Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹87.0 LAccepted-AOC | L1 | Accepted-AOC L1 | |
| 2 | L2₹89.8 L+₹2.8 L (3.24%)Rejected-AOC | L2 | Rejected-AOC L2 | |
| 3 | L3₹89.9 L+₹2.9 L (3.33%)Rejected-AOC GRA 525 KATTIL KUNNATHU HOUSE GOWREESHAPATTOM PATTOM P O TRIVANDRUM 695004 | THIRUVANANTHAPURAM | KERALA | 695001 | L3 | Rejected-AOC L3 | |
| 4 | L4₹90.0 L+₹3.0 L (3.40%)Rejected-Finance ALAPPUZHA | ALAPPUZHA | KERALA | 686534 | L4 | Rejected-Finance L4 | |
| 5 | Rejected-Technical | - | Rejected-Technical Disqualified |
Tender Value
₹93.6 L
EMD Value
₹50,000
Closing Date
4 Nov 2020, 3:00 pmClosed
Deputy Vice President (HCD)
HLL Lifecare Limited, HCD Projects, HLL Bhavan, 6th Floor, Golden Jubilee Block, Poojapura, Thiruvananthapuram - 695012
Civil, Electrical, HVAC and MGPS Works for Construction of Eye Ward and Eye OT at THQH Piravom, Ernakulam
2020_HLL_394250_1
HLL/CHO/HCD/CE/EYE/OT/PIRAVOM
Open Tender
Civil Works - Buildings
Item Rate
300 days
THQH Piravom
Please refer Tender documents.
11 documents required · 11 mandatory
₹2,800
Yes
online
₹50,000
Yes
4 Aug 2021
23 Oct 2020
5 Nov 2020
23 Oct 2020
4 Nov 2020
23 Oct 2020
Amount
Civil Work
Dismantling and Demolishing
Demolishing cement concrete manually / by mechanical means including disposal of material within 50 metres lead as per direction of Engineer - in-Charge.Nominal concrete 1:4:8 leaner mix ( including equivalent design mix)
Demolishing R.C.C. work manually / by mechanical means including stacking of steel bars and disposal of unserviceable material with in 50 metres lead as per direction of Engineer -in-Charge.
Extra for cutting reinforcement bars manually/ by mechanical means in R.C.C. or R.B. work ( Payment shall be made on the cross sectional area of R.C.C. or R.B work) as per direction of Engineer-in-charge.
Demolishing brick work manually / by mechanical means including stacking of serviceable material and disposal of unserviceable material within 50 metres lead as per direction of Engineer-in-Charge.In cement mortar
Dismantling doors, windows and clerestory windows (steel or wood ) shutter including chowkhats, architrave, holdfasts etc. complete and stacking within 50 metres lead:Of area 3 sq. metres and below
Taking out doors, windows and clerestory window shutters (steel or wood ) including stacking within 50 metres lead:Of area 3 sq. metes and below
Dismantling tile work in floors and roofs laid in cement mortar including stacking material within 50 metres lead.For thickness of tiles 10 mm to 25 mm
Dismantling old plaster or skirting raking out joints and cleaning the surface for plaster including disposal of rubbish to the dumping ground within 50 metres lead.
EARTH WORK
Earth work in excavation by mechanical means (Hydraulic excavator) /manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift up to 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m.All kinds of soil
Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundation etc. in layers not exceeding 20 cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift up to 1.5 m.
Filling with contractor own earth (excluding rock) in open areas in layers not exceeding 20 cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift up to 1.5 m as per direction of site Engineer-in-charge.
Felling trees of the girth (measured at a height of 1 m above ground level) including cutting of trunks and branches, removing the roots and stacking of serviceable material and disposal of unserviceable material.Beyound 30 cm girth up to and including 60 cm girth
Masonry Work
Random rubble masonry with hard stone in foundation and plinth including levelling up with cement concrete 1:6:12 (1 cement : 6 coarse sand : 12 graded stone aggregate 20 mm nominal size) up to plinth level with:Cement mortar 1:6 (1 cement : 6 coarse sand)
Half brick masonry with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level.Cement mortar 1:3 (1 cement : 3 coarse sand)
Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level in all shapes and sizes in:Cement mortar 1:4 ( 1 cement : 4 coarse sand)
12 mm cement plaster of mix:1:6 (1 cement : 6 fine sand).
Cement Concrete
Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level:1:4:8 (1 cement : 4 coarse sand : 8 graded stone aggregate 40 nominal size)
Reinforced cement concrete work in walls (any thickness), including attached pilasters, buttresses, plinth and string courses, fillets, columns, pillars, piers, abutments, posts and struts etc. up tot floor five level excluding cost of centering, shuttering, finishing and reinforcement :1:1.5:3( 1 cement : 1.5 coarse sand : 3 graded stone aggregate 20 mm nominal size)
Reinforced cement concrete work in beams, suspended floors, roofs, having slope up to 150 landings, balconies, shelves, chajjas, lintels, bands, plain window sills, staircases and spiral stair cases up to floor five level excluding the cost of centering, shuttering, finishing and reinforcement, with1:1.5:3 (1 cement : 1.5 coarse sand (Zone III) : 3 graded stone aggregate 20 mm nominal size).
Centering and shuttering including strutting, etc. and removal of form for:Lintels, beams, plinth beams, girders bressumers and cantilevers
Steel reinforcement for R.C.C work including straightening, cutting, bending, placing in position and binding all complete above plinth level.Thermo - Mechanically Treated bars of grade Fe-500D or more
Aluminium Works
Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS : 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminnium snap beading for glazing /paneling, C.P. brass/ stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge.(Glazing, paneling and dash fasteners to be paid for separately):For fixed portionPowder coated aluminium (minimum thickness of powder coating 50 micron)
For shutters of doors, windows & ventilators including providing and fixing hinges / pivots and making provision for fixing of fittings wherever required including the cost of EPDM rubber/ neoprene gasket required (Fittings shall be paid for separately)Powder coated aluminium (minimum thickness of powder coating 50 micron)
Providing and fixing 12 mm thick prelaminated particle board flat pressed three layer or graded wood particle board conforming to IS : 12823 Grade I Type II, in panelling fixed in aluminum doors, windows shutters and partition frames with C.P. brass / stainless steel screws etc. complete as per architectural drawings and directions of Engineer - in- Charge.Pre- laminated particle board with decorative lamination on both sides
Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of Engineer - in -Charge. ( Cost of aluminium snap beading shall be paid in basic item):With float glass panes of 5.50 mm thickness
Providing and fixing anodised aluminium grill ( anodised transparent or dyed to required shade according to IS : 1868 with minimum anodic coating of grade AC 15) of approved design/pattern, with approved standard section and fixed to the existing window frame with C.P brass/stainless steel screws @ 200 mm centre to centre, including cutting the grill to proper opening size for fixing and operation of handles and fixing approved anodised aluminium standard section around the opening, all complete as per requirement and direction of Engineer-in-charge.(Only weight of grill to be measured for payment ).
Providing and fixing 100 mm brass locks ( best make of approved quality ) for aluminium doors including necessary cutting and making good etc. complete
Providing and fixing PTMT Tower Bolts with 12 mm one piece rod inside and necessary screws etc., complete.202x42x18 mm weighing not less than 78 gms
Providing and fixing aluminium tubular handle bar 32 mm outer dia, 3.0mm thick & 2100 mm long with S.S. screws etc. complete as per direction of Engineer -in-Charge.Polyester powder coated minimum thickness 50 micron aluminium tubular handle bar
Providing and fixing aluminium extruded section body tubular type universal hydraulic door closer (having brand logo with ISI, IS : 3564, embossed on the body, door weight upto 36 kg to 80 kg and door width form 701 mm to 1000 mm), with double speed adjustment with necessary accessories and screws etc. complete.
Providing and fixing 150 mm bright finished floor brass door stopper with rubber cushion, necessary brass screws etc. to suit shutter thickness complete
Steel Works
Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete.
Providing and fixing stainless steel (Grade 304) railing made of Hollow tubes, channels, plates etc., including welding, grinding, buffing, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel nuts and bolts complete, i/c fixing the railing with necessary accessories & stainless steel dash fasteners, stainless steel bolts etc., of required size on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-in-charge, (for payment purpose only weight of stainless steel members shall be considered excluding fixing accessories such as nuts, bolts, fasteners etc.)
Providing and fixing 1 mm thick M.S. sheet door with frame of 40x40x6 mm angle iron and 3 mm M.S. gusset plates at the junctions and corners, all necessary fittings complete, including applying a priming coat of approved steel primer.Using M.S. angels 40x40x6 mm for diagonal braces
Steel work in built up G I tubular ( round, square or rectangular hollow tubes etc.) trusses etc., including cutting, hoisting,fixing in position and applying a priming coat of approved steel primer, including welding and bolted with special shaped washers etc. complete
Steel work for purlin/single section with G I pipes including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer, including welding and bolted with special shaped washers etc. complete
Providing at all heights, levels and locations 0.45 mm thick Galvalume sheet of Alloy 31500/31000/40800, conforming to IS 1254, IS 737, IS 2676. The sheet shall be fixed using self drilling/self tapping SS screws of size 5.5x65 mm with EPDM seal complete upto required pitch in horizontal, vertical or curved surfaces i/c cutting to size and shape where required as per the direction of Engineer-in-Charge. The rate shall be inclusive of all screws, seal, ridge, labour, scaffolding, machinery for fixing and approved sealant where required etc. but excluding the cost of purlins, rafters and trusses.
Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion, (i) Single socketed pipes.110 mm diameter
Item Shifted to head 14 as item 14.74Steel work welded in built up sections/framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required.In stringers, treads,landings etc. of stair cases, including use of chequered plate wherever required, all complete
Item Shifted to head 14 as item 14.74Steel work welded in built up sections/framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required.In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works
Providing and fixing hand rail of approved size by welding etc. to steel ladder railing, balcony railing, staircase railing and similar works, including applying priming coat of approves steel primer.M.S. tube
Flooring
Providing and laying vitrified floor tiles in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS : 15622, of approved make, in all colours and shades, laid on 20 mm thick cement mortar 1:4(1 cement : 4 coarse sand), including grouting the joints with white cement and matching pigments etc., complete.Size of Tile 600 x 600 mm.
Providing and laying rectified Glazed Ceramic floor tiles of size 300x300 mm or more (thickness to be specified by the manufacturer) of Ist quality conforming to IS: 15622 of approved make in all colours, shades, except white, Ivory, Grey Fume Red Brown, laid on 20 mm thick cement mortar 1:4 (1 Cement : 4 Coarse sand) including pointing the joints with white cement and matching pigments etc., complete.
Providing and fixing I st quality ceramic glazed wall tiles conforming to IS : 15622 (thickness to be specified by the manufacturer), of approved make, in all colours, shades except burgundy, bottle green, black of any size as approved by Engineer -in-Charge, in skirting, risers of steps and dados, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand) and jointing with grey cement slurry @ 3.3 kg per sqm, including pointing in white cement mixed with pigment of matching shade complete.
Chequerred precast cement concrete tiles 22 mm thick in footpath & courtyard, jointed with neat cement slurry mixed with pigment to match the shade of tiles, including rubbing and cleaning etc. complete on 20 mm thick bed of cement mortar 1:4 ( 1 cement : 4 coarse sand).Dark shade pigment using ordinary cement
Providing and fixing 18 mm thick gang saw cut, mirror, polished, premoulded and prepolished, machine cut for kitchen platforms, vanity counters, window sills, facias and similar locations, of required size, approved shade, colour and texture laid over 20 mm thick base cement mortar 1:4 ( 1 cement : 4 coarse sand), joints treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing, moulding and polishing to edges to give high gloss finish etc. complete at all levels.Area of slab over 0.50 sqm
Extra for providing opening or required size & shape for wash basin/kitchen sink in kitchen platform, vanity counter and similar location in marble/granite/ stone work, including necessary holes for pillar taps etc. including moulding, rubbing and polishing of cut edges etc. complete.
Painting
Removing white or colour wash by scrapping and sand papering and preparing the surface smooth including necessary repairs to scratches etc. complete.
Providing and applying plaster of paris putty of 2 mm thickness over plastered surface to prepare the surface even and smooth complete.
Finishing walls with Acrylic Smooth exterior paint of required shade:New work (Two or more coat applied @ 1.67 ltr/10 sqm over and including priming coat of exterior primer applied @ 2.20 kg/10 sqm)
Finishing with Deluxe Multi surface paint system for interiors and exteriors using primer as per manufacturers specifications:Two or more coats applied on walls @ 1.25 ltr/10 sqm over and including one coat of special primer applied @ 0.75 ltr /10 sqm
Finishing with Deluxe Multi surface paint system for interiors and exteriors using primer as per manufacturers specifications:Painting wood work with Deluxe Multi Surface Paint of required shade. Two or more coat applied @ 0.90 ltr/10 sqm over an under coat of primer applied @ 0.75 ltr/10 sqm of approved brand and manufacture
Finishing with Deluxe Multi surface paint system for interiors and exteriors using primer as per manufacturers specifications:Painting Steel work with Deluxe Multi Surface Paint to give an even shade. Two or more coat applied @ 0.90 ltr/10 sqm over an under coat of primer applied @ 0.80 ltr/10 sqm of approved brand and manufacture
False Ceiling
Providing and fixing tiled false ceiling of approved materials of size 595 x 595 mm in true horizontal level, suspended on inter locking metal grid of hot dipped galvanized steel sections (galvanized @ 120 grams per sqm, both side inclusive) consisting of main "T" runner with suitably spaced joints to get required length and of size 24x38 mm made from 0.30 mm thick (minimum) sheet, spaced at 1200mm center to center and cross "T" of size 24x25 mm made of 0.30 mm thick (minimum) sheet, 1200 mm long spaced between main "T" at 600 mm center to center to form a grid of 1200x600 mm and secondary cross "T" of length 600 mm and size 24x25 mm made of 0.30 mm thick (minimum) sheet to be interlocked at middle of the 1200x600 mm panel to form grids of 600x600 mm and wall angle of size 24x24x0.3 mm and laying false ceiling tiles of approved texture in the grid including, required cutting/making, opening for services like diffusers, grills, light fittings, fixtures, smoke detectors etc. Main "T" runners to be suspended from ceiling using GI slotted cleats of size 27 x 37 x 25 x 1.6 mm fixed to ceiling with 12.5mm dia and 50 mm long dash fasteners, 4 mm GI adjustable rods with galvanised butterfly level clips of size 85x 30x 0.8 mm spaced at 1200 mm center to center along main T, bottom exposed width of 24 mm of all T-sections shall be pre-painted with polyester paint, all complete for all heights as per specifications, drawings and as directed by Engineer -in-charge.12.5 mm thick square edge PVC Laminated Gypsum Tile size 595x595 mm made of Gypsum plasterboard , manufactured from natural gypsum as per IS 2095 part I and laminated with white 0.16 mm thick fire retardant PVC film on the face side and 12 micron metalized polyster on the back side with all edges sealed with the face side PVC film which goes around and wraps the edges and is bonded to the edges and the back side metalized polyster film so as to make the tile a completely sealed unit.
Providing and fixing false ceiling with 7.5 mm thick PVC wooden grains panel board ceiling of approved quality in aluminium frame work with necessary screws etc complete ( aluminium frame work shall be paid separately)
Providing and fixing powder coated aluminium work ( minimum thickness of powder coating 50 micron) consisting of tee /angle sections, of approved make conforming to IS : 733 in frames of false ceiling including aluminium angle cleats with necessary C.P brass/ stainless steel sunk screws, aluminium perimeter angles fixed to wall with stainless steel rawl plugs @ 450 mm centre to centre and fixing the frame work to G.I level adjusting hangers 6 mm dia. with necessary cadmium plated machine screws all complete as per approved architectural drawings and direction of the Engineer-in-Charge ( level adjusting hangers, ceiling cleats and expansion hold fasteners to be paid for separately ).
Providing and fixing Fiber Glass Reinforced plastic (FRP) Door Frames of cross- section 90 mm x 45 mm having single rebate of 32 mm x 15 mm to receive shutter of 30 mm thickness. The laminated shall be moulded with fire resistant grade unsaturated polyester resin and chopped mat. Door frame laminate shall be 2 mm thick and shall be filled with suitable wooden block in all the three legs. The frame shall be covered with fiber glass from all sides. M.S. stay shall be provided at the bottom to steady the frame.
Providing and fixing to existing door frames.30 mm thick Fiberglass Reinforced Plastic (F.R.P) flush door shutter in different plain and wood finish made with fire retardant grade unsaturated polyester resin, moulded to 3 mm thick FRP laminate all around, with suitable wooden blocks inside at required places for fixing of fittings and polyurethane foam (PUF) / Polystyrene foam to be used all filler material throughout the hollow panel, casted monoolithically with testing parameters of F.R.P. laminate conforming to table - 3 of IS : 14856, complete as per direction of Engineer-in-charge.
Providing and fixing 12 mm thick frameless toughened glass door shutter of approved brand and manufacture, including providing and fixing top & bottom pivot & spring type fixing arrangement and making necessary holes etc. for fixing required door fittings, all complete as per direction of Engineer-incharge ( Door handle, lock and stopper etc to be paid separately)
Providing and fixing Steel S.S- 304 (D) Door Pull Both Side Handle of 12 inch, one Set (2 Handles) ( best make of approved quality ) for Glass, Wooden or similar doors including necessary cutting and making good etc. complete
OT Room
Providing, Fixing, Supply, Installation, and Commissioning of Automatic Hermetically Sealing Sliding Door, having high pressure laminate on both sides that could withstand high abrasion , vision panels (300x300mm) , for smooth sliding .The door moves on nylon wheels within an single piece aluminium extruded track, etc inclusive of all accessories.
Providing, Fixing, Supply & installation of Pre Fabricated Modular Operation Theatre with 50mm thick SS Puff Panel of 0.8mm SS sheet on front side and 0.8mm SS Panel on back side. Filling of all joints and cavities with epoxy filler and sanded flush to provide a seamless finish .Applied with minimum three coats of Antibacterial & Antifungal paint ,wall glaze or equivalent to a minimum dry film thickness of 300 microns having overlap floor covering ,ceiling system and door frames by 25mm to provide a continous sealed surface
Surface Preparation Cleaning of surface free from dust, Dirt, moisture, oil & all foreign material from the floor. For floor cleaning all mechanized equipment's are to be used like scrubber, sanders, hot air blowers, vacuum cleaners, moisture test machine etc. Once cleaned, the surface is roughened to prepare the surface for application of epoxy primer. Leveling with epoxy screed Application of epoxy primer over prepared surface and then filling of cracks, crumbled joints small size damages in the epoxy floor with epoxy mortar having high compressive strength. The epoxy mortar should be so applied so as to acheve level of – 1 mm from adjoining top level of epoxy floor surface once the epoxy mortaris applied , the area should be left to dry for minimum 24 hours before final coat of EPU paint is applied. EPU Coating – Providing and application of concrete primer on top of epoxy screed. This is followed by self Leveling PU top coating of specified shade and colour of 1 mm thick with self leveling epoxy material by means of special spike rollers and other tools so as to remove all trapped air bubbles and achieve smooth, glossy and leveled surface.
Supplying and laying polyester, washable and stain free cloth(Bio-Active fabric washable germ free suitable for sterile area) curtain system with maximum curtain cloth height 230 cm(top 30 cm white colour net and 200cm light blue color as per approval) stitching with stifiner tape, pleats, ironing and laying around each bed using PVC runner with hooks & stopper for hanging/sliding etc. as per the direction of engineer in charge including conveyance to site, laying in line and level, sealing all cutting in false ceiling with powder coated MS cup, all leads and lifts including all labour charges etc. complete. (unpleated length of the cloth measurement will be considered for payment also the bottom and top foldings will not be considered in cloth measurement)/ supplying and fixing powder coated 20mm dia. GI round tube hanging support of required length(app. length 1.10m) one end fixing from slab by using 6mm dia expansion bolt at a distance not more than 2m, c/c down end fixed to powder coated aluminium channel frame 45 x 20mm x 1mm thick section by using SS screw as per the direction of engineer in charge including conveyance.
Shelves
Providing and fixing Thomson Multi wood board or equivalent make, in shelves with screws and fittings wherever required, edges to be painted with polyurethane primer (fittings to be paid separately) as per the direction of site Engineer-in-charge.
Providing and fixing bright finished brass handles with screws etc. complete:100 mm
Providing and fixing concealed hinge of approved quality for 19-20mm thickdoor with stainless steel screws complete :
Water Supply and Sanitary Works
Providing and fixing wash basin with C.I. brackets, 15 mm C.P. brass pillar taps, 32 mm C.P. brass waste of standard pattern, including painting of fittings and brackets, cutting and making good the walls wherever require:White Vitreous China Surgeon type wash basin of size 660x460 mm with a pair of 15 mm C.P. brass pillar taps with elbow operated levers.
Providing and fixing Stainless Steel A ISI 304 (18/8) kitchen sink as per IS 13983 with C.I. brackets and stainless steel plug 40 mm, including painting of fittings and brackets, cutting and making good the walls wherever required:Kitchen sink without drain board610x460 mm bowl depth 200 mm
Providing and fixing P.V.C. waste pipe for sink or wash basin including PVC.waste fittings complete.Semi rigid pipe32 mm dia
Providing and fixing PTMT Waste Coupling for wash basin and sink, of approved quality and colour.Waste coupling 31 mm dia of 79 mm length and 62 mm breadth weighing not less than 45 gms
Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end) :25 mm nominal bore
Providing and fixing white vitreous china pedestal type water closet (European type W.C. pan) with seat and lid, 10 litre low level white P.V.C. flushing cistern, including flush pipe, with manually controlled device (handle lever), conforming to IS : 7231, with all fittings and fixtures complete, including cutting and making good the walls and floors wherever required:W.C. pan with ISI marked white solid plastic seat and lid
Providing and fixing 8 mm dia C.P. / S.S. Jet with flexible tube upto 1 metre long with S.S. triangular plate to Eureopean type W.C. of quality and make as approved by Engineer - in - charge
Providing and fixing PTMT grating of approved quality and colour.Rectangular type with openable circular lid150 mm nominal size square 100 mm diameter of the inner hinged round grating
Providing and fixing PVC pipes, fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step PVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge 20 mm dia 10Kgf/cm2 External work- Exposed on wall
Providing and fixing PVC pipes, fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step PVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge 25 mm dia 10 Kgf/cm2- External work - Exposed on wall
Providing and fixing PVC pipes, fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step PVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge 32 mm dia 10 Kgf/cm2 - External work- Exposed on wall
Providing and fixing PVC pipes includings jointing of pipes with one step PVC solvent cement, trenching, refilling & testing of Joints complete as per direction of engineer in charge.110 mm dia 6Kgf/cm2
Supplying and fixing Stainless steel soap dish including cost of materials and labour charges etc complete as per the direction of site Engineer-in-charge.
Supplying and fixing CP Towel rod 45cm or nearest available length including cost of materials and labour charges etc complete as per the direction of site Engineer-in-charge.
Providing and fixing PVC pipes, fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes with one step PVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge. Concealed work, including cutting chased and making good the wall etc. 110 mm pipe 6kgf/cm2
Supplying and installing ready made PVC Septic tank including the cost of carriage, trenching, placing at the level below ground level as specified as per the direction of engineer in charge (Provision for CC/RCC/Sand/06mm aggregate for the preparation of bed shall be paid separately) 3. 25 to below 35 flush capacity
Providing and fixing 15 mm C.P. brass pillar taps with elbow operated levers
Providing and fixing C.P brass long nose bib cock of approved quality conforming to IS standards and weighing not less than 810 gms.15 mm nominal bore
ELECTRICAL WORKS
Water Supply and Sanitary Works
Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).Single Control light point with 6A, plate ceiling rose - Short point
Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).Single control ceiling fan point with 6 A, 3 plate ceiling rose & with socket size stepped electronic regulator. - Short point
Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).Independent plug - Short point
SUB MAIN ,CIRCUIT MAINS and MODULAR PLUGS
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2x1.5 sq.mm + 1x1.5 sq.mm earth wire
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2 X 4 sq. mm + 1 X 4 sq. mm earth wire
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required4 X 4 sq. mm + 2 X 4 sq. mm earth wire
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 amps switch
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.15/16 amp switch
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.3 pin 5/6 amp socket outlet
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.6 pin 15/16 amp socket outlet
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.Telephone socket outlet
Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.3 Module (100mmX75mm)
Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.6 Module (200mmX75mm)
Supplying and drawing following pair 0.5 mm dia FRLS PVC insulated annealed copper conductor,unarmored telephone cable in the existing surface/ recessed steel/ PVC conduit as required.2 Pair
Supplying and drawn of UTP 4 pair CAT 6 LAN cable in the existing surface/recessed steel/PVC conduit as required1 run of Cable
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm
Wall Mount Rack - 4U<br>Wall Mount Racks are made with solid steel structure 4U 19",with minimum dimensions 240x545x350 mm,(H x W x D), in a single section with front lockable glass door and with provision of two side cable entry from top and bottom with proper internal cable management and heat management. Having IP20 level protection.RAL 7035 SHADE , neatly finished etc as required
Supply and fixing RJ45 Keystone IO jack with cover and face plate, including crimbing/Punching of UTP 4 Pair CAT 6E LAN Cables on both ends with RJ45 Connector
SITC OF DG , MSB AND ASSOCIATED WORKS
PANEL BOARD - [1+ (4+2)]<br>Supply, Installation, Testing & Commissioning of cubicle type, made out of 1.6mm thick CRCA sheet,totally enclosed , free standing, floor mounting, dust and vermin proof, indoor, compartmentalized, suitable for operation on 3 phase , 415 V, 50Hz AC system with busbars , including internal wiring with suitable size wires/cable, interconnection, duly powder coated with seven tank process etc., including following components as per drawing and technical specifications.The panel shall be with Top/bottom entry to receive incoming & outgoing cable-EB SIDE Incomer-250A, FP 35/36 KA microprocessor type MCCB Having isolation duty with 3O/C+1E/F Release SET AT 200A - 1No.Instruments (incomer)-2A MCB - 6 Nos.-RYB indication lamp, LED type - 2set-Digital Multi function meter with Acc Cl1 with RS485 communication -1no - 1set (3P+1N).Busbar 300A ,35kA TPN busbar chamber with Aluminium busbar- Outgoings - 4+2(spare) No.s 16-100A, 25 kA FP MCCB with adjustable thermal magnetic release with OL & SC protection, with RS 485 communication facility as required. Earth Leakage relay upto 100A with CBCT as required shall be connected to the system via suitable end termination as required.
Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 25 sq mm with factory made clamp
Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 16 sq mm with factory made clamp
Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required2.65 mm copper conductor (12 SWG)
Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.
Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
HVAC SYSTEM and ASSOCIATED WORKS
GI VOLUME CONTROL DAMPER<br>Supply, installation, testing and commissioning of Gl volume control duct damper complete with neoprene rubber gaskets, nuts, bolts, screws linkages, flanges etc, as per specifications.
CANVAS CONNECTOR FOR AC WORKS<br>SITC of thermal insulated, flexible type canvas connector and ribbed rubber pads as vibration isolator in the existing machine to duct mouth using suitable adhesive compound as per technical specification, neatly bolted and adjusted for vibration free mounting etc as required.
SITC 5.5TR DUCTABLE SPLIT AC<br>SITC of DX type double skinned air handling units, ceiling suspended/ floor mounting type 5.5TR, 750lps capacity complete with suitable DIDW blower (as per approved make), blower section, static presure of 80 mm of water column, built in pre filter (EU4), fine filter (EU7) & hepa filter (EU 13) 99.97% effieciency down to 0.3 microns and controls connected to condensing units, insulated SS drain pan 6 row cooling coil, electric motor , direct driven package with TEFC motor class B insulation, suitable for 3 phase, 415V 50Hz supply, suitable AHU panel & cabling. AHU temp & speed control panel, ARI certified, with 0.8mm double skinned 40mm thick PUF panel, belt guards, suitable supports for suspending from slab, vibration isolator, etc. conforming to specifications. The air handling units shall have 1 inlet refrigerant coils and 1 outlets refrigent coils suitable for 1 numbers of 5.5TR capacity condensing unit (ODU) and shall conform to specifications Fresh Air 20% and RH 55%
NITRILE RUBBER INSULATION - 25 MM<br>Supplying and fixing of following thickness duly laminated aluminum foil of mat finish closed cell Nitrile rubber (Class “O”) insulation on existing duct after applying suitable adhesive for Nitrile rubber. The joints shall be sealed with 50 mm wide and 3 mm thick self adhesive nitrile rubber tape insulation complete as per specifications and as required.
NITRILE RUBBER INSULATION - 13MM<br>Supplying and fixing of following thickness duly laminated aluminum foil of mat finish closed cell Nitrile rubber (Class “O”) insulation on existing duct after applying suitable adhesive for Nitrile rubber. The joints shall be sealed with 50 mm wide and 3 mm thick self adhesive nitrile rubber tape insulation complete as per specifications and as required.
DUCTING 1.00mm GSS<br>Supply, installation, balancing and commissioning of fabricated at site GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required.<br>Site fabricated GSS sheet metal rectangular ducting as per IS 655-2006 for 1.00 mm thick
ACTUATOR ( FOR MOTORIZED GI VOLUME CONTROL-DUCT MOUNTING)<br>Supply, installation, testing and commissioning of Motorized (ON-OFF Type) duct mounted Gl volume control actuator with enthalpy sensor and necessary control wire (minimum 1.5 sqmm) for integration within AHU room/OH UNIT<br>Motorized (ON-OFF Type) duct mounted Gl volume control Actuator
MOTORIZED GI VOLUME CONTROL DAMPER <br>Supply, installation, testing and commissioning of Motorized (ON-OFF Type) duct mounted Gl volume control damper with enthalpy sensor and necessary control wire (minimum 1.5 sq mm) for integration within AHU room/OH UNIT etc as required.
DUCTING .8mm GSS<br>Supply, installation, balancing and commissioning of fabricated at site GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required.<br>Site fabricated GSS sheet metal rectangular ducting as per IS 655-2006 for 0.8. mm thick
DUCTING .6mm GSS<br>Supply, installation, balancing and commissioning of fabricated at site GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required.<br>Site fabricated GSS sheet metal rectangular ducting as per IS 655-2006 for 0.63 mm thick
HEPA FILTER<br>SITC of HEPA filter, not less than 99.97% for particles down to .3 micron, when measured at rated air flow (1700 SCMH), having temperature resistance upto 120 degree.C, Humidity resistance 100% RH,rigidly mounted on Aluminum frame or CRCA carbon steel as per IS: 513 of 16 SWG with one coat of epoxy primer and two coates of chemical resistant epoxy paint on all exposed surfaces. double turned 19mm (3/4in) wide flange on each face. complete water repellent micro glass fibre (borosilicate) filter medium with thickness not less than .4 mm and airflow resistance at 2.5 cms/sec not more than 25 mm W.G, with all complete make and separator, sealant, gasket, face guards. all test report of components shall be submitted to HLL Engineer in charge/ Bio medical/ Electrical Engineer before installation.including onsite validation etc as required.
SITC UPVC DRAIN PIPE
Copper Piping ( Refrigerant gas)
MEDICAL GAS PIPELINE SYSTEM
CEILING ANESTHESIA PENDANT - MGPS<br>Supplying and Fixing Anesthesia Pendent with Single Arm with load carrying capacity of 90 kg, Provision for Terminal units ‐O2 ‐ 2 no,Air 4‐2no,Vac‐2no,N2O ‐ 1no, AGSS ventury outlet – 1 no ,330 degree angle rotation of column and arm, with Pnenumatic break as standard for arm system, 2 shelves ,IV pole with arm‐ 1no.,Provision for 12 nos Electrical and 2 data points.
BED HEAD PANEL <br>Supply,Installation,testing and commissioning of Bed head panels(1.2m) with Terminal unit provisions as per tender drawing. Provision for Electrical and data points . Accessories including suction holder and one monitor tray
Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.1 or 2 Module
Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.6 Module
OXYGEN MANIFOLD - 4X4 Oxygen Manifold , High Pressure Tail Pipe with NRV Cylinder Oxygen Manifold would be suitable to withstand a pressure of 140 Kg/Cm2 and above along with high pressure copper annealed tail pipes with end Brass adapter suitable for Oxygen Cylinders and manifold.Top frame comprising of high pressure copper pipes of size 12mm I.D x 1.5mm wall thick, with high pressure brass fittings made of high tensile brass and connections through non-return values; high pressure copper tail pipes, made of high pressure copper pipe of size 7 mm I.D x 1.5 mm wall thick. The design of middle and bottom frames would be provided to fit both round and flat bottom cylinders safely. The manifold would be tested (hydraulically) at 3500 pig.
Area Line Pressure Medical Gas Alarm ( 4 gases)<br>SITC of Four channel microprocessor controlled alarm for pneumatic & vacuum services with Digital display of line pressure for all the services with factory calibrated pressure sensors.Color coded LED display of line pressure status (High-cautionnormal- caution-low) Audible Alarm for High & Low pressure condition. Test and Alarm Acknowledge (Mute) facility. (Alarm knowledge (mute) time span is programmable from 1 to 60 minutes). Protected programming facility of alarm limits.The electronic circuitry should be such that if the pressure / vacuum in the gas pipeline drops below the present limit, the equipment should give an audio-visual alarm. Visual alarm should remain active even after pressing of “Mute” button. It should come to normal condition only when gas pressure / vacuum return to normal level. Small and compact design.Mounted on a powder coated MS box. Nut & Nipples should be provided for connection with Pneumatic supply complete as required, all QA/QC should be furnished before Engineer (HLL) before installing the system.
Oxygen Flow meter with Humidifier Bottle<br>SITC of Flow meter Back pressure Compensated.Flow meter would be accurate gas flow measurement and control within a range of 0-15 liters per minute.It would meet strict precision and durability standards.Flow meter body would be made of brass material. Flow tube and shroud components would be made of clear, impact resistant polycarbonate. The humidifier bottle would be unbreakable polycarbonate material and autoclavable at 134 degrees centigrade.The humidifier would have built in safety valve.
SITC of 0-10 Bar pressure control in the pipeline system with necessary accessories and all mounting requirements. The control must be easy to operate and have provision for displaying line pressure with necessary cut of valve.
15 mm BALL VALVE (MGPS)<br>SITC of Line Valves for use in plant rooms and to facilitate the isolation of areas or areas where area zone valve are unnecessary. These shall be of the ball valve type and shall be constructed of a nickel plated brass body, PTFE seats and brass chrome plated ball. The valve shall be operated by a manual operating lever by 90º turn. All medical gas line ball valves shall provide a full bore flow and shall be cleaned for oxygen service and fully tested. The valve assembly shall terminate in copper stub pipes to enable brazing directly into the distribution system using the flux less brazing technique. A locking device shall be provided to lock the valve in either the fully open or fully closed position. Line valves shall be located in readily accessible areas of ducts and shafts, however care should to ensure safety to prevent danger from leakage. Line valve installation should be carried out as per HTM 2022/HTM 02-01 standards
22 mm BALL VALVE (MGPS)<br>SITC of Line Valves for use in plant rooms and to facilitate the isolation of areas or areas where area zone valve are unnecessary. These shall be of the ball valve type and shall be constructed of a nickel plated brass body, PTFE seats and brass chrome plated ball. The valve shall be operated by a manual operating lever by 90º turn. All medical gas line ball valves shall provide a full bore flow and shall be cleaned for oxygen service and fully tested. The valve assembly shall terminate in copper stub pipes to enable brazing directly into the distribution system using the flux less brazing technique. A locking device shall be provided to lock the valve in either the fully open or fully closed position. Line valves shall be located in readily accessible areas of ducts and shafts, however care should to ensure safety to prevent danger from leakage. Line valve installation should be carried out as per HTM 2022/HTM 02-01 standards.
28 mm Ball valve (MGPS)<br>SITC of Line Valves for use in plant rooms and to facilitate the isolation of \areas or areas where area zone valve are unnecessary. These shall be of the ball valve type and shall be constructed of a nickel plated brass body, PTFE seats and brass chrome plated ball. The valve shall be perated by a manual operating lever by 90º turn. All medical gas line ball valves shall provide a full bore flow and shall be cleaned for oxygen service and fully tested. The valve assembly shall terminate in copper stub pipes to enable brazing directly into the distribution system using the flux less brazing technique. A locking device shall be provided to lock the valve in either the fully open or fully closed position. Line valves shall be located in readily accessible areas of ducts and shafts, however care should to ensure safety to prevent danger from leakage. Line valve installation should be carried out as per HTM 2022/HTM 02-01 standards.
15mm OD X .9mm THICK Cu PIPE<br>SITC of copper pipes manufactured from phosphorous deoxidised non-arsenical copper of grade CW024A (Cu-DHP), manufactured EN 13348:2008 to metric outside diameters and having mechanical properties, pipes shall be of R250 (half hard)temper.Pipes shall be degreased suitable for oxygen use and cleanliness is to be maintained by filling each pipe with dry, clean, oil and oxygen free nitrogen, fitting suitable end caps and protectively wrapping. Solid drawn, seamless, deoxidised, non- arsenical, half hard, tempered and degreased copper tubes manufactured to metric outside diameters and should have mechanical properties in accordance with HTM 02-01 and conforming to EN13348:2008.The pipes should also be accompanied with manufacturer’s test certificate for the physical and chemical composition. Copper Fittings should be as per HTM 02-01. All plastic saddles should have brass screws. as per the specifications and requirements, painting of the pipes installed as per color code for medical gas system is also under the scope of contractor.
22mm OD X .9mm THICK Cu PIPE<br>SITC of copper pipes manufactured from phosphorous deoxidised non-arsenical copper of grade CW024A (Cu-DHP), manufactured EN 13348:2008 to metric outside diameters and having mechanical properties, pipes shall be of R250 (half hard)temper.Pipes shall be degreased suitable for oxygen use and cleanliness is to be maintained by filling each pipe with dry, clean, oil and oxygen free nitrogen, fitting suitable end caps and protectively wrapping. Solid drawn, seamless, deoxidised, non- arsenical, half hard, tempered and degreased copper tubes manufactured to metric outside diameters and should have mechanical properties in accordance with HTM 02-01 and conforming to EN13348:2008.The pipes should also be accompanied with manufacturer’s test certificate for the physical and chemical composition. Copper Fittings should be as per HTM 02-01. All plastic saddles should have brass screws. as per the specifications and requirements, painting of the pipes installed as per color code for medical gas system is also under the scope of contractor.
28mm OD X .9mm THICK Cu PIPE<br>SITC of copper pipes manufactured from phosphorous deoxidised non-arsenical copper of grade CW024A (Cu-DHP), manufactured EN 13348:2008 to metric outside diameters and having mechanical properties, pipes shall be of R250 (half hard)temper.Pipes shall be degreased suitable for oxygen use and cleanliness is to be maintained by filling each pipe with dry, clean, oil and oxygen free nitrogen, fitting suitable end caps and protectively wrapping. Solid drawn, seamless, deoxidised, non- arsenical, half hard, tempered and degreased copper tubes manufactured to metric outside diameters and should have mechanical properties in accordance with HTM 02-01 and conforming to EN13348:2008.The pipes should also be accompanied with manufacturer’s test certificate for the physical and chemical composition. Copper Fittings should be as per HTM 02-01. All plastic saddles should have brass screws. as per the specifications and requirements, painting of the pipes installed as per color code for medical gas system is also under the scope of contractor.
AUTOMATIC OXYGEN CONTROL PANEL<br>SITC of fully automatic control panel having following features -Would be enclosed in a metal cabinet with a hinged cover. The side covers of the panel would be made of fiber glass. Panel cover would be fitted with a lock to prevent unauthorized access can be swung open for maintenance. Would be Fully Automatic Changeover operation and no manual action The service gas would pneumatically operate gas change over system. Delivery of gas through control panel would not be dependent on electricity. Would be capable of delivering very high flow rate not less than 1300 liters per minute at delivery pressure. Would have Visual indication of the state of the manifold by 3 gauges within the control panel, which would be clearly visible through the transparent cover. Would have Audio – visual alarm indication for changeover of empty cylinder bank to filled cylinder bank. Built in transformer to ensure safe operation by low voltage. Microprocessor based alarm signal control with high ‘db’ Siren system. and can be operated with single/Three phase AC system at 50 hz.
SEMI AUTOMATIC NITROUS OXIDE CONTROL PANEL<br>Control panel should have two first stage regulators each capable of delivering 100 - 200 psi g outlet pressure.Both the first stage regulators in the nitrous oxide control panel should have non-halogenated polymer in the high pressure side to ensure that there will be no ignition due to adiabatic compression.40 micron filter should be provided at the inlet of each high pressure regulators of the nitrous oxide control panel.The first stage regulators should be connected to a common second stage regulator which will deliver an outlet pressure of 60 psi g.The first two regulators meant for first stage should be capable of switch over system incorporated from “RUNNING” to “RESERVE” bank due to differential pressure.The control panel should be provided for two individual content contact pressure gauges to indicate the cylinder pressure in the two wings of the manifold and common pressure gauge to indicate the delivery / line pressure.The control panel should have built in audio-visual signal lamp indications for bank changeover. The control panel will be covered with aesthetically suitable cover for safe operation indicating the respective services.Control panel should have built in transformer to ensure safe operation by low voltage. Nitrous Oxide control panel should have inbuilt heating arrangement to ensure that there will be no freezing in the delivery line during high flow requirement.Delivery flow capacity : Approx 500 l/min at 55-60 psi pressure,Nitrous Oxide Manifold -1 X 1 Manifold
NITROUS OXIDE MANIFOLD - 1X1<br>1+1 Size Nitrous oxide Manifold should be configured with 1 x 1 nos. should be suitable to withstand working pressure of 145 Kg/cm2, along with 2 nos. of high-pressure copper annealed tail pipes with end brass adapter suitable for Nitrous oxide cylinders and manifold.The manifold should be so designed that it should suit easy cylinder changing and positioning. The system should have non-return valves for easy changing of cylinders without closing the bank. The cylinder should be placed with the help of cylinder brackets and fixing chains which shall be zinc plated.
POWER CIRCUITRY
Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall, making good the damages, colour washing etc. as required4 way (8+12) - three phase double cover (IP 42/43)
Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required6 way (8+18) - three phase double cover (IP 42/43)
Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required12 way (8+36) - three phase double cover (IP 42/43)
Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required6 way (8+18) - double cover TPN vertical DB with provision for fixing 4P MCB / Isolator/ RCCB/ RCBO as incomer and SP/ TP MCB as outgoing (IP 42/43)
Supplying and fixing following rating, four pole, (three phase and neutral), 415 V, residual current breaker with overload (RCBO), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc.<br>25A 4P,30MA<
Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps
Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps
Supplying and fixing following rating, four pole, (three phase and neutral), 415 V, residual current breaker with overload (RCBO), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc.<br>40A 4P,30MA<
Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.100 amps
SITC 63A RCCB<br>Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 30 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.<br>63 amps
0A/63A TP MCB WITH SHEET STEEL ENCLOSURE<br>Supplying and fixing TP sheet steel enclosure on surface/ recess<br>along with 16/25/32/40/63 A, 415 V “C” curve TP MCB complete<br>with connections, testing and commissioning etc. as required
Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole
Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Triple pole
Supplying and fixing 20 amps, 240 volts, SPN industrial type, socket outlet, with 2 pole and earth,metal enclosed plug top along with 20 amps "C" curve, SP, MCB, in sheet steel enclosure, onsurface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required.
SITC FITTINGS
20W LED TUBE TYPE FIXTURE<br>SITC OF Modular type 20W LED tube type fixture directly on to wall including drilling and fixing, making necessary connections and make as approved by engineer in Charge or Electrical Engineer.
2X2 SQUARE TYPE RECESS MOUNTED LED LIGHT<br>SITC OF 600mmX600mm square type Cool White, Warm White, Pure White LED light fixture with Integrated Driver & Backlight Technology with a minimum system efficacy of 95w/Lm, Standard CCT: 3000K*, 4000K & 6500K, high color rendering CRI >80, with high efficiency driver, minimum of 35000 hours working life, and Surge protection -4KV (light variant as decided by engineer in charge),including connection with existing point using suitable gauge copper conductor directly to the ceiling rose. Each module should be tested and QC approved by competent authority and the same to be furnished before electrical engineer HLL Lifecare limited before purchase or else any higher version approved by the Electrical Engineer HLL Lifecare Limited
SITC 2 TON SPLIT AC<br>Supply, installation, testing and commissioning of 2 TR, 3 star rated (as per BEE) Air Cooled High Wall mounted Inverter type Split Air Conditioner consisting of high wall mounted type room unit (fan coil) with cordless remote control and one number outdoor condensing unit comprising of enegy efficient suitable rotary compressor for operation on single phase, 230 V, 50Hz supply, fixing the outdoor unit on a raised platform as per manufacturers recommendation and fixing of room (fan coil) unit on wall, standard 4 m distance refrigerant copper piping with 13mm nitrile rubber insulation, providing and making interconnection between room & condenser as per site conditions, comprising of 1" dia drain PVC pipe with insulation 4m, canvas connections, full electrical cabling from power plug near indoor unit and to outdoor unit, ODU MS stand, first charge refrigerant gas, suitable stabilizer etc complete as required. Make: Voltas, Toshiba, Blue Star, Siemens, Mitsubuishi, Hitachi or equivalent
EXHAUST FAN,SHUTTER TYPE <br>Supply and installation EXHAUST FAN,SHUTTER TYPE white colour, 9" OR 10" star rated as per BEE complete with its all accessories(Make Havells/bajaj/usha/Vguard)
Conveyance, installation, testing and commissioning of wall mounting fans of all types using mounting brackets supplied along with the fan
Charges for cutting holes suitable for accommodating exhaust fans above 305mm sweep and up to 450mm sweep including plastering colour washing etc. as required.
Conveyance, installation , testing and commissioning of exhaust fans of size up to 450mm in the existing opening, fixing necessary anchor bolts / bolt and nuts etc., as required including giving connections with the supplied wire along with the exhaust fan.
WALL FAN: Supply and installation of wall fan, white colour, 5 star rated as per BEE complete with blades, casing , wall mounting accessories etc(Make Havells/bajaj/usha/V-guard/crompton)
UPS with 20min backup with SMF battery of 2yr warranty. The system shall be true online, double conversion technology with input pf >0.98, input current THD <10% and 100% generator compatabile. The system shall comply to IEC /EN 62040-1 and relevant IS standard. 10kVA 3ph input / 3ph output
Supplying of Ceiling Fan 900mm Sweep complete with 300mm down rod, canopies, shackles and blades and without regulator working on 230/240V Single phase AC,as per latest BEE Standard & IS 374:2019
interprise innovation projects private limited
JPR Solutions
VARGHESE ANTONY
stage.html
html • 0.05 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .