø DI D/F valve - PN1.6 D.I double flanged Sluice Valves conforming to IS- 14846 (with up to date amendments, if any) including gear arrangements for the following dia. as per test pressure having Body, Bonnet, Dome, Stool cover,Wedge, Stuffing box, Gland, Thrust plate, Cap/Hand wheel with D.I; Stem,Body seat ring, Wedge facing ring, Bushes, Bolts, Nuts, Pinion and Pinion shaft with Stainless steel (IS 6603) ; Wedge nut, Shoe, Channel with Leaded Tin Bronze ( IS 318 ); Gasket with Neoprene Rubber; Gland packing with Rubber;Gear, Gear housing with Cast Steel and transportation, etc complete ISI marked PN 1.6 (MPa)
Supply, delivery and fixing in position of Single Chamber 150mm dia. PN1.6 DI Air Valve with Body and cover in Ductile Iron of grade SG 400/12 or equivalent grade as per I.S.3896-part2-1985 and subsequent revisions. All internal parts such as float, shell etc., all cover bolts, of stainless steel, and Gaskets and seals of EPDM food grade quality Epoxy powder coating (EP-P) inside and outside colour blue. Drilled as per IS:1538. The rate including and labour charges for placing and fixing in position etc.complete as per S.S. and as directed by the departmental authorities. as follows
Manufacture, Supply and delivery of Air Cushion valves / Quick Released damped Air Valves (QRDA) of 150mm dia. PN1.6 as per AWWA, Ex-factory including trasportation, ., complete15 kg/sqcm test pressure complete as per S.S. and as directed by the departmental authorities. as follows
Manufacture, Supply and delivery of 600mm dia DI D/F Swing Check Valves Slanted/Straight seated with metallic, corrosion proof and wear resistant seat faces resilient seat, Body and Disc of ductile cast iron GGG 40/SG Iron 420/12 or equivalent grade as per IS 3896(part2)-1985 and subsequent revisions. All the inside and outside of the body is to be coated with double coating of epoxy liquid. Drilled as per IS:1538. Specification and Dimensions as per I.S 5312 or equivalent codes.complete as per S.S. and as directed by the departmental authorities. as follows
Labour charges for lowering and keeping in position of C.I./DI Sluice valves(with cap/with hand wheel), reflux valves and scour valves.complete as per S.S. and as directed by the departmental authorities. as follows
600 mm dia
250 mm dia
150 mm dia
Labour charges for fixing of 150mm dia Kinetic Air Valves with isolating Sluice valves, Double Air valves/ Air Cushion valve excluding cost of jointing materials such as bolts, nuts and rubber insertions etc., .complete as per S.S. and as directed by the departmental authorities. as follows
Construction of R.C.C. thrust blocks using using VRCC M20 Gr. nominal mix using 20mm HBG metal from approved quarry including cost and conveyance of all materials at site, seignorage charges, labour charges for machine mixing, laying, vibrating including centering charges but excluding cost of steel for reinforcement and its fabrication including curing etc., complete as per S.S. and as directed by the departmental authorities..For Thrust Blocks
Providing concrete for plain/reinforced concrete in open foundations using 20mm nominal size Graded hard stone aggregate, mechanically mixed, placed in foundation and compacted by vibration including curing for 14 days complete as per drawings and technical specifications Clause 802, 803, 1202 & 1203 MORD and 1500, 1700 & 2100 MORTH.complete as per S.S. and as directed by the departmental authorities..For Thrust Blocks complete as per S.S. and as directed by the departmental authorities..For Anchor Blocks
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying including all materials etc., complete for finished item of work complete as per S.S. and as directed by the departmental authorities..For Thrust Blocks
Construction of PCC Sluice/scour Valve chambers suitable to the sluice/scour valves including cost and conveyance of all materials and all labour charges etc.complete as per S.S for finished item of work Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH Note : Classifications of Earth Work Specification are as per 302.2.1(a) of MORD and 301.2.1 of MORT&H--ordinary soil--manual means upto 3m depth manual means
Filling with Sand in Valve chamber bedding This rate including cost of Sand,all labour charges,watering,ramming,and other incidental charges etc as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH etc.,complete as per S.S and as directed by the departmental officer incharge of work
Providing PCC 1:4:8 using 40 mm graded SS 5 HBG m/c metal and OPC coarse and fine aggregate confirming to IS 383 including cost and conveyance of all materials and labour charges, machine mixing , vibration,laying in position, curing etc., complete as per S.S and as directed by the departmental officer incharge of work
RCC M-20 Nominal mix (cement,fine aggregate,coarse aggregate) corresponding to Table -9 of IS -456 using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including seigniorage charges ,sales and other taxes on all materials including all operational ,incidental and labour charges such as machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work,but including centering,shuttering for complete as per S.S and as directed by the departmental officer incharge of work as follows
Raft 0.10m thick
For side walls 0.20m thick 4x1.7=6.80
for cover slabs 150 mm thick
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying including complete for finished item of work in all floors.( APSS No.126) for pre cast slabs of valve chambers
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH Note : Classifications of Earth Work Specification are as per 302.2.1(a) of MORD and 301.2.1 of MORT&H--ordinary soil--manual means upto 3m depth manual means
Filling with Sand in Valve chamber bedding This rate including cost of Sand,all labour charges,watering,ramming,and other incidental charges etc as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH etc.,complete as per S.S and as directed by the departmental officer incharge of work
Providing PCC 1:4:8 using 40 mm graded SS 5 HBG m/c metal and OPC coarse and fine aggregate confirming to IS 383 including cost and conveyance of all materials and labour charges, machine mixing , vibration,laying in position, curing etc., complete as per S.S and as directed by the departmental officer incharge of work
RCC M-20 Nominal mix (cement,fine aggregate,coarse aggregate) corresponding to Table -9 of IS -456 using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including seigniorage charges on all materials including all operational ,incidental and labour charges such as machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work,but including centering,shuttering for complete as per S.S and as directed by the departmental officer incharge of work as follows
Raft 0.10m thick
For side walls 0.20m thick 4x1.40=5.60
for cover slabs 0.15 m thick
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying including all materials etc., complete for finished item of work in all floors.( APSS No.126) for pre cast slabs of valve chambers
Construction of PCC Air Valve chambers suitable to the Air Valve including cost and conveyance of all materials and all labour charges etc.complete as per S.S for finished item of work Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH Note : Classifications of Earth Work Specification are as per 302.2.1(a) of MORD and 301.2.1 of MORT&H--ordinary soil--manual means upto 3m depth manual means
Filling with Sand in Valve chamber bedding This rate including cost of Sand,all labour charges,watering,ramming,and other incidental charges etc as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH etc.,complete as per S.S and as directed by the departmental officer incharge of work
Providing PCC 1:4:8 using 40 mm graded SS 5 HBG m/c metal and OPC coarse and fine aggregate confirming to IS 383 including cost and conveyance of all materials and labour charges, machine mixing , vibration,laying in position, curing etc., complete as per S.S and as directed by the departmental officer incharge of work
RCC M-20 Nominal mix (cement,fine aggregate,coarse aggregate) corresponding to Table -9 of IS -456 using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including seigniorage charges ,on all materials including all operational ,incidental and labour charges such as machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work,but including centering,shuttering as follows
Raft 0.10m thick
For side walls 0.20m thick 2x1.55+2*1.75=6.6
for cover slabs 0.15 m thick
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying including on all materials etc., complete for finished item of work in all floors.( APSS No.126) for pre cast slabs of valve chambers
Cutting of existing B.T.road surface for pipe line trench (aswell as asphalt concrete up to 75mm thick) including water bound macadam including all labour charges for cutting, stacking this rate including hiring of machinary,fuel charges,wages of driver, complete as per the directions of departmental authorities.
Cutting and open of C.C. Road surface for pipe line trenches including stacking of excavated materials for lying of pipe lines,this rate including hiring of machinary,fuel charges,wages of driver, complete as per the directions of departmental authorities.
Cutting and open of Water bound macadam surface for pipe line trenches including stacking of excavated materials for lying of pipe lines,this rate including hiring of machinary,fuel charges,wages of driver, complete as per the directions of departmental authorities.as per the ditections of the departmental authorities.
Filling with Crusher Stone dust in valve chambers sand bedding. This rate including cost of Dust,all labour charges,watering,ramming,and other incidental charges etc as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH etc.,complete as per S.S and as directed by the departmental officer incharge of work
Restoration of CC Road by Using Concrete mixture Plain Cement concrete nominal mix M-30 (Cement : fine aggregate: coarse aggregate ) using 20mm size Hard Granite Machine Crushed Graded Metal including cost and conveyance of all materials like cement, sand, coarse aggregate water etc., to site , seigniorage charges on all materials, labour charges , for mixing , laying, concrete , ramming in 15 cm layers, finishing top surface to the required level curing etc., complete for finished item of work with nomonal reinforcement for Road restoration.
Manufacture, Supply and delivery of 500mm dia MS. Dismantling Joints with both side flange end suitable for installation in between flange end pipes. Thickness as per IS: 7322. These rates are excluding Excise duty, Taxes and transportation charges etc., complete
Railway crossings / Road crossings / Canal crossings by trenchless technology tunneling work through specialized pipe jacking method of 500mm dia MS pipe in co-ordination with concerned authorities for as per approved drawings, installing to correct level gradient and alignment by hydralic pipe jacking technique complete including tunneling excavation drive and receive pits ,excavation and all machines tranaportation charges and other required materials but excluding cost of encasing pipe for Nation High Way Crossing
Manufacture, Supply and Delivery of M.S Pipes Conforming to IS 3589/2001 including in lining with Cement motor(1:2)12mm thick using 4 numbers of 6mm dia M.S.Rings at each end of the pipe and Out coating cement motor(1:3)30mm thick by shorcreting or Guniting duly providing wire mesh of size 50x50x3mm including cost of all materials,Labour charges, transportation to anywhere in AP, for National high Way Crossing
Providing 400mm dia DI K7 Clear Water Gravity Main from Tatiparthi to Gollaprolu
Earth work excavation in all soils up to SDR & stone matrix by machinery as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and back filling in trenches with excavated suitable material as per Technical Specification No.305 MORD/304 MORTH up to initial lift of 3.0ms. For Pipe line trenches.
Filling with Sand in Pipe line trenches. This rate including cost of Sand,all labour charges,watering,ramming,and other incidental charges etc as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH etc.,complete as per S.S and as directed by the departmental officer incharge of work For 600 mm dia DI K7 Pipe line trenches.
Manufacture supply delivery,of centrifugally cast (spun) of 400 mm dia DI K7 ductile iron pipes for water with SOCKET SPIGOT ENDS CONFIRMING TO IS NO 8329/2000 in standard lengths of 4.00,5.00,5.50,6.00m suitable for push-on-joint (rubber gasket D jointing) with cement mortor lining inside and zinc coating out side (K9) including transportation ,loading,unloading, stacking complete as per S.S and as directed by the departmental officer incharge of work
Lowering the C.I. Pipes,400 mm dia DI K7 Pipes and fittings with S/S (Plain)ends carefully into the trenches and laying them true to alignment and gradient including all sundries, but excluding conveyance from source of supply as per BIS No.3114/94. complete as per S.S and as directed by the departmental officer incharge of work
Jointing the C.I,D.I. Pipes of 400 mm dia DI K7 fittings and valves with rubber gasket(push-on-joint) including the cost of the gasket but including all sundries, filling with water with a water lead upto 500 m and testing to required pressure etc., comp as per BIS No.3114/1994/12888/1987 Complete as per S.S and as directed by the departmental officer incharge of work
Supply and delivery of Centrifugally cast (spun) Ductile Iron pressure pies with flanged (welded) ends for water, gas, sewage conforming to I.S.: 8329/2000 in standard working Lengths of 1,2,3, 4, 5 mts. for classification k9 with Cement mortar lining inside the pipes with outside Zinc coating. The rates are including transportation, Complete as per S.S and as directed by the departmental officer incharge of work as follows
200mm dia 2.00m long DI DF pipes for scour
400mm dia 2.00m long DI DF pipes at intake well cum pump house
400mm dia 1.00m long DI DF pipes for sluice and check valves 8+2
Supply, delivery of D.I. fittings 200mm dia confirming to I.S.No.9523/2000 having dimensions as per table with Zinc coated externally and inside Cement Mortar lining (With finishing as per Class 13/IS 9523/2000) including cost of fittings, transportation, stacking carefully at site. The rate ,complete as per S.S. and as directed by the departmental authorities.
Lowering the C.I. Pipes, D.I. Pipes of all classes and fittings with flanged ends carefully into the trenches and laying them true to alignment and gradient including all sundries, as per BIS No.3114/94. complete as per S.S. and as directed by the departmental authorities. as follows
200 mm dia
400 mm dia
Jointing the D.I. Pipes, fittings and valves with flanged ends including cost of jointing materials such as bolts, nuts, rubber insertion, white lead and including filling with water with a water lead upto 500 m and testing to required pressure etc., comp as per BIS No.3114/85 complete as per S.S. and as directed by the departmental authorities. as follows
400 mm dia
200 mm dia
150 mm dia
Supply, delivery, of DI D/F Gate Valve (Soft Seated) Resilient seated soft sealing gate valves (Sluice valves) with body bonnet of ductile cast iron of grade GGG40/ SG 400/12 or equivalent grade as per I.S.3896-part2-1985 and subsequent revisions, wedge fully rubber lined with EPDM food grade quality and seals of NBR and the valves should be of vacuum tight and 100% leak proof with face to face dimensions as per BS5163-89/IS14846-2000/DIN 3202 F 4. All the valves should be with Electrostatic powder coating both inside and outside pocket less body passage. Drilled as per IS:1538. The rate including cost, and conveyance to work spot and stacking care fully at site etc.complete as per S.S. and as directed by the departmental authorities. as follows
250mm Ø DI D/F valve - PN16 for scour
150mm Ø DI D/F valve - PN16 for Air valves and Air release valves
Supply, Delivery of 400mm Ø DI D/F valve - PN1.6 D.I double flanged Sluice Valves conforming to IS- 14846 (with up to date amendments, if any) including gear arrangements for the following dia. as per test pressure having Body, Bonnet, Dome, Stool cover,Wedge, Stuffing box, Gland, Thrust plate, Cap/Hand wheel with D.I; Stem,Body seat ring, Wedge facing ring, Bushes, Bolts, Nuts, Pinion and Pinion shaft with Stainless steel (IS 6603) ; Wedge nut, Shoe, Channel with Leaded Tin Bronze ( IS 318 ); Gasket with Neoprene Rubber; Gland packing with Rubber;Gear, Gear housing with Cast Steel and transportation, etc complete ISI marked PN 1.6 (MPa) complete as per S.S. and as directed by the departmental authorities. as follows
Supply, delivery and fixing in position of Single Chamber 150mm dia PN 1.6 DI Air Valve with Body and cover in Ductile Iron of grade SG 400/12 or equivalent grade as per I.S.3896-part2-1985 and subsequent revisions. All internal parts such as float, shell etc., all cover bolts, of stainless steel, and Gaskets and seals of EPDM food grade quality Epoxy powder coating (EP-P) inside and outside colour blue. Drilled as per IS:1538. The rate including labour charges for placing and fixing in position etc. complete as per S.S. and as directed by the departmental authorities. as follows
Manufacture, Supply and delivery of 150mm dia PN1.6 Air Cushion valves / Quick Released damped Air Valves (QRDA) as per AWWA, Ex-factory including trasportation, etc., complete15 kg/sqcm test pressure complete as per S.S. and as directed by the departmental authorities. as follows
Manufacture, Supply and delivery of 400mm dia DI D/F Swing Check Valves Slanted/Straight seated with metallic, corrosion proof and wear resistant seat faces resilient seat, Body and Disc of ductile cast iron GGG 40/SG Iron 420/12 or equivalent grade as per IS 3896(part2)-1985 and subsequent revisions. All the inside and outside of the body is to be coated with double coating of epoxy liquid. Drilled as per IS:1538. Specification and Dimensions as per I.S 5312 or equivalent codes. complete as per S.S. and as directed by the departmental authorities. as follows
Labour charges for lowering and keeping in position of C.I./DI Sluice valves(with cap/with hand wheel), reflux valves and scour valves.complete as per S.S. and as directed by the departmental authorities. as follows
400 mm dia
200 mm dia
150 mm dia
Labour charges for fixing 150mm dia Kinetic Air Valves with isolating Sluice valves, Double Air valves/ Air Cushion valve excluding cost of jointing materials such as bolts, nuts and rubber insertions etc., complete as per S.S. and as directed by the departmental authorities.
Construction of R.C.C. thrust blocks using using VRCC M20 Gr. nominal mix using 20mm HBG metal from approved quarry including cost and conveyance of all materials at site, seignorage charges, labour charges for machine mixing, laying, vibrating including centering charges but excluding cost of steel for reinforcement and its fabrication including curing etc., complete as per S.S. and as directed by the departmental authorities.
Providing concrete for plain/reinforced concrete in open foundations using 20mm nominal size Graded hard stone aggregate, mechanically mixed, placed in foundation and compacted by vibration including curing for 14 days complete as per drawings and technical specifications Clause 802, 803, 1202 & 1203 MORD and 1500, 1700 & 2100 MORTH.Nominal mix for Anchor Blocks PCC M20 complete as per S.S. and as directed by the departmental authorities.
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying all materials etc., complete for finished item of work for Thrust Blocks
Construction of PCC Sluice/scour Valve chambers suitable to the sluice/scour valves including cost and conveyance of all materials and all labour charges etc.complete as per S.S for finished item of work Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH Note : Classifications of Earth Work Specification are as per 302.2.1(a) of MORD and 301.2.1 of MORT&H--ordinary soil--manual means upto 3m depth manual means
Filling with Sand in Valve chamber bedding This rate including cost of Sand,all labour charges,watering,ramming,and other incidental charges etc as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH etc.,complete as per S.S and as directed by the departmental officer incharge of work
Providing PCC 1:4:8 using 40 mm graded SS 5 HBG m/c metal and OPC coarse and fine aggregate confirming to IS 383 including cost and conveyance of all materials and labour charges, machine mixing , vibration,laying in position, curing etc., complete
RCC M-20 Nominal mix (cement,fine aggregate,coarse aggregate) corresponding to Table -9 of IS -456 using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including seigniorage charges ,sales and other taxes on all materials including all operational ,incidental and labour charges such as machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work,but including centering,shuttering as follows
Raft 0.10m thick
For side walls 0.20m thick 4x1.7=6.80
for cover slabs 150 mm thick
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying including sales and other taxes on all materials etc., complete for finished item of work in all floors.( APSS No.126) for pre cast slabs of valve chambers
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH Note : Classifications of Earth Work Specification are as per 302.2.1(a) of MORD and 301.2.1 of MORT&H--ordinary soil--manual means upto 3m depth manual means
Filling with Sand in Valve chamber bedding This rate including cost of Sand,all labour charges,watering,ramming,and other incidental charges etc as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH etc.,complete as per S.S and as directed by the departmental officer incharge of work
Providing PCC 1:4:8 using 40 mm graded SS 5 HBG m/c metal and OPC coarse and fine aggregate confirming to IS 383 including cost and conveyance of all materials and labour charges, machine mixing , vibration,laying in position, curing etc.,complete as per S.S and as directed by the departmental officer incharge of work
RCC M-20 Nominal mix (cement,fine aggregate,coarse aggregate) corresponding to Table -9 of IS -456 using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including seigniorage charges ,sales and other taxes on all materials including all operational ,incidental and labour charges such as machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work,but including centering,shuttering as follows
Raft 0.10m thick
For side walls 0.20m thick 4x1.40=5.60
for cover slabs 0.15 m thick
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying including all materials etc., complete for finished item of work in all floors.( APSS No.126) for pre cast slabs of valve chambers
Construction of PCC Air Valve chambers suitable to the Air Valve including cost and conveyance of all materials and all labour charges etc.complete as per S.S for finished item of work Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH Note : Classifications of Earth Work Specification are as per 302.2.1(a) of MORD and 301.2.1 of MORT&H--ordinary soil--manual means upto 3m depth manual means
Filling with Sand in Valve chamber bedding This rate including cost of Sand,all labour charges,watering,ramming,and other incidental charges etc as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH etc.,complete as per S.S and as directed by the departmental officer incharge of work
Providing PCC 1:4:8 using 40 mm graded SS 5 HBG m/c metal and OPC coarse and fine aggregate confirming to IS 383 including cost and conveyance of all materials and labour charges, machine mixing , vibration,laying in position, curing etc., complete as per S.S and as directed by the departmental officer incharge of work
RCC M-20 Nominal mix (cement,fine aggregate,coarse aggregate) corresponding to Table -9 of IS -456 using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including seigniorage charges ,sales and other taxes on all materials including all operational ,incidental and labour charges such as machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work,but including centering,shuttering as follows
Raft 0.10m thick
For side walls 0.20m thick 2x1.55+2*1.75=6.6
for cover slabs 0.15 m thick
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying including all materials etc., complete for finished item of work in all floors.( APSS No.126) for pre cast slabs of valve chambers
Cutting of existing B.T.road surface for pipe line trench (aswell as asphalt concrete up to 75mm thick) including water bound macadam including all labour charges for cutting, stacking this rate including hiring of machinary,fuel charges,wages of driver, complete as per the directions of departmental authorities. complete as per the directions of departmental authorities.
Cutting and open of C.C. Road surface for pipe line trenches including stacking of excavated materials for lying of pipe lines,this rate including hiring of machinary,fuel charges,wages of driver, complete as per the directions of departmental authorities.
Cutting and open of Water bound macadam surface for pipe line trenches including stacking of excavated materials for lying of pipe lines,this rate including hiring of machinary,fuel charges,wages of driver, complete as per the directions of departmental authorities.
Filling with Crusher Stone dust in valve chambers sand bedding. This rate including cost of Dust,all labour charges,watering,ramming,and other incidental charges etc as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH etc.,complete as per S.S and as directed by the departmental officer incharge of work
Restoration of CC Road by Using Concrete mixture Plain Cement concrete nominal mix M-30 (Cement : fine aggregate: coarse aggregate ) using 20mm size Hard Granite Machine Crushed Graded Metal including cost and conveyance of all materials like cement, sand, coarse aggregate water etc., to site , seigniorage charges on all materials, labour charges , for mixing , laying, concrete , ramming in 15 cm layers, finishing top surface to the required level curing etc., complete for finished item of work with nomonal reinforcement for Road restoration.
Manufacture, Supply and delivery of 500mm dia MS. Dismantling Joints with both side flange end suitable for installation in between flange end pipes. Thickness as per IS: 7322. ., complete for finished item of work with nomonal reinforcement for Road restoration.complete as per the directions of departmental authorities.
Railway crossings / Road crossings / Canal crossings by trenchless technology tunneling work through specialized pipe jacking method of inserting 500mm dia MS pipe in co-ordination with concerned authorities for as per approved drawings, installing to correct level gradient and alignment by hydralic pipe jacking technique complete including tunneling excavation drive and receive pits ,excavation and all machines tranaportation charges and other required materials complete as per the directions of departmental authorities. National high Way Crossing
Manufacture, Supply and Delivery of M.S Pipes Conforming to IS 3589/2001 including in lining with Cement motor(1:2)12mm thick using 4 numbers of 6mm dia M.S.Rings at each end of the pipe and Out coating cement motor(1:3)30mm thick by shorcreting or Guniting duly providing wire mesh of size 50x50x3mm including cost of all materials,Labour charges, transportation to anywhere in AP, for National high Way Crossing
Providing DI K7 Gravity Mains in Gollaprolu Town
Manufacture supply delivery,of centrifugally cast (spun) ductile iron pipes for water with SOCKET SPIGOT ENDS CONFIRMING TO IS NO 8329/2000 in standard lengths of 4.00, 5.00, 5.50, 6.00m suitable for push-on-joint (rubber gasket D jointing) with cement mortor lining inside and zinc coating out side (K9) including transportation ,loading,unloading, stacking, etc complete as per ss and as direceted by the departmental officer incharge of work as follows
300mm dia
250mm dia
200mm dia
Supply and delivery of "Resilient Seated Soft Sealing" Gate Valves (Sluice Valves) with Body and Bonnet of Ductile Iron GGG-40/SG-400/15 or GGG-50/SG-500/7 or Equivalent as per IS1865, IS:3896-2 and Wedge fully Rubber Lined with food grade quality grade W270 grade EPDM, Replaceable Spindle Nut without gland packing with 3-O ring protection system on the Shaft and Seals of NBR. The Valves should be Vacuum tight and 100% leak proof with face to face dimensions as BS:5163 Type A/IS:14846. All the valves should be with fusion bonded Electrostatic Powder coating both inside and outside (Min 250 Microns)- RAL 5005 with Pocket Less Straight through body Passage conforming to Design standards of DIN-3202F4/BS:5163 Type A Flange drilling as per IS - 1538 complete as per ss and as direceted by the departmental officer incharge of work as follows
300mm dia
250mm dia
200mm dia
Supply & Delivery of Tamper Proof DI Flanged Single Chamber Air Release Valves with body & cover made of Ductile Iron Grade GGG-40/SG-400/15 or GGG-50/SG-500/7 or Equivalent as per IS1865, IS:3896-2 with Food Grade Epoxy Powder Coating(EP-P) (Min:250 Micron) inside and Outside of Color Blue RAL 5005. All internal parts such as Float, shell, Cove Bolts etc. made of Austenitic alloy steel of SS AISI 304/316 and DN 50 float of and other components with ABS/PTFE/EPDM/NBR and generally conforming to DIN/BIS/AWWA standards (or) combination Flange drilling as per IS - 1538 complete as per ss and as direceted by the departmental officer incharge of work as follows
100mm dia on 300mm
80mm dia on 250mm
80mm dia on 200mm
Manufacture, supply and delivery of Centrifugally cast (Spun) Ductile Iron pressure pies with flanged (welded) ends for water, gas, sewage conforming to IS: 8329/2000 in standard working lengths of 1,2,3, 4, 5 mts for classification K9 with cement mortar lining inside the pipes with outside zinc coating. The rate including cost of pipes, transportation of site, etc., complete as per ss and as direceted by the departmental officer incharge of work as follows
300mm x 2.00m for SV
250mm x 2.00m for SV
200mm x 2.00m for SV
Manufacture, supply and delivery of Centrifugally cast (spun) Ductile Iron Fittings conforming to IS:9523/2000 having dimensions as per table. The rates mentioned here under are for fittings, zinc coated externally with inside mortar lining (with finishing as per class 13/IS 9523/2000) (ex-works) including complete as per ss and as direceted by the departmental officer incharge of work
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH etc., complete as per SS and as directed by the Departmental officer in charge of the work as follows
Mechanical 70%
Manual
Cutting of existing B.T.road surface for pipe line trench (aswell as asphalt concrete up to 75mm thick) including water bound macadam including all labour charges for cutting, stacking this rate including hiring of machinary,fuel charges,wages of driver, complete as per the directions of departmental authorities.
Lowering the C.I. Pipes, D.I. Pipes and fittings with S/S (Plain)ends carefully into the trenches and laying them true to alignment and gradient including all sundries, but excluding conveyance from source of supply as per BIS No.3114/94.complete as per the directions of departmental authorities. as follows
300mm dia
250mm dia
200mm dia
Jointing the C.I,D.I. Pipes, fittings and valves with rubber gasket(push-on-joint) including the cost of the gasket but including all sundries, filling with water with a water lead upto 500 m and testing to required pressure etc., comp as per BIS No.3114/1994/12888/1987 .complete as per the directions of departmental authorities. as follows
300mm dia
250mm dia
200mm dia
Labour charges for lowering and keeping in position of D.I. Sluice valves(with cap/with hand wheel), reflux valves and scour valves.this rate including all materials and other incidental charges complete as per the directions of departmental authorities. as follows
300mm dia
250mm dia
200mm dia
Labour charges for fixing Kinetic Air Valves with isolating Sluice valves, Double Air valves/ Air Cushion valve excluding cost of jointing materials such as bolts, nuts and rubber insertions etc., complete as per the directions of departmental authorities. as follows
100mm dia on 300mm
80mm dia on 250mm
80mm dia on 200mm
Lowering the C.I. Pipes, D.I. Pipes of all classes and fittings with flanged ends carefully into the trenches and laying them true to alignment and gradient including all sundries, but excluding conveyance from source of supply as per BIS No.3114/94. complete as per the directions of departmental authorities. as follows
350mm dia
300mm dia
250mm dia
200mm dia
Jointing the C.I. Pipes, fittings and valves with flanged ends including cost of jointing materials such as bolts, nuts, rubber insertion, white lead and including filling with water with a water lead upto 500 m and testing to required pressure etc., BIS No.3114/85.complete as per the directions of departmental authorities. as follows
350mm dia
300mm dia
250mm dia
200mm dia
Railway crossing/Road crossing/Canal crossing by adopting trenchless technology tunneling for insertion of 800mm dia MS pipe through specialized pipe jacking method by erecting the equipment to true to the alignment and gradient, by hydraulic pipe jacking technique complete including tunneling, excavation in all types of soils including hard rock and construction of RCC chambers suitable to casing pipe pits, and conveyance charges of machinery and other required materials but excluding cost of encasing pipe, in co-ordination with the concerned authorities as per approved drawings and directed by the Engineer-in –Charge.
Manufacture, supply and delivery of 800mm dia M.S Spirally Welded Pipes conforming to IS: 3589/2001 including in lining with cement mortar (1:2) 15mm thick using 4 numbers of 6mm dia. M.S. Rings at each end of the pipe and out coating with cement mortar (1:3) 30mm thick by short crating or guniting duly providing wire mesh of size 50x50x3mm including cost of all materials, labor charges, transportation to anywhere in AP.complete as per the directions of departmental authorities.
Construction of Valve Pits, Anchor Blocks, Thrust Blocks Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH etc., complete as per SS and as directed by the Departmental officer in charge of the work
Filling Dust in foundation trenches as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH . The rate including cost and conveyance of all material, labour charges for filling, watering, ramming, etc., complete as per SS and as directed by the departmental officer in charge of the work
Plain Cement concrete (1:4:8) using 40 mm metal with concrete mixer. All work upto plinth level including cost of all materials and labour charges etc., complete as per SS and as directed by the departmental officer in charge of the work
R.C.C grade M 20 (Nominal Mix) using 20mm &10mm metal. The rate including cost and conveyance of all material, labour charges for mixing, laying, vibrating, curing, etc., complete as per SS and as directed by the departmental officer in charge of the work
Walls
C.C grade M 20 (Nominal Mix) using 20mm &10mm metal. The rate including cost and conveyance of all material, labour charges for mixing, laying, vibrating, curing, etc., complete as per SS and as directed by the departmental officer in charge of the work
R.C.C grade M 20 (Nominal Mix) using 20mm &10mm metal. The rate including cost and conveyance of all material, labour charges for mixing, laying, vibrating, curing, etc., complete as per SS and as directed by the departmental officer in charge of the work for thrust blocks
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying including all materials etc., complete for finished item of work in all floors.( APSS No.126) for pre cast slabs of valve chambers
Construction of 700 KL ELSR with a staging of 18m at EBC Colony Zone-1
Construction of ELSRS With the following specification 700kl capacity with a staging of 18 m, without Seismic analysis.
All concrete components shall be designed with M30 Design Mix proportion. The rate are arrived with base rate of cement Rs 4220/- per MT and steel Rs 59000. 1.The foundations shall be designed for solid raft; 2.Rate inclusive of three coats of epoxy paint Food Grade of best quality to inner surface of the Reservoir including roof .3.The above rates are adopted for preparation of estimate for construction of ELSRs/OHSRs for finished work including 2 coats of weather proof emulsion painting for external surfaces, lettering, all required fixtures, Pipes,Pipe specials, valves of DI material, Valve chambers etc., for pipe connections including cost of pipes,specials and valves as per departmental designs and drawings. 4.The above rates adopted for a wind pressure upto "250 kg/sq m". For every 100 kg/sqm decrease in wind pressure, the rate shall be decreased by 5% 5.The Basic rate is adopted by considering the design for Seismic forces for Zone-I & II only of seismic zones 6.The basic rates shall be increased by 15% for Zone-III of seismic zones 7.The ELSR/OHSR shall be designed with minimum of two rows of columns for capacities above 500 KL & upto 1000KL 8.The ELSR/OHSR shall be designed with minimum of three rows of columns for capacities above 1000KL.
i) Pipe connections & Specials with D.I materials (a) All pipe connections for Inlet, Out let, Over Flow, Scour pipes shall be provided with D/F DI material. (b) The Valves for above pipe connections also shall be of DI material of PN 16 duty confirming to the specification of SoR item No.28 (c) All specials such as Bends, Tees, Reducers, Duck foot Bends, Bell mouths etc,. Shall be of DI material. II) The sizes of the verticals for ELSR/OHSR shall be: Above 1000KL three rows columns shall be provided a) For 500 KL to 750 Kl ELSRs Inlet Pipe - 300mm dia. Out let Pipe - 350mm dia. DI valves – 2 No’s Over Flow pipe - 350m dia. Scour Pipe - 200mm dia All Manholes Frames & covers
b) For 800 KL to 1500 Kl ELSRs Inlet Pipe - 400mm dia. Out let Pipe - 450mm dia. DI valves – 2 No’s Over Flow pipe - 450m dia. Scour Pipe - 200mm dia. c) For above 1500 KL to 2500 Kl ELSRs Inlet Pipe - 400mm dia. Out let Pipe - 500mm dia. DI valves – 2 No’s Over Flow pipe - 500m dia. Scour Pipe - 200mm dia. Note: Any deviation from the above sizes as per design, shall be paid or recovered. (iii) Manhole Frames & Covers All man hole Frames & Covers shall be made of CI/DI materials with min. size of 0.60mX 0.60m - For Roof & Valve Chambers. CI/D.I Double Swan neck ventilators (min. of 150mm dia.) shall be provided in top dome and slab with mosquito/fly proof nets - 4Nos. RCC Finial ventilator with fly/bird protection with GI mesh - 1 No. RCC precast ladders of 0.60 m width - 2 Nos. RCC dog legged stair case of 1.00 m flight width and 1.20 m landing width R.C.C hand railing of 1.0 m height – 1 No
The staircase shall be enclosed with brick masonary walls on three side and collapsible MS gate on front side up to 1st brace level, to prevent unauthorized entry Construction of R.C.C valve chambers as per Standard Drawings with RCC cover slab fixed with CI/DI manhole Frame & Cover with lock and Key arrangement. The Mix shall not be less than VRCC M 20 grade with 150mm thick side walls, 150mm thick top slab, 150mm thick base slab over base course of 100mm thick (1:4:8) prop. ) Balcony of 1.00 m width at floor slab level / middle ring beam level by using Stainless Steel pipe of grade 304 hand railing up to 1.20 m height, with top railing of 40mm dia. pipe & middle railing of 25mm dia. and verticals with 40mm dia. at an interval not more than of 1.00m c/c. Lightening Arrestor with all its accessories complete including earthing,with relevant IS Codes - 1 No.
Compound wall: Construction of compound wall including ornamentalM.S.Gate of size 3.0 X 2.40m is included in the basic rate of ELSRs. Length of compound wall hall be minimum of 150m. Min. height of the compound wall shall be 1.80m above plinth and thickness 230mm in brick masonry in CM(1:6).The compound wall shall be constructed including earth work excavation in all types of soils for plinth beam of 230mm X 300mm and 0.75X0.75X1.20m size for column footing portions. The footings shall be of0.75X0.75X0.25m in VRCC M20 grade and constructed over a C.C(1:4:8)prop bed of 100mm thick. The columns shall be of 230X230 mm in size with VRCC M20 grade at 3.00m c/c spacing, having depth of 1.20m below ground level and height of 2.00m above GL. The plinth beam of size of 230X300 mm shall be constructed in VRCC M20 grade at Gound level over a bed of CC(1:4:8)-100mmthick. 450X450mm size columns in M20 grade shall be constructed for gate pillars. All the materials shall be followed as per the standards grade shall be constructed for gate pillars. All the materials shall be followed as per the standards. Tie beam shall be provided above the brick work with 230X200mm size,fixed with MS angulars of 25mm X 25mm X 4mm in "Y" shape to hieght of 0.60m, with embedded length of 150mm in concrete. The barbed wire fencing with 3 ply of 18 gauge shall be streched in 4 rows (2x2). Plastering shall be done with 16mm thick in two coats i.e., base coat 12mm thick in CM(1:6)prop and 4mm thick 2nd coat CM(1:4) prop on both sides of brickwork.
Snowcem paint in two coats shall be provided for both sides of wall. The M.S ornamental gate as per the approved drawings shall be provided with minimum of 3.60mts width and 2.40mts height with enamel paint. Yard lighting shall be arranged on four corners of compound wall. If the length of the wall is increased/ decreased Note:-For every 1m increase/decrease in length of compound wall the increase/decrease in basic rates of ELSRs of the capacities from 500KL to 2500KL shall be as follows.: i) 500 KL : 0.086% ii) 1000 KL : 0.047% iii) 1500 KL : 0.034% iv) 2000 KL : 0.026% v) 2500 KL : 0.022 % For intermediate capacities, interpolated percentages shall be adopted Staff Quarter shall be constructed for a minimum plinth area of 40 sqm with the following specification: RCC framed structure withconcrete grade not less than M20 design mix at the locations specified by the department at the time of execution with verandah, hall, bed room, kitchen and bath &W/C with floor area of 40.00sqmts excluding balconies and staircases
MS hollow door frame with cold rolled processed steel sheet 1.25mm thick bright CRCA conforming to IS 4351/76, Flush door shutters with solid bond wood bond board doors shall be provided. N.C.L. Windows centre fixed both sides openable shutter window 1.35 X 1.35mts outer frame section 48x50mm shutter frame section with a size of 48 X20 mm mullion section of size 48 X 50mm fixed beading section of 12 X 12 mm shall be provided.Flooring with polished Kadapa stone shall be provided. Walls shall be provided with snowcem paint in two coats over primary coat. Electrical and water supply arrangement shall be provided as directed by dept officer.Water Storage tank made with plastic/polymer material of reputed makewith necessary out let and inlet connection pipes shall provided. Septic tank for 5 users shall be provided.
Construction of 500 KL ELSR with a staging of 18m at WTP Zone-2
Construction of ELSRS With the following specification 500 kl capacity with a staging of 18 m, without Seismic analysis.
All concrete components shall be designed with M30 Design Mix proportion. The rate are arrived with base rate of cement Rs 4220/- per MT and steel Rs 59000. 1.The foundations shall be designed for solid raft; 2.Rate inclusive of three coats of epoxy paint Food Grade of best quality to inner surface of the Reservoir including roof .3.The above rates are adopted for preparation of estimate for construction of ELSRs/OHSRs for finished work including 2 coats of weather proof emulsion painting for external surfaces, lettering, all required fixtures, Pipes,Pipe specials, valves of DI material, Valve chambers etc., for pipe connections including cost of pipes,specials and valves as per departmental designs and drawings. 4.The above rates adopted for a wind pressure upto "250 kg/sq m". For every 100 kg/sqm decrease in wind pressure, the rate shall be decreased by 5% 5.The Basic rate is adopted by considering the design for Seismic forces for Zone-I & II only of seismic zones 6.The basic rates shall be increased by 15% for Zone-III of seismic zones 7.The ELSR/OHSR shall be designed with minimum of two rows of columns for capacities above 500 KL & upto 1000KL 8.The ELSR/OHSR shall be designed with minimum of three rows of columns for capacities above 1000KL.
i) Pipe connections & Specials with D.I materials (a) All pipe connections for Inlet, Out let, Over Flow, Scour pipes shall be provided with D/F DI material. (b) The Valves for above pipe connections also shall be of DI material of PN 16 duty confirming to the specification of SoR item No.28 (c) All specials such as Bends, Tees, Reducers, Duck foot Bends, Bell mouths etc,. Shall be of DI material. II) The sizes of the verticals for ELSR/OHSR shall be: Above 1000KL three rows columns shall be provided a) For 500 KL to 750 Kl ELSRs Inlet Pipe - 300mm dia. Out let Pipe - 350mm dia. DI valves – 2 No’s Over Flow pipe - 350m dia. Scour Pipe - 200mm dia All Manholes Frames & covers
b) For 800 KL to 1500 Kl ELSRs Inlet Pipe - 400mm dia. Out let Pipe - 450mm dia. DI valves – 2 No’s Over Flow pipe - 450m dia. Scour Pipe - 200mm dia. c) For above 1500 KL to 2500 Kl ELSRs Inlet Pipe - 400mm dia. Out let Pipe - 500mm dia. DI valves – 2 No’s Over Flow pipe - 500m dia. Scour Pipe - 200mm dia. Note: Any deviation from the above sizes as per design, shall be paid or recovered. (iii) Manhole Frames & Covers All man hole Frames & Covers shall be made of CI/DI materials with min. size of 0.60mX 0.60m - For Roof & Valve Chambers. CI/D.I Double Swan neck ventilators (min. of 150mm dia.) shall be provided in top dome and slab with mosquito/fly proof nets - 4Nos. RCC Finial ventilator with fly/bird protection with GI mesh - 1 No. RCC precast ladders of 0.60 m width - 2 Nos. RCC dog legged stair case of 1.00 m flight width and 1.20 m landing width R.C.C hand railing of 1.0 m height – 1 No
The staircase shall be enclosed with brick masonary walls on three side and collapsible MS gate on front side up to 1st brace level, to prevent unauthorized entry Construction of R.C.C valve chambers as per Standard Drawings with RCC cover slab fixed with CI/DI manhole Frame & Cover with lock and Key arrangement. The Mix shall not be less than VRCC M 20 grade with 150mm thick side walls, 150mm thick top slab, 150mm thick base slab over base course of 100mm thick (1:4:8) prop. ) Balcony of 1.00 m width at floor slab level / middle ring beam level by using Stainless Steel pipe of grade 304 hand railing up to 1.20 m height, with top railing of 40mm dia. pipe & middle railing of 25mm dia. and verticals with 40mm dia. at an interval not more than of 1.00m c/c. Lightening Arrestor with all its accessories complete including earthing,with relevant IS Codes - 1 No.
Compound wall: Construction of compound wall including ornamentalM.S.Gate of size 3.0 X 2.40m is included in the basic rate of ELSRs. Length of compound wall hall be minimum of 150m. Min. height of the compound wall shall be 1.80m above plinth and thickness 230mm in brick masonry in CM(1:6).The compound wall shall be constructed including earth work excavation in all types of soils for plinth beam of 230mm X 300mm and 0.75X0.75X1.20m size for column footing portions. The footings shall be of0.75X0.75X0.25m in VRCC M20 grade and constructed over a C.C(1:4:8)prop bed of 100mm thick. The columns shall be of 230X230 mm in size with VRCC M20 grade at 3.00m c/c spacing, having depth of 1.20m below ground level and height of 2.00m above GL. The plinth beam of size of 230X300 mm shall be constructed in VRCC M20 grade at Gound level over a bed of CC(1:4:8)-100mmthick. 450X450mm size columns in M20 grade shall be constructed for gate pillars. All the materials shall be followed as per the standards grade shall be constructed for gate pillars. All the materials shall be followed as per the standards. Tie beam shall be provided above the brick work with 230X200mm size,fixed with MS angulars of 25mm X 25mm X 4mm in "Y" shape to hieght of 0.60m, with embedded length of 150mm in concrete. The barbed wire fencing with 3 ply of 18 gauge shall be streched in 4 rows (2x2). Plastering shall be done with 16mm thick in two coats i.e., base coat 12mm thick in CM(1:6)prop and 4mm thick 2nd coat CM(1:4) prop on both sides of brickwork.
Snowcem paint in two coats shall be provided for both sides of wall. The M.S ornamental gate as per the approved drawings shall be provided with minimum of 3.60mts width and 2.40mts height with enamel paint. Yard lighting shall be arranged on four corners of compound wall. If the length of the wall is increased/ decreased Note:-For every 1m increase/decrease in length of compound wall the increase/decrease in basic rates of ELSRs of the capacities from 500KL to 2500KL shall be as follows.: i) 500 KL : 0.086% ii) 1000 KL : 0.047% iii) 1500 KL : 0.034% iv) 2000 KL : 0.026% v) 2500 KL : 0.022 % For intermediate capacities, interpolated percentages shall be adopted Staff Quarter shall be constructed for a minimum plinth area of 40 sqm with the following specification: RCC framed structure withconcrete grade not less than M20 design mix at the locations specified by the department at the time of execution with verandah, hall, bed room, kitchen and bath &W/C with floor area of 40.00sqmts excluding balconies and staircases
MS hollow door frame with cold rolled processed steel sheet 1.25mm thick bright CRCA conforming to IS 4351/76, Flush door shutters with solid bond wood bond board doors shall be provided. N.C.L. Windows centre fixed both sides openable shutter window 1.35 X 1.35mts outer frame section 48x50mm shutter frame section with a size of 48 X20 mm mullion section of size 48 X 50mm fixed beading section of 12 X 12 mm shall be provided.Flooring with polished Kadapa stone shall be provided. Walls shall be provided with snowcem paint in two coats over primary coat. Electrical and water supply arrangement shall be provided as directed by dept officer.Water Storage tank made with plastic/polymer material of reputed makewith necessary out let and inlet connection pipes shall provided. Septic tank for 5 users shall be provided.
Construction of 800 KL ELSR with a staging of 18m at SC Colony Zone-3
Construction of ELSRS With the following specification 800kl capacity with a staging of 18 m, without Seismic analysis.
All concrete components shall be designed with M30 Design Mix proportion. The rate are arrived with base rate of cement Rs 4220/- per MT and steel Rs 59000. 1.The foundations shall be designed for solid raft; 2.Rate inclusive of three coats of epoxy paint Food Grade of best quality to inner surface of the Reservoir including roof .3.The above rates are adopted for preparation of estimate for construction of ELSRs/OHSRs for finished work including 2 coats of weather proof emulsion painting for external surfaces, lettering, all required fixtures, Pipes,Pipe specials, valves of DI material, Valve chambers etc., for pipe connections including cost of pipes,specials and valves as per departmental designs and drawings. 4.The above rates adopted for a wind pressure upto "250 kg/sq m". For every 100 kg/sqm decrease in wind pressure, the rate shall be decreased by 5% 5.The Basic rate is adopted by considering the design for Seismic forces for Zone-I & II only of seismic zones 6.The basic rates shall be increased by 15% for Zone-III of seismic zones 7.The ELSR/OHSR shall be designed with minimum of two rows of columns for capacities above 500 KL & upto 1000KL 8.The ELSR/OHSR shall be designed with minimum of three rows of columns for capacities above 1000KL.
i) Pipe connections & Specials with D.I materials (a) All pipe connections for Inlet, Out let, Over Flow, Scour pipes shall be provided with D/F DI material. (b) The Valves for above pipe connections also shall be of DI material of PN 16 duty confirming to the specification of SoR item No.28 (c) All specials such as Bends, Tees, Reducers, Duck foot Bends, Bell mouths etc,. Shall be of DI material. II) The sizes of the verticals for ELSR/OHSR shall be: Above 1000KL three rows columns shall be provided a) For 500 KL to 750 Kl ELSRs Inlet Pipe - 300mm dia. Out let Pipe - 350mm dia. DI valves – 2 No’s Over Flow pipe - 350m dia. Scour Pipe - 200mm dia All Manholes Frames & covers
b) For 800 KL to 1500 Kl ELSRs Inlet Pipe - 400mm dia. Out let Pipe - 450mm dia. DI valves – 2 No’s Over Flow pipe - 450m dia. Scour Pipe - 200mm dia. c) For above 1500 KL to 2500 Kl ELSRs Inlet Pipe - 400mm dia. Out let Pipe - 500mm dia. DI valves – 2 No’s Over Flow pipe - 500m dia. Scour Pipe - 200mm dia. Note: Any deviation from the above sizes as per design, shall be paid or recovered. (iii) Manhole Frames & Covers All man hole Frames & Covers shall be made of CI/DI materials with min. size of 0.60mX 0.60m - For Roof & Valve Chambers. CI/D.I Double Swan neck ventilators (min. of 150mm dia.) shall be provided in top dome and slab with mosquito/fly proof nets - 4Nos. RCC Finial ventilator with fly/bird protection with GI mesh - 1 No. RCC precast ladders of 0.60 m width - 2 Nos. RCC dog legged stair case of 1.00 m flight width and 1.20 m landing width R.C.C hand railing of 1.0 m height – 1 No
The staircase shall be enclosed with brick masonary walls on three side and collapsible MS gate on front side up to 1st brace level, to prevent unauthorized entry Construction of R.C.C valve chambers as per Standard Drawings with RCC cover slab fixed with CI/DI manhole Frame & Cover with lock and Key arrangement. The Mix shall not be less than VRCC M 20 grade with 150mm thick side walls, 150mm thick top slab, 150mm thick base slab over base course of 100mm thick (1:4:8) prop. ) Balcony of 1.00 m width at floor slab level / middle ring beam level by using Stainless Steel pipe of grade 304 hand railing up to 1.20 m height, with top railing of 40mm dia. pipe & middle railing of 25mm dia. and verticals with 40mm dia. at an interval not more than of 1.00m c/c. Lightening Arrestor with all its accessories complete including earthing,with relevant IS Codes - 1 No.
Compound wall: Construction of compound wall including ornamentalM.S.Gate of size 3.0 X 2.40m is included in the basic rate of ELSRs. Length of compound wall hall be minimum of 150m. Min. height of the compound wall shall be 1.80m above plinth and thickness 230mm in brick masonry in CM(1:6).The compound wall shall be constructed including earth work excavation in all types of soils for plinth beam of 230mm X 300mm and 0.75X0.75X1.20m size for column footing portions. The footings shall be of0.75X0.75X0.25m in VRCC M20 grade and constructed over a C.C(1:4:8)prop bed of 100mm thick. The columns shall be of 230X230 mm in size with VRCC M20 grade at 3.00m c/c spacing, having depth of 1.20m below ground level and height of 2.00m above GL. The plinth beam of size of 230X300 mm shall be constructed in VRCC M20 grade at Gound level over a bed of CC(1:4:8)-100mmthick. 450X450mm size columns in M20 grade shall be constructed for gate pillars. All the materials shall be followed as per the standards grade shall be constructed for gate pillars. All the materials shall be followed as per the standards. Tie beam shall be provided above the brick work with 230X200mm size,fixed with MS angulars of 25mm X 25mm X 4mm in "Y" shape to hieght of 0.60m, with embedded length of 150mm in concrete. The barbed wire fencing with 3 ply of 18 gauge shall be streched in 4 rows (2x2). Plastering shall be done with 16mm thick in two coats i.e., base coat 12mm thick in CM(1:6)prop and 4mm thick 2nd coat CM(1:4) prop on both sides of brickwork.
Snowcem paint in two coats shall be provided for both sides of wall. The M.S ornamental gate as per the approved drawings shall be provided with minimum of 3.60mts width and 2.40mts height with enamel paint. Yard lighting shall be arranged on four corners of compound wall. If the length of the wall is increased/ decreased Note:-For every 1m increase/decrease in length of compound wall the increase/decrease in basic rates of ELSRs of the capacities from 500KL to 2500KL shall be as follows.: i) 500 KL : 0.086% ii) 1000 KL : 0.047% iii) 1500 KL : 0.034% iv) 2000 KL : 0.026% v) 2500 KL : 0.022 % For intermediate capacities, interpolated percentages shall be adopted Staff Quarter shall be constructed for a minimum plinth area of 40 sqm with the following specification: RCC framed structure withconcrete grade not less than M20 design mix at the locations specified by the department at the time of execution with verandah, hall, bed room, kitchen and bath &W/C with floor area of 40.00sqmts excluding balconies and staircases
MS hollow door frame with cold rolled processed steel sheet 1.25mm thick bright CRCA conforming to IS 4351/76, Flush door shutters with solid bond wood bond board doors shall be provided. N.C.L. Windows centre fixed both sides openable shutter window 1.35 X 1.35mts outer frame section 48x50mm shutter frame section with a size of 48 X20 mm mullion section of size 48 X 50mm fixed beading section of 12 X 12 mm shall be provided.Flooring with polished Kadapa stone shall be provided. Walls shall be provided with snowcem paint in two coats over primary coat. Electrical and water supply arrangement shall be provided as directed by dept officer.Water Storage tank made with plastic/polymer material of reputed makewith necessary out let and inlet connection pipes shall provided. Septic tank for 5 users shall be provided.
Providing 500 kVA Transformer at Intakewell cum pumphouse including transformer yard & Providing 500KVA Generator at WTP including shed
Supply and erection of 7.50m long double pole structure fabricated with 150x75mm RS Joists,100x50mm MS channels, iron cross armstor fuse set and Lighting arrestrors etc.,including one coat of red oxide primer and two coats of bright Supply
Supply and fixing of 11 KV ,400 A 3 phase central post rotating double break type AB switch(isolator) as per IS 9921) without earth blade, gang operated, Horizontal type, operating mechanism with GI spring loaded reverse loop type fixed contact, solid HD electrolytic copper tubular moving contact with silver/Nickel plated at end points,9 Nos post insulators of 12 KV (IS 2594 and IS 5350) ,Hot Dip galvanizing hardware, GI pipe, Nuts and bolts etc., complete., ELEC 6.5.14/MAT 04113
Supply and fixing of 100 A 11 KV Horn Gap fuse set as per IS 9385 on existing DP structure with 6 no of 24 KV /22 KV post Insulators (IS 5350, Hot dipped Hardware, fuse wire of required size etc., complete ELEC 6.5.12/MAT 04111
Supply and fixing of distribution type lightning arrester 11 KV 5 kA as per IS 3070 with mounting base on the existing DP structure ELEC 6.5.11/MAT 04110
Supply and erection of 11KV Strain disc. Insulators with GI pins and top clamps Quotation Rate
Supply and fixing of 11 KV pin Insulator (IS 731/1971) with minimum creepage distance of 300 mm on existing cross arm including all accessories like Hot dip GI spindle and nuts etc., ELEC 6.5.8/MAT 04105
Providing jumper connections with I/O' SWG HDBC wire between the 11 KV equipment on the outdoor structures Quotation Rate
Supply and erection of GI stay set of dia 16mm,1.8 mtr long stay rod and anchor plate 380mmx380mmx6.4mm. including stay clamps, turn buckle and GI stay wire tight end through strain insulator including excavation of pit and cc work etc., complete ELEC 6.5.3/MAT 04097
Providing efficient earthing arrangement forthe DP structure lighting arresters and the HV equipment. Transformer body and neutral etc., with 25 x 3 mm copper flats and connecting them to the Earth Electrodes fabricated and buried accroding to standard specifications and as per the details given below:
A) Earth Electrodes
B) 25 x 3 mm HDB copper flat
C) Epoxy insulators
D) No.'8' SWG Copper wire.
Supply and erection of 500 kva KVA, 11KV/433 V, DY-11 Vectro group, out door type, plinth mounting type, Hint /make transformer with bushings on HT side and cable entry box on L V side to received 1.1 KV grade cable with all standard accessories transformer oil. tansformer having copper wound natural cooled with all standard accessories - ELEC-6.3.5
Supply and laying of 3.5 core x 400 sq.mm, 1.10 KV grade PVC insulated and armoured cable with alminium conductors Rs 1905+13.615% ELEC-4.1.46
Supply Installation Testing and commissioning of free-standing floor mounted dust and vermin proof compartmentalized cubical panel made out of CRCA sheet, required hardware, cleaning with 7 tank process duly painted by two coats of zinc/red oxide primer followed by Powder coated / epoxy / PU painted with phosphatisation in grey or required shade after rinsing. The panel having PU/ Neoprene rubber gasket of not less than 3mm thickness, separate detachable, gland plate M.S. base channel, hinged door with locking arrangement for equipment/switchgear. The thickness of sheet shall not be less than 1.6mm up to 600mm length/ width of any compartment and be 2.0mm above 600mm. The load bearing structure shall be of 2.0mm thick sheet supported by base M.S. channel if required. Side walls and cable alley compartments having bolted type doors with detachable extension type structure (only outer area on all sides shall be measured and panel to be fabricated from CPRI approved fabricator) MAT 03976
Supply and fixing of Electrolytic grade copper bus bar bus bar by means of SMC / DMC type insulator, high tensile nuts and bolts spring washers in existing panel including bending , cutting in required shape and size and colour coding with heat shrinkable PVC sleeves MAT 03978
Incoming a) . 630A TPN SFU for main switch
b) . 630 A pole change over switch
c) one set Metering Panel Comprisinga). 1( 0-500V) 96mm.SQ.flush type Digital Voltmeter.
e). ( 0-250A) 96mm SQ.flush type digital Ammeter
g).3RYB Phase indication lamps with leds
h).Supply and Fixing of Current Transformer, with all necessary support in existing panel including connection etc. as required from 200 / 5 to 400/5 Ratio, 10 VA, class 1 accuracy: Make: Kappa/L&T/Seimens/C&S/Schneider MAT 03986
Outgoing 630A TPN SDFU forCW pump house motors Makes:LauritzKnudsen(FormerlyL&T)/Schneider/ C&S/ ABB / SIEMENS MAT 02885
630A TPN SDFU for compressor/mechanical equipments Makes:LauritzKnudsen(FormerlyL&T)/Schneider/ C&S/ ABB / SIEMENS MAT 02885
630A TPN SDFU for low lift sump Raw water motors Makes:LauritzKnudsen(FormerlyL&T)/Schneider/ C&S/ ABB / SIEMENS MAT 02885
630A TPN SDFU for Space Makes:LauritzKnudsen(FormerlyL&T)/Schneider/ C&S/ ABB / SIEMENS MAT 02885
630A TPN SDFU for lighting section Makes:LauritzKnudsen(FormerlyL&T)/Schneider/ C&S/ ABB / SIEMENS MAT 02885
630A 4pole change over switch for lighting section Makes:Socomec/LauritzKnudsen(FormerlyL&T)/HPL / Havells/ C&SMAT MAT 02898
.KWH digital meter fro lighting section
Supply of 32 Amp………ISI marked TPN Switch Disconnector Fuse Unit, Cubical type without fuses as per IS: 13947/IEC 60947-3 Makes: As per list of recommended brands as category I.MAT-02879
Supply of 6A to 35 A……ISI marked HRC Fuse Links as per IS 13703-Part 2/IEC 60269- Part 2 Makes: As per list of recommended brands as category I MAT-02938
Standard duty Single phase 250 V / Three phase 440 V, 50 Hz capacitor (Bank) MAT-03998
500KV.LT/Transformer Errection.testing Commensing and Supply of drawing layout plans of installed transformer in tracing cloth and duly get approved from electrical inspector APEPDCL and leaflets for various equipments and opearation manuals etc., complete.
Supply and Laying of 3C X 95 Sq mm XLPE insulated IS:7098/II/85 H.T. cable for working voltage 11 KV Earthed with Stranded Compacted Circular Aluminium Conductor Screened with Extruded Semi-conducting compound, XLPE Insulated Screened with extruded semi-conducting compound in combination with Copper Tape, cores laid up, inner sheath of Thermoplastic tape, galvanized flat steel strip armoured and overall Extruded PVC Type ST- 2 Outer Sheathed cable etc., complete. Make: Torrent / Universal / Unicab / Havells / KEI/Polycab/Gloster/RR Kabel/RPG MAT 03460
Transformer yard Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH Note : Classifications of Earth Work Specification are as per 302.2.1(a) of MORD and 301.2.1 of MORT&H--ordinary soil--manual means upto 3m depth for foundations of buildings in restricted places By manual means for column footings
Providing river sand filling brought from approved quarry including cost and conveyance of all material and all labour charges such as filling in layers watering ramming etc complete as per ss and as directed by the departmental officer incharge of work for column footings
Providing PCC 1:4:8 using 40 mm graded SS 5 HBG m/c metal and OPC coarse and fine aggregate confirming to IS 383 including cost and conveyance of all materials and labour charges, machine mixing , vibration,laying in position, curing etc., complete as per ss and as directed by the departmental officer incharge of work for column footings
Supply and placing of the design mix concrete corresponding to IS -456 using WEIGH BATCHER/MIXER using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including seigniorage charges ,sales and other taxes on all materials including all operational ,incidental and labour charges such as weigh batching ,machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work (APSS NO 402) with minimum cement content as per IS Code from standard suppliers approved by the deparment including pumping , centering,shuttering,laying concrete, vibrating,curing etc M25 design mix concrete complete as per ss and as directed by the departmental officer incharge of work as follows
column footings
column
Plinth Beam
Painting Walls with Snowcem or other equal and approved Water Proof Cement Paint over Priming Coat, 2 Coats (All Colours)BLD-CSTN-10-3 the rate including all materials and other incidentaal charges complete as per ss and as directed by the departmental officer incharge of work
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, complete for finished item of work in all floors.( APSS No.126) complete as per ss and as directed by the departmental officer incharge of work for footings,columns,Plinth Beams
Supplying and fixing galvanised steel barbed wire (IS : 278-1962 Type I) weighing 9.38 Kg per 100 metres (min.), Straining and fixing to any type of standard, rails, straining bolts, including securing with and provision of galvanised mild steel wire, stapples or steel pins, etc., as directed (Posts and struts of wood, concrete, steel, etc.) and straining bolts shall be paid for separately)
Manufacture,supply,delivery of MS grill gates,window ornamental safety grill ,made with MS flats,MS angles,MS squares etc including welding, finishing, applying red oxide paint as primary coat etc complete as per ss and as directed by the departmental officer incharge of work
Providind Synthic enamil paint two coats over the primery coat excluding cost of primer including cost and conveyance of all matrial and all labour charges etc complete as per ss and as directed by the departmental officer incharge of work for 3 mts wide gate
Filling the transformer yard with 40mm HBG metal m/c The rate including cost and conveyance of all material, labour charges for filling, watering, ramming, etc., complete as per SS and as directed by the departmental officer in charge of the work
Providing 250KVA Generator at Intakewell including shed
Supply and erection of 7.50m long double pole structure fabricated with 150x75mm RS Joists,100x50mm MS channels, iron cross armstor fuse set and Lighting arrestrors etc.,including one coat of red oxide primer and two coats of bright Supply
Supply and fixing of 11 KV ,400 A 3 phase central post rotating double break type AB switch(isolator) as per IS 9921) without earth blade, gang operated, Horizontal type, operating mechanism with GI spring loaded reverse loop type fixed contact, solid HD electrolytic copper tubular moving contact with silver/Nickel plated at end points,9 Nos post insulators of 12 KV (IS 2594 and IS 5350) ,Hot Dip galvanizing hardware, GI pipe, Nuts and bolts etc., complete., ELEC 6.5.14/MAT 04113
Supply and fixing of 100 A 11 KV Horn Gap fuse set as per IS 9385 on existing DP structure with 6 no of 24 KV /22 KV post Insulators (IS 5350, Hot dipped Hardware, fuse wire of required size etc., complete ELEC 6.5.12/MAT 04111
Supply and fixing of distribution type lightning arrester 11 KV 5 kA as per IS 3070 with mounting base on the existing DP structure ELEC 6.5.11/MAT 04110
Supply and erection of 11KV Strain disc. Insulators with GI pins and top clamps
Supply and fixing of 11 KV pin Insulator (IS 731/1971) with minimum creepage distance of 300 mm on existing cross arm including all accessories like Hot dip GI spindle and nuts etc., ELEC 6.5.8/MAT 04105
Providing jumper connections with I/O' SWG HDBC wire between the 11 KV equipment on the outdoor structures
Supply and erection of GI stay set of dia 16mm,1.8 mtr long stay rod and anchor plate 380mmx380mmx6.4mm. including stay clamps, turn buckle and GI stay wire tight end through strain insulator including excavation of pit and cc work etc., complete ELEC 6.5.3/MAT 04097
Providing efficient earthing arrangement forthe DP structure lighting arresters and the HV equipment. Transformer body and neutral etc., with 25 x 3 mm copper flats and connecting them to the Earth Electrodes fabricated and buried accroding to standard specifications and as per the details given below:
A) Earth Electrodes
B) 20mm x 3mm Copper Flat(0.529Kgs/1Mtr) MAT 04146
C) Epoxy insulators
D) No.'8' SWG Copper wire. MAT 04141
Supply and Transportation of ISI marked copper wound Transformers 11/0.433 KV, Three Phase, 50 Hz, DYN 11, ONAN type , Standard accessories, winding temperature rise of 45°C/40°C first fill oil, having permissible total loss values not exceeding 7.5%of the maximum total loss values for 11 KV as per Energy Efficiency Level - 2 at basic Insulation level conforming to ISS 2026 (Part- I to Part - II), latest ammended and IS 1180 Part-I : 2014 described as above with Cable box on HV side and Bus duct on LV Side , ON load Tap changer(OLTC)+10% to -10%, with RTCC etc., with initial filling of oil as per IS 335-1993 complete and as per the following continuous rating. Makes : As per list of recommended brands as category I. MAT-04044c 250KVA
Supply and laying of 400Sq mm X 3.5 core XLPE insulated, 1100V grade armoured aluminum cable as per specification confirming to IS:7098 (Part- I)./1554-I Makes: Makes: Torent / Universal / Unicab / Havells / Finecab/ KEI / Gloster/ Polycab /RR Kabel/ Fortune Arrt ELEC-4.1.1q MAT-03431
Supply Installation Testing and commissioning of free-standing floor mounted dust and vermin proof compartmentalized cubical panel made out of CRCA sheet, required hardware, cleaning with 7 tank process duly painted by two coats of zinc/red oxide primer followed by Powder coated / epoxy / PU painted with phosphatisation in grey or required shade after rinsing. The panel having PU/ Neoprene rubber gasket of not less than 3mm thickness, separate detachable, gland plate M.S. base channel, hinged door with locking arrangement for equipment/switchgear. The thickness of sheet shall not be less than 1.6mm up to 600mm length/ width of any compartment and be 2.0mm above 600mm. The load bearing structure shall be of 2.0mm thick sheet supported by base M.S. channel if required. Side walls and cable alley compartments having bolted type doors with detachable extension type structure (only outer area on all sides shall be measured and panel to be fabricated from CPRI approved fabricator) MAT 03976
Supply and fixing of Electrolytic grade copper bus bar bus bar by means of SMC / DMC type insulator, high tensile nuts and bolts spring washers in existing panel including bending , cutting in required shape and size and colour coding with heat shrinkable PVC sleeves MAT 03978
Incoming a) 630A TPN SDFU for main switch Makes:LauritzKnudsen(FormerlyL&T)/Schneider/ C&S/ ABB / SIEMENS MAT 02885
b) 630A 4pole change over switch Makes:Socomec/LauritzKnudsen(FormerlyL&T)/HPL / Havells/ C&SMAT MAT 02898
c) Supply and fixing of (0-500) V range Voltmeter on existing panel, making connection by PVC insulated copper conductor with PVC sleeves /channel etc. as required Digital type Make: Conzerve/Elmeasure/Meco/HPL/L&T/socomec MAT 03980
e). Supply and fixing of CT operated direct reading type Ammeter on existing panel, making connection by PVC insulated copper conductor with PVC sleeves / channel etc. as required. Digital type Below 500 A Make: Conzerve/Elmeasure/Meco/HPL/L&T/Schneider/AE/Socomec MAT 03983
g).3RYB Phase indication lamps with leds
h).Supply and Fixing of Current Transformer, with all necessary support in existing panel including connection etc. as required from 200 / 5 to 400/5 Ratio, 10 VA, class 1 accuracy: Make: Kappa/L&T/Seimens/C&S/Schneider MAT 03986
Outgoing 630A TPN SDFU forCW pump house motors Makes:LauritzKnudsen(FormerlyL&T)/Schneider/ C&S/ ABB / SIEMENS MAT 02885
630A TPN SDFU for compressor/mechanical equipments Makes:LauritzKnudsen(FormerlyL&T)/Schneider/ C&S/ ABB / SIEMENS MAT 02885
630A TPN SDFU for low lift sump Raw water motors Makes:LauritzKnudsen(FormerlyL&T)/Schneider/ C&S/ ABB / SIEMENS MAT 02885
630A TPN SDFU for Space Makes:LauritzKnudsen(FormerlyL&T)/Schneider/ C&S/ ABB / SIEMENS MAT 02885
630A TPN SDFU for lighting section Makes:LauritzKnudsen(FormerlyL&T)/Schneider/ C&S/ ABB / SIEMENS MAT 02885
630A 4pole change over switch for lighting section Makes:Socomec/LauritzKnudsen(FormerlyL&T)/HPL / Havells/ C&SMAT MAT 02898
.KWH digital meter fro lighting section
Supply of 32 Amp………ISI marked TPN Switch Disconnector Fuse Unit, Cubical type without fuses as per IS: 13947/IEC 60947-3 Makes: As per list of recommended brands as category I.MAT-02879
Supply of 6A to 35 A……ISI marked HRC Fuse Links as per IS 13703-Part 2/IEC 60269- Part 2 Makes: As per list of recommended brands as category I MAT-02938
Standard duty Single phase 250 V / Three phase 440 V, 50 Hz capacitor (Bank) MAT-03998
1000KV LT/Transformer Errection.testing Commensing and Supply of drawing layout plans of installed transformer in tracing cloth and duly get approved from electrical inspector APEPDCL and leaflets for various equipments and opearation manuals etc., complete.
Supply and Laying of 3C X50 Sq mm XLPE insulated IS:7098/II/85 H.T. cable for working voltage 11 KV Earthed with Stranded Compacted Circular Aluminium Conductor Screened with Extruded Semi-conducting compound, XLPE Insulated Screened with extruded semi-conducting compound in combination with Copper Tape, cores laid up, inner sheath of Thermoplastic tape, galvanized flat steel strip armoured and overall Extruded PVC Type ST- 2 Outer Sheathed cable etc., complete. Make: Torrent / Universal / Unicab / Havells / KEI/Polycab/Gloster/RR Kabel/RPG MAT 03457b
Transformer Shed Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH etc., complete as per SS and as directed by the Departmental officer in charge of the work for Footings
Filling Sand in foundation trenches as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH . The rate including cost and conveyance of all material, labour charges for filling, watering, ramming, etc., complete as per SS and as directed by the departmental officer in charge of the work complete as per ss and as directed by the departmental officer incharge of work for footings
Plain Cement concrete (1:4:8) using 40 mm metal with concrete mixer. All work upto plinth level including cost of all materials and labour charges etc., complete as per SS and as directed by the departmental officer in charge of the work complete as per ss and as directed by the departmental officer incharge of work for footings
RCC M- 25 Design mix (Cement 380 kgs fine aggregate: coarse aggregate) corresponding to Table 9 of IS 456 using 20mm size graded machine crushed hard granite metal (coarse aggregate) from approved quarry including cost and conveyance of all materials like cement, fine aggregate (sand) coarse aggregate, water etc., to site and including Seigniorage charges, sales & other taxes on all materials including all operational, incidental and labour charges such as machine mixing, laying concrete, curing etc.,complete but excluding cost of steel and its fabrication charges for finished item of work, but excluding centering, shuttering. as per SS and as directed by the Departmental officer in charge of the work
Footings
Plinth Beam
Columns
Roof Beams
Roof slab 125mm thick
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, complete for finished item of work in all floors.( APSS No.126) complete as per ss and as directed by the departmental officer incharge of work for footings,columns,Plinth Beams
Brick masonary in CM (1:6) using 2nd class bricks of size 23 x 11 x 7cms. Cost including all materials,labour charges aand other incidental charges ,conveyance of all materials at site, labour charges for curing etc., complete as per S.S and as directed by the departmental officer incharge of work
Plastering with CM (1:3) 12mm thick including cost and conveyance of all materials at site, seignorage charges and labour charges for mixing of mortar, plastering and curing etc., complete as per S.S and as direceted by the departmental officer incharge of work for ceiling
Plastering with CM (1:4) 12mm thick including cost and conveyance of all materials at site, seignorage charges and labour charges for mixing of mortar, plastering and curing etc., complete as per S.S and as direceted by the departmental officer incharge of work for walls
Plastering with CM (1:3) 20mm thick including cost and conveyance of all materials at site, seignorage charges and labour charges for mixing of mortar, plastering and curing etc., complete as per S.S and as direceted by the departmental officer incharge of work for flooring
Manufacture,supply,delivery of MS grill gates,window ornamental safety grill ,made with MS flats,MS angles,MS squares etc including welding, finishing, applying red oxide paint as primary coat etc complete as per ss and as directed by the departmental officer incharge of work
Providing Painting with Synthetic Enamel paints - Two Coats - For new Iron Work over a primary coat of Red oxide over all three coats. The rate cinluding cost and conveyance of all material, labour charges, etc., complete as per SS and as directed by the departmental officer in charge of the work.
Painting to new walls with 2 coats of water proof cement paint of apporved brand and shade over a base coat of approved cement primer grade I making making 3 coats in all to give an even shade after thourughly brushing the surface to remove all dirt and remains of loose powdered materials, including cost and conveyance of all materials to work site and all operational, incidental, labour charges etc. complete for finished item of work as per SS 912 and as directed by the departmental officer in charge of the work
Construction 16 m dia clear water sump at proposed WTP Head Works(681 KL)
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH for foundations upto 3.00m depth Note : Classifications of Earth Work Specification are as per 302.2.1(a) of MORD and 301.2.1 of MORT&H--ordinary soil--
upto 3m depth
3-6.00m depth
Filling in for 681KL Clear Water Sump Bedding as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH for foundations RBR-FNDN-2(1) complete as per ss and as direceted by the departmentaal officer incharge of work
Plain cement concrete (1:4:8) using 40mm m/c SS5 HBG including machine mixing, laying, compacting, finishing, curing etc for foundations complete as per ss and as direceted by the departmentaal officer incharge of work
Supply and placing of the design mix concrete corresponding to IS -456 using WEIGH BATCHER/MIXER using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including seigniorage charges ,sales and other taxes on all materials including all operational ,incidental and labour charges such as weigh batching ,machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work (APSS NO 402) with minimum cement content as per IS Code from standard suppliers approved by the deparment including pumping , centering,shuttering,laying concrete ,vibrating,curing etc M30 design mix concrete with concrete mixer complete as per ss and as direceted by the departmentaal officer incharge of work
Raft slab
For side walls circular 0.30m thick initial height 3.00 m below GL
For side walls circular 0.30m thick above GL
Columns0.30 x 0.30 ,
Roof beams
Roof slab 0.15m thick 0.786*(13.10^2-6.00^2)
Roof dome slab 0.15m thick
Providing impervious coat to exposed RCC roof slab surface with CM(1:3), 20mm thick with 1kg of water proof compound per bag of cement laid over roof when it is green including cost of all materials, seigniorage charges, excluding conveyance charges of materials and including all operational, incidental and labour charges for mixing mortar, laying, rendering smooth and thread lining, curing, rounding off junctions of wall and slab etc,, complete for finished item of work
Colour washing two coats Using snowcem including cost and conveyance of all labour charges etc.,complete as per (in and out side) complete as per ss and as direceted by the departmentaal officer incharge of work
Supply and delivery and fixing in position M S gril of any design including all fabrication and all fixing charges etc compalete as per ss and as directed by the dept authorities complete as per ss and as direceted by the departmentaal officer incharge of work
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, rate including all materials etc., complete for finished item of work in all floors.( APSS No.126)
Providing Site filling to Head Water Works
Supply and delivery of Gravel/Quarry spall from approved quarries incl.cost, and conveyance to work spot including labour charges for stacking at site to departmentalgauge. The rate including spreading, sectioning of collected Crusher dust including all labour charges for filling, sectioning, watering and rolling with P.R etc., complete as per S.S.and as direceted by the departmental officer incharge of work
Construction of Staff Quarters at Intake well, Head Works site at Yeleswaram
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH Note : Classifications of Earth Work Specification are as per 302.2.1(a) of MORD and 301.2.1 of MORT&H--ordinary soil--manual means upto 3m depth for foundations of buildings in restricted places
Providing river sand filling including cost and conveyance of all material and all labour charges such as filling in layers watering ramming etc complete as per S.S.and as direceted by the departmental officer incharge of work
Providing PCC 1:4:8 using 40 mm graded SS 5 HBG m/c metal and OPC coarse and fine aggregate confirming to IS 383 including cost and conveyance of all materials and labour charges, machine mixing , vibration,laying in position, curing etc.,complete as per S.S.and as direceted by the departmental officer incharge of work
Supply and placing of the design mix concrete corresponding to IS -456 using WEIGH BATCHER/MIXER using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including seigniorage charges ,sales and other taxes on all materials including all operational ,incidental and labour charges such as weigh batching ,machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work (APSS NO 402) with minimum cement content as per IS Code from standard suppliers approved by the deparment including pumping , centering,shuttering,laying concrete ,vibrating,curing etc M25 design mix ,complete as per S.S.and as direceted by the departmental officer incharge of work
column footings
Columns
Plinth Beam
Lintle beams Windows
Roof Beams
Roof slab 0.125m thick with 0.30m extension all sides
Sunshades 0.60m wide, 0.10m at fixed end and 0.05m at free end Windows
Loft slab 0.075m thick kitchen
Brick work in CM 1:6 mix using 2nd class bricks brought from approved kilns including cost and conveyance of all materials and all labour charges ,curing for 21 days etc ,complete as per S.S.and as direceted by the departmental officer incharge of work as follows
Ground floor
1st floor
Cement plastering using opc in cm(1:5) prop 12 mm thick including cost of material, labour ,curing etc. complete as per S.S.and as direceted by the departmental officer incharge of work as follows out side & inside as follows
Ground floor
1st floor
Cement plastering using opc in cm(1:3) prop 12 mm thick including cost of material, labour ,curing etc. complete as per SS for walls out side & inside above 3.5 m Height
For ceiling slab area
Colour washing two coats using snowcem over the primery coat conveyance of all labour charges etc., complete as per (in and out side)
Supply delivary and fixing RCC Jollys includnig cost and conveyance of all material and all labour charges for fixing etc complete as ss and as direceted by the departmentaal officer incharge of work
Supply and fixing Aluminium Anodised Doors - Single Shutter as per approved drawing with aluminium anodised sections of Jindal sections and outer frame top horizontals & both verticals of 2408 of size 101.6 x 44.75 x 3.18 mm Shutter frame top, bottom and verticals of 4504 of size 44.45 mm x 47.62 mm x 3.18 and Middle lock rail of 4621 of size 49.91 x 44.45 x 3 mm with tinted-bronze/green glass 5 mm thick(middle to top),MDF Board-exterior both sides laminaed 12mm thick(middle to bottom) fixed including supply and fixing aluminium handles of 150 mm for each shutter and all labour charges for fixing the fixtures with required no.of screws, bolts and nuts and including labour charges for fixing the frame in position, fixing shutter to frame etc. completed for finished item of work complete as ss and as direceted by the departmentaal officer incharge of work
Door -D - 1.20X2.10 m
Doors D1 - 1.00X2.10m
Supply and fixing Aluminium Anodised Two/ Three Track Sliding Windows as per approved drawing with aluminium anodised sections of Series C Jindal sections and outer frame top horizontals & both verticals of 8774 of size 62 x 29.5 mm and bottom horizontal - two track frame of 8773 of size 62 x 29.5 mm, Shutter frame top, bottom and verticals of 8304 of size 50 mm x 20 mm and Weather interlocking frame of 8306 of size 50 x 20 with plain clear float glass 5 mm thick fixed including supply and fixing aluminium handles of 100 mm for each shutter, nylon rollers assembly and all labour charges for fixing the fixtures with required no.of screws, bolts and nuts and including labour charges for fixing the frame in position, fixing shutter to frame etc. completed for finished item of work for windows 1.20x1.20
Providing and fixing factory made polyvinyl chloride (PVC) Door Frame of the size 50 x 47mm with a wall thickness of 5mm, made out of extruded 5mm rigid PVC foam sheet, mitre cut at two corners and joined with 2nos. of 150mm long brackets of 15x15mm M.S. square tube. The two vertical door profiles are to be reinforced with 19x19mm M.S. Square tube of 19 gauge. The door frame shall be fixed to the wall using 65/100mm long M.S. Screws through the frame by using PVC fasteners. A minimum of 4nos. of screws to be provided for each vertical member & minimum 2nos. for horizontal member etc. complete as per manufacturers specification and direction of Engineer-in-Charge for finished item of work for Toilet door D2
Providing and fixing 30mm thick Solid panel PVC door shutter consisting of frame made out of M.S. tubes of 19 gauge thickness and size of 19mm x 19mm for stiles, & 15mm x 15mm for top & bottom rails. M.S. frame shall have a coat of steel primers of approved make and manufacture. M.S. frame shall be covered with 5mm thick heat moulded PVC ‘C’ channel of size 30 x 50mm forming stiles, and 5mm thick, 75mm wide PVC sheets for top rail, lock rail & bottom rail on either side, and 10mm (5mm x 2) thick, 20mm wide cross PVC sheet as gap insert for top rail & bottom rail. Panelling of 5mm thick PVC sheet to be fitted in the M.S. frame welded / sealed to the stiles & rails with 30mm wide x 5mm thick PVC sheet beading on either side, and joined together with solvent cement adhesive etc. An additional 5mm thick PVC strip of 20mm width is to be stuck on the interior side of the ‘C’ Channel using PVC solvent adhesive. Complete as per direction of Engineer-in-charge, manufacturer’s specification & drawing for finished item of work for Toilet Door D2
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying including all materials etc., complete for finished item of work in all floors.
Cement plastering using opc in cm(1:3) prop 20 mm thick including cost of material, labour ,curing etc. complete as per SS for floorring complete as per ss and as direceted by the departmental officer incharge of work
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying including all materials etc., complete for finished item of work in all floors.
