Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹2.2 CrAccepted-AOC VILL P O MIRAGPUR DISTT SAHARANPUR 247554 U P | SAHARANPUR | UTTAR PRADESH | 247554 | ₹2.2 Cr | L1 | Accepted-AOC Being L1 and reasonable. |
| 2 | L2₹2.3 Cr+₹9.6 L (4.45%)Rejected-Finance 4578 STREET 15 15A AGGARWAL ROAD DARYAGANJ CENTRAL DELHI DELHI 110002 UDYAM DL 01 0031798 | CENTRAL DELHI | DELHI | 110002 | ₹2.3 Cr+₹9.6 L (4.45%) | L2 | Rejected-Finance Being other than L1 |
| 3 | L3₹2.4 Cr+₹20.7 L (9.61%)Rejected-Finance | ₹2.4 Cr+₹20.7 L (9.61%) | L3 | Rejected-Finance Being other than L1 |
| 4 | L4₹3.0 Cr+₹81.8 L (37.9%)Rejected-Finance | ₹3.0 Cr+₹81.8 L (37.9%) | L4 | Rejected-Finance Being other than L1 |
| 5 | L5₹3.3 Cr+₹1.1 Cr (52.9%)Rejected-Finance SHOP NO 1 KARGI CHOWK HARIDWAR BY PASS DEHRADUN UTTARAKHAND | ₹3.3 Cr+₹1.1 Cr (52.9%) | L5 | Rejected-Finance Being other than L1 |
Tender Value
₹2.4 Cr
EMD Value
₹3.1 L
Closing Date
18 Oct 2021, 6:00 pmClosed
Chief Engineer Bareilly Zone
HQ Chief Engineer Bareilly Zone Military Engineer Services Sarvatra Bhawan Station Road Bareilly Cantt Bareilly 243001
PROVISION OF EXTERNAL SERVICES FOR TWO UNDERPASSES AT IMA DEHRADUN
2021_MES_419941_1
CEBZ/DDN/T-18 OF 2020-21
Open Tender
Civil Works
Item Rate
180 days
Dehradun
Please refer Tender documents.
8 documents required · 8 mandatory
₹2,000
GE IMA DEHRADUN
₹3.1 L
Yes
29 Oct 2021
8 Feb 2021
20 Oct 2021
8 Feb 2021
18 Oct 2021
30 Sept 2021
9 Feb 2021 - 26 Jul 2021
Amount
SCHEDULE 'A' PART- I (B/R WORK )
Surface excavation n.exc (not exceeding) 30 cm deep and averaging 15cm deep and getting out, in soft/loose soil complete all as specified and directed.
Rolling and consolidating formation surface road incl berms with 8 to 12 ton power roller complete to required level gradient, slope, camber and super elevation incl filling depressions with and incl approved earth which may occur during rolling process all as specified and directed.
M&L for Soling (or sub base) 150mm with broken boulders or quarried stone 40 -80mm size, inter stices filled, surface formed and rolled with 8 to 12 ton power roller and consolidated to required gradient and camber complete all as specified and directed.
M&L for 150mm thick (Compacted thickness) WBM in 2 layers(75mm thick each layer), laid and compacted separetely with brocken stone aggregate of grading to (63- 40 mm size) or of grading - 3 (50- 20mm size), rolled and consolidated to required gradient , camber level, super elevation with 8 to 12 ton power complete all as specified and directed.
M&L for laying premix bituminous macadem not exceeding 50mm consolidated thickness using 4 % binder content of paving bitumen VG-30 grade by weight of total mix, rolled and compacted to required gradient and camber with 8 to 12 ton power roller, complete all as specified and directed.
M&L for preparing unsurfaced water bound macadm by brushing with wire burshes for removing caked mud etc, sweeping with brooms and finally fanning the cleaned surface with gunny bags to remove all loose dirt, durt etc and applying evenly tack coat with bitumen VG-10 grade @ 10 kg/ 10 sqm, complete all as specified and directed.
M&L for applying evenly priming/tack coat @ 5 kg/ 10 Sqm using bitumen VG-10 grade on black top road surfaces, complete all as specified and directed.
M&L for laying semi dense asphaltic concrete (SDAC) 40mm consolidated thickness using 5.5% binder content of paving bitumen VG-30 grade as per mix design by weight of total mix, rolled to required camber and gradient with 8 to 12 Ton power road roller, complete all as specified and directed.
M&L for continuous brick edging using sub class 'B' bricks old size with width equal to the width of the brick, laid dry on end vertically complete all as specified and directred.
M&L for painting lines, dashes, arrows, letters etc on roads, pavements surface like exceeding 10 cm width with road marking paint white or golden yellow complete all as specified and directred.
Excavation in trenches, n. exc. 1.5 m wide and n. exc. 1.5 m in depth for foundation, etc, or shafts, wells, cesspits, manholes, pier holes, etc. n.exc 10sqm on plan and n.exc 1.5m in depth and getting out, in soft/loose soil complete all as specified & directed.
Excavation in trenches n.exc 1.5 m wide and n exc 1.5 m in depth; for foundation, or for shafts, wells, cesspits, manholes, pier holes, n.exc 10 sq m on plan and getting out, in hard/dense soil, complete all as specified and directed.
Excavation in trenches n.exc 1.5 m wide and exc 1.5 m but n.exc 3.0 m in depth for foundation, or for shafts, wells, cesspits, manholes, pier holes, n.exc 10 sq m on plan and getting out, in soft/loose soil, complete all as specified and directed.
Returning filling in, incl spreading, levelling, watering and well ramming in layers not exc 25 cm in any type of soil complete all as specified and directed.
Removing excavated material to a distance not exc 50m and depositing where directed at a level n exc 1.5m above the starting point complete all as specified and directed.
Removing excavated material to a distance exc 50 mtr but n.exc 250 mtr and depositing where directed at a level n exc 1.5m above the starting point complete all as specified and directed.
M&L PCC 1:4:8 type D-2 (using 40 mm graded stone aggregate) as in foundation filling and mass concrete etc complete all as specified and directed.
M&L PCC 1:3:6 type C-2 (using 40 mm graded stone aggregate) as in drain bed, foundation filling and mass concrete etc complete all as specified and directed.
M&L plain cement concrete 1:2:4 type B-1 (using 20mm graded stone aggregate) in lintels upto 1.5m clear span, cills, steps; seismic and other similar bands, plinth courses, copings, kneelers, apex stones, bed plates, kerbs not provided, including necessary form work, complete all as specified and directed.
M&L walling random rubble uncoursed stone masonry well bonded, bedded & solidly hearted, built in CM 1:4 complete all as specified and directed
M & L precast cement concrete bonders using PCC 1:3:6 type C-1 using 20 mm graded stone aggregate for stone walling and set in cement mortar 1:4 including necessary form work etc, complete all as specified and directed.
Extra over stone walling for hammer dressing with maximum depression from a straight edge, held against the dressed surface n.exc. 20 mm (lime or sand stone) complete all as specified and directed.
M&L for 15mm thick plaster on stone masonry surfaces in cement mortar 1:4 finished even and fair complete all as specified and directed.
M&L for fly ash brick work with using old size bricks straight or curved on plan exc. 6.00 m mean radius built in cement mortar 1:4 complete all as specified and directed.
M&L for Brick work with sub class ‘B’ bricks, straight or curved on plan exc 6m mean radius built in cement mortar 1:4 complete all as specified and directed.
M&L for 15mm thick rendering on brick or concrete surfaces in cement mortar 1:4 finished even and smooth without using extra cement complete all as specified and directed.
M&L for Extra for forming fair finished drain or channel 30 cm inner girth in cement concrete, using ex- tra cement, including forms, moulds, mi- tred/stopped ends etc. complete all as specified and directed.
Add or deduct for each 25 mm girth or part therof over or under 30 cm inner girth complete all as specified and directed.
M&L for 600 mm dia reinforced concrete hume pipes, class NP-3 with one collar per length of pipe complete all as specified and directed.
M&L for RCC M-25 design mix (20 mm graded stone aggregate) as in foundations, incuding rafts, footings , foundation beams , plinth beams , bases for columns etc , basement slabs , under reamed piles and mass concrete complete all as specified and directed.
M&L for RCC M-25 design mix (20 mm graded stone aggregate) as in columns , pillars , piers, posts and struts complete all as specified and directed.
M&L for providing precast cement concrete 1:2:4 type B-0 louvres and jallies, 40mm thick (measured solid), including all mouldings but excluding frame fixed with cement mortar 1:4 (Pre cast frame shall be measured separately and paid for under item) complete all as specified and directed.
S&F framed work as in doors or gates of angle or other section with gusset plates, rails, braces, etc., complete, drilled for fixing of steel sheeting or other covering. Doors, etc. to be prepared for hanging or sliding with and including either hooks and hinges or steel hanging door fittings (exclusive of steel sheeting or other covering, running rails and guides) and hanging; also fastening and fixing complete all as specified and directed.
S&F cast iron work grade FG 150, machined, in pulleys and similar articles complete all as specified and directed
S&F rolled steel section joist, channel, angle, or tee sections, fixed independently, without connecting plates, etc. (cut to ordinary lengths i.e. within 20mm of the length indicated) Fe-290 (Gde E- 165) complete all as specified and directed.
S&F steel pintle hinges: large hasps and staples; chains; hand made sliding bolts; clamps; hold fasts; wall ties; hooks for hanging fans; plain angle cleats for securing purlins to good trusses or rafters; knee piece inserts; two way and three way straps, plate washers and similar small articles conforming to Fe-290 Gde-E-165 complete all as specified and directed.
S&F mild steel, plain, black sheet 3.00 mm thick in wall cladding, steel gates and similar work, cut to size, holes punched; including round headed screws, clout nails or rivets and fixed to wood or steel framing with plain 40 mm lap joints with riveted or welded seams, including bending or turning up, mitred angles, etc. as requiredcomplete all as specified and directed.
M&L for TMT bars (Fe-500) 10 mm dia and over, cut to length, bent to shape required including cranking, bending spirally or hooping for columns and binding with and including mild steel wire (annealed) not less than 0.9 mm dia or securing with clips complete all as specified and directed.
M&L for TMT bars 5mm dia and over upto and including 10 mm dia bars as in stirrups , spacers , binders,including cut to Length bent to shape required incl cranking, bending, spirally for hooping for columns with an incl MS wire(annealed) not less than 0.90 mm dia or securing with clips complete all as specified and directed.
M&L for preparing surfaces plastered or unplastered of wall or concrete surfaces and applying three coat of white wash, complete all as specified and directed.
S&F mild steel work in posts and struts in fencing including cutting tops to shape as directed, drilling holes, notching for wire, etc.; flat iron fillets (for securing wire mesh etc.) including all necessary drilling, bolting or riveting, etc., and similar work conforming to Fe-290 Gde E-165 complete all as specified and directed.
S&F galvanised. 2 strand, steel barbed wire 2.24mm dia barbed with 2.00 mm dia barbs at 75mm spacings and straining and fixing to any type of standard rails straining bolts, ncluding, securing or tying at crossings with and provision of galvanised mild steel wire, staples or steel pins, etc. as directed (each line wire to be measured) complete all as speified and directed.
M&L for applying two coat of cement base paint over a coat of primer on new plaster surfaces, including preparation of new surface of walls, complete all as specified and directed.
M&L two coat of synthetic enamel paint over a coat of red oxide primer on steel surface of any description exc. 10 cm width or girth including preparation of new steel surfaces, complete all as specified and directed.
M&L for applying one coat of bituminous paint on surfaces of any description wood, steel, iron, concrete, brick, stone, etc. n exc 10cm in width or girth complete all as specified and directed.
SCHEDULE 'A' PART-II (E/M WORK )
M&L for sand cushioning to UG cables (8 cm deep before laying of cable and 15 cm deep over the cable) with clean, dry and unwashed sand free from sharp particles including gently punning around cable complete all as specified and directed. Note :- Punned thickness only will be considered for payment.
M&L for unreinforced precast concrete cable cover, Class LV type-I, flat size 250 mm x 180 mm x 40 mm for cable protection complete all as specified and directed.
M&L for galvanized iron pipes, light grade, 80mm bore with fittings laid for protection of cable under road crossing/culvert / drain or fixed to pole/wall with help of flat iron clamps etc. complete all as specified and directed.
M&L for galvanized iron pipes, light grade, 50mm bore with fittings laid for protection of cable under road crossing/culvert / drain or fixed to pole/wall with help of flat iron clamps etc. complete all as specified and directed.
M&L for galvanized iron pipes, light grade, 40mm bore with fittings laid for protection of cable under road crossing/culvert / drain or fixed to pole/wall with help of flat iron clamps etc. complete all as specified and directed.
Supply, laying and jointing LT XLPE Insulated, galvanized steel strip or wire armoured power electric cable (heavy duty) 1100 volt grade with aluminium stranded conductor of size 95 Sqmm x 3.5 core confirming to IS 7098 (Part-I) of 1988 passing through pipes, in duct, on poles, in trenches, under road etc complete all as specified and directed.
Supply, laying and jointing LT XLPE Insulated, galvanized steel strip or wire armoured power electric cable (heavy duty) 1100 volt grade with aluminium stranded conductor of size 16 Sqmm x 4 core confirming to IS 7098 (Part-I) of 1988 passing through pipes, in duct, on poles, in trenches, under road etc complete all as specified and directed.
Supply, laying and jointing LT XLPE Insulated, galvanized steel strip or wire armoured power electric cable (heavy duty) 1100 volt grade with aluminium stranded conductor of size 10 Sqmm x 4 core confirming to IS 7098 (Part-I) of 1988 passing through pipes, in duct, on poles, in trenches, under road etc complete all as specified and directed.
Supply, laying and testing PVC insulated, unsheathed cable electric cables with stranded copper conductor of size 1.5 sq mm 3 core 1100 volts grade complete all as specified and directed.
M&L brick sub class ‘B’ bricks, old size laid dry and flat adjoining each other as in protection to underground cable all as specified and directed.
M&L steel tubular pole swaged ISI Marked 9 mtr long type 410 SP-31 complete with cast iron base plate pole cap finial taper plug, nuts, washers etc and including painting two coats of aluminium paint over one coat of red oxide primer on steel pole surfaces, steel pole embeded in concrete complete all as specified and directed. (Excavation, earth work and PCC shall be measured separately under respective items)
Supply, fixing and testing LED street light energy saving and environment friendly, IP-66 powder coated pressure die-cast aluminium with high power LED as light source and electronic driver, AC, SP, 230 Volts 90 Watt includindg suitable size GI pipe bracket clamps, nut, bolts and washers complete all as specified and directed. Make : Havells Cat Part No .ENDURACITYLINERNEOSL90W LED757SASYBOTG/ Make: WIPRO Cat Part No.LR07-102-XXX-57-XX/ Make: PHILIPS Cat Part No. BRP409LED110CWMEFGPSUGRV3.
Supply and fix LED flood light fitting 140 watt energy saving and enviromental friendly long liife exclusive innovative made up of pressure die cast aluminium housing with high power LED as lightnig source, suitable for underpas lighting complete all as specified and directed. Make: Philips Cat Part No. BVP122 LED 142 CWHEAK55 FGXTFCL54 /Make : Havells Cat Part No.JETAPROPLUSFL150W LED757LTG / Make: WIPRO Cat Part No.LF20-102-060-57-G2.
Supply and fixing pole mounted street light junction box, waterproof and fire proof, sheet moulding compound(SMC) Sintex Make box of inside size 250mm x200mmx100mm deep complete with 4 Nos terminal end aluminum strip of 20x4 mm size fixing cable end terminal and 3 Nos MS bolts and nut of size 8 mm dia x 30 mm long and MCB mounting rail with 6 Amp MCB SP duly welded with box fixed on pole with MS clamp 25 mm x 3 mm MS strip duly painted and testing etc complete all as specified and directed. Make:- HENSEL/SINTEX/SUPREME
Supply, installation, commissioning and testing of bus bar chamber outdoor type made out of 3.15 mm CRCA sheet of size 750 mm x 450 mm x 400 mm, dust and vermin proof factory made CPRI approved openable from front and rear side with aluminum bus bar suitable fo 400 Amps rating 3 phase 4 wired system with locking arrangement weather proof complete with danger plate for fixing of with and including MCCB 4 pole, 415 volts, adustable type, 100 Amp 25 KA -01 No (incoming) and MCB TPN 230 volts, 32 Amps 10 KA - 05 Nos (outgoing) etc in side the chamber mounted on angle iron frame 50 X 50 X 6 mm imbedded in PCC (1:3:6) block type C-2 using 40 mm graded stone aggregate of size 200 x 200 x 300mm including connection of cable with lugs of suitable size etc complete all as specified and directed. Make:- ADUNIK SWICHGEAR PVT LTD/ SMS PANEL & SWITCHGEAR/ UNIVERSAL SWITCHGEAR CONTROL
Supply and fix street light control panel AC, outdoor type, pole/flour mounted made from 2.00 mm thick MS sheet min size 50 cm x 40 cm x 12 cm deep complete with 4 Nos mounting bolts of size 10 mm dia x 50 mm long fixed with 20 mm x 4 mm size MS strip with astronomical timer, contractor of 65 Amp rating 3 phase 1 Nos, MCB TPN 63 Amp of capacity 01 Nos, of capacity 12 KW complete all as specified and directed. Make: Havells, cat part No IHXTSO912A or equivalent make of L&T or Legrand.
Material and labour for boring of holes under roads, foot path/Hard Standing by trenchless technology including HDPE pipe of 150 mm dia suitable for 0.4 Mpa working pressure complete all as specified and directed.
Earthing complete with steel earth plate electrode of size 600 mm x 600 mm x 6 mm thick burried directly in ground (earth pit not less than 2.25 mtrs deep below normal ground level) vertically, with top edge of plate not less than 1.5 mtr below normal ground level connected to galvanised earth lead wire 4 mm dia by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No 3 of MES Schedule Part-I connecting to earthing test point & to main switch board and testing on completion with and including necessary excavation and earth work in any type soil, earth lead connected to earth test point & to main switch board etc with & including adequate quantity of charcoal dust and common salt, test point, PCC (1:3:6) type C-1 (using 20 mm graded crushed stone aggregate) for earth pit with 40 x 40 x 6 mm mild steel angle iron frame for cover, internal surface of concrete shall be given 10mm thick plaster in CM 1:4, pre cast RCC (1:2:4) type B-1 (using 20 mm graded crushed stone aggregate) 40mm thick cover, reinforced with 8mm dia deformed or TMT bars 3 Nos both way with 12mm dia round bar handle, GI medium grade watering pipe 20 mm dia with funnel and wire mesh and 15 mm dia GI light grade earth lead protection pipe etc complete all as specified and directed.
Earthing complete with steel earth plate electrode of size 600 mm x 600 mm x 6 mm thick buried directly in ground to a depth not less than 2.25 mtr deep below normal ground level with top edge of the earth plate not less than 1.5 mtr deep below normal ground level connected to galvanized iron strip of size 32 x 6 mm as earthing lead by means of nuts, bolts and washers of steel after welding of GI strip to earth electrode to the full lenght of earth plate,40mm dia GI tubing light grade protection pipe upto test point, 20 mm dia GI watering pipe with funnel and wire mesh, PCC pit 1:3:6 with pit cover of size 30X30 cm made of RCC 1:3:6 with suitable handle,angle iron frame made of angle iron of size 40x40x4 mm, adequate qty of charcoal dust and salt layers all around the earth plate, removal of surplus soil and returning filling in all as required at site including test point made out of steel plate of size 75x75x6 mm fixed to wall all as specified in plate No 3 of SSR Part-I and directed.
Material and Labour for Earth continuity conductor of size 32 X 6 mm GI. strip fixed to wall and batton or recess or chases or burried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc complete all as specified and directed.
Supply, installation, testing and commissioning of eco-friendly (CPCB-II Norms compliant) silent type diesel engine driven generating set of 25 KVA, directly coupled alternator and engine , water cooled,common base plateform with floor mounted fuel tank, RCC /PCC foundation,including neccessary excavation anti vibration pads/dampers as directed by manufacturers and other accessories comprising of the following:-
(A) ENGINE (Prime mover ):- Diesel Engine, 1500 RPM, direct injection,adequate Nos of cylinder as per manufacturer, four stroke, naturally turbo charged, capable of giving adequate BHP to drive Alternator capable of delivering 20 KW/25 KVA at outdoor atmospheric conditions.(Taking all derating factor into consideration, batteries one Nos of capacity as per manufacturer recommendations) Complete with fly wheel all standard fittings / fixtures as per manufacturer and including suitable panel with turbometer, lub oil temperature, pressure gauge , frequency meter self starer system with electronic governor and Engine protection system,(PROTECTION SYSTEM SHALL MONITOR AND SHUTDOWN THE ENGINE at high water temperature, low lub oil, oil pressure, over speed etc. ) with the following:-
i) Exhaust Gas turbo charger
ii) Residential type Exhaust silencer
iii) Air cleaner, replaceable element
iv) Fuel pump with fitted accessories
v) Lube oil cooler & replaceable spin-on type oil filters
vi) Centrifugal filter for extended lube change intervals
vii) Closed circuit engine cooling with water pump pusher fan & radiator
viii) Safety shut down system for low lub oil pressure & high coolant temperature
ix) 12 V Electric starting system
x) 12 V 70AH battery 01 No Make: Exide/Amaron
xi) MS fuel tank with level indicator with marking and capacity as per manufacturers specification (not less than 8 hrs continious operation)
xii) Engine operation/maintenance and spare parts as per manufacturer manual
xiii) Standard set of essential tools for preventive maintenance along with holding wall mounted board , screw driver set first aid box, spanner set one pipe wrench complete
xiv) Engine warranty and OEM test certificate
xv) Fuel tank and first fill of lub oil and other consumable etc.
Make:Kirloskar/Mahindra &Mahindra/Greaves Cotton Ltd etc.
(B) ALTERNATOR:-Silent pole brushless type , suitable for direct coupling to engine self excited self regulated class 'H' insulated AC generator devoloping 25 kVA/20 kw , 415V, 1500RPM,0.8 Pf considering derating factor factor with IP 23 protection all as per BS 5000 Pt-3/IS 4722 with following specifications:-
i) Single bearing, self excited , self regulated in brushless construction
ii)Thyristor type electronic automatic voltage regulator
iii) Class H insulation stator & Rotor winding
iv) The above Engine and AC generator are assembled on a sturdy channel section base frame ,aligned and tested at site
Make: Kirloskar /Greeves
(C) INBUILT AMF PANEL:-KIOSK type AMF panel 415V 3 Phase 50Hz 4 wire supply , factory assembled with front opening weather and vermin proof made out as per manufacturer and CRCA sheet not less than 2.0mm thick with rubber lining locking arrangement powder coated externally and comprising the following:-
i) LED type indicating lamps panel mounting type RYB for mains and DG set
ii) LED type indicating lamp for battery charging LLOP, HWT, OL trip SFS hooter 12 V
iii) Inbuilt battery charging unit complete for 12 V with auto trickle, boost & off modes Complete Make: Microstate
iv) Multifunction meter to to monitor voltage,current,frequency, power factor , complete with cast resign base CT of 100/5 Amp complete including connection with appropriate size PVC insulated copper wire complete all as specified and directed.Make: AE
v) RPM meter -1
vi) Hour meter digital panel mounted-1 set
vii) set of control MCB/MCCB
viii) Earthing terminals
(D) ACOUSTIC ENCLOSURE: Sheet metal fabricated cope type silent enclosure fitted inside of canopy manufactured on CNC machines as per CPCB norms and powder coated after seven tank process , the enclosure shall be designed for reducing the sound level 75db (A) at a distance of 1M at 75% load under field condition and 70db at 3M from Gen set when DG set is working at full load along with testing conformance labeling classification etc as laid down in GSR No 371 (E) dt 17 May 2002 incuding provision for cable entry and earth strip and complete all as per manufacturers design etc. Make:Kirloskar/greeves cotton
Note:(i) The acoustic enclosure is manufactured with 1.5 mm CRCA steel with and aesthatically pleasing finish
ii) Regerous pretreatement of sheet metal parts with nine tank phosphating and powder coated with pure polyster based compound.
iii) All nut bolt and hardware are zinc coated
iv) The doors are gasketed with EPDM gaskets.
v) Long lasting green passivated fastners. Cast aluminium hinges and stainless locks for long durability and ease of operation
vi) Accoustic insulation with fire retradent accoustic foam to better the statutory norms of 75db (A) at 1 mtr distance under free field condition as per CPCB-II norms.
vii) Adequate ventilation to meet air requirement for combution and heat removal
viii) Emergency stop push button outside the container
ix) Provn of light inside the canopy.
x) Complete with incoming cabling from alternator to control panel
(E) MISC : Operation and maintenance catalogue, control wiring diagram, spare part list, overhauling manuals, gauratee card etc. shall be provided as per manufacturer standard practices.
Supply, installation, testing and commissioning of eco-friendly (CPCB-II Norms compliant) silent type diesel engine driven generating set of 30 KVA, directly coupled alternator and engine , water cooled,common base plateform with floor mounted fuel tank, RCC /PCC foundation,including neccessary excavation anti vibration pads/dampers as directed by manufacturers and other accessories comprising of the following:-
(A) ENGINE (Prime mover ):- Diesel Engine, 1500 RPM, direct injection,adequate Nos of cylinder as per manufacturer, four stroke, naturally turbo charged, capable of giving adequate BHP to drive Alternator capable of delivering 24 KW /30 KVA at outdoor atmospheric conditions.(Taking all derating factor into consideration, batteries one Nos of capacity as per manufacturer recommendations) Complete with fly wheel all standard fittings / fixtures as per manufacturer and including suitable panel with turbometer, lub oil temperature, pressure gauge , frequency meter self starer system with electronic governor and Engine protection system,(PROTECTION SYSTEM SHALL MONITOR AND SHUTDOWN THE ENGINE at high water temperature, low lub oil, oil pressure, over speed etc. ) with the following:-
i) Exhaust Gas turbo charger
ii) Residential type Exhaust silencer
iii) Air cleaner, replaceable element
iv) Fuel pump with fitted accessories
v) Lube oil cooler & replaceable spin-on type oil filters
vi) Centrifugal filter for extended lube change intervals
vii) Closed circuit engine cooling with water pump pusher fan & radiator
viii) Safety shut down system for low lub oil pressure & high coolant temperature
ix) 12 V Electric starting system
x) 12 V 70AH battery 01 No Make: Exide/Amaron
xi) MS fuel tank with level indicator with marking and capacity as per manufacturers specification (not less than 8 hrs continious operation)
xii) Engine operation/maintenance and spare parts as per manufacturer manual
xiii) Standard set of essential tools for preventive maintenance along with holding wall mounted board , screw driver set first aid box, spanner set one pipe wrench complete
xiv) Engine warranty and OEM test certificate
xv) Fuel tank and first fill of lub oil and other consumable etc.
Make:Kirloskar/Mahindra &Mahindra/Greaves Cotton Ltd etc.
(B) ALTERNATOR:-Silent pole brushless type , suitable for direct coupling to engine self excited self regulated class 'H' insulated AC generator devoloping 25 kVA/20 kw , 415V, 1500RPM,0.8 Pf considering derating factor factor with IP 23 protection all as per BS 5000 Pt-3/IS 4722 with following specifications:-
i) Single bearing, self excited , self regulated in brushless construction
ii)Thyristor type electronic automatic voltage regulator
iii) Class H insulation stator & Rotor winding
iv) The above Engine and AC generator are assembled on a sturdy channel section base frame ,aligned and tested at site
Make: Kirloskar /Greeves
(C) INBUILT AMF PANEL:-KIOSK type AMF panel 415V 3 Phase 50Hz 4 wire supply , factory assembled with front opening weather and vermin proof made out as per manufacturer and CRCA sheet not less than 2.0mm thick with rubber lining locking arrangement powder coated externally and comprising the following:-
i) LED type indicating lamps panel mounting type RYB for mains and DG set
ii) LED type indicating lamp for battery charging LLOP, HWT, OL trip SFS hooter 12 V
iii) Inbuilt battery charging unit complete for 12 V with auto trickle, boost & off modes Complete Make: Microstate
iv) Multifunction meter to to monitor voltage,current,frequency, power factor , complete with cast resign base CT of 100/5 Amp complete including connection with appropriate size PVC insulated copper wire complete all as specified and directed.Make: AE
v) RPM meter -1
vi) Hour meter digital panel mounted-1 set
vii) set of control MCB/MCCB
viii) Earthing terminals
(D) ACOUSTIC ENCLOSURE: Sheet metal fabricated cope type silent enclosure fitted inside of canopy manufactured on CNC machines as per CPCB norms and powder coated after seven tank process , the enclosure shall be designed for reducing the sound level 75db (A) at a distance of 1M at 75% load under field condition and 70db at 3M from Gen set when DG set is working at full load along with testing conformance labeling classification etc as laid down in GSR No 371 (E) dt 17 May 2002 incuding provision for cable entry and earth strip and complete all as per manufacturers design etc. Make:Kirloskar/greeves cotton
Note:(i) The acoustic enclosure is manufactured with 1.5 mm CRCA steel with and aesthatically pleasing finish
ii) Regerous pretreatement of sheet metal parts with nine tank phosphating and powder coated with pure polyster based compound.
iii) All nut bolt and hardware are zinc coated
iv) The doors are gasketed with EPDM gaskets.
v) Long lasting green passivated fastners. Cast aluminium hinges and stainless locks for long durability and ease of operation
vi) Accoustic insulation with fire retradent accoustic foam to better the statutory norms of 75db (A) at 1 mtr distance under free field condition as per CPCB-II norms.
vii) Adequate ventilation to meet air requirement for combution and heat removal
viii) Emergency stop push button outside the container
ix) Provn of light inside the canopy.
x) Complete with incoming cabling from alternator to control panel
(E) MISC : Operation and maintenance catalogue, control wiring diagram, spare part list, overhauling manuals, gauratee card etc. shall be provided as per manufacturer standard practices.
Note : Tenderers may note that amount of credit Rs 0.00 will be deducted from the total amount arrived, at the time of Acceptance of contract.
M/s Kamal Traders
Sanjeev Construction Co
Som Prakash Gupta
OM TRADERS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .