Loading…
Loading…
Tender Value
Refer Docs
EMD Value
₹1 L
Closing Date
3 Jul 2026, 5:45 pm
Similar tender results from the same govt authority in the past 3 years.
PURCHASE EXECUTIVE
SUPPLY, INSTALLATION, CONFIGURATION, AND COMMISSIONING, TESTING AND ACCEPTANCE OF A CENTRALIZED DATA STORAGE SOLUTION (SAN STORAGE WITH BACKUP INFRASTRUCTURE), INCLUDING ASSOCIATED CIVIL, INTERIOR, ELECTRICAL, ELV, NETWORKING, COOLING, FIRE SUPPRESSION, UPS AND STABILIZER RELATED WORK
314929
PIND-2526-01670-R1
Open
IT - All
Vadodara
16 documents required · 15 mandatory · 1 optional
₹1 L
17 Jun 2026
17 Jun 2026
17 Jun 2026
3 Jul 2026
17 Jun 2026
PIND-2526-01670 BILL OF QUANTITY 18/12/2025
BOQ FOR CIVIL & INTERIOR WORKS
Unit Price Total Price
Sr.No. Description of items Unit Qty
Providing and constructing brick masonry in partition walls
in any shape & for all works with approved quality bricks
having minimum crushing strength 35 Kg./Sq.cm, at all
levels in CM 1:4 (1 part cement and 4 part coarse sand)
including scaffolding, racking out joints, FOR 100 MM THICK
PARTITION WALLS
Providing and applying 12 mm thick plain cement plaster
finish at all heights and below highest plinth level in Cement
Mortar (CM) 1:4 (1 part cement: 4 parts sand) in line, level
and plumb to the walls, concrete elements, beams, ceiling,
stair, columns, pardis, including making plaster bands,
stripes, moulds, pattas, grooves etc, over any brick or
concrete surface as specified including scaffolding, curing
and finishing smooth, complete as directed.
Providing and fixing of RCC lintel coping, 100 mm wide and
100 mm high, reinforced with 8 mm and 12 mm steel bars
Providing and Fixing of 600 x 600 Floor Tiles With Req.
1.40 Chemical or Cement Mortar and Other material Removing SFT
Old Tile and Bedris Outside Plant Area, Tile Basic Rate 50 Rs
1.50 Skirting Rn.FT
Providing and fixing of 100-250 mm Door granite framework
with required chemical anchoring and Dhar police
1.70 Removing Existign Window Nos
Dismantling a 3' x 3' wall, removing debris outside the
premises, finishing plaster in the window cutout area, and
providing and fixing a granite frame in the 3' x 3' window
Dismantling RCC slab (madiya) in the new server room,
1.90 approximately 8' x 3' in size, finishing the affected wall area Job
with plaster, and removing debris outside the premises
2.00 Antistatic Access floor/ Vinyl & LWF works
Raised Antistatic Access Flooring : Supply, laying and
fixation of false Flooring for Netwok S/w Room . For cut tiles
measurement shall be considered as one full 2’x2’ tile with
more than 12” as full tile and 2 Nos. of tiles with less than
12” to be considered as 2’x2’ full tile.Understructure for SFT
false flooring giving 450mm to 6000 mm height for false
floor on IPS. Price to include material labour, alignment, tile
cutting for Racks. including at corners and partial tiles.
Costs include final alignment after equipments are placed.
3.00 False Ceiling
Gypsum Board Suspended Ceiling : Providing and fixing
in position multi level FR MR grade GYPSUM board false-
ceiling suspended on G.I. frame work in design as shown in
the drawing. The G.I. frame work consist of Perimeter
channel of size 27mm x 0.5mm. Intermediate channel of
size 45mm x 0.5mm thick. Ceiling section of 0.5mm
thickness. 12.5mm thick tapered edge gypsum plaster
board fixed to ceiling channel with 25mm dry wall screws at
230mm centers Jointed and finished with requisite filler,
paper tape, finisher and primer suitable for Gypsum plaster
boards. Rate to include making necessary cut-
outs/openings for light fittings. This item includes all vertical
drops, niches in ceiling etc. Gypsum board to be of saint
gobin / India Gypsum.
PIND-2526-01670 BILL OF QUANTITY 18/12/2025
Grid Ceiling:-Providing & Fixing of micro-perforated-metal-
Suspended Ceiling System with TILES using GI .50 MM
Thick. Panels - Square - Beveled edge, Size -600 * 600mm.
Material: Galvanized Steel 0.5mm. Perforation Details:
2.5mm, Center to Center in Regular Pattern & Square
Perforation. Paint finish: 55 microns thick powder coating on
exposed surface or 25 microns polyester coil coated over
primer on visible surface with primer coat on rear side.
Suspension: Spring Steel Butterfly clip, 4mm dia GS Rod,
GS / Aluminum Edge Profile & recommended 'T' grid system.
Gypsum Board Cove : P/f Cove light pelmet/trough:
150mm high, 200mm wide in ceiling made of Lagyp board
3.30 with GI framing complete as per design. (Note :- Cove to be RFT
complete from inner side as well) Gypsum board to be of
saint gobin / India Gypsum
4.00 Alluminium Section Work
Alluminium Profile Shutter : Providing and fixing
4.10 aluminium section framing with a profile shutter and 5mm SFT
5.00 Doors / Shutters (Modi Guard, Saint Gobain toughened Glass)
Glass Door Only H/W :- The door will be fixed on Insta /
Ozone / Dorset MAKE fitting as top Pivot , top patch
bottom patch ,Floor Spring , corner lock with lock keeper
plate , door handle (300 mm long) as approved etc.
Glass door Hardware - 900 x 2100 MM NOS
6.00 Glazing and Glazed Openings
Frameless Glass Partition or Fix Glass : Providing &
fixing frameless glazed door shutters using 12 mm thick
toughened glass with all necessary hardware required &
necessary floor / glass cutting, making holes etc complete
as per design & detailed drawings (drawings shall be
prepared by the bidder).
Painting & Polishing Work
Providing and applying 2 or more coats of paint on walls or
ceiling wherever advised . The surface shall be thoroughly
cleaned and prepared by raking old paints (existing) by sand
7.00 papering and applying 2 coat putty to achieve smooth and
truly levelled surface. Required number of coats and type of
primer as prescribed by manufacture shall be applied before
the application of finishing coat as recommended by
manufactures' specifications
7.10 Fire Retardant Plastic Emulsion Paint SFT
Providing & applying surface cleaning proper then crack
filling and two or more coats of "Exterior Paint" Apex Ultima,
Dulux, Berger approved colour shade to give good and even
shade over Compound wall surfaces at all levels including
scaffolding, cleaning, washing the surface etc. complete as
per instructions of ERDA EIC.
Inside Painting /Interior Surfaces: Providing and applying
three or more coats of Acrylic Premium Emulsion paint of
"Asian or Berger" make of approved colour and shade one
coat of primer, brooming down and cleaning the surfaces,
finishing of holes and depressions including scaffolding and
staging of all levels with all labour and material at etc. all
levels including all complete As per instructions of ERDA
engineers-in-charge
PIND-2526-01670 BILL OF QUANTITY 18/12/2025
OIL Paint Colourwork:
Providing and applying two or more coats of synthetic
enamel paint or oil paint of "Asian or Berger" make, and of
7.40 approved colour and shade one coat of primer & 2 coat of SFT
Oilpaint colour cleaning the surfaces, with all labour and
material etc. complete at all levels. As per instructions of
ERDA engineers-in-charge
8.00 Internal Signages
General room Signage in foam sheet 2mm thick 300 x
General Luminous Fire Exit - 2 hours battery back up
Signages 300 x 150 MM
8.30 Fire evacuation plans foam sheet 2 mm thick 1000 x 600 MM NOS
8.40 Push/ Pull signages for all doors SS Finish 100 x 50 NOS
9.00 Special Feature Items
Entrance Floor Mat - Providing and installing trapper floor
matting (Heavy duty) as per manufacturer specification.
Deep Cleaning of Floor JOB
10.00 FIRE DOOR
10.10 Door Size: 900-1000mm (W) x 2100mm (H) – S.L. NOS
S.S. Ball Bearing Hinges (Dorma, Yale Make)
Vision Panel with Fire Rated Glass of Size: 200 x 300mm
(6mm Thick Clear Toughened Fire Glass)
Heavy Duty Door Closer (Dorma, Yale Make)
Dead Lock with Cylinder (Dorma, Yale Make)
S.S. “D” Type Handle (1 Set)
BOQ FOR ELECTRICAL WORK
Unit Price Total Price
ITEM DESCRIPTION UNIT QTY
1.0 LV DISTRIBUTION PANELs
1.1 LOW VOLTAGE PANEL BOARDS
Supply, Installation, assembling, connection, testing and
commissioning of Panels as per Specification, Technical
Data sheet, IS & relevant drawings.
All panels and DBs shall be manufacturerd by ERDA
approved (for 50kA/3S) panel busbar testing certificate in
last two years) panel manufacturer. Panel Support
Structure shall be pre-cast, pre-fabricated angle/channel
structure with sheet steel fabricated doors & partitions.
The unit rate for each item shall include :
1) SITC of panels
2) Testing of panels as per specifications at manufacturer's
works in presence of client's representative and/or
3) Delivery of the panels / DB's to site.
4) Shifting of the panels from site store to the suitable location.
5) Assembly and wiring of component supplied separately.
6) Touching of body with powder coating for demaged parts. All
the nuts bolts & joints exposed to the air shall be covered
with suitable anti - oxtidant material or as directed by the
Engineer incharge.
7) Supply all accessories and supporting structure.
8) Checking of Internal connection & wiring, operation of
switches, MCCB, MCB etc.
9) Testing of panels as per specifications at manufacturer's
works in presence of client's representative and/or
10) Delivery of the panels / DB's to site.
11) Shifting of the panels from site store to the suitable location.
11) Assembly and wiring of component supplied separately.
12) Installation of panels as per Location arranged by site
Engineer in charge including removing packing.
PIND-2526-01670 BILL OF QUANTITY 18/12/2025
13) Earthing all components, frame etc. to a common internal
14) Touching of body with powder coating for demaged parts. All
the nuts bolts & joints exposed to the air shall be covered
with suitable anti - oxtidant material or as directed by the
Engineer incharge.
15) Supply and fixing all accessories and supporting structure.
16) Checking of Internal connection & wiring, operation of
switches, MCCB, MCB etc.
17) Supply of necessary tools, hardware, testing hardware,
testing equipment during testing at site.
18) Supply & fixing of 100 mm main steel [No rolling mill
material shall be allowed] MS channels for fixing the panel,
alongwith all the required civil materials required to
complete the job as per the instruction of Engineer
19) To carry out the insulation test at site and all the readings
shall be submitted in duplicate to the consultant or engineer-
20) To co-ordinate with other agencies working at site
21) To prepare shop drawing and to take approval of consultant
& client at each stage.
22) To prepare & submit as-built drawing and handing over
document to end user.
Supply, Installation, assembly, connection, testing and
1.1.1 commissioning of MAIN LT as per Specification with energy No.
meter, Technical Data sheet & ISI PER SLD,
2.0 LIGHTING / POWER DISTRIBUTION BOARDS
2.1 Supply, installation, Testing & Commissioning of
Distribution Board as per following Description.
The distibution board shall be sheet steel clad (Fabricated /
ready made), concealed/recessed mounted, constructed
from 14 SWG sheet steel finished with rust proof red oxide
coating and two coats of paint with hinged gasketted door.
DBs shall have following features/Compliances:
1) Conforms to IS8623-1&3,IEC61439-1&3
2) IP-43 or 42 :- Ensures DB are protected against Foreign
bodies and liquids.
3) IK-08,09 :- Ensures that the DB are well protected against
Mechanical Impact
4) ROHS Compliance
5) Double door type with Reversible doors
6) Earthing facility with star washer (Per phase earthing strip)
7) Independently packed door, frame, shield cover
8) Removable Chasis
9) With Wiring kit (Insulated Busbars,Cablesties,Sticking
saddles, Blanking plates shall be provided)
10) Shall have high quality gaskets ensuring IP for life time.
11) Front shield cover with kNos.bs and locked screws
12) Locks with padlock facility
13) Cable kNos.ckouts on all sides
14) Mark for insertion on DB
15) Cement spill cover
16) Neutral Shrouded (per phase neutral links)
17) Per phase isolation (PPI Type), Prewired up to the cnnector
18) PVC insulated copper busbars with interconnections
19) Horizontal/Vertical series type Distribution boards with
MCB/MCCB as Incommer as per descriptions mentioned
The unit rate for each item shall include :
1) Supply of DBs
2) Delivery of the DB's to site.
PIND-2526-01670 BILL OF QUANTITY 18/12/2025
3) Shifting of the DBs from site store to the suitable location.
4) Assembly and wiring of component supplied separately.
5) Installation of DBs as per Location arranged by site Engineer
in charge including removing packing.
6) Earthing all components, frame etc. to a common internal
7) Touching of body with powder coating for demaged parts. All
the nuts bolts & joints exposed to the air shall be covered
with suitable anti - oxtidant material or as directed by the
Engineer incharge.
8) Supply and fixing all accessories and supporting structure.
9) Checking of Internal connection & wiring, operation of
switches, MCCB, MCB etc.
10) Supply of necessary tools, hardware, testing hardware,
testing equipment during testing at site.
11) To prepare submission drawing and to take approval of
consultant at each stage.
11) To prepare & submit as-built drawing and handing over
document to end user.
Note :The DBs shall be supplied at site to be used
during civil construction activity. It shold be supplied
with proper protection to avoid any physical damage
or ingress of water /cement during construction.
Supply , Installation , Testing and commissioning of Double Nos.
2.1.1 door type 6 WAY TPN LDB as per specifications and
relevant IS. Drawing
Incomer : 32A TPN MCB- C Class
Outgoing: 3Nos. 25A DP ELCB (One in each phase - 30mA) -
12 Nos. 10-16A SP MCB - C Class
Supply , Installation , Testing and commissioning of Double Nos.
2.1.2 door type 8 WAY TPN RPDB & AC DB as per specifications
and relevant IS. Drawing
Incomer : 63A TPN MCB C Class
Outgoing: 3 Nos. 40A DP ELCB (One in each phase -
18 Nos. 16 - 32A SP MCB - C Classs
Supply , Installation , Testing and commissioning of Double Nos.
2.1.3 door type 4 WAY V TPN UPS DB as per specifications
and relevant IS. Drawing
Incomer : 63A TPN MCB
Outgoing : 12 Nos. 32A SP MCB - C Class
Supply , Installation , Testing and commissioning of Double Nos.
2.1.4 door type 12 WAY SPN DB as per specifications and
relevant IS. Drawing
Incomer : 32A DP MCB- C Class
Outgoing: 10 Nos. 16A SP MCB
Supply , Installation , Testing and commissioning of 32 Amp Nos
DP MCB C Class With Encloser
Supply , Installation , Testing and commissioning of 63 Amp Nos
4P MCB C Class With Encloser
Supply , Installation , Testing and commissioning of 16 Amp Nos
DP sequence controller.
Supply , Installation , Testing and commissioning of 32 Amp Nos
4P sequence controller
Supply , Installation , Testing and commissioning of 32 Amp Nos
4P MCB C Class With Encloser
PIND-2526-01670 BILL OF QUANTITY 18/12/2025
Supply , Installation , Testing and commissioning of 125A 4P Nos
Mccb 25 AK With Outdoor Type Encloser
3.0 LOW VOLTAGE CABLE
3.1 Supply, laying, connection, testing and commissioning of
heavy duty, low voltage, XLPE (IS 7098 - PART-II)
insulated, stranded AL / Cu conductor Armoured cables
as per specification & IS.
The cable shall have inner sheeth of XLPE and outer sheath
of PVC ST2 (FRSL) type with stranded AL/Cu conductor
wherever specified.
Outside Building Installation: The cable shall be laid
underground in excavated trench / prepared trench / hume
pipes when laid outside the building.
Cost of excavation, trenches, hume pipes shall be
considered under separate head.
Within Building Installation: Cable shall be laid throught
preapred trench / cable tray / duct / hume pipe / channel /
floor trunks etc when laid inside the building.
Cost of excavation, trenches, trays, hume pipes, channel,
trunks shall be considered under separate head.
The scope shall include:
1) Supply of Cables.
2) Delivery of the cables at site.
3) Unloading at site store.
4) Shifting of cable from site store to place of installation.
5) Excavation in hard or soft murrem / rocky area upto
required depth, supply and laying of protection bricks,
supply and backfilling with fine sand, leveling the ground to
match with the existing condition.
5) Laying of cable in the excavated trench / prepared trench /
cable tray / duct / hume pipe / channel / floor trunks when
laid inside or outside the building.
6) Connection of cable.
7) Supply & fixing of cable clamps, brackets, supports, route
markers etc. where ever required to fix the cables safely.
8) Earthing the glands and armouring with earthing clamp and
jumper and also connecting to common earth bar.
9) Testing of insulation and continuity of cable and submission
of reports to the client's representative.
10) To prepare submission drawing and to take approval of
consultant at each stage.
11) To prepare & submit as-built drawing and handing over
document to end user.
3.1.1 4C X 240 mm² AL XLPE - FRLS Mtr.
3.1.2 4C X 50 mm² CU XLPE - FRLS Mtr.
3.1.3 4C X 10mm² CU XLPE CABLE - FRLS Mtr.
3.1.4 4C X 4 mm² CU XLPE CABLE - FRLS Mtr.
3.1.5 4C X 6 mm² CU XLPE CABLE - FRLS Mtr.
3.1.6 1C x 25 Sq.mm FRLS Fexible Cable Mtr.
3.2 CABLE END TERMINATION AND CONNECTION
PIND-2526-01670 BILL OF QUANTITY 18/12/2025
Supply, fixing, connection, testing & commissioning of
Double compression brass cable glands and crimping type
Bimetalic lugs / sockets with necessary tools and
equipments as specified in specifications and IS. For
outdoor installations, double compression glands shall be
considered. The glands and lugs / sockets shall be
suitable for cable size and type mentioned above. The job
also includes, if necessary, supply and fixing of extension
busbar of same material on circuit breaker or panel board
terminal / connector to connect more than one Nos. of
parallel cables or to connect higher size cable to lower size
unit. The job also includes earthing the glands and armour
of the cable with common earth bar or flexible copper mesh.
3.2.1 4C X 240 mm² AL XLPE - FRLS Nos.
3.2.2 4C X 50 mm² CU XLPE - FRLS Nos.
3.2.3 4C X 10mm² CU XLPE CABLE - FRLS Nos.
3.2.4 4C X 4 mm² CU XLPE CABLE - FRLS Nos.
3.2.5 4C X 6 mm² CU XLPE CABLE - FRLS Nos.
3.2.6 1C x 25 Sq.mm FRLS Fexible Cable Nos
4 CABLE TRAY WITH COVER
4.1 Supply and laying of pre galvanised, GI readymade
Perforated Cable Tray With Support & Cover
4.1.1 300 X 50 X 2 MM Thick Perforated Cable Tray With Cover Mtrs.
4.1.2 150 X 50 X 2 MM Thick Perforated Cable Tray With Cover Mtrs.
5.0 LIGHT FIXTURES AND FANS
5.1 Supply, Installation, assembling, connection, testing &
commissioning of fixtures complete with suitable rating LED
luminaries, high power factor improving capacitor, control
gears and all other necessary accessories to complete the
installations. Power rating of light fixture mentioned below is
bare minimum. Vender to supply equal or higher rating
5.1.1 Supply, Installation, testing and commissioning of 15-18 W
CEILING MOUNTED DOWN LIGHTER - 4000K LED
6.0 INTERNAL WIRING
6.1 Wiring for Light Points Controlled from Switch Boards
Supply, installation, connection, testing & commissioning of
following outlet points as per Specification & IS. The unit
rate for the point shall consist of the circuit wiring from LDB
and/or switch board to outlet point through switch as
required & including the outlet points with connector &
sockets. A point shall include in addition to phase & neutral
wire, earth continuity wire from LDB to the final termination
at outlet points.All the wiring, outlet points shall be done in
a surface / concealed manner with metal conduit of
minimum 25 mm. dia. using 1100 V FRLS copper conductor
wire. Supply and installation of Modular switches with
suitable plate, PVC/GI back box with brass chromium /
cadmium plated machine screws etc. shall be part of job.
PIND-2526-01670 BILL OF QUANTITY 18/12/2025
Phase & Neutral : 1.5 mm2 Cu FRLS flexible wire
Earth : 1.5 mm2 Cu FRLS flexible wire (1100 V)
6.1.1 light points controlled by one 6A switch or Loop Light Point Nos.
6.1.2 6A socket with one 6A switch on switch board with cover Nos.
plate and all required accessories
6.1.3 Supply ,fixing, connection and testing of 5-pin 16A power Nos.
plug socket alongwith 16A switch with top cover plate,
PVC/GI back box suitable for modular plate with all
accessories to complete the job.
6.1.4 32 Amp PVC Industrial Socket With Plug Nos.
6.2 Mains Wiring for Lighting Circuits
Supply, laying, connection and testing of lighting wiring
from DB to switch board with following wires to be laid
through Metal condiut in concealed/surface manner.
6.3.1 Supply, laying, connection and testing of 2R x 2.5 Sq.mm &
1R x 1.5 Sq.mm Cu FRLS flexible wire (1100 V) to be laid Mtr.
6.2.1 Supply, laying, connection and testing of 2R x 4 Sq.mm &
1R x 2.5 Sq.mm Cu FRLS flexible wire (1100 V) to be laid Mtr.
6.2.3 Supply, laying, connection and testing of 3C x 6 Sq.mm Cu
FRLS flexible wire (1100 V) to be laid Metal condiut. Mtr.
6.2.4 Supply, laying, connection and testing of 3C x 1.5 Sq.mm
Cu FRLS flexible wire (1100 V) to be laid Metal condiut. Mtr.
6.2.5 Removing existing cabling from the back side area near the
electrical panel and refixing all cables properly in the cable Job
tray using required materials and accessories
7.0 EARTHING SYSTEM & LA
7.1 Earthing Stations
Supply, installation, connection and testing of plate type /
pipe type earthing station for various electrical equipments
and systems as per IS with following.
1) Excavation in soft soil / hard marrum
2) Supply of copper plate electode / G.I. Pipe electrode.
3) Supply & fixing of watering 'B'Class pipe.
4) Supply of civil material and preperation of brick masonry
earth pit chamber with Heayy Duty C.I. frame and hinged
covers of suitable size as per drawing.
5) Supply and providing of charcoal and salt for filling in earth
6) Supply of tools and tackles necessary for excavation to a
desire depth and doing necessary civil work etc.
7) Testing earth resistivity before earthing and electrode
resistance after completion of work.
8) Supply and fixing of Equipotential bar with housing
alongwith necessary mounting accessories.
7.1.1 SITC of 600 MM X 600 MM X 3 MM PURE COPPER PLATE , 50 Nos.
MM DIA 3 MTR GI FUNNEL PIPE, 50 MM X MM COPPER
STRIP 6 MTR ], SALT [ 50 KG ],CHARCOAL [ 50 KG ], WITH
7.2 Earthing Conductor
PIND-2526-01670 BILL OF QUANTITY 18/12/2025
Supply, laying, connection and testing bare earthing
conductor for inter-connecting the earthing stations and
various equipment in built up trenches, walls/ceiling, buried
in ground generally as specified and shown on the drawing
complete with :
1) Supply & fixing accessories like earthing clamp, saddle, etc.
2) Supply of corrosion protection of buried conductors with
bitumi Nos.us coating
3) Supply of Test links (Copper/GI) etc.
7.2.1 10 Sq.mm Earthing Cable Mtr.
7.2.2 16 Sq.mm Earthing Cable Mtr.
7.3 Equipotential bar
Supply, installation, testing and commissioning of below
mentioned Equipotential bar with suitable size junction box
to inter connect different earthing conductor.
1) Supply and installation of Equipotential bar
2) Supply and installation of suitable size CRCA sheet junction
3) The bar shall be provided with min. six knockouts for
connecting the equipment to earthing station.
7.3.1 50 x 12 mm CU Equipotential bar of 500 mm length Nos.
7.4 ESE TYPE LIGHTING ARRESTER
7.4.1 ESE 45 MTR REDIUS TYPE LIGHTING ARRESTER SET
45 Meter Lightning Arrester(4.1) with non electronic ESE
(earthly steame Eremission) standardized accordng to
norms UNE 21.186 and NFC
17.102 duly tested and certified by CPRI Bangalore, having
coverage area 107 mtr. Level -1. Having Lightning charge
capacity 40 kA with 15 micro seconds delay. Mounting Pole
50 mm Diameter 3 mtr length insulated mounting pole
made of GI material to mount Ligthning Aresster. (Height as
level selection withnylon insulation for isolation Wind
120 kmph Mounting Base.
Mounting Base for counting and supporting mast
With Down Conductor 50 sq mm CABLE
PURE COPPER INSULATORE
ALL ACCESSORIES LIKE SADDELS & ANCHOR FASTNER NUT
EARTHING 50 MM DIA 3 MTR COPPER BONDED EARTHING
ELECTRODE INSTOLLATION As per noms proper instollation
8.1 SAFETY ACCESSORIES
8.1.1 Supply and installation of 440 V DANGER caution board in
Gujarati, Hindi & English made from vitreous enameled steel
and to be fixed on door/ shutter inside electrical room.
8.1.2 Supply and fixing of 4.5 Kg. Co2 type portable fire
extinguisher with necessary clamps, supports and trolley. No.
8.1.3 Supply of First Aid Box with necessary medicine. No.
8.1.4 Supply and fixing of First Aid Chart in glassed box with
laminated wooden frame mounted on wall.
PIND-2526-01670 BILL OF QUANTITY 18/12/2025
8.1.5 Supply and fixing of 6.0 Kg. abc type portable fire
extinguisher with necessary clamps, supports and trolley. No.
8.1.6 Supply and fixing For Safety Matt Rmtr
BOQ FOR PAC WORK
Unit Price Total Price
Sr. No Description Unit Total Qty
Supply, Installation, Testing and Commissioning of 3 TON
SRC Cooling Unit with Outdoor Unit.
Supply, Installation, Testing and Commissioning of
Standard Piping and Cabling.
Supply, Installation, Testing and Commissioning of
Fabrication stand
4 SITC of 1 tr split inverter ac With CU Piping and Stand Nos
BOQ FOR ELV WORK
Unit Price Total Price
Sr.No. Description of items Unit Qty
1 RODENT REPPELLANT SYSTEM
Supply, Installation, Testing and Commissioning of Master
Console without satellites for Rodent Repellent system
Supply, Installation, Testing and Commissioning of
1.02 Satellites to be installed with the Roden Repellant System at Nos
a minimum of 24 satellites per master console
Supply and surface laying of 2 core x 1 Sq.mm cable flexible
cable in 20mm dia PVC conduit
Supply of Laser based Absolute Smoke Detection system
with single pipe inlet, 250 m2 coverage; Wide sensitivity
range - 0.025%–20% obs/m; 4 alarm levels ; High
efficiency aspirator; Clean air barrier optics protection to
prevent contamination of detection chamber; Easy to
2.01 replace dual stage filter with memory; 3 Nos of inbuilt Nos
potential free relay outputs; supports linear pipe length of
25m or branched pipe up to 30m; supports 12 Nos of EN54
Class A sampling points, AutoLearn for automatic setup of
alarm threshold, Referencing & Event log (18000 events);
Approvals-UL, ULC, FM, ActivFire, VdS, CE , EN54-20.
Power supply unit with 110/230VAC input and 18 to 29VDC
Sampling Pipe - 25mm OD, 18 to 21mm ID smooth bore
PVC/UPVC/CVPC/ABS Plastc Pipe
Supply & installation of Capillary Set for False ceiling
2.05 Conventional hooter cum strobe Lot
2.06 2 core 1.5 Sqmm FRLS Cable for Power Supply Mtrs
2.07 Programmig , Testing & Commissioning Job
3 ADDRESSABLE FIRE DETECTION SYSTEM -
PIND-2526-01670 BILL OF QUANTITY 18/12/2025
SITC of UL, ULC listed and FM approved (UL 864 listed, 10th
Edition) 32-bit Microprocessor based Single loop Intelligent
Addressable, Peer-to-Peer networkable, expandable up to 4-
loop FACP (Fire Alarm Control Panel). FACP shall
accommodate up to 2 nos. of 12V/50AH batteries in its own
housing and shall have a battery charging capacity of (up
to) 2 nos. of 12V/100 AH housed externally. The cabinet
assembly shall be NEMA 1 rated and IP30. FACP shall have
80 ch. LCD display to show 2 simultaneous events at time
3.01 and at least 5 custom-programmable buttons for user- Nos
specific programmable functions. Each Detection Loop of
FACP shall accommodate up to 250 detectors and devices in
any combination (support of min. 200 detectors per loop).
FACP shall accommodate up to 1000 detectors and devices
at 100% capacity in any combination. FACP shall have a
supervised electronic provision to store site-related back-up
of Auto-CAD As-Built Drawings, Configuration Software Back-
Up, Reports, Logs etc. with Bacnet / MODBUS Module for 3rd
Party Integration
SITC of PC based Color Graphic User Interface Station to
provide Annunciation, Status display, Monitoring of each and
every element connected to Fire Alarm System and
Networks. It should support and have future provision for
mobile client iOS & Android (as applicable) to access system
information. It should support up to 5,00,000 events history
logs & 2,50,000 network points. The Centralized software
should be capable of monitoring up to 687 total Nodes with
100 Mbps Transmission rate on Fibre Optics Network and up
to 12 Mbps Transmission on Cu cable. The software should
be capable to offer multiple password access levels for
different users. It should work on Windows10, 64 bit OS
SITC of UL, ULC listed and FM approved Active Repeater
Panel with 80-Character (2x40) display with supervised
power supply from FACP. Repeater Panel shall monitor and
control (Scroll, Acknowledge, Reset & Mute) all the events of
the FACP to which it is connected and it shall have Port
Vectoring / Event Filtering capability of showing only
ALARMS, TROUBLES or SUPERVISORY or customized
combinations of user selected events.
SITC of UL, ULC listed and FM approved Intelligent
Addressable Multi-Sensor (Optical Smoke + Heat + RoR)
detector with base.
The optical sensor element shall have multiple selectable
sensitivity levels from 0.2% Obs/ft to 3.1% Obs/ft.
The ROR detection element shall have selectable rate of rise
setting of 8°C per minute & 11°C per minute (or close to
this value not deviating more than 1°C).
Fixed temp detection element shall have two selectable
3.04 settings of 57°C and 68°C (or closer to this value not Nos
deviating by 1°C). Multis-sensor detector shall have a
configuration mode that gives separate alarms for smoke
detection and heat detection and shall indicate the cause of
alarm (smoke or heat). Also the multi-sensor shall have
combined configuration mode of smoke and heat detection
that gives only one evaluated alarm from a multi-sensor
detector in case of a fire event. The detector shall have
operating temperature range from -9°C to 50°C and
humidity tolerance range up to 95% RH, Non-Condensing.
PIND-2526-01670 BILL OF QUANTITY 18/12/2025
SITC of UL, ULC listed and FM approved Intelligent
Addressable Double Action Indoor Application Manual Pull
Stations / Manual Call Points suitable for wall/column
mounting. MCP shall have red coloured housing with
molded, raised-letter operating instructions of contrast
colour. The MCP shall latch mechanically upon operation and
shall remain so until manually reset with its key by an
authorized operator. The MCP shall have operating
temperature range from 0°C to 50°C and humidity tolerance
range up to 93% RH, Non-Condensing.
SITC of UL, ULC listed and FM approved Addressable
Notification Devices (Hooter with Strobe). Hooter with
Strobe unit shall sit directly on addressable NAC
(Notification Appliance Circuit) of FACP, fully supervised and
powered from FACP. Hooter and Strobe elements of the
combined unit shall have independent activation &
deactivation criteria. Hooter shall stop at alarm
"Acknowledge" and the Strobe shall stop at panel "Reset".
The Hooter and Strobe element of Hooter cum Strobe
combined unit shall be selected and triggered independently
from FACP for performance check and maintenanace. Hooter
with Strobe unit shall have provision to be tested by a hand-
held field diagnostic tool in "Silent Mode" and "Full
Operation Sound Mode". The Strobe shall have multiple
selectable candela settings configured and selected from the
FACP. The hooter cum Strobe unit shall deliver ouput up to
94 db at 3m from its installed location. The sounder/strobe
unit shall display the voltage received by them at the control
panel. The activation & deactivation requirement of
Notification devices shall not be deviated.
Supply, Installation, Testing and commissioning of
Addressable UL and FM approved Control Module with
Feature of Polarity Incesentative and inbuilt fault isolator for
third party integration like AHU, Access control.
Supply, Installation, Testing and commissioning of
3.08 Addressable UL and FM approved Monitor Module with Nos
Feature of Polarity Incesentative and inbuilt fault isolator.
Supply, Installation, Testing and Commissioning of Junction
box for Detector, MCP and Sounder.
Supply, Installation, Testing and Commissioning of 2 core
3.10 1.5 Sq. MM CU PVC sheathed armoured cable in open Mtr
manner on wall through saddling.
Supply, Installation, Testing & Commissioning of 2 zone
Digital Voice Evacuation Master controller with built in
watt Amplifier. The System shall meet the standards of BS
EN54 - 32 & EN 60849. The System Shall have Built in 180W
Amplifier and it should be capable for the EVAC, Paging, PA
4.01 and BGM functions. The Controller shall have Speaker line NOS
supervision record out and amplifier auto changeover. The
Controller shall have following features: Separate Zone
volume control at the front side of panel, Status indications
on the Panel for EVAC,Fault ,AC,DC ,Fault, ALERT & Fireman
mic, Zone capacity up to 2 Zones,
Supplynstalling, testing and commissioning of 2 zone paging
microphone (call station) with necessary Zone wise, Group
Zones and all call facility. The Microphone should have LED
Indication, Can be Expand with additional units, Compress
function through microphone input to avoid distortion, NOS
Auxiliary input which supply local background music. Power
24V DC, Microphone should be able to Control the Music
also. Microphone Should supply with all accessaries and with
standard specification, complete.
PIND-2526-01670 BILL OF QUANTITY 18/12/2025
Supplying, installing, testing and commissioning of 6W
Recessed Ceiling speakers with following features:-Speaker
Drive 5", Complete metal grille and line matching
transformer 100/70V line. Variable wattage tapings of 6 / 3 NOS
/ 1.5 at 100v, Effective frequency range 90-18kHz
(BS6840), SPL@1m/1W=90dB, Peak SPL 98dB complete
with necessary mounting hardware & accessories.
Supply and laying of the 2C X 1 sq mm Speaker Wire With
5 ACCESS CONTROL SYSTEM
Supply, Installation, Testing and Commissioning of
Biometric Reader with standalone controller
Supply, Installation, Testing and Commissioning of EM Lock
Supply, Installation, Testing and Commissioning of Prox
Supply, Installation, Testing and Commissioning Resettable
Emergency release Boxetc.
Supply, Installation, Testing and Commissioning of Cat
cable in PVC MMS ISI conduit.
Supply, Installation, Testing and Commissioning of 10 Mtr
Water leak Detection Cable.
Supply, Installation, Testing and Commissioning of 20 Mtr
Water leak Detection Cable.
Supply, Installation, Testing and Commissioning of 8 Zone
water leak detection panel with battery backup.
Supply and Installation of Sounder cum Strobe for waterleak
Supply and surface laying of 2 core x 1 Sq.mm cable flexible
cable in 25mm dia PVC conduit
7 CCTV Survellance
Supply, Installation, Testing and Commissioning of 2 MP Fix
Supply, Installation, Testing and Commissioning of 2 MP Fix
Supply, Installation, Testing and Commissioning of 16 Ch
Network Video Recorder with 4 sata HDD.
Supply, Installation, Testing and Commissioning of 8 TB
Supply, Installation, Testing and Commissioning of 55" LED
Display for Monitoring
Supply, Installation, Testing and Commissioning of
Standard Workstation without Display for Monitoring.
Supply, Installation, Testing and Commissioning of 16 Port
Supply, Installation, Testing and Commissioning of Cat
cable in PVC conduit.
8 Building Monitoring System (iBMS)
Supply, Installation, Testing and Commissioning of BMS
8.01 Grafic Software with capacity 2000 point with Email Nos
Notification as per requirememnt.
Supply, Installation, Testing and Commissioning of
8.02 Standard Workstation for BMS with Standard Display for Nos
Supply, Installation, Testing and Commissioning of TCP IP
Base Controller with dual RS 485 port Control for Soft
integration enclosure and internal wiring as per
Supply, Installation, Testing and Commissioning of TCP IP
8.04 Base Controller with Hard IO controller Hard integration Nos
enclosure and internal wiring as per requirement.
Supply, Installation, Testing and Commissioning of Room
Mount Temperature and Humidity sensor with Display.
Supply, Installation, Testing and Commissioning of Third
Party Soft Integrator.
a Online UPS - 2 Qty
PIND-2526-01670 BILL OF QUANTITY 18/12/2025
b DG Set - 1 Qty
c Smart Cooling Unit ( SRC ) - 2 Qty
d Fire Detection System - 1 Qty
e Fire Suppression System - 1 Qty
f Waterleak Detection System - 1 Qty, RODENT - 1 Nos
g Electrical Panel - 1 Qty
Supply and surface laying of 4 core x 1 Sq.mm cable flexible
cable in 25mm dia PVC conduit
Supply and surface laying of 8 core x 1 Sq.mm cable flexible
cable in 25mm dia PVC conduit
Supply and surface laying of 2 core x 1 Sq.mm cable flexible
cable in 25mm dia PVC conduit
BOQ FOR SUPPRESSION SYSTEM WORK
Unit Price Total Price
Sr.No. Description of items Unit Qty
VDS APPROVED - SUPPRESSION SYSTEM - SERVER
Supply of PESO / CCOE Approved UL Listed FK5112
Seamless 80L Cylinder (Main) of below capacity from OEM
Factory filled with FK5112 Liquid of below capacity &
Pressurised to 25 BAR as per requirement with Valve
assembly, pressure guage, protection cap, container straps
etc. with complete required assembly.
1.02 Supply of FK5112 Fire Protection Fluid in Kg.(Factory Filled) Kgs
Supply, installation, testing & commissioning of Cylinder
1.03 Low Pressure Switch with required accessories. UL Listed / Nos.
Supply, installation, testing & commissioning of Discharge
1.04 Pressure Switch with required accessories. UL Listed / FM Nos.
Supply, installation, testing & commissioning of
1.05 Electrical(Solenoid) Actuator with required accessories. UL Nos.
Listed / FM approved
Supply, installation, testing & commissioning of Flexible
1.06 Cylinder Discharge Hose complete with all accessories, UL Nos.
Listed / FM approved
Supply, installation, testing & commissioning of Manual
Actuator with required accessories. UL Listed / FM approved
Supply, installation, testing & commissioning of Pneumatic
Actuator with required accessories. UL Listed / FM approved
Supply, installation, testing & commissioning of WARNING
PLATE-DO NOT ENTR
Supply, installation, testing & commissioning of WARNING
PLATE-VACATE AREA
Supply installation Testing & commissioning of Cylinder
mounting straps
Supply, installation, testing & commissioning of Nozzles,
1.12 Deg / 180 Deg Throw, selection as per approved hydraulic Nos.
flow calculations.
Supply, installation, testing & commissioning of MS
1.13 Seamless Pipes, Supports, with angles, painting to Indian Lot.
Supply installation Testing & commissioning of UL Listed
Single zone Gas Release Panel facility to connect Manual
Abort/Release switches. The Panel shall provide Potential
1.14 free contacts for Trouble / Fault Status. The Panel shall be Nos.
Complete with Red Colour Housing, Monitored Power supply
units for Notification devices & warning signages of the
system, including with Battery charger & batteries.
Supply installation Testing & commissioning of UL Listed
Manual Abort Stations with DPDT Relay, The Abort will be
monitored simultaneously by Fire Alarm and BMS System.
Complete with required mounting accessories.
PIND-2526-01670 BILL OF QUANTITY 18/12/2025
Supply installation Testing & commissioning of UL Listed
Manual Release Stations with DPDT Relay, The Release
switch will be monitored simultaneously by Fire Alarm and
BMS System. Complete with required mounting accessories.
Supply installation Testing & commissioning of Conventional
smoke detector with base.
Supply installation Testing & commissioning of Response
1.19 Supply installation Testing & commissioning of Hooter. Nos.
Supply installation Testing & commissioning of Hooter cum
Supply installation Testing & commissioning of Warning Sign
Board with Marking "GAS DISCHARGE. DO NOT ENTER".
Shall Operate on 24 V DC, Driven Through Gas Release
Panel. (for use outside room)
Supply installation Testing & commissioning of Warning Sign
Board with Marking "GAS DISCHARGE. EVACUATE
IMMEDIATELY". Shall Operate on 24 V DC, Driven Through
Gas Release Panel. (for use inside room)
Supply installation of ISI Marked 2 Core x 1.5 mm2,
Multistranded Annealed Tinned Copper, Shielded FRLS,
Armoured cable, RED in Colour. The cable shall be laid on
surface with hot dip GI Saddels and spacers every
meters. Complete with GI Junction Box, lugs, cable
compression glands, cable tags and Ferruling.
Towards Conducting Room Integrity Test : Door Fan test to
meet the Requirements of the NFPA 2001, and predicting
the efficacy of the Protected Area Enclosure from the
perspective of Fire Suppression.
Towards Hydraulic Flow Calculations for the Suppression
1.25 areas, and vetting of the Software Results from the OEM Nos.
Factory Engineer.
BOQ FOR NETWORKING, RACK, CCTV & ACCESS CONTROL
Unit Price Total Price
Nos SPECIFICATION Unit Qty
BILL OF QUANTITY FOR PASSIVE LAN CABLING AND
RACKS & INTELLEGENT PDU
A Multimode OM4 Fiber Connectivity
1 SITC of 12 core Multimode OM4 indoor fiber cable with LSZH
2 SITC of 19" 1U 48 LC Duplex Fiber panel fully loaded Nos
3 SITC of LC to LC duplex Multimode OM4 fiber patch cord of
4 SITC of Splicing fiber Cable Nos
5 SITC of Fiber Compass Box Nos
SITC of 48 Port 2 Nos SFP Network Mangable Switch L3 Nos
B Network and Server Racks
1 SITC of 42U Server Cabinet frame UL Listed with top panel (
800 X 1200 ) With All Accessories
2 SITC of 42U Network Cabinet frame UL Listed with top panel
(800X1200) With All Accessories
3 SITC of Intelligent PDU of 32 Amps Single Phase Vertical
1 Supply and Installation of 6 MP IR Fixed Dome Indoor
Network Camera with Audio and other Accessories, Night
Vision, Day/Night/Auto/Schedule, IP 67, IR range 30 Meter,
ONVIF protocol Compliant
D Access Control
1 Supply and Installation of Biometric Access Control of Door,
Matrix make, Model no: COSEC VEGA FAX, DOOR FOP
Fingerprint and RF Card Based Premium Door Controller with Nos
LCD & Keypad, Algatech EM Lock 600 Lbs for Single/Double
Door Exit Switch. Compitible with existing COSEC Software
PIND-2526-01670 BILL OF QUANTITY 18/12/2025
Unit Price Total Price
Nos SPECIFICATION Unit Qty
1.0 SITC of 20 KVA Online UPS With IGBT 3P IN & 3P Out Nos
2.0 Battery Pack for 20 KVA UPS With 30 Minut Battery Back Up Nos
3.0 Battery Rack & Link For 20 KVA UPS Nos
4.0 SITC of 6 KVA Online UPS With IGBT 1P IN & 1P Out Nos
5.0 Battery Pack for 6 KVA UPS With 30 Minut Battery Back Up Nos
6.0 Battery Rack & Link For 6 KVA UPS Nos
BOQ FOR STABILIZER
Unit Price Total Price
Nos SPECIFICATION Unit Qty
Providing, installation, testing, and commissioning of 60 KVA
1.0 oil-cooled servo voltage stabilizer having the following Nos
specifications:
Input Voltage Range: 320 VAC to 480 VAC
Output Voltage: 400 / 415 VAC (±1%)
Type: Oil-cooled, automatic, floor-mounted type
Protection: Equipped with MCCB having shunt trip coil
Accessories: Mandatory manual bypass switch and all
necessary connections, fittings, and accessories for
complete operation.
Providing, installation, testing, and commissioning of
KVA MCCB With Enclosed
BOQ FOR IT STORAGE
Unit Price Total Price
Nos SPECIFICATION Unit Qty
1.0 Primary Storage Infrastructure (60 TB Usable) Nos
2.0 Backup Storage Infrastructure (60 TB Usable) Nos
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
ABG Format.doc
DOC
PBG Format.doc
DOC
Bank Details_01.01.2021.pdf
Commercial Deviation Format.doc
DOC
Technical Deviation Format.doc
DOC
Letter of Undertaking - Ethics.doc
DOC
PIND-2526-01670-R1-BOQ.pdf
PIND-2526-01670-R1-Commercial Terms.pdf
PIND-2526-01670-R1-GCC-Data Centre.pdf
PIND-2526-01670-R1-PRICE BID.pdf
PIND-2526-01670-R1-Qualification Criteria.pdf
PIND-2526-01670-R1-Request For Quotation.pdf
PIND-2526-01670-R1-SCC-Data Centre.pdf
PIND-2526-01670-R1-Scope of work.pdf
PIND-2526-01670-R1-Specification of Material.pdf
PIND-2526-01670-R1-Training Doc.pdf
PIND-2526-01670-R1-Notice-Data Centre.pdf
Download all tender documents and submit your bid