Tender Value
₹1.3 Cr
EMD Value
₹2.6 L
Closing Date
21 Sept 2026, 3:00 pm
CE BDA
CE Office BDA Bareilly
Pilibhit Bypass Marg par Barrier No.-2 se Bada Bypass tak sadak chaudikaran hetu prastavit divider par prakash vyavastha ki sthapana evam 05 varsh ka sanchalan evam anurakshan ka karya.
2026_BDAUP_1179527_1
T-23/2026/14
Open Tender
Electrical Works
Percentage
270 days
Bareilly
Please refer Tender documents.
2 documents required · 2 mandatory
₹15,000
Vice Chairman, Bareilly Development Authority
₹2.6 L
24 Aug 2026
24 Aug 2026
22 Sept 2026
24 Aug 2026
21 Sept 2026
24 Aug 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Part A
Supply & fixing of 10 mtr GI Octagonal Pole of approved make (top dia 100 mm, Bottom dia 200 mm and base plate 16mm thick) having 3 mm thikness with Double arm bracket 1 Mtr length in 1:2:4 RCC foundation bolt including the cost of foundation, excavation & back filling and Required T&P complete in all respect. (S.I. 21.2.9 PWD SHEDULE 2024) (at the rate of 40416 X 0.8475=34253) | 156 | Nos. | 34,252.56 | ₹53,43,399.36 |
| 2 | Supply & fixing of 16 mtr High mast shaft of approved make with rising system hot dip glavanized inside & out side dip,heaving pole sheet thickness 4 mm. Top dia minium 150 mm, Bottom dia 360 mm base plate 32 mm thick suitable for wind velocity as per IS 875 part 3 & having no circumferential weld, with accessories for high mast such as head frame suitable for 6 to 12 luminaries & its control gear boxes 1.5 HP power tool moter, 3 point suspension system with steel wire rope 6 mm dia, double drum winch, including making suitable foundation as per manufature drawing/ site reuiment along with foundation bolts nuts, washers, anchor plates etc complete in all respect. (S.I. 21.3.1, PWD SHEDULE 2024) (at the rate of 291599 X 0.8475=247130) | 4 | Nos | 2,47,130.15 | ₹9,88,520.6 |
| 3 | LED Street light fixture, powder coated pressure die cast aluminium body (System lumen efficacy >135 Im/Watt). Supplying, Installation, Testing & Commissioning of Street light LED fixture, powder coated pressure die cast aluminium body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: 140-270 Volt AC. frequency 50/60 hz, Operating temp range -5 °C to 50 °C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F>0.95, IP-66, IK10, CRI > 70, under voltage and over voltage protection, EMI-EMC as per CISPR15, lenses for beam angle as per IESNA type I/II/ Ill as per the width of the oadand the projectrequirement., suitable to fit in up to 65mm dia pipe, life time (LED,Driver & electrical circuitary) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K /5700°K / 6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor Single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy >135 Im/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C) complete in all respect. as per D/Ich.Capacity-150 walt (S.I 8.14.17 CPWD SHEDULE 2025 (5090X0.755X0.97=3727.66) | 312 | Nos | 3,727.66 | ₹11,63,029.92 |
| 4 | LED Flood Light, powder coated pressure cast aluminium (System lumen efficacy ≥135 Im/Watt)
Supplying. Installation, Testing & Commissioning of Flood Light, powder coated pressure die cast aluminium body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: Input voltage: 140-270 Volt AC,frequency 50/60 hz, Operating temp range -5 °C to 50 °C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI ≥70, under voltage and over voltage protection,EMIEMC as per CISPR-15, lenses for beam angle 30 deg-120deg as per the application and the project requirement., suitable tilt able fitting, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K/ 4000°K / 5700°K /6500°K (As per ANSI Bin) SDCM(Standard Deviation Colour Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy >135 Im/Watt output. LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). complete in all respect. as per D/Ich. Capacity-200 Walt (S.I. 8.17.5 CPWD SHEDULE 2025) cat.AAA (5504X0.755X0.97=4030.85) | 48 | Nos | 4,030.85 | ₹1,93,480.8 |
| 5 | Supply and laying of almunium conductor PVC insulated aromoured served Sheathed cables 1100V grade in Existing RCC/Hime/Metal pipe as directed by Engineer in charge complete in all respect including excavation and refilling. The armouring of the cable shall be properly connected with the earth conductor by clamps etc. (S.I. 20b.1.9, 20b.1.12 LUCKNOW PWD SHEDULE 2024) (at the rate of 283 X 0.8475=240, 527 X 0.8475=447)
16 sqmm 4 Core | 4,650 | Rmt | 239.84 | ₹11,15,256 |
| 6 | 50 sqmm 3-1/2 Core | 500 | Rmt | 446.63 | ₹2,23,315 |
| 7 | Supply and Wiring of submains with two nos. of 2.5 sq.mm. FRLSH PVC insulated 1100 V grade single core multistrand copper conductor cable in existing conduit complete with supply of all material labour and T&P required for proper completion of the work as directed at site by Engineer in charge. (S.I. 289, PWD SHEDULE 2018) | 4,368 | Mtr | 55 | ₹2,40,240 |
| 8 | Trenchless boring with more than 2 mtr and upto 6mt below ground level by machine technology including laying of 11000 v HT cable 150mm Sqm to 400 sqmmm size with proper completion of the work. As per per direction of E/I. (Analysis Rate) (UPPCL Cost Data Book 2026) | 400 | Mtr | 852 | ₹3,40,800 |
| 9 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all aceesories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, Jointing etc.direct in ground(75cm below ground level), including excavation and refilling the trench but excluding sand cushioning and protective covering etc complete as required. 63mm dia (OD-63 mm& ID-51 mm nominal (S.I. No. 15.16) CPWD/2025 (289.00X0.755X0.97=212) | 4,275 | Rmt | 211.65 | ₹9,04,803.75 |
| 10 | Supply and laying of 25mm x 5mm G.I. strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bol, spring, washer etc. as required. (Jointing Shall be done by overlapping and with 2 sets of G.I. nit bolt & spring washer spaced at 50mm) complete in all respect.
(S.I. 5.9, CPWD SHEDULE 2025) (at the rate of 160 X0.755X0.97=117) | 100 | Rmt | 117.18 | ₹11,718 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.96 MB
TenderDocument.pdf
Tender Documents • 27.76 MB
BOQ_2217886.xls
BOQ • 0.39 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].