ADDL. CHIEF ENGINEER (M)-4
DELHI JAL BOARD GOVT OF N.C.T OF DELHI OFFICE OF THE EXECUTIVE ENGINEER (T)/ ACE (M)-4 LUCKNOW ROAD, TIMARPUR, DELHI-110054.
Providing and fixing of 12 Mtr. High Mast Light at Azadpur APMC BPS
2021_DJB_213301_1
NIT No. 5 Item No. 10 EE (T)/ACE( M)-4
Open Tender
Miscellaneous Works
Works
30 days
ADDL. CHIEF ENGINEER (M)-4
Please refer Tender documents.
9 documents required · 9 mandatory
₹500
Account No SB 50448339804
Exempted
24 Jan 2022
22 Dec 2021
29 Dec 2021
22 Dec 2021
29 Dec 2021
22 Dec 2021
Fabrication and supply of 12 Mtr high mast shaft in one section suitable for wind speed with raising lowering system comprising, head frame, luminaries carriage suitable to install 06 Nos. luminaries in symmetrical arrangement, double drum winch, 5 mm dia. SS wire rope cable connector, manual handle, junction box lightening .
Supply of foundation bolts, manufactured from special steel along with nuts, washer, anchor, plates and templates.
Supply of Energy efficient environment friendly, long life, exclusive innovative die-cast aluminum flood LED light as light source suitable for height lighting architectural features or retal spaces,1X200 watt LED Fitting complete as required. Make: Bajaj/Philips/Havells/DJB approved.
Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 4930, Part II complete with fitting and cutting, jointing etc..direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required.
Supply of MCB 63 Amp SPN, C-series. Make :- Havells/L&T/DJB approved.
Supply of MCB sheet steel enclosure for above MCB. Make :- Havells/L&T/DJB approved.
Supply of 4x16 sq. mm PVC insulated & PVC sheathed Aluminum armored conductor cable. Make :-Grandley/Gloster/ICC/Universal/DJB approved.
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1KV grade of following size In Pipe etc as reqd. upto 35sq mm.
Construction of shallow foundation with M25 grade concrete for the high mast consideration the safe soil bearing capacity at site as 10 T/SqMtr. at 2 Meter depth with all materials and labour.
Erection of the high mast with the help crane and suitable tools & tackles, foundation bolt, wiring & fixing of luminaries on pole with all materials like PVC insulated PVC sheathed Flexible cable of suitable copper conductor cores of 1.5 Sq. mm, lugs etc. i/c all labour. The job also includes fixing of MCB in control box, fixing of MCB DP ( and its connections with existing main switch) as taken above and connections of luminaries with control box with copper cable and from control box to main MCB DP with the help of aluminum cable with required thimbling, tapping etc as required.
Earthing with G. I. earth plate 600mmx600mmx3mm thick including accessories, and providing masonry enclosure with cover plate heaving locking arrangement and watering pipe of 2.7 meter long etc. with charcoal/ coke/ and salt as required.
Loading, unloading, cartage and transportation charges for the above high mast pole upto the side i/c charges of heavy labour etc. as per site requirement
Testing & Commissioning of complete work in the presence of Engineer-in-charge.
DEV ENGINEERS
SHREE KRISHANA ENGINEERING
Volts And Watts Electronics Pvt. ltd.
Devraj Enterprises
HYDROCON ENGINEERS
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .