Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹6.7 LAccepted-AOC | 1 | Accepted-AOC L1 |
Tender Value
Refer Docs
EMD Value
₹17,015
Closing Date
30 Jan 2023, 4:00 pmClosed
Secretary
secretary, Edavilangu Gramapanchayat
Generator to Panchayath office- Supply and installation of 25 kva Diesel generator set, Edavilangu GP-General Electrical Work
2022_DP_538934_2
400737/GAPG23/GPO/2022/6331
Open Tender
Electrical Works
Item Rate
7 days
Edavilangu Gramapanchayat
Please refer Tender documents.
8 documents required · 8 mandatory
₹1,505
₹17,015
13 May 2025
21 Jan 2023
1 Feb 2023
22 Jan 2023
30 Jan 2023
22 Jan 2023
Amount
INTSALLATION OF DIESEL GENERATOR AT GRAMA PANCHAYATH OFFICE EDAVILANGU
OD90406/2022-2023: Supply , conveyance and unloading of 25 KVA 240 V single phase DG set with company made acoustic canopy conforming to CPCB norms as per technical details given below. ENGINE make of Engine - Cummins / caterpiller/ VOLVO Type of Engine - Diesel Engine No. of Cylinders - suitable to develop the required BHP as per manufactures standards. Method of cooling - Water cooled with radiator Aspiration - Turbo charged / natural Design - suitable for generating set application Output - 33 HP at 1500 rpm under NTP Standard accessories with Diesel Engine Fly wheel to suit flexible coupling Close coupling Air cleaner Fuel pump Mechanical governor Fuel filter Lubricating oil filter Residential type Exhaust silencer Engine Instrument Panel Starting switch with key or button Lubricating oil pressure gauge Water temperature gauge RPM indicator with hour meter Supply Control for engine Battery control (trip) Trip for low lubricating oil pressure Battery control (trip) Trip for high water temperature providing necessary warning system and other safeties as contemplated in relevant ISS Fuel pipes Oil resistant hoses of 20 mm dia or nearest MS pipe as per manufactures requirement for fuel lines Alternator Make - STAMFORD/ Leyrose or equivalent. Type self excited and self regulated Capacity 25 KVA / 20 KW @ 0.8 P.F lag System Voltage Single phase 230 V AC 50 Hz Speed 1500 RPM Voltage regulation band 2.5% of rated voltage Insulation class F/H Alternator should confirm IS4722 The DG set should mount on a suitable size base frame with anti vibration mounting pad. Fuel tank 60 Ltr capacity fuel tank integrated with acoustic enclosure complete with fuel provision for filling the diesel electric fuel gauge. Battery Required number of suitable rated fully charged battery with leads and terminals as required as per manufactures requirements. Operation manual service manual list of spares etc. shall be submitted while the DG set is supplied. Standard control panel integral with the acoustic enclosure comprising the following 125 A 25 KA 4 pole MCB having adjustable setting having connection with statutory protective system like EFR and neutral CT etc. Digital type meter with accuracy class 0.5 to read parameters such as KWH, wattage, current, frequency etc. LED type phase indication type Fuse protection shall be provided for the meters and indication lamps. Exhaust piping Cost of DG set with charges of conveyance and unloading at site.
14.1:Excavation for foundation in soft soil including dressing of sides and ramming of bottoms, lift upto 1.5 m including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 metres.
14.7:Providing and laying in position cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) in foundation of pump, DG set etc including form work etc as required.
14.12:Providing 15mm thick cement plaster of mix 1:4(1 cement: 4 fine sand) at all levels
14.13.1:Providing, laying and fixing following dia G.I. pipe (medium class) in ground complete with G.I. fittings including trenching (75 cm deep)and re-filling etc as required50 mm dia
OD56821/2022-2023:Supply and clamping 80 mm dia medium class GI pipe with clamps made from 25x3mm MS flat (for extension of exhaust pipe) on wall with required accessories including cutting and making good the wall painting the exposed portion etc. as required.
OD57327/2022-2023:Installation, testing and commissioning of 25 KVA DG set on the newly constructed concrete basement after initial filling of oil and fuel, trial run etc.
5.4:Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
5.9:Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required.(Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm)
6.12:Providing and fixing testing joint, made of 20 mm X 3 mm thick G.I. strip, 125 mm long, with 4 nos. of G.I. bolts, nuts, chuck nuts and spring washers etc. complete as required.
5.14:Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required.
90.16.1.6:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required6.00 mm copper conductor (4 SWG)
90.16.1.3:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required3.15 mm copper conductor ( 10 SWG)
90.16.5.6:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.6. mm ( 4 SWG)
90.16.5.3:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.3.15 mm (10 SWG)
OD56825/2022-2023:Supply and providing the following sizes of bolt and nut with washers on the existing M.S box/ earth bus etc. as required including drilling necessary holes as required. 25x3mm brass nut and bolt .
OD56824/2022-2023:Supply and providing the following sizes of bolt and nut with washers on the existing M.S box/ earth bus etc. as required including drilling necessary holes as required. 25x6mm brass nut and bolt .
90.16.2.2:Supply and laying of the following sizes of B class GI pipe laid 0.6 m below ground level including excavating trench of suitable size and refilling etc, as required.20 mm dia. G.I pipe ( medium class)
90.2.1.1:Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).Single Control light point with 6A, plate ceiling rose - Short point
90.3.17.2:Supply, conveyance and erection of the following sizes of 'B' class GI pipe in single section for post top lantern of all types on concrete base (excluding charges for concrete base and excavation) and painting with 2 coats of synthetic enamel paint over a coat of zinc chromate primer etc. as required.40 mm dia GI pipe
90.15.4.2:Supply Conveyance, installation, testing and commissioning of 36/40W LED street light output greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminium pressure die-cast Powder coated housing,acrylic cover complete with THD less than 10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer)
90.15.4.3:Supply Conveyance, installation, testing and commissioning of 70W LED street light output greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminium pressure die-cast Powder coated housing,acrylic cover complete with THD Less than 10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer)
90.14.1.1:Fabrication, supply, conveyance, installation testing and commissioning of floor or wall mounting, dust and vermin proof, cubicle type MV panel board comprising of the following components/ devices & complying to IS 8623.<br> Fabrication of fully partitioned, dust and vermin proof enclosure for panel assembly as per form 4 of IS 8623 (with latest amendments) using CRCA sheet as per approved design and requirement, with front and rear access facility, bus bar chambers, hinged doors for all switch gear compartments, earthing the doors using 4 sq mm braided copper conductor, providing necessary cut-outs for mounting meters, relays, indication lamps, bus bar interconnection etc, detachable covers for bus bar chamber and cable alley, powder coating the assembly after subjecting to 7 tank process etc as required. CRCA sheet alone be used for the fabrication. Angles/ flats/ slotted angles etc shall not be used for the fabrication of panel assembly. The measurments will be taken the area of the complete sheets used for panel board including partitions, folding, shrouding etc.Supply and fabrication of MV panel board using 2.00mm CRCA sheet, powder coated (excluding base frame)
90.14.2.1:Supply and providing 2mm SMC sheet as shrouding for bus interconnection / terminations etc. including required nut & bolt etc.
90.14.3.2:Supply and providing heavy duty 'A' section neoprene gasket in the panel boardU' section rubber beeding suitable for 1.60/ 2.00 mm sheet
90.14.4:Supply and fabrication conveyance and installation of base frame of panel board using 75 x 40 mm rolled steel channel (ISMC)
90.14.5:Supply and fabrication conveyance and installation of angle iron frame work for wall mounting panel board
90.14.6:Supply and providing copper bus bars including finger type SMC bus bar supports in the bus chamber, suitable size nut & bolt, providng heat shrink sleeves etc. as required.
90.14.7:Supply and providing copper earth bus in the panel board
OD56822/2022-2023:Supply and providing multifunction meter to read V, A, f 3 phase accuracy class one.
2.1.4:Providing and fixing following capacity TP&N disconnector fuse switch unit inside the existing panel board with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required.125 Amp TP & N
2.1.2:Providing and fixing following capacity TP&N disconnector fuse switch unit inside the existing panel board with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required.63 Amp TP & N
OD58535/2022-2023:Supply and fixing 63 A HRC fuse base with HRC fuse link in the existing meter board and giving connections etc.
OD58528/2022-2023:Supply and installation of 63 A, 415V, 50Hz AC 23A 4 pole on load changeover switch in sheet steel enclosure complete with handle assembly, door interlock and pad locking arrangement on existing angle iron frame work or directly to wall using necessary bolts and nuts, fixing the unit to wall making good the damages colour washing etc. including giving necessary connections as required.
OD57314/2022-2023:Supply and installation of 415V, 100A TPN AC 23A switch disconnector unit including HRC fuses in sheet steel enclosure complete with handle, door interlock and pad locking using necessary bolts and nuts, fixing the unit to wall, making good the damages, colour washing etc. including giving necessary connections as required.
OD57346/2022-2023:S&F Danger notice board of size 100x75 mm with inception both in English and Malayalam and convention skull and bone in red.
OD56823/2022-2023:Supply and providing 2.00 mm thick 3.3 KV synthetic elastromeric fire retardant insulating sheet.
OD56826/2022-2023:Supply and installation of ABC Powder Type (Stored Pressure) Fire Extinguisher 4Kg. Capacity ISI Mark IS: 15683 consisting of M.S cylindrical body, squeeze leve,r discharge valve fitted with pressure indicating gauge, 30cm long, high pressure discharge hose, nozzle etc. with MAP Powder for 'A','B' & 'C' class fire, fixing on wall with wallhook etc as required.
90.12.5.42:Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.4 core 25 sq mm
90.12.5.43:Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.4 core 35 sq mm
90.12.10.3:Supply & laying of DWC pipe in ordinary soil 0.75m below ground level including excavation63/50 mm or nearest size
9.1.35:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 35 sq. mm (32mm)
9.1.34:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 25 sq. mm (28mm)
OD90524/2022-2023:Painting letters or figures of the sizes 2.5 cm, 4 cm, 5cm height with enamel paint as identification mark to SB, DB, Panel board etc. as required
OD90527/2022-2023:S$F LED indicators for all voltage ranges - Red, Green, Black, Yellow or Orange colour
OD57382/2022-2023:Supplying and providing earth clamps for siemens/ tropodur type cable glands of suitable and other dimensions noted along with each size of glands for the 25 sqmm with 12mm wide x 1 mm thick clip of cable as required.
OD57381/2022-2023:Charges for preparation of connected drawings for obtaining approval from electrical inspectorate.
Bidder Name
KOLAR MILL STORES
tech_eval.pdf
fin_eval.pdf
aoc.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .