Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.8 CrAccepted-AOC 102 SUBHASH ROAD HERITAGE HEIGHTS DEHRADUN | DEHRADUN | UTTARAKHAND | 248001 | ₹1.8 Cr | L1 | Accepted-AOC AOC |
| 2 | L2₹1.8 Cr+₹2.4 L (1.32%)Rejected-Finance | ₹1.8 Cr+₹2.4 L (1.32%) | L2 | Rejected-Finance Highest Rate Quoted by bidder |
Tender Value
₹1.8 Cr
EMD Value
₹3.6 L
Closing Date
26 Dec 2024, 12:00 pmClosed
General Manager (Garhwal)
Office of Chief General Manager, Construction Wing, Uttarakhand Peyjal Nigam, Kamla Nagar(Opp. ONGC Hospital), Dehradun
Electrification works for New Multipurpose Hall at Maharana Pratap Sports College Raipur Dehradun
2024_MDPEY_78686_1
4931/Nivida(Garh)Elect.DDun/37 Dt.11/12/24
Open Tender
Electrical Works
Item Rate
365 days
RAIPUR
Please refer tender document
3 documents required · 3 mandatory
₹5,900
PM,Const.Unit(Elect.),UKPJN, Dehradun
₹3.6 L
Dehradun
28 May 2025
13 Dec 2024
27 Dec 2024
13 Dec 2024
26 Dec 2024
16 Dec 2024
14 Dec 2024
Amount
DSR 1.10 Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.
DSR 1.10.3 Group C
DSR 1.14 Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.
DSR 1.14.2 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire
DSR 1.14.3 2 X 4 sq. mm + 1 X 4 sq. mm earth wire
DSR 5.4 Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
DSR 5.9 Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm)
DSR 2.4 Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)
DSR 2.4.1 4 way (4 + 12), Double door
DSR 2.4.2 6 way (4 + 18), Double door
DSR 2.4.3 8 way (4 + 24), Double door
DSR 2.5 Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.)
DSR 2.5.2 8 way (4 + 24), Double door
DSR 2.5.3 12 way (4 + 36), Double door
DSR 2.10 Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.
DSR 2.10.1 Single pole
DSR 2.10.5 Triple pole and neutral
DSR 2.13 Supplying and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.
DSR 2.13.1 40 amp
DSR 2.13.2 63 amp
DSR 2.13.3 100 amp
DSR 2.15 Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required
DSR 2.15.3 63 amp
DSR 7.1 Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.
DSR 7.1.1 Upto 35 sq. mm
DSR 7.1.14 Above 185 sq. mm and upto 400 sq. mm
DSR 9.1 Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
DSR 9.1.29 3½ X 240 sq. mm (62mm)
DSR 9.1.31 3½ X 400 sq. mm (82mm)
DSR 14.15 Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. in the existing trench, complete as required.
DSR 14.15.5 200 mm dia (OD-200 mm & ID-175 mm nominal)
PAR 3.1.2 Supply Installation Testing an Commisinoing of Passenger Elevator, 544 kg, (08 Passengers) G+1 , (2 Stop), With Machine Room, 2 opening Single Entrance Car, speed 1.5 m/s, Opening SS finish centre panel and all corners in SS finish, two-panel centre opening Doors , complete as required.
DSR 1.32 Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required.
DSR 11.1 Erection of RCC/PCC pole of following length in brick ballast and ramming the foundation with 150 mm thick cement concrete (1:3:6) layer on top with including excavation and refilling etc as required
DSR 11.1.2 Above 6.5 metre and upto 8.0 metre
DSR 4.3 Supplying and installing following size of perforated painted with powder coating M.S. cable trays Tee with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.
DSR 4.3.1 100 mm width X 50 mm depth X 1.6 mm thickness
DSR 4.3.2 150 mm width X 50 mm depth X 1.6 mm thickness
DSR 4.3.6 450 mm width X 50 mm depth X 2.0 mm thickness
DSR 2.2 Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required.
DSR 2.2.14 125 A,36KA,FPMCCB
DSR 2.2.15 200 A,36KA,FPMCCB (160 to 200)
Non Schedule Supply of 3.5 c x 240 sq.mm aluminium armoured cable
Non Schedule Supply of 3.5 c x 400 sq.mm aluminium armoured cable
Non Schedule Supply of 4 c x 6 sq.mm aluminium armoured cable
Non Schedule Supply of LED Floodlight luminaire with a housing of non-corrosive high pressure ADC with corrosion resistant powder coating and Anti-dust exposed Lens to ensure protection. The luminaire should have CRI > 70, SDCM <5 and CCT of 5700K and shall be compliant with IP66 and IK08 classification. Luminaire shall be designed to emit at least 59000 nominal lumens with maximum system wattage of 470W at a system efficacy of atleast 125 lumen/watt. The luminaire shall be designed so as to ensure lumen depreciation of up to 30% over 50k burning hours @ design ambient temp 35 deg C. The luminaire must have asymmetrical wide beam suiting sport lighting application. The luminaire should have fins on the back to ensure good heat dissipation and to prevent dirt from settling on the luminaire along with aiming angle scale. The electronic driver should be fully integrated and shall have a power factor >0.95 and THD <10% with a minimum inbuilt surge protection of 4kV/kA internal & 20Kv enternal and suitable for an operationg voltage range of 140-270V AC. The driver should be BIS approved, fully potted and encapsulated with 440V Stress Voltage protection for 8 Hrs. High Cut off : 325V(+/- 15V) and Auto Restart function should also be available within the fixture. The luminaire should comply with all the required IEC and IS standards and Marine Salt Protection (1000-hr test in lab).
Non Schedule Supply of LED Floodlight luminaire with a housing of non-corrosive high pressure ADC with corrosion resistant powder coating and Anti-dust exposed Lens to ensure protection. The luminaire should have CRI > 70, SDCM <5 and CCT of 5700K and shall be compliant with IP66 and IK08 classification. Luminaire shall be designed to emit at least 60000 nominal lumens with maximum system wattage of 470W at a system efficacy of atleast 125-130 lumen/watt. The luminaire shall be designed so as to ensure lumen depreciation of up to 30% over 50k burning hours @ design ambient temp 35 deg C. The luminaire must have flood light narrow beam suiting sport lighting application. The luminaire should have fins on the back to ensure good heat dissipation and to prevent dirt from settling on the luminaire along with aiming angle scale. The electronic driver should be fully integrated and shall have a power factor >0.95 and THD <10% with a minimum inbuilt surge protection of 4kV/kA internal & 20Kv enternal and suitable for an operationg voltage range of 140-270V AC. The driver should be BIS approved, fully potted and encapsulated with 440V Stress Voltage protection for 8 Hrs. High Cut off : 325V(+/- 15V) and Auto Restart function should also be available within the fixture. The luminaire should comply with all the required IEC and IS standards and Marine Salt Protection (1000-hr test in lab).
Non Schedule Hanging arrangement for LED light with G.I frame complete finishing under 2 ft to 6 ft variable height etc complete with installation of frame
Budhiraja Electricals (BID ID -353196)
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .