Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹17.8 LAccepted-AOC H NO 19 6 243 1 NGO S COLONY SHIV NAGAR NORTH BIDAR 585401 | BIDAR | KARNATAKA | 585401 | ₹17.8 L Quoted ₹18.5 L | L1 | Accepted-AOC L1 and reasonable |
| 2 | L2₹21.0 LRejected-AOC 0001D ATM HOUSE AIR FORCE NEENA THAPA GORAKHPUR UTTAR PRADESH 273008 UDYAM UP 32 0054752 | GORAKHPUR | UTTAR PRADESH | 273008 | ₹21.0 L | L2 | Rejected-AOC Not L1 |
| 3 | L3₹25.4 LRejected-AOC | ₹25.4 L | L3 | Rejected-AOC Not L1 |
| Sl No | Description | Qty | Unit | MAYUR ELECTRIC SERVICES L3 | om sai enterprises L2 | RAMESH CONSTRUCTION COMPANY L1 |
|---|---|---|---|---|---|---|
| 0.00Schedules of Works | ||||||
| 1.00 | Maintenance and general servicing to switchgear (VCB/RMU(up to 7 ways)/CSS as one unit) carrying out insulation resistance testing, CRM testing, 3 pole timing testing with transportation under AMC carrying out overhauling, calibration by using suitable test kits, and cleaning the switch gear terminals / moving parts of electric / mechanically with suitable cleaning agents in all respects by taking care of reference drawings & specifications of OEM, attending complaints on faults on faulty/requirement/emergency calls of any type within the contract period and testing to VCB/protection relay by disconnecting, opening of indoor/out door type VCB/RMU (Make : Crompton / Megawin / Yamuna Denson / ABB Ltd, Alsthom /Schneider/L&T) of any technical specification of 33/11 KV grade VCB current rating 400/630/800/1250 Amps (In/out going feeders) checking, examining complete VCB in terms of electrical and mechanical respects after complete servicing with reference to OEM drawings with automatic facilitated operating features, and review the control switches with wiring and replacement of minor spares like fuses, wires, terminals/blocks and removing/replace unserviceable / defective spare parts with new spares under relevant items, reassembling the VCB complete in all respects up to serviceability state of switch gear to satisfactory of Engr-In-charge complete all a specified and directed. | 14 | Each Job | 10,500 ₹1.5 L | 8,000 ₹1.1 L | 9,000 ₹1.3 L |
| 2.00Note for Item1 : (i) Replacement of unserviceable parts shall be measured and paid separately under relevant item of Sch 'A' as supply only but fixing charges of the parts replaced /repaired is deemed to be included in the item rate. (ii) Servicing shall be got carried out through a approved agency of any state/Central govt CEI (chief electrical Inspectorate) and RMU up to 7 ways/CSS of any type (compact sub station allied with VCB's) is consider as one unit. (iii) Engineer shall consider instructions of OEM specifications, drawings to carryout repair/servicing. The service engineer shall submit a service report and calibration certificate for each VCB/RMU/CSS. (iv) Any minor item not included in CA and required for successful operation of the panel will be provided by the contractor & same shall deemed to be included in the quoted rates. (v) Penalty shall be imposed in case of failing to attend the complaint lodged of any mode within 24 Hours @ Rs 1000/- fault for each day cumulatively and same shall be deducted from his dues within contract period. | ||||||
| 3.00 | Supply only cast resin potential transformer suitable to existing VCB 33 KV grade and conforming to IS 3156-1992, insulation class 'B' suitable for existing breakers ratio 33000/RT3/110/RT3/110/RT3V confirming to IS-3156-1992, VF 1.2 cont & 1.9 for 8 hours frequency 50 Hz model ECS33F volt 110/RT3 (S-1 &2), VA& PH iis 100VA & 50VA type Phase to Earth. Make :- Schneider or equivalent in AREVA/SIEMENS/ABB/Megawin/ Schneider | 2 | Each | 35,000 ₹70,000 | 35,000 ₹70,000 | 36,000 ₹72,000 |
| 4.00 | Supply only Spring charge motor existing capacity single phase for functional of HT VCB of capacity 33 KV grade type AGSH33022-01 & AGSH33022-01 of 220/250/AC/DC suitable for existing makes complete all as specified and as directed.
Make : MEGAWIN/ AREVA/SIEMENS/ABB/Schneider | 2 | Each | 10,000 ₹20,000 | 11,000 ₹22,000 | 10,800 ₹21,600 |
| 5.00 | Supply only Current transformer suitable for existing breakers of capacity 33 KV grade Indoor type ratio 200/5-5A, H.S.V-36KV, Insulation class B, R.P.C-200A, I.L 36/70/170 KV as per IS-2705-1992, IEC 61869-1&2 frequency 50Hz, 25 KA/Sec class 0.5/5P10, 15 VA/15VA. Make :- Megawin or equivalent in AREVA/SIEMENS/ABB/Schneider | 2 | Each | 29,000 ₹58,000 | 21,000 ₹42,000 | 18,000 ₹36,000 |
| 6.00 | Supply and fixing of Gear box of 33 KV HT VCB panel including taking out old U/S Gear box complete all as specified and as directed. Make Megawin or equivalent in AREVA/SIEMENS/ABB/Schneider | 2 | Each | 13,000 ₹26,000 | 9,000 ₹18,000 | 9,000 ₹18,000 |
| 7.00 | Supply only Tripping coil DC 24/110 volts suitable for existing breakers.
Make : MEGAWIN/ AREVA/SIEMENS/ABB/Schneider | 3 | Each | 2,000 ₹6,000 | 1,800 ₹5,400 | 1,800 ₹5,400 |
| 8.00 | Supply only Closing coil DC 24/110 volts suitable for existing breakers.
Make : MEGAWIN/ AREVA/SIEMENS/ABB/Schneider | 3 | Each | 2,000 ₹6,000 | 1,800 ₹5,400 | 1,800 ₹5,400 |
| 9.00 | Supply only Spring charge motor 1.5 KW single phase for functional of HT VCB suitable for existing makes complete all as specified and as directed.
Make : MEGAWIN/ AREVA/SIEMENS/ABB/Schneider | 2 | Each | 8,700 ₹17,400 | 12,000 ₹24,000 | 18,000 ₹36,000 |
Updated dates
Tender Value
₹26.4 L
EMD Value
₹52,800
Closing Date
4 May 2026, 6:00 pmClosed
GE (AF) Bidar
Garrison Engineer (Air Force) Bidar, Military Engineer Services, Air Force Station Bidar, Bidar-585401
REAPAIRS, MAINT OF VCBs AND OTHER HT INFRASTRCTURE AND ALLIED WORKS AT AFS BIDAR
2026_MES_758750_1
CA NO. GE(AF)/BID/TOKEN/65 OF 2025-2026 8216/E8
Open Tender
Electrical and Maintenance Works
180 days
Bidar
As per NIT
8 documents required · 8 mandatory
₹500
GE (AF) Bidar
₹52,800
Yes
19 Jun 2026
31 Mar 2026
11 May 2026
1 Apr 2026
4 May 2026
15 Apr 2026
1 Apr 2026 - 14 Apr 2026
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.34 MB
Tender8216.pdf
Tender Documents • 1.03 MB
BOQ_849865.xls
BOQ • 17.49 MB
Download all tender documents and submit your bid