Providing two coats of Synthic enamil paint over new Iron works including cost and conveyance of all material and all labour charges etc complete as per ss as direceted by the departmental officer incharge of work
Supply, delivery and fixing of 110mm dia single socket PVC pipes 4 kg/sqcm prince/Sudhakar or any ISI brand for rain water pipes with clamps complete as per ss as direceted by the departmental officer incharge of work
Supply and fixing of 25 mm dia 2.00 mm thick PVC pipe concealed in roof slab with all required accessories including masonary work all labour chages complete as per IE Rules as direceted by the departmental officer incharge of work
Supply and fixing of 20 mm dia 1.50 mm thick PVC pipe concealed in walls with all required accessories including masonary work for light , fan and plug point with metal deep box including all labour chages complete as per IE Rules as direceted by the departmental officer incharge of work
Wiring with 2 runs 14/0.3 mm. (1.0. sq.mm) Fire retardant PVC insulated Flexible copper cable in existing pipe with 6A siwtch, ceiling rose and 3 mm thick hyla sheet covering to switch control box including all labour charges etc,., complet for light, bell , fan and exhaust fan points in non - residential building complete as per IE Rules as direceted by the departmental officer incharge of work
Wiring with 2 runs 14/0.3 mm. (1.0. sq.mm) Fire retardant PVC insulated Flexible copper cable in existing pipe with 6A modular siwtch control and 3/2 pin sockets fixing on board including all labour charges complete as per IE Rules as direceted by the departmental officer incharge of work
supply and run of 2 of 36/0.3 mm. (1.5. sq.mm) Fire retardant PVC insulated Flexible copper cable in existing pipe for mains including all labour charges complete as per IE Rules as direceted by the departmental officer incharge of work
supply and run of 1 of 14/0.3 mm. (1.0. sq.mm) Fire retardant PVC insulated Flexible copper cable in existing pipe for earth continuity including all labour charges etc. complete as per IE Rules as direceted by the departmental officer incharge of work
supply and run of 2 of 6 sq.mm (7/18) WPSC alluminium cable along with No.10 SWG G.I barer wire through PVC cleats with all accessories including all labour charges etc., complete as per IE Rules as direceted by the departmental officer incharge of work
Providing independent earthing by excavating a trench to a depth of 2.10m in all soils, as per size specied in data ,using 40 mm dia B class GI pipe 2.50m long with necessary accessories with hume pipe ring duly providing staggered holes including filling with equal proportion of salt and charcoal in layers and all labour charges etc complete as per IE Rules as direceted by the departmental officer incharge of work
S&F of SPN distrubution board with IP 42 protection (metal door) suitable for 3 phase ELCB-RCCB-FP isolator as incomer and 10 KA SP MCBS as out going including internal connection and labour charges for surface-flush mounting etc -- 63 A FP isolator-1 no for incomer,6-32A SP MCBS -18 Nos for out going complete as per IE Rules as direceted by the departmental officer incharge of work
Supply and fixing of 48" (1200mm) Sweep Ceiling Fan without Regulator.of makes Crompton High Speed / Bajaj Ultima / Havells Velocity / Usha Astra / Orient Summer Pride complete as per IE Rules as direceted by the departmental officer incharge of work
Supply of stepped type Electronic Regulator of makes GM G Home / Gold Medal Olive / Million Zoom / Anchor Penta Cherry / Great white Omega complete as per IE Rules as direceted by the departmental officer incharge of work
Supply of 20W tube light luminaire powder coated CRCA sheet steel housing with Electronic Ballast Chokes and all standard accessoriesof makes Wipro / G.E. / Phillips / Crompton / Bajaj. complete as per IE Rules as direceted by the departmental officer incharge of work
Providing & Placing on Terrace (at all floor levels) polyethylene water storage tank with Double layer approved brand & manufacture with cover and suitable locking arrangement & making necessary holes for inlet & outlets and over flow pipes but without fittings & base support for tanks complete as per ss and as directed by the departmental officer incharge of work
Supplying & Fixing Orissa Pan white glazed W.C 1st quality ISI marked conforming to IS:2556-Part-3-1981 with "P" or "S" trap Hindware/ Parryware/ Neycer - ISI Mark: 630 mm x 450 mm size complete as per ss and as directed by the departmental officer incharge of work
Supplying & Fixing low down porcelain flushing tank 10 Lit Capacity Hindustan Sanitary ware/ parry/ Neycer with internal components complete as per ss and as directed by the departmental officer incharge of work
Supplying & Fixing Indian make Flat Back Wash Hand Basin (HSW/Parryware/ Neycer) 1st quality conforming to IS:2556-Part-4:1972 with waste fittings like rubber plug, chain, 32 mm nominal size C.P. Fitting with parallel pipe thread conforming to IS:2963-1979 and fitted with 15 mm nominal bore Chromium Plated Pillar Tap of 1st quality Indian make 400 grams Seiko/ Senior/ Nice/ Esso or equivalent complete with standard CI brackets including wooden block: 550 x 400 mm - Double C.P. Pillar cock complete as per ss and as directed by the departmental officer incharge of work
Supply of 110 mm dia 3 m single Socket PVC/SWR pipe - 6 Kg/sq.cm - Prince/Sudhakar/Kisan/Supreme or any ISI Brand.complete as per ss and as directed by the departmental officer incharge of work
Supply of 110 mm dia - Plain Bend 87.5 Degree - UPVC/SWR Pipe fittings (Prince/Sudhakar/Kisan/Supreme or any ISI Brand) complete as per ss and as directed by the departmental officer incharge of work
Supply of 110 mm dia - Coupler - UPVC/SWR Pipe fittings (Prince/Sudhakar/Kisan/Supreme or any ISI Brand complete as per ss and as directed by the departmental officer incharge of work
Labour charges for laying, fixing and commissioning the PVC pipes including couplers/ bends/ tees etc any diameter including fixing necessary fittings like bends, plugs, couplers, junctions, tees, etc with solvent jointing as per standard practice complete as per ss and as directed by the departmental officer incharge of work
Constructing 457.2 mm x 457.2 mm (1'6"x1'6") brick in CM 1:6 prop. Masonry. Inspection chamber up to 914.4 mm (3'0") and fitted with light weight 457.2 mm x 457.2 mm (1'6"x1'6") C.I frame and cover of 20 Kg complete as per ss and as directed by the departmental officer incharge of work
Supply & Fixing of GI pipe Medium Grade properties & weight as per IS 1239 ISI mark with GI fittings including the cost of pipe & its fittings & labour charges complete as per ss and as directed by the departmental officer incharge of work as follows
25 mm dia nominal bore -from tank to jn for of individual lines
20 mm dia nominal bore -from jn for of individual lines to toilets & Kitchen
15 mm dia nominal bore -for internal
Supply & Fixing of of GI & GM fittings including the cost of pipe & its fittings & labour charges complete as per ss and as directed by the departmental officer incharge of work as follows
GM Ball valve with SS Ball and SS Spindle as per IS - Class - I, Indian make heavy type - 25 mm NB Size
GM Ball valve with SS Ball and SS Spindle as per IS - Class - I, Indian make heavy type - 20 mm NB Size
GM Ball valve with SS Ball and SS Spindle as per IS - Class - I, Indian make heavy type - 15 mm NB Size
S&F 12.7 mm N.P bib tap Indian make heavy dutys Seiko/ Senior/ Nice or equivalent
Supply & Fixing of GI union rate including all materials and other incidental charges complete as per ss and as directed by the departmental officer incharge of work as follows
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH Note : Classifications of Earth Work Specification are as per 302.2.1(a) of MORD and 301.2.1 of MORT&H--ordinary soil--manual means upto 3m depth for foundations For Septic tank
Filling with sand in Septic Sand Bedding as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH rate including with ramming, and cost of Sand and other incidental charges
Providing PCC 1:4:8 using 40 mm graded SS 5 HBG m/c metal and OPC coarse and fine aggregate confirming to IS 383 including cost and conveyance of all materials and labour charges, machine mixing , vibration,laying in position, curing etc., complete as per ss and as direceted by the departmental officer incharge of work
Brick work in CM 1:6 mix using 2nd class bricks brought from approved kilns including cost and conveyance of all materials and all labour charges ,curing for 21 days etc complete as per ss and as direceted by the departmental officer incharge of work
Cement plastering using opc in cm(1:5) prop 12 mm thick including cost of material, labour ,curing etc. complete as per ss and as direceted by the departmental officer incharge of work out side & inside
RCC M-25 design mix (cement,fine aggregate,coarse aggregate) corresponding to Table -9 of IS -456 using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including seigniorage charges ,sales and other taxes on all materials including all operational ,incidental and labour charges such as machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work,but including centering,shuttering complete as per ss and as direceted by the departmental officer incharge of work for Septic Tank slab
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position,complete for finished item of work in all floors. for septic tank
Construction of Staff QuProviding Instrumentation and Automation of the Pumping System, Supervisory Control and Data Acuasation System (SCADA) & Providing 2x7 water supply system at 250 KL ELSR at Water works and 500 KL ELSR at Sai Baba mettaarters at Intake well, Head Works site at Yeleswaram
Providing, Installation, Testing and Commissioning of PRESSURE TRANSMITTER for suction, Delivery and common Header with specifications of Water Application: Range: 0-16 Bar / Power Supply: 24 V DC / Output: 4-20 mA / Diaphragm: SS316L / Process Connection: 1/2 "NPT (M) / Accuracy: 0.15% Protection: IP67 . The cost also includes the calibration of all the sensors manifold etc., complete including cost and conveyance of all material and labor excluding cost of taxes and duties and as per SS and as directed by the department officer
Supply, errection, testing and commissioning of Ultra sonic/ Altitude Level sensors make of SIEMENS/ ABB/ BAUMER/ DANFOSS with specifications of body construction with standard construction, measuring upto 6.00 Mtr depth, protection clause of IP 65, accuracy is +/- 5%, input power supply is 24 V.. DC, remote communication protocol of 4 to 20 ma, temperature safety is in-built to comprehensive over temperature range with in the -40 Deg to +80 Deg, installed in both conditions i.e., indoor and outdoor, charges excluding cost of taxes and duties including cost and conveyance of all material including transport and labor etc., complete and as directed by the dept., officer.
For Raw Water Pumping Station as per the above specification
Supply and delivery of DI D/F hydraulic and self-medium operated double chamber diaphragm control valve for the functions of pump control i.e. to ensure smooth startup and shutdown of pumps. Valve shall be activated by line pressure and 24V DC solenoid for its operation. Non-return function in built to prevent surges due to pump trip events. Valve closure started as soon as solenoids are deenergized and limit switch of valve position indicator triggered. The valve can be manually overridden to check function. The main valve body internals shall consist of three basic parts i.e. body, diaphragm assembly and top cover with a spring inside main body. The nylon reinforced natural rubber diaphragm of the valve shall close on a seating arrangement. The control tubing shall include inline filter unit. The coating shall be of epoxy BLUE. Charges including cost and conveyance of all material and labor excluding cost of taxes and duties per SS and as directed by the department officer
DN 100 - PN 16 pump control valve for Raw Water Pumping Station as per the above specification
Supply and delivery of separate version Electro Magnetic Flow Meter MAG 5100 model or equilant with the specification of flow body as per company standards, electrodes of SS316, accuracy of +/- 2%, cable length of 20 Mtrs, end connection of ANSI flanges as IS/DIN standards, flow bore protection is IP68, earth rings of SS ( If required as per site condition) flow transmitter body as per company standard and two line display, transmitter having 4-20mA, RS485 and modbus communication for data transfer through any network, power supply of 24 volts DC , and submittion of manufacturer test and calbrationreports charges and all charges including cost and conveyance of all material , freight, transport and labour etc and excluding of GST etc., complete, and as directed by the dept., officer.
700MM Dia Above Specification.
Supply and testing of panel mounted 96 mmx 48 mm size on line mounted pH Analyser with Display (4 Digit) make of FM/ JUMO / ABB/ SIEMENS/ HACH with the technical specifications of Measuring Range: 0-14 pH, Process pressure range : 1 bar @ 50 Deg C, Measuring method : Reference, Solution ground : Graphite, electrode body: Glass body (tip), Wetted Parts : Glass tip plastic shaft protection Operating Temp: 0 to 50 Deg C, Protection Class : IP 65 (front) & IP 20 (rear), Communication : RS485, Voltage : 24 V.. DC Cable : 10 mtrs of Poly made the charges are including test and calibration certificate, cost and conveyance of all material, labor and excluding cost of taxes.
outlet of Raw Water Pumping Station at Yeleswaram reservoir
Supply and testing of wall mounted 120(w), 140(H), 77(D) Turbidity analyser with display(4 digit) make of FM/ JUMO / ABB/ SIEMENS/ HACH with the technical specifications of Measuring range: 1-4000 Ntu, Process pressure range : 2 bar @ 50 deg c, Measuring method : Infrared light 90 deg scatter light method, Max. sampling rate for measured values: 1 Hz, Resolution : 0.01 to 1 depending on measuring range , Measurands : Turbidity & Temperature Operating temp: 0 to 50 deg c, Protection class : IP 67, Communication : RS 485/4-20 mA, Voltage : 24 v.. DC, Sensor case : PVC/POM-C, Optical window: PMMA, Cable : 10 mtrs of Poly made the charges are including test and calibration certificate, cost and conveyance of all material, labor and excluding cost of taxes.
outlet of Raw Water Pumping Station at Yeleswaram reservoir
Supply and testing of panel mounted 96 mm x 48 mm size on line mounted Conductivity/ TDS sensor with display (4 digit) make of FM/ JUMO / ABB/ SIEMENS/ HACH with the technical specifications of Measuring range: .1 to approx. 1000 μS/cm, Cell constant : 0.1, Process pressure range : 5 bar @ 50 deg c, Measuring method : Conductive 2 electrode, Sampling : 500 msec, Measurands : Conductivity / TDS, Operating temp : -5 to +80 °C, Protection class : IP 67, Communication : RS 485, Voltage : 24 v.. DC, Sensor case: Stainless Steel 1.4571, Body material: PEI, Cable : 10 Mtrs of Polyimide and the charges are including test and calibration certificate, cost and conveyance of all material, labor and excluding cost of taxes.
outlet of Raw Water Pumping Station at Yeleswaram reservoir
Supply and testing of panel mounted 96 mm x 48 mm size on line mounted Chlorine Analyzer with display (4 digit) make of FM/ JUMO / ABB/ SIEMENS/ HACH with the technical specifications of Measuring range: 0-10 PPM, Cell constant : 0.1, Process pressure range : 1 bar @ 50 deg c, Measuring method : 2 and 3 Electrode principle, Response time : Approx. 2 min, pH Dependency (loss of slope) : In the range from pH 5 to 7: no loss of slope, at pH 8 about 10%, at pH 9 about 20%, (starting from pH 7), Operating temp : 0 to 50°C, Protection class : IP 67, Communication : RS 485, Voltage : 24 v.. DC, Sensor Case: PVC, Body material : PEI, Cable : 10 Mtrs of Polyimide and the charges are including test and calibration certificate, cost and conveyance of all material, labor and excluding cost of taxes.
outlet of Water Treatment plant
Supply laying and fixing of tubing for Inlet and out let of raw water and clear water to the analyzers with necessary pipes with compressed fittings charges excluding cost of taxes and duties including cost and conveyance of all material including transport and labor etc., complete and as directed by the dept., officer.
Raw Water Outlet of Water Treatment plant
Supply, errection, Testing & Commissioning of Out door type PLC/Controller based Automation and communication Panel fabricating with 16 SWG CR sheet, internal and external surface coating with Epoxy powder coating, making internal wiring with suitable wires including nomenclature. The panel is suitable for the Control & Monitoring the Level, Flow & Pressure and Quality Parameters and Comunicating with Central SCADA for Auto logic, Local and Remote operation of the valves with specifications of fabricating with 16 SWG CR sheet, internal and external surface coating with powder coating, making internal wiring with suitable wires including nomenclature. The panel is suitable for the above operations with PLC/Controller, communication modules, HMI, Power back up and necessary modules and as per site conditions etc., complete charges including all material and labor and excluding of taxes and duties and as per SS and as directed by the department officer.
Raw Water outlet and 32 MLD outlet at WTP
Supply, errection, Testing & Commissioning of In door type Scada based RTU control panel for Opearating and monitoring of the Raw Water and Clear Water Pumping stations in auto logic and manual operations including synchornize with SCADA and the specifications of fabricating with 16 SWG CR sheet, internal and external surface coating with Epoxy powder coating, arrangement of required PLC/ Controller, Ethernet Switch, Required I/O Modules and DI, DO modules, all components powered by 24 V. DC with necesssary control MCB's, Relay cards, fixing of all termination with FTB's, Internal wiring by all power cables with suitable guage of Single core copper PVC sheated cables and all communication cables with SS Brided cables, and the panel having logic for the following and erection with required civil works as per site conditions etc., complete charges including all materials and labour and excluding of taxes and duties and as per SS and as directed by the department officer.
For Raw Water Pumping Station as per the above specification
Reservoir Inlet Management ::
supply and delivery of "Resilient Seated Soft Sealing" Gate Valves (Sluice Valves) with Body and Bonnet of Ductile Iron GGG-40/SG-400/15 or GGG-50/SG-500/7 or Equivalent as per IS1865, IS:3896-2 and Wedge fully Rubber Lined with food grade quality grade W270 grade EPDM, Replaceable Spindle Nut without gland packing with 3-O ring protection system on the Shaft and Seals of NBR. The Valves should be Vacuum tight and 100% leak proof with face to face dimensions as BS:5163 Type A/IS:14846. All the valves should be with fusion bonded Electrostatic Powder coating both inside and outside (Min 250 Microns)- RAL 5005 with Pocket Less Straight through body Passage conforming to Design standards of DIN-3202F4/BS:5163 Type A Flange drilling as per IS - 1538 and including transportation.
100MM Dia Above Specification.
150 MM Dia Above Specification.
200 MM Dia Above Specification.
Inlet of 2100 KL Existing SUMP at Samalkota
Supply and delivery of separate version Electro Magnetic Flow Meter MAG 5100 model or equilant with the specification of flow body as per company standards, electrodes of SS316, accuracy of +/- 2%, cable length of 20 Mtrs, end connection of ANSI flanges as IS/DIN standards, flow bore protection is IP68, earth rings of SS ( If required as per site condition) flow transmitter body as per company standard and two line display, transmitter having 4-20mA, RS485 and modbus communication for data transfer through any network, power supply of 24 volts DC , and submittion of manufacturer test and calbrationreports charges and all charges including cost and conveyance of all material , freight, transport and labour etc , complete, and as directed by the dept., officer.
100MM Dia Above Specification.
150 MM Dia Above Specification.
200 MM Dia Above Specification.
300 MM Dia Above Specification.
Supply and delivery of Electrically switched, DI D/F hydraulic and self-medium operated diaphragm Control valve for the functions of Pressure & Flow control at Tank inlet with the function to maintain a constant downstream flow and pressure by controlling the differential pressure between the inlet and outlet of an orifice plate, regardless of pressure variations. The valve shall be of globe pattern inline or angular pattern with a main valve body of full or reduced bore designed for full differential pressure. The seat shall be of stainless steel which is replaceable.The valve can use manually and electrically with 24 V.. AC/DC for operation. The control tubing with self cleaning filter unit to functions as per customer requirement. The internal & external coating with liquid/Powder form epoxy coating, all fastners with SS including cost and convayance of all material and labor excluding and as per SS and as directed by the department officer
100MM Dia Above Specification.
150 MM Dia Above Specification.
200 MM Dia Above Specification.
300 MM Dia Above Specification.
Supply ad delivery of M.S. Dismantling Joints /SS, D/F expansion bellows with specifications of bellow with SS ASTM A 240 TP 304 grade, tie rods with EN8/IS-2062 Grade, End connection flanges with IS 2062 Gr.B Sorf plate, Drilling and dimensions as per approved drawing as required by customer at the time of order confirmation charges excluding cost of taxes and duties including cost and conveyance of all material including transport and labor etc., complete and as directed by the dept., officer.
100MM Dia Above Specification.
150 MM Dia Above Specification.
200 MM Dia Above Specification.
300 MM Dia Above Specification.
Supply, errection, testing and commissioning of Ultra sonic/ Altitude Level sensors make of SIEMENS/ ABB/ BAUMER/ DANFOSS / KELLER with specifications of body construction with standard construction, mesuring upto 6.00 Mtr depth, protection clause of IP 65, accuracy is +/- 5%, input power supply is 24 V.. DC, remote comunication protocol of 4 to 20 ma, temperature safety is in-built to comperhencive over temprature range with in the -40 Deg to +80 Deg, installed in both conditions i.e., indoor and outdoor, charges including cost and conveyance of all material including transport and labor etc., complete and as directed by the dept., officer.
Providing, Installation, Testing and Commissioning of PRESSURE TRANSMITTER for Water Application: Range: 0-10 Bar / Power Supply: 24 V DC / Output: 4-20 mA / Diaphragm: SS316L / Process Connection: 1/2 "NPT (M) / Accuracy: 0.15% Protection: IP67 . The cost also includes the calibration of all the sensors manifold etc., complete including cost and convayance of all material and labor and as per SS and as directed by the department officer
Supply and testing of panel mounted 96 mm x 48 mm size on line mounted Chlorine Analyzer with display (4 digit) make of FM/ JUMO / ABB/ SIEMENS/ HACH with the technical specifications of Measuring range: 0-10 PPM, Cell constant : 0.1, Process pressure range : 1 bar @ 50 deg c, Measuring method : 2 and 3 Electrode principle, Response time : Approx. 2 min, pH Dependency (loss of slope) : In the range from pH 5 to 7: no loss of slope, at pH 8 about 10%, at pH 9 about 20%, (starting from pH 7), Operating temp : 0 to 50°C, Protection class : IP 67, Communication : RS 485, Voltage : 24 v.. DC, Sensor Case: PVC, Body material : PEI, Cable : 10 Mtrs of Polyimide and the charges are including test and calibration certificate, cost and conveyance of all material,
Supply laying and fixing of tubing for Inlet and out let of raw water and clear water to the analyzers with necessary pipes with compressed fittingsincluding cost and conveyance of all material including transport and labor etc., complete and as directed by the dept., officer.
Supply, errection, Testing & Commissioning of Out door type PLC/Controller based Automation and communication Panel fabricating with 16 SWG CR sheet, internal and external surface coating with Epoxy powder coating, making internal wiring with suitable wires including nomenclature. The panel is suitable for the Control & Monitoring the Level, Flow,Pressure and Quality Parameters and Comunicating with Central SCADA for Auto logic, Local and Remote operation of the valves with specifications of fabricating with 16 SWG CR sheet, internal and external surface coating with powder coating, making internal wiring with suitable wires including nomenclature. The panel is suitable for the above operations with PLC/Controller, communication modules, HMI, Power back up and necessary modules and as per site conditions etc., complete charges including all material and labor and excluding of taxes and duties and as per SS and as directed by the department officer.
Supply laying and jointing of 4 Sq.MM - 2 core PVC sheeted cable make of LAPP/Orbit/Polycab/Finolex for solar / Raw power for the instrumantation and automation at Raw water and clear water pumping with in the Head works compound/ pumping stations/Individual OHSR's and laying with necessary cable trays/Condutes/ Civil works from each and every panel through side walls/cealing / floorings etc., where ever is necessary with all related civil works etc., charges excluding cost of taxes and duties including cost and conveyance of all material including transport and labor etc., complete and as directed by the dept., officer.
Supply laying and jointing of 0.75 Sq.MM - 4 core SS Brided and PVC sheeted cable make of LAPP/Orbit/Polycab/Finolex for solar / Raw power for the instrumantation and automation at Raw water and clear water pumping/ with in the Head works compound/ pumping stations/ Individual OHSR,s and laying with necessary cable trays/Condutes/ Civil works from each and every panel through side walls/cealing / floorings etc., where ever is necessary with all related civil works etc., charges excluding cost of taxes and duties including cost and conveyance of all material including transport and labor etc., complete and as directed by the dept., officer.
Erection, testing and commissioning of Reservoir Management unit including dejointing of existing pipeline / flange joints, taking out already laid DI/MS or any kind of pipe barrel piece, lifting the said pipe, cleaning & returning to the departmental store as per direction of the Engineer-in-charge and lowering, aligning & placing the flow Meter unit, jointing the same with fabricating of fittings, reducers, flanges with necessary MS material as per flow meter manufacturer standards and as per the site conditions with necessary lifting equiment, fabrication works, fixing with new Nuts , bolts and Rubber insertion with arrangment of necessary earth work excavations, MS clamp brackets, lifting equipment, retrofit works to complete the job as per site condition (Excluding cost of Meter, Valve& Expansion bellow etc.,) charges excluding cost of taxes and duties including cost and conveyance of all material including transport and labor etc., complete and as directed by the dept., officer.
Integration of PLC panels with Developing necessary softwares and programming as per field condition and user interface, communicated from each panel and intigrated with central SCADA station charges excluding cost of taxes and duties including cost and conveyance of all material including transport and labor etc., complete and as directed by the dept., officer.
24 x 7 Water Supply :: DMA Management ::
supply and delivery of "Resilient Seated Soft Sealing" Gate Valves (Sluice Valves) with Body and Bonnet of Ductile Iron GGG-40/SG-400/15 or GGG-50/SG-500/7 or Equivalent as per IS1865, IS:3896-2 and Wedge fully Rubber Lined with food grade quality grade W270 grade EPDM, Replaceable Spindle Nut without gland packing with 3-O ring protection system on the Shaft and Seals of NBR. The Valves should be Vacuum tight and 100% leak proof with face to face dimensions as BS:5163 Type A/IS:14846. All the valves should be with fusion bonded Electrostatic Powder coating both inside and outside (Min 250 Microns)- RAL 5005 with Pocket Less Straight through body Passage conforming to Design standards of DIN-3202F4/BS:5163 Type A Flange drilling as per IS - 1538 excluding all taxes, duties and including transportation.
Inlet of DMA-1 under 250 KL ELSR at Water works
Inlet of DMA-1 under 500 KL ELSR at Sai Baba metta
Supply and delivery of Separate Version Electro Magnetic Flow Meter MAG 5100 model or equilant with the specification of flow body as per company standards, electrodes of SS316, accuracy of +/- 2%, cable length of 20 Mtrs, end connection of ANSI flanges as IS/DIN standards, flow bore protection is IP68, earth rings of SS ( If required as per site condition) flow transmitter body as per company standard and two line display, transmitter having 4-20mA, RS485 and modbus communication for data transfer through any network, power supply of 24 volts DC , and submittion of manufacturer test and calbrationreports charges and all charges including cost and conveyance of all material , freight, transport and labour etc and excluding of GST etc., complete, and as directed by the dept., officer.
150MM Dia Above Specification.
350MM Dia Above Specification.
Supply and delivery of Electrically switched, DI D/F hydraulic and self-medium operated diaphragm Control valve for the functions of Pressure & Flow control at Tank inlet with the function to maintain a constant downstream flow and pressure by controlling the differential pressure between the inlet and outlet of an orifice plate, regardless of pressure variations. The valve shall be of globe pattern inline or angular pattern with a main valve body of full or reduced bore designed for full differential pressure. The seat shall be of stainless steel which is replaceable.The valve can use manually and electrically with 24 V.. AC/DC for operation. The control tubing with self cleaning filter unit to functions as per customer requirement. The internal & external coating with liquid/Powder form epoxy coating, all fastners with SS including cost and convayance of all material and labor excluding cost of taxes and duties and as per SS and as directed by the department officer
150MM Dia Above Specification.
350MM Dia Above Specification.
Supply ad delivery of M.S. Dismantling Joints /SS, D/F expansion bellows with specifications of bellow with SS ASTM A 240 TP 304 grade, tie rods with EN8/IS-2062 Grade, End connection flanges with IS 2062 Gr.B Sorf plate, Drilling and dimensions as per approved drawing as required by customer at the time of order confirmation charges excluding cost of taxes and duties including cost and conveyance of all material including transport and labor etc., complete and as directed by the dept., officer.
150MM Dia Above Specification.
350MM Dia Above Specification.
Providing, Installation, Testing and Commissioning of PRESSURE TRANSMITTER for Water Application: Range: 0-10 Bar / Power Supply: 24 V DC / Output: 4-20 mA / Diaphragm: SS316L / Process Connection: 1/2 "NPT (M) / Accuracy: 0.15% Protection: IP67 . The cost also includes the calibration of all the sensors manifold etc., complete including cost and convayance of all material and labor excluding cost of taxes and duties and as per SS and as directed by the department officer
Supply, errection, Testing & Commissioning of Out door type PLC/Controller based Automation and communication Panel fabricating with 16 SWG CR sheet, internal and external surface coating with Epoxy powder coating, making internal wiring with suitable wires including nomenclature. The panel is suitable for the Control & Monitoring the Level, Flow, Pressure and Qaulity Parameters and Comunicating with Central SCADA for Auto logic, Local and Remote operation of the valves with specifications of fabricating with 16 SWG CR sheet, internal and external surface coating with powder coating, making internal wiring with suitable wires including nomenclature. The panel is suitable for the above operations with PLC/Controller, communication modules, HMI, Power back up and necessary modules and as per site conditions etc., complete charges including all material and labor and excluding of taxes and duties and as per SS and as directed by the department officer.
Supply laying and jointing of 4 Sq.MM - 2 core PVC sheeted cable make of LAPP/Orbit/Polycab/Finolex for solar / Raw power for the instrumantation and automation at Raw water and clear water pumping with in the Head works compound/ pumping stations/Individual OHSR's and laying with necessary cable trays/Condutes/ Civil works from each and every panel through side walls/cealing / floorings etc., where ever is necessary with all related civil works etc., charges excluding cost of taxes and duties including cost and conveyance of all material including transport and labor etc., complete and as directed by the dept., officer.
Supply laying and jointing of 0.75 Sq.MM - 4 core SS Brided and PVC sheeted cable make of LAPP/Orbit/Polycab/Finolex for solar / Raw power for the instrumantation and automation at Raw water and clear water pumping/ with in the Head works compound/ pumping stations/ Individual OHSR,s and laying with necessary cable trays/Condutes/ Civil works from each and every panel through side walls/cealing / floorings etc., where ever is necessary with all related civil works etc., charges excluding cost of taxes and duties including cost and conveyance of all material including transport and labor etc., complete and as directed by the dept., officer.
Erection, testing and commissioning of DMA management unit including dejointing of existing pipeline / flange joints, taking out already laid DI/MS or any kind of pipe barrel piece, lifting the said pipe, cleaning & returning to the departmental store as per direction of the Engineer-in-charge and lowering, aligning & placing the flow Meter unit, jointing the same with fabricating of fittings, reducers, flanges with necessary MS material as per flow meter manufacturer standards and as per the site conditions with necessary lifting equiment, fabrication works, fixing with new Nuts , bolts and Rubber insertion with arrangment of necessary earth work excavations, MS clamp brackets, lifting equipment, retrofit works to complete the job as per site condition (Excluding cost of Meter, Valve& Expansion bellow etc.,) charges excluding cost of taxes and duties including cost and conveyance of all material including transport and labor etc., complete and as directed by the dept., officer.
Integration of PLC panels with Developing necessary softwares and programming as per field condition and user interface, communicated from each panel and intigrated with central SCADA station charges excluding cost of taxes and duties including cost and conveyance of all material including transport and labor etc., complete and as directed by the dept., officer.
AMI Water Meter Management.
Providing, Installing and satisfactory field testing of domestic Water Meter with AMR Compatible Mechanical Water Meters with the specifications of minimum Dynamic ratio (Q3/Q1) of 160:1, fully body made up of composite material/ Brass/ Bronze, the metal Material that come in contact with the water supply shall withstand 2 ppm (Parts per million) of chlorine residual in the water supply and shall be resistant to corrosion, mechanical inferential type, multi jet, magnetically coupled, having dry dial, protection class of IP-68, Class ’B’ confirming to IS-779: 1994 with up to date amendments or ISO 4064:2014 standard with ISI/EEC/OIML/MID/CE certification mark shall be with meter and offer 5 years warranty and submittion of manufacturer test and calbrationreports charges and all charges including cost and conveyance of all material , freight, transport and labour etc and excluding of GST etc., complete, and as directed by the dept., officer. Note: Detailesd technical specifications enclosed as Anexure-A.
Supply, Delivery, Installing and satisfactory field testing of AMR Unit for domestic Water Meters from 15 mm to 40 mm with the specifications of fully body made up of composite material, magnetically coupled in between meter and AMR module, protection class of IP-68, In built battery with 3.60 V... Lithium Battery for life of 10 Years based on one communication /Day, Communication interface in between meter and AMR unit with Pulse/ Photo Electric, AMR unit can fetch the data from meter on hourly basis and store the data for 48 Hours on FIFO basis and send the data through NB IoT in every 24 Hours without fail through the provider registered in DOT, India, if the communication fails due to bad communication the AMR module can try for a maximum six times in different time intervals to ensure the data to reach to server. The AMR unit have option of Bluetooth for remote configurations at field. In the special event and field testing the data sending interval of AMR unit can be configurable and minimum time interval span is one Hour (The battery life can be calculated based on the time intervals of data communication) The data storage should be kept in Indian data centres for the data security, AMR unit can be registered the abnormalities like Reverse flow, Leak detection, Tampering and send to the server via reading data packet, Every communication from the AMR module to server should be in JSON format with real time stamping, The AMR can suitable for all the Mechanical Water meters supplied by the agency in this contract. The AMR Module offered with 5 years warranties and submittion of manufacturer test and calbrationreports charges and all charges including cost and conveyance of all material , freight, transport and labour etc and excluding of GST etc., complete, and as directed by the dept., officer. Note: Detailesd technical specifications enclosed as Anexure-B
Supplying and Fixing water meter BOX- with Weather resistant FRP box, press fitted Lid fixing & locking and locked with built-in or external lock. Charges including breather, NBR bushes for pipe entry, SS Grouting screws etc., complete and as directed by the departmment officer.
Local SCADA Control Sation:
Supply, erection, testing, commissioning of Hard ware for the SCADA system for Local control station where the SCADA room will be developed by the local ULB for operting & View from Service Reservoirs, DMA and AMI meter management where the instrumantation and automation developed under this project and synchornization by deploying the following components including cost and convayance of all material, user licences, communication networks, etc., complete and as directed by the department officer.
Design, Development, Deploy, testing & commissioning of Firmware for the WEB based SCADA system for Local control station where the SCADA room will be developed by the local ULB for operting & View from Service Reservoirs, DMA and AMI meter management and where the instrumantation and automation developed under this project by synchornization with the field instruments, configuration with the following features including cost and convayance of all material, user licences, communication networks, etc., complete and as directed by the department officer.
Laying new Distribution lines zone-I
Earth work excavation in all soils up to SDR & stone matrix by machinery for Pipe lines as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and back filling in trenches with excavated suitable material as per Technical Specification No.305 MORD/304 MORTH up to initial lift of 3.0m. For Pipe line trenches.
Machenical mans 70%
Manual means 30%
Manufacture, supply and delivery of PE 100-PN 6 HDPE pipes confirming to IS 4984-1995 including transportation to work spot, stacking etc. complete as per S.S and as directed by the departmental officer incharge of work.
110mm dia.
160mm dia.
200mm dia.
250mm dia.
315 mm dia
Manufacture, supply, & delivery of HDPE fittings conforming to IS 4984 - 1995 including transportation to work spot, stacking complete as per S.S and as directed by the departmental officer incharge of work.
a) Pipe ends - long neck
110mm dia.
110 mm dia for Air TEEs
160mm dia.
160 mm dia for Air TEEs
200mm dia.
200 mm dia for Air TEEs
250mm dia.
250 mm dia for Air TEEs
b) MS Flanges
110mm dia.
110 mm dia for Air TEEs
160mm dia.
160 mm dia for Air TEEs
200mm dia.
200 mm dia for Air TEEs
250mm dia.
250 mm dia for Air TEEs
c) End Caps
110mm dia.
160mm dia.
200mm dia.
250mm dia.
d) Reducers
110X125 mm dia
125x140 mm dia
140x160 mm dia
160x180 mm dia
180x200 mm dia
e) TEES
110mm dia.
160mm dia.
200mm dia.
250mm dia.
F)Bends
110mm dia.
160mm dia.
200mm dia.
250mm dia.
Lowering, laying and jointing of HDPE pipes and jointing by butt fusion welding as per IS 7634-part-II/1975 as amended from time to time to the alignment and gradient and testing the pipeline to required pressure etc.complete as per S.S and as directed by the departmental officer incharge of work.
110mm dia.
160mm dia.
200mm dia.
250mm dia.
315 mm dia
Supply and delivery of DI Pipes and fittings (Specials) confirming to specification No.I.S.No. 7181/1986, 5531/1988, 3950/1979 including VAT and other duties including transportation and conveyance to work spot and stacking etc., complete as per S.S and as directed by the departmental authorities.
DIDF pipes for scours
100X2.00m on 110 and 160 mm dia mains for scours
100x1.00m long DF pipes for sluice valves
150 mm dia x2.00m on 200 and 250 mm dia pipes for scours
150x1.00m long DF pipes for sluice valves
200 mm dia x2.00m on 315 and 355 mm dia pipes for scours
200x1.00m long DF pipes for sluice valves
100 mm dia deck foot bends
100x100x80 mm DIDF TEE for air valves
supply and delivery of "Resilient Seated Soft Sealing" Gate Valves (Sluice Valves) with Body and Bonnet of Ductile Iron GGG-40/SG-400/15 or GGG-50/SG-500/7 or Equivalent as per IS1865, IS:3896-2 and Wedge fully Rubber Lined with food grade quality grade W270 grade EPDM, Replaceable Spindle Nut without gland packing with 3-O ring protection system on the Shaft and Seals of NBR. The Valves should be Vacuum tight and 100% leak proof with face to face dimensions as BS:5163 Type A/IS:14846. All the valves should be with fusion bonded Electrostatic Powder coating both inside and outside (Min 250 Microns)- RAL 5005 with Pocket Less Straight through body Passage conforming to Design standards of DIN-3202F4/BS:5163 Type A Flange drilling as per IS - 1538 and including transportation. PN16 -
100 mm distrubution
150mm dia for distrubution
200mm dia for distrubution
250mm dia for distrubution
for scour
100mm dia on 110 mm and 160 mm dia mains
150 mm dia on 200 and 250 mm dia lines
Manufacture, supply and delivery of Single Chamber DI Air Valve with Body and cover in Ductile Iron of grade SG 400/12 or equivalent grade as per I.S.3896-part2-1985 and subsequent revisions. All internal parts such as float, shell etc., all cover bolts, of stainless steel, and Gaskets and seals of EPDM food grade quality Epoxy powder coating (EP-P) inside and outside colour blue. Drilled as per IS:1538. PN16
80 mm dia on 110 mm pipe
80 mm dia on 160 mm pipe
80mm dia 200 mm pipe
80mm dia 250 mm pipe
Labour charges for lowering and keeping in position of D.I. Sluice valves, reflux valves and scour valves. Rate including all the materials,labour charges and other incidental charges and complete as per ss and as directed by the departmental officer incharge of work
100 mm distrubution
150mm dia for distrubution
200mm dia for distrubution
250mm dia for distrubution
for scour
100mm dia on 110 mm and 160 mm dia mains
150 mm dia on 200 and 250 mm dia lines
Construction of sluice and scour Valve Chamber as per type design drawing with CC including, plastering, RCC cover slabs etc. including cost and conveyance of all material and all labour charges etc. complete as per S.S for finished item of work Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH Note : Classifications of Earth Work Specification are as per 302.2.1(a) of MORD and 301.2.1 of MORT&H--ordinary soil--manual means upto 3m depth manual means
Filling with Sand in Valve chamber bedding This rate including cost of Sand,all labour charges,watering,ramming,and other incidental charges etc as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH etc.,complete as per S.S and as directed by the departmental officer incharge of work
Providing PCC 1:4:8 using 40 mm graded SS 5 HBG m/c metal and OPC coarse and fine aggregate confirming to IS 383 including cost and conveyance of all materials and labour charges, machine mixing , vibration,laying in position, curing etc., complete as per ss and as direceted by the departmental officer incharge of work
RCC M-20 Nominal mix (cement,fine aggregate,coarse aggregate) corresponding to Table -9 of IS -456 using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including seigniorage charges ,sales and other taxes on all materials including all operational ,incidental and labour charges such as machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work,but including centering,shuttering for complete as per ss and as direceted by the departmental officer incharge of work as follows
Raft 0.10m thick
For side walls 0.20m thick 4x1.40=5.6
for cover slabs 0.15m thick
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying including sales and other taxes on all materials etc., complete for finished item of work in all floors.( APSS No.126) for pre cast slabs of valve chambers
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH Note : Classifications of Earth Work Specification are as per 302.2.1(a) of MORD and 301.2.1 of MORT&H--ordinary soil--manual means upto 3m depth manual means
Filling with Sand in Valve chamber bedding This rate including cost of Sand,all labour charges,watering,ramming,and other incidental charges etc as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH etc.,complete as per S.S and as directed by the departmental officer incharge of work
Providing PCC 1:4:8 using 40 mm graded SS 5 HBG m/c metal and OPC coarse and fine aggregate confirming to IS 383 including cost and conveyance of all materials and labour charges, machine mixing , vibration,laying in position, curing etc., complete as per S.S and as directed by the departmental officer incharge of work
RCC M-20 Nominal mix (cement,fine aggregate,coarse aggregate) corresponding to Table -9 of IS -456 using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including seigniorage charges ,sales and other taxes on all materials including all operational ,incidental and labour charges such as machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work,but including centering,shuttering complete as per S.S and as directed by the departmental officer incharge of work follows
Raft 0.10m thick
For side walls 0.20m thick 4x1.40=5.6
for cover slabs 0.15m thick
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying including etc., complete for finished item of work in all floors.( APSS No.126) for pre cast slabs of valve chambers
construction of valve chambers Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH Note : Classifications of Earth Work Specification are as per 302.2.1(a) of MORD and 301.2.1 of MORT&H--ordinary soil--manual means upto 3m depth manual means
Filling with Sand in Valve chamber bedding This rate including cost of Sand,all labour charges,watering,ramming,and other incidental charges etc as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH etc.,complete as per S.S and as directed by the departmental officer incharge of work
Providing PCC 1:4:8 using 40 mm graded SS 5 HBG m/c metal and OPC coarse and fine aggregate confirming to IS 383 including cost and conveyance of all materials and labour charges, machine mixing , vibration,laying in position, curing etc., complete as per S.S and as directed by the departmental officer incharge of work
RCC M-20 Nominal mix (cement,fine aggregate,coarse aggregate) corresponding to Table -9 of IS -456 using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including seigniorage charges ,sales and other taxes on all materials including all operational ,incidental and labour charges such as machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work,but including centering,shuttering complete as per S.S and as directed by the departmental officer incharge of work as follows
Raft 0.10m thick
For side walls 0.20m thick 4x1.40=5.60
for cover slabs 0.15 m thick
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying including on all materials etc., complete for finished item of work in all floors.( APSS No.126) for pre cast slabs of valve chambers
construction of valve chambers Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH Note : Classifications of Earth Work Specification are as per 302.2.1(a) of MORD and 301.2.1 of MORT&H--ordinary soil--manual means upto 3m depth manual means
Filling with Sand in Valve chamber bedding This rate including cost of Sand,all labour charges,watering,ramming,and other incidental charges etc as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH etc.,complete as per S.S and as directed by the departmental officer incharge of work
Providing PCC 1:4:8 using 40 mm graded SS 5 HBG m/c metal and OPC coarse and fine aggregate confirming to IS 383 including cost and conveyance of all materials and labour charges, machine mixing , vibration,laying in position, curing etc., ,complete as per S.S and as directed by the departmental officer incharge of work
RCC M-20 Nominal mix (cement,fine aggregate,coarse aggregate) corresponding to Table -9 of IS -456 using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including seigniorage charges ,sales and other taxes on all materials including all operational ,incidental and labour charges such as machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work,but including centering,shuttering complete as per S.S and as directed by the departmental officer incharge of work as follows
Raft 0.10m thick
For side walls 0.20m thick 4x1.40=5.60
for cover slabs 0.15 m thick
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, all materials etc., complete for finished item of work in all floors.( APSS No.126) for pre cast slabs of valve chambers
construction of valve chambers Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH Note : Classifications of Earth Work Specification are as per 302.2.1(a) of MORD and 301.2.1 of MORT&H--ordinary soil--manual means upto 3m depth manual means
Filling with Sand in Valve chamber bedding This rate including cost of Sand,all labour charges,watering,ramming,and other incidental charges etc as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH etc.,complete as per S.S and as directed by the departmental officer incharge of work
Providing PCC 1:4:8 using 40 mm graded SS 5 HBG m/c metal and OPC coarse and fine aggregate confirming to IS 383 including cost and conveyance of all materials and labour charges, machine mixing , vibration,laying in position, curing etc., complete as per S.S and as directed by the departmental officer incharge of work
RCC M-20 Nominal mix (cement,fine aggregate,coarse aggregate) corresponding to Table -9 of IS -456 using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including seigniorage charges ,sales and other taxes on all materials including all operational ,incidental and labour charges such as machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work,but including centering,shuttering for cover slabs complete as per ss and as direceted by the departmental officer incharge of work
Raft 0.10m thick
For side walls 0.20m thick 4x1.40=5.6
for cover slabs 0.15m thick
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying , complete for finished item of work in all floors.( APSS No.126) for pre cast slabs of valve chambers
construction of valve chambers Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH Note : Classifications of Earth Work Specification are as per 302.2.1(a) of MORD and 301.2.1 of MORT&H--ordinary soil--manual means upto 3m depth manual means
Filling with Sand in Valve chamber bedding This rate including cost of Sand,all labour charges,watering,ramming,and other incidental charges etc as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH etc.,complete as per S.S and as directed by the departmental officer incharge of work
Providing PCC 1:4:8 using 40 mm graded SS 5 HBG m/c metal and OPC coarse and fine aggregate confirming to IS 383 including cost and conveyance of all materials and labour charges, machine mixing , vibration,laying in position, curing etc., complete as per S.S and as directed by the departmental officer incharge of work
RCC M-20 Nominal mix (cement,fine aggregate,coarse aggregate) corresponding to Table -9 of IS -456 using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including seigniorage charges on all materials including all operational ,incidental and labour charges such as machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work,but including centering,shuttering ,complete as per S.S and as directed by the departmental officer incharge of work as follows
Raft 0.10m thick
For side walls 0.20m thick 4x1.40=5.6
for cover slabs 0.15m thick
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position,on all materials etc., complete for finished item of work in all floors.( APSS No.126) for pre cast slabs of valve chambers
Construction of Air Valve Chamber as per type design drawing with CC including, plastering, RCC cover slabs etc. including cost and conveyance of all material and all labour charges etc. complete as per S.S for finished item of work Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH Note : Classifications of Earth Work Specification are as per 302.2.1(a) of MORD and 301.2.1 of MORT&H--ordinary soil--manual means upto 3m depth manual means
Filling with Sand in Valve chamber bedding This rate including cost of Sand,all labour charges,watering,ramming,and other incidental charges etc as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH etc.,complete as per S.S and as directed by the departmental officer incharge of work
Providing PCC 1:4:8 using 40 mm graded SS 5 HBG m/c metal and OPC coarse and fine aggregate confirming to IS 383 including cost and conveyance of all materials and labour charges, machine mixing , vibration,laying in position, curing etc., complete as per S.S and as directed by the departmental officer incharge of work
RCC M-20 Nominal mix (cement,fine aggregate,coarse aggregate) corresponding to Table -9 of IS -456 using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including seigniorage charges on all materials including all operational ,incidental and labour charges such as machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work,but including centering,shuttering ,complete as per S.S and as directed by the departmental officer incharge of work as follows
Raft 0.10m thick
For side walls 0.20m thick 4x1.40=5.6
for cover slabs 0.15m thick
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying including sales and other taxes on all materials etc., complete for finished item of work in all floors.( APSS No.126) for pre cast slabs of valve chambers
Construction of Air Valve Chamber as per type design drawing with CC including, plastering, RCC cover slabs etc. including cost and conveyance of all material and all labour charges etc. complete as per S.S for finished item of work Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH Note : Classifications of Earth Work Specification are as per 302.2.1(a) of MORD and 301.2.1 of MORT&H--ordinary soil--manual means upto 3m depth manual means
Filling with Sand in Valve chamber bedding This rate including cost of Sand,all labour charges,watering,ramming,and other incidental charges etc as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH etc.,complete as per S.S and as directed by the departmental officer incharge of work
Providing PCC 1:4:8 using 40 mm graded SS 5 HBG m/c metal and OPC coarse and fine aggregate confirming to IS 383 including cost and conveyance of all materials and labour charges, machine mixing , vibration,laying in position, curing etc., complete as per S.S and as directed by the departmental officer incharge of work
RCC M-20 Nominal mix (cement,fine aggregate,coarse aggregate) corresponding to Table -9 of IS -456 using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including seigniorage charges on all materials including all operational ,incidental and labour charges such as machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work,but including centering,shuttering ,complete as per S.S and as directed by the departmental officer incharge of work as follows
Raft 0.10m thick
For side walls 0.20m thick 4x1.40=5.6
for cover slabs 0.15m thick
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, complete for finished item of work in all floors.( APSS No.126) for pre cast slabs of valve chambers
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH Note : Classifications of Earth Work Specification are as per 302.2.1(a) of MORD and 301.2.1 of MORT&H--ordinary soil--manual means upto 3m depth manual means
Filling with Sand in Valve chamber bedding This rate including cost of Sand,all labour charges,watering,ramming,and other incidental charges etc as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH etc.,complete as per S.S and as directed by the departmental officer incharge of work
Providing PCC 1:4:8 using 40 mm graded SS 5 HBG m/c metal and OPC coarse and fine aggregate confirming to IS 383 including cost and conveyance of all materials and labour charges, machine mixing , vibration,laying in position, curing etc., complete
RCC M-20 Nominal mix (cement,fine aggregate,coarse aggregate) corresponding to Table -9 of IS -456 using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including seigniorage charges on all materials including all operational ,incidental and labour charges such as machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work,but including centering,shuttering ,complete as per S.S and as directed by the departmental officer incharge of work as follows
Raft 0.10m thick
For side walls 0.20m thick 4x1.40=5.60
for cover slabs 0.15 m thick
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position,complete for finished item of work in all floors.( APSS No.126) for pre cast slabs of valve chambers
Lowering the C.I. Pipes, D.I. Pipes of all classes and fittings with flanged ends carefully into the trenches and laying them true to alignment and gradient including all sundries, from source of supply as per BIS No.3114/94.complete as per ss and as direceted by the departmental officer incharge of work
150 mm dia
200 mm dia
250 mm dia
Jointing the C.I. Pipes, fittings and valves with flanged ends including cost of jointing materials such as bolts, nuts, rubber insertion, white lead and including filling with water with a water lead upto 500 m and testing to required pressure etc., BIS No.3114/85 complete as per ss and as direceted by the departmental officer incharge of work.
100 mm dia
150 mm dia
200 mm dia
250 mm dia
Cutting of existing B.T.road surface for pipe line trench (aswell as asphalt concrete up to 75mm thick) including water bound macadam including all labour charges for cutting, stacking this rate including hiring of machinary,fuel charges,wages of driver, complete as per the directions of departmental authorities. complete as per the directions of departmental authorities.
Cutting and open of C.C. Road surface for pipe line trenches including stacking of excavated materials for lying of pipe lines,this rate including hiring of machinary,fuel charges,wages of driver, complete as per the directions of departmental authorities.
Cutting and open of Water bound macadam surface for pipe line trenches including stacking of excavated materials for lying of pipe lines,this rate including hiring of machinary,fuel charges,wages of driver, complete as per the directions of departmental authorities.
Filling with Crusher Stone dust in valve chambers sand bedding. This rate including cost of Dust,all labour charges,watering,ramming,and other incidental charges etc as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH etc.,complete as per S.S and as directed by the departmental officer incharge of work
Restoration of CC Road by Using Concrete mixture Plain Cement concrete nominal mix M-30 (Cement : fine aggregate: coarse aggregate ) using 20mm size Hard Granite Machine Crushed Graded Metal including cost and conveyance of all materials like cement, sand, coarse aggregate water etc., to site , seigniorage charges on all materials, labour charges , for mixing , laying, concrete , ramming in 15 cm layers, finishing top surface to the required level curing etc., complete for finished item of work with nomonal reinforcement for Road restoration.
Laying new Distribution lines zone-II
Earth work excavation in all soils up to SDR & stone matrix by machinery for Pipe lines as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and back filling in trenches with excavated suitable material as per Technical Specification No.305 MORD/304 MORTH up to initial lift of 3.0m. For Pipe line trenches.
Machenical mans 70%
Manual means 20%
Filling with Sand in pipe line bedding This rate including cost of Sand,all labour charges,watering,ramming,and other incidental charges etc as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH etc.,complete as per S.S and as directed by the departmental officer incharge of work
Manufacture, supply and delivery of PE 100-PN 6 HDPE pipes confirming to IS 4984-1995 including transportation to work spot, stacking etc. complete as per S.S and as direceted by the departmental officer incharge of work
110mm dia.
160mm dia.
200mm dia.
250mm dia.
Manufacture, supply, & delivery of HDPE fittings conforming to IS 4984 - 1995 including transportation to work spot, stacking etc.complete as per ss and as direceted by the departmental officer incharge of work
a) Pipe ends - long neck
110mm dia.
110 mm dia for Air TEEs
160mm dia.
160 mm dia for Air TEEs
200mm dia.
200 mm dia for Air TEEs
250mm dia.
250 mm dia for Air TEEs
b) MS Flanges
110mm dia.
110 mm dia for Air TEEs
160mm dia.
160 mm dia for Air TEEs
200mm dia.
200 mm dia for Air TEEs
250mm dia.
250 mm dia for Air TEEs
c) End Caps
110mm dia.
160mm dia.
200mm dia.
250mm dia.
d) Reducers
110X125 mm dia
125x140 mm dia
140x160 mm dia
160x180 mm dia
180x200 mm dia
e) TEES
110mm dia.
160mm dia.
200mm dia.
250mm dia.
F)Bends
110mm dia.
160mm dia.
200mm dia.
250mm dia.
Lowering, laying and jointing of HDPE pipes and jointing by butt fusion welding as per IS 7634-part-II/1975 as amended from time to time to the alignment and gradient and testing the pipeline to required pressure etc.complete as per S.S and as directed by the departmental authorities.
110mm dia.
160mm dia.
200mm dia.
250mm dia.
Supply and delivery of DI Pipes and fittings (Specials) confirming to specification No.I.S.No. 7181/1986, 5531/1988, 3950/1979 including VAT and other duties including transportation and conveyance to work spot and stacking etc., complete as per S.S and as directed by the departmental authorities.
100X2.00m on 110 and 160 mm dia mains for scours
100x1.00m long DF pipes for sluice valves
150 mm dia x2.00m on 200 and 250 mm dia pipes for scours
150x1.00m long DF pipes for sluice valves
200 mm dia x2.00m on 315 and 355 mm dia pipes for scours
200x1.00m long DF pipes for sluice valves
250x1.00m long DF pipes for sluice valves
100 mm dia deck foot bends
100x100x80 mm DIDF TEE for air valves
supply and delivery of "Resilient Seated Soft Sealing" Gate Valves (Sluice Valves) with Body and Bonnet of Ductile Iron GGG-40/SG-400/15 or GGG-50/SG-500/7 or Equivalent as per IS1865, IS:3896-2 and Wedge fully Rubber Lined with food grade quality grade W270 grade EPDM, Replaceable Spindle Nut without gland packing with 3-O ring protection system on the Shaft and Seals of NBR. The Valves should be Vacuum tight and 100% leak proof with face to face dimensions as BS:5163 Type A/IS:14846. All the valves should be with fusion bonded Electrostatic Powder coating both inside and outside (Min 250 Microns)- RAL 5005 with Pocket Less Straight through body Passage conforming to Design standards of DIN-3202F4/BS:5163 Type A Flange drilling as per IS - 1538 and including transportation. PN16 -
100 mm distrubution
150mm dia for distrubution
200mm dia for distrubution
250mm dia for distrubution
for scour
100mm dia on 110 mm and 160 mm dia mains
150 mm dia on 200 and 250 mm dia lines
200 mm dia on 315 and 355 mm lines
Manufacture, supply and delivery of Single Chamber DI Air Valve with Body and cover in Ductile Iron of grade SG 400/12 or equivalent grade as per I.S.3896-part2-1985 and subsequent revisions. All internal parts such as float, shell etc., all cover bolts, of stainless steel, and Gaskets and seals of EPDM food grade quality Epoxy powder coating (EP-P) inside and outside colour blue. Drilled as per IS:1538. PN16
80 mm dia on 110 mm pipe
80 mm dia on 160 mm pipe
80mm dia 200 mm pipe
80mm dia 250 mm pipe
Labour charges for lowering and keeping in position of D.I. Sluice valves, reflux valves and scour valves.rate including all materials and other incidental charges complete as per S.S and as directed by the departmental authorities.
100 mm distrubution
150mm dia for distrubution
200mm dia for distrubution
250mm dia for distrubution
for scour
100mm dia on 110 mm and 160 mm dia mains
150 mm dia on 200 and 250 mm dia lines
200 mm dia on 315 and 355 mm lines
Construction of sluice and scour Valve Chamber as per type design drawing with CC including, plastering, RCC cover slabs etc. including cost and conveyance of all material and all labour charges etc. complete as per S.S for finished item of work Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH Note : Classifications of Earth Work Specification are as per 302.2.1(a) of MORD and 301.2.1 of MORT&H--ordinary soil--manual means upto 3m depth manual means
Filling with Sand in Valve chamber bedding This rate including cost of Sand,all labour charges,watering,ramming,and other incidental charges etc as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH etc.,complete as per S.S and as directed by the departmental officer incharge of work
Providing PCC 1:4:8 using 40 mm graded SS 5 HBG m/c metal and OPC coarse and fine aggregate confirming to IS 383 including cost and conveyance of all materials and labour charges, machine mixing , vibration,laying in position, curing etc., complete
RCC M-20 Nominal mix (cement,fine aggregate,coarse aggregate) corresponding to Table -9 of IS -456 using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including seigniorage charges on all materials including all operational ,incidental and labour charges such as machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work,but including centering,shuttering ,complete as per S.S and as directed by the departmental officer incharge of work as follows
Raft 0.10m thick
For side walls 0.20m thick 4x1.40=5.6
for cover slabs 0.15m thick
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying including on all materials etc., complete for finished item of work in all floors.( APSS No.126) for pre cast slabs of valve chambers
Earthwork in excavation for Valve Chambers as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH Note : Classifications of Earth Work Specification are as per 302.2.1(a) of MORD and 301.2.1 of MORT&H--ordinary soil--manual means upto 3m depth manual means
Filling with Sand in Valve chamber bedding This rate including cost of Sand,all labour charges,watering,ramming,and other incidental charges etc as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH etc.,complete as per S.S and as directed by the departmental officer incharge of work
Providing PCC 1:4:8 using 40 mm graded SS 5 HBG m/c metal and OPC coarse and fine aggregate confirming to IS 383 including cost and conveyance of all materials and labour charges, machine mixing , vibration,laying in position, curing etc., complete
RCC M-20 Nominal mix (cement,fine aggregate,coarse aggregate) corresponding to Table -9 of IS -456 using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including seigniorage charges on all materials including all operational ,incidental and labour charges such as machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work,but including centering,shuttering ,complete as per S.S and as directed by the departmental officer incharge of work as follows
Raft 0.10m thick
For side walls 0.20m thick 4x1.40=5.6
for cover slabs 0.15m thick
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position,., complete for finished item of work in all floors.( APSS No.126) for pre cast slabs of valve chambers
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH Note : Classifications of Earth Work Specification are as per 302.2.1(a) of MORD and 301.2.1 of MORT&H--ordinary soil--manual means upto 3m depth manual means
Filling with Sand in Valve chamber bedding This rate including cost of Sand,all labour charges,watering,ramming,and other incidental charges etc as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH etc.,complete as per S.S and as directed by the departmental officer incharge of work
Providing PCC 1:4:8 using 40 mm graded SS 5 HBG m/c metal and OPC coarse and fine aggregate confirming to IS 383 including cost and conveyance of all materials and labour charges, machine mixing , vibration,laying in position, curing etc., complete
RCC M-20 Nominal mix (cement,fine aggregate,coarse aggregate) corresponding to Table -9 of IS -456 using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including seigniorage charges on all materials including all operational ,incidental and labour charges such as machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work,but including centering,shuttering ,complete as per S.S and as directed by the departmental officer incharge of work as follows
Raft 0.10m thick
For side walls 0.20m thick 4x1.40=5.60
for cover slabs 0.15 m thick
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying including sales and other taxes on all materials etc., complete for finished item of work in all floors.( APSS No.126) for pre cast slabs of valve chambers
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH Note : Classifications of Earth Work Specification are as per 302.2.1(a) of MORD and 301.2.1 of MORT&H--ordinary soil--manual means upto 3m depth manual means
Filling with Sand in Valve chamber bedding This rate including cost of Sand,all labour charges,watering,ramming,and other incidental charges etc as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH etc.,complete as per S.S and as directed by the departmental officer incharge of work
Providing PCC 1:4:8 using 40 mm graded SS 5 HBG m/c metal and OPC coarse and fine aggregate confirming to IS 383 including cost and conveyance of all materials and labour charges, machine mixing , vibration,laying in position, curing etc., complete
RCC M-20 Nominal mix (cement,fine aggregate,coarse aggregate) corresponding to Table -9 of IS -456 using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including seigniorage charges on all materials including all operational ,incidental and labour charges such as machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work,but including centering,shuttering ,complete as per S.S and as directed by the departmental officer incharge of work as follows
Raft 0.10m thick
For side walls 0.20m thick 4x1.40=5.60
for cover slabs 0.15 m thick
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, complete for finished item of work in all floors.( APSS No.126) for pre cast slabs of valve chambers
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH Note : Classifications of Earth Work Specification are as per 302.2.1(a) of MORD and 301.2.1 of MORT&H--ordinary soil--manual means upto 3m depth manual means
Filling with Sand in Valve chamber bedding This rate including cost of Sand,all labour charges,watering,ramming,and other incidental charges etc as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH etc.,complete as per S.S and as directed by the departmental officer incharge of work
Providing PCC 1:4:8 using 40 mm graded SS 5 HBG m/c metal and OPC coarse and fine aggregate confirming to IS 383 including cost and conveyance of all materials and labour charges, machine mixing , vibration,laying in position, curing etc., complete
RCC M-20 Nominal mix (cement,fine aggregate,coarse aggregate) corresponding to Table -9 of IS -456 using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including seigniorage charges on all materials including all operational ,incidental and labour charges such as machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work,but including centering,shuttering ,complete as per S.S and as directed by the departmental officer incharge of work as follows
Raft 0.10m thick
For side walls 0.20m thick 4x1.40=5.6
for cover slabs 0.15m thick
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying including sales and other taxes on all materials etc., complete for finished item of work in all floors.( APSS No.126) for pre cast slabs of valve chambers
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH Note : Classifications of Earth Work Specification are as per 302.2.1(a) of MORD and 301.2.1 of MORT&H--ordinary soil--manual means upto 3m depth manual means
Filling with Sand in Valve chamber bedding This rate including cost of Sand,all labour charges,watering,ramming,and other incidental charges etc as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH etc.,complete as per S.S and as directed by the departmental officer incharge of work
Providing PCC 1:4:8 using 40 mm graded SS 5 HBG m/c metal and OPC coarse and fine aggregate confirming to IS 383 including cost and conveyance of all materials and labour charges, machine mixing , vibration,laying in position, curing etc., complete
RCC M-20 Nominal mix (cement,fine aggregate,coarse aggregate) corresponding to Table -9 of IS -456 using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including seigniorage charges on all materials including all operational ,incidental and labour charges such as machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work,but including centering,shuttering ,complete as per S.S and as directed by the departmental officer incharge of work as follows
Raft 0.10m thick
For side walls 0.20m thick 4x1.40=5.6
for cover slabs 0.15m thick
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying including all materials etc., complete for finished item of work in all floors.( APSS No.126) for pre cast slabs of valve chambers
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH Note : Classifications of Earth Work Specification are as per 302.2.1(a) of MORD and 301.2.1 of MORT&H--ordinary soil--manual means upto 3m depth manual means
Filling with Sand in Valve chamber bedding This rate including cost of Sand,all labour charges,watering,ramming,and other incidental charges etc as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH etc.,complete as per S.S and as directed by the departmental officer incharge of work
Providing PCC 1:4:8 using 40 mm graded SS 5 HBG m/c metal and OPC coarse and fine aggregate confirming to IS 383 including cost and conveyance of all materials and labour charges, machine mixing , vibration,laying in position, curing etc., complete
RCC M-20 Nominal mix (cement,fine aggregate,coarse aggregate) corresponding to Table -9 of IS -456 using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including seigniorage charges on all materials including all operational ,incidental and labour charges such as machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work,but including centering,shuttering ,complete as per S.S and as directed by the departmental officer incharge of work as follows
Raft 0.10m thick
For side walls 0.20m thick 4x1.40=5.60
for cover slabs 0.15 m thick
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying ., complete for finished item of work in all floors.( APSS No.126) for pre cast slabs of valve chambers
Construction of Air Valve Chamber as per type design drawing with CC including, plastering, RCC cover slabs etc. including cost and conveyance of all material and all labour charges etc. complete as per S.S for finished item of work Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH Note : Classifications of Earth Work Specification are as per 302.2.1(a) of MORD and 301.2.1 of MORT&H--ordinary soil--manual means upto 3m depth manual means
Filling with Sand in Valve chamber bedding This rate including cost of Sand,all labour charges,watering,ramming,and other incidental charges etc as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH etc.,complete as per S.S and as directed by the departmental officer incharge of work
Providing PCC 1:4:8 using 40 mm graded SS 5 HBG m/c metal and OPC coarse and fine aggregate confirming to IS 383 including cost and conveyance of all materials and labour charges, machine mixing , vibration,laying in position, curing etc., complete
RCC M-20 Nominal mix (cement,fine aggregate,coarse aggregate) corresponding to Table -9 of IS -456 using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including seigniorage charges on all materials including all operational ,incidental and labour charges such as machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work,but including centering,shuttering ,complete as per S.S and as directed by the departmental officer incharge of work as follows
Raft 0.10m thick
For side walls 0.20m thick 4x1.40=5.6
for cover slabs 0.15m thick
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, complete for finished item of work in all floors.( APSS No.126) for pre cast slabs of valve chambers
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH Note : Classifications of Earth Work Specification are as per 302.2.1(a) of MORD and 301.2.1 of MORT&H--ordinary soil--manual means upto 3m depth manual means
Filling with Sand in Valve chamber bedding This rate including cost of Sand,all labour charges,watering,ramming,and other incidental charges etc as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH etc.,complete as per S.S and as directed by the departmental officer incharge of work
Providing PCC 1:4:8 using 40 mm graded SS 5 HBG m/c metal and OPC coarse and fine aggregate confirming to IS 383 including cost and conveyance of all materials and labour charges, machine mixing , vibration,laying in position, curing etc., complete
RCC M-20 Nominal mix (cement,fine aggregate,coarse aggregate) corresponding to Table -9 of IS -456 using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including seigniorage charges on all materials including all operational ,incidental and labour charges such as machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work,but including centering,shuttering ,complete as per S.S and as directed by the departmental officer incharge of work as follows
Raft 0.10m thick
For side walls 0.20m thick 4x1.40=5.6
for cover slabs 0.15m thick
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, , complete for finished item of work in all floors.( APSS No.126) for pre cast slabs of valve chambers
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH Note : Classifications of Earth Work Specification are as per 302.2.1(a) of MORD and 301.2.1 of MORT&H--ordinary soil--manual means upto 3m depth manual means
Filling with Sand in Valve chamber bedding This rate including cost of Sand,all labour charges,watering,ramming,and other incidental charges etc as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH etc.,complete as per S.S and as directed by the departmental officer incharge of work
Providing PCC 1:4:8 using 40 mm graded SS 5 HBG m/c metal and OPC coarse and fine aggregate confirming to IS 383 including cost and conveyance of all materials and labour charges, machine mixing , vibration,laying in position, curing etc., complete
RCC M-20 Nominal mix (cement,fine aggregate,coarse aggregate) corresponding to Table -9 of IS -456 using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including seigniorage charges on all materials including all operational ,incidental and labour charges such as machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work,but including centering,shuttering ,complete as per S.S and as directed by the departmental officer incharge of work as follows
Raft 0.10m thick
For side walls 0.20m thick 4x1.40=5.60
for cover slabs 0.15 m thick
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, , complete for finished item of work in all floors.( APSS No.126) for pre cast slabs of valve chambers
Lowering the C.I. Pipes, D.I. Pipes of all classes and fittings with flanged ends carefully into the trenches and laying them true to alignment and gradient including all sundries, as per BIS No.3114/94.complete as per ss and as direceted by the departmental officer incharge of work
150 mm dia
200 mm dia
250 mm dia
Jointing the C.I. Pipes, fittings and valves with flanged ends including cost of jointing materials such as bolts, nuts, rubber insertion, white lead and including filling with water with a water lead upto 500 m and testing to required pressure etc., complete as per ss and as direceted by the departmental officer incharge of work BIS No.3114/85.
100 mm dia
150 mm dia
200 mm dia
250 mm dia
Cutting of existing B.T.road surface for pipe line trench (aswell as asphalt concrete up to 75mm thick) including water bound macadam including all labour charges for cutting, stacking this rate including hiring of machinary,fuel charges,wages of driver, complete as per the directions of departmental authorities. complete as per the directions of departmental authorities.
Cutting and open of C.C. Road surface for pipe line trenches including stacking of excavated materials for lying of pipe lines,this rate including hiring of machinary,fuel charges,wages of driver, complete as per the directions of departmental authorities.
Cutting and open of Water bound macadam surface for pipe line trenches including stacking of excavated materials for lying of pipe lines,this rate including hiring of machinary,fuel charges,wages of driver, complete as per the directions of departmental authorities.
Filling with Crusher Stone dust in valve chambers sand bedding. This rate including cost of Dust,all labour charges,watering,ramming,and other incidental charges etc as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH etc.,complete as per S.S and as directed by the departmental officer incharge of work
Restoration of CC Road by Using Concrete mixture Plain Cement concrete nominal mix M-30 (Cement : fine aggregate: coarse aggregate ) using 20mm size Hard Granite Machine Crushed Graded Metal including cost and conveyance of all materials like cement, sand, coarse aggregate water etc., to site , seigniorage charges on all materials, labour charges , for mixing , laying, concrete , ramming in 15 cm layers, finishing top surface to the required level curing etc., complete for finished item of work with nomonal reinforcement for Road restoration.
Laying new Distribution lines zone-III
Earth work excavation in all soils up to SDR & stone matrix by machinery for Pipe lines as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and back filling in trenches with excavated suitable material as per Technical Specification No.305 MORD/304 MORTH up to initial lift of 3.0m. For Pipe line trenches.
Machenical mans 70%
Manual means 20%
Filling with Sand in pipe line bedding This rate including cost of Sand,all labour charges,watering,ramming,and other incidental charges etc as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH etc.,complete as per S.S and as directed by the departmental officer incharge of work
Manufacture, supply and delivery of PE 100-PN 6 HDPE pipes confirming to IS 4984-1995 including transportation to work spot, stacking including all taxes etc. complete as per S.S and as directed by the departmental officer incharge of work
110mm dia.
160mm dia.
200mm dia.
250mm dia.
Manufacture, supply, & delivery of HDPE fittings conforming to IS 4984 - 1995 including transportation to work spot, stacking excluding all taxes and duties etc.complete as per S.S and as directed by the departmental officer incharge of work
a) Pipe ends - long neck
110mm dia.
110 mm dia for Air TEEs
160mm dia.
160 mm dia for Air TEEs
200mm dia.
200 mm dia for Air TEEs
250mm dia.
250 mm dia for Air TEEs
b) MS Flanges
110mm dia.
110 mm dia for Air TEEs
160mm dia.
160 mm dia for Air TEEs
200mm dia.
200 mm dia for Air TEEs
250mm dia.
250 mm dia for Air TEEs
c) End Caps
160mm dia.
200mm dia.
250mm dia.
d) Reducers
110X125 mm dia
125x140 mm dia
140x160 mm dia
160x180 mm dia
180x200 mm dia
e) TEES
160mm dia.
200mm dia.
250mm dia.
F)Bends
160mm dia.
200mm dia.
250mm dia.
Lowering, laying and jointing of HDPE pipes and jointing by butt fusion welding as per IS 7634-part-II/1975 as amended from time to time to the alignment and gradient and testing the pipeline to required pressure etc.complete as per S.S and as directed by the departmental officer incharge of work
110mm dia.
160mm dia.
200mm dia.
250mm dia.
Supply and delivery of DI Pipes and fittings (Specials) confirming to specification No.I.S.No. 7181/1986, 5531/1988, 3950/1979 including VAT and other duties including transportation and conveyance to work spot and stacking etc., complete as per S.S and as directed by the departmental authorities.
100X2.00m on 110 and 160 mm dia mains for scours
100x1.00m long DF pipes for sluice valves
150 mm dia x2.00m on 200 and 250 mm dia pipes for scours
150x1.00m long DF pipes for sluice valves
200 mm dia x2.00m on 315 and 355 mm dia pipes for scours
200x1.00m long DF pipes for sluice valves
250x1.00m long DF pipes for sluice valves
100 mm dia deck foot bends
100x100x80 mm DIDF TEE for air valves
supply and delivery of "Resilient Seated Soft Sealing" Gate Valves (Sluice Valves) with Body and Bonnet of Ductile Iron GGG-40/SG-400/15 or GGG-50/SG-500/7 or Equivalent as per IS1865, IS:3896-2 and Wedge fully Rubber Lined with food grade quality grade W270 grade EPDM, Replaceable Spindle Nut without gland packing with 3-O ring protection system on the Shaft and Seals of NBR. The Valves should be Vacuum tight and 100% leak proof with face to face dimensions as BS:5163 Type A/IS:14846. All the valves should be with fusion bonded Electrostatic Powder coating both inside and outside (Min 250 Microns)- RAL 5005 with Pocket Less Straight through body Passage conforming to Design standards of DIN-3202F4/BS:5163 Type A Flange drilling as per IS - 1538 and including transportation. PN1.6 -
100 mm distrubution
150mm dia for distrubution
200mm dia for distrubution
250mm dia for distrubution
for scour
100mm dia on 110 mm and 160 mm dia mains
150 mm dia on 200 and 250 mm dia lines
200 mm dia on 315 and 355 mm lines
Manufacture, supply and delivery of Single Chamber DI Air Valve with Body and cover in Ductile Iron of grade SG 400/12 or equivalent grade as per I.S.3896-part2-1985 and subsequent revisions. All internal parts such as float, shell etc., all cover bolts, of stainless steel, and Gaskets and seals of EPDM food grade quality Epoxy powder coating (EP-P) inside and outside colour blue. Drilled as per IS:1538. PN16
80 mm dia on 110 mm pipe
80 mm dia on 160 mm pipe
80mm dia 200 mm pipe
80mm dia 250 mm pipe
Labour charges for lowering and keeping in position of D.I. Sluice valves, reflux valves and scour valves.
100 mm distrubution
150mm dia for distrubution
200mm dia for distrubution
250mm dia for distrubution
for scour
100mm dia on 110 mm and 160 mm dia mains
150 mm dia on 200 and 250 mm dia lines
200 mm dia on 315 and 355 mm lines
Construction of sluice and scour Valve Chamber as per type design drawing with CC including, plastering, RCC cover slabs etc. including cost and conveyance of all material and all labour charges etc. complete as per S.S for finished item of work Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH Note : Classifications of Earth Work Specification are as per 302.2.1(a) of MORD and 301.2.1 of MORT&H--ordinary soil--manual means upto 3m depth manual means
Filling with Sand in Valve chamber bedding This rate including cost of Sand,all labour charges,watering,ramming,and other incidental charges etc as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH etc.,complete as per S.S and as directed by the departmental officer incharge of work
Providing PCC 1:4:8 using 40 mm graded SS 5 HBG m/c metal and OPC coarse and fine aggregate confirming to IS 383 including cost and conveyance of all materials and labour charges, machine mixing , vibration,laying in position, curing etc., complete
RCC M-20 Nominal mix (cement,fine aggregate,coarse aggregate) corresponding to Table -9 of IS -456 using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including seigniorage charges on all materials including all operational ,incidental and labour charges such as machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work,but including centering,shuttering ,complete as per S.S and as directed by the departmental officer incharge of work as follows
Raft 0.10m thick
For side walls 0.20m thick 4x1.40=5.6
for cover slabs 0.15m thick
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, complete for finished item of work in all floors.( APSS No.126) for pre cast slabs of valve chambers
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH Note : Classifications of Earth Work Specification are as per 302.2.1(a) of MORD and 301.2.1 of MORT&H--ordinary soil--manual means upto 3m depth manual means
Filling with Sand in Valve chamber bedding This rate including cost of Sand,all labour charges,watering,ramming,and other incidental charges etc as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH etc.,complete as per S.S and as directed by the departmental officer incharge of work
Providing PCC 1:4:8 using 40 mm graded SS 5 HBG m/c metal and OPC coarse and fine aggregate confirming to IS 383 including cost and conveyance of all materials and labour charges, machine mixing , vibration,laying in position, curing etc.,,complete as per S.S and as directed by the departmental officer incharge of work
RCC M-20 Nominal mix (cement,fine aggregate,coarse aggregate) corresponding to Table -9 of IS -456 using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including seigniorage charges on all materials including all operational ,incidental and labour charges such as machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work,but including centering,shuttering ,complete as per S.S and as directed by the departmental officer incharge of work as follows
Raft 0.10m thick
For side walls 0.20m thick 4x1.40=5.6
for cover slabs 0.15m thick
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position,, complete for finished item of work in all floors.( APSS No.126) for pre cast slabs of valve chambers
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH Note : Classifications of Earth Work Specification are as per 302.2.1(a) of MORD and 301.2.1 of MORT&H--ordinary soil--manual means upto 3m depth manual means
Filling with Sand in Valve chamber bedding This rate including cost of Sand,all labour charges,watering,ramming,and other incidental charges etc as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH etc.,complete as per S.S and as directed by the departmental officer incharge of work
Providing PCC 1:4:8 using 40 mm graded SS 5 HBG m/c metal and OPC coarse and fine aggregate confirming to IS 383 including cost and conveyance of all materials and labour charges, machine mixing , vibration,laying in position, curing etc., complete
RCC (M20) Nominal Mix using 20mm metal using concrete mixer for sluice/scour/Air val chambers
Raft 0.10m thick
For side walls 0.20m thick 4x1.40=5.60
RCC M-20 Nominal mix (cement,fine aggregate,coarse aggregate) corresponding to Table -9 of IS -456 using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including seigniorage charges ,sales and other taxes on all materials including all operational ,incidental and labour charges such as machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work,but including centering,shuttering for cover slabs
for cover slabs 0.15 m thick
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying including sales and other taxes on all materials etc., complete for finished item of work in all floors.( APSS No.126) for pre cast slabs of valve chambers
250mm dia for distrubution
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH Note : Classifications of Earth Work Specification are as per 302.2.1(a) of MORD and 301.2.1 of MORT&H--ordinary soil--manual means upto 3m depth manual means
Filling with Sand in Valve chamber bedding This rate including cost of Sand,all labour charges,watering,ramming,and other incidental charges etc as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH etc.,complete as per S.S and as directed by the departmental officer incharge of work
Providing PCC 1:4:8 using 40 mm graded SS 5 HBG m/c metal and OPC coarse and fine aggregate confirming to IS 383 including cost and conveyance of all materials and labour charges, machine mixing , vibration,laying in position, curing etc., complete
RCC M-20 Nominal mix (cement,fine aggregate,coarse aggregate) corresponding to Table -9 of IS -456 using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including seigniorage charges on all materials including all operational ,incidental and labour charges such as machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work,but including centering,shuttering ,complete as per S.S and as directed by the departmental officer incharge of work as follows
Raft 0.10m thick
For side walls 0.20m thick 4x1.40=5.60
for cover slabs 0.15 m thick
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position,., complete for finished item of work in all floors.( APSS No.126) for pre cast slabs of valve chambers
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH Note : Classifications of Earth Work Specification are as per 302.2.1(a) of MORD and 301.2.1 of MORT&H--ordinary soil--manual means upto 3m depth manual means
Filling with sand in foundations /pipe line trenches as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH
Providing PCC 1:4:8 using 40 mm graded SS 5 HBG m/c metal and OPC coarse and fine aggregate confirming to IS 383 including cost and conveyance of all materials and labour charges, machine mixing , vibration,laying in position, curing etc., complete
RCC (M20) Nominal Mix using 20mm metal using concrete mixer for sluice/scour/Air val chambers
Raft 0.10m thick
For side walls 0.20m thick 4x1.40=5.6
RCC M-20 Nominal mix (cement,fine aggregate,coarse aggregate) corresponding to Table -9 of IS -456 using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including seigniorage charges ,sales and other taxes on all materials including all operational ,incidental and labour charges such as machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work,but including centering,shuttering for cover slabs
for cover slabs 0.15m thick
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying including sales and other taxes on all materials etc., complete for finished item of work in all floors.( APSS No.126) for pre cast slabs of valve chambers
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH Note : Classifications of Earth Work Specification are as per 302.2.1(a) of MORD and 301.2.1 of MORT&H--ordinary soil--manual means upto 3m depth manual means
Filling with Sand in Valve chamber bedding This rate including cost of Sand,all labour charges,watering,ramming,and other incidental charges etc as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH etc.,complete as per S.S and as directed by the departmental officer incharge of work
Providing PCC 1:4:8 using 40 mm graded SS 5 HBG m/c metal and OPC coarse and fine aggregate confirming to IS 383 including cost and conveyance of all materials and labour charges, machine mixing , vibration,laying in position, curing etc., complete
RCC M-20 Nominal mix (cement,fine aggregate,coarse aggregate) corresponding to Table -9 of IS -456 using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including seigniorage charges ,sales and other taxes on all materials including all operational ,incidental and labour charges such as machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work,but including centering,shuttering for cover slabs
Raft 0.10m thick
For side walls 0.20m thick 4x1.40=5.6
for cover slabs 0.15m thick
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tcomplete for finished item of work in all floors.( APSS No.126) for pre cast slabs of valve chambers
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH Note : Classifications of Earth Work Specification are as per 302.2.1(a) of MORD and 301.2.1 of MORT&H--ordinary soil--manual means upto 3m depth manual means
Filling with Sand in Valve chamber bedding This rate including cost of Sand,all labour charges,watering,ramming,and other incidental charges etc as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH etc.,complete as per S.S and as directed by the departmental officer incharge of work
Providing PCC 1:4:8 using 40 mm graded SS 5 HBG m/c metal and OPC coarse and fine aggregate confirming to IS 383 including cost and conveyance of all materials and labour charges, machine mixing , vibration,laying in position, curing etc., complete
RCC M-20 Nominal mix (cement,fine aggregate,coarse aggregate) corresponding to Table -9 of IS -456 using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including seigniorage charges ,sales and other taxes on all materials including all operational ,incidental and labour charges such as machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work,but including centering,shuttering for cover slabs
Raft 0.10m thick
For side walls 0.20m thick 4x1.40=5.60
for cover slabs 0.15 m thick
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, , complete for finished item of work in all floors.( APSS No.126) for pre cast slabs of valve chambers
Construction of Air Valve Chamber as per type design drawing with CC including, plastering, RCC cover slabs etc. including cost and conveyance of all material and all labour charges etc. complete as per S.S for finished item of work Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH Note : Classifications of Earth Work Specification are as per 302.2.1(a) of MORD and 301.2.1 of MORT&H--ordinary soil--manual means upto 3m depth manual means
Filling with Sand in Valve chamber bedding This rate including cost of Sand,all labour charges,watering,ramming,and other incidental charges etc as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH etc.,complete as per S.S and as directed by the departmental officer incharge of work
Providing PCC 1:4:8 using 40 mm graded SS 5 HBG m/c metal and OPC coarse and fine aggregate confirming to IS 383 including cost and conveyance of all materials and labour charges, machine mixing , vibration,laying in position, curing etc., complete
RCC M-20 Nominal mix (cement,fine aggregate,coarse aggregate) corresponding to Table -9 of IS -456 using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including seigniorage charges ,sales and other taxes on all materials including all operational ,incidental and labour charges such as machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work,but including centering,shuttering for cover slabs
For side walls 0.20m thick 4x1.40=5.6
For side walls 0.20m thick 4x1.40=5.6
for cover slabs 0.15m thick
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, ., complete for finished item of work in all floors.( APSS No.126) for pre cast slabs of valve chambers
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH Note : Classifications of Earth Work Specification are as per 302.2.1(a) of MORD and 301.2.1 of MORT&H--ordinary soil--manual means upto 3m depth manual means
Filling with Sand in Valve chamber bedding This rate including cost of Sand,all labour charges,watering,ramming,and other incidental charges etc as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH etc.,complete as per S.S and as directed by the departmental officer incharge of work
Providing PCC 1:4:8 using 40 mm graded SS 5 HBG m/c metal and OPC coarse and fine aggregate confirming to IS 383 including cost and conveyance of all materials and labour charges, machine mixing , vibration,laying in position, curing etc., complete
RCC M-20 Nominal mix (cement,fine aggregate,coarse aggregate) corresponding to Table -9 of IS -456 using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including seigniorage charges ,sales and other taxes on all materials including all operational ,incidental and labour charges such as machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work,but including centering,shuttering for cover slabs
Raft 0.10m thick
For side walls 0.20m thick 4x1.40=5.6
for cover slabs 0.15m thick
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, complete for finished item of work in all floors.( APSS No.126) for pre cast slabs of valve chambers
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH Note : Classifications of Earth Work Specification are as per 302.2.1(a) of MORD and 301.2.1 of MORT&H--ordinary soil--manual means upto 3m depth manual means
Filling with Sand in Valve chamber bedding This rate including cost of Sand,all labour charges,watering,ramming,and other incidental charges etc as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH etc.,complete as per S.S and as directed by the departmental officer incharge of work
Providing PCC 1:4:8 using 40 mm graded SS 5 HBG m/c metal and OPC coarse and fine aggregate confirming to IS 383 including cost and conveyance of all materials and labour charges, machine mixing , vibration,laying in position, curing etc., complete
RCC M-20 Nominal mix (cement,fine aggregate,coarse aggregate) corresponding to Table -9 of IS -456 using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including seigniorage charges ,sales and other taxes on all materials including all operational ,incidental and labour charges such as machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work,but including centering,shuttering for cover slabs
Raft 0.10m thick
For side walls 0.20m thick 4x1.40=5.60
for cover slabs 0.15 m thick
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, complete for finished item of work in all floors.( APSS No.126) for pre cast slabs of valve chambers
Lowering the C.I. Pipes, D.I. Pipes of all classes and fittings with flanged ends carefully into the trenches and laying them true to alignment and gradient including all sundries, as per BIS No.3114/94.complete as per ss and as direceted by the departmental officer incharge of work
150 mm dia
200 mm dia
250 mm dia
Jointing the C.I. Pipes, fittings and valves with flanged ends including cost of jointing materials such as bolts, nuts, rubber insertion, white lead and including filling with water with a water lead upto 500 m and testing to required pressure etc., BIS No.3114/85.complete as per ss and as direceted by the departmental officer incharge of work
100 mm dia
150 mm dia
200 mm dia
250 mm dia
Cutting and open of C.C. Road surface for pipe line trenches including stacking of excavated materials for lying of pipe lines,this rate including hiring of machinary,fuel charges,wages of driver, complete as per the directions of departmental authorities.
Cutting and open of Water bound macadam surface for pipe line trenches including stacking of excavated materials for lying of pipe lines,this rate including hiring of machinary,fuel charges,wages of driver, complete as per the directions of departmental authorities.
Filling with Crusher Stone dust in valve chambers sand bedding. This rate including cost of Dust,all labour charges,watering,ramming,and other incidental charges etc as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH etc.,complete as per S.S and as directed by the departmental officer incharge of work
Restoration of CC Road by Using Concrete mixture Plain Cement concrete nominal mix M-30 (Cement : fine aggregate: coarse aggregate ) using 20mm size Hard Granite Machine Crushed Graded Metal including cost and conveyance of all materials like cement, sand, coarse aggregate water etc., to site , seigniorage charges on all materials, labour charges , for mixing , laying, concrete , ramming in 15 cm layers, finishing top surface to the required level curing etc., complete for finished item of work with nomonal reinforcement for Road restoration.
Construction of un-reinforced, plain cement concrete pavement, thickness as per design, over a prepared sub base, with 43 grade cement or any other type as per Clause 1501.2.2 M30 (Grade), coarse and fine aggregates conforming to IS : 383, maximum in a concrete mixer of not less than 0.2 cum capacity and appropeiate weigh batcher using approved mix design, laid in approved fixed side formwork (steel channel, wedges, steel plates including levelling the formwork as per drawing), spreading the concrete with sholvels, rakes, compacted using needle, scareed and plate vibrators and finished in continuous operation including provision of contraction and expansion, construction joints, applying debonding strips, primer, sealant, dowel bars, near approaches to bridge / culvert and construction joints, admixtures as approved, curing of concrete slabs for 14- days, curing compound (where specified) and water finishing to lines and grade as per drawing and Technical Specification Clause 1501 MORD. for Road restoration.
Providing house service connections on HDPE mains at House hold side in Earthen Roads with Earthwork Excavation in all type of soils fixing PP Saddle,PP Clamp Saddle shall be manufactured by injection moulding using virigin Polypropylene,Mechanical tapping saddles for water works purposes and designed for use with PVC/PE pipe as per IS 4985/IS 4984 respectively. These saddles should be contoured to fit around the pipe. PP saddles shall be Blue/Black moulded-in with Nickel plated Brass / SS 304 metal female threaded outlets. Seal shall be thermoplastic elastomer rubber suitable for drinking water and nut-bolt-washer with SS. The PP Clamp saddle fittings shall be mouldedwith SS 304/Nickel plated Brass female threaded outlet inserted to connect necessary fittings. Thread dimension shall conform to IS-554/ISO-7. Adequate thickness of PP shall be provided to hold brass insert in place and avoid leakage while pressure applications. Fasteners shall be threaded type, with SS. Fasteners of size 125mm and above. The grade of raw material used must be certified by WRAS, UK for type test as per BS 6920 from their certified laboratories like NSF International Ltd. UK and certificate of Compliance to be produced for the following parameters: i) Odour&Flavour of water ii) Appearance of water iii) Growth of Micro Organismaxes etc,FOR main pipes Hdpe /PVC of 110mm dia .flow control valve SS 316 NRV 10 LPM ,Compression adaptor with one side compression end to suit 1/2 "to1''(15mmOD to25 mm OD) MDPE pipe and other side with female threaded with SS-304 material inserts of sizes 1/2" BSP threads,body,nut, and cap of poly propylene,clip ring PP Compression Metal insert female Threaded Adaptorcompression adaptor with one side compression end to suit 1/2'' to 1'' mdpe pipe and other side with female thread with ss-304 material inserts of sizes 1/2'' BSP thread,PP compression elbow to suit 1/2 " to 1'' (15mm OD to 25 mm OD) MDPE pipe body, nuts, and caps of polypropelene, clip ring of POM(Acetylic resin) and and "O" ring of NBR material,as per ISO 14236 standardsDouble compression elbow to suit 20mm OD for 100mm, MDPE PE80 Blue pipe as per ISO 4427 up to date 1. for conveyance of potable water ,MDPE 20mm OD pipe (2.00 m avg length for each of 1/2'' HSC) of SDR 9-PN-16 for pipes side,Premium make UPVC Pipes with Fittings.(IS 4985/2000)(PH SSR :20) UPVC pipe for 40 mm (Casing for drain crossing)fixing of 12.7 mm brass bib cock indian make heavy duty long bodyFixing of House service connections,including fixing of ferrule, MDPE/GI pipes and specials and connecting newly laid pipe (For HDPE / PVC Pipes)Making Holes upto 18 mm Dia in RCC/any Stones up to 50 mm Thick( BMS-W78)Fixing of 25.4 mm Holder Back Clamps at Drain Crossing this rate cost of above all materials ,Including all Labour Charges ,other incidental charges etc for finished item of work and as directed by the departmental officer in charge of work
Providing house service connections on HDPE mains at other side in Earthen Roads with Earthwork Excavation in all type of soils fixing PP Saddle,PP Clamp Saddle shall be manufactured by injection moulding using virigin Polypropylene,Mechanical tapping saddles for water works purposes and designed for use with PVC/PE pipe as per IS 4985/IS 4984 respectively. These saddles should be contoured to fit around the pipe. PP saddles shall be Blue/Black moulded-in with Nickel plated Brass / SS 304 metal female threaded outlets. Seal shall be thermoplastic elastomer rubber suitable for drinking water and nut-bolt-washer with SS. The PP Clamp saddle fittings shall be mouldedwith SS 304/Nickel plated Brass female threaded outlet inserted to connect necessary fittings. Thread dimension shall conform to IS-554/ISO-7. Adequate thickness of PP shall be provided to hold brass insert in place and avoid leakage while pressure applications. Fasteners shall be threaded type, with SS. Fasteners of size 125mm and above. The grade of raw material used must be certified by WRAS, UK for type test as per BS 6920 from their certified laboratories like NSF International Ltd. UK and certificate of Compliance to be produced for the following parameters: i) Odour&Flavour of water ii) Appearance of water iii) Growth of Micro Organismaxes etc,FOR main pipes Hdpe /PVC of 110mm dia .flow control valve SS 316 NRV 10 LPM ,Compression adaptor with one side compression end to suit 1/2 "to1''(15mmOD to25 mm OD) MDPE pipe and other side with female threaded with SS-304 material inserts of sizes 1/2" BSP threads,body,nut, and cap of poly propylene,clip ring PP Compression Metal insert female Threaded Adaptorcompression adaptor with one side compression end to suit 1/2'' to 1'' mdpe pipe and other side with female thread with ss-304 material inserts of sizes 1/2'' BSP thread,PP compression elbow to suit 1/2 " to 1'' (15mm OD to 25 mm OD) MDPE pipe body, nuts, and caps of polypropelene, clip ring of POM(Acetylic resin) and and "O" ring of NBR material,as per ISO 14236 standardsDouble compression elbow to suit 20mm OD for 100mm, MDPE PE80 Blue pipe as per ISO 4427 up to date 1. for conveyance of potable water ,MDPE 20mm OD pipe (2.00 m avg length for each of 1/2'' HSC) of SDR 9-PN-16 for pipes side,Premium make UPVC Pipes with Fittings.(IS 4985/2000)(PH SSR :20) UPVC pipe for 40 mm (Casing for drain crossing)fixing of 12.7 mm brass bib cock indian make heavy duty long bodyFixing of House service connections,including fixing of ferrule, MDPE/GI pipes and specials and connecting newly laid pipe (For HDPE / PVC Pipes)Making Holes upto 18 mm Dia in RCC/any Stones up to 50 mm Thick( BMS-W78)Fixing of 25.4 mm Holder Back Clamps at Drain Crossing this rate cost of above all materials ,Including all Labour Charges ,other incidental charges etc for finished item of work and as directed by the departmental officer in charge of work
Providing house service connections on HDPE mains at other side in B.T & CC Roads with Earthwork Excavation in all type of soils fixing PP Saddle,PP Clamp Saddle shall be manufactured by injection moulding using virigin Polypropylene,Mechanical tapping saddles for water works purposes and designed for use with PVC/PE pipe as per IS 4985/IS 4984 respectively. These saddles should be contoured to fit around the pipe. PP saddles shall be Blue/Black moulded-in with Nickel plated Brass / SS 304 metal female threaded outlets. Seal shall be thermoplastic elastomer rubber suitable for drinking water and nut-bolt-washer with SS. The PP Clamp saddle fittings shall be mouldedwith SS 304/Nickel plated Brass female threaded outlet inserted to connect necessary fittings. Thread dimension shall conform to IS-554/ISO-7. Adequate thickness of PP shall be provided to hold brass insert in place and avoid leakage while pressure applications. Fasteners shall be threaded type, with SS. Fasteners of size 125mm and above. The grade of raw material used must be certified by WRAS, UK for type test as per BS 6920 from their certified laboratories like NSF International Ltd. UK and certificate of Compliance to be produced for the following parameters: i) Odour&Flavour of water ii) Appearance of water iii) Growth of Micro Organismaxes etc,FOR main pipes Hdpe /PVC of 110mm dia .flow control valve SS 316 NRV 10 LPM ,Compression adaptor with one side compression end to suit 1/2 "to1''(15mmOD to25 mm OD) MDPE pipe and other side with female threaded with SS-304 material inserts of sizes 1/2" BSP threads,body,nut, and cap of poly propylene,clip ring PP Compression Metal insert female Threaded Adaptorcompression adaptor with one side compression end to suit 1/2'' to 1'' mdpe pipe and other side with female thread with ss-304 material inserts of sizes 1/2'' BSP thread,PP compression elbow to suit 1/2 " to 1'' (15mm OD to 25 mm OD) MDPE pipe body, nuts, and caps of polypropelene, clip ring of POM(Acetylic resin) and and "O" ring of NBR material,as per ISO 14236 standardsDouble compression elbow to suit 20mm OD for 100mm, MDPE PE80 Blue pipe as per ISO 4427 up to date 1. for conveyance of potable water ,MDPE 20mm OD pipe (2.00 m avg length for each of 1/2'' HSC) of SDR 9-PN-16 for pipes side,Premium make UPVC Pipes with Fittings.(IS 4985/2000)(PH SSR :20) UPVC pipe for 40 mm (Casing for drain crossing)fixing of 12.7 mm brass bib cock indian make heavy duty long bodyFixing of House service connections,including fixing of ferrule, MDPE/GI pipes and specials and connecting newly laid pipe (For HDPE / PVC Pipes)Making Holes upto 18 mm Dia in RCC/any Stones up to 50 mm Thick( BMS-W78)Fixing of 25.4 mm Holder Back Clamps at Drain Crossing this rate cost of above all materials ,Including all Labour Charges ,other incidental charges etc for finished item of work and as directed by the departmental officer in charge of work
Providing house service connections on HDPE mains at House hold side in B.T & CC Roads with Earthwork Excavation in all type of soils fixing PP Saddle,PP Clamp Saddle shall be manufactured by injection moulding using virigin Polypropylene,Mechanical tapping saddles for water works purposes and designed for use with PVC/PE pipe as per IS 4985/IS 4984 respectively. These saddles should be contoured to fit around the pipe. PP saddles shall be Blue/Black moulded-in with Nickel plated Brass / SS 304 metal female threaded outlets. Seal shall be thermoplastic elastomer rubber suitable for drinking water and nut-bolt-washer with SS. The PP Clamp saddle fittings shall be mouldedwith SS 304/Nickel plated Brass female threaded outlet inserted to connect necessary fittings. Thread dimension shall conform to IS-554/ISO-7. Adequate thickness of PP shall be provided to hold brass insert in place and avoid leakage while pressure applications. Fasteners shall be threaded type, with SS. Fasteners of size 125mm and above. The grade of raw material used must be certified by WRAS, UK for type test as per BS 6920 from their certified laboratories like NSF International Ltd. UK and certificate of Compliance to be produced for the following parameters: i) Odour&Flavour of water ii) Appearance of water iii) Growth of Micro Organismaxes etc,FOR main pipes Hdpe /PVC of 110mm dia .flow control valve SS 316 NRV 10 LPM ,Compression adaptor with one side compression end to suit 1/2 "to1''(15mmOD to25 mm OD) MDPE pipe and other side with female threaded with SS-304 material inserts of sizes 1/2" BSP threads,body,nut, and cap of poly propylene,clip ring PP Compression Metal insert female Threaded Adaptorcompression adaptor with one side compression end to suit 1/2'' to 1'' mdpe pipe and other side with female thread with ss-304 material inserts of sizes 1/2'' BSP thread,PP compression elbow to suit 1/2 " to 1'' (15mm OD to 25 mm OD) MDPE pipe body, nuts, and caps of polypropelene, clip ring of POM(Acetylic resin) and and "O" ring of NBR material,as per ISO 14236 standardsDouble compression elbow to suit 20mm OD for 100mm, MDPE PE80 Blue pipe as per ISO 4427 up to date 1. for conveyance of potable water ,MDPE 20mm OD pipe (2.00 m avg length for each of 1/2'' HSC) of SDR 9-PN-16 for pipes side,Premium make UPVC Pipes with Fittings.(IS 4985/2000)(PH SSR :20) UPVC pipe for 40 mm (Casing for drain crossing)fixing of 12.7 mm brass bib cock indian make heavy duty long bodyFixing of House service connections,including fixing of ferrule, MDPE/GI pipes and specials and connecting newly laid pipe (For HDPE / PVC Pipes)Making Holes upto 18 mm Dia in RCC/any Stones up to 50 mm Thick( BMS-W78)Fixing of 25.4 mm Holder Back Clamps at Drain Crossing this rate cost of above all materials ,Including all Labour Charges ,other incidental charges etc for finished item of work and as directed by the departmental officer in charge of work
Implementation of Environmental Management plan
Air Quality Monitoring (5 Monitoring station) once in a month for three seasons during the construction period at SS Tank, sump/pumphouse, WTP, ELSR's, pipe line & Distribution network
Noise level (5 Monitoring station) once in a month for three seasons during the construction period at SS Tank, sump/pumphouse, WTP, ELSR's, pipe line & Distribution network
Water Quality Monitoring surface / ground(5 Monitoring station) once in a month for three seasons during the construction period at SS Tank, sump/pumphouse, WTP, ELSR's, pipe line & Distribution network
Air Quality Monitoring (5 Monitoring station) once in a month for three seasons during the construction period at SS Tank, sump/pumphouse, WTP, ELSR's, pipe line & Distribution network
Noise level (5 Monitoring station) once in a month for three seasons during the construction period at SS Tank, sump/pumphouse, WTP, ELSR's, pipe line & Distribution network
Water Quality Monitoring surface / ground(5 Monitoring station) once in a month for three seasons during the construction period at SS Tank, sump/pumphouse, WTP, ELSR's, pipe line & Distribution network
Compensatory plantation and three years maintenance (Compensatory afforestation ratio is 1:5) inlcuding plantation and Maintainance watering ,Trimming,Pesticides to maintain APCB Norms and as direceted by the departmental officer incharge of work
Greenbelt development and maintenance in the surroundings / Buffer zone
Providing Health checkups and free medical distribution centers for awareness health issues as per the APCB Norms and as direceted by the departmental officer incharge of work
Providing Awareness program/training centers including necessary Training kits,tents,pamplets necessary equipment as direceted by the departmental officer incharge of work
Sprinkling of water once in a day for two years (excluding rainy days): 400 days @ Rs.1000/trip
Hiring for 1 Nos. Vehicles for 24 Months during execution period including hire charges of vehicle, diesel, lubrication, driver charges, repairs ,General maintainance,services and all incidental charges etc., as per the departmental officer incharge of work
Providing Technical Graduate for co-ordinating the process of interconnections of the existing and proposed systems, preparation of documents related to inter departmental permissions and liaison with line departments to obtain permissions including preparation of build drawings as instructed by the Engineer in charge.
Providing the services such as consumer survey and mapping, asset mapping, ground validation, component wise structural and hydraulic designs as per site condition, GIS based hydraulic modelling of all components of both existing and proposed water supply infrastructure and any other documentation/ plan/ designs related to the whole scheme as per the instructions of the Engineer incharge and CPHEEO Manual as directed by the departmental officer incharge of work
Engaging of Man Mazdoor (Skilled / Semi Skilled) Like Electrician, pump Operator, Mechanic, Helpers, watch man, Filter bed operator, Diploma Engineer, Lab Technician, Technical work inspector etc, as per the requirment. The rate includes wages along with Municipal allowance, conveyancer charges for transporation to the work site including statutory provisions as per norms etc complete for sucessful by Maintainace of the entire scheme as directed by the departmental officer incharge of the work (for 10 years + 2 years Defect liablity period as follows
Personal required for operating Intake/Offtake well/Pump houses a)Operator
b)Fitter/Helper
c)Watch man
Personal required at operating Raw water rising mains
Operator
Personal required at operating Water treatment plants & Sump
Operator
Fitter/Helper
Lab Technician
Electrician /Mechanic
Watch man
Personal required at operating Clear water rising mains
Fitter/Helper
Personal required at operating Gravity mains
Watch man
Personal required at operating Service reservoirs
Watch man
Personal required at operating distribution system
Fitter/Helper
Repairs to pumpsets & Water pipe lines (2 years after execution period) complete as per ss and as directed by the departmental officer incharge of work
iv)Replacement of glands of sluice valves
v) Replacements of balls of Air valves
vi) Greease
vii) Gland Packing
Provision towards purchase pipe jointing materials, etc
LEAKAGES
Earth work Excavation,Bailing out water from Pipe Line Trench and replacement damaged DI Pipe for 2 M length including the Cost of Pipe Collar M/F Joint and refilling etc complete
315 mm HDPE Pipes
280 mm HDPE Pipes
250 mm HDPE Pipes
200 mm HDPE Pipes
160 mm HDPE Pipes
110 mm HDPE Pipes
I) ESTABLISHMENT :
Application Engineer (Graduate Engineer) Rate as per Labour Rates LAB-00130 of CSSR 2025-26
System Engineer (Diploma Engineer) Rate as per Labour Rates LAB-00130 of CSSR 2025-26
Sr. Service Engineer (Graduate Engineer ) Rate as per Labour Rates LAB-00130 of CSSR 2025-26
Data Operator Rate as per Labour Rates LAB-00134 of CSSR 2025-26
Office assistant Rate as per Labour Rates LAB-00124 of CSSR 2025-26
II) MAINTAINANCE OF LOCAL CONTROL STATION :
BSNL Charges for static IP
Data base management for WEB reporting
Charges for maintainance of PC's, Hardware consumables, Minor repair & Servers ,servomax Stabliser, UPS, maintainance of entire system including cost and convayance of all material and labor and attending minor repairs to instrumantation and automation equipment etc., complete
YELESWARAM NAGAR PANCHAYAT
Construction of 13.00m dia Intakewell cum pumphouse in Yeleru Reservoir
Well sinking for construction of internal 13.00m dia Intake well cum pump house by Manual or Machanical in sandy and other losse soils under water by using sinker and labour divers or dredgers, weighting the top and stening to assit sinker etc. This rate including cost of all labour charges, dewatering, hireing of machinery fuil charges, wages of driver, transporation of materials, machinery and other incidental charges etc complete as per SS and as directed by the departmental officers incharge of work for following depth
a) Up to 2.00mdepth from Side wall
b) 2.00m to 4.00m depth
c) 4.00m to 6.00m depth
d) 6.00m to 8.00m depth
e) 8.00m to 10.00m depth
f) 10.00m to 11.00m depth
g) 11.00m to 12.00 depth
h) 12.00m to 13.00mdepth
i) 13.00m to 14.00m depth
j) 14.00m to 15.00m depth
k) 15.00m to 16.00m depth
l) 16.00m to 17.00 m depth
l) 17.00m to 18.00 m depth
l) 18.00m to 19.00 m depth
l) 19.00m to 20.00 m depth
l) 20.00m to 21.00 m depth
Plain cement concrete (1:4:8) by using 40mm size hard machine crushed metal with concrete mixer mixing upto plinth level. This rates incluidng cost of materials transporation, machine mixing, vibrating charges, centerings, laying, concrete finishing other incidental charges delifting upto 22.00 mts etc complete as per SS and as directed by the departmental officers incidental charge for well botton plegging
Providing C.C.mix (M15 grade in open foundations from approved quarries including cost & conveyance of all materials, all labour charges delisting up to 22.00 m depth for machine mixing, laying, vibrating, tamping and curing including all delifts etc., complete as per S.S and as directed by the departmental authorities for well bottom plugging.
Providing VRCC M30 Grade Design Concrete Mix corresponding to IS 456 using WEIGH BATCHER / MIXER with 20mm size graded machine crushed hard granite metal (coarse aggregate) from approved quarry including cost and conveyance of all materials like cement, fine aggregate (sand) coarse aggregate, water etc., to site and including seignorage charges including all operational, incidental and labour charges such as weigh batching, machine mixing, laying concrete, curing with cement content 400Kgs/Cum as per I.S code from standard suppliers approved by the department including centering, shuttering, laying concrete, vibrating, curing etc. complete with all de-lift charges but excluding cost of steel and its fabrication charges for finished item of work (APSS No. 402) as follows.
for Well Curb 1.5m thick
Side Wall of the Well of 1.5 M thick upto HFL
Side Wall of the Well of 1.00M thick upto HFL
Providing VRCC M30 Grade Design Concrete Mix corresponding to IS 456 using WEIGH BATCHER / MIXER with 20mm size graded machine crushed hard granite metal (coarse aggregate) from approved quarry including cost and conveyance of all materials like cement, fine aggregate (sand) coarse aggregate, water etc., to site and including seignorage charges including all operational, incidental and labour charges such as weigh batching, machine mixing, laying concrete, curing with cement content 400Kgs/Cum as per I.S code from standard suppliers approved by the department including centering, shuttering, laying concrete, vibrating, curing etc. complete but excluding cost of steel and its fabrication charges for finished item of work (APSS No. 402) as follows
a) for Pump house Columns (8+3)
Centre Beams
c) for Roof Slab 0.20 m thick including 1.00m walk way
d) for Lintel Beams alround
e) for Roof Beams
f) for Roof slab 0.40m thick 0.45m extension
g) for Sunshade of 0.60mts wide and thickness of .075mts at fixed end and 0.05mts.at free end
Brick masonary in CM (1:6) using 2nd class bricks of size 23 x 11 x 7cms. Cost including cost and conveyance of all materials at site, labour charges for curing lifting, seaffolding charges, other incidental charge etc., complete as per S.S and as directed by the departmental officer incharge of work as follows.
for Super structure of Pump house
for Pump house Parapet wall
Supply and fixing of 40mm thick pre-cast Cement Jali of approved design including cost and conveyance to work spot and all labour charges for fixing in position etc.complete as per S.S and as directed by the departmental officer incharge of work
Plastering with CM (1:5) 12mm thick including cost and conveyance of all materials at site labour charges for finishing and curing etc., complete as per S.S for the Pump house as per S.S and as directed by the departmental officer incharge of work as follows
for Pump house inside
for Parapet wall
Providing impervious course with C.M (1:3) 20mm thick and mixing with acco proof compound of 1kg per one bag of cement including cost and conveyance of all materials and labour charges for finishing and curing etc., complete as per SS (APDSS NO:903) as directed by the departmental officer incharge of work
Plastering with CM (1:3) 12mm thick including cost and conveyance of all materials at site labour charges for finishing and curing seaffolding, lifting smooth finishing etc., complete and other incidental charge etc complete as directed by the departmental officer incharge of work.
Painting two coats with snowcem paint or equiled 1st quality of approved colour including cost of primary coat with white cement. The rate includes cost and conveyance of all materials at site, labour charges, scaffolding charges, other incidental charges etc., complete as directed by the departmental authorities for super structure walls.
Painting two coats with synthetic enamel paint over a base coat of red led. The rate includeds cost and conveyance of all materilas at site, labour charges, scaffolding charges etc., complete as directed by the departmental authorities (APDSS No:1201) for rolling slutter and winder
Supply & fixing of Rolling shutter made of 80 x 1.25 mm machine rolled CRCA laths, interlocked together through their entire length and jointed together at the ends by end-locks, mounted on specially designed pipe shaft of 50mm dia nominal bore MS B class pipe with brackets, plates, guide channels, stoppers, bottom locking plates and arrangements for inside & outside locking with push-pull operations including cost of hood cover and springs complete, painted with one coat of approved steel primer, locks, ball bearings, all accessories etc complete for finished item of work as per special spn: 1108 and as directed by the departmental officers incharge of work.
Supply and fixing Aluminium Anodised Two/ Three Track Sliding Windows as per approved drawing with aluminium anodised sections of Series C Jindal sections and outer frame top horizontals & both verticals of 8774 of size 62 x 29.5 mm and bottom horizontal - two track frame of 8773 of size 62 x 29.5 mm, Shutter frame top, bottom and verticals of 8304 of size 50 mm x 20 mm and Weather interlocking frame of 8306 of size 50 x 20 with plain clear float glass 5 mm thick fixed including supply and fixing aluminium handles of 100 mm for each shutter, nylon rollers assembly and all labour charges for fixing the fixtures with required no.of screws, bolts and nuts and including labour charges for fixing the frame in position, fixing shutter to frame etc. completed for finished item of work as per SS and as directed by the departmental officers incharge of work.
Supply, delivery, fabrication and erection of Cutting toe for Well curb with ISA 150x150x12mm including cost and conveyance to work spot including all labour charges for fabrication and erection etc.,complete as directed by the departmental authorities.
Supply, delivery and fabrication of HYSD Steel of various sizes including cutting, bending, tying of grills with binding wire, fabrication charges and placing grills in position including cost and conveyance of all materials including cost of binding wire delifting and all labour charge etc., complete as per S.S and directed by the departmental authorities incharges of work.
Supply and delivery of 350mm dia "Resilient Seated SoftSealing" Gate Valves (Sluice Valves) with Bodyand Bonnet of Ductile Iron GGG-40/SG-400/15or GGG-50/SG-500/7 or Equivalent as perIS1865, IS:3896-2 and Wedge fully Rubber Linedwith food grade quality grade W270 gradeEPDM, Replaceable Spindle Nut without gland packing with 3-O ring protection system on theShaft and Seals of NBR. The Valves should beVacuum tight and 100% leak proof with face toface dimensions as BS:5163 Type A/IS:14846. Allthe valves should be with fusion bondedElectrostatic Powder coating both inside andoutside (Min 250 Microns)- RAL 5005 with Pocket Less Straight through body Passageconforming to Design standards of DIN-3202F4/BS:5163 Type A Flange drilling as per IS- 1538 Drilled as per IS:1538. PN16 including cost of materials transportion charges other incidental charges etc complete as directed by the deaprtmental officer incharge of work.
Supply and delivery of 350mm dia. 2.0m. long centrifugally cast (spun) Ductile Iron pressure pipes with flanged (welded) ends of K-9 Class confirming to specification No.IS 8329/2000 of standard working lengths with cement lining inside the pipe, out side Zinc Coating including cost of Pipe, VAT and other duties. The rate including transportation and conveyance to work spot and stacking at site etc., complete as per S.S and as directed by the departmental authorities. incharge of work.
Supply and delivery of SS/C.I/M.S 12.00m. long operating handle with rod & wheel for operation of D.I. Sluice valve inside the intake well as per the actuals and as directed by the departmental authorities.
Supply, delivery and erection of 5 tonnes capacity double girder gantry arrangements to move and lift the installations of the pump house one way with required MS ISMB of best quality 250 x 100 mm of standard make, including the required MS ISMC, MS angular iron, 5 tonne capacity travelling trolley and 5 tonne capacity chain pulley block with chains of suitable capacity for lifting and moving arrangements to length of 10.00 m rate is inclusive of the cost of materials, labour charges, site welding etc.,complete as per ss and as direceted by the departmental officer incharge of work
Supply and delivery ss 304 grade operating Steel Ladder inside the intake well as per the actuals and this rate including cost of ss 304 , fabrication charges, erection at site of work cost of welding charges and other incidental charges etc., complete as per ss and as directed by the departmental officer in charge of work.
Providing electrification including fixures
Supply and fixing of 25 mm dia 2.00 mm thick PVC pipe concealed in roof slab with all required accessories including masonary work all labour chages other incidental charges as per IE Rules and as directed by the departmenal officers incharge of work.
Supply and fixing of 20 mm dia 1.50 mm thick PVC pipe concealed in walls with all required accessories including masonary work for light , fan and plug point with metal deep box including all labour charges other incidental charges as per IE Rules and as directed by the departmenal officers incharge of work
Wiring with 2 runs 14/0.3 mm. (1.0. sq.mm) Fire retardant PVC insulated Flexible copper cable in existing pipe with 6A siwtch, ceiling rose and 3 mm thick hyla sheet covering to switch control box including all labour charges etc,., complet for light, bell , fan and exhaust fan points in non - residential building other incidental charges as directed by the departmenal officers incharge of work
Wiring with 2 runs 14/0.3 mm. (1.0. sq.mm) Fire retardant PVC insulated Flexible copper cable in existing pipe with 6A modular siwtch control and 3/2 pin sockets fixing on board including all labour charges other incidental charges as per IE Rules and as directed by the departmenal officers incharge of work
supply and run of 2 of 36/0.3 mm. (1.5. sq.mm) Fire retardant PVC insulated Flexible copper cable in existing pipe for mains including all labour charges other incidental charges as per IE Rules and as directed by the departmenal officers incharge of work
supply and run of 1 of 14/0.3 mm. (1.0. sq.mm) Fire retardant PVC insulated Flexible copper cable in existing pipe for earth continuity including all labour charges etc. other incidental charges as per IE Rules and as directed by the departmenal officers incharge of work
supply and run of 2 of 6 sq.mm (7/18) WPSC alluminium cable along with No.10 SWG G.I barer wire through PVC cleats with all accessories including all labour charges etc., as per IE Rules and as directed by the departmenal officers incharge of work
Providing independent earthing by excavating a trench to a depth of 2.10m in all soils, as per size specied in data ,using 40 mm dia B class GI pipe 2.50m long with necessary accessories with hume pipe ring duly providing staggered holes including filling with equal proportion of salt and charcoal in layers and all labour charges etc complete as per IE Rules and as directed by the departmenal officers incharge of work
Supply and fixing SPN Distribution board with IP-20 protection suitable for single phase Earth Leakage Circute Braker (ELCB) / Residual Current Circute Braker (RCCB) / Double Pole (DP) Isolator as incomer and 10kA SP MCBs as out going including internal connections and labour charges for surface / flush mounting etc., complete. as per IE Rules and as directed by the departmenal officers incharge of work
Supply and fixing of 48" (1200mm) Sweep Ceiling Fan without Regulator.of makes Crompton High Speed / Bajaj Ultima / Havells Velocity / Usha Astra / Orient Summer Pride as per IE Rules and as directed by the departmenal officers incharge of work
Supply of stepped type Electronic Regulator of makes GM G Home / Gold Medal Olive / Million Zoom / Anchor Penta Cherry / Great white Omega as per IE Rules and as directed by the departmenal officers incharge of work
Supply of 9" (225mm), Light duty exhaust fan with double ball bearing and wire guard etc complete. Makes: Crompton / Bajaj Bahar WG / Havells Ventil Air-DS / Orient hill air / MIIT as per IE Rules and as directed by the departmenal officers incharge of work
Supply and transportation of 20W, 2000 lumens, T8,1200mm length LED retro tube light,wide operating voltage with double side connection, PF≥0.9,Surge protection: > 2KV, THD<15%, with inbuilt driver and frosted cover CCT: 3000K - 6500K as desired by the department and as per IS specifications, minimum CRI≥80,.etc complete with 5 years warranty. as per IE Rules and as directed by the departmenal officers incharge of work LUMINAIRE MAKE: Phillips / OSRAM / GE / Crompton /VIN / Bajaj / Havells / Halonix / HPL. LED MAKE : PHILIPS LUMILEDS / CREE / NICHIA /OSRAM / SAMSUNG / LG LEDs.
Labour charges for Fixing of Ceiling fan and regulator including transportation and giving connections with twin core wire etc., complete as per IE Rules and as directed by the departmenal officers incharge of work
Labour charges for fixing of Exhaust fan in wall with necessary connections and masonary work of making hole, finishing etc., complete as per IE Rules and as directed by the departmenal officers incharge of work
Labour charges Fixing of 20W tube light luminaire on wall / Ceiling with / TW round blocks with all accessories including giving connections and all labour charges etc., complete.as per IE Rules and as directed by the departmenal officers incharge of work
Formation of temporary island of 30m diameter in Yeleru Reservoir for Constgruction of 13.00m dia intakewell cum pumphouse.
Providing and construction of Temporary island of 30.00m. Diameter and 13 metres height for preparation of platform etc.with laying of sand bags in the stipulated places including cost of empty cement bag, sand thread, stiching charges and labour charges . During the emergency conditions such as floods .and other natural calamities, the above rate is allowed to enhance by 25% for 1st warning level and above, keeping in view of the difficulty in availability of labour and vehicles for ring bund by using crane with grap, consumbles, wooden ballies shutable dia and shutable height and braceings, for construction of 8.00m dia Raw water intake well in River in Godavari near Bridge. This rate including cost of all materials,all labour charges conveyance charges and all operational, incidental and labour charges etc., complete for finished item of work and as per ss and as adirected by the departmental officer in charge of work..
Formation of bund/approach ramp with Gravel/Quarry spall from approved quarry including cost and conveyance of all materials and labour charges for formation of protection bund by filling, sectioning, levelling, compacting etc.complete as per S.S and as directed by the departmental officer incharge of work.
Construction of 60m long RCC Walkway Bridge from Intakewell to Bund in Yeleru Reservoir
Earthwork in excavation in all Types of soils for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH as per Specification drawings and as directed by the departmental Officer including all Incidental and operational Charges etc
Filling Sand in foundation trenches as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH . The rate including cost and conveyance of all material, labour charges for filling, watering, ramming, etc., complete as per SS and as directed by the departmental officer in charge of the work but excluding seigniroage charges for column bed
Plain Cement concrete (1:4:8) using 40 mm metal with concrete mixer. All work upto plinth level including cost of all materials and labour charges etc., complete as per SS and as directed by the departmental officer in charge of the work but excluding seigniorage charges for column bed
Providing VRCC M30 Grade Design Concrete Mix corresponding to IS 456 using WEIGH BATCHER / MIXER with 20mm size graded machine crushed hard granite metal (coarse aggregate) from approved quarry including cost and conveyance of all materials like cement, fine aggregate (sand) coarse aggregate, water etc., to site and including seignorage charges including all operational, incidental and labour charges such as weigh batching, machine mixing, laying concrete, curing with cement content 400Kgs/Cum as per I.S code from standard suppliers approved by the department including centering, shuttering, laying concrete, vibrating, curing etc. complete but excluding cost of steel and its fabrication charges for finished item of work (APSS No. 402) as follows
Footinggs
For columns
For Intermediate Braces
For Carriage Slab Beams
For Carriage Slab 0.20m thick
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying including sales and other taxes on all materials etc., complete for finished item of work in all floors.( APSS No.126)
Construction of R.C.C. railing of M 25 grade in cast-in-situ with 20 mm nominal size aggregate, true to line and grade, 3 time tolerance of vertical railing post not to exceed 1 in 500, centre-to-centre spacing between vertical posts not to exceed 2000 mm as per drawing and technical specifications Clauses 800, 900 and 1208.3 MORD. as directed by the departmental officer incharge of work.
Providing 700mm dia DI K9 Raw Water Pumping main from proposed Intake well cum Pump House to proposed WTP at Yeleswaram
Manufacture supply delivery,of 700mm dia DI K9 centrifugally cast (spun) ductile iron pipes for water with SOCKET SPIGOT ENDS CONFIRMING TO IS NO 8329/2000 in standard lengths of 4.00, 5.00, 5.50, 6.00m suitable for push-on-joint (rubber gasket D jointing) with cement mortor lining inside and zinc coating out side (K9) including transportation ,loading,unloading, stacking, etc complete as per SS and as directed by the departmental officer incharge of work.
Supply and delivery of 700mm dia PN 1.6 "Resilient Seated Soft Sealing" Gate Valves (Sluice Valves) with Body and Bonnet of Ductile Iron GGG-40/SG-400/15 or GGG-50/SG-500/7 or Equivalent as per IS1865, IS:3896-2 and Wedge fully Rubber Lined with food grade quality grade W270 grade EPDM, Replaceable Spindle Nut without gland packing with 3-O ring protection system on the Shaft and Seals of NBR. The Valves should be Vacuum tight and 100% leak proof with face to face dimensions as BS:5163 Type A/IS:14846. All the valves should be with fusion bonded Electrostatic Powder coating both inside and outside (Min 250 Microns)- RAL 5005 with Pocket Less Straight through body Passage conforming to Design standards of DIN-3202F4/BS:5163 Type A Flange drilling as per IS - 1538 and transportation. as per SS and as directed by the departmental officer incharge of work
Supply & Delivery of 150mm dia Tamper Proof DI Flanged Single Chamber Air Release Valves with body & cover made of Ductile Iron Grade GGG-40/SG-400/15 or GGG-50/SG-500/7 or Equivalent as per IS1865, IS:3896-2 with Food Grade Epoxy Powder Coating(EP-P) (Min:250 Micron) inside and Outside of Color Blue RAL 5005. All internal parts such as Float, shell, Cove Bolts etc. made of Austenitic alloy steel of SS AISI 304/316 and DN 50 float of and other components with ABS/PTFE/EPDM/NBR and generally conforming to DIN/BIS/AWWA standards (or) combination Flange drilling as per IS - 1538 and transportation as per SS and as directed by the departmental officer incharge of work
Manufacture, supply and delivery of 700mm dia DI D/f Centrifugally cast (Spun) Ductile Iron pressure pies with flanged (welded) ends for water, gas, sewage conforming to IS: 8329/2000 in standard working lengths of 1,2,3, 4, 5 mts for classification K9 with cement mortar lining inside the pipes with outside zinc coating. The rate including cost of pipes, transportation of site, etc., complete. as per SS and as directed by the departmental officer incharge of work
Manufacture, supply and delivery of 500mm dia Centrifugally cast (spun) Ductile Iron Fittings conforming to IS:9523/2000 having dimensions as per table. The rates mentioned here under are for fittings, zinc coated externally with inside mortar lining (with finishing as per class 13/IS 9523/2000) (ex-works) including Transportation and other incidental charge charges etc complete as per SS and as directed by the departmental officer incharge of work.
Cutting the Open BT Road Surface( as well as asphalt concrete upto 75mm thick) including water bound macadam. The rate including labour charges for cutting, all incidental charges, etc., complete as directed by the departmental officer in charge of the work
Cutting the Open CC road surface with concrete saw cutter and removal with breaker including stacking the ueful material . The rate including labour charges for cutting, all incidental charges, etc., complete as directed by the departmental officer in charge of the work
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH etc., complete as per SS and as directed by the Departmental officer in charge of the work as follows
Mechanical 70%
Manual
Lowering the of 700mm dia DI K9 C.I. Pipes, D.I. Pipes and fittings with S/S (Plain)ends carefully into the trenches and laying them true to alignment and gradient including all sundries, but excluding conveyance from source of supply as per BIS No.3114/94. as per SS and as directed by the departmental officer incharge of work
Jointing the 700mm dia DI K9C.I,D.I. Pipes, fittings and valves with rubber gasket(push-on-joint) including the cost of the gasket but including all sundries, filling with water with a water lead upto 500 m and testing to required pressure etc., comp as per BIS No.3114/1994/12888/1987 as per SS and as directed by the departmental officer incharge of work
Labour charges for 700mm dia lowering and keeping in position of D.I. Sluice valves(with cap/with hand wheel), reflux valves and scour valves.as per SS and as directed by the departmental officer incharge of work
Labour charges for 150mm dia fixing Kinetic Air Valves with isolating Sluice valves, Double Air valves/ Air Cushion valve excluding cost of jointing materials such as bolts, nuts and rubber insertions etc., complete. as per SS and as directed by the departmental officer incharge of work
Lowering the 700mm dia C.I. Pipes, D.I. Pipes of all classes and fittings with flanged ends carefully into the trenches and laying them true to alignment and gradient including all sundries, but excluding conveyance from source of supply as per BIS No.3114/94.as per SS and as directed by the departmental officer incharge of work
Jointing of 700mm dia the C.I. Pipes, fittings and valves with flanged ends including cost of jointing materials such as bolts, nuts, rubber insertion, white lead and including filling with water with a water lead upto 500 m and testing to required pressure etc., comp as per BIS No.3114/85.as per SS and as directed by the departmental officer incharge of work
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH etc., complete as per SS and as directed by the Departmental officer in charge of the work
Filling Dust in foundation trenches as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH . The rate including cost and conveyance of all material, labour charges for filling, watering, ramming, etc., complete as per SS and as directed by the departmental officer in charge of the work but excluding seigniroage charges.
Plain Cement concrete (1:4:8) using 40 mm metal with concrete mixer. All work upto plinth level including cost of all materials and labour charges etc., complete as per SS and as directed by the departmental officer in charge of the work but excluding seigniorage charges
R.C.C grade M 20 (Nominal Mix) using 20mm &10mm metal. The rate including cost and conveyance of all material, labour charges for mixing, laying, vibrating, curing, etc., complete as per SS and as directed by the departmental officer in charge of the work but excluding seigniorage charges.
Walls
C.C grade M 20 (Nominal Mix) using 20mm &10mm metal. The rate including cost and conveyance of all material, labour charges for mixing, laying, vibrating, curing, etc., complete as per SS and as directed by the departmental officer in charge of the work but excluding seigniorage charges for Ancher Block
R.C.C grade M 20 (Nominal Mix) using 20mm &10mm metal. The rate including cost and conveyance of all material, labour charges for mixing, laying, vibrating, curing, etc., complete as per SS and as directed by the departmental officer in charge of the work but excluding seigniorage charges.for thrust block
Supplying, fitting and placing HYSD bar reinforcement in foundation complete as per drawings and technical specifications for Bars below 36 mm dia including over laps and wastage, where they are not welded. The rate including cost and conveyance of steel, binding wire, labour charges for fabrication of grills, placing in position, etc., complete as per SS and as directed by the departmental Officer in charge of the work.
Provivding 3 Nos 87.50 KW of Raw Water Vertical Turbine pumpsets with a duty of 404 LPS against a head of 33m with 50% stand bye
Provivding 3 Nos 87.50 KW of Raw Water Vertical Turbine pumpsets with a duty of 404 LPS against a head of 33m with 50% stand bye
Supply, delivery, errection and commissioning of Motors with a speed of 1500 RPM 50 Hz TEFC horizontal foot mounted squirrel cage induction motor of reputed standard make suitable to operate 440volts to suit above pump sets fitted on a common base plate including cost and conveyance of all materials including errection and commissioning charges and dismantling the existing motors carefully if any and all taxes , duties, labour and transportation charges to site and all other incidental and operational chrages etc; complete including all taxes
Supply, delivery and errection of suitable capacity vaccum pumpsets with all necessary Electrical connections, GI pipe connections & other accessories for self priming with 100 % Stand bye including cost and conveyance of all materials, errection and commissioning charges and dismantling the existing pumpsets carefully if any and all taxes, duties, labour and transportation charges to site and all other incidental and operational charges etc; complete including all taxes
Supply and fixing of control Pannel Board with suitable capacity bus bar suitable to operate above 3 Nos Pump Sets. The accessories all are internally wired with necessary earthing terminations. The Panel Board is made of 16 guage MS sheet metal cubical/industrial indoor type and duty painted with 2 coats enamel paint with cost of material as follows. conveyance, all taxes, duties, labour charges and all other incidents etc; complete for finished item of work
Out-going cable of suitable size of Alluminium armoured cable of 3.50core of standard make from Panel Board to Starter and to Motor Cable Joints with jointing materials such as lugs glands, adhesive taps etc; to join the above cables a per I.E Rules Supply and errection of suitable suction and delivery DI/MS pipes and connections upto manfold including heavy duty Sluice Valves on suction side per stipulations of water supply mannual and I.S.Codes Supply,delivery,errection and commissioning of suitable capacity vaccum pump to operate ablve pumpsets including connecting or pumpsets with required G.I Pipes, Specials and fixing in concrete bed etc; Supply, laying and fixing of 40x6mm G.I flat patti double earthing for electrical protection for motor, pump and panel board efficiently earthing duly providing earth pits and filling with coal and salt and G.I pipe 1 1/2 x 6" long and bottom 2'x2' G.I.Plate welded as per I.E.Rules and Specifications with cost of materialss, conveyance, taxes,duties, labour charges and all other incidental charges and providing 1 1/2' x 1 1/2' earth pit chamber with brick masonary with top cover
Supply and delivery of necessary suitable errection tools of reputed make mounted on polished teak wood board including cost of materials and all taxes and duties etc; 1) Ring Spanner 3/16 to 1" - 1No 2) Double end spanner set 3/16" to 1" - 1 No 3) Pipe Wrench 18" & 4" - 2Nos 4)Screw drivers 6", 10" & 12" - 3 Nos 5) Cutting Plier 12" - 1No 6) 2 Kgs Hammer with Handle - 1 No 7) Nose Plier - 1 No 8) Flat and Half round smooth file - 2 Nos 9) Adjustable Spanner 6" 10) Column pipe Clamps - 2 pairs 11) Line Shaft Clamps - 1 Pair 12) Line rope and clamps double the weight of pump - 2 sets 13) Spitter removing Spanner - 1 No 14) Gland thghtening Spanner - 1 No
Supply and delivery of necessary safety equipments as per IE Rules including cost of materials and all taxes and duties etc; complete 1) Fire extiguisher 3Kg capacity - 2 Nos 2) Rubber Mat 6" x 4" - 2Nos 3) Fire Buckets with stand and three buckets - 1 No 4) Rubber Hand Gloves - 1 Sets 5) Danger Board Plates - 4 Nos 6) First aid kit with chart - 1No 7) Shock Treatment Chart - 1No 8) Portable rechargeble torch light - 1 No
Supply and delivery of indigeneous make 500V insulation tested a portable type technometer and megger etc; Supply, delivery and erection of 5 tonnes capacity double girder gantry arrangements to move and lift the installations of the pump house one way with required MS ISMB of best quality 250 x 100 mm of standard make, including the required MS ISMC, MS angular iron, 5 tonne capacity travelling trolley and 5 tonne capacity chain pulley block with chains of suitable capacity for lifting and moving arrangements to length of 10.00 m rate is inclusive of the cost of materials, labour charges, site welding etc., All Civil Works Such as anchor Blocks ,Thrust Blocks, Platform for Pannel Board and Cable trench etc Complete as directed by the Field Engineer Testing and maintanance of the complete equipment covered and trial run for 30 days at 8 hours per day after completion of errection
Construction of 32.00 MLD Rapid Gravity Filtration Plant at Head Water Works
Construction of 32.00 MLD Rapid Gravity Filtration Plant at Head Water Works
Construction of Rapid Gravity Filtration Plant including all civil, mechanical and electrical works using sand as filter media, compatible with SCADA arrangements, duly following relevant IS codes in the design of plant components including trial running for 90 days etc., including chlorine contact tank & consumables etc., complete.
NOTE :- a) For Intermediate Capacities proportional rates may be adopted b) The above rates are arrived with base rate of Cement Rs.4220/- per MT (as per G.o.Rt.No.2029 Water Resources (Reforms) Dept. Dt:06-10-2022) & Steel Rs 60000/- per MT(Fe 500) c) The above rates shall be increased / decreased due to increase / decrease in the cost of cement by Basic Rate x {(Rc-4220)/4220} x 0.07 Rc = Rate of cement (Rs per Mt) at the time of preparation of estimate d) The above rates shall be increased / decreased due to increase / decrease in the cost of steel by Basic Rate x { (Rs-63000)/63000} x0.2 Rs = Rate of Steel (Rs per MT) at the time of preparation of estimate. e) For Rural areas an extra allowance of 10% shall be given on basic rate. i) For SBC below 10T/Sqm to 7.5 T/Sqm, solid raft shall be provided and for solid raft the rate shall be increased by 10% on basic rate. ii) For SBC below 7.5 T/Sqm to 5 T/Sqm, solid raft shall be provided and for solid raft the rate shall be increased by 15% on basic rate. g) For SBC value of less than 5 T/Sqm, soil improvement shall be adopted, for which additional payment shall be made as per field condition.
h) For components immersed in water Stain less Steel of Grade 304L shall be used. for other components 304 Grade steel shall be used. i) Lab testing equipment of reputed make and consumables for one year. The testing equipment for conducting all laboratory tests shall be installed & training shall be imparted to the Municipal staff. The above rates of Filtration Plants shall include all the following components. A) Civil Works (All works of VRCC Shall be in M30 design mix) 1). Stilling Chamber and Aeration cascade 2) Pre settling tank shall be provided for 30 MLD and above capacities of WTP for a minimum of 1 hr capacity. 3). Raw water channel with Stainless Steel Weir of SS 304 L Grade material and also with digital flow meters 4) Flash Mixer chamber with Flash mixing arrangements including SS shaft & SS Blades with gear wheel arrangements etc, using 304 L Grade Steel. 5-a) Clariflocculator / Flocculation tanks with the components of central driven circular clarifier with scrapper & bridge arrangements made with Stainless Steel Grade 304 L tubes /angular for durability & chemical resistant with wheel arrangements etc,
5-b) Two numbers of Clariflocculator shall be provided for WTP's of more than 30 MLD capacity. 6) Filter house, Chemical house, Alum store, Laboratory room, Chlorination plant room, toilet etc. (All structures shall be provided RCC roof only).Chemical house & Chlorinator rooms are to be isolated and shall be as per CPHEEO manual. 7) Wash water tank of suitable capacity shall be constructed at minimum clearance of 2.00m, above the roof slab of Filter beds / any other structure, and the minimum residual head at the top of under drain system shall not be less than 8.0 meters. 8) Chlorine contact tank 9) All the Doors and Windows shall be of Best Teak wood/Aluminum / UPVC make, except entrance door. The entrance door including shutter in filter house shall be with best teak wood of minimum size of 2.40 X 2.40 mts. a) Main Doors of all individual Buildings shall be made of Best Teak wood b) Other Internal Doors of the buildings shall be of Compressed wood/ Aluminum/ UPVC materials. c) Ventilators shall be provided for each building/structure of suitable size as per NBC standards. 10) a) All pipes in Plant shall be of D.I., D/F materials. All Connecting pipes of the plant components such as from Flash mixer to Clariflocculator/ Clarifier/Flocculation tank, to Filter beds, sludge disposal pipes shall be of D.I., D/F material. The size of sludge disposal pipe shall be minimum of 450 mm dia. with D.I D/F pipe and minimum length of 100 meters. b) All the Valves in Plant shall be heavy duty and as per the specification of SoR item No.28
11) The Pipe gallery way for Clear water/ Back wash water/ pipe connections shall be sufficiently spaced for easy operation & maintenance and inspection, as per standard norms. 12) The bottom level of the wash water control chamber must be above G.L so as to dispose the wash water and sludge from Clariflocculator by gravity to disposal point. Additional specifications 13) Railing for all the components (Clariflocculator, Filter House, Staircase etc,.) shall be provided with Stainless Steel of grade 304 for a height of 1.00m, with 40mm dia. pipe for top horizotals,25mm dia. for middle row and 40mm dia. verticals spaced at interval of not more than 1.00m c/c. 14) Inspection / Path ways in filter beds: Middle pathway: Minimum of 1.50m, Side pathway: Minimum of 1.20m 15) i) Flooring in the buildings (Filter house, Chemical House, Chlorinator Room, Laboratory) shall be provided with Non-skid ceramic tiles of approved make & quality, as per standard specifications. ii) All water Channels such as inlet, outlet channels and chambers shall be provided with tiles. 16) The basement of the Filtration plant building shall be minimum of 1.20m and pipe gallery shall be minimum 0.3m above the existing nearby Road top level. 17) Minimum head room of 2.00m shall be provided, at the alum mixing chambers in alum store for inspection & maintenance.
18) The minimum width of entrance hall for the Filter House shall be 4.50m, and Laboratory of min size of 3.30 X 4.50m. 18) b) For various components of the WTP should be designed by considering the uplift pressure also. 19) a) High efficient Air Blowers shall be installed to the design requirement with low noise pollution, environmental pollution as per PCB guide lines & Testing of blowers as per I.S Standards at site. b) The Piping from Blower to Filter Beds shall be GI and submerged pipe in water shall be HDPE. 20) UPVC pipes shall be provided for under drain system. Filter pipe manifolds shall be assembled with HDPE pipes. 21) Alum storage capacity shall be designed for minimum period of 90 days. Consumables shall be provided for 2115 Running Hours of WTP. 22) Chlorinator : Vacuum type chlorinator shall be provided with following specifications: a) Vacuum operated solution feeding type Vacuum Regulator, Rotameter, Rate setting Valve, built-in NRV, Gas Overflow out let by man folding to mount the system with the unit. b) The unit shall consist of Ejector with necessary accessories such as Check Valve, Drain Valve and Vacuum relief Valves - for control of chlorinator dosage. c) The Accessories and manifolds shall be chlorine resistant and made of carbon steel seam less pipes, copper tube with brass fittings of suitable size & dimensions, with diaphragm sealed chlorine pressure gauge arrangements
d) Water Booster Pump of pumping capacity ranging from 2 cum/hr to 12 cum/hr, with Head ranging from 16 to 35 m e) The water & solution carrying pipes shall be made of UPVC material of suitable size incl. all specials such as Tee's , Bends, couplings & NRVs and also Pressure Gauges of suitable range. f) Chlorine Gas Leak detector with alarm indicator. The installation includes all necessary accessories, civil and mechanical works, manifold header installations, injector fixing, connection with UPVC pipes, solution piping’s, fixing of motors as per standard specifications and commissioning of Chlorination Plant to the required demand, with a defect liability period of 1 year. The chlorinator of may be of any reputed make or any make of Metito/Toshocow-Jesco Siemens Industrial Devices. g) Life breathing apparatus. h) Chlorine escape BA set i) 2 to 10 MLD Plants - 1Kg/hr Chlorinator- For Post Chlorination ii) 10 MLD to 20 MLD Plants - 2 Kg/hr Chlorinator - For Post Chlorination. iii) 20 MLD to 50 MLD Plants - 5 Kg/hr Chlorinator - For Post Chlorination. B) Mechanical Equipment
1) Alum dosing equipment with SS 304 material made stirrers & paddles for chemical resistance. (Alum tanks must be bound with corrosion resistant material (HDPE Lining, Bitumen Coating, tiles etc) 2) Flash mixer equipment with SS 304 material made stirrers & paddles for chemical resistance. 3) Filtration plant equipment instrumentation and piping. 4) Clarifloccualation equipment (with stainless steel blades) with rotating bridge arrangement etc., 5) Pneumatic tyre wheel shall be provided for the bridge Clariflocculator. 6) Wash water tank fittings and pump sets with 100% stand by. 7) Air blower with motor of 100% stand by and pipe connections made with of SS pipes confirming to SS 304 Grade, in filter bed region. 8) Chlorination equipment and pipe connections with chlorinator of 100% standby. 9) Spares & Tools for 2 years. 10) Gaseous Chlorination with cylinders has to be provided with protection measures. C) Electrical Equipment 1) Necessary power supply wiring to motors and switches bus bar connections as per IE Rules
2) Internal wiring and illumination and fittings and fixtures for internal and external lighting exhaust fans, ceiling fans etc. 3) Erecting mechanical and electrical equipment, trial run for 90 days at 23.50 hours per day testing the treated water as per CPHEEO standards and maintenance of records and imparting training to staff. 4) Supply of 6 - Sets of completion plans and maintenance manual and brochures. 5) All cables shall be of copper material, Cable ducts shall be covered with MS / Aluminum cheque plate. 6) Min LUX levels inside the treatment plant shall be maintained. 7) Yard lighting shall be provided as per norms. D ) Equipment for Flow measurements 1) Equipment for measuring Conductivity, Turbidity, Ph value, Residual Chlorine with recording & data storage facility (Computer based) & Alarm by SMS or other methods. 2) Off - Site Supervisory and Data Acquisition (OSSADA) system for Raw water & Clear water flows by installing Digital Flow meters to measure the flows at Raw water Channel and at each filter bed individually and combined for measuring the quantities of water treated with a facility to record and store the readings & also to send messages to the assigned designators about the variations/ deficiencies in the flow including alerts for back wash requirements of filter beds, and recovery of data for the past 360 days. All the Digital Flow Meters & Pressure Gauges shall be provided of standard approved make. The equipment shall have the following specifications.
Hardware: i) Wall mounted Sensor House for measuring Raw water & Clear water flow from Filter bed out lets with accessories consists of ii) Electrode Type: General type, Scraper type or replaceable type Electrode made with material of SS external Ultra Touch Sensors as per requirement. iii) Customized Application Requirement : Sensors with Interface logic control board with serial interfaces, including accessories such as Add-on port, external DC Power Socket, On - sensor Board Buffer, Timer, RS485 Communication, Analog to Digital Sensing Sensor Circuit, 32 Sensors Sensing Tags, Interval Power Supply System , LCD 16c/2L, Filter Bed Working Status Indication LED, Filter Bed Wash Indication Button and memory of Data Storage for 30Days , status of Filter Bed Level indicator, Rating, Reading on LCB Display, Menu Driven Data for sending to Onsite Big Display, operated with Battery Power of any reputed make or any equivalent make.
iv) Customized Application Requirement: Power Sensors Interface logic control board with support 8 Power Sensing tags, Central System Interfacing Communication, On - board analog to Digit Convert Integrate Circuit of any reputed make or any equivalent make. v) Customized Application Requirement: Centralized System with two serial interfaces, 3 No’s of Add-On ports, One external DC Power Socket, On - Board Buffer, On - Board Timer, On - Board RS485 Communication, On - Board RS 232 Communication, On - Board GPRS/GSM Module, On - Board Voice Chip, On - Board Power Sensing Module, LCD 16c/2L, Filter Bed Wash Precaution Indication with Stop Button, Memory of Data Storage for 30 Days, Total Bed Rating, Reading display on LCD Display, Menu Driven, Menu Navigate Keypad, sending data to the Web Server, Communication with GPRS , operated with Battery Power of any reputed make or any equivalent make. Software: The software shall be designed with Web Domain with Data Base Server and Web Name as per the directions of the Departmental Authorities.
The application of Software for Web design & Desktop shall meet the following requirements: i)Onsite Display: Letters with size of 1.5’ seven Segment LED Display with Interface for each Filter Bed, for Onsite Display, by displaying the Bed Levels, Ratings, Readings in 3 Columns, for each bed of the plant in successive rows and cumulative results at the bottom of the screen. ii) Off Site Display: Letters with size of 1.5’ seven Segment LED Display with Interface GPRS/GSM Modules Offsite Display, with Display of Bed Total Rating, Total Cumulative Reading as specified on On-site Display Features. The system shall have also the features of Onsite Bed Wash Voice Precautions for Bed Levels, Readings, Ratings, Bed Capacity Readings and Ratings and Bed Low Level Triggering, before & after Bed wash. The software shall also have the features of sending messages to the mobiles of the Departmental designators indicating Bed Low Levels, Power Supply timings, Bed Wash timings and its status, Power Supply timings and its status Grid View Table, Motor Working time and its status Grid View Table, all trigger events and schedule information and including all Snap View Reports, all Daily, Monthly, Yearly Reports, all Power Working Reports, all Power Events Information etc,.
Construction of Wash Water Recirculation of sump of 8.00m dia ( 150KL) at WTP
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH as follows
Mechanical Means
Manual Means
Filling Dust in foundation trenches as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH . The rate including cost and conveyance of all material, labour charges for filling, watering, ramming, etc., complete as per SS and as directed by the departmental officer in charge of the work but excluding seigniroage charges.
Plain Cement concrete (1:4:8) using 40 mm metal with concrete mixer. All work upto plinth level including cost of all materials and labour charges etc., complete as per SS and as directed by the departmental officer in charge of the work but excluding seigniorage charges
Supply and placing of the M30 design mix concrete corresponding to IS -456 using WEIGH BATCHER/MIXER using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including all operational ,incidental and labour charges such as weigh batching ,machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work (APSS NO 402) with minimum cement content as per IS Code from standard suppliers approved by the deparment including pumping , centering,shuttering,laying concrete ,vibrating,curing etc M30 design mix concrete with concrete mixer as follows
For side walls circular 0.30m thick
Columns 0.30 x 0.30m 3.60-0.30
Roof beams
Roof slab 0.15m thick 0.786x(7.60^2-3.00^2)
Roof dome slab 0.15m thick
Providing impervious coat to exposed RCC roof slab surface with CM(1:3), 20mm thick with 1kg of water proof compound per bag of cement laid over roof when it is green including cost of all materials, conveyance charges of materials and including all operational, incidental and labour charges for mixing mortar, laying, rendering smooth and thread lining, curing, rounding off junctions of wall and slab etc,, complete for finished item of work
Painting with two coats of water proof cement paint of apporved brand and shade over a base coat of approved cement primer grade II making making three coats in all to give an even shade after thoroughly brushing the surface to remove all dirt and remains of loose powdered materials, including cost and conveyance of all materials to work site, Scoffolding, Curing charges and all operational, incidental, labour charges etc. complete for finished item of work for External walls
Supply and delivery and fixing in position M S grill of any design including all fabrication and all fixing charges etc compalete as per ss and as directed by the dept authorities
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying etc., complete for finished item of work in all floors.( APSS No.126)
Construction of R.C.C. railing of M 25 grade in cast-in-situ with 20 mm nominal size aggregate, true to line and grade, 3 time tolerance of vertical railing post not to exceed 1 in 500, centre-to-centre spacing between vertical posts not to exceed 2000 mm as per drawing and technical specifications Clauses 800, 900 and 1208.3 MORD.as per SS and as directed by the departmental officer incharge of work
Supply, Delivery, Errection and Trial running of 2 Nos of 2.61KW CF pumpsets each with a duty of 12LPS against a total head of 15m ( one stand bye) for pumping wash water to aerator for recirculation
Supply and erection of 2# of 2.61 KW CF Pumpsets each with a duty of 12 LPS and a total head of 15m ( one working and one stand bye) for pumping wash waterto Areatorm for recirculation
Providing 350mm/250mm/150mm/100 mm dia DI K7 Gravity main to various ELSRS in the town
Manufacture supply delivery,of centrifugally cast (spun) ductile iron pipes for water with SOCKET SPIGOT ENDS CONFIRMING TO IS NO 8329/2000 in standard lengths of 4.00, 5.00, 5.50, 6.00m suitable for push-on-joint (rubber gasket D jointing) with cement mortor lining inside and zinc coating out side (K7) including transportation ,loading,unloading, stacking, etc complete as per SS and as directed by the departmental officer incharge of work as follows
350mm dia DI K7
250mm dia DI K7
150mm dia DI K7
100mm dia DI K7
Supply and delivery of "Resilient Seated Soft Sealing" Gate Valves (Sluice Valves) with Body and Bonnet of Ductile Iron GGG-40/SG-400/15 or GGG-50/SG-500/7 or Equivalent as per IS1865, IS:3896-2 and Wedge fully Rubber Lined with food grade quality grade W270 grade EPDM, Replaceable Spindle Nut without gland packing with 3-O ring protection system on the Shaft and Seals of NBR. The Valves should be Vacuum tight and 100% leak proof with face to face dimensions as BS:5163 Type A/IS:14846. All the valves should be with fusion bonded Electrostatic Powder coating both inside and outside (Min 250 Microns)- RAL 5005 with Pocket Less Straight through body Passage conforming to Design standards of DIN-3202F4/BS:5163 Type A Flange drilling as per IS - 1538 including and transportation. other incidental charges etc complet as follows.
350mm dia PN 16
250mm dia PN 16
150mm dia PN 16
100mm dia PN 16
Supply & Delivery of Tamper Proof DI Flanged Single Chamber Air Release Valves with body & cover made of Ductile Iron Grade GGG-40/SG-400/15 or GGG-50/SG-500/7 or Equivalent as per IS1865, IS:3896-2 with Food Grade Epoxy Powder Coating(EP-P) (Min:250 Micron) inside and Outside of Color Blue RAL 5005. All internal parts such as Float, shell, Cove Bolts etc. made of Austenitic alloy steel of SS AISI 304/316 and DN 50 float of and other components with ABS/PTFE/EPDM/NBR and generally conforming to DIN/BIS/AWWA standards (or) combination Flange drilling as per IS - 1538 and transportation
Manufacture, supply and delivery of Centrifugally cast (Spun) Ductile Iron pressure pies with flanged (welded) ends for water, gas, sewage conforming to IS: 8329/2000 in standard working lengths of 1,2,3, 4, 5 mts for classification K9 with cement mortar lining inside the pipes with outside zinc coating. The rate including cost of pipes, transportation of site, etc., complete. as follows
350mm x 1.00m Pipe
250mm x 1.00mPipe
150mm x 1.00m Pipe
100mm x 1.00m Pipe
Manufacture, supply and delivery of Centrifugally cast (spun) Ductile Iron Fittings conforming to IS:9523/2000 having dimensions as per table. The rates mentioned here under are for fittings, zinc coated externally with inside mortar lining (with finishing as per class 13/IS 9523/2000) (ex-works) including Transportation and other incidental charge.
Cutting the Open BT Road Surface( as well as asphalt concrete upto 75mm thick) including water bound macadam. The rate including labour charges for cutting, all incidental charges, etc., complete as directed by the departmental officer in charge of the work
Cutting the Open CC road for pipeline tranch portion surface with concrete saw cutter and removal with breaker including stacking the ueful material . The rate including labour charges for cutting, all incidental charges, etc., complete as directed by the departmental officer in charge of the work
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH etc., complete as per SS and as directed by the Departmental officer in charge of the work
Mechanical 70%
Manual
Lowering the C.I. Pipes, D.I. Pipes and fittings with S/S (Plain)ends carefully into the trenches and laying them true to alignment and gradient including all sundries, but excluding conveyance from source of supply as per BIS No.3114/94 as follows
350mm dia DI K7
250mm dia DI K7
150mm dia DI K7
100mm dia DI K7
Jointing the C.I,D.I. Pipes, fittings and valves with rubber gasket(push-on-joint) including the cost of the gasket but including all sundries, filling with water with a water lead upto 500 m and testing to required pressure etc., comp as per BIS No.3114/1994/12888/1987 as follows
350mm dia DI K7
250mm dia DI K7
150mm dia DI K7
100mm dia DI K7
Labour charges for lowering and keeping in position of D.I. Sluice valves(with cap/with hand wheel), reflux valves and scour valves. as follows
350mm dia
250mm dia
150mm dia
100mm dia
Labour charges for 80mm dia fixing Kinetic Air Valves with isolating Sluice valves, Double Air valves/ Air Cushion valve excluding cost of jointing materials such as bolts, nuts and rubber insertions etc., complete.
Lowering the C.I. Pipes, D.I. Pipes of all classes and fittings with flanged ends carefully into the trenches and laying them true to alignment and gradient including all sundries, but excluding conveyance from source of supply as per BIS No.3114/94. as follows
350mm dia
250mm dia
150mm dia
100mm dia
Jointing the C.I. Pipes, fittings and valves with flanged ends including cost of jointing materials such as bolts, nuts, rubber insertion, white lead and including filling with water with a water lead upto 500 m and testing to required pressure etc., comp as per BIS No.3114/85. as follows
350mm dia
250mm dia
150mm dia
100mm dia
Construction of Valve Pits, Anchor Blocks, Thrust Blocks
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH etc., complete as per SS and as directed by the Departmental officer in charge of the work
Filling Dust in foundation trenches as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH . The rate including cost and conveyance of all material, labour charges for filling, watering, ramming, etc., complete as per SS and as directed by the departmental officer in charge of the work but excluding seigniroage charges.
Plain Cement concrete (1:4:8) using 40 mm metal with concrete mixer. All work upto plinth level including cost of all materials and labour charges etc., complete as per SS and as directed by the departmental officer in charge of the work but excluding seigniorage charges
R.C.C grade M 20 (Nominal Mix) using 20mm &10mm metal. The rate including cost and conveyance of all material, labour charges for mixing, laying, vibrating, curing, etc., complete as per SS and as directed by the departmental officer in charge of the work but excluding seigniorage charges.
Walls
C.C grade M 20 (Nominal Mix) using 20mm &10mm metal. The rate including cost and conveyance of all material, labour charges for mixing, laying, vibrating, curing, etc., complete as per SS and as directed by the departmental officer in charge of the work but excluding seigniorage charges for Ancher Block
R.C.C grade M 20 (Nominal Mix) using 20mm &10mm metal. The rate including cost and conveyance of all material, labour charges for mixing, laying, vibrating, curing, etc., complete as per SS and as directed by the departmental officer in charge of the work but excluding seigniorage charges for ancher Block
Supplying, fitting and placing HYSD bar reinforcement in foundation complete as per drawings and technical specifications for Bars below 36 mm dia including over laps and wastage, where they are not welded. The rate including cost and conveyance of steel, binding wire, labour charges for fabrication of grills, placing in position, etc., complete as per SS and as directed by the departmental Officer in charge of the work.
Construction of 850KL Capacity ELSR at YPC Junction with a staging of 20m ( Balance work)
Construction of 850KL Capacity ELSR at YPC Junction with a staging of 20m ( Balance work), with Seismic analysis. All concrete components shall be designed with M30 Design Mix proportion. The foundations shall be designed for Annular Raft Footings. The above rates are applicable for Elevated Level Services Reservoirs / OHSRs for SBC of 15 T/Sqm. For SBC below 10T/Sqm , solid raft shall be provided For SBC value of less than 5 T/Sqm, soil improvement shall be adopted, for which additional payment shall be made as per field condition. Rate inclusive of three coats of epoxy paint Food Grade of best quality to inner surface of the Reservoir including roof. b)The rate inclusive of 2 coats of weather proof emulsion painting for external surfaces, lettering, all required fixtures, Pipes, Pipe specials, valves of DI material, Valve chambers etc., for pipe connections including cost of pipes, specials and valves as per departmental designs and drawings. The above rates adopted for a wind pressure up to "250 kg/Sqm". The ELSR/OHSR shall be designed with minimum of two rows of columns for capacities above 500 KL & up to 1000KL.
The ELSR/OHSR shall be designed with minimum of three rows of columns for capacities above 1000KL. 14. The shaft type staging with slip form can also be provided with proper approval from competent authority without any additional cost. 15) The basic rate is inclusive of following Fixtures i) Pipe connections & Specials with D.I materials (a) All pipe connections for Inlet, Out let, Over Flow, Scour pipes shall be provided with D/F DI material. (b) The Valves for above pipe connections also shall be of DI material of PN 16 duty confirming to the specification of SoR item No.28 (c) All specials such as Bends, Tees, Reducers, Duck foot Bends, Bell mouths etc,. Shall be of DI material. II) The sizes of the verticals for ELSR/OHSR shall be:
a) For 500 KL to 750 Kl ELSRs Inlet Pipe - 300mm dia. Out let Pipe - 350mm dia. DI valves – 2 No’s Over Flow pipe - 350m dia. Scour Pipe - 200mm dia. b) For 800 KL to 1500 Kl ELSRs Inlet Pipe - 400mm dia. Out let Pipe - 450mm dia. DI valves – 2 No’s Over Flow pipe - 450m dia. Scour Pipe - 200mm dia. c) For above 1500 KL to 2500 Kl ELSRs Inlet Pipe - 400mm dia. Out let Pipe - 500mm dia. DI valves – 2 No’s Over Flow pipe - 500m dia. Scour Pipe - 200mm dia. Note: Any deviation from the above sizes as per design, shall be paid or recovered. (iii) Manhole Frames & Covers a) All man hole Frames & Covers shall be made of CI/DI materials with min. size of 0.60mX 0.60m - For Roof & Valve Chambers. iv) CI/D.I Double Swan neck ventilators (min. of 150mm dia.) shall be provided in top dome and slab with mosquito/fly proof nets - 4Nos. v) RCC Finial ventilator with fly/bird protection with GI mesh - 1 No. vi) RCC precast ladders of 0.60 m width - 2 Nos. vii) RCC dog legged stair case of 1.00 m flight width and 1.20 m landing width R.C.C hand railing of 1.0 m height – 1 No
viii) The staircase shall be enclosed with brick masonry walls on three sides and collapsible MS gate on front side up to 1st brace level, to prevent unauthorized entry. ix) Construction of R.C.C valve chambers as per Standard Drawings with RCC cover slab fixed with CI/DI manhole Frame & Cover with lock and Key arrangement. The Mix shall not be less than VRCC M 20 grade with 150mm thick side walls, 150mm thick top slab, 150mm thick base slab over base course of 100mm thick (1:4:8) prop. x) Balcony of 1.00 m width at floor slab level / middle ring beam level by using Stainless Steel pipe of grade 304 hand railing up to 1.20 m height, with top railing of 40mm dia. pipe & middle railing of 25mm dia. and verticals with 40mm dia. at an interval not more than of 1.00m c/c. xi) Water Level Indicator of reputed make – Digital type (1 No) and Conventional type (1 No) xii) Lightening Arrestor with all its accessories complete including earthing, with relevant IS Codes - 1 No.
xiii) Compound wall: Construction of compound wall including ornamental M.S.Gate of size 3.0 X 2.40m is included in the basic rate of ELSRs. Length of compound wall hall is minimum of 150m. Min. height of the compound wall shall be 1.80m above plinth and thickness 230mm in brick masonry in CM (1:6).The compound wall shall be constructed including earth work excavation in all types of soils for plinth beam of 230mm X 300mm and 0.75X0.75X1.20m size for column footing portions. The footings shall be of 0.75X0.75X0.25m in VRCC M20 grade and constructed over a C.C (1:4:8) prop bed of 100mm thick. The columns shall be of 230X230 mm in size with VRCC M20 grade at 3.00m c/c spacing, having depth of 1.20m below ground level and height of 2.00m above GL. The plinth beam of size of 230X300 mm shall be constructed in VRCC M20 grade at Ground level, over a bed of CC(1:4:8)-100mmthick. 450X450mm size columns in M20 grade shall be constructed for gate pillars. All the materials shall be followed as per the standards. Tie beam shall be provided above the brick work with 230X200mm size, fixed with MS angular of 25mm X 25mm X 4mm in "Y" shape to height of 0.60m, with embedded length of 150mm in concrete. The barbed wire fencing with 3 ply of 18 gauges shall be stretched in 4 rows (2x2). Plastering shall be done with 16mm thick in two coats i.e., base coat 12mm thick in CM(1:6)prop and 4mm thick 2nd coat CM(1:4) prop on both sides of brick work.
Snowcem paint in two coats shall be provided for both sides of wall. The M.S ornamental gate as per the approved drawings shall be provided with minimum of 3.60mts width and 2.40mts height with enamel paint. Yard lighting shall be arranged on four corners of compound wall. If the length of the wall is increased/ decreased Note:-For every 1m increase/decrease in length of compound wall the increase/decrease in basic rates of ELSRs of the capacities from 500KL to 2500KL shall be as follows.: i)500 KL : 0.086% ii)1000 KL : 0.047% iii)1500 KL : 0.034% iv)2000 KL : 0.026% v)2500 KL : 0.022 % For intermediate capacities, interpolated percentages shall be adopted. xiv) Staff Quarter shall be constructed for a minimum plinth area of 40 Sqm with the following specification: RCC framed structure with concrete grade not less than M20 design mix at the locations specified by the department at the time of execution with veranda, hall, bed room, kitchen and bath &W/C with floor area of 40.00sqmts excluding balconies and staircases.
MS hollow door frame with cold rolled processed steel sheet 1.25mm thick bright CRCA conforming to IS 4351/76, Flush door shutters with solid bond wood bond board doors shall be provided. N.C.L. Windows centre fixed both sides open able shutter window 1.35 X 1.35mts outer frame section 48 x50mm shutter frame section with a size of 48 X20 mm mullion section of size 48 X 50mm fixed beading section of 12 X 12 mm shall be provided. Flooring with polished Kadapa stone shall be provided. Walls shall be provided with snowcem paint in two coats over primary coat. Electrical and water supply arrangement shall be provided as directed by dept officer. Water Storage tank made with plastic/polymer material of reputed make with necessary out let and inlet connection pipes shall provided. Septic tank for 5 users shall be provided.
Construction of 800 KL Capacity ELSR at YPC Junction with a staging of 20m ( Balance work)
Construction of 800 KL Capacity ELSR at YPC Junction with a staging of 20m ( Balance work) with Seismic analysis.
All concrete components shall be designed with M30 Design Mix proportion. The foundations shall be designed for Annular Raft Footings. The above rates are applicable for Elevated Level Services Reservoirs / OHSRs for SBC of 15 T/Sqm. For SBC below 10T/Sqm , solid raft shall be providedFor SBC below 10T/Sqm , solid raft shall be provided For SBC value of less than 5 T/Sqm, soil improvement shall be adopted, for which additional payment shall be made as per field condition. Rate inclusive of three coats of epoxy paint Food Grade of best quality to inner surface of the Reservoir including roof. b)The rate inclusive of 2 coats of weather proof emulsion painting for external surfaces, lettering, all required fixtures, Pipes, Pipe specials, valves of DI material, Valve chambers etc., for pipe connections including cost of pipes, specials and valves as per departmental designs and drawings. The above rates adopted for a wind pressure up to "250 kg/Sqm". The ELSR/OHSR shall be designed with minimum of two rows of columns for capacities above 500 KL & up to 1000KL. The ELSR/OHSR shall be designed with minimum of three rows of columns for capacities above 1000KL.
14. The shaft type staging with slip form can also be provided with proper approval from competent authority without any additional cost. 15) The basic rate is inclusive of following Fixtures i) Pipe connections & Specials with D.I materials (a) All pipe connections for Inlet, Out let, Over Flow, Scour pipes shall be provided with D/F DI material. (b) The Valves for above pipe connections also shall be of DI material of PN 16 duty confirming to the specification of SoR item No.28 (c) All specials such as Bends, Tees, Reducers, Duck foot Bends, Bell mouths etc,. Shall be of DI material. II) The sizes of the verticals for ELSR/OHSR shall be: a) For 500 KL to 750 Kl ELSRs Inlet Pipe - 300mm dia. Out let Pipe - 350mm dia. DI valves – 2 No’s Over Flow pipe - 350m dia. Scour Pipe - 200mm dia.
c) For above 1500 KL to 2500 Kl ELSRs Inlet Pipe - 400mm dia. Out let Pipe - 500mm dia. DI valves – 2 No’s Over Flow pipe - 500m dia. Scour Pipe - 200mm dia. Note: Any deviation from the above sizes as per design, shall be paid or recovered. (iii) Manhole Frames & Covers a) All man hole Frames & Covers shall be made of CI/DI materials with min. size of 0.60mX 0.60m - For Roof & Valve Chambers. iv) CI/D.I Double Swan neck ventilators (min. of 150mm dia.) shall be provided in top dome and slab with mosquito/fly proof nets - 4Nos. v) RCC Finial ventilator with fly/bird protection with GI mesh - 1 No. vi) RCC precast ladders of 0.60 m width - 2 Nos. vii) RCC dog legged stair case of 1.00 m flight width and 1.20 m landing width R.C.C hand railing of 1.0 m height – 1 No viii) The staircase shall be enclosed with brick masonry walls on three sides and collapsible MS gate on front side up to 1st brace level, to prevent unauthorized entry.
ix) Construction of R.C.C valve chambers as per Standard Drawings with RCC cover slab fixed with CI/DI manhole Frame & Cover with lock and Key arrangement. The Mix shall not be less than VRCC M 20 grade with 150mm thick side walls, 150mm thick top slab, 150mm thick base slab over base course of 100mm thick (1:4:8) prop. x) Balcony of 1.00 m width at floor slab level / middle ring beam level by using Stainless Steel pipe of grade 304 hand railing up to 1.20 m height, with top railing of 40mm dia. pipe & middle railing of 25mm dia. and verticals with 40mm dia. at an interval not more than of 1.00m c/c. xi) Water Level Indicator of reputed make – Digital type (1 No) and Conventional type (1 No) xii) Lightening Arrestor with all its accessories complete including earthing, with relevant IS Codes - 1 No.
xiii) Compound wall: Construction of compound wall including ornamental M.S.Gate of size 3.0 X 2.40m is included in the basic rate of ELSRs. Length of compound wall hall is minimum of 150m. Min. height of the compound wall shall be 1.80m above plinth and thickness 230mm in brick masonry in CM (1:6).The compound wall shall be constructed including earth work excavation in all types of soils for plinth beam of 230mm X 300mm and 0.75X0.75X1.20m size for column footing portions. The footings shall be of 0.75X0.75X0.25m in VRCC M20 grade and constructed over a C.C (1:4:8) prop bed of 100mm thick. The columns shall be of 230X230 mm in size with VRCC M20 grade at 3.00m c/c spacing, having depth of 1.20m below ground level and height of 2.00m above GL. The plinth beam of size of 230X300 mm shall be constructed in VRCC M20 grade at Ground level, over a bed of CC(1:4:8)-100mmthick. 450X450mm size columns in M20 grade shall be constructed for gate pillars. All the materials shall be followed as per the standards.
Tie beam shall be provided above the brick work with 230X200mm size, fixed with MS angular of 25mm X 25mm X 4mm in "Y" shape to height of 0.60m, with embedded length of 150mm in concrete. The barbed wire fencing with 3 ply of 18 gauges shall be stretched in 4 rows (2x2). Plastering shall be done with 16mm thick in two coats i.e., base coat 12mm thick in CM(1:6)prop and 4mm thick 2nd coat CM(1:4) prop on both sides of brick work. Snowcem paint in two coats shall be provided for both sides of wall. The M.S ornamental gate as per the approved drawings shall be provided with minimum of 3.60mts width and 2.40mts height with enamel paint. Yard lighting shall be arranged on four corners of compound wall. If the length of the wall is increased/ decreased Note:-For every 1m increase/decrease in length of compound wall the increase/decrease in basic rates of ELSRs of the capacities from 500KL to 2500KL shall be as follows.: i)500 KL : 0.086% ii)1000 KL : 0.047% iii)1500 KL : 0.034% iv)2000 KL : 0.026% v)2500 KL : 0.022 % For intermediate capacities, interpolated percentages shall be adopted.
xiv) Staff Quarter shall be constructed for a minimum plinth area of 40 Sqm with the following specification: RCC framed structure with concrete grade not less than M20 design mix at the locations specified by the department at the time of execution with veranda, hall, bed room, kitchen and bath &W/C with floor area of 40.00sqmts excluding balconies and staircases. MS hollow door frame with cold rolled processed steel sheet 1.25mm thick bright CRCA conforming to IS 4351/76, Flush door shutters with solid bond wood bond board doors shall be provided. N.C.L. Windows centre fixed both sides open able shutter window 1.35 X 1.35mts outer frame section 48 x50mm shutter frame section with a size of 48 X20 mm mullion section of size 48 X 50mm fixed beading section of 12 X 12 mm shall be provided. Flooring with polished Kadapa stone shall be provided. Walls shall be provided with snowcem paint in two coats over primary coat. Electrical and water supply arrangement shall be provided as directed by dept officer. Water Storage tank made with plastic/polymer material of reputed make with necessary out let and inlet connection pipes shall provided. Septic tank for 5 users shall be provided.
Construction of Local Scada Room 8.00 x 12.00 Size at WTP
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH for Manual Means.
Supply and filling with Sand complying with standard specifications including cost and conveyance of sand to site to work labour charges watering tamping, ramming etc complete and as directed by the Engineer-in-Charge of the work (APDSS No.101).
Laying Cement concrete (1:4:8) using 40mm nominal size HBG metal M/C including cost and conveyance of all materials from approved quarry, machine mixing, vibrating, laying, levelling, ramming, curing and labour charges etc., complete. as per SS and as directed by the departmental officer incharge of work.
Construction of RR Masonary in C.M (1: 6) prop. Using hard granite stone including cost and conveyance of all materials like cement, sand, water, Granite stone etc. including cost of seigniorage charges on all materials, all taxes including labour for cutting stones to required size and shape, mixing of cement mortar construction, Scaffolding charges etc. complete for finished item of work.
Plain Cement concrete (M 25) Nominal Mix using 20mm metal using concrete mixer including cost and conveyance of all materials like cement, fine aggregate (sand) coarse aggregate, water etc., to site and including Seigniorage charges, sales & other taxes on all materials including all operational, incidental and labour charges such as machine mixing, laying concrete, curing, centering, shuttering etc.,complete for Bed.
Plain Cement concrete (M 25) Nominal Mix using 20mm metal using concrete mixer including cost and conveyance of all materials like cement, fine aggregate (sand) coarse aggregate, water etc., to site and including Seigniorage charges, sales & other taxes on all materials including all operational, incidental and labour charges such as machine mixing, laying concrete, curing, centering, shuttering etc.,complete For Side Walls of Septic Tank.
Supply and placing of the RCC M - 25 Design Mix Concrete corresponding to IS 456 using MIXER with 20mm size graded machine crushed hard granite metal (coarse aggregate) from approved quarry including cost and conveyance of all materials like cement, fine aggregate (sand) coarse aggregate, water etc., to site and including Seigniorage charges, sales & other taxes on all materials including all operational, incidental and labour charges such as weigh batching, machine mixing, laying concrete, curing etc.,complete but excluding cost of steel and its fabrication charges for finished item of work (APSS No. 402)with minimum cement content as per IS code from standard suppliers approved by the department including pumping, centering, shuttering, laying concrete, vibrating, curing etc. complete but excluding cost of steel and its fabrication charges for finished item of work as follows.
Footings
Pedastals around Columns
Columns Up to plinth
Plinth Beams 300 x 400
Columns
Up to First Floor Roof Level
Beams 230 x 500
Lintels
Sunshades
Staircase slab 0.15 m thick
RCC Slab 150mm thick
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying including sales and other taxes on all materials etc., complete for finished item of work in all floors.( APSS No.126) for pre cast slabs of culverts - RBR-FNDN-8 & Revised Data sl.No-5
Brick Masonry in CM (1:6) for 230mm thick with 2nd class Bricks traditional size 23x11x7cms including cost and conveyance of materials to site, mixing of cement mortar and laying of bricks and mortar to specified thickness, watering and curing, scaffolding charges, etc complete for finished item of work (BLD-CSTN-3-1) as follows.
For Ground Floor Level
For First Floor Level
11.5 cm wide Brick masonry for super-structure on ground floor in cm (1:3) using second class traditional size bricks including cost of all materials, seigniorage charges, labour and all operations for constructing half brick masonry, mixing cement mortar, curing etc., complete for finished item of work, but excluding conveyance charges of materials.
Plastering with CM (1:4), 20 mm thick including cost and conveyance of all materials and water to work site and all operational incidental, labour charges such as scaffolding, mixing mortar lift charges curing etc., complete for finished item of work.
For Ground Floor
For First Floor
Plastering with CM (1:3), 12 mm thick including cost and conveyance of all materials and water to work site and all operational incidental, labour charges such as scaffolding, mixing mortar lift charges curing etc., complete for finished item of work.
Plastering with CM (1:3), 12 mm thick including cost and conveyance of all materials and water to work site and all operational incidental, labour charges such as scaffolding, mixing mortar lift charges curing etc., complete for finished item of work.
Flooring with 50 mm thick Rough Cuddapah/Shabad stones, set over base coat of cement mortar (1 : 8) 12 mm thick over CC bed already laid or RCC roof slab, including pointing with cement mortar 1:3 duly filling joints nearly, including cost of all materials like flooring stone, cement, sand, and water etc., complete, including seigniorage charges, labour charges for dressing of flooring stones etc., complete for finished item of work, but excluding the cost of conveyance of all materials.
Flooring with ceramic tiles, set over base coat of cement mortar (1:8), 12 mm thick over CC bed already laid or RCC roof slab, including neat cement slurry of honey like consistency spread @ 3.3.kgs per sqm & jointed neatly with white cement paste to full depth mixed with pigment of matching shade, including cost of all materials like cement, sand water and tiles etc., complete, including seigniorage charges, etc., complete for finished item of work, including the cost of conveyance of all materials.
Dadooing to walls with first quality glazed coloured tiles approved colour of any size set over base coat of C.M(1:3)prop. 12mm thick and neat grey cement slurry of honey like consistency spread at the rate of 3.3Kg of cement per sqm and jointed with neat white cement paste at 0.20 kg per sqm mixed with pigment of matching shade to match the shade of tiles including cost and conveyance of all materials labour charges, water to work site,seignourage and all operational .incidental , mixing mortar , fixing in position ,lift charges, curing etc., complete as per SS or as directed by the departmental authorities for finished item of work.
Painting Walls with two coat Snowcem or other equal and approved Water Proof Cement Paint over Priming Coat, 2 Coats (All Colours)
Painting Walls with two coat Snowcem or other equal and approved Water Proof Cement Paint over Priming Coat, 2 Coats (All Colours)
Painting Walls with two coat Snowcem or other equal and approved Water Proof Cement Paint over Priming Coat, 2 Coats (All Colours)
Providing & Fixing of Scientific Doors with metal door frames and door shutters made of galvanize steel (base steel as per IS 513 of 0.58 mm thick D quality, galvanized as per IS 277 with Zinc of 120 GSM) pure polyester powder upto 50-60 microns thick, outer frame section of 100 x 58 mm x 1.2 mm thick, shutter section of 0.80 mm thick galvanized steel sheet pressed (roll formed) for 46mm thick fully flush, double skin door shell seam joints at stile edges, in-fill of honeycomb kraft paper used to give the equired rigidity and effective acoustic insulation with 6” Tower bolt – 1 No., 6” D handles – 2 Nos., 10” Aldrop – 1 No., Butt Hinges – 3 Nos, Mortise Lock of approved quality – 1 No, frames fixed to the concrete/masonry wall by means of self expanding screws complete for finished item of work for Single leaf Door
Supply and fixing of pre-painted steel windows & top hung and fixed louvered ventilators made of pre - painted steel (base steel as per IS 513 of -0.58 mm thick 'D" quality, galvanized as per IS 277 with zinc of 120 GSM) primer coated with epoxy primer of 5-7 microns thick, finish painted with a polyester paint of 12-16 microns thick and back coated with 5-7 microns thick alkyd backer, section for outer frame of 46 x 52 mm section and for shutter of 46 x 46 mm section for mullion 46 x 70 mm, and section for beading should be 18 x 25 mm and section for louvered ventilation of 33 x 56 mm Box section and the windows panelled with 5 mm thick plain float glass & 4 mm pinhead glass for ventilators with Ethyl propylene Diamine monomer Gasket (EPDM) and the sections cut to length mitre joined with corner brocket centre mullions fixed using mullion cap and with handle made of high grade aluminium powder coated and nylon receiver, corner brackets made of CRCA with Zinc Phosphate, Mullion caps made of glass filled nylon, frames fixed to the concrete /masonry wall by means of self expanding screws including 10 mm square guard bars with 6" pitch complete for finished item of work.
Providing & fixing 30 mm thick solid panel PVC door shutter consisting of frame made out of 19 guage M.S tube of 19 x 19 mm for stiles, top & bottom rail, with a coat of primer of approved make. M.S. Frame covered with 5 mm thick heat moulded PVC “C” channel of size of 30 x 50 mm forming stiles, 5 mm thick 75 mm wide PVC sheet for top, lock & bottom rail on either side 20 mm wide cross PVC sheet as gap insert for top & bottom rail, panelling of 10mm(+/-)( 5mm+5mm)” thick PVC sheet fitted in the M.S. frame welded /sealed to the stiles, on either side joined together with solvent cement adhesive etc., additional 5 mm thick PVC strip of 20 mm width stuck on the interior side of the C channel using solvent cement, complete as per direction of Engineer–in–charge, manufacturers specification. (SoR 2018-19, BMT-N.51).
Supplying and fixing of Top Hung Ventilators made of pre - painted steel (base steel as per IS 513 of -0.58 mm thick 'D" quality, galvanized as per IS 277 with zinc of 120 GSM) primer coated with epoxy primer of 5-7 microns thick, finish painted with a polyester paint of 12-16 microns thick and back coated with 5-7 microns thick alkyd backer, section for outer frame of 46 x 52 mm section and for shutter of 46 x 46 mm section for mullion 46 x 70 mm, The Ventilator to be panelled 4 mm pinhead glass with Ethyl propylene Diamine monomer Gasket (EPDM) and the sections cut to length mitre joined with corner brocket mullions fixed using mullion cap and with handle made of high grade aluminium powder coated and nylon receiver, corner brackets made of CRCA with Zinc Phosphate, Mullion caps made of glass filled nylon, frames fixed to the concrete /masonry wall by means of self expanding screws including 10 mm square guard bars with 6" pitch complete for finished item of work
Providing and fixing Thermocole False ceiling in true horizontal level 600 mm x 600 mm using 15 mm/ 19 mm thick Thermocole sheet anodised Aluminium Tee sections of size 24.50 mm x 24.0 mm x 2.4 mm in grid with cross tee of size 24 x 24.5 mm at every 600 mm c/c and anodised aluminium wall angle of size 24 x 24 mm fixed to periphery of the wall and the above grid is suspended at every 1200 mm c/c in both directions using 2.0 mm thick GI Wire for finished of size 600 x 600 mm including Cost &conveyance of all materials and labour charges such as cutting , fixing of standing of frame work exposing roof making complete for finished item of work
Supply and fixing of 25 mm dia 2.00 mm thick PVC pipe concealed in roof slab with all required accessories including masonary work all labour chages
Supply and fixing of 20 mm dia 1.50 mm thick PVC pipe concealed in walls with all required accessories including masonary work for light , fan and plug point with metal deep box including all labour chages
Wiring with 2 runs 14/0.3 mm. (1.0. sq.mm) Fire retardant PVC insulated Flexible copper cable in existing pipe with 6A siwtch, ceiling rose and 3 mm thick hyla sheet covering to switch control box including all labour charges etc,., complete for light, bell , fan and exhaust fan points in non - residential building
Wiring with 2 runs 14/0.3 mm. (1.0. sq.mm) Fire retardant PVC insulated Flexible copper cable in existing pipe with 6A modular siwtch control and 3/2 pin sockets fixing on board including all labour charges
supply and run of 2 of 36/0.3 mm. (1.5. sq.mm) Fire retardant PVC insulated Flexible copper cable in existing pipe for mains including all labour charges
supply and run of 1 of 14/0.3 mm. (1.0. sq.mm) Fire retardant PVC insulated Flexible copper cable in existing pipe for earth continuity including all labour charges etc.
supply and run of 4 of 6 sq.mm (7/18) WPSC alluminium cable along with No.10 SWG G.I barer wire through PVC cleats with all accessories including all labour charges etc.,
Providing independent earthing by excavating a trench to a depth of 2.10m in all soils, as per size specied in data ,using 40 mm dia B class GI pipe 2.50m long with necessary accessories with hume pipe ring duly providing staggered holes including filling with equal proportion of salt and charcoal in layers and all labour charges etc complete
Supply and fixing TPN Distribution board with IP-30 protection suitable for 3 phase ELCB / RCCB / FP Isolator as incomer and 10kA SP MCBs as outing going including internal connection and labour charges for surface / flush mounting etc., complete.BLD-ELEC-4.4.3
Supply and fixing of 48" (1200mm) Sweep Ceiling Fan without Regulator.of makes Crompton High Speed / Bajaj Ultima / Havells Velocity / Usha Astra / Orient Summer Pride
Supply of stepped type Electronic Regulator of makes GM G Home / Gold Medal Olive / Million Zoom / Anchor Penta Cherry / Great white Omega
Supply and transportation of 20W, 2000 lumens, T8,1200mm length LED retro tube light,wide operating voltage with double side connection, PF≥0.9,Surge protection: > 2KV, THD<15%, with inbuilt driver and frosted cover CCT: 3000K - 6500K as desired by the department and as per IS specifications, minimum CRI≥80,.etc complete with 5 years as per IE Rules and as directed by the departmental officer incharge of work warranty.LUMINAIRE MAKE: Phillips / OSRAM / GE / Crompton /VIN / Bajaj / Havells / Halonix / HPL. LED MAKE : PHILIPS LUMILEDS / CREE / NICHIA /OSRAM / SAMSUNG / LG LEDs.
Labour charges for Fixing of Ceiling fan and regulator including transportation and giving connections with twin core wire etc., complete
Labour charges for Fixing of towtube light luminaiu on wall / ceiling with tw ground blockes well all accsseries includeing giving connections with twin core wire etc., complete
Supply and fixing of 16A 3/2 pin flush type wall plug modular socket with shutter and 16A modular switche controll on a common switch board with earth continuity including wire leads, earth connections along with all labour charges etc., complete. Makes of Switches : GM G Home /Anchor Penta Cherry / Gold Madel Olive / Million Zoom / Great White
Supply of 2.0 TR 5 Star capable of delivering 24000 BTU/ hr and above with operating on refrigerant R-32 / R-410A AC unit with high wall mounted indoor unit and outdoor condencing unit Hermetically sealed compressor suitable for operation on 230V, 50Hz, 1Phase AC supply capable of performing cooling dehumidifying air circulating and filtering with cooling and condensing units with 3 mts of copper piping, insulation kit and 4 mts of 3 core copper flexible cable including cordless remote control etc.as per IE Rules and as directed by the departmental officer incharges of work
Providing & Placing on Terrace (at all floor levels) polyethylene water storage tank with Double layer approved brand & manufacture with cover and suitable locking arrangement & making necessary holes for inlet & outlets and over flow pipes but without fittings & base support for tanks
Supplying and fixing 580mm x 440mm long Orissa pan white glazed Water Closet 1st quality ISI marked confirming to IS:2556-Part-3-1981 with "P" or "S" trap, ISI marked and providing masonry seat, CC squatting plate and 10 litres capacity single flush PVC low level cistern with internal components fixed on 2 Nos. of teak wood blocks of size 76.20mm x 101.60mm using required size of nails, screws as approved by Engineer-in-charge, 15 mm nominal size CP finish brass angled stop valve screw type with internal /external threaded conforming to IS 8931, 12.70mm PVC connection with brass union nuts CP coated , 31.75mm brass plumber union, P trap or S trap of Indian W.C. shall be encased on CC (1:2:4) 150mm alround well above the joint to stop leakage at the joint etc., complete including cost and conveyance of all materials to site, cost of CC bed, labour charges and seigniorage charges, overheads & contractors profit etc., complete for finished item of work
SSupplying and fixing Indian make Flat Back Wash Hand Basin 1st quality conforming to IS:2556-Part-4:1972 of size 550mm x 400mm with 32 mm nominal size C.P. Fitting with parallel pipe thread conforming to IS:2963-1979 and fitted with 15 mm nominal bore Chromium Plated Pillar Tap of 1st quality Indian make heavy duty complete with standard CI brackets including wooden blocks ,1 No.12.70mm PVC connection with brass union nuts CP coated , angle stop cock 12.70mm dia. first quality Indian make heavy duty, 30mm dia. PVC flexible waste pipe 914.4mm length of 1st quality including cost and conveyance of all materials to site, labour charges , overheads & contractors profit for finished item of work
Supplying and fixing CP finish brass soap dish of approved make ISI quality including cost and conveyance of all materials, labour charges for fixing , overheads & contractors profit for finished item of work in all floors
Supplying and fixing TV shape mirror with plastic frame of size 609.6mm x 457.2mm , plywood back with NP screws 1st quality including cost and conveyance of all materials, labour charges , overheads & contractors profit for finished item of work in all floors.
Supplying and fixing of 25.4mm dia , 609.6mm long aluminium anodized towel rods with brackets and aluminium screws including cost and conveyance of all materials, labour charges , overheads & contractors profit for finished item of work.
Supplying and fixing white glazed flat back Bowl urinals of size 440 mm x 265 mm x 315 mm with integral flushing rim fixed with screws complete Indian make (HSW/Parry/Neycer) conforming to IS:2556-1995 as approved by Engineer-in-charge, including supply and fixing 12.7mm PVC connection with brass plumber union nuts CP coated, 12.70mm push cock 1st quality of approved make , 30mm dia PVC flexible waste pipe of 914.4 mm length of Ist quality including cost and conveyance of all materials to site, labour charges , overheads & contractors profit complete for finished item of work for all floors
Supply of 110 mm dia 3 m single Socket PVC/SWR pipe - 6 Kg/sq.cm - Prince/Sudhakar/Kisan/Supreme or any ISI Brand.
Supply of 110 mm dia - Plain Bend 87.5 Degree - UPVC/SWR Pipe fittings (Prince/Sudhakar/Kisan/Supreme or any ISI Brand)
Supply of 110 mm dia - Coupler - UPVC/SWR Pipe fittings (Prince/Sudhakar/Kisan/Supreme or any ISI Brand
Labour charges for laying, fixing and commissioning the PVC pipes including couplers/ bends/ tees etc any diameter including fixing necessary fittings like bends, plugs, couplers, junctions, tees, etc with solvent jointing as per standard practice
Constructing 457.2 mm x 457.2 mm (1'6"x1'6") brick in CM 1:6 prop. Masonry. Inspection chamber up to 914.4 mm (3'0") and fitted with light weight 457.2 mm x 457.2 mm (1'6"x1'6") C.I frame and cover of 20 Kg as per SS and as directed by the departmental officer incharge of work
S& F GI pipe Medium Grade properties & weight as per IS 1239 ISI mark with GI fittings including the cost of pipe & its fittings & labour charges complete as follows
25 mm dia nominal bore -from tank to jn for of individual lines and inlet
20 mm dia nominal bore -from jn for of individual lines to toilets
15 mm dia nominal bore -for internal
S&F of GI & GM fittings
GM Ball valve with SS Ball and SS Spindle as per IS - Class - I, Indian make heavy type - 25 mm NB Size
GM Ball valve with SS Ball and SS Spindle as per IS - Class - I, Indian make heavy type - 20 mm NB Size
GM Ball valve with SS Ball and SS Spindle as per IS - Class - I, Indian make heavy type - 15 mm NB Size
S&F 12.7 mm N.P bib tap Indian make heavy dutys Seiko/ Senior/ Nice or equivalent
S& F GI union Ist Quality
Carting away the surplus excavated materials i.e., earth from the site to a suitable distance of about 5 kms including loading, unloading, conveyance charges and dumping the carted materials at the contractors cost, labour charges, all leads and lifts, all other incidental and operational charges etc complete
Providing Environmanagement Plan
Monitoring Costs : Construction Phase (Two years)
Air Quality Monitoring (4 Monitoring station) once in a month for three seasons during the construction period at Intake well, WTP, GLBR, ELSR's, Raw/Clear Pipe Line & Distribution network. This rate including cost of all labour charges other incidental charges etc complete
Noise level (4 Monitoring station) once in a month for three seasons during the construction period Intake well, WTP, GLBR, ELSR's, Raw/Clear Pipe Line & Distribution network. This rate including cost of all labour charges other incidental charges etc complete
Water Quality Monitoring surface / ground (4 Monitoring station) once in a month for three seasons during the construction period at Intake well, WTP, GLBR, ELSR's, Raw/Clear Pipe Line & Distribution network. This rate including cost of all labour charges other incidental charges etc complete
Compensatory plantation and three years maintenance (Compensatory afforestation ratio is 1:5)-plants & tree guards. This rate including cost of all labour charges other incidental charges etc complete
Sprinkling of water once in a day for two years (excluding rainy days):. This rates including cost of water, transportion charges charges wages of driver, fuil charge, and other incidental charge etc.,
Hiring for 1 Nos. Vehicles for 24 Months during execution period including hire charges of vehicle, diesel, lubrication, driver charges, repairs and all incidental charges etc.,
Providing HDPE/ DI Distribution net work in Zone-1 area
Earth work excavation in all soils up to SDR & stone matrix by machinery for Pipe lines as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and back filling in trenches with excavated suitable material as per Technical Specification No.305 MORD/304 MORTH up to initial lift of 3.0m. For Pipe line trenches.
Machenical mans 70%
Manual means 30%
Supply and filling with Sand complying with standard specifications including cost and conveyance of sand to site to work labour charges watering ramming other incidental charge etc complete and as directed by the Engineer-in-Charge of the work.
Manufacture, supply and delivery of PE 100-PN 6 HDPE pipes confirming to IS 4984-1995 including transportation to work spot, stacking including etc. complete as per S.S and as directed by the departmental officer incharge of work.
110mm dia.
160mm dia.
200mm dia.
250mm dia.
Manufacture, supply, & delivery of HDPE fittings conforming to IS 4984 - 1995 including transportation to work spot, stacking excluding all taxes and duties etc.complete
a) Pipe ends - long neck
110mm dia.
110 mm dia for Air TEEs
160mm dia.
160 mm dia for Air TEEs
200mm dia.
200 mm dia for Air TEEs
b) MS Flanges
110mm dia.
110 mm dia for Air TEEs
160mm dia.
160 mm dia for Air TEEs
200mm dia.
200 mm dia for Air TEEs
c) End Caps
110mm dia.
160mm dia.
200mm dia.
250mm dia.
d) Reducers
110X125 mm dia
125x140 mm dia
140x160 mm dia
160x180 mm dia
180x200 mm dia
e) TEES
110mm dia.
160mm dia.
200mm dia.
250mm dia.
F)Bends
110mm dia.
160mm dia.
200mm dia.
250mm dia.
Lowering, laying and jointing of HDPE pipes and jointing by butt fusion welding as per IS 7634-part-II/1975 as amended from time to time to the alignment and gradient and testing the pipeline to required pressure etc.complete as per S.S and as directed by the departmental officer incharge of work
110mm dia.
160mm dia.
200mm dia.
250mm dia.
Supply and delivery of DI Pipes and fittings (Specials) confirming to specification No.I.S.No. 7181/1986, 5531/1988, 3950/1979 including VAT and other duties including transportation and conveyance to work spot and stacking etc., complete as per S.S and as directed by the departmental authorities as follows
DIDF pipes for scours
100X2.00m on 110 and 160 mm dia mains for scours
100x1.00m long DF pipes for sluice valves
150 mm dia x2.00m on 200 and 250 mm dia pipes for scours
150x1.00m long DF pipes for sluice valves
200 mm dia x2.00m on 315 and 355 mm dia pipes for scours
200x1.00m long DF pipes for sluice valves
250x1.00m long DF pipes for sluice valves
100 mm dia deck foot bends
100x100x80 mm DIDF TEE for air valves
supply and delivery of "Resilient Seated Soft Sealing" Gate Valves (Sluice Valves) with Body and Bonnet of Ductile Iron GGG-40/SG-400/15 or GGG-50/SG-500/7 or Equivalent as per IS1865, IS:3896-2 and Wedge fully Rubber Lined with food grade quality grade W270 grade EPDM, Replaceable Spindle Nut without gland packing with 3-O ring protection system on the Shaft and Seals of NBR. The Valves should be Vacuum tight and 100% leak proof with face to face dimensions as BS:5163 Type A/IS:14846. All the valves should be with fusion bonded Electrostatic Powder coating both inside and outside (Min 250 Microns)- RAL 5005 with Pocket Less Straight through body Passage conforming to Design standards of DIN-3202F4/BS:5163 Type A Flange drilling as per IS - 1538 and including transportation. PN16 - as per SS and directed by the departmental officer incharge of work as follows.
100 mm distrubution
150mm dia for distrubution
200mm dia for distrubution
250mm dia for distrubution
for scour
100mm dia on 110 mm and 160 mm dia mains
150 mm dia on 200 and 250 mm dia lines
Manufacture, supply and delivery of Single Chamber DI Air Valve with Body and cover in Ductile Iron of grade SG 400/12 or equivalent grade as per I.S.3896-part2-1985 and subsequent revisions. All internal parts such as float, shell etc., all cover bolts, of stainless steel, and Gaskets and seals of EPDM food grade quality Epoxy powder coating (EP-P) inside and outside colour blue. Drilled as per IS:1538. PN16
80 mm dia on 110 mm pipe
80 mm dia on 160 mm pipe
80mm dia 200 mm pipe
80mm dia 250 mm pipe
Labour charges for lowering and keeping in position of D.I. Sluice valves, reflux valves and scour valves.
100 mm distrubution
150mm dia for distrubution
200mm dia for distrubution
250mm dia for distrubution
for scour
100mm dia on 110 mm and 160 mm dia mains
150 mm dia on 200 and 250 mm dia lines
Construction of sluice and scour Valve Chamber as per type design drawing with CC including, plastering, RCC cover slabs Earth work execavation, sand bedding, VCC 1:4:8 etc. including cost and conveyance of all material and all labour charges other incidental charges as per approved type design etc. complete as per S.S for finished item of work
100 mm distrubution
150mm dia for distrubution
200mm dia for distrubution
250mm dia for distrubution
for scour
100mm dia on 110 mm and 160 mm dia mains
150 mm dia on 200 and 250 mm dia lines
Construction of Air Valve Chamber as per type design drawing with CC including, plastering, RCC cover slabs as over land etc. including cost and conveyance of all material and all labour charges etc. complete as per S.S for finished item of work
80 mm dia on 110 mm pipe
80 mm dia on 160 mm pipe
80mm dia 200 mm pipe
Lowering the C.I. Pipes, D.I. Pipes of all classes and fittings with flanged ends carefully into the trenches and laying them true to alignment and gradient including all sundries, but excluding conveyance from source of supply as per BIS No.3114/94 as follows
150 mm dia
200 mm dia
Jointing the C.I. Pipes, fittings and valves with flanged ends including cost of jointing materials such as bolts, nuts, rubber insertion, white lead and including filling with water with a water lead upto 500 m and testing to required pressure etc., comp as per BIS No.3114/85.
100 mm dia
150 mm dia
200 mm dia
250 mm dia
Cutting BT road surface as well as asphalt (75mm thick) including water bound. The rate including labour charges for cutting, incidental charges etc., complete as directed by the departmental officer in charge of the work.
Cutting the CC road surface for pipeline trech portion . The rate including labour charges for cutting, incidental charges etc., complete as directed by the departmental officer in charge of the work.
Cutting the open water bound macadam. The rate including labour charges for cutting, incidental charges etc., complete as directed by the departmental officer in charge of the work.
Collection, Supply and filling of Stone dust / Quarry spall from approved quarry to work site and stacking at work site for pre measurements including cost and convenyance of all material and all labour charges etc. complete for road restoration
BLD-CSTN-3-11-(28) Using Concrete mixture up to Plinth Level : Plain Cement concrete nominal mix M-20 (Cement : fine aggregate: coarse aggregate ) using 20mm size Hard Granite Machine Crushed Graded Metal including cost and conveyance of all materials like cement, sand, coarse aggregate water etc., to site , seigniorage charges on all materials, labour charges , for mixing , laying, concrete , ramming in 15 cm layers, finishing top surface to the required level curing etc., complete for finished item of work with nomonal reinforcement for Road restoration.
Providing HDPE/ DI Distribution net work in Zone-2 area
Earth work excavation in all soils up to SDR & stone matrix by machinery for Pipe lines as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and back filling in trenches with excavated suitable material as per Technical Specification No.305 MORD/304 MORTH up to initial lift of 3.0m. For Pipe line trenches.
Machenical mans 70%
Manual means 20%
Filling inpipe line trenches as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH sand filling
Manufacture, supply and delivery of PE 100-PN 6 HDPE pipes confirming to IS 4984-1995 including transportation to work spot, stacking including all taxes etc. complete as per S.S and as directed by the departmental officer incharge of work.
110mm dia.
160mm dia.
200mm dia.
250mm dia.
Manufacture, supply, & delivery of HDPE fittings conforming to IS 4984 - 1995 including transportation to work spot, stacking etc.complete as per SS and as directed by the departmental officer incharge of work.
a) Pipe ends - long neck
110mm dia.
110 mm dia for Air TEEs
160mm dia.
160 mm dia for Air TEEs
200mm dia.
200 mm dia for Air TEEs
b) MS Flanges
110mm dia.
110 mm dia for Air TEEs
160mm dia.
160 mm dia for Air TEEs
200mm dia.
200 mm dia for Air TEEs
c) End Caps
110mm dia.
160mm dia.
200mm dia.
d) Reducers
110X125 mm dia
125x140 mm dia
140x160 mm dia
160x180 mm dia
180x200 mm dia
e) TEES
110mm dia.
160mm dia.
200mm dia.
250mm dia.
F)Bends
110mm dia.
160mm dia.
200mm dia.
250mm dia.
Lowering, laying and jointing of HDPE pipes and jointing by butt fusion welding as per IS 7634-part-II/1975 as amended from time to time to the alignment and gradient and testing the pipeline to required pressure etc.complete as per S.S and as directed by the departmental officer incharge of work
110mm dia.
160mm dia.
200mm dia.
250mm dia.
Supply and delivery of DI Pipes and fittings (Specials) confirming to specification No.I.S.No. 7181/1986, 5531/1988, 3950/1979 including VAT and other duties including transportation and conveyance to work spot and stacking etc., complete as per S.S and as directed by the departmental authorities.
DIDF pipes for scours
100X2.00m on 110 and 160 mm dia mains for scours
100x1.00m long DF pipes for sluice valves
150 mm dia x2.00m on 200 and 250 mm dia pipes for scours
150x1.00m long DF pipes for sluice valves
200x1.00m long DF pipes for sluice valves
250x1.00m long DF pipes for sluice valves
100 mm dia deck foot bends
100x100x80 mm DIDF TEE for air valves
supply and delivery of "Resilient Seated Soft Sealing" Gate Valves (Sluice Valves) with Body and Bonnet of Ductile Iron GGG-40/SG-400/15 or GGG-50/SG-500/7 or Equivalent as per IS1865, IS:3896-2 and Wedge fully Rubber Lined with food grade quality grade W270 grade EPDM, Replaceable Spindle Nut without gland packing with 3-O ring protection system on the Shaft and Seals of NBR. The Valves should be Vacuum tight and 100% leak proof with face to face dimensions as BS:5163 Type A/IS:14846. All the valves should be with fusion bonded Electrostatic Powder coating both inside and outside (Min 250 Microns)- RAL 5005 with Pocket Less Straight through body Passage conforming to Design standards of DIN-3202F4/BS:5163 Type A Flange drilling as per IS - 1538 excluding all taxes, duties and including transportation. PN16 - as directed by the departmental officer incharge of work.
100 mm distrubution
150mm dia for distrubution
200mm dia for distrubution
100mm dia on 110 mm and 160 mm dia mains
Manufacture, supply and delivery of Single Chamber DI Air Valve with Body and cover in Ductile Iron of grade SG 400/12 or equivalent grade as per I.S.3896-part2-1985 and subsequent revisions. All internal parts such as float, shell etc., all cover bolts, of stainless steel, and Gaskets and seals of EPDM food grade quality Epoxy powder coating (EP-P) inside and outside colour blue. Drilled as per IS:1538. PN16
80 mm dia on 110 mm pipe
80 mm dia on 160 mm pipe
80mm dia 200 mm pipe
80mm dia 250 mm pipe
Labour charges for lowering and keeping in position of D.I. Sluice valves, reflux valves and scour valves and as directed by the departmental officer incharge of work.
100 mm distrubution
150mm dia for distrubution
200mm dia for distrubution
100mm dia on 110 mm and 160 mm dia mains
Construction of R.C.C valve chambers as per Standard Drawings with RCC cover slab fixed with CI/DI manhole Frame & Cover with lock and Key arrangement. The Mix shall not be less than VRCC M 20 grade with 150mm thick side walls, 150mm thick top slab, 150mm thick base slab over base course of 100mm thick (1:4:8) propall material and all labour charges etc. complete as per S.S for finished item of work
100 mm distrubution
150mm dia for distrubution
200mm dia for distrubution
250mm dia for distrubution
100mm dia on 110 mm and 160 mm dia mains
150 mm dia on 200 and 250 mm dia lines
Construction of Air Valve Chamber as per type design drawing with CC including, plastering, RCC cover slabs etc. including cost and conveyance of all material and all labour charges etc. complete as per S.S for finished item of work
80 mm dia on 110 mm pipe
80 mm dia on 160 mm pipe
80mm dia 200 mm pipe
Lowering the C.I. Pipes, D.I. Pipes of all classes and fittings with flanged ends carefully into the trenches and laying them true to alignment and gradient including all sundries, but excluding conveyance from source of supply as per BIS No.3114/94.
150 mm dia
200 mm dia
250 mm dia
Jointing the C.I. Pipes, fittings and valves with flanged ends including cost of jointing materials such as bolts, nuts, rubber insertion, white lead and including filling with water with a water lead upto 500 m and testing to required pressure etc., comp as per BIS No.3114/85.
100 mm dia
150 mm dia
200 mm dia
250 mm dia
Cutting BT road surface as well as asphalt (75mm thick) including water bound. The rate including labour charges for cutting, incidental charges etc., complete as directed by the departmental officer in charge of the work.
Cutting the CC road surface for pipeline trench cutting portion. The rate including labour charges for cutting, incidental charges etc., complete as directed by the departmental officer in charge of the work.
Cutting the open water bound macadam for pipeline trench cutting portion. The rate including labour charges for cutting, incidental charges fixing of machinery, fuil charge, wage of driver other incidental charge etc., complete as directed by the departmental officer in charge of the work.
Collection, Supply and filling of Stone dust / Quarry spall from approved quarry to work site and stacking at work site for pre measurements including cost and convenyance of all material and all labour charges etc. complete for road restoration
BLD-CSTN-3-11-(28) Using Concrete mixture up to Plinth Level : Plain Cement concrete nominal mix M-20 (Cement : fine aggregate: coarse aggregate ) using 20mm size Hard Granite Machine Crushed Graded Metal including cost and conveyance of all materials like cement, sand, coarse aggregate water etc., to site , seigniorage charges on all materials, labour charges , for mixing , laying, concrete , ramming in 15 cm layers, finishing top surface to the required level curing etc., complete for finished item of work with nomonal reinforcement for Road restoration.
Providing HDPE/ DI Distribution net work in Zone-3 area
Earth work excavation in all soils up to SDR & stone matrix by machinery for Pipe lines as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and back filling in trenches with excavated suitable material as per Technical Specification No.305 MORD/304 MORTH up to initial lift of 3.0m. For Pipe line trenches.
Machenical mans 70%
Manual means 20%
Supply and filling with Sand complying with standard specifications including cost and conveyance of sand to site to work labour charges watering ramming other incidental charge etc complete and as directed by the Engineer-in-Charge of the work.
Manufacture, supply and delivery of PE 100-PN 6 HDPE pipes confirming to IS 4984-1995 including transportation to work spot, stacking including all taxes etc. complete as per S.S
110mm dia.
160mm dia.
200mm dia.
250mm dia.
Manufacture, supply, & delivery of HDPE fittings conforming to IS 4984 - 1995 including transportation to work spot, stacking excluding all taxes and duties etc.complete as directed by the departmental other incidental incharge of work.
a) Pipe ends - long neck
110mm dia.
110 mm dia for Air TEEs
160mm dia.
160 mm dia for Air TEEs
200mm dia.
200 mm dia for Air TEEs
250mm dia.
b) MS Flanges
110mm dia.
110 mm dia for Air TEEs
160mm dia.
160 mm dia for Air TEEs
200mm dia.
200 mm dia for Air TEEs
250mm dia.
c) End Caps
110mm dia.
160mm dia.
200mm dia.
d) Reducers
110X125 mm dia
125x140 mm dia
140x160 mm dia
160x180 mm dia
180x200 mm dia
e) TEES
110mm dia.
160mm dia.
200mm dia.
250mm dia.
F)Bends
110mm dia.
160mm dia.
200mm dia.
250mm dia.
Lowering, laying and jointing of HDPE pipes and jointing by butt fusion welding as per IS 7634-part-II/1975 as amended from time to time to the alignment and gradient and testing the pipeline to required pressure etc.complete as per S.S and as directed by the departmental officer incharge of work
110mm dia.
160mm dia.
200mm dia.
250mm dia.
Supply and delivery of DI Pipes and fittings (Specials) confirming to specification No.I.S.No. 7181/1986, 5531/1988, 3950/1979 including VAT and other duties including transportation and conveyance to work spot and stacking etc., complete as per S.S and as directed by the departmental authorities.
DIDF pipes for scours
100X2.00m on 110 and 160 mm dia mains for scours
100x1.00m long DF pipes for sluice valves
150 mm dia x2.00m on 200 and 250 mm dia pipes for scours
150x1.00m long DF pipes for sluice valves
200x1.00m long DF pipes for sluice valves
250x1.00m long DF pipes for sluice valves
100 mm dia deck foot bends
100x100x80 mm DIDF TEE for air valves
supply and delivery of "Resilient Seated Soft Sealing" Gate Valves (Sluice Valves) with Body and Bonnet of Ductile Iron GGG-40/SG-400/15 or GGG-50/SG-500/7 or Equivalent as per IS1865, IS:3896-2 and Wedge fully Rubber Lined with food grade quality grade W270 grade EPDM, Replaceable Spindle Nut without gland packing with 3-O ring protection system on the Shaft and Seals of NBR. The Valves should be Vacuum tight and 100% leak proof with face to face dimensions as BS:5163 Type A/IS:14846. All the valves should be with fusion bonded Electrostatic Powder coating both inside and outside (Min 250 Microns)- RAL 5005 with Pocket Less Straight through body Passage conforming to Design standards of DIN-3202F4/BS:5163 Type A Flange drilling as per IS - 1538 and including transportation. PN16 -
100 mm distrubution
150mm dia for distrubution
200mm dia for distrubution
250mm dia for distrubution
for scour
100mm dia on 110 mm and 160 mm dia mains
150 mm dia on 200 and 250 mm dia lines
Manufacture, supply and delivery of Single Chamber DI Air Valve with Body and cover in Ductile Iron of grade SG 400/12 or equivalent grade as per I.S.3896-part2-1985 and subsequent revisions. All internal parts such as float, shell etc., all cover bolts, of stainless steel, and Gaskets and seals of EPDM food grade quality Epoxy powder coating (EP-P) inside and outside colour blue. Drilled as per IS:1538. PN16 as follows
80 mm dia on 110 mm pipe
80 mm dia on 160 mm pipe
80mm dia 200 mm pipe
80mm dia 250 mm pipe
Labour charges for lowering and keeping in position of D.I. Sluice valves, reflux valves and scour valves.
100 mm distrubution
150mm dia for distrubution
200mm dia for distrubution
250mm dia for distrubution
for scour
100mm dia on 110 mm and 160 mm dia mains
150 mm dia on 200 and 250 mm dia lines
Construction of R.C.C valve chambers as per Standard Drawings with RCC cover slab fixed with CI/DI manhole Frame & Cover with lock and Key arrangement. The Mix shall not be less than VRCC M 20 grade with 150mm thick side walls, 150mm thick top slab, 150mm thick base slab over base course of 100mm thick (1:4:8) prop all material and all labour charges etc. complete as per S.S for finished item of work
100 mm distrubution
150mm dia for distrubution
200mm dia for distrubution
250mm dia for distrubution
for scour
100mm dia on 110 mm and 160 mm dia mains
150 mm dia on 200 and 250 mm dia lines
Construction of Air Valve Chamber as per type design drawing with CC including, plastering, RCC cover slabs etc. including cost and conveyance of all material and all labour charges etc. complete as per S.S for finished item of work
80 mm dia on 110 mm pipe
80 mm dia on 160 mm pipe
80mm dia 200 mm pipe
Lowering the C.I. Pipes, D.I. Pipes of all classes and fittings with flanged ends carefully into the trenches and laying them true to alignment and gradient including all sundries, but excluding conveyance from source of supply as per BIS No.3114/94.
150 mm dia
200 mm dia
250 mm dia
Jointing the C.I. Pipes, fittings and valves with flanged ends including cost of jointing materials such as bolts, nuts, rubber insertion, white lead and including filling with water with a water lead upto 500 m and testing to required pressure etc., comp as per BIS No.3114/85.
100 mm dia
150 mm dia
200 mm dia
250 mm dia
Cutting BT road surface as well as asphalt (75mm thick) including water bound. The rate including labour charges for cutting, incidental charges etc., complete as directed by the departmental officer in charge of the work.
Cutting the CC road surface. The rate including labour charges for cutting, incidental charges etc., complete as directed by the departmental officer in charge of the work.
Cutting the open water bound macadam. The rate including labour charges for cutting, incidental charges etc., complete as directed by the departmental officer in charge of the work.
Collection, Supply and filling of Stone dust / Quarry spall from approved quarry to work site and stacking at work site for pre measurements including cost and convenyance of all material and all labour charges etc. complete for road restoration
BLD-CSTN-3-11-(28) Using Concrete mixture up to Plinth Level : Plain Cement concrete nominal mix M-20 (Cement : fine aggregate: coarse aggregate ) using 20mm size Hard Granite Machine Crushed Graded Metal including cost and conveyance of all materials like cement, sand, coarse aggregate water etc., to site , seigniorage charges on all materials, labour charges , for mixing , laying, concrete , ramming in 15 cm layers, finishing top surface to the required level curing etc., complete for finished item of work with nomonal reinforcement for Road restoration.
Providing HDPE/ DI Distribution net work in Zone-4 area
Earth work excavation in all soils up to SDR & stone matrix by machinery for Pipe lines as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and back filling in trenches with excavated suitable material as per Technical Specification No.305 MORD/304 MORTH up to initial lift of 3.0m. For Pipe line trenches.
Machenical mans 70%
Manual means 20%
Supply and filling with Sand complying with standard specifications including cost and conveyance of sand to site to work labour charges watering ramming other incidental charge etc complete and as directed by the Engineer-in-Charge of the work.
Manufacture, supply and delivery of PE 100-PN 6 HDPE pipes confirming to IS 4984-1995 including transportation to work spot, stacking including all taxes etc. complete as per S.S
110mm dia.
160mm dia.
200mm dia.
250mm dia.
Manufacture, supply, & delivery of HDPE fittings conforming to IS 4984 - 1995 including transportation to work spot, stacking excluding all taxes and duties etc.complete
a) Pipe ends - long neck
110mm dia.
110 mm dia for Air TEEs
160mm dia.
160 mm dia for Air TEEs
200mm dia.
200 mm dia for Air TEEs
b) MS Flanges
110mm dia.
110 mm dia for Air TEEs
160mm dia.
160 mm dia for Air TEEs
200 mm dia for Air TEEs
c) End Caps
110mm dia.
160mm dia.
200mm dia.
d) Reducers
110X125 mm dia
125x140 mm dia
140x160 mm dia
355x405 mm dia
e) TEES
110mm dia.
160mm dia.
200mm dia.
250mm dia.
400 mm dia
F)Bends
110mm dia.
160mm dia.
200mm dia.
250mm dia.
Lowering, laying and jointing of HDPE pipes and jointing by butt fusion welding as per IS 7634-part-II/1975 as amended from time to time to the alignment and gradient and testing the pipeline to required pressure etc.complete as per S.S and as directed by the departmental officer incharge of work
110mm dia.
160mm dia.
250mm dia.
Supply and delivery of DI Pipes and fittings (Specials) confirming to specification No.I.S.No. 7181/1986, 5531/1988, 3950/1979 including VAT and other duties including transportation and conveyance to work spot and stacking etc., complete as per S.S and as directed by the departmental authorities.
DIDF pipes for scours
100X2.00m on 110 and 160 mm dia mains for scours
100x1.00m long DF pipes for sluice valves
150 mm dia x2.00m on 200 and 250 mm dia pipes for scours
150x1.00m long DF pipes for sluice valves
200x1.00m long DF pipes for sluice valves
250x1.00m long DF pipes for sluice valves
100 mm dia deck foot bends
100x100x80 mm DIDF TEE for air valves
supply and delivery of "Resilient Seated Soft Sealing" Gate Valves (Sluice Valves) with Body and Bonnet of Ductile Iron GGG-40/SG-400/15 or GGG-50/SG-500/7 or Equivalent as per IS1865, IS:3896-2 and Wedge fully Rubber Lined with food grade quality grade W270 grade EPDM, Replaceable Spindle Nut without gland packing with 3-O ring protection system on the Shaft and Seals of NBR. The Valves should be Vacuum tight and 100% leak proof with face to face dimensions as BS:5163 Type A/IS:14846. All the valves should be with fusion bonded Electrostatic Powder coating both inside and outside (Min 250 Microns)- RAL 5005 with Pocket Less Straight through body Passage conforming to Design standards of DIN-3202F4/BS:5163 Type A Flange drilling as per IS - 1538 and including transportation. PN16 - as directed by the departmental officer incharge of work.
100 mm distrubution
150mm dia for distrubution
100mm dia on 110 mm and 160 mm dia mains
150 mm dia on 200 and 250 mm dia lines
Manufacture, supply and delivery of Single Chamber DI Air Valve with Body and cover in Ductile Iron of grade SG 400/12 or equivalent grade as per I.S.3896-part2-1985 and subsequent revisions. All internal parts such as float, shell etc., all cover bolts, of stainless steel, and Gaskets and seals of EPDM food grade quality Epoxy powder coating (EP-P) inside and outside colour blue. Drilled as per IS:1538. PN16
80 mm dia on 110 mm pipe
80 mm dia on 160 mm pipe
80mm dia 200 mm pipe
Labour charges for lowering and keeping in position of D.I. Sluice valves, reflux valves and scour valves. as per SS and as directed by the departmental officer incharge of work.
100 mm distrubution
150mm dia for distrubution
100mm dia on 110 mm and 160 mm dia mains
150 mm dia on 200 and 250 mm dia lines
Construction of R.C.C valve chambers as per Standard Drawings with RCC cover slab fixed with CI/DI manhole Frame & Cover with lock and Key arrangement. The Mix shall not be less than VRCC M 20 grade with 150mm thick side walls, 150mm thick top slab, 150mm thick base slab over base course of 100mm thick (1:4:8) propall material and all labour charges etc. complete as per S.S for finished item of work
100 mm distrubution
150mm dia for distrubution
100mm dia on 110 mm and 160 mm dia mains
150 mm dia on 200 and 250 mm dia lines
Construction of R.C.C valve chambers as per Standard Drawings with RCC cover slab fixed with CI/DI manhole Frame & Cover with lock and Key arrangement. The Mix shall not be less than VRCC M 20 grade with 150mm thick side walls, 150mm thick top slab, 150mm thick base slab over base course of 100mm thick (1:4:8) prop all material and all labour charges etc. complete as per S.S for finished item of work
80 mm dia on 110 mm pipe
80 mm dia on 160 mm pipe
80mm dia 200 mm pipe
Lowering the C.I. Pipes, D.I. Pipes of all classes and fittings with flanged ends carefully into the trenches and laying them true to alignment and gradient including all sundries, but excluding conveyance from source of supply as per BIS No.3114/94.
150 mm dia
200x1.00m long DF pipes for sluice valves
Jointing the C.I. Pipes, fittings and valves with flanged ends including cost of jointing materials such as bolts, nuts, rubber insertion, white lead and including filling with water with a water lead upto 500 m and testing to required pressure etc., comp as per SS and as directed by the departmental officer incharge of work. BIS No.3114/85.
100 mm dia
150 mm dia
200 mm dia
250 mm dia
Cutting BT road surface as well as asphalt (75mm thick) including water bound. The rate including labour charges for cutting, incidental charges etc., complete as directed by the departmental officer in charge of the work.
Cutting the CC road surface. The rate including labour charges for cutting, incidental charges etc., complete as directed by the departmental officer in charge of the work.
Cutting the open water bound macadam. The rate including labour charges for cutting, incidental charges etc., complete as directed by the departmental officer in charge of the work.
Collection, Supply and filling of Stone dust / Quarry spall from approved quarry to work site and stacking at work site for pre measurements including cost and convenyance of all material and all labour charges etc. complete for road restoration
BLD-CSTN-3-11-(28) Using Concrete mixture up to Plinth Level : Plain Cement concrete nominal mix M-20 (Cement : fine aggregate: coarse aggregate ) using 20mm size Hard Granite Machine Crushed Graded Metal including cost and conveyance of all materials like cement, sand, coarse aggregate water etc., to site , seigniorage charges on all materials, labour charges , for mixing , laying, concrete , ramming in 15 cm layers, finishing top surface to the required level curing etc., complete for finished item of work with nomonal reinforcement for Road restoration.
Providing house service connections on HDPE mains at House hold side in Earthen Roads with Earthwork Excavation in all type of soils fixing PP Saddle,PP Clamp Saddle shall be manufactured by injection moulding using virigin Polypropylene,Mechanical tapping saddles for water works purposes and designed for use with PVC/PE pipe as per IS 4985/IS 4984 respectively. These saddles should be contoured to fit around the pipe. PP saddles shall be Blue/Black moulded-in with Nickel plated Brass / SS 304 metal female threaded outlets. Seal shall be thermoplastic elastomer rubber suitable for drinking water and nut-bolt-washer with SS. The PP Clamp saddle fittings shall be mouldedwith SS 304/Nickel plated Brass female threaded outlet inserted to connect necessary fittings. Thread dimension shall conform to IS-554/ISO-7. Adequate thickness of PP shall be provided to hold brass insert in place and avoid leakage while pressure applications. Fasteners shall be threaded type, with SS. Fasteners of size 125mm and above. The grade of raw material used must be certified by WRAS, UK for type test as per BS 6920 from their certified laboratories like NSF International Ltd. UK and certificate of Compliance to be produced for the following parameters: i) Odour&Flavour of water ii) Appearance of water iii) Growth of Micro Organismaxes etc,FOR main pipes Hdpe /PVC of 110mm dia .flow control valve SS 316 NRV 10 LPM ,Compression adaptor with one side compression end to suit 1/2 "to1''(15mmOD to25 mm OD) MDPE pipe and other side with female threaded with SS-304 material inserts of sizes 1/2" BSP threads,body,nut, and cap of poly propylene,clip ring PP Compression Metal insert female Threaded Adaptorcompression adaptor with one side compression end to suit 1/2'' to 1'' mdpe pipe and other side with female thread with ss-304 material inserts of sizes 1/2'' BSP thread,PP compression elbow to suit 1/2 " to 1'' (15mm OD to 25 mm OD) MDPE pipe body, nuts, and caps of polypropelene, clip ring of POM(Acetylic resin) and and "O" ring of NBR material,as per ISO 14236 standardsDouble compression elbow to suit 20mm OD for 100mm, MDPE PE80 Blue pipe as per ISO 4427 up to date 1. for conveyance of potable water ,MDPE 20mm OD pipe (2.00 m avg length for each of 1/2'' HSC) of SDR 9-PN-16 for pipes side,Premium make UPVC Pipes with Fittings.(IS 4985/2000)(PH SSR :20) UPVC pipe for 40 mm (Casing for drain crossing)fixing of 12.7 mm brass bib cock indian make heavy duty long bodyFixing of House service connections,including fixing of ferrule, MDPE/GI pipes and specials and connecting newly laid pipe (For HDPE / PVC Pipes)Making Holes upto 18 mm Dia in RCC/any Stones up to 50 mm Thick( BMS-W78)Fixing of 25.4 mm Holder Back Clamps at Drain Crossing this rate cost of above all materials ,Including all Labour Charges ,other incidental charges etc for finished item of work and as directed by the departmental officer in charge of work
Providing house service connections on HDPE mains at other side in Earthen Roads with Earthwork Excavation in all type of soils fixing PP Saddle,PP Clamp Saddle shall be manufactured by injection moulding using virigin Polypropylene,Mechanical tapping saddles for water works purposes and designed for use with PVC/PE pipe as per IS 4985/IS 4984 respectively. These saddles should be contoured to fit around the pipe. PP saddles shall be Blue/Black moulded-in with Nickel plated Brass / SS 304 metal female threaded outlets. Seal shall be thermoplastic elastomer rubber suitable for drinking water and nut-bolt-washer with SS. The PP Clamp saddle fittings shall be mouldedwith SS 304/Nickel plated Brass female threaded outlet inserted to connect necessary fittings. Thread dimension shall conform to IS-554/ISO-7. Adequate thickness of PP shall be provided to hold brass insert in place and avoid leakage while pressure applications. Fasteners shall be threaded type, with SS. Fasteners of size 125mm and above. The grade of raw material used must be certified by WRAS, UK for type test as per BS 6920 from their certified laboratories like NSF International Ltd. UK and certificate of Compliance to be produced for the following parameters: i) Odour&Flavour of water ii) Appearance of water iii) Growth of Micro Organismaxes etc,FOR main pipes Hdpe /PVC of 110mm dia .flow control valve SS 316 NRV 10 LPM ,Compression adaptor with one side compression end to suit 1/2 "to1''(15mmOD to25 mm OD) MDPE pipe and other side with female threaded with SS-304 material inserts of sizes 1/2" BSP threads,body,nut, and cap of poly propylene,clip ring PP Compression Metal insert female Threaded Adaptorcompression adaptor with one side compression end to suit 1/2'' to 1'' mdpe pipe and other side with female thread with ss-304 material inserts of sizes 1/2'' BSP thread,PP compression elbow to suit 1/2 " to 1'' (15mm OD to 25 mm OD) MDPE pipe body, nuts, and caps of polypropelene, clip ring of POM(Acetylic resin) and and "O" ring of NBR material,as per ISO 14236 standardsDouble compression elbow to suit 20mm OD for 100mm, MDPE PE80 Blue pipe as per ISO 4427 up to date 1. for conveyance of potable water ,MDPE 20mm OD pipe (2.00 m avg length for each of 1/2'' HSC) of SDR 9-PN-16 for pipes side,Premium make UPVC Pipes with Fittings.(IS 4985/2000)(PH SSR :20) UPVC pipe for 40 mm (Casing for drain crossing)fixing of 12.7 mm brass bib cock indian make heavy duty long bodyFixing of House service connections,including fixing of ferrule, MDPE/GI pipes and specials and connecting newly laid pipe (For HDPE / PVC Pipes)Making Holes upto 18 mm Dia in RCC/any Stones up to 50 mm Thick( BMS-W78)Fixing of 25.4 mm Holder Back Clamps at Drain Crossing this rate cost of above all materials ,Including all Labour Charges ,other incidental charges etc for finished item of work and as directed by the departmental officer in charge of work
Providing house service connections on HDPE mains at other side in B.T & CC Roads with Earthwork Excavation in all type of soils fixing PP Saddle,PP Clamp Saddle shall be manufactured by injection moulding using virigin Polypropylene,Mechanical tapping saddles for water works purposes and designed for use with PVC/PE pipe as per IS 4985/IS 4984 respectively. These saddles should be contoured to fit around the pipe. PP saddles shall be Blue/Black moulded-in with Nickel plated Brass / SS 304 metal female threaded outlets. Seal shall be thermoplastic elastomer rubber suitable for drinking water and nut-bolt-washer with SS. The PP Clamp saddle fittings shall be mouldedwith SS 304/Nickel plated Brass female threaded outlet inserted to connect necessary fittings. Thread dimension shall conform to IS-554/ISO-7. Adequate thickness of PP shall be provided to hold brass insert in place and avoid leakage while pressure applications. Fasteners shall be threaded type, with SS. Fasteners of size 125mm and above. The grade of raw material used must be certified by WRAS, UK for type test as per BS 6920 from their certified laboratories like NSF International Ltd. UK and certificate of Compliance to be produced for the following parameters: i) Odour&Flavour of water ii) Appearance of water iii) Growth of Micro Organismaxes etc,FOR main pipes Hdpe /PVC of 110mm dia .flow control valve SS 316 NRV 10 LPM ,Compression adaptor with one side compression end to suit 1/2 "to1''(15mmOD to25 mm OD) MDPE pipe and other side with female threaded with SS-304 material inserts of sizes 1/2" BSP threads,body,nut, and cap of poly propylene,clip ring PP Compression Metal insert female Threaded Adaptorcompression adaptor with one side compression end to suit 1/2'' to 1'' mdpe pipe and other side with female thread with ss-304 material inserts of sizes 1/2'' BSP thread,PP compression elbow to suit 1/2 " to 1'' (15mm OD to 25 mm OD) MDPE pipe body, nuts, and caps of polypropelene, clip ring of POM(Acetylic resin) and and "O" ring of NBR material,as per ISO 14236 standardsDouble compression elbow to suit 20mm OD for 100mm, MDPE PE80 Blue pipe as per ISO 4427 up to date 1. for conveyance of potable water ,MDPE 20mm OD pipe (2.00 m avg length for each of 1/2'' HSC) of SDR 9-PN-16 for pipes side,Premium make UPVC Pipes with Fittings.(IS 4985/2000)(PH SSR :20) UPVC pipe for 40 mm (Casing for drain crossing)fixing of 12.7 mm brass bib cock indian make heavy duty long bodyFixing of House service connections,including fixing of ferrule, MDPE/GI pipes and specials and connecting newly laid pipe (For HDPE / PVC Pipes)Making Holes upto 18 mm Dia in RCC/any Stones up to 50 mm Thick( BMS-W78)Fixing of 25.4 mm Holder Back Clamps at Drain Crossing this rate cost of above all materials ,Including all Labour Charges ,other incidental charges etc for finished item of work and as directed by the departmental officer in charge of work
Providing house service connections on HDPE mains at House hold side in B.T & CC Roads with Earthwork Excavation in all type of soils fixing PP Saddle,PP Clamp Saddle shall be manufactured by injection moulding using virigin Polypropylene,Mechanical tapping saddles for water works purposes and designed for use with PVC/PE pipe as per IS 4985/IS 4984 respectively. These saddles should be contoured to fit around the pipe. PP saddles shall be Blue/Black moulded-in with Nickel plated Brass / SS 304 metal female threaded outlets. Seal shall be thermoplastic elastomer rubber suitable for drinking water and nut-bolt-washer with SS. The PP Clamp saddle fittings shall be mouldedwith SS 304/Nickel plated Brass female threaded outlet inserted to connect necessary fittings. Thread dimension shall conform to IS-554/ISO-7. Adequate thickness of PP shall be provided to hold brass insert in place and avoid leakage while pressure applications. Fasteners shall be threaded type, with SS. Fasteners of size 125mm and above. The grade of raw material used must be certified by WRAS, UK for type test as per BS 6920 from their certified laboratories like NSF International Ltd. UK and certificate of Compliance to be produced for the following parameters: i) Odour&Flavour of water ii) Appearance of water iii) Growth of Micro Organismaxes etc,FOR main pipes Hdpe /PVC of 110mm dia .flow control valve SS 316 NRV 10 LPM ,Compression adaptor with one side compression end to suit 1/2 "to1''(15mmOD to25 mm OD) MDPE pipe and other side with female threaded with SS-304 material inserts of sizes 1/2" BSP threads,body,nut, and cap of poly propylene,clip ring PP Compression Metal insert female Threaded Adaptorcompression adaptor with one side compression end to suit 1/2'' to 1'' mdpe pipe and other side with female thread with ss-304 material inserts of sizes 1/2'' BSP thread,PP compression elbow to suit 1/2 " to 1'' (15mm OD to 25 mm OD) MDPE pipe body, nuts, and caps of polypropelene, clip ring of POM(Acetylic resin) and and "O" ring of NBR material,as per ISO 14236 standardsDouble compression elbow to suit 20mm OD for 100mm, MDPE PE80 Blue pipe as per ISO 4427 up to date 1. for conveyance of potable water ,MDPE 20mm OD pipe (2.00 m avg length for each of 1/2'' HSC) of SDR 9-PN-16 for pipes side,Premium make UPVC Pipes with Fittings.(IS 4985/2000)(PH SSR :20) UPVC pipe for 40 mm (Casing for drain crossing)fixing of 12.7 mm brass bib cock indian make heavy duty long bodyFixing of House service connections,including fixing of ferrule, MDPE/GI pipes and specials and connecting newly laid pipe (For HDPE / PVC Pipes)Making Holes upto 18 mm Dia in RCC/any Stones up to 50 mm Thick( BMS-W78)Fixing of 25.4 mm Holder Back Clamps at Drain Crossing this rate cost of above all materials ,Including all Labour Charges ,other incidental charges etc for finished item of work and as directed by the departmental officer in charge of work
Providing Technical Graduate for co-ordinating the process of interconnections of the existing and proposed systems, preparation of documents related to inter departmental permissions and liaison with line departments to obtain permissions including preparation of build drawings as instructed by the Engineer in charge.
Providing the services such as consumer survey and mapping, asset mapping, ground validation, component wise structural and hydraulic designs as per site condition, GIS based hydraulic modelling of all components of both existing and proposed water supply infrastructure and any other documentation/ plan/ designs related to the whole scheme as per the instructions of the Engineer incharge and CPHEEO Manual
Operation and Maintenance for the Seven (7) Years including Defect Liability Period-From Source to ELSR's
Engaging of Man Mazdoor (Skilled / Semi Skilled) Like Electrician, pump Operator, Mechanic, Helpers, watch man, Filter bed operator, Diploma Engineer, Lab Technician, Technical work inspector etc, as per the requirment. The rate includes wages along with Municipal allowance, conveyancer charges for transporation to the work site including statutory provisions as per norms etc complete for sucessful by Maintainace of the entire scheme as directed by the departmental officer incharge of the work (for 7 years + 2 years Defect liablity period as follows
Operator
Fitter/Helper
Watch man
Personal required at operating Raw water rising mains Fitter/Helper
Personal required at operating Water treatment plants & Sump Operator
Personal required at operating Water treatment plants & Sump Fitter/Helper
Personal required at operating Water treatment plants & Sump Lab Technician
Personal required at operating Water treatment plants & Sump Electrician /Mechanic
Personal required at operating Water treatment plants & Sump Watch man
Personal required at operating Clear water rising mains and Distribution lines Fitter/Helper
Personal required at operating Gravity mains Watch man
Personal required at operating Service reservoirs Watch man
Supply, delivery and stacking of Chorine gas as per relevant indian standards in cylinders including cost of material, coveyance, stacking at the location specified by the Department and inclusive of all taxes except GST etc., complete to be used as a disinfectant in accordance with CPHEEO manual guidelines.1st year
B) Alumino -Ferric (Alum) @ 20 mg/Lt
Supply and delivery of Alumino -Ferric (Alum) as per IS standards including the cost of material, conveyance, stacking at the location specified by the Dept., and including etc., complete.rement at 15 mg/lit 1st year
Repairs to pumpsets & Water pipe lines (2 years after execution period)
i) Replacement of bearings of pumpsets
ii) Replacement of sleeves
iii) Rewinding of Motors
iv) Raw Water Motors
Clear Water Motors
iv)Replacement of glands of sluice valves
v) Replacements of balls of Air valves
vi) Greease
vii) Gland Packing
Operation and Maintenance for the Seven (7) Years including Defect Liability Period-For Distribution network
Personal required at operating distribution system Fitter/Helper
Earth work Excavation,Bailing out water from Pipe Line Trench and replacement damaged HDPE Pipe for 1 M length including the Cost of Pipe Collar M/F Joint and refilling etc complete
110 mm Dia
160 mm Dia
200 mm Dia
250 mm Dia
Operation and Maintenance for Local SCADA at ULB
Jr. Service Engineer (Diploma Engineer) To asist to attend the service calls by the seniour service engineer
Data Operator With assistance of the DBA, preparation of daily reports, monthly billing, correspondence with consumers and also co-ordinate with the GVMC Officials for obtaining of required information when ever asks.
Office assistant To assist the entire team, dispatches and also maintain SCADA station clean and neat
Replacement of necessary servicable materials(Reagents) for Chlorine Analysers Each Reagent bottle will work for 90 days (Self life) as per the Caluculation based on the Sampling interval in every 10 Minuets.
Replacement of necessary tranducers for PH analysers
Replacement of necessary tranducers for Turbidity analysers
BSNL Charges for static IP Interconnection for Data receive station from all Local Contol RTU panels.
Data transfer from RTU control panels
Charges for maintainance of PC's, Hardware consumables, Minor repair & Servers ,servomax Stabliser, UPS, maintainance of entire system including cost and convayance of all material and labor and attending minor repairs to instrumantation and automation equipment etc., complete for day to day operation and reporting to the departmental officers
Operation and Maintenance for Central SCADA for ULB
Application Engineer (Graduate Engineer) To monitor all issues related to both operation & service
System Engineer (Diploma Engineer) To monitor all meters location through SCADA station and give feedback to the service engineers.
Data Operator With assistance of the DBA, preparation of daily reports, monthly billing, correspondence with consumers and also co-ordinate with the Officials for obtaining of required information when ever asks.
Office assistant To assist the entire team, dispatches and also maintain SCADA station clean and neat
BSNL Charges for static IP Interconnection for Data receive station from all Local Contol RTU panels.
Data base management for WEB reporting Data storage and reporting system for view through WEB and Mobile networks
Charges for maintainance of PC's, Hardware consumables, Minor repair & Servers ,servomax Stabliser, UPS, maintainance of entire system including cost and convayance of all material and labor and attending minor repairs to instrumantation and automation equipment etc., complete for day to day operation and reporting to the departmental officers
MUMMIDIVARAM NAGAR PANCHAYAT
Construction of Raw Water Intake Well in River Godavari at Bobbarlanka
Well sinking in sandy and other loose soils under water either by manual labour,divers,or dredgers,weighing the top of steining to assist sinking etc.,including dewatering and other incidental charges such as hire charges for mechanical equipment etc,complete for an internal dia of 8.00m
a) Up to 2.00m depth
b) 2.00m to 4.00m depth
c) 4.00m to 6.00m depth
d) 6.00m to 8.00m depth
e) 8.00m to 10.00m depth
f) 10.00m to 11.00m depth
g) 11.00m to 12.00m depth
h) 12.00m to 13.00m depth
i) 13.00m to 14.00m depth
j) 14.00m to 15.00m depth
k) 15.00m to 16.00m depth
Providing PCC 1:4:8 using 40 mm graded SS 5 HBG m/c metal and OPC coarse and fine aggregate confirming to IS 383 including cost and conveyance of all materials and labour charges, machine mixing , vibration,laying in position, curing etc., complete as per ss and as directed by the departmental officer incharge of work
Providing VRCC M30 Grade Design Concrete Mix corresponding to IS 456 using WEIGH BATCHER / MIXER with 20mm size graded machine crushed hard granite metal (coarse aggregate) from approved quarry including cost and conveyance of all materials like cement, fine aggregate (sand) coarse aggregate, water etc., to site and including seignorage charges including all operational, incidental and labour charges such as weigh batching, machine mixing, laying concrete, curing with cement content 400Kgs/Cum as per I.S code from standard suppliers approved by the department including centering, shuttering, laying concrete, vibrating, curing etc. complete with all de-lift charges but excluding cost of steel and its fabrication charges for finished item of work (APSS No. 402)
a) for Base slab & Plugging
b) for Well Curb 0.50m thick
Side Wall of the Well of 0.50m thick upto Normal water level+0.50m +14.50m(-)+0.00m
Side Wall of the Well of 0.50m thick upto bottom of floor slab to Normal water level + 22.22m to +14.50m=7.72m
Side Wall of the Well of 0.50m thick upto bottom of floor slab to Normal water level + 22.22m to +14.50m=7.72m
Side Wall of the Well of 0.50m thick upto bottom of floor slab to Normal water level + 22.22m to +14.50m=7.72m
Side Wall of the Well of 0.50m thick upto bottom of floor slab to Normal water level + 22.22m to +14.50m=7.72m
Side Wall of the Well of 0.50m thick upto bottom of floor slab to Normal water level + 22.22m to +14.50m=7.72m
Side Wall of the Well of 0.50m thick upto bottom of floor slab to Normal water level + 22.22m to +14.50m=7.72m
platform for placing Sluice Valves
Providing VRCC M30 Grade Design Concrete Mix corresponding to IS 456 using WEIGH BATCHER / MIXER with 20mm size graded machine crushed hard granite metal (coarse aggregate) from approved quarry including cost and conveyance of all materials like cement, fine aggregate (sand) coarse aggregate, water etc., to site and including seignorage charges including all operational, incidental and labour charges such as weigh batching, machine mixing, laying concrete, curing with cement content 400Kgs/Cum as per I.S code from standard suppliers approved by the department including centering, shuttering, laying concrete, vibrating, curing etc. complete but excluding cost of steel and its fabrication charges for finished item of work (APSS No. 402)
a) for Pump house Columns
b) for floor beams
c) for Floor Slab 0.25m thick with allrouns walk way
d) ring Beams at lintel level
e) for Roof Beams
f) for Roof slab 0.15m thick with slab extension 0.30m
g) for Sunshade of 0.60m wide and thickness of .075m at fixed end and 0.05m.at free end
Brick masonary in CM (1:5) using 2nd class bricks of size 23 x 11 x 7cms. Cost including cost and conveyance of all materials at site, labour charges for curing,lifting,scaffolding etc., complete as per ss and as directed by the departmental officer incharge of work as follows
for Super structure of Pump house
for Pump house Parapet wall
Supply and fixing of 50mm thick pre-cast Cement Jali of approved design including cost and conveyance to work spot and all labour charges for fixing in position etc.complete as per ss and as directed by the departmental officer incharge of work
Plastering with CM (1:4) 12mm thick including cost and conveyance of all materials at site labour charges,lifting,scaffolding and other incidental charges etc for finishing and curing etc., complete as per S.S for the Pump house
for Pump house inside & outside
for Parapet wall
Providing impervious course with C.M (1:3) 20mm thick and mixing with acco proof compound of 1kg per one bag of cement including cost and conveyance of all materials and labour charges for finishing and curing lifting,scaffolding and other incidental charges etc., complete as per SS (APDSS NO:903)
Plastering with CM (1:3) 12mm thick including cost and conveyance of all materials at site, and labour charges for mixing of mortar, plastering and curing etc.,of all materials and labour charges for finishing and curing lifting,scaffolding and other incidental charges etc complete as per S.S for ceiling
Painting two coats with snowcem paint of approved colour including cost of primary coat with white cement. The rate includes cost and conveyance of all materials at site, labour charges, scaffolding charges etc., complete as directed by the departmental authorities.
Manufacture,supply,delivery of MS grill gates,window ornamental safety grill ,made with MS flats,MS angles,MS squares etc including welding,finishing,applying red oxide paint as primary coat etc complete as directed by the departmental authorities.
Painting two coats with synthetic enamel paint over a base coat of red led. The rate includeds cost and conveyance of all materilas at site, labour charges, scaffolding charges etc., complete as directed by the departmental authorities (APDSS No:1201)
Supply & fixing of Rolling shutter made of 80 x 1.25 mm machine rolled CRCA laths, interlocked together through their entire length and jointed together at the ends by end-locks, mounted on specially designed pipe shaft of 50mm dia nominal bore MS B class pipe with brackets, plates, guide channels, stoppers, bottom locking plates and arrangements for inside & outside locking with push-pull operations including cost of hood cover and springs complete, painted with one coat of approved steel primer, locks, ball bearings, all accessories etc complete for finished item of work as per special spn: 1108 complete as directed by the departmental authorities.
Supply and fixing Aluminium Anodised Two/ Three Track Sliding Windows as per approved drawing with aluminium anodised sections of Series C Jindal sections and outer frame top horizontals & both verticals of 8774 of size 62 x 29.5 mm and bottom horizontal - two track frame of 8773 of size 62 x 29.5 mm, Shutter frame top, bottom and verticals of 8304 of size 50 mm x 20 mm and Weather interlocking frame of 8306 of size 50 x 20 with plain clear float glass 5 mm thick fixed including supply and fixing aluminium handles of 100 mm for each shutter, nylon rollers assembly and all labour charges for fixing the fixtures with required no.of screws, bolts and nuts and including labour charges for fixing the frame in position, fixing shutter to frame etc. completed for finished item of work BLD-CSTN-11-30 complete as directed by the departmental authorities.
Supply, delivery, fabrication and erection of Cutting toe for Well curb with ISA 150x150x12mm including cost and conveyance to work spot including all labour charges for fabrication and erection etc.,complete as directed by the departmental authorities.
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, ., complete for finished item of work in all floors.( APSS No.126)
Supply, delivery, lowering and keeping in position of 350mm dia PN(1.6) DI D/F Gate Valve (Soft Seated) Resilient seated soft sealing gate valves (Sluice valves) with body bonnet of ductile cast iron of grade GGG40/ SG 400/12 or equivalent grade as per I.S.3896-part2-1985 and subsequent revisions, wedge fully rubber lined with EPDM food grade quality and seals of NBR and the valves should be of vacuum tight and 100% leak proof with face to face dimensions as per BS5163-89/IS14846-2000/DIN 3202 F 4. All the valves should be with Electrostatic powder coating both inside and outside pocket less body passage. Drilled as per IS:1538. The rate including cost, CST, Excise duty and conveyance to work spot and stacking care fully at site etc. complete as directed by the departmental authorities.
Supply and delivery of 350mm dia. 2.00m. long centrifugally cast (spun) Ductile Iron pressure pipes with flanged (welded) ends of K-9 Class confirming to specification No.IS 8329/2000 of standard working lengths with cement lining inside the pipe, out side Zinc Coating including cost of Pipe, VAT and other duties. The rate including transportation and conveyance to work spot and stacking at site etc., complete as per S.S and as directed by the departmental authorities.
Labour charges for lowering of 350mm dia Pipe and keeping in position of C.I. Sluice valves(with cap/with hand wheel), reflux valves and scour valves complete as per S.S and as directed by the departmental authorities.
Supply and delivery of upto 500mm dia centrifugally cast (spun) Ductile Iron fittings of K9 Class confirming to IS:9523/2000 having dimensions as per table with cement lining inside, out side Zinc Coating with finishing as per Class 13/IS9523/2000 including cost of Pipe,and The rate including transportation and conveyance to work spot and stacking at site etc., complete as per S.S and as directed by the departmental authorities.
Lowering the 350mm dia 2 mts Long , D.I. D/F K9 Pipes of all classes and fittings with flanged ends carefully into the trenches and laying them true to alignment and gradient including all sundries, but excluding conveyance from source of supply as per BIS No.3114/94.
Jointing the 350mm dia D.I. Pipes, fittings and valves with flanged ends including cost of jointing materials such as bolts, nuts, rubber insertion, white lead and including filling with water with a water lead upto 500 m and testing to required pressure etc., comp as per BIS No.3114/85
Supply and delivery of S.S 304 grade operating handle with rod & wheel for operation of D.I. Sluice valve inside the intake well as per the actuals and as directed by the departmental authorities.
Supply, delivery and erection of 5 tonnes capacity double girder gantry arrangements to move and lift the installations of the pump house one way with required MS ISMB of best quality 250 x 100 mm of standard make, including the required MS ISMC, MS angular iron, 5 tonne capacity travelling trolley and 5 tonne capacity chain pulley block with chains of suitable capacity for lifting and moving arrangements to length of 10.00 m rate is inclusive of the cost of materials, labour charges, site welding etc.,complete as per ss and as direceted by the departmental officer incharge of work
Supply and fixing of Stain less steel ladder made out of suitable sections for access from floor slab to Base slab this rate including all materials and other incidental charges complete as per ss and as direceted by the deepartment officer incharge of work
Supply and fixing of 25 mm dia 2.00 mm thick PVC pipe concealed in roof slab with all required accessories including masonary work all labour chages completed as per IE Rules and as directed by the departmental officer incharge of work
Supply and fixing of 20 mm dia 1.50 mm thick PVC pipe concealed in walls with all required accessories including masonary work for light , fan and plug point with metal deep box including all labour chages completed as per IE Rules and as directed by the departmental officer incharge of work
Wiring with 2 runs 14/0.3 mm. (1.0. sq.mm) Fire retardant PVC insulated Flexible copper cable in existing pipe with 6A siwtch, ceiling rose and 3 mm thick hyla sheet covering to switch control box including all labour charges etc,., complet for light, bell , fan and exhaust fan points in non - residential building completed as per IE Rules and as directed by the departmental officer incharge of work
Wiring with 2 runs 14/0.3 mm. (1.0. sq.mm) Fire retardant PVC insulated Flexible copper cable in existing pipe with 6A modular siwtch control and 3/2 pin sockets fixing on board including all labour charges completed as per IE Rules and as directed by the departmental officer incharge of work
supply and run of 2 of 36/0.3 mm. (1.5. sq.mm) Fire retardant PVC insulated Flexible copper cable in existing pipe for mains including all labour charges
supply and run of 1 of 14/0.3 mm. (1.0. sq.mm) Fire retardant PVC insulated Flexible copper cable in existing pipe for earth continuity including all labour charges etc.
supply and run of 2 of 6 sq.mm (7/18) WPSC alluminium cable along with No.10 SWG G.I barer wire through PVC cleats with all accessories including all labour charges etc.,
Providing independent earthing by excavating a trench to a depth of 2.10m in all soils, as per size specied in data ,using 40 mm dia B class GI pipe 2.50m long with necessary accessories with hume pipe ring duly providing staggered holes including filling with equal proportion of salt and charcoal in layers and all labour charges etc completed as per IE Rules and as directed by the departmental officer incharge of work
Supply and fixing SPN Distribution board with IP-20 protection suitable for single phase Earth Leakage Circute Braker (ELCB) / Residual Current Circute Braker (RCCB) / Double Pole (DP) Isolator as incomer and 10kA SP MCBs as out going including internal connections and labour charges for surface / flush mounting etc., completed as per IE Rules and as directed by the departmental officer incharge of work
Supply of 48" (1200mm) Sweep 5 star rated Ceiling Fan , with double ball bearings, air delivery more than 200 cubic meter/min but without Regulator.Makes : Crompton HS Plus / Havells ES Neo/Orient Energy Star/ Halonix(Zephyr)/Polycab(Synergy Star) unit each complete as per IE Rules and as directed by the departmental officer incharge of work
Supply of stepped type Electronic Regulator of makes GM G Home / Gold Medal Olive / Million Zoom / Anchor Penta Cherry / Great white Omega complete as per IE Rules and as directed by the departmental officer incharge of work
Supply of 9" (225mm), Light duty exhaust fan with double ball bearing and wire guard etc complete. Makes: Crompton / Bajaj Bahar WG / Havells Ventil Air-DS / Orient hill air / MIIT complete as per IE Rules and as directed by the departmental officer incharge of work
Supply and transportation of 20W, 2000 lumens, T8,1200mm length LED retro tube light,wide operating voltage with double side connection, PF≥0.9,Surge protection: > 2KV, THD<15%, with inbuilt driver and frosted cover CCT: 3000K - 6500K as desired by the department and as per IS specifications, minimum CRI≥80,.etc complete with 5 years warranty.LUMINAIRE MAKE: Phillips / OSRAM / GE / Crompton /VIN / Bajaj / Havells / Halonix / HPL. LED MAKE : PHILIPS LUMILEDS / CREE / NICHIA /OSRAM / SAMSUNG / LG LEDs.complete as per IE Rules and as directed by the departmental officer incharge of work
Labour charges for Fixing of Ceiling fan and regulator including transportation and giving connections with twin core wire etc., complete as per IE Rules and as directed by the departmental officer incharge of work
Labour charges for fixing of Exhaust fan in wall with necessary connections and masonary work of making hole, finishing etc., complete as per IE Rules and as directed by the departmental officer incharge of work
Labour charges Fixing of 40W tube light luminaire on wall / Ceiling with / TW round blocks with all accessories including giving connections and all labour charges etc., complete as per IE Rules and as directed by the departmental officer incharge of work
Providing temporory Island for preparation platform for sinking of Intake well
Providing and construction of Temporary island of 30.00m. Diameter and 8 metres height for preparation of platform etc.with laying of sand bags in the stipulated places with in minimum height of 4.5 mts including cost of empty cement bag, sand thread, stiching charges and labour charges . During the emergency conditions such as floods .and other natural calamities, the above rate is allowed to enhance by 25% for 1st warning level and above, keeping in view of the difficulty in availability of labour and vehicles for ring bund by using crane with grap, consumbles, wooden ballies shutable dia and shutable height and braceings, for construction of 8.00m dia Raw water intake well in River in Godavari near Bridge. This rate including cost of all materials,all labour charges conveyance charges and all operational, incidental and labour charges etc., complete for finished item of work and as per ss and as adirected by the departmental officer in charge of work.
Formation of bund/approach ramp for Temporary Island with Gravel from approved quarry including cost of gravel and conveyance of all materials and labour charges for formation of filling, raming,sectining,including supporting the sides for water flow etc., Complegte for approch ram from bund to intake well at bridge to Godavari river .This rate including cost of all materials,all labour charges conveyance charges and all operational,other incidental and labour charges etc., complete for finished item of work and as per ss and as adirected by the departmental officer in charge of work.
supply of Wooden ballies 8" Dia and 9 m long including fixing in the river protection of bund as per the instructions of the departmental officer icharge of the work
supply of Wooden ballies 2" Dia for bracing 9.00m long including fixing in the river protection of bund as per the instructions of the departmental officer icharge of the work
Sand bags for formation of temporary bund (Laying Sand Bags in the stipulated places including cost of empty cement bag, sand, thread,stiching charges and labour charges complete as per ss and as direceted by the departmental officer incharge of work
Construction of Approach Bridge for Intake well in Godavari River
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH Note : Classifications of Earth Work Specification are as per 302.2.1(a) of MORD and 301.2.1 of MORT&H--ordinary soil--manual means upto 3m depth for foundations of buildings in restricted places
Filling with Sand for approach bridge bedding This rate including cost of Sand,all labour charges,watering,ramming,and other incidental charges etc as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH etc.,complete as per S.S and as directed by the departmental officer incharge of work
Providing PCC 1:4:8 using 40 mm graded SS 5 HBG m/c metal and OPC coarse and fine aggregate confirming to IS 383 including cost and conveyance of all materials and labour charges, machine mixing , vibration,laying in position, curing etc., complete as per S.S and as directed by the departmental officer incharge of work
Providing VRCC M30 Grade Design Concrete Mix corresponding to IS 456 using WEIGH BATCHER / MIXER with 20mm size graded machine crushed hard granite metal (coarse aggregate) from approved quarry including cost and conveyance of all materials like cement, fine aggregate (sand) coarse aggregate, water etc., to site and including seignorage charges including all operational, incidental and labour charges such as weigh batching, machine mixing, laying concrete, curing with cement content 400Kgs/Cum as per I.S code from standard suppliers approved by the department including centering, shuttering, laying concrete, vibrating, curing etc. complete but excluding cost of steel and its fabrication charges for finished item of work (APSS No. 402) as follows
column footings
For columns
For Intermediate Braces
For Carriage Slab Beams
For Carriage Slab 0.20m thick
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, complete for finished item of work in all floors.( APSS No.126)
Construction of R.C.C. railing of M 25 grade in cast-in-situ with 20 mm nominal size aggregate, true to line and grade, 3 tier tolerance of vertical railing post not to exceed 1 in 500, centre-to-centre spacing between vertical posts not to exceed 2000 mm as per drawing and technical specifications Clauses 800, 900 and 1208.3 MORD including cost of necessary reinforcement etc complete as per S.S and as directed by the departmental officer incharge of work
Providing 3 Nos of 75 KW VT Pumpsets Each with a duty of 90LPS and a total head of 60m (two working and one stand bye) for pumping Raw water from intake well to proposed OHBR at Bobbarlanka
Supply, delivery and erection of 3# of 67.14 KW electrically driven vertical foot mounted heavy duty ball bearing type VT Rawr water pump sets. The pump should be fitted with S.S / Bronze impiller, S.S shaft as per IS spesification with casing of heavy duty and gland packing capable of discharging of 90 LPS at total head of 60.00m. operated at required RPM coupled for operation on combined variation of +/-10% AC Supply. Motor with Class ‘F” insulation and suitable for ambient tempareture up to 500 C S1 duty continuous rated and performance in general conform to IS325. The rate including all taxes and duties etc.complete with suction, delivery arrengements,DI valves,DI and MS specials,gauges,panel board for motors, capacitors, startes, earthening arrengements, change over switch,bed blocks under pumps,valves,suitable cables etc complete for finished item of work.
Providing 500 KVA Transformer at intake well with Transformer yard
Supply and erection of 7.50m long double pole structure fabricated with 150x75mm RS Joists,100x50mm MS channels, iron cross armstor fuse set and Lighting arrestrors etc.,including one coat of red oxide primer and two coats of bright Supply
Supply and fixing of 11 KV ,400 A 3 phase central post rotating double break type AB switch(isolator) as per IS 9921) without earth blade, gang operated, Horizontal type, operating mechanism with GI spring loaded reverse loop type fixed contact, solid HD electrolytic copper tubular moving contact with silver/Nickel plated at end points,9 Nos post insulators of 12 KV (IS 2594 and IS 5350) ,Hot Dip galvanizing hardware, GI pipe, Nuts and bolts etc., complete., ELEC 6.5.14/MAT 04113 complete as per IE rules and other incidental charges and as directed by the departmental officer incharge of work
Supply and fixing of 100 A 11 KV Horn Gap fuse set as per IS 9385 on existing DP structure with 6 no of 24 KV /22 KV post Insulators (IS 5350, Hot dipped Hardware, fuse wire of required size etc., complete ELEC 6.5.12/MAT 04111 complete as per IE rules and other incidental charges and as directed by the departmental officer incharge of work
Supply and fixing of distribution type lightning arrester 11 KV 5 kA as per IS 3070 with mounting base on the existing DP structure ELEC 6.5.11/MAT 04110 complete as per IE rules and other incidental charges and as directed by the departmental officer incharge of work
Supply and erection of 11KV Strain disc. Insulators with GI pins and top clamps
Supply and fixing of 11 KV pin Insulator (IS 731/1971) with minimum creepage distance of 300 mm on existing cross arm including all accessories like Hot dip GI spindle and nuts etc., ELEC 6.5.8/MAT 04105
Providing jumper connections with I/O' SWG HDBC wire between the 11 KV equipment on the outdoor structures
Supply and erection of GI stay set of dia 16mm,1.8 mtr long stay rod and anchor plate 380mmx380mmx6.4mm. including stay clamps, turn buckle and GI stay wire tight end through strain insulator including excavation of pit and cc work etc., complete ELEC 6.5.3/MAT 04097
Providing efficient earthing arrangement forthe DP structure lighting arresters and the HV equipment. Transformer body and neutral etc., with 25 x 3 mm copper flats and connecting them to the Earth Electrodes fabricated and buried accroding to standard specifications and as per the details given below: complete as per IE rules and other incidental charges and as directed by the departmental officer incharge of work
A) Earth Electrodes
B) Supply aand fixing of 20mm x 3mm Copper Flat(0.529Kgs/1Mtr) MAT 04146 as per IE rules and as directed by the departmental officer incharge of work
C) Supply aand fixing Epoxy insulators as per IE rules and as directed by the departmental officer incharge of work
D) Supply and fixing No.'8' SWG Copper wire. MAT 04141 as per IE rules and as directed by the departmental officer incharge of work
Supply and Transportation of ISI marked copper wound Transformers 11/0.433 KV, Three Phase, 50 Hz, DYN 11, ONAN type , Standard accessories, winding temperature rise of 45°C/40°C first fill oil, having permissible total loss values not exceeding 7.5%of the maximum total loss values for 11 KV as per Energy Efficiency Level - 2 at basic Insulation level conforming to ISS 2026 (Part- I to Part - II), latest ammended and IS 1180 Part-I : 2014 described as above with Cable box on HV side and Bus duct on LV Side , ON load Tap changer(OLTC)+10% to -10%, with RTCC etc., with initial filling of oil as per IS 335-1993 complete and as per the following continuous rating. Makes : Makes Schinder/Kirlosaakr/Voltamp/Esennar/Toshiba/KPEL/Powertech/SSE/THOTA/Vajra/Sri jeta/Haritha/VVE/Voltek/Star Gazer As per list of recommended brands as category I. MAT-04046e 500KVA complete as per IE rules and other incidental charges and as directed by the departmental officer incharge of work
1. Quantity : 1,2. Rated KVA : 500 KVA,3. Service & Location: Continuous Outdoor Distribution Transformer,4. Mounting : Plinth.,5. Wound : Copper Double wound ,6. Type : Core type oil immersed,7. Cooling : ONAN,8. Temp Rise : 40⁰C in oil 45⁰C by resistance,9. Vector Group: Dyn 11,10. Primary Connection : Delta,11. Nominal Voltage / Current : ______,12. Highest system Voltage: 12000V,13. Primary Frequency :50 HZ +/- 3%,14. Number of Phases : 3,15. Primary wires: 3,h. Oil filling hole with cap :One, g. Conservator with Drain plug:one,i. Oil level indicator : One, j. Dehydrating Silicagel Breather : One,k. Terminal Arrangement: HV With Treminal Box, l. Terminal Arrangement : LV Cable Box, m. Separate Neutral Bushing : One, n. Filter valve with blanking plate : One, o. Drain cum filter valve with blanking plate : One , p. Air release device : One , q. Thermometer Pocket : One, r. Four :Unidirectional flat rollers, s. One :10Cm dial thermometer(Rigid stem type)16. Secondary connection : Star,17. Secondary Volts / Current : 433V,18. Secondary phases : 3,19. Secondary wires: 4,20. Taps on primary winding for primary voltage variation : +5% to - 10% in steps of 2.5% of 7 position (6 Steps),21. Terminal arrangement., a.HV: HT terminal box as per the site condition.,b. LV: Cable box suitable to receive ------------Sq.mm XLPE cable,22. LV:One separate terminal for earthing.,23. Total Losses at 50% Loading [Watts] [Max] : 955 Wats,24. Total Losses at 100% Loading [Watts] [Max] : 2750 Wats, f. Explosion vent with Diaphragm :One ,e. Radiators ( Attachable) :Adequate 25. Percentage Impedance at 75 deg C AT 4.5,26. No load Current Less than 2% of full load Current, 27. Standrad Fittings & Accessories.,a. Rating and terminal marking plate: One, b. Lifting Lugs:Two, c. Off-circuit tap switch :One, d. Earthing Terminals
Supply and laying of 400Sq mm X 3.5 core XLPE insulated, 1100V grade armoured aluminum cable as per specification confirming to IS:7098 (Part- I)./1554-I Makes: Makes: Torent / Universal / Unicab / Havells / Finecab/ KEI / Gloster/ Polycab /RR Kabel/ Fortune Arrt ELEC-4.1.1q MAT-03431 complete as per IE rules and other incidental charges and as directed by the departmental officer incharge of work
Supply Installation Testing and commissioning of free-standing floor mounted dust and vermin proof compartmentalized cubical panel made out of CRCA sheet, required hardware, cleaning with 7 tank process duly painted by two coats of zinc/red oxide primer followed by Powder coated / epoxy / PU painted with phosphatisation in grey or required shade after rinsing. The panel having PU/ Neoprene rubber gasket of not less than 3mm thickness, separate detachable, gland plate M.S. base channel, hinged door with locking arrangement for equipment/switchgear. The thickness of sheet shall not be less than 1.6mm up to 600mm length/ width of any compartment and be 2.0mm above 600mm. The load bearing structure shall be of 2.0mm thick sheet supported by base M.S. channel if required. Side walls and cable alley compartments having bolted type doors with detachable extension type structure (only outer area on all sides shall be measured and panel to be fabricated from CPRI approved fabricator) MAT 03976 complete as per IE rules and other incidental charges and as directed by the departmental officer incharge of work
Supply and fixing of Electrolytic grade copper bus bar bus bar by means of SMC / DMC type insulator, high tensile nuts and bolts spring washers in existing panel including bending , cutting in required shape and size and colour coding with heat shrinkable PVC sleeves MAT 03978 complete as per IE rules and other incidental charges and as directed by the departmental officer incharge of work
a) 630A TPN SDFU for main switch Makes:LauritzKnudsen(FormerlyL&T)/Schneider/ C&S/ ABB / SIEMENS MAT 02885 complete as per IE rules and other incidental charges and as directed by the departmental officer incharge of work
b) 630A 4pole change over switch Makes:Socomec/LauritzKnudsen(FormerlyL&T)/HPL / Havells/ C&SMAT MAT 02898 complete as per IE rules and other incidental charges and as directed by the departmental officer incharge of work
c) Supply and fixing of (0-500) V range Voltmeter on existing panel, making connection by PVC insulated copper conductor with PVC sleeves /channel etc. as required Digital type Make: Conzerve/Elmeasure/Meco/HPL/L&T/socomec MAT 03980 complete as per IE rules and other incidental charges and as directed by the departmental officer incharge of work
e). Supply and fixing of CT operated direct reading type Ammeter on existing panel, making connection by PVC insulated copper conductor with PVC sleeves / channel etc. as required. Digital type Below 500 A Make:Conzerve/Elmeasure/Meco/HPL/L&T/Schneider/AE/Socomec MAT 03983 complete as per IE rules and other incidental charges and as directed by the departmental officer incharge of work
g).3RYB Phase indication lamps with leds complete as per IE rules and other incidental charges and as directed by the departmental officer incharge of work
h).Supply and Fixing of Current Transformer, with all necessary support in existing panel including connection etc. as required from 200 / 5 to 400/5 Ratio, 10 VA, class 1 accuracy: Make: Kappa/L&T/Seimens/C&S/Schneider MAT 03986 complete as per IE rules and other incidental charges and as directed by the departmental officer incharge of work
630A TPN SDFU forCW pump house motors Makes:LauritzKnudsen(FormerlyL&T)/Schneider/ C&S/ ABB / SIEMENS MAT 02885 complete as per IE rules and other incidental charges and as directed by the departmental officer incharge of work
630A TPN SDFU for compressor/mechanical equipments Makes:LauritzKnudsen(FormerlyL&T)/Schneider/ C&S/ ABB / SIEMENS MAT 02885 complete as per IE rules and other incidental charges and as directed by the departmental officer incharge of work
630A TPN SDFU for low lift sump Raw water motors Makes:LauritzKnudsen(FormerlyL&T)/Schneider/ C&S/ ABB / SIEMENS MAT 02885 complete as per IE rules and other incidental charges and as directed by the departmental officer incharge of work
630A TPN SDFU for Space Makes:LauritzKnudsen(FormerlyL&T)/Schneider/ C&S/ ABB / SIEMENS MAT 02885 complete as per IE rules and other incidental charges and as directed by the departmental officer incharge of work
630A TPN SDFU for lighting section Makes:LauritzKnudsen(FormerlyL&T)/Schneider/ C&S/ ABB / SIEMENS MAT 02885 complete as per IE rules and other incidental charges and as directed by the departmental officer incharge of work
630A 4pole change over switch for lighting section Makes:Socomec/LauritzKnudsen(FormerlyL&T)/HPL / Havells/ C&SMAT MAT 02898 complete as per IE rules and other incidental charges and as directed by the departmental officer incharge of work
.KWH digital meter fro lighting section complete as per IE rules and other incidental charges and as directed by the departmental officer incharge of work
Supply of 32 Amp………ISI marked TPN Switch Disconnector Fuse Unit, Cubical type without fuses as per IS: 13947/IEC 60947-3 Makes: As per list of recommended brands as category I.MAT-02879 complete as per IE rules and other incidental charges and as directed by the departmental officer incharge of work
Supply of 6A to 35 A……ISI marked HRC Fuse Links as per IS 13703-Part 2/IEC 60269- Part 2 Makes: As per list of recommended brands as category I MAT-02938 complete as per IE rules and other incidental charges and as directed by the departmental officer incharge of work
Standard duty Single phase 250 V / Three phase 440 V, 50 Hz capacitor (Bank) MAT-03998 complete as per IE rules and other incidental charges and as directed by the departmental officer incharge of work
1000KV LT/Transformer Errection.testing Commensing and Supply of drawing layout plans of installed transformer in tracing cloth and duly get approved from electrical inspector APEPDCL and leaflets for various equipments and opearation manuals etc., complete. complete as per IE rules and other incidental charges and as directed by the departmental officer incharge of work
Supply and Laying of 3C X 95 Sq mm XLPE insulated IS:7098/II/85 H.T. cable for working voltage 11 KV Earthed with Stranded Compacted Circular Aluminium Conductor Screened with Extruded Semi-conducting compound, XLPE Insulated Screened with extruded semi-conducting compound in combination with Copper Tape, cores laid up, inner sheath of Thermoplastic tape, galvanized flat steel strip armoured and overall Extruded PVC Type ST- 2 Outer Sheathed cable etc., complete. Make: Torrent / Universal / Unicab / Havells / KEI/Polycab/Gloster/RR Kabel/RPG MAT 03460 complete as per IE rules and other incidental charges and as directed by the departmental officer incharge of work
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH
Providing river sand filling brought from approved quarry including cost and conveyance of all material and all labour charges such as filling in layers watering ramming etc complete as per ss and as directed by the departmental officer incharge of work.
Providing PCC 1:4:8 using 40 mm graded SS 5 HBG m/c metal and OPC coarse and fine aggregate confirming to IS 383 including cost and conveyance of all materials and labour charges, machine mixing , vibration,laying in position, curing etc., complete as per ss and as directed by the departmental officer incharge of work.
Supply and placing of the design mix concrete corresponding to IS -456 using WEIGH BATCHER/MIXER using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including all operational ,incidental and labour charges such as weigh batching ,machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work (APSS NO 402) with minimum cement content as per IS Code from standard suppliers approved by the deparment including pumping , centering,shuttering,laying concrete, vibrating,curing etc M25 design mix concrete
column footings
Columns 1.20-0.10-0.10-0.30+1.80
Plinth beam 2(15+12)=54-gate3.00=51.00
Painting Walls with Snowcem or other equal and approved Water Proof Cement Paint 2 Coats (All Colours) over a base coat of aproved cement primer making 3 coats in total including cost of all materials all labour charges, conveyance charges of materials and other incidental charges, scaffolding, lifting and as directed by the departmental officer in charge of work. For Pump house
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying etc., complete for finished item of work in all floors.( APSS No.126)
Supplying and fixing galvanised steel barbed wire (IS : 278-1962 Type I) weighing 9.38 Kg per 100 metres (min.), Straining and fixing to any type of standard, rails, straining bolts, including securing with and provision of galvanised mild steel wire, stapples or steel pins, etc., as directed (Posts and struts of wood, concrete, steel, etc.) and straining bolts shall be paid for separately). complete as per ss and as directed by the departmental officer incharge of work.
Manufacture,supply,delivery of MS grill gates,window ornamental safety grill ,made with MS flats,MS angles,MS squares etc including welding, finishing, etc complete as per ss and as directed by the departmental officer incharge of work.
Providind Synthic enamil paint two coats over the primery coat excluding cost of primer including cost and conveyance of all matrial and all labour charges etc complete as per ss and as directed by the departmental officer incharge of work.
supply and filling the transformer yard with 40mm HBG metal including cost of all materials, conveyance charges of materials and all operational, incidental and labour charges etc.,complete as per ss and as directed by the departmental officer incharge of work.
Providing 500mm dia. D.I. K9 Raw Water Pumping main from Intake well in Godavari River to proposed OHBR at Bobbarlanka
Cutting and open of B.T. Road surface (as well as asphalt concrete upto 75mm thick) including water bound macadam including stacking of excavated materials,hiring of maachinery ,fuel charges,wages of drivers of for lying of pipe lines as per the ditections of the departmental authorities. For Pipe line trenches.
Earth work excavation in all soils up to SDR & stone matrix by machinery as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and back filling in trenches with excavated suitable material as per Technical Specification No.305 MORD/304 MORTH up to initial lift of 3.0Mts. For Pipe line trenches.
Filling with Sand for pipe line trenches This rate including cost of Sand,all labour charges,watering,ramming,and other incidental charges etc as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH etc.,complete as per S.S and as directed by the departmental officer incharge of work
Supply and delivery of D.I. Socket and spigot centrigually cast (spun) Ductile Iron pressure pipes of K-9 Class confirming to specification No.IS 8329/2000 of standard lengths suitable for push-on joint (Rubber gasket D jointing) with cement lining inside the pipe, out side Zinc Coating including cost of Pipe, excluding GST and other duties. The rate including transportation and conveyance to work spot and stacking at site etc., complete as per S.S and as directed by the departmental authorities. For 500mm dia. D.I K9 Pumping main
Supply and delivery of Centrifugally cast (spun) upto 500mm dia Ductile Iron fittings conforming to is:9523/2000 having dimentions as per table. The rate including zinc coated externally with inside mortar lining (with finishing as per class 13/is 9523/2000) including transportation, taxes and duties etc., complete as per S.S and as directed by the departmental authorities.
Supply and delivery of Centrifugally cast (spun) upto 500mm dia Ductile Iron fittings conforming to is:9523/2000 having dimentions as per table. The rate including zinc coated externally with inside mortar lining (with finishing as per class 13/is 9523/2000) including transportation, taxes and duties etc., complete as per S.S and as directed by the departmental authorities.
Supply and delivery of centrifugally cast (spun) Ductile Iron pressure pipes with flanged (welded) ends for water, gas, sewage conforming to I.S.: 8329/2000 in standard working lengths of1,2,3, 4, 5 mts for classification K9 with cement mortar lining inside the pipes with outside zinc coating including transportation, ecomplete as per S.S and as directed by the departmental officer incharge of work as follows
300mm dia. 2.00m. Long for scours
500mm dia. 1.00m. Long for sluice and non return valves and flow meter
500mm dia. 2.00m. Long at intake well
Lowering of 500mm dia D.I. socket and spigot Pipes and fittings carefully in to the trench and laying them true to alignment and gradient including all labour charges, sundries as per BIS No. 3114/85 etc., complete as per S.S and as directed by the departmental authorities.
Jointing of D.I. Pipes & fittings with Rubber Gasket including all sundries filling with water with a water lead up to 500m and testing to required pressure etc., complete as per BISNo.3114/85 and as directed by the departmental authorities.
Lowering of 500mm dia D.I. Pipes of all classes and fittings with flanged ends carefully into the trenches and laying them true to alignment and gradient including all sundries, but excluding conveyance from source of supply as per BIS No.3114/94. 500nn dia complete as per S.S and as directed by the departmental authorities.
Lowering of 500mm dia D.I. Pipes of all classes and fittings with flanged ends carefully into the trenches and laying them true to alignment and gradient including all sundries, but excluding conveyance from source of supply as per BIS No.3114/94. 300 mm dia complete as per S.S and as directed by the departmental authorities.
Jointing the 500mm dia C.I. Pipes, fittings and valves with flanged ends including cost of jointing materials such as bolts, nuts, rubber insertion, white lead and including filling with water with a water lead upto 500 m and testing to required pressure etc., comp as per BIS No.3114/85. complete as per S.S and as directed by the departmental authorities.as follows
500mm dia.
300mm dia.
150mm dia.
Manufacture, supply and delivery at work site 500mm dia internal dia M.S.Pipe fabricated with 10mm thick MS plates confirming to IS 2062-1992 of grade A manufactured as per IS 3589-2001 in suitable lengths to suit the sit conditionse , in co-ordination with the concerned authorities as per approved drawings and directed by the Engineer-in –charge 600 mm dia 10 mm thick plate
Supply and delivery of "Resilient Seated Soft Sealing" Gate Valves (Sluice Valves) with Bodyand Bonnet of Ductile Iron GGG-40/SG-400/15 or GGG-50/SG-500/7 or Equivalent as per IS1865, IS:3896-2 and Wedge fully Rubber Lined with food grade quality grade W270 grade EPDM, Replaceable Spindle Nut without gland packing with 3-O ring protection system on the Shaft and Seals of NBR. The Valves should be Vacuum tight and 100% leak proof with face to face dimensions as BS:5163 Type A/IS:14846. All the valves should be with fusion bonded Electrostatic Powder coating both inside and outside (Min 250 Microns)- RAL 5005 with Pocket Less Straight through body Passage conforming to Design standards of DIN- 3202F4/BS:5163 Type A Flange drilling as per IS - 1538 and per IS:1538. PN16 including transportation PN 1.6 as follows as per ss and as directed by the departmental officer incharge of work
500mm Ø DI D/F valve - PN16
300mm Ø DI D/F valve - PN16 (for Scour)
Supply & Delivery of 150mm dia Tamper Proof DI Flanged Single Chamber Air Release Valves with body & cover made of Ductile Iron Grade GGG-40/SG- 400/15 or GGG-50/SG-500/7 or Equivalent as per IS1865, IS:3896-2 with Food Grade Epoxy Powder Coating(EP-P) (Min:250 Micron) inside and Outside of Color Blue RAL 5005. All internal parts such as Float, shell, Cove Bolts etc. made of Austenitic alloy steel of SS AISI 304/316 and DN 50 float of and other components with ABS/ PTFE/ EPDM/ NBR and generally conforming to DIN/BIS/AWWA standards (or) combination Flange drilling as per IS - 1538 and ,including transportation. -150mm dia. PN16 on 500 mm line as per ss and as directed by the departmental officer incharge of work
Supply, Delivery of 500mm dia D.I Double Flanged Swing Check type Reflux valves (Non Return Valves) of following dia. conforming to IS- 5312 (Pts-1&2) (with amendments up to date, if any) having Body, Cover, Door, Bearing holder with D.I; Hinge pin, Door pin, Door suspension pin with Stainless Steel (IS 6603);Body seat ring , Door face ring, Bearing bushes, Plugs for hinge pin with Leaded Tin Bronze ( IS 318 ); Bolts, Nuts with Carbon steel; Gaskets with Rubber; Hinges with Cast steel; including transportation and complete.PN 1.6 (MPa) 500 mm dia as per ss and as directed by the departmental officer incharge of work
Manufacture and supply of- 150mm dia Air Release – Vacuum Break – Surge Alleviation” Valve for potable water. Construction material Cylindrical Body of Ductile Iron GGG-50/SG-500-7, Three cylindrical Floats of High Density Poly Ethylene. Baffle Plate, Orifice venture and all construction bolts of stainless steel, coating internally and externally. Electrostatically applied epoxy (1) Flange connection as per IS 1538, (2) Female (BSP/NTP Threaded for sizes 25 mm PN 16- 150mm dia. PN16 on 500 mm line as per ss and as directed by the departmental officer incharge of work
Labour charges for lowering and keeping in position of C.I./DI Sluice valves(with cap/with hand wheel), reflux valves and scour valves and flow meter
500mm dia.
300mm dia for scour
Labour charges for fixing Kinetic Air Valves with isolating Sluice valves, Double Air valves/ Air Cushion valve excluding cost of jointing materials such as bolts, nuts and rubber insertions etc., complete. dia. of Air Valve in mm 150 mm Dia as per ss and as directed by the departmental officer incharge of work
Construction of R.C.C. thrust blocks using using VRCC M20 Gr. nominal mix using 20mm HBG metal from approved quarry including cost and conveyance of all materials at site, seignorage charges, labour charges for machine mixing, laying, vibrating including centering charges but excluding cost of steel for reinforcement and its fabrication including curing etc., complete.
Construction of Anchor blocks with P.C.C. M20 nominal mix using 20mm HBG crushed metal from approved quarry including cost and conveyance of all materials, seignorage charges and all labour charges for machine mixing, laying, vibrating and curing including centering charges etc.,complete as per S.S and as directed by the departmental authorities.
Providing High Yield Strength Deformed (HYSD)/Thermo Mechanically Treated (TMT)/Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works,including labour charges for straightening, cutting,bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG,forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps,couplings,chairs,spacer bars including cost and conveyance of binding wire,cover blocks and all incidental,operational,labour charges such as cutting, bending, placing in position,tying including all materials etc.,complete for finished item of work in all floors.( APSS No.126) for pre cast slabs of culverts - RBR-FNDN-8 & Revised Data sl.No-5
Construction of R.C.C valve chambers as per Standard Drawings with RCC cover slab fixed with CI/DI manhole Frame & Cover with lock and Key arrangement. The Mix shall not be less than VRCC M 20 grade with 150mm thick side walls, 150mm thick top slab, 150mm thick base slab over base course of 100mm thick (1:4:8) prop including cost and conveyance of all materials and all labour charges etc.complete as per S.S finished item of work for 500mm dia
Construction of CC Scour Valve Construction of R.C.C valve chambers as per Standard Drawings with RCC cover slab fixed with CI/DI manhole Frame & Cover with lock and Key arrangement. The Mix shall not be less than VRCC M 20 grade with 150mm thick side walls, 150mm thick top slab, 150mm thick base slab over base course of 100mm thick (1:4:8) propost and conveyance of all materials and all labour charges etc.complete as per S.S for finished item of work. For 300mm dia
Construction of CC Air Valve chambers suitable to the Air Valve Construction of R.C.C valve chambers as per Standard Drawings with RCC cover slab fixed with CI/DI manhole Frame & Cover with lock and Key arrangement. The Mix shall not be less than VRCC M 20 grade with 150mm thick side walls, 150mm thick top slab, 150mm thick base slab over base course of 100mm thick (1:4:8) propincluding cost and conveyance of all materials and all labour charges etc.complete as per S.S for finished item of work
Filling with crusher stone Dust This rate including cost of Sand,all labour charges,watering,ramming,and other incidental charges etc as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH etc.,complete as per S.S and as directed by the departmental officer incharge of work
Restoration of CC Road by Using Concrete mixture Plain Cement concrete nominal mix M-30 (Cement : fine aggregate: coarse aggregate ) using 20mm size Hard Granite Machine Crushed Graded Metal including cost and conveyance of all materials like cement, sand, coarse aggregate water etc., to site , seigniorage charges on all materials, labour charges , for mixing , laying, concrete , ramming in 15 cm layers, finishing top surface to the required level curing etc., complete for finished item of work with nomonal reinforcement for Road restoration.
Supply, delivery of 500mm dia Electromagnetic flow meter manufacture should have ISO 9001:2008 certification anf flow meter testing confirming to ISO 17025; Flow meter tube SS 304; Flnages Carbon steel as per DIN PN 10 or higher rating as per requirement ;Liner;Hard rubber or PTFE suitsble for drinking water application; Grounding:Grounding rings SS 304/Grounding electrodes of material SS 316; Coil housing and junction box SS 304 Die cast Aluminium / Carbon steel with anticorrossive apoxy coating of minimim thickness 150 Micron /Equivalent as per EN-ISO-12944 standard as per site condition ingress protection ; IP 68 for Sensor and IP 67 for Transmitter; Flow Transmitter accuracy +/- 0.50% of measured values of velocities 0.50m/sec and above ,Display:Digital LCD/LED (backlit LCD/LED) Display instantaneous flow ,Bi-directional flow,totalised flow, Cable beween flow head and Transmitter maximum 25 m including PVC conduit,Surge arrester to be provided.Power supply and out put 230 V AC or 24V DC as appilicable to site condition and -4-20m A HART;Compatible to SCADA/WEB based data acqusition system;Flow meter test lab certification should be provided from NABL approved lab/FCRI Excluding taxes and duties with 5 years warrenty (make M/S krohne Marshall / Endress+Hauser / Yokagawa / siemens / Emerson / ABB / or equivalent make
Supply,delivery of 500mm dia strainer /dirt box of T type of the following dia suitable to respective meters of same size inclusive of costs,transportation, etc complete(rate as per quatation)
Manufacture, Supply and delivery of 500mm dia MS. Dismantling Joints with both side flange end suitable for installation in between flange end pipes. Thickness as per IS: 7322. These rates are and transportation charges etc., complete - 500 n Dia complete as per ss and as direceted by departmental officer incharge of work
providing P.C.C. M20 nominal mix using 20mm HBG crushed metal from approved quarry including cost and conveyance of all materials, seignorage charges and all labour charges for machine mixing, laying, vibrating and curing including centering charges etc.,complete as per S.S and as directed by the departmental authorities for encasing .
Construction of electrician / operator/watchman quarters at intake well (OHBR)
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD. Note : Classifications of Earth Work Specification are as per 302.2.1(a) of MORD and 301.2.1 of MORT&H--ordinary soil--manual means upto 3m depth for foundations of buildings in restricted places
Filling with Sand in structures bedding This rate including cost of Sand,all labour charges,watering,ramming,and other incidental charges etc as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH etc.,complete as per S.S and as directed by the departmental officer incharge of work
Providing PCC 1:4:8 using 40 mm graded SS 5 HBG m/c metal and OPC coarse and fine aggregate confirming to IS 383 including cost and conveyance of all materials and labour charges, machine mixing , vibration,laying in position, curing etc., complete as per ss and as directed by the departmental officer incharge of work
Supply and placing of the design mix concrete corresponding to IS -456 using WEIGH BATCHER/MIXER using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including seigniorage charges ,sales and other taxes on all materials including all operational ,incidental and labour charges such as weigh batching ,machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work (APSS NO 402) with minimum cement content as per IS Code from standard suppliers approved by the deparment including pumping , centering,shuttering,laying concrete ,vibrating,curing etc M20 design mix
column footings
Columns 1.50-0.15-0.15-0.20-0.25 =0.75 + basement 0.75m+superstructure 3.35m=4.85m
Plinth beam
Lintle beams Windows
Roof Beams
Roof slab 0.125m thick with 0.30m extension all sides
Sunshades 0.60m wide, 0.10m at fixed end and 0.05m at free end Windows
Loft slab 0.075m thick kitchen
Brick work in CM 1:6 mix using 2nd class bricks brought from approved kilns including cost and conveyance of all materials and all labour charges ,curing for 21 days etc complete as per ss and as directed by the departmental officer incharge of work
Ground floor
1st floor
Plastering with CM (1:5), 12 mm thick including cost and conveyance of all materials and labour charges, watering , smooth finishing cost material, scoffoliding other incidental charges etc.,complete as per ss and directed by the departmental authorities of the work as per site conditions.But excluding seigniorage Charges.As follows.
Ground floor
1st floor
Plastering with CM (1:3), 12 mm thick including cost and conveyance of all materials and labour charges, watering , smooth finishing cost material, scoffoliding other incidental charges etc.,complete as per ss and directed by the departmental authorities of the work as per site conditions.But excluding seigniorage Charges.As follows.
Painting Walls with Snowcem or other equal and approved Water Proof Cement Paint 2 Coats (All Colours) over a base coat of aproved cement primer making 3 coats in total including cost of all , conveyance charges of materials and other incidental charges, scaffolding, lifting and as directed by the departmental officer in charge of work
Supply delivary and fixing RCC Jollys includnig cost and conveyance of all material and all labour charges for fixing etc complete as ss per ss and as direceted by the departmental officer incharge of work
Supply and fixing Aluminium Anodised Doors - Single Shutter as per approved drawing with aluminium anodised sections of Jindal sections and outer frame top horizontals & both verticals of 2408 of size 101.6 x 44.75 x 3.18 mm Shutter frame top, bottom and verticals of 4504 of size 44.45 mm x 47.62 mm x 3.18 and Middle lock rail of 4621 of size 49.91 x 44.45 x 3 mm with tinted-bronze/green glass 5 mm thick(middle to top),MDF Board-exterior both sides laminaed 12mm thick(middle to bottom) fixed including supply and fixing aluminium handles of 150 mm for each shutter and all labour charges for fixing the fixtures with required no.of screws, bolts and nuts and including labour charges for fixing the frame in position, fixing shutter to frame etc. completed for finished item of work
Door -D - 1.20X2.10 m
doors D1 - 1.0X2.10m
Supply and fixing Aluminium Anodised Two/ Three Track Sliding Windows as per approved drawing with aluminium anodised sections of Series C Jindal sections and outer frame top horizontals & both verticals of 8774 of size 62 x 29.5 mm and bottom horizontal - two track frame of 8773 of size 62 x 29.5 mm, Shutter frame top, bottom and verticals of 8304 of size 50 mm x 20 mm and Weather interlocking frame of 8306 of size 50 x 20 with plain clear float glass 5 mm thick fixed including supply and fixing aluminium handles of 100 mm for each shutter, nylon rollers assembly and all labour charges for fixing the fixtures with required no.of screws, bolts and nuts and including labour charges for fixing the frame in position, fixing shutter to frame etc. completed for finished item of work
Providing and fixing factory made polyvinyl chloride (PVC) Door Frame of the size 50 x 47mm with a wall thickness of 5mm, made out of extruded 5mm rigid PVC foam sheet, mitre cut at two corners and joined with 2nos. of 150mm long brackets of 15x15mm M.S. square tube. The two vertical door profiles are to be reinforced with 19x19mm M.S. Square tube of 19 gauge. The door frame shall be fixed to the wall using 65/100mm long M.S. Screws through the frame by using PVC fasteners. A minimum of 4nos. of screws to be provided for each vertical member & minimum 2nos. for horizontal member etc. complete as per manufacturers specification and direction of Engineer-in-Charge for finished item of work
Providing and fixing 30mm thick Solid panel PVC door shutter consisting of frame made out of M.S. tubes of 19 gauge thickness and size of 19mm x 19mm for stiles, & 15mm x 15mm for top & bottom rails. M.S. frame shall have a coat of steel primers of approved make and manufacture. M.S. frame shall be covered with 5mm thick heat moulded PVC ‘C’ channel of size 30 x 50mm forming stiles, and 5mm thick, 75mm wide PVC sheets for top rail, lock rail & bottom rail on either side, and 10mm (5mm x 2) thick, 20mm wide cross PVC sheet as gap insert for top rail & bottom rail. Panelling of 5mm thick PVC sheet to be fitted in the M.S. frame welded / sealed to the stiles & rails with 30mm wide x 5mm thick PVC sheet beading on either side, and joined together with solvent cement adhesive etc. An additional 5mm thick PVC strip of 20mm width is to be stuck on the interior side of the ‘C’ Channel using PVC solvent adhesive. Complete as per direction of Engineer-in-charge, manufacturer’s specification & drawing for finished item of work
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, etc., complete for finished item of work in all floors.( APSS No.126)
Plastering with CM (1:3), 20 mm thick including cost and conveyance of all materials and labour charges, watering , smooth finishing cost material, scoffoliding other incidental charges etc.,complete as per ss and directed by the departmental authorities of the work as per site conditions.But excluding seigniorage Charges.for flooring
Manufacture,supply,delivery of MS grill gates,window ornamental safety grill ,made with MS flats,MS angles,MS squares etc including welding,finishing,applying red oxide paint as primary coat etc complete as per ss and as direceted by the departmental officer incharge of work
Providing two coats of Synthic enamil paint over new Iron works including cost and conveyance of all material and all labour charges etc complete as per ss and as direceted by the departmental officer incharge of work
Supply, delivery and fixing of 110mm dia single socket PVC pipes 4 kg/sqcm prince/Sudhakar or any ISI brand for rain water pipes with clamps complete as per ss and as direceted by the departmental officer incharge of work
Supply and fixing of 25 mm dia 2.00 mm thick PVC pipe concealed in roof slab with all required accessories including masonary work all labour chages complete as per ss and as direceted by the departmental officer incharge of work
Supply and fixing of 20 mm dia 1.50 mm thick PVC pipe concealed in walls with all required accessories including masonary work for light , fan and plug point with metal deep box including all labour chages
Wiring with 2 runs 14/0.3 mm. (1.0. sq.mm) Fire retardant PVC insulated Flexible copper cable in existing pipe with 6A siwtch, ceiling rose and 3 mm thick hyla sheet covering to switch control box including all labour charges etc,., complet for light, bell , fan and exhaust fan points in non - residential building complete as per IE Rules and as direceted by the departmental officer incharge of work
Wiring with 2 runs 14/0.3 mm. (1.0. sq.mm) Fire retardant PVC insulated Flexible copper cable in existing pipe with 6A modular siwtch control and 3/2 pin sockets fixing on board including all labour charges complete as per IE Rules and as direceted by the departmental officer incharge of work
supply and run of 2 of 36/0.3 mm. (1.5. sq.mm) Fire retardant PVC insulated Flexible copper cable in existing pipe for mains including all labour charges complete as per IE Rules and as direceted by the departmental officer incharge of work
supply and run of 1 of 14/0.3 mm. (1.0. sq.mm) Fire retardant PVC insulated Flexible copper cable in existing pipe for earth continuity including all labour charges etc.complete as per IE Rules and as direceted by the departmental officer incharge of work
supply and run of 2 of 6 sq.mm (7/18) WPSC alluminium cable along with No.10 SWG G.I barer wire through PVC cleats with all accessories including all labour charges etc.,complete as per IE Rules and as direceted by the departmental officer incharge of work
Providing independent earthing by excavating a trench to a depth of 2.10m in all soils, as per size specied in data ,using 40 mm dia B class GI pipe 2.50m long with necessary accessories with hume pipe ring duly providing staggered holes including filling with equal proportion of salt and charcoal in layers and all labour charges etc complete complete as per IE Rules and as direceted by the departmental officer incharge of work
Supply and fixing SPN Distribution board with IP-20 protection suitable for single phase Earth Leakage Circute Braker (ELCB) / Residual Current Circute Braker (RCCB) / Double Pole (DP) Isolator as incomer and 10kA SP MCBs as out going including internal connections and labour charges for surface / flush mounting etc., complete complete as per IE Rules and as direceted by the departmental officer incharge of work
Supply of 48" (1200mm) Sweep 5 star rated Ceiling Fan , with double ball bearings, air delivery more than 200 cubic meter/min but without Regulator.Makes : Crompton HS Plus / Havells ES Neo/Orient Energy Star/ Halonix(Zephyr)/Polycab(Synergy Star) unit each complete as per IE Rules and as directed by the departmental officer incharge of work
Supply of stepped type Electronic Regulator of makes GM G Home / Gold Medal Olive / Million Zoom / Anchor Penta Cherry / Great white Omega
Supply and transportation of 20W, 2000 lumens, T8,1200mm length LED retro tube light,wide operating voltage with double side connection, PF≥0.9,Surge protection: > 2KV, THD<15%, with inbuilt driver and frosted cover CCT: 3000K - 6500K as desired by the department and as per IS specifications, minimum CRI≥80,.etc complete with 5 years warranty.LUMINAIRE MAKE: Phillips / OSRAM / GE / Crompton /VIN / Bajaj / Havells / Halonix / HPL. LED MAKE : PHILIPS LUMILEDS / CREE / NICHIA /OSRAM / SAMSUNG / LG LEDs.complete as per IE Rules and as directed by the departmental officer incharge of work
Labour charges for Fixing of Ceiling fan and regulator including transportation and giving connections with twin core wire etc., complete as per IE Rules and as directed by the departmental officer incharge of work
Labour charges Fixing of 40W tube light luminaire on wall / Ceiling with / TW round blocks with all accessories including giving connections and all labour charges etc., complete.complete as per IE Rules and as directed by the departmental officer incharge of work
Providing & Placing on Terrace (at all floor levels) polyethylene water storage tank with Double layer approved brand & manufacture with cover and suitable locking arrangement & making necessary holes for inlet & outlets and over flow pipes but without fittings & base support for tanks complete as per ss and as directed by the departmental officer incharge of work
Supplying & Fixing Orissa Pan white glazed W.C 1st quality ISI marked conforming to IS:2556-Part-3-1981 with "P" or "S" trap Hindware/ Parryware/ Neycer - ISI Mark: 630 mm x 450 mm unit each
Supplying & Fixing Indian make Flat Back Wash Hand Basin (HSW/Parryware/ Neycer) 1st quality conforming to IS:2556-Part-4:1972 with waste fittings like rubber plug, chain, 32 mm nominal size C.P. Fitting with parallel pipe thread conforming to IS:2963-1979 and fitted with 15 mm nominal bore Chromium Plated Pillar Tap of 1st quality Indian make 400 grams Seiko/ Senior/ Nice/ Esso or equivalent complete with standard CI brackets including wooden block: 550 x 400 mm - Double C.P. Pillar cock unit each complete as per ss and as directed by the departmental officer incharge of work
Supply of 110 mm dia 3 m single Socket PVC/SWR pipe - 6 Kg/sq.cm - Prince/Sudhakar/Kisan/Supreme or any ISI Brand. complete as per ss and as directed by the departmental officer incharge of work
Supply of 110 mm dia - Plain Bend 87.5 Degree - UPVC/SWR Pipe fittings (Prince/Sudhakar/Kisan/Supreme or any ISI Brand) complete as per ss and as directed by the departmental officer incharge of work
Supply of 110 mm dia - Coupler - UPVC/SWR Pipe fittings (Prince/Sudhakar/Kisan/Supreme or any ISI Brand complete as per ss and as directed by the departmental officer incharge of work
Labour charges for laying, fixing and commissioning the PVC pipes including couplers/ bends/ tees etc any diameter including fixing necessary fittings like bends, plugs, couplers, junctions, tees, etc with solvent jointing as per standard practice complete as per ss and as directed by the departmental officer incharge of work
Constructing 457.2 mm x 457.2 mm (1'6"x1'6") brick in CM 1:6 prop. Masonry. Inspection chamber up to 914.4 mm (3'0") and fitted with light weight 457.2 mm x 457.2 mm (1'6"x1'6") C.I frame and cover of 20 Kg complete as per ss and as directed by the departmental officer incharge of work
S& F GI pipe Medium Grade properties & weight as per IS 1239 ISI mark with GI fittings including the cost of pipe & its fittings & labour charges complete complete as per ss and as directed by the departmental officer incharge of work as follows
25 mm dia nominal bore -from tank to jn for of individual lines
20 mm dia nominal bore -from jn for of individual lines to toilets & Kitchen
15 mm dia nominal bore -for internal
S&F of GI &GM fittings
GM Ball valve with SS Ball and SS Spindle as per IS - Class - I, Indian make heavy type - 25 mm NB Size
GM Ball valve with SS Ball and SS Spindle as per IS - Class - I, Indian make heavy type - 20 mm NB Size
GM Ball valve with SS Ball and SS Spindle as per IS - Class - I, Indian make heavy type - 15 mm NB Size
S&F 12.7 mm N.P bib tap Indian make heavy dutys Seiko/ Senior/ Nice or equivalent
Supply and fixing GI union Ist Quality complete as per ssa and as directed by the departmentaal officer incharge of work
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD. Note : Classifications of Earth Work Specification are as per 302.2.1(a) of MORD and 301.2.1 of MORT&H--ordinary soil--manual means upto 3m depth by manual means upto 3.00m depth
Filling in for for a struture Bedding as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH for foundations RBR-FNDN-2(1) complete as per ss and as direceted by the departmentaal officer incharge of work
Providing PCC 1:4:8 using 40 mm graded SS 5 HBG m/c metal and OPC coarse and fine aggregate confirming to IS 383 including cost and conveyance of all materials and labour charges, machine mixing , vibration,laying in position, curing etc., complete
Brick work in CM 1:6 mix using 2nd class bricks brought from approved kilns including cost and conveyance ,sacfolding,lifting,of all materials and all labour charges ,curing for 21 days etc complete as per ss and as direceted by the departmentaal officer incharge of work
Plastering with CM (1:3), 20 mm thick including cost and conveyance of all materials and labour charges, watering , smooth finishing cost material, scoffoliding other incidental charges etc.,complete as per ss and directed by the departmental authorities of the work as per site conditions.But excluding seigniorage Charges
RCC M-25 Design mix (cement,fine aggregate,coarse aggregate) corresponding to Table -9 of IS -456 using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including seigniorage charges ,sales and other taxes on all materials including all operational ,incidental and labour charges such as machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work,but including centering,shuttering unit 1.00cum for culvert slabs RBR-SBST-5 A
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying including sales and other taxes on all materials etc., complete for finished item of work in all floors.( APSS No.126)
Construction of OHBR with 33m staging at Bobbarlanka
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH as follows
Mechanical Means up to 3 metres depth
Mechancal means 3 to 6 metres depth in ordinary soils
Manual means 3 to 6 metres depth in ordinary soils
Filling sand in for structure Bedding as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH for foundations RBR-FNDN-2(1) complete as per ss and as direceted by the departmentaal officer incharge of work
Providing CC(1:4:8) using 40mm HBG metal. The rate including cost and conveyance of all material, labour charges for mixing, laying, curing, etc., complete as per SS. And as direceted by the departmentaal officer incharge of work
Supply and placing M30 Grade of the Design Mix Concrete corresponding to IS 456 using WEIGH BATCHER / MIXER with 20mm size graded machine crushed hard granite metal (coarse aggregate) from approved quarry including cost and conveyance of all materials like cement, fine aggregate (sand) coarse aggregate, water etc., to site and including all operational, incidental and labour charges such as weigh batching, machine mixing, laying concrete, curing etc.,complete but excluding cost of steel and its fabrication charges for finished item of work (APSS No. 402)with minimum cement content as per IS code from standard suppliers approved by the department including pumping, centering, shuttering, laying concrete, vibrating, curing etc. complete but excluding cost of steel and its fabrication charges for finished item of work. with steel scafolding'complete for raft excluding cost of steel.
Supply and placing M30 Grade of the Design Mix Concrete corresponding to IS 456 using WEIGH BATCHER / MIXER with 20mm size graded machine crushed hard granite metal (coarse aggregate) from approved quarry including cost and conveyance of all materials like cement, fine aggregate (sand) coarse aggregate, water etc., to site and including Seigniorage charges, sales & other taxes on all materials including all operational, incidental and labour charges such as weigh batching, machine mixing, laying concrete, curing etc.,complete but excluding cost of steel and its fabrication charges for finished item of work (APSS No. 402)with minimum cement content as per IS code from standard suppliers approved by the department including pumping, centering, shuttering, laying concrete, vibrating, curing etc. complete but excluding cost of steel and its fabrication charges for finished item of work. with steel scafolding'complete for raft excluding cost of steel.
Supply and placing M30 Grade of the Design Mix Concrete corresponding to IS 456 using WEIGH BATCHER / MIXER with 20mm size graded machine crushed hard granite metal (coarse aggregate) from approved quarry including cost and conveyance of all materials like cement, fine aggregate (sand) coarse aggregate, water etc., to site and including Seigniorage charges, sales & other taxes on all materials including all operational, incidental and labour charges such as weigh batching, machine mixing, laying concrete, curing etc.,complete but excluding cost of steel and its fabrication charges for finished item of work (APSS No. 402)with minimum cement content as per IS code from standard suppliers approved by the department including pumping, centering, shuttering, laying concrete, vibrating, curing etc. complete but excluding cost of steel and its fabrication charges for finished item of work. with steel scafolding'complete for raft excluding cost of steel. lifting upto 32mts and above
32m above
Supply and placing M30 Grade of the Design Mix Concrete corresponding to IS 456 using WEIGH BATCHER / MIXER with 20mm size graded machine crushed hard granite metal (coarse aggregate) from approved quarry including cost and conveyance of all materials like cement, fine aggregate (sand) coarse aggregate, water etc., to site and including all operational, incidental and labour charges such as weigh batching, machine mixing, laying concrete, curing etc.,complete but excluding cost of steel and its fabrication charges for finished item of work (APSS No. 402)with minimum cement content as per IS code from standard suppliers approved by the department including pumping, centering, shuttering, laying concrete, vibrating, curing etc. complete but excluding cost of steel and its fabrication charges for finished item of work. with steel scafolding'complete forBottom slab
Supply and placing M30 Grade of the Design Mix Concrete corresponding to IS 456 using WEIGH BATCHER / MIXER with 20mm size graded machine crushed hard granite metal (coarse aggregate) from approved quarry including cost and conveyance of all materials like cement, fine aggregate (sand) coarse aggregate, water etc., to site and including Seigniorage charges, sales & other taxes on all materials including all operational, incidental and labour charges such as weigh batching, machine mixing, laying concrete, curing etc.,complete but excluding cost of steel and its fabrication charges for finished item of work (APSS No. 402)with minimum cement content as per IS code from standard suppliers approved by the department including pumping, centering, shuttering, laying concrete, vibrating, curing etc. complete but excluding cost of steel and its fabrication charges for finished item of work.for ring beam
Supply and placing M30 Grade of the Design Mix Concrete corresponding to IS 456 using WEIGH BATCHER / MIXER with 20mm size graded machine crushed hard granite metal (coarse aggregate) from approved quarry including cost and conveyance of all materials like cement, fine aggregate (sand) coarse aggregate, water etc., to site and including Seigniorage charges, sales & other taxes on all materials including all operational, incidental and labour charges such as weigh batching, machine mixing, laying concrete, curing etc.,complete but excluding cost of steel and its fabrication charges for finished item of work (APSS No. 402)with minimum cement content as per IS code from standard suppliers approved by the department including pumping, centering, shuttering, laying concrete, vibrating, curing etc. complete but excluding cost of steel and its fabrication charges for finished item of work. with steel scafolding'complete for raft excluding cost of steel.
staging from 25-26m
staging from 26-27m
staging from 27-28m
staging from 28-29m
Supply and placing M30 Grade of the Design Mix Concrete corresponding to IS 456 using WEIGH BATCHER / MIXER with 20mm size graded machine crushed hard granite metal (coarse aggregate) from approved quarry including cost and conveyance of all materials like cement, fine aggregate (sand) coarse aggregate, water etc., to site and including Seigniorage charges, sales & other taxes on all materials including all operational, incidental and labour charges such as weigh batching, machine mixing, laying concrete, curing etc.,complete but excluding cost of steel and its fabrication charges for finished item of work (APSS No. 402)with minimum cement content as per IS code from standard suppliers approved by the department including pumping, centering, shuttering, laying concrete, vibrating, curing etc. complete but excluding cost of steel and its fabrication charges for finished item of work. with steel scafolding'complete for top ring beam
Supply and placing M30 Grade of the Design Mix Concrete corresponding to IS 456 using WEIGH BATCHER / MIXER with 20mm size graded machine crushed hard granite metal (coarse aggregate) from approved quarry including cost and conveyance of all materials like cement, fine aggregate (sand) coarse aggregate, water etc., to site and including Seigniorage charges, sales & other taxes on all materials including all operational, incidental and labour charges such as weigh batching, machine mixing, laying concrete, curing etc.,complete but excluding cost of steel and its fabrication charges for finished item of work (APSS No. 402)with minimum cement content as per IS code from standard suppliers approved by the department including pumping, centering, shuttering, laying concrete, vibrating, curing etc. complete but excluding cost of steel and its fabrication charges for finished item of work. with steel scafolding'complete for top slab
Providing impervious coat to exposed RCC roof slab surface with CM(1:3), 20mm thick with 1kg of water proof compound per bag of cement laid over roof when it is green including cost of all materials, seigniorage charges, excluding conveyance charges of materials and including all operational, incidental and labour charges for mixing mortar, laying, rendering smooth and thread lining, curing, rounding off junctions of wall and slab etc,, complete for finished item of work
S&F HYSD/TMT/MS bars (Lap splicing)Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars ( Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying including on all materials etc., complete for finished item of work in all floors.( APSS No.126).
Painting Walls with Snowcem or other equal and approved Water Proof Cement Paint 2 Coats (All Colours) over a base coat of aproved cement primer making 3 coats in total including cost of all materials, conveyance charges of materials and including all operational, incidental and labour charges etc,, complete for finished item of work as directed by the departmental authorities.
Centrifugally cast (Spun) Ductile Iron pressure pies with flanged (welded) ends for water, gas, sewage conforming to IS: 8329/2000 in standard working lengths of 1,2,3, 4, 5 mts for classification K9 with cement mortar lining inside the pipes with outside zinc coating. Rates are ex-factory, including transportation complete as per ss and as direceted by the departmentaal officer incharge of work as follows
inlet 500 mm DIDF pipes 4.00 m long
inlet 500 mm DIDF pipes 1.00 m long
out let 600 mm dia DIDF pipes 4.00m
out let 600 mm dia DIDF pipes 1.00m
scour 300 mm dia DIDF pipes 4.00 m long
scour 300 mm dia DIDF pipes 1.00 m long
over floe pipes 400 mm dia DIDF 4.00m long
over floe pipes 400 mm dia DIDF 1.00m long
Centrifugally cast (spun) upto 500mm dia Ductile Iron Fittings conforming to IS:9523/2000 having dimensions as per table. The rates mentioned here under are for fittings, zinc coated externally with inside mortar lining (with finishing as per class 13/IS 9523/2000) ( ex-works) including Transportation complete as per ss and as direceted by the departmentaal officer incharge of work
Centrifugally cast (spun) above 500mm dia Ductile Iron Fittings conforming to IS:9523/2000 having dimensions as per table. The rates mentioned here under are for fittings, zinc coated externally with inside mortar lining (with finishing as per class 13/IS 9523/2000) ( ex-works) including complete as per ss and as direceted by the departmentaal officer incharge of work
Supply and delivery of 500mm dia PN 1.6"Resilient Seated Soft Sealing" Gate Valves (Sluice Valves) with Body and Bonnet of Ductile Iron GGG-40/SG-400/15 or GGG-50/SG-500/7 or Equivalent as per IS1865, IS:3896-2 and Wedge fully Rubber Lined with food grade quality grade W270 grade EPDM, Replaceable Spindle Nut without gland packing with 3-O ring protection system on the Shaft and Seals of NBR. The Valves should be Vacuum tight and 100% leak proof with face to face dimensions as BS:5163 Type A/IS:14846. All the valves should be with fusion bonded Electrostatic Powder coating both inside and outside (Min 250 Microns)- RAL 5005 with Pocket Less Straight through body Passage conforming to Design standards of DIN-3202F4/BS:5163 Type A Flange drilling as per IS - 1538 including all taxes, duties and transportation. PN1.6 Mpa - 300 mm Scoure complete as per ss and as direceted by the departmentaal officer incharge of work
Labour charges for lowering and keeping in position of 300mm diaDI Sluice valves(with cap/with hand wheel), reflux valves and scour valves. complete as per ss and as direceted by the departmentaal officer incharge of work
Lowering the C.I. Pipes, D.I. Pipes of all classes and fittings with flanged ends carefully into the trenches and laying them true to alignment and gradient including all sundries, but excluding conveyance from source of supply as per BIS No.3114/94.PHE-LCIF-2 as follows
inlet 500 mm DIDF pipes 4.00 m long
inlet 500 mm DIDF pipes 1.00 m long
out let 600 mm dia DIDF pipes 4.00m
out let 600 mm dia DIDF pipes 1.00m
scour 300 mm dia DIDF pipes 4.00 m long
scour 300 mm dia DIDF pipes 1.00 m long
over floe pipes 400 mm dia DIDF 4.00m long
over floe pipes 400 mm dia DIDF 1.00m long
Centrifugally cast (spun) Ductile Iron Fittings conforming to IS:9523/2000 having dimensions as per table. The rates mentioned here under are for fittings, zinc coated externally with inside mortar lining (with finishing as per class 13/IS 9523/2000) ( ex-works) including Transportation as follows
inlet 500 mm deck foot bends
out let 600 mm deck foot bends
over flow 400 mm deck foot bends
scour 300 mm deck foot bends
inlet 500 mm bends
out let 600 mm bends
over flow 400 mm bends
scour 300 mm bends
Jointing the C.I. Pipes, fittings and valves with flanged ends including cost of jointing materials such as bolts, nuts, rubber insertion, white lead and including filling with water with a water lead upto 500 m and testing to required pressure etc., comp as per BIS No.3114/85 as follows
600 mm dia
500 mm dia
400 mm dia
300mm dia
Construction of R.C.C valve chambers as per Standard Drawings with RCC cover slab fixed with CI/DI manhole Frame & Cover with lock and Key arrangement. The Mix shall not be less than VRCC M 20 grade with 150mm thick side walls, 150mm thick top slab, 150mm thick base slab over base course of 100mm thick (1:4:8) prop.as per type design approved by the depaartment
Installation and commissioning of advanced lighting protection systems which includes 1. Laying of CC Bed 2. Installation of Lighting Rod 3. Laying of Down conductor 4. Installation of Counter 5. Installation of GI Mast with stay wire. 6. Installation of Earth Electrodes 7. Interconnection between the Electrodes 8. Termination of down conductor to earth bus etc complete.
Supply, Delivery, Installation and Commissioning of Water Level Indicator including all incidental, operational and labourcharges for finsihed item of work and as directed by the Engineer-in-Charge
Supply, Delivery and instalation of Stainless steel Railing all around the walk ways of bottom and Top slab including the cost of materials, all incidental, operational and labourcharges for finsihed item of work and as directed by the Engineer-in-Charge
Supplying & fixing of Door frame made of roll formed section of 1.25 mm thick CRCA section, size should be 50 x 60 mm with 32 mm rebate. The corner of the frame should be welded. The frame should be painted with one coat of primer and finished painted with pure polyester paint. The frame should be provided with approved quality butt hinges of 3 Nos. Complete for finished item of work.: Single shutter 3'- 0" x 7'-0" (914.4x2133.6mm) outer frame section size of 50 x 75 mm
Supply & Fixing SOLID STEEL DOOR door shutter made out of G I Precoated Sheet with an average wall thickness of 0.35 mm on both sides. MS Tube having dimensions of 19 x 19 mm is inserted along the hinge side of the door, core of the door shutter filled with High Density Polyurethane foam injected with the help of hydraulic injection method, four sides of the door covered with G I Precoated Sheet and the hardware locations reinforced with suitable wooden blocks as per drawing and stickers indicating location of the hardware pasted at appropriate places, etc complete
Supply, Delivery and instalation of Fly proof ventilators including the cost of materials, all incidental, operational and labourcharges for finsihed item of work and as directed by the Engineer-in-Charge
Manufacture as per BIS:12592 (Part 1&2) Supply & Delivery of manhole covers and frames with ISI marking anywhere in A.P., F.O.R. destination including, loading, un-loading & stacking at site complete as per ss and as direceted by the departmental offcier incharge of work
Laying of 600 dia.DI K7 combined Gravity main from proposed 500 KL OHBR at Bobbarlanka to junction at Vanapalli
Cutting of existing B.T.road surface (aswell as asphalt concrete up to 75mm thick) including water bound macadam including all labour charges for cutting, stacking of materials hiring of machinary, fuil charges, wages of driver etc.,complete as per the directions of departmental authorities. For pipe line trenches.
Cutting and open of C.C. Road surface including all labour charges for cutting, stacking of materials hiring of machinary, fuil charges, wages of driver etc.,complete as per the directions of departmental authorities. For pipe line trenches.
Cutting and open of Water bound macadam surface including all labour charges for cutting, stacking of materials hiring of machinary, fuil charges, wages of driver etc.,complete as per the directions of departmental authorities. For pipe line trenches.
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH as per the ditections of the departmental authorities as follows
Mechanical Means up to 3 metres depth in ordinary soils
Manual Means up to 3 metres depth in ordinary sils
Providing river sand filling brought from approved quarry including cost and conveyance of all material and all labour charges such as filling in layers watering ramming etc complete as per ss and as directed by the departemntal officer in charges of work.
Centrifugally cast 600 mm dia DIK7 (Spun) Ductile Iron pressure pipes for water, gas and sewage with Socket Spigot ends conforming to IS.: 8329/2000 in standard working lengths of 4, 5 5.5 & 6 meter for classification K9 & K7 suitable for push-on-joint (rubber gasket d jointing) with cement mortar lining inside the pipes with outside zinc coating. Rates are ex-factory, including transportation and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work.
Centrifugally cast (Spun) Ductile Iron pressure pies with flanged (welded) ends for water, gas, sewage conforming to IS: 8329/2000 in standard working lengths of 1,2,3, 4, 5 mts for classification K9 with cement mortar lining inside the pipes with outside zinc coating. Rates are ex-factory, including transportation and and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work. as follows
350mm dia. Scour lines on 600 mm line for scours 2.00m long DI DF pipes
for sluice valves,non return valves and flow meters 1.00m long DI DF pipes 600 mm 1.00m lond
MAnufacture, supply and delivery at work site 600mm dia internal dia M.S.Pipe fabricated with 10mm thick MS plates confirming to IS 2062-1992 of grade A manufactured as per IS 3589-2001 in suitable lengths painted with two coats of food grade epoxy paint inside and outside to suit the site conditions, in co-ordination with the concerned authorities as per approved drawings and directed by the Engineer-in –charge including Cost of Laying, Jointing, Hydrostatic Filed Test Pressure, Including Cost of Site Welding, Jointing Materials And Cost of Transportation of Water Including Emptying Pipe Line After Completion Of Field Testing 600mm Dia canal crossing including transportation and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work.
Lowering of 600mm dia DI K9 D.I. socket and spigot Pipes and fittings carefully in to the trench and laying them true to alignment and gradient including all labour charges, sundries as per BIS No. 3114/85 etc., complete as per S.S and as directed by the departmental authorities.
Jointing of 600mm dia DI K9 D.I. Pipes & fittings with Rubber Gasket including all sundries filling with water with a water lead up to 500m and testing to required pressure etc., complete as per BISNo.3114/85 and as directed by the departmental authorities.
Supply, Delivery of 600 mm Dia D.I double flanged Sluice Valves conforming to IS- 14846 (with up to date amendments, if any) including gear arrangements for the following dia. as per test pressure having Body, Bonnet, Dome, Stool cover, Wedge, Stuffing box, Gland, Thrust plate, Cap/Hand wheel with D.I; Stem, Body seat ring, Wedge facing ring, Bushes, Bolts, Nuts, Pinion and Pinion shaft with Stainless steel (IS 6603) ; Wedge nut, Shoe, Channel with Leaded Tin Bronze ( IS 318 ); Gasket with Neoprene Rubber; Gland packing with Rubber; Gear, Gear housing with Cast Steel and including transportation, etc. complete ISI marked.PN 1.6 (MPa) including transportation and and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work.
Supply and delivery 350mm DiaPN 16 Sluice Valve of "Resilient Seated Soft Sealing" Gate Valves (Sluice Valves) with Body and Bonnet of Ductile Iron GGG-40/SG-400/15 or GGG-50/SG-500/7 or Equivalent as per IS1865, IS:3896-2 and Wedge fully Rubber Lined with food grade quality grade W270 grade EPDM, Replaceable Spindle Nut without gland packing with 3-O ring protection system on the Shaft and Seals of NBR. The Valves should be Vacuum tight and 100% leak proof with face to face dimensions as BS:5163 Type A/IS:14846. All the valves should be with fusion bonded Electrostatic Powder coating both inside and outside (Min 250 Microns)- RAL 5005 with Pocket Less Straight through body Passage conforming to Design standards of DIN-3202F4/BS:5163 Type A Flange drilling as per IS - 1538 duties and transportation.- PN 1.6 MPa including transportation and and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work.
Supply & Delivery of Tamper Proof 150mm dia PN 16 DI Flanged Single Chamber Air Release Valves with body & cover made of Ductile Iron Grade GGG-40/SG-400/15 or GGG-50/SG-500/7 or Equivalent as per IS1865, IS:3896-2 with Food Grade Epoxy Powder Coating(EP-P) (Min:250 Micron) inside and Outside of Color Blue RAL 5005. All internal parts such as Float, shell, Cove Bolts etc. made of Austenitic alloy steel of SS AISI 304/316 and DN 50 float of and other components with ABS/PTFE/EPDM/NBR and generally conforming to DIN/BIS/AWWA standards (or) combination Flange drilling as per IS - 1538 and and including transportation. PN 1.6 MPa including transportation and and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work.
Supply, Delivery of 600mm dia D.I Double Flanged Swing Check type Reflux valves (Non Return Valves) of following dia. conforming to IS- 5312 (Pts-1&2) (with amendments up to date, if any) having Body, Cover, Door, Bearing holder with D.I; Hinge pin, Door pin, Door suspension pin with Stainless Steel (IS 6603); Body seat ring , Door face ring, Bearing bushes, Plugs for hinge pin with Leaded Tin Bronze ( IS 318 ); Bolts, Nuts with Carbon steel; Gaskets with Rubber; Hinges with Cast steel; including transportation and complete. PN 1.6 MPa including transportation and and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work.
Labour charges for lowering and keeping in position of C.I./DI Sluice valves(with cap/with hand wheel), reflux valves and scour valves.incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work. As follows.
600mm dia PN 16 Sluice Valve
Sluice valve of 350mm dia - PN16 on 600 mm dia main
Labour charges for 150mmdia -PN16 fixing Kinetic Air Valves with isolating Sluice valves, Double Air valves/ Air Cushion valve excluding cost of jointing materials such as bolts, nuts and rubber insertions etc.incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work.
Centrifugally cast (spun) Ductile Iron Fittings conforming to IS:9523/2000 having dimensions as per table. The rates mentioned here under are for fittings, zinc coated externally with inside mortar lining (with finishing as per class 13/IS 9523/2000) ( ex-works) including Transportation and .including and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work. as follows.
600 mm dia
350 mm dia
Lowering the C.I. Pipes, D.I. Pipes of all classes and fittings with flanged ends carefully into the trenches and laying them true to alignment and gradient including all sundries, but excluding conveyance from source of supply as per BIS No.3114/94.including and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work. as follows.
600 mm dia
350 mm dia
Jointing the D.I. Pipes, fittings and valves with flanged ends including cost of jointing materials such as bolts, nuts, rubber insertion, white lead and including filling with water with a water lead upto 500 m and testing to required pressure etc., comp as per BIS No.3114/85 including and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work. as follows.
600 mm dia
450 mm dia
400 mm dia
350 mm dia
150 mm dia
Construction of R.C.C. thrust blocks using RCC M- 20 Nominal mix (Cement:fine aggregate: coarse aggregate) corresponding to Table 9 of IS 456 using 20mm size graded machine crushed hard granite metal (coarse aggregate) from approved quarry including cost and conveyance of all materials like cement, fine aggregate (sand) coarse aggregate, water etc., to site and including all operational, incidental and labour charges such as machine mixing, laying concrete, curing etc.,complete but excluding cost of steel and its fabrication charges for finished item of work, as per ss and as directed by the departemntal officer in charges of work.
Construction of Anchor blocks VCC M- 20 Nominal mix (Cement:fine aggregate: coarse aggregate) corresponding to Table 9 of IS 456 using 20mm size graded machine crushed hard granite metal (coarse aggregate) from approved quarry including cost and conveyance of all materials like cement, fine aggregate (sand) coarse aggregate, water etc., to site and including all operational, incidental and labour charges such as machine mixing, laying concrete, curing etc.,complete but excluding cost of steel and its fabrication charges for finished item of work,as per ss and as directed by the departemntal officer in charges of work.
Collection, Supply and filling of Stone dust / Quarry spall from approved quarry to work site and stacking at work site including cost and convenyance of all material and all labour charges etc. complete using crusher stone dust as per ss and as directed by the departemntal officer in charges of work.
Construction of Sluice Valvechambers with VRCC M20 Concrete suitable to the sluice valves with VRCC Cover Slab including cost and conveyance of all materials and all labour charges etc.complete as per S.S for finished item of work
Construction of 600mm dia Scour Valvechambers with VRCC M20 Concrete suitable to the Scour valves with VRCC Cover Slab including cost and conveyance of all materials and all labour charges etc.complete as per S.S for finished item of work as per ss and as directed by the departemntal officer in charges of work.
Construction of 150mm dia PN-16 Air Valvechambers with VRCC M20 Concrete suitable to the Air valves with VRCC Cover Slab including cost and conveyance of all materials and all labour charges etc.complete as per S.S for finished item of work
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying including sales and other taxes on all materials etc., complete for finished item of work in all floors.( APSS No.126) For Thrusy Blocks.
Using Concrete mixture up to Plinth Level : Plain Cement concrete nominal mix M-30 (Cement : fine aggregate: coarse aggregate ) using 20mm size Hard Granite Machine Crushed Graded Metal including cost and conveyance of all materials like cement, sand, coarse aggregate water etc., to site , seigniorage charges on all materials, labour charges , for mixing , laying, concrete , ramming in 15 cm layers, finishing top surface to the required level curing etc., complete for finished item of work with nomonal reinforcement for Road restoration BT Road etc complete as per ss and as directed by the departemntal officer in charges of work.
Providing concrete for plain/reinforced concrete in open foundations using 20 mm nominal size Graded hard stone aggregate, mechanically mixed, placed in foundation and compacted by vibration including curing for 14 days complete as per drawings and technical specifications Clause 802, 803, 1202 & 1203 MORD and 1500, 1700 & 2100 MORTH Nominal mix M20 etc complete as per ss and as directed by the departemntal officer in charges of work. For encasing MS pipes for canal crossing.
Shifting of existing Electrical Pole and transformers for lying on the Pipe line alignment including shifting charges payble to AP Transco and other incidental charges etc.,complete as per direction of the departmental authorities as per ss and as directed by the departemntal officer in charges of work.
Manufacture, Supply and Delivery of 600mm dia M.S. Dismantling Joints with both side flange end suitable for installation in between flange end pipes. Thickness as per IS: 7322. including transportation and and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work.
Providing 450 dia.DI K7 Gravity main from junction at Vanapalli to sump at pallamkurru canal
Cutting of existing B.T.road surface (aswell as asphalt concrete up to 75mm thick) including all labour charges for cutting, stacking of materials hiring of machinary, fuil charges, wages of driver etc.,complete as per the directions of departmental authorities. For pipe line trenches.
Cutting and open of C.C. Road surface including all labour charges for cutting, stacking of materials hiring of machinary, fuil charges, wages of driver etc.,complete as per the directions of departmental authorities. For pipe line trenches..
Cutting and open of Water bound macadam surface including all labour charges for cutting, stacking of materials hiring of machinary, fuil charges, wages of driver etc.,complete as per the directions of departmental authorities. For pipe line trenches.
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH etc complete as per ss and as directed by the departemntal officer in charges of work.
450 mm dia. DI K7-from junction at Vanapalli to clear water sump at WTP Mummidivaram
For 250mm dia. Scour lines
Providing river sand filling brought from approved quarry including cost and conveyance of all material and all labour charges such as filling in layers watering ramming etc complete as per ss
Centrifugally castof 450mm dia DI K7 (Spun) Ductile Iron pressure pipes for water, gas and sewage with Socket Spigot ends conforming to IS.: 8329/2000 in standard working lengths of 4, 5 5.5 & 6 meter for classification K9 & K7 suitable for push-on-joint (rubber gasket d jointing) with cement mortar lining inside the pipes with outside zinc coating. Rates are ex-factory, including transportation and and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work.
Centrifugally cast (Spun) Ductile Iron pressure pies with flanged (welded) ends for water, gas, sewage conforming to IS: 8329/2000 in standard working lengths of 1,2,3, 4, 5 mts for classification K9 with cement mortar lining inside the pipes with outside zinc coating. Rates are ex-factory, including transportation and including transportation and and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work as follows
250mm dia. Scour lines on 400 mm line 2.00m long
for sluice valves,non return valves and flow meters 1.00m long DI DF pipes 400 mm dia
Lowering of 450mm dia D.I. socket and spigot Pipes and fittings carefully in to the trench and laying them true to alignment and gradient including all labour charges, sundries as per BIS No. 3114/85 etc., complete as per S.S and as directed by the departmental authorities.
Jointing of 450mm dia D.I. Pipes & fittings with Rubber Gasket including all sundries filling with water with a water lead up to 500m and testing to required pressure etc., complete as per BISNo.3114/85 and as directed by the departmental authorities.etc., complete as per S.S and as directed by the departmental authorities.
Supply and delivery of "Resilient Seated Soft Sealing" Gate Valves (Sluice Valves) with Body and Bonnet of Ductile Iron GGG-40/SG-400/15 or GGG-50/SG-500/7 or Equivalent as per IS1865, IS:3896-2 and Wedge fully Rubber Lined with food grade quality grade W270 grade EPDM, Replaceable Spindle Nut without gland packing with 3-O ring protection system on the Shaft and Seals of NBR. The Valves should be Vacuum tight and 100% leak proof with face to face dimensions as BS:5163 Type A/IS:14846. All the valves should be with fusion bonded Electrostatic Powder coating both inside and outside (Min 250 Microns)- RAL 5005 with Pocket Less Straight through body Passage conforming to Design standards of DIN-3202F4/BS:5163 Type A Flange drilling as per IS - 1538 and transportation.- PN 1.6 MPa including transportation and and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work. as follows
Sluice valve of 450mm dia - PN16
Sluice valve of 250mm dia - PN16
100 mm dia
Supply & Delivery of 100mm dia Tamper Proof DI Flanged Single Chamber Air Release Valves with body & cover made of Ductile Iron Grade GGG-40/SG-400/15 or GGG-50/SG-500/7 or Equivalent as per IS1865, IS:3896-2 with Food Grade Epoxy Powder Coating(EP-P) (Min:250 Micron) inside and Outside of Color Blue RAL 5005. All internal parts such as Float, shell, Cove Bolts etc. made of Austenitic alloy steel of SS AISI 304/316 and DN 50 float of and other components with ABS/PTFE/EPDM/NBR and generally conforming to DIN/BIS/AWWA standards (or) combination Flange drilling as per IS - 1538 and and including transportation. PN 1.6 MPa including transportation and and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work.
Supply, Delivery of 450mm dia D.I Double Flanged Swing Check type Reflux valves (Non Return Valves) of following dia. conforming to IS- 5312 (Pts-1&2) (with amendments up to date, if any) having Body, Cover, Door, Bearing holder with D.I; Hinge pin, Door pin, Door suspension pin with Stainless Steel (IS 6603); Body seat ring , Door face ring, Bearing bushes, Plugs for hinge pin with Leaded Tin Bronze ( IS 318 ); Bolts, Nuts with Carbon steel; Gaskets with Rubber; Hinges with Cast steel; including transportation and complete. PN 1.6 MPa including transportation and and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work.
Labour charges for lowering and keeping in position of C.I./DI Sluice valves(with cap/with hand wheel), reflux valves and scour valves.etc complete as per ss and as directed by the departemntal officer in charges of work. As follows
450 mm dia
Sluice valve of 250mm dia - PN16
Labour charges for 10mm dia fixing Kinetic Air Valves with isolating Sluice valves, Double Air valves/ Air Cushion valve excluding cost of jointing materials such as bolts, nuts and rubber insertions etc complete as per ss and as directed by the departemntal officer in charges of work.
Centrifugally cast (spun) Ductile Iron Fittings conforming to IS:9523/2000 having dimensions as per table. The rates mentioned here under are for fittings, zinc coated externally with inside mortar lining (with finishing as per class 13/IS 9523/2000) ( ex-works) including transportation and and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work. as follows
450 mm dia
250 mm dia
Lowering the C.I. Pipes, D.I. Pipes of all classes and fittings with flanged ends carefully into the trenches and laying them true to alignment and gradient including all sundries, conveyance from source of supply as per BIS No.3114/94.including all abour charges and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work. as follows
450 mm dia
250 mm dia
Jointing the D.I. Pipes, fittings and valves with flanged ends including cost of jointing materials such as bolts, nuts, rubber insertion, white lead and including filling with water with a water lead upto 500 m and testing to required pressure etc., comp as per BIS No.3114/85 including all abour charges and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work. as follows
450 mm dia
250 mm dia
100 mm dia
Construction of R.C.C. thrust blocks using RCC M- 20 Nominal mix (Cement:fine aggregate: coarse aggregate) corresponding to Table 9 of IS 456 using 20mm size graded machine crushed hard granite metal (coarse aggregate) from approved quarry including cost and conveyance of all materials like cement, fine aggregate (sand) coarse aggregate, water etc., to site and including all operational, incidental and labour charges such as machine mixing, laying concrete, curing etc.,complete but excluding cost of steel and its fabrication charges for finished item of work, and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work. For Thrust Blocks
Construction of Anchor blocks VCC M- 20 Nominal mix (Cement:fine aggregate: coarse aggregate) corresponding to Table 9 of IS 456 using 20mm size graded machine crushed hard granite metal (coarse aggregate) from approved quarry including cost and conveyance of all materials like cement, fine aggregate (sand) coarse aggregate, water etc., to site and including all operational, incidental and labour charges such as machine mixing, laying concrete, curing etc.,complete but excluding cost of steel and its fabrication charges for finished item of work, and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work. For Anchor Blocks
Collection, Supply and filling of Stone dust / Quarry spall from approved quarry to work site and stacking at work site including cost and convenyance of all material and all labour charges etc. complete using crusher stone dust as per ss and as directed by the departemntal officer in charges of work.
Construction of 450mm dia Sluice Valvechambers with VRCC M20 Concrete suitable to the sluice valves with VRCC Cover Slab including cost and conveyance of all materials and all labour charges etc.complete as per S.S for finished item of work as per type design approved by the department authorities
Construction of 100mm dia PN -16 Scour Valvechambers with VRCC M20 Concrete suitable to the Scour valves with VRCC Cover Slab including cost and conveyance of all materials and all labour charges etc.complete as per S.S for finished item of work as per type design approved by the department authorities
Construction of Air Valvechambers with VRCC M20 Concrete suitable to the Air valves with VRCC Cover Slab including cost and conveyance of all materials and all labour charges etc.complete as per S.S for finished item of work as per type design approved by the department authorities for thrust blocks
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying including sales and other taxes on all materials etc., complete for finished item of work in all floors.( APSS No.126) as per ss and as directed by the departemntal officer in charges of work. For Thrust Blocks
Using Concrete mixture up to Plinth Level : Plain Cement concrete nominal mix M-30 (Cement : fine aggregate: coarse aggregate ) using 20mm size Hard Granite Machine Crushed Graded Metal including cost and conveyance of all materials like cement, sand, coarse aggregate water etc., to site , seigniorage charges on all materials, labour charges , for mixing , laying, concrete , ramming in 15 cm layers, finishing top surface to the required level curing etc., complete for finished item of work with nomonal reinforcement for Road restoration.including and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work.
Shifting of existing Electrical Pole and transformers for lying on the Pipe line alignment including shifting charges payble to AP Transco and other incidental charges etc.,complete as per IE rules and as directed by the departemntal officer in charges of work.
Manufacture, Supply and Delivery of 450mm dia M.S. Dismantling Joints with both side flange end suitable for installation in between flange end pipes. Thickness as per IS: 7322. These rates etc complete as per ss and as directed by the departemntal officer in charges of work. This rate including cost of all labour charges etc complete as per ss and as directed by the departemntal officer in charges of work.
Construction of Compound wall at OHBR Bobbralanka
Constuction of compound wall with the following specifications 1. Earth work excavation for column footings ,providing sand bed in foundations,providing CC 1:4:8 for foundations,VRCC M 20 for column footings,plinth beams,columns,Brick work in CM 1:6 , Plastering CM 1:5, Snowcem painting, etc complete and other incidental charges as per ss and as directed by the departemntal officer in charges of work.
Manufacture,supply,delivery of 4.50m Gate MS grill gates,window ornamental safety grill ,made with MS flats,MS angles,MS squares etc including welding,finishing, etc complete
Painting two coats with synthetic enamel paint on new iron work over a base coat of red-oxide making 3 coats in total including cost of all materials, conveyance charges of materials and including all operational, incidental and labour charges etc,, complete for finished item of work as directed by the departmental authorities.(APDSS No:1201)
Providing dedicated HT electrical power line to proposed intakewell from nearest substation
Cost data per KM of 11 KV HT line with 55 sqmm AAA conductor over 9.10m PSCC poles at 60m span,75 kg/sqm wind pressure working load 140 kgs excluding over heads,other charges,taxes etc complete as per IE rules and as directed by the departemntal officer in charges of work.
Construction of New Off take Chamber at Pallamkur canal near Vivekanda varadhi
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work.
Mechanical Means up to 3 metres depth in ordinary soils
Mechancial Means 3 to 6 metres depth in ordinary soils
Manual Means 3 to 6 metres depth in ordinary soils
Providing river sand filling brought from approved quarry including cost and conveyance of all material and all labour charges such as filling in layers watering ramming etc complete as per ss for wing walls & return
Providing PCC 1:4:8 using 40 mm graded SS 5 HBG m/c metal and OPC coarse and fine aggregate confirming to IS 383 including cost and conveyance of all materials and labour charges, machine mixing , vibration,laying in position, curing etc., complete as per ss and as directed by the departemntal officer in charges of work.
Supply and placing of the design mix concrete corresponding to IS -456 using WEIGH BATCHER/MIXER using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including all operational ,incidental and labour charges such as weigh batching ,machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work (APSS NO 402) with minimum cement content as per IS Code from standard suppliers approved by the deparment including pumping , centering,shuttering,laying concrete ,vibrating,curing etc M30 design mix concrete etc complete as per ss and as directed by the departemntal officer in charges of work. For 150mm thick slab
Supply and placing of the design mix concrete corresponding to IS -456 using WEIGH BATCHER/MIXER using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including all operational ,incidental and labour charges such as weigh batching ,machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work (APSS NO 402) with minimum cement content as per IS Code from standard suppliers approved by the deparment including pumping , centering,shuttering,laying concrete ,vibrating,curing etc M30 design mix concrete etc complete as per ss and as directed by the departemntal officer in charges of work.
Cement plastering using opc in cm(1:3) prop 12 mm thick including cost of all materials, conveyance charges of materials and all operational, incidental and labour charges etc., complete for finished item of work as per S.S out side & inside and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work.
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying including sales and other taxes on all materials etc., complete for finished item of work in all floors.( APSS No.126) and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work. for slab , body walls
Supply and placing of the M20 Nominal mix concrete corresponding to IS -456 using WEIGH BATCHER/MIXER using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including all operational ,incidental and labour charges such as weigh batching ,machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work (APSS NO 402) with minimum cement content as per IS Code from standard suppliers approved by the deparment including pumping , centering,shuttering,laying concrete ,vibrating,curing and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work. Flooring in side chamber
Supply and delivary and fixing of MS Grills of any design including cost and conveyance of all material and all labour charges such as cutting welding ,gringing and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work. for grating, ladder.
Bailing out water from the pipe line trenches with oil engine driven pump sets, including hire charges, fuel charges and wages for Driver and Helper and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work.
Providing Shutter gate and locking , Screen arrangement as per drawings and rate as per quatations as per ss and as directed by the departemntal officer in charges of work.
Laying of 400 mm dia DI K7 Raw water gravity main from proposed off take chamber to raw water sump cum pump house at Pallamkur canal near Vivekanda varadhi
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work.
Mechanical means up to 3 metres depth in ordinary soil
Manual means up to 3 metres depth in ordinary soil
Centrifugally cast 400 mm dia DI K7 (Spun) Ductile Iron pressure pipes for water, gas and sewage with Socket Spigot ends conforming to IS.: 8329/2000 in standard working lengths of 4, 5 5.5 & 6 meter for classification K9 & K7 suitable for push-on-joint (rubber gasket d jointing) with cement mortar lining inside the pipes with outside zinc coating. Rates are ex-factory, including transportation and and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work.
Lowering the 400 mm dia DI K7 C.I. Pipes, D.I. Pipes and fittings with S/S (Plain)ends carefully into the trenches and laying them true to alignment and gradient including all sundries, including conveyance from source of supply as per BIS No.3114/94.and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work.
Jointing the 400 mm dia DI K7 C.I,D.I. Pipes, fittings and valves with rubber gasket(push-on-joint) including the cost of the gasket but including all sundries, filling with water with a water lead upto 500 m and testing to required pressure etc., comp as per BIS No.3114/1994/12888/1987 and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work.
Supply and delivery of "Resilient Seated Soft Sealing" Gate Valves (Sluice Valves) with Body and Bonnet of Ductile Iron GGG-40/SG-400/15 or GGG-50/SG-500/7 or Equivalent as per IS1865, IS:3896-2 and Wedge fully Rubber Lined with food grade quality grade W270 grade EPDM, Replaceable Spindle Nut without gland packing with 3-O ring protection system on the Shaft and Seals of NBR. The Valves should be Vacuum tight and 100% leak proof with face to face dimensions as BS:5163 Type A/IS:14846. All the valves should be with fusion bonded Electrostatic Powder coating both inside and outside (Min 250 Microns)- RAL 5005 with Pocket Less Straight through body Passage conforming to Design standards of DIN-3202F4/BS:5163 Type A Flange drilling as per IS - 1538 , including transportation and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work.
Labour charges for 400 mm dia lowering and keeping in position of D.I. Sluice valves(with cap/with hand wheel), reflux valves and scour valves.and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work.
Centrifugally cast 400 mm dia 1.00m long DIDF pipes for sluice valves (Spun) Ductile Iron pressure pies with flanged (welded) ends for water, gas, sewage conforming to IS: 8329/2000 in standard working lengths of 1,2,3, 4, 5 mts for classification K9 with cement mortar lining inside the pipes with outside zinc coating. Rates are ex-factory, including transportation and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work.
Centrifugally cast 400 mm DI Special (spun) Ductile Iron Fittings conforming to IS:9523/2000 having dimensions as per table. The rates mentioned here under are for fittings, zinc coated externally with inside mortar lining (with finishing as per class 13/IS 9523/2000) ( ex-works) including Transportation and including transportation and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work. including transportation and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work.
Lowering the C.I. Pipes, D.I. Pipes of all classes and fittings with flanged ends carefully into the trenches and laying them true to alignment and gradient including all sundries, including conveyance from source of supply as per BIS No.3114/94.including all labour charges and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work.
Jointing the 400 mm dia C.I. Pipes, fittings and valves with flanged ends including cost of jointing materials such as bolts, nuts, rubber insertion, white lead and including filling with water with a water lead upto 500 m and testing to required pressure etc., comp as per BIS No.3114/85.including all labour charges and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work.
Bailing out water from the pipe line trenches with oil engine driven pump sets, including hire charges, fuel charges and wages for Driver and Helper and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work.
Construction of 400 mm dia Sluice Valvechambers with VRCC M20 Concrete suitable to the sluice valves with VRCC Cover Slab including cost and conveyance of all materials and all labour charges etc.complete as per S.S for finished item of work and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work.
Construction of 5.00 m dia.(58.82 KL) Raw Water sump cum pump house at proposed Off take Chamber at Pallamkur canal near Vivekanda varadhi
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH for foundations upto 3.00m depth and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work. as follows
Mechanical Means up to 3 metres depth in ordinary soil
Mechanical means 3 to 6 metres depth in ordinary soils
Manual Means 3 to 6 metres depth in ordinary soil
Providing river sand filling brought from approved quarry including cost and conveyance of all material and all labour charges such as filling in layers watering ramming etc complete as per ss and as directed by the departmental officer in chrges of work Raw water sump cum pump house.
Providing PCC 1:4:8 using 40 mm graded SS 5 HBG m/c metal and OPC coarse and fine aggregate confirming to IS 383 including cost and conveyance of all materials and labour charges, machine mixing , vibration,laying in position, curing etc complete as per ss and as directed by the departmental officer in chrges of work Raw water sump cum pump house.
Providing VRCC M30 Grade Design Concrete Mix corresponding to IS 456 using WEIGH BATCHER / MIXER with 20mm size graded machine crushed hard granite metal (coarse aggregate) from approved quarry including cost and conveyance of all materials like cement, fine aggregate (sand) coarse aggregate, water etc., to site and including all operational, incidental and labour charges such as weigh batching, machine mixing, laying concrete, curing with cement content 400Kgs/Cum as per I.S code from standard suppliers approved by the department including centering, shuttering, laying concrete, vibrating, curing etc. complete with all de-lift charges but excluding cost of steel and its fabrication charges for finished item of work (APSS No. 402)including all labour charges and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work. as follows
Raft slab
vertical wall 3.00m intial height below GL
vertical wall 1.00m height over intial height
vertical wall 3.00m intial height Above GL
floor slab 0.25 m thick
beams for placing motors
Providing VRCC M30 Grade Design Concrete Mix corresponding to IS 456 using WEIGH BATCHER / MIXER with 20mm size graded machine crushed hard granite metal (coarse aggregate) from approved quarry including cost and conveyance of all materials like cement, fine aggregate (sand) coarse aggregate, water etc., to site and including all operational, incidental and labour charges such as weigh batching, machine mixing, laying concrete, curing with cement content 400Kgs/Cum as per I.S code from standard suppliers approved by the department including centering, shuttering, laying concrete, vibrating, curing etc. complete but excluding cost of steel and its fabrication charges for finished item of work (APSS No. 402) including all labour charges other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work.
a) for Pump house Columns
b) for roof beams -
c) for roof slab 0.15 m thick with 0.30 m extension
d) for Lintel Beams alround
g) for Sunshade of 0.60m wide and thickness of .075m at fixed end and 0.05mts.at free end
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying including sales and other taxes on all materials etc., complete for finished item of work in all floors.( APSS No.126) etc complete as per ss and as directed by the departemntal officer in charges of work.
Brick masonary in CM (1:5) using 2nd class bricks of size 23 x 11 x 7cms. Cost including cost of all materials, conveyance charges of materials and all operational, incidental and labour charges for mixing mortar, laying, rendering smooth , curing,etc,, complete for finished item of work and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work. as follows
for Super structure of Pump house
for Pump house Parapet wall
Supply and fixing of 50mm thick pre-cast Cement Jollys of approved design including cost and conveyance to work spot and all labour charges for fixing in position and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work. for pump house
Plastering with CM (1:3) 12mm thick including cost of all materials, conveyance charges of materials and all operational, incidental and labour charges for mixing mortar, laying, rendering smooth , curing,etc,, complete for finished item of work for ceiling as per ss and as directed by the departemntal officer in charges of work
Plastering with CM (1:4) 12mm thick including cost of all materials, conveyance charges of materials and all operational, incidental and labour charges for mixing mortar, laying, rendering smooth , curing,etc,, complete for finished item of work for the Pump house as per ss and as directed by the departemntal officer in charges of work as per follows
Ground floor
First floor
Plastering with CM (1:3) 20mm thick including cost of all materials, conveyance charges of materials and all operational, incidental and labour charges for mixing mortar, laying, rendering smooth , curing,etc,, complete for finished item of work over floor slab for fixing pumps and motors for Slab as per ss and as directed by the departemntal officer in charges of work for floor slab
Painting Walls with Snowcem or other equal and approved Water Proof Cement Paint 2 Coats (All Colours) over a base coat of aproved cement primer making 3 coats in total including cost of all materials, conveyance charges of materials and including all operational, incidental and labour charges etc,, complete for finished item of work as directed by the departmental authorities.
Painting two coats with synthetic enamel paint on new iron work over a base coat of red-oxide making 3 coats in total including cost of all materials, conveyance charges of materials and including all operational, incidental and labour charges etc,, complete for finished item of work as directed by the departmental authorities.(APDSS No:1201) as per ss and as directed by the departemntal officer in charges of work
Supply & fixing of Rolling shutter made of 80 x 1.25 mm machine rolled CRCA laths, interlocked together through their entire length and jointed together at the ends by end-locks, mounted on specially designed pipe shaft of 50mm dia nominal bore MS B class pipe with brackets, plates, guide channels, stoppers, bottom locking plates and arrangements for inside & outside locking with push-pull operations including cost of hood cover and springs complete, painted with one coat of approved steel primer, locks, ball bearings, all accessories etc complete for finished item of work as per special spn: 1108 as per ss and as directed by the departemntal officer in charges of work
Supply and fixing Aluminium Anodized Two/ Three Track Sliding Windows as per approved drawing with aluminium anodized sections of Series C Jindal or approved equivalent make sections and outer frame top horizontals & both verticals of 8774 of size 62 x 29.5 mm and bottom horizontal - two track frame of 8773 of size 62 x 29.5 mm, Shutter frame top, bottom and verticals of 8304 of size 50 mm x 20 mm and Weather interlocking frame of 8306 of size 50 x 20 with plain clear float glass 5 mm thick fixed including supply and fixing aluminium handles of 100 mm for each shutter, nylon rollers assembly and all labour charges for fixing the fixtures with required no. of screws, bolts and nuts and including labour charges for fixing the frame in position, fixing shutter to frame etc. completed for finished item of work as per ss and as directed by the departemntal officer in charges of work
Bailing out of water with oil engine, driven pumpset including hire charges, fuel charges and wages of driver and helper etc., complete as per the directions of departmental authorities and other incidental charges as per ss and as directed by the departemntal officer in charges of work
Supply and erection of MS Gantry girder as per the approved designs and drawings 3 T capacity etc., complete as per the directions of departmental authorities and other incidental charges as per ss and as directed by the departemntal officer in charges of work
Supply and fixing of Stainless steel ladder made out of suitable sections for access from floor slab to Base slab etc., complete as per the directions of departmental authorities and other incidental charges as per ss and as directed by the departemntal officer in charges of work
Supply and fixing of 25 mm dia 2.20 mm thick PVC pipe concealed in roof slab with all required accessories including masonary work all labour chages etc complete as per IE rules and as directed by the departemntal officer in charges of work.
Supply and fixing of 20 mm dia 2.10 mm thick PVC pipe concealed in walls with all required accessories including masonary work for light , fan and plug point with metal deep box including all labour chages etc complete as per IE rules and as directed by the departemntal officer in charges of work.
Wiring with 2 runs 14/0.3 mm. (1.0. sq.mm) Fire retardant PVC insulated Flexible copper cable in existing pipe with 6A siwtch, ceiling rose and 3 mm thick hyla sheet covering to switch control box including all labour charges etc,., complet for light, bell , fan and exhaust fan points in non - residential building including all labour chages etc complete as per IE rules and as directed by the departemntal officer in charges of work.
Wiring with 2 runs 14/0.3 mm. (1.0. sq.mm) Fire retardant PVC insulated Flexible copper cable in existing pipe with 6A modular siwtch control and 3/2 pin sockets fixing on board including, material and all labour charges including all labour chages etc complete as per IE rules and as directed by the departemntal officer in charges of work.
supply and run of 2 of 36/0.3 mm. (1.5. sq.mm) Fire retardant PVC insulated Flexible copper cable in existing pipe for mains including all labour charges including all labour charges including, all material and all labour charges other incidental chages etc complete as per IE rules and as directed by the departemntal officer in charges of work.
supply and run of 1 of 14/0.3 mm. (1.0. sq.mm) Fire retardant PVC insulated Flexible copper cable in existing pipe for earth continuity including all labour charges etc. including, all material and all labour charges other incidental chages etc complete as per IE rules and as directed by the departemntal officer in charges of work.
supply and run of 2 of 6 sq.mm (7/18) WPSC alluminium cable along with No.10 SWG G.I barer wire through PVC cleats with all accessories including, all material and all labour charges other incidental chages etc complete as per IE rules and as directed by the departemntal officer in charges of work.
Providing independent earthing by excavating a trench to a depth of 2.10m in all soils, as per size specied in data ,using 40 mm dia B class GI pipe 2.50m long with necessary accessories with hume pipe ring duly providing staggered holes including filling with equal proportion of salt and charcoal in layers and all labour charges etc complete including, material and all labour charges other incidental chages etc complete as per IE rules and as directed by the departemntal officer in charges of work.
Supply and fixing SPN Distribution board with IP-20 protection suitable for single phase Earth Leakage Circute Braker (ELCB) / Residual Current Circute Braker (RCCB) / Double Pole (DP) Isolator as incomer and 10kA SP MCBs as out going including internal connections and labour charges for surface / flush mounting etc., complete.including, material and all labour charges other incidental chages etc complete as per IE rules and as directed by the departemntal officer in charges of work.
Supply of 48" (1200mm) Sweep 5 star rated Ceiling Fan , with double ball bearings, air delivery more than 200 cubic meter/min but without Regulator.Makes : Crompton HS Plus / Havells ES Neo/Orient Energy Star/ Halonix(Zephyr)/Polycab(Synergy Star) including, material and all labour charges other incidental chages etc complete as per IE rules and as directed by the departemntal officer in charges of work.
Supply of stepped type Electronic Regulator of including, material and all labour charges other incidental chages etc complete as per IE rules and as directed by the departemntal officer in charges of work. Makes: GM G Home / Gold Medal Olive / Million Zoom / Great white Omega/Koncept/Vimal opel/ Anchor/Vihan/CPL
Supply and transportation of 20W, 2000 lumens, T8,1200mm length LED retro tube light,wide operating voltage with double side connection, PF≥0.9,Surge protection: > 2KV, THD<15%, with inbuilt driver and frosted cover CCT: 3000K - 6500K as desired by the department and as per IS specifications, minimum CRI≥80,.etc complete with 5 years warranty.LUMINAIRE including, material and all labour charges other incidental chages etc complete as per IE rules and as directed by the departemntal officer in charges of work. MAKE: Phillips / OSRAM / GE / Crompton /VIN / Bajaj / Havells / Halonix / HPL. LED MAKE : PHILIPS LUMILEDS / CREE / NICHIA /OSRAM / SAMSUNG / LG LEDs.. Unit each
Labour charges for Fixing of Ceiling fan and regulator including transportation and giving connections with 23/0060 Twin Core twisted / flat heavy Copper wire etc., complete including, material and all labour charges other incidental chages etc complete as per IE rules and as directed by the departemntal officer in charges of work.
Labour charges Fixing of 40W tube light luminaire on wall / Ceiling with 23/0060 Twin Core twisted / flat heavy Copper wire / TW round blocks with all accessories including giving connections and all labour charges etc., complete. including, material and all labour charges other incidental chages etc complete as per IE rules and as directed by the departemntal officer in charges of work.
Providing 350mm,dia.DI K9 Raw Water pumping main from Raw water sump cum pump house at proposed off take at Pallamkur canal near Vivekanda varadhi to proposed Aerator of WTP
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH for foundations upto 3.00m depth For Pipe line trenches.including labour charges and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work. as follows
Mechanical means up to 3 metres depth in ordinary soils
Manual means up to 3 metres depth in ordinary soils
Providing river sand filling brought from approved quarry including cost and conveyance of all material and all labour charges such as filling in layers watering ramming etc complete as per ss and as directed by the departmental officer in chrges of work
Centrifugally cast 350mm dia DI K9 (Spun) Ductile Iron pressure pipes for water, gas and sewage with Socket Spigot ends conforming to IS.: 8329/2000 in standard working lengths of 4, 5 5.5 & 6 meter for classification K9 & K7 suitable for push-on-joint (rubber gasket d jointing) with cement mortar lining inside the pipes with outside zinc coating. Rates are ex-factory, including transportation and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work.
Lowering the 350 mm dia DI K9 C.I. Pipes, D.I. Pipes and fittings with S/S (Plain)ends carefully into the trenches and laying them true to alignment and gradient including all sundries, including conveyance from source of supply as per BIS No.3114/94.and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work.
Jointing the 350mm dia DI K9 C.I,D.I. Pipes, fittings and valves with rubber gasket(push-on-joint) including the cost of the gasket but including all sundries, filling with water with a water lead upto 500 m and testing to required pressure etc., comp as per BIS No.3114/1994/12888/1987 and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work.
Centrifugally cast (Spun) Ductile Iron pressure pies with flanged (welded) ends for water, gas, sewage conforming to IS: 8329/2000 in standard working lengths of 1,2,3, 4, 5 mts for classification K9 with cement mortar lining inside the pipes with outside zinc coating. Rates are ex-factory, including transportation and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work. including transportation and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work. as follows
200mm dia 2.00m long DI DF pipes for scour
350mm dia 1.00m long DI DF pipes for sluice and check valves 2+1+1
250mm dia 1.00m long DI DF pipes at sump cum pump house
Centrifugally cast (spun) Ductile Iron Fittings conforming to IS:9523/2000 having dimensions as per table. The rates mentioned here under are for fittings, zinc coated externally with inside mortar lining (with finishing as per class 13/IS 9523/2000) ( ex-works) including transportation and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work.
Lowering the C.I. Pipes, D.I. Pipes of all classes and fittings with flanged ends carefully into the trenches and laying them true to alignment and gradient including all sundries, but excluding conveyance from source of supply as per BIS No.3114/94.including labour charges and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work. as follows
200 mm dia
350 mm dia
Jointing the D.I. Pipes, fittings and valves with flanged ends including cost of jointing materials such as bolts, nuts, rubber insertion, white lead and including filling with water with a water lead upto 500 m and testing to required pressure etc., comp as per BIS No.3114/85 including labour charges and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work. as follows
350 mm dia
200 mm dia
100 mm dia
Supply and delivery of "Resilient Seated Soft Sealing" Gate Valves (Sluice Valves) with Body and Bonnet of Ductile Iron GGG-40/SG-400/15 or GGG-50/SG-500/7 or Equivalent as per IS1865, IS:3896-2 and Wedge fully Rubber Lined with food grade quality grade W270 grade EPDM, Replaceable Spindle Nut without gland packing with 3-O ring protection system on the Shaft and Seals of NBR. The Valves should be Vacuum tight and 100% leak proof with face to face dimensions as BS:5163 Type A/IS:14846. All the valves should be with fusion bonded Electrostatic Powder coating both inside and outside (Min 250 Microns)- RAL 5005 with Pocket Less Straight through body Passage conforming to Design standards of DIN-3202F4/BS:5163 Type A Flange drilling as per IS - 1538 and including transportation.PN 1.6 MPa including transportation and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work. as follows
350mm Ø DI D/F valve - PN16
200mm Ø DI D/F valve - PN16 for scour
Supply & Delivery of 100 mm dia PN16 Tamper Proof DI Flanged Single Chamber Air Release Valves with body & cover made of Ductile Iron Grade GGG-40/SG-400/15 or GGG-50/SG-500/7 or Equivalent as per IS1865, IS:3896-2 with Food Grade Epoxy Powder Coating(EP-P) (Min:250 Micron) inside and Outside of Color Blue RAL 5005. All internal parts such as Float, shell, Cove Bolts etc. made of Austenitic alloy steel of SS AISI 304/316 and DN 50 float of and other components with ABS/PTFE/EPDM/NBR and generally conforming to DIN/BIS/AWWA standards (or) combination Flange drilling as per IS - 1538 and and including transportation - PN1.6 MPa including transportation and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work.
Supply, Delivery of 350mm dia D.I Double Flanged Swing Check type Reflux valves (Non Return Valves) of following dia. conforming to IS- 5312 (Pts-1&2) (with amendments up to date, if any) having Body, Cover, Door, Bearing holder with D.I; Hinge pin, Door pin, Door suspension pin with Stainless Steel (IS 6603); Body seat ring , Door face ring, Bearing bushes, Plugs for hinge pin with Leaded Tin Bronze ( IS 318 ); Bolts, Nuts with Carbon steel; Gaskets with Rubber; Hinges with Cast steel; including transportation and complete. PN 1.6 MPa including transportation and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work.
Labour charges for lowering and keeping in position of C.I./DI Sluice valves(with cap/with hand wheel), reflux valves and scour valves.including labour charges and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work. as follows
350 mm dia
200 mm dia
Labour charges for fixing Kinetic Air Valves with isolating Sluice valves, Double Air valves/ Air Cushion valve including cost of jointing materials such as bolts, nuts and rubber insertions etc., complete.including labour charges and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work
Construction of R.C.C. thrust blocks using RCC M- 20 Nominal mix (Cement:fine aggregate: coarse aggregate) corresponding to Table 9 of IS 456 using 20mm size graded machine crushed hard granite metal (coarse aggregate) from approved quarry including cost and conveyance of all materials like cement, fine aggregate (sand) coarse aggregate, water etc., to site and including all operational, incidental and labour charges such as machine mixing, laying concrete, curing etc.,complete but excluding cost of steel and its fabrication charges for finished item of work including all labour charges and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work. for thrust blocks
Construction of Anchor blocks VCC M- 20 Nominal mix (Cement:fine aggregate: coarse aggregate) corresponding to Table 9 of IS 456 using 20mm size graded machine crushed hard granite metal (coarse aggregate) from approved quarry including cost and conveyance of all materials like cement, fine aggregate (sand) coarse aggregate, water etc., to site and including all operational, incidental and labour charges such as machine mixing, laying concrete, curing etc.,complete but excluding cost of steel and its fabrication charges for finished item of work, including all labour charges and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work for anchor block
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, including sales and other taxes on all materials etc., complete for finished item of work including all labour charges and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work
Construction of Sluice Valve chambers with VRCC M20 Concrete suitable to the sluice valves with VRCC Cover Slab including cost and conveyance of all materials and all labour charges etc.complete as per S.S for finished item of work as follows
350 mm dia
200 mm dia
Construction of 100mm dia Air Valvechambers with VRCC M20 Concrete suitable to the Air valves with VRCC Cover Slab including cost and conveyance of all materials and all labour charges etc.complete as per S.S for finished item of work
Cutting of existing B.T.road surface (aswell as asphalt concrete up to 75mm thick) including water bound macadamincluding all labour charges for cutting, stacking of materials hiring of machinary, fuil charges, wages of driver etc.,complete as per the directions of departmental authorities. For pipe line trenches.
Cutting and open of C.C. Road surface including all labour charges for cutting, stacking of materials hiring of machinary, fuil charges, wages of driver etc.,complete as per the directions of departmental authorities. For pipe line trenches.
Collection ,supply,spreading and compaction of crusher stone dust including cost and conveyance of all material nad all operational, incidental, labour charges, hire charges etc. complete for finished item of work
BLD-CSTN-3-11-(28) Using Concrete mixture up to Plinth Level : Plain Cement concrete nominal mix M-30 (Cement : fine aggregate: coarse aggregate ) using 20mm size Hard Granite Machine Crushed Graded Metal including cost and conveyance of all materials like cement, sand, coarse aggregate water etc., to site , seigniorage charges on all materials, labour charges , for mixing , laying, concrete , ramming in 15 cm layers, finishing top surface to the required level curing etc., complete for finished item of work with nomonal reinforcement for Road restoration. as per ss and as directed by the departemntal officer in charges of work.
Manufacture, Supply and Delivery 350 mm dia of M.S. Dismantling Joints with both side flange end suitable for installation in between flange end pipes. Thickness as per IS: 7322. including transportation and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work.
Errection of 3# of 7.46 KW (10 HP)CF Pumpsets each with a duty of 40 LPS and a total head of 13.00m(one working and one stand bye) for pumping Raw water from Raw water sump to proposed Aerater of proposed 6.00 MLD WTP for intermediate requirements 2033
Errection of 3# of 7.46 KW (10 HP)CF Pumpsets each with a duty of 40 LPS and a total head of 13.00m(one working and one stand bye) for pumping Raw water from Raw water sump to proposed Aerater of proposed 6.00 MLD WTP for intermediate requirements 2033
Supply, delivery, erection and commissioning of reputed make Energy Efficiency as per BEE Horizontal Split case Pumpset Capable of Discharging 40 LPS and a total head of 13m , directly coupled by pin and rubber bush type couplings to a squirrel cage induction motor having a duty of suitable capacity, with standard CI construction with bronze impeller of reputed/standard make alongwith all pressure guages and vaccum guages siphon and cock including cost of base frame including cost and conveyance of all materials, errection and commissioning charges and dismantling the existing pumpsets carefully if any and all taxes, duties, labour and transportation charges to site and all other incidental and operational charges etc; complete including all taxes but excluding GST. Supply, delivery, errection and commissioning of Motors with a speed of 1500 RPM 50 Hz TEFC horizontal foot mounted squirrel cage induction motor of reputed standard make suitable to operate 440volts to suit above pump sets fitted on a common base plate including cost and conveyance of all materials including errection and commissioning charges and dismantling the existing motors carefully if any and all taxes , duties, labour and transportation charges to site and all other incidental and operational chrages etc; complete including all taxes but excluding GST.
Supply, delivery and errection of suitable capacity vaccum pumpsets with all necessary Electrical connections, GI pipe connections & other accessories for self priming with 100 % Stand bye including cost and conveyance of all materials, errection and commissioning charges and dismantling the existing pumpsets carefully if any and all taxes, duties, labour and transportation charges to site and all other incidental and operational charges etc; complete including all taxes but excluding GST. Supply and fixing of control Pannel Board with suitable capacity bus bar suitable to operate above 3 Nos Pump Sets. The accessories all are internally wired with necessary earthing terminations. The Panel Board is made of 16 guage MS sheet metal cubical/industrial indoor type and duty painted with 2 coats enamel paint with cost of material as follows. conveyance, all taxes, duties, labour charges and all other incidents etc; complete for finished item of work
Out-going cable of suitable size of Alluminium armoured cable of 3.50core of standard make from Panel Board to Starter and to Motor Cable Joints with jointing materials such as lugs glands, adhesive taps etc; to join the above cables a per I.E Rules Supply and errection of suitable suction and delivery DI/MS pipes and connections upto manfold including heavy duty Sluice Valves on suction side per stipulations of water supply mannual and I.S.Codes Supply,delivery,errection and commissioning of suitable capacity vaccum pump to operate ablve pumpsets including connecting or pumpsets with required G.I Pipes, Specials and fixing in concrete bed etc; Supply, laying and fixing of 40x6mm G.I flat patti double earthing for electrical protection for motor, pump and panel board efficiently earthing duly providing earth pits and filling with coal and salt and G.I pipe 1 1/2 x 6" long and bottom 2'x2' G.I.Plate welded as per I.E.Rules and Specifications with cost of materialss, conveyance, taxes,duties, labour charges and all other incidental charges and providing 1 1/2' x 1 1/2' earth pit chamber with brick masonary with top cover
Supply and delivery of necessary suitable errection tools of reputed make mounted on polished teak wood board including cost of materials and all taxes and duties etc; Ring Spanner 3/16 to 1" - 1No Double end spanner set 3/16" to 1" - 1 No Pipe Wrench 18" & 4" - 2Nos Screw drivers 6", 10" & 12" - 3 Nos Cutting Plier 12" - 1No 2 Kgs Hammer with Handle - 1 No Nose Plier - 1 No Flat and Half round smooth file - 2 Nos Adjustable Spanner 6" Column pipe Clamps - 2 pairs Line Shaft Clamps - 1 Pair Line rope and clamps double the weight of pump - 2 sets Gland thghtening Spanner - 1 No Spitter removing Spanner - 1 No Supply and delivery of necessary safety equipments as per IE Rules including cost of materials and all taxes and duties etc; complete Fire extiguisher 3Kg capacity - 2 Nos Rubber Mat 6" x 4" - 2Nos Fire Buckets with stand and three buckets - 1 No Rubber Hand Gloves - 1 Sets Danger Board Plates - 4 Nos First aid kit with chart - 1No Shock Treatment Chart - 1No Portable rechargeble torch light - 1 No
Supply and delivery of indigeneous make 500V insulation tested a portable type technometer and megger etc; Supply, delivery and erection of 5 tonnes capacity double girder gantry arrangements to move and lift the installations of the pump house one way with required MS ISMB of best quality 250 x 100 mm of standard make, including the required MS ISMC, MS angular iron, 5 tonne capacity travelling trolley and 5 tonne capacity chain pulley block with chains of suitable capacity for lifting and moving arrangements to length of 10.00 m rate is inclusive of the cost of materials, labour charges, site welding etc., All Civil Works Such as anchor Blocks ,Thrust Blocks, Platform for Pannel Board and Cable trench etc Complete as directed by the Field Engineer Testing and maintanance of the complete equipment covered and trial run for 30 days at 8 hours per day after completion of errection
Errection of 100 KVA Transformer at Raw water sump cum pump house off take with Transformer yard 15.00x12.00m
Supply and erection of 7.50m long double pole structure fabricated with 150x75mm RS Joists,100x50mm MS channels, iron cross armstor fuse set and Lighting arrestrors etc.,including one coat of red oxide primer and two coats of bright Supply including all labour charges and other incidental charges etc complete as per IE rules and as directed by the departemntal officer in charges of work.
Supply and fixing of 11 KV ,400 A 3 phase central post rotating double break type AB switch(isolator) as per IS 9921) without earth blade, gang operated, Horizontal type, operating mechanism with GI spring loaded reverse loop type fixed contact, solid HD electrolytic copper tubular moving contact with silver/Nickel plated at end points,9 Nos post insulators of 12 KV (IS 2594 and IS 5350) ,Hot Dip galvanizing hardware, GI pipe, Nuts and bolts etc., complete., including all labour charges and other incidental charges etc complete as per IE rules and as directed by the departemntal officer in charges of work.
Supply and fixing of 100 A 11 KV Horn Gap fuse set as per IS 9385 on existing DP structure with 6 no of 24 KV /22 KV post Insulators (IS 5350, Hot dipped Hardware, fuse wire of required size etc., complete including all labour charges and other incidental charges etc complete as per IE rules and as directed by the departemntal officer in charges of work.
Supply and fixing of distribution type lightning arrester 11 KV 5 kA as per IS 3070 with mounting base on the existing DP structure including all labour charges and other incidental charges etc complete as per IE rules and as directed by the departemntal officer in charges of work.
Supply and erection of 11KV Strain disc. Insulators with GI pins and top clamps including all labour charges and other incidental charges etc complete as per IE rules and as directed by the departemntal officer in charges of work.
Supply and fixing of 11 KV pin Insulator (IS 731/1971) with minimum creepage distance of 300 mm on existing cross arm including all accessories like Hot dip GI spindle and nuts etc., including all labour charges and other incidental charges etc complete as per IE rules and as directed by the departemntal officer in charges of work.
Providing jumper connections with I/O' SWG HDBC wire between the 11 KV equipment on the outdoor structures including all labour charges and other incidental charges etc complete as per IE rules and as directed by the departemntal officer in charges of work.
Supply and erection of GI stay set of dia 16mm,1.8 mtr long stay rod and anchor plate 380mmx380mmx6.4mm. including stay clamps, turn buckle and GI stay wire tight end through strain insulator including excavation of pit and cc work etc., complete including all labour charges and other incidental charges etc complete as per IE rules and as directed by the departemntal officer in charges of work.
Providing efficient earthing arrangement forthe DP structure lighting arresters and the HV equipment. Transformer body and neutral etc., with 25 x 3 mm copper flats and connecting them to the Earth Electrodes fabricated and buried accroding to standard specifications including all labour charges and other incidental charges etc complete as per IE rules and as directed by the departemntal officer in charges of work. and as per the details given below:
A) Earth Electrodes
B) 20mm x 3mm Copper Flat(0.529Kgs/1Mtr) MAT 04146
C) Epoxy insulators
D) No.'8' SWG Copper wire.
Supply, Transportation, Installation, Testing and Commissioning of 11/0.433 KV TRANSFORMER with all test reports. The Transformer shall be designed and manufactured as per Energy Efficiency Level - 2 at basic Insulation level conforming to ISS 2026 (Part- I to Part - II) with latest ammended and as per IS 1180 Part-I : 2014 latest ammended, OCTC with initial filling of oil as per IS 335-1993. The basic details of the Transformer are as under.including transportation and other incidental charges etc complete as per IE Rules and as directed by the departemntal officer in charges of work. Makes : As per list of recommended brands as category I. 100KVA 1.Quantity: 1 2.Rated KVA : 100KVA 3. Service & Location: Continuous out door Distributin Transformer. 4. Mounting : Plinth
5. Woumd: Copper oil Double wound. 6. type: Core type oil immersed 7.cooling : ONAN 8.Temp Rise :40ºc in oil 45º C by resistance 9. Vector Group : Dyn 11 10.PrimaryvConnection: Detla 11.Nominal Voltage:/ Current: _________ 12.Highest system Voltage :12000V 13.Primary Frequency : 50HZ +/- 3% 14.Number of Phases: 3 15.Primary wires :3 16.Secondry Connection: Star 17.Secondry Volts/ Current :433V 18.Secondry phase : 3 19.Secondrywires: 4 20.Taps on primary winding for Primary voltage variation:+5% to -10%in steps of 2.5% of 7 position (6Steps) 21. Terminal arrangement a. HV: HT terminal box as per the site condition. b. LV: Cable box suitable to receive ---------- --Sq.mm XLPE cable 22. LV: One separate terminal for earthing. 23. Total Losses at 50% Loading [Watts] [Max] --- as per IS 24. Total Losses at 100% Loading [Watts] [Max]--- as per IS 25.Percentage Impedance at 75 deg. C at -----as per IS 26. No Load current: Less than 2% of full load current. 27. Standard Fittings & Accessories. a. Rating and terminal marking plate: One b. Lifting Lugs: Two c. Off-circuit tap switch: One. d. Earthing Terminals : Two e. Radiators (Attachable): Adequate f. Explosion vent with Diaphragm : One g. Conservator with Drain plug: one h. Oil filling hole with cap :One i. Oil level indicator: One j. Dehydrating Silica gel Breather: One k. Terminal Arrangement: HV With Terminal Box l. Terminal Arrangement: LV Cable Box m. Separate Neutral Bushing : One n. Drain cum filter valve with blanking plate: One o. Air release device: One p. Thermometer Pocket: One q. Four: Unidirectional flat rollers r. One :10Cm dial thermometer (Rigid stem type)
Supply and laying of 400Sq mm X 3.5 core XLPE insulated, 1100V grade armoured aluminum cable as per specification confirming to IS:7098 (Part- I)./1554-I including transportation and other incidental charges etc complete as per IE Rules and as directed by the departemntal officer in charges of work. Makes: Makes: Torent / Universal / Unicab / Havells / Finecab/ KEI / Gloster/ Polycab /RR Kabel/ Fortune Arrt
Supply Installation Testing and commissioning of free-standing floor mounted dust and vermin proof compartmentalized cubical panel made out of CRCA sheet, required hardware, cleaning with 7 tank process duly painted by two coats of zinc/red oxide primer followed by Powder coated / epoxy / PU painted with phosphatisation in grey or required shade after rinsing. The panel having PU/ Neoprene rubber gasket of not less than 3mm thickness, separate detachable, gland plate M.S. base channel, hinged door with locking arrangement for equipment/switchgear. The thickness of sheet shall not be less than 1.6mm up to 600mm length/ width of any compartment and be 2.0mm above 600mm. The load bearing structure shall be of 2.0mm thick sheet supported by base M.S. channel if required. Side walls and cable alley compartments having bolted type doors with detachable extension type structure (only outer area on all sides shall be measured and panel to be fabricated from CPRI approved fabricator) including transportation and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work.
Supply and fixing of Electrolytic grade copper bus bar bus bar by means of SMC / DMC type insulator, high tensile nuts and bolts spring washers in existing panel including bending , cutting in required shape and size and colour coding with heat shrinkable PVC sleeves including all labour charges and other incidental charges etc complete as per IE Rules and as directed by the departemntal officer in charges of work
a) 630A TPN SDFU for main switch including all labour charges and other incidental charges etc complete as per IE Rules and as directed by the departemntal officer in charges of workMakes:LauritzKnudsen(FormerlyL&T)/Schneider/ C&S/ ABB / SIEMENS MAT 02885
b) 630A 4pole change over switch including all labour charges and other incidental charges etc complete as per IE Rules and as directed by the departemntal officer in charges of workMakes:Socomec/LauritzKnudsen(FormerlyL&T)/HPL / Havells/ C&SMAT MAT 02898
c) Supply and fixing of (0-500) V range Voltmeter on existing panel, making connection by PVC insulated copper conductor with PVC sleeves /channel etc. as required Digital type including all labour charges and other incidental charges etc complete as per IE Rules and as directed by the departemntal officer in charges of work Make: Conzerve/Elmeasure/Meco/HPL/L&T/socomec MAT 03980
e). Supply and fixing of CT operated direct reading type Ammeter on existing panel, making connection by PVC insulated copper conductor with PVC sleeves / channel etc. as required. Digital type Below 500 A including all labour charges and other incidental charges etc complete as per IE Rules and as directed by the departemntal officer in charges of work Make: Conzerve/Elmeasure/Meco/HPL/L&T/Schneider/AE/Socomec MAT 03983
g).3RYB Phase indication lamps with leds including all labour charges and other incidental charges etc complete as per IE Rules and as directed by the departemntal officer in charges of work
h).Supply and Fixing of Current Transformer, with all necessary support in existing panel including connection etc. as required from 200 / 5 to 400/5 Ratio, 10 VA, class 1 accuracy: including all labour charges and other incidental charges etc complete as per IE Rules and as directed by the departemntal officer in charges of workMake: Kappa/L&T/Seimens/C&S/Schneider
630A TPN SDFU for CW pump house motors and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work. Makes:LauritzKnudsen(FormerlyL&T)/Schneider/ C&S/ ABB / SIEMENS MAT 02885
630A TPN SDFU for compressor/mechanical equipments and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work. Makes:LauritzKnudsen(FormerlyL&T)/Schneider/ C&S/ ABB / SIEMENS MAT 02885
630A TPN SDFU for low lift sump Raw water motors and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work. Makes:LauritzKnudsen(FormerlyL&T)/Schneider/ C&S/ ABB / SIEMENS MAT 02885
630A TPN SDFU for Space and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work. Makes:LauritzKnudsen(FormerlyL&T)/Schneider/ C&S/ ABB / SIEMENS MAT 02885
630A TPN SDFU for lighting section and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work. Makes:LauritzKnudsen(FormerlyL&T)/Schneider/ C&S/ ABB / SIEMENS MAT 02885
630A 4pole change over switch for lighting section etc complete as per IE rules and as directed by the departemntal officer in charges of work. Makes:Socomec/LauritzKnudsen(FormerlyL&T)/HPL / Havells/ C&SMAT MAT 02898
.KWH digital meter fro lighting section etc complete as per IE rules and as directed by the departemntal officer in charges of work.
Supply of 32 Amp………ISI marked TPN Switch Disconnector Fuse Unit, Cubical type without fuses as per IS: 13947/IEC 60947-3 etc complete as per IE rules and as directed by the departemntal officer in charges of work. Makes: As per list of recommended brands as category I.
Supply of 6A to 35 A……ISI marked HRC Fuse Links as per IS 13703-Part 2/IEC 60269- Part 2 etc complete as per IE rules and as directed by the departemntal officer in charges of work. Makes: As per list of recommended brands as category I MAT-02938
Standard duty Single phase 250 V / Three phase 440 V, 50 Hz capacitor (Bank) etc complete as per IE rules and as directed by the departemntal officer in charges of work.
1000KV LT/Transformer Errection.testing Commensing and Supply of drawing layout plans of installed transformer in tracing cloth and duly get approved from electrical inspector APEPDCL and leaflets for various equipments and opearation manuals etc., complete.etc complete as per IE rules and as directed by the departemntal officer in charges of work.
Supply and Laying of 3C X 35 Sq mm XLPE insulated IS:7098/II/85 H.T. cable for working voltage 11 KV Earthed with Stranded Compacted Circular Aluminium Conductor Screened with Extruded Semi-conducting compound, XLPE Insulated Screened with extruded semi-conducting compound in combination with Copper Tape, cores laid up, inner sheath of Thermoplastic tape, galvanized flat steel strip armoured and overall Extruded PVC Type ST- 2 Outer Sheathed cable etc., complete. etc complete as per IE rules and as directed by the departemntal officer in charges of work. Make: Torrent / Universal / Unicab / Havells / KEI/Polycab/Gloster/RR Kabel/RPG MAT 03456
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH Note : Classifications of Earth Work Specification are as per 302.2.1(a) of MORD and 301.2.1 of MORT&H--ordinary soil--manual means upto 3m depth for foundations of buildings in restricted places By manual means and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work.
Providing river sand filling brought from approved quarry including cost and conveyance of all material and all labour charges such as filling in layers watering ramming etc complete as per ss and as directed by the departmental officer in chrges of work
Providing PCC 1:4:8 using 40 mm graded SS 5 HBG m/c metal and OPC coarse and fine aggregate confirming to IS 383 including cost and conveyance of all materials and labour charges, machine mixing , vibration,laying in position, curing etc., complete etc complete as per ss and as directed by the departmental officer in chrges of work
Supply and placing of the design mix concrete corresponding to IS -456 using WEIGH BATCHER/MIXER using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including all operational ,incidental and labour charges such as weigh batching ,machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work (APSS NO 402) with minimum cement content as per IS Code from standard suppliers approved by the deparment including pumping , centering,shuttering,laying concrete, vibrating,curing etc M25 design mix concrete etc complete as per ss and as directed by the departmental officer in chrges of work as follows
column footings
Columns 1.20-0.10-0.10-0.30+1.80
Plinth beam 2(15+12)=54-gate3.00=51.00
Painting Walls with Snowcem or other equal and approved Water Proof Cement Paint 2 Coats (All Colours) over a base coat of aproved cement primer making 3 coats in total including cost of all materials, conveyance charges of materials and including all operational, incidental and labour charges etc,, complete for finished item of work as directed by the departmental authorities.
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying ietc., complete for finished item of work in all floors.( APSS No.126) and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work.
Supplying and fixing galvanised steel barbed wire (IS : 278-1962 Type I) weighing 9.38 Kg per 100 metres (min.), Straining and fixing to any type of standard, rails, straining bolts, including securing with and provision of galvanised mild steel wire, stapples or steel pins, etc., as directed (Posts and struts of wood, concrete, steel, etc.) and straining bolts shall be paid for separately).
Manufacture,supply,delivery of MS grill gates,window ornamental safety grill ,made with MS flats,MS angles,MS squares etc including welding, finishing, etc complete and all labour charges,and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work.
Painting two coats with synthetic enamel paint on new iron work over a base coat of red-oxide making 3 coats in total including cost of all materials, conveyance charges of materials and including all operational, incidental and labour charges etc,, complete for finished item of work as directed by the departmental authorities.(APDSS No:1201)
supply and filling the transformer yard with 40mm HBG metal including cost of all materials, conveyance charges of materials and all operational, incidental and labour charges etc., complete for finished item of work as per ss and as directed by the departemntal officer in charges of work.
Construction of 6.00 MLD Rapid Gravity Filtration plant
Construction of 6 MLD Rapid Gravity Filtration Plant including all civil, mechanical and electrical works using sand as filter media, compatible with SCADA arrangements, duly following relevant IS codes in the design of plant components including trial running for 90 days etc., including chlorine contact tank & consumables etc., complete. For components immersed in water Stain less Steel of Grade 304L shall be used. for other components 304 Grade steel shall be used. Lab testing equipment of reputed make and consumables for one year. The testing equipment for conducting all laboratory tests shall be installed & training shall be imparted to the Municipal staff.
The above rates of Filtration Plants shall include all the following components. CivilWorks (All works of VRCC Shall be in M30 design mix) Stilling Chamber and Aeration cascade Pre settling tank shall be provided for 30 MLD and above capacities of WTP for a minimum of 1 hr capacity. Raw water channel with Stainless Steel Weir of SS 304 L Grade material and also with digital flow meters Flash Mixer chamber with Flash mixing arrangements including SS shaft & SS Blades with gear wheel arrangements etc, using 304 L Grade Steel. Clariflocculator / Flocculation tanks with the components of central driven circular clarifier with scrapper & bridge arrangements made with Stainless Steel Grade 304 L tubes /angular for durability & chemical resistant with wheel arrangements etc
Two numbers of Clariflocculator shall be provided for WTP's of more than 30 MLD capacity. Filter house, Chemical house, Alum store, Laboratory room, Chlorination plant room, toilet etc. (All structures shall be provided RCC roof only). Chemical house & Chlorinator rooms are to be isolated and shall be as per CPHEEO manual. Wash water tank of suitable capacity shall be constructed at minimum clearance of 2.00m, above the roof slab of Filter beds / any other structure, and the minimum residual head at the top of under drain system shall not be less than 8.0 meters. Chlorine contact tank All the Doors and Windows shall be of Best Teak wood/Aluminum / UPVC make, except entrance door. The entrance door including shutter in filter house shall be with best teak wood of minimum size of 2.40 X 2.40 mts. a) Main Doors of all individual Buildings shall be made of Best Teak wood b) Other Internal Doors of the buildings shall be of Compressed wood/ Aluminum/ UPVC materials. c) Ventilators shall be provided for each building/structure of suitable size as per NBC standards.
a) All pipes in Plant shall be of D.I., D/F materials. All Connecting pipes of the plant components such as from Flash mixer to Clariflocculator/ Clarifier/Flocculation tank, to Filter beds, sludge disposal pipes shall be of D.I., D/F material. The size of sludge disposal pipe shall be minimum of 450 mm dia. with D.I D/F pipe and minimum length of 100 meters. b) All the Valves in Plant shall be heavy duty and as per the specification of SoR item No.28. The Pipe gallery way for Clear water/ Back wash water/ pipe connections shall be sufficiently spaced for easy operation & maintenance and inspection, as per standard norms. The bottom level of the wash water control chamber must be above G.L so as to dispose the wash water and sludge from Clariflocculator by gravity to disposal point Additional specifications Railing for all the components (Clariflocculator, Filter House, Staircase etc,.) shall be provided with Stainless Steel of grade 304 for a height of 1.00m, with 40mm dia. pipe for top horizotals,25mm dia. for middle row and 40mm dia. verticals spaced at interval of not more than 1.00m c/c.
Inspection / Path ways in filter beds: Middle pathway: Minimum of 1.50m, Side pathway: Minimum of 1.20m Flooring in the buildings (Filter house, Chemical House, Chlorinator Room, Laboratory) shall be provided with Non-skid ceramic tiles of approved make & quality, as per standard specifications. ii) All water Channels such as inlet, outlet channels and chambers shall be provided with tiles. The basement of the Filtration plant building shall be minimum of 1.20m and pipe gallery shall be minimum 0.3m above the existing nearby Road top level. 17) Minimum head room of 2.00m shall be provided, at the alum mixing chambers in alum store for inspection & maintenance. The minimum width of entrance hall for the Filter House shall be 4.50m, and Laboratory of min size of 3.30 X 4.50m.
b) For various components of the WTP should be designed by considering the uplift pressure also. a) High efficient Air Blowers shall be installed to the design requirement with low noise pollution, environmental pollution as per PCB guide lines & Testing of blowers as per I.S Standards at site. b) The Piping from Blower to Filter Beds shall be GI and submerged pipe in water shall be HDPE. UPVC pipes shall be provided for under drain system. Filter pipe manifolds shall be assembled with HDPE pipes. 21) Alum storage capacity shall be designed for minimum period of 90 days. Consumables shall be provided for 2115 Running Hours of WTP. Chlorinator : Vacuum type chlorinator shall be provided with following specifications: a) Vacuum operated solution feeding type Vacuum Regulator, Rotameter, Rate setting Valve, built-in NRV, Gas Overflow out let by man folding to mount the system with the unit. b) The unit shall consist of Ejector with necessary accessories such as Check Valve, Drain Valve and Vacuum relief Valves - for control of chlorinator dosage. c) The Accessories and manifolds shall be chlorine resistant and made of carbon steel seam less pipes, copper tube with brass fittings of suitable size & dimensions, with diaphragm sealed chlorine pressure gauge arrangements
d) Water Booster Pump of pumping capacity ranging from 2 cum/hr to 12 cum/hr, with Head ranging from 16 to 35 m e) The water & solution carrying pipes shall be made of UPVC material of suitable size incl. all specials such as Tee's , Bends, couplings & NRVs and also Pressure Gauges of suitable range. f) Chlorine Gas Leak detector with alarm indicator. The installation includes all necessary accessories, civil and mechanical works, manifold header installations, injector fixing, connection with UPVC pipes, solution piping’s, fixing of motors as per standard specifications and commissioning of Chlorination Plant to the required demand, with a defect liability period of 1 year. The chlorinator of may be of any reputed make or any make of Metito/Toshocow-Jesco Siemens Industrial Devices. g) Life breathing apparatus. h) Chlorine escape BA set 2 to 10 MLD Plants - 1Kg/hr Chlorinator- For Post Chlorination ii) 10 MLD to 20 MLD Plants - 2 Kg/hr Chlorinator - For Post Chlorination. iii) 20 MLD to 50 MLD Plants - 5 Kg/hr Chlorinator - For Post Chlorination.
B) Mechanical Equipment 1) Alum dosing equipment with SS 304 material made stirrers & paddles for chemical resistance. (Alum tanks must be bound with corrosion resistant material (HDPE Lining, Bitumen Coating, tiles etc) 2) Flash mixer equipment with SS 304 material made stirrers & paddles for chemical resistance. 3) Filtration plant equipment instrumentation and piping. 4) Clarifloccualation equipment (with stainless steel blades) with rotating bridge arrangement etc., 5) Pneumatic tyre wheel shall be provided for the bridge Clariflocculator. 6) Wash water tank fittings and pump sets with 100% stand by. 7) Air blower with motor of 100% stand by and pipe connections made with of SS pipes confirming to SS 304 Grade, in filter bed region. 8) Chlorination equipment and pipe connections with chlorinator of 100% standby. 9) Spares & Tools for 2 years. 10) Gaseous Chlorination with cylinders has to be provided with protection measures. C) Electrical Equipment 1) Necessary power supply wiring to motors and switches bus bar connections as per IE Rules 2) Internal wiring and illumination and fittings and fixtures for internal and external lighting exhaust fans, ceiling fans etc. 3) Erecting mechanical and electrical equipment, trial run for 90 days at 23.50 hours per day testing the treated water as per CPHEEO standards and maintenance of records and imparting training to staff. 4) Supply of 6 - Sets of completion plans and maintenance manual and brochures. 5) All cables shall be of copper material, Cable ducts shall be covered with MS / Aluminum cheque plate. 6) Min LUX levels inside the treatment plant shall be maintained. 7) Yard lighting shall be provided as per norms. D ) Equipment for Flow measurements
1) Equipment for measuring Conductivity, Turbidity, Ph value, Residual Chlorine with recording & data storage facility (Computer based) & Alarm by SMS or other methods. 2) Off - Site Supervisory and Data Acquisition (OSSADA) system for Raw water & Clear water flows by installing Digital Flow meters to measure the flows at Raw water Channel and at each filter bed individually and combined for measuring the quantities of water treated with a facility to record and store the readings & also to send messages to the assigned designators about the variations/ deficiencies in the flow including alerts for back wash requirements of filter beds, and recovery of data for the past 360 days. All the Digital Flow Meters & Pressure Gauges shall be provided of standard approved make. The equipment shall have the following specifications. Hardware: i) Wall mounted Sensor House for measuring Raw water & Clear water flow from Filter bed out lets with accessories consists of ii) Electrode Type: General type, Scraper type or replaceable type Electrode made with material of SS external Ultra Touch Sensors as per requirement.
iii) Customized Application Requirement : Sensors with Interface logic control board with serial interfaces, including accessories such as Add-on port, external DC Power Socket, On - sensor Board Buffer, Timer, RS485 Communication, Analog to Digital Sensing Sensor Circuit, 32 Sensors Sensing Tags, Interval Power Supply System , LCD 16c/2L, Filter Bed Working Status Indication LED, Filter Bed Wash Indication Button and memory of Data Storage for 30Days , status of Filter Bed Level indicator, Rating, Reading on LCB Display, Menu Driven Data for sending to Onsite Big Display, operated with Battery Power of any reputed make or any equivalent make. iv) Customized Application Requirement: Power Sensors Interface logic control board with support 8 Power Sensing tags, Central System Interfacing Communication, On - board analog to Digit Convert Integrate Circuit of any reputed make or any equivalent make. Customized Application Requirement: Centralized System with two serial interfaces, 3 No’s of Add-On ports, One external DC Power Socket, On - Board Buffer, On - Board Timer, On - Board RS485 Communication, On - Board RS 232 Communication, On - Board GPRS/GSM Module, On - Board Voice Chip, On - Board Power Sensing Module, LCD 16c/2L, Filter Bed Wash Precaution Indication with Stop Button, Memory of Data Storage for 30 Days, Total Bed Rating, Reading display on LCD Display, Menu Driven, Menu Navigate Keypad, sending data to the Web Server, Communication with GPRS , operated with Battery Power of any reputed make or any equivalent make.
Software: The software shall be designed with Web Domain with Data Base Server and Web Name as per the directions of the Departmental Authorities. The application of Software for Web design & Desktop shall meet the following requirements: i)Onsite Display: Letters with size of 1.5’ seven Segment LED Display with Interface for each Filter Bed, for Onsite Display, by displaying the Bed Levels, Ratings, Readings in 3 Columns, for each bed of the plant in successive rows and cumulative results at the bottom of the screen. ii) Off Site Display: Letters with size of 1.5’ seven Segment LED Display with Interface GPRS/GSM Modules Offsite Display, with Display of Bed Total Rating, Total Cumulative Reading as specified on On-site Display Features. The system shall have also the features of Onsite Bed Wash Voice Precautions for Bed Levels, Readings, Ratings, Bed Capacity Readings and Ratings and Bed Low Level Triggering, before & after Bed wash.
Centrifugally cast (Spun) Ductile Iron pressure pies with flanged (welded) ends for water, gas, sewage conforming to IS: 8329/2000 in standard working lengths of 1,2,3, 4, 5 mts for classification K9 with cement mortar lining inside the pipes with outside zinc coating. Rates are ex-factory, including transportation and etc complete and all labour charges,and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work. as follows
300 mm dia DI DF pipes from WTP to clear water sump
300mm from WTP to sump horizantal
Centrifugally cast (spun) Ductile Iron Fittings conforming to IS:9523/2000 having dimensions as per table. The rates mentioned here under are for fittings, zinc coated externally with inside mortar lining (with finishing as per class 13/IS 9523/2000) ( ex-works) including etc complete and all labour charges,and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work.
Supply and delivery of 300 mm dia "Resilient Seated Soft Sealing" Gate Valves (Sluice Valves) with Body and Bonnet of Ductile Iron GGG-40/SG-400/15 or GGG-50/SG-500/7 or Equivalent as per IS1865, IS:3896-2 and Wedge fully Rubber Lined with food grade quality grade W270 grade EPDM, Replaceable Spindle Nut without gland packing with 3-O ring protection system on the Shaft and Seals of NBR. The Valves should be Vacuum tight and 100% leak proof with face to face dimensions as BS:5163 Type A/IS:14846. All the valves should be with fusion bonded Electrostatic Powder coating both inside and outside (Min 250 Microns)- RAL 5005 with Pocket Less Straight through body Passage conforming to Design standards of DIN-3202F4/BS:5163 Type A Flange drilling as per IS - 1538 etc complete and all labour charges,and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work. .PN 1.6 MPa
Labour charges for 300 mm dia lowering and keeping in position of C.I./DI Sluice valves(with cap/with hand wheel), reflux valves and scour valves etc complete and all labour charges,and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work.
Lowering the C.I. Pipes, D.I. Pipes of all classes and fittings with flanged ends carefully into the trenches and laying them true to alignment and gradient including all sundries, but excluding conveyance from source of supply as per BIS No.3114/94.etc complete and all labour charges,and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work.
Jointing the 300 mm dia C.I. Pipes, fittings and valves with flanged ends including cost of jointing materials such as bolts, nuts, rubber insertion, white lead and including filling with water with a water lead upto 500 m and testing to required pressure etc., comp as per BIS No.3114/85.etc complete and all labour charges,and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work.
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH for pipe line trench etc complete and all labour charges,and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work.
Providing river sand filling brought from approved quarry including cost and conveyance of all material and all labour charges such as filling in layers watering ramming etc complete as per ss and as directed by the departmental officer in chrges of work
Construction of Sluice Valvechambers with VRCC M20 Concrete suitable to the sluice valves with VRCC Cover Slab including cost and conveyance of all materials and all labour charges etc.complete as per S.S for finished item of work etc complete and all labour charges,and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work.
Construction 10.00m dia m dia (188.64 KL) clear water sump at WTP
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH for foundations upto 3.00m depth etc complete and all labour charges,and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work. as follows
Mechanical Means up to 3 metres depth in ordinary soils
Mechanical Means 3 to 6 metres depth in ordinary soils
Manual Means 3 to 6 metres depth in ordinary soils
Providing river sand filling brought from approved quarry including cost and conveyance of all material and all labour charges such as filling in layers watering ramming etc complete as per ss and as directed by the departmental officer in chrges of work
Plain cement concrete (1:4:8) using 40mm m/c SS5 HBG including machine mixing, laying, compacting, finishing, curing etc for foundations etc complete and all labour charges,and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work.
Supply and placing of the design mix concrete corresponding to IS -456 using WEIGH BATCHER/MIXER using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including all operational ,incidental and labour charges such as weigh batching ,machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work (APSS NO 402) with minimum cement content as per IS Code from standard suppliers approved by the deparment including pumping , centering,shuttering,laying concrete ,vibrating,curing etc M30 design mix concrete with concrete mixer etc complete and all labour charges,and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work. as follows
For side walls circular 0.30m thick below GL
For side walls circular 0.30m thick above GL
Columns 0.30 x 0.30m 3.60-0.30
Roof beams
Roof slab 0.15m thick 0.786x(10.60^2-4.00^2)
Roof dome slab 0.15m thick
Providing impervious coat to exposed RCC roof slab surface with CM(1:3), 20mm thick with 1kg of water proof compound per bag of cement laid over roof when it is green including cost of all materials, conveyance charges of materials and including all operational, incidental and labour charges for mixing mortar, laying, rendering smooth and thread lining, curing, rounding off junctions of wall and slab etc,, complete for finished item of work etc complete and all labour charges,and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work.
Painting Walls with Snowcem or other equal and approved Water Proof Cement Paint 2 Coats (All Colours) over a base coat of aproved cement primer making 3 coats in total including cost of all materials, conveyance charges of materials and including all operational, incidental and labour charges etc,, complete for finished item of work as directed by the departmental authorities.
Supply and delivery and fixing in position M S grill of any design including etc complete and all labour , fixing charges,and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work.
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying etc., complete for finished item of work in all floors.( APSS No.126) etc complete and all labour charges,and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work.
Construction of R.C.C. railing of M 25 grade in cast-in-situ with 20 mm nominal size aggregate, true to line and grade, tolerance of vertical railing post not to exceed 1 in 500, centre-to-centre spacing between vertical posts not to exceed 2000 mm as per drawing and technical specifications Clauses 800, 900 and 1208.3 MORD. etc complete and all labour charges,and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work.
Construction of 10.50x7.50m pump house for clear water pumps and motors at proposed WTP
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH etc complete and all labour charges,and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work. as follows
Mechanical means up to 3 metres depth in ordinary soil
Manual Means up to 3 metres depth in ordinary soil
Providing river sand filling brought from approved quarry including cost and conveyance of all material and all labour charges such as filling in layers watering ramming etc complete as per ss and as directed by the departmental officer in chrges of work
Providing PCC 1:4:8 using 40 mm graded SS 5 HBG m/c metal and OPC coarse and fine aggregate confirming to IS 383 etc complete and all labour charges,and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work.
Providing PCC 1:3:6 using 40 mm graded SS 5 HBG m/c metal and OPC coarse and fine aggregate confirming to IS 383 etc complete and all labour charges,and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work.
Supply and placing of the M25 design mix concrete corresponding to IS -456 using WEIGH BATCHER/MIXER using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including all operational ,incidental and labour charges such as weigh batching ,machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work (APSS NO 402) with minimum cement content as per IS Code from standard suppliers approved by the deparment including pumping , centering,shuttering,laying concrete ,vibrating,curing etc M25 design mix concrete etc complete and all labour charges,and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work. as follows
Column footings
Pedestals
Columns
Plinth beam 3.50-0.30
Lintel beams
Roof Beams
Roof slab 0.125m thick,
Sunshades 0.60m wide, 0.10m at fixed end and 0.05m at free end etc complete and all labour charges,and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work.
Brick work in CM 1:6 mix using 2nd class bricks Cost including cost of all materials, conveyance charges of materials and all operational, incidental and labour charges for mixing mortar, laying, rendering smooth , curing,etc,, complete for finished item of work etc complete and all labour charges,and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work. as follows
Ground floor
1st floor Parapet wall 2(11.70+8.63)=40.66
Cement plastering using opc in cm(1:5) prop 12 mm Cost including cost of all materials, conveyance charges of materials and all operational, incidental and labour charges for mixing mortar, laying, rendering smooth , curing,etc,, complete for finished item of work out side & inside etc complete and all labour charges,and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work. as follows
Ground floor
1st floor Parapet wall
Cement plastering using opc in cm(1:3) prop 12 mm Cost including cost of all materials, conveyance charges of materials and all operational, incidental and labour charges for mixing mortar, laying, rendering smooth , curing,etc,, complete for finished item of work as per SS for ceiling etc complete and all labour charges,and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work. as follows
Cement plastering using opc in cm(1:3) prop 20 mm thick including cost of all materials, conveyance charges of materials and all operational, incidental and labour charges for mixing mortar, laying, rendering smooth , curing,etc,, complete for finished item of work and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work.
Painting Walls with Snowcem or other equal and approved Water Proof Cement Paint 2 Coats (All Colours) over a base coat of aproved cement primer making 3 coats in total including cost of all materials, conveyance charges of materials and including all operational, incidental and labour charges etc,, complete for finished item of work as directed by the departmental authorities.
Supply & fixing of Rolling shutter made of 80 x 1.25 mm machine rolled CRCA laths, interlocked together through their entire length and jointed together at the ends by end-locks, mounted on specially designed pipe shaft of 50mm dia nominal bore MS B class pipe with brackets, plates, guide channels, stoppers, bottom locking plates and arrangements for inside & outside locking with push-pull operations including cost of hood cover and springs complete, painted with one coat of approved steel primer, locks, ball bearings, all accessories etc complete for finished item of work as per special spn: 1108 etc complete and all labour charges,and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work.
Supply and fixing Aluminium Anodized Two/ Three Track Sliding Windows as per approved drawing with aluminium anodized sections of Series C Jindal or approved equivalent make sections and outer frame top horizontals & both verticals of 8774 of size 62 x 29.5 mm and bottom horizontal - two track frame of 8773 of size 62 x 29.5 mm, Shutter frame top, bottom and verticals of 8304 of size 50 mm x 20 mm and Weather interlocking frame of 8306 of size 50 x 20 with plain clear float glass 5 mm thick fixed including supply and fixing aluminium handles of 100 mm for each shutter, nylon rollers assembly and all labour charges for fixing the fixtures with required no. of screws, bolts and nuts and including labour charges for fixing the frame in position, fixing shutter to frame etc. completed for finished item of work
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying etc., complete for finished item of work in all floors.( APSS No.126) etc complete and all labour charges,and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work.
Manufacture,supply,delivery of MS grill gates,window ornamental safety grill ,made with MS flats,MS angles,MS squares etc including welding,finishing,etc complete etc complete and all labour charges,and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work.
Painting two coats with synthetic enamel paint on new iron work over a base coat of red-oxide making 3 coats in total including cost of all materials, conveyance charges of materials and including all operational, incidental and labour charges etc,, complete for finished item of work as directed by the departmental authorities.(APDSS No:1201) etc complete and all labour charges,and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work.
Supply delivary and fixing RCC Jollys includnig cost and conveyance of all material and all labour charges for fixing etc complete as ss and as directed by the departemntal officer in charges of work.
Supply, delivery and fixing of 110mm dia single socket PVC pipes 4 kg/sqcm prince/Sudhakar or any ISI brand for rain water pipes with clamps etc complete and all labour charges,and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work.
Supply and fixing of 25 mm dia 2.20 mm thick PVC pipe concealed in roof slab with all required accessories including masonary work all labour chages etc complete and all labour charges,and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work.
Supply and fixing of 20 mm dia 2.10 mm thick PVC pipe concealed in walls with all required accessories including masonary work for light , fan and plug point with metal deep box including all labour chages etc complete ,and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work.
Wiring with 2 runs 14/0.3 mm. (1.0. sq.mm) Fire retardant PVC insulated Flexible copper cable in existing pipe with 6A siwtch, ceiling rose and 3 mm thick hyla sheet covering to switch control box including all labour charges etc,., complete for light, bell , fan and exhaust fan points in non - residential building etc complete as per IE rules and as directed by the departemntal officer in charges of work.
Wiring with 2 runs 14/0.3 mm. (1.0. sq.mm) Fire retardant PVC insulated Flexible copper cable in existing pipe with 6A modular siwtch control and 3/2 pin sockets fixing on board including all labour charges etc complete as per IE rules and as directed by the departemntal officer in charges of work. for hall
supply and run of 2 of 36/0.3 mm. (1.5. sq.mm) Fire retardant PVC insulated Flexible copper cable in existing pipe for mains including all labour charges including all labour charges etc complete as per IE rules and as directed by the departemntal officer in charges of work. for hall
supply and run of 1 of 14/0.3 mm. (1.0. sq.mm) Fire retardant PVC insulated Flexible copper cable in existing pipe for earth continuity including all labour charges etc.including all labour charges etc complete as per IE rules and as directed by the departemntal officer in charges of work.
supply and run of 2 of 6 sq.mm (7/18) WPSC alluminium cable along with No.10 SWG G.I barer wire through PVC cleats with all accessories including all labour charges etc.,including all labour charges etc complete as per IE rules and as directed by the departemntal officer in charges of work. for hall
Providing independent earthing by excavating a trench to a depth of 2.10m in all soils, as per size specied in data ,using 40 mm dia B class GI pipe 2.50m long with necessary accessories with hume pipe ring duly providing staggered holes including filling with equal proportion of salt and charcoal in layers and all labour charges etc complete
S&F of SPN distrubution board with IP 42 protection (metal door) suitable for 3 phase ELCB-RCCB-FP isolator as incomer and 10 KA SP MCBS as out going including internal connection and labour charges for surface-flush mounting etc -- 63 A FP isolator-1 no for incomer,6-32A SP MCBS -18 Nos for out going
Supply of 48" (1200mm) Sweep 5 star rated Ceiling Fan , with double ball bearings, air delivery more than 200 cubic meter/min but without Regulator.Makes : Crompton HS Plus / Havells ES Neo/Orient Energy Star/ Halonix(Zephyr)/Polycab(Synergy Star)
Supply of stepped type Electronic Regulator of Makes: GM G Home / Gold Medal Olive / Million Zoom / Great white Omega/Koncept/Vimal opel/ Anchor/Vihan/CPL
Supply and transportation of 20W, 2000 lumens, T8,1200mm length LED retro tube light,wide operating voltage with double side connection, PF≥0.9,Surge protection: > 2KV, THD<15%, with inbuilt driver and frosted cover CCT: 3000K - 6500K as desired by the department and as per IS specifications, minimum CRI≥80,.etc complete with 5 years warranty.LUMINAIRE MAKE: Phillips / OSRAM / GE / Crompton /VIN / Bajaj / Havells / Halonix / HPL. LED MAKE : PHILIPS LUMILEDS / CREE / NICHIA /OSRAM / SAMSUNG / LG LEDs.. Unit each
Labour charges for Fixing of Ceiling fan and regulator including transportation and giving connections with 23 / 0060 twin core twisted / flat heavy Copper wire etc., complete
Labour charges Fixing of 40W tube light luminaire on wall / Ceiling with 23 / 0060 twin core twisted / flat heavy Copper wire / TW round blocks with all accessories including giving connections and all labour charges etc., complete.
Supply ,Erection and Commissioning of Crane Gantry Girder of Capacity of 3.00 T including cost and conveyance of all material and all labour charges etc complete as per ISI and as directed by the dept . Including all taxes & Labour cess
Errection of 3# of 26.11 Kw (35HP)CF Pumpsets each with a duty of 38 LPS and a total head of 48m (one working and one stand bye) for pumping clear water from cklear water sump to proposed ELSRs for intermediate requirements 2033
Errection of 3# of 26.11 Kw (35HP)CF Pumpsets each with a duty of 38 LPS and a total head of 48m (one working and one stand bye) for pumping clear water from cklear water sump to proposed ELSRs for intermediate requirements 2033
Supply, delivery, erection and commissioning of reputed make Energy Efficiency as per BEE Horizontal Split case Pumpset Capable of Discharging 38 LPS and a total head of 48m , directly coupled by pin and rubber bush type couplings to a squirrel cage induction motor having a duty of suitable capacity, with standard CI construction with bronze impeller of reputed/standard make alongwith all pressure guages and vaccum guages siphon and cock including cost of base frame including cost and conveyance of all materials, errection and commissioning charges and dismantling the existing pumpsets carefully if any and all taxes, duties, labour and transportation charges to site and all other incidental and operational charges etc; complete including all taxes but excluding GST. Supply, delivery, errection and commissioning of Motors with a speed of 1500 RPM 50 Hz TEFC horizontal foot mounted squirrel cage induction motor of reputed standard make suitable to operate 440volts to suit above pump sets fitted on a common base plate including cost and conveyance of all materials including errection and commissioning charges and dismantling the existing motors carefully if any and all taxes , duties, labour and transportation charges to site and all other incidental and operational chrages etc; complete including all taxes but excluding GST.
Supply, delivery and errection of suitable capacity vaccum pumpsets with all necessary Electrical connections, GI pipe connections & other accessories for self priming with 100 % Stand bye including cost and conveyance of all materials, errection and commissioning charges and dismantling the existing pumpsets carefully if any and all taxes, duties, labour and transportation charges to site and all other incidental and operational charges etc; complete including all taxes but excluding GST. Supply and fixing of control Pannel Board with suitable capacity bus bar suitable to operate above 3 Nos Pump Sets. The accessories all are internally wired with necessary earthing terminations. The Panel Board is made of 16 guage MS sheet metal cubical/industrial indoor type and duty painted with 2 coats enamel paint with cost of material as follows. conveyance, all taxes, duties, labour charges and all other incidents etc; complete for finished item of work
Out-going cable of suitable size of Alluminium armoured cable of 3.50core of standard make from Panel Board to Starter and to Motor Cable Joints with jointing materials such as lugs glands, adhesive taps etc; to join the above cables a per I.E Rules Supply and errection of suitable suction and delivery DI/MS pipes and connections upto manfold including heavy duty Sluice Valves on suction side per stipulations of water supply mannual and I.S.Codes Supply,delivery,errection and commissioning of suitable capacity vaccum pump to operate ablve pumpsets including connecting or pumpsets with required G.I Pipes, Specials and fixing in concrete bed etc; Supply, laying and fixing of 40x6mm G.I flat patti double earthing for electrical protection for motor, pump and panel board efficiently earthing duly providing earth pits and filling with coal and salt and G.I pipe 1 1/2 x 6" long and bottom 2'x2' G.I.Plate welded as per I.E.Rules and Specifications with cost of materialss, conveyance, taxes,duties, labour charges and all other incidental charges and providing 1 1/2' x 1 1/2' earth pit chamber with brick masonary with top cover Supply and delivery of necessary suitable errection tools of reputed make mounted on polished teak wood board including cost of materials and all taxes and duties etc;
Ring Spanner 3/16 to 1" - 1No Double end spanner set 3/16" to 1" - 1 No Pipe Wrench 18" & 4" - 2Nos Screw drivers 6", 10" & 12" - 3 Nos Cutting Plier 12" - 1No 2 Kgs Hammer with Handle - 1 No Nose Plier - 1 No Flat and Half round smooth file - 2 Nos Adjustable Spanner 6" Column pipe Clamps - 2 pairs Line Shaft Clamps - 1 Pair Line rope and clamps double the weight of pump - 2 sets Gland thghtening Spanner - 1 No Spitter removing Spanner - 1 No Supply and delivery of necessary safety equipments as per IE Rules including cost of materials and all taxes and duties etc; complete Fire extiguisher 3Kg capacity - 2 Nos Rubber Mat 6" x 4" - 2Nos Fire Buckets with stand and three buckets - 1 No Rubber Hand Gloves - 1 Sets Danger Board Plates - 4 Nos First aid kit with chart - 1No Shock Treatment Chart - 1No Portable rechargeble torch light - 1 No
Supply and delivery of indigeneous make 500V insulation tested a portable type technometer and megger etc; Supply, delivery and erection of 5 tonnes capacity double girder gantry arrangements to move and lift the installations of the pump house one way with required MS ISMB of best quality 250 x 100 mm of standard make, including the required MS ISMC, MS angular iron, 5 tonne capacity travelling trolley and 5 tonne capacity chain pulley block with chains of suitable capacity for lifting and moving arrangements to length of 10.00 m rate is inclusive of the cost of materials, labour charges, site welding etc., All Civil Works Such as anchor Blocks ,Thrust Blocks, Platform for Pannel Board and Cable trench etc Complete as directed by the Field Engineer Testing and maintanance of the complete equipment covered and trial run for 30 days at 8 hours per day after completion of errection
Construction of electrician / operator/watchman quarters at HWW
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD.
Mechanical means up to 3 metres depth in ordinary soil
Manual Means up to 3 metres depth in ordinary soil
Providing river sand filling brought from approved quarry including cost and conveyance of all material and all labour charges such as filling in layers watering ramming etc complete as per ss and as directed by the departmental officer in chrges of work
Providing PCC 1:4:8 using 40 mm graded SS 5 HBG m/c metal and OPC coarse and fine aggregate confirming to IS 383 including cost and conveyance of all materials and labour charges, machine mixing , vibration,laying in position, curing etc., complete etc complete and all labour charges,and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work.
Supply and placing of the M25 design mix concrete corresponding to IS -456 using WEIGH BATCHER/MIXER using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including all operational ,incidental and labour charges such as weigh batching ,machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work (APSS NO 402) with minimum cement content as per IS Code from standard suppliers approved by the deparment including pumping , centering,shuttering,laying concrete ,vibrating,curing etc etc complete and all labour charges,and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work. as follows
column footings
Columns 1.50-0.15-0.15-0.20-0.25 =0.75 + basement 0.75m+superstructure 3.35m=4.85m
Plinth beam
Lintle beams Windows
Roof Beams
Roof slab 0.125m thick with 0.30m extension all sides
Sunshades 0.60m wide, 0.10m at fixed end and 0.05m at free end Windows
Loft slab 0.075m thick kitchen
Brick work in CM 1:6 mix using 2nd class bricks Cost including cost of all materials, conveyance charges of materials and all operational, incidental and labour charges for mixing mortar, laying, rendering smooth , curing,etc,, complete for finished item of worketc complete and all labour charges,and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work.
Ground floor
1st floor
Cement plastering using opc in cm(1:5) prop 12 mm Cost including cost of all materials, conveyance charges of materials and all operational, incidental and labour charges for mixing mortar, laying, rendering smooth , curing,etc,, complete for finished item of work out side & inside etc complete and all labour charges,and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work.
Ground floor
1st floor
Cement plastering using opc in cm(1:3) prop 12 mm Cost including cost of all materials, conveyance charges of materials and all operational, incidental and labour charges for mixing mortar, laying, rendering smooth , curing,etc,, complete for finished item of work for walls out side & inside etc complete and all labour charges,and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work.
Painting Walls with Snowcem or other equal and approved Water Proof Cement Paint 2 Coats (All Colours) over a base coat of aproved cement primer making 3 coats in total including cost of all materials, conveyance charges of materials and including all operational, incidental and labour charges etc,, complete for finished item of work as directed by the departmental authorities.
Supply delivary and fixing RCC Jollys including all labou cgRGES etc complete and all labour charges,and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work.
Supply and fixing Aluminium Anodized Doors - Single Shutter as per approved drawing with aluminium anodized sections of Jindal or approved equivalent make sections and outer frame top horizontals & both verticals of 2408 of size 101.6 x 44.75 of specified thickness Shutter frame top, bottom and verticals of 4504 of size 44.45 mm x 47.62 mm of specified thickness and Middle lock rail of 4621 of size 49.91 x 44.45 x 3 mm with plain clear float glass 5 mm thick fixed including supply and fixing aluminium handles of 100 mm for each shutter, floor springs/ hydraulic door closure assembly and all labour charges for fixing the fixtures with required no. of screws, bolts and nuts and including labour charges for fixing the frame in position, fixing shutter to frame etc. completed for finished item of work etc complete and all labour charges,and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work. AS FOLLOWS
Door -D - 1.20X2.10 m
doors D1 - 1.0X2.10m
Supply and fixing Aluminium Anodized Two/ Three Track Sliding Windows as per approved drawing with aluminium anodized sections of Series C Jindal or approved equivalent make sections and outer frame top horizontals & both verticals of 8774 of size 62 x 29.5 mm and bottom horizontal - two track frame of 8773 of size 62 x 29.5 mm, Shutter frame top, bottom and verticals of 8304 of size 50 mm x 20 mm and Weather interlocking frame of 8306 of size 50 x 20 with plain clear float glass 5 mm thick fixed including supply and fixing aluminium handles of 100 mm for each shutter, nylon rollers assembly and all labour charges for fixing the fixtures with required no. of screws, bolts and nuts and including labour charges for fixing the frame in position, fixing shutter to frame etc. completed for finished item of work etc complete and all labour charges,and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work.
Providing and fixing factory made polyvinyl chloride (PVC) Door Frame of the size 50 x 47mm with a wall thickness of 5mm, made out of extruded 10 mm rigid PVC foam sheet,mitre cut at two corners and joined with 2nos. of 150mm long brackets of 15x15mm M.S. square tube. The two vertical door profiles are to be reinforced with 19x19mm M.S. Square tube of 19 gauge. The door frame shall be fixed to the wall using 65/100mm long M.S. Screws through the frame by using PVC fasteners. A minimum of 4nos. of screws to be provided for each vertical member & minimum 2nos. for horizontal member etc. complete as per manufacturers specification and direction of Engineer-in- Charge for finished item of work
Providing and fixing 30mm thick Solid panel PVC door shutter consisting of frame made out of M.S. tubes of 19 gauge thickness and size of 19mm x 19mm for stiles, & 15mm x 15mm for top & bottom rails. M.S. frame shall have a coat of steel primers of approved make and manufacture. M.S. frame shall be covered with 5mm thick heat moulded PVC „C‟ channel of size 30 x 50mm forming stiles, and 5mm thick, 75mm wide PVC sheets for top rail, lock rail &bottom rail on either side, and 10mm (5mm x 2) thick, 20mm wide cross PVC sheet as gap insert for top rail & bottom rail. Panelling of 5mm thick PVC sheet to be fitted in the M.S. frame welded / sealed to the stiles & rails with 30mm wide x 5mm thick PVC sheet beading on either side, and joined together with solvent cement adhesive etc. An additional 5mm thick PVC strip of 20mm width is to be stuck on the interior side of the „C‟ Channel using PVC solvent adhesive.Complete as per direction of Engineer-in-charge, manufacturer‟s specification & drawing for finished item of work .
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying etc., complete for finished item of work in all floors.( APSS No.126) etc complete and all labour charges,and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work.
Cement plastering using opc in cm(1:3) prop 20 mm thick including cost of all materials, conveyance charges of materials and all operational, incidental and labour charges for mixing mortar, laying, rendering smooth , curing,etc,, complete for finished item of work for floorring
Manufacture,supply,delivery of MS grill gates,window ornamental safety grill ,made with MS flats,MS angles,MS squares etc including welding,finishing,etc complete etc complete and all labour charges,and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work.
Painting two coats with synthetic enamel paint on new iron work over a base coat of red-oxide making 3 coats in total including cost of all materials, conveyance charges of materials and including all operational, incidental and labour charges etc,, complete for finished item of work as directed by the departmental authorities.(APDSS No:1201)
Supply, delivery and fixing of 110mm dia single socket PVC pipes 4 kg/sqcm prince/Sudhakar or any ISI brand for rain water pipes with clamps
Supply and fixing of 25 mm dia 2.20 mm thick PVC pipe concealed in roof slab with all required accessories including masonary work all labour chages
Supply and fixing of 20 mm dia 2.10 mm thick PVC pipe concealed in walls with all required accessories including masonary work for light , fan and plug point with metal deep box including all labour chages
Wiring with 2 runs 14/0.3 mm. (1.0. sq.mm) Fire retardant PVC insulated Flexible copper cable in existing pipe with 6A siwtch, ceiling rose and 3 mm thick hyla sheet covering to switch control box including all labour charges etc,., complet for light, bell , fan and exhaust fan points in non - residential building
Wiring with 2 runs 14/0.3 mm. (1.0. sq.mm) Fire retardant PVC insulated Flexible copper cable in existing pipe with 6A modular siwtch control and 3/2 pin sockets fixing on board including all labour charges
supply and run of 2 of 36/0.3 mm. (1.5. sq.mm) Fire retardant PVC insulated Flexible copper cable in existing pipe for mains including all labour charges
supply and run of 1 of 14/0.3 mm. (1.0. sq.mm) Fire retardant PVC insulated Flexible copper cable in existing pipe for earth continuity including all labour charges etc.
supply and run of 2 of 6 sq.mm (7/18) WPSC alluminium cable along with No.10 SWG G.I barer wire through PVC cleats with all accessories including all labour charges etc.,
Providing independent earthing by excavating a trench to a depth of 2.10m in all soils, as per size specied in data ,using 40 mm dia B class GI pipe 2.50m long with necessary accessories with hume pipe ring duly providing staggered holes including filling with equal proportion of salt and charcoal in layers and all labour charges etc complete
Supply and fixing SPN Distribution board with IP-20 protection suitable for single phase Earth Leakage Circute Braker (ELCB) / Residual Current Circute Braker (RCCB) / Double Pole (DP) Isolator as incomer and 10kA SP MCBs as out going including internal connections and labour charges for surface / flush mounting etc., complete
Supply of 48" (1200mm) Sweep 5 star rated Ceiling Fan , with double ball bearings, air delivery more than 200 cubic meter/min but without Regulator.Makes : Crompton HS Plus / Havells ES Neo/Orient Energy Star/ Halonix(Zephyr)/Polycab(Synergy Star)
Supply of stepped type Electronic Regulator of Makes: GM G Home / Gold Medal Olive / Million Zoom / Great white Omega/Koncept/Vimal opel/ Anchor/Vihan/CPL
Supply and transportation of 20W, 2000 lumens, T8,1200mm length LED retro tube light,wide operating voltage with double side connection, PF≥0.9,Surge protection: > 2KV, THD<15%, with inbuilt driver and frosted cover CCT: 3000K - 6500K as desired by the department and as per IS specifications, minimum CRI≥80,.etc complete with 5 years warranty.LUMINAIRE MAKE: Phillips / OSRAM / GE / Crompton /VIN / Bajaj / Havells / Halonix / HPL. LED MAKE : PHILIPS LUMILEDS / CREE / NICHIA /OSRAM / SAMSUNG / LG LEDs.. Unit each
Labour charges for Fixing of Ceiling fan and regulator including transportation and giving connections with 23 / 0060 twin core twisted / flat heavy Copper wire etc., complete
Labour charges Fixing of 40W tube light luminaire on wall / Ceiling with 23 / 0060 twin core twisted / flat heavy Copper wire / TW round blocks with all accessories including giving connections and all labour charges etc., complete.
Sanitary and water supply
Providing & Placing on Terrace (at all floor levels) polyethylene water storage tank with Double layer approved brand & manufacture with cover and suitable locking arrangement & making necessary holes for inlet & outlets and over flow pipes but without fittings & base support for tanks
Supplying and fixing 580mm x 440mm long Orissa pan white glazed Water Closet 1st quality ISI marked confirming to IS:2556-Part-3-1981 with "P" or "S" trap, ISI marked and providing masonry seat, CC squatting plate and 10 litres capacity single flush PVC low level cistern with internal components fixed on 2 Nos. of teak wood blocks of size 76.20mm x 101.60mm using required size of nails, screws as approved by Engineer-in-charge, 15 mm nominal size CP finish brass angled stop valve screw type with internal /external threaded conforming to IS 8931, 12.70mm PVC connection with brass union nuts CP coated , 31.75mm brass plumber union, P trap or S trap of Indian W.C. shall be encased on CC (1:2:4) 150mm alround well above the joint to stop leakage at the joint etc., complete including cost and conveyance of all materials to site, cost of CC bed, labour charges and seigniorage charges, overheads & contractors profit etc., complete for finished item of work
Supplying and fixing Indian make Flat Back Wash Hand Basin 1st quality conforming to IS:2556-Part-4:1972 with waste fittings like rubber plug, chain,32 mm nominal size C.P. Fitting with parallel pipe thread conforming to IS:2963-1979 and fitted with 15 mm nominal bore Chromium Plated Pillar Tap of 1st quality Indian make 400 grams Seiko/ Senior/ Nice/ Esso or equivalent complete with standard CI brackets including wooden block: 550 x 400 mm - Single C.P. Pillar cock ,1 No.12.70mm PVC connection with brass union nuts CP coated , angle stop cock 12.70mm dia. first quality Indian make heavy duty, 31.75mm brass plumber union, 31.75mm dia PVC flexible waste pipe of 914.4mm length of Ist quality including cost and conveyance of all materials to site, labour charges , overheads & contractors profit for finished item of work
Supply of 110 mm dia 3 m single Socket PVC/SWR pipe - 6 Kg/sq.cm - Prince/Sudhakar/Kisan/Supreme or any ISI Brand.
Supply of 110 mm dia - Plain Bend 87.5 Degree - UPVC/SWR Pipe fittings (Prince/Sudhakar/Kisan/Supreme or any ISI Brand)
Supply of 110 mm dia - Coupler - UPVC/SWR Pipe fittings (Prince/Sudhakar/Kisan/Supreme or any ISI Brand
Labour charges for laying, fixing and commissioning the PVC pipes including couplers/ bends/ tees etc any diameter including fixing necessary fittings like bends, plugs, couplers, junctions, tees, etc with solvent jointing as per standard practice
Constructing 457.2 mm x 457.2 mm (1'6"x1'6") brick in CM 1:6 prop. Masonry. Inspection chamber up to 914.4 mm (3'0") and fitted with light weight 457.2 mm x 457.2 mm (1'6"x1'6") C.I frame and cover of 20 Kg
S& F GI pipe Medium Grade properties & weight as per IS 1239 ISI mark with GI fittings including the cost of pipe & its fittings & labour charges complete
25 mm dia nominal bore -from tank to jn for of individual lines
20 mm dia nominal bore -from jn for of individual lines to toilets & Kitchen
15 mm dia nominal bore -for internal
S&F of GI &GM fittings
GM Ball valve with SS Ball and SS Spindle as per IS - Class - I, Indian make heavy type - 25 mm NB Size
GM Ball valve with SS Ball and SS Spindle as per IS - Class - I, Indian make heavy type - 20 mm NB Size
GM Ball valve with SS Ball and SS Spindle as per IS - Class - I, Indian make heavy type - 15 mm NB Size
S&F 12.7 mm N.P bib tap Indian make heavy dutys Seiko/ Senior/ Nice or equivalent
S& F GI union Ist Quality
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD. Note : Classifications of Earth Work Specification are as per 302.2.1(a) of MORD and 301.2.1 of MORT&H--ordinary soil--manual means upto 3m depth by manual means upto 3.00m depth
Filling with sand in foundations /pipe line trenches as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH
Providing PCC 1:4:8 using 40 mm graded SS 5 HBG m/c metal and OPC coarse and fine aggregate confirming to IS 383 including cost and conveyance of all materials and labour charges, machine mixing , vibration,laying in position, curing etc., complete
Brick work in CM 1:5 mix using 2nd class bricks including cost of all materials, conveyance charges of materials and all operational, incidental and labour charges for mixing mortar, laying, rendering smooth , curing,etc,, complete for finished item of work
Cement plastering using opc in cm(1:3) prop 20 mm thick including cost of all materials, conveyance charges of materials and all operational, incidental and labour charges for mixing mortar, laying, rendering smooth , curing,etc,, complete for finished item of workas per SS out side & inside
RCC M-25 Nominal mix (cement,fine aggregate,coarse aggregate) corresponding to Table -9 of IS -456 using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including all operational ,incidental and labour charges such as machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work,but including centering,shuttering unit 1.00cum for culvert slabs RBR-SBST-5 A
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying including sales and other taxes on all materials etc., complete for finished item of work in all floors.( APSS No.126)
Errection of 250 KVA Transformer at at Head Water Works Mummidivaram with Transformer yard 15.00x12.00m
Supply and erection of 7.50m long double pole structure fabricated with 150x75mm RS Joists,100x50mm MS channels, iron cross armstor fuse set and Lighting arrestrors etc.,including one coat of red oxide primer and two coats of bright Supply
Supply and fixing of 11 KV ,400 A 3 phase central post rotating double break type AB switch(isolator) as per IS 9921) without earth blade, gang operated, Horizontal type, operating mechanism with GI spring loaded reverse loop type fixed contact, solid HD electrolytic copper tubular moving contact with silver/Nickel plated at end points,9 Nos post insulators of 12 KV (IS 2594 and IS 5350) ,Hot Dip galvanizing hardware, GI pipe, Nuts and bolts etc., complete., ELEC 6.5.14/MAT 04113
Supply and fixing of 100 A 11 KV Horn Gap fuse set as per IS 9385 on existing DP structure with 6 no of 24 KV /22 KV post Insulators (IS 5350, Hot dipped Hardware, fuse wire of required size etc., complete ELEC 6.5.12/MAT 04111
Supply and fixing of distribution type lightning arrester 11 KV 5 kA as per IS 3070 with mounting base on the existing DP structure ELEC 6.5.11/MAT 04110
Supply and erection of 11KV Strain disc. Insulators with GI pins and top clamps
Supply and fixing of 11 KV pin Insulator (IS 731/1971) with minimum creepage distance of 300 mm on existing cross arm including all accessories like Hot dip GI spindle and nuts etc., ELEC 6.5.8/MAT 04105
Providing jumper connections with I/O' SWG HDBC wire between the 11 KV equipment on the outdoor structures
Supply and erection of GI stay set of dia 16mm,1.8 mtr long stay rod and anchor plate 380mmx380mmx6.4mm. including stay clamps, turn buckle and GI stay wire tight end through strain insulator including excavation of pit and cc work etc., complete ELEC 6.5.3/MAT 04097
Providing efficient earthing arrangement forthe DP structure lighting arresters and the HV equipment. Transformer body and neutral etc., with 25 x 3 mm copper flats and connecting them to the Earth Electrodes fabricated and buried accroding to standard specifications and as per the details given below:
A) Earth Electrodes
B) 20mm x 3mm Copper Flat(0.529Kgs/1Mtr) MAT 04146
C) Epoxy insulators
D) No.'8' SWG Copper wire. MAT 04141
Supply and Transportation of ISI marked copper wound Transformers 11/0.433 KV, Three Phase, 50 Hz, DYN 11, ONAN type , Standard accessories, winding temperature rise of 45°C/40°C first fill oil, having permissible total loss values not exceeding 7.5%of the maximum total loss values for 11 KV as per Energy Efficiency Level - 2 at basic Insulation level conforming to ISS 2026 (Part- I to Part - II), latest ammended and IS 1180 Part-I : 2014 described as above with Cable box on HV side and Bus duct on LV Side , ON load Tap changer(OLTC)+10% to -10%, with RTCC etc., with initial filling of oil as per IS 335-1993 complete and as per the following continuous rating. Makes : As per list of recommended brands as category I. MAT-04044c 250KVA
Supply and laying of 400Sq mm X 3.5 core XLPE insulated, 1100V grade armoured aluminum cable as per specification confirming to IS:7098 (Part- I)./1554-I Makes: Makes: Torent / Universal / Unicab / Havells / Finecab/ KEI / Gloster/ Polycab /RR Kabel/ Fortune Arrt ELEC-4.1.1q MAT-03431
Supply Installation Testing and commissioning of free-standing floor mounted dust and vermin proof compartmentalized cubical panel made out of CRCA sheet, required hardware, cleaning with 7 tank process duly painted by two coats of zinc/red oxide primer followed by Powder coated / epoxy / PU painted with phosphatisation in grey or required shade after rinsing. The panel having PU/ Neoprene rubber gasket of not less than 3mm thickness, separate detachable, gland plate M.S. base channel, hinged door with locking arrangement for equipment/switchgear. The thickness of sheet shall not be less than 1.6mm up to 600mm length/ width of any compartment and be 2.0mm above 600mm. The load bearing structure shall be of 2.0mm thick sheet supported by base M.S. channel if required. Side walls and cable alley compartments having bolted type doors with detachable extension type structure (only outer area on all sides shall be measured and panel to be fabricated from CPRI approved fabricator) MAT 03976
Supply and fixing of Electrolytic grade copper bus bar bus bar by means of SMC / DMC type insulator, high tensile nuts and bolts spring washers in existing panel including bending , cutting in required shape and size and colour coding with heat shrinkable PVC sleeves MAT 03978
a) 630A TPN SDFU for main switch Makes:LauritzKnudsen(FormerlyL&T)/Schneider/ C&S/ ABB / SIEMENS MAT 02885
b) 630A 4pole change over switch Makes:Socomec/LauritzKnudsen(FormerlyL&T)/HPL / Havells/ C&SMAT MAT 02898
c) Supply and fixing of (0-500) V range Voltmeter on existing panel, making connection by PVC insulated copper conductor with PVC sleeves /channel etc. as required Digital type Make: Conzerve/Elmeasure/Meco/HPL/L&T/socomec MAT 03980
e). Supply and fixing of CT operated direct reading type Ammeter on existing panel, making connection by PVC insulated copper conductor with PVC sleeves / channel etc. as required. Digital type Below 500 A Make: Conzerve/Elmeasure/Meco/HPL/L&T/Schneider/AE/Socomec MAT 03983
g).3RYB Phase indication lamps with leds
h).Supply and Fixing of Current Transformer, with all necessary support in existing panel including connection etc. as required from 200 / 5 to 400/5 Ratio, 10 VA, class 1 accuracy: Make: Kappa/L&T/Seimens/C&S/Schneider MAT 03986
630A TPN SDFU forCW pump house motors Makes:LauritzKnudsen(FormerlyL&T)/Schneider/ C&S/ ABB / SIEMENS MAT 02885
630A TPN SDFU for compressor/mechanical equipments Makes:LauritzKnudsen(FormerlyL&T)/Schneider/ C&S/ ABB / SIEMENS MAT 02885
630A TPN SDFU for low lift sump Raw water motors Makes:LauritzKnudsen(FormerlyL&T)/Schneider/ C&S/ ABB / SIEMENS MAT 02885
630A TPN SDFU for Space Makes:LauritzKnudsen(FormerlyL&T)/Schneider/ C&S/ ABB / SIEMENS MAT 02885
630A TPN SDFU for lighting section Makes:LauritzKnudsen(FormerlyL&T)/Schneider/ C&S/ ABB / SIEMENS MAT 02885
630A 4pole change over switch for lighting section Makes:Socomec/LauritzKnudsen(FormerlyL&T)/HPL / Havells/ C&SMAT MAT 02898
.KWH digital meter fro lighting section
Supply of 32 Amp………ISI marked TPN Switch Disconnector Fuse Unit, Cubical type without fuses as per IS: 13947/IEC 60947-3 Makes: As per list of recommended brands as category I.MAT-02879
Supply of 6A to 35 A……ISI marked HRC Fuse Links as per IS 13703-Part 2/IEC 60269- Part 2 Makes: As per list of recommended brands as category I MAT-02938
Standard duty Single phase 250 V / Three phase 440 V, 50 Hz capacitor (Bank) MAT-03998
1000KV LT/Transformer Errection.testing Commensing and Supply of drawing layout plans of installed transformer in tracing cloth and duly get approved from electrical inspector APEPDCL and leaflets for various equipments and opearation manuals etc., complete.
Supply and Laying of 3C X50 Sq mm XLPE insulated IS:7098/II/85 H.T. cable for working voltage 11 KV Earthed with Stranded Compacted Circular Aluminium Conductor Screened with Extruded Semi-conducting compound, XLPE Insulated Screened with extruded semi-conducting compound in combination with Copper Tape, cores laid up, inner sheath of Thermoplastic tape, galvanized flat steel strip armoured and overall Extruded PVC Type ST- 2 Outer Sheathed cable etc., complete. Make: Torrent / Universal / Unicab / Havells / KEI/Polycab/Gloster/RR Kabel/RPG MAT 03457b
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH Note : Classifications of Earth Work Specification are as per 302.2.1(a) of MORD and 301.2.1 of MORT&H--ordinary soil--manual means upto 3m depth for foundations of buildings in restricted places By manual means
Providing river sand filling brought from approved quarry including cost and conveyance of all material and all labour charges such as filling in layers watering ramming etc complete as per ss
Providing PCC 1:4:8 using 40 mm graded SS 5 HBG m/c metal and OPC coarse and fine aggregate confirming to IS 383 including cost and conveyance of all materials and labour charges, machine mixing , vibration,laying in position, curing etc., complete
Supply and placing of the design mix concrete corresponding to IS -456 using WEIGH BATCHER/MIXER using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including all operational ,incidental and labour charges such as weigh batching ,machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work (APSS NO 402) with minimum cement content as per IS Code from standard suppliers approved by the deparment including pumping , centering,shuttering,laying concrete, vibrating,curing etc M25 design mix concrete
column footings
Columns 1.20-0.10-0.10-0.30+1.80
Plinth beam 2(15+12)=54-gate3.00=51.00
Painting Walls with Snowcem or other equal and approved Water Proof Cement Paint 2 Coats (All Colours) over a base coat of aproved cement primer making 3 coats in total including cost of all materials, conveyance charges of materials and including all operational, incidental and labour charges etc,, complete for finished item of work as directed by the departmental authorities.
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying etc., complete for finished item of work in all floors.( APSS No.126)
Supplying and fixing galvanised steel barbed wire (IS : 278-1962 Type I) weighing 9.38 Kg per 100 metres (min.), Straining and fixing to any type of standard, rails, straining bolts, including securing with and provision of galvanised mild steel wire, stapples or steel pins, etc., as directed (Posts and struts of wood, concrete, steel, etc.) and straining bolts shall be paid for separately).
Manufacture,supply,delivery of MS grill gates,window ornamental safety grill ,made with MS flats,MS angles,MS squares etc including welding, finishing, t etc complete
Painting two coats with synthetic enamel paint on new iron work over a base coat of red-oxide making 3 coats in total including cost of all materials, conveyance charges of materials and including all operational, incidental and labour charges etc,, complete for finished item of work as directed by the departmental authorities.(APDSS No:1201)
supply and filling the transformer yard with 40mm HBG metal including cost of all materials, conveyance charges of materials and all operational, incidental and labour charges etc., complete for finished item of work
Providing site filling to Head water works
Granular sub-base/base/surface course with local materials (Table 400.13) by mix in place method normal Construction of granular sub-base by providing local material spreading in uniform layers with motor grader on prepared surface, mixing by mix in place method with rotavator at once and compacting with smooth wheel roller to achieve the desired density complete as per Clause 401.4 as per Technical Specification Clause 408 MORD. with Gravel
Providing service road to Head water works
Granular sub-base/base/surface course with local materials (Table 400.13) by mix in place method normal Construction of granular sub-base by providing local material spreading in uniform layers with motor grader on prepared surface, mixing by mix in place method with rotavator at once and compacting with smooth wheel roller to achieve the desired density complete as per Clause 401.4 as per Technical Specification Clause 408 MORD. using Gravel
Construction of granular sub-base by providing well graded material / Close graded material, spreading in uniform layers with motor grader on prepared surface, mixing by mix in place method with rotavator at OMC, and compacting with smooth wheel roller 80-100 kN / Vibratory Roller to achieve the desired density, complete as per Technical Specification Clause 401 MORD / MORTH For Grading II Material (CBR Value minimum 25)
Providing, laying, spreading and compacting graded stone aggregate to wet mix macadam specification including premixing the material with water at OMC in mechanical mixer (Pug Mill), carriage of mixed material by tipper to site, laying in uniform layers in sub-base/base course on a well prepared sub-base and compacting with smooth wheel roller of 80 to 100kN / Vibratory Roller 80-100 kN weight to achieve the desired density including lighting, barricading and maintenance of diversion, etc as per Tables 400.11 & 400.12 and Technical Specification Clause 406 MORD / MORTH.
Construction of un-reinforced, dowel jointed at expansion and construction joint only, plain cement concrete pavement, thickness as per design, over a prepared sub base, with 43 grade cement or any other type as per Clause 1501.2.2 M30 (Grade), coarse and fine aggregates conforming to IS : 383, maximum in a concrete mixer of not less than 0.2 cum capacity and appropeiate weigh batcher using approved mix design, laid in approved fixed side formwork (steel channel, laying and fixing of 125 mictron thick polythene film, wedges, steel plates including levelling the formwork as per drawing), spreading the concrete with sholvels, rakes, compacted using needle, scareed and plate vibrators and finished in continuous operation including provision of contraction and expansion, construction joints, applying debonding strips, primer, sealant, dowel bars, near approaches to bridge / culvert and construction joints, admixtures as approved, curing of concrete slabs for 14- days, curing compound (where specified) and water finishing to lines and grade as per drawing and Technical Specification Clause 1501 MORD.
Construction of 600 mm size CC disposal drain from proposed WTP
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH
Mechanical means up to 3 meters depth
Manual means up to 3 meters depth
Filling in foundation trenches as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH for pipe line trench RBR-FNDN-2(1)
Providing PCC 1:4:8 using 40 mm graded SS 5 HBG m/c metal and OPC coarse and fine aggregate confirming to IS 383 including cost and conveyance of all materials and labour charges, machine mixing , vibration,laying in position, curing etc., complete
PCC M-10 Nominal mix (cement,fine aggregate,coarse aggregate) corresponding to Table -9 of IS -456 using 20 mm size graded machine crushed hard granite metal (coarse agggregate) from approved quarry including cost and conveyance of all materials like cement,fine aggregate(sand),coarse aggregate ,water etc to site and including all operational ,incidental and labour charges such as machine mixing ,laying concrete ,curing etc complete but excluding cost of steel and its fabrication charges for finished item of work,but including centering,shuttering unit 1.00cum for CC drains RBR-SBST-5 A
600X600 mm CC drain bottom layer
walls (0.20+0.30)/2=0.25
Construction of 600 KL ELSR with 18m staging at Ayyavari cheruvu( siyalayam) zone -I
Construction of ELSR With the following specification 600 kl capacity with a staging of 18 m, with Seismic analysis.
All concrete components shall be designed with M30 Design Mix proportion. 4) The foundations shall be designed for Annular Raft Footings. The above rates are applicable for Elevated Level Services Reservoirs / OHSRs for SBC of 15 T/Sqm. c) For SBC below 10T/Sqm , solid raft shall be provided d) For SBC value of less than 5 T/Sqm, soil improvement shall be adopted, for which additional payment shall be made as per field condition. a) Rate inclusive of three coats of epoxy paint Food Grade of best quality to inner surface of the Reservoir including roof. b)The rate inclusive of 2 coats of weather proof emulsion painting for external surfaces, lettering, all required fixtures, Pipes, Pipe specials, valves of DI material, Valve chambers etc., for pipe connections including cost of pipes, specials and valves as per departmental designs and drawings. 11) The above rates adopted for a wind pressure up to "250 kg/Sqm". The ELSR/OHSR shall be designed with minimum of two rows of columns for capacities above 500 KL & up to 1000KL. The ELSR/OHSR shall be designed with minimum of three rows of columns for capacities above 1000KL. 14. The shaft type staging with slip form can also be provided with proper approval from competent authority without any additional cost.
15) The basic rate is inclusive of following Fixtures i) Pipe connections & Specials with D.I materials (a) All pipe connections for Inlet, Out let, Over Flow, Scour pipes shall be provided with D/F DI material. (b) The Valves for above pipe connections also shall be of DI material of PN 16 duty confirming to the specification of SoR item No.28 (c) All specials such as Bends, Tees, Reducers, Duck foot Bends, Bell mouths etc,. Shall be of DI material. II) The sizes of the verticals for ELSR/OHSR shall be: a) For 500 KL to 750 Kl ELSRs Inlet Pipe - 300mm dia. Out let Pipe - 350mm dia. DI valves – 2 No’s Over Flow pipe - 350m dia. Scour Pipe - 200mm dia. b) For 800 KL to 1500 Kl ELSRs Inlet Pipe - 400mm dia. Out let Pipe - 450mm dia. DI valves – 2 No’s Over Flow pipe - 450m dia. Scour Pipe - 200mm dia. c) For above 1500 KL to 2500 Kl ELSRs Inlet Pipe - 400mm dia. Out let Pipe - 500mm dia. DI valves – 2 No’s Over Flow pipe - 500m dia. Scour Pipe - 200mm dia.
Note: Any deviation from the above sizes as per design, shall be paid or recovered. (iii) Manhole Frames & Covers a) All man hole Frames & Covers shall be made of CI/DI materials with min. size of 0.60mX 0.60m - For Roof & Valve Chambers. iv) CI/D.I Double Swan neck ventilators (min. of 150mm dia.) shall be provided in top dome and slab with mosquito/fly proof nets - 4Nos. v) RCC Finial ventilator with fly/bird protection with GI mesh - 1 No. vi) RCC precast ladders of 0.60 m width - 2 Nos. vii) RCC dog legged stair case of 1.00 m flight width and 1.20 m landing width R.C.C hand railing of 1.0 m height – 1 No viii) The staircase shall be enclosed with brick masonry walls on three sides and collapsible MS gate on front side up to 1st brace level, to prevent unauthorized entry. ix) Construction of R.C.C valve chambers as per Standard Drawings with RCC cover slab fixed with CI/DI manhole Frame & Cover with lock and Key arrangement. The Mix shall not be less than VRCC M 20 grade with 150mm thick side walls, 150mm thick top slab, 150mm thick base slab over base course of 100mm thick (1:4:8) prop. x) Balcony of 1.00 m width at floor slab level / middle ring beam level by using Stainless Steel pipe of grade 304 hand railing up to 1.20 m height, with top railing of 40mm dia. pipe & middle railing of 25mm dia. and verticals with 40mm dia. at an interval not more than of 1.00m c/c.
xi) Water Level Indicator of reputed make – Digital type (1 No) and Conventional type (1 No) xii) Lightening Arrestor with all its accessories complete including earthing, with relevant IS Codes - 1 No. xiii) Compound wall: Construction of compound wall including ornamental M.S.Gate of size 3.0 X 2.40m is included in the basic rate of ELSRs. Length of compound wall hall is minimum of 150m. Min. height of the compound wall shall be 1.80m above plinth and thickness 230mm in brick masonry in CM (1:6).The compound wall shall be constructed including earth work excavation in all types of soils for plinth beam of 230mm X 300mm and 0.75X0.75X1.20m size for column footing portions. The footings shall be of 0.75X0.75X0.25m in VRCC M20 grade and constructed over a C.C (1:4:8) prop bed of 100mm thick. The columns shall be of 230X230 mm in size with VRCC M20 grade at 3.00m c/c spacing, having depth of 1.20m below ground level and height of 2.00m above GL. The plinth beam of size of 230X300 mm shall be constructed in VRCC M20 grade at Ground level, over a bed of CC(1:4:8)-100mmthick. 450X450mm size columns in M20 grade shall be constructed for gate pillars. All the materials shall be followed as per the standards. Tie beam shall be provided above the brick work with 230X200mm size, fixed with MS angular of 25mm X 25mm X 4mm in "Y" shape to height of 0.60m, with embedded length of 150mm in concrete. The barbed wire fencing with 3 ply of 18 gauges shall be stretched in 4 rows (2x2). Plastering shall be done with 16mm thick in two coats i.e., base coat 12mm thick in CM(1:6)prop and 4mm thick 2nd coat CM(1:4) prop on both sides of brick work.
Snowcem paint in two coats shall be provided for both sides of wall. The M.S ornamental gate as per the approved drawings shall be provided with minimum of 3.60mts width and 2.40mts height with enamel paint. Yard lighting shall be arranged on four corners of compound wall. If the length of the wall is increased/ decreased Note:-For every 1m increase/decrease in length of compound wall the increase/decrease in basic rates of ELSRs of the capacities from 500KL to 2500KL shall be as follows.: i)500 KL : 0.086% ii)1000 KL : 0.047% iii)1500 KL : 0.034% iv)2000 KL : 0.026% v)2500 KL : 0.022 % For intermediate capacities, interpolated percentages shall be adopted. xiv) Staff Quarter shall be constructed for a minimum plinth area of 40 Sqm with the following specification: RCC framed structure with concrete grade not less than M20 design mix at the locations specified by the department at the time of execution with veranda, hall, bed room, kitchen and bath &W/C with floor area of 40.00sqmts excluding balconies and staircases.
MS hollow door frame with cold rolled processed steel sheet 1.25mm thick bright CRCA conforming to IS 4351/76, Flush door shutters with solid bond wood bond board doors shall be provided. N.C.L. Windows centre fixed both sides open able shutter window 1.35 X 1.35mts outer frame section 48 x50mm shutter frame section with a size of 48 X20 mm mullion section of size 48 X 50mm fixed beading section of 12 X 12 mm shall be provided. Flooring with polished Kadapa stone shall be provided. Walls shall be provided with snowcem paint in two coats over primary coat. Electrical and water supply arrangement shall be provided as directed by dept officer. Water Storage tank made with plastic/polymer material of reputed make with necessary out let and inlet connection pipes shall provided. Septic tank for 5 users shall be provided.
Construction of 500 KL ELSR with 18m staging at Krapu Chintalapudi zone -II A
Construction of ELSR With the following specification 500 kl capacity with a staging of 18 m, with Seismic analysis.
All concrete components shall be designed with M30 Design Mix proportion. 4) The foundations shall be designed for Annular Raft Footings. The above rates are applicable for Elevated Level Services Reservoirs / OHSRs for SBC of 15 T/Sqm. c) For SBC below 10T/Sqm , solid raft shall be provided d) For SBC value of less than 5 T/Sqm, soil improvement shall be adopted, for which additional payment shall be made as per field condition. a) Rate inclusive of three coats of epoxy paint Food Grade of best quality to inner surface of the Reservoir including roof. b)The rate inclusive of 2 coats of weather proof emulsion painting for external surfaces, lettering, all required fixtures, Pipes, Pipe specials, valves of DI material, Valve chambers etc., for pipe connections including cost of pipes, specials and valves as per departmental designs and drawings. 11) The above rates adopted for a wind pressure up to "250 kg/Sqm". The ELSR/OHSR shall be designed with minimum of two rows of columns for capacities above 500 KL & up to 1000KL. The ELSR/OHSR shall be designed with minimum of three rows of columns for capacities above 1000KL. 14. The shaft type staging with slip form can also be provided with proper approval from competent authority without any additional cost.
15) The basic rate is inclusive of following Fixtures i) Pipe connections & Specials with D.I materials (a) All pipe connections for Inlet, Out let, Over Flow, Scour pipes shall be provided with D/F DI material. (b) The Valves for above pipe connections also shall be of DI material of PN 16 duty confirming to the specification of SoR item No.28 (c) All specials such as Bends, Tees, Reducers, Duck foot Bends, Bell mouths etc,. Shall be of DI material. II) The sizes of the verticals for ELSR/OHSR shall be: a) For 500 KL to 750 Kl ELSRs Inlet Pipe - 300mm dia. Out let Pipe - 350mm dia. DI valves – 2 No’s Over Flow pipe - 350m dia. Scour Pipe - 200mm dia. b) For 800 KL to 1500 Kl ELSRs Inlet Pipe - 400mm dia. Out let Pipe - 450mm dia. DI valves – 2 No’s Over Flow pipe - 450m dia. Scour Pipe - 200mm dia. c) For above 1500 KL to 2500 Kl ELSRs Inlet Pipe - 400mm dia. Out let Pipe - 500mm dia. DI valves – 2 No’s Over Flow pipe - 500m dia. Scour Pipe - 200mm dia.
Note: Any deviation from the above sizes as per design, shall be paid or recovered. (iii) Manhole Frames & Covers a) All man hole Frames & Covers shall be made of CI/DI materials with min. size of 0.60mX 0.60m - For Roof & Valve Chambers. iv) CI/D.I Double Swan neck ventilators (min. of 150mm dia.) shall be provided in top dome and slab with mosquito/fly proof nets - 4Nos. v) RCC Finial ventilator with fly/bird protection with GI mesh - 1 No. vi) RCC precast ladders of 0.60 m width - 2 Nos. vii) RCC dog legged stair case of 1.00 m flight width and 1.20 m landing width R.C.C hand railing of 1.0 m height – 1 No viii) The staircase shall be enclosed with brick masonry walls on three sides and collapsible MS gate on front side up to 1st brace level, to prevent unauthorized entry. ix) Construction of R.C.C valve chambers as per Standard Drawings with RCC cover slab fixed with CI/DI manhole Frame & Cover with lock and Key arrangement. The Mix shall not be less than VRCC M 20 grade with 150mm thick side walls, 150mm thick top slab, 150mm thick base slab over base course of 100mm thick (1:4:8) prop. x) Balcony of 1.00 m width at floor slab level / middle ring beam level by using Stainless Steel pipe of grade 304 hand railing up to 1.20 m height, with top railing of 40mm dia. pipe & middle railing of 25mm dia. and verticals with 40mm dia. at an interval not more than of 1.00m c/c.
xi) Water Level Indicator of reputed make – Digital type (1 No) and Conventional type (1 No) xii) Lightening Arrestor with all its accessories complete including earthing, with relevant IS Codes - 1 No. xiii) Compound wall: Construction of compound wall including ornamental M.S.Gate of size 3.0 X 2.40m is included in the basic rate of ELSRs. Length of compound wall hall is minimum of 150m. Min. height of the compound wall shall be 1.80m above plinth and thickness 230mm in brick masonry in CM (1:6).The compound wall shall be constructed including earth work excavation in all types of soils for plinth beam of 230mm X 300mm and 0.75X0.75X1.20m size for column footing portions. The footings shall be of 0.75X0.75X0.25m in VRCC M20 grade and constructed over a C.C (1:4:8) prop bed of 100mm thick. The columns shall be of 230X230 mm in size with VRCC M20 grade at 3.00m c/c spacing, having depth of 1.20m below ground level and height of 2.00m above GL. The plinth beam of size of 230X300 mm shall be constructed in VRCC M20 grade at Ground level, over a bed of CC(1:4:8)-100mmthick. 450X450mm size columns in M20 grade shall be constructed for gate pillars. All the materials shall be followed as per the standards. Tie beam shall be provided above the brick work with 230X200mm size, fixed with MS angular of 25mm X 25mm X 4mm in "Y" shape to height of 0.60m, with embedded length of 150mm in concrete. The barbed wire fencing with 3 ply of 18 gauges shall be stretched in 4 rows (2x2). Plastering shall be done with 16mm thick in two coats i.e., base coat 12mm thick in CM(1:6)prop and 4mm thick 2nd coat CM(1:4) prop on both sides of brick work.
Snowcem paint in two coats shall be provided for both sides of wall. The M.S ornamental gate as per the approved drawings shall be provided with minimum of 3.60mts width and 2.40mts height with enamel paint. Yard lighting shall be arranged on four corners of compound wall. If the length of the wall is increased/ decreased Note:-For every 1m increase/decrease in length of compound wall the increase/decrease in basic rates of ELSRs of the capacities from 500KL to 2500KL shall be as follows.: i)500 KL : 0.086% ii)1000 KL : 0.047% iii)1500 KL : 0.034% iv)2000 KL : 0.026% v)2500 KL : 0.022 % For intermediate capacities, interpolated percentages shall be adopted. xiv) Staff Quarter shall be constructed for a minimum plinth area of 40 Sqm with the following specification: RCC framed structure with concrete grade not less than M20 design mix at the locations specified by the department at the time of execution with veranda, hall, bed room, kitchen and bath &W/C with floor area of 40.00sqmts excluding balconies and staircases.
MS hollow door frame with cold rolled processed steel sheet 1.25mm thick bright CRCA conforming to IS 4351/76, Flush door shutters with solid bond wood bond board doors shall be provided. N.C.L. Windows centre fixed both sides open able shutter window 1.35 X 1.35mts outer frame section 48 x50mm shutter frame section with a size of 48 X20 mm mullion section of size 48 X 50mm fixed beading section of 12 X 12 mm shall be provided. Flooring with polished Kadapa stone shall be provided. Walls shall be provided with snowcem paint in two coats over primary coat. Electrical and water supply arrangement shall be provided as directed by dept officer. Water Storage tank made with plastic/polymer material of reputed make with necessary out let and inlet connection pipes shall provided. Septic tank for 5 users shall be provided.
Construction of 500 KL ELSR with 20m staging at Near M.M.P School zone -III(Balance Work)
Construction of ELSR With the following specification 500 kl capacity with a staging of 20m, with Seismic analysis.
All concrete components shall be designed with M30 Design Mix proportion. 4) The foundations shall be designed for Annular Raft Footings. The above rates are applicable for Elevated Level Services Reservoirs / OHSRs for SBC of 15 T/Sqm. c) For SBC below 10T/Sqm , solid raft shall be provided d) For SBC value of less than 5 T/Sqm, soil improvement shall be adopted, for which additional payment shall be made as per field condition. a) Rate inclusive of three coats of epoxy paint Food Grade of best quality to inner surface of the Reservoir including roof. b)The rate inclusive of 2 coats of weather proof emulsion painting for external surfaces, lettering, all required fixtures, Pipes, Pipe specials, valves of DI material, Valve chambers etc., for pipe connections including cost of pipes, specials and valves as per departmental designs and drawings. 11) The above rates adopted for a wind pressure up to "250 kg/Sqm". The ELSR/OHSR shall be designed with minimum of two rows of columns for capacities above 500 KL & up to 1000KL. The ELSR/OHSR shall be designed with minimum of three rows of columns for capacities above 1000KL. 14. The shaft type staging with slip form can also be provided with proper approval from competent authority without any additional cost.
15) The basic rate is inclusive of following Fixtures i) Pipe connections & Specials with D.I materials (a) All pipe connections for Inlet, Out let, Over Flow, Scour pipes shall be provided with D/F DI material. (b) The Valves for above pipe connections also shall be of DI material of PN 16 duty confirming to the specification of SoR item No.28 (c) All specials such as Bends, Tees, Reducers, Duck foot Bends, Bell mouths etc,. Shall be of DI material. II) The sizes of the verticals for ELSR/OHSR shall be: a) For 500 KL to 750 Kl ELSRs Inlet Pipe - 300mm dia. Out let Pipe - 350mm dia. DI valves – 2 No’s Over Flow pipe - 350m dia. Scour Pipe - 200mm dia. b) For 800 KL to 1500 Kl ELSRs Inlet Pipe - 400mm dia. Out let Pipe - 450mm dia. DI valves – 2 No’s Over Flow pipe - 450m dia. Scour Pipe - 200mm dia. c) For above 1500 KL to 2500 Kl ELSRs Inlet Pipe - 400mm dia. Out let Pipe - 500mm dia. DI valves – 2 No’s Over Flow pipe - 500m dia. Scour Pipe - 200mm dia.
Note: Any deviation from the above sizes as per design, shall be paid or recovered. (iii) Manhole Frames & Covers a) All man hole Frames & Covers shall be made of CI/DI materials with min. size of 0.60mX 0.60m - For Roof & Valve Chambers. iv) CI/D.I Double Swan neck ventilators (min. of 150mm dia.) shall be provided in top dome and slab with mosquito/fly proof nets - 4Nos. v) RCC Finial ventilator with fly/bird protection with GI mesh - 1 No. vi) RCC precast ladders of 0.60 m width - 2 Nos. vii) RCC dog legged stair case of 1.00 m flight width and 1.20 m landing width R.C.C hand railing of 1.0 m height – 1 No viii) The staircase shall be enclosed with brick masonry walls on three sides and collapsible MS gate on front side up to 1st brace level, to prevent unauthorized entry. ix) Construction of R.C.C valve chambers as per Standard Drawings with RCC cover slab fixed with CI/DI manhole Frame & Cover with lock and Key arrangement. The Mix shall not be less than VRCC M 20 grade with 150mm thick side walls, 150mm thick top slab, 150mm thick base slab over base course of 100mm thick (1:4:8) prop. x) Balcony of 1.00 m width at floor slab level / middle ring beam level by using Stainless Steel pipe of grade 304 hand railing up to 1.20 m height, with top railing of 40mm dia. pipe & middle railing of 25mm dia. and verticals with 40mm dia. at an interval not more than of 1.00m c/c.
xi) Water Level Indicator of reputed make – Digital type (1 No) and Conventional type (1 No) xii) Lightening Arrestor with all its accessories complete including earthing, with relevant IS Codes - 1 No. xiii) Compound wall: Construction of compound wall including ornamental M.S.Gate of size 3.0 X 2.40m is included in the basic rate of ELSRs. Length of compound wall hall is minimum of 150m. Min. height of the compound wall shall be 1.80m above plinth and thickness 230mm in brick masonry in CM (1:6).The compound wall shall be constructed including earth work excavation in all types of soils for plinth beam of 230mm X 300mm and 0.75X0.75X1.20m size for column footing portions. The footings shall be of 0.75X0.75X0.25m in VRCC M20 grade and constructed over a C.C (1:4:8) prop bed of 100mm thick. The columns shall be of 230X230 mm in size with VRCC M20 grade at 3.00m c/c spacing, having depth of 1.20m below ground level and height of 2.00m above GL. The plinth beam of size of 230X300 mm shall be constructed in VRCC M20 grade at Ground level, over a bed of CC(1:4:8)-100mmthick. 450X450mm size columns in M20 grade shall be constructed for gate pillars. All the materials shall be followed as per the standards. Tie beam shall be provided above the brick work with 230X200mm size, fixed with MS angular of 25mm X 25mm X 4mm in "Y" shape to height of 0.60m, with embedded length of 150mm in concrete. The barbed wire fencing with 3 ply of 18 gauges shall be stretched in 4 rows (2x2). Plastering shall be done with 16mm thick in two coats i.e., base coat 12mm thick in CM(1:6)prop and 4mm thick 2nd coat CM(1:4) prop on both sides of brick work.
Snowcem paint in two coats shall be provided for both sides of wall. The M.S ornamental gate as per the approved drawings shall be provided with minimum of 3.60mts width and 2.40mts height with enamel paint. Yard lighting shall be arranged on four corners of compound wall. If the length of the wall is increased/ decreased Note:-For every 1m increase/decrease in length of compound wall the increase/decrease in basic rates of ELSRs of the capacities from 500KL to 2500KL shall be as follows.: i)500 KL : 0.086% ii)1000 KL : 0.047% iii)1500 KL : 0.034% iv)2000 KL : 0.026% v)2500 KL : 0.022 % For intermediate capacities, interpolated percentages shall be adopted. xiv) Staff Quarter shall be constructed for a minimum plinth area of 40 Sqm with the following specification: RCC framed structure with concrete grade not less than M20 design mix at the locations specified by the department at the time of execution with veranda, hall, bed room, kitchen and bath &W/C with floor area of 40.00sqmts excluding balconies and staircases.
MS hollow door frame with cold rolled processed steel sheet 1.25mm thick bright CRCA conforming to IS 4351/76, Flush door shutters with solid bond wood bond board doors shall be provided. N.C.L. Windows centre fixed both sides open able shutter window 1.35 X 1.35mts outer frame section 48 x50mm shutter frame section with a size of 48 X20 mm mullion section of size 48 X 50mm fixed beading section of 12 X 12 mm shall be provided. Flooring with polished Kadapa stone shall be provided. Walls shall be provided with snowcem paint in two coats over primary coat. Electrical and water supply arrangement shall be provided as directed by dept officer. Water Storage tank made with plastic/polymer material of reputed make with necessary out let and inlet connection pipes shall provided. Septic tank for 5 users shall be provided.
Construction of 500 KL ELSR with 20m staging at Bondaikodu(Balance work)
Construction of ELSR With the following specification 500 kl capacity with a staging of 20 m, with Seismic analysis.
All concrete components shall be designed with M30 Design Mix proportion. 4) The foundations shall be designed for Annular Raft Footings. The above rates are applicable for Elevated Level Services Reservoirs / OHSRs for SBC of 15 T/Sqm. c) For SBC below 10T/Sqm , solid raft shall be provided d) For SBC value of less than 5 T/Sqm, soil improvement shall be adopted, for which additional payment shall be made as per field condition. a) Rate inclusive of three coats of epoxy paint Food Grade of best quality to inner surface of the Reservoir including roof. b)The rate inclusive of 2 coats of weather proof emulsion painting for external surfaces, lettering, all required fixtures, Pipes, Pipe specials, valves of DI material, Valve chambers etc., for pipe connections including cost of pipes, specials and valves as per departmental designs and drawings. 11) The above rates adopted for a wind pressure up to "250 kg/Sqm". The ELSR/OHSR shall be designed with minimum of two rows of columns for capacities above 500 KL & up to 1000KL. The ELSR/OHSR shall be designed with minimum of three rows of columns for capacities above 1000KL. 14. The shaft type staging with slip form can also be provided with proper approval from competent authority without any additional cost.
15) The basic rate is inclusive of following Fixtures i) Pipe connections & Specials with D.I materials (a) All pipe connections for Inlet, Out let, Over Flow, Scour pipes shall be provided with D/F DI material. (b) The Valves for above pipe connections also shall be of DI material of PN 16 duty confirming to the specification of SoR item No.28 (c) All specials such as Bends, Tees, Reducers, Duck foot Bends, Bell mouths etc,. Shall be of DI material. II) The sizes of the verticals for ELSR/OHSR shall be: a) For 500 KL to 750 Kl ELSRs Inlet Pipe - 300mm dia. Out let Pipe - 350mm dia. DI valves – 2 No’s Over Flow pipe - 350m dia. Scour Pipe - 200mm dia. b) For 800 KL to 1500 Kl ELSRs Inlet Pipe - 400mm dia. Out let Pipe - 450mm dia. DI valves – 2 No’s Over Flow pipe - 450m dia. Scour Pipe - 200mm dia. c) For above 1500 KL to 2500 Kl ELSRs Inlet Pipe - 400mm dia. Out let Pipe - 500mm dia. DI valves – 2 No’s Over Flow pipe - 500m dia. Scour Pipe - 200mm dia.
Note: Any deviation from the above sizes as per design, shall be paid or recovered. (iii) Manhole Frames & Covers a) All man hole Frames & Covers shall be made of CI/DI materials with min. size of 0.60mX 0.60m - For Roof & Valve Chambers. iv) CI/D.I Double Swan neck ventilators (min. of 150mm dia.) shall be provided in top dome and slab with mosquito/fly proof nets - 4Nos. v) RCC Finial ventilator with fly/bird protection with GI mesh - 1 No. vi) RCC precast ladders of 0.60 m width - 2 Nos. vii) RCC dog legged stair case of 1.00 m flight width and 1.20 m landing width R.C.C hand railing of 1.0 m height – 1 No viii) The staircase shall be enclosed with brick masonry walls on three sides and collapsible MS gate on front side up to 1st brace level, to prevent unauthorized entry. ix) Construction of R.C.C valve chambers as per Standard Drawings with RCC cover slab fixed with CI/DI manhole Frame & Cover with lock and Key arrangement. The Mix shall not be less than VRCC M 20 grade with 150mm thick side walls, 150mm thick top slab, 150mm thick base slab over base course of 100mm thick (1:4:8) prop. x) Balcony of 1.00 m width at floor slab level / middle ring beam level by using Stainless Steel pipe of grade 304 hand railing up to 1.20 m height, with top railing of 40mm dia. pipe & middle railing of 25mm dia. and verticals with 40mm dia. at an interval not more than of 1.00m c/c.
xi) Water Level Indicator of reputed make – Digital type (1 No) and Conventional type (1 No) xii) Lightening Arrestor with all its accessories complete including earthing, with relevant IS Codes - 1 No. xiii) Compound wall: Construction of compound wall including ornamental M.S.Gate of size 3.0 X 2.40m is included in the basic rate of ELSRs. Length of compound wall hall is minimum of 150m. Min. height of the compound wall shall be 1.80m above plinth and thickness 230mm in brick masonry in CM (1:6).The compound wall shall be constructed including earth work excavation in all types of soils for plinth beam of 230mm X 300mm and 0.75X0.75X1.20m size for column footing portions. The footings shall be of 0.75X0.75X0.25m in VRCC M20 grade and constructed over a C.C (1:4:8) prop bed of 100mm thick. The columns shall be of 230X230 mm in size with VRCC M20 grade at 3.00m c/c spacing, having depth of 1.20m below ground level and height of 2.00m above GL. The plinth beam of size of 230X300 mm shall be constructed in VRCC M20 grade at Ground level, over a bed of CC(1:4:8)-100mmthick. 450X450mm size columns in M20 grade shall be constructed for gate pillars. All the materials shall be followed as per the standards. Tie beam shall be provided above the brick work with 230X200mm size, fixed with MS angular of 25mm X 25mm X 4mm in "Y" shape to height of 0.60m, with embedded length of 150mm in concrete. The barbed wire fencing with 3 ply of 18 gauges shall be stretched in 4 rows (2x2). Plastering shall be done with 16mm thick in two coats i.e., base coat 12mm thick in CM(1:6)prop and 4mm thick 2nd coat CM(1:4) prop on both sides of brick work.
Snowcem paint in two coats shall be provided for both sides of wall. The M.S ornamental gate as per the approved drawings shall be provided with minimum of 3.60mts width and 2.40mts height with enamel paint. Yard lighting shall be arranged on four corners of compound wall. If the length of the wall is increased/ decreased Note:-For every 1m increase/decrease in length of compound wall the increase/decrease in basic rates of ELSRs of the capacities from 500KL to 2500KL shall be as follows.: i)500 KL : 0.086% ii)1000 KL : 0.047% iii)1500 KL : 0.034% iv)2000 KL : 0.026% v)2500 KL : 0.022 % For intermediate capacities, interpolated percentages shall be adopted. xiv) Staff Quarter shall be constructed for a minimum plinth area of 40 Sqm with the following specification: RCC framed structure with concrete grade not less than M20 design mix at the locations specified by the department at the time of execution with veranda, hall, bed room, kitchen and bath &W/C with floor area of 40.00sqmts excluding balconies and staircases.
MS hollow door frame with cold rolled processed steel sheet 1.25mm thick bright CRCA conforming to IS 4351/76, Flush door shutters with solid bond wood bond board doors shall be provided. N.C.L. Windows centre fixed both sides open able shutter window 1.35 X 1.35mts outer frame section 48 x50mm shutter frame section with a size of 48 X20 mm mullion section of size 48 X 50mm fixed beading section of 12 X 12 mm shall be provided. Flooring with polished Kadapa stone shall be provided. Walls shall be provided with snowcem paint in two coats over primary coat. Electrical and water supply arrangement shall be provided as directed by dept officer. Water Storage tank made with plastic/polymer material of reputed make with necessary out let and inlet connection pipes shall provided. Septic tank for 5 users shall be provided.
Laying of 350mm,300 mm , 250mm,200 mm 150 mm and 100 mm dia . DI K9 Pumping mains for clear water from clear water sump at proposed 6.50 MLD WTP to various proposed and existing ELSRs
Cutting of existing B.T.road surface (aswell as asphalt concrete up to 75mm thick) including all labour charges for cutting, stacking of materials hiring of machinary, fuil charges, wages of driver etc.,complete as per the directions of departmental authorities. For pipe line trenches.
Cutting and open of C.C. Road surface including all labour charges for cutting, stacking of materials hiring of machinary, fuil charges, wages of driver etc.,complete as per the directions of departmental authorities. For pipe line trenches.
Cutting and open of WBM. Road surface including all labour charges for cutting, stacking of materials hiring of machinary, fuil charges, wages of driver etc.,complete as per the directions of departmental authorities. For pipe line trenches.
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH
Mechanical Means up to 3 metres depth in ordinary soil
Manual means up to 3 metres depth in ordinary soil
Providing river sand filling brought from approved quarry including cost and conveyance of all material and all labour charges such as filling in layers watering ramming etc complete as per ss and as directed by the departmental officer in chrges of work
Centrifugally cast (Spun) Ductile Iron pressure pipes for water, gas and sewage with Socket Spigot ends conforming to IS.: 8329/2000 in standard working lengths of 4, 5 5.5 & 6 meter for classification K9 & K7 suitable for push-on-joint (rubber gasket d jointing) with cement mortar lining inside the pipes with outside zinc coating. Rates are ex-factory, including transportation and etc complete and all labour charges,and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work.
300mm dia DIK9
250mm dia DIK9
200mm dia DIK9
150mm dia DIK9
100mm dia DIK9
Centrifugally cast (Spun) Ductile Iron pressure pies with flanged (welded) ends for water, gas, sewage conforming to IS: 8329/2000 in standard working lengths of 1,2,3, 4, 5 mts for classification K9 with cement mortar lining inside the pipes with outside zinc coating. Rates are ex-factory, including transportation and etc complete and all labour charges,and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work. as follows
200 mm dia 2.00m long DIDF pipes for scours on 300 mm dia pipe
150 mm dia 2.00m long DIDF pipes for scours on 250 mm dia pipe
150 mm dia 2.00m long DIDF pipes for scours on 200 mm dia pipe
100 mm dia 2.00m long DIDF pipes for scours on 150 mm dia pipe
300 mm dia 1.00m long DI DF pipes for sluice and non return valves and bulk flow meters 3+1+1
250 mm dia 1.00m long DI DF pipes for sluice and non return valves 2+1
200 mm dia 1.00m long DI DF pipes for sluice and non return valves 6+4
150 mm dia 1.00m long DI DF pipes for sluice and non return valves 7+4
100 mm dia 1.00m long DI DF pipes for sluice and non return valves 2+2
Centrifugally cast (spun) Ductile Iron Fittings conforming to IS:9523/2000 having dimensions as per table. The rates mentioned here under are for fittings, zinc coated externally with inside mortar lining (with finishing as per class 13/IS 9523/2000) ( ex-works) including Transportation and etc complete and all labour charges,and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work.
Lowering of D.I. socket and spigot Pipes and fittings carefully in to the trench and laying them true to alignment and gradient including all labour charges, sundries as per BIS No. 3114/85 etc., complete as per S.S and as directed by the departmental authorities.as follow
300mm dia DIK9
250mm dia DIK9
200mm dia DIK9
150mm dia DIK9
100mm dia DIK9
Jointing of D.I. Pipes & fittings with Rubber Gasket including all sundries filling with water with a water lead up to 500m and testing to required pressure etc., complete as per BISNo.3114/85 and as directed by the departmental authorities.
300mm dia DIK9
250mm dia DIK9
200mm dia DIK9
150mm dia DIK9
100mm dia DIK9
Supply and delivery of "Resilient Seated Soft Sealing" Gate Valves (Sluice Valves) with Body and Bonnet of Ductile Iron GGG-40/SG-400/15 or GGG-50/SG-500/7 or Equivalent as per IS1865, IS:3896-2 and Wedge fully Rubber Lined with food grade quality grade W270 grade EPDM, Replaceable Spindle Nut without gland packing with 3-O ring protection system on the Shaft and Seals of NBR. The Valves should be Vacuum tight and 100% leak proof with face to face dimensions as BS:5163 Type A/IS:14846. All the valves should be with fusion bonded Electrostatic Powder coating both inside and outside (Min 250 Microns)- RAL 5005 with Pocket Less Straight through body Passage conforming to Design standards of DIN-3202F4/BS:5163 Type A Flange drilling as per IS - 1538 , duties and including transportation.PN 1.6 MPa etc complete and all labour charges,and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work. as follows
300 mm dia sluice valves
250 mm dia sluice valves
200 mm dia sluice valves
150 mm dia sluice valves
100 mm dia sluice valves
Supply & Delivery of Tamper Proof DI Flanged Single Chamber Air Release Valves with body & cover made of Ductile Iron Grade GGG-40/SG-400/15 or GGG-50/SG-500/7 or Equivalent as per IS1865, IS:3896-2 with Food Grade Epoxy Powder Coating(EP-P) (Min:250 Micron) inside and Outside of Color Blue RAL 5005. All internal parts such as Float, shell, Cove Bolts etc. made of Austenitic alloy steel of SS AISI 304/316 and DN 50 float of and other components with ABS/PTFE/EPDM/NBR and generally conforming to DIN/BIS/AWWA standards (or) combination Flange drilling as per IS - 1538 and exclusive of all taxes and including transportation - PN1.6 MPa
80mm dia. PN 16 on 300 mm dia
80mm dia. PN 16 on 250 mm dia
80mm dia. PN 16 on 200 mm dia
80mm dia. PN 16 on 150 mm dia
Supply, Delivery of D.I Double Flanged Swing Check type Reflux valves (Non Return Valves) of following dia. conforming to IS- 5312 (Pts-1&2) (with amendments up to date, if any) having Body, Cover, Door, Bearing holder with D.I; Hinge pin, Door pin, Door suspension pin with Stainless Steel (IS 6603); Body seat ring , Door face ring, Bearing bushes, Plugs for hinge pin with Leaded Tin Bronze ( IS 318 ); Bolts, Nuts with Carbon steel; Gaskets with Rubber; Hinges with Cast steel; including transportation and excluding all taxes complete. PN 1.6 MPa
300 mm dia
250mm dia DI
200mm dia DI
150mm dia DI
100mm dia DI
Labour charges for lowering and keeping in position of C.I./DI Sluice valves(with cap/with hand wheel), reflux valves and scour valves.etc complete and all labour charges,and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work. as follows
300 mm dia sluice valves
250 mm dia sluice valves
200 mm dia sluice valves
150 mm dia sluice valves
100 mm dia sluice valves
Labour charges for fixing Kinetic Air Valves with isolating Sluice valves, Double Air valves/ Air Cushion valve excluding cost of jointing materials such as bolts, nuts and rubber insertions etc.
Lowering the C.I. Pipes, D.I. Pipes of all classes and fittings with flanged ends carefully into the trenches and laying them true to alignment and gradient including all sundries, but excluding conveyance from source of supply as per BIS No.3114/94.
300mm dia
250 mm dia
200 mm dia DI
150mm dia
100 mm dia
Jointing the D.I. Pipes, fittings and valves with flanged ends including cost of jointing materials such as bolts, nuts, rubber insertion, white lead and including filling with water with a water lead upto 500 m and testing to required pressure etc., comp as per BIS No.3114/85
300 mm dia
250 mm dia
150 mm dia
100 mm dia
80 mm dia air valves
Construction of R.C.C. thrust blocks using RCC M- 20 Nominal mix (Cement:fine aggregate: coarse aggregate) corresponding to Table 9 of IS 456 using 20mm size graded machine crushed hard granite metal (coarse aggregate) from approved quarry including cost and conveyance of all materials like cement, fine aggregate (sand) coarse aggregate, water etc., to site and including all operational, incidental and labour charges such as machine mixing, laying concrete, curing etc.,complete but excluding cost of steel and its fabrication charges for finished item of work
Construction of Anchor blocks VCC M- 20 Nominal mix (Cement:fine aggregate: coarse aggregate) corresponding to Table 9 of IS 456 using 20mm size graded machine crushed hard granite metal (coarse aggregate) from approved quarry including cost and conveyance of all materials like cement, fine aggregate (sand) coarse aggregate, water etc., to site and including all operational, incidental and labour charges such as machine mixing, laying concrete, curing etc.,complete but excluding cost of steel and its fabrication charges for finished item of work,
Collection ,supply,spreading and compaction of crusher stone dust including curing as per SS
Construction of Sluice Valve chambers with VRCC M20 Concrete suitable to the sluice valves with VRCC Cover Slab including cost and conveyance of all materials and all labour charges etc.complete as per S.S for finished item of work
For 300mm dia. Sluice Valves and swing check valves
For 250mm dia. Sluice Valves and swing check valves
For 200mm dia. Sluice Valves and swing check valves
For 150mm dia. Sluice Valves and swing check valves
For 100mm dia. Sluice Valves and swing check valves
Construction of Scour Valve chambers with VRCC M20 Concrete suitable to the Scour valves with VRCC Cover Slab including cost and conveyance of all materials and all labour charges etc.complete as per S.S for finished item of work
For 200mm dia. Scour Valves
For 150mm dia. Scour Valves
For 100mm dia. Scour Valves
Construction of Air Valvechambers with VRCC M20 Concrete suitable to the Air valves with VRCC Cover Slab including cost and conveyance of all materials and all labour charges etc.complete as per S.S for finished item of work
For 80 mm dia. Air Valves and Air release valves on 300 mm dia
For 80 mm dia. Air Valves and Air release valves on 250 mm dia
For 80mm dia. Air release valves on 200 mm dia
For 80mm dia. Air valves on 150 mm dia
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars (Fe 415/ Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying etc., complete for finished item of work
Using Concrete mixture up to Plinth Level : Plain Cement concrete nominal mix M-30 (Cement : fine aggregate: coarse aggregate ) using 20mm size Hard Granite Machine Crushed Graded Metal including cost and conveyance of all materials like cement, sand, coarse aggregate water etc., to site , seigniorage charges on all materials, labour charges , for mixing , laying, concrete , ramming in 15 cm layers, finishing top surface to the required level curing etc., complete for finished item of work with nomonal reinforcement for Road restoration.
Manufacture, Supply and Delivery of C.I Dismantling Joints with both side flange end suitable for installation in between flange end pipes. These rates are excluding all taxes and including transportation
300mm dia
250mm dia
200mm dia
150 mm dia
100 mm dia
Items for implementation of EMP to be included in the estimate
Air Quality Monitoring (4 Monitoring station) once in a month for three seasons during the construction period at Intake well, WTP, GLBR, ELSR's, Raw/Clear Pipe Line & Distribution network
Noise level (4 Monitoring station) once in a month for three seasons during the construction period Intake well, WTP, GLBR, ELSR's, Raw/Clear Pipe Line & Distribution network
Water Quality Monitoring surface / ground (4 Monitoring station) once in a month for three seasons during the construction period at Intake well, WTP, GLBR, ELSR's, Raw/Clear Pipe Line & Distribution network
Air Quality Monitoring (4 Monitoring station) once in a month for three seasons during the construction period at Intake well, WTP, GLBR, ELSR's, Raw/Clear Pipe Line & Distribution network
Noise level (4 Monitoring station) once in a month for three seasons during the construction period Intake well, WTP, GLBR, ELSR's, Raw/Clear Pipe Line & Distribution network
Water Quality Monitoring surface / ground (4 Monitoring station) once in a month for three seasons during the construction period at Intake well, WTP, GLBR, ELSR's, Raw/Clear Pipe Line & Distribution network
Compensatory plantation and three years maintenance (Compensatory afforestation ratio is 1:5)-plants & tree guards
Greenbelt development and maintenance in the surroundings / Buffer zone
Health checkups and free medical distribution (4 Camps)
Awareness program/training (every Six Months - 4 Camps)
Sprinkling of water once in a day for two years (excluding rainy days)
Hiring for 1 Nos. Vehicle during execution period including hire charges of vehicle, diesel, lubrication, driver charges, repairs and all incidental charges etc.,
Construction of Clear Water SCADA Room 8.00 x 12.00 Size at WTP.
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH for Manual Means.
Manual Means upto 3 metres depth in ordinary soil
Mechanical Means up to 3 metres depth in Ordinary Soil
Providing river sand filling brought from approved quarry including cost and conveyance of all material and all labour charges such as filling in layers watering ramming etc complete as per ss and as directed by the departmental officer in chrges of work
Laying Cement concrete (1:4:8) using 40mm nominal size HBG metal M/C including cost and conveyance of all materials from approved quarry, machine mixing, vibrating, laying, levelling, ramming, curing and labour charges etc., complete. As per APSS 402 (BLD-CSTN-2-5).
Construction of RR Masonary in C.M (1: 6) prop. Using hard granite stone including cost and conveyance of all materials like cement, sand, water, Granite stone etc. including cost of seigniorage charges on all materials, all taxes including labour for cutting stones to required size and shape, mixing of cement mortar construction, Scaffolding charges etc. complete for finished item of work.
Providing VRCC M25 Grade Design Concrete Mix corresponding to IS 456 using WEIGH BATCHER / MIXER with 20mm size graded machine crushed hard granite metal (coarse aggregate) from approved quarry including cost and conveyance of all materials like cement, fine aggregate (sand) coarse aggregate, water etc., to site and including all operational, incidental and labour charges such as weigh batching, machine mixing, laying concrete, curing with cement content 380Kgs/Cum as per I.S code from standard suppliers approved by the department including centering, shuttering, laying concrete, vibrating, curing etc. complete but excluding cost of steel and its fabrication charges for finished item of work (APSS No. 402)
Providing VRCC M25 Grade Design Concrete Mix corresponding to IS 456 using WEIGH BATCHER / MIXER with 20mm size graded machine crushed hard granite metal (coarse aggregate) from approved quarry including cost and conveyance of all materials like cement, fine aggregate (sand) coarse aggregate, water etc., to site and including all operational, incidental and labour charges such as weigh batching, machine mixing, laying concrete, curing with cement content 380Kgs/Cum as per I.S code from standard suppliers approved by the department including centering, shuttering, laying concrete, vibrating, curing etc. complete but excluding cost of steel and its fabrication charges for finished item of work (APSS No. 402)
Providing VRCC M25 Grade Design Concrete Mix corresponding to IS 456 using WEIGH BATCHER / MIXER with 20mm size graded machine crushed hard granite metal (coarse aggregate) from approved quarry including cost and conveyance of all materials like cement, fine aggregate (sand) coarse aggregate, water etc., to site and including all operational, incidental and labour charges such as weigh batching, machine mixing, laying concrete, curing with cement content 380Kgs/Cum as per I.S code from standard suppliers approved by the department including centering, shuttering, laying concrete, vibrating, curing etc. complete but excluding cost of steel and its fabrication charges for finished item of work (APSS No. 402)
Footings
Pedastals around Columns
Columns Up to plinth
Plinth Beams 300 x 400
Columns
Up to First Floor Roof Level
Beams 230 x 500
Lintels
Sunshades
Staircase slab 0.15 m thick
RCC Slab 150mm thick
Providing High Yield Strength Deformed (HYSD)/ Thermo Mechanically Treated (TMT) / Mild steel (MS) steel bars Fe 500 grade as per IS 1786-1979) of different diameters for RCC works , including labour charges for straightening, cutting, bending to required sizes and shapes, placing in position with cover blocks of approved materials and size and tying and lap-splicing with binding wire of 18 SWG, forming grills for reinforcement work as per approved designs and drawings, including cost and conveyance of steel bars, including all wastages such as overlaps, couplings, chairs, spacer bars including cost and conveyance of binding wire, cover blocks and all incidental, operational, labour charges such as cutting, bending, placing in position, tying etc., complete for finished item of work in all floors.( APSS No.126) for pre cast slabs of culverts - RBR-FNDN-8 & Revised Data sl.No-5
Brick Masonry in CM (1:6) for 230mm thick with 2nd class Bricks traditional size 23x11x7cms including cost and conveyance of materials to site, mixing of cement mortar and laying of bricks and mortar to specified thickness, watering and curing, scaffolding charges, etc complete for finished item of work (BLD-CSTN-3-1).
For Ground Floor Level
For First Floor Level
11.5 cm wide Brick masonry for super-structure on ground floor in cm (1:3) using second class traditional size bricks including cost of all materials, seigniorage charges, labour and all operations for constructing half brick masonry, mixing cement mortar, curing etc., complete for finished item of work, but excluding conveyance charges of materials.
Plastering with CM (1:3), 20 mm thick including cost and conveyance of all materials and water to work site and all operational incidental, labour charges such as scaffolding, mixing mortar lift charges curing etc., complete for finished item of work.
Ground Floor
For First Floor
Plastering with CM (1:3), 12 mm thick including cost and conveyance of all materials and water to work site and all operational incidental, labour charges such as scaffolding, mixing mortar lift charges curing etc., complete for finished item of work.
Plastering with CM (1:3), 12 mm thick including cost and conveyance of all materials and water to work site and all operational incidental, labour charges such as scaffolding, mixing mortar lift charges curing etc., complete for finished item of work.
Flooring with Nano polished /stain free soluble salt porcelain vitrified tiles screen printed of size 600 x 600 mm and thickness between 8-10 mm 1st quality conforming to IS:13711, IS:13712, IS:13630 (Parts 1 to 15) of any colour and finish in all shades and designs, set over base coat of cement mortar (1:8), 12 mm thick over CC bed already laid or RCC roof slab, including neat cement slurry of honey like consistency spread @ 3.3.kgs per sqm & jointed neatly with white cement paste to full depth mixed with pigment of matching shade, including cost of all materials like cement, sand water and tiles etc., complete for finished item of work
Flooring with ceramic tiles of size (600X 600, set over base coat of cement mortar (1:8), 12 mm thick over CC bed already laid or RCC roof slab, including neat cement slurry of honey like consistency spread @ 3.3.kgs per sqm & jointed neatly with white cement paste to full depth mixed with pigment of matching shade, including cost of all materials like cement, sand water and tiles etc., complete, including seigniorage charges, etc., complete for finished item of work, including the cost of conveyance of all materials.
Dadooing to walls with first quality glazed coloured tiles approved colour of any size set over base coat of C.M(1:3)prop. 12mm thick and neat grey cement slurry of honey like consistency spread at the rate of 3.3Kg of cement per sqm and jointed with neat white cement paste at 0.20 kg per sqm mixed with pigment of matching shade to match the shade of tiles including cost and conveyance of all materials labour charges, water to work site,seignourage and all operational .incidental , mixing mortar , fixing in position ,lift charges, curing etc., complete as per SS or as directed by the departmental authorities for finished item of work.
Painting Walls with Snowcem or other equal and approved Water Proof Cement Paint 2 Coats (All Colours) over a base coat of aproved cement primer making 3 coats in total including cost of all materials, conveyance charges of materials and including all operational, incidental and labour charges etc,, complete for finished item of work as directed by the departmental authorities.
Painting Walls with Snowcem or other equal and approved Water Proof Cement Paint 2 Coats (All Colours) over a base coat of aproved cement primer making 3 coats in total including cost of all materials, conveyance charges of materials and including all operational, incidental and labour charges etc,, complete for finished item of work as directed by the departmental authorities.
Painting Walls with Snowcem or other equal and approved Water Proof Cement Paint 2 Coats (All Colours) over a base coat of aproved cement primer making 3 coats in total including cost of all materials, conveyance charges of materials and including all operational, incidental and labour charges etc,, complete for finished item of work as directed by the departmental authorities.
Providing & Fixing of Scientific Doors with metal door frames and door shutters made of galvanize steel (base steel as per IS 513 of 0.58 mm thick D quality, galvanized as per IS 277 with Zinc of 120 GSM)coated with Zinc Phosphate Primer to receive any paint on site or finished with Thermosetting Polyurethane paint of Aliphatic Grade providing high levels of scratch resistance and durability/Epoxy polyester powder for powder coating paint thickness 50-60 microns (Dry film thickness) outer frame section of 100 x 58 mm x 1.2 mm thick, shutter section of 0.80 mm thick galvanized steel sheet pressed (roll formed) for 46mm thick fully flush, double skin door shell seam joints at stile edges, in-fill of honeycomb kraft paper used to give the required rigidity and effective acoustic insulation with 6” Tower bolt – 1 No., 6” D handles – 2 Nos., 10” Aldrop – 1 No., Butt Hinges – 3 Nos, Mortise Lock of approved quality – 1 No, frames fixed to the concrete/masonry wall by means of self expanding screws complete for finished item of work for Single leaf Door
Supply and fixing of pre-painted steel openable windows base steel as per IS 513 of -0.58 mm thick 'D" quality, galvanized as per IS 277 , finish painted with a polyester paint of 12-16 microns thick and back coated with 5-7 microns thick alkyd backer, section for outer frame of 46 x 52 mm section and for shutter of 46 x 46 mm section for mullion 46 x 70 mm, and section for beading should be 18 x 25 mm with 5 mm thick plain float glass fitted with Ethyl propylene Diamine monomer Gasket (EPDM) and handle made of high grade aluminium powder coated with frames fixed to the concrete /masonry wall by means of self expanding screws including 10 mm square guard bars with 6" pitch complete for finished item of work .
Door Frame section of 63.5x100 MM The two Vertical members are to be joined together with the horizontal member using 8x75 MM long MS Star full thread screws to be used with reverse forward speed control hand drilling machine. The ready/assembled door frame is fixed to the wall using hold fast or bolt fasteners. A minimum of 4 No.s of screws to be provided for each vertical member & minimum 2no.s for horizontal member
Providing and fixing 28 -30 MM thick solid Wood Polymer Composite(WPC) single extruded door shutter with 3MM top and bottom rigid layer with an overall density of 750kg/Cum. It will be fixed to the frame using 3 inch /4 inch hinges. A minimum of 4 hinges will be required for fixing the door with the frame
Supplying and fixing of Top Hung Ventilators made of pre - painted steel (base steel as per IS 513 of -0.58 mm thick 'D" quality, galvanized as per IS 277 with zinc of 120 GSM) primer coated with epoxy primer of 5-7 microns thick, finish painted with a polyester paint of 12-16 microns thick and back coated with 5-7 microns thick alkyd backer, section for outer frame of 46 x 52 mm section and for shutter of 46 x 46 mm section for mullion 46 x 70 mm, The Ventilator to be panelled 4 mm pinhead glass with Ethyl propylene Diamine monomer Gasket (EPDM) and the sections cut to length mitre joined with corner brocket mullions fixed using mullion cap and with handle made of high grade aluminium powder coated and nylon receiver, corner brackets made of CRCA with Zinc Phosphate, Mullion caps made of glass filled nylon, frames fixed to the concrete /masonry wall by means of self expanding screws including 10 mm square guard bars with 6" pitch complete for finished item of work.
Providing and fixing Thermocole False ceiling in true horizontal level 600 mm x 600 mm using 15 mm/ 19 mm thick Thermocole sheet anodized Aluminium Tee sections of size 24.50 mm x 24.0 mm x 2.4 mm in grid with cross tee of size 24 x 24.5 mm at every 600 mm c/c and anodized aluminium wall angle of size 24 x 24 mm fixed to periphery of the wall and the above grid is suspended at every 1200 mm c/c in both directions using 2.0 mm thick GI Wire for finished of size 600 x 600 mm including Cost &conveyance of all materials and labour charges such as cutting , fixing of standing of frame work exposing roof making complete for finished item of work
Supply and fixing of 25 mm dia 2.20 mm thick PVC pipe concealed in roof slab with all required accessories including masonary work all labour chages
Supply and fixing of 20 mm dia 2.10 mm thick PVC pipe concealed in walls with all required accessories including masonary work for light , fan and plug point with metal deep box including all labour chages
Wiring with 2 runs 14/0.3 mm. (1.0. sq.mm) Fire retardant PVC insulated Flexible copper cable in existing pipe with 6A siwtch, ceiling rose and 3 mm thick hyla sheet covering to switch control box including all labour charges etc,., complete for light, bell , fan and exhaust fan points in non - residential building
Wiring with 2 runs 14/0.3 mm. (1.0. sq.mm) Fire retardant PVC insulated Flexible copper cable in existing pipe with 6A modular siwtch control and 3/2 pin sockets fixing on board including all labour charges
supply and run of 2 of 36/0.3 mm. (1.5. sq.mm) Fire retardant PVC insulated Flexible copper cable in existing pipe for mains including all labour charges
supply and run of 1 of 14/0.3 mm. (1.0. sq.mm) Fire retardant PVC insulated Flexible copper cable in existing pipe for earth continuity including all labour charges etc.
supply and run of 4 of 6 sq.mm (7/18) WPSC alluminium cable along with No.10 SWG G.I barer wire through PVC cleats with all accessories including all labour charges etc.,
Providing independent earthing by excavating a trench to a depth of 2.10m in all soils, as per size specied in data ,using 40 mm dia B class GI pipe 2.50m long with necessary accessories with hume pipe ring duly providing staggered holes including filling with equal proportion of salt and charcoal in layers and all labour charges etc complete
Supply and fixing TPN Distribution board with IP-30 protection suitable for 3 phase ELCB / RCCB / FP Isolator as incomer and 10kA SP MCBs as outing going including internal connection and labour charges for surface / flush mounting etc., complete.BLD-ELEC-4.4.3
Supply of 48" (1200mm) Sweep 5 star rated Ceiling Fan , with double ball bearings, air delivery more than 200 cubic meter/min but without Regulator.Makes : Crompton HS Plus / Havells ES Neo/OrientEnergy Star/ Halonix(Zephyr)/Polycab(Synergy Star) unit each
Supply of stepped type Electronic Regulator of Makes: GM G Home / Gold Medal Olive / Million Zoom / Great white Omega/Koncept/Vimal opel/ Anchor/Vihan/CPL
Supply and transportation of 20W, 2000 lumens, T8,1200mm length LED retro tube light,wide operating voltage with double side connection, PF≥0.9,Surge protection: > 2KV, THD<15%, with inbuilt driver and frosted cover CCT: 3000K - 6500K as desired by the department and as per IS specifications, minimum CRI≥80,.etc complete with 5 years warranty.LUMINAIRE MAKE: Phillips / OSRAM / GE / Crompton /VIN / Bajaj / Havells / Halonix / HPL. LED MAKE : PHILIPS LUMILEDS / CREE / NICHIA /OSRAM / SAMSUNG / LG LEDs.. Unit each
Labour charges for Fixing of Ceiling fan and regulator including transportation and giving connections with 23 / 0060 twin core twisted / flat heavy Copper wire etc., complete
Labour charges Fixing of 40W tube light luminaire on wall / Ceiling with 23 / 0060 twin core twisted / flat heavy Copper wire / TW round blocks with all accessories including giving connections and all labour charges etc., complete.
Supply of 2.0 TR 5 Star capable of delivering 24000 BTU/hr and above with operating on refrigerant R-410A / R-32 INVERTER Model Cool type split AC unit with high wall mounted Single Split indoor unit and outdoor condencing unit Hermetically sealed compressor suitable for operation on 230V, 50Hz, 1Phase AC supply capable of performing Heat cool dehumidifying air circulating and filtering with cooling and condensing units with 3 mts of copper piping, insulation kit and 4 mts of 4 core copper flexible chord with cordless remote control etc., dual barrier coating in order to protect coil form oxidigation. Makes: Blue star BAFU-DAFU series / Hitachi / Daikin
Providing & Placing on Terrace (at all floor levels) polyethylene water storage tank with Double layer approved brand & manufacture with cover and suitable locking arrangement & making necessary holes for inlet & outlets and over flow pipes but without fittings & base support for tanks
Supplying and fixing 580mm x 440mm long Orissa pan white glazed Water Closet 1st quality ISI marked confirming to IS:2556-Part-3-1981 with "P" or "S" trap, ISI marked and providing masonry seat, CC squatting plate and 10 litres capacity single flush PVC low level cistern with internal components fixed on 2 Nos. of teak wood blocks of size 76.20mm x 101.60mm using required size of nails, screws as approved by Engineer-in-charge, 15 mm nominal size CP finish brass angled stop valve screw type with internal /external threaded conforming to IS 8931, 12.70mm PVC connection with brass union nuts CP coated , 31.75mm brass plumber union, P trap or S trap of Indian W.C. shall be encased on CC (1:2:4) 150mm alround well above the joint to stop leakage at the joint etc., complete including cost and conveyance of all materials to site, cost of CC bed, labour charges and seigniorage charges, overheads & contractors profit etc., complete for finished item of work
Supplying and fixing Indian make Flat Back Wash Hand Basin 1st quality conforming to IS:2556-Part-4:1972 with waste fittings like rubber plug, chain,32 mm nominal size C.P. Fitting with parallel pipe thread conforming to IS:2963-1979 and fitted with 15 mm nominal bore Chromium Plated Pillar Tap of 1st quality Indian make 400 grams Seiko/ Senior/ Nice/ Esso or equivalent complete with standard CI brackets including wooden block: 550 x 400 mm - Single C.P. Pillar cock ,1 No.12.70mm PVC connection with brass union nuts CP coated , angle stop cock 12.70mm dia. first quality Indian make heavy duty, 31.75mm brass plumber union, 31.75mm dia PVC flexible waste pipe of 914.4mm length of Ist quality including cost and conveyance of all materials to site, labour charges , overheads & contractors profit for finished item of work
Supply of 110 mm dia 3 m single Socket PVC/SWR pipe - 6 Kg/sq.cm - Prince/Sudhakar/Kisan/Supreme or any ISI Brand.
Supply of 110 mm dia - Plain Bend 87.5 Degree - UPVC/SWR Pipe fittings (Prince/Sudhakar/Kisan/Supreme or any ISI Brand)
Supply of 110 mm dia - Coupler - UPVC/SWR Pipe fittings (Prince/Sudhakar/Kisan/Supreme or any ISI Brand
Labour charges for laying, fixing and commissioning the PVC pipes including Supplying & fixing 76.2 mm W.I clamps/ couplers/ bends/ tees etc any diameter including fixing necessary fittings like bends, plugs, couplers, junctions, tees, etc with solvent jointing as per standard practice
Constructing 457.2 mm x 457.2 mm (1'6"x1'6") brick in CM 1:6 prop. Masonry. Inspection chamber up to 914.4 mm (3'0") and fitted with light weight 457.2 mm x 457.2 mm (1'6"x1'6") C.I frame and cover of 20 Kg
S& F GI pipe Medium Grade properties & weight as per IS 1239 ISI mark with GI fittings including the cost of pipe & its fittings & labour charges complete
25 mm dia nominal bore -from tank to jn for of individual lines and inlet
20 mm dia nominal bore -from jn for of individual lines to toilets
15 mm dia nominal bore -for internal
S&F of GI & GM fittings
GM Ball valve with SS Ball and SS Spindle as per IS - Class - I, Indian make heavy type - 25 mm NB Size
GM Ball valve with SS Ball and SS Spindle as per IS - Class - I, Indian make heavy type - 20 mm NB Size
GM Ball valve with SS Ball and SS Spindle as per IS - Class - I, Indian make heavy type - 15 mm NB Size
S&F 12.7 mm N.P bib tap Indian make heavy dutys Seiko/ Senior/ Nice or equivalent
S& F GI union Ist Quality
Laying new Distribution lines zone-I
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH for pipe line trenches etc complete and all labour charges,and other incidental charges etc complete as per ss and as directed by the departemntal officer in charges of work.
Mechanical Means Upto 3 m depth 70%
Manual means 30%
Providing river sand filling brought from approved quarry including cost and conveyance of all material and all labour charges such as filling in layers watering ramming etc complete as per ss and as directed by the departmental officer in chrges of work
Manufacture, supply and delivery of PE 100-PN 6 HDPE pipes confirming to IS 4984-1995 including transportation to work spot, stacking including all taxes etc. complete as per S.S as directed by the departemntal officer in charges of work.
110mm dia.
160mm dia.
200mm dia.
250mm dia.
315 mm dia.
355 mm dia.
Manufacture, supply, & delivery of HDPE fittings conforming to IS 4984 - 1995 including transportation to work spot, stacking excluding all taxes and duties etc.complete
a) Pipe ends - long neck
110mm dia.
160mm dia.
160 mm dia for Air TEEs
200mm dia.
200 mm dia for Air TEEs
250mm dia.
250 mm dia for Air TEEs
315 mm dia.
315 mm dia for Air TEEs
315 mm dia for bulk flow meter
b) MS Flanges
110mm dia.
160mm dia.
160 mm dia for Air TEEs
200mm dia.
200 mm dia for Air TEEs
250mm dia.
250 mm dia for Air TEEs
315 mm dia.
315 mm dia for Air TEEs
315 mm dia for bulk flow meter
c) End Caps
110mm dia.
160mm dia.
200mm dia.
d) Reducers
110X125 mm dia
125x140 mm dia
140x160 mm dia
160x180 mm dia
180x200 mm dia
200x225 mm dia
225x250 mm dia
250x280 mm dia
280x315 mm dia
e) TEES
110mm dia.
160mm dia.
200mm dia.
250mm dia.
315 mm dia.
F)BENDS
110mm dia.
160mm dia.
200mm dia.
250mm dia.
315 mm dia.
Lowering, laying and jointing of HDPE pipes and jointing by butt fusion welding as per IS 7634-part-II/1975 as amended from time to time to the alignment and gradient and testing the pipeline to required pressure etc.complete
110mm dia.
160mm dia.
200mm dia.
250mm dia.
315 mm dia.
355 mm dia.
Supply and delivery of DI Pipes and fittings (Specials) confirming to specification No.I.S.No. 7181/1986, 5531/1988, 3950/1979 excluding GST and other duties including transportation and conveyance to work spot and stacking etc., complete as per S.S and as directed by the departmental authorities.
100X2.00m on 110 dia mains for scours
100X2.00m on 160 dia mains for scours
100x1.00m long DF pipes for sluice valves
150X2.00m on 200 mm dia mains for scours
150X2.00m on 250 mm dia mains for scours
150x1.00m long DF pipes for sluice valves
200x1.00m long DF pipes for sluice valves
250x1.00m long DF pipes for sluice valves
300x1.00m long DF pipes for sluice valves
300x1.00m long DF pipes for for bulk flow meter
Supply and delivery of DI Pipes and fittings (Specials) confirming to specification No.I.S.No. 7181/1986, 5531/1988, 3950/1979 excluding GST and other duties including transportation and conveyance to work spot and stacking etc., complete as per S.S and as directed by the departmental authorities.
supply and delivery of "Resilient Seated Soft Sealing" Gate Valves (Sluice Valves) with Body and Bonnet of Ductile Iron GGG-40/SG-400/15 or GGG-50/SG-500/7 or Equivalent as per IS1865, IS:3896-2 and Wedge fully Rubber Lined with food grade quality grade W270 grade EPDM, Replaceable Spindle Nut without gland packing with 3-O ring protection system on the Shaft and Seals of NBR. The Valves should be Vacuum tight and 100% leak proof with face to face dimensions as BS:5163 Type A/IS:14846. All the valves should be with fusion bonded Electrostatic Powder coating both inside and outside (Min 250 Microns)- RAL 5005 with Pocket Less Straight through body Passage conforming to Design standards of DIN-3202F4/BS:5163 Type A Flange drilling as per IS - 1538 excluding all taxes, duties and including transportation. PN16 - as follows
100 mm distrubution
150mm dia for distrubution
200mm dia for distrubution
250mm dia for distrubution
300mm dia for distrubution
for scour
100mm dia on 110 mm dia mains
100mm dia on 160 mm dia mains
150 mm dia on 200 mm dia lines
Manufacture, supply and delivery of Single Chamber DI Air Valve with Body and cover in Ductile Iron of grade SG 400/12 or equivalent grade as per I.S.3896-part2-1985 and subsequent revisions. All internal parts such as float, shell etc., all cover bolts, of stainless steel, and Gaskets and seals of EPDM food grade quality Epoxy powder coating (EP-P) inside and outside colour blue. Drilled as per IS:1538. PN16 as follows
80 mm dia on 160 mm pipe
80 mm dia on 200 mm pipe
80mm dia 250 mm pipe
80mm dia 315 mm pipe
Labour charges for lowering and keeping in position of D.I. Sluice valves, reflux valves and scour valves. as follows
100 mm distrubution
150mm dia for distrubution
200mm dia for distrubution
250mm dia for distrubution
300mm dia for distrubution
300 mm for bulk flow meter
for scour
100mm dia on 110 mm dia mains
100mm dia on 160 mm dia mains
150 mm dia on 200 mm dia lines
Labour charges for fixing Kinetic Air Valves with isolating Sluice valves, Double Air valves/ Air Cushion valve excluding cost of jointing materials such as bolts, nuts and rubber insertions etc., complete.
Construction of sluice and scour Valve Chamber as per type design drawing with RCC including, plastering, RCC cover slabs etc. including cost and conveyance of all material and all labour charges etc. complete as per S.S for finished item of work
100 mm distrubution
150mm dia for distrubution
200mm dia for distrubution
250mm dia for distrubution
300mm dia for distrubution
300 mm for bulk flow meter
for scour
100mm dia on 110 mm dia mains
100mm dia on 160 mm dia mains
150 mm dia on 200 mm dia lines
Construction of Air Valve Chamber as per type design drawing with RCC including, plastering, RCC cover slabs etc. including cost and conveyance of all material and all labour charges etc. complete as per S.S for finished item of work
80 mm dia on 160 mm pipe
80 mm dia on 200 mm pipe
80mm dia 250 mm pipe
80mm dia 315 mm pipe
Lowering the C.I. Pipes, D.I. Pipes of all classes and fittings with flanged ends carefully into the trenches and laying them true to alignment and gradient including all sundries, but excluding conveyance from source of supply as per BIS No.3114/94.
150 mm dia
200 mm dia
250 mm dia
300 mm dia
Jointing the C.I. Pipes, fittings and valves with flanged ends including cost of jointing materials such as bolts, nuts, rubber insertion, white lead and including filling with water with a water lead upto 500 m and testing to required pressure etc., comp as per BIS No.3114/85.
80 mm dia
100 mm dia
150 mm dia
200 mm dia
250 mm dia
300 mm dia
Cutting BT road surface as well as asphalt (75mm thick) including water bound. The rate including labour charges for cutting, incidental charges etc., complete as directed by the departmental officer in charge of the work.
Cutting the CC road surface. The rate including labour charges for cutting, incidental charges etc., complete as directed by the departmental officer in charge of the work.
Cutting the open water bound macadam. The rate including labour charges for cutting, incidental charges etc., complete as directed by the departmental officer in charge of the work.
Filling crushur stone dust in pipe line trenches as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH
Using Concrete mixture up to Plinth Level : Plain Cement concrete nominal mix M-30 (Cement : fine aggregate: coarse aggregate ) using 20mm size Hard Granite Machine Crushed Graded Metal including cost and conveyance of all materials like cement, sand, coarse aggregate water etc., to site , seigniorage charges on all materials, labour charges , for mixing , laying, concrete , ramming in 15 cm layers, finishing top surface to the required level curing etc., complete for finished item of work with nomonal reinforcement for Road restoration. for BT&CC roads
Laying new Distribution lines zone-II
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH for pipe line trenches
Mechanical Means Upto 3 m depth 70%
Manual means 30%
Providing bedding with sand for pipelines trencehs as per specification and drawing including cost and conveyance of materials to site with all leads, lifts including watering, tamping, ramming, labour charges, all other incidental and operational charges etc., complete as per detailed specification and directed by the Engineer - in - Charge
Manufacture, supply and delivery of PE 100-PN 6 HDPE pipes confirming to IS 4984-1995 including transportation to work spot, stacking including all taxes etc. complete as per S.S as follows
110mm dia.
160mm dia.
200mm dia.
250mm dia.
315 mm dia.
355 mm dia.
Manufacture, supply, & delivery of HDPE fittings conforming to IS 4984 - 1995 including transportation to work spot, stacking excluding all taxes and duties etc.complete as follows
a) Pipe ends - long neck
110mm dia.
160mm dia.
160 mm dia for Air TEEs
200mm dia.
200 mm dia for Air TEEs
250mm dia.
250 mm dia for Air TEEs
315 mm dia.
315 mm dia for Air TEEs
355 mm dia for bulk flow meter
355 mm dia
355 mm dia for Air TEEs
b) MS Flanges
110mm dia.
160mm dia.
160 mm dia for Air TEEs
200mm dia.
200 mm dia for Air TEEs
250mm dia.
250 mm dia for Air TEEs
315 mm dia.
315 mm dia for Air TEEs
355 mm dia for bulk flow meter
355 mm dia
355 mm dia for Air TEEs
c) End Caps
110mm dia.
160mm dia.
200mm dia.
250mm dia.
315 mm dia.
d) Reducers
110X125 mm dia
125x140 mm dia
140x160 mm dia
160x180 mm dia
180x200 mm dia
200x225 mm dia
225x250 mm dia
250x280 mm dia
280x315 mm dia
315x355 mm dia
e) TEES
110mm dia.
160mm dia.
200mm dia.
250mm dia.
315 mm dia.
355 mm dia
F)BENDS
110mm dia.
160mm dia.
200mm dia.
250mm dia.
315 mm dia.
355 mm dia
Lowering, laying and jointing of HDPE pipes and jointing by butt fusion welding as per IS 7634-part-II/1975 as amended from time to time to the alignment and gradient and testing the pipeline to required pressure etc.complete as follows
110mm dia.
160mm dia.
200mm dia.
250mm dia.
315 mm dia.
355 mm dia.
Supply and delivery of DI Pipes and fittings (Specials) confirming to specification No.I.S.No. 7181/1986, 5531/1988, 3950/1979 excluding GST and other duties including transportation and conveyance to work spot and stacking etc., complete as per S.S and as directed by the departmental authorities.
DIDF pipes for scours
100X2.00m on 110 dia mains for scours
100X2.00m on 160 dia mains for scours
100x1.00m long DF pipes for sluice valves
150x1.00m long DF pipes for sluice valves
200x1.00m long DF pipes for sluice valves
250x1.00m long DF pipes for sluice valves
300x1.00m long DF pipes for sluice valves
350x1.00m long DF pipes for for bulk flow meter
350x1.00m long DF pipes for sluice valves
Supply and delivery of DI Pipes and fittings (Specials) confirming to specification No.I.S.No. 7181/1986, 5531/1988, 3950/1979 excluding GST and other duties including transportation and conveyance to work spot and stacking etc., complete as per S.S and as directed by the departmental authorities.
supply and delivery of "Resilient Seated Soft Sealing" Gate Valves (Sluice Valves) with Body and Bonnet of Ductile Iron GGG-40/SG-400/15 or GGG-50/SG-500/7 or Equivalent as per IS1865, IS:3896-2 and Wedge fully Rubber Lined with food grade quality grade W270 grade EPDM, Replaceable Spindle Nut without gland packing with 3-O ring protection system on the Shaft and Seals of NBR. The Valves should be Vacuum tight and 100% leak proof with face to face dimensions as BS:5163 Type A/IS:14846. All the valves should be with fusion bonded Electrostatic Powder coating both inside and outside (Min 250 Microns)- RAL 5005 with Pocket Less Straight through body Passage conforming to Design standards of DIN-3202F4/BS:5163 Type A Flange drilling as per IS - 1538 excluding all taxes, duties and including transportation. PN16 -
100 mm distrubution
150mm dia for distrubution
200mm dia for distrubution
250mm dia for distrubution
300mm dia for distrubution
350mm dia for distrubution
for scour
100mm dia on 110 mm dia mains
100mm dia on 160 mm dia mains
150 mm dia on 200 mm dia lines
150 mm dia on 250 mm dia lines
Manufacture, supply and delivery of Single Chamber DI Air Valve with Body and cover in Ductile Iron of grade SG 400/12 or equivalent grade as per I.S.3896-part2-1985 and subsequent revisions. All internal parts such as float, shell etc., all cover bolts, of stainless steel, and Gaskets and seals of EPDM food grade quality Epoxy powder coating (EP-P) inside and outside colour blue. Drilled as per IS:1538. PN16
80 mm dia on 160 mm pipe
80 mm dia on 200 mm pipe
80mm dia 250 mm pipe
80mm dia 315 mm pipe
80mm dia 355 mm pipe
Labour charges for lowering and keeping in position of D.I. Sluice valves, reflux valves and scour valves.
100 mm distrubution
150mm dia for distrubution
200mm dia for distrubution
250mm dia for distrubution
300mm dia for distrubution
350mm dia for distrubution
350mm dia for bulk flow meter
for scour
100mm dia on 110 mm dia mains
100mm dia on 160 mm dia mains
Labour charges for fixing Kinetic Air Valves with isolating Sluice valves, Double Air valves/ Air Cushion valve excluding cost of jointing materials such as bolts, nuts and rubber insertions etc., complete.
Construction of sluice and scour Valve Chamber as per type design drawing with RCC including, plastering, RCC cover slabs etc. including cost and conveyance of all material and all labour charges etc. complete as per S.S for finished item of work as follows
100 mm distrubution
150mm dia for distrubution
200mm dia for distrubution
250mm dia for distrubution
300mm dia for distrubution
350mm dia for distrubution
350mm dia for bulk flow meter
for scour
100mm dia on 110 mm dia mains
100mm dia on 160 mm dia mains
Construction of Air Valve Chamber as per type design drawing with RCC including, plastering, RCC cover slabs etc. including cost and conveyance of all material and all labour charges etc. complete as per S.S for finished item of work as follows
80 mm dia on 160 mm pipe
80 mm dia on 200 mm pipe
80mm dia 250 mm pipe
80mm dia 315 mm pipe
80mm dia 355 mm pipe
Lowering the C.I. Pipes, D.I. Pipes of all classes and fittings with flanged ends carefully into the trenches and laying them true to alignment and gradient including all sundries, but excluding conveyance from source of supply as per BIS No.3114/94.as follows
150 mm dia
200 mm dia
250 mm dia
300 mm dia
350 mm dia
Jointing the C.I. Pipes, fittings and valves with flanged ends including cost of jointing materials such as bolts, nuts, rubber insertion, white lead and including filling with water with a water lead upto 500 m and testing to required pressure etc., comp as per BIS No.3114/85.as follows
80 mm dia
100 mm dia
150 mm dia
200 mm dia
250 mm dia
300 mm dia
350 mm dia
Cutting BT road surface as well as asphalt (75mm thick) including water bound. The rate including labour charges for cutting, incidental charges etc., complete as directed by the departmental officer in charge of the work.
Cutting the CC road surface. The rate including labour charges for cutting, incidental charges etc., complete as directed by the departmental officer in charge of the work.
Cutting the open water bound macadam. The rate including labour charges for cutting, incidental charges etc., complete as directed by the departmental officer in charge of the work.
Filling crushur stone dust in pipe line trenches as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH
Using Concrete mixture up to Plinth Level : Plain Cement concrete nominal mix M-30 (Cement : fine aggregate: coarse aggregate ) using 20mm size Hard Granite Machine Crushed Graded Metal including cost and conveyance of all materials like cement, sand, coarse aggregate water etc., to site , seigniorage charges on all materials, labour charges , for mixing , laying, concrete , ramming in 15 cm layers, finishing top surface to the required level curing etc., complete for finished item of work with nomonal reinforcement for Road restoration. for BT&CC roads
Laying new Distribution lines zone-III
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH for pipe line trenches
Mechanical Means Upto 3 m depth 70%
Manual means 30%
Providing bedding with sand for pipelines trencehs as per specification and drawing including cost and conveyance of materials to site with all leads, lifts including watering, tamping, ramming, labour charges, all other incidental and operational charges etc., complete as per detailed specification and directed by the Engineer - in - Charge
Manufacture, supply and delivery of PE 100-PN 6 HDPE pipes confirming to IS 4984-1995 including transportation to work spot, stacking including all taxes etc. complete as per S.S as follows
110mm dia.
160mm dia.
200mm dia.
250mm dia.
315 mm dia.
355 mm dia.
Manufacture, supply, & delivery of HDPE fittings conforming to IS 4984 - 1995 including transportation to work spot, stacking excluding all taxes and duties etc.complete as follows
a) Pipe ends - long neck
110mm dia.
160mm dia.
160 mm dia for Air TEEs
200mm dia.
200 mm dia for Air TEEs
250mm dia.
250 mm dia for Air TEEs
315 mm dia.
315 mm dia for Air TEEs
315 mm dia for bulk flow meter
b) MS Flanges
110mm dia.
160mm dia.
160 mm dia for Air TEEs
200mm dia.
200 mm dia for Air TEEs
250mm dia.
250 mm dia for Air TEEs
315 mm dia.
315 mm dia for Air TEEs
315 mm dia for bulk flow meter
c) End Caps
110mm dia.
160mm dia.
200mm dia.
d) Reducers
110X125 mm dia
125x140 mm dia
140x160 mm dia
160x180 mm dia
180x200 mm dia
200x225 mm dia
225x250 mm dia
250x280 mm dia
280x315 mm dia
e) TEES
110mm dia.
160mm dia.
200mm dia.
250mm dia.
315 mm dia.
F)BENDS
110mm dia.
160mm dia.
200mm dia.
250mm dia.
315 mm dia.
355 mm dia
Lowering, laying and jointing of HDPE pipes and jointing by butt fusion welding as per IS 7634-part-II/1975 as amended from time to time to the alignment and gradient and testing the pipeline to required pressure etc.complete as follows
110mm dia.
160mm dia.
200mm dia.
250mm dia.
315 mm dia.
Supply and delivery of DI Pipes and fittings (Specials) confirming to specification No.I.S.No. 7181/1986, 5531/1988, 3950/1979 excluding GST and other duties including transportation and conveyance to work spot and stacking etc., complete as per S.S and as directed by the departmental authorities.
100X2.00m on 110 dia mains for scours
100x1.00m long DF pipes for sluice valves
150X2.00m on 200 mm dia mains for scours
150x1.00m long DF pipes for sluice valves
200x1.00m long DF pipes for sluice valves
250x1.00m long DF pipes for sluice valves
300x1.00m long DF pipes for sluice valves
300x1.00m long DF pipes for for bulk flow meter
Supply and delivery of DI Pipes and fittings (Specials) confirming to specification No.I.S.No. 7181/1986, 5531/1988, 3950/1979 excluding GST and other duties including transportation and conveyance to work spot and stacking etc., complete as per S.S and as directed by the departmental authorities.
supply and delivery of "Resilient Seated Soft Sealing" Gate Valves (Sluice Valves) with Body and Bonnet of Ductile Iron GGG-40/SG-400/15 or GGG-50/SG-500/7 or Equivalent as per IS1865, IS:3896-2 and Wedge fully Rubber Lined with food grade quality grade W270 grade EPDM, Replaceable Spindle Nut without gland packing with 3-O ring protection system on the Shaft and Seals of NBR. The Valves should be Vacuum tight and 100% leak proof with face to face dimensions as BS:5163 Type A/IS:14846. All the valves should be with fusion bonded Electrostatic Powder coating both inside and outside (Min 250 Microns)- RAL 5005 with Pocket Less Straight through body Passage conforming to Design standards of DIN-3202F4/BS:5163 Type A Flange drilling as per IS - 1538 excluding all taxes, duties and including transportation. PN16 - as follows
100 mm distrubution
150mm dia for distrubution
200mm dia for distrubution
250mm dia for distrubution
300mm dia for distrubution
for scour
100mm dia on 110 mm dia mains
150 mm dia on 200 mm dia lines
150 mm dia on 250 mm dia lines
Manufacture, supply and delivery of Single Chamber DI Air Valve with Body and cover in Ductile Iron of grade SG 400/12 or equivalent grade as per I.S.3896-part2-1985 and subsequent revisions. All internal parts such as float, shell etc., all cover bolts, of stainless steel, and Gaskets and seals of EPDM food grade quality Epoxy powder coating (EP-P) inside and outside colour blue. Drilled as per IS:1538. PN16 as follows
80 mm dia on 160 mm pipe
80 mm dia on 200 mm pipe
80mm dia 250 mm pipe
80mm dia 315 mm pipe
Labour charges for lowering and keeping in position of D.I. Sluice valves, reflux valves and scour valves. as follows
100 mm distrubution
150mm dia for distrubution
200mm dia for distrubution
250mm dia for distrubution
300mm dia for distrubution
300 mm for bulk flow meter
for scour
100mm dia on 110 mm dia mains
100mm dia on 160 mm dia mains
150 mm dia on 200 mm dia lines
150 mm dia on 250 mm dia lines
Labour charges for fixing Kinetic Air Valves with isolating Sluice valves, Double Air valves/ Air Cushion valve excluding cost of jointing materials such as bolts, nuts and rubber insertions etc., complete.
Construction of sluice and scour Valve Chamber as per type design drawing with RCC including, plastering, RCC cover slabs etc. including cost and conveyance of all material and all labour charges etc. complete as per S.S for finished item of work as follows
100 mm distrubution
150mm dia for distrubution
200mm dia for distrubution
250mm dia for distrubution
300mm dia for distrubution
300 mm for bulk flow meter
for scour
100mm dia on 110 mm dia mains
150 mm dia on 200 mm dia lines
Construction of Air Valve Chamber as per type design drawing with RCC including, plastering, RCC cover slabs etc. including cost and conveyance of all material and all labour charges etc. complete as per S.S for finished item of work as follows
80 mm dia on 160 mm pipe
80 mm dia on 200 mm pipe
80mm dia 250 mm pipe
80mm dia 315 mm pipe
Lowering the C.I. Pipes, D.I. Pipes of all classes and fittings with flanged ends carefully into the trenches and laying them true to alignment and gradient including all sundries, but excluding conveyance from source of supply as per BIS No.3114/94.as follows
150 mm dia
200 mm dia
250 mm dia
300 mm dia
Jointing the C.I. Pipes, fittings and valves with flanged ends including cost of jointing materials such as bolts, nuts, rubber insertion, white lead and including filling with water with a water lead upto 500 m and testing to required pressure etc., comp as per BIS No.3114/85.as follows
80 mm dia
100 mm dia
150 mm dia
200 mm dia
250 mm dia
300 mm dia
Cutting BT road surface as well as asphalt (75mm thick) including water bound. The rate including labour charges for cutting, incidental charges etc., complete as directed by the departmental officer in charge of the work.
Cutting the CC road surface. The rate including labour charges for cutting, incidental charges etc., complete as directed by the departmental officer in charge of the work.
Cutting the open water bound macadam. The rate including labour charges for cutting, incidental charges etc., complete as directed by the departmental officer in charge of the work.
Filling crushur stone dust in pipe line trenches as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH
Using Concrete mixture up to Plinth Level : Plain Cement concrete nominal mix M-30 (Cement : fine aggregate: coarse aggregate ) using 20mm size Hard Granite Machine Crushed Graded Metal including cost and conveyance of all materials like cement, sand, coarse aggregate water etc., to site , seigniorage charges on all materials, labour charges , for mixing , laying, concrete , ramming in 15 cm layers, finishing top surface to the required level curing etc., complete for finished item of work with nomonal reinforcement for Road restoration. for BT&CC roads
Laying new Distribution lines zone-IV
Earthwork in excavation for structures as per drawing and technical specifications Clause 305.1 including setting out, construction of shoring and bracing, removal of stumps and other deleterious material and disposal upto a lead of 50 m, dressing of sides and bottom and backfilling in trenches with excavated suitable material as per Technical Specification 305 MORD / 304 MORTH for pipe line trenches
Mechanical Means Upto 3 m depth 70%
Manual means 30%
Providing bedding with sand for pipelines trencehs as per specification and drawing including cost and conveyance of materials to site with all leads, lifts including watering, tamping, ramming, labour charges, all other incidental and operational charges etc., complete as per detailed specification and directed by the Engineer - in - Charge
Manufacture, supply and delivery of PE 100-PN 6 HDPE pipes confirming to IS 4984-1995 including transportation to work spot, stacking including all taxes etc. complete as per S.S as follows
110mm dia.
160mm dia.
250mm dia.
315 mm dia.
Manufacture, supply, & delivery of HDPE fittings conforming to IS 4984 - 1995 including transportation to work spot, stacking excluding all taxes and duties etc.complete as follows
a) Pipe ends - long neck
110mm dia.
160mm dia.
160 mm dia for Air TEEs
250mm dia.
250 mm dia for Air TEEs
315 mm dia.
315 mm dia for Air TEEs
315 mm dia for bulk flow meter
b) MS Flanges
110mm dia.
160mm dia.
160 mm dia for Air TEEs
250mm dia.
250 mm dia for Air TEEs
315 mm dia.
315 mm dia for Air TEEs
315 mm dia for bulk flow meter
c) End Caps
110mm dia.
160mm dia.
d) Reducers
110X125 mm dia
125x140 mm dia
140x160 mm dia
160x180 mm dia
180x200 mm dia
200x225 mm dia
225x250 mm dia
250x280 mm dia
280x315 mm dia
e) TEES
110mm dia.
160mm dia.
250mm dia.
315 mm dia.
F)BENDS
110mm dia.
160mm dia.
250mm dia.
315 mm dia.
Lowering, laying and jointing of HDPE pipes and jointing by butt fusion welding as per IS 7634-part-II/1975 as amended from time to time to the alignment and gradient and testing the pipeline to required pressure etc.complete as follows
110mm dia.
160mm dia.
200mm dia.
250mm dia.
315 mm dia.
Supply and delivery of DI Pipes and fittings (Specials) confirming to specification No.I.S.No. 7181/1986, 5531/1988, 3950/1979 excluding GST and other duties including transportation and conveyance to work spot and stacking etc., complete as per S.S and as directed by the departmental authorities.
100X2.00m on 110 dia mains for scours
100X2.00m on 160 dia mains for scours
100x1.00m long DF pipes for sluice valves
150x1.00m long DF pipes for sluice valves
250x1.00m long DF pipes for sluice valves
300x1.00m long DF pipes for sluice valves
300x1.00m long DF pipes for for bulk flow meter
Supply and delivery of DI Pipes and fittings (Specials) confirming to specification No.I.S.No. 7181/1986, 5531/1988, 3950/1979 excluding GST and other duties including transportation and conveyance to work spot and stacking etc., complete as per S.S and as directed by the departmental authorities.
supply and delivery of "Resilient Seated Soft Sealing" Gate Valves (Sluice Valves) with Body and Bonnet of Ductile Iron GGG-40/SG-400/15 or GGG-50/SG-500/7 or Equivalent as per IS1865, IS:3896-2 and Wedge fully Rubber Lined with food grade quality grade W270 grade EPDM, Replaceable Spindle Nut without gland packing with 3-O ring protection system on the Shaft and Seals of NBR. The Valves should be Vacuum tight and 100% leak proof with face to face dimensions as BS:5163 Type A/IS:14846. All the valves should be with fusion bonded Electrostatic Powder coating both inside and outside (Min 250 Microns)- RAL 5005 with Pocket Less Straight through body Passage conforming to Design standards of DIN-3202F4/BS:5163 Type A Flange drilling as per IS - 1538 excluding all taxes, duties and including transportation. PN16 - as follows
100 mm distrubution
150mm dia for distrubution
250mm dia for distrubution
300mm dia for distrubution
for scour
100mm dia on 110 mm dia mains
100mm dia on 160 mm dia mains
150 mm dia on 200 mm dia lines
150 mm dia on 250 mm dia lines
Manufacture, supply and delivery of Single Chamber DI Air Valve with Body and cover in Ductile Iron of grade SG 400/12 or equivalent grade as per I.S.3896-part2-1985 and subsequent revisions. All internal parts such as float, shell etc., all cover bolts, of stainless steel, and Gaskets and seals of EPDM food grade quality Epoxy powder coating (EP-P) inside and outside colour blue. Drilled as per IS:1538. PN16 as follows
80 mm dia on 160 mm pipe
80mm dia 250 mm pipe
80mm dia 315 mm pipe
Labour charges for lowering and keeping in position of D.I. Sluice valves, reflux valves and scour valves.
100 mm distrubution
150mm dia for distrubution
250mm dia for distrubution
300mm dia for distrubution
300 mm for bulk flow meter
for scour
100mm dia on 110 mm dia mains
100mm dia on 160 mm dia mains
Labour charges for fixing Kinetic Air Valves with isolating Sluice valves, Double Air valves/ Air Cushion valve excluding cost of jointing materials such as bolts, nuts and rubber insertions etc., complete.
Construction of sluice and scour Valve Chamber as per type design drawing with RCC including, plastering, RCC cover slabs etc. including cost and conveyance of all material and all labour charges etc. complete as per S.S for finished item of work as follows
100 mm distrubution
150mm dia for distrubution
250mm dia for distrubution
300mm dia for distrubution
300 mm for bulk flow meter
for scour
100mm dia on 110 mm dia mains
100mm dia on 160 mm dia mains
Construction of Air Valve Chamber as per type design drawing with RCC including, plastering, RCC cover slabs etc. including cost and conveyance of all material and all labour charges etc. complete as per S.S for finished item of work as follows
80 mm dia on 160 mm pipe
80mm dia 250 mm pipe
80mm dia 315 mm pipe
Lowering the C.I. Pipes, D.I. Pipes of all classes and fittings with flanged ends carefully into the trenches and laying them true to alignment and gradient including all sundries, but excluding conveyance from source of supply as per BIS No.3114/94.as follows
150 mm dia
250 mm dia
300 mm dia
Jointing the C.I. Pipes, fittings and valves with flanged ends including cost of jointing materials such as bolts, nuts, rubber insertion, white lead and including filling with water with a water lead upto 500 m and testing to required pressure etc., comp as per BIS No.3114/85.as follows
80 mm dia
100 mm dia
150 mm dia
250 mm dia
300 mm dia
Cutting BT road surface as well as asphalt (75mm thick) including water bound. The rate including labour charges for cutting, incidental charges etc., complete as directed by the departmental officer in charge of the work.
Cutting the CC road surface. The rate including labour charges for cutting, incidental charges etc., complete as directed by the departmental officer in charge of the work.
Cutting the open water bound macadam. The rate including labour charges for cutting, incidental charges etc., complete as directed by the departmental officer in charge of the work.
Filling crushur stone dust in pipe line trenches as per drawing and technical specification Clause 305.3.9 MORD & 304 MORTH
Using Concrete mixture up to Plinth Level : Plain Cement concrete nominal mix M-30 (Cement : fine aggregate: coarse aggregate ) using 20mm size Hard Granite Machine Crushed Graded Metal including cost and conveyance of all materials like cement, sand, coarse aggregate water etc., to site , seigniorage charges on all materials, labour charges , for mixing , laying, concrete , ramming in 15 cm layers, finishing top surface to the required level curing etc., complete for finished item of work with nomonal reinforcement for Road restoration. for BT&CC roads
Providing & Shifiting of house service connections at house holds side in earthern roads
Providing house service connections on HDPE mains at House hold side in Earthen Roads with Earthwork Excavation in all type of soils fixing PP Saddle,PP Clamp Saddle shall be manufactured by injection moulding using virigin Polypropylene,Mechanical tapping saddles for water works purposes and designed for use with PVC/PE pipe as per IS 4985/IS 4984 respectively. These saddles should be contoured to fit around the pipe. PP saddles shall be Blue/Black moulded-in with Nickel plated Brass / SS 304 metal female threaded outlets. Seal shall be thermoplastic elastomer rubber suitable for drinking water and nut-bolt-washer with SS. The PP Clamp saddle fittings shall be mouldedwith SS 304/Nickel plated Brass female threaded outlet inserted to connect necessary fittings. Thread dimension shall conform to IS-554/ISO-7. Adequate thickness of PP shall be provided to hold brass insert in place and avoid leakage while pressure applications. Fasteners shall be threaded type, with SS. Fasteners of size 125mm and above. The grade of raw material used must be certified by WRAS, UK for type test as per BS 6920 from their certified laboratories like NSF International Ltd. UK and certificate of Compliance to be produced for the following parameters: i) Odour&Flavour of water ii) Appearance of water iii) Growth of Micro Organismaxes etc,FOR main pipes Hdpe /PVC of 110mm dia .flow control valve SS 316 NRV 10 LPM ,Compression adaptor with one side compression end to suit 1/2 "to1''(15mmOD to25 mm OD) MDPE pipe and other side with female threaded with SS-304 material inserts of sizes 1/2" BSP threads,body,nut, and cap of poly propylene,clip ring PP Compression Metal insert female Threaded Adaptorcompression adaptor with one side compression end to suit 1/2'' to 1'' mdpe pipe and other side with female thread with ss-304 material inserts of sizes 1/2'' BSP thread,PP compression elbow to suit 1/2 " to 1'' (15mm OD to 25 mm OD) MDPE pipe body, nuts, and caps of polypropelene, clip ring of POM(Acetylic resin) and and "O" ring of NBR material,as per ISO 14236 standardsDouble compression elbow to suit 20mm OD for 100mm, MDPE PE80 Blue pipe as per ISO 4427 up to date 1. for conveyance of potable water ,MDPE 20mm OD pipe (2.00 m avg length for each of 1/2'' HSC) of SDR 9-PN-16 for pipes side,Premium make UPVC Pipes with Fittings.(IS 4985/2000)(PH SSR :20) UPVC pipe for 40 mm (Casing for drain crossing)fixing of 12.7 mm brass bib cock indian make heavy duty long bodyFixing of House service connections,including fixing of ferrule, MDPE/GI pipes and specials and connecting newly laid pipe (For HDPE / PVC Pipes)Making Holes upto 18 mm Dia in RCC/any Stones up to 50 mm Thick( BMS-W78)Fixing of 25.4 mm Holder Back Clamps at Drain Crossing this rate cost of above all materials ,Including all Labour Charges ,other incidental charges etc for finished item of work and as directed by the departmental officer in charge of work
Fixing of House service connections,including fixing of ferrule, MDPE/GI pipes and specials and connecting newly laid pipe including labour charges,hire charges etc complete (For HDPE / PVC Pipes) ( supplied items)
Providing & Shifiting of house service connections at other side in earthern roads
Providing house service connections on HDPE mains at other side in Earthen Roads with Earthwork Excavation in all type of soils fixing PP Saddle,PP Clamp Saddle shall be manufactured by injection moulding using virigin Polypropylene,Mechanical tapping saddles for water works purposes and designed for use with PVC/PE pipe as per IS 4985/IS 4984 respectively. These saddles should be contoured to fit around the pipe. PP saddles shall be Blue/Black moulded-in with Nickel plated Brass / SS 304 metal female threaded outlets. Seal shall be thermoplastic elastomer rubber suitable for drinking water and nut-bolt-washer with SS. The PP Clamp saddle fittings shall be mouldedwith SS 304/Nickel plated Brass female threaded outlet inserted to connect necessary fittings. Thread dimension shall conform to IS-554/ISO-7. Adequate thickness of PP shall be provided to hold brass insert in place and avoid leakage while pressure applications. Fasteners shall be threaded type, with SS. Fasteners of size 125mm and above. The grade of raw material used must be certified by WRAS, UK for type test as per BS 6920 from their certified laboratories like NSF International Ltd. UK and certificate of Compliance to be produced for the following parameters: i) Odour&Flavour of water ii) Appearance of water iii) Growth of Micro Organismaxes etc,FOR main pipes Hdpe /PVC of 110mm dia .flow control valve SS 316 NRV 10 LPM ,Compression adaptor with one side compression end to suit 1/2 "to1''(15mmOD to25 mm OD) MDPE pipe and other side with female threaded with SS-304 material inserts of sizes 1/2" BSP threads,body,nut, and cap of poly propylene,clip ring PP Compression Metal insert female Threaded Adaptorcompression adaptor with one side compression end to suit 1/2'' to 1'' mdpe pipe and other side with female thread with ss-304 material inserts of sizes 1/2'' BSP thread,PP compression elbow to suit 1/2 " to 1'' (15mm OD to 25 mm OD) MDPE pipe body, nuts, and caps of polypropelene, clip ring of POM(Acetylic resin) and and "O" ring of NBR material,as per ISO 14236 standardsDouble compression elbow to suit 20mm OD for 100mm, MDPE PE80 Blue pipe as per ISO 4427 up to date 1. for conveyance of potable water ,MDPE 20mm OD pipe (2.00 m avg length for each of 1/2'' HSC) of SDR 9-PN-16 for pipes side,Premium make UPVC Pipes with Fittings.(IS 4985/2000)(PH SSR :20) UPVC pipe for 40 mm (Casing for drain crossing)fixing of 12.7 mm brass bib cock indian make heavy duty long bodyFixing of House service connections,including fixing of ferrule, MDPE/GI pipes and specials and connecting newly laid pipe (For HDPE / PVC Pipes)Making Holes upto 18 mm Dia in RCC/any Stones up to 50 mm Thick( BMS-W78)Fixing of 25.4 mm Holder Back Clamps at Drain Crossing this rate cost of above all materials ,Including all Labour Charges ,other incidental charges etc for finished item of work and as directed by the departmental officer in charge of work
Fixing of House service connections,including fixing of ferrule, MDPE/GI pipes and specials and connecting newly laid pipe including labour charges,hire charges etc complete (For HDPE / PVC Pipes) ( supplied items)
Providing & Shifiting of house service connections at HH side in BT &CC roads
Providing house service connections on HDPE mains at other side in B.T & CC Roads with Earthwork Excavation in all type of soils fixing PP Saddle,PP Clamp Saddle shall be manufactured by injection moulding using virigin Polypropylene,Mechanical tapping saddles for water works purposes and designed for use with PVC/PE pipe as per IS 4985/IS 4984 respectively. These saddles should be contoured to fit around the pipe. PP saddles shall be Blue/Black moulded-in with Nickel plated Brass / SS 304 metal female threaded outlets. Seal shall be thermoplastic elastomer rubber suitable for drinking water and nut-bolt-washer with SS. The PP Clamp saddle fittings shall be mouldedwith SS 304/Nickel plated Brass female threaded outlet inserted to connect necessary fittings. Thread dimension shall conform to IS-554/ISO-7. Adequate thickness of PP shall be provided to hold brass insert in place and avoid leakage while pressure applications. Fasteners shall be threaded type, with SS. Fasteners of size 125mm and above. The grade of raw material used must be certified by WRAS, UK for type test as per BS 6920 from their certified laboratories like NSF International Ltd. UK and certificate of Compliance to be produced for the following parameters: i) Odour&Flavour of water ii) Appearance of water iii) Growth of Micro Organismaxes etc,FOR main pipes Hdpe /PVC of 110mm dia .flow control valve SS 316 NRV 10 LPM ,Compression adaptor with one side compression end to suit 1/2 "to1''(15mmOD to25 mm OD) MDPE pipe and other side with female threaded with SS-304 material inserts of sizes 1/2" BSP threads,body,nut, and cap of poly propylene,clip ring PP Compression Metal insert female Threaded Adaptorcompression adaptor with one side compression end to suit 1/2'' to 1'' mdpe pipe and other side with female thread with ss-304 material inserts of sizes 1/2'' BSP thread,PP compression elbow to suit 1/2 " to 1'' (15mm OD to 25 mm OD) MDPE pipe body, nuts, and caps of polypropelene, clip ring of POM(Acetylic resin) and and "O" ring of NBR material,as per ISO 14236 standardsDouble compression elbow to suit 20mm OD for 100mm, MDPE PE80 Blue pipe as per ISO 4427 up to date 1. for conveyance of potable water ,MDPE 20mm OD pipe (2.00 m avg length for each of 1/2'' HSC) of SDR 9-PN-16 for pipes side,Premium make UPVC Pipes with Fittings.(IS 4985/2000)(PH SSR :20) UPVC pipe for 40 mm (Casing for drain crossing)fixing of 12.7 mm brass bib cock indian make heavy duty long bodyFixing of House service connections,including fixing of ferrule, MDPE/GI pipes and specials and connecting newly laid pipe (For HDPE / PVC Pipes)Making Holes upto 18 mm Dia in RCC/any Stones up to 50 mm Thick( BMS-W78)Fixing of 25.4 mm Holder Back Clamps at Drain Crossing this rate cost of above all materials ,Including all Labour Charges ,other incidental charges etc for finished item of work and as directed by the departmental officer in charge of work
Fixing of House service connections,including fixing of ferrule, MDPE/GI pipes and specials and connecting newly laid pipe including labour charges,hire charges etc complete (For HDPE / PVC Pipes) ( supplied items)
Providing & Shifiting of house service connections at other side in BT &CC roads
Providing house service connections on HDPE mains at House hold side in B.T & CC Roads with Earthwork Excavation in all type of soils fixing PP Saddle,PP Clamp Saddle shall be manufactured by injection moulding using virigin Polypropylene,Mechanical tapping saddles for water works purposes and designed for use with PVC/PE pipe as per IS 4985/IS 4984 respectively. These saddles should be contoured to fit around the pipe. PP saddles shall be Blue/Black moulded-in with Nickel plated Brass / SS 304 metal female threaded outlets. Seal shall be thermoplastic elastomer rubber suitable for drinking water and nut-bolt-washer with SS. The PP Clamp saddle fittings shall be mouldedwith SS 304/Nickel plated Brass female threaded outlet inserted to connect necessary fittings. Thread dimension shall conform to IS-554/ISO-7. Adequate thickness of PP shall be provided to hold brass insert in place and avoid leakage while pressure applications. Fasteners shall be threaded type, with SS. Fasteners of size 125mm and above. The grade of raw material used must be certified by WRAS, UK for type test as per BS 6920 from their certified laboratories like NSF International Ltd. UK and certificate of Compliance to be produced for the following parameters: i) Odour&Flavour of water ii) Appearance of water iii) Growth of Micro Organismaxes etc,FOR main pipes Hdpe /PVC of 110mm dia .flow control valve SS 316 NRV 10 LPM ,Compression adaptor with one side compression end to suit 1/2 "to1''(15mmOD to25 mm OD) MDPE pipe and other side with female threaded with SS-304 material inserts of sizes 1/2" BSP threads,body,nut, and cap of poly propylene,clip ring PP Compression Metal insert female Threaded Adaptorcompression adaptor with one side compression end to suit 1/2'' to 1'' mdpe pipe and other side with female thread with ss-304 material inserts of sizes 1/2'' BSP thread,PP compression elbow to suit 1/2 " to 1'' (15mm OD to 25 mm OD) MDPE pipe body, nuts, and caps of polypropelene, clip ring of POM(Acetylic resin) and and "O" ring of NBR material,as per ISO 14236 standardsDouble compression elbow to suit 20mm OD for 100mm, MDPE PE80 Blue pipe as per ISO 4427 up to date 1. for conveyance of potable water ,MDPE 20mm OD pipe (2.00 m avg length for each of 1/2'' HSC) of SDR 9-PN-16 for pipes side,Premium make UPVC Pipes with Fittings.(IS 4985/2000)(PH SSR :20) UPVC pipe for 40 mm (Casing for drain crossing)fixing of 12.7 mm brass bib cock indian make heavy duty long bodyFixing of House service connections,including fixing of ferrule, MDPE/GI pipes and specials and connecting newly laid pipe (For HDPE / PVC Pipes)Making Holes upto 18 mm Dia in RCC/any Stones up to 50 mm Thick( BMS-W78)Fixing of 25.4 mm Holder Back Clamps at Drain Crossing this rate cost of above all materials ,Including all Labour Charges ,other incidental charges etc for finished item of work and as directed by the departmental officer in charge of work
Fixing of House service connections,including fixing of ferrule, MDPE/GI pipes and specials and connecting newly laid pipe including labour charges,hire charges etc complete (For HDPE / PVC Pipes) ( supplied items)
:: EAST GODAVARI PUBLIC HEALTH CIRCLE :: MUMMIDIVARAM DISTRICT::
Providing, Installation, Testing and Commissioning of PRESSURE TRANSMITTER for suction, Delivery and common Header with specifications of Water Application: Range: 0-16 Bar / Power Supply: 24 V DC / Output: 4-20 mA / Diaphragm: SS316L / Process Connection: 1/2 "NPT (M) / Accuracy: 0.15% Protection: IP67 . The cost also includes the calibration of all the sensors manifold etc., complete including cost and conveyance of all material and labor excluding cost of taxes and duties and as per SS and as directed by the department officer
Supply, errection, testing and commissioning of Ultra sonic/ Altitude Level sensors make of SIEMENS/ ABB/ BAUMER/ DANFOSS with specifications of body construction with standard construction, measuring upto 6.00 Mtr depth, protection clause of IP 65, accuracy is +/- 5%, input power supply is 24 V.. DC, remote communication protocol of 4 to 20 ma, temperature safety is in-built to comprehensive over temperature range with in the -40 Deg to +80 Deg, installed in both conditions i.e., indoor and outdoor, charges excluding cost of taxes and duties including cost and conveyance of all material including transport and labor etc., complete and as directed by the dept., officer.
Supply and delivery of 25 MM Dia electrical actuated valves for Vaccume operation for each pump with specification of Thread end, 24 V.. DC and required limit switches and manual override facility complete charges including cost and convayance of all the material, labor etc., complete and excluding cost of Taes and duties
Supply and delivery of DI D/F hydraulic and self-medium operated double chamber diaphragm control valve for the functions of pump control i.e. to ensure smooth startup and shutdown of pumps. Valve shall be activated by line pressure and 24V DC solenoid for its operation. Non-return function in built to prevent surges due to pump trip events. Valve closure started as soon as solenoids are deenergized and limit switch of valve position indicator triggered. The valve can be manually overridden to check function. The main valve body internals shall consist of three basic parts i.e. body, diaphragm assembly and top cover with a spring inside main body. The nylon reinforced natural rubber diaphragm of the valve shall close on a seating arrangement. The control tubing shall include inline filter unit. The coating shall be of epoxy BLUE. Charges including cost and conveyance of all material and labor excluding cost of taxes and duties per SS and as directed by the department officer
DN 200 - PN 16 pump control valve for Raw Water Pumping Station as per the above specification
DN 150 - PN 16 pump control valve for Clear Water Pumping Station as per the above specification
Supply and delivery of separate version Electro Magnetic Flow Meter MAG 5100 model or equilant with the specification of flow body as per company standards, electrodes of SS316, accuracy of +/- 2%, cable length of 20 Mtrs, end connection of ANSI flanges as IS/DIN standards, flow bore protection is IP68, earth rings of SS ( If required as per site condition) flow transmitter body as per company standard and two line display, transmitter having 4-20mA, RS485 and modbus communication for data transfer through any network, power supply of 24 volts DC , and submittion of manufacturer test and calbrationreports charges and all charges including cost and conveyance of all material , freight, transport and labour etc and excluding of GST etc., complete, and as directed by the dept., officer.
300 MM Dia Above Specification.
400 MM Dia Above Specification.
500 MM Dia Above Specification.
Supply and testing of panel mounted 96 mmx 48 mm size on line mounted pH Analyser with Display (4 Digit) make of FM/ JUMO / ABB/ SIEMENS/ HACH with the technical specifications of Measuring Range: 0-14 pH, Process pressure range : 1 bar @ 50 Deg C, Measuring method : Reference, Solution ground : Graphite, electrode body: Glass body (tip), Wetted Parts : Glass tip plastic shaft protection Operating Temp: 0 to 50 Deg C, Protection Class : IP 65 (front) & IP 20 (rear), Communication : RS485, Voltage : 24 V.. DC Cable : 10 mtrs of Poly made the charges are including test and calibration certificate, cost and conveyance of all material, labor and excluding cost of taxes.
Supply and testing of wall mounted 120(w), 140(H), 77(D) Turbidity analyser with display(4 digit) make of FM/ JUMO / ABB/ SIEMENS/ HACH with the technical specifications of Measuring range: 1-4000 Ntu, Process pressure range : 2 bar @ 50 deg c, Measuring method : Infrared light 90 deg scatter light method, Max. sampling rate for measured values: 1 Hz, Resolution : 0.01 to 1 depending on measuring range , Measurands : Turbidity & Temperature Operating temp: 0 to 50 deg c, Protection class : IP 67, Communication : RS 485/4-20 mA, Voltage : 24 v.. DC, Sensor case : PVC/POM-C, Optical window: PMMA, Cable : 10 mtrs of Poly made the charges are including test and calibration certificate, cost and conveyance of all material, labor and excluding cost of taxes.
Supply and testing of panel mounted 96 mm x 48 mm size on line mounted Conductivity/ TDS sensor with display (4 digit) make of FM/ JUMO / ABB/ SIEMENS/ HACH with the technical specifications of Measuring range: .1 to approx. 1000 μS/cm, Cell constant : 0.1, Process pressure range : 5 bar @ 50 deg c, Measuring method : Conductive 2 electrode, Sampling : 500 msec, Measurands : Conductivity / TDS, Operating temp : -5 to +80 °C, Protection class : IP 67, Communication : RS 485, Voltage : 24 v.. DC, Sensor case: Stainless Steel 1.4571, Body material: PEI, Cable : 10 Mtrs of Polyimide and the charges are including test and calibration certificate, cost and conveyance of all material, labor and excluding cost of taxes.
Supply and testing of panel mounted 96 mm x 48 mm size on line mounted Chlorine Analyzer with display (4 digit) make of FM/ JUMO / ABB/ SIEMENS/ HACH with the technical specifications of Measuring range: 0-10 PPM, Cell constant : 0.1, Process pressure range : 1 bar @ 50 deg c, Measuring method : 2 and 3 Electrode principle, Response time : Approx. 2 min, pH Dependency (loss of slope) : In the range from pH 5 to 7: no loss of slope, at pH 8 about 10%, at pH 9 about 20%, (starting from pH 7), Operating temp : 0 to 50°C, Protection class : IP 67, Communication : RS 485, Voltage : 24 v.. DC, Sensor Case: PVC, Body material : PEI, Cable : 10 Mtrs of Polyimide and the charges are including test and calibration certificate, cost and conveyance of all material, labor and excluding cost of taxes.
Supply laying and fixing of tubing for Inlet and out let of raw water and clear water to the analyzers with necessary pipes with compressed fittings charges excluding cost of taxes and duties including cost and conveyance of all material including transport and labor etc., complete and as directed by the dept., officer.
Supply, errection, Testing & Commissioning of Out door type PLC/Controller based Automation and communication Panel fabricating with 16 SWG CR sheet, internal and external surface coating with Epoxy powder coating, making internal wiring with suitable wires including nomenclature. The panel is suitable for the Control & Monitoring the Level, Flow & Pressure and Quality Parameters and Comunicating with Central SCADA for Auto logic, Local and Remote operation of the valves with specifications of fabricating with 16 SWG CR sheet, internal and external surface coating with powder coating, making internal wiring with suitable wires including nomenclature. The panel is suitable for the above operations with PLC/Controller, communication modules, HMI, Power back up and necessary modules and as per site conditions etc., complete charges including all material and labor and excluding of taxes and duties and as per SS and as directed by the department officer.
Supply, errection, Testing & Commissioning of In door type Scada based RTU control panel for Opearating and monitoring of the Raw Water and Clear Water Pumping stations in auto logic and manual operations including synchornize with SCADA and the specifications of fabricating with 16 SWG CR sheet, internal and external surface coating with Epoxy powder coating, arrangement of required PLC/ Controller, Ethernet Switch, Required I/O Modules and DI, DO modules, all components powered by 24 V. DC with necesssary control MCB's, Relay cards, fixing of all termination with FTB's, Internal wiring by all power cables with suitable guage of Single core copper PVC sheated cables and all communication cables with SS Brided cables, and the panel having logic for the following and erection with required civil works as per site conditions etc., complete charges including all materials and labour and excluding of taxes and duties and as per SS and as directed by the department officer.
Reservoir Inlet Management ::
supply and delivery of "Resilient Seated Soft Sealing" Gate Valves (Sluice Valves) with Body and Bonnet of Ductile Iron GGG-40/SG-400/15 or GGG-50/SG-500/7 or Equivalent as per IS1865, IS:3896-2 and Wedge fully Rubber Lined with food grade quality grade W270 grade EPDM, Replaceable Spindle Nut without gland packing with 3-O ring protection system on the Shaft and Seals of NBR. The Valves should be Vacuum tight and 100% leak proof with face to face dimensions as BS:5163 Type A/IS:14846. All the valves should be with fusion bonded Electrostatic Powder coating both inside and outside (Min 250 Microns)- RAL 5005 with Pocket Less Straight through body Passage conforming to Design standards of DIN-3202F4/BS:5163 Type A Flange drilling as per IS - 1538 excluding all taxes, duties and including transportation.
Supply and delivery of separate version Electro Magnetic Flow Meter MAG 5100 model or equilant with the specification of flow body as per company standards, electrodes of SS316, accuracy of +/- 2%, cable length of 20 Mtrs, end connection of ANSI flanges as IS/DIN standards, flow bore protection is IP68, earth rings of SS ( If required as per site condition) flow transmitter body as per company standard and two line display, transmitter having 4-20mA, RS485 and modbus communication for data transfer through any network, power supply of 24 volts DC , and submittion of manufacturer test and calbrationreports charges and all charges including cost and conveyance of all material , freight, transport and labour etc and excluding of GST etc., complete, and as directed by the dept., officer.
Supply and delivery of Electrically switched, DI D/F hydraulic and self-medium operated diaphragm Control valve for the functions of Pressure & Flow control at Tank inlet with the function to maintain a constant downstream flow and pressure by controlling the differential pressure between the inlet and outlet of an orifice plate, regardless of pressure variations. The valve shall be of globe pattern inline or angular pattern with a main valve body of full or reduced bore designed for full differential pressure. The seat shall be of stainless steel which is replaceable.The valve can use manually and electrically with 24 V.. AC/DC for operation. The control tubing with self cleaning filter unit to functions as per customer requirement. The internal & external coating with liquid/Powder form epoxy coating, all fastners with SS including cost and convayance of all material and labor excluding cost of taxes and duties and as per SS and as directed by the department officer
Supply ad delivery of M.S. Dismantling Joints /SS, D/F expansion bellows with specifications of bellow with SS ASTM A 240 TP 304 grade, tie rods with EN8/IS-2062 Grade, End connection flanges with IS 2062 Gr.B Sorf plate, Drilling and dimensions as per approved drawing as required by customer at the time of order confirmation charges excluding cost of taxes and duties including cost and conveyance of all material including transport and labor etc., complete and as directed by the dept., officer.
Supply, errection, testing and commissioning of Ultra sonic/ Altitude Level sensors make of SIEMENS/ ABB/ BAUMER/ DANFOSS / KELLER with specifications of body construction with standard construction, mesuring upto 6.00 Mtr depth, protection clause of IP 65, accuracy is +/- 5%, input power supply is 24 V.. DC, remote comunication protocol of 4 to 20 ma, temperature safety is in-built to comperhencive over temprature range with in the -40 Deg to +80 Deg, installed in both conditions i.e., indoor and outdoor, charges excluding cost of taxes and duties including cost and conveyance of all material including transport and labor etc., complete and as directed by the dept., officer.
Providing, Installation, Testing and Commissioning of PRESSURE TRANSMITTER for Water Application: Range: 0-10 Bar / Power Supply: 24 V DC / Output: 4-20 mA / Diaphragm: SS316L / Process Connection: 1/2 "NPT (M) / Accuracy: 0.15% Protection: IP67 . The cost also includes the calibration of all the sensors manifold etc., complete including cost and convayance of all material and labor excluding cost of taxes and duties and as per SS and as directed by the department officer
Supply and testing of panel mounted 96 mm x 48 mm size on line mounted Chlorine Analyzer with display (4 digit) make of FM/ JUMO / ABB/ SIEMENS/ HACH with the technical specifications of Measuring range: 0-10 PPM, Cell constant : 0.1, Process pressure range : 1 bar @ 50 deg c, Measuring method : 2 and 3 Electrode principle, Response time : Approx. 2 min, pH Dependency (loss of slope) : In the range from pH 5 to 7: no loss of slope, at pH 8 about 10%, at pH 9 about 20%, (starting from pH 7), Operating temp : 0 to 50°C, Protection class : IP 67, Communication : RS 485, Voltage : 24 v.. DC, Sensor Case: PVC, Body material : PEI, Cable : 10 Mtrs of Polyimide and the charges are including test and calibration certificate, cost and conveyance of all material, labor and excluding cost of taxes.
Supply laying and fixing of tubing for Inlet and out let of raw water and clear water to the analyzers with necessary pipes with compressed fittings charges excluding cost of taxes and duties including cost and conveyance of all material including transport and labor etc., complete and as directed by the dept., officer.
Supply, errection, Testing & Commissioning of Out door type PLC/Controller based Automation and communication Panel fabricating with 16 SWG CR sheet, internal and external surface coating with Epoxy powder coating, making internal wiring with suitable wires including nomenclature. The panel is suitable for the Control & Monitoring the Level, Flow,Pressure and Quality Parameters and Comunicating with Central SCADA for Auto logic, Local and Remote operation of the valves with specifications of fabricating with 16 SWG CR sheet, internal and external surface coating with powder coating, making internal wiring with suitable wires including nomenclature. The panel is suitable for the above operations with PLC/Controller, communication modules, HMI, Power back up and necessary modules and as per site conditions etc., complete charges including all material and labor and excluding of taxes and duties and as per SS and as directed by the department officer.
Supply laying and jointing of 4 Sq.MM - 2 core PVC sheeted cable make of LAPP/Orbit/Polycab/Finolex for solar / Raw power for the instrumantation and automation at Raw water and clear water pumping with in the Head works compound/ pumping stations/Individual OHSR's and laying with necessary cable trays/Condutes/ Civil works from each and every panel through side walls/cealing / floorings etc., where ever is necessary with all related civil works etc., charges excluding cost of taxes and duties including cost and conveyance of all material including transport and labor etc., complete and as directed by the dept., officer.
Supply laying and jointing of 0.75 Sq.MM - 4 core SS Brided and PVC sheeted cable make of LAPP/Orbit/Polycab/Finolex for solar / Raw power for the instrumantation and automation at Raw water and clear water pumping/ with in the Head works compound/ pumping stations/ Individual OHSR,s and laying with necessary cable trays/Condutes/ Civil works from each and every panel through side walls/cealing / floorings etc., where ever is necessary with all related civil works etc., charges excluding cost of taxes and duties including cost and conveyance of all material including transport and labor etc., complete and as directed by the dept., officer.
Erection, testing and commissioning of Reservoir Management unit including dejointing of existing pipeline / flange joints, taking out already laid DI/MS or any kind of pipe barrel piece, lifting the said pipe, cleaning & returning to the departmental store as per direction of the Engineer-in-charge and lowering, aligning & placing the flow Meter unit, jointing the same with fabricating of fittings, reducers, flanges with necessary MS material as per flow meter manufacturer standards and as per the site conditions with necessary lifting equiment, fabrication works, fixing with new Nuts , bolts and Rubber insertion with arrangment of necessary earth work excavations, MS clamp brackets, lifting equipment, retrofit works to complete the job as per site condition (Excluding cost of Meter, Valve& Expansion bellow etc.,) charges excluding cost of taxes and duties including cost and conveyance of all material including transport and labor etc., complete and as directed by the dept., officer.
Integration of PLC panels with Developing necessary softwares and programming as per field condition and user interface, communicated from each panel and intigrated with central SCADA station charges excluding cost of taxes and duties including cost and conveyance of all material including transport and labor etc., complete and as directed by the dept., officer.
24 x 7 Water Supply :: DMA Management ::
supply and delivery of "Resilient Seated Soft Sealing" Gate Valves (Sluice Valves) with Body and Bonnet of Ductile Iron GGG-40/SG-400/15 or GGG-50/SG-500/7 or Equivalent as per IS1865, IS:3896-2 and Wedge fully Rubber Lined with food grade quality grade W270 grade EPDM, Replaceable Spindle Nut without gland packing with 3-O ring protection system on the Shaft and Seals of NBR. The Valves should be Vacuum tight and 100% leak proof with face to face dimensions as BS:5163 Type A/IS:14846. All the valves should be with fusion bonded Electrostatic Powder coating both inside and outside (Min 250 Microns)- RAL 5005 with Pocket Less Straight through body Passage conforming to Design standards of DIN-3202F4/BS:5163 Type A Flange drilling as per IS - 1538 excluding all taxes, duties and including transportation.
Supply and delivery of Separate Version Electro Magnetic Flow Meter MAG 5100 model or equilant with the specification of flow body as per company standards, electrodes of SS316, accuracy of +/- 2%, cable length of 20 Mtrs, end connection of ANSI flanges as IS/DIN standards, flow bore protection is IP68, earth rings of SS ( If required as per site condition) flow transmitter body as per company standard and two line display, transmitter having 4-20mA, RS485 and modbus communication for data transfer through any network, power supply of 24 volts DC , and submittion of manufacturer test and calbrationreports charges and all charges including cost and conveyance of all material , freight, transport and labour etc and excluding of GST etc., complete, and as directed by the dept., officer.
Supply and delivery of Electrically switched, DI D/F hydraulic and self-medium operated diaphragm Control valve for the functions of Pressure & Flow control at Tank inlet with the function to maintain a constant downstream flow and pressure by controlling the differential pressure between the inlet and outlet of an orifice plate, regardless of pressure variations. The valve shall be of globe pattern inline or angular pattern with a main valve body of full or reduced bore designed for full differential pressure. The seat shall be of stainless steel which is replaceable.The valve can use manually and electrically with 24 V.. AC/DC for operation. The control tubing with self cleaning filter unit to functions as per customer requirement. The internal & external coating with liquid/Powder form epoxy coating, all fastners with SS including cost and convayance of all material and labor excluding cost of taxes and duties and as per SS and as directed by the department officer
Supply ad delivery of M.S. Dismantling Joints /SS, D/F expansion bellows with specifications of bellow with SS ASTM A 240 TP 304 grade, tie rods with EN8/IS-2062 Grade, End connection flanges with IS 2062 Gr.B Sorf plate, Drilling and dimensions as per approved drawing as required by customer at the time of order confirmation charges excluding cost of taxes and duties including cost and conveyance of all material including transport and labor etc., complete and as directed by the dept., officer.
Providing, Installation, Testing and Commissioning of PRESSURE TRANSMITTER for Water Application: Range: 0-10 Bar / Power Supply: 24 V DC / Output: 4-20 mA / Diaphragm: SS316L / Process Connection: 1/2 "NPT (M) / Accuracy: 0.15% Protection: IP67 . The cost also includes the calibration of all the sensors manifold etc., complete including cost and convayance of all material and labor excluding cost of taxes and duties and as per SS and as directed by the department officer
Supply, errection, Testing & Commissioning of Out door type PLC/Controller based Automation and communication Panel fabricating with 16 SWG CR sheet, internal and external surface coating with Epoxy powder coating, making internal wiring with suitable wires including nomenclature. The panel is suitable for the Control & Monitoring the Level, Flow, Pressure and Qaulity Parameters and Comunicating with Central SCADA for Auto logic, Local and Remote operation of the valves with specifications of fabricating with 16 SWG CR sheet, internal and external surface coating with powder coating, making internal wiring with suitable wires including nomenclature. The panel is suitable for the above operations with PLC/Controller, communication modules, HMI, Power back up and necessary modules and as per site conditions etc., complete charges including all material and labor and excluding of taxes and duties and as per SS and as directed by the department officer.
Supply laying and jointing of 4 Sq.MM - 2 core PVC sheeted cable make of LAPP/Orbit/Polycab/Finolex for solar / Raw power for the instrumantation and automation at Raw water and clear water pumping with in the Head works compound/ pumping stations/Individual OHSR's and laying with necessary cable trays/Condutes/ Civil works from each and every panel through side walls/cealing / floorings etc., where ever is necessary with all related civil works etc., charges excluding cost of taxes and duties including cost and conveyance of all material including transport and labor etc., complete and as directed by the dept., officer.
Supply laying and jointing of 0.75 Sq.MM - 4 core SS Brided and PVC sheeted cable make of LAPP/Orbit/Polycab/Finolex for solar / Raw power for the instrumantation and automation at Raw water and clear water pumping/ with in the Head works compound/ pumping stations/ Individual OHSR,s and laying with necessary cable trays/Condutes/ Civil works from each and every panel through side walls/cealing / floorings etc., where ever is necessary with all related civil works etc., charges excluding cost of taxes and duties including cost and conveyance of all material including transport and labor etc., complete and as directed by the dept., officer.
Erection, testing and commissioning of DMA management unit including dejointing of existing pipeline / flange joints, taking out already laid DI/MS or any kind of pipe barrel piece, lifting the said pipe, cleaning & returning to the departmental store as per direction of the Engineer-in-charge and lowering, aligning & placing the flow Meter unit, jointing the same with fabricating of fittings, reducers, flanges with necessary MS material as per flow meter manufacturer standards and as per the site conditions with necessary lifting equiment, fabrication works, fixing with new Nuts , bolts and Rubber insertion with arrangment of necessary earth work excavations, MS clamp brackets, lifting equipment, retrofit works to complete the job as per site condition (Excluding cost of Meter, Valve& Expansion bellow etc.,) charges excluding cost of taxes and duties including cost and conveyance of all material including transport and labor etc., complete and as directed by the dept., officer.
Integration of PLC panels with Developing necessary softwares and programming as per field condition and user interface, communicated from each panel and intigrated with central SCADA station charges excluding cost of taxes and duties including cost and conveyance of all material including transport and labor etc., complete and as directed by the dept., officer.
AMI Water Meter Management.
Providing, Installing and satisfactory field testing of domestic Water Meter with AMR Compatible Mechanical Water Meters with the specifications of minimum Dynamic ratio (Q3/Q1) of 160:1, fully body made up of composite material/ Brass/ Bronze, the metal Material that come in contact with the water supply shall withstand 2 ppm (Parts per million) of chlorine residual in the water supply and shall be resistant to corrosion, mechanical inferential type, multi jet, magnetically coupled, having dry dial, protection class of IP-68, Class ’B’ confirming to IS-779: 1994 with up to date amendments or ISO 4064:2014 standard with ISI/EEC/OIML/MID/CE certification mark shall be with meter and offer 5 years warranty and submittion of manufacturer test and calbrationreports charges and all charges including cost and conveyance of all material , freight, transport and labour etc and excluding of GST etc., complete, and as directed by the dept., officer. Note: Detailesd technical specifications enclosed as Anexure-A.
Supply, Delivery, Installing and satisfactory field testing of AMR Unit for domestic Water Meters from 15 mm to 40 mm with the specifications of fully body made up of composite material, magnetically coupled in between meter and AMR module, protection class of IP-68, In built battery with 3.60 V... Lithium Battery for life of 10 Years based on one communication /Day, Communication interface in between meter and AMR unit with Pulse/ Photo Electric, AMR unit can fetch the data from meter on hourly basis and store the data for 48 Hours on FIFO basis and send the data through NB IoT in every 24 Hours without fail through the provider registered in DOT, India, if the communication fails due to bad communication the AMR module can try for a maximum six times in different time intervals to ensure the data to reach to server. The AMR unit have option of Bluetooth for remote configurations at field. In the special event and field testing the data sending interval of AMR unit can be configurable and minimum time interval span is one Hour (The battery life can be calculated based on the time intervals of data communication) The data storage should be kept in Indian data centres for the data security, AMR unit can be registered the abnormalities like Reverse flow, Leak detection, Tampering and send to the server via reading data packet, Every communication from the AMR module to server should be in JSON format with real time stamping, The AMR can suitable for all the Mechanical Water meters supplied by the agency in this contract. The AMR Module offered with 5 years warranties and submittion of manufacturer test and calbrationreports charges and all charges including cost and conveyance of all material , freight, transport and labour etc and excluding of GST etc., complete, and as directed by the dept., officer. Note: Detailesd technical specifications enclosed as Anexure-B
Supplying and Fixing water meter BOX- with Weather resistant FRP box, press fitted Lid fixing & locking and locked with built-in or external lock. Charges including breather, NBR bushes for pipe entry, SS Grouting screws etc., complete and as directed by the departmment officer.
Establishment of Local SCADA station at Mummidivaram Municipality with the above specifications.
Establishment of Local SCADA station at Mummidivaram Municipality with the above specifications.
Providing Technical Graduate for co-ordinating the process of interconnections of the existing and proposed systems, preparation of documents related to inter departmental permissions and liaison with line departments to obtain permissions including preparation of build drawings as instructed by the Engineer in charge.
Providing the services such as consumer survey and mapping, asset mapping, ground validation, component wise structural and hydraulic designs as per site condition, GIS based hydraulic modelling of all components of both existing and proposed water supply infrastructure and any other documentation/ plan/ designs related to the whole scheme as per the instructions of the Engineer incharge and CPHEEO Manual
Manning, Operation and Maintenance of Water Supply Improvement Scheme
Engary man power skilled/ Semiskilled like operation, Electrician., ump operation machanic, helper,watch man , filer bed peration, Diploma Engineering, lab technician technical work inspector as per requriment .This rate including wagrs along with miunicipal allowance, cinveyance charges transportion to site including statutory provisions as per norm complete for sucessful Maintenance of the entire scheme and s directed by the departmental officer in charge sof work for 7yers including 2years Defect liabiliy period as follows
Personal required for operating Intake/Offtake well/Pump houses Operator
Personal required for operating Intake/Offtake well/Pump houses Fitter/Helper
Personal required at operating Raw water rising mains Fitter/Helper
Personal required at operating Water treatment plants & Sump Operator
Personal required at operating Water treatment plants & Sump Fitter/Helper
Lab Technician
Electrician /Mechanic
Watch man
Personal required at operating Clear water rising mains Fitter/Helper
Personal required at operating Service reservoirs Watch man
Personal required at operating distribution system Fitter/Helper
Supply, delivery and stacking of Chorine gas as per relevant indian standards in cylinders including cost of material, coveyance, stacking at the location specified by the Department and inclusive of all taxes except GST etc., complete to be used as a disinfectant in accordance with CPHEEO manual guidelines.
Supply and delivery of Alumino -Ferric (Alum) as per IS standards including the cost of material, conveyance, stacking at the location specified by the Dept., and including all taxes except GST etc., complete.rement at 15 mg/lit
Repairs to pumpsets & Water pipe lines (2 years after execution period)
i) Replacement of bearings of pumpsets
ii) Replacement of sleeves
iii) Raw Water Motors
iv)Replacement of glands of sluice valves
v) Replacements of balls of Air valves
vi) Greease
vii) Gland Packing
LEAKAGES
Earth work Excavation,Bailing out water from Pipe Line Trench and replacement damaged DI Pipe for 2 M length including the Cost of Pipe Collar M/F Joint and refilling etc complete as follows
500 mm DI Pipes
350 mm DI Pipes
300 mm DI Pipes
200 mm DI Pipes
150 mm DI Pipes
Rectification of Leakages due to damage of Rubber rings by cocking the joint with lead wool and Hump yarn etc complete as follows
500 mm DI Pipes
350 mm DI Pipes
300 mm DI Pipes
200 mm DI Pipes
150 mm DI Pipes
Earth work Excavation,Bailing out water from Pipe Line Trench and replacement damaged HDPE Pipe for 1 M length including the Cost of Pipe Collar M/F Joint and refilling etc complete as follows
250 mm HDPE Pipes
200 mm HDPE Pipes
160 mm HDPE Pipes
110 mm HDPE Pipes
:: LOCAL SCADA at ULB LEVEL ::
To asist to attend the service calls by the seniour service engineer
With assistance of the DBA, preparation of daily reports, monthly billing, correspondence with consumers and also co-ordinate with the GVMC Officials for obtaining of required information when ever asks.
To assist the entire team, dispatches and also maintain SCADA station clean and neat
Replacement of necessary servicable materials(Reagents) for Chlorine Analysers * Each Reagent bottle will work for 90 days (Self life) as per the Caluculation based on the Sampling interval in every 10 Minuets.
Replacement of necessary tranducers for PH analysers
Replacement of necessary tranducers for Turbidity analysers
Interconnection for Data receive station from all Local Contol RTU panels.
Data transfer from RTU control panels
Charges for maintainance of PC's, Hardware consumables, Minor repair & Servers ,servomax Stabliser, UPS, maintainance of entire system including cost and convayance of all material and labor and attending minor repairs to instrumantation and automation equipment etc., complete
:: CENTRAL SCADA at CIRCLE LEVEL ::
To monitor all issues related to both operation & service
To monitor all meters location through SCADA station and give feedback to the service engineers.
To attend the service calls by the feedback from SCADA Engineer and supervise to overcome major/minor shutdowns
With assistance of the DBA, preparation of daily reports, monthly billing, correspondence with consumers and also co-ordinate with the Officials for obtaining of required information when ever asks.
To assist the entire team, dispatches and also maintain SCADA station clean and neat
Interconnection for Data receive station from all Local Contol RTU panels.
Data storage and reporting system for view through WEB and Mobile networks
for day to day Operations & Reporting
End of BoQ
Please Enable Macros to View BoQ information
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 4.03 MB
AIIBIOCTTendeDocumentOandM.rar
Additional Documents • 0.16 MB
BOQ_922209.xls
BOQ • 4.21 MB
Otherdocuments.rar
Additional Documents • 16.89 MB
10-12-202120211218_13091908.pdf
Additional Documents • 1.49 MB
IOCTTenderDocumentRajamahendravaramCircle.pdf
Tender Documents • 4.02 MB
drawingsotherreports.rar
Additional Documents • 26.78 MB
Download all tender documents and submit your bid