Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | LI₹36.7 LAccepted-AOC | LI | Accepted-AOC Found Lowest bidder | |
| 2 | L2₹38.0 LRejected-Finance VILLAGE BHARAPUR P O DHAULAKUAN TEHSIL PAONTA SAHIB DISTRICT SIRMOUR H P | L2 | Rejected-Finance Not Found Lowest Bidder | |
| 3 | L3₹38.6 LRejected-Finance SET NO 75 TYPE III BROACK HURST CHHOTA SHIMLA TEHSIL DISTRICT SHIMLA HP 171002 | SHIMLA | HIMACHAL PRADESH | 171002 | L3 | Rejected-Finance Not Found Lowest Bidder | |
| 4 | L4₹38.8 LRejected-Finance | L4 | Rejected-Finance Not Found Lowest Bidder | |
| 5 | L5₹39.4 LRejected-Finance | L5 | Rejected-Finance Not Found Lowest Bidder |
Tender Value
₹34.1 L
EMD Value
₹59,000
Closing Date
19 Aug 2019, 11:00 amClosed
Executive Engineer
Irrigation and Public Health Division Paonta Sahib
Replacement of A.C. Pressure Pipe with MSERW Pipe of 300mm dia Rising Main
2019_HPIPH_30696_1
5118-5217 datd 26.07.2019
Open Tender
Civil Works
Item Rate
180 days
Parduni
Please refer to tender documents
6 documents required · 6 mandatory
₹400
Executive Engineer, IPH Division, Paonta Sahib.
₹59,000
Yes
1 Jan 2020
6 Aug 2019
19 Aug 2019
6 Aug 2019
19 Aug 2019
6 Aug 2019
6 Aug 2019 - 19 Aug 2019
Amount
Excavation in drains and channels etc. in earth work for pipes upto all depths in all classification of earth work such as pick work jumper work saturated soil including bailing or pumping out water , blasting soft/hard rock or chiseling soft /hard rock where blasting is prohibited in all lifts including jungle clearance whereever required trimming & dressing of sides levelling of beds to correct graded including shoring/struting ,planking timbering & dewatering whereever required stacking the useable/unuseable material /soil separately & after laying jointing & testing of pipes returning the useable soil in trenches in 15 cm. layers including consolidating of such deposited layer by ramming & watering & then disposing of all surplus excavated soil/unuseable material as directed within all leads,lifts including restoration of unmetalled surfaces to its original condition & including cost of diversion for traffic ,night signals ,fixing caution boards crossing over trenches for success to houses ,fencing etc. complete in all respectsd within all leads,lifts as per direction of Engineer-in-charge.
Prov. Laying , jointing ,Testing & commissioning at site in trenches belevelled ended MSERW Pipes of grade A confirming to IS/ISO 3183-2007 ,having wall thickness & per Rmt.weight as mentioned below & capable of withstanding required test pressure as prescribed in BIS code, in random lengths of 5.5 to 6.5 Mtr. The pipes ends shall bevelled suitable for Butt welding ,including the cost of jointing with butt welding confirming to IS 816-1969 or latest as applicable ends with upto date ammendments(leak proof) in three layers at site of work with welding rods of standard make & all allied accessories whatever required for werlding at site, tail pieces, tees, bends & other specials manufactured from parent pipes as applicable to the particular reach & of approved specification as per site conditions and cutting of pipes whereever required as per site requirement including carriage in all leads,lifts and as directed by the Engineer-in-charge.The pipes shall 's have zinc coating in side and out side confirming to IS 4736-1986 or latest with upto date ammendments and shall be engaved with Grade A . The laying shall confirm to BIS 5822-1970 or latest with upto date ammendments to the entire satisfaction o the Engineer-in-charge.(Earth work shall be measured & paid seperately)
From To Diameter Thickness Wt.(kg./m) Length Pipe specification.
0 1170 300mm 4.40mm 34.67 1170 Grade "A"
Dismentalling of old MSERW Pipe 400mm dia outer dia 406.40mm MSERW pipe of grade YST--210 confirming to IS 1978-1982 and 4.80 mm dia thickness & weight 47.54 Kg./Mtr. Plain flanges of table No.5 confirming to IS 6392-1971 along with nuts and bolts of 1.5 Hindustan Ferrdo Ltd. Bombay confirming to IS 2712/Q bends of required degree (or any thickness) make out of parent pipe of the same dia painting with anti corrosive bitumen paint complete in all respect and as per direction of the Engineer-in-charge.
Dismentaling of existing AC pressure pipe of 400mm dia class-10 & CAD Join complete in all respect and as per direction of the Engineer-in-charge.
Progviding and fixing M.S plate flanges of 300 mm dia(Nominal bore) of following Flange Tables confirming to IS 6392-1971 or latest with upto date ammendments to MSERW pipes after every 90 metres or as per site requirehment including cutting of pipes wherever required welding in three layers (leak proof) confirming to specifications as prescribed in relevent IS code i.e.IS 816-1969 or latest as applicable with upto date ammendments with nuts bolts & washers & special etc confirming to IS -1963 or latest with upto date amhmendments including packing sheet i.e asbestos fibre sheet minimum 3mm thick and painting with anticorosive paints complete in all respect in all leads,lifts and carriage of material at site and as directed by the Engineer-in-charge.
Sr No RD's Nominal dia Length(In Mtrs) Flange Table From To
RAMNIK THAKUR
GAURAV SHARMA
Shamshad Ali Contractor
M/S Sharma Enterpirses
MAHOKAM SINGH
DINESH KUMAR GUPTA
M/S Apurva Construction
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .