Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹39.9 LAccepted-AOC CHANGANACHERRY GENERAL ELECTRICAL WORK | ERNAKULAM | KERALA | 682001 | 1 | Accepted-AOC L1 | |
| 2 | 2₹46.0 L+₹6.1 L (15.4%)Rejected-AOC KRISHNAKRIPA KOTTARAKARA | 2 | Rejected-AOC L2 |
Tender Value
₹43.5 L
EMD Value
₹50,000
Closing Date
11 Mar 2024, 6:55 pmClosed
Chief Electrical Engineer
O/o The Chief Electrical Engineer, PWD Electrical Wing, Public Office, Thiruvananthapuram
DEPOSIT District Public Service Commission Office Kottayam Providing Additional Electrical Requirements and setting up of Online Examination Hall Basement Floor and providing Transformer and DG Set HT Electrical Work
2024_PWD_667855_1
PWD/BLDG/TR/18323/2023_26_1_1
Open Tender
Electrical Works
Item Rate
180 days
Public Service Commission Office Kottayam
Please refer Tender documents.
7 documents required · 7 mandatory
₹2,760
₹50,000
Yes
20 Jun 2024
6 Mar 2024
13 Mar 2024
6 Mar 2024
11 Mar 2024
6 Mar 2024
6 Mar 2024 - 11 Mar 2024
Amount
Electrification of cellar floor & SITC of 160KVA Transformer
1.10.3:Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.Group C
1.33:Supplying and fixing 3 pin, 5 amp ceiling rose on the existing junction box/ wooden block including connection etc as required.
90.4.5.4:Supply, Installation, testing and commissioning of ceiling fan of following sizes including wiring the down rods of standard length (up to 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable etc. as required. 1200mm sweep - ceiling fan complete with service value minimum 4.0(cub meter/minute/Watt), Air delivery minimum 210(cubic meter/minute), Copper winding suitable for 230V/240V single phase AC supply
1.25:Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required.
90.3.20.3:Supply & installation of light fittings on TW round block Supply, conveyance installation testing and commissioning the light fittings of following types made of CRCA with 0.5mm thickness complete with all accessories and lamps etc. directly on wall or ceiling with PVC round block neatly painted to suit the fitting and giving connection with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS and giving connections as required.1200 mm 1X20W LED Lamp with box type fixture
OD221993/2023-2024:Supply and fixing LED Bulk head with IP65 protection, 700 lm, Luminous Efficacy): 107 lm/W suitable for surface and wall mounting application including giving connection etc as required -
90.4.1:Supply and installation of suitable size MS rod type fan clamp in the RCC slab as per IS 732 as required.
1.48:Supplying and fixing extra conduit down rod of 20 cm length G.I. pipe 15 mm dia, heavy gauge including painting etc. as required. (Note : More than 5 cm length shall be rounded to the nearest 10 cm and 5 cm or less shall be ignored)
OD146726/2023-2024:Supply, conveyance, installation , testing and commissioning of exhaust fans of size 300/305 mm sweep Light Duty Exhaust fan in metal frame working on 230 V A/C in the existing opening, fixing necessary anchor bolts / bolt and nuts etc., as required including giving connections with the supplied wire along with the exhaust fan.
90.4.8:Charges for cutting holes suitable for accommodating exhaust fans up to 305mm sweep including plastering colour washing etc. as required.
1.27.1:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.1 or 2 Module (75mmX75mm)
1.27.2:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.3 Module (100mmX75mm)
1.27.4:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.6 Module (200mmX75mm)
1.27.5:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.8 Module (125mmX125mm)
90.10.1.5:Supply & Fixing the following types/ sizes of boxes suitable for modular accessories in surface/ recess including making good the damages, colour washing etc as required (RoHS compliant )6 module moulded plastic box on surface
90.10.1.6:Supply & Fixing the following types/ sizes of boxes suitable for modular accessories in surface/ recess including making good the damages, colour washing etc as required (RoHS compliant )8 module moulded plastic box on surface
1.28.4:Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.6 Module
1.28.5:Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.8 Module
1.24.1:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 amps switch
1.24.3:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.15/16 amp switch
90.10.3.14:Supply and Fixing the following modular switches & accessories in the existing front plates and giving necessary connections as required (RoHS compliant )25A SP switch with indicator
90.10.3.15:Supply and Fixing the following modular switches & accessories in the existing front plates and giving necessary connections as required (RoHS compliant )32A DP switch with indicator
1.24.4:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.3 pin 5/6 amp socket outlet
1.24.5:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.6 pin 15/16 amp socket outlet
90.10.3.33:Supply and Fixing the following modular switches & accessories in the existing front plates and giving necessary connections as required (RoHS compliant )25A 3pin Shuttered socket
1.21.1:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm
1.21.2:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm
1.17.3:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 X 1.5 sq.mm
1.17.5:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.5 X 1.5 Sq. mm
1.17.6:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.6 x 1.5 sq. mm
1.17.7:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.7 x 1.5 sq. mm
1.17.9:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.9 x 1.5 sq. mm
1.17.10:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.10 x 1.5 sq. mm
1.17.12:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 2.5 sq. mm
1.17.15:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.6 x 2.5 sq. mm
1.17.18:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.9 x 2.5 sq. mm
1.17.21:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 4 sq. mm
1.17.22:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.4 x 4 sq. mm
1.17.23:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.5 x 4 sq. mm
1.17.24:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.6 x 4 sq. mm
1.17.31:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.4 x 6 sq. mm
2.10.1:Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole
2.10.4:Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Triple pole
2.12.1:Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.13.1:Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.13.2:Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps
2.14.1:Supplying and fixing following rating, double pole, (single phase and neutral), 240 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.25 amps
2.15.1:Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.25 amps
2.15.2:Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.15.3:Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps
2.3.2:Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCBIRCCB/Isolator8 way, Double door
90.11.1.11:Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required6 way (8+18) - three phase double cover (IP 42/43)
90.11.1.10:Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required4 way (8+12) - three phase double cover (IP 42/43)
90.11.1.15:Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required6 way (8+18) - double cover TPN vertical DB with provision for fixing 4P MCB / Isolator/ RCCB/ RCBO as incomer and SP/ TP MCB as outgoing (IP 42/43)
90.9.1.1:Supply and fixing 50 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.50x50mm Cable Management System with base and lid
90.9.1.2:Supply and fixing 50 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.External angle 90 degree
90.9.1.3:Supply and fixing 50 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.Flat angle 90 Degree /Tee
90.9.1.4:Supply and fixing 50 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.Internal angle 90 degree
90.9.1.7:Supply and fixing 50 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.End cap
90.9.1.10:Supply and fixing 50 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.Cable retainer
90.9.1.16:Supply and fixing 50 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.Flat tee
90.9.2.1:Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.100 x 50 mm CMS with base and lid
90.9.2.2:Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.Cable devider
90.9.2.3:Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.External angle 90 degree
90.9.2.4:Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.Flat angle 90 degree
90.9.2.5:Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.Internal angle 90 degree
90.9.2.8:Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.End cap
90.9.2.11:Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.Cable retainer
90.9.2.24:Supply and fixing 100 x 50 mm PVC Cable Management System with base and lid along with the following accessories conforming to IEC 61084/ BS 476 & 4678 on surface / recess including cutting the wall and making good the damages in case of recessed installation as required.Flat Tee
90.14.1.2:Fabrication, supply, conveyance, installation testing and commissioning of floor or wall mounting, dust and vermin proof, cubicle type MV panel board comprising of the following components/ devices & complying to IS 8623. Fabrication of fully partitioned, dust and vermin proof enclosure for panel assembly as per form 4 of IS 8623 (with latest amendments) using CRCA sheet as per approved design and requirement, with front and rear access facility, bus bar chambers, hinged doors for all switch gear compartments, earthing the doors using 4 sq mm braided copper conductor, providing necessary cut-outs for mounting meters, relays, indication lamps, bus bar interconnection etc, detachable covers for bus bar chamber and cable alley, powder coating the assembly after subjecting to 7 tank process etc as required. CRCA sheet alone be used for the fabrication. Angles/ flats/ slotted angles etc shall not be used for the fabrication of panel assembly. The measurments will be taken the area of the complete sheets used for panel board including partitions, folding, shrouding etc.Supply and fabrication of MV panel board using 1.6mm CRCA sheet, powder coated (excluding base frame)
90.14.2.1:Supply and providing 2mm SMC sheet as shrouding for bus interconnection / terminations etc. including required nut & bolt etc.
90.14.3.2:Supply and providing heavy duty 'A' section neoprene gasket in the panel boardU' section rubber beeding suitable for 1.60/ 2.00 mm sheet
90.14.4:Supply and fabrication conveyance and installation of base frame of panel board using 75 x 40 mm rolled steel channel (ISMC)
90.14.5:Supply and fabrication conveyance and installation of angle iron frame work for wall mounting panel board
90.14.6:Supply and providing copper bus bars including finger type SMC bus bar supports in the bus chamber, suitable size nut & bolt, providng heat shrink sleeves etc. as required.
90.14.7:Supply and providing copper earth bus in the panel board
OD146582/2023-2024:Supply and providing Panel mounting fresh air fan150 mm as required.
OD148316/2023-2024:Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required. 250A, 4 pole, MCCB with Isolation Duty.
OD221994/2023-2024:Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required. 125A 25/36KA (Ics=100%Icu), 4 pole, current limiting type MCCB having thermal setting range of 80 - 100% with thermal magnetic release having adjustable OL .
90.14.10.4:Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.16 A-100A, 25/35 kA (Ics=100%Icu), 4 pole, current limiting type MCCB having thermal setting range of 80 - 100% with thermal magnetic release having adjustable OL
OD148446/2023-2024:Supply and installation of switch gear units in existing enclosure complete with handle assembly, door interlock and pad locking arrangement of 100A 4 pole on-load COS AC 23A duty
OD222348/2023-2024:Supply and fixing one set of spreader/ terminal adapter kit Extended terminal for 4 pole MCCB of rating 200 A & 250 A (8 Pcs),
OD222349/2023-2024:Supply and fixing one set of spreader/ terminal adapter kit Extended terminal for 4 pole MCCB of rating up to 100A (8 Pcs)
OD148317/2023-2024:Supply and fixing one number 250 A (AC1 rating), 4 pole, power contactor with AC coil & with 2 NO & 2 NC auxiliary contacts in the existing panel assembly as required
90.14.11.12:MCCB AccessoriesSupply and fixing shunt release for all voltage range up to 630A.
90.14.11.13:MCCB AccessoriesSupply and fixing rotary handle, External type (including BUC handle with door interlock ) in the existing MCCB of rating up to 250 A
90.14.24.2:Supply & fixing the following Power Capacitors 3 phase delta connected in positon and giving connection.2 KVAr, 3 phase, 440 V, delta connected standard duty Metalised Poly Propylene Capacitor, Cylinderical Type, suitable for direct connection to motors.
90.14.24.3:Supply & fixing the following Power Capacitors 3 phase delta connected in positon and giving connection.3 KVAr, 3 phase, 440 V, delta connected standard duty Metalised Poly Propylene Capacitor, Cylinderical Type suitable for direct connection to motors.
90.14.24.31:Supply & fixing the following Power Capacitors 3 phase delta connected in positon and giving connection.5 KVAr, 3 phase, 440 V, Metalised Poly Propylene Heavy duty Cylindrical Gas filled Capacitor suitable for APFC panel without block reactor.
90.14.24.34:Supply & fixing the following Power Capacitors 3 phase delta connected in positon and giving connection.10 KVAr, 3 phase, 440 V, Metalised Poly Propylene Heavy duty Cylindrical Gas filled Capacitor suitable for APFC panel without block reactor.
OD148333/2023-2024:Supply and fixing 3 pole, capacitor duty contactor with AC coil for switching capacitor banks of rating 2 - 3 KVAR & with 1 NO auxiliary contact in the existing panel assembly as required.
OD146587/2023-2024:Supply and fixing 3 pole, capacitor duty contactor with AC coil for switching capacitor banks of rating 5 KVAR & with 1 NO auxiliary contact in the existing panel assembly as required.
OD146588/2023-2024:Supply and fixing 3 pole, capacitor duty contactor with AC coil for switching capacitor banks of rating 10 KVAR & with 1 NO auxiliary contact in the existing panel assembly as required.
OD146592/2023-2024:Supply & fixing 8 stage, 440/ 110 V, 5 A/ 1 A intelligent power factor controller.accessories in position and giving connection.
OD148344/2023-2024:Supply and Installation of Flush head Push Button with 1 NC Block
OD148345/2023-2024:Supply and Installation of Flush head Push Button with 1 NC Block
OD146604/2023-2024:Supply and providing Blue colour LED indicator lamp, AC/DC, 22.5 cm cut out dia-
OD146605/2023-2024:Supply and providing Red, Green, Black, Yellow, Orange colours LED indicators, AC/DC 22.5mm cut out dia-
2.10.5:Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Triple pole and neutral
OD146596/2023-2024:Carrying out control wiring for panel with normal meters and indication lamps alone with 650/1100 V grade PVC insulated stranded single core copper conductor cables 6.0 sq mm single run with required sockets.conforming to IS 694 part I 1990 for interconnecting the control devices/ equipment's including providing suitable size insulated sockets at the termination points or soldered properly, providing numbering ferrules for the proper identification of the wiring, keeping the wiring firm by suitable tie/ tie mounts/ PVC duct etc as required.-
OD146597/2023-2024:Carrying out control wiring for panel with normal meters and indication lamps alone with 650/1100 V grade PVC insulated stranded single core copper conductor cables 4.0 sq mm single run with required sockets.conforming to IS 694 part I 1990 for interconnecting the control devices/ equipment including providing suitable size insulated sockets at the termination points or soldered properly, providing numbering ferrules for the proper identification of the wiring, keeping the wiring firm by suitable tie/ tie mounts/ PVC duct etc as required.
OD146598/2023-2024:Carrying out control wiring for panel with normal meters and indication lamps alone with 650/1100 V grade PVC insulated stranded single core copper conductor cables 2.5 sq mm single run with required sockets.conforming to IS 694 part I 1990 for interconnecting the control devices/ equipments including providing suitable size insulated sockets at the termination points or soldered properly, providing numbering ferrules for the proper identification of the wiring, keeping the wiring firm by suitable tie/ tie mounts/ PVC duct etc as required.
OD146599/2023-2024:Carrying out control wiring for panel with normal meters and indication lamps alone with 650/1100 V grade PVC insulated stranded single core copper conductor cables 1.5 sq mm single run with required sockets.conforming to IS 694 part I 1990 for interconnecting the control devices/ equipments including providing suitable size insulated sockets at the termination points or soldered properly, providing numbering ferrules for the proper identification of the wiring, keeping the wiring firm by suitable tie/ tie mounts/ PVC duct etc as required.
OD146600/2023-2024:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured copper power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required. 2 core 2.5 sq mm with factory made clamp
OD146601/2023-2024:Supply and fixing 250/5 A, 15 VA, accuracy class 1, Resin Cast Metering CT
OD146603/2023-2024:Supply and installation of Three phase multi function meters to read V, A and F, accuracy class 1
OD146608/2023-2024:Supply and fixing water proof emergency stop Rotary Self-locking Push-button Switch with IP65 protection and giving connections required.
90.12.5.34:Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.3.5 core 185 sq mm
90.12.7.34:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 185 sq mm
90.12.5.28:Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.3.5 core 35 sq mm
90.12.7.28:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 35 sq mm with factory made clamp
90.12.7.41:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 16 sq mm with factory made clamp
90.12.7.42:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 25 sq mm with factory made clamp
90.12.7.39:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 6 sq mm with factory made clamp
90.12.5.2:Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.2 core 6 sq mm
90.12.7.2:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.2 core 6 sq mm with factory made clamp
9.1.21:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 35 sq. mm (32mm)
9.1.23:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 70 sq. mm (38mm)
9.1.27:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 185 sq. mm (57mm)
9.1.33:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 16 sq. mm (28mm)
9.1.1:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.2 X 6 sq. mm (19mm)
9.1.34:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 25 sq. mm (28mm)
90.12.10.2:Supply & laying of DWC pipe in ordinary soil 0.75m below ground level including excavation50/38 mm or nearest size
90.12.10.5:Supply & laying of DWC pipe in ordinary soil 0.75m below ground level including excavation90/75 mm or nearest size
90.12.9.2:Supplying, laying and jointing of the following sizes of double wall corrugated (DWC) pipes made out of HDPE conforming to IS 14930 Part II for mechanical protection to underground power cables with all required accessories in ground in the existing trench50/38 mm or nearest size
90.12.9.5:Supplying, laying and jointing of the following sizes of double wall corrugated (DWC) pipes made out of HDPE conforming to IS 14930 Part II for mechanical protection to underground power cables with all required accessories in ground in the existing trench90/75 mm or nearest size
OD146579/2023-2024:Supply, conveyance, installation, testing and commissioning of 160 KVA Out Door type unitized sub station of IP class 54, with cast resin Transformer with 630A VCB on H.T.side, and Metering CT and PT ,with Top/bottom entry cable box, The LT Portion Shall include 250A 4 pole 36KA microprocessor based MCCB, Neutral CT with MC12 Relay on L.T. side. Transformer Portion consists of 160 K.V.A , 11 K.V, 50 Hz, Delta/Star connected cast resin insulated copper wound transformer. The core shall be made of high grade grain oriented silicon M4 steel lamination insulated and oxide layer and outside of the core shall be protected against corrosion by epoxy resin finish. Class 'F' insulation level shall be maintained. OFF load tap changing facility shall be incorporated so as to achieve tap positions of +5% to -10% in step of 2.5%. four channel Temperature Scanner with 4 nos Sensors, annunciator and trip mechanism shall be provided. The Transformer shall conform to IEC 726 & IS 11171/1985 re-affirmed in 1991. The maximum allowable loss limited to values designated by ECBC Norms 2007 . All inter connection from HT Side to transformer and to LT Side shall be given using electrolytic copper bus bar insulated with heat shrink sleeves and tinned at the point of contacts. All internal earth connections are to be given as per standards. Necessary protection shall be made for giving cable connections on the HT side as well as LT side. Phase barriers and shrouding as per rules has to be given. The enclosure shall be fabricated from 2.00mm CRCA sheet, complying with of IP 54 standards and shall be powder coated over a coat of Zinc chromate primer after seven tank processing and phosphatizing. The USS shall be installed as per the directions at site.
OD146609/2023-2024:Supply & laying of one No. PVC insulated and PVC sheathed armoured aluminium power cable of 11 KV grade of the following sizes in the existing masonry open duct as required. 3 core 300 sqm stranded compact circular aluminium conductor, conductors screened with extruded semi conducting compound XLPE insulated, insulation screened with extruded semi conducting compound in combination with copper tape (0.3KA for I sec.) cores laid up. inner sheath of PVC tape, galvanized steel flat strip armoured, and overall PVC sheathed cable conforming to IS: 7098 part II 1985 with latest amendments. --
OD146610/2023-2024:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminum power cable, 11 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required 3 core 300 sqm stranded compact circular aluminum conductor, conductors screened with extruded semi conducting compound XLPE insulated, insulation screened with extruded semi conducting compound in combination with copper tape (0.3KA for I sec.) cores laid up. inner sheath of PVC tape, galvanized steel flat strip armored, and overall PVC sheathed cable conforming to IS: 7098 part II 1985 with latest amendments. --
OD146611/2023-2024:Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 11 KV grade of the following sizes in ground including excavation of trench of size 35 x 100 cm, refilling the trench etc. as required 3 core 300 sqm stranded compact circular aluminum conductor, conductors screened with extruded semi conducting compound XLPE insulated, insulation screened with extruded semi conducting compound in combination with copper tape (0.3KA for I sec.) cores laid up. inner sheath of PVC tape, galvanized steel flat strip armored, and overall PVC sheathed cable conforming to IS: 7098 part II 1985 with latest amendments. --
90.12.9.6:Supplying, laying and jointing of the following sizes of double wall corrugated (DWC) pipes made out of HDPE conforming to IS 14930 Part II for mechanical protection to underground power cables with all required accessories in ground in the existing trench110/94 mm or nearest size
10.4.4:Supplying and making indoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required:300 sq. mm
10.5.4:Supplying and making outdoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required :300 sq. mm
OD146612/2023-2024:Supply and providing cable trays or frame work of all sizes with angle iron/flat iron suitable size painted with 2 coats of synthetic enamel paint over a coat of red oxide primer & with drilled holes to mount the switch gears/Cable/machines for support , fixed to wall/floor using suitable size anchor bolts etc grouted to wall, making good the damages, colour washing etc as required
OD146613/2023-2024:Earthing with CI/GI earth plate 1200X1200X12 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
OD148879/2023-2024:Supply and laying the following sizes of strips laid 0.60 m below ground level including excavating trench of suitable size and refilling etc. as required (in ordinary soil). 25 x 3 mm copper strip.-
90.16.4.8:Supply and clamping the following sizes of strips on surface of wall / parapet/ existing cable tray using clamps fabricated from 20 x3 mm GI flat duly painted or heavy duty GI spacer saddles, spacing of clamps not exceeding 1 m , making good the damages, colour washing etc. as required ( for vertical run).25 x 3 mm copper strip
90.16.3.9:Supply and clamping the following size of strips on surface of wall/ parapet/ existing cable tray using clamps fabricated from 20 X 3 mm GI flat duly painted or heavy duty GI spacer saddles spacing of clamps not exceeding 1 m, making good the damages, colour washing etc. as required ( for horizontal run)25 x 3 mm copper strip
90.16.1.1:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required2.00 mm copper conductor ( 14 SWG)
90.16.1.2:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required2.65 mm copper conductor (12 SWG)
90.16.1.3:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required3.15 mm copper conductor ( 10 SWG)
90.16.5.1:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.2.00 mm (14 SWG)
90.16.5.2:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.2.65 mm (12 SWG)
90.16.5.3:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.3.15 mm (10 SWG)
OD147143/2023-2024:Supply and providing 25x3mm brass nut and bolt etc. as required.
4.1.5:Supplying and installing following size of perforated pre-painted M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.375 mm width X 50 mm depth X 2.0 mm thickness
14.1:Excavation for foundation in soft soil including dressing of sides and ramming of bottoms, lift upto 1.5 m including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 metres.
14.9:Providing and laying in position cement concrete 1 :3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size) in foundation of pump, DG set etc. including form work etc. as required.
14.11:Providing brick work (in width 225 mm or more) with F.P.S. bricks of class designation 7.5 in cement mortar 1:4 (1 cement : 4 coarse sand) at all levels.
14.12:Providing 15mm thick cement plaster of mix 1:4(1 cement: 4 fine sand) at all levels
4.1.2:Supplying and installing following size of perforated pre-painted M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.150 mm width X 50 mm depth X 1.6 mm thickness
4.1.4:Supplying and installing following size of perforated pre-painted M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.300 mm width X 50 mm depth X 1.6 mm thickness
OD146614/2023-2024:Reinforcement for R.C.C works, bend tied and placed in position (plain grill requiring bend cold) using tor steel as required.
OD146615/2023-2024:Supply and providing MS chequered plate of suitable thickness including cutting, welding, painting etc. as required for the outdoor cat walk plat form.
OD146616/2023-2024:Supply and providing Danger 415 V, 125 x 75 mm aluminium anodised legend plates in the existing panel board as required-
OD146617/2023-2024:Painting letters or figures of the following sizes with enamel paint as identification mark to SB, DB, panel board etc as required. 2.5 cm, 4 cm, 5 cm height
OD146618/2023-2024:Supply and providing First Aid Chart duly framed and placed in a conspicuous location for clear vision.
OD146619/2023-2024:Supply and providing 2mm thick Elastomeric fire retardent insulating mat as per IS 15652/2006 to withstand 3.3 KV dielectric strength.
OD146620/2023-2024:Supply and providing 9 Litre capacity GI Fire Bucket painted in post office red with primer coat of red oxide and written with white paint 'FIRE' mounted on MS angle frame work/ wall bracket filled with fine sand, painting the bracket/ floor stand including making good the damages, colour washing etc. as required.
OD146621/2023-2024:Supply and installation of ABC type fire extinguisher of 5 kg. Capacity complete with initial charges and installation brackets conforming to IS15683 with ISI mark -
OD146623/2023-2024:Charges for preparation of Electrical/fire Drawing per A3 sheet first copy
OD146624/2023-2024:Copying charges of Electrical/fire Drawing per A3 sheet additional copies
SITC of 125KVA DG
OD146566/2023-2024:Supply, Conveyance, Installation, testing and Commissioning of 125 KVA DG set on suitable CC foundation as per technical details given below :- i. Engine a. Make of Engine : As Specified in the make of material list b. Type of Engine : Diesel Engine c. No. of Cylinders : Suitable to develop the required BHP as per manufacturers’ standard d.Method of Cooling: Water Cooling (with radiator) e. Aspiration : Tubro charged ,inter cooled f. Design : Suitable for generator set application g. Output : BHP ratings specified by the respective manufacturers’ capable of delivering the required power for alternator. " "ii. Standard accessories with Diesel Engine a. Flywheel housing and flywheel to suit single bearing alternator (Close coupled arrangement) b. Air Cleaner c. Coolant Kit d. Fuel Pump e. Electronic governor with solid state potentiometer accepting digital pulse input from PLC(backed with mechanical governor –if supplied as standard with the set by the manufacturer) f. Fuel filter g. Lubricating Oil filter h. Residential type exhaust silencer iii. Engine Instrument Panel a. Starting switch with key or button b. Lubricating oil temperature guage c. Lubricating oil pressure guage" "d. Water temperature guage e. RPM Indicator with hour meter f. Battery charging ammeter iv. Safety Controls for Engine a. Trip for low lubricating oil pressure b. Trip for high water temperature c. Providing necessary warning system and other safeties as contemplated in relevant ISS d. Fuel shunt off facility at over speed. iv. Fuel Pipe: " "Oil resistant flexible hoses & 25mm dial or nearest size MS pipe as per manufacturers’ requirement for fuel line extension with regulator valve. v. Alternator a. Make : As Specified in the make of material list b. Type : Self exited and self regulated c. Capacity : 125KVA at 0.8PF d. System of Voltage : 3phase, 415V e. Speed : 1500rpm f. Voltage regulation band : +1.00% of rated voltage g. Insulation : Class H h. AVR : AVR shall be provided with a motorized or solid state potentiometer. i. IP rating of enclosure : IP 23 j. Waveform distortion : No load < 1.5%, non- distorting, balanced Linear load <5% k. Telephone interference : Better than 50 l. Total harmonic factor : Better than 2% m. Standard control panel with Suitably rated MCCB/ACB .The characteristics of the DG set shall be such as to operate them in parallel mode. Routine tests as per relevant ISS shall be conducted and test reports of the same shall be furnished at the time of delivery. vii. Fuel tank. Integral type fuel tank of adequate capacity . viii. Battery: Required number of suitably rated fully charged battery with leads and terminals as required as per manufacturers’ requirement." "ix Operation manual, service manual, list of spares etc x. Acoustic Enclosure a. The DG set shall be supplied along with specially designed, company fabricated (to be fabricated in the same company from where the DG set is delivered) acoustic enclosure to meet the stringent MOEF/CPCB norms ." "b. Sufficient space and clearance shall be maintained inside the enclosure to have optimum serviceability. c. Air inlet louvers shall be designed in such a way as to operate the set at rated load even at 50 degree Celsius enclosure temperature. d. The enclosure shall be with UV resistant powder coating capable to withstand extreme environment. e. Hardware used shall be of only stainless steel make. f. Insulation material shall conform to IS 8183 specifications for better attenuation. xi. Documents to be supplied. a. Engine manual. b. Spares parts book c. Warranty certificate d. Alternator manual & test certificate 1 set control wiring drawing xii. Installation It shall be installed in the pre-constructed concrete bed complying to relevant IS standards, IE rules and as per the direction of the departmental officials. xiii. Testing and Commissioning The DG set shall be tested as per relevant IS standards. Block load testing shall also be conducted. The DG should have capacity to withstand blocked load of at least 55%.Droop characteristics shall also be tested and adjusted for enabling parallel operation. "xiv. Warranty During the 3 year Guarantee period comprehensive maintenance (excluding oil changes) and services as per manufacture recommendation and repairs shall be arranged from date of commissioning. The DG shall comply CPCB II norms.
90.12.5.33:Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.3.5 core 150 sq mm
90.12.7.33:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 150 sq mm
9.1.26:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2 X 150 sq. mm (50mm)
90.12.9.2:Supplying, laying and jointing of the following sizes of double wall corrugated (DWC) pipes made out of HDPE conforming to IS 14930 Part II for mechanical protection to underground power cables with all required accessories in ground in the existing trench50/38 mm or nearest size
OD146567/2023-2024: Supply and Installation of AMF Logic Relay, EC2 Relay in the existing panel board and to made all control wiring with all accessories and make it proper working condition of automatic operation of DG and EB supply. (C&S Make/equivalent)
OD146568/2023-2024:Supply and providing Plug in Relay , 10Amps, 2Pole, 240V AC, suitable for AMF operation with base plate for proper mounting and giving connections etc: as required. (Salzer Make)
OD146569/2023-2024:Supply and providing Auxilary contactor for Control Relay , Type MXO 22E, 2 No: + 2NC:, 415V, L&T make for AMF Operation,
OD146570/2023-2024:Supply, Fixing of Mechanical Inter Lock with 4 NO and 4 NC , in the existing AMF Panel. (L&T make MCX 22-23/equivalent)
OD146571/2023-2024:Supply and providing electronic on delay timer for AMF operation. (Salzer Make/ equivalent)
OD146574/2023-2024:Supply, laying and clamping of 1 no. 2.5 sqmm 8 core PVC/ XLPE insulated armoured control cables with copper conductors for working voltages up to and including 1100 V conforming to IS 1554 part I 1988 for PVC and IS 7098 Part I for XLPE with the cables, spacing of clamps with factory made clamp not exceeding 60cms, making good the damages , colour washing etc. as required.
OD146575/2023-2024:Charges for conducting load test of 125 KVA DG set at standardized Factory bed as per standard norms and condition. ie in various steps load up to full load for 3 hours & 10% over load for 20 minutes and the rate includes hire and rent of test bed equipment's, labour charges ,loading and unloading and fuel etc. The test certificate should be given the client in standard format.
OD146576/2023-2024:Supply and filling high speed Diesel for generator
OD146577/2023-2024:Supply and providing 12V,15A, Automatic Battery charger suitable for 180Ah Battery, having . Full protection against battery overcharging & reverse polarity. Over voltage, overload & short circuit protection, reverse battery protection. Digital meters for voltage & current display , attery connecting terminals with lead wire, Float and Boost Charging Mode , LED Indication for charger status indication, etc: and giving necessary connections as required .
5.4:Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
90.17.7.7:Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required :100 mm dia
K K Associates
Bidder Name
K K Associates
ELCON ELECTRICALS
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_1038130.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .