HQ CWE(AF) Chandigarh PIN 160 003
REPAIR TO SEWAGE PLANTS, EXTERNAL WATER SUPPLY AND SUMMER/ COOLING APPLIANCES AT AF STATION HIGH GROUNDS UNDER GE (AF) CHANDIGARH
2020_MES_359888_2
CWE/AF CHD/CHD/T-04/2020-2021
Open Tender
Civil Works
Item Rate
180 days
High Ground
As per NIT
8 documents required · 8 mandatory
₹500
GE(AF) Chandigarh
₹23,800
Yes
7 Oct 2020
29 Aug 2020
14 Sept 2020
29 Aug 2020
12 Sept 2020
29 Aug 2020
Amount
WATER SUPPLY
Taking out defective submersible pump & motor set 6 to 8 stage, 700-900 LPM at 112mtr head of any dia upto 150mm from bore well with the help of chain pulley after disconnecting electrical connections from motor starter, disconnecting the column pipe from supply pipe line, opening each column pipe by unscrewing nut bolt, rubber packing of each column pipe, submersible cable and keeping aside for reuse, the number of column pipeS to be taken out upto 24-28 Nos. alongwith submersible cable, for repair / replacement of parts to make it fully functional, reassembling the same after repair, lowering/ installation to its original position, electric connection of input/ output electric supply, connecting the column pipe to supply pipe line, testing to its full load capacity at least for 4 hours and all other relevant tests including any minor repair, replacement of rubber gasket for column pipe etc. including transportation to workshop and vice-versa, complete all as specified and directed by the Engineer-in-Charge.
Dismantling of submersible motor 35 to 38 HP 415 volts 50 Hz 3 phase AC electric supply, taking out the burnt winding of stator, removal of burnt insulation material from the slots, cleaning the stator slots and preparation for rewinding the same and material and labour for winding the stator of motor with PVC insulated copper wire of standard size and superior quality copper winding wire as per the existing gauge including the F class insulation materials, turning, balancing & alignment of rotor etc. to get the proper RPM and torque & tested to its full load capacity complete all as specified and directed Note :- Spare parts required to be replaced shall be measured and paid separately as 'Supply only'.
Opening of pump set 6 to 8 stage, 700-900LPM at 112mtr head for repair and replacement of unserviceable parts, reassembling the same after repair, machining work of impeller housing, remetaling of pump shaft, grinding, scraping, cleaning and balancing the same to make it fully functional at the full load capacity including turning, balancing & alignment of shaft etc. reassembling of complete Pump & Motor set and testing on completion for the entire satisfaction of Engineer – in - Charge all as directed. Note:- Spare parts required to be replaced shall be measured and paid separately as 'Supply only'.
Supply only of motor housing rotor bush for 35 to 38 HP submersible motor complete all as specified and directed.
Supply only of water seal for 35 to 38 HP submersible motor complete all as specified and directed.
Supply only of thrust bearing set for 35 to 38 HP submersible pump complete all as specified and directed.
Supply only bush Gun metal for 700-900 LPM submersible motor complete all as specified and directed.
Supply only impeller Gun metal for 700-900LPM submersible pump complete all as specified and directed.
Supply only impeller neck ring for 700-900LPM submersible pump complete all as specified and directed.
Supply only impeller bush for 700-900LPM submersible pump complete all as specified and directed.
Supply only impeller locknut for 700-900LPM submersible pump complete all as specified and directed.
Supply only stainless steel shaft for 700-900LPM submersible pump complete all as specified and directed.
Supply only Coupling set including key and MS nut bolt suitable for submersible pump sets, complete all as specified and directed.
Taking out old unserviceable column pipe from tubewell and supply and lowering MS column pipe confirming to relevant IS heavy duty 6 mtr depth of size 80mm dia with both ends flanged /drilled and connecting complete with rubber gasket ,nuts bolts and washer complete all as specified and directed by Engineer-in-charge. Note:- 1. unserviceable column pipe shall be deposited in MES store yard by contractor at his own arrangement. 2. All T&P required for taking out /lowering of pipe shall be managed by contractor and no extra shall be admissible on this account.
Supply and fixing/laying in replacement cable submersible PVC insulated water proof with copper conductor cable 3x16sqmm ,1100 volt grade confirming to IS after taking out old unserviceable cable complete all as specified and directed by Engineer-in-charge.
Taking out self priming non clog submersible pump set after removal of electrical connections, disconnecting suction/ delivery pipeline connection, from sewage well upto 6m depth and transportation to workshop for repair & vice versa. Refixing after carrying out repair /rewinding of submersible pump set 7.5HP capacity electrically driven by 3phase 415volts complete all as specified and directed by Engineer-in-charge. Note:- Repair / spare parts shall be measured & paid for separately
All as per item No 1.16 but pump set 5HP capacity electrically driven by 3phase 415volts complete all as specified and directed by Engineer-in-charge.
Taking out the burnt winding of stator of submersible/squirrel cage/TFT motor, removal of burnt insulation material from the slots, cleaning the stator slots and preparation for rewinding the same. Material and labour for winding the stator of motor 7.5HP with PVC insulated copper wire of standard size and superior quality as per the existing turns & gauge including 'F' class insulation materials to get the proper RPM and torque. Turning, balancing & alignment of rotor etc. Complete all as specified and directed.
All as per item No 1.18 but electric motor of capacity 5HP complete all as specified and directed by Engineer-in-charge.
Supply only sodium Hypo chlorite( NaOCL) chemical solution conforming to IS-1673/86 having chloride content 10 % by weight (bleach liquid solution) complete all as specified and directed by Engineer-in Charge. Note : Chemical solution shall be supplied by the contractor as on requirement basis throughout the currency of the contract .Therefore the contractor shall procure the chemical solution in piecemeal as per requirement .The material shall be deposited with AGE E/M-1 (A/F) High ground and RV shall be prepared accordingly. Contractor shall also arrange independent testing of chemical from Govt authorized laboratory at his own expense. The cost of testing shall be deemed to be included in the quoted rate. Payment of supply of Sodium Hypo Chlorite solution shall only be made on production of test report.
Supply and fix in repair electronic metering dozing pump with following technical specification, complete all as specified :- Item : Dosing Pump Model : TJ - MD 8 Capacity (lph) : 0 – 6 Back Pressure (kg/cm2) : 10 Drive : Solenoid Capacity adjustment :- 1. Adjustable stroke frequency between 0 to 100 strokes/min 2. Adjustable stroke length between 0 to 100% MOC of wetted parts : PP MOC of diaphragm : PTFE coated EPDM Power (W) : 30 Power supply : Single phase 230V, 50 Hz Accessories : Foot Valve, Injection Fitting and 3 mtrs Hose pipe Make : Toshcon Jesco or equivalent in Appx `B'
Taking down carefully electrically operated gear box suitable for secondary clarifier mechanism/ aerator/ cylindrical rotor of capacity 480 KLD x 300PPM, BOD loading of any make/ size. Cleaning, removal of dust and dirt, oiling /greasing the bearing, replacement of fan belt, gearbox central coupling etc. by opening it complete all as specified and directed and testing on completion for the entire satisfaction of Engineer-in-Charge.
Excavation in trenches not exceeding 1.5m wide and 1.5m deep, as in soft/loose soil for laying pipe lines, including getting out, complete all as specified and directed.
Returning filling in, including spreading, leveling, watering and well ramming in layers not exceeding 25cm thick, as in soft/loose soil, complete all as specified and directed.
Removal of excavated material (surplus soil) to a distance not exceeding 50m and depositing where directed at level not exceeding 1.5m above the starting point, complete all as specified and directed.
Taking out/down old GI pipe 15mm dia bore with fittings, laid in trenches, under floors or on roof, along walls etc, stacking serviceable pipe and removal of unserviceable pipe, complete all as specified and directed. Note : Excavation & earthwork shall be measured and paid separately.
All as per item No 1.26 but GI pipe 20mm bore complete all as specified and directed by Engineer-in-charge.
All as per item No 1.26 but GI pipe 25mm bore complete all as specified and directed by Engineer-in-charge.
All as per item No 1.26 but GI pipe 40mm bore complete all as specified and directed by Engineer-in-charge.
All as per item No 1.26 but GI pipe 50mm bore complete all as specified and directed by Engineer-in-charge.
Supply and laying GI pipe medium grade 15mm dia with all fittings laid in trenches/fixed along walls or laid under floors, complete all as specified and directed. Note :- Excavation & earthwork shall be measured and paid separately.
All as per item No 1.31 but GI pipe 20mm bore, complete all as specified and directed .
All as per item No 1.31 but GI pipe 25mm bore, complete all as specified and directed .
All as per item No 1.31 but GI pipe 40mm bore, complete all as specified and directed .
All as per item No 1.31 but GI pipe 50mm bore, complete all as specified and directed .
Supply and fix, Gun Metal gate valve with iron wheel head, screwed both ends for 15mm dia bore pipe, including taking down old and removal, complete all as specified and directed.
All as per item No 1.36 but Gun metal gate valve 20mm bore complete all as specified and directed .
All as per item No 1.36 but Gun metal gate valve 25mm bore complete all as specified and directed .
All as per item No 1.36 but Gun metal gate valve 40mm bore complete all as specified and directed .
All as per item No 1.36 but Gun metal gate valve 50mm bore complete all as specified and directed .
Taking down old unserviceable cast iron water mains (including all fittings) of size 80mm bore with spigot & socket/ flanged ends and lead joints including burning out joints and recovering lead, complete all as specified and directed. Note for item :- (i) Excavation in trenches will be measured and paid for separately (ii) These items may also be used in the maintenance of sewage installation/pipe lines etc
All as per item No 1.41 but CI pipe 100mm bore complete all as specified and directed.
All as per item No 1.41 but CI pipe 150mm bore complete all as specified and directed.
All as per item No 1.41 but CI pipe 200mm bore complete all as specified and directed.
Supply, laying, jointing and testing, CI pipe 80mm dia bore, spigot and socket ends, centrifugally cast, class LA, laid in trenches/duct etc or along wall, complete all as specified and directed. Note:- Excavation and earth work ,joints and CI fitting will be measured and paid for separately
All as per item No 1.45 but CI pipe 100mm bore complete all as specified and directed by Engineer-in-charge.
All as per item No 1.45 but CI pipe 150mm bore complete all as specified and directed by Engineer-in-charge.
All as per item No 1.45 but CI pipe 200mm bore complete all as specified and directed by Engineer-in-charge.
Relaying, jointing and testing, CI pipe 80mm dia bore, spigot and socket ends, centrifugally cast, any class , laid in trenches/duct etc or along wall, complete all as specified and directed. Note:- Excavation and earth work ,joints and CI fitting will be measured and paid for separately
All as per item No 1.49 but CI pipe 100mm bore complete all as specified and directed .
All as per item No 1.49 but CI pipe 150mm bore complete all as specified and directed .
All as per item No 1.49 but CI pipe 200mm bore complete all as specified and directed .
Supply and fix, cast iron sluice valve for 100mm dia bore pipe, with flanged and drilled ends, any pattern, heavy duty, class PN 1.6, ISI marked & of specified make, Cast iron wheel, including joints and jointing materials as rubber washers/gaskets, bolts and nuts, etc, also taking down and removal of old sluice valve, complete all as specified and directed.
Supply and fix, cast iron sluice valve for 150mm dia bore pipe, with flanged and drilled ends, any pattern, heavy duty, class PN 1.6, ISI marked & of specified make, Cast iron wheel, including joints and jointing materials as rubber washers/gaskets, bolts and nuts, etc, also taking down and removal of old sluice valve, complete all as specified and directed.
Material and labour, run lead joint for 80mm dia bore CI pipe and fittings, complete all as specified and directed.
Material and labour, run lead joint for 100mm dia bore CI pipe and fittings, complete all as specified and directed.
Material and labour, run lead joint for 150mm dia bore CI pipe and fittings, complete all as specified and directed.
Material and labour, run lead joint for 200mm dia bore CI pipe and fittings, complete all as specified and directed.
Material and labour for construction of brick masonry valve pit in CM 1:4 of size 60cmx60cmx90cm (internal dimension), PCC 1:5:10 as in foundation 50mm thick, 15mm thick cement plaster in CM 1:4 internally including exposed surfaces externally and pointing flush in cement mortar 1:2 as the work proceeds externally, angle iron frame of size 40mm x 40mm x 6mm embedded in 50mm thick coping as in PCC 1:2:4, MS sheet cover 3mm thick and locking arrangements with MS handle made out of 12mm dia bar, duly painted with two coats of synthetic enamel paint over a coat of red oxide primer, including dismantling of old valve pit and removal of retrieved material outside MoD land, complete all as specified and directed.
All as per item No 1.59 but of size 90x90x90Cm complete all as specified and directed.
All as per item No 1.59 but of size 105x105x105mm complete all as specified and directed.
All as per item No 1.59 but of size 120x120x120mm complete all as specified and directed.
Draining out water completely from RCC over head Reservoir of capacity 275000 gallons in two parts at 60 feet staging and material and labour for desludging of RCC over head reservoir manually ,cleaning the inner portion of RCC tank by brooming with fine brush ,removing complete silt,sludge,vegetations unwanted foreign materials etc manually under artificial pressure from the tank, filling of cracks with pidilite /Dr fixit non shrink compound suitable to potable water to make tank leak proof. Plastering in CM 1:4, 15mm thick to the internal & external surfaces of the damaged portions of the reservoir and staging and applying two coats of cement base paint to the external surface of the reservoir and staging. Painting with black synthetic enamel paint to the all CI pipe line and other MS work etc fitted with the RCC OH reservoir and staging including making a block in Synthetic enamel paint 1mtr in height black base and writing in 50mmx50mm size letters with white synthetic enamel paint, DATE OF TANK CLEANING complete all as specified and as directed.
Excavation & earth work in any type soil for locating the leakage in existing cast iron water mains any type/size 80mm bore (including all fittings) and rectifying the leakage complete all as specified and directed. Note: Any CI fittings/specials, joint & jointing material etc required for the rectification of leakage shall be measured & paid for separately.
All as per Serial Item No 1.64 here-in-before but CI pipe of 100mm bore complete all as specified and directed.
All as per Serial Item No 1.64 here-in-before but CI pipe of 150mm bore complete all as specified and directed.
All as per Serial Item No 1.64 here-in-before but GI pipe up to 25mm bore complete all as specified and directed. Note - Cost of all GI fittings/special required deemed to be included in the rate quoted and nothing extra shall be admissible on this account.
All as per Serial Item No 1.67 here-in-before but GI pipe up to 40/50mm bore complete all as specified and directed.
All as per Serial Item No 1.67 here-in-before but GI pipe up to 80/100mm bore complete all as specified and directed.
Collection of the water sample from the borewell duly sealed by the Engineer- in - Charge, carrying to the PHE UT Chandigarh/ Govt lab for testing, depositing it and collecting the test report from the lab & deposited with the department complete all as specified and directed.
Supply and fix fully automatic star - Delta Starter suitable for 40 HP Submersible motor 415 volts 50 HZ AC including over load relay, range and power contactor, single phase preventer with volt meter and ammeter and MCB TP etc complete all accessories pre-wired /connected with suitable size copper conductor. complete all as specified and directed. Make :- Havells Cat Part No IHDASAV5* E or equivalent in Appx 'B'
Supply only DOL starter in sheet steel enclosure suitable for non clog 5 HP submersible motor 415 volt 50 Hz complete including Power contactor, over load relay range 9 to 13 Amp, single phase preventer, pre-wired complete all as specified and directed. Make:- Havells Cat Part No IHSDOAMB*A or equivalent in Appx 'B'
SEWAGE DISPOSAL
Opening of underground sludge sump of size 5.00x 3.00 x 10.00 metre depth of capacity 480 KLD, removal of settled sludge, cleaning the sewage from walls / ceiling etc. to the entire satisfaction of Engineer-in-Charge.
Opening of underground grit chamber of size 1.00 x 18.00 x 0.50 metre depth, removal of settled sludge, cleaning the sewage from walls/ ceiling etc. for the entire satisfaction of Engineer-in-Charge.
Opening of underground secondary clarifier ditch 8.00 m dia x 5.00 m depth, removal of settled sludge, cleaning the sewage from walls/ ceiling etc.to the entire satisfaction of Engineer-in-Charge.
Opening of underground oxidation ditch 36mx6mx2.5mtr depth, removal of settled sludge, cleaning the Sewage from walls/ ceiling etc. including one coat of cement based paint to outer surfaces after scraping of old surfaces and painting to iron rails/ supports/ ladders etc. with two coats of synthetic enamel paint of approved quality over a coat of red oxide primer after scraping of old painted surfaces, complete all as specified and as directed by the Engineer-in-Charge.
Opening of underground return sludge tank of size 1.50 m dia x 5.00 m depth, removal of settled sludge, cleaning the sewage from walls/ ceiling etc. including one coat of cement based paint to outer surfaces and painting to iron rails/ supports/ ladders etc. with two coats of synthetic enamel paint of approved quality over a coat of red oxide primer after scraping of old painted surfaces, complete all as specified and as directed by the Engineer-in-Charge.
Removal of sludge from dry bed of size 10x5x1.50mtr depth, removal of settled sludge, cleaning the sewage from walls/ ceiling etc. including one coat of cement based paint on surfaces after scraping of old painted surfaces, complete all as specified and as directed by the Engineer-in-Charge.
Opening of underground sump of size 5.00 m dia x 12.00 m depth, at sewage booster installation, removal of settled sludge, cleaning the sewage from walls/ ceiling etc. including one coat of cement based paint to outer surfaces and painting to iron rails/ supports/ ladders etc. with two coats of synthetic enamel paint of approved quality over a coat of red oxide primer after scraping of old painted surfaces, complete all as specified and as directed by the Engineer-in-Charge.
Taking down carefully electrically operated clarifier mechanism with complete accessories from ditch 8m dia and 5 mtr depth and repair/replacement of damaged periphery MS strip (rail) of size 150mm wide 6mm thick and 34 mtr length and re assemble the complete accessories of the mechanism such as aerator cylindrical rotor of capacity 480 KLD x 300 RPM, gear box etc including turning balancing and alignment of mechanism made fully functionable by replacement of unserviceable item carbon brushes of motor bearing of clarifier, in CM (1:4) cement plaster 15mm thick to periphery where required including assembling completed all as specified and directed by Engineer-in-Charge.
SUMMER APPLIANCES
Material and labour for servicing to Split type AC operated on 240 volts single phase AC electric supply of any make/type capacity 1.5/2.0 Ton, both internal / external units of AC, dry cleaning with blower / vacuum cleaner, washing with soap solution and cleaning with water pressure through jet, making it fully serviceable , complete all as specified and as directed by Engineer-in-Charge.
All as per item No 3.01 here - in- before but for window type AC unit of any make /model and capacity, complete all as specified and as directed by Engineer-in-Charge.
Supply and fixing sealed unit Hermatic Compressor operated on "R-22 refrigerant" Company replaced only, suitable for split/window type AC 1.5 Ton capacity of existing make and model duly filled of gas, compressor oil including taking out old/US compressor complete all as specified and as directed by Engineer-in-Charge.
All as per item No 3.03 here in - before but for AC 2 Ton capacity complete all as specified and as directed by Engineer-in-Charge.
Supply & fixing sealed unit Rotary Compressor operated on "R-22 refrigerant" Company replaced only, suitable for split / window type AC 1.5 Ton capacity of existing make and model duly filled of gas, compressor oil including taking out old US compressor complete all as specified and as directed by Engineer-in-Charge.
All as per item No 3.05 here - in - before but for AC 3 Ton capacity complete all as specified and as directed by Engineer-in-Charge.
Supply & fixing the following spares/parts for split /window type AC unit including taking out old /US spares/parts complete all as specified and as directed:-
Copper tube 1/2 inch bore including necessary insulation.
Copper tube 1/4 inch bore including necessary insulation.
Copper tube 5/8 inch bore including necessary insulation.
Copper tube 3/8 inch bore including necessary insulation.
Blade only for blower outdoor motor split unit any type.
Blade only for blower window type unit any type.
Starting relay Make:Renutral/Indfoss/Denfoss
Over Load Protector Make:Renutral/Indfoss/Denfoss
Thermostat switch Make:Renutral/Indfoss/Denfoss
Starting Capacitor 80-100MFD any capacity Make:Epcos/Usha/Tesla
Starting Capacitor 100-120MFD any capacity Make:Epcos/Usha/Tesla
Running Capacitor 36MFD any capacity Make:Epcos/Usha/Tesla
Running Capacitor 45MFD any capacity Make:Epcos/Usha/Tesla
Running Capacitor 50MFD any capacity Make:Epcos/Usha/Tesla
Blower motor for outdoor unit. Make:AUE/Cool Home/Universal
Blower motor for indoor unit. Make:AUE/Cool Home/Universal
Remote Control system complete including PC Cards /Circuits.
Blower motor double shaft for Window AC unit. Make:AUE/Cool Home/Universal
Capacitor 4MFD 230Volts. Make:Epcos/Usha/Tesla
Contactor 3100-15U complete.
PC Cards /Circuits only
Material and labour for Internal wiring for split unit of any capacity with single core copper conductor FRLS cable as per existing size only complete all as specified and as directed by Engineer-in-Charge.
Material and labour for Internal wiring for window unit of any capacity with single core copper conductor FRLS cable as per existing size only complete all as specified and as directed by Engineer-in-Charge.
M&L for repairing the leaking area and recharging refrigerant gas R-22 in window/Split type AC’s/water cooler /deep freezer/refrigerator all as directed by Engineer-in-Charge.
Supply and fixing sealed unit Hermatic Compressor Company replaced only, suitable for Water Cooler 40/80Ltrs capacity of existing make and model duly filled of gas, compressor oil including taking out old/US compressor complete all as specified and as directed by Engineer-in-Charge.Make:Kirloskar
All as per item No 3.32 here in - before but for Water Cooler 150Ltrs capacity complete all as specified and as directed by Engineer-in-Charge.Make:Kirloskar
All as per item No 3.32 here in - before but for Refrigerator 165 to 180Ltrs capacity complete all as specified and as directed by Engineer-in-Charge. Make:Kirloskar
All as per item No 3.32 here in - before but for Refrigerator 300 to 320Ltrs capacity complete all as specified and as directed by Engineer-in-Charge. Make:Kirloskar
S&F in replacement the following items of existing make and model suitable for refrigerator 165/320 capacity including taking out old /US spares / parts complete all as specified and as directed by Engineer-in-Charge:-
Steel Shelves PVC coated 165 -180Ltrs. capacity
Starting Relay Box 165 - 180Ltrs. capacity. Make:Renutral/Indfoss/Denfoss
Overload Protection Box 165 - 180Ltrs. capacity. Make:Renutral/Indfoss/Denfoss
Steel Shelves PVC coated 300-320Ltrs. capacity Make:Renutral/Indfoss/Denfoss
Starting Relay Box 300 - 320Ltrs. capacity.
Overload Protection Box 300 - 320Ltrs. capacity.
Running Capacitor 10MFD 230volts.
Thermostat switch any capacity.
Supply and fixing the following items of existing make and model suitable for water cooler any capacity including taking out old /US spares/parts complete all as specified and as directed by Engineer-in-Charge:-
Condensor motor only
Push Cock CP 15mm.
Magnetic Rubber gasket for top cover any capacity.
PVC Drain pipe 32mm bore not less than 1mtr in length.
Internal wiring of refrigerator/deep freezer/water cooler etc of any capacity
Cleaning of water storage tank, detection of water leakage, brazing / welding to restore the leakage, scraping old paint, completely and painted with 2 coat of synthetic enamel paint over a coat of red oxide primer after filling the cavities of MS Sheet with filler to external surface complete all as specified and as directed by Engineer-in-Charge.
Taking down carefully the following accessories /parts from existing desert cooler and providing new accessories /parts in desert cooler complete all as specified and as directed by Engineer-in-Charge:-
Fan motor 350Watts 230Volts 3Speed copper winding single phase complete. Make: KHAITAN/Crompton/Universal
Submersible type Tulu pump 230Volts single phase 1750LPH at 1.5 mtr head complete Make : KHAITAN/Crompton/Universal
Fan blade only
Front grill of M S /PVC complete with slides operation and indicator lamps.
Wood wool pad set of three of best quality including fixed wth bamboo stick any size.
PVC pipe heavy duty 15mm bore ISI Marked.
PVC Distribution Tee, Elbows and other minor items (heavy duty) 15mm bore ISI Marked.E101
Internal wiring of desert cooler of any capacity as per existing specifications
Taking down to desert cooler of any make/capacity carefully without damaging, scraping old paint, completely and painted with 2 coats of synthetic enamel paint over a coat of red oxide primer after filling the cavities of MS Sheet with filler to external surface and inner surface of bottom & sides painted with 2 - coat of black Japan paint completed all as specified and as directed by Engineer-in-Charge. Note : Taking down and re-fixing in the same position after painting work shall be deemed to include in the unit rate of this item.
Material and labour for taking down voltage stabilizer of cap 0.5 KVA to 5 KVA single phase 230/240 volts of any make & type tightening of all electric connections, assembling & testing after repair work including transportation to workshop & vice - versa and connection at site complete all as specified and as directed by Engineer-in-Charge.
Material and labour for rewinding to burnt transformer of voltage stabilizer 5 KVA with copper winding wire including varnishing with super quality varnish, suitable size of thimble , mica paper and testing after rewinding complete all as specified and as directed by Engineer-in-Charge.
All as per above item No 3.64 here-in-before but 4 KVA complete all as specified and as directed by Engineer-in-Charge.
All as per above item No 3.64 here-in-before but 3KVA complete all as specified and as directed by Engineer-in-Charge.
All as per above item No 3.64 here-in-before but 2 KVA complete all as specified and as directed by Engineer-in-Charge.
All as per above item No 3.64 here-in-before but 0.5KVA to1 KVA complete all as specified and as directed by Engineer-in-Charge.
Supply and fixing in replacement circuit plate as existing make and model suitable for 5 KVA . Complete all as specified and as directed by Engineer-in-Charge.
All as per above item No 3.69 here-in-before but 4 KVA Complete all as specified and as directed by Engineer-in-Charge.
All as per above item No 3.69 here-in-before but 3 KVA Complete all as specified and as directed by Engineer-in-Charge.
All as per above item No 3.69 here-in-before but 2 KVA Complete all as specified and as directed by Engineer-in-Charge.
All as per above item No 3.69 here-in-before but 0.5 to1 KVA Complete all as specified and as directed by Engineer-in-Charge.
S&F in replacement the following items as per existing make and model for 0.5 to 5KVA Complete all as specified and as directed by Engineer-in-Charge:-
Time delay relay
Toggle switch
Auxiliary transformer up to 24 Volt
Step up relay
PVC connector base plate.
Supply and fixing connection lead of PVC insulated and sheathed copper conductor cable of size 1.5Sqmm 3 core complete all as specified and directed. Make: Plaza/Kailnga/Finolex/Havells.
All as Srl item No.3.80 above but of size 2.5 Sqmm. complete all as specified and directed.
All as Srl item No.3.80 above but of size 4 Sqmm, complete all as specified and directed.
Disconnecting the input and outgoing connection of cable of voltage stabilizer 3 phase unbalancing type for 400 KVA capacity, transportation to civil work shop for repair , taking out AVR, visual/electronic test for locating the fault including replacement of worn out parts, complete all as specified and directed. Note:- Spare parts shall be measured and paid separately .
S&F in replacement the following parts for 400KVA voltage stabilizer :-
(i) AVR transformers
(ii) Servo motor
(iii) RC net work Servo motor
(iv) Internal Wiring
(v) Micro Process Switch
(vi) Dimmer state unit
(vii) Electronic Circuit
(viii) DPDT switch
(ix) Trigger
Supply, installation and testing of voltage stabilizers for automatic operation three phase naturally air cooled indoor type & designed for input variation between 140 to 250 V with output voltage stabilized at 230 Volts with accuracy +/- 2.05% and speed of correction 8 Volts per second and of capacity 5KVA. including taking down/ out old/ unserviceable voltage stabilizer complete all as specified and directed. Make : Carrier/Blue Bird/ V Guard
Note: The Total amount shall subject to adjustment of credit of Rs.59510.00 for old Materials as per Schedule of Credit
R D Bansal
HARISH SALES CORPORATION
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .