Loading…
Loading…
Tender Value
₹61.5 Cr
Closing Date
16 Jul 2026, 6:00 pmClosed
Chief Engineer (SD&P), DGVCL, Corporate Office
Tender for Fully Turnkey Contract Work for Supply, Laying, Installation, Testing & Commissioning of 11KV Underground cable , Transformers, Ring Main Unit (RMU) with dismantling work of existing TC-DODP/Pole and crediting at GIDC Area, Umargam, Dist.-Valsad (Gujarat) under Umargam sub division, Vapi Industrial Division in A.I.I.-SI Scheme.
305142
DGVCL/SD&P/Umargam/202604
Open
Electrical
Turn-key
Surat
10 documents required · 10 mandatory
₹11,800
DGVCL, Surat
15 May 2026
15 May 2026
27 Jul 2026
15 May 2026
8 Jun 2026
15 May 2026
Particulars of Item Unit Qty. In Rs.
H.T Supply Portion
Supply of 11/0.433KV three Phase 800KVA (Copper Wound) Star-
1 1 (Level-1) rated CRGO Cold Distributed transformer as per Nos. 35
DGVCL technical Specification
Supply of 11/0.433KV three Phase 1000KVA (Copper Wound) Star-
2 1 (Level-1) rated CRGO Cold Distributed transformer as per Nos. 49
DGVCL technical Specification
Supply of 11/0.433KV three Phase 1250KVA (Copper Wound) Star-
3 1 (Level-1) rated CRGO Cold Distributed transformer as per Nos. 32
DGVCL technical Specification
Supply of 11KV, 630 Amp, Scada Compatible RRL Type -3 Way
(i.e 2 Nos. of Isolator and 1 Nos. of Breaker ) Ring Main Unit
including all accessories (i.e. Earthing material for RMU side,
indoor termination kit etc) as per DGVCL Technical Specification.
Including 2nos. of Earthing. Eathing as per drawing. (All Material
is under Bidder Scope )
Supply of 11KV, 630 Amp, Scada Compatible RRR Type -3 Way
(i.e 3 Nos. of Isolator ) Ring Main Unit including all accessories
5 (i.e. Earthing material for RMU side, indoor termination kit etc) as Nos. 0
per DGVCL Technical Specification. Including 2nos. of Earthing.
Eathing as per drawing. (All Material is under Bidder Scope )
Supply of 11KV, 630 Amp, Scada Compatible RRLL Type -4 Way
(i.e 2 Nos. of Isolator and 2 Nos. of Breaker ) Ring Main Unit
including all accessories (i.e. Earthing material for RMU side,
indoor termination kit etc) as per DGVCL Technical Specification.
Including 2nos. of Earthing. Eathing as per drawing. (All Material
is under Bidder Scope )
Supply of 11KV, 630 Amp, Scada Compatible RRRL Type -4 Way
(i.e 3 Nos. of Isolator and 1 Nos. of Breaker ) Ring Main Unit
including all accessories (i.e. Earthing material for RMU side,
indoor termination kit etc) as per DGVCL Technical Specification.
Including 2nos. of Earthing. Eathing as per drawing. (All Material
is under Bidder Scope )
Supply of 11KV 3C 240mm2 XLPE Under Ground cable as per
DGVCL Technical Specification
Supply of 11KV 3C 185mm2 XLPE Under Ground cable as per
DGVCL Technical Specification
H.T Labour Portion
Particulars of Item Unit Qty. In Rs.
Installation, Testing, Commissioning of 11/0.433KV three Phase
800KVA (Copper Wound) Star-1 (Level-1) rated CRGO Cold
1 Distributed transformer as per DGVCL technical Specification (all Nos. 35
the related materials are under Scop of Bidder- including 2 Nos.
of Maintenance free Earthing and H.T and L.T Side Termination)
Construction of plinth/ Foundation for11/0.433KV three Phase
800KVA (Copper Wound) Star-1 (Level-1) rated CRGO Cold
2 Distributed technical specification and Drawing. All required Nos. 35
material will be supplied by contractor. The Design should be
approved from structure Engineer.
Installation, Testing, Commissioning of 11/0.433KV three Phase
1000KVA (Copper Wound) Star-1 (Level-1) rated CRGO Cold
3 Distributed transformer as per DGVCL technical Specification (all Nos. 49
the related materials are under Scop of Bidder- including 2 Nos.
of Maintenance free Earthing and H.T and L.T Side Termination)
Construction of plinth/ Foundation for11/0.433KV three Phase
1000KVA (Copper Wound) Star-1 (Level-1) rated CRGO Cold
4 Distributed technical specification and Drawing. All required Nos. 49
material will be supplied by contractor. The Design should be
approved from structure Engineer.
Installation, Testing, Commissioning of 11/0.433KV three Phase
1250KVA (Copper Wound) Star-1 (Level-1) rated CRGO Cold
5 Distributed transformer as per DGVCL technical Specification (all Nos. 32
the related materials are under Scop of Bidder- including 2 Nos.
of Maintenance free Earthing and H.T and L.T Side Termination)
Construction of plinth/ Foundation for11/0.433KV three Phase
1250KVA (Copper Wound) Star-1 (Level-1) rated CRGO Cold
6 Distributed technical specification and Drawing. All required Nos. 32
material will be supplied by contractor. The Design should be
approved from structure Engineer.
Installation, Testing and commissioning of 11KV, 630 Amp, Scada
Compatible RRL Type -3 Way (i.e 2 Nos. of Isolator and 1 Nos. of
Breaker ) Ring Main Unit including all accessories (i.e. Earthing
material for RMU side, indoor termination kit etc) as per DGVCL
Technical Specification. Including 2nos. of Earthing. Eathing as
per drawing. (All Material is under Bidder Scope )
Construction of plinth for 11KV, 630 Amp, Scada Compatible RRL
Type -3 Way (i.e 2 Nos. of Isolator and 1 Nos. of Breaker) Ring
Main Unit as per DGVCL's technical specification mentioned in
drawing no: Drg. All required material will be supplied by
contractor. The Design should be approved from structure
Installation, Testing and commissioning of 11KV, 630 Amp, Scada
Compatible RRR Type -3 Way (i.e 3 Nos. of Isolator ) Ring Main
Unit including all accessories (i.e. Earthing material for RMU side,
indoor termination kit etc) as per DGVCL Technical Specification.
Including 2nos. of Earthing. Eathing as per drawing. (All Material
is under Bidder Scope )
Construction of plinth for 11KV, 630 Amp, Scada Compatible RRR
Type -3 Way (i.e 3 Nos. of Isolator ) Ring Main Unit as per
10 DGVCL's technical specification mentioned in drawing no: Drg. All Nos. 0
required material will be supplied by contractor. The Design
should be approved from structure Engineer.
Installation, Testing and commissioning of 11KV, 630 Amp, Scada
Compatible RRLL Type -4 Way (i.e 2 Nos. of Isolator and 2 Nos.
of Breaker ) Ring Main Unit including all accessories (i.e. Earthing
material for RMU side, indoor termination kit etc) as per DGVCL
Technical Specification. Including 2nos. of Earthing. Eathing as
per drawing. (All Material is under Bidder Scope )
Construction of plinth for 11KV, 630 Amp, Scada Compatible RRLL
Type -4 Way (i.e 2 Nos. of Isolator and 2 Nos. of Breaker ) Ring
Main Unit as per DGVCL's technical specification mentioned in
drawing no: Drg. All required material will be supplied by
contractor. The Design should be approved from structure
Installation, Testing and commissioning of 11KV, 630 Amp, Scada
Compatible RRRL Type -4 Way (i.e 3 Nos. of Isolator and 1 Nos.
of Breaker ) Ring Main Unit including all accessories (i.e. Earthing
material for RMU side, indoor termination kit etc) as per DGVCL
Technical Specification. Including 2nos. of Earthing. Eathing as
per drawing. (All Material is under Bidder Scope )
Construction of plinth for 11KV, 630 Amp, Scada Compatible RRRL
Type -4 Way (i.e 3 Nos. of Isolator and 1 Nos. of Breaker ) Ring
Main Unit as per DGVCL's technical specification mentioned in
drawing no: Drg. All required material will be supplied by
contractor. The Design should be approved from structure
Labour charge for horizontal drilling using Auger machine without
damage to surface road at max 2.0 mtrs depth & putting of
kg/cm2 , class-4,Green color, 110mm O.D. , 8.5mm thickness
H.D.P.E. pipe confirms to IS 4984-1987(3rd revision) and BIS
certification and laying of 11KV/22KV XLPE cable of size up to
mm2 in HDPE pipe, as per Site Condition (excluding cost of
pipe). The detail map obtained from HDD machine and excell
sheet(hard and soft copy) indicating the respective depth and
distance from adjacent landmark for each segment for HDD is
must required to be submitted. HDD to be carried out at depth
1.5 mtrs to 2.0 mtrs as per site conditions and as per instruction
Labour charge for excavation of cable trench of 400mm width x
1200mm depth, in any type of soil for laying of cable of size up to
240 mm2 (For additional cable 200 mm additional width shall be
considered i.e. half trench length is to be considered)
Labour charge for laying of 11kV / 22 kV XLPE Cable of size up to
240 mm2 & preparation of sand layer 100mm thick, in the cable
trench & covering the cable with 150 mm dia (Inner), thickness
25 mm, 1.0 meter long RCC half round muffs and providing and
fixing of 4inch width yellow colour polyethylene tape with printing
"CAUTION ELECTRIC CABLE BELOW" at 0.75 m depth from
ground surface after laying cable in trench. This will provide
indication that electric cable is passing underground so as to
protect cable from mechnical injuries, refilling the same, as per
Instruction of Engineer in Charge (EIC).
Providing & fixing concrete stone route marker of 300 mm width
x 150 mm thick x 650 mm height embedded in earth at least
mm below & 350 mm above ground level respectively at distance
approx 50 meters along the length of cable. The RCC concreting
(1:2:4)(all necessary maeterials will be in bidder's scope) of route
marker is to be carried out 300 mm width x 150 mm thick x
18 mm below ground level as per instruction of EIC. The route Nos. 425
marker should be with name of company with approved yellow
colour-DGVCL. The distance from marker to cable and cable
depth with feeder name etc., marked with arrow sign is to be
painted on it.The route marker is to be fixed at location near to
any fixed permanent location (not necessary to fix exact on top of
cable) as per instruction of EIC.
Labour work for RCC concreting on disputed location and
repairing of damage portion of road crossing for the work carried
out for roads crossing as well as concreting & muffing of ploes
including all materials (1:2:4)
Supply & fixing of heat shrink type end terminations
20 (outdoor/indoor) for 11kV 3C x 240 mm2 size XLPE cable as per Nos. 731
DGVCL technical specification
Supply & fixing of heat shrinkable straight through joint for 11kV
21 3C x 240 mm2 size XLPE cableas per DGVCL technical Nos. 50
Supply & fixing of heat shrink type end terminations
22 (outdoor/indoor) for upto 11kV 3C x 185 mm2 size XLPE cable as Nos. 309
per DGVCL technical specification
Labour charge for excavation of 2100mm long x 1200mm wide x
1200 mm deep joint pits for installation of 11kV / 22kV Straight
through joints as per instruction of engineer-in-charge & covering
the cable with 150 mm dia (Outer), thickness 25 mm, 1.0 meter
long RCC half round muffs & refilling same as per instruction of
Preparation and submission of 6 (six) copies, of complete layout
drawings with GIS mapping (with latest Version) as per actual
cable routing showing road crossing, HDPE pipe sleeving, jointing
locations, markers etc.
Providing and fixing of Sign Board at junction point Made out of
mm aluminium sheet size 750x300 mm (2.5 x 1ft) rectangle, as
per design, pre treated with phosphate process and acid etching
coated with one coat of epoxy primer and two coats of best
quality paints, refloctrorised with Hi-Intensity retro – reflective
sheeting as per the latest and frame fabricated from suitable size
iron angle. The Sign Board is to be fixed on the base prepared
from channel and bracing angles which is grouted by means of
cement concreting of 1:2:4 for size of 300 mm dia x 800 mm
height (500 mm to be grouted in ground). The details to be
displayed on sign board will be given by In-charge Engineer.
(a) Hi intensity Micro prismatic Grade
Providing & fixing of aluminium tag of size 250 mm (L) x 75 mm
(W) from 3 mm aluminium sheet along with 1.0 mm dia
aluminium binding wire for fixing of aluminium tag near end
26 termination joint at DP structure for identifyng the cable. The No. 165
details of feeder i.e. 11 / 22 KV with feeder name shound be
punched on the tag by letter punch of size 16 mm as per
instruction of In-charge Engineer.
Supply of 6.11kg/cm2 , class-4,Green color, 110mm O.D. ,
mm thickness H.D.P.E. pipe confirms to IS 4984 and BIS
certification for laying of underground 11KV / 22KV XLPE cable up
to 240 mm2 size.
Labour charge for erecting of 11kV / 22 kV XLPE cable of size up
to 240 mm2 on DP Structure with fixing of 02 Nos polymer cleats PerJob
on top and middle part.Polymer cleats, nut bolts etc. fixing
material to be provided by contractor.
Providing and fixing of pipe type earthing from 80 mm dia class-B
GI pipe with pit to be filled with salt & coke and construction of
chamber as per DGVCL Drg. No. dg /100 for DP and cable. The
earthing pit should be joined with cable by G.I. strip of size 1”
width & 2 mm thick. All material GI pipe, Coke, Salt etc will be
supplied by bidder.
DISMENTALLING OF TRANSFORMER CENTRE (8 MTR PSC POLE)
(WITH TRANSFORMER) WITH CREDITING OF FABRICATION &
30 TRANSFORMER AT STORE & STACKING OF POLE SAFELY ON Nos. 591
ROAD SIDE AND CREDITING TO DEPARTMENTAL STORE OR AS
PER INSTRUCTION OF ENGINEER IN CHARGE
DISMENTALLING OF TRANSFORMER CENTRE (8 MTR PSC POLE)
(WITHOUT TRANSFORMER) WITH CREDITING OF FABRICATION
31 AT STORE & STACKING OF POLE SAFELY ON ROAD SIDE AND Nos. 81
CREDITING TO DEPARTMENTAL STORE OR AS PER
INSTRUCTION OF ENGINEER IN CHARGE
DISMENTALING OF TRANSFORMER CENTER ON 10MTR,270KG
PSC POLE(WITHOUT TRANSFORMER) WITH CREDITING OF
FABRICATION AT STORE AND STACKING OF POLE SAFELY ON
ROAD SIDE OR CREDITING TO DEPARTMENTAL STOREROAD
SIDE AND CREDITING TO DEPARTMENTAL STORE OR AS PER
INSTRUCTION OF ENGINEER IN CHARGE
DISMENTALING OF TRANSFORMER CENTER ON 10MTR,270KG
PSC POLE(WITH TRANSFORMER) WITH CREDITING OF
33 FABRICATION AT STORE AND STACKING OF POLE SAFELY ON Nos. 0
ROAD SIDE AND CREDITING TO DEPARTMENTAL STORE OR AS
PER INSTRUCTION OF ENGINEER IN CHARGE
DISMENTALING OF RSJ (9/11 METER) POLE AND CREDITING
34 THE OLD MATERIAL TO DEPARTMENTAL STORE OR AS PER Nos. 437
INSTRUCTION OF ENGINEER IN CHARGE
Dismentalling of existing Dist.X'mer center(RSJ /STP POLE)
25/63/100/200 KVA with all fabrication & creditig the old material
CREDITING TO DEPARTMENTAL STORE OR AS PER
INSTRUCTION OF ENGINEER IN CHARGE
DISMENTALLING OF 8 MTR PSC POLE WITH CREDITING OF
FABRICATION AT STORE & STACKING OF POLE SAFELY ONROAD
SIDE AND CREDITING TO DEPARTMENTAL STORE OR AS PER
INSTRUCTION OF ENGINEER IN CHARGE
DISMENTALLING OF 10 MTR PSC POLE WITH CREDITING OF
FABRICATION AT STORE & STACKING OF POLE SAFELY ON
ROAD SIDE AND CREDITING TO DEPARTMENTAL STORE OR AS
PER INSTRUCTION OF ENGINEER IN CHARGE
Providing and fixing of FRP fencing of 1500mm height at
Distribution Transformer Centers with necessary excavation,
concreting for grouting vertical posts up to 450 mm in ground,
38 Hardware, accessories, fittings, lock, etc. complete as shown in RMT 2111.5
specifications and drawing enclosed. The fencing shall comprise
of one gate 2000 mm wide having two flaps and payment for the
same shall be measured on Rmt basis.
providing and fixing pre-cast rubber dye inter locking concrete
block 60 mm thick with grade of concrete M300 pneumatic
compressed/vibrated mechanically and as per approved design
confirming to IS 15658:2006 including 35 mm sand layer for
levelling and filling the joint with sand in proper line and level as
per guidelines of IRC:SP 63-2018 etc. complete.
Estimate Sheet for Umargam GIDC LT - Underground Cable Work
Particulars of Item Unit Qty. In Rs.
L.T Supply Side
LT XLPE Cable Supply of XLPE (IS:7098) (I) -88 ISI marked
1 Armoured cable multistrand aluminium conductor for 1.1 KV of
following Size of Cable
a 1C 300mm2 XLPE Cable Meter 4640
b 4C x 240 MM Aluminium Meter 1480
LT Cable Terminetion: Supply of Cable Termination on LT Pole,
FSP, LT Distribution Trasformer Box of pole mounted trasformer
of LT cable grade as specified below. LT CABLE including
cutting,stripping of cable,insulations,providing compression type
terminals,suitable cable glands,crimping lugs with necessary
connections.Work carried out up to consumer premises with
meter shifting, and provide load side cable as per site conditions
and as per EIC. All the accessories in the scope of biddier.
a 1C X 300mm2 XLPE Cable Nos. 1854
b 3.5C x 240 MM Aluminium Nos. 592
CABLE TERMINAL FERRULS: The PVC Cable terminal ferruls for
identification of phase sequence and feeder/PSS/FSP name of
HT/LT cables shall be provided at every termination of all cables
stating detail as under. HT Cable :Feeder name/Phase(R/Y/B) LT
Cable : TC/FSP name/Phase(R/Y/B/N). All the accessories in the
scope of biddier.
CABLE TAG: The PVC tag for identification of
feeder/PSS/FSP/RMU name of HT/LT cables shall be provided at
every 10 MTR HT feeder:station/Feeder LT Feeder :
PSS/Transformer/FSP
5 Supply of FSP as per technical specification attched Nos. 148
Supply of earthing strip 50 x 3 mm
G.I. strip for pole mounted transformer and upto FSP,MSP,SFU,
6 Busbar Etc as well as connection to be made to the earth pit. Meters 1480
Rates inclusive of hot dipped hardwares. All the accessories in the
scope of biddier.
Suppy of Busbar Chamber-100 Amp switch fuse unit made by
metal box and capacity of 250 A, Mostaly used in flat/Socity area.
Installation worked caried out with instruction of EIC. And as per
the drawing approved by CA- Minimum 16 Nos. of CKT ( As per
Technical specification), All the accessories in the scope of
L.T Labour Side
Sr. Unit Cost In Rs. (with
Particulars of Item Unit Qty.
LT XLPE CABLE providing erection and XLPE (IS:7098) (I) -88 ISI
marked armoured cable multistrand aluminium conductor 1.1kv to
be laid by diging cable trench method of following size cable in
a 3.5C x 300 MM Aluminium Meter 2060
b 3.5C x 240 MM Aluminium Meter 6180
Warning Tap: For laying on trench after laying cable on trench to
2 provide cable route below land surface in underground trench to Meter 0
protect cable for mechenical injuries
LT Cable Termination: Cable Termination on LT Pole, FSP, LT
Distribution Trasformer Box of pole mounted trasformer of LT
cable grade as specified below. LT CABLE including
cutting,stripping of cable,insulations,providing compression type
terminals,suitable cable glands,crimping lugs with necessary
connections.Work carried out up to consumer premises with
meter shifting, and provide load side cable as per site conditions
and as per EIC.
a 1C x 300 MM Aluminium Nos. 824
b 3.5C x 240 MM Aluminium Nos. 1648
CABLE TERMINAL FERRULS: The PVC Cable terminal ferruls for
identification of phase sequence and feeder/PSS/FSP name of
4 HT/LT cables shall be provided at every termination of all cables Nos 2472
stating detail as under. HT Cable :Feeder name/Phase(R/Y/B) LT
Cable : TC/FSP name/Phase(R/Y/B/N)
CABLE TAG: The PVC tag for identification of
feeder/PSS/FSP/RMU name of HT/LT cables shall be provided at
every 10 MTR HT feeder:station/Feeder LT Feeder :
PSS/Transformer/FSP
Installation, Comissioning and Testing of FSP as per technical
6 specification attched. Erection shall be carried out as per Nos. 148
approved drawing and site condition.
Instalation, Testing, Commissioning Busbar Chamber switch fuse
unit made by metal box and capacity of 250 A, Mostaly used in
flat/Socity area.
Installation worked caried out with instruction of EIC. And as per
the drawing approved by CA- Minimum 16 Nos. of CKT ( As per
Technical specification)
Supply, Installation, Testing and commissioning erecting earth pit
of minimum bore dia. 150 mm size approved make safe Earthing
Electrode consisting Pipe in pipe Technology as per IS 3043-1987
made of corrosion free G.I. Pipes having Outer pipe dia of 48 mm
having 80-200 Micron galvanising connections, terminal dia of
mm with constant ohmic value surrounded by highly conductive
compound with high charge dissipation with civil works of
earthing chamber. For Electrical installation covering Transformer
neutrals,HT & LT switchgears for independent earthing in normal
soil, Length of Pipe 2/3 mtrs.Backfilling compound 2 bags of
Kg each. ( As per technical specification and drawing .)
2000 MM electrode Nos. 0
3000 MM electrode Nos. 296
intstallation, Supply, Installation, Testing and commissioning of
a 40mm/32mm Meter 0
b 90mm/75 mm Meter 0
Lt cable saddling works: Direct cable saddleing with wall and etc
this work GI type saddle and nail shall be used.
installation & commissioning of earthing conductor 50 x 3 mm
G.I. strip for pole mounted transformer and upto
FSP,RMU,MSP,SFU, Busbar Etc as well as connection to be made
to the earth pit. Rates inclusive of hot dipped hardwares.
Paint Pointed Letter 2 inch size(Marking on RMU,
12 Transformer, FSP, MSP, SFU Etc In any palce.(As per directive of Ea 2000
Engineer Incharge) with supply of color
Dismentaling & removing of service line from pole & crediting to
Dismentaling & removing of service line from pole & crediting to
Total Cost (Supply+Labour)
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
Final Re tender NIT- Turnky base Tender Umargam GIDC.pdf
DGVCL 11KV RMU Tech Spec.pdf
R2 TS_LT Feeder Pillar.pdf
Tech. Speci. LT Cable.pdf
Tech. Speci. XLPE UG Cable.pdf
Technical Specification 800kVA-1000kVA and 1250kVA DTR.pdf
Technical Specificatioof End Termination St. joint and HDPE Pipe.pdf
Earthing. Drawing .pdf
High rated TC Plinth_LT Feeder Pillar and RMU Plinth Drawing.pdf
Tender Schedule B for Umargam GIDC Project.pdf
Final Corrigendum-3_Umargam-AII_Tender_202604.pdf
CORRIGENDUM
Final Revised Tender Schedule B for Umargam GIDC Project .pdf
CORRIGENDUM
Sign Corrigendum-2_Umargam Tender.pdf
CORRIGENDUM
Earthing. Drawing .pdf
CORRIGENDUM
Tender Schedule B for Umargam GIDC Project.pdf
CORRIGENDUM
High rated TC Plinth_LT Feeder Pillar and RMU Plinth Drawing.pdf
CORRIGENDUM
Final Re tender NIT- Turnky base Tender Umargam GIDC.pdf
CORRIGENDUM
Final Corrigendum-1_Umargam-AII_Tender_202604.pdf
CORRIGENDUM
DGVCL 11KV RMU Tech Spec.pdf
CORRIGENDUM
R2 TS_LT Feeder Pillar.pdf
CORRIGENDUM
Tech. Speci. LT Cable.pdf
CORRIGENDUM
Tech. Speci. XLPE UG Cable.pdf
CORRIGENDUM
Technical Specification 800kVA-1000kVA and 1250kVA DTR.pdf
CORRIGENDUM
Technical Specificatioof End Termination St. joint and HDPE Pipe.pdf
CORRIGENDUM
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .