Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹7.3 LAccepted-AOC | L1 | Accepted-AOC Techno Commercially Accepted L1 Bidder | |
| 2 | L2₹8.5 L+₹1.2 L (16.4%)Rejected-Finance | L2 | Rejected-Finance Rejected Since L2 Bidder |
Tender Value
₹8.5 L
EMD Value
₹10,700
Closing Date
19 Jun 2023, 12:00 pmClosed
SO EnM Argada Area
GM Office Argada Area
Complete Rewiring of Damodar Tongi Club of Argada Area.
2023_CCL_280794_1
SO(EnM)/AA/e-NIT/23-24/11
Open Tender
Electrical and Maintenance Works
Item Rate
60 days
GM Unit Argada Area
Please refer Tender documents.
2 documents required · 2 mandatory
₹10,700
8 Jul 2023
3 Jun 2023
20 Jun 2023
4 Jun 2023
19 Jun 2023
4 Jun 2023
4 Jun 2023 - 11 Jun 2023
Amount
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable PVC/GI box (as per requirement in surface/recess) and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required. Group C. (Total 178 Light Points, 38 Fan Points, 18 Exhaust Fan Points) (Refer CPWD General Specifications for Scope, Standards for Work and Measurement Criteria)
Supplying and fixing 3 pin, 5 amp ceiling rose on the existing junction box/ wooden block including connection etc as required. (Refer CPWD General Specifications for Scope, Standards for Work and Measurement Criteria)
Supplying and fixing brass batten/ angle holder including connection etc. as required. (Refer CPWD General Specifications for Scope, Standards for Work and Measurement Criteria)
Providing of slim, compact, recess mounting LED Panel Light Square complete with LED Light, mounting and mounting fixtures, Electronic Drivers etc for 1ft X1ft Ceiling Cut-Out (18 watt or higher)
Providing of slim, compact, recess mounting LED Round Down Light complete with LED Light, mounting and mounting fixtures, Electronic Drivers etc (15 watt or higher)
Installation, testing and commissioning of pre-wired, fluorescent fitting / compact fluorescent fitting of all types, complete with all accessories and tube/lamp etc. directly on ceiling/ wall, including connections with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. as required. (Refer CPWD General Specifications for Scope, Standards for Work and Measurement Criteria)
Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. (Refer CPWD General Specifications for Scope, Standards for Work and Measurement Criteria)
Supplying and fixing suitable size GI/PVC box (as per requirement in surface/recess) with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 amps modular socket outlet and 5/6 amps modular switch, connection etc. as required. (Refer CPWD General Specifications for Scope, Standards for Work and Measurement Criteria)
Supplying and fixing suitable size GI/PVC box (as per requirement in surface/recess) with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. (Refer CPWD General Specifications for Scope, Standards for Work and Measurement Criteria)
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire (Refer CPWD General Specifications for Scope, Standards for Work and Measurement Criteria)
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. 2 X 4 sq. mm + 1 X 4 sq. mm earth wire (Refer CPWD General Specifications for Scope, Standards for Work and Measurement Criteria)
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. 2 X 10 sq. mm + 1 X 6 sq. mm earth wire (Refer CPWD General Specifications for Scope, Standards for Work and Measurement Criteria)
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. 4X 16 sq. mm + 2 X 16 sq. mm earth wire (Refer CPWD General Specifications for Scope, Standards for Work and Measurement Criteria)
Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole (Refer CPWD General Specifications for Scope, Standards for Work and Measurement Criteria)
Supplying and fixing following rating, double pole, (single phase and neutral), 240 V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required. 40 A (Refer CPWD General Specifications for Scope, Standards for Work and Measurement Criteria)
Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 8 way , Double door (Refer CPWD General Specifications for Scope, Standards for Work and Measurement Criteria)
Supplying and fixing 20 amps, 240 volts, SPN industrial type, socket outlet, with 2 pole and earth, metal enclosed plug top alongwith 20 amps “C” curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required. (Refer CPWD General Specifications for Scope, Standards for Work and Measurement Criteria)
Providing and fixing following rating and breaking capacity MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. 200 A, 36 kA, FPMCCB (Refer CPWD General Specifications for Scope, Standards for Work and Measurement Criteria)
Providing and fixing of MCCB enclosure (metal body) compatible with Item Sl. No. 16 above.
Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 volts, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 amps tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCB’s (but without MCB’s and incomer ) as required . 8 way (4 + 24) Double Door (Refer CPWD General Specifications for Scope, Standards for Work and Measurement Criteria)
Providing and fixing following capacity 4 pole ON-Load Changeover Switch (I-O-II) with handle with door interlock, phase barriers, in stainless steel enclosure on surface including drilling holes, making connection, earthing the body etc. as required. 200 A, 4-Pole conforming to IS:60947-3 or equivalent standard.
Providing and laying (minimum 150mm deep) earth connection from earth electrode with 6 SWG dia G.I. Wire in 15 mm dia G.I. pipe from earth electrode including connections with G.I. thimbles excavation and re-filling as required. (Refer CPWD General Specifications for Scope, Standards for Work and Measurement Criteria)
Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia (with charcoal/ coke and salt) including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe, excavation, re-filling etc. as required. (Refer CPWD General Specifications for Scope, Standards for Work and Measurement Criteria)
Dismantling of old installation including storage, cartage, transportation etc.
Total impact of GST for the purpose of CTC
RIYA ENTERPRISES
stage.html
html • 0.04 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_290713.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .