| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹20.2 LAccepted-AOC | L1 | Accepted-AOC L1 | |
| 2 | L2₹22.3 L+₹1.4 L (6.64%)Rejected-Finance | L2 | Rejected-Finance L2 | |
| 3 | L3₹24.0 L+₹3.1 L (14.7%)Rejected-Finance 9 SHUBHASH BHAWAN RAJENDAR MARG MOUNT ABU 307 501 | MOUNT ABU | SIROHI | RAJASTHAN | 307501 | L3 | Rejected-Finance L3 | |
| 4 | L4₹24.5 L+₹3.6 L (17.1%)Rejected-Finance 190 B VIJAY BHAWAN SUBHASH CHOWK RATANADA JODHPUR RAJ 342001 | JODHPUR | RAJASTHAN | 342001 | L4 | Rejected-Finance L4 | |
| 5 | L5₹27.0 L+₹6.1 L (29.1%)Rejected-Finance | L5 | Rejected-Finance L5 |
Tender Value
₹26 L
EMD Value
₹52,000
Closing Date
19 May 2020, 6:00 pmClosed
GE (AF) NO 2 JODHPUR
GE (AF) NO 2 JODHPUR
REPAIR AND MAINT OF EXTERNAL ELECTRIFICATION, STREET LIGHT, E/M INSTALLATIONS, E/M EQUIPMENTS AND DAY TO DAY MAINTENANCE AT AF STN MOUNT ABU AND GURUSHIKHAR UNDER AGE E/M, GE (AF) NO 2 JODHPUR
2020_MES_340123_1
8137/E8
Open Tender
Civil Works
Item Rate
180 days
GE (AF) NO 2 JODHPUR
AS PER TENDER DOCUMENTS.
6 documents required · 6 mandatory
₹500
Yes
GE (AF) NO 2 JODHPUR
₹52,000
Yes
16 Jun 2020
22 Apr 2020
21 May 2020
22 Apr 2020
19 May 2020
6 May 2020
Amount
Excavation in trenches n.exc 1.5 Mtr wide and n.exc 1.5 Mtr in depth in soft/loose soil and getting out complete all as directed.
Returning, filling in trenches including spreading, levelling, watering and well ramming in layers n.exc 25cm complete all as directed.
Removal of excavated material to a distance n.exc 50 mtr and depositing where directed at a level n.exc 1.5 m above the starting point complete all as specified and as directed.
M&L sand cushioning / filling for underground cable protection, filling under floors ,consolidated and compacted with clean dry sand complete all as specified and as directed.
Supply & Laying burnt brick sub class 'B' laid dry abutting each other for cable protection size 230mmx 100mmx 70mm complete all as specified & directed.
Taking out defective LTUG cable XLPE/PVC sheathed 1100 volt grade heavy duty armoured with aluminium conductor from trenches, shifting serviceable cable 4 core 16 sqmm for relaying or taking the unserviceable cable as credit complete all as specified and directed for the following:- Note: Excavation and earth work shall be measured and paid for separately.
All as per itme No 7 above but 3.5 core 25 Sqmm
All as per itme No 7 above but 3.5 core 35 Sqmm
All as per itme No 7 above but 3.5 core 50 Sqmm
All as per itme No 7 above but 3.5 core 95 Sqmm
All as per itme No 7 above but 2 core 10 Sqmm
All as per itme No 7 above but 2 core 6 Sqmm
Taking out defective HTUG cable XLPE insulate, Screened PVC bedded galvanised steel strip or wire armoured, electric power cable with aluminium conductor, 11000 volt grade crossenctional area 95 sqmm 3 core laid in trenches/ duct/pipe including all electrical connection with required lugs and nuts, bolts complete all as specified and directed by Engr -in-charge.
Supplying, Laying, Jointing and testing of under ground cable XLPE insulated, 1100 volt grade heavy duty armoured with stranded aluminium conductor 4 core 16 sqmm laid in trenches/ duct/ pipe including all electrical connection with required lugs and nuts, bolts complete all as specified and directed by Engr-in-Charge.
All as per itme No 9 above but 3.5 core 25 Sqmm
All as per itme No 9 above but 3.5 core 35 Sqmm
All as per itme No 9 above but 3.5 core 50 Sqmm
All as per itme No 9 above but 3.5 core 95 Sqmm
All as per itme No 9 above but 2 core 10 Sqmm
All as per itme No 9 above but 2 core 6 Sqmm
Supply, laying & testing of cable XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) with stranded aluminium conductor, 11000 (E)volts, grade cross sectional area 95 sq mm 3 core including taking down old unserviceable cable complete all as specified and as directed.
Taking out of existing LT UG cable of any size after joining using LT cable joining kit provided in item No 9 complete all as specified and directed.
S&F LT Cable joining kit straight through heat shrinkable type complete with joining materials suitable for LT Armoured cables of size upto10- 25 Sqmm 2/3.5/4 core all as directed.
S&F LT Cable joining kit straight through heat shrinkable type complete with joining materials suitable for LT Armoured cables of size 35-70 Sqmm 3.5 core all as directed.
S&F LT Cable joining kit straight through heat shrinkable type complete with joining materials suitable for LT Armoured cables of size 95 Sqmm 3.5 core all as directed.
S&F LT Cable joining kit straight through heat shrinkable type complete with joining materials suitable for LT Armoured cables of size 185-240 Sqmm 3.5 core all as directed.
Supply & jointing cable jointing kit for 11 KV (Earthed) grade cable for straight through cold shrinkable type joint complete with jointing material & accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95Sqmm including taking out old unserviceable jointing kit complete all as specified and as directed.
Supply & jointing cable jointing kit for 11 KV (Earthed) grade cable for indoor termination cold shrinkable type joint complete with jointing material & accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95Sqmm including taking out old unserviceable jointing kit complete all as specified and as directed.
Supply & jointing cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination cold shrinkable type joint complete with jointing material & accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95Sqmm including taking out old unserviceable jointing kit complete all as specified and as directed.
M&L for detecting of fault in 11KV (E) HT Cable 3 core of any size laid in trenches/ducts with the help of elecronic fault locating machine comprising of surge generator pulse, echo fault locator with high frequency distance calculator etc, exposing the cable fault, removal of deteriorated portion of cable, treating the cable including making it ready for jointing work complete all as specified and as directed by Eng- in Charge. Note: (i) The quoted rate shall deemed to include for the cost of excavation, earthwork as required. (ii) Cable & jointing kit if replaced shall be measured and paid separately under relevant items in the Schedule.
M/L for boring of road crossing of size 100mm dia by sing trenchless technology with use of machinery equipment complete without damaging the surface at suitable depth for drawing cables/ pipe lines etc.
Dismantling and taking out the stay assembly complete incl demolition of plain cement.
M/L for stay assemble complete with accessories as shown in electrical plate No 1 incl GI adjustable stay Rod of 16mm Dia, GI Stay wire of size 7/4 mm incl stay clamps, loop type insulator excavation in any strata with PCC 1:3:6 & Concrete all as specified and directed incl taking down old unserviceable stay assembly.
Dismantling and taking down air break gang operated switches vertical/ horizontal mounted including insulators and operating mechanism/ replacement of old serviceable air break switches of 400/200 Amps.
Supplying and fixing installing commissioning and testing HT 11 KV, 3 Phase system, outdoor type gang operated switch, air break type suitable for vertical mounting complete with necessary insulators and separators, set of drop out fuses (12 insulators) and operating handle of GI pipe 25 mm dia, medium grade rod of suitable length (Mechanically operating arrangement) locking arrangement with lock and two keys complete or rating 400 Amp including painting with EPOXY paint over handle of GOD upto 2 feet from handle complete including taking down defective/ unserviceable GOD all as specified and directed MakeL JAIPURIA/ PACTIL
All as per Ser No 24 above but Horizontally operated w/o dropout fuses (9 insulator)
Supply and fixing drop out fuse assembly complete set with insulator 6 Nos and connected accessories for 11000 V grade with suitable size of drop out fuses incl taking down old unsv.
M& L for preparation of old steel surfaces and applying one coat of superior quality aluminium paint on LT steel tubular with single light bracket complete all as specified & directed.
M&L for lighting arrestor expulsion type transmission class 65 Kilo Amps 11000V Grade incl connecting and taking down old unsv and removing from site as directed by Engr-in-Charge.
M&L for lighting arrestor LT outdoor Non-Linear type with Arcing Horns 1100V grade incl connecting and taking down old UNSV and removing from site as directed by Engr-in-Charge.
Supply and fix in repairs GI Strip 32 x 6 mm burried in ground/ laid in floor/ fixed to wll on saddles/ on porcelain insulators etc as directed.
Material and labour for earthing complete with galvanized steel earth plate electrode 60cmx60cmx6mm thick, buried directly in ground, vertically to a depth not less than 2.25 mtr deep below ground level with top edge of the earth plate at depth not lss than 1.5 mtr below ground level earth plate surrounded by 15 cm thick and packed layers of charcoal, dust and common salt, earth lead GI strip 32 x 6mm by means of bolts, nuts, check-nuts and washers of galvanised iron and thimbles and of earth wire protected by galvanised iron pipe light grade 40mm bore and water pipe 20mm bore GI medium grade with funnel and wire mesh complete 1:3:6 type C-1 using 20mm graded stone aggregate in lieu of CI cover and frame etc all as specified and shown in electrical plate No 3 of SSR- 2009 (Part-1)
Supply and fixing MCCB in replacement of 63 Amps, 4 pole, 415 volts, 50 HZ, rupturing capacity 16KA, connection with proper size of thimbles complete including taking out defective/ unserviceable MCCB all as specified and directed.
All as per item No 31 above but 100 Amps, 16 KA
Supply and fix MCCB in replacement with thermal magnetic release adjustable type DU 160, 125A, 16KA, 415 Volts 4 pole all as specified & directed.
Supply and fix MCCB in replacement with thermal magnetic release adjustable type DU 160, 160A, 36KA, 415 Volts 4 pole all as specified & directed.
All as per item No 33 above but 200 Amps, 36 KA
Supply and fix MCCB in replacement with thermal magnetic release adjustable type DN2-250D, 250A, 415 Volts 4 pole 36KA all as specified & directed.
Supply and fix MCCB in replacement with thermal magnetic release adjustable type DN3-400D, 400A, 415 Volts 4 pole 36KA all as specified & directed.
S & F Change over main switch, on load, four poles, 250 Amps, 415 Volts, 36 KA ,50 Hz, with enclosure, fixed in the existing LT panel board/ sheet metal enclosure including connecting up incoming/ out going cables with suitable lugs and testing complete all as specified and as directed.
M & L in repair incl taking down old GI tubing Light grade 80mm incl all accessories for protection cable complete all as specified and directed in engr-in-charge
All as per item No 38 above but 50mm
All as per item No 38 above but 40mm
S & F in repair GI Bracket for mounting street light fittings made out of light grade 32mm GI pipe and have angle of 120 degree incl fixing arrangement complete all as specified and as directed by engr-in-charge.
Dismantling of damaged PCC Pole of size 9 mtr long disposal all as specified and as directed.
M&L steel tubular swaged pole complete with cast iron base plate , finial taper plug , bolts , nuts & screws as specified type 410 SP-22 (8.5 mtrs long ) .
Taking down the unserviceable and defective street / security lights / flood light fittings MH/CFL/HPMV/HPSV/ Halogen lamp of any type, make, and wattage from the pole /wall along with the pole fixing attachments complete after replacement or defective /unserviceable spare parts / accessories including connecting up and testing for satisfactory functioning and complete all as specified and as directed.
Supply and fix pressure die cast aluminium housing with heat resistant toughened glass and IP66 protection LED Street light luminaire 60 Watts Capacity including connected accessories complete all as directed by Engr-in -Charge Make : Bajaj, or equivalent in Philips /CG
Supply and fix pressure die cast aluminium housing with heat resistant toughened glass and IP66 protection LED Street light luminaire 72 Watts Capacity including connected accessories complete all as directed by Engr-in -Charge Make : Bajaj, or equivalent in Philips /CG
Supply and fix pressure die cast aluminium housing with heat resistant toughened glass and IP66 protection LED Street light luminaire 90 Watts Capacity including connected accessories complete all as directed by Engr-in -Charge Make : Bajaj, or equivalent in Philips /CG
Supply and fix pressure die cast aluminium housing with heat resistant toughened glass and IP66 protection LED Street light luminaire 100 Watts Capacity including connected accessories complete all as directed by Engr-in -Charge Make : Bajaj, or equivalent in Philips /CG
Supply and fix pressure die cast aluminium housing with heat resistant toughened glass and IP66 protection LED Street light luminaire 150 Watts Capacity including connected accessories complete all as directed by Engr-in -Charge Make : Bajaj, or equivalent in Philips /CG
Supply and fix single core PVC insulated FR cable with multi stranded copper conductor 1.5 sq mm cross sectional area ,1100 volts grade all as specified and as directed.
Supply and laying cable PVC insulated armoured and PVC sheathed with multi stranded aluminium conductor of size 10 sq mm 2 core and connecting to the street light feeder.
Disconnecting the voltage stabilizer by taking out oil and storing for reuse after cleaning and removing moisture from it taking all the assembly of voltage stabilizer and removing / repairing the unserviceable parts, reassembling it after repair testing and commissioning the voltage stabilizer of capacity 250 KVA balanced type .Note-Replacement of UNSV spares shall be included as follows.
Replacement of sensing card low and high including connecting wire.
Replacing carbon bushes (set of three) Make as per sample
Replacement of servo/voltage synchronising motor 240 Volt, 50 HZ Make as per sample
Rewinding of dimmer stat complete with super enamelled copper winding wire including insulating material and labour for winding for voltage stabilizer of capacity 250KVA.
Push buttons (as per sample).
Voltmeter (0-500) square shape as per sample Make : AE.
Ammeter (0-100) / (0-200) square shape as per sample Make : AE.
Toggle switch Make (as per sample).
Material and labour for connecting and testing complete including copper wire of required as per sample with complete accessories.
Checking of VCB 11 KV cap 1200 Amps Make- ABB and servicing/maintenance through authorised dealer for rectification of fault, connecting and testing on load all as directed by Engr-in-charge. Note: Replacement of unserviceable spares shall be included as follows:-
Supply and fixing of Vacuum Interrupter as per existing make and model complete
Supply and fixing of spring charging motor assy as per existing make and model complete
Supply and fixing of limit switch as per existing make and model complete
Supply and fixing of trip coil as per existing make and model complete
Supply and fixing of close coil as per existing make and model complete
Checking and repairing of heater/blower circuit wiring incl replacement of defective wire, coil, thermostat, sensor etc for VCB one incoming and two outgoing.
Checking of ACB 1100 Volt cap 800 Amps model NH800 and servicing/maintenance through authorised dealer for rectification of fault, connecting and testing on load all as directed by Engr-in-charge. Note: Replacement of unserviceable spares shall be included as follows:-
Supply and fixing of manual charging handle assy as per existing make and model complete
Supply and fixing of trip coil as per existing make and model complete
Supply and fixing of close coil as per existing make and model complete
M/L for Repairs to out door LT panel including taking down for repair as follows :-
Supply and fixing of MS sheet 16 SWG( 1.6 mm ) and fabrication of back side cover of LT panel including cutting to required size and shape fixing in position by bending, welding all as required for proper functioning of LT panel shutters including two coats of coats of synthetic enamel paint over a coat of red oxide.
Supply and fixing of hinges , tee type stove enamelled black medium weight , cold rolled and mild steel 30 mm size and fixed door shutters .
Supply and fixing of locking arrangement with MS sliding door bolts hasp and suitable for use with pad lock of size 200 mm.
Mild steel work conforming to Fe-410-0 or Fe-310-0 as in angle iron frame work , cut to size including bending and welding angles as necessary and re -fixing of MS sheet of panel including a shop coat of red oxide primer.
Comprehensive maintenance servicing and testing of APFC panel of capacity 90 KVAr -120 KVAr including checking of Phase cap capacitors in all capacitor banks ,all MCCB's ,duty contactors, st relay and all connected wiring including refitting of all as directed by Engr-in- charge.. Note :- (a) Spares required for replacement shall be included in item rate.
taking out unserviceable capacitors from the site of any/size complete
S&F phase cap capacitor of capacity 5 KVAr in APFC panel complete all as directed by Engr-In-Charge
S&F phase cap capacitor of capacity 10 KVAr in APFC panel complete all as directed by Engr-In-Charge
S&F phase cap capacitor of capacity 12.5 KVAr in APFC panel complete all as directed by Engr-In-Charge
S&F phase cap capacitor of capacity 15 KVAr in APFC panel complete all as directed by Engr-In-Charge
S&F power factor controller ST relay ,230 Volt suitable for 120 KVAr APFC panel in APFC panel complete all as directed by Engr-In-Charge
Supply and fixing of copper thimbles using crimping tool for electrical connections with cable and connecting with suitable size of nuts / bolts and washers of size 240 to 500 sqmm LT cable size.
All as per the description of item No 10 here in before but of size 120 to 185 Sqmm.
All as per the description of item No 10 here in before but of size 50 to 95 Sqmm.
Maintenance and servicing of following mentioned Diesel Generator Sets including connected Alternator, Panel Board (AMF/ Non AMF) Note :- (i) Control switches such as MCCB, Main switch, contactors, multi display meter and engine control unit shall be out of scope of the item of work and the rate quoted shall exclusive of servicing/ maintenance of the above said fittings (ii) Servicing of DG Set along with connected Alternator and Panel Board as directed by the Engineer-in-charge and the Contractor shall carry out periodical inspections during the maintenance period and he shall be responsible for the smooth functioning of the DG set service and shall also attend all the maintenance works as and when required in that period except in case of Major repairs. (iii) Spare parts required for replacement during the maintenance period shall be measured and paid separately at supply only rates and cost of labour for fixing these spares shall be deemed to be included in the rate quoted for this item. (iv) Cost of all consumables required during the maintenance shall be deemed to be included in the rate quoted for this item.
125 KVA DG set
75 KVA DG set
63.5 KVA DG set
15 KVA DG set
Supply only Lead acid battery, 12 volt, 180 AH Make :- Exide/ Amco
Supply only Engine oil SAE 20W-40W Make :- VOLVOLINE/ IOC/HP
Supply and filling radiator coolant Make : VOLVOLINE/ IOC/HP
Supply only fan belt as per existing make for the following capacities of DG sets.
125 KVA/75 KVA
Supply only Air filter element , Fuel Filter and oil filter as per existing make for the following capacities of DG sets.
S & F control coil of AMF Panel of DG Set capacity of 125/75/63.5/15KVA that the exting make and model and voltage complete all as specified
S & F Temperature Gauge of DG Set capacity of 125/75/63.5/15KVA that the exting make and model and any description complete all as specified
Dismantling of the existing Unsv self starter assy by removing the all nut bolts and disconnecting from DG Set , opening of self starter , replace the worn out armature , bearing , carbon brushes, field coil etc reconnecting testing and commissioning of 24 V complete all as specified and as directed by engr-in-charge
Dismantling of the existing defective charging dynomo 24V removing the all nut bolts and disconnecting from DG Set , cleaning agent and overhauling lubricating the same , replacing the armature field coil reconnecting testing the same , refixing back , in original position testing and commissioning complete all as specified and as directed by engr-in-charge
Removing of the existing defective Alternator of capacity 24 , and disconnecting from DG Set , , cleaning agent and overhauling lubricating the same , replacing the armature field coil reconnecting testing the same , refixing back , in original position testing and commissioning complete all as specified and as directed by engr-in-charge
M & L for painting of exhaust pipe of DG sets with heat resistant paint of approved quality including preparation of surfaces of exhaust pipe complete all as specified and as directed.
Disconnecting the transformer by taking out transformer oil for comprehensive maintenance of all parts including winding and terminals , replacement of rubber gasket sheet ,silica gel, cleaning and removing moisture from it taking all the assembly of transformer and removing / repairing the unserviceable parts, reassembling it after repair testing and commissioning the transformer of capacity 100 KVA to 400 KVA stepdown type complete all specified and directed. Note. Rewinding of transformer complete with super enamelled copper winding wire including insulating material and labour for winding of transformer of capacity 250KVA to 400 KVA included in item rate.
Dehydration and filtration of the transformer oil with the help of oil filtration plant of any capacity of distribution transformer indoor/outdoor type 11/0.433 KV of capacity 100 to 400 KVA complete all as specified and as directed.
Supply & filling transformer oil of superior quality conforming to IS 335:93 complete all as specified and as directed by Engineer-in-Charge. Make: POWEROIL/CASTROL/ SAVITA
Supply and fixing in replacement LT bushing assembly complete with insulator, brass stud rod, nuts, washers, gasket etc complete with accessories suitable for 100 KVA to 400 KVA transformer indoor/outdoor 11KV/ 433V including taking out old LT bushing assembly complete all as specified and directed.
All as per Ser No 80 above but HT bushing
Supply and fixing in replacement oil drain valve cast copper ally and dia suitable for upto 400 KVA transformer indoor/outdoor 11KV/ 433V of existing make including taking out old drained valve complete allas specified and directed
M & L fixing in replacement breather assembly complete set suitable for upto 400 KVA transformer indoor/outdoor 11KV/ 433V of existing make complete all as specified and directed
Supply and replacement silica gel complete all as specified and directed.
M & L in replacement temperature gauge suitable for upto 400 KVA transformer indoor/outdoor 11KV /433V including taking down old temperature gauge complete all as specified and as directed by engr -in-charge
Taking down copper/aluminium point wiring for (light, fan, bell, socket power socket etc )complete including fixture and fittings such as switches, sockets lamp holder bracket light fittings tube light fittings, regulators, ceiling rose , mirror light fitting , ceiling light fitting, fancy light fitting , fall ceiling light fitting bell/ buzzer and removing materials to store for keeping in safe custody or for taking credit ( credit for above items should be made as per condition separately) and making good disturbed surfaces of wall floor etc.
Taking down old U/S distribution boards complete and removing materials to store for keeping in safe custody or for taking credit .
M&L Point wiring complete with 1.5 Sqmm single core multi standard copper conductor PVC FLRS insulated unsheathed cable in and incl PVC casing capping with accessories existing pressed steel terminal boxes (sunk in wall) including new 3.00 mm thick plastic laminated sheet top cover with 1.50 Sqmm insulated unsheathed PVC covered copper conductor for common earth and connecting to earth dolly for :-
One light point controlled by one one way switch
One fan point controlled by one one way switch
One bell point controlled by one bell push switch
One socket out let 5 Amps on the same board
One socket out 3 pin 5 Amps on the independent board.
All as per item No 87 above but with 2.5 Sq mm single core multi standard copper conductor cable for 6 pin 15 Amps socket out let on independent board.
S&F switch flush type 5 Amp, 240 V single pole one way ISI Marked.
S&F switch socket combination 2 in 1,5 Amps flush type
S&F switch socket combination 3 pin 16 Amps flush type
S&F ceiling rose, 3 Terminal Point/PVC/polycarbonate, isolated body.
S&F lamp holder , PVC /Polycarbonate type with back plate suitable for batten fitting complete with necessary wire connection etc.
M&L for sheet metal enclosures distribution board where MCB to be used with 200 Amps rated bus bar CL-IP-43 240 V, 8 way single pole & neutral link
All as per itme No 91 above but 12 way 240 V, Make :Standerd or eqlt
All as per item No 91 above but 4 way 240 V,
Taking down old u/s MCB's complete of any size& make
M&L in replacement for MCB single pole 6 Amps, 240 V .
M&L in replacement for MCB single pole 10 Amps, 240 V .
M&L in replacement for MCB single pole 16Amps, 240 V .
M&L in replacement for MCB single pole and neutral 20 Amps, 240 V.
M&L in replacement for MCB single pole & neutral 40 Amps, 240 V .
M&L in replacement for MCB triple pole & neutral 63 Amps, 240 V
Taking down of old u/s LED fitting complete of any type
S&F in repair LED batten (1.2 m) made of CRCA sheet housing with a PC glossy diffuser and mounting accessories duly prewired connection having a nominal system lumen output of 2000 lumens at a minimum system efficacy of 105 lumens per watt and total power consumption not more than 19 watt including driver. It has a rated system life time of 40000 burning hours at L70 and should have a color temperature of 6500K, CRI>80, THD < 10% and PF > 0.95 complete. Make - Crompton Cat No DMLN1LT8-16 & LTT8-20 or equivalent in Philips/Wipro.
S&F in repair LED Stud Bulk Head 10 watt fixture perfect interior and exterier application within car parks, walkway, stairwells, carridoors, local authorities and housing accosiation as well as commercial building including connection all as per cat ref no. LBHP-10-CDL complete all as specified and directed by Engineer in Charge. Make -Philips or equivalent CG/ Havells
S&F in repair Building Security LED 36 Watt fixture made of pressure die cast housing with toughened glass and high power LEDs with option of secondary optic with IP65 protection ,commercial building including connection all as per cat ref no. LSTS-36-CDL-M complete all as specified and directed by Engineer in Charge. Make -Philips or equivalent CG/ Havells .
Taking out od old u/s elect door bell of any type & make
S/F elect bell AC 230 V single pole ISI Marked.
S/F elect bell ding dong AC 230 V single pole ISI Marked.
Taking down existing sub main wiring in casing capping/conduit pipe of any size complete.
S&F sub main wiring with 2 run of 4 Sq mm single core copper conductor cable drawn through in rigid PVC conduit ISI marked with fitting and 4.0 Sq mm single core copper conductor cable for continues earth wire all as directed
S&F sub main wiring with 2 run of 6 Sq mm single core copper conductor cable drawn through in rigid PVC conduit ISI marked with fitting and 6.0 Sq mm single core copper conductor cable for continues earth wire all as directed.
Taking out existing earthing complete at site.
M&L for earthing complete with galvanized steel earth plate electrode 60 cm x 60 cm 6.0mm thick, buried directly in ground (earth pith not less than 2.25 mtr deep below ground level) with top edge of plated not less than 1.5 mtr below normal ground level connected toincl galvanized iron or steel earth lead wire 4.0mm dia by mean of bolts nuts check nuts & washers of galvanized iron or steel pipe 15mm dia medium grade and connected to main switch board watering pipe shall be 20mm dia GI medium grade incl excavation earth work in any type of soil pit RCC cover complete.
Taking down old u/s mirror light fitting complete
S&F mirror light fitting LED of 10 Watt 2 feet long complete 230V, 6000k rated CCT energy efficient with automatic ballast pen holders stsrters blocks ,diffusers complete with all accessories including tube internally prewired and including connecting with twin core twisted flexible copper cable complete all as specified and as directed.Make -orient model no-LBLN-10-C /bajaj/crompton
Taking down old /ruptured fan regulator complete
Supply and fixing fan electronic regulator 300w step type all as specified and as directed by Engr-in-Charge.
Taking down old /ruptured casing/capping complete
S&F Casing/capping complete all as specified and directed
Choudhary Traders and Engineers
Haritwal traders
M/S Balkishan Panwar Construction
vinayandsons
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .