executive engineer kadodara division
Tender for Work for Laying, Testing & Commissioning of 11/22KV under Ground XLPE Cable (185 SQ MM XPLE cable by DGVCL) with cable end Termination & Straight jointing Kits ( by contractor) on ARC Basis for Feeder bifurcation work & other work under various schemes at Kadodara Ind Sdn under Kadodara Division.
286406
KAD/O&M/EXP/N-Procure/2026/03/No.222 date. 07-03-2026 SR. NO.08
Open
Electrical
Works
Surat
3 documents required · 3 mandatory
₹1,180
DAKSHIN GUJARAT VIJ COMPANY LTD.
₹40,000
14 Mar 2026
14 Mar 2026
14 Mar 2026
24 Mar 2026
14 Mar 2026
ARC work of Laying, Testing and commissioning of 11/22kV XLPE UG cable
Sr. No. Item Code Item Unit
Labour charge for excavation of cable trench of 400mm width x 1200mm depth, in any type of soil
140 9925000001 for laying of cable of size up to 240 mm2 (For additional cable 200 mm additional width shall be Meter
considered i.e. half trench length is to be considered)
Labour charge for excavation of cable trench of 600mm width x 1200mm depth, in any type of soil
141 9925000002 for laying of cable of size up to 240 mm2 (For additional cable 200 mm additional width shall be Meter
considered i.e. half trench length is to be considered)
Labour charge for excavation of cable trench of 400mm width x 1500mm depth, in any type of soil
142 9925000003 for laying of cable of size up to 240 mm2 (For additional cable 200 mm additional width shall be Meter
considered i.e. half trench length is to be considered)
Labour charge for laying of 11kV / 22 kV XLPE Cable of size up to 240 mm2 & preparation of sand
layer 100mm thick, in the cable trench & covering the cable with 150 mm dia (Inner), thickness
mm, 1.0 meter long RCC half round muffs and providing and fixing of 4inch width yellow colour
143 9925000004 polyethylene tape with printing "CAUTION ELECTRIC CABLE BELOW" at 0.75 m depth from Meter
ground surface after laying cable in trench. This will provide indication that electric cable is passing
underground so as to protect cable from mechnical injuries, refilling the same, as per Instruction of
Engineer in Charge (EIC).
Labour charge for horizontal drilling using Auger machine without damage to surface road at
max 2.0 mtrs depth & putting of 6.11 kg/cm2 , class-4,Green color, 110mm O.D. , 8.5mm thickness
H.D.P.E. pipe confirms to IS 4984- 1987(3rd revision) and BIS certification and laying of 11KV/22KV
XLPE cable of size up to 240 mm2 in HDPE pipe, as per Site Condition (excluding cost of pipe).
The detail map obtained from HDD machine and excell sheet(hard and soft copy) indicating the
respective depth and distance from adjacent landmark for each segment for HDD is must required
to be submitted. HDD to be carried out at depth 1.5 mtrs to 2.0 mtrs as per site conditions and as
per instruction of EIC.
Labour charge for horizontal drilling manually without damage to surface road at max 2.0 mtrs
depth & putting of 6.11 kg/cm2 , class-4,Green color, 110mm
O.D. , 8.5mm thickness H.D.P.E. pipe confirms to IS 4984-1987(3rd revision) and BIS certification
145 9925000006 and laying of 11KV/22KV XLPE cable of size up to 240 mm2 size, as per Site Condition (excluding Meter
cost of pipe). The detail map and excell sheet(hard and soft copy) indicating the respective depth
and distance from adjacent landmark for each segment of cable to be submitted. Drilling to be
carried out at depth Minimum 1.2 mtrs to 2.0 mtrs as per site conditions as per instruction of EIC.
Supply of 6.11kg/cm2 , class-4,Green color, 110mm O.D. , 8.5 mm thickness
146 9925000007 H.D.P.E. pipe confirms to IS 4984 and BIS certification for laying of underground 11KV / 22KV Meter
XLPE cable up to 240 mm2 size.
Labour work for RCC concreting on disputed location and repairing of damage portion of road
147 9925000008 crossing for the work carried out for roads crossing as well as concreting & muffing of ploes CMT
including all materials (1:2:4)
Providing & fixing concrete stone route marker of 300 mm width x 150 mm thick x 650 mm height
embedded in earth at least 300 mm below & 350 mm above ground level respectively at distance
approx 50 meters along the length of cable. The RCC concreting (1:2:4)(all necessary maeterials
will be in bidder's scope) of route marker is to be carried out 300 mm width x 150 mm thick x
148 9925000009 mm below ground level as per instruction of EIC. The route marker should be with name of No.
company with approved yellow colour-DGVCL. The distance from marker to cable and cable depth
with feeder name etc., marked with arrow sign is to be painted on it.The route marker is to be fixed
at location near to any fixed permanent location (not necessary to fix exact on top of cable) as per
instruction of EIC.
Erection of D.P. (double pole) structure using 9 / 11 Mtr. RSJ pole with cable connection
149 9925000010 arrangement along with fitting of necessary fabrication for 11KV cable including excavation of pit & No.
refilling of earth as per instruction of EIC. (Exclusive of concreting & muffing of poles)
Erection of Single pole structure using 9 / 11 Mtr RSJ pole with cable connection arrangement
150 9925000011 along with fitting ofnecessary fabrication for 11KV/22 KV cable including excavation of pit & refilling No.
of earth as per instruction of EIC. (Exclusive of concreting & muffing of poles)
Erection of D.P. (double pole) structure using 8.0 Mtr. PSC pole with cable connection
151 9925000012 arrangement along with fitting of necessary fabrication for 11KV cable including excavation of pit & No.
refilling of earth as per instruction of EIC. (Exclusive of concreting & muffing of poles)
Erection of Single pole structure using 8.0 Mtr PSC pole with cable connection arrangement
152 9925000013 along with fitting ofnecessary fabrication for 11KV/22 KV cable including excavation of pit & refilling No.
of earth as per instruction of EIC. (Exclusive of concreting & muffing of poles)
Labour charge for erecting of 11kV / 22 kV XLPE cable of size up to 240 mm2 on DP Structure
153 9925000014 with fixing of 02 Nos polymer cleats on top and middle part.Polymer cleats, nut bolts etc. fixing Per Job
material to be provided by contractor.
Providing & fixing of 6.11kg/cm2 , class-4,Green color, 110mm O.D. , 8.5mm thickness H.D.P.E.
pipe confirms to IS 4984 and BIS certification on the erected DP structure for the mechanical
protection of cable by inserting the cable inside HDPE pipe. The HDPE pipe shall be erected in
such a way that 300mm shall be below the ground level and the rest 2700 mm shall be supported
on the DP Structure with 01 No Polymer cleat.All materials including polymer cleat and Nut bolt to
be provided by contractor.
Providing and fixing of pipe type earthing from 80 mm dia class-B GI pipe with pit to be filled with
salt & coke and construction of chamber as per DGVCL Drg. No. dg /100 for DP and cable. The
earthing pit should be joined with cable by G.I. strip of size 1” width & 2 mm thick. All material GI
pipe, Coke, Salt etc will be supplied by bidder.
Supply & fixing of heat shrink type end terminations (outdoor) for upto 11kV 3C x 185 mm2
size XLPE cable as per DGVCL technical specification
Supply & fixing of heat & shrinkable end terminations (outdoor) for upto 22 kV
3C x 185 mm2 size XLPE cable as per DGVCL technical specification)
Supply & fixing of heat shrink type end terminations (indoor) for upto 11kV 3C x 185 mm2 size
XLPE cable as per DGVCL technical specification)
Supply & fixing of heat & shrinkable end terminations (indoor) for upto 22 kV
3C x 185 mm2 size XLPE cable as per DGVCL technical specification
Supply & fixing of heat shrinkable straight through joint for upto 11kV 3C x
185 mm2 size XLPE cableas per DGVCL technical specification.
Supply & fixing of heat shrinkable straight through joint type for upto 22kV 3C x 185 mm2 size
XLPE cable as per DGVCL technical specification
Labour charge for excavation of 2100mm long x 1200mm wide x 1200 mm deep joint pits for
installation of 11kV / 22kV Straight through joints as per instruction of engineer-in-charge &
covering the cable with 150 mm dia (Outer), thickness 25 mm, 1.0 meter long RCC half round
muffs & refilling same as per instruction of EIC .
Providing and fixing of insulating bus bar, made from 11KV/22KV XLPE cable after removal of semi
conducting layer and applying of PVC heat shrinkable anti- tracking core insulating tubing (1.1KV),
on both end terminal using Aluminium long barrel heavy duty up to 240 sq mm lugs, Aluminium bus
163 9925000024 connector. Taping with PG- clamp for bus conductor as per drawing and as per instruction of EIC. No.
The Alluminium lugs and PG clamp shall be covered with 11KV/22KV HT insulating
tapes.(11KV/22KV XLPE cable will be in scope of DGVCL while all other materials will be in bidder's
Testing of cable at various points and commissioning the feeder as per instruction of engineer-in-
charge.Test result shall be submitted by contractor with bill.
Preparation and submission of 6 (six) copies, of complete layout drawings with
GIS mapping as per actual cable routing showing road crossing, HDPE pipe sleeving, jointing Set
locations, markers etc.
Providing & fixing of aluminium tag of size 250 mm (L) x 75 mm (W) from 3 mm aluminium sheet
along with 1.0 mm dia aluminium binding wire for fixing of aluminium tag near end termination joint
166 9925000029 at DP structure for identifyng the cable. The details of feeder i.e. 11 / 22 KV with feeder name No.
shound be punched on the tag by letter punch of size 16 mm as per instruction of In-charge
Supply & fixing of heat shrink type end terminations (outdoor) for 11kV 3C x 240 mm2 size XLPE
cable as per DGVCL technical specification
Supply & fixing of heat & shrinkable end terminations (outdoor) for 22 kV 3C x 240 mm2 size
XLPE cable as per DGVCL technical specification)
Supply & fixing of heat shrink type end terminations (indoor) for 11kV 3C x 240 mm2 size XLPE
cable as per DGVCL technical specification)
Supply & fixing of heat & shrinkable end terminations (indoor) for 22 kV 3C x 240 mm2 size XLPE
cable as per DGVCL technical specification
Supply & fixing of heat shrinkable straight through joint for 11kV 3C x 240 mm2 size XLPE
cableas per DGVCL technical specification.
Supply & fixing of heat shrinkable straight through joint type for 22kV 3C x 240 mm2 size XLPE
cable as per DGVCL technical specification
173 9925000047 Laying of any size of 11/ 22 KV XLPE /PILC Cable in redaymade trench or in open space Cable
174 9925000060 Labour charges for Lying of O/H XLPE cable pole to pole KM
175 9925000064 Supply of 150 mm dia (Inner), thickness 25 mm, 1.0 meter long RCC half round pipe No.
HT TAPPING FROM THE EXISTING POLE INCLUDING FIXING OF CROSS ARMS, CLAMPS
ANTI-CLIMBING DEVICES, DANGER BOARD, INSULATORS ETC. COMPLETE AND PAINTING
OF FABRICATED MATERIALS AND NUMBERING COMPLETE WITH COST OF PAINTS AS PER
STANDARD SPECIFICATION BUT EXCLUDING ERECTION OF GUY SET AND EARTHING.
ERECTION OF PSC POLES OF 8 *200 KG INCLUDING EXCAVATION OF PIT AND REFILLING
OF EARTH, FIXING OFCROSS ARMS, TOP FITTING CLAMPS ANTI-CLIMBING DEVICES,
INSULATORS ETC. COMPLETE AND PAINTING OF FABRICATED MATERIALS USED ON THE
POLES AND NUMBERING WITH COST OF PAINT AS PER STANDARD SPECIFICATION BUT
EXCLUDING ERECTION OF GUY SET AND EARTHING.
ERECTION OF STEEL POLES OF 9 TO 11 METERS INCLUDING EXCAVATION OF PIT AND
REFILLING OF EARTH, FIXING OFCROSS ARMS, TOP FITTING CLAMPS ANTI- CLIMBING
DEVICES, DANGER BOARD, INSULATORS ETC. COMPLETE AND PAINTING OF STEEL POLE,
FABRICATED MATERIALS USED ON THE POLEAND NUMBERING WITH COST OF PAINT AS
PER STANDARD SPECIFICATION BUT EXCLUDING ERECTION OF GUY SET AND EARTHING.
ERECTION OF STEEL POLE OF 13 METERS FOR RAILWAY CROSSING ON BG/MG/NG LINE
FOR 0.400/11/22KV OVERHEAD LINES I.E INCLUDING EXCAVATION OF PIT & REFILLING OF
EARTH, FIXING CROSS ARMS, TOP FITTING CLAMPS,ANTI-CLIMBING DEVICES DANGER
BOARD, INSULATORS ETC. COMPLETE AND PAINTING OF STEEL POLES, FABRICATED
4 9926000004 MATERIALS USED ON THE POLES AND NUMBERING WITH COSTOF PAINT AS PER No.
STANDARD SPECIFICATION BUT EXCLUDING ERECTION OF GUY SETS AND EARTHING.
ERECTION OF DOUBLE POLE STRUCTURE OF 8 METERS 200 KG PSC POLES INCLUDING
EXCAVATION OF PITS & REFILLING OF EARTHING, FIXING OF CHANNELS, SUPPORTING
ANGLES,CLAMPS, ANTI-CLIMBING DEVICES DANGER BOARDS,INSULATORS
ETC.COMPLETE AND PAINTING OF FABRICATED MATERIALS USED ON THE POLES AND
NUMBERING WITH COST OF PAINT AS PER STANDARD SPECIFICATION BUT EXCLUDING
ERECTION OF GUY SETS AND EARTHING.(WITHOUT
ERECTION OF DOUBLE POLE STRUCTURE OF 9 TO 11 METERS.STEEL POLE INCLUDING
EXCAVATION OF PITS & REFILLING OFEARTH, FIXING OF CHANNELS, SUPPORTING
ANGLES, CLAMPS,ANTI-CLIMBING DEVICES DANGER BOARDS, INSULATORS
ETC.COMPLETE & PAINTING OF POLES,FABRICATED MATERIALSUSED ON THE POLES AND
6 9926000006 NUMBERING WITH COST OF PAINTSAS PER STANDARD SPECIFICATION BUT EXCLUDING No.
ERECTION OF GUY SET AND EARTHING.(WITHOUT AB SWITCH)
ERECTION OF DOUBLE POLE STRUCTURE WITH MOUNTING OF AB SWITCH, HG FUSES OF
8 MTRS 200 KG PSC POLES INCLUDING EXCAVATION OF PITS AND REFILLING OF
EARTH,FIXING OF CHANNELS SUPPORTING ANGLES, CLAMPS, ANTI- CLIMBING DEVICES,
DANGER BOARDS, INSULATORS,DOFUSES ETC. COMPLETE AND PAINTING OF
FABRICATED MATERIALS USED ON THE POLES AND NUMBERING WITH COSTOF PAINT AS
PER STANDARD SPECIFICATION BUT EXCLUDINGOF ERECTION OF GUY SET AND
EARTHING.(WITH AB SWITCH)
ERECTION OF DOUBLE POLE STRUCTURE WITH MOUNTING OF AB SWITCH,HG FUSES,
9 TO 11 METERS STEEL POLES INCLUDING EXCAVATION OF PITS AND REFILLING OF
EARTH, FIXING OFCHANNEL, SUPPORTING ANGLES, CLAMPS, ANTI- CLIMBING DEVICES
DANGER BOARDS, INSULATORS, ETC. COMPLETE AND PAINTING OF POLES FABRICATED
8 9926000008 MATERIALS USED ON THE POLES AND NUMBERING WITH COST OF PAINT AS PER No.
STANDARD SPECIFICATION BUT EXCLUDING ERECTION OF GUY SET AND
EARTHING.(WITH AB SWITCH)
ERECTION OF DOUBLE POLE STRUCTURES WITH MOUNTING OFAB SWITCH, HG FUSES,
TRANSFORMERS, LIGHTENING ARRESTORS, DISTRIBUTION BOX. OF 8 METER,200KG
PSC POLE METERS POLES INCLUDING EXCAVATION OF PITS AND REFILLING OF EARTH,
CARTING OF TRANSFORMERS FROMSTORES TO SITE, FIXING OF CHANNELS,
SUPPORTING ANGLES,BRACINGS CROSS ARMS CLAMPS, ANTICLIMBING DEVICES
DANGER BOARDS, CONDUCTOR AND CABLE WIRING ETC.COMPLETE AND PAINTING OF
FABRICATED MATERIALS USEDON THE POLES AND NUMBERING WITH COST OF PAINT AS
PER STANDARD SPECIFICATION BUT EXCLUDING ERECTION OF GUY SETS AND
ERECTION OF DOUBLE POLE STRUCTURE WITH MOUNTING OF AB SWITCH,HG FUSES
TRANSFORMERS, LIGHTENING ARRESTORS, DISTRIBUTION BOX 9 TO 11 METERS STEEL
POLES INCLUDING EXCAVATION OF PITS & REFILLING OF EARTH CARTING OF
TRANSFORMERS FROM STORE TO SITE, FIXINGOF CHANNELS SUPPORTING ANGLES,
BRACING, CROSS ARMS,CLAMPS, ANTICLIMBING DEVICES, DANGER
BOARDS,CONDUCTOR AND CABLE WIRING ETC. COMPLETE AND PAINTING OF POLES
FABRICATED MATERIALS USED ON THE POLES AND NUMBERING AS PER STANDARD
SPECIFICATION BUT EXCLUDING ERECTIONS OF GUY SETS AND EARTHING.
ERECTION OF GUY SET INCLUDING EXCAVATION OF PITS & REFILLING OF EARTH AS PER
STANDARD SPECIFICATION WITH STAY CLAMPS, STAY WIRE, ANCHOR ROD, TURN
11 9926000011 BUCKLE, EYEBOLT, GUY INSULATOR, CEMENT CONCRETE BLOCK ETC. BUT EXCLUDING No.
9926000012 CONCRETING OF POLES, GUYS, ETC. INCLUDING COST OF CEMENT SAND METAL (1:2:4) CMT
AND WATER ETC. AS PER STANDARD SPECIFICATION.(cement Should be
grade) used for Concreting.
9926000013 ERECTION OF COIL TYPE EARTHING INCLUDING COST OF COAL,SALT ETC. BUT WITHOUT No.
13 COST OF GI WIRE AS PER STANDARD SPECIFICATION(20kg solt+20kg coal)
9926000014 ERECTION OF GI PIPE/CI PLATE TYPE EARTHING INCLUDINGCOST OF COAL SALT ETC. No.
BUT WITHOUT COST OF PIPE/GIPLATE GI WIRE AS PER STANDARD
SPECIFICATION.(20kg solt+20kg coal)
9926000015 ERECTION OF STREET LIGHT FIXTURE COMPLETE WITH CLAMPS, BRASS NIPPLE, BRASS No.
HOLDER TECK WOOD BUSH,REFLECTORS FUSE, WIRING ETC. AS PER STANDARD
SPECIFICATION BUT EXCLUDING COST OF MATERIALS.
9926000016 STRINGING OF(30mm2)ACSR/34MM@,55MM2 AAA CONDUCTOR for ALL TYPE OF ONE
CONDUCTOR (EXCEPT DOG CONDUCTOR) FOR 11/22KV & LT LINES INCLUDING FIXING OF COND
INSULATORS, BINDING JUMPERING ETC. PER
9926000017 STRINGING OF GI WIRE 8 SWG INCLUDING BINDING JUMPERING ETC. DO
PROVIDING SINGLE PHASE SERVICE CONNECTION WITH PVC 2.5/4MM2 TWIN CORE
CABLE FROM TERMINAL POLE TO METERING POINT INCLUDING FIXING OF METER WITH
18 9926000018 METER EARTHING COMPLETE WORK AS PER STANDARD SPECIFICATION BUT No.
EXCLUDING COST OF MATERIALS.
PROVIDING THREE PHASE 4 WIRE SERVICE CONNECTION WITH PVC 4MM2/10MM2 FOUR
CORE CABLE FROM TERMINAL POLE TO METERING POINT INCLUDING FIXING OF METER
19 9926000019 WITH METER EARTHING COMPLETE WORK AS PER STANDARD SPECIFICATION BUT No.
EXCLUDING COST OF MATERIALS.
9926000020 ADDITIONAL COST FOR EXCAVATION OF PIT IN HARD ROCK AREA FOR ERECTION OF No.
POLE/ GUY ETC. AS PER STANDARD SPECIFICATION OVER & ABOVE NORMAL COST
COVERED AGAINST EXCAVATION OF PIT UNDER NORMAL SOIL FOR ERECTION OF
POLE,GUY, DOUBLE POLE STRUCTURE EARTHING WITH THE APPROVAL OF
SUPDT.ENGINEER.
21 9926000021 PROVIDING GUARDING TO HT LINE ON ROAD/ RAIL CROSSING. MTR
22 9926000022 PROVIDING GUARDING OF LT LINES ON ROAD/RAIL CROSSING. MTR
23 9926000023 LT LINE TAPPING- SINGLE PHASE No.
24 9926000024 LT LINE TAPPING- THREE PHASE No.
9926000025 Stringing/LAYING OF OVER HEAD LT CABLE FOR ROAD CROSSING,HT LINE CROSSING AND No.
25 TELEPHONE LINE CROSSING ETC.(PER SPAN)
ERECTION OF SINGLE POLE STRUCTURES WITH , HG FUSES,TRANSFORMERS,
LIGHTENING ARRESTOR, DISTRIBUTION BOX. ON 8 METERS 200 KGAND PSC POLE
INCLUDING EXCAVATION OF PITS AND REFILLING OF EARTH, CARTING OF
TRANSFORMERS FROM STORES TO SITE, FIXING OF CHANNELS, SUPPORTING
ANGLES,BRACINGS CROSS ARMS CLAMPS, ANTICLIMBING DEVICES DANGER BOARDS,
CONDUCTOR AND CABLE WIRING ETC.COMPLETE AND PAINTING OF FABRICATED
MATERIALS USED ON THE POLE AND NUMBERING WITH COST OF PAINT AS PER
STANDARD SPECIFICATION BUT EXCLUDING ERECTION OFGUY SETS AND EARTHING.
ERECTION OF SINGLE POLE STRUCTURES WITH MOUNTING OFAB SWITCH , HG
FUSES,TRANSFORMERS, LIGHTENINGARRESTOR, DISTRIBUTION BOX. ON 9 to
METERS RSJ POLE INCLUDING EXCAVATION OF PITS AND REFILLING OF EARTH, CARTING
OF TRANSFORMERS FROM STORES TO SITE, FIXING OF CHANNELS, SUPPORTING
ANGLES,BRACINGS CROSS ARMS CLAMPS, ANTICLIMBING DEVICES DANGER BOARDS,
CONDUCTOR AND CABLE WIRING ETC.COMPLETE AND PAINTING OF FABRICATED
MATERIALS USED ON THE POLE AND NUMBERING WITH COST OF PAINT AS PER
STANDARD SPECIFICATION BUT EXCLUDING ERECTION OFGUY SETS AND EARTHING.
ERECTION OF PSC POLES OF 10 *270 KG INCLUDING EXCAVATION OF PIT AND REFILLING
OF EARTH, FIXING OF CROSS ARMS, TOP FITTING CLAMPS ANTI-CLIMBING DEVICES,
INSULATORS ETC. COMPLETE AND PAINTING OF FABRICATED MATERIALS USED ON THE
28 9926000028 POLES AND NUMBERING WITH COST OF PAINT AS PER STANDARD SPECIFICATION BUT No.
EXCLUDING ERECTION OF GUY SET AND EARTHING.
ERECTION OF DOUBLE POLE STRUCTURE OF 10 METERS 270 KG PSC POLES INCLUDING
EXCAVATION OF PITS & REFILLING OF EARTHING, FIXING OF CHANNELS, SUPPORTING
ANGLES,CLAMPS, ANTI-CLIMBING DEVICES DANGER BOARDS,INSULATORS
ETC.COMPLETE AND PAINTING OF FABRICATED MATERIALS USED ON THE POLES AND
29 9926000029 NUMBERING WITH COST OF PAINT AS PER STANDARD SPECIFICATION BUT EXCLUDING No.
ERECTION OF GUY SETS AND EARTHING.(WITHOUT AB SWITCH)
9926000030 STRINGING OF 100MM2 ACSR/100MM2 AAAC CONDUCTOR FOR 11/22KV & LT LINES ONE
INCLUDING FIXING OFINSULATORS, BINDING JUMPERING ETC. COND
9926000031 STRINGING OF DOG CONDUCTOR FOR 11/22KV & HT LINES INCLUDING FIXING OF ONE
INSULATORS, BINDING JUMPERING ETC. COND
ERECTION OF DOUBLE POLE STRUCTURES WITH MOUNTING OF AB SWITCH, HG FUSES,
TRANSFORMERS, LIGHTENING ARRESTORS, DISTRIBUTION BOX. OF 10 METERS
KGAND PSC POLES INCLUDING EXCAVATION OF PITS AND REFILLING OF EARTH,
CARTING OF TRANSFORMERS FROMSTORES TO SITE, FIXING OF CHANNELS,
SUPPORTING ANGLES,BRACINGS CROSS ARMS CLAMPS, ANTI-CLIMBING
DEVICES,DANGER BOARDS, CONDUCTOR AND CABLE WIRING ETC.COMPLETE AND
PAINTING OF FABRICATED MATERIALS USED ON THE POLES AND NUMBERING WITH COST
OF PAINT AS PER STANDARD SPECIFICATION BUT EXCLUDING ERECTION OF GUY SETS
9926000033 DISMENTALLING OF 8 MTR PSC POLE WITH CREDITING OF FABRICATION AT STORE & No.
33 STACKING OF POLE SAFELY ON ROAD SIDE OR CREDITING TO DEPARTMENTAL STORE
9926000034 DISMENTALLING OF 10 MTR PSC POLE WITH CREDITING OF FABRICATION AT STORE & No.
34 STACKING OF POLE SAFELY ON ROAD SIDE OR CREDITING TO DEPARTMENTAL STORE
DISMENTALLING OF TRANSFORMER CENTRE (8 MTR PSC POLE) (WITH TRANSFORMER)
WITH CREDITING OF FABRICATION & TRANSFORMER AT STORE & STACKING OF POLE
SAFELY ON ROAD SIDE OR CREDITING TO DEPARTMENTAL STORE
DISMENTALLING OF TRANSFORMER CENTRE (8 MTR PSC POLE) (WITHOUT
TRANSFORMER) WITH CREDITING OF FABRICATION AT STORE & STACKING OF POLE
SAFELY ON ROAD SIDE OR CREDITING TO DEPARTMENTAL STORE
STRINGING OF LT ABC OF 1*35 SQ MM + 1*25 SQ MM INCLUDING FITTING OF ALL
ACESSARIES I.E. SPECIAL DESIGN SUSPENSION / TENSION CLAMP, FIXING OF CROSS
ARM, LT SHACKLE INSULATOR ETC. FOR FIXING OF MESSENGER WIRE AND TO PROVIDE
SERVICE CONNECTION ON AERIAL BUNCH CABLE BY INSULATED PIERCEING
CONNECTORS THROUGH SERVICE CONNECTION BOX COMPLETE AS REQUIRED &
DIRECTED BY ENGINEER IN CHARGE.
STRINGING OF LT ABC OF 3*50 SQ MM +1*25 SQ MM+1*35 SQ MM INCLUDING FITTING OF
ALL ACESSARIES I.E. SPECIAL DESIGN SUSPENSION / TENSION CLAMP, FIXING OF CROSS
ARM, LT SHACKLE INSULATOR ETC. FOR FIXING OF MESSENGER WIRE AND TO PROVIDE
SERVICE CONNECTION ON AERIAL BUNCH CABLE BY INSULATED PIERCEING
CONNECTORS THROUGH SERVICE CONNECTION BOX COMPLETE AS REQUIRED &
DIRECTED BY ENGINEER IN CHARGE.
STRINGING OF 11KV ABC OF 3*95 SQ MM +80 SQ MM INCLUDING FITTING OF ALL
ACESSARIES I.E. SPECIAL DESIGN SUSPENSION / TENSION CLAMP, FIXING OF CROSS
39 9926000039 ARM, BINDING TO PIN INSULATOR,PREPARING SHACKLE POINT,JUMPERS ETC. AS KM
REQUIRED & DIRECTED BY ENGINEER IN CHARGE
STRINGING OF 22 KV ABC OF 3*70 SQ MM +95 SQ MM INCLUDING FITTING OF ALL
ACESSARIES I.E. SPECIAL DESIGN SUSPENSION / TENSION CLAMP, FIXING OF CROSS
ARM, BINDING TO PIN INSULATOR,PREPARING SHACKLE POINT,JUMPERS ETC. AS
REQUIRED AND DIRECTED BY ENGINEER IN CHARGE
STRINGING OF LT ABC OF 2*50 SQ MM +1*25 SQ MM+ 35 SQ MM INCLUDING FITTING OF
ALL ACESSARIES I.E. SPECIAL DESIGN SUSPENSION / TENSION CLAMP, FIXING OF CROSS
ARM, LT SHACKLE INSULATOR ETC. FOR FIXING OF MESSENGER WIRE AND TO PROVIDE
SERVICE CONNECTION ON AERIAL BUNCH CABLE BY INSULATED PIERCEING
CONNECTORS THROUGH SERVICE CONNECTION BOX COMPLETE AS REQUIRED &
DIRECTED BY ENGINEER IN CHARGE.
9926000042 DISMENTALING OF RSJ (9/11 METER) POLE AND CREDITING THE OLD MATERIAL TO STORE No.
DISMENTALING OF TRANSFORMER CENTER ON 10MTR,270KG PSC POLE(WITHOUT
TRANSFORMER) WITH CREDITING OF FABRICATION AT STORE AND STACKING OF POLE
SAFELY ON ROAD SIDE OR CREDITING TO DEPARTMENTAL STORE
DISMENTALING OF TRANSFORMER CENTER ON 10MTR,270KG PSC POLE(WITH
TRANSFORMER) WITH CREDITING OF FABRICATION AT STORE AND STACKING OF POLE
SAFELY ON ROAD SIDE OR CREDITING TO DEPARTMENTAL STORE
9926000045 DISMENTLING OF 11KV ABC OF 3*95 SQ MM +80 SQ MM AND CREDITING FITTING OF ALL KM
45 ACESSARIES AND FABRICATION TO DEPARTMENTAL STORE
DISMENTLING OF 22 KV ABC OF 3*70 SQ MM +95 SQ MM AND CREDITING FITTING OF ALL
46 9926000046 ACESSARIES AND FABRICATION TO DEPARTMENTAL STORE KM
9926000047 DISMENTALING OF LT ABC OF 1*35 SQ MM + 1*25 SQ MM AND CREDITING FITTING OF ALL KM
47 ACESSARIES TO DEPARTMENTAL STORE.
9926000048 DISMENTALING OF LT ABC OF 3*50 SQ MM +1*25 SQ MM+1*35 SQ MM AND CREDITING KM
48 FITTING OF ALL ACESSARIES TO DEPARTMENTAL STORE.
9926000049 DISMENTALING OF LT ABC OF 2*50 SQ MM +1*25 SQ MM+ 35 SQ MM AND CREDITING KM
49 FITTING OF ALL ACESSARIES TO DEPARTMENTAL STORE.
9926000050 RESTRINGING OF ALL TYPE OF CONDUCTOR (EXCEPT DOG CONDUCTOR) FOR 11/22KV & ONE
LT LINES INCLUDING FIXING OF INSULATORS, BINDING JUMPERING ETC. COND
9926000051 RESTRINGING OF DOG CONDUCTOR FOR 11/22KV HT LINES INCLUDING , BINDING ONE
JUMPERING ETC. COND
9926000052 LABOUR CHARGE FOR THE INSTALLATION OF NEW DTR METER. (METER WILL BE No.
PROVIDED BY DGVCL)
9926000053 LABOUR CHARGE FOR THE REPLACEMENT OF DTR METER AND OLD METER SHOULD BE No.
53 CREDITED TO SDN STORE. (METER WILL BE PROVIDED BY DGVCL)
9926000054 LABOUR CHARGE FOR PROVIDING CT COIL FOR DTR METER CONNECTION. (CT COIL PER
WILL BE PROVIDED BY DGVCL) CT
LABOUR CHARGE FOR REPLACEMENT OF CT COIL FOR DTR METER CONNECTION AND
55 9926000055 OLD CT SHOULD BE CREDITED TO SDN STORE. (CT COIL WILL BE PROVIDED BY DGVCL)
LABOUR CHARGE FOR FIXING OF MMB FOR DTR METER (MMB WILL BE PROVIDED BY
9926000057 LABOUR CHARGE FOR REPLACEMENT OF DTR METER BOX. (METER WILL BE PROVIDED No.
9926000058 PROVIDING / REPLACEMENT OF 1.5 SQ MM 10 CORE COPPER CABLE 3.5 METER (CABLE No.
TO BE PROVIDED BY AGENCY)
9926000059 LABOUR CHARGE FOR PROVIDING/RECONNECTION OF TERMINAL CONNECTION WITH PER
PROPER SIZE OF LUGS. (LUGS COST IS BORNE BY AGENCY) TERMI
LABOUR CHARGE FOR THE SPOT READING OF DTR METER WITH DETAIL SURVEY OF
DEFECT IF ANY. A DULY SIGN COPY BY SURVEYOR PERSON OF AGENCY IN PRO- FORMA
REPORT SHOULD BE SUBMITTED TO SDN OFFICE.(* ONLY IF ALL PARAMETER OF
60 9926000060 VOLTAGE, CURRENT & LOAD AS SHOWN IN PER-FORMA IS FILLED) AS PER THE
INSTRUCTION OF ENGINEER IN-CHARGE.
LABOUR CHARGE FOR THE SPOT READING OF DTR METER WITH DETAIL SURVEY OF
DEFECT IF ANY. A DULY SIGN COPY BY SURVEYOR PERSON OF AGENCY IN PRO- FORMA
REPORT SHOULD BE SUBMITTED TO SDN OFFICE. (DULY FILL PER-FORMA IN FAULT PER
CONDITION IN WHICH READING PARAMETER IS NOT SHOWN IN METER) DTR
9926000062 INSTALLATION OF DTR METER INCLUDING METER BOX, PROVIDING & FIXING OF 1.5SQ MM No.
SINGLE STRAND 10 CORE ARMOURED COPPER CABLE (3.5METER), TERMINATION IN
62 METER & COIL ETC.(METER, METER BOX, C.T./P.T. COIL WILL BE PROVIDED BY DGVCL)
9926000063 INSTALLATION OF DTR METER INCLUDING METER BOX, TERMINATION IN METER & COIL No.
ETC. (WITHOUT 10CORE COPPER CABLE) (METER, METER BOX, C.T./P.T. COIL WILL BE
PROVIDED BY DGVCL)
Binding of messanger Conductorat with a distance not more than 0.75 mtr with 6 turns minimum on XLPE
Cable with single strand binding wire (including cost of binding wire)
1.DGVCL will provide key material like M.S. materials,ABC/Bare conductors,PSC/RSJ
Poles,Insulators,Fabricated
materials etc. to the contractor.
2.All fabricated items shall be fabricated as per DGVCL approved drawing and by welding rods confirming to
the relevent ISI specification and as directed by Engineer in charge.
3.Necessary electricity connection for fabrication items shall be provided by DGVCL on payment of required
charge for connection & electricity bill of the same shall be paid by the agency.
4.All the rates are inclusive of PF & Exclusive of GST applicable time to time.
5.All steel material are to be painted as below:
(a) Scrubbing of rusted surface properly before applying the paints on to the RSJ poles & steel fabricated
materials of RSJ/PSC poles is must required.
(b) Two coats of approved ISI mark red oxide (primer) is to be properly painted for the RSJ poles & steel
fabricated materials of RSJ/PSC poles.
(c) Two coats of approved ISI mark silver paint (i.e. triple mangoes or equivalent quality silver paint) is to be
properly painted on to the RSJ poles & steel fabricated materials of RSJ/PSC poles.
Total Tender Estimated Amount-
Rupees FourtySeven Lakh Only (Excluding. Gst)
Executive Engineer (O&M),
DGVCL Kadodara Division.
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
NOTICE.pdf
Integrity Part.pdf
Detail Technical Specification.pdf
DRAFT TENDER CONDITION.pdf
Schedule-B.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .