Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹277 CrAccepted-AOC PLOT NO 137 2ND FLOOR AVTAR ENCLAVE PASCHIM VIHAR NEW DELHI 110063 | WEST | DELHI | 110063 | ₹277 Cr | L1 | Accepted-AOC L1 Bidder |
| 2 | L2₹284.8 CrRejected-Finance CHINAR COMMERCIAL COMPLEX THE BUND RESIDENCY ROAD SRINAGAR 190 001 | SRINAGAR | SRINAGAR | JAMMU AND KASHMIR | 190001 | ₹284.8 Cr | L2 | Rejected-Finance Not Being L1 |
| 3 | L3₹286.8 CrRejected-Finance L 87 STREET NO 7C MAHIPALPUR EXTENSION NEW DELHI 110037 | NEW DELHI | NEW DELHI | DELHI | 110037 | ₹286.8 Cr | L3 | Rejected-Finance Not Being L1 |
| 4 | L4₹308.4 CrRejected-Finance | ₹308.4 Cr | L4 | Rejected-Finance Not Being L1 |
| 5 | L5₹329.3 CrRejected-Finance 48 19 6 2ND FLR MVR COMPLEX DWARAKANAGAR OPP RTC COMPLEX VISAKHAPATNAM 530003 | VISAKHAPATANAM | ANDHRA PRADESH | 530003 | ₹329.3 Cr | L5 | Rejected-Finance Not Being L1 |
Tender Value
₹339.5 Cr
EMD Value
₹15 L
Closing Date
7 Apr 2025, 6:00 pmClosed
CE NAVY STATION ROAD VISAKHAPATNAM
CE NAVY STATION ROAD VISAKHAPATNAM
PROVN OF INFRASTRUCTURE FOR CERTAIN TECHNICAL BUILDINGS SOIL STABILISATION AND PAVEMENT PART II AT INS DEGA UNDER GE P No 3 VISAKHAPATNAM
2025_MES_691480_1
85431
Open Tender
Civil Works
1080 days
VISAKHAPATNAM
AS PER NIT
13 documents required · 13 mandatory
₹3,000
Garrison Engineer Project No 3
₹15 L
Yes
CE NAVY VISAKHAPATNAM
2 Jun 2025
2 Jan 2025
14 Apr 2025
2 Jan 2025
7 Apr 2025
24 Mar 2025
2 Jan 2025 - 11 Jan 2025
20 Jan 2025
Amount
Schedule "A" Part – I (BUILDINGS & STRUCTURES)
Design, Procurement and erection and commissioning of Pre-Engineered Building (PEB) steel structure for Maintenance Hangar (F2) (as per drawings) made up with hot rolled sections confirming to IS 2062 and cold formed sections confirming to IS 1079, Alu zinc colour coated profiled steel roofing sheets 0.63 mm thick (TCT) and yield strength of 550 mPa in wall cladding and roofing (max 15% roof/wall sheeting with semi transparent triple layer Polycarbonate sheet, including brackets, design, fabricate and erect electro mechanical operated sliding doors with steel frames on both the sides, bird proofing and connected accessories including Pile Foundation, anchor bolts, base plates and all structural steel items and RCC M30 design mix concrete for Columns, PCC Block Masonry (below GL) and fly ash brick work (above GL), and including internal, external finishes and 400mm thick PQC Flooring to achieve flexural strength 45 kg/cm2 in 28 days over one layer of high density polythene sheet (virgin quality) 400 micron thick and of weight not less than 380 g/sqm over 10mm thick sand cushioning over 100mm thick dry lean concrete with min 150 kg/cum of cement and compressive strength not less than 10 mPa in 7days over 225 mm (compacted thickness) WMM in layers not less than 75 mm and not more than 200 mm each over 300 mm thick granular sub base grading V with broken boulders of trap/granite stone in 2 layers including provision of contraction, construction and expansion joints, filler board, sealant primer, joint sealant, backer rod, de ponding strip as per drawing and Providing and application of self-smoothing epoxy topping 5mm (Epoxy quartz screed 3mm thick plus top 2mm thick self-levelling polyurethane hybrid scratch resistance floor) over PQC flooring complete all as specified and as directed including Design, Procurement and Construction of Annex Bldg (on both sides of PEB steel structure) for Maintenance Hangar (F2) (as per drawings) with permanent specifications including Pile foundations, RCC framed structure (G+2 configuration) using RCC M30 design mix concrete, PCC Block Masonry (below GL) and fly ash brick work (above GL), powder coated Aluminium windows with deco grill RCC roof with slope provided with water proofing treatment, internal, external and floor finishes etc. and paved open courtyard complete all as specified, shown on Architectural drgs and as directed.
Design, Procurement and erection and commissioning of Pre-Engineered Building (PEB) steel structure for Technical Hangar (as per drawings) made up with hot rolled sections confirming to IS 2062 and cold formed sections confirming to IS 1079, Alu zinc colour coated profiled steel roofing sheets 0.63 mm thick (TCT) and yield strength of 550 mPa in wall cladding and roofing (max 15% roof/wall sheeting with semi transparent triple layer Polycarbonate sheet, including brackets, design, fabricate and erect electro mechanical operated sliding doors with steel frames on both the sides, bird proofing and connected accessories including Pile Foundation, anchor bolts, base plates and all structural steel items and RCC M30 design mix concrete for Columns, PCC Block Masonry (below GL) and fly ash brick work (above GL), and including internal, external finishes and 400mm thick PQC Flooring to achieve flexural strength 45 kg/cm2 in 28 days over one layer of high density polythene sheet (virgin quality) 400 micron thick and of weight not less than 380 g/sqm over 10mm thick sand cushioning over 100mm thick dry lean concrete with min 150 kg/cum of cement and compressive strength not less than 10 mPa in 7days over 225 mm (compacted thickness) WMM in layers not less than 75 mm and not more than 200 mm each over 300 mm thick granular sub base grading V with broken boulders of trap/granite stone in 2 layers including provision of contraction, construction and expansion joints, filler board, sealant primer, joint sealant, backer rod, de ponding strip as per drawing and Providing and application of self-smoothing epoxy topping 5mm (Epoxy quartz screed 3mm thick plus top 2mm thick self-levelling polyurethane hybrid scratch resistance floor) over PQC flooring complete all as specified and as directed including Design, Procurement and Construction of Annex Bldg (on both sides of PEB steel structure) for Technical Hangar (as per drawings) with permanent specifications including Pile foundations, RCC framed structure (G+2 configuration) using RCC M30 design mix concrete, PCC Block Masonry (below GL) and fly ash brick work (above GL), powder coated Aluminium windows with deco grill RCC roof with slope provided with water proofing treatment, internal, external and floor finishes etc. and paved open courtyard complete all as specified, shown on Architectural drgs and as directed.
Design, Procurement and erection and commissioning of Pre-Engineered Building (PEB) steel structure for Maintenance Hangar for HAWK (as per drawings) made up with hot rolled sections confirming to IS 2062 and cold formed sections confirming to IS 1079, Alu zinc colour coated profiled steel roofing sheets 0.63 mm thick (TCT) and yield strength of 550 mPa in wall cladding and roofing (max 15% roof/wall sheeting with semi transparent triple layer Polycarbonate sheet, including brackets, design, fabricate and erect electro mechanical operated sliding doors with steel frames on both the sides, bird proofing and connected accessories including Pile Foundation, anchor bolts, base plates and all structural steel items and RCC M30 design mix concrete for Columns, PCC Block Masonry (below GL) and fly ash brick work (above GL), and including internal, external finishes and 400mm thick PQC Flooring to achieve flexural strength 45 kg/cm2 in 28 days over one layer of high density polythene sheet (virgin quality) 400 micron thick and of weight not less than 380 g/sqm over 10mm thick sand cushioning over 100mm thick dry lean concrete with min 150 kg/cum of cement and compressive strength not less than 10 mPa in 7days over 225 mm (compacted thickness) WMM in layers not less than 75 mm and not more than 200 mm each over 300 mm thick granular sub base grading V with broken boulders of trap/granite stone in 2 layers including provision of contraction, construction and expansion joints, filler board, sealant primer, joint sealant, backer rod, de ponding strip as per drawing and Providing and application of self-smoothing epoxy topping 5mm (Epoxy quartz screed 3mm thick plus top 2mm thick self-levelling polyurethane hybrid scratch resistance floor) over PQC flooring complete all as specified and as directed including Design, Procurement and Construction of Annex Bldg (on both sides of PEB steel structure) for Maintenance Hangar (HAWK) (as per drawings) with permanent specifications including Pile foundations, RCC framed structure (G+2 configuration) using RCC M30 design mix concrete, PCC Block Masonry (below GL) and fly ash brick work (above GL), powder coated Aluminium windows with deco grill RCC roof with slope provided with water proofing treatment, internal, external and floor finishes etc. and paved open courtyard complete all as specified, shown on Architectural drgs and as directed.
Design, Procurement and erection and commissioning of Pre-engineered building (PEB) steel structure for Sun Shelter as per drawings (comprising Sun shelters-06 Nos in one row) made up with hot rolled sections confirming to IS 2062 and cold formed sections confirming to IS 1079, Alu zinc colour coated profiled steel roofing sheets 0.63 mm thick (TCT) and yield strength of 550 mPa in wall cladding and roofing (max 15% roof/wall sheeting with semi transparent triple layer Polycarbonate sheet, including Pile Foundation, anchor bolts, base plates and all structural steel items and RCC M30 design mix concrete for Columns, with Brick wall (PCC Block Masonry (below GL) and fly ash brick work (above GL)) and including internal, external finishes and 400mm thick PQC Flooring to achieve flexural strength 45 kg/cm2 in 28 days over one layer of high density polythene sheet (virgin quality) 400 micron thick and of weight not less than 380 g/sqm over 10mm thick sand cushioning over 100mm thick dry lean concrete with min 150 kg/cum of cement and compressive strength not less than 10 mPa in 7days over 225 mm (compacted thickness) WMM in layers not less than 75 mm and not more than 200 mm each over 300 mm thick granular sub base grading V with broken boulders of trap/granite stone in 2 layers including provision of contraction, construction and expansion joints, filler board, sealant primer, joint sealant, backer rod, de ponding strip as per drawing complete all as specified, shown on Architectural drgs and as directed.
Notes for above items: (i) Only Soil stabilisation process involved in the bldgs will not be forming part of LS quoted and will be measured and paid separately under respective items of BOQ
(ii) The contractor shall be responsible for design of foundation and all RCC structures from qualified Structural Designers as per tender provisions and approved by Accepting Officers duly vetted by any of the IITs as provided in the Contract Agreement and Carrying out structural design (PEB structure) based on independent soil investigation as per guidelines mentioned on DBR (Design Based Report) included in the tender documents from the approved structural designers, vetting the design from any of the approved IITs, getting approval from the Accepting Officer and submission of bill of quantities, yardsticks etc.
(iii) The architectural drawings enclosed with contract documents are the guidance for designing the structural members. The Plinth Area shall remain same and any minor changes which are technically/ functionally required as per user requirement at ground shall be executed by the contractor without any extra cost.
(vi) Earth work, excavation, returning filling, compaction and disposal of surplus soil to a distance after area development /Soil stabilisation as specified and directed by Engineer-in-charge in footings (Pile caps, below pile caps), base columns up to MGL/FFL as shown in the drawings for building portion (i.e. for Hangars, Sun shelter) is deemed to be included in the scope of lump sum quoted against these items and nothing extra shall be paid. Please note that the quantity of moorum items specified in BoQ is only applicable for Soil stabilisation only.
(vii) Care shall be taken during excavation of footings without damaging the PVD installed for drainage purpose.
(viii) Internal water supply & internal electric supply acoustic design are not inclusive of this item and will be measured and paid for under relevant schedules.
(ix) The contractor shall facilitate the Third Party Inspection Team appointed by the Accepting Officer during execution of work.
Design, procurement and Construction of AC Plant Room for Hangars building (S/S) including pile foundation with RCC framed structure in RCC M30 design mix concrete, PCC solid block (below GL) and fly ash brick masonry (above GL), powder coated aluminium windows with deco grill, RCC roof with slope, provided with water proofing treatment, including internal, external surface finishes, floor finishes, construction of Ramp & open platform complete all as specified, shown on drgs and as directed.
Design, procurement and Construction of Utility Room for Air Craft Washing Platform including pile foundation with permanent specifications RCC framed structure in RCC M30 grade concrete, PCC solid block (below GL) and fly ash brick masonry (above GL), powder coated aluminium windows with deco grill, RCC roof with slope, provided with water proofing treatment, including internal, external surface finishes, floor finishes, construction of plat form for water tank complete all as specified, shown on drgs and as directed.
Design, procurement and Construction of Storage Preservation and De-Preservation of Buildings (S/S) including pile foundation with RCC Columns in RCC M30 grade concrete, roof truss with 0.63 mm thick galvalume sheet roofing, PCC solid block (below GL) and fly ash brick masonry (above GL), powder coated Aluminium windows with deco grill, RCC roof with slope, provided with water proofing treatment, including internal, external surface finishes, floor finishes, construction of Ramp complete all as specified, shown on drgs and as directed.
Design, procurement and Construction of AC plant Room for Storage Preservation and De-Preservation of Buildings (S/S) including pile foundation with RCC framed structure in M30 design mix concrete, PCC solid block (below GL) and fly ash brick masonry (above GL), powder coated aluminium windows with deco grill, RCC roof with slope, provided with water proofing treatment, including internal, external surface finishes, floor finishes, construction of Ramp & open platform complete all as specified, shown on drgs and as directed.
Design, procurement and Construction of Battery Charging, Ext Charging for Fire fighting equipments, special charging station (S/S) including pile foundation with RCC framed structure in M30 design mix concrete, PCC solid block (below GL) and fly ash brick masonry (above GL), powder coated Aluminium windows with deco grill, RCC roof with slope provided with water proofing treatment, including internal, external surface finishes and floor finishes, construction of Ramp and acid proof tile for floor complete all as specified shown on drgs and as directed.
Design, procurement and Construction of Pump House for Regular water supply (S/S) including pile foundation with RCC framed structure in M30 design mix concrete, PCC solid block (below GL) and fly ash brick masonry (above GL), powder coated Aluminium windows with deco grill, RCC roof with slope provided with water proofing treatment, including internal, external surface finishes and floor finishes, construction of Ramp complete all as specified, shown on drgs and as directed.
Design, procurement and Construction of Pump House (S/S) for fire fighting of all Hangars including pile foundation with RCC framed structure in M30 design mix concrete, PCC solid block (below GL) and fly ash brick masonry (above GL), powder coated Aluminium windows with deco grill, RCC roof with slope provided with water proofing treatment, including Internal, external surface finishes and floor finishes, construction of Ramp complete all as specified, shown on drgs and as directed.
Design, procurement and Construction of POL Store (S/S) including pile foundation with RCC framed structure in M30 design mix concrete, PCC solid block (below GL) and fly ash brick masonry (above GL), powder coated Aluminium windows with deco grill, RCC roof with slope provided with water proofing treatment, including Internal, External surface finishes and floor finishes, construction of Ramp and raised Hard standing complete all as specified, shown on drgs and as directed.
Design, procurement and Construction of Sub Station Building Regular for Proposed Assets (S/S) including pile foundation with RCC framed structure in M30 design mix concrete, PCC solid block (below GL) and fly ash brick masonry (above GL), powder coated Aluminium windows with deco grill, RCC roof with slope provided with water proofing treatment, including Internal, External surface finishes and floor finishes, construction of ramp complete all as specified, shown on drgs and as directed.
Design, Procurement and Construction of Static Water Tank -125 KL capacity for Fire Fighting on pile foundation, RCC M30 design mix concrete, RCC roof, all as shown in site plan and all Inside accessories shall be provided as per standard practice/drg complete all as specified, shown on drgs and as directed.
Design, procurement and Construction of Semi Underground Sump (15x15x2.5 m) for Fire Hydrant System on RCC pile foundation, RCC M30 design mix concrete, RCC roof, all as shown in site plan and all Inside accessories shall be provided as per standard practice/drg complete all as specified, shown on drgs and as directed.
Design, procurement and Construction of UG Sump 3.0 Lakh Litres for Regular Water Supply on RCC pile foundation, RCC M30 design mix concrete, RCC roof complete all as shown in site plan and all Inside accessories shall be provided as per standard practice/drg complete all as specified, shown on drgs and as directed.
Blank
Blank
Design, procurement and Construction of Air Stores complex (D/S) including pile foundation with permanent specifications RCC framed structure in M30 design mix concrete, PCC solid Block Masonry in below GL and fly ash brick work in above GL, powder coated Aluminium windows with deco grill, RCC roof with slope provided with water proofing treatment, including Internal, External surface finishes and floor finishes, construction of Ramp and raised Hard standing/plat form complete all as specified, shown on drgs and as directed.
Design, procurement and Construction of Substation building (SS) including pile foundation with permanent specifications RCC framed structure in M30 design mix concrete, PCC solid Block Masonry in below GL and fly ash brick work in above GL, powder coated Aluminium windows with deco grill, RCC roof with slope provided with water proofing treatment, including Internal, External surface finishes and floor finishes, construction of Ramp and open platform complete all as specified, shown on drgs and as directed.
Design, procurement and Construction of Compressor Room (SS) including pile foundation with permanent specifications RCC framed structure in M30 design mix concrete, PCC solid Block Masonry in below GL and fly ash brick work in above GL, powder coated Aluminium windows with deco grill, RCC roof with slope provided with water proofing treatment, including Internal, External surface finishes and floor finishes, construction of Ramp and open platform complete all as specified, shown on drgs and as directed. Notes for above RCC structures: (i) The contractor shall be responsible for design of foundation and all RCC members from qualified Structural Designers as per tender provisions and approved by Accepting Officer duly vetted by any of the IITs as provided in the tender document and Carrying out structural design based on independent soil investigation as per guidelines mentioned on DBR (Design Based Report) and submission of bill of quantities, yardsticks etc. (ii) The architectural drawings enclosed with tender documents are the guidance for designing the structural members. The Plinth Area shall remain same and any minor changes which are technically/ functionally required as per user requirement at ground shall be executed by the contractor without any extra cost. (iii) Earth work, Excavation, returning filling, compaction and disposal of surplus soil to a distance after area development as specified and directed by Engineer-in-charge in footings (Pile caps, below pile caps), base columns up to MGL/FFL as shown in the drawings for building portion (i.e. for Hangars, Sun shelter) is deemed to be included in the scope of lump sum quoted against these items and nothing extra shall be paid. Please note that the quantity of moorum items specified in BoQ is only applicable for Soil stabilisation only. (iv) Internal water supply & internal electric supply are not inclusive of this item and will be measured and paid for under relevant schedules.
M&L for Construction of RCC Septic tank for 150 users designed to carry sewage and sullage water, excavation in any type of soil, PCC 1:4:8 below foundation, RCC M-30 Design mix in Walls, Base slab, Baffle walls and Roof slab including beams etc. with Vent shaft, manhole openings with cover connection etc., complete all as specified and as shown in drawing and as directed.
M&L for Construction of RCC Septic tank for 50 users designed to carry sewage and sullage water, excavation in any type of soil, PCC 1:4:8 below foundation, RCC M-30 Design Mix in Walls, Base slab, Baffle walls and Roof slab including beams etc. with Vent shaft, manhole openings with cover connection etc. complete all as specified and as shown in drawing and as directed.
M&L for Construction of LLDPE septic tank 10 users designed to carry sewage and sullage water, excavation in any type of soil, PCC 1:4:8 below foundation, vent shaft, connection etc. complete all as specified and as shown in drawing and as directed.
M&L for Construction of LLDPE septic tank 25 users designed to carry sewage and sullage water, excavation in any type of soil, PCC 1:4:8 below foundation, vent shaft, connection etc. complete all as specified and as shown in drawing and as directed.
M&L for Construction of Soakage wells upto 25 users, excavation in any type of soil, foundation in PCC 1:4:8 walls of honey combed masonry with RCC cover slab in M30 design mix, interconnecting pipes of RCC complete filled with brick bats complete all as specified and as shown in drawing and as directed.
M&L for 'Construction of Soakage wells upto 50 users excavation, in any type of soil, foundation in PCC 1:4:8 walls of honey combed masonry with RCC cover slab in M30 design mix, interconnecting pipes of RCC complete filled with brick bats complete all as specified and as shown in drawing and as directed.
Schedule "A" Part – II to Schedule "A" Part – XV: Note: Schedule "A" Part – II to Part – XV are prepriced by MES. Bidders shall insert their Lumpsum amount in Green coloured field under Column - 6 only
Lumpsum price worked out by the contractor for "SITE CLEARANCE & AREA DEVELOPMENT/ EARTH WORK/EXCAVATION", as listed in Schedule "A" Part – II
Lumpsum price worked out by the contractor for "SEWAGE DISPOSAL", as listed in Schedule "A" Part – III
Lumpsum price worked out by the contractor for "EXTERNAL WATER SUPPLY", as listed in Schedule "A" Part – IV
Lumpsum price worked out by the contractor for "EXTERNAL ELECTRIFICATION", as listed in Schedule "A" Part – V
Lumpsum price worked out by the contractor for "ROADS & CULVERT", as listed in Schedule "A" Part – VI
Lumpsum price worked out by the contractor for "AREA DRAINAGE", as listed in Schedule "A" Part – VII
Lumpsum price worked out by the contractor for "FIRE FIGHTING/ FIRE ALARM SYSTEM", as listed in Schedule "A" Part – VIII
Lumpsum price worked out by the contractor for ""LIGHTENING PROTECTION ", as listed in Schedule "A" Part – IX
Lumpsum price worked out by the contractor for "COOLING APPLIANCES", as listed in Schedule "A" Part – X
Lumpsum price worked out by the contractor for "LIFTS & DG SET", as listed in Schedule "A" Part – XI
Lumpsum price worked out by the contractor for "INTERNAL ELECTRIFICATION", as listed in Schedule "A" Part – XII
Lumpsum price worked out by the contractor for "INTERNAL WATER SUPPLY", as listed in Schedule "A" Part – XIII
Lumpsum price worked out by the contractor for "RETAINING WALL", as listed in Schedule "A" Part – XIV
Schedule "A" Part - XV: [Miscellaneous Items]
SOIL STABILIZATION/PAVEMENT/PVD:
Preparation and surface treatment of formation by removing mud and slurry, trimming to the required line, grade, profile and rolling with smooth wheeled roller of capacity 8 to 12 tonne, including diversion of existing drain water, stagnated water etc. if any, all as specified and directed.
Supply and laying/wrapping of Non woven Geotextile having wt 285 gsm and min thickness 2.50 mm (confirming to clause 702, Table 700-5 of MoRTH 5th revision) including lapping complete all as specified and directed. Note : (i) The geotextile for separation and for filter layer shall be measured as per planned dimension with no allowance for overlapping at transverse and longitudinal joints. (ii) The rate quoted shall include the cost of overlaps
Supply, Depositing, spreading and levelling in layers not exc 15 cm thick of smaller gradation filter material manually, without damage to drainage pipe (as per MORTH Table 300-3 (Class-1)) in trenches for sub surface drain including all necessary arrangement for maintaining geotextile on vertical position complete all as specified and directed. (around and over 630 mm HDPE pipes)
Supply, Depositing, spreading and levelling in layers not exc 15 cm thick of large gradation filter material manually, without damage to drainage pipe (as per MORTH Table 300-3 (Class-3)) in trenches for sub surface drain including all necessary arrangement for maintaining geotextile on vertical position complete all as specified and directed. (around and over 630 mm HDPE pipes)
Supply and laying of 630 mm outer dia (PE-100, PN-16) HDPE pipe confirming to IS 4984-2016 and shall be jointed/laid in accordance with latest IS 7634 Part-2, with slots of 65 mm length and 5 mm width spaced at 25mm on surface and specified for sub surface drain including necessary bend, connectors etc to maintain proper gradient to drain out water to the final disposal point all as specified and directed.
M&L for Crushed stone dust filling with consolidated thickness of 50 mm including levelling, rolling and compaction by mechanical means to obtain true level surfaces complete all as specified and directed.
M&L for filling of River sand in pavements in layers not exc 300mm (Granular sand blanket measuring 600 mm thick) including watering, levelling, rolling and consolidating the surface by heavy compaction (IS 2720 Part-8) using vibratory roller of 8 to 10 tonne capacity to obtain 98 % of Max dry density complete all as specified and directed. NOTE: Care shall be taken not to disturb PVDs while filling and compacting the sand layer.
Supply and installation of Prefabricated Vertical Drains (PVD) of size 100 mm wide and 5 mm thick (Minimum thickness) at a spacing of 1.0 m in triangular pattern shall be installed using an installation rig/stitcher mounted on a base machine (Hydraulic operated) over the entire area as shown on drawing and complete all as specified and directed. NOTES : (i) PVDs shall be cut after installation in such a manner that PVD head length of 450 mm can be embedded in a sand blanket of 600 mm thickness as shown in drawing. (ii) PVD shall be measured in linear metre of its length. The rate quoted shall include the cost of overlaps, patches, sewn seams and securing pins required for installation of PVDs. (iii) PVDs shall consist of corrugated inner core wrapped in non woven geotextile (Poly propylene) and shall have discharge capacity not less than 100 x 10-6 m3/s under hydraulic gradient of 1 at pressure of 250 kPa. (iv) The rate quoted shall include the cost of labour, equipment, material, marking etc. required for installation of PVDs (v) PVD installation shall be got done as per manufacturer’s instructions and through authorized/ nominated applicator/ installer of manufacturer of PVD. (vi) PVD shall be procured directly from M/s TECHFAB OR M/s TENCATE OR M/s NYLEX OR M/s MACCAFERRI (vii) PVD shall be procured from main manufacturer. (viii) Independent test shall be carried out in BTRA.
M&L for Moorum filling in embankment with proper side slope as per drawing ( for surcharge preloading stage I, 1.2m height over 0.6m sand blanket), spread, levelled, rolled and compacted with 8 to 12 tonne vibratory roller maintaining a minimum degree of compaction of min 98% of MDD (bottom 500 mm) including watering and necessary T&P all as per cross section details shown in drawing and as specified and directed. NOTE: 1. Moorum shall be brought from outside MD land. 2. Bottom 500 mm compacted in two 250 mm layers to achieve compaction 98% of MDD and balance top portion compacted not exc 500 mm to achieve comp[action min 9 % MDD. 3. Compacted thickness shall be measured for payment. 4. The rate are inclusive of forming embankment. 5. This item shall be used in portion Phase I of pavement as pre-loading surcharge shown in drawing. 6. Moorum shall have liquid limit (LL) less than 35%, plasticity Index (PI) less than 15% and minimum soaked CBR of 12%. 7. Moorum shall not contain particles of size more than 40mm. 8. Source/quarry of moorum shall be approved by GE.
M&L for Moorum filling in embankment with proper side slope as per drawing (for surcharge preloading stage II, 1.8m height over 1.2m ht compacted moorum stage I), spread, levelled, rolled and compacted with 8 to 12 tonne vibratory roller maintaining a minimum degree of compaction of min 90% of MDD (bottom 500 mm) including watering and necessary T&P all as per cross section details shown in drawing and as specified and directed. NOTE: 1. Moorum shall be brought from outside MD land. 2. Moorum shall be compacted in layers not exc 500 mm to achieve compaction 90% of MDD. 3. Compacted thickness shall be measured for payment. 4. The rate is inclusive of forming embankment. 5. This item shall be used in portion "A" and "B" of pavement as pre-loading surcharge shown in drawing. 6. Moorum shall have liquid limit (LL) less than 35%, plasticity Index (PI) less than 15% and minimum soaked CBR of 12%. 7. Moorum shall not contain particles of size more than 40mm. 8. Source/quarry of moorum shall be approved by GE.
M&L for Moorum filling in embankment with proper side slope as per drawing (for surcharge preloading stage III, 1.8m height over 1.8m height compacted moorum stage II ), spread, levelled, rolled and compacted with 8 to 12 tonne vibratory roller maintaining a minimum degree of compaction of min 90% of MDD including watering and necessary T&P all as per cross section details shown in drawing and as specified and directed. NOTE: 1. Moorum shall be brought from outside MD land. 2. Moorum shall be compacted in layers not exc 500mm to achieve compaction 90% of MDD . 3. Compacted thickness shall be measured for payment. 4. These rate are inclusive of forming embankment. 5. This item shall be used in portion 'A' and B of Pavement as pre-loading surcharge shown in drawing. 6. Moorum shall have liquid limit (LL) less than 35%, plasticity Index (PI) less than 15% and minimum soaked CBR of 12%. 7. Moorum shall not contain particles of size more than 40mm. 8. Source/quarry of moorum shall be approved by GE.
Supplying and installation of settlement gauges including all fittings & accessories as shown in drawing to monitor the consolidation of soil during ground improvement by PVD method during surcharge loading complete all as specified and as directed.
Supplying and installation of Settlement Gauges including all fittings & accessories as shown in drawing to monitor the consolidation of soil during ground improvement by PVD method during surcharge loading complete all as specified and directed.
Supply and installation of temporary sump with Rotational moulded polyethylene water storage tanks (cylindrical vertical) of capacity 2000 litre and fixed in position at the end of each phase on both sides of pavement as shown in drawing for collection of sub drain & underground water during the surcharge period including excavation, dewatering and necessary pumping arrangement for disposal of water from the storage tank to the nearest storm drains and loose filling of sump with size of 20-40 mm aggregate after completion of soil stabilization without any extra cost complete all as specified and directed.
Excavation of compacted surcharge loading (Moorum) by Mechanical means (Hydraulic excavator) up to 4.8m deep and getting out including dressing of sides and ramming of bottoms including dewatering etc all as specified and directed. Note: (i) Disposal will be measured separately. (ii) After excavation, top portion of the Sub grade shall be compacted 98% of MDD. (rate quoted shall be inclusive of compaction of top portion.)
Forming embankment with proper side slope as per drawing (for surcharge preloading stage I, 1.2m height over 600mm compacted sand blanket ), with using moorum obtained by excavating compacted excess moorum available in Phase-I after surcharge preloading , spread, levelled, rolled and compacted with 8 to 12 tonne vibratory roller maintaining a minimum degree of compaction 98% MDD (Bottom 500mm) including watering and necessary T&P all as per cross section details shown in drawing and as specified and directed. NOTE: 1. Moorum shall be obtained by excavating compacted excess moorum available in Phase-I after surcharge loading . 2. Bottom 500mm compacted in two 250mm layers to achieve compaction of 98% of MDD and Balance Top portion compacted not exc 500mm in layers to achieve compaction min 90% of MDD. 3. Compacted thickness shall be measured for payment. 4. These rate are inclusive of forming embankment. 5. This item shall be used in portion 'Phase-II' of Pavement as pre-loading surcharge shown in drawing. 6. Lead for moorum will be measured and paid in separate items.
Forming embankment with proper side slope as per drawing (for surcharge preloading stage II, 1.8m height over 1.2m height compacted moorum stage I), with using moorum obtained by excavating compacted excess moorum available in Phase-I after surcharge preloading , spread, levelled, rolled and compacted with 8 to 12 tonne vibratory roller maintaining a minimum degree of compaction 90% MDD including watering and necessary T&P all as per cross section details shown in drawing and as specified and directed. NOTE: 1. Moorum shall be obtained by excavating compacted excess moorum available in PH-I after surcharge preloading 2. Moorum shall be compacted in layers not exc 500mm to achieve compaction 90% of MDD . 3. Compacted thickness shall be measured for payment. 4. These rate are inclusive of forming embankment. 5. This item shall be used in portion 'Phase-II' of Pavement as pre-loading surcharge shown in drawing. 6. Lead for moorum will be measured and paid in separate items.
Forming embankment with proper side slope as per drawing (for surcharge preloading stage III, 1.8m height over 1.8m height compacted moorum stage II), with using moorum obtained by excavating compacted excess moorum available in Phase-I after surcharge preloading, spread, levelled, rolled and compacted with 8 to 12 tonne vibratory roller maintaining a minimum degree of compaction 90% of MDD including watering and necessary T&P all as per cross section details shown in drawing and as specified and directed. NOTE: 1. Moorum shall be obtained by excavating compacted excess moorum available in Phase-I after surcharge preloading. 2. Moorum shall be compacted in layers not exc 500mm to achieve compaction 90% of MDD . 3. Compacted thickness shall be measured for payment. 4. These rate are inclusive of forming embankment. 5. This item shall be used in portion 'Phase-II' of Pavement as pre-loading surcharge shown in drawing. 6. Lead for moorum will be measured and paid in separate items.
Supply and laying of Uni-axial high strength Geo-grids of minimum 200 kN/m tensile strength and 2120 kN Secant modulus @ 5% strength (BBA certified) in top portion of compacted moorum (i.e. at improved subgrade level (spaced at 50mm) shall be placed to serve as basal reinforcement. Note: (i) An overlap of 300 mm or as directed by Engineer shall be provided between the adjacent rolls. There should be no joints or seams along the principal strength direction of the basal reinforcement. However, if unavoidable, the overlap should have sufficient anchorage length so that overlaps are strong enough to carry design loads. (ii) The geogrid shall be measured in square metres as per planned dimensions with no allowance for overlapping at joints, anchoring at toe and crest of the slope. Make : M/s TECHFAB OR M/s TENCATE OR M/s NYLEX OR M/s MACCAFERRI
Labour only for construction of sub grade (moorum filling between two Uni-axial high strength Geo-grids layer), earthen shoulders with material obtained from above laid in layers n exc. 15 cm thick, spread, levelled to required slope, rolled and compacted with 8 to 12 tonne vibratory roller maintaining a minimum degree of compaction 98% of MDD including watering and necessary T&P all as per cross section details shown in drawing and as specified and directed. NOTE: 1. Moorum shall be obtained by excavating compacted excess moorum available after surcharge preloading. 2. Compacted thickness shall be measured for payment. 3. Lead for moorum will be measured and paid in separate items.
Labour only for Moorum filling in low lying area including spreading and levelling and necessary T&P complete all as specified and directed.
Removing excavated soil/moorum n exc. 500m and depositing where directed completed all as specified and directed. Note: Rates inclusive of removal of stacked moorum by loading and unloading.
Removing Excavated soil/moorum exc 500 m and n.exc 1.0 km and depositing where directed completed all as specified and directed. Note: Rates inclusive of removal of stacked moorum by loading and unloading.
Removing Excavated soil/moorum exc 1.0 km and n. exc 1.5 km and depositing where directed completed all as specified and directed. Note: Rates inclusive of removal of stacked moorum by loading and unloading.
Removing Excavated soil/moorum exc 1.50 km and n. exc 5.0 km and depositing where directed completed all as specified and directed. Note: Rates inclusive of removal of stacked moorum by loading and unloading.
M&L for laying and compacting 300mm (compacted thickness) Granular Sub Base (GSB) Grade V in two layers of 150mm each (grading and physical requirements as per Table 400-1 and 400-2 respectively of MORTH specification for road and bridge works) over compacted sub grade with natural sand, crushed gravel, crushed stone, crushed slag, or combination thereof as per grading required, all the materials mechanically mixed, spread and levelled on the sub grade by using motor grader of adequate capacity, and rolling with vibratory roller of capacity 80-100 kN static weight for achieving required compaction density of at least 98% of the maximum dry density including consolidating to required gradient and camber complete all as specified and as directed and finishing the surface tolerance as per table 900-1 of MORTH specifications for Road and Bridge works, 2013 complete all as specified and as directed. Notes: 1. Payment shall be made for solid quantity arrived after consolidation. 2. Compaction of granular sub base filling shall be carried out under optimum moisture conditions to achieve 98 % of modified proctor density. 3. Before execution of this item the approved material obtained from outside MD land shall be tested/checked for suitability to use. 4. The lead/royalty involved is to be ascertained by the contractor before quoting his tender and no extra payment/adjustment for increased in lead or rate of royalty due to whatsoever reason shall be admissible on his account. 5. The contractor shall use vibratory earth compactor in lieu of power roller to achieve 98% maximum dry density (MDD) at OMC without any extra cost and the method of compaction to be adopted as per recommendation of agency reporting max density at OMC 6. GSB shall be as per MORTH specification as detailed in particular specification.
M&L for laying 540 mm thick (compacted thickness) Granular Sub Base (GSB) grading as per Grade V laid in three layers of 180mm each as specified Table 400-1 of MoRTH specifications for Road and Bridge works, 2013, over compacted subgrade with natural sand, crushed gravel, crushed stone, crushed slag or combination thereof as per the grading required. The materials are mechanically mixed, spread and leveling on the subgrade by using motor grader of adequate capacity, and rolling with vibratory roller of capacity 80-100 kN static weight for achieving required compaction density of atleast 98% of the Maximum Dry Density. Consolidating to required gradient and camber complete all as specified and directed with finished surface tolerances as per Table 900-1 of MoRTH specifications for Road and Bridge works, 2013. Note: (i) Payment shall be made for solid quantity after compaction. (ii) Compaction of granular sub base filling shall be carried out under optimum moisture conditions to achieve 98% of MDD. (iii) GSB shall be laid as per MoRTH Specifications.
M&L for laying and compacting 225mm thick (compacted thickness) of Wet Mixed Macadam (WMM), in three layers of 75mm thick each manufactured in WMM plant, each layer compacted separately (physical requirements and grading as per Table 400-12 and 400-13 respectively of MORTH specification for Road and Bridge works), material comprising of clean, crushed, graded aggregate and granular material premixed with water to as dense mass, spreading using sensor paver including spreading and compacting using double drum smooth wheeled vibratory roller with 80-100 kN static weight for achieving required compaction density of at least 98% of the maximum dry density and rolled consolidated to required gradient and camber complete as specified, including the soundness test catered out on the material delivered at site as per IS 2386 (Part-5) in case the water absorption value of coarse aggregates is grater than 2%, and finishing the surface tolerances as per Table 900-1 of MORTH specifications for Road and Bridge works complete all as specified and as directed. Notes: 1. The rate quoted shall be for the entire compacted thickness (each layer shall be rolled and compacted separately as described). 2. The Maximum Dry Density shall be determined using modified proctor density determination method as per IS code on prepared GSB surface.
M&L for laying and compacting 150mm thick (compacted thickness) of Wet Mixed Macadam (WMM), in two layers of 75mm thick each manufactured in WMM plant, each layer compacted separately (physical requirements and grading as per Table 400-12 and 400-13 respectively of MORTH specification for Road and Bridge works), material comprising of clean, crushed, graded aggregate and granular material premixed with water to as dense mass, spreading using sensor paver including spreading and compacting using double drum smooth wheeled vibratory roller with 80-100 kN static weight for achieving required compaction density of at least 98% of the maximum dry density and rolled consolidated to required gradient and camber complete as specified, including the soundness test catered out on the material delivered at site as per IS 2386 (Part-5) in case the water absorption value of coarse aggregates is grater than 2%, and finishing the surface tolerances as per Table 900-1 of MORTH specifications for Road and Bridge works complete all as specified and as directed. Notes: 1. The rate quoted shall be for the entire compacted thickness (each layer shall be rolled and compacted separately as described). 2. The Maximum Dry Density shall be determined using modified proctor density determination method as per IS code on prepared GSB surface.
M&L for dry clean river sand passing through IS sieve 2.36mm and held in IS sieve 600 micron, spread and compacted to 10mm thickness complete all as specified and as directed.
M&L for 400 micron HDPE transparent sheet (Virgin Quality) water proof, wrinkle free polyethylene sheeting without puncture having minimum weight 390 gm/Sq.m. over tack coat/sand cushion as specified in design with overlap between adjacent strips as minimum 300mm and transverse joints at ends as minimum 300mm with maximum standard width available as approved by GE without joints, manufactured by multilayer technology using 100% virgin raw material, confirming to IS: 10889 complete all as specified and as directed. Notes: 1. Sand layer shall be measured and paid separately under BoQ item No. 83. 2. Company logo, IS code, and batch number shall be marked on HDPE sheet at every 2 meters. 3. Rate is inclusive of overlaps at joints.
M&L for Pavement Quality Concrete (PQC) 400 mm thick of minimum 28 days field flexural strength 45 Kg/Sq.cm. or 4.5 mPa, aggregate gradation as per Table 3 of IRC 15-2017, coarse aggregate of clean, hard, strong, dense, non-porous and durable pieces of crushed stone, fine aggregates of clean natural sand using minimum 360 Kg/Cu.m. of cement content with non-circular synthetic fibre of 12-18mm length, specific gravity 1.34 to 1.39, UV stable, alkali resistant, with equivalent dia., 15-40 micron, minimum melting temperature as 240°C and minimum tensile strength of 300 mPa and at the rate 0.25% by weight of cement, PQC laid, spread and compacted with slip-form paver of minimum 9.0m width, including curing and tinning by texturing cum curing machine including required surface texturing all as specified in Clause 10.1.14 and Table 9 of IRC 15-2017 complete all as specified and as directed. Notes: 1. Construction joints/dummy joints and expansion joints shall be measured and paid separately under respective items. 2. Deduction shall be made in computing concrete quantity for expansion joints. 3. Contractor shall consider minimum 400 Kg of cement per cubic meter of concrete while quoting this item. Actual quantity of cement shall be used as per approved design mix. No price adjustment shall be applicable for excess quantity of cement content i.e. beyond 400 Kg as per approved design mix in execution of work. 4. Non circular synthetic fibre shall be mixed in the PQC @ 0.25% of cement all as per manufacturers instructions and as directed. 5. Supply only of non circular synthetic fibre shall be measured and paid separately. 6. Cost of steel formwork and testing as specified shall be deemed to be included in the rate quoted by the tenderer. 7. Maximum working temperature shall not exceed 30 degree centigrade of atmosphere. 8. Required surface texturing to be done as specified in Clause 10.1.14 and Table 9 of IRC: 15-2017.
M&L for Pavement Quality Concrete (PQC) 150 mm thick of minimum 28 days field flexural strength 45 Kg/Sq.cm. or 4.5 mPa, aggregate gradation as per Table 3 of IRC 15-2017, coarse aggregate of clean, hard, strong, dense, non-porous and durable pieces of crushed stone, fine aggregates of clean natural sand using minimum 360 Kg/Cu.m. of cement content with non-circular synthetic fibre of 12-18mm length, specific gravity 1.34 to 1.39, UV stable, alkali resistant, with equivalent dia., 15-40 micron, minimum melting temperature as 240°C and minimum tensile strength of 300 mPa and at the rate 0.25% by weight of cement, PQC laid, spread and compacted with slip-form paver of minimum 9.0m width, including curing and tinning by texturing cum curing machine including required surface texturing all as specified in Clause 10.1.14 and Table 9 of IRC 15-2017 complete all as specified and as directed. Notes: 1. Construction joints/dummy joints and expansion joints shall be measured and paid separately under respective items. 2. Deduction shall be made in computing concrete quantity for expansion joints. 3. Contractor shall consider minimum 400 Kg of cement per cubic meter of concrete while quoting this item. Actual quantity of cement shall be used as per approved design mix. No price adjustment shall be applicable for excess quantity of cement content i.e. beyond 400 Kg as per approved design mix in execution of work. 4. Non circular synthetic fibre shall be mixed in the PQC @ 0.25% of cement all as per manufacturers instructions and as directed. 5. Supply only of non circular synthetic fibre shall be measured and paid separately. 6. Cost of steel formwork and testing as specified shall be deemed to be included in the rate quoted by the tenderer. 7. Maximum working temperature shall not exceed 30 degree centigrade of atmosphere. 8. Required surface texturing to be done as specified in Clause 10.1.14 and Table 9 of IRC: 15-2017.
Supply only non-circular, virgin, synthetic, monofilament polyester fibres of length 12mm to 18mm, specific gravity 1.34 to 1.39, UV stable, alkali resistant, equivalent diameter 15-40 micron, minimum melting temperature 250o C and minimum tensile strength 300 MPa complete all as specified and as directed. Notes:1. All properties/specifications to meet test parameters as per IS 16481:2016. 2. Design mix to be prepared after incorporating fibres.
M&L for forming 25mm wide expansion joint for 400mm thick PQC by cutting using high RPM diamond cutter of appropriate size, straight and smooth edges, early entry saw and subsequent full depth cutting, cleaning the joint thoroughly with application of compressed air and making dry, vacuum cleaned and free of dirt, oil, vegetation and other debris and filling the joint with pre-moulded 25mm thick compressible polyethylene closed cell type filler board as specified and thereafter applying two coats of primer with thin brush by forward and backward movement at an interval of 30 minutes before placing the backup rod and pouring the sealant, placing the closed cell, medium density, crossed linked polyethylene foam backup rod of 30mm dia., over filler board and filled with polyurethane based sealant (fuel resistant) complying with BS-5212, BS 4254 and EN-141875-2003 with minimum movement accommodation factor (MAF) of +/- 30% having minimum 10 years performance guarantee, applying masked tape on the edges of joints to prevent accidental spill age of sealant and removing the masking tape after filling of sealant and removing the masking tape after filling of sealant as per the method specified and directed by the manufacturer complete all as specified and as directed. Notes: 1. The polyethylene rod shall be of desired diameter having minimum density of 22 Kg/Cu.m. and compression strength of 0.40 Kg/Sq.m. of white colour. 2. Primer to be used before filling sealant. 3. The joint filler shall be pre-moulded, compressive filler board with high performance closed-cell material available in board form (HD 100) and shall comply with the requirements of ASTM-D3575/IS standards (latest revision).
M&L for forming 25mm wide expansion joint for 150mm thick PQC by cutting using high RPM diamond cutter of appropriate size, straight and smooth edges, early entry saw and subsequent full depth cutting, cleaning the joint thoroughly with application of compressed air and making dry, vacuum cleaned and free of dirt, oil, vegetation and other debris and filling the joint with pre-moulded 25mm thick compressible polyethylene closed cell type filler board as specified and thereafter applying two coats of primer with thin brush by forward and backward movement at an interval of 30 minutes before placing the backup rod and pouring the sealant, placing the closed cell, medium density, crossed linked polyethylene foam backup rod of 30mm dia., over filler board and filled with polyurethane based sealant (fuel resistant) complying with BS-5212, BS 4254 and EN-141875-2003 with minimum movement accommodation factor (MAF) of +/- 30% having minimum 10 years performance guarantee, applying masked tape on the edges of joints to prevent accidental spill age of sealant and removing the masking tape after filling of sealant and removing the masking tape after filling of sealant as per the method specified and directed by the manufacturer complete all as specified and as directed. Notes: 1. The polyethylene rod shall be of desired diameter having minimum density of 22 Kg/Cu.m. and compression strength of 0.40 Kg/Sq.m. of white colour. 2. Primer to be used before filling sealant. 3. The joint filler shall be pre-moulded, compressive filler board with high performance closed-cell material available in board form (HD 100) and shall comply with the requirements of ASTM-D3575/IS standards (latest revision).
M&L for cutting of construction joints 25mm deep and 10mm wide by early entry saw cut using diamond bit cutter of appropriate size, straight and smooth edges, cleaning the joint thoroughly with application of compressed air, making dry, vacuum cleaned and free of dirt, oil, vegetation and other debris, applying two coats of primer with thin brush by forward and backward movement at an interval of 30 minutes before placing the backup rod and pouring the sealant, placing of closed cell, medium density, crossed linked polyethylene foam backup rod of 12mm dia., applying the bond breaker tape on top of back up rod for complete width of the joint and filled with polyurethane based sealant (fuel resistant) complying with BS-5212, BS-4254 and EN-141875-2003 with minimum movement accommodation factor (MAF) of +/- 30% having minimum 10 year performance guarantee, applying masked tape on the edges of joints to prevent accidental spill age of sealant and removing the masking tape after filling of sealant as per the method specified and directed by the manufacturer complete all as specified and as directed. Notes: 1. The polyethylene rod shall be of desired diameter having minimum density of 22 Kg/Cu.m. and compression strength of 0.40 Kg/Sq.m., of white colour. 2. Primer to be used before filling sealant. 3. The Joint filler shall be pre-moulded, compressive filler board with high performance closed-cell material available in board form (HD 100) and shall comply with the requirements of ASTM-D3575/IS Standards (latest revision).
M&L for forming contraction (Dummy) joints of 8mm wide and depth 1/3 to 1/4 the thickness of slab (400mm thick PQC) using high RPM diamond cutter with and initial saw cut of 3mm soon after concrete has set, widening the first saw cut to 8mm width and 24mm deep from the top using diamond bit cutter of appropriate size, straight and smooth edges, cleaning the joint thoroughly with application of compressed air and making dry, vacuum cleaned and free of dirt, oil, vegetation and other debris, applying two coats of primer with thin brush by forward and backward movement at an interval of 30 minutes before placing the backup rod and pouring the sealant, placing of closed cell, medium density, crossed linked polyethylene foam backup rod of 10mm dia., applying the bond breaker tape on top of back up rod for complete width of the joint and filled with polyurethane based sealant (fuel resistant) complying with BS-5212, BS-4254 and EN-141875-2003 with minimum movement accommodation factor (MAF) of +/- 30% having minimum 10 year performance guarantee, applying masked tape on the edges of joints to prevent accidental spill age of sealant and removing the masking tape after filling of sealant as per the method specified and directed by the manufacturer complete all as specified and as directed. Notes: 1. The polyethylene rod shall be of desired diameter having minimum density of 22 Kg/Cu.m. and compression strength of 0.40 Kg/Sq.m., of white colour. 2. Primer to be used before filling sealant. 3. The Joint filler shall be pre-moulded, compressive filler board with high performance closed-cell material available in board form (HD 100) and shall comply with the requirements of ASTM-D3575/IS Standards (latest revision). 4. Cutting of joints shall be completed within 24 hours.
M&L for forming contraction (Dummy) joints of 8mm wide and depth 1/3 to 1/4 the thickness of slab (150mm thick PQC) using high RPM diamond cutter with and initial saw cut of 3mm soon after concrete has set, widening the first saw cut to 6mm width and 24mm deep from the top using diamond bit cutter of appropriate size, straight and smooth edges, cleaning the joint thoroughly with application of compressed air and making dry, vacuum cleaned and free of dirt, oil, vegetation and other debris, applying two coats of primer with thin brush by forward and backward movement at an interval of 30 minutes before placing the backup rod and pouring the sealant, placing of closed cell, medium density, crossed linked polyethylene foam backup rod of 10mm dia., applying the bond breaker tape on top of back up rod for complete width of the joint and filled with polyurethane based sealant (fuel resistant) complying with BS-5212, BS-4254 and EN-141875-2003 with minimum movement accommodation factor (MAF) of +/- 30% having minimum 10 year performance guarantee, applying masked tape on the edges of joints to prevent accidental spill age of sealant and removing the masking tape after filling of sealant as per the method specified and directed by the manufacturer complete all as specified and as directed. Notes: 1. The polyethylene rod shall be of desired diameter having minimum density of 22 Kg/Cu.m. and compression strength of 0.40 Kg/Sq.m., of white colour. 2. Primer to be used before filling sealant. 3. The Joint filler shall be pre-moulded, compressive filler board with high performance closed-cell material available in board form (HD 100) and shall comply with the requirements of ASTM-D3575/IS Standards (latest revision). 4. Cutting of joints shall be completed within 24 hours.
M&L for painting lines, dashes, arrows, letters etc. on roads surface with hot applied retro reflective thermoplastic paint confirming to MORTH (Clause 803.40) all as specified with 8% glass beads using special applicator machine with heating arrangement up to 160oC, including cleaning & drying the road surfaces to ensure dust, oil, grease & moisture free surface before applying paint complete all as specified and as directed.
EXTERNAL WATER SUPPLY
S&F Cast iron air release valves with two air Outlets fittings such as bends (any type, radius and angle) tapers any type, (straight, bend, increasing, decreasing or double socket etc.) tee pieces single branch, "Y" junction, double branch, cross (all sockets or socket and spigot) collars, caps and plugs up to 200 mm dia bore conforming to IS 14845 and fixing up in Cast Iron Water supply mains complete all as specified and as directed.
M&L for cutting the existing 200 mm dia DI/MS pipe for additions and alterations including necessarily done in position without taking down and inserting Tee 200x200x 150 mm for tapping including all fittings and fixtures complete all as specified and as directed.
M&L for 150 mm dia ductile iron pipe spigot and socket type centrifugally cast (spun) all as per IS:8329-2000, class K9 with flexible rubber gasket push on type joint having cement mortar lining with portland slag cement as per IS 455 : 1989 bituminous coating as per Annex 'C' of IS 8329, including provision of specials, such as tee's, elbows, bends, reducers, taper pieces complete all as specified and directed.
S&F Centrifugal pump set, 40m head and 20 LPS discharge, capacity 30 HP with suitable induction motor 1450 RPM, 3 phase AC supply complete with base, DOL starter and all accessories including all necessary electrical and water supply connections complete all as specified and as directed.
M&L for earthing complete with galvanised steel earth plate electrode 600x600x6 mm thick burried directly in ground [earth pit not less than 2.25 m deep below ground level] with top edge of Plate not less than 1.50 m below normal ground level connected to 32x6mm thick GI strip [earth lead] and GI pipe 50 mm, medium grade for earthing lead protection to the extent of maximum 7.5m, earth plate electrode surrounded by 150 mm thick packed layers of charcoal and common salt filled in alternate layers, connected to the Plate by means of GI Bolts & Nuts complete all as per electrical plate No. 3 of SSR Part – I, connected to panel / DB including testing on completion including main earthing, charcoal, common salt, PCC (1:2:4, Type B1) Pit with RCC 1:2:4, Type B1 cover, 50 mm thick with 6 Nos, 8 mm dia TMT bars in both ways, MS frame made with 40x40x6 mm Angle Iron, MS Funnel with 20 mm bore, medium grade GI Watering pipe, wire mesh, earth work excavation, return filling, removal of surplus soil etc. complete all as specified. Note: GI earth strip upto 7.5 m shall be deemed to be included in the quoted lumpsum and beyond 7.5 m shall be measured and paid separately under relevant item.
Supply, Install, test and commissioning of LT panel outdoor type floor mounted made of 3.15 mm thick, MS sheet front operated cubical type 3 phase, 4 wire AC 415 Volts complete with 50x50x6mm angle iron frame work, ventilated side louvers, suitable aluminium links/conductor from bus bar, powder coating painting as per CPRI norms complete with and including the following complete all as specified and directed.
M&L for masonry valve chamber of size 1000x1000x1000 mm (internal dimensions) comprising of 50mm thick PCC for valve including excavation and earth work in any type of soil and 200 mm thick PCC 1:4:8 type D2 (Using 40 mm graded stone aggregate) foundation, brick work in CM (1:6), plastering internal surface 15 mm thick in CM (1:4), PCC (1:3:6) type C1 (Using 20 mm graded stone aggregate) coping 50x50x6 mm angle iron 3 mm thick MS plate cover complete with locking arrangement painting steel and iron surface with two coat of synthetic enamel paint over a coat of zinc chrome primer complete all as specified and as directed.
EXTERNAL ELECTRIFICATION
Blank
Supply and lay 2 core 6 Sq.mm. cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of the following sizes complete all as specified and as directed.
M&L for cable route indicator made of CI disc 100mm dia., 6mm thick with inscription of HT cable 11000 Volts, fixed to MS angle of size 40x40x6mm, 750mm long with bolts & nuts, duly grouted in PCC 1:3:6 type C1 (Using 20mm grade stone aggregate) complete including necessary excavation and earth work complete all as specified and as directed.
Supply and lay 90x75mm bore double walled corrugated (DWC) pipe, heavy duty, for cable protection as a guard pipe including required accessories etc., of the following sizes complete all as specified and as directed.
All as per SI item No 107 above but for 40x32mm bore
Supply, Installation, testing & commissioning of Floor mounted, Outdoor Type Factory manufactured, Extendable HT 33 kV 25 kA VCB panels switchboard consisting of 800A, VCB 33 kV - 2 Nos as outgoing (suitable to existing VCB). VCB panel Outdoor type totally enclosed, free standing floor mounting type, compartment based with truck mounted vacuum circuit breaker spring operated electrically and manually charged operating mechanism suitable for horizontal isolation, horizontal draw out type VCBs with Aluminum bus bars, Self supported Insulated Busbar with full Voltage rated should be used. Complete VCB panel confirming to IEC 62271-200 standards and IP 4X class of protection comprising necessary bus-bars extension and connections and following protective and control devices as specified below. Vacuum Interrupters of the circuit breakers shall be completely encapsulated in epoxy housing. The manufacturer of circuit breaker shall also be the manufacturer of the Vacuum Interrupter, Relay. The switchgear and control gear panels shall be complete all as specified and as directed. Make: Refer List of Makes given at PS
OUTGOING - 2 Nos ( Each consisting of ) 33 kV Indoor Switchgear Panel consisting of Breaker-800A, 25 kA draw out type having following accessories for Transformer Outgoing a) 230VAC Spring Charge Motor b)110VDC Closing Coil c)110VDC Shunt Trip Coil d) Current Transformer Indoor Single Phase Resin Cast Ratio: 200-100/5-5A Core-1: 15VA Class 0.5, Core -2 15VA 5P10 e) Potential Transformer Resin cast Ratio : 33 kV/√3/110V/√3 50VA, Class: 0.5 -3 Nos g) Digital Voltmeter with VSS h) Multifunction Load Manager Class 0.5 with RS485 & Ethernet communication i) Master Trip Relay j) Auxiliary Relays for Transformer Protection k) Numerical Protection IEC 61850 Draw out Relay with Graphical display- 1 No with Three Phase O/C & E/F (50, 51, 50N, 51N, 50G, 51G), Three Phase Directional O/C & E/F (67/67N), Negative Phase Sequence O/C (46), Inrush Detection (68), Circuit Breaker Failure Protection (50BF), Broken Conductor (46BC), Three Phase O/V, U/V & NDR (27, 59, 59N) , Thermal Overload (49), Negative Sequence Overvoltage (47), Reverse Power (32), Over Frequency (81O), Under Frequency (81U), CT Supervision (60 CTS), VT Fuse Failure (60 VTS) , Auto Recloser (79), Relay shall have 8 DI and 8 DO. Makes: Refer List of Makes given at PS
l) Suitable space heater arrangement to prevent moisture condensation m) Regulated 230 VAC supply shall be arranged from an external source for misc. requirements like space heater, LED illumination etc. shall be provided at a single location inside the panel by the contractor n) Construction of plinth for 33 kV VCB: Excavation of pit of size 3.5x2.5x0.6 m, filling with sand for 150mm depth, laying bed concrete with PCC (1:4:8) using 40mm HBG metal for 150mm, construction of plinth as per drawing (2 supports) with RR Masonry as per used design/site condition and plastering all around the outer side with CM (1:5), 12 mm thick and white washing 3 coats including cost and transport of all material and labour charges for all operation incidental charges etc. completes all as specified and as directed.
Supply, Installation, testing & commissioning of floor mounted, Indoor type factory manufactured, Cable in, Cable Out HT 33 kV 25kA VCB panel switchboard consisting of 800A, VCB 33 kV - 1No. VCB panel indoor type totally enclosed, free standing floor mounting type, compartment based with truck mounted vacuum circuit breaker spring operated electrically and manually charged operating mechanism suitable for horizontal isolation, horizontal draw out type VCBs with Aluminum bus bars, Self supported Insulated Busbar with full voltage rated should be used. Complete VCB panel confirming to IEC 62271-200 standards and IP 4x class of protection comprising necessary bus-bars extension and connections and following protective and control devices as specified below. Vacuum Interrupters of the circuit breakers shall be completely encapsulated in epoxy housing. The manufacturer of circuit breaker shall also be the manufacturer of the Vacuum Interrupter, Relay. The switchgear and control gear panels shall be complete all as specified and as directed. Make: Refer List of Makes given at PS.
33 kV Indoor Switchgear Panel consisting of Breaker-800A, 25kA draw out type having following accessories a) 230V AC Spring Charge Motor b)110V DC Closing Coil c)110V DC Shunt Trip Coil d) Current Transformer Indoor Single Phase Resin Cast Ratio: 100-50/5-5A Core-1: 15VA Class 0.5, Core -2 15VA 5P10, Core -3: Class PS - 3 Nos e) Potential Transformer Resin cast Ratio : 33kV/√3/110V/√3 50VA, Class: 0.5 -3 Nos f) 12 window Annunciator g) Digital Ammeter with ASS h) Digital Voltmeter with VSS i) Multifunction Load Manager Class 0.5 with RS485 & Ethernet communication j) Master Trip Relay k) Power pack 100W with battery backup l) Numerical Protection IEC 61850 Draw out Relay with Graphical display- 1 No with Three Phase O/C & E/F (50, 51, 50N, 51N, 50G, 51G), Three Phase Directional O/C & E/F (67/67N), Negative Phase Sequence O/C (46), Inrush Detection (68), Circuit Breaker Failure Protection (50BF), Broken Conductor (46BC), Three Phase O/V, U/V & NDR (27, 59, 59N), Thermal Overload (49), Negative Sequence Overvoltage (47), Reverse Power (32), Over Frequency (81O), Under Frequency (81U), CT Supervision (60 CTS), VT Fuse Failure (60 VTS), Auto Recloser (79). Relay shall have 8 DI and 8 DO.
m) Numerical Relay Differential protection (87T) - 1 No n) Control panel consisting of Relays for WTI Alram & Trip, OTI Alarm & Trip, Bucholtz Alarm & Trip, Over load Alarm & Trip. Makes: Refer List of Makes given at PS.
Supply installation testing and commissioning of 3150 kVA 33/11 kV, delta/Star, vector group, DYN11 ONAN, outdoor type copper wound transformer with On load tap Changers having AVS relay & RTCC for automatic sensing of incoming Voltage, automatic operation of OLTC & facility for remote manual operation of OLTC, suitable for incoming voltage variation of +5% to - 15% in equal steps of 1.25% to give a constant secondary Voltage, the transformer shall be provided with fitting accessories, protection, first filling of oil & confirming to IS 2026 (P-1 to P-5) etc. i/c Buchholz relay, oil/winding temperature alarm/trip protection complete as per specifications as required, the transformer oil-Natural Oil cooled should have dielectric strength of 60 kV. No Load Losses maximum of 3.5 kW and Load Loss 27 kW, the transformer shall be provided with arrangement to terminate upto 3 core 300 sq mm XLPE cable on primary and secondary side including supplying and laying of copper conductor multicore control cable from transformer to breaker for safety tripping, suitably mounted on MS channel i/c supply and grouting of suitable MS channel with all accessories as required as directed, (temperature rise for top oil shall not exceed 50 Deg C above ambient and winding temperature rise shall not exceed 55 deg C over ambient. The transformer shall be provided with 3 Nos Surge Arrestor on HT side, Manufacturer should have Short circuit test report for similar or Higher rating transformer (Any rating), If SC test report is not available, then bidder has to conduct the same without any extra cost to the purchaser. Make: Refer List of Makes given at PS.
i) Applicable Standard IS:2026 ii) Service Outdoor iii) Fittings and Accessories iv) Rating,3.5 kVA v) Rated no load voltage a) HV, 33 kV b) LV, 11kV vi) Frequency 50 Hertz vii) List Of Accessories a) Oil Temperature Indicator 1 No. b) Winding Temperature Indicator 1 No. c) Pressure Relief Device 1 No. d) Magnetic Oil Level Gauge 1 No. e) Buchholz Relay 1 No. f) Marshalling Box (IP-65) 1 No. g) Bi-directional Roller 4 No. h) Jacking Pads 4 No. i) Conservator 1 No. j) Silica Gel Breather 1 No. k) AVR (Microcontroller Type) 1 No. l) RTCC Panel (IP-42) 1 No. m) Note: Only those figures subject to tolerances as per IS:2026 are guaranteed Upward and downward revision in weights and dimensions shall not form the basis for upward or downward revision in prices later. Prepared By: Checked By: HV, LV line and N CT's are not considered in the offer because of no technical details and if required later shall be provided on additional cost.
viii) Overloading Of Transformer IS 2026 - 7 ix) Radiator Sheet Thickness / Material 1 mm / CRCA 29 Insulating Oil Natural ESTER OIL x) Tank Sheet Thickness (Side/Top/Bottom) 5 / 5 / 5 mm xi) Paint Type Epoxy xii) Short Circuit Withstand Capability As per IS 2026 xiii) % Efficiency at 75degC/0.8 P.F. a) At 100% load 98.64 b) At 75% load 98.91 c) At 50% load 99.13 xiv) % Efficiency at 75degC/Unity PF a) At 100% load 98.91 b) At 75% load 99.12 c) At 50% load 99.30 xv) % Regulation at full load a) Unity P.F. 1.25 b) At 0.8 P.F. 5.18 xvi) Performance figures @ 3.5 MVA Base a) No load loss, kW (Max) 3.5 b) Load loss, kW (Max) 27 c) Auxiliary loss, kW NA d) Impedance,% (IS Tol) 7.15 xvii) Number of phases 3 xviii) Vector Group reference Dyn11
xix) Winding Insulation - LV Uniform - Class A xx) Winding Insulation - HV Uniform - Class A xxi) Winding BIL - HV 170 kVp/ 70 kVrms Winding BIL - HV-N NA Winding BIL - LV 75kVp / 28 kVrms Winding BIL - LV-N 75kVp / 28 kVrms xxii) Terminal arrangement, HV/LV Cable Box / cable box xxiii) Taps on winding a) Off ckt / On load On load tap changer b) Tapping range +5% to -15 % c) No. of steps 16 Steps @ 1.25% d) Tap Switch CTR/OLG xxiv) Temp. rise oil/wdg. 50/55
Supply, Installation, Testing & Commissioning of Battery Bank consisting of 110V, 55 Nos of 2 Volt 100AH VRLA Battery along with terminal connectors, wooden rack and all other accessories as per Technical specification complete all as specified and directed. Make: Amararaja/Exide/Tata Green/ Luminous
Supply, Installation, Testing and Commissioning of 110V/100AH 25A FCBC Thyristor based with in-built DCDB and RS485 communication , three Phase 4 Wire, Full Wave, Full Controlled, Thyrister based Charger with VRLA Battery in complete as specified and directed. Make: Amararaja/Exide/Tata Green/ Luminous
Supply, Lay, test and commissioning 33kV(E) grade cable suitable for earthed system having compacted circular stranded aluminum conductor shielded with semi- conducting compound water tree retardant (TR) extruded layer XLPE insulated dry and nitrogen cooled, dry cured core shielded with semi-conducting compound extruded layer followed by metallic copper foil, screened inner sheath of extruded PVC Type St 2, galvanized single flat steel strip armoured and PVC Type St 2 sheathed overall conforming to IS: 7098/Part-II/1985, amended upto date with ISI marked of size 3 core 120 Sqmm complete in trenches/ ducts/ on pole etc complete all as directed.
S&F cable jointing kit for 33 kV grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE, armoured, Aluminium conductor cable of size 120 sqmm complete all as specified and directed.
S&F cable jointing kit for 33 kV grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE, armoured, Aluminium conductor cable of size 120 Sqmm complete all as specified and directed.
S&F cable jointing kit for 33 kV grade cable for outdoor straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE, armoured, Aluminium conductor cable of size 120 Sqmm complete all as specified and directed.
Supply, lay and testing XLPE insulated and PVC sheathed, FRLS, GI Strip / Wire armoured heavy duty cable, ISI marked with Multi-stranded Copper Conductor 1100 Volt grade of size 4 Core, 2.5 Sq.mm cross section suitable for earthed system, laying in trenches / duct / fixed to poles / drawn through pipes / sleeving through pipe in duct, including suitable size Double compression copper stainless steel cable gland, crimping type cable lugs, sockets etc., complete all as specified and as directed.
Supplying, laying and testing XLPE insulated and PVC sheathed, FRLS, GI Strip / Wire armoured heavy duty cable, ISI marked with Multi-stranded Copper Conductor 1100 Volt grade of size 5 Core, 4 Sq.mm cross section suitable for earthed system, laying in trenches / duct / fixed to poles / drawn through pipes / sleeving through pipe in duct, including suitable size Double compression copper stainless steel cable gland, crimping type cable lugs, sockets etc. including taking down old Cables of any description complete all as specified and as directed.
Supplying, laying and testing XLPE insulated and PVC sheathed, FRLS, GI Strip / Wire armoured heavy duty cable, ISI marked with Multi-stranded Copper Conductor 1100 Volt grade of size 14 Core, 2.5 Sq.mm cross section suitable for earthed system, laying in trenches / duct / fixed to poles / drawn through pipes / sleeving through pipe in duct, including suitable size Double compression copper stainless steel cable gland, crimping type cable lugs, sockets etc. including taking down old Cables of any description complete all as specified and as directed.
Supply of 33kV Grade Insulating Mat as per IS 15652, of size 2000x1000 mm complete all as specified and as directed.
Material and labour for earthing of copper earth plate electrode 600x600x3.15 mm thick buried directly in ground (earth pit not less than 2.25 mtr depth below normal ground level) with top edge of earth not less than 1.5m below normal ground level connected to and including earth lead wire 4.0 mm by means of steel bolts, nuts, check nuts and washers, test point made of copper strip 20x3 mm, 10cm long PCC 1:2:4, type B1 in pit with precast RCC 1:2:4 type B1 in cover reinforced with XPM not less than 4 Kg per Sqm with 15mm bore GI light grade protection pipe, 20mm bore GI medium grade watering pipe with funnel including charcoal, dust, salt, all as shown in electric plate No 3 of SSR Part-I (2209) Specifications, complete with necessary earth work in any type of soil, removal to a distance not exceeding 50 m, including testing on completion, all as specified and directed. Note:The cost of earth work, PCC pit, CI cover,funnel, watering pipe, wire mesh, charcoal, dust, common salt, 20mm bore medium grade watering pipe & 15 mm bore light grade GI pipe as protection to earth lead wire shall be deemed included in the unit rate for earthing complete all as specified and as directed.
S&F 50x6 mm earth continuity copper strip or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit / pipe or fixed to poles or any other indicated situation for loop earthing etc. as required complete all as specified and as directed.
Supply, Install, testing & commissioning of Factory Made 11 kV, 630 Amps, 21kA for 3 Seconds, AFLR, SF6 Insulated, Motorised, Outdoor extensible type, 4 Way RMU Consisting of 1 No VCB as Incoming and 3 Nos. of VCBs as Outgoing and Metering Module With FRTU & SCADA Compatible with complete all specified and as directed and shall comprise of the following: Make: ABB / Schneider / Siemens / BHEL The make of Vacuum Interrupter & VCB of same make as the Ring Main unit. Important Note: The RMU should be manufactured at OEM factory only. No other mode of manufacturing is accepted.
(A) RMU shall be 11 kV, 630 Amps, 21 kA for 3 Seconds, Internal Arc 21kA/1Sec, AFLR, SF6 Insulated, Motorized, Outdoor, 4 Way RMU, left side extensible, right side metering Unit, SACADA compatible Overload and eart fault protection Relay (Ashidha / CSPDR) with Air Insulated Bus Connected Metering unit (Type +VVVVVV+M), type tested in line with latest IEC Standards, suitable for operations at a height up to 1000 m above sea level and at 40ºC Ambient Temperature, Switchgear and Busbar shall all be contained in a SF6 Tank shall be sealed for life robotically welded non magnetic and non ferrite Stainless Steel Enclosure (2.5 mm thickness SS304), nominal operating gas pressure 1.3 BAR @20 Deg C, RMU Tank shall provide full Insulation and Switchgear shall be insensitive to the environment with Degree of Protection of IP67 filled with SF6 gas as insulation with leakage rate less than 0.1% per year tested as per IEC 62271-200. Painting thickness shall be atleast 60 microns, Breaker shall be M2 Class- 10,000 operations at rated normal current and 10 operations at rated Short circuit breaking current. Manual welding or hermetic sealing of tank shall be not be accepted. The unit shall have front cable entry (Suitable for termination of 1R x 3C x 95.120/150 Sqmm Cable ) for ease of installation and shall have site replaceable bushings for ease of troubleshooting during breakdown. RMU should be complete with all accessories such as Terminal boots, VPIS, cable supports, all front cable terminations, mechanical indications for VCB and Load break switch ON/OFF, Manometer as per with IEC standards 62271-200, 60056, 60129, 60265, 60298, 60420, 60529 and 60694.
Altitude of installation up to 1000m as per IEC 60120. Bushings bolted type top mounted outside the tank for connection of external bus bar. Switchgear Operating Mechanism shall have an IP2X Protection and Cable Chamber shall have IP3X Protection, Outer Enclosure shall be IP 54 type tested, Painting (FRONT COVER RMU: RAL7035 & (FOR MIMIC RAL7043)) & ENCLOSURE: RAL7035 & (TOP COVER & BASE STAND IN RAL 7043)). The unit shall be internal arc proof 21kA for 1 se with AFLR classification, tested and totally safe for human beings. The gas release & personnel safety from internal arc shall not depend on plinth design. The release of gas to be from the top of the unit, so that, even if the person is operating the unit, opening the cover, & there are personnel near the sides of the RMU/plinth, top release will ensure their safety. The hot gas release, in case of an internal arc, in no case should be from any side or bottom of the unit, as the same is unsafe for the operating personnel/pedestrian or general public. Bidder shall provide type test report to prove compliance to the Internal Arc fault IAC-AFLR as per IEC 62271-200. Internal arc testing shall be done with enclosure door in open condition, with switching devices in operation mode as per specified standard. The Vacuum Bottle shall be of same make as RMU Manufacturer .
(B) Vacuum Circuit Breaker (VCB) Each shall be comprising of the following: (i) 11 kV, 630 Amps, 21 kA/ 3s, 3 Pole Manual/ Motorised VCB with 3 pole manual disconnector and 3 pole manual earth switch, manual/ motorized Spring Assisted Mechanism and Series Trip Coil – 1 No. (ii) Self Powered Relay with O/C, S/C, E/F Protection – 1 No (iii) CT Ratio 200-100/1A, Class - 1.0, 2.5VA for Metering and CT Ratio 200-100/1A, Class 5P10, 2.5 VA for Protection – 1 Set each (iv) Live Cable Indicator with indications at the Front and Three Inlets to check the Synchronization of Phases – 1 No (v) Cable Termination Bushing suitable for up to 1 Run, 3 Core, 185 Sq.mm, XLPE Cable – 1 Set (vi) Cable Termination Cover Boots (Push on type) – 1 Set (C) Vacuum Circuit Breaker (VCB) Each shall be comprising of the following: (i) 11 kV, 630 Amps, 21 kA/ 3s, 3 Pole Manual/ Motorised VCB with 3 pole manual disconnector and 3 pole manual earth switch, manual/ motorized Spring Assisted Mechanism and Series Trip Coil – 1 No. (ii) Self Powered Relay with O/C, S/C, E/F Protection – 1 No (iii) CT Ratio 200-100/1A, Class - 1.0, 2.5VA for Metering and CT Ratio 200-100/1A, Class 5P10, 2.5 VA for Protection – 1 Set each (iv) Live Cable Indicator with indications at the Front and Three Inlets to check the Synchronization of Phases – 1 No (v) Cable Termination Bushing suitable for up to 1 Run, 3 Core, 185 Sqmm, XLPE Cable-1 Set (vi) Cable Termination Cover Boots (Push on type) – 1 Set
Supply, Fix, connecting, testing and commissioning of OEM Manufactured APFC Panel (automatic and manual operation) with 7% Aluminium reactor of capacity 100 kVAR (Output) @ 440 V AC interconnection with LT Panel/ Transformer (outdoor/indoor) with appropriate size of electric power cable 1.1 kV . The stage rating shall be (50+25+15) + (5x2) kVAR. The APFC Panel shall be fully type tested at an independent Laboratory and shall comply with IEC 61439-1&2 and IEC 61921, IS-16636-2017. The degree of protection of enclosure system of the APFC Panel shall be min IP 54 (Outdoor) in accordance with IEC 60529. The capacitor bank shall be internet of things (IoT) enabled and communicable / integral with BMS. The APFC Panel shall be Outdoor type confirming to IS 13341:1992 & IS13440:1993 floor mounted design fabricated out of 14 SWG CRCA Sheet treated through chemical with 8 tank process method of degreasing,derusting and phosphating powder coating (60-80 microns), painted in SIEMENS GREY (RAL 7032) shade powder coating paint, weather, dust and vermin proof suitable for humidity upto 95% and having four nos iron legs made of 50x50x6mm thick, 60cm long angle iron below frame with front door and side/back opening having locking arrangement prewired with copper conductor PVC insulated wire size 2.5 sqmm/ extension strips and connected with suitable size thimbles & lugs. The legs duly embedded in ground (45cm) in PCC 1:3:6 type C1 (using 20mm aggregate), Cable entry from bottom.
Transparent Acrylic sheet/Bakelite sheet will be provided for shrouding, Average daily temperature : +35 degree celcius max, Ambient temperature :-5 degree celcius to 40 degree celcius, Maximum altitude 2000m. The OEM 's specified cannot authorize any other partners / sub vendors to manufacture APFC Panels on their behalf . The APFC Panel manufactured by OEM's only will be accepted & factory acceptance test (FAT) will be carried out at OEM's plant only. The APFC Panel shall be comprising of the followings:-
(D) Accessories D(i) Capacitor Units: The capacitor unit shall be metalized polypropylene film with Zn/Al alloy for 480Volts. The capacitors shall be encapsulated in an aluminium enclosure. The capacitor unit shall have a rated Voltage of 480Volts and shall have a maximum over current capacity of 2.5 In. The capacitor unit shall have a built in 3 phase over pressure protection and shall have discharge resistors (50V in 1min) factory fitted and shall be tamper proof . Capacitance Tolerance -5% +10%. Maximum permissible over Voltage 1.1 x Un, 8h every 24 Hour. The capacitor unit shall be of certified design confirming to IS-13340-1993,13341-1992 & IEC-60831-1&2. Approved makes: ABB/SCHNEIDER/SIEMENS/L&T (applicable for inside components of Panel Board) D(ii). Short circuit and Overload Protection : Each stage of the APFC Panel shall have a suitably rated MCCB for short circuit and overload protection. The over current setting shall be adjustable & breaking capacity Ics => 36KA . The MCCB shall be of certified design fort TP 36 kA T/M based release with O/L & S/C Protection-01 No confirming to IEC 60947-1, 2 & 3. The Detuned Reactor (Al wound) should be equipped with Thermal switch inside the winding which should cut off the respective contactor in case of Over temperature. Tolerance of reactors shall not exceed +/-3% of rated value. Approved makes: ABB/SCHNEIDER/SIEMENS/L&T (applicable for inside components of Panel Board) D(iii) Stage Contactor : The capacitor duty contactors shall be rated for 230 Volts AC and shall be 3 pole type and shall be employed for switching on and switching off operations in capacitor banks. The contactor shall be AC-3 duty type. The contactor shall be of certified design conforming to IEC 60947-1 & 4-1. Approved makes: ABB/SCHNEIDER/SIEMENS/L&T (applicable for inside components of Panel Board)
D(iv) Reactor: Harmonics blocks reactors(01 No) Al wound with 7% filtering factor shall be connected in series with each capacitor stage and shall be of iron cored type . The Reactor should be equipped with thermal switch inside the winding which should cutoff the respective contactor in case of Over temperature. Tolerance of reactors shall not exceed +/-3% of rated value. The reactors shall be of certified design confirming to IEC 60076-6. Approved makes: ABB/SCHNEIDER/SIEMENS/L&T (applicable for inside components of Panel Board)
All as per Serial Item No. 136-140 above but 200 kVAR (3x50)+ (2x12.5)+ (1x25)
All as per Serial Item No. 136-140 above but 300 kVAR (1x100)+ (3x50)+ (2x25)
Supply, fix, testing and commissioning of LT FPB made out of CRCA sheet 3 mm thick indoor Pedestal type totally enclosed with front and rear opening, hinged doors with projected an raised platform of suitable size weather and water proof with necessary locking arrangements along with lugs, cable glands of various sizes for cables, danger notice plate, stickering of Switcher gear about termination of switch gear, and the nuts/ bolts etc., used are to be made of rust proof material including as per IS: 8623 tinned copper bus bar with insulators suitable for three phase and four wire LT AC, 50 Hz 415 V 1500 A capacity complete with powder coating, necessary internal electric connection as required with and including the following complete all as specified and as directed.
Incoming: LT switch gear 440 Volts 3 phase, 4 wire 50 cycles, cubicle or truck type complete with air circuit breaker, with microprocessor release IPR -E electrical draw type 1000 Amps, 100 kA , overload protection, No-Volt release with necessary CTs, meter and cable boxes of rating upto - 01 No Outgoing: a) MCCB, AC 3 Phase, 415 V, 50Hz, 4 pole, 800Amps capacity 100 kA with adjustable type thermal and magnetic setting relays - 02 Nos b) MCCB AC 3 Phase 415 V, 50Hz 4 pole 200 A capacity 36 kA with adjustable type thermal and magnetic setting relays - 01 Nos c) Intelligent Panel meter to measure Voltage, current, frequency, power factor, etc with all connected CTs d) LED indicating lamps with colour Red, Yellow, Blue - 01 Set Approved makes: ABB/SCHNEIDER/SIEMENS/L&T (applicable for inside components of Panel Board)
Supply, fix, testing and commissioning of LT FPB made out of CRCA sheet 3.15 mm thick outdoor Pedestal type totally enclosed with front and rear opening, hinged doors with projected an raised platform of suitable size weather and water proof with necessary locking arrangements along with lugs, cable glands of various sizes for cables, danger notice plate, stickering of Switcher gear about termination of switch gear, and the nuts/ bolts etc used are to be made of rust proof material incl as per IS: 8623 tinned copper bus bar with insulators suitable for three phase and four wire LT AC, 50 Hz 415 V 1200 A capacity complete with powder coating, necessary internal electric connection as required with and including the following complete all as specified and as directed.
Incoming: MCCB AC 3 Phase 415 V, 50Hz 4 pole 800A capacity 100 kA with adjustable type thermal and magnetic setting relays - 01 No Outgoing: a) MCCB AC 3 Phase 415 V, 50Hz 4 pole 500A capacity 36 kA with adjustable type thermal and magnetic setting relays - 02 Nos b) MCCB AC 3 Phase 415 V, 50Hz 4 pole 100 A capacity 50 kA with adjustable type thermal and magnetic setting relays - 01 No c) MCCB AC 3 Phase 415 V, 50Hz 4 pole 63A capacity 25 kA with adjustable type thermal and magnetic setting relays - 01 No d) MCCB AC 3 Phase 415 V, 50Hz 4 pole 125A capacity 50 kA with adjustable type thermal and magnetic setting relays - 01 No e) MCCB AC 3 Phase 415 V, 50Hz 4 pole 32 A capacity 25 kA with adjustable type thermal and magnetic setting relays - 01 No f) MCB TPN 20 Amp 10 kA, 3 Pole, thermal magnetic release, with adjustable type overload protection, short circuit protection, with necessary CTs, meters and cable boxes -03 Nos g) Intelligent Panel meter to measure Voltage, current, frequency, power factor, etc with all connected CTs h) LED indicating lamps with colour Red, Yellow, Blue - 01 Set Approved makes: ABB/SCHNEIDER/SIEMENS/L&T (applicable for inside components of Panel Board)
Supply, fix, testing and commissioning of LT FPB made out of CRCA sheet 2 mm thick indoor Pedestal type totally enclosed with front and rear opening, hinged doors with projected an raised platform of suitable size weather and water proof with necessary locking arrangements along with lugs, cable glands of various sizes for cables, danger notice plate, stickering of Switcher gear about termination of switch gear, and the nuts/ bolts etc used are to be made of rust proof material incl as per IS: 8623 tinned copper bus bar with insulators suitable for three phase and four wire LT AC, 50 Hz 415 V 3000 A capacity complete with powder coating, necessary internal electric connection as required with and including the following complete all as specified and as directed.
Incoming: LT switch gear 440 Volts 3 phase, 4 wire 50 cycles, cubicle or truck type complete with air circuit breaker, with microprocessor release IPR -E electrical draw type 2000 Amp, 200 kA , overload protection, no-Volt release with necessary CTs, meter and cable boxes of rating upto - 01 No Outgoing: MCCB AC 3 Phase 415 V, 50Hz 4 pole 1600A capacity 100 kA with adjustable type thermal and magnetic setting relays - 02 Nos MCCB AC 3 Phase 415 V, 50Hz 4 pole 400 A capacity 36 kA with adjustable type thermal and magnetic setting relays - 01 Nos d) Intelligent Panel meter to measure Voltage, current, frequency, power factor, etc with all connected CTs c) LED indicating lamps with colour Red, Yellow, Blue - 01 Set Approved makes: ABB/SCHNEIDER/SIEMENS/L&T (applicable for inside components of Panel Board)
Supply, fix, testing and commissioning of LT FPB made out of CRCA sheet 3.15 mm thick outdoor Pedestal type totally enclosed with front and rear opening, hinged doors with projected an raised platform of suitable size weather and water proof with necessary locking arrangements along with lugs, cable glands of various sizes for cables, danger notice plate, stickering of Switcher gear about termination of switch gear, and the nuts/ bolts etc used are to be made of rust proof material incl as per IS: 8623 tinned copper bus bar with insulators suitable for three phase and four wire LT AC, 50 Hz 415 V 2400 A capacity complete with powder coating, necessary internal electric connection as required with and including the following complete all as specified and as directed.
Incoming: MCCB AC 3 Phase 415 V, 50Hz 4 pole 1600A capacity 100 kA with adjustable type thermal and magnetic setting relays - 01 Nos Outgoing: a) MCCB AC 3 Phase 415 V, 50Hz 4 pole 630A capacity 36 kA with adjustable type thermal and magnetic setting relays - 02 Nos b) MCCB AC 3 Phase 415 V, 50Hz 4 pole 160 A capacity 36 kA with adjustable type thermal and magnetic setting relays - 02 Nos c) MCCB AC 3 Phase 415 V, 50Hz 4 pole 400 A capacity 50 kA with adjustable type thermal and magnetic setting relays - 02 Nos d) MCCB AC 3 Phase 415 V, 50Hz 4 pole 500 A capacity 50 kA with adjustable type thermal and magnetic setting relays - 01 Nos e) MCB TPN 20 Amp 10 kA, 3 Pole, thermal magnetic release, with adjustable type overload protection, short circuit protection, with necessary CTs, meters and cable boxes-03 Nos f) MCB SPN 20 Amp 10 kA, 3 Pole, thermal magnetic release, with adjustable type overload protection, short circuit protection, with necessary CTs, meters and cable boxes -01 Nos g) Intelligent Panel meter to measure Voltage, current, frequency, power factor, etc with all connected CTs h) LED indicating lamps with colour Red, Yellow, Blue - 01 Set Approved makes: ABB/SCHNEIDER/SIEMENS/L&T (applicable for inside components of Panel Board)
Supply, fix, testing and commissioning of LT FPB made out of CRCA sheet 3.15 mm thick outdoor Pedestal type totally enclosed with front and rear opening, hinged doors with projected an raised platform of suitable size weather and water proof with necessary locking arrangements along with lugs, cable glands of various sizes for cables, danger notice plate, stickering of Switcher gear about termination of switch gear, and the nuts/ bolts etc used are to be made of rust proof material incl as per IS: 8623 tinned copper bus bar with insulators suitable for three phase and four wire LT AC, 50 Hz 415 V 800 A capacity complete with powder coating, necessary internal electric connection as required with and including the following complete all as specified and as directed.
Incoming: MCCB AC 3 Phase 415 V, 50Hz 4 pole 500A capacity 36 kA with adjustable type thermal and magnetic setting relays - 01 Nos Outgoing: a) Deleted b) MCCB AC 3 Phase 415 V, 50Hz 4 pole 40 A capacity 36 kA with adjustable type thermal and magnetic setting relays - 03 Nos c) MCCB AC 3 Phase 415 V, 50Hz 4 pole 63 A capacity 25 kA with adjustable type thermal and magnetic setting relays - 06 Nos d) MCCB AC 3 Phase 415 V, 50Hz 4 pole 32 A capacity 25 kA with adjustable type thermal and magnetic setting relays - 01 Nos e) Intelligent Panel meter to measure Voltage, current, frequency, power factor, etc with all connected CTs f) LED indicating lamps with colour Red, Yellow, Blue - 01 Set Approved makes: ABB/SCHNEIDER/SIEMENS/L&T (applicable for inside components of Panel Board)
Supply, fix, testing and commissioning of LT FPB made out of CRCA sheet 3.15 mm thick outdoor Pedestal type totally enclosed with front and rear opening, hinged doors with projected an raised platform of suitable size weather and water proof with necessary locking arrangements along with lugs, cable glands of various sizes for cables, danger notice plate, stickering of Switcher gear about termination of switch gear, and the nuts/ bolts etc used are to be made of rust proof material incl as per IS: 8623 tinned copper bus bar with insulators suitable for three phase and four wire LT AC, 50 Hz 415 V 600 A capacity complete with powder coating, necessary internal electric connection as required with and including the following complete all as specified and as directed.
Incoming: MCCB AC 3 Phase 415 V, 50Hz 4 pole 400A capactiy 36 kA with adjustable type thermal and magnetic setting relays - 01 Nos Outgoing: a) Deleted b) Deleted c) MCCB AC 3 Phase 415 V, 50Hz 4 pole 40 A capacity 25 kA with adjustable type thermal and magnetic setting relays - 03 Nos d) MCCB AC 3 Phase 415 V, 50Hz 4 pole 32 A capacity 25 kA with adjustable type thermal and magnetic setting relays - 01 Nos e) MCCB AC 3 Phase 415 V, 50Hz 4 pole 63 A capacity 25 kA with adjustable type thermal and magnetic setting relays - 06 Nos f) Intelligent Panel meter to measure Voltage, current, frequency, power factor, etc with all connected CTs g) LED indicating lamps with colour Red, Yellow, Blue - 01 Set Approved makes: ABB/SCHNEIDER/SIEMENS/L&T (applicable for inside components of Panel Board)
Supply, fix, testing and commissioning of LT FPB made out of CRCA sheet 2.0 mm thick indoor Pedestal type totally enclosed with front and rear opening, hinged doors with projected an raised platform of suitable size weather and water proof with necessary locking arrangements along with lugs, cable glands of various sizes for cables, danger notice plate, stickering of Switcher gear about termination of switch gear, and the nuts/ bolts etc used are to be made of rust proof material incl as per IS: 8623 tinned copper bus bar with insulators suitable for three phase and four wire LT AC, 50 Hz 415 V 3000 A capacity complete with powder coating, necessary internal electric connection as required with and including the following complete all as specified and as directed.
Incoming: LT switch gear 440 Volts 3 phase, 4 wire 50 cycles, cubicle or truck type complete with air circuit breaker, with microprocessor release IPR -E eletrical draw type 2000 Amps, 100 kA, overload protection, No-Volt release with necessary CTs, meter and cable boxes of rating upto - 01 No Outgoing: MCCB AC 3 Phase 415 V, 50Hz 4 pole 1600A capacity 1000 kA with adjustable type thermal and magnetic setting relays - 02 Nos MCCB AC 3 Phase 415 V, 50Hz 4 pole 400 A capacity 36 kA with adjustable type thermal and magnetic setting relays - 01 Nos d) Intelligent Panel meter to measure Voltage, current, frequency, power factor, etc with all connected CTs c) LED indicating lamps with colour Red, Yellow, Blue - 01 Set Approved makes: ABB/SCHNEIDER/SIEMENS/L&T (applicable for inside components of Panel Board)
Supply, fix, testing and commissioning of LT FPB made out of CRCA sheet 3.15 mm thick outdoor Pedestal type totally enclosed with front and rear opening, hinged doors with projected an raised platform of suitable size weather and water proof with necessary locking arrangements along with lugs, cable glands of various sizes for cables, danger notice plate, stickering of Switcher gear about termination of switch gear, and the nuts/ bolts etc used are to be made of rust proof material incl as per IS: 8623 tinned copper bus bar with insulators suitable for three phase and four wire LT AC, 50 Hz 415 V 2400 A capacity complete with powder coating, necessary internal electric connection as required with and including the following complete all as specified and as directed.
Incoming: MCCB AC 3 Phase 415 V, 50Hz 4 pole 1600A capacity 100 kA with adjustable type thermal and magnetic setting relays - 01 Nos Outgoing: a) MCCB AC 3 Phase 415 V, 50Hz 4 pole 500 capacity 36 kA with adjustable type thermal and magnetic setting relays - 02 Nos b) MCCB AC 3 Phase 415 V, 50Hz 4 pole 160 A capacity 36 kA with adjustable type thermal and magnetic setting relays - 01 No c) MCCB AC 3 Phase 415 V, 50Hz 4 pole 400 A capacity 50 kA with adjustable type thermal and magnetic setting relays - 02 Nos d) MCCB AC 3 Phase 415 V, 50Hz 4 pole 320 A capacity 50 kA with adjustable type thermal and magnetic setting relays - 01 Nos e) MCB TPN 20 Amp 10 kA, 3 Pole, thermal magnetic release, with adjustable type overload protection, short circuit protection, with necessary CTs, meters and cable boxes. -03 Nos f) MCB SPN 20 Amp 10 kA, 3 Pole, thermal magnetic release, with adjustable type overload protection, short circuit protection, with necessary CTs, meters and cable boxes. -01 Nos g) Intelligent Panel meter to measure Voltage, current, frequency, power factor, etc with all connected CTs h) LED indicating lamps with colour Red, Yellow, Blue - 01 Set Approved makes: ABB/SCHNEIDER/SIEMENS/L&T (applicable for inside components of Panel Board)
Supply, fix, testing and commissioning of LT FPB made out of CRCA sheet 3.15 mm thick outdoor Pedestal type totally enclosed with front and rear opening, hinged doors with projected an raised platform of suitable size weather and water proof with necessary locking arrangements along with lugs, cable glands of various sizes for cables, danger notice plate, stickering of Switcher gear about termination of switch gear, and the nuts/ bolts etc used are to be made of rust proof material incl as per IS: 8623 tinned copper bus bar with insulators suitable for three phase and four wire LT AC, 50 Hz 415 V 500 A capacity complete with powder coating, necessary internal electric connection as required with and including the following complete all as specified and as directed.
Incoming: MCCB AC 3 Phase 415 V, 50Hz 4 pole 320A capacity 100 kA with adjustable type thermal and magnetic setting relays - 01 Nos Outgoing: a) Deleted b) MCCB AC 3 Phase 415 V, 50Hz 4 pole 40 A capacity 36 kA with adjustable type thermal and magnetic setting relays - 05 Nos c) MCCB AC 3 Phase 415 V, 50Hz 4 pole 32 A capacity 50 kA with adjustable type thermal and magnetic setting relays - 02 Nos d) MCCB AC 3 Phase 415 V, 50Hz 4 pole 63 A capacity 50 kA with adjustable type thermal and magnetic setting relays - 04 Nos e) Intelligent Panel meter to measure Voltage, current, frequency, power factor, etc with all connected CTs f) LED indicating lamps with colour Red, Yellow, Blue - 01 Set Approved makes: ABB/SCHNEIDER/SIEMENS/L&T (applicable for inside components of Panel Board)
Supply, fix, testing and commissioning of LT FPB made out of CRCA sheet 3.15 mm thick outdoor Pedestal type totally enclosed with front and rear opening, hinged doors with projected an raised platform of suitable size weather and water proof with necessary locking arrangements along with lugs, cable glands of various sizes for cables, danger notice plate, stickering of Switcher gear about termination of switch gear, and the nuts/ bolts etc used are to be made of rust proof material incl as per IS: 8623 tinned copper bus bar with insulators suitable for three phase and four wire LT AC, 50 Hz 415 V 600 A capacity complete with powder coating, necessary internal electric connection as required with and including the following complete all as specified and as directed.
Incoming: MCCB AC 3 Phase 415 V, 50Hz 4 pole 400A capacity 100 kA with adjustable type thermal and magnetic setting relays - 01 No Outgoing: MCCB AC 3 Phase 415 V, 50Hz 4 pole 32A capacity 50 kA with adjustable type thermal and magnetic setting relays - 01 No MCCB AC 3 Phase 415 V, 50Hz 4 pole 250 A capacity 50 kA with adjustable type thermal and magnetic setting relays - 02 Nos MCCB AC 3 Phase 415 V, 50Hz 4 pole 63 A capacity 50 kA with adjustable type thermal and magnetic setting relays - 01 No d) Intelligent Panel meter to measure Voltage, current, frequency, power factor, etc with all connected CTs c) LED indicating lamps with colour Red, Yellow, Blue - 01 Set Approved makes: ABB/SCHNEIDER/SIEMENS/L&T (applicable for inside components of Panel Board)
Supply, fix, testing and commissioning of LT FPB made out of CRCA sheet 2.00 mm thick indoor Pedestal type totally enclosed with front and rear opening, hinged doors with projected an raised platform of suitable size weather and water proof with necessary locking arrangements along with lugs, cable glands of various sizes for cables, danger notice plate, stickering of Switcher gear about termination of switch gear, and the nuts/ bolts etc used are to be made of rust proof material incl as per IS: 8623 tinned copper bus bar with insulators suitable for three phase and four wire LT AC, 50 Hz 415 V 3800 A capacity complete with powder coating, necessary internal electric connection as required with and including the following complete all as specified and as directed.
Incoming: LT switch gear 440 Volts 3 phase, 4 wire 50 cycles, cubicle or truck type complete with air circuit breaker, with microprocessor release IPR -E electrical draw type 2500 Amps, 200 kA , overload protection, No-Volt release with necessary CTs, meter and cable boxes of rating upto - 01 No Outgoing: MCCB AC 3 Phase 415 V, 50Hz 4 pole 2000A capacity 100 kA with adjustable type thermal and magnetic setting relays - 02 Nos MCCB AC 3 Phase 415 V, 50Hz 4 pole 500 A capacity 36 kA with adjustable type thermal and magnetic setting relays - 01 No d) Intelligent Panel meter to measure Voltage, current, frequency, power factor, etc with all connected CTs c) LED indicating lamps with colour Red, Yellow, Blue - 01 Set Approved makes: ABB/SCHNEIDER/SIEMENS/L&T (applicable for inside components of Panel Board)
Supply, fix, testing and commissioning of LT FPB made out of CRCA sheet 3.15 mm thick outdoor Pedestal type totally enclosed with front and rear opening, hinged doors with projected an raised platform of suitable size weather and water proof with necessary locking arrangements along with lugs, cable glands of various sizes for cables, danger notice plate, stickering of Switcher gear about termination of switch gear, and the nuts/ bolts etc used are to be made of rust proof material incl as per IS: 8623 tinned copper bus bar with insulators suitable for three phase and four wire LT AC, 50 Hz 415 V 3800 A capacity complete with powder coating, necessary internal electric connection as required with and including the following complete all as specified and as directed.
Incoming: MCCB AC 3 Phase 415 V, 50Hz 4 pole 2000A capacity 100 kA with adjustable type thermal and magnetic setting relays - 01 No Outgoing: MCCB AC 3 Phase 415 V, 50Hz 4 pole 63 capacity 50 kA with adjustable type thermal and magnetic setting relays - 01 No MCCB AC 3 Phase 415 V, 50Hz 4 pole 800 A capacity 36 kA with adjustable type thermal and magnetic setting relays - 01 No MCCB AC 3 Phase 415 V, 50Hz 4 pole 500 A capacity 36 kA with adjustable type thermal and magnetic setting relays - 01 No MCCB AC 3 Phase 415 V, 50Hz 4 pole 1000 A capacity 25 kA with adjustable type thermal and magnetic setting relays - 02 Nos d) Intelligent Panel meter to measure Voltage, current, frequency, power factor, etc with all connected CTs c) LED indicating lamps with colour Red, Yellow, Blue - 01 Set Approved makes: ABB/SCHNEIDER/SIEMENS/L&T (applicable for inside components of Panel Board)
Supply, fix, testing and commissioning of LT FPB made out of CRCA sheet 3.15 mm thick outdoor Pedestal type totally enclosed with front and rear opening, hinged doors with projected an raised platform of suitable size weather and water proof with necessary locking arrangements along with lugs, cable glands of various sizes for cables, danger notice plate, stickering of Switcher gear about termination of switch gear, and the nuts/ bolts etc used are to be made of rust proof material incl as per IS: 8623 tinned copper bus bar with insulators suitable for three phase and four wire LT AC, 50 Hz 415 V 1200 A capacity complete with powder coating, necessary internal electric connection as required with and including the following complete all as specified and as directed.
Incoming: MCCB AC 3 Phase 415 V, 50Hz 4 pole 800A capacity 36 kA with adjustable type thermal and magnetic setting relays - 01 No Outgoing: a) MCCB AC 3 Phase 415 V, 50Hz 4 pole 400 A capacity 20 kA with adjustable type thermal and magnetic setting relays - 03 No b) MCCB AC 3 Phase 415 V, 50Hz 4 pole 40 A capacity 36 kA with adjustable type thermal and magnetic setting relays - 01 No c) Intelligent Panel meter to measure Voltage, current, frequency, power factor, etc with all connected CTs d) LED indicating lamps with colour Red, Yellow, Blue - 01 Set Approved makes: ABB/SCHNEIDER/SIEMENS/L&T (applicable for inside components of Panel Board)
Supply, fix, testing and commissioning of LT FPB made out of CRCA sheet 3.15 mm thick outdoor Pedestal type totally enclosed with front and rear opening, hinged doors with projected an raised platform of suitable size weather and water proof with necessary locking arrangements along with lugs, cable glands of various sizes for cables, danger notice plate, stickering of Switcher gear about termination of switch gear, and the nuts/ bolts etc used are to be made of rust proof material incl as per IS: 8623 tinned copper bus bar with insulators suitable for three phase and four wire LT AC, 50 Hz 415 V 800 A capacity complete with powder coating, necessary internal electric connection as required with and including the following complete all as specified and as directed.
Incoming: MCCB AC 3 Phase 415 V, 50 Hz 4 pole 500 A capacity 36 kA with adjustable type thermal and magnetic setting relays - 01 No Outgoing: a)MCCB AC 3 Phase 415 V, 50Hz 4 pole 250 A capacity 20 kA with adjustable type thermal and magnetic setting relays - 03 Nos b) Intelligent Panel meter to measure Voltage, current, frequency, power factor, etc with all connected CTs c) LED indicating lamps with colour Red, Yellow, Blue - 01 Set Approved makes: ABB/SCHNEIDER/SIEMENS/L&T (applicable for inside components of Panel Board)
Supply, fix, testing and commissioning of LT FPB made out of CRCA sheet 3.15 mm thick outdoor Pedestal type totally enclosed with front and rear opening, hinged doors with projected and raised platform of suitable size weather and water proof with necessary locking arrangements along with lugs, cable glands of various sizes for cables, danger notice plate, stickering of Switcher gear about termination of switch gear, and the nuts/ bolts etc used are to be made of rust proof material incl as per IS: 8623 tinned copper bus bar with insulators suitable for three phase and four wire LT AC, 50 Hz 415 V 1500 A capacity complete with powder coating, necessary internal electric connection as required with and including the following complete all as specified and as directed.
Incoming: MCCB AC 3 Phase 415 V, 50Hz 4 pole 1000A capacity 36 kA with adjustable type thermal and magnetic setting relays - 01 No Outgoing: MCCB AC 3 Phase 415 V, 50Hz 4 pole 250A capacity 20 kA with adjustable type thermal and magnetic setting relays - 03 Nos MCCB AC 3 Phase 415 V, 50Hz 4 pole 40 A capacity 20 kA with adjustable type thermal and magnetic setting relays - 01 No MCCB AC 3 Phase 415 V, 50Hz 4 pole 125 A capacity 20 kA with adjustable type thermal and magnetic setting relays - 04 Nos d) Intelligent Panel meter to measure Voltage, current, frequency, power factor, etc with all connected CTs c) LED indicating lamps with colour Red, Yellow, Blue - 01 Set Approved makes: ABB/SCHNEIDER/SIEMENS/L&T (applicable for inside components of Panel Board)
S&F Loop in loop out box of FRP made with IP 65 protection of thermoplastic circuit breaker boxes with metric knock outs for cable entry and exit, combi climate cable glands of IP 66/ IP 67 for cable entry and Grommets IP 65 for conduit for cable exit with MCB 6 Amps, 10 kA, 'C' Curve Overload and Short Circuit protection, terminals as bus terminals for cable with necessary fixing arrangements and with cable glands, etc., complete all as specified and as directed.
S&F time switches 415 Volts, three Phase, 20 Amps rating with contactor fitted inside steel enclosure complete all as specified and as directed.
Supply and Lay 180x152 mm bore Double walled corrugated pipe (DWC) heavy duty for cable protection as a guard pipe including required accessories etc., complete all as specified and directed.
Supply and Lay 160x135 mm bore Double walled corrugated pipe (DWC) heavy duty for cable protection as a guard pipe including required accessories etc., complete all as specified and directed.
Supply and Lay 120x103 mm bore Double walled corrugated pipe (DWC) heavy duty for cable protection as a guard pipe including required accessories etc., complete all as specified and directed.
Supply and Lay 110x95mm bore Double walled corrugated pipe (DWC) heavy duty for cable protection as a guard pipe including required accessories etc., complete all as specified and directed.
Supply and Lay 90x75mm bore Double walled corrugated pipe (DWC) heavy duty for cable protection as a guard pipe including required accessories etc., complete all as specified and directed.
Supply and Lay 77x63mm bore Double walled corrugated pipe (DWC) heavy duty for cable protection as a guard pipe including required accessories etc., complete all as specified and directed.
M&L for Cable Route Indicator made of CI disc of size 100mm dia, 6mm thick with inscription of HT Cable / 11000 Volts fixed to MS angle of size 40x40x6mm, 750mm long with bolts & nuts, duly embedded in PCC, 1:3:6, Type C1 complete including necessary excavation and earth work all as specified and as directed.
M&L for RCC Cable Route Indicator semi-circular shape on top of size 600x450x100 mm casted in PCC 1:3:6 with TMT bars 10 mm dia and foundation base casted in RCC 1:2:4 embedded in earth upto 550 mm duly engraved the following letters "HT UG Cable 33 kV" with two coats of anti fungal weather proof paint etc., complete all as specified and as directed.
Boring of holes under road, pavement, hard standing by trenchless technology using ultra sounding technique and necessary machine including HDPE pipe of 150 mm dia suitable for 0.4 mPa working pressure complete all as specified and as directed.
Blank
M&L for Cutting the tarmac / hard standings and excavating in trenches across the road for laying cable including making good the excavated portion by means of PCC 1:3:6, type C1 matching with the surroundings complete all as specified and as directed.
Sewage Disposal
M&L for precast cement concrete solid block masonry with PCC 1:3:6 type C1 (using 20 mm graded stone aggregate) exc 10 cm in width as in Walls set in cement mortar 1:4 complete all as specified and as directed.
RETAINING WALL:
Boring for bored cast-in-situ piles 500mm dia. in any type of soil/clay/ soft rock except hard rock/fractured rock using DMC (Direct Mud Circulation) method of boring and getting out and disposal of spoil out side MD land complete all as specified and as directed.
Boring for 500mm dia. bored cast in situ piles in hard rock using DMC method (Direct Mud Circulation) complete and getting out and disposal of spoil out side MD land all as specified and as directed.
Cutting, chipping of laitance concrete in piles above cut of level up to a maximum of 1m from cut of level and disposal to distance of exc. 1.5 km but not exc. 5 km and depositing where directed complete all as specified and as directed.
M&L for MS pipe liner fabricated out of 6mm thick plain MS plate confirming to Fe-410 S by welding the joints, strengthening wherever required, providing stiffeners, lifting hooks including all T&P required, shifting the same from position to positions required, driving in true vertical alignment in position to the required level for piles complete all as specified and as directed. Note: MS Pipe liner shall be casted as mentioned in drawing. How ever for payment purpose, the depth of pile liner shall be measured up to cut off level only irrespective of the depth provide for retaining concrete/ bentonite slurry. The unit rate/lumpsum price quoted shall be deemed to include for the above aspect.
S&F 25mm thick pre-formed compressible polyethylene closed cell type filler board for expansion joints complete all as specified and as directed.
Carrying out initial load test (Vertical load) on 500mm dia cast in situ pile as per IS 2911 Part-IV, complete all as specified and as directed.
Carrying out initial load test (Lateral load) on 500mm dia cast in situ pile as per IS 2911 Part-IV, complete all as specified and as directed.
Carrying out routine load test (Vertical load) on 500mm dia cast in situ pile as per IS 2911 Part-IV, complete all as specified and as directed.
Carrying out routine load test (Lateral load) on 500mm dia cast in situ pile as per IS 2911 Part-IV, complete all as specified and as directed.
Carrying out low strain integrity test on cast in situ piles 500mm dia including analysing the result as per ASTM D 5882 complete all as specified and as directed. Note for Item Nos. 194 to 198: Test results shall be approved by the CWE. The GE shall intimate CWE before commencing the load test and the test shall be carried out in presence of the authorised representative detailed by the CWE.
FIRE FIGHTING SYSTEM/ FIRE ALARM SYSTEM
S&F standard fireman’s axe as per IS 926 with heavy duty insulated rubber handle complete all as specified and directed.
S&F Booster pump Panel 40 Amps, 4 pole MCB, DOL starter with AMP & Volt meter, RYB indicator Lamp, Mild steel fabricated Powder Coated with suitable cable for connection of required flow switch to reduce flow as required complete all as specified and directed.
Supply, install, testing and commissioning of compartmentalised common PLC control panel for Electrical motor driven pumps and Diesel engine driven pumps with and including complete all as specified and directed.
S&F 32 mm bore lever operated brass/ bronze ball valve of full flow with SS Balls having minimum working pressure of 16 Kg /cm2 approved quality (screwed end) complete all as specified and as directed.
S&F 25mm dia. gunmetal Air release valve PN 1.6 with all fittings and forged ball valve on header as required complete all as specified and as directed.
M&L for masonry valve chamber of size 1200x1200x1000 mm (internal dimensions) comprising of 50mm thick PCC for valve including excavation and earth work in any type of soil and 200 mm thick PCC 1:4:8 type D2 (Using 40 mm graded stone aggregate) foundation, brick work in CM (1:6) plastering internal surface 15 mm thick in CM (1:4), PCC (1:3:6) type C1 (Using 20 mm graded stone aggregate) coping 50x50x6 mm angle iron 3 mm thick MS plate cover complete with locking arrangement painting steel and iron surface with two coat of synthetic enamel paint over a coat of zinc chrome primer complete all as specified and as directed.
S&F electrical short circuit isolation Modules to protect the system against wire to wire short circuits on loops, to be installed at the rate of every 5 Nos monitor modules complete as per manufacturer specifications and in an accessible location as per site, excluding wiring to Annunciation Panel, with UL/EN approval complete all as specified and as directed.
S&F Microprocessor operated based UL/EN listed (Latest version) wall mounted hooter-cum-strobe with minimum 90 db out put at distance of 1 m and with required power supply converter (230V AC to 12/24 VDC ) complete with termination etc as required complete all as specified and as directed.
S&F 25 mm bore, MS ERW pipe, heavy duty surface/ recess mounted and including bend/ elbows and necessary welding at site for making necessary tapings including painting with two coats synthetic enamel paint over a coat of primer complete all as specified and as directed.
S&F 20 mm bore, MS ERW pipe, heavy duty surface/ recess mounted and including bend/ elbows and necessary welding at site for making necessary tapings including painting with two coats synthetic enamel paint over a coat of primer complete all as specified and as directed.
S&F FRLS PVC insulated copper conductor single core of size 2x1.5 sq mm armoured aluminium foil sealed cable in the exiting surface/recess steel /PVC conduit as required complete all as specified and as directed.
S&F ISI marked portable type fire extinguishers CO2 type 4.5 kg capacity as per IS- 15683 complete all as specified and as directed
S&F ISI marked portable type fire extinguishers 22.5 kg capacity CO2 type cylindrical shape fire extinguisher (Trolley mounted) as per IS- 15683 complete all as specified and as directed.
S&F ISI marked portable type fire extinguishers 6 Kg capacity ABC Dry Powder type as per IS- 15683 complete all as specified and as directed.
S&F ISI marked portable type fire extinguishers 9 kg Mechanical foam as per IS- 15683 complete all as specified and as directed.
S&F Mechanical Foam type (AFFF media) 50 Liters Capacity cylindrical shape fire extinguisher with gas cartridge, hose, trolley and all required accessories, complete as per IS-1338- trolley mounted type for portable use complete all as specified and as directed.
S&F 3 Nos. GI sand buckets painted "Red Color" complete with GI stand duly painted "Red Colour" of suitable size to hang 3 Buckets at a time as per required specifications and as directed.
S&F internal fire hose cabinet fabricated from 14 gauge SS-304, 2mm Thick sheet with single or double door, glazed front door and locking arrangement, vinyl tape 50% front side, “Fire Hose” with stove enamelled paint, written on front, including necessary supports of approximate size 2100x900x715 mm deep to house two lengths of canvas hose with couplings, branch pipe, fire hose reel, nozzle, fireman axe, single outlet landing valve and first-aid hose reel, complete in all respects complete all as specified and as directed.
LIGHTENING PROTECTION
Supply, fix, testing and commissioning of Aviation lights, complete including PCC & 20mm dia pipe of length 1.5 m complete with flasher as required complete all as specified and as directed. Cat No. BGAV 302 LED of Bajaj or its equivalent in Philips / Havells / CG / Wipro
S&F wiring with 2x2.5 Sqmm for circuit wiring along with earth wire with 1x1.5 sq mm PVC insulated stranded copper conductor, single core cable in 25 mm dia PVC conduit from lift machine room DB to aviation light as required complete all as specified and as directed.
Blank
Blank
Blank
Blank
Blank
COOLING APPLIANCES
S&F Voltage stabilizer for automatic operation, single phase naturally air cooled indoor type designed for input variation between 170 V to 250 V with output Voltage stabilized at 230 V with accuracy of +/- 2.5% and of capacity 0.5 kVA complete all as specified and directed.
DG SET
(A) Alternator: Standard design alternator rated at 320 kVA net output at site after considering de-rating as per site conditions at 0.8 (Lag) power factor AC, 3 Phase, 4 wire, 415 Volts, 50 Hz, 1500 RPM, self excited self regulated screen protected drip proof IP 23 enclosure brushless design with winding in pole faces, insulating class 'H' and voltage regulation of +/-1% at rated Voltage from no load to full load. The alternator shall be conforming to BS 2613/5000 and shall be imposition to generate supply with frequency regulation with in +/-1% tolerance. The alternator will be suitable for tropical climate and shall generally conform to BS-2613/5000/IS-4722. (i) Insulation class-'H‘ (ii) Temperature rise Class-'H‘ (iii) Excitation: Self Excited (iv) Regulation Performance: The voltage is kept constant with +/-1%, manual Voltage adjustment within +/-5% (v) Frequency regulation +/-1%
(B) Diesel Engine: Adequate capacity of Diesel engine as approved by the Accepting Officer based on manufacturers technical details water cooled to drive independently above alternator and after considering de-rating as per site conditions after generating and reducing power consumed by accessories directly coupled through flexible coupling multi cylinder multi stroke direct injection, cold starting 1500 RPM, as per relevant ISI/BS-5514 with an overload capacity of 10% for one hour in 12 hours continuous running complete with standard accessories all as specified and required for safe handling and operation salient features of accessories shall be as under: (i) Fly wheel with housing (ii) Cooling System: Moulded radiator with fan & belts (iii) Cooling Water Pump: Centrifugal type belt driven (iv) Exhaust System: Exhaust System complete with exhaust piping of 150mm dia. with MS pipe light grade up to & outside and 1 meter away from the enclosure, covered with asbestos rope and aluminium foil of 28 SWG complete with in the enclosure for safe exhaust without transforming vibration to the wall of the enclosure. Exhaust gas turbo charger type. Exhaust manifold Silencer: Residual type Bellows (v) Fuel System: Fuel injection system with fuel injectors, fuel injection solenoid switch controlled by electronic governor for 1% speed/ frequency regulation, Fuel filters, Fuel hoses. (vi) Lub oil System: Lubricating oil filter, Lubricating oil pump (vii) Air Intake System: Air intake Manifold, Air cleaner dry type (viii) Governor: Electronic Governor
(ix) Starting System: Electric Self starter with maintenance free battery including battery charging alternator (x) Batteries: Batteries of maintenance free of capacity as recommended by the manufacturer complete with copper conductor multi stranded leads of suitable length from self starter to the battery terminals complete with initial charge and initial fill of electrolyte all as specified and starter gear ring start and stop push button, Ignition key/switch. Handling and Operation: Salient features of accessories shall be as under: Radiator with blower fan Corrosion inhibitor coolant Paper element filters for fuel, lub oil and by pass Electronic governor controlled direct fuel injection system Fly wheel housing and fly wheel (xi) Generator Monitoring Panel: Comprising of all standard items as mentioned under this schedule or as per standard practice ignition key switch and start/stop arrangement, indications for engine parameters, hour run meter, RPM meter, engine oil pressure indicator, water/coolant temperature indicator, battery Volt display. (xii) Safety Controls: Engine low lube oil pressure high water temperature and over speeding of engine (xiii) Coupling Arrangement: Flexible coupling, fly wheel to suit flexible coupling. (xiv) Accessories: AVM Pads built in enclosure and for entire unit on platform.
(xv) Base Frame: Should be provided as OEM norms. (xvi) Fuel Tank: Additional fuel tank of capacity to suit daily service fuel tank made out of 3mm thick (10G) HR sheet top and bottom with Calibrated level indicating arrangement, stop cock, drain plug, fuel pump of suitable capacity complete on a common base out side the acoustic enclosure. (xvii) MS pipe line to and from the fuel tank to the DG Set (C) AMF Panel : Factory made inbuilt type control cubical made out of 2mm thick CRCA sheet dust and vermin proof totally enclosed with front opening of 415 Volts, 3 Phase, 4 wire, AC, 50 Hz, including powder coated, copper bus bar of one and half times the rated load of 300 kVA alternator complete with internal wiring with PVC insulated single core copper conductor multi stranded wire of 1100 Volts grade of suitable capacity, fuses, name plates consisting of 4 Pole ACBs 50 kA rated and Contactors of capacity as recommended by the manufacturer. Detachable cable gland plates, all controls, indicators and standard microprocessor based LED/LCD display for indicating Voltage, current, frequency, speed, kW, kWh, pf, temperature, battery Voltage etc.
(v) Construction details/specification are as follows: (a) Outer body: CRCA sheet of 1.6mm thick (b) Doors: CRCA sheet of 1.6mm thick (c) Sound Insulation: As per OEM Norms (vi) The acoustic should be composite in construction and fully assembled integral unit (vii) The batteries should be placed inside the enclosure beside the DG Set on a suitable insulated platform (viii) The fuel tank is to be located in Sub Station Building and cost of the fuel lines is deemed to be included in the offer (ix) The DG Set should be provided with external emergency stop push button (x) The enclosure should be suitably illuminated by LED lamp fittings (xi) The noise level should be 75 dba at 1m under free field conditions. (xii) The acoustic enclosure parts shall be of powder coated after pre treatment process. The powder coating shade should be Gen Set Green. The base frame should be painted with epoxy based black shade.
(E) The coated rate includes excavation, removing of soft/loose soil and PCC, cement concrete foundation, filling and mass concrete 1:2:4 type B2 using 40mm graded stone aggregate, foundation size not less than 4.6x3.0x0.8m for placing of DG Set complete all as specified and directed by the Engineer-in-Charge. Notes: 1. The tenderer shall submit the detail, drawing, specification, features to the accepting officer and obtain approval before the procurement of equipment. 2. The tenderer shall make necessary arrangements for pre-despatch inspection from rep of Accepting Officer. 3. Testing & commissioning certificate shall be obtained from rep. of AO/IEM.
All as per Sl item No. 233-240 above but of capacity 750 kVA
All as per Sl item No. 233-240 above but of capacity 1010 kVA
All as per Sl item No. 233-240 above but of capacity 1250 kVA
Design supply, install testing & commissioning goods lift 2000 Kg, speed 0.5 m/sec, lift with single speed motor 415 Volts, 3 phase, AC 50 Hz supply conforming to IS-14665 and as amended, suitable to serve G + 2 (18 m height) upper floors with AC Variable Voltage & Variable Frequency drive (VVVF drive) complete with all standard accessories, simplex automatic & manual dual controlled operation with/without attendant, centre opening doors with door drive (electric motor driven mechanism), sliding stainless steel doors, including automatic rescue device (ARD) system, 3D infra red sensor in full height of door & built in announcing system without hand set, complete all as specified.
(a) Fire man switch (b) Automatic rescue divide (ARD) during power failure including manual operation provision with suitable capacity of battery designed for funning the lift with full load. c) Battery operated emergency light (LED ceiling fitting), alarm (speaker for emergency alarm system to be fixed) and stop button in car with rechargeable arrangement for battery. d) Four sleek circular LED light fitting in false ceiling . e) One Sleek circular PVC heavy duty fan in false ceiling. Make for(c) & (d) : Philips / Bajaj / Havells / Crompton Greaves. f) Aluminum chequered plate (3 mm thick) as flooring joint in chequered plate should not more than one and top covering with PVC flooring complete. g) Non stop button / independent operation. h) Over load warning indicator both audio and visual type with tripping system having relays etc., (overload protecting / tripping system). j) Front landing door of stainless steel mirror finish operations with a minimum time of 10 seconds and up to a maximum time of 30 seconds. k) Car size shall be conforming to IS-3534-1976 and body to be stainless steel of 16 gauge mirror finish with stainless steel hand rail 38 mm hairline finish.
l) Set of three in number limit switches at the bottom and top most position of lift hoist ways as specified in IS. m) Mirror of 4 mm thickness of suitable size as specified. n) Specification plate with complete details . o) Continuous earthling for machine and equipments. p) Steel wire rope of adequate size as per relevant IS and as per manufacturer specifications. q) Other standard fixtures and fitting like guide rails, sheaves, counter weights with guards, buffers, gear unit breaks, control panel, locks, governor, car operational panel, power, control and trailing cables complete. r) Full length display indicator panel. s) Main drives and control shall be of latest, high effective and low power consumption. t) Suitable phase reversal relay shall be provided on the controller to protect lift/ equipment against phase reversal, phase failure and low voltage. u) Stainless steel front opening type landing door & car door with small opening for vision of size 200 mm x 800 mm with toughened glass not less than 8mm thick. Make of Toughened Glass : Safe / Saint Goblin Glass / Modiguard float glass / kesar / Aashi Indian / Atul Tuf / Hindustan pilkington glass works / Trivenin float glass. v) Three-way Intercom connectivity i.e. Ground floor, security post, car cabin and machine room. w) Brail push button to be provided in the lift car.
AIR CONDITIONING
Design, supply, installation, testing and commissioning of Screw Chiller type Water Cooled Central Air Conditioning Plant with Semi Hermitic Compressor comprising of Flooded type Evaporator, Shell and Tube type Condenser complete with all equipment and accessories of minimum nominal capacity of 3x120 TR each (02 No. working and 01 No. standby) for Air Conditioning at 20° C to 25° C with Relative Humidity less than 80% ( at 25° C) all as per specifications, with IPLV.SI (IkW/TR) not less than 0.53 required all as per specifications, drawings and with design conditions comprising of the following: Notes: (Hanger F-2 & Technical Hanger) 1. Design of AC Plant, layout of all eqpts including duct layout shall be catered by NIT/IIT. 2. The tenderer shall submit the detail, drawing, specification, duct layout complete for approval of CWE before the commencement of work. A. Compressors: Supply, installation, testing and commissioning of floor-mounted compact screw-type chiller machine complete with semi-hermatic twin screw type compressors with independent circuits, water-cooled S/T type condenser, S/T horizontal flooded type evaporator with carbon steel shell and seamless copper tubes with 19mm nitrile rubber insulation, common base frame, interconnected copper refrigerant piping and wiring, vibration isolators, gauge panel, automatic safety controls, flow switch at evaporator and condenser and ozone friendly CFC-free refrigerant gas R-134a/407C. The refrigerant flow control shall use an electronic expansion valve.
The chiller shall be designed for a working pressure of 150 psig and hydraulically tested at 225 psig. A number of properly spaced baffles shall be provided for maintaining optimum water velocity and heat transfer and the tubes shall be adequately supported. B. CHILLERS: Chillers shall be factory AHRI tested at design conditions at 100%, 75%, 50% and 25% load respectively; test certificates shall be produced for all three chillers. The chiller shall be BMS compatible and shall have RS485/RS232 serial communication protocol; the motor shall be suitable for 3-Phase, 415 Volts ± 10%, 50 Hz, AC electric supply; electric panel shall have an IP 54 rating, as per specification and drawings. The chiller shall be as per the approved particular technical specifications and shall meet the following design criteria: (a) Chiller: (i) Chilled Water IN: 12° C, (ii) Chilled Water OUT: 7°C (iii) Fouling Factor: 0.0005 (in FPS units) (iv) Water Flow Rate: 2.67 USgpm/TR (b) Condenser: (i) Condenser Water IN: 32.2° C (ii) Condenser Water OUT: 38° C (iii) Fouling Factor: 0.001 (in FPS units) (iv) Water Flow Rate: 4.25 USgpm/TR (c) Minimum COP (at ARI conditions): 4.15 (d) Condenser Section: Shell and Tube type condenser internally knurled copper tubes. (e) Expansion Valve: Electronic expansion valve should be capable enough to operate on wider temperature range with energy efficient improvement at part load conditions, as per manufacturer’s specifications.
(f) Evaporator: Flooded type evaporator all as per manufacturer’s specifications. (g) Safety Protection: Safety protection on low cooling temperature, low oil pressure, high refrigerant pressure, electric leak, compressor overload, high/low voltage and single phasing shall be provided. Automatic control of refrigerant condition and compressor ON/OFF status and loading sequence system shall be provided. (h) Refrigerant: HFC-134 A/HFC-410 A/HFC-407 C of zero ozone depletion potential refrigeration circuits of total capacity as per manufacturers specifications (j) Control: Micro Processor control with LCD interface capable of monitoring all machine operating parameters like suction/discharge pressure, oil pressure, compressor operating hours, set point, air temperature, entering/leaving water temperature etc complete and precisely manages the operation of compressors, expansion devices, fans and of the evaporator/chiller water pump for optimum energy efficiency as per manufacturers specifications.
(C) CONDENSER WATER CIRCULATION SYSTEM: The condenser water circulation system shall be comprising of the following: (i) FRP induced draft cooling tower of total 110% plant working capacity suitable for above plant conditions complete with spray section, honey comb fill, basin, CT fan, TEFC Motor, intake bird screen and other accessories (Technical Specifications as per the manufacturer) (ii) HDPE make up water tank of 5,000 Litres capacity (2 Nos.) installed on PCC/brick staging for makeup water requirement including brass float valve with polyethylene ball, over flow and drain arrangement, incoming connection of GI pipe 50mm bore medium grade from tank to tapping point including necessary cutting of existing pipe line and tapping of branch connections with GI pipe 25mm bore medium grade all as directed (The item rate is inclusive of provisioning all connected incoming pipe lines from existing sources and all outgoing) -01 Job. (iii) Energy saving Split casing type 3 Phase electric driven pump set of 50% capacity and discharge as per capacity of plant working on 415 Volts, AC, FASD starter for re-circulation of condenser water with ribbed rubber vibration isolation pads 02 Nos. (01 No. working and 01 No. as stand by). 100mm dia. pressure gauges on both discharge and suction side of pumps shall be provided at the outlet of each pump. (01 No. working and 01 No. stand by) Note: Pump Casing-Cast Iron, Impeller-Bronze/Cast Iron, Shaft-HSS or as per manufacturer, Material of Seal-Mechanical Seal. The condenser water pumps shall have minimum flow rate of 4.0 US GPM/TON respectively.
(iv) Condenser water MS Class 'B' tubing medium grade of suitable size by electric arc continuous welding, including two coats of synthetic enamel paint over a coat of red oxide primer as per approved colour code fixed on supports, walls, floors etc. for connecting chiller package unit, pump sets and cooling tower, including filters, fittings, valves, pressure gauges, purge cocks at upper most position, blind flanges, strainers with bypass arrangements. (D) CHILLED WATER CIRCULATION SYSTEM: The chilled water circulation system shall be comprising of the following: (i) Energy saving Split casing type 3 phase electric driven pump sets working on 415 Volts, AC for recirculation of chilled water of 50%, plant capacity-2 Nos. (One working and one No standby) including 100mm dia. pressure gauge shall be provided on delivery side of pumps including rubber vibration isolation pads for mounding including all connections complete. Note: Pump casing-Cast iron, Impeller-Bronze/Cast Iron, Shaft-HSS or as per manufacturer, Material of Seal-Mechanical seal. The chilled water pumps shall have minimum flow rate of 2.4 US GPM/TON (ii) Chilled water MS class 'B' tubing medium grade of suitable size, fixed on supports, walls, floors etc for connecting chiller package units, pump sets, AHUs including fittings, valves, pressure gauges, purge cocks at upper most position, blind flanges, strainers joined by electric arc continuous welding all joints sealed with bitumen, laced with chilled water piping insulated with 50mm thick EPS pipe section of TF quality of density 16 KG/Cu.m. and then cladded with aluminium sheet of 28 SWG thick or plastering using sand cement 15mm thick in two layers over chicken wire mesh where buried under earth.
(iii) HDPE /PVC expansion tank of 2000 litres capacity including pipe connections and insulation with 50mm thick fibre glass wool covered with chicken wire mesh of density of 24 kg/cu.m. finished with sand cement plaster including civil works and painting with 3 coats of cement based paint and necessary piping, control valves on inlets and wash out, float valve etc.-01 No. (E) AIR TREATMENT SYSTEM: The air treatment system shall be comprising of the following: (a) Design, supply, Installation, testing and commissioning factory made high static double skinned horizontal type backward curved Air Handling Unit (AHU) with minimum 50mm static pressure with suitable CFM with 0.6mm thick pre coated outer skin & 0.6mm thick inner skin made out of GI sheet not less than 22 gauge. The insulation with 25mm thick PUF panels. The AHUs will be floor mounting (with anti-vibration pads) for cooling the air with all accessories and controls comprising the following including painting etc as per standard practice: Notes: (i) Static pressure may vary according to the design. (ii) The same should be got approved by the Accepting officer and along with the number of AHU's and its CFM also. (b) SITC hot water generator of suitable capacity for re-heat in monsoon. (c) Acoustic Insulation with 25mm thick fibre glass rigid boards and finished with RP tissue paper and 28mm gauge aluminium perforated sheet up to 5m from outlet of the air plenum including 5 micron filters in air plenum for all AHUs all as specified and directed. (d) Fresh air damper with GI bowl/fittings and mosquito proof netting shall be provided for each AHU.
(e) Under deck insulation in AHU Rooms with Fire Retardant XLPE closed cell of thickness 18mm with metalized polyester film and self adhesive backing with protection peel off paper. (F) AIR DISTRIBUTION SYSTEM: The air distribution system shall be comprising of the following: (i) Supply & Return Air ducting factory made out of commercial grade GI sheet zinc coating 120 grade, IS-277 and factory fabricated as per SMACNA-1995 standards and IS-655, but not less than 22 SWG thick. Ducting wherever passing through un-conditioned space shall be insulated with resin bonded Fibre Glass Wool 25mm thick (density 24 kg/Cu.m.) covered with GI chicken wire mesh and cladded with aluminium foil fixed with adhesive tape. Where these ducts are exposed to the sky these will be insulated with 50mm thick fibre glass wool density 24 kg/Cu.m., covered with polythene sheet faced Hessian cloth, GI chicken wire mesh and cladded with sand cement plaster-1 Job (ii) Aluminium powder coated double deflection adjustable type Supply air grills/diffusers with MS volume control dampers and aluminium powder coated fixed bar type return air grills/diffusers as required without volume control damper, for return air-1 Job (iii) Strip type Heater bank of suitable capacity in three banks as required to achieve design conditions with necessary copper conductor wiring for banking complete for each AHU
(iv) Fire dampers automatic type UL stamped fusible plug (CBRI Certified) and operated with stainless steel spring made out of 16 SWG GI sheet and limit switch to be provided in each main supply air duct near plenum in AHU room for each AHU and interlocked with AHU motor to cut off circulation of air in case of fire-01 Job (G) ELECTRICAL DISTRIBUTION SYSTEM: The electrical distribution system shall be comprising of the following: (i) Main Electrical Panel Board: Cubicle type floor mounted, vermin proof, dust proof as per IE standards, powder coated switch board panel made out of CRCA sheet not less than 2mm thick powder coated paint suitable for operation on 415 Volts, 50 Hz, AC supply internally wired with copper conductor wire comprising of the following: (a) TPN Copper bus bar of suitable rating. (b) Main incoming ACB four wire and 35 KA rupturing capacity and outgoing 25 KA MCCBs of suitable capacity. (c) One electronic Energy meter of suitable capacity at main incoming (d) Voltmeter for 0-500 Volts digital type meter (e) Ammeter of required rating digital type (f) LED indicating lamps (g) FASD Starters with suitable rating/size, contactors, relays, SPP and glow type push button switches for compressor, chiller pump and humidifier etc. (h) Provision of insulating Mat Class A, 2mm thick as per IS-15652 (Technical specification as per Annexure ‘A’), first Aid box & Shock treatment chart (Mat at all locations as directed by Engineer-in-Charge). (j) Provision of Suitable heavy duty power capacitors to maintain PF value not less than 0.98 lagging.
22. The rate quoted deemed to be inclusive for nearest higher available capacity of plant as per OEM recommendations and no extra shall be paid on this account. Note for all:- AC plant design shall be approved by Chief Engineer before executing the work
All as per serial item No. 249 - 262 but of capacity 3x60 TR each (02 Nos working and 01 No standby).
All as per serial item No. 249 - 262 but of capacity 3x45 TR each (02 Nos working and 01 No standby).
EOT/ HOT CRANE
Design, fabrication, supply, erection, testing & commissioning of double girder EOT Cranes of 5 Ton Capacity EOT Crane with a Span of 20 m, Height of Lift 6.0 m with Gantry Rail and DSL System complete all as specified and as directed. Speeds Hoist - 2 m/min Cross travel - 5 m/min Long travel - 10 m/min
Design, fabrication, supply, erection, testing & commissioning of double girder EOT Cranes of 5 Ton Capacity EOT Crane with a Span of 9 m, Height of Lift 6m with Gantry Rail and DSL System complete all as specified and as directed. Speeds Hoist - 2 m/min Cross travel - 5 m/min Long travel - 10 m/min
Design, fabrication, supply, erection, testing & commissioning of double girder EOT Cranes of 5 Ton Capacity EOT Crane with a Span of 50 m, Height of Lift 6.0m with Gantry Rail and DSL System complete all as specified and as directed. Speeds Hoist - 3 m/min Cross travel - 5 m/min Long travel - 10 m/min
Design, fabrication, supply, erection, testing & commissioning of double girder EOT Cranes of 5 Ton Capacity EOT Crane with a Span of 42.5 m, Height of Lift 6.0m with Gantry Rail and DSL System complete all as specified and as directed. Speeds Hoist - 2 m/min Cross travel - 5 m/min Long travel - 10 m/min
SPECIAL POWER SUPPLY
Supply, install, commissioning and testing static frequency converter 415 Volt A/C 50 cycle input & output Voltage 208 Volts + 1% tolerance output, 400Hz, 3 phase, 60 kVA with Programmable Controller for output Voltage & Frequency adjustment with password protection complete as per specification given here in below :- Rated power @ 0.8 pf lag: 60kVA INPUT Voltage - Nominal : 400V AC Range : 340 to 460 V AC Frequency- Nominal : 50Hz Range : 47-53Hz Phase : Three AC to AC Efficiency : 92% Rectifier Technology: 12 Pulse Rectifier SCR based fully controlled Power walk in: 10 to 15 secs THDi (input current Harmonic Distortion ): < 10% at rated load Input power Factor > 0.92lag Galvanic isolation: Inbuilt Galvanic Isolation OUT PUT Voltage - Nominal: 208V AC (Programmable) Regulation: 1% Frequency - Nominal : 400Hz (Programmable)
Stability : 0.05% Phase : Three Phase Waveform : Sine Wave Total Harmonic Distortion : < 2% on linear load Transient Response: less than +/-8% for 100% step loads Recovery Time: less than 25milli secs to reach within +/-1% of nominal value Load power factor range : 0.8 lag to unity within kW rating Overload Protection: 120% for 30 min., 150% for1min, 200% for 10 cycles. Protections: Input over/under Voltage, Input Phase fail, overload, Output over/under Voltage, snubber circuits for power devices, over temperature, fuses for semi conductor devices, high speed electronic fuseless tripping for output short circuit Indications: Input ON,Output ON, Input abnormal, Output over/Under Voltage, overload, overheat Remote Alarm Potential free contacts for input fault & output trip Metering: 16x2 LCD panel to measure the following: AC input Voltage, output Voltage, load percentage, input & output frequency GENERAL Operating Temperature : 0 to 45 Deg C (50 Deg C Peak) Storage Temperature : -20 to 45 deg C Relative Humidity : 95% non condensing Cooling : Forced Air using localized cooling technique with multiple fractional HP fans Panel: Welded structure MS Covers 2mm and frame 3mm thick Enclosure protection: IP 55
Cable Entry : Front Bottom
Supply, install, commission and testing static frequency converter 415 Volt A/C 50 cycle input & output Voltage 208 Volts + 1% tolerance output, 400Hz, 3 phase, 45 kVA with Programmable Controller for output Voltage & Frequency adjustment with password protection for 1 No each, complete as per specification given here in below :- Rated power @ 0.8 pf lag: 45kVA INPUT Voltage - Nominal : 400V AC Range : 340 to 460 V AC Frequency- Nominal : 50Hz Range : 47-53Hz Phase : Three AC to AC Efficiency : 92% Rectifier Technology: 12 Pulse Rectifier SCR based fully controlled Power walk in: 10 to 15 secs THDi (input current Harmonic Distortion ): < 10% at rated load Input power Factor > 0.92lag Galvanic isolation: Inbuilt Galvanic Isolation
OUT PUT Voltage - Nominal: 208V AC (Programmable) Regulation: 1% Frequency - Nominal : 400Hz (Programmable) Stability : 0.05% Phase : Three Phase Waveform : Sine Wave Total Harmonic Distortion : < 2% on linear load Transient Response: less than +/-8% for 100% step loads Recovery Time: less than 25milli secs to reach within +/-1% of nominal value Load power factor range : 0.8 lag to unity within kW rating Overload Protection: 120% for 30 min., 150% for1min, 200% for 10 cycles. Protections: Input over/under Voltage, Input Phase fail, overload, Output over/under Voltage, snubber circuits for power devices, over temperature, fuses for semi conductor devices, high speed electronic fuseless tripping for output short circuit Indications: Input ON,Output ON, Input abnormal, Output over/Under Voltage, overload, overheat Remote Alarm Potential free contacts for input fault & output trip Metering: 16x2 LCD panel to measure the following: AC input Voltage, output Voltage, load
GENERAL Operating Temperature : 0 to 45 Deg C (50 Deg C Peak) Storage Temperature : -20 to 45 deg C Relative Humidity : 95% non condensing Cooling : Forced Air using localized cooling technique with multiple fractional HP fans Panel: Welded structure MS Covers 2mm and frame 3mm thick Enclosure protection: IP 55 Cable Entry : Front Bottom
Supply, install, commission and testing static frequency converter 415 Volt A/C 50 cycle input & output Voltage 440 Volts + 1% tolerance output, 400Hz, 3 phase, 100 kVA with Programmable Controller for output Voltage & Frequency adjustment with password protection for 1 No each complete as per specification given here in below :- Rated power @ 0.8 pf lag: 100kVA INPUT Voltage - Nominal : 400V AC Range : 340 to 460 V AC Frequency- Nominal : 50Hz Range : 47-53Hz Phase : Three AC to AC Efficiency : 92% Rectifier Technology: 12 Pulse Rectifier SCR based fully controlled Power walk in: 10 to 15 secs THDi (input current Harmonic Distortion ): < 10% at rated load Input power Factor > 0.92lag Galvanic isolation: Inbuilt Galvanic Isolation
OUT PUT Voltage - Nominal: 440V AC (Programmable) Regulation: 1% Frequency - Nominal : 400Hz (Programmable) Stability : 0.05% Phase : Three Phase Waveform : Sine Wave Total Harmonic Distortion : < 2% on linear load Transient Response: less than +/-8% for 100% step loads Recovery Time: less than 25milli secs to reach within +/-1% of nominal value Load power factor range : 0.8 lag to unity within kW rating Overload Protection: 120% for 30 min., 150% for1min, 200% for 10 cycles. Protections: Input over/under Voltage, Input Phase fail, overload, Output over/under Voltage, snubber circuits for power devices, over temperature, fuses for semi conductor devices, high speed electronic fuseless tripping for output short circuit Indications: Input ON,Output ON, Input abnormal, Output over/Under Voltage, overload, overheat Remote Alarm " Potential free contacts for input fault & output trip Metering: 16x2 LCD panel to measure the following: AC input Voltage, output Voltage, load percentage, input & output frequency
GENERAL Operating Temperature : 0 to 45 Deg C (50 Deg C Peak) Storage Temperature : -20 to 45 deg C Relative Humidity : 95% non condensing Cooling : Forced Air using localized cooling technique with multiple fractional HP fans Panel: Welded structure MS Covers 2mm and frame 3mm thick Enclosure protection: IP 55 Cable Entry : Front Bottom
Supply, install, commission and testing static frequency converter 415 Volt A/C 50 cycle input & output Voltage 115 Volts + 1% tolerance output, 400Hz, 1 phase, 8 kVA with Programmable Controller for output Voltage & Frequency adjustment with password protection complete as per specification given here in below :- Rated power @ 0.8 pf lag: 8 kVA INPUT Voltage - Nominal : 400V AC Range : 340 to 460 V AC Frequency- Nominal : 50Hz Phase : Three AC to AC Efficiency : 92% Rectifier Technology: 12 Pulse Rectifier SCR based fully controlled Power walk in: 10 to 15 secs THDi (input current Harmonic Distortion ): < 10% at rated load Input power Factor > 0.92lag Galvanic isolation: Inbuilt Galvanic Isolation
OUT PUT Voltage - Nominal: 115 V AC (Programmable) Regulation: 1% Frequency - Nominal : 400Hz (Programmable) Stability : 0.05% Phase : Single Phase Waveform : Sine Wave Total Harmonic Distortion : < 2% on linear load Transient Response: less than +/-8% for 100% step loads Recovery Time: less than 25 milli secs to reach within +/-1% of nominal value Load power factor range : 0.8 lag to unity within kW rating Overload Protection: 120% for 30 min., 150% for1min, 200% for 10 cycles. Protections: Input over/under Voltage, Input Phase fail, overload, Output over/under Voltage, snubber circuits for power devices, over temperature, fuses for semi conductor devices, high speed electronic fuseless tripping for output short circuit Indications: Input ON,Output ON, Input abnormal, Output over/Under Voltage, overload, overheat Remote Alarm Potential free contacts for input fault & output trip Metering: 16x2 LCD panel to measure the following: AC input Voltage, output Voltage, load percentage, input & output frequency GENERAL Operating Temperature : 0 to 45 Deg C (50 Deg C Peak) Storage Temperature : -20 to 45 deg C Relative Humidity : 95% non condensing Cooling : Forced Air using localized cooling technique with multiple fractional HP fans
Panel : Welded structure MS Covers 2mm and frame 3mm thick Enclosure protection: IP 55 Cable Entry : Front Bottom
Supply, install, commission and testing static frequency converter 415 Volt A/C 50 cycle input & output Voltage 115 Volts + 1% tolerance output, 400Hz, 1 phase, 5kVA with Programmable Controller for output Voltage & Frequency adjustment with password protection complete as per specification given here in below :- Rated power @ 0.8 pf lag: 5kVA INPUT Voltage - Nominal : 400V AC Range : 340 to 460 V AC Frequency- Nominal : 50Hz Range : 47-53Hz Phase : Three AC to AC Efficiency : 92% Rectifier Technology: 12 Pulse Rectifier SCR based fully controlled Power walk in: 10 to 15 secs THDi (input current Harmonic Distortion ): < 10% at rated load Input power Factor > 0.92lag Galvanic isolation: Inbuilt Galvanic Isolation
OUT PUT Voltage - Nominal: 115 V AC (Programmable) Regulation: 1% Frequency - Nominal : 400Hz (Programmable) Stability : 0.05% Phase : Single Phase Waveform : Sine Wave Total Harmonic Distortion : < 2% on linear load Transient Response: less than +/-8% for 100% step loads Recovery Time: less than 25 milli secs to reach within +/-1% of nominal value Load power factor range : 0.8 lag to unity within kW rating Overload Protection: 120% for 30 min., 150% for1min, 200% for 10 cycles. Protections: Input over/under Voltage, Input Phase fail, overload, Output over/under Voltage, snubber circuits for power devices, over temperature, fuses for semi conductor devices, high speed electronic fuseless tripping for output short circuit Indications: Input ON,Output ON, Input abnormal, Output over/Under Voltage, overload, overheat Remote Alarm Potential free contacts for input fault & output trip
Metering: 16x2 LCD panel to measure the following: AC input Voltage, output Voltage, load percentage, input & output frequency GENERAL Operating Temperature : 0 to 45 Deg C (50 Deg C Peak) Storage Temperature : -20 to 45 deg C Relative Humidity : 95% non condensing Cooling : Forced Air using localized cooling technique with multiple fractional HP fans Panel : Welded structure MS Covers 2mm and frame 3mm thick Enclosure protection: IP 55 Cable Entry : Front Bottom
Supply, install, commission and testing static frequency converter 415 Volt A/C 50 cycle input & output Voltage 115 Volts + 1% tolerance output, 400Hz, 1 phase, 15kVA with Programmable Controller for output Voltage & Frequency adjustment with password protection 1 No each complete as per specification given here in below :- Rated power @ 0.8 pf lag: 15kVA INPUT Voltage - Nominal : 400V AC Range : 340 to 460 V AC Frequency- Nominal : 50Hz Range : 47-53Hz Phase : Three AC to AC Efficiency : 92% Rectifier Technology: 12 Pulse Rectifier SCR based fully controlled Power walk in: 10 to 15 secs THDi (input current Harmonic Distortion ): < 10% at rated load Input power Factor > 0.92lag Galvanic isolation: Inbuilt Galvanic Isolation
OUT PUT Voltage - Nominal: 115 V AC (Programmable) Regulation: 1% Frequency - Nominal : 400 Hz (Programmable) Stability : 0.05% Phase : Single Phase Waveform : Sine Wave Total Harmonic Distortion : < 2% on linear load Transient Response: less than +/-8% for 100% step loads Recovery Time: less than 25milli secs to reach within +/-1% of nominal value Load power factor range : 0.8 lag to unity within kW rating Overload Protection: 120% for 30 min., 150% for 1 min, 200% for 10 cycles. Protections: Input over/under Voltage, Input Phase fail, overload, Output over/under Voltage, snubber circuits for power devices, over temperature, fuses for semi conductor devices, high speed electronic fuseless tripping for output short circuit Indications: Input ON, Output ON, Input abnormal, Output over/Under Voltage, overload, overheat Remote Alarm Potential free contacts for input fault & output trip Metering: 16x2 LCD panel to measure the following: AC input Voltage, output Voltage, load percentage, input & output frequency GENERAL Operating Temperature : 0 to 45 Deg C (50 Deg C Peak) Storage Temperature : -20 to 45 deg C Relative Humidity : 95% non condensing Cooling : Forced Air using localized cooling technique with multiple fractional HP fans
Panel : Welded structure MS Covers 2mm and frame 3mm thick Enclosure protection: IP 55 Cable Entry : Front Bottom
Supply, install, commission and testing static frequency converter 415 Volt A/C 50 cycle input & output Voltage 115 Volts + 1% tolerance out put, 400Hz, 1 phase, 16 kVA with Programmable Controller for output Voltage & Frequency adjustment with password protection complete as per specification given here in below :- Rated power @ 0.8 pf lag: 16kVA INPUT Voltage - Nominal : 400V AC Range : 340 to 460 V AC Frequency- Nominal : 50Hz Range : 47-53Hz Phase : Three AC to AC Efficiency : 92% Rectifier Technology: 12 Pulse Rectifier SCR based fully controlled Power walk in: 10 to 15 secs THDi (input current Harmonic Distortion): < 10% at rated load Input power Factor > 0.92lag Galvanic isolation: Inbuilt Galvanic Isolation
OUT PUT Voltage - Nominal: 115 V AC (Programmable) Regulation: 1% Frequency - Nominal : 400Hz (Programmable) Stability : 0.05% Phase : Single Phase Waveform : Sine Wave Total Harmonic Distortion : < 2% on linear load Transient Response: less than +/-8% for 100% step loads Recovery Time: less than 25 milli secs to reach within +/-1% of nominal value Load power factor range : 0.8 lag to unity within kW rating Overload Protection: 120% for 30 min., 150% for1min, 200% for 10 cycles. Protections: Input over/under Voltage, Input Phase fail, overload, Output over/under Voltage, snubber circuits for power devices, over temperature, fuses for semi conductor devices, high speed electronic fuseless tripping for output short circuit Indications: Input ON,Output ON, Input abnormal, Output over/Under Voltage, overload, overheat Remote Alarm Potential free contacts for input fault & output trip Metering: 16x2 LCD panel to measure the following: AC input Voltage, output Voltage, load percentage, input & output frequency GENERAL Operating Temperature : 0 to 45 Deg C (50 Deg C Peak) Storage Temperature : -20 to 45 deg C Relative Humidity : 95% non condensing Cooling : Forced Air using localized cooling technique with multiple fractional HP fans
Panel : Welded structure MS Covers 2mm and frame 3mm thick Enclosure protection: IP 55 Cable Entry : Front Bottom
Supply, install, commission and testing static frequency converter 415 Volt A/C 50 cycle input & output Voltage 115 Volts + 1% tolerance output, 400Hz, 1 phase, 25 kVA with Programmable Controller for output Voltage & Frequency adjustment with password protection for Technical Hanger ( Second Floor, Left Side) complete as per specification given here in below :- Rated power @ 0.8 pf lag: 25kVA INPUT Voltage - Nominal : 400V AC Range : 340 to 460 V AC Frequency- Nominal : 50Hz Range : 47-53Hz Phase : Three AC to AC Efficiency : 92% Rectifier Technology: 12 Pulse Rectifier SCR based fully controlled Power walk in: 10 to 15 secs THDi (input current Harmonic Distortion ): < 10% at rated load Input power Factor > 0.92lag Galvanic isolation: Inbuilt Galvanic Isolation
OUT PUT Voltage - Nominal: 115 V AC (Programmable) Regulation: 1% Frequency - Nominal : 400Hz (Programmable) Stability : 0.05% Phase : Single Phase Waveform : Sine Wave Total Harmonic Distortion : < 2% on linear load Transient Response: less than +/-8% for 100% step loads Recovery Time: less than 25milli secs to reach within +/-1% of nominal value Load power factor range : 0.8 lag to unity within kW rating Overload Protection: 120% for 30 min., 150% for1min, 200% for 10 cycles. Protections: Input over/under Voltage, Input Phase fail, overload, Output over/under Voltage, snubber circuits for power devices, over temperature, fuses for semi conductor devices, high speed electronic fuseless tripping for output short circuit Indications: Input ON, Output ON, Input abnormal, Output over/Under Voltage, overload, overheat Remote Alarm Potential free contacts for input fault & output trip Metering: 16x2 LCD panel to measure the following: AC input Voltage, output Voltage, load percentage, input & output frequency GENERAL Operating Temperature : 0 to 45 Deg C (50 Deg C Peak) Storage Temperature : -20 to 45 deg C Relative Humidity : 95% non condensing Cooling : Forced Air using localized cooling technique with multiple fractional HP fans
Panel : Welded structure MS Covers 2mm and frame 3mm thick Enclosure protection: IP 55 Cable Entry : Front Bottom
Supply, install, commission and testing static frequency converter 220 Volt A/C 50 cycle input & output Voltage 36 Volts + 1% tolerance output, 50Hz, 1 phase, 1kVA with Programmable Controller for output Voltage & Frequency adjustment with password protection complete as per specification given here in below :- Rated power @ 0.8 pf lag: 1kVA INPUT Voltage - Nominal : 220V AC Range : 140 to 270 V AC Frequency- Nominal : 50Hz Range : 47-53Hz Phase : Single AC to AC Efficiency : 92% Rectifier Technology: 12 Pulse Rectifier SCR based fully controlled Power walk in: 10 to 15 secs THDi (input current Harmonic Distortion ): < 10% at rated load Input power Factor > 0.92lag Galvanic isolation: Inbuilt Galvanic Isolation
OUT PUT Voltage - Nominal: 36 V AC (Programmable) Regulation: 1% Frequency - Nominal : 50Hz (Programmable) Stability : 0.05% Phase : Single Phase Waveform : Sine Wave Total Harmonic Distortion : < 2% on linear load Transient Response: less than +/-8% for 100% step loads Recovery Time: less than 25milli secs to reach within +/-1% of nominal value Load power factor range : 0.8 lag to unity within kW rating Overload Protection: 120% for 30 min., 150% for1min, 200% for 10 cycles. Protections: Input over/under Voltage, Input Phase fail, overload, Output over/under Voltage, snubber circuits for power devices, over temperature, fuses for semi conductor devices, high speed electronic fuseless tripping for output short circuit Indications: Input ON, Output ON, Input abnormal, Output over/Under Voltage, overload, overheat Remote Alarm Potential free contacts for input fault & output trip Metering: 16x2 LCD panel to measure the following: AC input Voltage, output Voltage, load percentage, input & output frequency GENERAL Operating Temperature : 0 to 45 Deg C (50 Deg C Peak) Storage Temperature : -20 to 45 deg C Relative Humidity : 95% non condensing Cooling : Forced Air using localized cooling technique with multiple fractional HP fans
Panel : Welded structure MS Covers 2mm and frame 3mm thick Enclosure protection: IP 55 Cable Entry : Front Bottom
Supply, install, commission and testing static frequency converter 220 Volt A/C 50 cycle input & output Voltage 36 Volts + 1% tolerance output, 50Hz, 1 phase, 2kVA with Programmable Controller for output Voltage & Frequency adjustment with password protection complete as per specification given here in below :- Rated power @ 0.8 pf lag: 2kVA INPUT Voltage - Nominal : 220V AC Range : 140 to 270 V AC Frequency- Nominal : 50Hz Range : 47-53Hz Phase : Single AC to AC Efficiency : 92% Rectifier Technology: 12 Pulse Rectifier SCR based fully controlled Power walk in: 10 to 15 secs THDi (input current Harmonic Distortion ): < 10% at rated load Input power Factor > 0.92lag Galvanic isolation: Inbuilt Galvanic Isolation
OUT PUT Voltage - Nominal: 36 V AC (Programmable) Regulation: 1% Frequency - Nominal : 50Hz (Programmable) Stability : 0.05% Phase : Single Phase Waveform : Sine Wave Total Harmonic Distortion : < 2% on linear load Transient Response: less than +/-8% for 100% step loads Recovery Time: less than 25milli secs to reach within +/-1% of nominal value Load power factor range : 0.8 lag to unity within kW rating Overload Protection: 120% for 30 min., 150% for1min, 200% for 10 cycles. Protections: Input over/under Voltage, Input Phase fail, overload, Output over/under Voltage, snubber circuits for power devices, over temperature, fuses for semi conductor devices, high speed electronic fuseless tripping for output short circuit Indications: Input ON,Output ON, Input abnormal, Output over/Under Voltage, overload, overheat Remote Alarm Potential free contacts for input fault & output trip Metering: 16x2 LCD panel to measure the following: AC input Voltage, output Voltage, load percentage, input & output frequency GENERAL Operating Temperature : 0 to 45 Deg C (50 Deg C Peak) Storage Temperature : -20 to 45 deg C Relative Humidity : 95% non condensing Cooling : Forced Air using localized cooling technique with multiple fractional HP fans
Panel : Welded structure MS Covers 2mm and frame 3mm thick Enclosure protection: IP 55 Cable Entry : Front Bottom
Supply, install, commission and testing static frequency converter 220 Volt A/C 50 cycle input & output Voltage 36 Volts + 1% tolerance output, 50Hz, 1 phase, 3kVA with Programmable Controller for output Voltage & Frequency adjustment with password protection complete as per specification given here in below :- Rated power @ 0.8 pf lag: 3kVA INPUT Voltage - Nominal : 220V AC Range : 140 to 270 V AC Frequency- Nominal : 50Hz Range : 47-53Hz Phase : Single AC to AC Efficiency : 92% Rectifier Technology: 12 Pulse Rectifier SCR based fully controlled Power walk in: 10 to 15 secs THDi (input current Harmonic Distortion ): < 10% at rated load Input power Factor > 0.92lag Galvanic isolation: Inbuilt Galvanic Isolation
OUT PUT Voltage - Nominal: 36 V AC (Programmable) Regulation: 1% Frequency - Nominal : 50Hz (Programmable) Stability : 0.05% Phase : Single Phase Waveform : Sine Wave Total Harmonic Distortion : < 2% on linear load Transient Response: less than +/-8% for 100% step loads Recovery Time: less than 25milli secs to reach within +/-1% of nominal value Load power factor range : 0.8 lag to unity within kW rating Overload Protection: 120% for 30 min., 150% for1min, 200% for 10 cycles. Protections: Input over/under Voltage, Input Phase fail, overload, Output over/under Voltage, snubber circuits for power devices, over temperature, fuses for semi conductor devices, high speed electronic fuseless tripping for output short circuit Indications: Input ON,Output ON, Input abnormal, Output over/Under Voltage, overload, overheat Remote Alarm Potential free contacts for input fault & output trip Metering: 16x2 LCD panel to measure the following: AC input Voltage, output Voltage, load percentage, input & output frequency GENERAL Operating Temperature : 0 to 45 Deg C (50 Deg C Peak) Storage Temperature : -20 to 45 deg C Relative Humidity : 95% non condensing Cooling : Forced Air using localized cooling technique with multiple fractional HP fans
Panel : Welded structure MS Covers 2mm and frame 3mm thick Enclosure protection: IP 55 Cable Entry : Front Bottom
Supply, install, commission and testing static frequency converter 220 Volt A/C 50 cycle input & output Voltage 36 Volts + 1% tolerance output, 50Hz, 1 phase, 4kVA with Programmable Controller for output Voltage & Frequency adjustment with password protection complete as per specification given here in below :- Rated power @ 0.8 pf lag: 4kVA INPUT Voltage - Nominal : 220V AC Range : 140 to 270 V AC Frequency- Nominal : 50Hz Range : 47-53Hz Phase : Single AC to AC Efficiency : 92% Rectifier Technology: 12 Pulse Rectifier SCR based fully controlled Power walk in: 10 to 15 secs THDi (input current Harmonic Distortion ): < 10% at rated load Input power Factor > 0.92lag Galvanic isolation: Inbuilt Galvanic Isolation
OUT PUT Voltage - Nominal: 36 V AC (Programmable) Regulation: 1% Frequency - Nominal : 50Hz (Programmable) Stability : 0.05% Phase : Single Phase Waveform : Sine Wave Total Harmonic Distortion : < 2% on linear load Transient Response: less than +/-8% for 100% step loads Recovery Time: less than 25milli secs to reach within +/-1% of nominal value Load power factor range : 0.8 lag to unity within kW rating Overload Protection: 120% for 30 min., 150% for1min, 200% for 10 cycles. Protections: Input over/under Voltage, Input Phase fail, overload, Output over/under Voltage, snubber circuits for power devices, over temperature, fuses for semi conductor devices, high speed electronic fuseless tripping for output short circuit Indications: Input ON,Output ON, Input abnormal, Output over/Under Voltage, overload, overheat Remote Alarm Potential free contacts for input fault & output trip Metering: 16x2 LCD panel to measure the following: AC input Voltage, output Voltage, load percentage, input & output frequency GENERAL Operating Temperature : 0 to 45 Deg C (50 Deg C Peak) Storage Temperature : -20 to 45 deg C Relative Humidity : 95% non condensing Cooling : Forced Air using localized cooling technique with multiple fractional HP fans
Panel : Welded structure MS Covers 2mm and frame 3mm thick Enclosure protection: IP 55 Cable Entry : Front Bottom
Supply, install, commission and testing static frequency converter 220Volt A/C 50 cycle input & output Voltage 36 Volts + 1% tolerance output, 50Hz, 1 phase, 7.5kVA with Programmable Controller for output Voltage & Frequency adjustment with password protection complete as per specification given here in below :- Rated power @ 0.8 pf lag: 7.5kVA INPUT Voltage - Nominal : 220V AC Range : 140 to 270 V AC Frequency- Nominal : 50Hz Range : 47-53Hz Phase : Single AC to AC Efficiency : 92% Rectifier Technology: 12 Pulse Rectifier SCR based fully controlled Power walk in: 10 to 15 secs THDi (input current Harmonic Distortion ): < 10% at rated load Input power Factor > 0.92lag Galvanic isolation: Inbuilt Galvanic Isolation
OUT PUT Voltage - Nominal: 36 V AC (Programmable) Regulation: 1% Frequency - Nominal : 50Hz (Programmable) Stability : 0.05% Phase : Single Phase Waveform : Sine Wave Total Harmonic Distortion : < 2% on linear load Transient Response: less than +/-8% for 100% step loads Recovery Time: less than 25milli secs to reach within +/-1% of nominal value Load power factor range : 0.8 lag to unity within kW rating Overload Protection: 120% for 30 min., 150% for1min, 200% for 10 cycles. Protections: Input over/under Voltage, Input Phase fail, overload, Output over/under Voltage, snubber circuits for power devices, over temperature, fuses for semi conductor devices, high speed electronic fuseless tripping for output short circuit Indications: Input ON, Output ON, Input abnormal, Output over/Under Voltage, overload, overheat Remote Alarm Potential free contacts for input fault & output trip Metering: 16x2 LCD panel to measure the following: AC input Voltage, output Voltage, load percentage, input & output frequency GENERAL Operating Temperature : 0 to 45 Deg C (50 Deg C Peak) Storage Temperature : -20 to 45 deg C Relative Humidity : 95% non condensing Cooling : Forced Air using localized cooling technique with multiple fractional HP fans
Panel : Welded structure MS Covers 2mm and frame 3mm thick Enclosure protection: IP 55 Cable Entry : Front Bottom
Supply, install, commission and testing static frequency converter 220 Volt A/C 50 cycle input & output Voltage 36 Volts + 1% tolerance output, 400Hz, 1 phase, 1 kVA with Programmable Controller for output Voltage & Frequency adjustment with password protection complete as per specification given here in below :- Rated power @ 0.8 pf lag: 1kVA INPUT Voltage - Nominal : 220V AC Range : 140 to 270 V AC Frequency- Nominal : 50Hz Range : 47-53Hz Phase : Single AC to AC Efficiency : 92% Rectifier Technology: 12 Pulse Rectifier SCR based fully controlled Power walk in: 10 to 15 secs THDi (input current Harmonic Distortion ): < 10% at rated load Input power Factor > 0.92lag Galvanic isolation: Inbuilt Galvanic Isolation
OUT PUT Voltage - Nominal: 36 V AC (Programmable) Regulation: 1% Frequency - Nominal : 400Hz (Programmable) Stability : 0.05% Phase : Single Phase Waveform : Sine Wave Total Harmonic Distortion : < 2% on linear load Transient Response: less than +/-8% for 100% step loads Recovery Time: less than 25milli secs to reach within +/-1% of nominal value Load power factor range : 0.8 lag to unity within kW rating Overload Protection: 120% for 30 min., 150% for1min, 200% for 10 cycles. Protections: Input over/under Voltage, Input Phase fail, overload, Output over/under Voltage, snubber circuits for power devices, over temperature, fuses for semi conductor devices, high speed electronic fuseless tripping for output short circuit Indications: Input ON, Output ON, Input abnormal, Output over/Under Voltage, overload, overheat Remote Alarm Potential free contacts for input fault & output trip Metering: 16x2 LCD panel to measure the following: AC input Voltage, output Voltage, load percentage, input & output frequency GENERAL Operating Temperature : 0 to 45 Deg C (50 Deg C Peak) Storage Temperature : -20 to 45 deg C Relative Humidity : 95% non condensing Cooling : Forced Air using localized cooling technique with multiple fractional HP fans
Panel : Welded structure MS Covers 2mm and frame 3mm thick Enclosure protection: IP 55 Cable Entry : Front Bottom
Supply, install, commission and testing static frequency converter 415 Volt A/C 50 cycle input & output Voltage 36 Volts + 1% tolerance output, 400 Hz, 3 phase, 2 kVA with Programmable Controller for output Voltage & Frequency adjustment with password protection complete 1 No each as per specification given here in below :- Rated power @ 0.8 pf lag: 2kVA INPUT Voltage - Nominal : 400V AC Range : 340 to 460 V AC Frequency- Nominal : 50Hz Range : 47-53Hz Phase : Single AC to AC Efficiency : 92% Rectifier Technology: 12 Pulse Rectifier SCR based fully controlled Power walk in: 10 to 15 secs THDi (input current Harmonic Distortion ): < 10% at rated load Input power Factor > 0.92lag Galvanic isolation: Inbuilt Galvanic Isolation
OUT PUT Voltage - Nominal: 36 V AC (Programmable) Regulation: 1% Frequency - Nominal : 400 Hz (Programmable) Stability : 0.05% Phase : Three Phase Waveform : Sine Wave Total Harmonic Distortion : < 2% on linear load Transient Response: less than +/-8% for 100% step loads Recovery Time: less than 25milli secs to reach within +/-1% of nominal value Load power factor range : 0.8 lag to unity within kW rating Overload Protection: 120% for 30 min., 150% for1min, 200% for 10 cycles. Protections: Input over/under Voltage, Input Phase fail, overload, Output over/under Voltage, snubber circuits for power devices, over temperature, fuses for semi conductor devices, high speed electronic fuseless tripping for output short circuit Indications: Input ON, Output ON, Input abnormal, Output over/Under Voltage, overload, overheat Remote Alarm Potential free contacts for input fault & output trip Metering: 16x2 LCD panel to measure the following: AC input Voltage, output Voltage, load percentage, input & output frequency GENERAL Operating Temperature : 0 to 45 Deg C (50 Deg C Peak) Storage Temperature : -20 to 45 deg C Relative Humidity : 95% non condensing Cooling : Forced Air using localized cooling technique with multiple fractional HP fans
Panel : Welded structure MS Covers 2mm and frame 3mm thick Enclosure protection: IP 55 Cable Entry : Front Bottom
Supply, install, commission and testing static frequency converter 415 Volt A/C 50 cycle input & output Voltage 36 Volts + 1% tolerance output, 400 Hz, 3 phase, 5kVA with Programmable Controller for output Voltage & Frequency adjustment with password protection complete as per specification given here in below :- Rated power @ 0.8 pf lag: 5kVA INPUT Voltage - Nominal : 400V AC Range : 340 to 460 V AC Frequency- Nominal : 50Hz Range : 47-53Hz Phase : Single AC to AC Efficiency : 92% Rectifier Technology: 12 Pulse Rectifier SCR based fully controlled Power walk in: 10 to 15 secs THDi (input current Harmonic Distortion ): < 10% at rated load Input power Factor > 0.92lag Galvanic isolation: Inbuilt Galvanic Isolation
OUT PUT Voltage - Nominal: 36 V AC (Programmable) Regulation: 1% Frequency - Nominal : 400Hz (Programmable) Stability : 0.05% Phase : Three Phase Waveform : Sine Wave Total Harmonic Distortion : < 2% on linear load Transient Response: less than +/-8% for 100% step loads Recovery Time: less than 25milli secs to reach within +/-1% of nominal value Load power factor range : 0.8 lag to unity within kW rating Overload Protection: 120% for 30 min., 150% for1min, 200% for 10 cycles. Protections: Input over/under Voltage, Input Phase fail, overload, Output over/under Voltage, snubber circuits for power devices, over temperature, fuses for semi conductor devices, high speed electronic fuseless tripping for output short circuit Indications: Input ON, Output ON, Input abnormal, Output over/Under Voltage, overload, overheat Remote Alarm Potential free contacts for input fault & output trip Metering: 16x2 LCD panel to measure the following: AC input Voltage, output Voltage, load percentage, input & output frequency GENERAL Operating Temperature : 0 to 45 Deg C (50 Deg C Peak) Storage Temperature : -20 to 45 deg C Relative Humidity : 95% non condensing Cooling : Forced Air using localized cooling technique with multiple fractional HP fans
Panel : Welded structure MS Covers 2mm and frame 3mm thick Enclosure protection: IP 55 Cable Entry : Front Bottom
Supply, install, commission and testing static frequency converter 415 Volt A/C 50 cycle input & output Voltage 27 Volts DC + 1% tolerance output, 400Hz, 3 phase, 2kVA with Programmable Controller for output Voltage & Frequency adjustment with password protection complete 1 No. each complete as per specification given here in below :- Rated power @ 0.8 pf lag: 2kVA INPUT Voltage - Nominal : 400V AC Range : 340 to 460 V AC Frequency- Nominal : 50Hz Range : 47-53Hz Phase : Single AC to AC Efficiency : 92% Rectifier Technology: 12 Pulse Rectifier SCR based fully controlled Power walk in: 10 to 15 secs THDi (input current Harmonic Distortion ): < 10% at rated load Input power Factor > 0.92lag Galvanic isolation: Inbuilt Galvanic Isolation
OUT PUT Voltage - Nominal: 27 V AC (Programmable) Regulation: 1% Frequency - Nominal : 400 Hz (Programmable) Stability : 0.05% Phase : Three Phase Waveform : Sine Wave Total Harmonic Distortion : < 2% on linear load Transient Response: less than +/-8% for 100% step loads Recovery Time: less than 25milli secs to reach within +/-1% of nominal value Load power factor range : 0.8 lag to unity within kW rating Overload Protection: 120% for 30 min., 150% for 1min, 200% for 10 cycles. Protections: Input over/under Voltage, Input Phase fail, overload, Output over/under Voltage, snubber circuits for power devices, over temperature, fuses for semi conductor devices, high speed electronic fuseless tripping for output short circuit Indications: Input ON, Output ON, Input abnormal, Output over/Under Voltage, overload, overheat Remote Alarm Potential free contacts for input fault & output trip Metering: 16x2 LCD panel to measure the following: AC input Voltage, output Voltage, load percentage, input & output frequency GENERAL Operating Temperature : 0 to 45 Deg C (50 Deg C Peak) Storage Temperature : -20 to 45 deg C Relative Humidity : 95% non condensing Cooling : Forced Air using localized cooling technique with multiple fractional HP fans
Panel : Welded structure MS Covers 2mm and frame 3mm thick Enclosure protection: IP 55 Cable Entry : Front Bottom
Supply, install, commission and testing static Voltage converter 415 Volt A/C 50 cycle input & output Voltage 380 Volts + 1% tolerance output, 50Hz, 1 phase, 50 kVA with Programmable Controller for output Voltage & Frequency adjustment with password protection for 1 No each in complete as per specification given here in below :- Rated power @ 0.8 pf lag: 50kVA INPUT Voltage - Nominal : 400V AC Range : 340 to 460 V AC Frequency- Nominal : 50Hz Range : 47-53Hz Phase : Single AC to AC Efficiency : 92% Rectifier Technology: 12 Pulse Rectifier SCR based fully controlled Power walk in: 10 to 15 secs THDi (input current Harmonic Distortion ): < 10% at rated load Input power Factor > 0.92lag Galvanic isolation: Inbuilt Galvanic Isolation
OUT PUT Voltage - Nominal: 380 V AC (Programmable) Regulation: 1% Frequency - Nominal : 50Hz (Programmable) Stability : 0.05% Phase : Single Phase Waveform : Sine Wave Total Harmonic Distortion : < 2% on linear load Transient Response: less than +/-8% for 100% step loads Recovery Time: less than 25milli secs to reach within +/-1% of nominal value Load power factor range : 0.8 lag to unity within kW rating Overload Protection: 120% for 30 min., 150% for1min, 200% for 10 cycles. Protections: Input over/under Voltage, Input Phase fail, overload, Output over/under Voltage, snubber circuits for power devices, over temperature, fuses for semi conductor devices, high speed electronic fuseless tripping for output short circuit Indications: Input ON, Output ON, Input abnormal, Output over/Under Voltage, overload, overheat Remote Alarm Potential free contacts for input fault & output trip Metering: 16x2 LCD panel to measure the following: AC input Voltage, output Voltage, load percentage, input & output frequency GENERAL Operating Temperature : 0 to 45 Deg C (50 Deg C Peak) Storage Temperature : -20 to 45 deg C Relative Humidity : 95% non condensing Cooling : Forced Air using localized cooling technique with multiple fractional HP fans
Panel : Welded structure MS Covers 2mm and frame 3mm thick Enclosure protection: IP 55 Cable Entry : Front Bottom
Supply, install, commission and testing 1 kVA Static DC Power Supply 220 Volt A/C 50 cycle input & 27 VDC +1% tolerance output with Programmable Controller for output Voltage with Password Protection 1 No. each complete specification given here in below :- Rated power @ 0.8 pf lag : 27V DC, 1kVA INPUT Voltage - Nominal : 220V AC Range : 140 - 280V AC Frequency- Nominal : 50Hz Range : 47-53Hz Phase : Single AC to AC Efficiency : 92% Rectifier Technology: 12 Pulse Rectifier SCR based fully controlled Power walk in: 10 to 15 secs THDi (input current Harmonic Distortion ): < 10% at rated load Input power Factor > 0.92lag Galvanic isolation: Inbuilt Galvanic Isolation
OUT PUT Voltage - Nominal: 27 V DC (Programmable) Regulation: 1% Total Harmonic Distortion : < 2% on linear load Transient Response: less than +/-8% for 100% step loads Recovery Time: less than 25milli secs to reach within +/-1% of nominal value Load power factor range : 0.8 lag to unity within kW rating Overload Protection: 120% for 30 min., 150% for1min, 200% for 10 cycles. Protections: Input over/under Voltage, Input Phase fail, overload, Output over/under Voltage, snubber circuits for power devices, over temperature, fuses for semi conductor devices, high speed electronic fuseless tripping for output short circuit Indications: Input ON, Output ON, Input abnormal, Output over/Under Voltage, overload, overheat Remote Alarm Potential free contacts for input fault & output trip Metering: 16x2 LCD panel to measure the following: AC input Voltage, output Voltage, load percentage, input & output frequency GENERAL Operating Temperature : 0 to 45 Deg C (50 Deg C Peak) Storage Temperature : -20 to 45 deg C Relative Humidity : 95% non condensing Cooling : Forced Air using localized cooling technique with multiple fractional HP fans
Panel : Welded structure MS Covers 2mm and frame 3mm thick Enclosure protection: IP 55 Cable Entry : Front Bottom
Supply, install, commission and testing 12 kW Static DC Power Supply 415 Volt A/C 50 cycle input & 27 VDC +1% tolerance output with Programmable Controller for output Voltage with Password Protection with complete specification given here in below :- Rated power @ 0.8 pf lag : 27V DC, 12 kW INPUT Voltage - Nominal : 400V Range : 340 - 480V Ac Frequency- Nominal : 50Hz Range : 47-53Hz Phase : Single AC to AC Efficiency : 92% Rectifier Technology: 12 Pulse Rectifier SCR based fully controlled Power walk in: 10 to 15 secs THDi (input current Harmonic Distortion ): < 10% at rated load Input power Factor > 0.92lag Galvanic isolation: Inbuilt Galvanic Isolation
OUT PUT Voltage - Nominal: 27 V DC (Programmable) Regulation: 1% Total Harmonic Distortion : < 2% on linear load Transient Response: less than +/-8% for 100% step loads Recovery Time: less than 25milli secs to reach within +/-1% of nominal value Load power factor range : 0.8 lag to unity within kW rating Overload Protection: 120% for 30 min., 150% for1min, 200% for 10 cycles. Protections: Input over/under Voltage, Input Phase fail, overload, Output over/under Voltage, snubber circuits for power devices, over temperature, fuses for semi conductor devices, high speed electronic fuseless tripping for output short circuit Indications: Input ON, Output ON, Input abnormal, Output over/Under Voltage, overload, overheat Remote Alarm Potential free contacts for input fault & output trip Metering: 16x2 LCD panel to measure the following: AC input Voltage, output Voltage, load percentage, input & output frequency GENERAL Operating Temperature : 0 to 45 Deg C (50 Deg C Peak) Storage Temperature : -20 to 45 deg C Relative Humidity : 95% non condensing Cooling : Forced Air using localized cooling technique with multiple fractional HP fans
Panel : Welded structure MS Covers 2mm and frame 3mm thick Enclosure protection: IP 55 Cable Entry : Front Bottom
Supply, install, commission and testing 9kVA Static DC Power Supply 415 Volt A/C 50 cycle input & 27 VDC +1% tolerance output with Programmable Controller for output Voltage with Password Protection with complete specification given here in below :- Rated power @ 0.8 pf lag : 27V DC, 9kVA INPUT Voltage - Nominal : 400V Range : 340 - 480V Ac Frequency- Nominal : 50Hz Range : 47-53Hz Phase : Single AC to AC Efficiency : 92% Rectifier Technology: 12 Pulse Rectifier SCR based fully controlled Power walk in: 10 to 15 secs THDi (input current Harmonic Distortion ): < 10% at rated load Input power Factor > 0.92lag Galvanic isolation: Inbuilt Galvanic Isolation
OUT PUT Voltage - Nominal: 27 V DC (Programmable) Regulation: 1% Total Harmonic Distortion : < 2% on linear load Transient Response: less than +/-8% for 100% step loads Recovery Time: less than 25 milli secs to reach within +/-1% of nominal value Load power factor range : 0.8 lag to unity within kW rating Overload Protection: 120% for 30 min., 150% for 1min, 200% for 10 cycles. Protections: Input over/under Voltage, Input Phase fail, overload, Output over/under Voltage, snubber circuits for power devices, over temperature, fuses for semi conductor devices, high speed electronic fuseless tripping for output short circuit Indications: Input ON, Output ON, Input abnormal, Output over/Under Voltage, overload, overheat Remote Alarm Potential free contacts for input fault & output trip Metering: 16x2 LCD panel to measure the following: AC input Voltage, output Voltage, load percentage, input & output frequency GENERAL Operating Temperature : 0 to 45 Deg C (50 Deg C Peak) Storage Temperature : -20 to 45 deg C Relative Humidity : 95% non condensing Cooling : Forced Air using localized cooling technique with multiple fractional HP fans
Panel : Welded structure MS Covers 2mm and frame 3mm thick Enclosure protection: IP 55 Cable Entry : Front Bottom
Supply, install, commission and testing 5 kW Static DC Power Supply 415 Volt A/C 50 cycle input & 27 VDC +1% tolerance output with Programmable Controller for output Voltage with Password Protection with complete specification given here in below :- Rated power @ 0.8 pf lag : 27V DC, 5 kW INPUT Voltage - Nominal : 400V Range : 340 - 480V Ac Frequency- Nominal : 50Hz Range : 47-53Hz Phase : Single AC to AC Efficiency : 92% Rectifier Technology: 12 Pulse Rectifier SCR based fully controlled Power walk in: 10 to 15 secs THDi (input current Harmonic Distortion ): < 10% at rated load Input power Factor > 0.92lag Galvanic isolation: Inbuilt Galvanic Isolation
OUT PUT Voltage - Nominal: 27 V DC (Programmable) Regulation: 1% Total Harmonic Distortion : < 2% on linear load Transient Response: less than +/-8% for 100% step loads Recovery Time: less than 25milli secs to reach within +/-1% of nominal value Load power factor range : 0.8 lag to unity within kW rating Overload Protection: 120% for 30 min., 150% for 1min, 200% for 10 cycles. Protections: Input over/under Voltage, Input Phase fail, overload, Output over/under Voltage, snubber circuits for power devices, over temperature, fuses for semi conductor devices, high speed electronic fuseless tripping for output short circuit Indications: Input ON, Output ON, Input abnormal, Output over/Under Voltage, overload, overheat Remote Alarm Potential free contacts for input fault & output trip Metering: 16x2 LCD panel to measure the following: AC input Voltage, output Voltage, load percentage, input & output frequency GENERAL Operating Temperature : 0 to 45 Deg C (50 Deg C Peak) Storage Temperature : -20 to 45 deg C Relative Humidity : 95% non condensing Cooling : Forced Air using localized cooling technique with multiple fractional HP fans
Panel : Welded structure MS Covers 2mm and frame 3mm thick Enclosure protection: IP 55 Cable Entry : Front Bottom
Supply, install, commission and testing 10 kVA Static DC Power Supply 415 Volt A/C 50 cycle input & 27 VDC +1% tolerance output with Programmable Controller for output Voltage with Password Protection with complete specification given here in below :- Rated power @ 0.8 pf lag : 27V DC, 10kVA INPUT Voltage - Nominal : 400V Range : 340 - 480V Ac Frequency- Nominal : 50Hz Range : 47-53Hz Phase : Single AC to AC Efficiency : 92% Rectifier Technology: 12 Pulse Rectifier SCR based fully controlled Power walk in: 10 to 15 secs THDi (input current Harmonic Distortion ): < 10% at rated load Input power Factor > 0.92lag Galvanic isolation: Inbuilt Galvanic Isolation
OUT PUT Voltage - Nominal: 27 V DC (Programmable) Regulation: 1% Total Harmonic Distortion : < 2% on linear load Transient Response: less than +/-8% for 100% step loads Recovery Time: less than 25milli secs to reach within +/-1% of nominal value Load power factor range : 0.8 lag to unity within kW rating Overload Protection: 120% for 30 min., 150% for1min, 200% for 10 cycles. Protections: Input over/under Voltage, Input Phase fail, overload, Output over/under Voltage, snubber circuits for power devices, over temperature, fuses for semi conductor devices, high speed electronic fuseless tripping for output short circuit Indications: Input ON, Output ON, Input abnormal, Output over/Under Voltage, overload, overheat Remote Alarm Potential free contacts for input fault & output trip Metering: 16x2 LCD panel to measure the following: AC input Voltage, output Voltage, load percentage, input & output frequency GENERAL Operating Temperature : 0 to 45 Deg C (50 Deg C Peak) Storage Temperature : -20 to 45 deg C Relative Humidity : 95% non condensing Cooling : Forced Air using localized cooling technique with multiple fractional HP fans
Panel : Welded structure MS Covers 2mm and frame 3mm thick Enclosure protection: IP 55 Cable Entry : Front Bottom
Supply, install, commission and testing 18 kVA Static DC Power Supply 415 Volt A/C 50 cycle input & 27 VDC +1% tolerance output with Programmable Controller for output Voltage with Password Protection with complete specification given here in below :- Rated power @ 0.8 pf lag : 27V DC, 18kVA INPUT Voltage - Nominal : 400V Range : 340 - 480V Ac Frequency- Nominal : 50Hz Range : 47-53Hz Phase : Single AC to AC Efficiency : 92% Rectifier Technology: 12 Pulse Rectifier SCR based fully controlled Power walk in: 10 to 15 secs THDi (input current Harmonic Distortion ): < 10% at rated load Input power Factor > 0.92lag Galvanic isolation: Inbuilt Galvanic Isolation
OUT PUT Voltage - Nominal: 27V DC (Programmable) Regulation: 1% Total Harmonic Distortion : < 2% on linear load Transient Response: less than +/-8% for 100% step loads Recovery Time: less than 25milli secs to reach within +/-1% of nominal value Load power factor range : 0.8 lag to unity within kW rating Overload Protection: 120% for 30 min., 150% for1min, 200% for 10 cycles. Protections: Input over/under Voltage, Input Phase fail, overload, Output over/under Voltage, snubber circuits for power devices, over temperature, fuses for semi conductor devices, high speed electronic fuseless tripping for output short circuit Indications: Input ON, Output ON, Input abnormal, Output over/Under Voltage, overload, overheat Remote Alarm Potential free contacts for input fault & output trip Metering: 16x2 LCD panel to measure the following: AC input Voltage, output Voltage, load percentage, input & output frequency GENERAL Operating Temperature : 0 to 45 Deg C (50 Deg C Peak) Storage Temperature : -20 to 45 deg C Relative Humidity : 95% non condensing Cooling : Forced Air using localized cooling technique with multiple fractional HP fans
Panel : Welded structure MS Covers 2mm and frame 3mm thick Enclosure protection: IP 55 Cable Entry : Front Bottom
Supply, install, commission and testing 30kVA Static DC Power Supply 415 Volt A/C 50 cycle input & 27 VDC +1% tolerance output with Programmable Controller for output Voltage with Password Protection with complete specification given here in below :- Rated power @ 0.8 pf lag : 27V DC, 30 kVA INPUT Voltage - Nominal : 400V Range : 340 - 480V Ac Frequency- Nominal : 50Hz Range : 47-53Hz Phase : Single AC to AC Efficiency : 92% Rectifier Technology: 12 Pulse Rectifier SCR based fully controlled Power walk in: 10 to 15 secs THDi (input current Harmonic Distortion ): < 10% at rated load Input power Factor > 0.92lag Galvanic isolation: Inbuilt Galvanic Isolation
OUT PUT Voltage - Nominal: 27 V DC (Programmable) Regulation: 1% Total Harmonic Distortion : < 2% on linear load Transient Response: less than +/-8% for 100% step loads Recovery Time: less than 25milli secs to reach within +/-1% of nominal value Load power factor range : 0.8 lag to unity within kW rating Overload Protection: 120% for 30 min., 150% for1min, 200% for 10 cycles. Protections: Input over/under Voltage, Input Phase fail, overload, Output over/under Voltage, snubber circuits for power devices, over temperature, fuses for semi conductor devices, high speed electronic fuseless tripping for output short circuit Indications: Input ON, Output ON, Input abnormal, Output over/Under Voltage, overload, overheat Remote Alarm Potential free contacts for input fault & output trip Metering: 16x2 LCD panel to measure the following: AC input Voltage, output Voltage, load percentage, input & output frequency GENERAL Operating Temperature : 0 to 45 Deg C (50 Deg C Peak) Storage Temperature : -20 to 45 deg C Relative Humidity : 95% non condensing Cooling : Forced Air using localized cooling technique with multiple fractional HP fans
Panel : Welded structure MS Covers 2mm and frame 3mm thick Enclosure protection: IP 55 Cable Entry : Front Bottom
Supply, install, commission and testing of 40 kVA Special AC Power Supply Single Phase I/P - Single Phase O/P Electro Mechanical Type comprising of Motorized Dimmer-stat, Buck-Boost Transformer, AC Step- Synchronous Motor, solid state electronic control circuits with switching Triacs & Surge Suppresion provision complete as per specification given here in below :- System Construction : Conforming to IS:9815-1994 INPUT Voltage - Nominal : 230 VAC Range : 140 to 280 V AC Frequency- Nominal : 50Hz Range : 45-60Hz Phase : Single
OUT PUT Voltage - 220+/- 1%, 1Ph, 2 wire Frequency- 50Hz Speed of Correction: Voltage Correction Rate60V/Sec Insulation Resistance: Above 5m Ohms at 500V DC, Class-H High Voltage: Can withstand 2.5kV for 5 Sec Dielectric Strength: 1.5kV rms for 1 minute Power Loss: Max 2% Efficiency: Not less than 98% Duty Cycle: 100% continuous Load PF: There should be no effect to output due to load PF Response Time: Less than 20milli sec Metering: Digital AC Voltmeter for Input & Output Voltage & AC Ammeter for output current. Operation: Auto or Manual Indications: LED indication for Input Voltage, High/Low & Overload Protections: High/Low Voltage Cut off, Overload & Surge Suppressor, Harmonic Filter to reduce THD at output to less than 10%, short circuit Lamination: CRGO lamination with 99% copper By-Pass: Stabiliser By-pass facility to be provided Transformer Oil: Transformer oil should confirm to IS 335, IEC 296 first filling to be provided at the time of supply. Terminations: Input & Output terminations as per IS:3347 Cabling: Input & Output terminations with provision for fixing cable glands. Earthing: with Earth terminals Indications: Input/output Voltage , input/output current, Frequency, High/Low Voltage with Buzzer, oil level Indicator
Supply, install, commission and testing of 20 kVA Special AC Power Supply Single Phase I/P - Single Phase O/P Electro Mechanical Type comprising of Motorized Dimmer-stat, Buck-Boost Transformer, AC Step- Synchronous Motor, solid state electronic control circuits with switching Triacs & Surge Suppresion provision complete as per specification given here in below :- System Construction : Conforming to IS:9815-1994 INPUT Voltage - Nominal : 230 VAC Range : 140 to 280 V AC Frequency- Nominal : 50Hz Range : 45-60Hz Phase : Single
OUT PUT Voltage - 220+/- 1%, 1Ph, 2 wire Frequency- 50Hz Speed of Correction: Voltage Correction Rate60V/Sec Insulation Resistance: Above 5m Ohms at 500V DC, Class-H High Voltage: Can withstand 2.5kV for 5 Sec Dielectric Strength: 1.5kV rms for 1 minute Power Loss: Max 2% Efficiency: Not less than 98% Duty Cycle: 100% continuous Load PF: There should be no effect to output due to load PF Response Time: Less than 20milli sec Metering: Digital AC Voltmeter for Input & Output Voltage & AC Ammeter for output current. Operation: Auto or Manual Indications: LED indication for Input Voltage, High/Low & Overload Protections: High/Low Voltage Cut off, Overload & Surge Suppressor, Harmonic Filter to reduce THD at output to less than 10%, short circuit Lamination: CRGO lamination with 99% copper By-Pass: Stabiliser By-pass facility to be provided Transformer Oil: Transformer oil should confirm to IS 335, IEC 296 first filling to be provided at the time of supply. Terminations: Input & Output terminations as per IS:3347 Cabling: Input & Output terminations with provision for fixing cable glands. Earthing: with Earth terminals Indications: Input/output Voltage, input/output current, Frequency, High/Low Voltage with Buzzer, oil level Indicator
Supply, install, commission and testing of 10 kVA Special AC Power Supply Single Phase I/P - Single Phase O/P Electro Mechanical Type comprising of Motorized Dimmer-stat, Buck-Boost Transformer, AC Step- Synchronous Motor, solid state electronic control circuits with switching Triacs & Surge Suppresion provision complete as per specification given here in below :- INPUT Voltage - Nominal : 230 VAC Range : 140 to 280 V AC Frequency- Nominal : 50Hz Range : 45-60Hz Phase : Single
OUT PUT Voltage - 220+/- 1%, 1Ph, 3 wire Frequency- 50Hz Speed of Correction: Voltage Correction Rate60V/Sec Insulation Resistance: Above 5M Ohms at 500V DC, Class-H High Voltage: Can withstand 2.5kV for 5 Sec Dielectric Strength: 1.5kV rms for 1 minute Power Loss: Max 2% Efficiency: Not less than 98% Duty Cycle: 100% continuous Load PF: There should be no effect to output due to load PF Response Time: Less than 20milli sec Metering: Digital AC Voltmeter for Input & Output Voltage & AC Ammeter for output current. Operation: Auto or Manual Indications: LED indication for Input Voltage, High/Low & Overload Protections: High/Low Voltage Cut off, Overload & Surge Suppressor, Harmonic Filter to reduce THD at output to less than 10%, short circuit Lamination: CRGO lamination with 99% copper By-Pass: Stabiliser By-pass facility to be provided Transformer Oil: Transformer oil should confirm to IS 335, IEC 296 first filling to be provided at the time of supply. Terminations: Input & Output terminations as per IS:3347 Cabling: Input & Output terminations with provision for fixing cable glands. Earthing: with Earth terminals Indications: Input/output Voltage , input/output current, Frequency, High/Low Voltage with Buzzer, oil level Indicator
Supply, install, commission and testing un-interrupted Power Supply System 415 Volt A/C 50 cycle input & output Voltage 220Volts + 0.5% tolerance output, 50Hz, 1 phase, 30 kVA with Programmable Controller for output Voltage with password protection, Enclosure Protection IP-55 alongwith SMF Batteries for 30 minutes back up complete as per specification given here in below :- Rated power @ 0.8 pf lag : 30kVA INPUT Voltage - Nominal : 400V Range : 340 - 480V Ac Frequency- Nominal : 50Hz Range : 47-53Hz Phase : Single AC to AC Efficiency : 92% Rectifier Technology: 12 Pulse Rectifier SCR based fully controlled Power walk in: 10 to 15 secs THDi (input current Harmonic Distortion ): < 10% at rated load Input power Factor > 0.92lag Galvanic isolation: Inbuilt Galvanic Isolation
OUT PUT Voltage - Nominal: 220V AC (Programmable) Regulation: 1% Frequency - Nominal : 50Hz (Programmable) Stability : 0.05% Phase : Single Phase Waveform : Sine Wave Total Harmonic Distortion : < 2% on linear load Transient Response: less than +/-8% for 100% step loads Recovery Time: less than 25milli secs to reach within +/-1% of nominal value Load power factor range : 0.8 lag to unity within kW rating Overload Protection: 120% for 30 min., 150% for1min, 200% for 10 cycles. Protections: Input over/under Voltage, Input Phase fail, overload, Output over/under Voltage, snubber circuits for power devices, over temperature, fuses for semi conductor devices, high speed electronic fuseless tripping for output short circuit Indications: Input ON, Output ON, Input abnormal, Output over/Under Voltage, overload, overheat Remote Alarm Potential free contacts for input fault & output trip Metering: 16x2 LCD panel to measure the following: AC input Voltage, output Voltage, load percentage, input & output frequency GENERAL Operating Temperature : 0 to 45 Deg C (50 Deg C Peak) Storage Temperature : -20 to 45 deg C Relative Humidity : 95% non condensing Cooling : Forced Air using localized cooling technique with multiple fractional HP fans
Panel : Welded structure MS Covers 2mm and frame 3mm thick Enclosure protection: IP 55 Cable Entry : Front Bottom
Supply, install, commission and testing Uninterrupted Power Supply System 415 Volt A/C 50 cycle input & output Voltage 220Volts + 0.5% tolerance output, 50Hz, 1 phase, 20kVA with Programmable Controller for output Voltage with password protection, Enclosure Protection IP-55 alongwith SMF Batteries for 30 minutes back up for "O' Level, "I" Level, complete as per specification given here in below :- Rated power @ 0.8 pf lag: 20 kVA INPUT Voltage - Nominal : 400V Range : 340 - 460V Ac Frequency- Nominal : 50Hz Range : 47-53Hz Phase : Single AC to AC Efficiency : 92% Rectifier Technology: 12 Pulse Rectifier SCR based fully controlled Power walk in: 10 to 15 secs THDi (input current Harmonic Distortion ): < 10% at rated load Input power Factor > 0.92lag Galvanic isolation: Inbuilt Galvanic Isolation
OUT PUT Voltage - Nominal: 220V AC (Programmable) Regulation: 1% Frequency - Nominal : 50Hz (Programmable) Stability : 0.05% Phase : Single Phase Waveform : Sine Wave Total Harmonic Distortion : < 2% on linear load Transient Response: less than +/-8% for 100% step loads Recovery Time: less than 25milli secs to reach within +/-1% of nominal value Load power factor range : 0.8 lag to unity within kW rating Overload Protection: 120% for 30 min., 150% for1min, 200% for 10 cycles. Protections: Input over/under Voltage, Input Phase fail, overload, Output over/under Voltage, snubber circuits for power devices, over temperature, fuses for semi conductor devices, high speed electronic fuseless tripping for output short circuit Indications: Input ON, Output ON, Input abnormal, Output over/Under Voltage, overload, overheat Remote Alarm Potential free contacts for input fault & output trip Metering: 16x2 LCD panel to measure the following: AC input Voltage, output Voltage, load percentage, input & output frequency GENERAL Operating Temperature : 0 to 45 Deg C (50 Deg C Peak) Storage Temperature : -20 to 45 deg C Relative Humidity : 95% non condensing Cooling : Forced Air using localized cooling technique with multiple fractional HP fans
Panel : Welded structure MS Covers 2mm and frame 3mm thick Enclosure protection: IP 55 Cable Entry : Front Bottom
Supply, install, commission and testing Uninterrupted Power Supply System 415 Volt A/C 50 cycle input & output Voltage 220 Volts + 0.5% tolerance output, 50Hz, 1 phase, 15kVA with Programmable Controller for output Voltage with password protection, Enclosure Protection IP-55 alongwith SMF Batteries for 30 minutes back up for complete as per specification given here in below :- Rated power @ 0.8 pf lag: 15 kVA INPUT Voltage - Nominal : 400V Range : 340 - 460V Ac Frequency- Nominal : 50Hz Range : 47-53Hz Phase : Single AC to AC Efficiency : 92% Rectifier Technology: 12 Pulse Rectifier SCR based fully controlled Power walk in: 10 to 15 secs THDi (input current Harmonic Distortion ): < 10% at rated load Input power Factor > 0.92lag Galvanic isolation: Inbuilt Galvanic Isolation
OUT PUT Voltage - Nominal: 220V AC (Programmable) Regulation: 1% Frequency - Nominal : 50Hz (Programmable) Stability : 0.05% Phase : Single Phase Waveform : Sine Wave Total Harmonic Distortion : < 2% on linear load Transient Response: less than +/-8% for 100% step loads Recovery Time: less than 25milli secs to reach within +/-1% of nominal value Load power factor range : 0.8 lag to unity within kW rating Overload Protection: 120% for 30 min., 150% for1min, 200% for 10 cycles. Protections: Input over/under Voltage, Input Phase fail, overload, Output over/under Voltage, snubber circuits for power devices, over temperature, fuses for semi conductor devices, high speed electronic fuseless tripping for output short circuit Indications: Input ON, Output ON, Input abnormal, Output over/Under Voltage, overload, overheat Remote Alarm Potential free contacts for input fault & output trip Metering: 16x2 LCD panel to measure the following: AC input Voltage, output Voltage, load percentage, input & output frequency GENERAL Operating Temperature : 0 to 45 Deg C (50 Deg C Peak) Storage Temperature : -20 to 45 deg C Relative Humidity : 95% non condensing Cooling : Forced Air using localized cooling technique with multiple fractional HP fans
Panel : Welded structure MS Covers 2mm and frame 3mm thick Enclosure protection: IP 55 Cable Entry : Front Bottom
Supply, install, commission and testing Uninterrupted Power Supply System 415 Volt A/C 50 cycle input & output Voltage 220 Volts + 0.5% tolerance output, 50Hz, 1 phase, 10kVA with Programmable Controller for output Voltage with password protection, Enclosure Protection IP-55 alongwith SMF Batteries for 30 minutes back up for complete as per specification given here in below :- Rated power @ 0.8 pf lag: 10 kVA INPUT Voltage - Nominal : 400V Range : 340 - 460V Ac Frequency- Nominal : 50Hz Range : 47-53Hz Phase : Single AC to AC Efficiency : 92% Rectifier Technology: 12 Pulse Rectifier SCR based fully controlled Power walk in: 10 to 15 secs THDi (input current Harmonic Distortion ): < 10% at rated load Input power Factor > 0.92lag Galvanic isolation: Inbuilt Galvanic Isolation
OUT PUT Voltage - Nominal: 220V AC (Programmable) Regulation: 1% Frequency - Nominal : 50Hz (Programmable) Stability : 0.05% Phase : Single Phase Waveform : Sine Wave Total Harmonic Distortion : < 2% on linear load Transient Response: less than +/-8% for 100% step loads Recovery Time: less than 25milli secs to reach within +/-1% of nominal value Load power factor range : 0.8 lag to unity within kW rating Overload Protection: 120% for 30 min., 150% for 1min, 200% for 10 cycles. Protections: Input over/under Voltage, Input Phase fail, overload, Output over/under Voltage, snubber circuits for power devices, over temperature, fuses for semi conductor devices, high speed electronic fuseless tripping for output short circuit Indications: Input ON, Output ON, Input abnormal, Output over/Under Voltage, overload, overheat Remote Alarm Potential free contacts for input fault & output trip Metering: 16x2 LCD panel to measure the following: AC input Voltage, output Voltage, load percentage, input & output frequency GENERAL Operating Temperature : 0 to 45 Deg C (50 Deg C Peak) Storage Temperature : -20 to 45 deg C Relative Humidity : 95% non condensing Cooling : Forced Air using localized cooling technique with multiple fractional HP fans
Panel : Welded structure MS Covers 2mm and frame 3mm thick Enclosure protection: IP 55 Cable Entry : Front Bottom
Supply, install, commission and testing Uninterrupted Power Supply System 415 Volt A/C 50 cycle input & output Voltage 220Volts + 0.5% tolerance output, 50Hz, 1 phase, 5kVA with Programmable Controller for output Voltage with password protection, Enclosure Protection IP-55 alongwith SMF Batteries for 30 minutes back up for complete as per specification given here in below :- Rated power @ 0.8 pf lag: 5 kVA INPUT Voltage - Nominal : 400V Range : 340 - 460V Ac Frequency- Nominal : 50Hz Range : 47-53Hz Phase : Single AC to AC Efficiency : 92% Rectifier Technology: 12 Pulse Rectifier SCR based fully controlled Power walk in: 10 to 15 secs THDi (input current Harmonic Distortion ): < 10% at rated load Input power Factor > 0.92lag Galvanic isolation: Inbuilt Galvanic Isolation
OUT PUT Voltage - Nominal: 220V AC (Programmable) Regulation: 1% Frequency - Nominal : 50Hz (Programmable) Stability : 0.05% Phase : Single Phase Waveform : Sine Wave Total Harmonic Distortion : < 2% on linear load Transient Response: less than +/-8% for 100% step loads Recovery Time: less than 25milli secs to reach within +/-1% of nominal value Load power factor range : 0.8 lag to unity within kW rating Overload Protection: 120% for 30 min., 150% for1min, 200% for 10 cycles. Protections: Input over/under Voltage, Input Phase fail, overload, Output over/under Voltage, snubber circuits for power devices, over temperature, fuses for semi conductor devices, high speed electronic fuseless tripping for output short circuit Indications: Input ON, Output ON, Input abnormal, Output over/Under Voltage, overload, overheat Remote Alarm Potential free contacts for input fault & output trip Metering: 16x2 LCD panel to measure the following: AC input Voltage, output Voltage, load percentage, input & output frequency GENERAL Operating Temperature : 0 to 45 Deg C (50 Deg C Peak) Storage Temperature : -20 to 45 deg C Relative Humidity : 95% non condensing Cooling : Forced Air using localized cooling technique with multiple fractional HP fans
Panel : Welded structure MS Covers 2mm and frame 3mm thick Enclosure protection: IP 55 Cable Entry : Front Bottom
S&F Wall/Floor mounted Mains Distribution Panel for Maintenance Hanger F 1, F2, Hawk & Technical Hanger made out of 2mm thick CRCA sheet with V&F digital meters indoor type with following:. Input Side:- Copper Bus bar mounted on insulators suitable for 415V, 50Hz, 3Ph, 4 wire, 500A, 15 inch long with 7 tap off points, with VIF meter. Output Side:- (i) 200A, MCCB, 4P,415V, 25KA "C" curve (for 100kVA, 440V SFC) -01 No. (ii) 100A MCCB, 4P,415V, 25KA "C" Curve (for 45kVA, 208V SFC & 50kVA, 380V/1Ph) -02 Nos. (iii) 26A TPN, MCB, 415V, 35 kA "C" Curve (for 15kVA, 115V SFC)-01No. (iv) 16A DP, MCB, 220V, 10 kA "C" Curve (for 2kVA, 36/3Ph, 2kVA, 27V/3Ph & 1kVA 27VDC) -03No.
S&F wall mounted Output distribution panel made out of 2mm thick CRCA sheet with V & F digital meters for all outputs indoor type for Maintenance Hanger F1& F2, Hawk Hanger & Technical Hanger output suitable to accommodate: (i) 160A, MCCB, 4P, 25 kA "C" Curve . on Input side & 6 ''Copper Bus bar mounted on insulators with 2 tap off points suitable for 440V, 3Ph, 400 Hz, 4 wire, 200A on output side (for 100kVA, 440V SFC) (ii) 125A, MCCB, 4P, 35 kA, "C" Curve on Input side & 6'' copper Bus bar mounted on insulators with 2 tap off points suitable for 208V, 3Ph, 400Hz, 4 wire, 150A on output side (for 45kVA (208V) SFC) (iii) 63A, TPN,10KA on input side & Copper bus bar mounted on Insulators with 2 tap off points suitable for 115V, 1Ph, 400Hz, 2 wire, 150A (for 15 kVA SFC) (iv) 32A TPN, 10 kA on input side & 6" Copper bus bar mounted on insulators with 1 tap off point suitable for , 36V/3Ph, 400Hz, 50A, 4 wire (for 2kVA, 36V/3Ph SFC)
S&F wall mounted boxes made out of 2mm Rick CRCA Sheet indoor type suitable to Accommodate : Input Side : 63A, TPN,MCB, 10 kA C Curve - 3 Nos. 63A, DP,MCB, 10 kA, C Curve - 1 No. Output Side : 63A, 3 Pin, Industrial Type Male Female Sockets- 2 Nos. 63A, 5 Pin, Industrial Type Male Female Sockets- 2 Nos.
S&F wall mounted boxes made out of 2 mm Rick CRCA Sheet indoor type suitable to accommodate Input Side: 32A TPN, MCB, 10 kA, C Curve- 2 No. 32 DP, MCB, 10 kA, C Curve-1 No. Copper Bus Bar mounted on insulators of 4" Suitable for 40A, 2 wire, DC 27V Output side : 32A, 5 Pin, Industrial Type Male Female Sockets -2 No 32A, 3 Pin, Industrial Type Male-Female Sockets- 1 No.
S&F of wall mounted Mains distribution panel made out of 2mm thick CRCA Sheet indoor type with V&F digital meters comprising of : Input side : 1. 100A MCCB, 4P, 25 KA along with bus bar suitable for 415V, 3 phase 4 wire, 50 HZ, 4" Long Output side 1. 40A, TPN,MCB, 10 KA (for 27VDCPS) 2. 26A, TPN,MCB, 10 KA (for 10 kVA UPS)
S&F of floor mounted output panel made out of 2 mm thick CRCA Sheet Indoor type with V & F meters for AC output & V meter for DC O/P comprising of : 1. 250 A MCCB, 4P, 25 KA, along with 4" long bus bar suitable for 600A, 2 wire, 27VDC. 2. 32ADP, 10 kA along with 5A Sockets x 4 No's & I5A Sockets x 2 No's for 220V, 1 Ph, 50 Hz.
S&F of wall mounted UPS output panel indoor type comprising of 100A, 3P MCB, 25kA along with 8" long bus bar mounted on insulators suitable for 100A, 215V, 1 Ph, 2 wire, 50 Hz complete all as specified and directed.
S&F wall mounted mains distribution panel made out of 2mm thick CRCA Sheet with V & F digital meters for First floor left side Hawk hanger indoor type comprising of : Input Side 100A, MCCB, 4P, 25 kA with bus bar mounted on insulators suitable for 100A, 415V, 4 wire, 50 Hz, 10" Long. Outside : 1. 26A TPN,MCB, 10 kA- 1 No. (for DCPS) 2. 16A TPN,MCB, 10 kA-2 No. (for 115V & 36/3Ph SFC) 3. 16A DP,MCB, 10 kA- 1 No. (for 36/1SFC) 4. 80A DP,MCB, 10 kA-1 No. (for 10 kVA Stab)
S&F of wall mounted output distribution panel made out of 2 mm thick CRCA Sheet with suitable V & F digital meters for all outputs complete all as specified and directed. Indoor type comprising of : 1. 125A, MCCB, 4P, 25 kA alongwith bus bar suitable for 27VDC, 2 wire, 250A- 1 No. (for DCPS) 2. 100A MCCB, 4P, 25 kA along with bus bar suitable for 36V, 3 phase 4 wire, 400 Hz, 100A- 1 No (for 36V/3 phase SFC) 3. 26A TPN, MCB, 10kA, Alongwith bus bar suitable for 115V, 1phase 2 wire, 400 Hz, 50A- 1 No. (for 115V SFC) 4. 63A, DP, MCB, 10 kA alongwith bus bar suitable for 36V, 1 phase 2 wire, 60A-1 No. (for 36V/1PhSFC) 5. 63A DP, MCB, 10 kA alongwith bus bar suitable for 220V, 1phase 2 wire, 60A- 1 No. (for 220V Stab.)
S&F of Bus bar Panel made out of 2mm thick CRCA Sheet indoor type for Radio lab I comprising of 1. Bus Bar mounted on insulator suitable for 150A, 2 wire, 27VDC, 6" long. 2. Bus bar Mounted on insulator suitable for 30A, 2wire 115V, 400 Hz, 6" long. 3. Bus bar Mounted on insulator suitable for 30A, 2 wire, 220 V, 50 Hz 6" long. 4. Bus bar Mounted on insulator suitable for 50A, 4 wire, 3 Ph, 36V, 400 Hz 6:" long. 5. Bus Bar Mounted on insulator suitable for 40A, 2 wire, 1 Ph, 36V AC, 6" long.
S&F of wall/Table mounted supply boxes indoor type (4 No. Rectification lab, 4 No. Radio Section II, & 4 No. for Radio Section I) comprising of: 1. 6A, DP,MCB, 10 kA along with Industrial Type Male Female Socket 16A, 3 Pin (For 115V, 400HZSFC). 2. 32A, DP,MCB, 10 kA alongwith Industrial Type Male Female Socket 32A, 3 Pin (for 27 VDC) 3. 16A, TPN,MCB, 10 kA alongwith Industrial Type Male female socket 16A, 5 Pin (for 36V/3Ph SFC) 4. 16A, DP,MCB, 10 kA alongwith Industrial/type Male-Female Socket 16A, 3 Pin for 36V/1phase SFC 5. 32A, DP,MCB 10 kA alongwith 16A, 3 Pin, 2 No. sockets.
S&F of wall/floor mounted mains distribution panel made out of 2 mm thick CRCA sheet indoor type comprising of: Incoming Side : 160A, MCCB, 25kA, 4P alongwith Copper Bus bar mounted on insulators suitable for 200A, 415V, 3 phase 4 wire, 50 Hz, 8" long, with V & F Digital meters. Outgoing Side 1. 32A TPN,MCB, 10 kA (for 16 kVA, 115V, 1 phase SFC) 2. 10A, TPN,MCB, 10 kA (for 4 kVA, 36V, Iphase SFC) 3. 63A, TPN,MCB, 10 kA (for 18 AVA DCPS) 4. 100A, MCCB, 4P,MCB, 25kA (for 40 kVA Stab)
S&F of output distribution panel wall mounted made out of 2 mm thick CRCA Sheet indoor type with suitable V & F digital meters comprising of 1. 100 A, MCCB, 4P, 25kA (for 115V SFC) alongwith copper bus bar mounted on suitable insulators for 150 A, 2 wire, 115V, 400 Hz, 1' long. 2. 63A, TPN, MCB, 10 kA (for 36V/IPh SFC) alongwith copper bus bar mounted on suitable insulators for 120A, 2 wire, 36V, 1Ph, 1' long. 3. 350A, MCCB, 4 P, 35 kA (for 27VDC) alongwith copper bus bar mounted on insulators for 700 A, 2 wire, 27V DC, 1' long. 4. 63A TPN, MCB, 10 kA (for 415VAC) alongwith bus bar mounted on insulators for 70A, 4 wire, 415 VAC, 1' long.
S&F of wall mounted sub output distribution panel comprising of: Bus Bar set mounted on insulator suitable for: 1. 50A, 115V, 1 Ph, 2 wire, 400 Hz, 8" Long. 2. 200A, 27V DC, 2 wire, 8" Long 3. 80A, 220V, 2 wire, 50 Hz, 8" Long. In addition above 63A, 36V, 1 phase 400Hz, 2 wire bus bar 8" long needed for room No. 3 only. Suitable Digital V & F meters to be provided.
S&F of wall/table mounted supply box 1. 6A, DP,MCB, 10 kA with 5A x 2 No. Sockets 2. 32A,DP,MCB, 10 kA with 32A, 3 Pin, industrial type male Female connectors 3. 32A, DP,MCB,10 kA with 10A x 4 No's sockets.
S&F wall mounted output distribution panel made with 2 mm thick CRCA Sheet Indoor type comprising of : 1. 125A, MCCB, 4P, 25kA alongwith copper bus bar suitable for 27VDC, 2 wire, 250A- 1 No. (for DCPS) 2. 100A, MCCB,4P, 25kA along with copper bus bar suitable for 36V, 3 Ph, 4 wire, 400 Hz, 100A- 2 No (for 36V/3Ph SFC) 3.26A, TPN, MCB, 10kA, alongwith bus bar suitable for 115V, 1Ph, 2 wire, 400 Hz, 50A- 1 No. (for 115V/1Ph SFC) 4. 63A, DP MCB 10 kA alongwith bus bar suitable for 36V, 1 phase 2 wire, 60A-1 No. (for 36V/1PhSFC) 5. 63A, DP, MCB, 10 kA alongwith bus bar suitable for 220V, 1phase 2 wire, 60A- 1 No. (for 220V Stab.) 6. 16A DP 10 kA with 10A x 1 No. Socket.
S&F wall/floor mounted mains distribution panel made with 2 mm thick CRCA Sheet with V & F digital meters indoor type Comprising of: Incoming Side 160A, MCCB, 4P, 25kA alongwith copper bus bar mounted on insulators suitable for 415V, 3 Ph, 4 wire, 50 Hz, 200A, 8" Long. Outgoing Side 1. 100A, MCCB, 4 P, 25 kA (for 60 kVA/208V SFC) 2. 16A, TPN,MCB, 10 kA (for 3 kVA/36V, 1 Ph, SFC) 3. 32A, TPN,MCB, 10 kA, (for 10 kVA DCPS) 4. 40A TPN, MCB, 10 kA (for 20 kVA Stab.)
S&F of wall/floor mounted output distribution panel made with 2mm thick CRCA Sheet with V & F digital meters for all outputs indoor type for Second Floor (Right Side) Technical Hanger Comprising of Incoming Side : 1. 200A, MCCB, 4P, 25 kA (for 60 kVA, 208V SFC) 2. 80A, DP, MCB, 10 kA (for 3 kVA, 36V/IPh SFC) 3. 200A, MCCB, 4P, 25 kA (for 27V DC) 4. 42A, TPN, MCB, 10 kA (for 415V, 3 Ph, Stab.) Outgoing side : 1. Copper bus bar mounted on insulators suitable for 200A, 208V, 3Ph, 4 wire, 400 Hz, 10" Long. 2. Copper bus bar mounted on insulators suitable for 36V, 1 Ph, 2 wire, 50 H z, 100A, 10" long. 3. Copper bus mounted on insulators suitable for 200A, 27V, 2 wire, DC, 10" long. 4. Copper bus bar mounted on insulators suitable for 415V, 3 phase 4 wire, 50 Hz, 50A, 10" Long.
S&F of panel for Emergency escape facility room I & II (Second floor, Right Side of Technical Hanger) 1. Copper Bus Bar Mounted on insulators suitable for 27V DC, 2 wire, 60A, 6" long. 2. Copper Bus Bar Mounted on insulators suitable for 36V, 1 Ph, 2 wire, 60 A, 50 Hz, 6 "long.
S&F of wall/table mounted supply box made with 2 mm thick CRCA Sheet for Emergency Escape facility rooms I & II (Second Floor right side of Technical Hanger) comprising of 1. 16A,DP, MCB, 10 kA along with 15Ax 1No. Plug & Socket. 2. 16A,DP, MCB, 10 kA along with 16A, 3 Pin Industrial Type Male-Female connector.
S&F of wall/Table mounted supply box made with 2 mm thick CRCA Sheet for ZHUK-ME Test Restoration LCS work station 1. 50A, TPN, MCB, 10 kA with 63A, 5 Pin Industrial Type Male-Female connector 2. 32A, DP MCB, 10 kA with 32A, 3 Pin Industrial Type Male-Female Connector.
S&F of wall /Table mounted supply box made out of 2 mm thick CRCA Sheet for ZHUK-ME Test Restoration ERP-2, Work Station 1. 40A, TPN, MCB, 10 kA with 63A, 5 Pin Industrial Type Male-Female Connector. 2. 40A DP, MCB, 10 kA with industrial type 3 Pin, Male-Female connector 3. 32A DP, 10 kA with 10Ax3 No's Socket.
S&F of wall/Table mounted supply box made out of 2 mm thick CRCA Sheet for ZHUK-ME Test restoration Comprising of : 1. 32A, DP, MCB, 10 KA, alongwith 5A x 5 No. & 15A x 5 No. Sockets. 2. 32A TPN MCB, 10 KA alongwith 16A, 5 Pin Industrial Type Male Female Sockets- 2 No.s and 5A Sockets, 2 No's 3. 10A DP, MCB, 10KA alongwith 5A x 2 No. Sockets.
S&F of wall/table mounted supply box made out of 2 mm thick CRCA Sheet for ZHUK-ME Test Restoration MPR 1&5 Work Station Comprising of 1. 32A, DP, MCB, 10 kA, alongwith 5A x 5 No. & 15A x 5 No.Sockets. 2. 26A, TPN, MCB, 10 kA alongwith 32A, 5 Pin Industrial type Male Female Connector. 3. 10A, DP, MCB, 10 kA alongwith 5A x 2 No. Sockets.
S&F of wall/Table mounted supply box made with 2 mm thick CRCA Sheet for ZHUK-ME Test Restoration MPR 2 & 4 Work Station comprising of: 1. 32A, DP, MCB, 10 kA alongwith 5A x 5 No. & 15A x 5 No. Sockets. 2. 10A, DP, MCB, 10 kA alongwith 5A x 2 No. Sockets.
S&F of wall mounted mains distribution panel made with 2 mm thick CRCA Sheet with V & F digital meters Comprising of Incoming Side 100A, 4 P, MCCB, 25 kA, alongwith Copper bus bar mounted on insulators suitable for 415V, 3 Ph,4 wire, 50 Hz, 150A. Outgoing side 1. 16A,TPN, MCB, 10 kA (for 8 kVA/115V SFC) 2. 10A, DP, MCB, 10 kA (for 1 kVA/36V, 1 phase SFC) 3. 32A, TPN, MCB, 10 kA (for 27VDC) 4. 40A, TPN, MCB, 10 kA (for 20 kVA Stab).
S&F wall mounted output distribution Panel made with 2 mm thick CRCA Sheet with V & F meters for all outputs Comprising of 1. 80A, DP, MCB, 10 kA alongwith copper bus bar mounted on insulators suitable for 100A, 115V, 1 Ph, 2 wire, 400 Hz, 1 ft long. 2. 32A, DP, MCB, 10kA, alongwith copper bus bar mounted on insulators suitable for 32A, 36, V, 2 wire 50 Hz, 1 ft. long. 3. 200A, 4 P, MCCB, 25kA alongwith copper bus bar mounted on insulators suitable for 400A, 27V, 2 wire, DC, 1 ft. long. 4. 32A, TPN, MCB, 10kA alongwith Copper bus bar mounted on insulators suitable for 40A, 415V, 4 wire, 3 Ph, 50 Hz, 1 ft long .
S&F wall mounted table supply box made with 2 mm thick CRCA Sheet comprising of 1. 40A, DP, MCB, 10 kA alongwith 16A, 3 Pin Industrial tpe Male Female Connector, 2x15A, Sockets & 2x5A Sockets. 2.40A, DP, MCB, 10 kA alongwith 16A, 3 Pin Industrial Type Male-Female Connector 3. 40A, DP,MCB, 10 kA alongwith 32A, 3 Pin Industrial Type male-Female connector.
S&F of wall mounted mains distribution panel Indoor type made out of 2 mm thick CRCA Sheet with V & F digital meters comprising of. Incoming side : 160A, MCCB, 4 P, 25kA, alongwith copper bus bar mounted on insulators suitable for 415V AC, 4 wire 3 Ph, 50 Hz. 200A, 1 ft. long. Outgoing side : 1. 42A, TPN, MCB, 10 kA (for 115V SFC) 2. 6A, TPN, MCB, 10 kA (for 36V/3Ph SFC) 3. 16A, TPN, MCB, 10 kA (for 36/1Ph SFC) 4. 63A, TPN, MCB, 10 kA (for 27DVC) 5. 42A, TPN, MCB, 10 kA (for 220V Stab.) 6. 10A, DP, MCB, 10 kA (for 36/1Ph,400 Hz, SFC)
S&F wall mounted output distribution panel, indoor type made with 2mm thick CRCA sheet with V & F digital meters for all outputs Comprising of : 1. 125A, MCCB, 4P, 25kA alongwith Copper bus bar mounted on insulators suitable for 115V, 1 Ph, 2 wire, 400 Hz, 250A, 8" long. 2. 32A, TPN, MCB, 10 kA alongwith Copper bus bar mounted on insulators suitable for 36V, 3 Ph, 4 wire, 400 Hz, 40A, 8" long. 3. 100A, MCCB, 4P, 25kA alongwith Copper bus bar mounted on insulators suitable for 26V, 1 Ph, 2 wire, 50 Hz 200A, 8" long. 4. 630A, MCCB, 4P, 35kA alongwith copper bus bar mounted on insulators suitable for 27V, 2 wire, DC, 1400A, 12" long. 5. 32A, TPN, MCB, 10 kA alongwith Copper bus bar Mounted an insulators suitable for 415V, 3 Ph, 4 wire, 50 Hz, 40A 8" long. 6. 26A, DP, MCB, 10kA alongwith copper bus bar mounted on insulators suitable for 36V, 1Ph, 2 wire, 400 Hz, 30A, 8" long.
S&F of wall/table mounted supply box made out of CRCA sheet comprising of: 1. 6A, DP, MCB, 10 kA with 5A x 2 No. Sockets 2. 32A,DP, MCB, 10 kA with 32A, 3 Pin, industrial type male Female connectors 3. 32A, DP, MCB 10 kA with 10A x 4 No's sockets.
S&F of wall/Table mounted supply box, indoor type comprising of: 1. 10A, DP, MCB, 10KA alongwith 5A, x 2 No. Sockets. 2. 6A,DP, MCB, 10KA alongwith 5A, Socket 3. 16A, D,P MCB, 10KA alongwith 15A, Socket. 4. 16A, DP, MCB, 10 KA alongwith Industrial type 16A, 3 Pin Male Female
S&F of wall/table mounted supply box, indoor type comprising of : 1. 10A, DP, MCB, 10 kA alongwith 5A x2No. Sockets. 2. 6A, DP, MCB, 10 kA alongwith 5A Socket. 3. 32A, DP, MCB, 10 kA alongwith Industrial Type 32A, 3 Pin Male Female Connector.
Blank
S&F of wall/Table mounted supply box, indoor type 1. 10A, DP, MCB, 10kA alongwith 5A x 2 No. Sockets. 2. 6A, DP, MCB, 10 kA alongwith 5A Socket. 3. 16A,DP, MCB, 10kA alongwith Industrial type Male-Female 16A, 3 Pin Connector. 4. 16A,DP, MCB, 10kA alongwith 15A Socket. 5. 16A TPN, MCB, 10 kA alongwith 15A Socket.
S&F of panel made out of CRCA sheet comprising of: 1. Copper Bus Bar Mounted on insulators suitable for 27V DC, 2 wire, 250A, 6" Long. 2. Copper Bus Bar Mounted on insulators suitable for 208V, 3 Ph, 4 wire, 170 A, 50 Hz, 6" long. 3. Copper bus bar mounted on insulators suitable for 150A, 220V, 1Ph, 2 wire, 50Hz, 6" long
S&F panel made out of CRCA sheet comprising of: 1. Copper Bus Bar Mounted on insulators suitable for 27V DC, 2 wire, 60A, 6" Long. 2. Copper Bus Bar Mounted on insulators suitable for 36V, 1Ph, 2 wire, 60 A, 50 Hz, 6" long. 3. Copper bus bar mounted on insulators suitable for 80A, 220V, 1Ph, 2 wire, 50Hz, 6" long
S&F of Bus bar Panel made out of 2mm thick CRCA Sheet indoor type for Second Floor, Left side, Technical hanger comprising of : 1.Copper bus Bar mounted on insulator suitable for 300A, 2 wire, 27VDC, 6" long. 2. Copper bus bar Mounted on insulator suitable for 60A, 2wire 115V, 400 Hz, 6" long. 3. Copper bus bar Mounted on insulator suitable for 100A, 2 wire, 220 V, 50 Hz 6" long. 4.Copper bus bar Mounted on insulater suitable for 30A, 4 wire, 3 Ph, 36V, 400 Hz 6" long. 5. Copper bus bar Mounted on insulator suitable for 120A, 2 wire, 1 Ph, 36V AC, 6" long. 6. Copper bus bar mounted on insulator suitable for 30A, 36V, 1Ph, 2 wire, 400Hz, 6" long.
S&F of Bus bar Panel made out of 2mm thick CRCA Sheet indoor type for Second Floor, Left side, Technical hanger comprising of : 1.Copper bus Bar mounted on insulator suitable for 300A, 2 wire, 27VDC, 6" long. 2. Copper bus bar Mounted on insulator suitable for 60A, 2wire 115V, 400 Hz, 6" long. 3. Copper bus bar Mounted on insulator suitable for 100A, 2 wire, 220 V, 50 Hz 6" long. 4. Copper bus bar Mounted on insulator suitable for 120A, 2 wire, 1 Ph, 36V AC, 6" long. Note : For BOQ Srl item Nos 271 to 408 being a Special Power Supply items following makes shall only be followed and should not be clubbed with the general makes given in PS :- Static Frequency Converter, Voltage Converter, AC and DC Power Supply : Protech Services/Merlin Hawk/Electronika AXA/AE/ Numax/ Liveline/Aplab Switchgear/MCB : Legrand/ABB/Schneider/L&T/Siemens/ Mitsubishi Meter & Panel : AE/ Protech Services/ Merlin Hawk/ Schneider/ L&T/ Mitsubishi/ Siemens UPS : Numero Uno/ Eaton/ Riello/ Toshiba/ APC/ V Guard/ Schneider
Supply, Install, testing and commissioning of single Core flexible copper cable of size 2.5 Sq mm complete all as specified & directed.
Supply, Install, testing and commissioning of single Core flexible copper cable of size 4.0 Sq mm complete all as specified & directed.
Supply, Install, testing and commissioning of flexible copper cable of size 6.0 Sq mm complete all as specified & directed.
Supply, Install, testing and commissioning of single Core flexible copper cable of size 10.0 Sq mm complete all as specified & directed.
Supply, Install, testing and commissioning of single Core flexible copper cable of size 16 Sq mm complete all as specified & directed.
Supply, Install, testing and commissioning of single Core flexible copper cable of size 25 Sq mm complete all as specified & directed.
Supply, Install, testing and commissioning of single Core flexible copper cable of size 35 Sq mm complete all as specified & directed.
Supply, Install, testing and commissioning of single Core flexible copper cable of size 50 Sq mm complete all as specified & directed.
Supply, Install, testing and commissioning of single Core flexible copper cable of size 70 Sq mm complete all as specified & directed.
Supply, Install, testing and commissioning of single Core flexible copper cable of size 95 Sq mm complete all as specified & directed.
Supply, Install, testing and commissioning of single Core flexible copper cable of size 120 Sq mm complete all as specified & directed.
Supply, Install, testing and commissioning of single Core flexible copper cable of size 150 Sq mm complete all as specified & directed.
Supply, Install, testing and commissioning of single Core flexible copper cable of size 185 Sq mm complete all as specified & directed.
Supply, Install, testing and commissioning of single Core flexible copper cable of size 240 Sq mm complete all as specified & directed.
Supply, Install, testing and commissioning of single Core flexible copper cable of size 300 Sq mm complete all as specified & directed.
Supply, Install, testing and commissioning of single Core flexible copper cable of size 400 Sq mm complete all as specified & directed.
S&F of PVC slotted cable trays of 100x100mm to accommodate the cables as per site requirement including support, nuts, bolts, washers etc complete as directed.
S&F of PVC slotted cable trays of 75x75mm to accommodate the cables as per site requirement including support, nuts, bolts, washers etc complete as directed.
Supply, Install 240 Sq.mm Single Core Rubberised, unarmoured flexible copper cable (for Output of 40 kW "O" Level & "I" Level, 2 strands of 35 m each)
Supply, Installation 185 Sq. mm Single Core Rubberised, unarmoured flexible copper cable (for Output of 90kVA "O" Level & "I" Level, 4 strands of 35 metre each)
Supply, Install 25 Sq. mm Single Core Rubberised, unarmoured flexible copper cable of (for Output of 45 kVA (63A), Maintenance Hanger F1, F2, Technical Hanger & Hawk Hanger 4 strands of 30 m each x 4 outlets in each hanger x 4 Hangers )
Supply & Install 25 Sq. mm Single Core Rubberised, unarmoured flexible copper cable of (for Output of 27V DC (30A), 2 strands of 30 m each x 2 outlets in each hanger x 4 Hangers ) complete all as specified and directed.
Supply & Install 240 Sqmm Single Core Rubberised, unarmoured flexible copper cable of (for Output of 27V DC (12kW) 2 strands of 30 m each x 9 No.) complete all as specified and directed.
S&F NATO Connector for 27V DC complete all as specified and directed.
S&F NATO Connector for 208V, 3Ph, 400Hz complete all as specified and directed.
ACOUSTIC WORK
S&F in position Acoustical wall panelling at upper reach above 5ft to all heights with eco friendly light weight calcium silicate fully perforated acoustical wall panels/ tiles of size 595x595mm fixed to 50mm width vertical stud framing, eco friendly light weight calcium silicate wall panels/tiles shall be made of non-cementitious hydrated wet moulded calcium silicate slurry, reinforced with fibres and natural fillers, Free from formaldehyde and other harmful materials, does not contain any toxic ingredients, wall panels/ tiles shall be GRIHA accredited product suitable for green building applications complete all as specified and directed.
Supply and Install Modular fluted acoustic wall panel using Wooden Perforated Slats made of pine/Eucalyptus wood core E1 grade fibreboard with melamine/ veneer/ laminated finish, the surface is maintained for Acoustics by groove perforated slats pattern L16-3/L23-3/L32-3 - (3mm grooves @16/23/32mm pitch with 27% open area), the edges of the panels shall be “tongue-and-grooved” to receive special clips for installation. the back of the perforated panel shall have Sound absorbing non-woven acoustical fleece of 0.27 mm thick, surface density 64g/m2, the panels shall be mounted on special Aluminium keel cross channel using clips, tongue-groove edge for a seamless look, Fire retardant grade, size 128/192 x2440x16mm, volume density of base board 700Kg/m3, weight 9Kg/m2 installed by using Sal wood framework system. Sal wood framework system shall be done by using wooden battens of size 30x50mm and length of 3000mm is fastened to the wall positioned both sides horizontally & vertically at every 600mm centre to centre. Synth PF 30mm thickness 1000 GSM to be filled in side the Sal wood framing for acoustical support. Aluminium core cross channel CC18, thickness 0.5mm, length 2400mm, web 15mm & 27mm, depth 18mm and flanges of 7mm with suitable edge & centre brackets is then fixed perpendicular to the Sal wood frame with the help of fasteners at every 400mm centres/as preferred by the manufacturer. Perforated Wooden SLATS of customized colour as per architect/Engineer choice (128/192)x2440x16mm to be then fixed perpendicular to Aluminium cross channel CC18 with suitable edge & centre brackets. Contractor to provide expansion joints gap of 3mm at every 4.88m length wise and 4.992m width wise.
Technical Parameters • Fire (Class) - 1 & P • Acoustics NRC =0.75 •Climate (°C, RH) - 50, 70 • Light reflectance (%) - Color Based • Green (VOC, RC %) - El, 25 Note: Wooden perforated SLATS panels will be customized as per design intent & Shop drawing needs to be submitted based on concept design intent before execution of work
S&F eco-friendly light weight calcium silicate acoustical false ceiling tiles in module size of 600x600mm GI powder coated 24mm T grid system, eco friendly light weight calcium silicate tiles shall be made of non-cementitious hydrated wet moulded calcium silicate slurry, reinforced with fibres and natural fillers, free from formaldehyde and other harmful materials, does not contain any toxic ingredients, tiles shall be GRIHA accredited product suitable for green building applications complete all as specified and as directed.
S&F Acoustic Doors Acoustic Door Timber Frame: The door frame profile is 125x150mm of TRIPLE REBATE, rebated shall be constructed out of treated “Engineered Hardwood/ Teak Wood”, the frame shall be provided with acoustical seal ‘Lorient’ brand Batwing 1212 (LAS-1212) on vertical and top sides. The frame shall be provided with (Lorient LP 1004) fire and smoke intumescent seal of size 10x4 mm - 2 Nos. The frame shall be fixed to the wall made up of AAC block/RCC with adequate numbers of counter sunk M10x140 Gl "anchor fasteners of approved Make on each vertical side on top horizontal member. The frames are provided with a label indicating the Sound Transmission Classification rating (STC). The Door frame shall be finished with Polish / Paint/ Wrapping of Laminate or Veneer or Unfinished to match with door shutter, as per Client's requirement complete all as specified and as directed.
S&F Sliding window make Salamander window system GmbH - Germany, 3 track - 2 Glass and 1 mesh with DGU glass and EPDM gasket sealing 6 mm toughened glass + 10 mm air gap with Argon gas + 5 mm toughened glass total 21 mm DGU Glass and STC of 30 dB, Polyvinyl Chloride un plasticized (PVC-U) white colour, Type of opening Sliding; Opening direction Sash left before sash right with all related window accessories, with Operating forces according to EN 13115:2001-07 Class: 1, Air permeability according to EN 12207:2016-12 Class - 4, Resistance to wind load according to EN 12210:2016-03 Class: C1/B3 and Water tightness according to EN 12208:1999-11 Class: 7A complete all as specified and as directed.
INTERNAL ELECTRIFICATION
M&L earthing complete with galvanised steel earth plate electrode 600x600x6 mm thick burried directly in ground [earth pit not less than 2.25 m deep below ground level] with top edge of Plate not less than 1.50 m below normal ground level connected to GI earth lead wire 4.0 mm dia (earth lead) and GI pipe 15 mm, light grade for earthing lead protection to the extent of maximum 7.5m, earth plate electrode surrounded by 150 mm thick packed layers of charcoal and common salt filled in alternate layers, connected to the plate by means of GI Bolts & Nuts complete all as per electrical plate No. 3 of SSR Part – I, connected to panel / DB including testing on completion including main earthing, charcoal, common Salt, PCC (1:2:4, Type B1) Pit with RCC 1:2:4, type B1 Cover, 50 mm thick with 6 Nos, 8 mm dia TMT bars in both ways, MS frame made with 40x40x6 mm angle Iron, MS Funnel with 20 mm bore, medium grade GI Watering pipe, wire mesh, earth work excavation, return filling, removal of surplus soil etc. complete all as specified. Note: GI earth wire upto 7.5 m shall be deemed to be included in the quoted lumpsum and beyond 7.5 m shall be measured and paid separately
M&L for Point wiring with two runs of 1.5 Sq.mm. FRLS PVC insulated unsheathed copper conductor multi stranded 1100 Volts grade, ISI marking drawn through and including non metallic PVC rigid concealed conduit and conduit accessories medium grade, ISI marked, including modular metal flush box with and including modular white cover plate with frame for mounting modular switches/sockets/fan regulators etc. including one run of 1.5 Sq.mm. PVC insulated unsheathed copper cable for earth continuity, connected to earth dolly, for One light/bell point controlled by one no. one way switch or One fan (ceiling fan/exhaust fan/wall mounted) point controlled by one switch or one 3 pin socket outlet 5 Amps on independent board on independent board complete all as specified and as directed.
All as per Sl Item No. 443 above but for one 3 pin socket outlet 15 Amps on independent board with two runs of 4 Sq.mm. FRLS PVC wire and one run of 4 Sq.mm. copper cable for earth continuity.
M&L for Point Wiring complete with 1100 Volts, FRLS Grade, 1.5 Sq.mm, Single Core, PVC Insulated, Unsheathed, Multi-stranded Copper Conductor Cable, confirming to IS - 694 drawn through and including heavy duty PVC Conduit, 20 mm dia including all accessories concealed in Walls / Roofs / Floors / Ceiling etc. and Pressed Metal Flush Box made out of 2mm thick MS Sheet of suitable size and 3 mm thick Hylam Sheet top cover for fixing switches, fittings, regulators etc concealed in walls, including 1100 Volts, FRLS Grade, 1.5 Sq.mm, Single Core, PVC Insulated, Unsheathed, Multi-stranded Copper Conductor cable as earth continuity conductor with colour coding and connecting to Earth Dolly for One Light / Fan Point / Bell Point controlled by One Switch complete all as specified.
All as per Item No. 445 above but One 3 Pin Switch Socket Outlet 5 Amps on Independent Board complete all as specified.
All as per Serial Item No. 445 above but one 3 Pin Switch Socket Outlet 6 Amps on independent board, with 1100 Volts, FRLS grade, 2.5 Sq.mm, Single Core, PVC Insulated, Unsheathed, Multi-stranded Copper Conductor Cable confirming to IS - 694 and including 1100 Volts, FRLS grade, 2.5 Sq.mm, Single Core, PVC Insulated, unsheathed, Multi-stranded Copper Conductor Cable as Earth Continuity Conductor.
All as per Serial Item No. 445 above but one 3 Pin Switch Socket Outlet 16 Amps on independent board, with 1100 Volts, FRLS grade, 4.0 Sq.mm, Single Core, PVC Insulated, Unsheathed, Multi-stranded Copper Conductor Cable confirming to IS - 694 and including 1100 Volts, FRLS grade, 4.0 Sq.mm, Single Core, PVC Insulated, Unsheathed, Multi-stranded Copper Conductor Cable as Earth Continuity Conductor.
M&L for Sub main wiring with 2 runs of single core 1.5 Sq.mm Single Core, PVC Insulated, Unsheathed, Multi-stranded Copper Conductor cable, 1100 Volts, FRLS Grade, ISI Marked, drawing through and including heavy duty PVC Conduit, 20 mm dia with all accessories concealed in Walls / Roofs / Floors / Ceiling etc. including One run of 1.5 Sq.mm, Single Core, PVC Insulated, Unsheathed, Multi-stranded Copper Conductor cable, 1100 Volts, FRLS Grade earth continuity conductor complete all as specified. Note: 3 runs of 1.5 Sq.mm & one run of 20mm dia PVC Conduit will be measured as one unit.
M&L for Sub main wiring with 2 runs of single core 2.5 Sq.mm Single Core, PVC Insulated, Unsheathed, Multi-stranded Copper Conductor cable, 1100 Volts, FRLS Grade, ISI Marked, drawing through and including heavy duty PVC Conduit, 20 mm dia with all accessories concealed in Walls / Roofs / Floors / Ceiling etc. including One run of 2.5 Sq.mm, Single Core, PVC Insulated, Unsheathed, Multi-stranded Copper Conductor cable, 1100 Volts, FRLS Grade earth continuity conductor complete all as specified. Note: 3 runs of 2.5 Sq.mm & one run of 20mm dia PVC Conduit will be measured as one unit.
M&L Sub main wiring with 2 runs of single core 4.0 Sq.mm Single Core, PVC Insulated, Unsheathed, Multi-stranded Copper Conductor cable, 1100 Volts, FRLS Grade, ISI Marked, drawing through and including heavy duty PVC Conduit, 20 mm dia with all accessories concealed in Walls / Roofs / Floors / Ceiling etc. including One run of 4.0 Sq.mm, Single Core, PVC Insulated, Unsheathed, Multi-stranded Copper Conductor cable, 1100 Volts, FRLS Grade earth continuity conductor complete all as specified. Note: 3 runs of 4.0 Sq.mm & one run of 20mm dia PVC Conduit will be measured as one unit.
M&L for Sub main wiring with 2 runs of single core 6.0 Sq.mm Single Core, PVC Insulated, Unsheathed, Multi-stranded Copper Conductor cable, 1100 Volts, FRLS Grade, ISI Marked, drawing through and including heavy duty PVC Conduit, 20 mm dia with all accessories concealed in Walls / Roofs / Floors / Ceiling etc. including One run of 6.0 Sq.mm, Single Core, PVC Insulated, Unsheathed, Multi-stranded Copper Conductor cable, 1100 Volts, FRLS Grade earth continuity conductor complete all as specified. [Note: 3 runs of 6.0 Sq.mm & one run of 20mm dia PVC Conduit will be measured as one unit]
S&F energy efficient LED tube light fitting (mirror optic) with tube 2x20 Watts, 240 Volts, 50 Hz, luminous efficiency 100 Lumen per Watt, CRI>80, PF>0.9, surface mounted, decorative ultra slim square profile LED lighting fixture etc., with extruded polycarbonate environmental friendly, energy efficient ready to use pack complete with mounting bracket etc., including connecting up with 1.0 Sq.mm, 3 core flexible copper conductor complete all as specified and as directed.
S&F energy efficient LED tube light fitting (mirror optic) with tube 20 Watts, 240 Volts, 50 Hz, luminous efficiency 100 Lumen per Watt, CRI>80, PF>0.9, surface mounted, decorative ultra slim square profile LED lighting fixture etc., with extruded polycarbonate environmental friendly, energy efficient ready to use pack complete with mounting bracket etc., including connecting up with 1.0 Sq.mm, 3 core flexible copper conductor complete all as specified and as directed.
S&F of ceiling fan complete with blades, down rod and other accessories, AC 230 Volts, 1200 mm sweep, min air delivery 210 CFM with service value 6.00, BEE, 5 star rated with brushless direct current motor (BLDC) including connecting with 1.0 Sqmm, 2 core copper conductor from ceiling rose complete all as specified and as directed.
S&F exhaust fan, 300 mm sweep, made out of sturdy engineering plastic, 1200 RPM heavy duty with louvers, AC single phase, 230 Volts , connection with 1.0 sqmm twin core copper conductor flexible wire from ceiling rose including making necessary opening and making good the disturbed surface complete all as specified and as directed.
S&F telephone socket (JACK TYPE) RJ 11 with modular cover plate complete with all accessories complete all as specified and directed.
S&F internet socket (JACK TYPE) RJ 45 with modular cover plate complete with all accessories complete all as specified and directed.
S&F 30 W LED flame proof well glass fitting in die cast alu housing with heat resistant toughened glass, made of aluminium alloy, LMG, CIMFR certified, recommended for gas/ vapour group of IIM & IIB and Zone 1 & 2 IP 65 protected complete with all accessories prewired including connecting up with twin core twisted flexible copper conductor of suitable size complete all as specified and as directed.
S&F energy efficient LED Porch light fitting with 24 Watt LED down light including all holding mechanism in floor/ wall, 240 Volts, 50 Hz, luminous efficiency 100 Lumen per Watt, CRI>80, PF>0.9, surface mounted, decorative ultra slim square profile LED lighting fixture etc., with extruded polycarbonate environmental friendly, energy efficient ready to use pack complete with mounting bracket etc., including connecting up with 1.0 Sq.mm, 3 core flexible copper conductor complete all as specified and as directed.
S&F building security light fitting 36 Watt , luminous efficiency 100 Lumen per Watt, CRI>80, PF>0.9, new generation energy saving & environmental friendly long life, made up of pressure die cast aluminium housing with high efficient LED as lighting source and PC cover having top opening separate driver compartment with IP66 protection pre-wired and connecting up with 1.0 Sqmm copper conductor cable upto connector including 1.5m long GI tubing light grade bracket of 32 mm dia bend to shape for fixing on wall/ pole with suitable MS bracket nuts, bolts etc., complete all as specified and directed.
S&F energy efficient LED suspended light fitting (high bay light) with 90 Watt LED including all holding mechanism, 240 Volts, 50 Hz, luminous efficiency 120 Lumen per Watt, CRI>80, PF>0.9, surface mounted, IP 54 decorative ultra slim square profile LED lighting fixture etc., complete with mounting bracket etc., including connecting up with 1.5 Sq.mm, 3 core flexible copper conductor complete all as specified and as directed.
S&F energy efficient LED suspended light fitting (mirror optic) with 210 Watts, pendant, LED light including all holding mechanism in floor/ wall, 240 Volts, 50 Hz, luminous efficiency 100 Lumen per Watt, CRI>80, PF>0.9, surface mounted, decorative ultra slim square profile LED lighting fixture etc., with extruded polycarbonate environmental friendly, energy efficient ready to use pack complete with mounting bracket etc., including connecting up with 1.0 Sq.mm, 3 core flexible copper conductor complete all as specified and as directed.
S&F energy efficient LED recess mount light fitting 10 Watts, LED down light including all holding mechanism in floor/ wall, 240 Volts, 50 Hz, luminous efficiency 100 Lumen per Watt, CRI>80, PF>0.9, surface mounted, decorative ultra slim square profile LED lighting fixture etc., with extruded polycarbonate environmental friendly, energy efficient ready to use pack complete with mounting bracket etc., including connecting up with 1.0 Sq.mm, 3 core flexible copper conductor complete all as specified and as directed.
S&F energy efficient LED recess mount light fitting 10 Watts, LED mirror light including all holding mechanism in floor/ wall, 240 Volts, 50 Hz, luminous efficiency 100 Lumen per Watt, CRI>80, PF>0.9, surface mounted, decorative ultra slim square profile LED lighting fixture etc., with extruded polycarbonate environmental friendly, energy efficient ready to use pack complete with mounting bracket etc., including connecting up with 1.0 Sq.mm, 3 core flexible copper conductor complete all as specified and as directed.
S&F energy efficient LED recess mount light fitting 20 Watts, LED down light including all holding mechanism in floor/ wall, 240 Volts, 50 Hz, luminous efficiency 100 Lumen per Watt, CRI>80, PF>0.9, surface mounted, decorative ultra slim square profile LED lighting fixture etc., with extruded polycarbonate environmental friendly, energy efficient ready to use pack complete with mounting bracket etc., including connecting up with 1.0 Sq.mm, 3 core flexible copper conductor complete all as specified and as directed.
S&F MCB DB, double door, SPN, 12 way, sheet steel, with 200 Amps rated bus bar, 240 Volts, 50 Hz, IP : 43 protection, concealed in walls, complete all as specified and as directed.
S&F MCB DB, double door, SPN, 8 way, sheet steel, with 200 Amps rated bus bar, 240 Volts, 50 Hz, IP : 43 protection, concealed in walls, complete all as specified and as directed.
S&F MCB DB, double door, SPN, 4 way, sheet steel, 415 Volts, 50 Hz, IP : 43 protection, including provision for fixing MCCB 4 Pole as incomer and outgoing circuit MCB SP/TP complete fill empty way with blanking plates complete all as specified and as directed.
S&F MCB DB, double door, TPN, 4 way, sheet steel, 415 Volts, 50 Hz, IP : 43 protection, including provision for fixing MCB 4 Pole as incomer and outgoing circuit MCB SP/TP complete fill empty way with blanking plates complete all as specified and as directed.
S&F MCCB DB, double door, VTPN, 4 way, sheet steel, 415 Volts, 50 Hz, IP: 43 protection, including provision for fixing MCCB 4 Pole as incomer and outgoing circuit MCB SP/TP complete fill empty way with blanking plates complete all as specified and as directed.
Schedule 'A' Part-XVI: Outsourcing Services for Operation of Lifts (06 Nos) and Central AC plants (3x120 TR-01 No., 3x60 TR-02 Nos, 3x45 TR-01 No.) for the First Year of the three year Defect Liability Period:
Outsourcing of services for operation of Goods lifts (6 Nos.) of capacity 2000 kg any type and make to serve G+2 floors, during First Year of the three years Defect Liability Period by providing services of Six Lift Operators (Semi Skilled) per Shift of 08 hrs duration on all working days including taking care of from any pilferage, theft or damage etc. to ensure smooth and trouble free operation of lifts to the entire satisfaction of users/department including attending telephonic complaints, maintaining necessary records and documents etc. complete all as specified and as directed by the Engineer-in-Charge. (Qty Details: 6 Nos x 12 months x 25 days/shifts=1800 shifts).
Outsourcing of services for operation of Central AC Plants (4 Nos.) of capacity (3x120 TR-01 No., 3x60 TR-02 Nos, 3x45 TR-01 No.) including cooling towers, AHUs, Electric control panels, Pumps and connected equipment in complete AC system per Shift of 08 hrs duration on all working days during 1st year of three years defects liability period by providing service services of four skilled trades man of AC and refrigeration mechanic (ITI Qualified) with 02 to 03 yrs relevant experience including taking care from any pilferage, theft or damage etc to ensure smooth and trouble free operation of AC plant to the entire satisfaction of users/department including maintaining necessary records and documents etc. complete all as specified and as directed by the Engineer-in-Charge. (Qty Details: 4 Nos x 12 months x 25 days/shifts= 1200 shifts).
Schedule 'A' Part-XVII: Outsourcing Services for Operation of Lifts (06 Nos) and Central AC plants (3x120 TR-01 No., 3x60 TR-02 Nos, 3x45 TR-01 No.) for the Second Year of the three year Defect Liability Period:
Outsourcing of services for operation of Goods lifts (6 Nos.) of capacity 2000 kg any type and make to serve G+2 floors, during Second Year of the three years Defect Liability Period by providing services of Six Lift Operators (Semi Skilled) per Shift of 08 hrs duration on all working days including taking care of from any pilferage, theft or damage etc. to ensure smooth and trouble free operation of lifts to the entire satisfaction of users/department including attending telephonic complaints, maintaining necessary records and documents etc. complete all as specified and as directed by the Engineer-in-Charge. (Qty Details: 6 Nos x 12 months x 25 days/shifts=1800 shifts).
Outsourcing of services for operation of Central AC Plants (4 Nos.) of capacity (3x120 TR-01 No., 3x60 TR-02 Nos, 3x45 TR-01 No.) including cooling towers, AHUs, Electric control panels, Pumps and connected equipment in complete AC system per Shift of 08 hrs duration on all working days during 2nd year of three years defects liability period by providing service services of four skilled trades man of AC and refrigeration mechanic (ITI Qualified) with 02 to 03 yrs relevant experience including taking care from any pilferage, theft or damage etc to ensure smooth and trouble free operation of AC plant to the entire satisfaction of users/department including maintaining necessary records and documents etc. complete all as specified and as directed by the Engineer-in-Charge. (Qty Details: 4 Nos x 12 months x 25 days/shifts= 1200 shifts).
Schedule 'A' Part-XVIII: Outsourcing Services for Operation of Lifts (06 Nos) and Central AC plants (3x120 TR-01 No., 3x60 TR-02 Nos, 3x45 TR-01 No.) for the Third Year of the three year Defect Liability Period:
Outsourcing of services for operation of Goods lifts (6 Nos.) of capacity 2000 kg any type and make to serve G+2 floors, during Third Year of the three years Defect Liability Period by providing services of Six Lift Operators (Semi Skilled) per Shift of 08 hrs duration on all working days including taking care of from any pilferage, theft or damage etc. to ensure smooth and trouble free operation of lifts to the entire satisfaction of users/department including attending telephonic complaints, maintaining necessary records and documents etc. complete all as specified and as directed by the Engineer-in-Charge. (Qty Details: 6 Nos x 12 months x 25 days/shifts=1800 shifts).
Outsourcing of services for operation of Central AC Plants (4 Nos.) of capacity (3x120 TR-01 No., 3x60 TR-02 Nos, 3x45 TR-01 No.) including cooling towers, AHUs, Electric control panels, Pumps and connected equipment in complete AC system per Shift of 08 hrs duration on all working days during 3rd year of three years defects liability period by providing service services of four skilled trades man of AC and refrigeration mechanic (ITI Qualified) with 02 to 03 yrs relevant experience including taking care from any pilferage, theft or damage etc to ensure smooth and trouble free operation of AC plant to the entire satisfaction of users/department including maintaining necessary records and documents etc. complete all as specified and as directed by the Engineer-in-Charge. (Qty Details: 4 Nos x 12 months x 25 days/shifts= 1200 shifts).
Schedule 'A' Part-XIX: Outsourcing Services and Comprehensive maintenance of Lifts (06 Nos) and Central AC plants (3x120 TR-01 No., 3x60 TR-02 Nos, 3x45 TR-01 No.) during First Year after expiry of Defect Liability Period
Outsourcing of services for operation of Goods lifts (6 Nos.) of capacity 2000 kg any type and make to serve G+2 floors, during First Year after expiry of Defect Liability Period by providing services of Six Lift Operators (Semi Skilled) per Shift of 08 hrs duration on all working days including taking care of from any pilferage, theft or damage etc. to ensure smooth and trouble free operation of lifts to the entire satisfaction of users/department including attending telephonic complaints, maintaining necessary records and documents etc. complete all as specified and as directed by the Engineer-in-Charge. (Qty Details: 6 Nos x 12 months x 25 days/shifts=1800 shifts).
Comprehensive maintenance of Goods lifts, 6 Nos., of capacity 2000 kg to serve G+2 floors complete including ARD and all connected components of lift during First Year after expiry of Defect Liability Period complete all as specified and as directed by the Engineer-in-Charge.
Outsourcing of services for operation of Central AC Plants (4 Nos.) of capacity (3x120 TR-01 No., 3x60 TR-02 Nos, 3x45 TR-01 No.) including cooling towers, AHUs, Electric control panels, Pumps and connected equipment in complete AC system per Shift of 08 hrs duration on all working days during First Year after expiry of Defect Liability Period by providing service services of four skilled trades man of AC and refrigeration mechanic (ITI Qualified) with 02 to 03 yrs relevant experience including taking care from any pilferage, theft or damage etc to ensure smooth and trouble free operation of AC plant to the entire satisfaction of users/department including maintaining necessary records and documents etc. complete all as specified and as directed by the Engineer-in-Charge. (Qty Details: 4 Nos x 12 months x 25 days/shifts= 1200 shifts).
Comprehensive maintenance of Central AC Plants (4 Nos.) of capacity (3x120 TR-01 No., 3x60 TR-02 Nos, 3x45 TR-01 No.) and all connected components of AC during First Year after expiry of Defect Liability Period complete all as specified and as directed by the Engineer-in-Charge.
Schedule 'A' Part-XX: Outsourcing Services and Comprehensive maintenance of Lifts (06 Nos) and Central AC plants (3x120 TR-01 No., 3x60 TR-02 Nos, 3x45 TR-01 No.) during 2nd Year after expiry of Defect Liability Period
Outsourcing of services for operation of Goods lifts (6 Nos.) of capacity 2000 kg any type and make to serve G+2 floors, during 2nd Year after expiry of Defect Liability Period by providing services of Six Lift Operators (Semi Skilled) per Shift of 08 hrs duration on all working days including taking care of from any pilferage, theft or damage etc. to ensure smooth and trouble free operation of lifts to the entire satisfaction of users/department including attending telephonic complaints, maintaining necessary records and documents etc. complete all as specified and as directed by the Engineer-in-Charge. (Qty Details: 6 Nos x 12 months x 25 days/shifts=1800 shifts).
Comprehensive maintenance of Goods lifts, 6 Nos., of capacity 2000 kg to serve G+2 floors complete including ARD and all connected components of lift during 2nd Year after expiry of Defect Liability Period complete all as specified and as directed by the Engineer-in-Charge.
Outsourcing of services for operation of Central AC Plants (4 Nos.) of capacity (3x120 TR-01 No., 3x60 TR-02 Nos, 3x45 TR-01 No.) including cooling towers, AHUs, Electric control panels, Pumps and connected equipment in complete AC system per Shift of 08 hrs duration on all working days during 2nd Year after expiry of Defect Liability Period by providing service services of four skilled trades man of AC and refrigeration mechanic (ITI Qualified) with 02 to 03 yrs relevant experience including taking care from any pilferage, theft or damage etc to ensure smooth and trouble free operation of AC plant to the entire satisfaction of users/department including maintaining necessary records and documents etc. complete all as specified and as directed by the Engineer-in-Charge. (Qty Details: 4 Nos x 12 months x 25 days/shifts= 1200 shifts).
Comprehensive maintenance of Central AC Plants (4 Nos.) of capacity (3x120 TR-01 No., 3x60 TR-02 Nos, 3x45 TR-01 No.) and all connected components of AC during 2nd Year after expiry of Defect Liability Period complete all as specified and as directed by the Engineer-in-Charge.
M M SHAWL Engineers and contractors pvt ltd (BID ID -3277185)
NSC Projects Pvt. Ltd. (BID ID -3277554)
Inderjit Mehta Constructions Pvt Ltd (BID ID -3272100)
M. Venkata Rao Infra Projects Pvt. Ltd. (BID ID -3276701)
Som Projects Pvt. Ltd. (BID ID -3277127)
Varindera Constructions Limited (BID ID -3274812)
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.07 MB
Download all tender documents and submit your bid