Commander Works Engineer Bldg No. P-9, Sitabuldi Fort, Nagpur - 440 001 Pin-900419, C/o 56 APO
SPECIAL REP / REPLACEMENT OF OLD TRANSFORMER AND HT BREAKER AT EME SCHOOL, VADODARA
2026_MES_798922_1
85069/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE (Army) Baroda
As per tender documents
9 documents required · 9 mandatory
₹500
GE (Army) Baroda
₹95,500
Yes
16 Nov 2026
16 Nov 2026
9 Dec 2026
16 Nov 2026
7 Dec 2026
30 Nov 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply, installation, testing and commissioning of Outdoor type, step down transformer 11KV/433 Volts (at no load) AC, 3 phases, 50 Hz,250 KVA capacity, core type copper wound on HV & LV coil immerse, naturally cooled, oil natural-air natural (ONAN) with external cooling tubes, delta connected on primary side (HV) and star connected on secondary side (LV side) in accordance with vector group DYN-11 with neutral brought out on secondary side (LV side) and having 7 step tappings (Tapping Range ( + ) 7.5% in step of 2.5%) on HV side to be changed by means of hand operated off load tap changer gear, the maximum temperature rise should not exceed 45 degree Celsius, in oil and 55 degree celcius the transformer shall be in accordance with latest EEL- 3 of IS : 1180 (Part-1)-2014 with latest amendments and with BIS marked and BEE 3 Star label and comprise of the following in note :- | 1 | Job | - | - |
| 2 | Supply, installation, testing and commissioning of Outdoor type, step down transformer 11KV/433 Volts (at no load) AC, 3 phases, 50 Hz,200 KVA capacity, core type copper wound on HV & LV coil immerse, naturally cooled, oil natural-air natural (ONAN) with external cooling tubes, delta connected on primary side (HV) and star connected on secondary side (LV side) in accordance with vector group DYN-11 with neutral brought out on secondary side (LV side) and having 7 step tappings (Tapping Range ( + ) 7.5% in step of 2.5%) on HV side to be changed by means of hand operated off load tap changer gear, the maximum temperature rise should not exceed 45 degree Celsius, in oil and 55 degree celcius the transformer shall be in accordance with latest EEL- 3 of IS : 1180 (Part-1)-2014 with latest amendments and with BIS marked and BEE 3 Star label and comprise of the following in note :- | 1 | Job | - | - |
| 3 | Supply, installation, testing and commissioning of Outdoor type, step down transformer 11KV/433 Volts (at no load) AC, 3 phases, 50 Hz,160 KVA capacity, core type copper wound on HV & LV coil immerse, naturally cooled, oil natural-air natural (ONAN) with external cooling tubes, delta connected on primary side (HV) and star connected on secondary side (LV side) in accordance with vector group DYN-11 with neutral brought out on secondary side (LV side) and having 7 step tappings (Tapping Range ( + ) 7.5% in step of 2.5%) on HV side to be changed by means of hand operated off load tap changer gear, the maximum temperature rise should not exceed 45 degree Celsius, in oil and 55 degree celcius the transformer shall be in accordance with latest EEL- 3 of IS : 1180 (Part-1)-2014 with latest amendments and with BIS marked and BEE 3 Star label and comprise of the following in note :- | 1 | Job | - | - |
| 4 | Earthing Complete with galvanised steel earth plate electrode 60cmx60cmx6mm thick burried directly in ground vertically to a depth not less than 2.5 metre below ground level with top edge of the earth plate at a depth not less than 1.5 mtr below ground level earth plate surrounded from all sides by 15cm thick packed layer of charcoal dust and common salt filling in alternate layers and electrode connection by using galvanized earth lead wire 32 x 6 mm dia by means of bolts, nuts, check nuts and washers made of galvanised iron and thimbles and other end of the earth wire connected to main switch board protected by galvanised iron medium grade pipe 40mm bore in wall/floor/and GI Pipe 20 mm bore light grade for watering with funnel and wire mesh PCC chamber in cement concrete 1:3:6 type C-2 and RCC pit cover including necessary excavation and earth work in any type of soil, returning slurry approved soil and disposed of surplus soil to a distance not exceeding 50 Mtr away all as shown in electrical plate No 3 of SSR 2009 ( Part-I).
Notes
(a) The unit rate shall include for GI protection pipe, GI watering pipe, wire mesh, funnel and excavation, RCC pit cover, test point, galvanised iron strip from top of earth plate upto 7.5 metres above ground level and if GI protection pipe is less than 7.5 metres, no price adjustment shall be made.
(b) PCC pit shall be provided at least 50cm away from the earth pit and not just on the earth pit and extra cost of additional length of water pipes and fittings, junction, elbow etc shall be deemed to be included in the unit rate.
(c) If the testing result of earthing is not found below 3 Ω then the contractor shall do another earthing work at his own cost and nothing shall be permissible on this account.
(d) Earthing work will be carried out in presence of MES representative. | 14 | Each | - | - |
| 5 | Supply, laying, commissioning and testing in repairs of XLPE insulated, seceened, PVC bedded, galvanised steel wire armoured heavy duty electric power cable with aluminium conductor, 11 KV suitable for 11000 volts grade, cross-sectional area 95 sqmm 3 core complete . | 100 | RM | - | - |
| 6 | Construction of Plinth of size 2.0 mx 2.0 mx1.5 m for transformer/RMU, using 100 mm thick PCC 1:4:8 type D-2 as in lean concrete, flyash brick masonry in CM 1:6, the top of the plinth shall consist of 100 mm thick PCC 1:2:4 type B-1 (using 20 mm graded stone aggregates) over 75 mm thick PCC 1:4:8 type D-2 over compacted moorum filling, 10 mm thick rendering in CM 1:4 on brick surface with and including 25 cm thick stone aggregates of size 12.5 mm all around upto and including 1.5 m from the edge of the plinth including the RCC Gate and fencing with angle iron post in lieu of RCC post complete all as specified, directed by the Engineer-in-charge and as shown on TD drawing No CEPZ/98/TD/6, Sheet No 2/2. | 4 | Each | - | - |
| 7 | Supply and fix cable jointing kit for 11 KV grade (E) cable for outdoor termination cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured Aluminium conductor cable of size 95 sqmm all as directed. | 3 | Each | - | - |
| 8 | Supply and fix cable jointing kit for 11 KV grade (E) cable for indoor termination cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured Aluminium conductor cable of size 95 sqmm all as directed. | 3 | Each | - | - |
| 9 | Supply and fix cable jointing kit for 11 KV grade (E) cable for straight through cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured Aluminium conductor cable of size 95 sqmm all as directed. | 3 | Each | - | - |
| 10 | Taking down existing Four Pole Structure Complete all as directed by Engineer-in-charge. | 1 | Each | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.40 MB
Tender69.pdf
Tender Documents • 2.31 MB
BOQ_896282.xls
BOQ • 0.65 MB
TD6.pdf
Additional Documents • 0.22 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .