Loading…
Loading…
Tender ID
| # | Company | Status |
|---|---|---|
| 1 | Accepted-Technical KOTHENALLOOR KAKKADA P O THIRUVANANTHAPURAM 695505 | THIRUVANANTHAPURAM | THIRUVANANTHAPURAM | KERALA | 695505 | Accepted-Technical Accepted |
| 2 | Accepted-Technical 1696 VICTORY BUILDING KADAMPAZHIPPURAM PALAKKAD 678633 | PALAKKAD | PALAKKAD | KERALA | 678633 | Accepted-Technical Accepted |
| 3 | Accepted-Technical 24 234 2 NEAR VYDHYUTHI BHAVAN KOTTAPPURAM ROAD PUNKUNNAM THRISSUR KERALA 680002 | THRISSUR | KERALA | 680002 | Accepted-Technical Accepted |
Tender Value
Refer Docs
EMD Value
₹50,000
Closing Date
20 May 2026, 6:55 pmClosed
MANAGING DIRECTOR
UNITED ELECTRICAL INDUSTRIES,REGD OFFICE,PALLIMUKK KOLLAM 691010
SITC OF 1 NOS OF 12M HIGH MAST LIGHTING SYSTEM AND 30 NOS OF 8 Mtr MINI MAST LIGHTING SYSTEM AT VARIOUS LOCATIONS OF KOVALAM LAC IN THIRUVANANTHAPURAM DISTRICT
2026_UNILE_837739_2
PMC/MARKETING/247/2025-2026
Open Tender
Electrical Works
Item Wise
45 days
KOVALAM
REFER TENDER DOCUMENTS
6 documents required · 6 mandatory
₹2,950
Yes
₹50,000
Yes
11 Jun 2026
5 Mar 2026
21 May 2026
5 Mar 2026
20 May 2026
5 Mar 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1Civil Works | |||||
| 1.01 | 2.6.1 : Earth work in excavation by mechanical means (Hydraulic excavator)/manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including disposal of excavated earth, lead up to 50 m and lift up to 1.5 m, disposed earth to be levelled and neatly dressed.All kinds of soil | 1 | cum | - | - |
| 1.02 | 4.1.8 : Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level:1:4:8 (1 cement : 4 coarse sand : 8 graded stone aggregate 40 nominal size) | - | cum | - | - |
| 1.03 | 5.22.6 : Steel reinforcement for R.C.C work including straightening, cutting, bending, placing in position and binding all complete upto plinth levelThermo - Mechanically Treated bars of grade Fe-500D or more | 0.6 | kilogram | - | - |
| 1.04 | 5.9.1 : Centering and shuttering including strutting, etc. and removal of form for:Foundations, footings, bases of columns, etc for mass concrete | - | sqm | - | - |
| 1.05 | 5.1.3 Providing and laying in position specified grade of reinforced cement concrete,
excluding the cost of centering, shuttering, finishing and reinforcement - All work up
to plinth level:1:1:5:3 (1 cement 1.5 coarse sand :3 graded stone aggregate 20 mm
nominal size derived from natural sources) | - | cum | - | - |
| 1.06 | 2.25 : Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20 cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift up to 1.5 m.Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundation etc. in layers not exceeding 20 cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift up to 1.5 m. | 1 | cum | - | - |
| 2Electrical Works | |||||
| 2.01 | OD22458/2025-2026
Supply, installation, testing and commissioning of Outdoor Floor / Wall Mounting
Cubical Type KSEBL Metering Panel with Double Door and Canopy suitable for 415
V, Three Phase, 4 Wire 50 Hz AC supply system having sufficient front surface area
fabricated in compartmentalized design from CRCA sheet steel of 2 mm thick for
frame works and covers, 2 mm thick for gland plates, cleaning and finishing complete
with 7 tank process for Powder Coating in approved shade and then provided with
Clear Coating, fabrication shall be done in transportable sections, entire panel shall
have a common copper earth bar of size 12 mm x 3 mm at the rear with 2 Nos. earth
stud and control wiring with 2.5 / 1.5 Sq.mm FRLS (Flame Retardant Low Smoke) or
HRFR (Heat Resistant Flame Retardant) PVC insulated single core copper conductor
cables, cable alleys etc. complete as required. The panel shall conform to the Electrical
Inspectorate and KSEBL standards and it shall only be manufactured after getting
approval from the Engineer-in-charge and the Consultant.
INCOMER
1 Nos - Provision for Fixing Single Phase Energy Meter
3 Nos - 63A Bakelite Fuse Units with HRC Fuse of Suitable Rating
1 Nos - 63A Neutral Link
1 Nos - 40A/63A 10kA 4P C Curve MCB
There shall be Separate Compartment for Energy Meter and Fuse Units/Neutral Link
with KSEBL Sealing Provision
SURGE PROTECTION DEVICE
1 Nos - 4 Module DIN Rail Mounting Type 1 + Type 2 / Class 1 + Class II 100kA
SPD on the Incoming / Outgoing Side of Incomer MCB along with Green and Red
Indication Lamps with Control MCBs [The connections to RYB Phases, Neutral and
Earth shall be done using 16 Sq.mm FRLS (Flame Retardant Low Smoke) or HRFR
(Heat Resistant Flame Retardant) PVC insulated single core copper conductor cables
with less than 0.45m in length]
OUTGOING 1
1 Nos - 16A/25A 10kA 4P C Curve MCB with 25A 100mA 4P RCB
OUTGOING 2
1 Nos - Outdoor / Street Light Compartment with 6A/10A 10kA DP C Curve MCB,
25A 30mA DP RCCB, 9A/12A 3P AC3 Duty Contactor with Auxiliary Contacts,
24Hour Digital Timer Switch, Auto - Manual Selector Switch (2 Pole 2 Way), ON
(Red), OFF (Green) Push Buttons and ON (Red), OFF (Red) Indication lamps with
Control MCBs | - | each | - | - |
| 2.02 | Supply, installation, testing and commissioning of Outdoor Floor / Wall Mounting
Cubical Type KSEBL Metering Panel with Double Door and Canopy suitable for 240
V, Single Phase, 2 Wire 50 Hz AC supply system having sufficient front surface area
fabricated in compartmentalized design from CRCA sheet steel of 2 mm thick for
frame works and covers, 2 mm thick for gland plates, cleaning and finishing complete
with 7 tank process for Powder Coating in approved shade and then provided with
Clear Coating, fabrication shall be done in transportable sections, entire panel shall
have a common copper earth bar of size 12 mm x 3 mm at the rear with 2 Nos. earth
stud and control wiring with 2.5 / 1.5 Sq.mm FRLS (Flame Retardant Low Smoke) or
HRFR (Heat Resistant Flame Retardant) PVC insulated single core copper conductor
cables, cable alleys etc. complete as required. The panel shall conform to the Electrical
Inspectorate and KSEBL standards and it shall only be manufactured after getting
approval from the Engineer-in-charge and the Consultant.
INCOMER
1 Nos - Provision for Fixing Single Phase Energy Meter
1 Nos - 32A Bakelite Fuse Units with HRC Fuse of Suitable Rating
1 Nos - 32A Neutral Link
1 Nos - 16A/25A 10kA DP C Curve MCB
There shall be Separate Compartment for Energy Meter and Fuse Units/Neutral Link
with KSEBL Sealing Provision
SURGE PROTECTION DEVICE
1 Nos - 2 Module DIN Rail Mounting Type 1 + Type 2 / Class 1 + Class II 50kA SPD
on the Incoming / Outgoing Side of Incomer MCB along with Green and Red
Indication Lamps with Control MCBs [The connections to Phase, Neutral and Earth
shall be done using 16 Sq.mm FRLS (Flame Retardant Low Smoke) or HRFR (Heat
Resistant Flame Retardant) PVC insulated single core copper conductor cables with
less than 0.45m in length]
OUTGOING
1 Nos - Outdoor / Street Light Compartment with 6A/10A 10kA DP C Curve MCB,
25A 30mA DP RCCB, 9A/12A TP AC3 Duty Contactor with Auxiliary Contacts,
24Hour Digital Timer Switch, Auto - Manual Selector Switch (2 Pole 2 Way), ON
(Red), OFF (Green) Push Buttons and ON (Red), OFF (Red) Indication lamps with
Control MCBs | - | each | - | - |
stage.html
html • 0.02 MB
tech_bid_open.pdf
tech_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.28 MB
GC.pdf
Tender Documents • 0.56 MB
BOQ_1425254.xls
BOQ • 0.32 MB
Crri247.pdf
PDF • 0.75 MB
extension.pdf
PDF • 0.15 MB
Crri247.pdf
PDF • 0.75 MB
Crri247.pdf
PDF • 0.75 MB
CORREGENDUM.pdf
PDF • 0.52 MB
Corri247.pdf
PDF • 0.66 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .