Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹5.0 CrAccepted-AOC B 1703 MODERN INDUSTRIAL ESTATE BAHADURGARH HARYANA 124507 | BAHADURGARH | JHAJJAR | HARYANA | 124507 | ₹5.0 Cr | L1 | Accepted-AOC LOA |
| 2 | L2₹5.2 CrRejected-Finance PLOT NO F AND G RAKBA DARAKHERA PROFESSOR COLONY NAGAR PARISAD THANESAR KURUKSHETRA HARYANA 136 118 | ₹5.2 Cr | L2 | Rejected-Finance Highest |
| Sl No | Description | Qty | Unit | Hemcool Engineers L1 | SKG INFRATECH PRIVATE LIMITED L2 |
|---|---|---|---|---|---|
| 1.00 | Providing and fixing in position the following 32mm dia MS `C` class pipes, cut to required length and installed with welded joints, providing and fixing all necessary fittings such as bends, elbows, tees, reducers, flanges, sockets etc. Chilled water piping shall be insulated with 50 mm thick EPS Pipe Section (TF Quality) covered with 2 layers of sand cement plaster each layer of 8 mm for exposed piping or 26 SWG Aluminium cladding over piping for indoor installation complete in all respect upto entire satisfaction of Engineer in charge of work. | 250 | Each | 550 ₹1.4 L | 575 ₹1.4 L |
| 2.00 | Supplying, Fixing, testing and commissioning of fire dampers in supply air duct/main branch and return air path as and where required of required sizes i/c control wiring, the damper shall be motorized and spring return so as to close the damper in the event of power failure automatically and open the same in case of power being restored. The spring return action shall be inbuilt mechanism and not externally mounted. The damper shall also be closed in the event of fire signal complete as required and as per specifications. Make : Swirl Air/ Systemaire/Carryair/ Airmod | 54 | Sqm | 9,850 ₹5.3 L | 11,000 ₹5.9 L |
| 3.00 | SITC of Sub Panel :- P2 for AHUsWall mounted sub panel boards for AHUs with starter inter connections, Current operated single phase preventors A/M switch etc as per specifications and drawings as required.1 No incoming 100 Amps 4 pole TP plus NL MCB, 1 No star delta starter for motor, 3 Nos indication lights, 2 Nos Push Buttons, complete in all respect upto entire satisfaction of Engineer in Charge of work | 75 | Each | 30,000 ₹22.5 L | 35,000 ₹26.3 L |
| 4.00 | Supply and Fixing of 3C x 1.5 Sqmm Providing and Fixing of control cable of shielded and analyed tinned copper for inter locking. complete in all respect upto entire satisfaction of Engineer in charge of work. Make as per attached list. | 1,300 | Metre | 140 ₹1.8 L | 165 ₹2.1 L |
| 5.00 | FCU:- Supply, installation, testing and commissioning of 3.0 TR. 1200 CFM 7 mm of WC 3 Deep 10 Level factory fabricated Double Skin Chilled Water Air- handling unit horizontal type fabricated out of extruded aluminium section consisting with 0.63 mm pre-plasticized/pre-coated Galvanized steel sheet outside and 0.63 mm plain aluminium sheet inside with blower, blower section and Blower shall be DIDW forward / Backward Curved blade from and blower motor TEFC type suitable for operation on 415 volts ± 10%, 50 Hz ± 5% AC supply, Multi Row deep cooling coil made of Aluminium finned Copper tube with coil section, pre - filter section with non woven synthetic media of 10 micron particle size with an efficiency of 90% , stainless steel drain pan made out of 18 G sheet duly insulated complete with motor and belt drive package etc. The AHU panels shall be insulated with 25 plus 2 mm thick and 38 Kg/m³ density PU foam. The motor and blower assembly shall be mounted on Aluminium extruded section. The complete AHU/FCU shall conform to standard specification complete in all respect upto entire satisfaction of Engineer in charge of work. Make : as per attached list. | 2 | Each | 37,700 ₹75,400 | 36,500 ₹73,000 |
| 6.00 | Providing and fixing in position the following 25mm dia MS `C` class pipes, cut to required length and installed with welded joints, providing and fixing all necessary fittings such as bends, elbows, tees, reducers, flanges, sockets etc. Chilled water piping shall be insulated with 50 mm thick EPS Pipe Section (TF Quality) covered with 2 layers of sand cement plaster each layer of 8 mm for exposed piping or 26 SWG Aluminium cladding over piping for indoor installation complete in all respect upto entire satisfaction of Engineer in charge of work. Make as per attached list. | 425 | Each | 435 ₹1.8 L | 450 ₹1.9 L |
| 7.00 | Providing and fixing of duct insulation with 25mm thick closed cell nitrile rubber sheet as per specs complete in all respect upto entire satisfaction of Engineer in charge of work. Make as per attached list... | 5,000 | Sqm | 625 ₹31.3 L | 550 ₹27.5 L |
| 8.00 | Supplying and fixing of powder coated extruded aluminium return Air Grills / diffusers without volume control dampers as per specifications, Make as per attached list. | 200 | Sqm | 3,950 ₹7.9 L | 4,300 ₹8.6 L |
| 9.00 | SITC of Actuators Motor for Fire Dampers complete in all respect upto entire satisfaction of engineer in charge. Make as per attached list. | 60 | Sqm | 8,465 ₹5.1 L | 8,850 ₹5.3 L |
| 10.00 | Ceiling Suspended Units : Supply, installation, testing and commissioning of 12 TR 4800 CFM 65 mm 6 Row 5 Microns factory fabricated Double Skin Chilled Water Air- handling unit horizontal type fabricated out of extruded aluminium section consisting with 0.63 mm pre-plasticized/pre-coated Galvanized steel sheet outside and 0.63 mm plain aluminium sheet inside with blower, blower section and Blower shall be DIDW forward / Backward Curved blade from and blower motor TEFC type suitable for operation on 415 volts ± 10%, 50 Hz ± 5% AC supply, Multi Row deep cooling coil made of Aluminium finned Copper tube with coil section, pre - filter section with non woven synthetic media of 10 micron particle size with an efficiency of 90% , stainless steel drain pan made out of 18 G sheet duly insulated complete with motor and belt drive package etc. The AHU panels shall be insulated with 25 plus 2 mm thick and 38 Kg/m³ density PU foam. The motor and blower assembly shall be mounted on Aluminium extruded section. The complete AHU/FCU shall conform to standard specification complete in all respect upto entire satisfaction of Engineer in charge of work. Make as per attached list. | 1 | Each | 1,95,000 ₹1.9 L | 2,01,000 ₹2.0 L |
Updated dates
Tender Value
₹4.8 Cr
EMD Value
₹9.6 L
Closing Date
19 Jan 2026, 11:00 amClosed
NAVEEN RATHEE
ED - Ambala
Upgradation of Civil Hospital 200 Bedded to 300 Bedded at Ambala City in Ambala Distt (Pdg. Additional Chiller and Allied Work) (Recall)
2026_HRY_495182_1
202672899519 E097 4126 B77B B7688D5151A6663BAR
Open Tender
Civil Works
365 days
Ambala
Upgradation of Civil Hospital 200 Bedded to 300 Bedded at Ambala City in Ambala Distt (Pdg. Additional Chiller and Allied Work) (Recall)
2 documents required · 2 mandatory
₹15,000
₹9.6 L
Yes
18 Feb 2026
6 Jan 2026
19 Jan 2026
7 Jan 2026
19 Jan 2026
7 Jan 2026
Select, Excess (+), Less (-) Less (-)
Tender Inviting Authority: Executive Engineer Electrical Division PWD B&R Br., Ambala Cantt
Name of Work: Upgradation of Civil Hospital 200 Bedded to 300 Bedded at Ambala City in Ambala Distt (Pdg. Additional Chiller and Allied Work).
Estimated Cost Rs. 478.97 lacs
Name of the Bidder/ Bidding Firm / Company :
Sl. No. HSR Items / Description Item Code / Make Quantity Units Estimated Rate in Rs. P Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency BASIC RATE In Figures To be entered by the Bidder in Rs. P Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Other Taxes 2 IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category TOTAL AMOUNT in Rs. P TOTAL AMOUNT With Taxes TOTAL AMOUNT In Words
1 Providing and fixing in position the following 32mm dia MS `C` class pipes, cut to required length and installed with welded joints, providing and fixing all necessary fittings such as bends, elbows, tees, reducers, flanges, sockets etc. Chilled water piping shall be insulated with 50 mm thick EPS Pipe Section (TF Quality) covered with 2 layers of sand cement plaster each layer of 8 mm for exposed piping or 26 SWG Aluminium cladding over piping for indoor installation complete in all respect upto entire satisfaction of Engineer in charge of work. BI01010001010000000000000515BI0100001113 Each Excess(+) Full Conversion INR 1.01 Supplying, Conveying and fixing spls. Including eart item1 123.223 Nos
45 Acousting Insulation of Duct from inside with covered 10 mm open cell insulation complete in all respect upto entire satisfaction of Engineer in charge of work. As per attached list . BI01010001010000000000000515BI0100001157 Sqm Excess(+) Full Conversion INR 2 Construction of chamber for 100mm sluices valve item3 10 Nos
109 [25.6.6]Supplying, fixing, testing and commissioning o STRAINER flanged end and PN 16 pressure rating as specified. 6. 65mm dia. [Through Rate] BI01010001010000000000000515BI0100001221 Each Excess(+) Full Conversion INR 3 Supplying, Conveying and fixing spls. Including ea item4 10 Nos
Please Enable Macros to View BoQ information
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.20 MB
BOQ_573646.xls
BOQ • 0.33 MB
Download all tender documents and submit your bid