Loading…
Loading…
Tender ID
Tender Value
₹1.0 Cr
EMD Value
₹1.0 L
Closing Date
16 Mar 2026, 5:00 pmClosed
Executive Engineer, Sachivalay complex Electrical Division, Sector-16, Gandhinagar,
Providing & Erecting Supply cables, switchgears and Panel for Roof top solar system at Vidhansabha,Block 1 to 14 , SS-1 & SS-2 terrece & Parking area of New Sachivalay Dist. Gandhinagar [2ND ATTEMPT
284756
25/01 OF 2025/2026
Open
Electrical
Works
Gandhinagar
10 documents required · 10 mandatory
₹3,600
Yes
Executive Engineer, Sachivalaya Complex Electrical Division, Gandhinagar.
₹1.0 L
Yes
10 Mar 2026
10 Mar 2026
10 Mar 2026
16 Mar 2026
10 Mar 2026
Item No Qty Unit Amount
specifications) Figure
Providing and erecting XLPE(IS:7098)(I)-88 ISI armoured cable multistrand
Aluminium conductor for 1.1 KV. to be laid on wall with necessary clamps or
in existing trench / pipe of following size of cables(D) 3 1/2 core 70 Sq. mm
( 35 Sq. mm 1/2 core) 220 mtr 378.75
(E) 3 1/2 core 95 Sq. mm ( 50 Sq. mm 1/2 core) 510 mtr 490.86
(F) 3 1/2 core 120 Sq. mm ( 70 Sq. mm 1/2 core) 242 mtr 540.35
(G) 3 1/2 core 150 Sq. mm ( 70 Sq. mm 1/2 core) 923 mtr 731.24
(H) 3 1/2 core 185 Sq. mm ( 95 Sq. mm 1/2 core) 470 mtr 904.96
(K) 3 1/2 core 400 Sq.mm ( 185 Sq. mm 1/2 core) 3200 mtr 1747.3
Making trench in soft soil of suitable width of 90 cm deep for laying cable or
2 locating the fault all over the run and back filling the same and making the
surface as normal ground. 910 mtr 55.55
Drilling the road without breaking the road surface (Asphalt) for laying of
3 cable for feeding power supply by making up to following size of holes at both
ends complete.(B) Up to 150 mm bore dia 134 mtr 616.1
Making trench in Hard Murrum / Tar Road of suitable width of 90 cm or
required depth for laying any size of cable or locating the fault all over the
run and back filling the same and making the surface as normal ground. (B) If
additional machinery like hammer driller or JCB use [Add] 160 mtr 432.28
Providing and, fixing heavy duty flange type brass double compression type
cable gland with rubber ring for PVC insulated armoured cable complete with
out going tails, insulating tape etc for following size of cables. (C) 3 & 1/2
core 70 Sq. mm 4 Ea. 103.02
(D) 3 & 1/2 core 95 Sq. mm 8 Ea. 131.3
(E) 3 & 1/2 core 120 Sq. mm 8 Ea. 140.39
(F) 3 & 1/2 core 150 Sq. mm 14 Ea. 190.89
(G) 3 & 1/2 core 185 Sq. mm 8 Ea. 238.36
(J) 3 & 1/2 core 400 Sq. mm 20 Ea. 369.66
Solder less crimping type Aluminium lugs conforming to IS suitable for cable
of following size evenly crimped with high pressure tool & connected to
switchgear terminals with brass/cadmium plated nut bolts in an approved
manner. (D) 35/50 Sq.mm. 20 Ea. 20.2
Providing and erecting Approved make Four pole moulded case circuit
breaker having breaking capacity ICU of 25 KA. at 415 V,having normal
current rating up to 25 A to 100A. with Fixed thermal & magnetic release
suitable to work on A.C. supply 50 c/s. with all internal connections, spreader
tinned copper & complete erected in existing 16 G.M.S. housing.
ICS=100% of ICU only Cat III 1 Ea. 6173.12
Providing and erecting Approved make Four pole moulded case circuit
breaker having breaking capacity ICU of 35 KA. at 415 V. having normal
current rating 125A. with Fixed thermal & magnetic release suitable to work
on A.C.supply 50 c/s. with all internal connections, spreader tinned copper &
complete erected in existing 16 G.M.S. housing. ICS=100% of ICU only
Cat III 5 Ea. 8055.76
Providing and erecting Approved make Four pole moulded case circuit
breaker having breaking capacity ICU of 35 KA. at 415 V. having Normal
current rating 200A.with variable Thermal & magnetic release suitable to
work on A.C.supply 50 c/s. with all internal connections, spreader tinned
copper & complete erected in existing 16 G.M.S.housing ICS=100% of
ICU only Cat III 2 Ea. 16221.61
Providing and erecting Approved make Four pole moulded case circuit
breaker having breaking capacity ICU of 35 KA. and above at 415 V . having
normal current rating 250A. with variable thermal & magnetic release
suitable to work on A.C.supply 50 c/s. with all internal connections, spreader
tinned copper & complete erected in existing 16 G.M.S. housing.
ICS=100% of ICU only Cat III 13 Ea. 20946.39
Providing and erecting Approved make Four pole moulded case circuit
breaker having breaking capacity ICU of 50 K.A. and above at 415 V having
normal current rating up to 630A. with variable thermal & magnetic release
suitable to work on A.C.supply 50 c/s. with all internal connections, spreader
tinned copper & complete erected in existing 16 G.M.S. housing
ICS=100% of ICU only Cat III 4 Ea. 28173.95
Approved make standard Draw out type 4 Pole Air circuit breaker. Having
kA breaking capacity with ICU=ICS=ICW (1 sec)Vsr=690 v, Ui=1kv ,impulse
voltage=12 kv with following type of relay and accessories.(1) Manual Draw
out type (MDO) with following type of relay system (B) with microprocessor
Release with over load, short circuit, earth fault protection and metering
display in modular design with LED display and Test Trip button facility, CTs
and auxiliary contacts, of following current ratings.(iii) 1250Amp 50 kA Cat
III 2 Ea. 161515.16
(iv) 1600Amp 50 kA Cat III 2 Ea. 174516.89
(vi) 2500 Amp 60kA Cat III 2 Ea. 253570.6
Supplying and erecting approved make panel mounting type Digital
Voltmeter having 3 digits LED display, 0 to 750 AC Volts range erected on
existing panel board with all connection, wiring etc .with manufacturers
calibration certificate. 5 Ea. 1275.63
Supplying and erecting approved make panel mounting type Digital Ammeter
having 3 digits LED display, external CT operated, calibrated for 0 to
Amps suitable to operate on 500 Volt AC , erected on existing panel board
with all connection, wiring etc .with manufacturers calibration certificate. 5 Ea. 1558.43
Supply 500 V on existing panel board with necessary connections. 10 Ea. 317.14
Supplying and erecting approved make suitable panel indicator LED type
lamp, lens cover, complete erected with necessary connections. 50 Ea. 43.43
Description of item(with brief specification and reference to book of Rate in
Item No Qty Unit Amount
specifications) Figure
Providing & erecting L.T. Current Transformer with bar primary 50/5 to
17 1000/5 ratio 15 VA burden erected in existing CRCA box duly secured with
insulating materials connected to the meter 20 Ea. 274.72
Providing and erecting multifunctional meter suitable for application of Power
monitoring and showing measurement of following Voltage, Frequency,
Apparent energy, Apparent power, Active and reactive energy, Active and
reactive power, Average voltage Vavg, Peak demand power PM, QM, SM,
Demand power P, Q, S, Apparent power S, S1, S2, S3, Unbalance current,
Power factor and displacement PF (signed, four quadrant), Calculated neutral
18 current, Active, reactive, apparent energy (signed, four quadrant), Active
power P, P1, P2, P3, Voltage U21, U32, U13, V1, V2, V3, Phase currents,
Average current Iag, Peak demand currents, Reactive power Q, Q1, Q2, Q3,
Demand current I1, I2, I3, [Us] rated supply voltage 40...300 V AC 45...65 Hz,
40...300 V DC, Network frequency 50 Hz, Type of network 3P, Display type
segments LED, Display colour Red, Messages display capacity 3 fields of
characters, Display digits 12 digit(s) - 14.2 mm in height ( RS-485 Compitible) 9 Ea. 14123.84
providing and erecting Miniature circuit breaker single pole 6A to 25A suitable
19 to operate on 240 V A.C. system and having breaking capacity 10 KA to be
erected in existing box. confirming to IS 8828/1996 with ISI Mark 56 Ea. 112.11
Providing & erecting 415 V MCB Four Pole for Motor & Inductive Load (C
20 Curve) having 10KA breaking capacity & confirms to IS :8828 in existing box
having following capacity (b)40 Amp. Cat.III 4 Ea. 668.62
Providing & laying. R.C.C. Hume pipe for cable to be laid 90 cm. below
21 ground across the road crossing or on floor with necessary material in an
approved manner and making the ground as per original.(B) 400 mm dia 126 mtr 397.94
Providing and erecting required size HOT deep Galvanised iron strip for
22 earthing of H.T. , OCB/ ACB/ Transformer LT panel board, Motors etc. using
proper clamp. 42 kg 77.77
Supplying & erecting earth pit of minimum bore dia.150mm size approved
make Earthing Electrode consisting Pipe-in-Pipe Technology as per IS 3043-
1987 made of corrosion free hot dipped G.I.Pipes having Outer pipe dia of
50mm having 80-200 Micron galvanising, Inner pipe dia of 25 mm having
200-250 Micron galvanising, connection terminal dia of 12mm with constant
ohmic value surrounded by highly conductive compound with high charge
dissipation suitable for following type of applications with chamber and heavy
duty cover. (A)(approved make OEM has to submit test certificate including
23 value of earth resistance of installation duly stamped and signed by agency
and officer Incharge has to ensure the value of earthing resistane mentioned
in test Certificate) & having back filling compound of (B) Inner chemical
(CCM Compound)- Resistivity:- 0.2 ohm / meter testing as per IEC 62561-
2017, Voltage drop:- < 1 volt at no load & dry form, Sulphar content:- <2%(C)
Back fill Compound :- Earthing compound should be capable to retain
moisture for long time Necessary test report must be submitted by Agency.
(b)For Electrical installation up to 11 KV in normal soil. Length of Pipe :
mtrs. Back filling Compound :1 no. Bag of 25 Kg. 7 Ea. 5760.03
Providing , erecting , fabricating the M.S. structure as per requirement on site
incorporating proper size of M.S. angles,square,round, flats, bars, channels,
24 sections complete with cutting, welding, grinding & finishing duly painted with
one coat of red oxide with erection on site as per direction of engineer in
charge with necessary grouting, cementing, plastering & finishing complete. 440 kg 77.77
Providing & erecting weather proof, dust & vermin proof, floor mounted front
operated outdoor type double door cubical panel board necessary IP-54 and
above protection as per approval from engineer incharge made from
SWG thick CRC M.S. sheet for outer body & doors, 16 SWG thick CRC
M.S.sheet for internal partitions with necessary accesories , supporting
angles/ flats channel including cutting, bending, drilling, welding, riveting
with internal partitions & cable alley as per requirements & instruction of
engineer-in-charge with erection of supplied switch gears, BUSBARS,
suitable size of inter connecting PVC copper wire / copper-aluminium strips,
25 rubber grommets, rib, bakelite control fuses/MCB for measuring instruments,
earth bus & earth bolts, foundation flange - bolts-base Plates, sufficient nos.
of hinged doors, handles with locking arrangement and rubber gasket,heavy
duty end terminal connection,danger notice board,necessary
ventilation,earthing strip complete. The Panel shall be painted with epoxy
powder coating. (The rates excludes the cost of switchgears, bus bars, inter
connecting mains & Copper Aluminium strips, meters, Fuses etc. The
dimension shall be measured excluding base beams) The panel shall be
supplied with following approved manufacturers with following size.(A) locally
fabricated panel board (ii) With 550 mm. Depth 6 sq mtr 14885.38
0 (iii)with 750 mm. Depth 3.2 sq mtr 24660.16
Supplying and erecting triple pole & neutral 440V / 500V panel mounting
Copper Busbars with four equal Nos. of electrolyte bus having current density
not more than 1.6 Amp. / sq.mm (Rated current / cross section area) duly
26 wrapped with colour insulating tape for phase sequence of following current
carrying capacity, erected with necessary bus bar supports /insulators, main
cable socket to each bar, erected in existing cubical panel with necessary
connections.(F) Suitable for 800 Amp. capacity 12 Rn.Mtr 13199.69
(G) Suitable for 1200 Amp. Capacity 26 Rn.Mtr 16499.36
Providing and erecting iron clad cable route marker duly marked with
27 ELE.CABLE of size 23 cm.X 12 cm. Flushed with ground in cement
foundation as directed by Engineer in charge. 440 Ea. 240.38
Amount Put
For Rs. ₹1,01,82,568.71
One crore, one lakh eighty-two thousand five hundred sixty-eight point seven one two
I/ We am/are willing to carry out the work at_________% above / below percent (should be written in figure & words) of the estimated mentioned above. Amount of my /
our tender works out as under.
Estimated amount put to Estimated amount put to
Tender Rs. ___________________________ Tender Rs. ___________________________
Deduct ________ % below Rs. ____________ Add_______%Above Rs.________________
Net Rs. _______________________________ Net Rs. _____________________________
In words ______________________________ In words ____________________________
(a) I/we hereby declare that we have visited the site and fully exquisite myself/ourselves with the Local situation regarding materials labour and other factors
pertaining to work before submitting Tender.
(b) I/we hereby declare that we have carefully studies the conditions of contracts. Detailed Specification and other tender document of this work and agree to
execute the same accordingly.
If required and found necessary material to be used for this work and brought at site will have to sent to Govt.approved laboratory. The qualified agency/
1 manufacturer of Particular product under testing will have to pay/ bear necessary charges.
Description of item(with brief specification and reference to book of Rate in
Item No Qty Unit Amount
specifications) Figure
All works shall be carried out as per public works Department hand book and
other Specification.
Rates are inclusive of 1% Labour cess in tender amount so 1% of total amount of bill will be deducted from the bill.
Rates are inclusive of 1% Labour cess in tender amount so 1% of total amount of bill will be deducted from the bill.
The material to be used in this work must be as per instruction by under liason of Engg. In charge.The agency will have to agree to carried out the work
as per brand/make demand of concern deptt.
5 Contractor must have registration in C & above class registered under elect. (R & B) division.
6 Refer Additional technical specification before quoting rates.
Dy. Exe. Engineer Exe. Engineer
Contractor
Sachivalay Complex Elect. Sub-Div.No.-2 Sachivalay Complex Elect. Div
R. & B. Deptt. Gandhinagar R. & B. Deptt. Gandhinagar
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
NOTICE NO 25.pdf
GR AND GST LTR.pdf
additional technical specification.pdf
Solar phase 2 SBD Book.pdf
solar phase 2_anx_A.pdf
solar phase 2_anx_c.pdf
solar phase 2_make list.pdf
solar phase 2_memorandum.pdf
solar phase 2_pq.pdf
solar phase 2_boq r1.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .