Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹48.1 LAdmitted-Finance | L1 | Admitted-Finance | |
| 2 | L2₹49.5 L+₹1.4 L (2.95%)Admitted-Finance | L2 | Admitted-Finance | |
| 3 | L3₹54.7 L+₹6.6 L (13.7%)Admitted-Finance | L3 | Admitted-Finance | |
| 4 | L4₹57.0 L+₹8.9 L (18.6%)Admitted-Finance D NO 3 9 560 P 17 E ROAD NO 4 SRI BALAJI NAGAR MANSOORABAD HYDERABAD 500068 | HYDERABAD | MEDCHAL MALKAJGIRI | TELANGANA | 500068 | L4 | Admitted-Finance | |
| 5 | Rejected-Technical | - | Rejected-Technical Enlistment Not uploaded. |
| Sl No | Description | Qty | Unit | J.V.V.K.PRABHAKARARAO L4 | asmath enterprises L3 | Onkar Electricals L1 | M/S SRIDEVI ENTERPRISES L2 |
|---|---|---|---|---|---|---|---|
| 1.00 | Supply, install, commissioning & testing of Motor Control Panel "out-door type" of size 900 mm (height) x 900 mm (breadth) x 500 mm (depth) (minimum dimensions) factory fabricated CPRI approved (type-tested) with suitable neoprene rubber gasket to make it completely dust & vermin proof & degree of protection not less than IP-55 & general construction confirming to IS-13947, double door, front & back openable. The panel shall be provided with ventilation facility in the form of louvers for better heat dissipation & tinned copper bus-bar wrapped with coloured PVC tape/sleeves of rating in conformity to the Incoming MCCB/MCB rating. The panel board shall be fabricated out of 3.15 mm thick (for outer portions) & 2.0 mm thick (for inner portions) CRCA sheet duly pre-treated & powder coated, supporting angle iron frame & MC channel base suitable for 3 Ph, 4 wire system 415/440 volts grade incl complete internal wiring with not less than 2.5 sqmm copper wire incl cable glands of suitable sizes incl suitable PCC (1:3:6) type C-2 foundation , necessary earthwork (if any) incl taking down old unsv one complete all as specified & as directed & to the entire satisfaction of the Engr-In-Charge with & incl the following accessories : [ For Watch Tower Borewells ] | 16 | Each Job | 1,21,000 ₹19,36,000 | 1,15,000 ₹18,40,000 | 35,000 ₹5,60,000 | 30,499 ₹4,87,984 Lowest |
| 1.01BUS-BAR & INTERNAL CONNECTIONS : The bus-bars shall be made up of 04 Nos high grade Aluminium 100 A rated, duly insulated with 1100 V grade standard colour coded PVC sleeves & rigidly mounted on suitable sized "F" class insulators of non-hygroscopic, non-combustible, all internal connections from main bus-bars to switch gears etc. PROVISION FOR CABLE ENTRY : The provision for cable entry/exit shall be provided in the bottom for both incoming & out-going cables with the help of glands matching the existing LT cable sizes. INCOMING : (a) MCCB 4P (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting,suitable for isolation, having breaking capacity 25 KA & of rating 20 to 32 A - 01 Nos. Make : Cat No : DZ0F0020-32CXC1AOOOO of Make L&T or techno-commercially equivalent of LEGRAND/SIEMENS. OUTGOINGS : (a) MCB, SPN, 10KA, 230V, "C" curve, 06-32 A, ISI marked - 03 Nos (2W + 1S). Make : LEGRAND/ABB/SIEMENS (b) Single Phase DOL Starter perfectly suitable for Submersible Pumping Set of capacity upto 2 HP, conforming to IS/IEC : 60947-4-1, IP-54, with & incl Extended wide band coil, FRLS Copper Internal Wiring, Starter Type - Air Break, Class-H Insulation with Contactor Rating - 12A, Overload Relay Range - 2.8A to 4.2A incl testing complete. Make : SIEMENS/L&T/HAVELLS/BCH - 02 Nos (1W + 1S) INSTRUMENTATION SYSTEM : (a) Digital type Multi-Function meter with built in selector Switch & 03 Nos CTs matching with the I/C breaker, Accuracy Class - 1.0, 3 phase, Size 96 x 96 mm. Make : Cat No WL411010OOOO of make L&T or techno-commercially equivalent of ELMEASURE/SECURE. (b) Indicator lamp with integral circuit (230/240V) & cluster LED (Red, Orange, Blue) - 01 Set. (c) Danger notice plate of size 20 x 15 cm of 1.6mm thick mild-steel sheet, vitreous enamelled white, with letters, figures and conventioinal skul and bones in signal-red colour and fixed with MS clamps, bolts and nuts of approved size, for LT conforming to IS-2551 - 02 Nos (Front & Back). | |||||||
| 2.00 | Supply, install, commissioning & testing of Motor Control Panel "out-door type" of size 1200 mm (height) x 1000 mm (breadth) x 600 mm (depth) (minimum dimensions) factory fabricated CPRI approved (type-tested) with suitable neoprene rubber gasket to make it completely dust & vermin proof & degree of protection not less than IP-55 & general construction confirming to IS-13947, double door, front & back openable. The panel shall be provided with ventilation facility in the form of louvers for better heat dissipation & tinned copper bus-bar wrapped with coloured PVC tape/sleeves of rating in conformity to the Incoming MCCB/MCB rating. The panel board shall be fabricated out of 3.15 mm thick (for outer portions) & 2.0 mm thick (for inner portions) CRCA sheet duly pre-treated & powder coated, supporting angle iron frame & MC channel base suitable for 3 Ph, 4 wire system 415/440 volts grade incl complete internal wiring with not less than 2.5 sqmm copper wire incl cable glands of suitable sizes incl suitable PCC (1:3:6) type C-2 foundation , necessary earthwork (if any) incl taking down old unsv one complete all as specified & as directed & to the entire satisfaction of the Engr-In-Charge with & incl the following accessories : [ For Other Borewells ] | 6 | Each Job | 1,31,000 ₹7,86,000 | 1,31,000 ₹7,86,000 | 55,000 ₹3,30,000 Lowest | 1,52,999 ₹9,17,994 |
| 2.01BUS-BAR & INTERNAL CONNECTIONS : The bus-bars shall be made up of 04 Nos high grade Aluminium 100 A rated, duly insulated with 1100 V grade standard colour coded PVC sleeves & rigidly mounted on suitable sized "F" class insulators of non-hygroscopic, non-combustible, all internal connections from main bus-bars to switch gears etc. PROVISION FOR CABLE ENTRY : The provision for cable entry/exit shall be provided in the bottom for both incoming & out-going cables with the help of glands matching the existing LT cable sizes. INCOMING : (a) MCCB 4P (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting,suitable for isolation, having breaking capacity 25 KA & of rating 40 to 50 A - 02 Nos. Make : Cat No : DZ0F0050CXC1AOOOO of Make L&T or techno-commercially equivalent of LEGRAND/SIEMENS. (b) Compact Enclosed ATS (Automatic Transfer Switch) suitable for inside panel mounting & I-O-II operation, 4 Pole, 63 A, confirming to IEC 60947-6-1 - 01 No complete with following features/specifications : (i) Double-Break Contact System offering High Short-time Withstand. (ii) Ample Space for Cable Termination. (iii) Ease of Generator Control (ON-OFF, Cooling Cycle Self-Test). (iv) Cyclic Event Logger. (v) Priority Source Selection. (vi) Adjustable Time Delay (0.1 Sec to 3 Hrs). (vii) Suitable for 3-Phase as well as 1-Phase sources. (viii) Protections - UV/OV, Phase Sequence, Single Phasing, Frequency. (ix) Terminal Shrouds, Phase Barriers & Source Separator etc. Cat No : 1SYN151254R1001 of make ABB or techno-commercially equivalent of L&T/Siemens. | |||||||
| 2.02OUTGOINGS : (a) MCB, TPN, 10KA, 415V, "C" curve, 40-63 A, ISI marked - 03 Nos (2W + 1S). Make : LEGRAND/ABB/SIEMENS (b) Three Phase Fully Automatic Starter perfectly suitable for Submersible Pumping Set of capacity upto 15 HP, conforming to IS/IEC : 60947-4-1, IP-54, with & incl Single Phasing Protection (SPP) with Auto Manual Switch, FRLS Copper Internal Wiring, Combined V / A Meter, Voltmer Selector Switch, ON / OFF Indication, Star-Delta Timer etc., Class-H Insulation with Contactor Rating AC3 (A) - 20A, Overload Relay Range - 13.2A to 20A incl testing complete. Make : SIEMENS/L&T/HAVELLS/BCH - 02 Nos (1W + 1S) INSTRUMENTATION SYSTEM : (a) Digital type Multi-Function meter with built in selector Switch & 03 Nos CTs matching with the I/C breaker, Accuracy Class - 1.0, 3 phase, Size 96 x 96 mm. Make : Cat No WL411010OOOO of make L&T or techno-commercially equivalent of ELMEASURE/SECURE. (b) Indicator lamp with integral circuit (230/240V) & cluster LED (Red, Orange, Blue) - 01 Set. (c) Danger notice plate of size 20 x 15 cm of 1.6mm thick mild-steel sheet, vitreous enamelled white, with letters, figures and conventioinal skul and bones in signal-red colour and fixed with MS clamps, bolts and nuts of approved size, for LT conforming to IS-2551 - 02 Nos (Front & Back). NOTE: 1) Design / drawing / BOM of the Panel Board incl all accessories showing the dimensions is to be obtained from the Manufacturer / Supplier & is to be got approved from the Engr-In-Charge & GE before placing final order to the manufacturer. 2) Anything missed out in the technical specifications but technically required for efficient working is deemed to be included in the quoted rates. 3) The electrical connection of digital Multi Functional Meter in the MCC panel is to be done from load side so that monitoring of various parameters viz. Voltage, Current, KW, KVA, power factor, frequency etc. can be done for both SEB mains & DG mains. 4) Necessary PCC foundation/plinth shall be as per the recommendations of OEM / Supplier etc. & cost of the same is deemed to be included in the quoted rates. | |||||||
| 3.00 | M&L for development / flushing of tube / bore wells with air compressor of suitable capacity till sand / mud free water of potable quality is obtained & to achieve minimum discharge capacity of 24000 LPH or as directed by the Engr-In-Charge based on size / type of borewells (Compressor with accessories & tube etc. shall be arranged by the contractor) complete all as specified & as directed & to the entire satisfaction of Engr-In-Charge. | 132 | Per Hour | 140 ₹18,480 | 135 ₹17,820 | 2,000 ₹2,64,000 | 129 ₹17,028 Lowest |
| 3.01NOTE : (i) Quoted rate is deemed to be inclusive of hire as well as transportation cost of Compressor with allied accessories, Tripod, Chain Pulley etc. for the said job. (ii) Quoted rate is deemed to be inclusive of taking down of the existing column pipes, submersible pump & connected items & refixing / installation of the same incl testing after the complete development / flushing process. (iii) The contractor / firm is required to visit the proposed sites of borewells prior to quoting of the subject items/ work so as to ascertain the actual ground requirements. Any further query at a later date shall not be entertained & responsibility of the same shall rest on the contractor/ firm. (iv) Anything missed out in the technical specifications but technically required for efficient working is deemed to be included in the quoted rates. | |||||||
| 4.00 | M&L for Submersible cable, PVC insulated, PVC sheathed 1100 volts grade, multistranded copper conductor, flat, 3 core, 4.0 Sqmm incl testing & taking down old unsv one etc. complete all as specified and as directed & to the entire satisfaction of Engr-In-Charge. Make : Havells/Polycab/Finolex/KEI | 960 | RM | 230 ₹2,20,800 | 215 ₹2,06,400 | 190 ₹1,82,400 Lowest | 209 ₹2,00,640 |
| 5.00 | M&L for Submersible cable, PVC insulated, PVC sheathed 1100 volts grade, multistranded copper conductor, flat, 3 core, 6.0 Sqmm incl testing & taking down old unsv one etc. complete all as specified and as directed & to the entire satisfaction of Engr-In-Charge. Make : Havells/Polycab/Finolex/KEI | 720 | RM | 320 ₹2,30,400 | 310 ₹2,23,200 | 260 ₹1,87,200 Lowest | 269 ₹1,93,680 |
| 6.00 | S&F Gun Metal Non Return Valve, ISI marked with flanged and connecting to GI pipe of size 32 mm bore including jointing materials, nuts, bolts, washers and necessary accessories incl testing & taking down old unsv one etc. complete all as specified and as directed & to the entire satisfaction of Engr-In-Charge. Make : Kirloskar/Leader/Upadhyay/Kartar/RMCO | 16 | Each | 4,550 ₹72,800 | 4,400 ₹70,400 | 1,000 ₹16,000 Lowest | 3,499 ₹55,984 |
Tender Value
₹48.5 L
EMD Value
₹97,100
Closing Date
9 May 2026, 6:00 pmClosed
GE (AFA) Hyderabad
GE (AFA) Hyderabad, Dundigal, Hyderabad
SPECIAL REPAIRS REPLACEMENT OF OLD UNSERVICEABLE LT FEEDER PILLAR BOXES AND LT CONTROL PANELS AT CERTAIN EM INSTALLATIONS AT AFA HYDERABAD
2026_MES_754442_2
8658
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
HYDERABAD
As per NIT
5 documents required · 5 mandatory
₹500
GE (AFA) HYDERABAD
₹97,100
Yes
21 May 2026
11 Apr 2026
11 May 2026
11 Apr 2026
9 May 2026
18 Apr 2026
11 Apr 2026 - 18 Apr 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| - | Supply, install, commissioning & testing of Motor Control Panel "out-door type" of size 900 mm (height) x 900 mm (breadth) x 500 mm (depth) (minimum dimensions) factory fabricated CPRI approved (type-tested) with suitable neoprene rubber gasket to make it completely dust & vermin proof & degree of protection not less than IP-55 & general construction confirming to IS-13947, double door, front & back openable. The panel shall be provided with ventilation facility in the form of louvers for better heat dissipation & tinned copper bus-bar wrapped with coloured PVC tape/sleeves of rating in conformity to the Incoming MCCB/MCB rating. The panel board shall be fabricated out of 3.15 mm thick (for outer portions) & 2.0 mm thick (for inner portions) CRCA sheet duly pre-treated & powder coated, supporting angle iron frame & MC channel base suitable for 3 Ph, 4 wire system 415/440 volts grade incl complete internal wiring with not less than 2.5 sqmm copper wire incl cable glands of suitable sizes incl suitable PCC (1:3:6) type C-2 foundation , necessary earthwork (if any) incl taking down old unsv one complete all as specified & as directed & to the entire satisfaction of the Engr-In-Charge with & incl the following accessories : [ For Watch Tower Borewells ] | - | Each Job | - | - |
| - | BUS-BAR & INTERNAL CONNECTIONS :
The bus-bars shall be made up of 04 Nos high grade Aluminium 100 A rated, duly insulated with 1100 V grade standard colour coded PVC sleeves & rigidly mounted on suitable sized "F" class insulators of non-hygroscopic, non-combustible, all internal connections from main bus-bars to switch gears etc.
PROVISION FOR CABLE ENTRY :
The provision for cable entry/exit shall be provided in the bottom for both incoming & out-going cables with the help of glands matching the existing LT cable sizes.
INCOMING :
(a) MCCB 4P (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting,suitable for isolation, having breaking capacity 25 KA & of rating 20 to 32 A - 01 Nos. Make : Cat No : DZ0F0020-32CXC1AOOOO of Make L&T or techno-commercially equivalent of LEGRAND/SIEMENS.
OUTGOINGS :
(a) MCB, SPN, 10KA, 230V, "C" curve, 06-32 A, ISI marked - 03 Nos (2W + 1S). Make : LEGRAND/ABB/SIEMENS
(b) Single Phase DOL Starter perfectly suitable for Submersible Pumping Set of capacity upto 2 HP, conforming to IS/IEC : 60947-4-1, IP-54, with & incl Extended wide band coil, FRLS Copper Internal Wiring, Starter Type - Air Break, Class-H Insulation with Contactor Rating - 12A, Overload Relay Range - 2.8A to 4.2A incl testing complete. Make : SIEMENS/L&T/HAVELLS/BCH - 02 Nos (1W + 1S)
INSTRUMENTATION SYSTEM :
(a) Digital type Multi-Function meter with built in selector Switch & 03 Nos CTs matching with the I/C breaker, Accuracy Class - 1.0, 3 phase, Size 96 x 96 mm. Make : Cat No WL411010OOOO of make L&T or techno-commercially equivalent of ELMEASURE/SECURE.
(b) Indicator lamp with integral circuit (230/240V) & cluster LED (Red, Orange, Blue) - 01 Set.
(c) Danger notice plate of size 20 x 15 cm of 1.6mm thick mild-steel sheet, vitreous enamelled white, with letters, figures and conventioinal skul and bones in signal-red colour and fixed with MS clamps, bolts and nuts of approved size, for LT conforming to IS-2551 - 02 Nos (Front & Back). | - | - | - | - |
| - | Supply, install, commissioning & testing of Motor Control Panel "out-door type" of size 1200 mm (height) x 1000 mm (breadth) x 600 mm (depth) (minimum dimensions) factory fabricated CPRI approved (type-tested) with suitable neoprene rubber gasket to make it completely dust & vermin proof & degree of protection not less than IP-55 & general construction confirming to IS-13947, double door, front & back openable. The panel shall be provided with ventilation facility in the form of louvers for better heat dissipation & tinned copper bus-bar wrapped with coloured PVC tape/sleeves of rating in conformity to the Incoming MCCB/MCB rating. The panel board shall be fabricated out of 3.15 mm thick (for outer portions) & 2.0 mm thick (for inner portions) CRCA sheet duly pre-treated & powder coated, supporting angle iron frame & MC channel base suitable for 3 Ph, 4 wire system 415/440 volts grade incl complete internal wiring with not less than 2.5 sqmm copper wire incl cable glands of suitable sizes incl suitable PCC (1:3:6) type C-2 foundation , necessary earthwork (if any) incl taking down old unsv one complete all as specified & as directed & to the entire satisfaction of the Engr-In-Charge with & incl the following accessories : [ For Other Borewells ] | - | Each Job | - | - |
| - | BUS-BAR & INTERNAL CONNECTIONS :
The bus-bars shall be made up of 04 Nos high grade Aluminium 100 A rated, duly insulated with 1100 V grade standard colour coded PVC sleeves & rigidly mounted on suitable sized "F" class insulators of non-hygroscopic, non-combustible, all internal connections from main bus-bars to switch gears etc.
PROVISION FOR CABLE ENTRY :
The provision for cable entry/exit shall be provided in the bottom for both incoming & out-going cables with the help of glands matching the existing LT cable sizes.
INCOMING :
(a) MCCB 4P (Ics = 100% Icu) with thermal magnetic release, adjustable short circuit & adjustable overload setting,suitable for isolation, having breaking capacity 25 KA & of rating 40 to 50 A - 02 Nos. Make : Cat No : DZ0F0050CXC1AOOOO of Make L&T or techno-commercially equivalent of LEGRAND/SIEMENS.
(b) Compact Enclosed ATS (Automatic Transfer Switch) suitable for inside panel mounting & I-O-II operation, 4 Pole, 63 A, confirming to IEC 60947-6-1 - 01 No complete with following features/specifications :
(i) Double-Break Contact System offering High Short-time Withstand.
(ii) Ample Space for Cable Termination.
(iii) Ease of Generator Control (ON-OFF, Cooling Cycle Self-Test).
(iv) Cyclic Event Logger.
(v) Priority Source Selection.
(vi) Adjustable Time Delay (0.1 Sec to 3 Hrs).
(vii) Suitable for 3-Phase as well as 1-Phase sources.
(viii) Protections - UV/OV, Phase Sequence, Single Phasing, Frequency.
(ix) Terminal Shrouds, Phase Barriers & Source Separator etc.
Cat No : 1SYN151254R1001 of make ABB or techno-commercially equivalent of L&T/Siemens. | - | - | - | - |
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.12 MB
TENDERPAGES8658.pdf
Tender Documents • 0.47 MB
BOQ_851355.xls
BOQ • 0.60 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .