Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹245.1 CrAccepted-AOC | ₹245.1 Cr | L1 | Accepted-AOC Accepted being reasonable workable rates |
| 2 | L2₹248.7 CrRejected-Finance | ₹248.7 Cr | L2 | Rejected-Finance being L2 |
| 3 | L3₹251.5 CrRejected-Finance PLOT NO 65 SECTOR 18 OPP HIPA SARHAUL GURUGRAM 122 001 | ₹251.5 Cr | L3 | Rejected-Finance being L3 |
| 4 | L4₹251.9 CrRejected-Finance DEE VEE HOUSE MAULSHREE VIHAR IN FRONT OF HOTEL BABYLON INTERNATIONAL VIP ROAD RAIPUR 492006 CHHATTISGARH | ₹251.9 Cr | L4 | Rejected-Finance being L4 |
| 5 | L5₹253.2 CrRejected-Finance | ₹253.2 Cr | L5 | Rejected-Finance being L5 |
Tender Value
₹251.4 Cr
EMD Value
₹15 L
Closing Date
27 Sept 2021, 6:00 pmClosed
DDG CE
DDG CE DGNP NAVAL BASE POST VISAKHAPATNAM 530014
PROVISION OF MARRIED AND SINGLE ACCOMMODATION FOR JUNIOR SAILORS, DSC PERSONNEL AND CIVILIANS ALONG WITH RELATED FACILITIES AND SERVICES AT NAVAL STATION
2021_MES_457331_1
DDG CE TOKEN 04 2020 2021
Open Tender
Civil Works
915 days
VISAKHAPATNAM
As per NIT
8 documents required · 8 mandatory
₹3,000
DGNP
₹15 L
Yes
CONFERENCE HALL
29 Oct 2021
5 Jul 2021
29 Sept 2021
5 Jul 2021
27 Sept 2021
10 Sept 2021
5 Jul 2021 - 31 Jul 2021
20 Jul 2021
Amount
Lump sum amount worked out by the contractor for "Buildings & Structures" as listed in Schedule 'A' Part-I on Serial Page No.55
Lump sum amount worked out by the contractor for "Site clearance / Area Development / Earthwork excavation/Hill cutting" as listed in Schedule 'A' Part-II on Serial Page No. 58
Lump sum amount worked out by the contractor for "Internal Water Supply" as listed in Schedule 'A' Part-III on Serial Page No. 60
Lump sum amount worked out by the contractor for "Internal Electrification including Telephone / TV / Internet" as listed in Schedule 'A' Part-IV on Serial Page No. 64
Lump sum amount worked out by the contractor for "External Water Supply" as listed in Schedule 'A' Part-V on Serial Page No. 66
Lump sum amount worked out by the contractor for "External Electrification" as listed in Schedule 'A' Part-VI on Serial Page No. 69
Lump sum amount worked out by the contractor for "Road/Path/Culvert" as listed in Schedule 'A' Part-VII on Serial Page No. 72
Lump sum amount worked out by the contractor for "Retaining Wall" as listed in Schedule 'A' Part-VIII on Serial Page No. 73
Lump sum amount worked out by the contractor for "Area Drainage" as listed in Schedule 'A' Part-IX on Serial Page No. 74
Lump sum amount worked out by the contractor for "Gate & Fencing" as listed in Schedule 'A' Part-X on Serial Page No. 76
Lump sum amount worked out by the contractor for "Recreation Ground" as listed in Schedule 'A' Part-XI on Serial Page No. 80
Lump sum amount worked out by the contractor for "FIRE PROTECTION OF BUILDINGS AND EXTERNAL FIRE FIGHTING" as listed in Schedule 'A' Part-XII on Serial Page No. 84
Lump sum amount worked out by the contractor for "Lightning Protection" as listed in Schedule 'A' Part-XIII on Serial Page No. 85
Lump sum amount worked out by the contractor for "Cooling Appliance" as listed in Schedule 'A' Part-XIV on Serial Page No. 86
Lumpsum price worked out by the contractor for "Solar Water Heater System" as listed in Schedule "A" Part –XV on Serial Page No. 88
Lumpsum price worked out by the contractor for "Lifts", as listed in Schedule "A" Part –XVI on Serial Page No.91
Schedule "A" Part - XVII: [Miscellaneous Items] [Internal Water Supply, External Water Supply, Internal Electrification, Telephone/TV/Internet, External Electrification, Lightning Protection, Fire Protection of Buildings, External Fire Fighting, Road/Path/Hard standing and Culvert, Sewage Disposal, Aviation lights, Lightning Protection, Air Conditioning and Cooling Appliance]: [To be quoted by the bidder.]
M&L for Point wiring with 1.5 Sq.mm FRLSH PVC insulated unsheathed copper conductor cable, single core multi stranded 1100Volt grade confirming to IS 694: 1977, drawn in and including rigid PVC conduit not less than 20mm bore, concealed type, medium grade as per IS 9537 (Part 1-1983) with conduit accessories, junction boxes, tees, terminal boxes with and including factory made MS boxes, modular cover plates with frame for mounting modular switches, including one run of 1.5 Sq.mm single core FRLS PVC unsheathed copper conductor cable as earth continuity conductor and connected to common earth dolly, for one light / fan point controlled by one way switch, complete all as specified and as directed. Note: Cutting chases and making good surfaces shall be included in the unit rate.
Description all as per Serial Item No. 18 here in before but for light / fan point controlled by two twoway switches complete.
Description all as per Serial Item No. 18 here-in-before but with 2.5 Sqmm copper conductor cable and 2.5 Sqmm cable as earth continuity conductor for 3 pin 5Amp switch socket point, on independent board, complete all as specified.
Description all as per Serial Item No. 20 here-in-before but for 3 pin 5Amp switch socket point, on Same board, complete all as specified.
Description all as per Serial Item No. 18 here-in-before but with 4.0Sqmm copper conductor cable and 4.0 Sqmm cable as earth continuity conductor for 3 pin 5/15Amp switch socket point, on independent board, complete all as specified.
Supply and fixing twin core copper telephone cable of size 0.5sqmm, PVC insulated PVC sheathed, complete all as specified.
Description all as per Serial Item No. 18 here in before but for Bell / Buzzer point controlled by bell push complete.
S&F Telephone jack with shutter glossy white RJ 11 port with suitable gang box, complete all as specified and directed.
S&F Data socket white glossy RJ 45 and RJ 11 Port with suitable gang box and face, complete all as specified and directed.
S&F TV socket outlet, delux with suitable gang box, complete all as specified and directed.
M&L for Earthing complete with galvanised steel earth plate electrode 60cm X 60cm X 6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to galvanised earth lead 4mm GI wire by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No.3 of SSR Part-I, including excavation / earth work in any strata, adequate quantity of charcoal and common salt, PCC chamber with with RCC 1:2:4 type B1 40mm thick cover slab with suitable handle and angle iron frame of suitable size to fix the cover, with 20mm bore GI pipe light grade for watering with funnel, wire mesh and 15mm bore GI pipe medium grade for GI wire protection and 4mm GI earth wire, including testing after completion, complete all as specified and directed. Note : Earth wire will be measured after 7.5mtr from the earth strip or earth testing terminal block whichever is lesser under relevant item.
All as per Serial Item No. 28 here in before but using galvanised iron strip 25 x 4mm earthing lead and 40mm bore GI pipe medium grade as protection pipe.
All as per Serial Item No. 28 here in before but using galvanised iron strip 32 x 6mm earthing lead and 50mm bore GI pipe medium grade as protection pipe. .
M&L for Earthing complete with galvanised steel earth pipe electrode 40mm bore, buried directly in ground (earth pit not less than 2.5 metres deep below ground level) with top edge of the plate not less than 1.25 metres below normal ground level, connected to galvanised earth lead 4mm GI wire by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No.2 of SSR Part-I, including excavation / earth work in any strata, adequate quantity of charcoal and common salt, PCC 1:3:6 type C1 chamber with RCC 1:2:4 type B1 40mm thick cover slab with suitable handle and angle iron frame of suitable size to fix the cover, including testing after completion, complete all as specified and directed.
All as per Serial Item No. 31 here in before but using galvanised iron strip 25 x 4mm earthing lead.
All as per Serial Item No. 31 here in before but using galvanised iron strip 32 x 6mm earthing lead.
Supply, install and testing of Refrigerator, electric driven (Single Phase), capacity 195 litres BEE 5 Star rated, double door, complete all as specified and as directed.
S&F Voltage stabilizer 5 KVA for automatic operation, suitable for deep freezers / refrigerator / water cooler / 2 Ton AC, single phase naturally air cooled indoor type and designed for input variation 160V to 270V, output voltage stabilized at 230Volt with accuracy of ± 2.50%, complete all as specified and as directed.
Supply, fixing and installation of Invertor type split AC [Indoor and Out door units] of capacity 2.0 Ton with in-built ioniser and plasma filter for better indoor air quality, with R-410A and minimum 5 star energy rating, fixed with and including out door stand, copper condenser tubes, drain pipe, including drilling holes and making good the disturbed surface, with cordless remote control unit and testing on completion, complete all as specified and as directed.
Supply, fixing and installation of Integral LED 48Watts aviation obstruction light new generation, PF>0.95, with aluminium housing and polycarbonate enclosure and IP 66 protection, with suitable GI pipe bracket with clamps, all accessories and internally pre wired and connecting up with three core twisted flexible copper conductor cable with suitable size, complete all as specified and as directed. Make Bajaj /Philips / Wipro/GE/CG / Havells
S&F Sheet metal enclosure SPN, 8 way 230 volts, single door type, without bus bar complete all as specified and as directed, with and including following :- (i) MCB SPN, 6-32Amps, 10kA - 01 No (ii) Timer switch ON/Off - 01 No
S&F AFFF type fire extinguishers - mechancial foam type 9 litres capacity, complete with initial charge, gun metal cap, discharge hose with nozzle, wall fixing brackets, etc., complete all as specified.
S&F CO2 fire extinguishers - 4.5 Kg capacity, complete with initial charge, gun metal cap, discharge hose with nozzle, wall fixing brackets etc confirming to IS : 15683 with ISI mark, complete all as specified.
S&F Dry chemical powder extinguishers, 9Kg capacity, complete with intial charge, gun metal cap, discharge hose with nozzle wall fixing brackets etc., confirming to IS : 15683 with ISI mark, complete all as specified and as directed.
Design, Supply, Install, testing and commissioning of pumping set, electrically driven, horizontal split case, centrifugal type conforming to IS and as per CPHEE manual with CI casing, bronze impeller and stainless steel shaft mounted on heavy duty bearings, suitable for continuous operation with range of operation 0% to 150% of rated capacity for 440V, 3 phase, 50Hz, 30mtr head, 450 LPM discharge, with and including DOL starter, single phase preventer, control switch gear MFM meter, with suitable foot valve with Y strainer with cored hole/slots and LT panel necessary MS frame and PCC foundation as per OEM Specification, complete all as specified and as directed. Note: Contractor has to submit drawings for approval before manufacturing at factory and pump / motors shall be confirming to GRIHA 3 rating.
Supply, laying, testing and commissioning of Ductile Iron pressure pipe of 150mm bore with flanged type ends jointed with with rubber or fibre board gasket and confirming to IS-8329:2000, class K-9, PN-10 rating, with pipe lining inside with cement mortar (CML) outside with bituminous coating all as per Annx `C' of IS-8329, laid in trenches / floor, complete all as specified and as directed. Note: 1. Necessary earth work will be measured and paid separately. 2. Necessary fittings will be measured and paid separately
Supply, laying, testing and commissioning of Ductile Iron pressure pipe of 100mm bore with flanged type both ends jointed with with rubber or fibre board gasket and confirming to IS-8329:2000, class K-9, PN-10 rating, with pipe lining inside with cement mortar (CML) outside with bituminous coating all as per Annx `C' of IS-8329, laid in trenches / floor, complete all as specified and as directed. Note: 1. Necessary earth work will be measured and paid separately. 2. Necessary fittings will be measured and paid separately
Supply, laying, testing and commissioning of Ductile Iron pressure pipe of 80mm bore with flanged type both ends jointed with with rubber or fibre board gasket and confirming to IS-8329:2000, class K-9, PN-10 rating, with pipe lining inside with cement mortar (CML) outside with bituminous coating all as per Annx `C' of IS-8329, laid in trenches / floor, complete all as specified and as directed. Note: 1. Necessary earth work will be measured and paid separately. 2. Necessary fittings will be measured and paid separately
M&L for DI Specials such as Bends , tapers any type, Tee pieces, single branch, "Y" junction, double branch, cross (for all flanged pipe) collars, caps and plugs for connecting up to 200mm bore DI Pipe all as per IS:9523, complete all as specified and as directed. Note: Fittings shall be of same grade and class as per main pipe.
Design, Supply, Install, testing and commissioning of pumping set, electrically driven, horizontal split case centrifugal type conforming to IS and as per CPHEE manual with CI casing, bronze impeller and stainless steel shaft mounted on heavy duty bearings, suitable for continuous operation with range of operation 0% to 150% of rated capacity for 440V, 3 phase, 50Hz, 50mtr head, 55Cum/Hr discharge, with and including soft starter, single phase preventer, control switch gear MFM meter and LT panel necessary MS frame and PCC foundation as per OEM Specification, complete all as specified and as directed. Note: Contractor has to submit drawings for approval before manufacturing at factory and pump / motors shall be confirming to GRIHA 3 rating.
Supply, Install, testing and commissioning of pumping set, electrically driven, horizontal split case centrifugal type conforming to IS and as per CPHEE manual with CI casing, bronze impeller and stainless steel shaft mounted on heavy duty bearings, suitable for continuous operation with range of operation 0% to 150% of rated capacity for 440V, 3 phase, 50Hz, 50mtr head, 306Cum/Hr discharge, with and including soft starter, single phase preventer, control switch gear MFM meter and LT panel necessary MS frame and PCC foundation as per OEM Specification, with suitable foot valve with Y strainer with cored hole/slots, complete all as specified and as directed. Note: Contractor has to submit drawings for approval before manufacturing at factory and pump / motors shall be confirming to GRIHA 3 rating.
S&F Cast Iron Air release valve suitable for 80mm bore, flanged of class PN 1.6, rubber lined, including brass spindle and necessary fixing arrangement like rubber gasket etc., complete all as specified and as directed.
S&F Cast Iron Foot valve suitable for 150mm bore, shall conform to IS:4038-1986, fitted with and including 'Y' strainer which will have cored holes / slotsand, including necessary fixing arrangement, complete all as specified and as directed.
S&F Water meter made with brass with connected accessories, for tubing upto 25mm diameter complete with union joints and jointing materials, complete all as specified and as directed.
Supply, lay, test and commissioning of two runs of minimum 6 Fibre OFC cable with and including 40mm HDPE duct pipe with and including all its connected accessories, laid in trenches or ducts or through the pipe etc., complete all as specified and as directed. Note: Two runs of Cable and two runs of duct Pipe shall be measured as one RM.
M&L for Valve chamber of size 1500mm x 1500mm x 1000mm internal dimensions, with and including excavation in any type of soil, spreading, levelling and refilling etc. PCC (1:4:8) type D2 for foundation, Fly ash brick work of one brick thick wall in CM (1:4) including internal plaster 15mm thick in CM (1:4) external plaster 15mm thick(1:4) upto 150mm below GL and providing coping in PCC (1;2:4) type B1, angular iron frame of size 50x50x6mm with 6mm thick MS plate cover complete including locking arrangements and having FRP coating of 2mm thick on both inside and outside surfaces, complete all as specified and shown in TD drawing.
Design, Supply, install, test and commissioning of Programmable logic control [PLC] panel for controlling 03 Nos of pumps with and including all its connected accessories, complete all as specified and as directed. Note: Contractor has to submit drawings for approval before manufacturing at factory and PLC panels shall be confirming to GRIHA 3 rating.
Supply, install, Retrofitting, test and commissioning of Motor Actuated Butterfly Valve, non rising type conforming to IS-14846, ISI marked, consisting of multitier single phase actuator and sluice valve of 150mm dia, 430Volt, AC, PN 1.6, double flanged with CI body wheel and brass spindle and nuts etc., with bracket / mounting arrangement, two limit switches for open / close, torque limit switch and splash proof enclosure, with inbuilt Serial / USB port, data logger with memory, SD card, space heater, with and including jointing materials, rubber gasket , nuts &bolts etc., complete all as specified and as directed.
M&L Boring of holes under road, pavement, hard standing by trenchless technology using ultra sound technique and necessary machine with and including HDPE pipe of 150mm dia suitable for 6 KGF/Sq.cm working pressure, complete all as specified and as directed.
M&L for Cable route indicator for cable route marker, made out of cast iron round shape of 100mm dia, with supporting length of GI flat 20mm wide and 6mm thick and 750mm long, duly marked with word such as LT Cable / 1.1KV as directed, duly painted with two coats of super enamel silver colour over a coat of primer, including grouting in ground 300mm x 300mm x 300mm deep with and including PCC 1:2:4 (Type B1), complete all as specified and directed.
M&L for Galvanized Steel High mast light 16m height, mast shaft with hot dip galvanized, suitable for wind velocity of 250 Km/hour and soil bearing capacity of 20 TON/Sqm as per IS-875, 3mm section thickness with top 150mm dia and bottom 340mm dia, suitable for 9 lantern symmetrically fitted along with their control gear and having two point suspension system with stainless steel wire rope of 6mm dia, 97/19 gauge and double drum winch with luminaire mounting arm, pulley assembly, galvanised carriage arrangement for 9 lights, 3 phase integral power tool with motor for lifting and lowering, lightning arrester spike, with foundation bolts manufactured from special steel along with nuts, washers, anchor plates, control panel with control cable, outdoor standard feeder pillar with 32A TPN MCB incomer, single dial time switch, 25A TP Contactor for automatic operation of luminaries, power tool control with 2 Nos Contacts and raise lower push button, switch gears and templates, with all accessories, including excavation, earth work, RCC M30 foundation as per OEM recommendations, complete all as specified and as directed. Note: Light fittings will be measured and paid for separately.
Supply, laying, testing and commissioning of FRLSH PVC insulated unsheathed copper conductor cable of size 3.0 core x 1.5Sqmm, 1100 volts grade and including cable glands, ferrules and connected accessories, multi stranded 1100 Volt grade confirming to IS 694: 1977, complete all as specified and as directed.
Supply, laying, testing and commissioning of FRLSH PVC insulated unsheathed copper conductor cable of size 2.0 core x 1.5Sqmm, 1100 volts grade and including cable glands, ferrules and connected accessories, multi stranded 1100 Volt grade confirming to IS 694: 1977, complete all as specified and as directed.
S&F Fire escape route map drawn on glow sign board / flex in required colour, letters and arrows at every 2m interval, for upto G+8 floor buildings, complete all as directed by Engineer- in- charge.
Supply, fix and testing of Loop in Loop Out box of size 4"x 8" of FRP made with IP 65 protection of thermoplastic circuit breaker boxes with metric knockouts for cable entry and exit, comb climate Cable Glands of IP66/IP67 for cable entry and Grommets IP 65 for conduit for cable exit with MCB 6 Amps, 10KA, C Curve overload and short Circuit protection, with 4 way connector, terminals as bus terminals for cable with necessary fixing arrangements and with cable glands etc all as specified and directed.
S&F Hot dip Galvanised perforated cable tray with cover for fixing XLPE cables at various places to accommodate the cables for MCBs, Panel etc of size not less than 75X50mm, 2mm thick with necessary bends, angles, supports for fixing etc., complete all as specified and as directed.
S&F Compact type Timer Panel of capacity 6KW including of Power contactor of 32Amp TP, MCB 40 Amps TP and Digital Timer switch 415Volt, steel encloser allas directed. Make: Havell's Ca no. IHXTS03060 or Equivalent in other makes specified in PS.
S&F Load bank enclosure 8 way TPN with IP 20 protection, double door, sheet steel phosphetised powder painted with 200 amps rated busbar, with and including one MCCB 4 Pole, 415 Volt, Adjustable type, 200Amps with breaking capacity 25 KA as incomming and 8 Nos of MCCB 3 Pole, 415 Volt, Adjustable type, 32Amps with breaking capacity 25 KA as outgoing, complete all as specefied and as directed.
Supply, Install, testing and commissioning of OEM factory made, Type tested blockset as per IEC 61439 Part 1&2 (Switchgear & Panel OEM Type Tested design) confirming to IP 65, Free standing mounted on PCC pedestal, dust and vermin proof LT cubical panel board, compartmentalised, outdoor type, fabricated with 3.15mm thick CRCA sheet with pre-treatment in seven tank process and powder coated with RAL7035 coat with matt finish including preparation of surfaces, high conductivity Aluminium Alloy bus bar TPN of rating 1.5 times the main incoming switchgear, colour coded heat shrinkable sleeves mounted on porcelain insulator supports, suitable double compression copper cable glands, separate compartments for each switch, gland plates lifting hooks, shutter type ventilating louver at top & bottom duly internally secured with wire mesh, including instrumentation such as digital Ampere meter, digital Volt meter, Phase indicating lamps [RYB] etc with double stud hinged door, Operating handle & locking arrangement with back door common openable (screwed/Lockable) including interlocking with switch gears and suitable for 1100 volts Grade, 3 phase, 4 wire with rated operational voltage 433V, 50Hz, AC supply and to withstand short circuit fault level of not less than 100KA, rated insulation voltage of 1000V and Impulse withstand of 12kV and minimum internal Arc with-stand of 65kA, 500mSec as per IEC61641, weather proof. (contd...)
All as per Serial Item No. 67 here in before but with following accessories:- Incoming- MCCB 125Amp Microprocessor based adjustable type thermo magnetic release based, FP, 16kA, 415V - 01 No. Outgoing: (a) MCB 40Amp, SPN, 10kA, 230V - 04 Nos (b) Temper proof digital energy meter of accuracy class 1, 240V, 50Hz with LCD display, 10-60A, [Measures and displays KWH, V, I, KW, PF, last month history of KWH, MD is KW] - 04 No (f) Space for 2Nos of 125Amp MCCB 4P.
M&L Reinforced concrete pipes of 1200mm bore, class NP2 laid and jointed and tested complete with collars, complete all as specified and as directed.
S&F Thermoplastic material raised pavement marker with shanks double sided lenses of retro reflective micro plastic tough poly carbonate lens fixed using bitumen lens colour as approved, complete all as specified and as directed.
S&F Median marker made up of tough, high impact resistant, injection moulded thermoplastic with flurecent yellow retro reflective sheeting with full cube corner optics technology with one or either sides as required of optically stable non metalized polycarbonate cubes, complete all as specified and as directed.
S&F Convex mirror 5.0mm thick with polycaronate frame 800mm dia with and including angle iron / pipe post of standared pattern, embeded in ground with PCC 1:3:6 type C1, including earth work excavation, complete all as specified and as directed.
S&F Mandatory / Regulatory reflective sign board duly indicating Speed/width limits as directed, circular in shape of size 600mm in dia, made out of 16SWG MS sheet, painted with one coat of Zinc chromate stoving primer on both side of white back ground , red border and black symbol, reflective on front side and back side gray stove enameled as per IRC-67/2001, with and including angle post of standared pattern embeded in ground with PCC 1:3:6 type C1, including earth work excavation, complete all as specified and as directed.
M&L for Thermoplastic road making paint as per MORT&H specification, exceeding 10cm wide with hot thermo plast material @5kg/Sqm of white / yellow confirming to BS-3262-1989, by fully automatic paint applicator machine fitted with profile shoe, glass beads dispenser, propane tank heater and profile shoe heater, driven by skilled operator, including preparation of surface, complete all as specified and as directed.
M&L Metal beam crash barrier of size 75mm x 150mm x 5mm with and including tie beam back up plate, post bolts nuts hardware and other galvanized steel fittings, complete all as per standard specified of NHAI, complete all as specified and as directed.
S&F Road safety reflector, round shape of dai 144.5mm, Colour in Red, Amber or White, complete all as specified.
Supply & fixing Basket Ball Pole [Single Pole type] with and including acrylic sheet basket ball board of size 1.8m x 1.08m x 20mm thick, with and including angular iron frame of size 35x35x5mm all around fixed with nuts & bolts, including dunken goal rings and net as per sports standard, with all suitable arrangements, complete all as directed by Engineer-in-Charge.
M&L Reinforced concrete pipes of 150mm bore, class NP2 laid and jointed and tested complete with collars, complete all as specified and as directed.
S&F CAT 6 Ethernet cable, 6core RJ 45, complete all as directed by Engineer-in-Charge.
S&F LED bulb 1x8w, 220volt, P.F>0.95 with and including lamp holder PVC/polycarbonate type with cord grip cap suitable for LED lamp, complete all as directed by Engr-in-charge.
S&F Air Circulator fan 450mm sweep osculation type of approved colour and model, with complete accessories (Energy Efficient) including provision of suitable clamp, flexible cable suitable for 230volt, AC 50 HZ, complete all as specified and as directed.
S&F Air Circulator fan 600mm sweep osculation type of approved colour and model, with complete accessories (Energy Efficient) including provision of suitable clamp, flexible cable suitable for 230volt, AC 50 HZ, complete all as specified and as directed.
S&F Energy saving, environmentally friendly & robust High bay light LED 80 Watt energy efficient, P.F>0.95, >100 lum/watt, with and including LED light driver holder connecting of with three core flexible copper conductor cable of suitable size, complete all as directed by Engr-in-charge. Make: Cat No. LHELAAU7PG7S080 of Havells or Equivalent in makes given here-in-after.
S&F Decorative luminary suspended type mounting 30/35 watt, 220Volt, P.F>0.95, >100 lum/watt, complete with 30/35 watt, lamp holder, complete made up of polycarbonate, connecting of with three core flexible copper conductor cable of suitable size, complete all as directed by Engr-in-charge. Make Cat. BLRL 35CDMT 35W of Bajaj or equivalent in in makes given here-in-after.
S&F Cast Iron Air release valve suitable for 150mm bore, flanged of class PN 1.6, rubber lined, including brass spindle and necessary fixing arrangement like rubber gasket etc., complete all as specified and as directed.
S&F Cast Iron Air release valve suitable for 50mm bore, flanged of class PN 1.6, rubber lined, including brass spindle and necessary fixing arrangement like rubber gasket etc., complete all as specified and as directed.
S&F Cast Iron Non Return Sluice valve suitable for 80mm bore, flanged of class PN 1.6, rubber lined, including brass spindle and necessary fixing arrangement like rubber gasket etc., complete all as specified and as directed.
SCHEDULE 'A' PART-XVIII [PHASE -III]: OUTSOURCING SERVICES FOR MANNING & OPERATION LIFTS DURING FIRST YEAR OF DEFECTS LIABILITY PERIOD:- Outsourcing Services for manning and operation of Electrically Operated passenger lifts 13/08 passengers (2Nos in each block) to serve different floors as mentioned at Items in Schedule 'A' Part-XVI, during 1st year of defects liability period, in 03 shifts (each shift 08 hours) per day including Sundays & Holidays, by providing one Lift Operator (Semi Skilled) for each Shift, complete all as specified and as directed.
SCHEDULE 'A' PART - XIX [PHASE -IV]: OUTSOURCING SERVICES FOR MANNING & OPERATION LIFTS DURING SECOND YEAR OF DEFECTS LIABILITY PERIOD: Outsourcing Services for manning and operation of Electrically Operated passenger lifts 13/08 passengers (2Nos in each block) to serve different floors as mentioned at Items in Schedule 'A' Part-XVI, during 2nd of defects liability period, in 03 shifts (each shift 08 hours) per day including Sundays & Holidays, by providing one Lift Operator (Semi Skilled) for each Shift, complete all as specified and as directed.
Outsourcing Services for manning and operation of Electrically Operated passenger lifts 13/08 passengers (2Nos in each block) to serve different floors as mentioned at Items in Schedule 'A' Part-XVI, during 1st year after expiry of defects liability period, in 03 shifts (each shift 08 hours) per day including Sundays & Holidays, by providing one Lift Operator (Semi Skilled) for each Shift, complete all as specified and as directed.
Outsourcing Services for manning and operation of Electrically Operated passenger lifts 13/08 passengers (2Nos in each block) to serve different floors as mentioned at Items in Schedule 'A' Part-XVI, during 2nd year after expiry of defects liability period and After completion of first year Comprehensive Maintenance, in 03 shifts (each shift 08 hours) per day including Sundays & Holidays, by providing one Lift Operator (Semi Skilled) for each Shift, complete all as specified and as directed.
Outsourcing Services for manning and operation of Electrically Operated passenger lifts 13/08 passengers (2Nos in each block) to serve different floors as mentioned at Items in Schedule 'A' Part-XVI, during 3rd year after expiry of defects liability period and After completion of 2nd year Comprehensive Maintenance, in 03 shifts (each shift 08 hours) per day including Sundays & Holidays, by providing one Lift Operator (Semi Skilled) for each Shift, complete all as specified and as directed.
Rds Project ltd.
Varindera Constructions Limited
DEE VEE PROJECTS LIMITED
Vijay Nirman Company Pvt Ltd
Som Projects Pvt. Ltd.
RAMJI DAS DHAL CONSTRUCTION PVT LTD
SLC PROJECTS Pvt Ltd
M/s KPC Projects Limited
Kanwarji Construction Co.
Montecarlo Limited
URC Construction (P) Ltd.
Hombale Constructions and Estates Pvt Ltd.,
stage.html
html • 0.08 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.05 MB
Download all tender documents and submit your bid