EXECUTIVE ENGG (P.W.D), D/DINAJPUR ELEC DIVN
OFFICE OF THE EXECUTIVE ENGINEER (P.W.D), DAKSHIN DINAJPUR ELECTRICAL DIVISION, BALURGHAT Dakshin Dinajpur - 733101
Construction Of Meeting hall 300 Capacity at Balurghat Collectorate Compound in the district of Dakshin Dinajpur during the year 2016-17.- SITC of Fire Detection.
2018_WBPWD_165844_1
WBPWD/EE/DDED/e-NIQ-17/2017-18 (2nd Call)
Open Tender
ELECTRICAL WORKS ORG
Item Rate
15 days
Balurghat
Please refer tender documents
5 documents required · 5 mandatory
₹20,000
15 Dec 2020
21 Mar 2018
30 Mar 2018
21 Mar 2018
28 Mar 2018
21 Mar 2018
Amount
Supply, Installation,Testing & Commisioning of EN Standerd, VDS approved Microprocessor based 2Loops fire alarm control panel fully networkable (Vender should provide Network card for panel to panel networking) with each loop capable of taking 125 devices, 1/4 VGA display character alpha-numeric liquid crystal display.The panel shall be soft addressable type. The panel shall be able to give pin point location of all fire/fault conditions. Further, the panel must be able to automatically switch off respective control switches when ever any alarm is triggered. The panel shall have in built rectifier, provision for external & internal printer (if required),Loop cards, LCD unit to indicate Fire/Fault Signal with address and analog output, complete in all respects, having 1000 event memory, integral SMF lead acid batteries with sealed cells of 24 V capable of running for a minimum of 8 hours with integral battery charger complete as required and as per specification following VDS;EN54, with following Number of Loops configaration. (Make:Esser/Secutron/Siemens)
Supply, installation, testing & commissioning of EN Standard, VDS approved Addressable Multi-Sensor Detector (optical smoke as well as heat) with inbuilt / equal number of additional Isolator for each detector and integral LED status indicator with 360 degree viewing angle. Detector shall communicate 3 danger levels for differentiated alarm activation and high tolerance to dust,dirt, temperature fluctuations and air currents. Detector should have unquie address for communication and assigned through panel with Mounting Base as required. (Approved Make : Esser/ Secutron/ Siemens)
Supply, installation, testing & commissioning of EN Standard, VDS approved Intelligent Analog Addressable Heat Detector (Static + ROR) with inbuilt / equal number of additional Isolator for each detector and integral LED status indicator with 360 degree viewing angle. Detector shall communicate 3 danger levels for differentiated alarm activation. Detector should have unquie address for communication and assigned through panel with Mounting Base as required. (Approved Make : Esser/ Secutron/ Siemens)
Supply, installation, testing & commissioning of Beem detector complete with all other accessories. (Approved Make: System Sensor/Ravel)
Supply, installation, testing & commissioning of EN Standard with VDS approved Addressable One input & One output module with inbuilt isolator and shall have the LED indication for Normal, Fault, test, and activation.The module shall have the option for configuration as fail safe operation. (Approved Make: Honeywell/Siemens / Secutorn)
Supply, installation, testing & commissioning of EN Standard, VDS approved Inteliigent addressable manual call point with inbuilt / equal number of additional Isolator for each manual call point suitable for flush or surface mounting, call point shall include test key feature without removing the glass with extra acceesories as required. (Approved Make : Esser/ Secutron/ Siemens)
Supply, Installation, Testing & Commissioning of Addressable Loop Powered Hooter (sound output of minimum 90 db )cum strobe (strength of light 10 cd)complete with inbuilt isolator & IP65 base and as required following VDS;EN54. (Approved Make : Esser/ Secutron/Siemens)
Supply, erection, testing & commissioning of RESPONSE INDICATOR Complete with base, mounting box, gland, lugs, etc. as required completing in all respect. ( (Make:Esser(Honeywell)/Secutron/Siemens)
Supply & Laying of 2 Core 1.5 sq.mm FRLS shielded copper Cable . (Make. Finolex / Havells)
Supply & Fixing of 19 mm PVC conduit complete with all accessories (Make: Precisson-Medium/Prestoplast)
NOTE : 1. The Fire Alarm system shall comply with latest requirements of -- 1. National Fire Protection Association (NFPA) Standards. 2. IS 2189 3. NFPA 70 National Electric Code 4. NFPA 72 National Fire Alarm Code 5. local Statutory Regulations 6. Manufacturer Recommendation.
TESTS:1.The system shall be tested and commissioned by a qualified competent,trained engineer or technician authorized by the manufacturer of the fire alarm equipment to technically supervise and participate during all of the adjustments and tests for the system. 2. Before energizing the cables and wires, check for correct connections and test for short circuits, ground faults, continuity, and insulation and other tests as per above standards must be done.
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .