EXECUTIVE ENGINEER RNB ELECTRIC DIVISION KASHMIR
RNB ELECTRIC DIVISION KASHMIR ENGINEERING COMPLEX
Construction of Tree House at Aharbal B.W.O Electric work
2025_PWDJK_298243_1
NIT No.221/2025-26 Dt/15/12/2025
Open Tender
Electrical Works
Percentage
Aharbal
Please refer Tender documents.
4 documents required · 4 mandatory
₹200
EXECUTIVE ENGINEER RNB ELECTRIC DIVISION KASHMIR
₹4,205
15 Dec 2025
15 Dec 2025
23 Dec 2025
15 Dec 2025
22 Dec 2025
15 Dec 2025
Wiring for lighting points/fan points/exhaust fan points/call bell points with 2x1.5 sq mm FRLS PVC insulated flexible stranded copper conductor wires in recessed or surface medium class PVC conduit, with 240V 6A modular switch ,modular plate, suitable GI box and earthing the point with 1.5 sq mm FRLS PVC insulated copper conductor single core cable, etc. as required. (Havells/ Polycab/ Anchor/ SSK/KEI/RR or equivalent make ) excluding the cost of conduit.
Supply, Installation, Testing and Commissioning of 15-18W/+ or as directed by EIC LED recessed/mounted (round or square) Down lighters having aluminum body, minimum 100lm/w, average life 50000 hours, Operating temperature -10°C to +45°C.Certification:- LM79 & LM80 test report should be from govt approved In-house NABL lab/ government of India.The job includes replacement warranty of fixture if damaged/ burnt out what so ever reason for a period of two years reckoned from the date of successful commissioning/ handing over of site to the intending department. (Havells/ Philips/ Crompton/ Jaguar/Wipro/ eq. make to be approved by EIC
Supply, Installation, Testing and Commissioning of 50W (Havells/ PhillIps/Wipro skyline/ eq. make to be approved by EIC ) new generation energy saving and environmental friendly long life L.E.D Flood Light made up of pressure die cast Aluminum housing with high efficiency LEDs as lighting source with efficacy >110lm/w ,CRI>80 ,CCT>5000 ,Avg Life L70 50000 hours ,No haremful UV and IR radiators, Operating Temp -10 to 45C ,Surge Voltage Protection, IP66 Protection and impact resistance of IK07.The job includes replacement warranty of fixture if damaged/ burnt out what so ever reason for a period of two years reckoned from the date of successful commissioning/ handing over of site to the intending department.
Supply, installation, testing and commissioning of 1200 mm sweep ceiling fans 5 Star BEE Rated BLDC Remote Controlled,,30W,3 no.of blades , 340-410 rpm,AC 230V 50Hz, high Quality Copper Motor with double ball bearing incl. 1N Downrod,Shackle Assembly, cost of ceiling rose (if required) and making of necessary connections.The job includes replacement warranty of fixture if damaged/burn out what so ever reason for a period of two years reckoned from the date of sucessful commissioning / handing over of site to the intending department.(To be got approved before installation from EIC).Crompton Energion Hyperjet/ V Guard Windle Deco / Havells Artemis/ eq. make to be approved by EIC
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch connections etc. as required.( Anchor roma plus/Legrand Mylinc /SSK/Schneider Zencelo /Crabtree athena / eq. make to be approved by EIC).
Supplying and fixing of GI box along with modular base and cover plate for modular sockets, switches in recess etc as required 6 module (200mm x 75mm)
Supplying and fixing of 5pin 5-10A socket and 5-10A switch on existing modular plate, incl connections etc as required. (Havells/SSK/Anchor/ABB/Schneider/ eq. make to be approved by EIC)
Wiring for light/power plug points (15/16A heating points) with 2x4 sq mm FRLS PVC insulated flexible stranded copper conductor wires in recessed or surface medium class PVC conduit along with 1x4 sq. mm FRLS PVC insulated copper conductor single core cable for earthing, etc. as required.(Havells/ Polycab/ Anchor/ SSK/KEI/RR / eq. make to be approved by EIC ) excluding the cost of conduit.
Wiring for 5-10A socket out lets for computer with 2X2.5 sq. mm FRLS PVC insulated copper conductor (Havells/ Polycab/ Anchor/ SSK/KEI/RR or equivalent make ) as directed by engineer incharge.) single core cable in surface/recessed medium class PVC conduit, alongwith 1 No. 2.5 sq. mm FRLS PVC insulated copper conductor single core cable for earthing etc. as required excluding the cost of conduit.
Supplying and fixing of indicators on existing modular plate and switch box , incl. connections, etc. as required. (Havells/ SSK/ Anchor/ ABB/Schneider or equivalent).
Supply and fixing of 8 way (4+24), Double door surface/ recess mounting, Horizontal type, 240 V, SP&N MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs, excluding cost of MCBs and Incomer. (Havells/Legrand/SSK/Schnider/ABB/ eq. make to be approved by EIC)
Supply, installation, testing and commissloning of 5-32A single pole rating 240/415V,10 KA "C" curve MCB of Legrand/ Havells/ L&T/ABB suitable for inductive load in the MCB distribution board complete with necessary connections.
Supply, installation, testing and commissioning of 32A DP rating 240/415V,10 KA "C" curve MCB of Legrand/ Havells/L&T/ABB / eq. make to be approved by EICsuitable for inductive load in the MCB distribution board complete with necessary connections.
Supply, installation, testing and commissioning of 40A DP rating 240/415V,10 KA "C" curve MCB of Legrand/ Havells/ L&T/ABB / eq. make to be approved by EICsuitable for inductive load in the MCB distribution board complete with necessary connections.
Supply, installation, testing and commissioning of 63A DP rating 240/415V,10 KA "C" curve MCB of Legrand/ Havells/ L&T/ABB/ eq. make to be approved by EIC suitable for inductive load in the MCB distribution board complete with necessary connections.
Main Panel
Design, Fabrication, Supplying, Installation, Testing and Commissioning of following panel, duly manufactured from CPRI approved manufacturer, made out of 2mm thick M.S. sheet steel , floor/wall mounted, vermin and dust proof, indoor type with suitable size of angle iron legs for grouting in the ground, with lockable type hinged doors, duly painted with provision for fixing of following switch gears, , Aluminium Bus Bar of various ratings after taking Derating factor into account, and other allied accessories etc. as required. (As per approved design,size may vary as per site requirement)
Providing and fixing of following protection equipments and other allied accessories including connections, inter connections, with suitable size of PVC insulated copper conductor cable including earthing etc. as required.
1. Normal INCOMING:
a)125A DP MCB 10 KA Havells/Legrand/ Schinider/ABB/L&T/ eq. make. sample to be approved before installation..
b) 4 No. of Aluminium Bus Bar of 300 Amp.
c)Digital meters and phase indicators -1 set.
3.INVERTER
a) 32A DP MCB 10KA
b) 2 No. of Aluminium Bus Bar of 63 Amp.
c) Digital meter and phase indicators 01 set.
Wiring for Circuit/Sub mains along with earth wire in FRLS PVC insulated 660/1100 volt grade flexible stranded copper conductor wires in recessed or surface conduiting system, excluding the cost of conduit. (Havells/ Polycab/ Finolex/ Anchor/KEI/RR or equivalent).
2x10 sq mm +1x6 sq mm Heating submain
2x 6 sq mm + 1x 6 sq mm Inverter Lighting submain
2x 4 sq mm + 1x 4 sq mm Lighting submain
2x 2.5 sq mm + 1x 2.5 sq mm Lighting circuit
Supplying and fixing of 25-32mm wide medium class PVC Casing Capping (channel) ( Anchor/ Ravindra/ Eq. make) along with accessories complete job.
Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.Complete Job.
Providing and laying earth connection from earth electrode with 8 mm dia copper wire in 15 mm dia G.l. pipe from earth electrode including connection with copper thimble excavation and re-filling as required.
Supply, laying, connecting and commissioning of 25 sq mm 2 core XLPE/ PVC Insulated and steel armored 1.1 KV grade Aluminum LT cable for Service line, incl. cost of required al. thimbles duly crimped. (Over head/ under ground).
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 2.04 MB
BOQ_966702.xls
BOQ • 0.27 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .