Office of the Assisstant Executive Engineer PWD Electrical Subdivision Thalassery
GENERAL-Live Stock Management Training Centre Kannur-Electrification- Balance worksGeneral Electrical Work
2023_PWD_622658_3
PWD/BLDG/TR/985/2022_6_1_1/1
Open Tender
Electrical Works
Item Rate
120 days
Kannur
Please refer Tender documents.
7 documents required · 7 mandatory
₹2,205
₹24,977
22 Dec 2024
13 Jun 2024
22 Jun 2024
13 Jun 2024
19 Jun 2024
13 Jun 2024
Amount
SITC of 30kVA DG
OD113054/2021-2022:Supply, Loading, Conveyance, Unloading, Erection, Testing and Commissioning of 30 KVA capacity Diesel Generator set with AMF and integral acoustic enclosure as per latest CPCB norms with slandered accessories as per technical details given below. 1. Engine : a) Make of Engine - As specified in materials list b) Type of Engine - Diesel Engine c) No. of Cylinders - As per manufactures standards. d) Method of Cooling - Water cooled with radiator. e) Design - Suitable for generating set operation 2.Standard accessories with Diesel Engine a) Fly wheel to suit flexible coupling b) Close Coupling c) Air cleaner d) Radiator with fan provided with fan guard. e) Fuel Pump f) Fuel filter g) Lubricating oil filter h) Exhaust silencer i) Exhaust Muffler j) Battery Charger/Generator 3. Engine Instrument Panel with the following items a) Starting switch with key or button b) Lubricating oil pressure gauge. c) Water temperature gauge. d) RPM Indicator with hour meter e) Battery charging Ammeter 4. Safety Controls for Engine a) Trip for low lubricating oil pressure b) Trip for high water temperature. 6. Brush less Alternator a) Make -As specified in material list b) Type - Self exited and self regulated. c) System of Voltage - 3 phase, 415 V, d) Frequency - 50 Hz e) Insulation - Class F/H The Alternator should confirm to IS 4722. Operation and service manual, spares and tools shall be provided. 7. Fuel Tank Suitable size built in type integrated with the acoustic enclosure Fuel connection shall be done as per standards 8. Battery Suitable size built in type integrated battery with leads and terminals of appropriate AH capacity as per Manufactures requirement. Automatic Battery charger Solid state phase indication lamp for supply ON/OFF with HRC protection. standard control panel as per Kerala Electrical Inspectorate requirements and accessories such as Multi function meter and separate Energy meter etc. Complete. The DG set shall have a warrantee period of 3 years and 3 year AMC from date of commissioning. (10) First Full fill of Lubrication Oil & Diesel.
14.1:Excavation for foundation in soft soil including dressing of sides and ramming of bottoms, lift upto 1.5 m including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 metres.
14.9:Providing and laying in position cement concrete 1 :3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size) in foundation of pump, DG set etc. including form work etc. as required.
90.12.5.41:Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.4 core 16 sq mm
90.12.7.41:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 16 sq mm with factory made clamp
90.12.10.2:Supply & laying of DWC pipe in ordinary soil 0.75m below ground level including excavation50/38 mm or nearest size
90.16.1.5:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required4.75 mm copper conductor (6 SWG)
90.16.5.5:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.4.75 mm (6 SWG)
9.1.33:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 16 sq. mm (28mm)
5.4:Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
OD113168/2021-2022:Supply and providing earth lead from the test joint to the earth electrode using the following sizes of conductors/ strips including cutting, drilling necessary holes (in case of strip) and fixing firmly with plate test joint etc as required. 25 mm X 5 mm G.I. strip
OD113169/2021-2022:Supply and providing the following sizes of bolt and nut with washers on the existing MS box / earth bus etc. as required including drilling necessary holes as required a) 25x6mm brass bolt with hexagonal/square head, nut and washer
OD113170/2021-2022:Supply and providing test joint for the earthing system using 2 Nos of the following sizes of strips including cutting and bending to shape, drilling necessary holes and fixed to the watering pipe etc as required. 2 x 25 x 5 mm GI strip
OD113174/2021-2022:Supply , loading and conveyance of HSD for full load testing of DG.
OD113191/2021-2022:Supply and providing the following size of B class MS pipe conforming to relevant IS specifications complete with heavy gauge specials such as bends, flanges etc welded and fixed at appropriate locations, providing cork sheet in between the flanges at the joints, bolting the flanges together, painting the pipe, flange etc with 2 coats of heat resistant paint suitable for outdoor applications, fixing the pipe firmly with fabricated structure/wall/any other mechanical support etc as required.- 80/75 mm dia B class MS pipe as extended exhaust pipe.
90.14.5:Supply and fabrication conveyance and installation of angle iron frame work for wall mounting panel board
OD113202/2021-2022:Supply and installation of ABC type fire extinguisher of 5 kg. Capacity complete with initial charges and installation brackets confirming to IS 15683 with ISI mark
OD113232/2021-2022:Supply and providing 2.5mm thick Elastomeric fire retardent insulating mat as per IS 15652/2006 to withstand 11 KV dielectric strength including fixing with suitable synthetic adhesive
OD129444/2023-2024:Charges for preparation of fire drawing per A3 sheets first copy
OD129443/2023-2024:copying charges for A3 sheets
Balance of Electrification work
1.10.3:Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.Group C
OD128811/2023-2024:Supply ,Conveyance, installation, testing and commissioning of 6.5 W LED Bulkhead Light fittings Lumen output - 600, Housing - High pressure die cast aluminum directly on wall including giving connections with required length of 16/0.20mm 3 core round copper conductor flex wire conforming to relevant ISS or with the extended original wiring, making good the damages, colour washing etc as required.(PHILIPS Vista Glow 6.5 Watts Square Bulkhead Wall Lamp/equivalent)
OD128838/2023-2024:Supply , conveyance , installation and testing of recess mounting down light fittings 4200 lumen square (2ft X 2ft) recessed fitting made of crca sheet of thickness 0.5mm, having efficacy not less than 110l/w, pf greater than 0.95, THD less than or equal to 10%, Chip make Cree/Osram/lumilled/Nichea (UGR less than 19)all types complete with all accessories in the existing opening of false ceiling, giving connections with the existing wire etc., as required.
OD129215/2023-2024:Supply , conveyance , installation and testing of recess mounting down light fittings 1200 lumen round recessed fitting made of crca sheet of thickness 0.5mm, having efficacy not less than 110l/w, pf greater than 0.95, THD less than or equal to 10%, Chip make Cree/Osram/lumilled/Nichea (UGR less than 19)all types complete with all accessories in the existing opening of false ceiling, giving connections with the existing wire etc., as required.
OD129216/2023-2024:Supply , conveyance , installation and testing of recess mounting down light fittings 2000 lumen square (1ft X 1ft) recessed fitting made of crca sheet of thickness 0.5mm, having efficacy not less than 110l/w, pf greater than 0.95, THD less than or equal to 10%, Chip make Cree/Osram/lumilled/Nichea (UGR less than 19)all types complete with all accessories in the existing opening of false ceiling, giving connections with the existing wire etc., as required.
90.4.1:Supply and installation of suitable size MS rod type fan clamp in the RCC slab as per IS 732 as required.
90.4.5.4:Supply, Installation, testing and commissioning of ceiling fan of following sizes including wiring the down rods of standard length (up to 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable etc. as required. 1200mm sweep - ceiling fan complete with service value minimum 4.0(cub meter/minute/Watt), Air delivery minimum 210(cubic meter/minute), Copper winding suitable for 230V/240V single phase AC supply
90.10.1.3:Supply & Fixing the following types/ sizes of boxes suitable for modular accessories in surface/ recess including making good the damages, colour washing etc as required (RoHS compliant )3 module moulded plastic box on surface
1.24.1:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 amps switch
1.24.4:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.3 pin 5/6 amp socket outlet
1.28.2:Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.3 Module
90.11.1.14:Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required4 way (8+12) - double cover TPN vertical DB with provision for fixing 4P MCB / Isolator/ RCCB/ RCBO as incomer and SP/ TP MCB as outgoing (IP 42/43)
90.11.1.19:Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required6 way (8+12) - double cover TPN vertical DB with provision for fixing MCCB as incomer and SP/ TP MCB as outgoing (IP 42/43)
2.3.2:Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCBIRCCB/Isolator8 way, Double door
2.10.1:Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole
2.10.4:Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Triple pole
2.11:Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.
2.12.1:Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.14.1:Supplying and fixing following rating, double pole, (single phase and neutral), 240 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.25 amps
2.13.1:Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.15.2:Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
90.12.7.28:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 35 sq mm with factory made clamp
90.12.7.31:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 95 sq mm
90.12.7.40:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 10 sq mm with factory made clamp
9.1.21:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 35 sq. mm (32mm)
9.1.24:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 95 sq. mm (45mm)
9.1.32:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 10 sq. mm (25mm)
9.1.20:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X25 sq.mm (28mm)
90.16.1.3:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required3.15 mm copper conductor ( 10 SWG)
90.16.1.2:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required2.65 mm copper conductor (12 SWG)
90.16.5.2:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.2.65 mm (12 SWG)
90.16.5.3:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.3.15 mm (10 SWG)
1.21.1:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm
1.21.2:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm
1.17.3:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 X 1.5 sq.mm
1.17.12:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 2.5 sq. mm
1.17.21:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 4 sq. mm
1.17.23:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.5 x 4 sq. mm
1.17.31:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.4 x 6 sq. mm
90.6.5.11:Supply and drawing the following sizes of multi-core PVC insulated & FRLS PVC sheathed 650/1100 V grade copper conductor round flexible cables conforming to IS 694 part I 1960 in the existing surface / recess conduit as required including giving necessary connections of the following sizes.3 core 1.50 sq mm
1.48:Supplying and fixing extra conduit down rod of 20 cm length G.I. pipe 15 mm dia, heavy gauge including painting etc. as required. (Note : More than 5 cm length shall be rounded to the nearest 10 cm and 5 cm or less shall be ignored)
2.16:Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32amps 240 volts "C" curve DP MCB complete with connections, testing and commissioning etc. as required.
OD128827/2023-2024:Supplying and fixing FP sheet steel enclosure on surface/ recess along with 40amps 415 volts Isolator complete with connections, testing and commissioning etc. as required.
90.10.3.15:Supply and Fixing the following modular switches & accessories in the existing front plates and giving necessary connections as required (RoHS compliant )32A DP switch with indicator
90.10.3.32:Supply and Fixing the following modular switches & accessories in the existing front plates and giving necessary connections as required (RoHS compliant )25A 3 pin plug top with indicator
90.10.3.33:Supply and Fixing the following modular switches & accessories in the existing front plates and giving necessary connections as required (RoHS compliant )25A 3pin Shuttered socket
90.14.1.2:Fabrication, supply, conveyance, installation testing and commissioning of floor or wall mounting, dust and vermin proof, cubicle type MV panel board comprising of the following components/ devices & complying to IS 8623.<br> Fabrication of fully partitioned, dust and vermin proof enclosure for panel assembly as per form 4 of IS 8623 (with latest amendments) using CRCA sheet as per approved design and requirement, with front and rear access facility, bus bar chambers, hinged doors for all switch gear compartments, earthing the doors using 4 sq mm braided copper conductor, providing necessary cut-outs for mounting meters, relays, indication lamps, bus bar interconnection etc, detachable covers for bus bar chamber and cable alley, powder coating the assembly after subjecting to 7 tank process etc as required. CRCA sheet alone be used for the fabrication. Angles/ flats/ slotted angles etc shall not be used for the fabrication of panel assembly. The measurments will be taken the area of the complete sheets used for panel board including partitions, folding, shrouding etc.Supply and fabrication of MV panel board using 1.6mm CRCA sheet, powder coated (excluding base frame)
90.14.2.1:Supply and providing 2mm SMC sheet as shrouding for bus interconnection / terminations etc. including required nut & bolt etc.
90.14.3.1:Supply and providing heavy duty 'A' section neoprene gasket in the panel boardA' section neoprene beeding suitable for 1.60/ 2.00 mm sheet
90.14.5:Supply and fabrication conveyance and installation of angle iron frame work for wall mounting panel board
90.14.6:Supply and providing copper bus bars including finger type SMC bus bar supports in the bus chamber, suitable size nut & bolt, providng heat shrink sleeves etc. as required.
90.14.7:Supply and providing copper earth bus in the panel board
OD128830/2023-2024:Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.125A, 18 kA (Ics=100%Icu), 4 pole, current limiting type MCCB with thermal release with overload setting of 80 - 100% having adjustable OL & SC
90.14.10.3:Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.16 A-100A, 16 kA (Ics=100%Icu), 4 pole, current limiting type MCCB having thermal setting range of 80 - 100% with thermal magnetic release having adjustable OL
OD128832/2023-2024:Providing and fixing 63A, TPN switch disconnector unit inside the existing panel board including drilling holes in cubicle panel, making connections, etc. as required.
90.14.11.13:MCCB AccessoriesSupply and fixing rotary handle, External type (including BUC handle with door interlock ) in the existing MCCB of rating up to 250 A
OD128834/2023-2024: Supply and fixing 2A, HRC Fuse with HRC Fuse link with connections, in existing meter board
OD128835/2023-2024:Supply and providing Red, Green, Black, Yellow, Orange colours LED indicators, AC/DC 22.5mm cut out dia
OD128836/2023-2024:Supply and providing Blue colour LED indicators, AC/DC 22.5mm cut out dia
2.21:Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required.
OD128837/2023-2024:Providing and fixing following capacity TP&N disconnector fuse switch unit with enclosure and front handle with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required.125 Amp TP & N
Bidder Name
G S ELECTRICALS
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_1050915.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .