Supply, installation, testing and commissioning of 800 Amp, Indoor type VCB panel and allied works at water Supply Scheme Dalband Nishat along with 3.5kVA, 36 Volt battery Charger/ Inverter for tripping system. (Annexure E)
2026_PHE_330613_3
JSMDS/e-NIT 36 of 11/2026
Open Tender
Miscellaneous Works
Percentage
20 days
Dalbund
As Per NIT
2 documents required · 2 mandatory
₹500
Ex Engineer Jal Shakti PHE Mech. Div. Sgr
₹20,800
Yes
7 Nov 2026
7 Nov 2026
1 Dec 2026
7 Nov 2026
30 Nov 2026
7 Nov 2026
180 days
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply, installation, testing and commissioning (SITC) of 11KV, 800A, 25 kA for 3s, Indoor Type, Metal-Clad, Fully Compartmentalized Vacuum Circuit Breaker (VCB) Switchboard complete unit comprising ONE (01) INCOMER and ONE (01) OUTGOING FEEDER (1 + 1 Configuration), conforming to IEC 62271-200 / IS 12729, with Loss of Service Continuity Category LSC-2B, Partition Class PM, and Internal Arc Classification IAC AFLR 25 kA for 1 sec. The panel board shall be fully factory-assembled, wired, and equipped with horizontal draw-out carriage breakers, modern 110V DC control/tripping architecture, microprocessor-based numeric protection, and multi-function metering as detailed below:
1.1 Standards, Classification & Constructional Design:
• Applicable Standards: IEC 62271-200, IEC 62271-100, IS 12729, IS/IEC 60947, CEA safety regulations, and JKPCL/DISCOM technical norms.
• Service Continuity & Safety: Loss of Service Continuity Class LSC-2B (maintenance in cable or breaker chamber without de-energizing the main busbar) and Partition Class PM (metallic segregation partitions between all chambers).
• Internal Arc Classification (IAC): Fully type-tested for IAC AFLR 25 kA for 1 sec (Access: A-Authorized personnel, Front, Lateral, Rear) complete with individual gas exhaust / overpressure relief flaps for each chamber venting upwards.
• Degree of Protection: IP:4X / IP:44 for external enclosure and IP:2X / IP:26 between internal segregated functional chambers.
• Enclosure Sheet Thickness: Rigid, floor-standing extensible structure fabricated from min. 2.0 mm CRCA sheet metal for load-bearing members and frame, and min. 1.6 mm / 2.0 mm CRCA sheet for non-load bearing covers/doors. Pre-treated through 7-tank process and powder-coated with pebble light grey (RAL 7032 shade).
• Compartments: Four segregated earthed metal-clad compartments per panel: (a) Busbar chamber, (b) Breaker chamber, (c) Cable & Instrument Transformer chamber, and (d) Low Voltage (LV) Control & Metering chamber.
1.2 Vacuum Circuit Breaker (VCB) Mechanism:
• Breaker Quantity & Rating: 02 Nos. (01 No. Incomer + 01 No. Outgoing) 11KV (Rated Voltage 12 kV), 3-Phase, 50 Hz, 800A continuous normal current rating, 25 kA symmetrical short-circuit breaking capacity for 3 seconds, 62.5 kA peak making capacity.
• Truck & Racking Mechanism: Retractable / Fully Horizontal Draw-out Carriage Type with distinct Service, Test, and Disconnected positions. Mechanically and electrically interlocked to prevent racking when breaker is closed.
• Operating Mechanism: Motor-operated spring charged type with mechanical trip-free feature and manual spring charging handle facility.
• Auxiliary / Control Voltage (Modern Standard): Spring charging motor suitable for 230V AC; Shunt Trip Coil, Closing Coil, and Trip Circuit Supervision suitable for 110V DC.
• Safety Shutters & Interlocks: Automatic gravity-fall or mechanically driven earthed metal shutters that positively close and screen busbar and cable spouts when breaker carriage is moved to Test/Disconnected position; with independent padlocking facilities.
1.3 Busbar System & Surge Arresters:
• Busbar Material: High-conductivity Electrolytic Copper (EC Grade) busbars rated for 800A continuous current, sized for 25 kA short-time thermal withstand for 3s. Insulated throughout with heat-shrinkable high-dielectric cross-linked polyolefin sleeves (Raychem or equivalent) and insulated shrouds/boots over all bolted joints.
• Surge Arresters: 01 Set of 11 kV, 10 kA Class 3 (heavy-duty station class) Gapless Zinc Oxide (ZnO) Surge / Lightning Arresters (LAs) provided in the incoming cable chamber to protect vacuum bottles and downstream pump equipment from line surges and switching transients.
1.4 Instrument Transformers:
• Current Transformers (CTs) - Dual Core, Cast Resin Epoxy Insulated:
- Incomer: 03 Nos. CTs (Ratio 100/5-5A or as per site requirement). Core 1: Class 5P10 / 5P20, 15VA (Protection); Core 2: Class 0.5s / 0.2s, 15VA (Metering & Energy Billing).
- Outgoing Feeder: 03 Nos. CTs (Ratio suitable / 5-5A). Core 1: Class 5P10, 15VA (Protection); Core 2: Class 0.5s / 1.0, 15VA (Metering).
• Potential Transformers (PTs): 03 Nos. Single-Phase Draw-out type, epoxy cast resin PTs mounted on a dedicated draw-out trolley with primary HT HRC fuses and secondary MCBs. Ratio: (11000/√3) / (110/√3) Volts, Class 0.5 for metering and 3P for protection, rated burden 50VA per phase.
1.5 Numerical Protection Relays, Metering & Automation:
• Protection Relays (Individual for Incomer and Outgoing):
- Advanced Microprocessor-based Numerical Feeder Protection Relays (50/51/50N/51N) with Non-directional Overcurrent and Earth Fault IDMT curves plus Instantaneous High-Set protection.
- Inbuilt / External Trip Circuit Supervision Relay (95/TCSR) monitoring pre-closing and post-closing healthiness of trip coil on 110V DC.
- High-speed Master Trip Relay (86) with hand reset and electrically reset contacts.
- Under-voltage (27) and Over-voltage (59) protection elements on Incomer/Bus PT.
- Communication Protocol: Native IEC 61850 protocol compliance and RS-485 Modbus serial communication port for SCADA / PLC / Remote telemetry integration.
• Metering & Instrumentation (Modern Tri-Vector / Multi-Function):
- Microprocessor-based 3-Phase 4-Wire Tri-Vector Energy Meter (TVM) / Multifunction Power Monitor (MFM), Class 0.5s accuracy, measuring kW, kVA, kVAr, kWh, kVAh, PF, Frequency, THD, V, I with dual communication ports (RS-485 Modbus) on Incomer.
- Digital Multi-Function Meter (MFM) (96x96 mm flush type, Class 0.5 / 1.0) on the Outgoing Feeder.
- High-luminance cluster LED status indicating lamps: Red (ON), Green (OFF), Amber (Auto Trip), White (Trip Circuit Healthy), Blue (Spring Charged), Yellow (PT Supply Healthy).
• Annunciation System: Solid-state 8-window micro-controller based alarm annunciation fascia panel with flashing fault sequence, test/accept/reset push buttons, covering DC Fail, Trip Coil Fail, O/C Trip, E/F Trip, Under/Over Voltage.
1.6 Cable Termination Chambers:
• Cable Box Clearance: Spacious cable compartments with minimum 650 mm vertical clearance between terminal palms and detachable brass/aluminum gland plates to facilitate termination of 11 kV 3-Core up to 400 sq. mm XLPE insulated, armored cables with heat-shrinkable kits.
• Cable Support: Robust mechanical cable clamping arrangements (trefoil/flat aluminum clamps) inside the cable chamber to relieve cable weight from breaker bushings.
Testing, Pre-Commissioning & Statutory Clearance:
• Site high-voltage withstand testing, contact resistance, breaker timing, insulation resistance (IR), and secondary injection relay testing with calibrated test kit.
• Liaisoning, statutory inspection fee, drawing approvals, and obtaining formal energization certificate / safety clearance from the Chief Electrical Inspectorate (CEI / Electrical Inspector to Govt. of J&K). All requisite cabling of requisite size required in the said panel from tapping point and outgoing cabling of requsiste size to connect the system/ electromechanical machinery for which it has been installed, thimbling, tapping etc for connections are included in the job | 1 | Set | 8,67,000 | ₹8,67,000 |
| 2 | Supply, installation, testing and commissioning of 110V DC SMPS / SCR-based Automatic Float-cum-Boost Battery Charger along with matching maintenance-free Valve Regulated Lead Acid (VRLA) / Low-Maintenance Tubular Battery Bank (approx. 110V, 26AH - 50AH capacity) housed in a dedicated self-standing enclosure, complete with digital DC voltmeter, ammeter, float/boost auto-switchover, low DC voltage alarm, and DC distribution board (DCDB) for VCB trip coils, closing coils, protection relays, and annunciation circuits. (Make: Exide / Amara Raja / HBL / Statcon or approved equivalent, min. 24 months warranty). | 1 | Set | 1,35,000 | ₹1,35,000 |
| 3 | Supply of Essential Operational Tooling, Safety PPE & Commissioning Spares comprising:
• 01 No. Manual breaker racking handle & 01 No. manual spring charging handle.
• 01 Set 11 kV Telescopic / Fiber-glass Earthing & Discharge Rod with ground clamping cable.
• Supply and laying of 15 kV dielectric electrical safety rubber insulation matting conforming to IS 15652 (Class B, 2.5mm/3.0mm thickness) along front and rear lengths of switchgear.
• Base foundation mounting channel frames (ISMC 100/75) including anchor grouting fasteners. | 1 | Lot | 35,000 | ₹35,000 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.65 MB
BOQ_1121771.xls
BOQ • 0.39 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .