Loading…
India Infra Updates on WhatsApp
Join the Tenderkart WhatsApp channel for India Infra Updates
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹52.5 LAccepted-AOC ERNAKULAM 682025 | ERNAKULAM | ERNAKULAM | KERALA | 682025 | 1 | Accepted-AOC L1 |
| Sl No | Description | Qty | Unit | INFRA ELEVATORS INDIA PVT LTD L1 |
|---|---|---|---|---|
| 1.00SITC OF LIFT | ||||
| 1.00 | OD17887/2023-2024:Supply, installation,testing and commissioning of 20 person bed cum passenger Lift with
the following specification including all required standard features.1 .Type of Lift: 20 person bed cum passenger ,
Gearless (With Machine room type ) 2. Load / Persons :1360Kg. / 20persons 3 .Rated speed :1M/Sec. 4.
Travel :15 Mtr ( Approx) 5. No. of floor and entrance served :Basement + 4 Floor, 5stops and 5openings 6. No. of floor
served :Five floors 7. Method of control : Micro processor based V3F with ARD system. 8. Location of
machine room: above lift well 9. Size of lift well : 2150 mm x3000mm, 10. Car entrance: As per IS
11. .Leveling accuracy : As per IS 12. Car door opening : As per IS 13. Drive : Variable voltage variable
frequency(V3F) 14 .Operation : Simplex full selective collective control with ON/OFF switch 15.
Construction of design and furnishing of car body work:Vandal proof Stainless
steel(SS304,make:Tata/Jindal) finish cabinet with Scratch proof Stainless steel door(sheet 1mm minimum
thickness), Stainless steel mirror finish ceiling, Aluminium 3mm minimum thickness anti skid flooring, fan
with timer cut-off, push to talk, LED display, LED light, hand rails and floor announcement system. All
buttons in car and all landings should have Braille sign. 16. Landing entrance : Automatic
centre/Telescopic opening Vandal proof stainless steel sliding door as per ISS with provision for
mechanical opening key for emergency with full length infra red light curtains and half framed glass door 17. Call and position indicators : Up/down direction & position Dot Matrix
LED indication shall be provided at all landings 18. Electric supply : 1) Light 230/50C/s single phase 2 wire
system. 2) 415V 50C/s 3 phase 4 wire system. 19. Infra red door opening system: To be provide for
entire length of the door 20. Automatic Rescue Device :Provide automatic rescue device with an
electronic controller powered by maintenance free batteries with capacity for minimum four rescue
operation . The rescue operation should act within 10 seconds of power failure 21. Regulation :350V-
450V (SMPS based) 22. Indication in the car : a) Car position b) Call indicator c) Door close/open push
button d) Emergency stop button e) Flush mounted switch for fan and light f) Non stop button g) Battery
operated emergency lamp with rechargeable batteries. h) Battery operated alarm bell i) Intercom wiring
with one master unit with two slaves j) Fireman's switch at main lobby i) Auto attendant control (inside
the car) 23. Winding handle Manual winding handle for use in emergency. 24. Safeties a) Over speed
governor, operated safety gear b) Buffers c) Motor over load protection d) Phase reversal protection e)
Other safeties as per ISS f) Single phase preventer g) Final limit switch 25. Leveling Automatic leveling at
all landing as per IS 26. Guarantee: Company shall carry out free maintenance during warranty period of
36 months which also includes a) Cleaning lift equipment b) Lubrication of all moving parts c) Replacing
of lubricating oil when required d) Checking and adjusting contacts e) Replacing fusible item alarm etc. f)
Recharging batteries in case of drain/ renewing batteries g ) Replacing /rewinding of all defective parts
of the lift including motors and V3F unit. 27. Control panel :Control panel will be dust and vermin proof
of sheet metal enclosure 28. Announcement System: To provide lift announcement system 29. Tests :At
site test as per IS to be carried out and approval from Electrical Inspectorate before Handing over. 30.
Scope of work:- a) Supply of lift materials b)Minor civil works such as removal of temporary brick work in
the lift entrance without affecting the building structure, finishing/ altering civil works in lift entrance/
pit by providing brick work & plastering if necessary including minor civil works such as construction of
buffer block in the pit machine foundation in the machine room, cutting pockets and grounding brackets
for the guide rails, grouting boxes for control units, correction of wall opening in the front side of the
wall by additional brick work or cutting existing brick work including core cutting of machine room and
water proofing in lift pit c) Scaffolding d) Door frames e) Supporting steel f) Temporary electric supply
for installation of lift. Electric supply for testing and commissioning of lift is to be arranged by the firm on
their own account. g) Intercom facilities with one master and two slaves h) Battery operated alarm i)
Obtaining Scheme approval as well as energization Certificate from the electrical Inspectorate including
preparation of necessary drawing for the same. Necessary fee shall remitted to the Inspectorate by the
firm for which no refund will be made from the department including taking insurance for one year as
per new lift rule. j) Supply of book let with complete details of maintenance schedule and control
diagram. k) Giving training to department staff for attending trouble shooting | 1 | each | 24,98,000 ₹24,98,000 Lowest |
| 1.00 | OD39402/2023-2024:Supply, Installation,Testing and Commissioning of 26 person Bed cum passenger Lift machine room type gearless with
the following specification including all required standard features.1 .Type of Lift: 26 person bed cum Passenger ,
Gearless (With Machine room type ) 2. Load / Persons :1768Kg. / 26persons 3 .Rated speed :1M/Sec. 4.
Travel :8 Mtr ( Approx) 5. No. of floor and entrance served: basement + 2 Floor: 3 stops and 3openings 6. No. of floor
served :Three floors 7. Method of control : Micro processor based V3F with ARD system. 8. Location of
machine room: above lift well 9. Size of lift well : 2500 mm x2800mm, 10. Car entrance: As per IS
11. .Leveling accuracy : As per IS 12. Car door opening : As per IS 13. Drive : Variable voltage variable
frequency(V3F) 14 .Operation : Simplex full selective collective control with ON/OFF switch 15.
Construction of design and furnishing of car body work:Vandal proof Stainless
steel(SS304,make:Tata/Jindal) finish cabinet with Scratch proof Stainless steel door(sheet 1mm
minimum thickness), Stainless steel mirror finish ceiling, Aluminium 3mm minimum thickness anti skid flooring, fan
with timer cut-off, push to talk, LED display, LED light, hand rails and floor announcement system. All
buttons in car and all landings should have Braille sign. 16. Landing entrance : Automatic
centre/Telescopic opening Vandal proof stainless steel sliding door as per ISS with provision for
mechanical opening key for emergency with full length infra red light curtains and half framed glass door 17. Call and position indicators : Up/down direction & position Dot Matrix
LED indication shall be provided at all landings 18. Electric supply : 1) Light 230/50C/s single phase 2 wire
system. 2) 415V 50C/s 3 phase 4 wire system. 19. Infra red door opening system: To be provide for
entire length of the door 20. Automatic Rescue Device :Provide automatic rescue device with an
electronic controller powered by maintenance free batteries with capacity for minimum four rescue
operation . The rescue operation should act within 10 seconds of power failure 21. Regulation :350V-
450V (SMPS based) 22. Indication in the car : a) Car position b) Call indicator c) Door close/open push
button d) Emergency stop button e) Flush mounted switch for fan and light f) Non stop button g) Battery
operated emergency lamp with rechargeable batteries. h) Battery operated alarm bell i) Intercom wiring
with one master unit with two slaves j) Fireman's switch at main lobby i) Auto attendant control (inside
the car) 23. Winding handle Manual winding handle for use in emergency. 24. Safeties a) Over speed
governor, operated safety gear b) Buffers c) Motor over load protection d) Phase reversal protection e)
Other safeties as per ISS f) Single phase preventer g) Final limit switch 25. Leveling Automatic leveling at
all landing as per IS 26. Guarantee: Company shall carry out free maintenance during warranty period of
36 months which also includes a) Cleaning lift equipment b) Lubrication of all moving parts c) Replacing
of lubricating oil when required d) Checking and adjusting contacts e) Replacing fusible item alarm etc. f)
Recharging batteries in case of drain/ renewing batteries g ) Replacing /rewinding of all defective parts
of the lift including motors and V3F unit. 27. Control panel :Control panel will be dust and vermin proof
of sheet metal enclosure 28. Announcement System: To provide lift announcement system 29. Tests :At
site test as per IS to be carried out and approval from Electrical Inspectorate before Handing over. 30.
Scope of work:- a) Supply of lift materials b)Minor civil works such as removal of temporary brick work in
the lift entrance without affecting the building structure, finishing/ altering civil works in lift entrance/
pit by providing brick work & plastering if necessary including minor civil works such as construction of
buffer block in the pit machine foundation in the machine room, cutting pockets and grounding brackets
for the guide rails, grouting boxes for control units, correction of wall opening in the front side of the
wall by additional brick work or cutting existing brick work including core cutting of machine room and
water proofing in lift pit c) Scaffolding d) Door frames e) Supporting steel f) Temporary electric supply
for installation of lift. Electric supply for testing and commissioning of lift is to be arranged by the firm on
their own account. g) Intercom facilities with one master and two slaves h) Battery operated alarm i)
Obtaining Scheme approval as well as energization Certificate from the electrical Inspectorate including
preparation of necessary drawing for the same. Necessary fee shall remitted to the Inspectorate by the
firm for which no refund will be made from the department including taking insurance for one year as
per new lift rule. j) Supply of book let with complete details of maintenance schedule and control
diagram. k) Giving training to department staff for attending trouble shooting | 1 | each | 27,47,000 ₹27,47,000 Lowest |
Tender Value
₹54.8 L
EMD Value
₹50,000
Closing Date
21 Mar 2024, 6:55 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Chief Electrical Engineer
office of the CEE PWD Electrical wing public office, Thiruvananthapuram
GENERAL Health and Family welfareDepartment Implementation of Annul Plan Scheme for 2021 22 Ensuring Disabled andElderly Friendly Environment in MCH Manjeri Providing Passenger Lifts in Hospital Electrical Lift Work
2024_PWD_664566_2
PWD/BLDG/TR/6800/2023_15_1_1/1
Open Tender
Electrical Works
Item Rate
120 days
Thiruvananthapuram
Please refer Tender documents.
6 documents required · 6 mandatory
₹2,760
₹50,000
Yes
12 Dec 2025
14 Mar 2024
23 Mar 2024
14 Mar 2024
21 Mar 2024
14 Mar 2024
14 Mar 2024 - 21 Mar 2024
Amount
SITC OF LIFT
Bidder Name
INFRA ELEVATORS INDIA PVT LTD
stage.html
html • 0.03 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_1042567.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .