Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹9.8 LAccepted-AOC | L1 | Accepted-AOC AOC | |
| 2 | L2₹10.8 L+₹94,000 (9.58%)Rejected-Finance SIMURALI NADIA | PURBA BARDHAMAN | WEST BENGAL | 713502 | L2 | Rejected-Finance Rejected as L2 | |
| 3 | L3₹10.9 L+₹1.1 L (11.6%)Rejected-Finance 14 SURI LANE KOLKATA 700 014 | KOLKATA | KOLKATA | WEST BENGAL | 700014 | L3 | Rejected-Finance Rejected as L3 |
Tender Value
Refer Docs
EMD Value
₹19,069
Closing Date
10 May 2025, 1:00 pmClosed
Executive Engineer
Dist Hospital Campus Saktinagar Krishnahar Nadia
SITC of UPS for 56 beds SNCU on the First Floor of the Gynae Building in Nadia District Hospital
2025_WBPWD_837300_1
WBPWD/EE/NED/NIQ/e-T/93/ (2nd Call)24-25
Open Tender
ELECTRICAL WORKS ORG
Item Rate
30 days
Dist Hospital Campus Saktinagar Krishnagar Nadia
Please refer Tender documents.
5 documents required · 5 mandatory
₹19,069
Nadia Electrical Division
15 Jul 2025
21 Apr 2025
14 May 2025
21 Apr 2025
10 May 2025
23 Apr 2025
23 Apr 2025
Amount
SITC of 3 Phase online UPS system with 30 minutes backup including batteries, interconnecting cables, battery rack etc. Nominal Power( KVA) : 40 (Make-Numeric/APC) Active Power(KW) : 40 @ 40deg C Technology : True online double convertion confirming (VFI-SS-III) can be parallel in (N+ 1) configuration minimum 4 nos. IGBT besd as rectifirer as well as both Side. INPUT Nominal Voltage : 380/400/415 Vac3Ph +N+PE Operating Voltage Range : 320 – 476 Input Voltage Range for 100% : -20/+20 % @ full load (320-476V) Input Voltage Range for 50% load : - 35% @ 50% load (260-476V) Operating Frequency Range : 45-55 Hz Power Factor : Unity Bypass Frequency Range : ± 10% Harmonic distortion (THDi) : ≤ 3% at rated load Input auto phase sequence correction : Inbuilt
OUTPUT Output Voltage : 380/400/415 Vac 3Ph +N+PE Power Factor : Unity Voltage Regulation : ± 1% (balanced load) Frequency (Online Mode) : 50Hz ± 10% (with sync mode & adjustable) Frequency (Battery Mode) : 50Hz ± 0.1 Hz Harmonic distortion (THDv) : ≤ 2% with Linear Load ≤ 5% with Non-linear load Isolation Transformer : should be Inbuilt Crest Factor : 03:01:00 Cold Start : Must available Overload : ≤ 110% for 60min ≤ 125% for 10min ≤150% for 60 Sec Adjustable DC BUS : Should be available Auto Battery Test : Should be available Power Walking : Should be available Efficiency : 94%
COMMUNICATION Standard : LCD Display, LED Indication, RS232 port, RS485 port, Dry Contact Remote monitoring : Option available Remote shutdown : Option available ENVIRONMENT Operating Temperature for UPS : 0 degree C – 40 degree C Relative Humidity Range : 0-95 % (non-condensing) Noise Level : Max 65Dba at 100% load and ≤55Dba at 50% Certificate IEC 6240-1 , IEC6240-2 , IEC6240-3 , CE, ROHS & PEP : Should be available Service point Service Center : Company should have there own service center in local area near the site Register Service Toll Free no : Company should have there own registered toll free no for service to attain the call & resolve the issue immediately
BATTERY Battery Type : SMF battery Back up time : 30 mins Minimum Battery VAH : 36000 Charger Capacity for UPS : Long backup charger ( at least upto 20Amps) Warranty : 2-Years on UPS & 2-Years on SMF Batteries
LOKNATH ENGINEERING (BID ID -6355131)
T.D.K. ENTERPRISE (BID ID -6366242)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .