GE FORT KOCHI
GARRISON ENGINEER MILITARY ENGINEER SERVICES GE FORT KOCHI -682001
REPAIR/ MAINT OF LT PANEL BOARDS, SWITCH GEARS, EARTHINGS AND CONNECTED MISC WORKS ETC AT ELECTRIC SUPPLY INSTALLATION AT INS DRONACHARYA UNDER GE FORT KOCHI
2026_MES_794271_1
8434/E8_GE_FORT_KOCHI
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
FORT KOCHI
Please refer Tender documents.
7 documents required · 7 mandatory
₹500
GE FORT KOCHI
₹27,500
Yes
16 Oct 2026
16 Oct 2026
13 Nov 2026
16 Oct 2026
6 Nov 2026
30 Oct 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Excavation in trenches not exc 1.5m wide and not exc 1.5m deep and making good bottom surface for laying /removing of cable, erection of poles in soft/ loose soil complete, all as specified and as directed. | 108 | Cum | - | - |
| 2 | Material and Labour for removing excavated soil to a distance not exceeding 50 m and not exceeding 1.5 m above the starting point, and depositing where directed complete all as specified and as directed. | 35 | Cum | - | - |
| 3 | Material and Labour for sand cushioning (dry) in trenches/ducts for protection of UG Cables (below, above and around the UG Cable laid) of 23 cm spread thickness (8 cm in depth before laying the cable and 15 cm in depth after laying the Cable) and consolidated (punned) up to 180mm thickness, complete all as specified and as directed.
Note: For the purpose of payment, punned thickness of Sand Cushioning only will be measured. | 32.4 | Cum | - | - |
| 4 | Material and labour for burnt bricks subclass B laid in trenches for cable protection complete, all as specified and as directed. | 3.2 | Per 1000 Nos | - | - |
| 5 | Returning filling in excavated soil in trenches, watering and well ramming in layers not exc 25 cm complete all as specified and as directed. | 73 | Cum | - | - |
| 6 | Taking out unserviceable UG cables of any sizes from trenches/walls including all mounting accessories and GI tubing including making good to disturbed area complete all as specified and as directed | 650 | RM | - | - |
| 7 | Material and Labour for XLPE insulated PVC sheathed armoured with multistranded aluminium conductor cable having cross sectional area 16 sqmm 4 core, 1100-volt grade, Earthed, Heavy grade conforming to IS :7098 (Part 1) laid in trenches/Ducts or passing through pipes or fixing on poles etc. with stranded aluminium conductor of size laid in trenches, ducts etc. complete all as specified and as directed. | 200 | RM | - | - |
| 8 | Material and Labour for XLPE insulated PVC sheathed armoured with multistranded aluminium conductor cable having cross sectional area 25 sqmm 4 core, 1100-volt grade, Earthed, Heavy grade conforming to IS :7098 (Part 2) laid in trenches/Ducts or passing through pipes or fixing on poles etc complete all as specified and directed. with stranded aluminium conductor of size laid in trenches, ducts etc. complete all as specified and as directed. | 150 | RM | - | - |
| 9 | Material and Labour for XLPE insulated PVC sheathed armoured with multistranded aluminium conductor cable having cross sectional area 50 sqmm 3.5 core, 1100-volt grade, Earthed, Heavy grade conforming to IS :7098 (Part 4) laid in trenches/Ducts or passing through pipes or fixing on poles etc complete all as specified and directed. with stranded aluminium conductor of size laid in trenches, ducts etc. complete all as specified and as directed. | 150 | RM | - | - |
| 10 | Material and Labour for XLPE insulated PVC sheathed armoured with multistranded aluminium conductor cable having cross sectional area 70 sqmm 3.5 core, 1100-volt grade, Earthed, Heavy grade conforming to IS :7098 (Part 5) laid in trenches/Ducts or passing through pipes or fixing on poles etc complete all as specified and directed. with stranded aluminium conductor of size laid in trenches, ducts etc. complete all as specified and as directed. | 150 | RM | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.26 MB
BOQ_890802.xls
BOQ • 0.38 MB
8434Tenderdocu.pdf
Tender Documents • 0.96 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .