Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance B 22 2ND FLOOR HIMALAYA HOUSE 23 K G MARG CANNAUGHT PLACE NEW DELHI 110 001 | NEW DELHI | DELHI | 110001 | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Rejected-Technical | Rejected-Technical Not Meeting the required critera as per eNIT. |
| 4 | Rejected-Technical | Rejected-Technical Not Meeting the required critera as per eNIT. |
| 5 | Rejected-Technical | Rejected-Technical Not Meeting the required critera as per eNIT. |
Tender Value
Refer Docs
EMD Value
₹28.4 L
Closing Date
1 Feb 2021, 3:00 pmClosed
CHIEF MECHANICAL ENGINEER /VPT, VSP
CMEs Dept.,2nd Floor,AOB,VPT,VSP 0891- 287-3209/3213/3202
Providing New Fire Fighting Facilities suitable to the upgrading capacities of Berths OR-I n OR-II to accommodate 50,000 to 1,00,000 DWT Vessels (Panamax Vessels) as per OISD 156 guidelines in a phased manner Phase-II.
2020_VPT_65481_1
35/2020-21/IMnEE/MOF/MII/ORI n II/Ph-II,
Open Tender
Miscellaneous Works
450 days
VPT
Please refer Tender documents.
2 documents required · 2 mandatory
₹1,770
Yes
AS PER NIT
₹28.4 L
Yes
CMEs Dept.,2nd Floor,AOB,VPT,VSP
26 Mar 2021
25 Dec 2020
3 Feb 2021
25 Dec 2020
1 Feb 2021
11 Jan 2021
6 Jan 2021
Amount
Fire Hydrant, Jumbo curtain Nozzles and Water/ Foam Monitors Supply, Erection, Testing and Commissioning of Water Cum Foam Tower Monitors in SS316 construction
UL Listed Tower Mounted Long Range Water Cum foam Monitor with fixtures, clamps, SS Fasteners, supporting for riser pipe and monitor suitable to discharge 5678 LPM of water at horizontal range of 80-100 m and vertical range 30-40 m or 5678 LPM foam & water mixture with a horizontal throw range of 70-90 m and vertical range 30-40m with electrical /electro hydraulic equipment's for horizontal and vertical rotation, with base operation control. The operation of tower monitor shall be remote controlled, electrically operated from control tower and from Local flame proof Control panel . MOC of Nozzle, Body, Elbow, Bend, Flange, shall be SS316. The Monitor shall be suitable to install on structural platform at height of 20 mtr. All electrical component of shall be flameproof type suitable for gas group IIA/IIB. Make: HD Fire/ SBJ / Newage/Fire Tech
Supply, Erection, Testing and Commissioning of Water Cum Foam Ground Monitors in SS316 construction UL listed Water Cum foam monitors shall includes all fixtures, clamps, SS Fasteners and flanged connection as per ANSI B16.5 150# . Monitor suitable to discharge 2820 LPM of water at horizontal range of 60 m and vertical range 30 m or 2820 LPM foam & water mixture with a horizontal throw range of 55 m and vertical range 25 m with hadweel for horizontal and vertical rotation, with Manual operation control. MOC of Nozzle, Body, Elbow, Bend, Flange, shall be SS316 Make: HD Fire/ SBJ / Newage/Fire Tech
Supply, Erection, Testing and Commissioning of Jumbo curtain nozzles in SS 316 Jumbo Water curtain nozzles in SS 316 construction, capacity 5000 lpm flanged connection as per ANSI B16.5 150# Complete with all required accessories as per OISD 156-2017 . JC nozzle are required on the central loading platform in front of the loading/ unloading arms . JC Nozzzle shall be capable of operating from the local control panel for each Oil Jetty and operational from Remote Control Panel The MOC of Body, flange shall be SS316. Coverage of nozzle shall be min 40 Mtr horizontally & 20mtrs vertical height. Make: SBJ / Newage / HD Fire
Supply, erection, testing and commissioning of Double Headed Standard Fire Hydrants (SS-316 size 63mm) Make: SBJ / Sukan / Newage Hydrant valve Confirming to IS : 5290 Type - A, ISI marked (S.S 316) with two separate landing valve including 80mm dia flanged inlet & 63mm dia female outlet complete with cap and other accessories.
Double headed hydrant valves
Supply , erection , Testing and commissioning 80 mm dia SS 316 with 3mm thk Orifice plates for Hydrant Valve
Supplying , installing, testing and commissioning of 63 mm dia RRL Fire Hose of Type B (as per IS : 636) with SS316 coupling of 63 mm dia and length as described below including SS 316 male and female instantaneous type coupling, suitable for burst pressure of min 35.7 kg/sq.cm. Hose shall be permaline hose and coupling to I.S.903-1975 with ISI certification, rivetted to hose pipe with copper rivets & 1.5 mm copper wire Make: SBJ / Newage /Rapiddrop
Supplying , installing, testing and commissioning of standard size SS316 Branch pipe with Tripple purpose nozzle standard instantaneous type 63 mm dia coupling as per IS 2871 Make: SBJ / Newage /Rapiddrop
Hydrant valve Confirming to IS : 5290 Type - A, ISI marked (S.S 316) with single landing valve including 80mm dia flanged inlet & 63mm dia female outlet complete with cap and other accessories. Make: SBJ / Sukan / Newage
SINGLE headed hydrant valves
Supply , erection , Testing and commissioning 80 mm dia SS 316 with 3mm thk Orifice plates for Hydrant Valve
Supplying , installing, testing and commissioning of 63 mm dia RRL Fire Hose of Type B (as per IS : 636) with SS316 coupling of 63 mm dia and length as described below including SS 316 male and female instantaneous type coupling, suitable for burst pressure of min 35.7 kg/sq.cm. Hose shall be permaline hose and coupling to I.S.903-1975 with ISI certification, rivetted to hose pipe with copper rivets & 1.5 mm copper wire Make: SBJ / Newage /Rapiddrop
Supplying , installing, testing and commissioning of standard size SS316 Branch pipe with Tripple purpose nozzle standard instantaneous type 63 mm dia coupling as per IS 2871 Make: SBJ / Newage /Rapiddrop
Supplying , installing, testing and commissioning of M.S. Swing type of Hose Reel, Wall Mounting type with 19 mm bore with 36 M long Nylon braided high pressure rubber Hose as per IS 884, 6mm bronze shut off nozzle and valve confirming to IS 884. along the SS Isolation valve at tapping point. Make: SBJ / Newage /Rapiddrop
Supplying , installing, testing and commissioning of SS 316 Air Release valve with isolation valve of 25 mm. dia. Make: Leader / Zoloto / Flowchem
Supply , Installation , Testing and commissioning of 25NB Gunmatal (Globe Valve ) Valve for above pressure gauges. Make: L&T(Audco), Flowcehm, Advance valves,Venus,Zolato,KBL
Supplying , installing, testing and commissioning of M.S. Swing type of Hose Reel, Wall Mounting type with 19 mm bore with 36 M long Nylon braided high pressure rubber Hose as per IS 884, 6mm bronze shut off nozzle and valve confirming to IS 884. along the SS Isolation valve at tapping point. Make: SBJ / Newage /Rapiddrop
Supply, erection, testing & commissioning of the following ERW steel pipe as per IS 1239 /3589 Make: Jindal / Surya Roshni / TATA /Apollo/Lloyds SITC of Above ground M S ERW Heavy (Class C) Pipe as per IS:1239 Part-1 for 150mm dia and below & IS:3589 Gr. Fe. 410 with .thk.6.35mm for 200 mm dia and above. Pipes for all sizes shall be provided with internal Poly-Glass coating of 1000 micron including cutting, screwing, welding etc. and providing all fittings (thickens of fittings shall be matched with parents pipes) like elbow, tee, reducer, companion flanges, All fittings shall be A234 WPB. All flanged valves shall be as per ASME B 16.20 and all gaskets shall be of metallic with SS316 spiral wounded CAF filler. All studs and nuts shall be SS 316 As per ASTM A 193 Gr.B7/194 Gr.2H All ERW pipe with internal bead flushed fully with internal surface of pipe or maximum 0.2 mm projection or below throughout the length of pipe and flange fixing for Poly-Glass coating. Pipe to pipe joint shall be flanged type with Poly-Glass coating. External painting of pipe shall be as per Annexure-1 painting specification. The pipes has to be provided with corrosion and RF pads. Hume pipes, wrapping and coating to be provided where ever pipes are laying under grond.
Supplying, installing, testing and commissioning of M.S Raised Face flange as per IS 2062 Gr. B , Flange dimensional standard as per ANSI B 16.5 Class 150 and above . All flange shall be provided with internally Poly galss coating 1000 micron Make: Fittech/Amforce/ Pipefit/ Montex
Supplying , installing, testing and commissioning of SS Super duplex Gate Valve With Rising Spindle ,as per API 603 with flange end connection as per ANSI B 16.5 150 # and SS 316 Nut and Bolt as per ASTM A 193 Gr.B8M . The valve shall be tested as per API598. MOC of valve Body, cover & bonnet shall be as per A890GR.F5A, Trim, Body seat, disc shall be UNS J93404 Make: L&T(Audco), Flowcehm, Advance valves, Venus,Zolato,KBL
Supply, Erection, Testing and Commissioning of Motorised SS Super duplex Gate Valve with Actuator.(For Jumbo Curtain & Tower monitor )- 200 NB dia Make: L&T(Audco), Flowcehm, Advance valves/CMRI approved : Brans Auma / Rotork / Emerson / Siemens / Danfoss Venus,Zolato,KBL SS Super duplex Gate Valve with Rising Spindle ,as per API 603 with falnge end connection as per ANSI B 16.5 150 # and Nut and Bolt as per ASTM A 193 Gr.B8M .The valve shall be tested as per AP I598. MOC of valve Body, cover & bonnet shall be as per A890GR.F5A, Trim, Body seat, disc shall be UNS J93404 with open/close limit switches for Position sensing. Torque limit switches for instant torque releasing and control. a) MOV With Operating Voltage of 415 V AC 50 HZ and flameproof Enclosure with zone IIA/ II B application and 3-phase squirrel cage motor TEFC class F insulated (temperature rise limited to class B) both for motor and its terminal box, for outdoor duty, the motor shall be provided with anti-condensation heater. b) Actuator shall be provided with motor over-riding feature like hand wheel for emergency manual operation and a limit switch shall be provided whose contacts shall be used in the motor control circuit to forbid the motorized operation during manual operation by hand wheel. Internal wiring shall be tropical grade PVC insulated, stranded copper conductor cable of 10A rating for control circuits and required rating for motor.
Providing & Fixing of Structural steel like Angle, Channels with fabrication, MC200 or MC150 GI coated 200 microns, welding, fasteners etc. complete with corrosion protection as per tender Specifications. Make: SAIL /TATA/Essar/Jindal
International Shore Fire Connection (IFSC) through which water could be supplied to a tanker fire main if required for shipboard fire fighting. With required accessories. Make:SBJ / Sukan / Newage Outside Dia : 178 mm Bolt Circle Dia. : 132 mm Inside dia : 64 mm Pipe connection 150NB Slots in flange : 4 Holes 19 mm in dia spaced equidistantly on a bolt circle of above dia, slotted to flange periphery flange thickness 14.5 mm minimum. Bolts and Nuts : 4 Nos. each of 16 mm diameter, 50 mm in length.
Supplying , Installing, Testing and Commissioning of pressure gauges with siphon tube and cock, Glycerine filled, 150mm dial, range - 0 to 25 kg/cm2 as per ,with isolation valve/cock including required all fixing accessories. MOC - SS316 for inlet of Tower Monitor , Water monitor and Water Curtain Nozzle. Make: H Guru /General Instruments / Wika
Butterfly Valves of Body Cast Carbon steel ASTM A216 Gr. WCB conforming to BS: 5155 , disc AISI 316, Spindles and retainer ring SSAISI 410, having Nitrile rubber disc seal and body seat, Bronze bearing Bush, Nuts and Bolts SS 316 (For Tower Monitors and Hydrant Valves isolation) Make: L&T(Audco), Flowcehm, Advance valves, Venus,Zolato,KBL 100 NB
Supply, Installation, Testing & Commissioning of Modular type ceiling mounted Clean agent type fire extinguisher, ISI Marked IS 15683:2006, having sprinkler with glass bulb rated at 68 deg.C, suitable for Class A,B and C type of fires, Capacity - 15 Kg. (required for Control room). Make: Supremex/FireFite/Safex
Fire Water Pump room
Supply, Erection, Testing and Commissioning of Diesel Engine driven Vertical Turbine pump suitable for rating mentioned below : Pump as per FM/UL listed. Make: Pump : Amstrong /Grundfos/KBL/Flowmore/Pentair Diesel Engine : Caterpilar / Cummins / MWM, RUSTON /KOEL
Supply, Installation, Testing & Commissioning of Electric driven Vertical Turbine Jockey pump suitable for rating mentioned below capable of starting automatically and also manually. Make: Pump : KBL/Flowmore/Pentair Motor : ABB/CGL/Seimens/WEG SITC of Electrical driven Vertical turbine Jockey pump set Capacity : 900 LPM (54 m3/hr)@150 MWC at discharge flange complete with suitable LT Motor , base frame, coupling, coupling guard and all other accessories as required. The pump , Motor and accessories manfacturing and installation shall comply to OISD codes. The pump set and its water contact parts shall be suitable for sea water application (1) MOC of Pump - (a) Casing diffuser: Super Duplex SS, (b) Suction bell mouth: Super Duplex SS, (c) Impeller and allied wear rings: Super Duplex SS, (d) Shaft & Shaft Sleeve: Super Duplex (e) Bearing bush: Thordon (f) Rising (Column) Pipe: Super duplex, (g) Discharge bend: Super Duplex (h) Muff Coupling with collar etc: Super duplex, (i) Suction strainer: Super duplex, (j) Stuffing box: Super duplex, (k) Sleeve, gland: Super Duplex, (l)Fasteners: SS316L, (m) Sole plate, Motor stool: M.S with epoxy coating, (n) Foundation bolts: SS316L, (o) Auto release valve: SS316L, 1)Motor Shall be Non Flameproof having Suitable KW Rating @ 1500 Rpm 2)Type : 3-phase squirrel cage motor TEFC class F insulated and IE2 3) Motor Protection : IP 55 4) min 18HP / 13.2KW ( bidder shall validate the same during the contruction stage) 4) Operting Voltage : 415 V AC Supply @ 50 Hz 5) Column Length - 16.3 Meter
SITC of Cassion pipe cover for vertical turbine pump shaft, MOC, SS316L with all required fixing accessories including painting as per Tender specification. (Length shall be as per postiive suction requirement). The unit rate of pipe shall include cost of fittings and painting. Make: Fabricated
800 mm dia - 8 mm Thickness
400 mm dia - 8 mm thickness
Supply, erection, testing & commissioning of the following ERW steel pipe as per IS 1239 /3589. Make: Pipes: Jindal / Surya Roshni / TATA / Fittings: Fittech/ Pipefit/ Montex SITC of Above ground M S ERW Heavy ( Class C ) Pipe as per IS:1239 Part-1 for 150mm dia and below & IS:3589 Gr.Fe. 410 with .thk.6.35mm for 200 mm dia and above. Pipes for all sizes shall be provided with internal Poly-Glass coating of 1000 micron including cutting, screwing, welding etc. and providing all fittings (thickens of fittings shall be matched with parents pipes) like elbow, tee, reducer, companion flanges, All fittings shall be A234 WPB-W.All flanged valves shall be as per ASME B 16.20 and all gaskets shall be of metallic with SS316 spiral wounded CAF filler. All studs and nuts shall be SS 316 As per ASTM A 193 All ERW pipe with internal bead flushed fully with internal surface of pipe or maximum 0.2 mm projection or below throughout the length of pipe and flange fixing for Poly-Glass coating. Pipe to pipe joint shall be flanged type with Poly-Glass coating. External painting of pipe shall be as per Tender (Annexure-1 ) painting specification
MCC Panel- Supply , installation, testing & commissioning of Non Flameproof Modular compartmentalized Motor Control Centre fabricated main body from 14 SWG CRCA sheet. The panel shall be dust and vermin proof, 415V 3Ph, 50 Hz as per IP 42 construction. The panel shall be powder coated with FIRE RED with 7 tank process for clearing and phosphating before powder coating. The panel should be with Suitable incomer & outgoing to meet the above mentioned pumps puls with required starter and MCCBs CT, Voltmeter, Phase indicators, indication lamps, Aluminium bus bars with colour coded heat shrinkable insulating sleeves, All MCCB shall be suitable for motor duty application. Main components shall be of Siemens/Merlin Gerin / L&T / Schneider/ ABB. Cost including for required fabricated angle support, earthing & required also. ( as per site conditions it should be placed inside the pump room-indoor) - Vendor shall submit the GA/SLD drawing for review. Note :( STARTER FOR BOTH JOCKEY PUMPS TO BE INSTALLED IN THIS PANEL ONLY ) Make: SGPL/ Pyrotech/ Positronics/ Sunlight/ APJ A.Outgoing Feeder a) 415 V Soft Starter for 37 KW motor rating for Jockey Pump - 2 Nos b) Out going feeders to diesel pumps-3 No's B.Incoming Feeder-250A MCCB, 25KA with required RYB Al. Bus bars.
SITC of Diesel engine Non Flameproof Control panel with 2 set of battery charger , on/off push buttons , Hooter for all Diesel engine Fire Pumps with required control cables. Make:SGPL/ Pyrotech/ Positronics/ Sunlight/ APJ
SITC of Annunciation cum Remote Control panel (at Control Room) with on/off push buttons for all Fire Pumps with required control cables from Main panels. Make: Baliga / FCG / CEAG / Sudheer
Supplying , Installing, Testing and Commissioning of SS Super duplex valve as per A890GR.F5A with double flanged connection as per ANSI B 16.5 Class 150 , Swing type Non-return valve including SS 316 nuts, bolts, as per ASTM A 193 Gr.88 M & 15mm thick compressed asbestos gasket including matching flanges complete as per requirement. Make: L&T(Audco), Flowcehm, Advance valves, Venus,Zolato,KBL
400 mm nominal dia
300 mm nominal dia
100 mm nominal dia
Supplying , installing, testing and commissioning of SS Super Duplex Gate Valve With Rising Spindle ,as per API 603 with flange end connection as per ANSI B 16.5 150 # and SS 316 Nut and Bolt as per ASTM A 193 Gr.B8M . The valve shall be tested as per API598. MOC of valve Body, cover & bonnet shall be as per A890GR.F5A, Trim, Body seat, disc shall be UNS J93404. Make: L&T(Audco), Flowcehm, Advance valves, Venus,Zolato,KBL
400 mm nominal dia
300 mm nominal dia
100 mm nominal dia
Supply , Installation , Testing and commissioning of Gunmatal (Globe Valve ) Valve. Make:L&T(Audco), Flowcehm, Advance valves, Venus,Zolato,KBL
Supplying , Installing, Testing and Commissioning of pressure gauges with siphon tube and cock, Glycerine filled, 150mm dial, range - 0 to 16 kg/cm2 as per ,with isolation valve/cock including required all fixing accessories. MOC - SS316. Make: H Guru /General Instruments / Wika
Supplying , Installing, Testing and Commissioning of pressure switches with tubing, isolation valves. complete as per requirement steel plated with IP 33 protection.(Inside the Pump room) MOC - SS 316 , DPST Contacts. Make: Indfos / Switzer / Wika / Emerson
Supplying , Fixing, commissioning of Electromagnetic Type Flow Meter complete with all accessories Flowmeter of size 300 NB having flow handling capacity of 150% of single pump discharge for test line Body - WCB , Flange 300# - with required accessories matching flanges, nuts, bolts gaskets etc. Make: E&H/ Emerson/ Yokogawa/ ABB/ Krohne Marshal
Providing & Fixing of 300NB Pressure Releif Valve . Flange end connection as per ASTM A 16.5 150#. with matching flanges, nuts, bolts, gaskets etc. which ever required as per site conditions. Make: Darling muesco / Rapidrop / Viking/Tyco
Supplying , installing, testing and commissioning of Precharged air vessel (size 250 mm dia & 1200 mm height) complete with adequate pressure gauge (as per design / requirement) with valves to operate as per operating sequences including 25 mm dia drain valve, air release valve with stop cock on the top, required inlet with isolating valve duly painted from inside and outside complete as required. (The vessel should be suitable of working pressure of 16 Kg/Sqcm including synthetic enamel paint over a coat of primer). Make: FABRICATED
LT CABLES
Supplying, laying, testing and commissioning of 1100 Volt grade XLPE insulated PVC type aluminium conductor FRLS armoured cables with required accessories. For Jockey Pump. Make: Finolex / Universal /RR Cables / Havells /Polycab 3 C x35 Sq.mm Al Arm cable for main electrical Jokey and Foam pumps
12 C x 2.5 sqmm Cu Conductor, FRLS armoured as Control Cabling for diesel engine complete with all accessories like double compression cable glands
24C x 1.5 sqmm Cu Control Armoured Cable for FWPH to Control Room complete with all accessories like double compression cable glands
4C x 1.5 Sq.mm Cu.conductor armoured cable for Flow meter complete with all accessories like double compression cable glands
2 C x 1.5 sqmm Cu. Conductor, FRLS armoured cable for Instrumentation complete with all accessories like double compression cable glands
G.I. Earthing strips of suitable size shall be run on floor / ceiling / walls, from the equipment to the nearest earth pit with necessary accessories as required. (50 X 10 mm). Make: ISI Approved
CABLE TRAY FRP Ladder / Perforated type cable tray with necessary bands, tees and clamps for fixing. All material shall be FRP. Cable Trays shall be considered with Double Coupler Plates. All Bolts shall be SS 316 .Thickness of the cable tray material shall be 6 mm for 300 mm & above & 4 mm for below 300 mm size. Make: EPP/ Sumip/ Ercon
Providing & Fixing of Structural steel like Angle, Channels with fabrication, GI coated 100 microns, welding, fasteners etc. complete with corrosion protection as per tender Specifications. Make: SAIL /TATA/Essar/Jindal
Foam system
i) Relocating, Erection and testing of Existing Foam Tanks made of 6mm thick SS-316 plate of 15,000 Litres capacity with inlet, outlet connections, drain, venting, ladder, staging, manhole, level indicator, low and high level alarms, with transparent graduated scale & supports / saddles etc.,( Valves & Piping are of SS). Suitable dyke wall to be constructed to house the tank. The cost shall include the temporary storing arrangement for storage of Foam during relocation of foam tank. and shall attend any repairs required
ii) Supply, testing & commissioning of Motor Driven Gear Operated Foam Supply Pump Set with Non Flameproof motor of capacity 350 LPM at 17 kg/cm2 with all accessories for transfer of AR-AFFF foam. The contractor should provide foundation arrangements to suit grouting and install the same as per clients requirement. MOC of PUMP casing, Rotor/Stator Gear, Rotor/Stator Shaft, Relief Valve shall be SS316. . Motor type shall be TEFC , IP 55 and Power Supply suitable for 415 V AC @ 50 Hz ,45kw motor rating. Make: Rotadel/Delta / Delpd / ABB/SIEMENS / BBL / CG)
iii)Supply, testing & commissioning of Diesel Engine Driven Gear Operated Foam Supply Pump Set with engine of capacity 375 LPM at 17 kg/cm2 with all accessories for transfer of AFFF foam. The contractor should provide foundation arrangements to suit grouting and install the same as per clients requirement. MOC of PUMP casing, Rotor/Stator Gear, Rotor/Stator Shaft, Relief Valve shall be SS316. Make: Rotadel/Delta / Delpd
iv) Supply & testing of Portable Hand Operated Rotary Pump capacity 50 LPM for filling of foam tank complete with all accessories. The material of construction of rotary pump shall be suitable for foam handling. Make: Rotadel/Delta / Delpd
MCC Panel- Supply , installation, testing & commissioning of Modular compartmentalized Motor Control Centre fabricated main body from 14 SWG CRCA sheet. The panel shall be dust and vermin proof, 415V 3Ph, 50 Hz as per IP 42 construction. The panel shall be powder coated with FIRE RED with 7 tank process for clearing and phosphating before powder coating. The panel should be with Suitable incomer & outgoing to meet the above mentioned pumps puls with required Star Soft starter and MCCBs CT, Voltmeter, Phase indicators, indication lamps, Aluminium bus bars with colour coded heat shrinkable insulating sleeves, All MCCB shall be suitable for motor duty application. Main components shall be of Siemens/Merlin Gerin / L&T / Schneider. Cost including for required fabricated angle support, earthing & required also. ( as per site conditions it should be placed inside the pump room-indoor) - Vendor shall submit the GA/SLD drawing for review. (STARTER to be installed in control panel). Make: SGPL/ Pyrotech/ Positronics/ Sunlight/ APJ a.Outgoing Feeder a) 415 V Soft Starter for 45 KW motor rating for main Pump - 1 Nos b) Out going feeders to diesel pumps-1 No's B) Incoming Feeder-250A MCCB, 25KA with required RYB Al. Bus bars.
SITC of Diesel engine Control panel with 2 set of battery charger , on/off push buttons , Hooter for all Diesel engine Fire Pumps with required control cables. Make:SGPL/ Pyrotech/ Positronics/ Sunlight/ APJ
SITC of UL listed AR- AFFF 3% foam as IS: 4986:2006 / UL-162. Make: Integrated / KV fire / Newage
Design, supply, erection and testing of SS-316L Inline Balance Pressure Foam Proportionating System consisting of proportioner, spool valves, foam concentrate valve, drain cock valves, duplex gauge, pressure gauge, check valves at foam concentrate inlet, water & foam sensing line, automatic concentrate control valve with flush connection complete in all respect and suitable for out door installation.(Capable for Flow Max - 12000 LPM with 0.5 max. bar pressure drop). Make:Fire Tech /HD Fire
SITC of Above ground Seamless SS316L pipe as per ASTM-A-312, TP-316L, Schedule-20 including cutting, screwing, welding etc. and providing all fittings like elbow, tee, reducer, companion flanges, SS316 nut-bolt, SS washer, EPDM gasket etc as per ASTM-A-403, WP-316L, Schedule-20 / ASTM-A-182, F-316, Class 3000# and including structure supports like clamps, ISMC, ISA, Base plate, hanger, U-Bolt etc. and including cutting holes and chases in brick/RCC wall / slabs complete with External painting with SS pipes painting as per tender specification. The unit rate of pipe shall include the cost of fittings and painting. Make: Jindal / Surya Roshni / TATA
100 NB foam Pump Suction
80 NB- Foam Pump Delivery and up to Propotioner assembly
50 NB - foam fill line
40 NB -Foam Pump Return Line
Instruments
SITC of Pressure Switch in SS316 enclosure with SS316 internals, range 0-25kg/cm2 with three way valve manifold of SS construction and all other accessories & SS pipe tubing. Make: Indfos / Switzer / Wika / Emerson
SITC of Pressure Gauge, Bourdon type, Case- Die cast aluminium with polyethylene paint, movement - Ph bronze, wetted parts - brass, 150mm dial, Range 0 - 30 Kg/cm2, accuracy - +/- 1%. Make: H Guru /General Instruments / Wika /
SITC Level Switch (For Foam tank)Capacitance type, Enclosure - Die cast aluminium with polyethylene paint Electrode - SS316, Insulation on electrode - PVDF, Process connection - SS304. Make: Sigma / Levcon
SITC of Local Push Button Stations with start, stop PB, local/remote switch, auto/manual switch & ammeter
SITC of A351GR.CF8M (SS316) Gate valve, Rising Spindle type with indication of close / open positions, class 300,as per API 600 including SS companion flanges, gasket, SS 316 nut-bolt & washer as per specification. Make: L&T(Audco) / GM Engineering /Advance valves Venus,Zolato,KBL
40 NB SS quick coupling with rubber hose
25 NB ball valve
SITC of A351GR.CF8M (SS316) Non Return valve (bolted cover) Swing check type, as per API594, class 300 including SS companion flanges, gasket, nut-bolt & washer as per specification. Make: L&T(Audco) / GM Engineering /Advance valves Venus,Zolato,KBL
SITC of Casting Strainer of SS 316L, including SS companion flanges, gasket, SS 316 nut-bolt & washer as per specification. End connection as per ANSI B 16,.5 Class 150. Make: Gujarat Autofit / C thru / Multitex / Grand Prix / Otoklin/Nilon
SITC of Stainles steel SS 316L Pressure regulating valve including companion flanges, gasket, SS 316 nut-bolt & washer as per specification. Make: Darling Muesco/ Nirmal/ Sanmar
SITC of Rectangular type Pressure relief valve of SS 316L (Range 16-20 kg/cm2) of size 40 NB including all fixing accessories. Make: Darling Muesco/ Nirmal/ Sanmar
SS 316 drain valve -40 NB/25 NB for foam storage tank , Suction and delivery manifold. Make: L&T(Audco), Flowcehm, Advance valves, Venus,Zolato,KBL
SITC of Foam barrel for 3% AR- AFFF foam storage of solution (Each Cap 200 litre) - with foam concentrate for Ground water Monitor. Make:Integrated / KV fire / Firetech
SITC of Foam barrel for 3% AR- AFFF foam storage of solution (Each Cap 200 litre) - with foam concentrate for testing Purpose. Make: Integrated / KV fire / Firetech
Structural supports including ISA, ISMC, M.S Plates, stiffener plate, u bolts, clamps etc. for piping and cable tray inside pump house complete with corrosion protection as per tender Specifications.(Annuxure-1). Make: SAIL /TATA/Essar/Jindal
SITC of Trolley mounted Foam concentrate tank (for Monitor capacity 2580lpm) of CS Construction (corrosion allowance for plate shall be considered minimum 2mm) with internal 4mm thick FRP lining of effective capacity:500 litre including drain valve etc. with Foam concentrate. Make: Fire Tech / HD Fire / New Age
MVWS FOR LOADING /UNLOADING MANIFOLD SS Super duplex Gate Valve SS with Rising Spindle ,as per API 603 with flange end connection as per ANSI B 16.5 150 # and Nut and Bolt as per ASTM A 193 Gr.B8M .The valve shall be tested as per AP I598. MOC of valve Body, cover & bonnet shall be as per A890GR.F5A, Trim, Body seat, disc shall be UNS J93404. a)MOV With Operating Voltage of 415 V AC 50 HZ and flameproof Enclosure with zone IIA/ II B application and 3-phase squirrel cage motor TEFC class F insulated (temperature rise limited to class B) both for motor and its terminal box, for outdoor duty, the motor shall be provided with anti-condensation heater. b)Actuator shall be provided with motor over-riding feature like hand wheel for emergency manual operation and a limit switch shall be provided whose contacts shall be used in the motor control circuit to forbid the motorized operation during manual operation by hand wheel. Internal wiring shall be tropical grade PVC insulated, stranded copper conductor cable of 10A rating for control circuits and required rating for motor. Make: L&T(Audco), Flowcehm, Advance valves, Venus,Zolato,KBL
25 NB BALL VALVE
SITC of Pressure Gauge, Bourdon type, Case- Die cast aluminium with polyethylene paint, movement - Ph bronze, wetted parts - brass, 150mm dial, Range 0 - 30 Kg/cm2, accuracy - +/- 1%. The instrument shall be suitable for zone IIA / IIB area classification. Make: H Guru /General Instruments / Wika
Providing and fixing a set of UL Listed SS316 MOC Medium Velocity spray nozzle (housing as per A351-CF8M) as per technical specification of Size 1/2" NPT, SS with required Spray angle. Each Nozzle body permanently marked with model number, batch number, spray angle, K-factor & UL mark. Make: HD fire /Tyco/ Viking
SITC of Above ground Seamless SS316L pipe as per ASTM-A-312, TP-316L, Schedule-20 including cutting, screwing, welding etc. and providing all fittings like elbow, tee, reducer, companion flanges, SS316 nut-bolt, washer(80-100micron galvanised)), EPDM gasket etc as per ASTM-A-403, WP-316L, Schedule-20 / ASTM-A-182, F-316, Class 3000# and including structure supports like clamps, ISMC, ISA, Base plate, hanger, U-Bolt etc. and including cutting holes and chases in brick/RCC wall / slabs complete with External painting with SS pipes painting as per tender specification. The unit rate of pipe shall include the cost of fittings and painting. Make: Jindal/ TATA/ Surya Roshni
Flame proof Local control panel of Die-Cast Aluminium construction with Push button and indication lamp for two valve Operation for each manifold. Make: FEPL/Baliga/Flexpro/CEAG/FCG/Sudheer.
Supplying, laying, testing and commissioning of 1100 Volt grade XLPE insulated PVC type aluminium conductor FRLS armoured cables with required accessories. Make: Universal / Havells / RR Cables / Gloster Polycab/KEI
2C x 1.5 mm2 Copper Armoured FRLS Cable for pressure switch connection
Structural supports including ISA, ISMC, M.S Plates, stiffener plate, u bolts, clamps etc. for piping and cable tray inside pump house complete with corrosion protection SUCH AS zinc coated 200 MICRONS. Make: SAIL /TATA/Essar/Jindal
CONTROL SYSTEM FOR TOWER MONITOR
Supply, erection and testing of Flameproof Electrical System for remote Operation of tower monitor. Make:Honeywell/ Siemens / Rockwell/ ABB/ Yokogawa a) Common Modular PLC Based remote control panel With Redundant CPU and Dual redundant Power supply Module for Powering field devices for operation of Tower monitor , Water Curtain Nozzle . Control panel shall be CRCA Construction with tender painting scheme including Control Desk with required joy-sticks, Push-buttons, emergency stop switch, indicator lamps including inside wiring, earthing etc. up to terminals, System mimic diagram for displaying and overall view of configuration of tower monitors at Jetty (Status of tower monitors function to be indicated by LED indicators) including all required accessories. .PLC should have sufficient I/O with Several sensor/actuator Bus networks with Ethernet TCP/IP, Multi-task application software, Extended application-specific functions :Counting/position control, Analog/PID, Math functions, Fuzzy logic, etc, Compact pocket-size modules, Open network-Profibus-DP, Device Net, Fast Ethernet. compliant to IEC 61131. b) PLC panel have provision of connecting Redundant FO cable to connect Local Control Panel . C) Remote panel have provision of fire Pump and foam pump operation and status signal D) Control Wiring shall be - 0.75 sq.mm Copper Flexible wires & all wiring enclosed in PVC channels . E) Separate Grounding bus will be Provided at bottom of the Panel . F) All PLC function shall be tested at Factory before dispatched to site g)Third party interface over MODBUS TCP/IP h)Gas detection i)Communication j) MVW Spray System
Flame Proof Local control panel of Die-Cast Aluminium construction with sufficient I/O Module , Interface module for Control & Operation of ROM & MOV for ROM & Water Curtain system consisting of ,FORWARD, REVERSE, LEFT, Right, Jet & Fog Push Buttons, SS316 , Explosion proof with double compression flameproof glands, suitable for installation in zone IIA/IIB classified area. wire with 25 % spare TB inside. Local control panel connected to PLC panel through Redundant FO cable Local control panel inclusive of: a) Input/Output Cards b) Analogue Input cards for interfacing of gas detector/flame detectors c) Push Buttons d) Indicating Lamps e) MCB's 6TM AND 6 JC Make: Honeywell/ Siemens / Rockwell/ ABB/ Yokogawa
Explosion proof Junction box of Die-cast Aluminium construction complete with all required fixing accessories as per E&I Specification. (JB shall be suitable for installation in zone IIA / IIB classified area). Make: FCG / CEAG/Sudheer / FEPL/ Baliga /Flexpro
Supply , Installation , Testing and commissioning of 6C single mode Fibre optic FRLS armoured Cable, PVC jacket, Armoured for Interconnection. Make: Molex/ Lapp/ Finolex/ Reliance
Supplying, laying, testing and commissioning of 1100 Volt grade armoured Fire Survival cables with required accessories. Make: Eloster / Havells / RPG/Finolex Polycab/KEI
24C x 1.5sq.mm, Cu. Armoured Cable - Control Cable - (RCP to MCC)
4C x 4sq.mm, Cu. Armoured Cable - Power Cable - (MCC to LCP)
12C x 2.5sq.mm Cu. Armoured Cable - Power Cable - (LCP to JB
6P x 1.5sq.mm Cu. Armouted Cable - Control Cable - (LCP to JB)
4C x 2.5sq.mm Cu. Armoured Cable - Power Cable - (LCP to MOV)
5P x 1.5sq.mm Cu. Armouted Cable - Control Cable - (LCP to MOV)
CABLETRAY FRP Ladder / Perforated type cable tray with necessary bands, tees and clamps for fixing. All material shall be FRP. Cable Trays shall be considered with Double Coupler Plates. All Bolts shall be SS 316 .Thickness of the cable tray material shall be 6 mm for 300 mm & above & 4 mm for below 300 mm size. Make: EPP/ Sumip/ Ercon
Structural supports including ISA, ISMC, M.S Plates, stiffener plate, u bolts, clamps etc. for piping and cable tray complete with corrosion protection LIKE ZINC COATING OF 200 MICRONS
VHF- Radio System Make: Motoroloa
Supply, Installation, Testing & configuration of Hand heel units with 1850 mAh li ion, 16 programmable Channels 12.5 kHz / 25 kHz Channel Spacing, 1-5 Watts Power Output, User manual, 2.5" rugged belt clip, Heliflex Antenna, Rapid Charger etc..
Supply, Installation, Testing & configuration of VHF Synthesized Transceiver – REPEATER STATION Frequency range 136Mhz to 174Mhz,12.5/25 KHz Channel Spacing,50 Watts Power Output , Compact Microphone & cable Installation Kit (Trunnion), Power Cable, Front facing internal 4WSpeaker, Meets MIL STD 810. RG 213 U CO-AXIAL CABLE WITH CONNECTORS With GP Antenna 0db.
Supply, Installation, Testing & configuration of VHF Base station with required accociated accessories to full fill the requirement.
Liasioning charge for getting the license for Two Way radios systems Govt. Of India under VPT scope. ( renewable every year for the Two way radio also under VPT scope )
Portable Fire Extinguishers Make: Kanex / Safex / ANSUL / SBJ/ Zenith Fire
Supply, erection, testing & commissioning of Portable fire extinguisher 9 kg Capacity DCP (Dry chemical powder) Extinguishers , MS seamless body, as per IS:15683
75 kg capacity wheel mounted dry chemical powder fire extinguisher , as per IS : 10658/1999
50Lit capacity wheel mounted AFFF foam fire extinguishers as per IS: 13386
4.5 Kg CO2 fire extinguishers
Dismantling of Existing under ground / above ground pipes, Fire awater Pumps and associated accessories, Valves (Gate Valves, Butterfly Valves, etc).
Dismantling includes : Cutting of Pipes and dismattling of Valves Handing over the pipes and Valves to VPT designated location. Dismantling of Electric Pumps and Motor and its associated accessories Replacing of Suction, Delivery, Priming Lines, By Pass Lines Pertaining to proposed New Fire Fighting Pumpsets at New Pump House as per drawings enclosed. Dismantling of old MS works in joists, angles, plates, bracings, pipes of different sizes etc. including cutting rusty bolts and nuts etc. from damaged / corroded structures of jetty and stacking the materials at shore within 150 mtr. lead. Include for loading the dismantled steel materials into truck at Oil Jetty area, carriage of the materials over pucca road lead upto 2-4 Kms. and unload at the VPT Store Division after weighment, stack properly in stack yard etc. as directed including carriage by head load upto a lead of about 30 m of each of the two points. Existing Pipe 450 NB Existing Tower monitor - Structral Steel , height 15 meter Foam Pump and accessories Existing valves Size from 400 NB to 100 NB Exiting Hydrant Valve and Water monitor with Accessories
Civil work
Construction of 20 meter Height RCC civil structure for remote operated monitor with fire proof coating. The top platform of the tower structure shall be 2.5m x 2.5m dimension. The design of RCC structure shall be suitable for wind, sway & siesmic load calculation and calcuation shall be performed on approved licensed software. The tower shall be applied with fire paint UL listed for 2hr fire rating, Min. 7mm thick. The cost shall also include Pile/Open/Raft Foundation as suitable for the given soil load barring capacity. Price for Civil including the following work . Excavation and bacfilling , Civil foundation and operating platform and strair case with hand rail ( concrete ) Design and drawing to be approved by NIT/IIT/Any ICAS member
Tower for Monitor with platform on top of the tower and necessary safety guards, ladder, & mid landing, etc. The tower shall design a taper lattice type steel structure of height 20 m and operating plateform shall be 2.5 m x 2.5 m & the base shall be as per the suitable wind, sway & siesmic load calculation. The calculation shall be performed on approved licensed software. The lattice structure/round pipe structure made from Structural supports including ISA/ISMC/M.S Pipe/M.S Plates/stiffener plate /u bolts/clamps etc. The entire steel structure shall be applied with vermiculite based lightweight fireproof cementitious of thickness corresponding to 2 hours fire rating as per respective UL design number under UL-1709 (XR category) subject to a minimum of 30mm. Vermiculite based lightweight cementitiuos fireproofing system
RCC Pedestal for above ground pipe .( 400 NB ) Price for civil including Excavation and backfilling and PCC footting etc
For 400 NB Pipe Double Pipe Support( RCC civil foundation height 300/400 mm from above FFL ) min 1.5Mtrs width. The scope of work including all related civil works like digging, refilling , making flat PCC all in scope of work.
For 400 NB Pipe Single Pipe Support ( RCC civil foundation height 300/400 mm from above FFL ) min. 900mm width. The scope of work including all related civil works like digging, refilling , making flat PCC all in scope of work.
For 200 NB/150NB/100NB Pipe Single Pipe Support ( RCC civil foundation height 300/400 mm from above FFL ) min. 700mm width. The scope of work including all related civil works like digging, refilling , making flat PCC all in scope of work.
RCC foundation for Fire Water pumps , includes reinforment for founadation Foam pumps and Foam Storage tank
RCC/PCC Foundation for Water monitor Operating Plat form and Hose Box foundation
Excavation and backfilling of Soft Soil for under ground piping
RCC Civil foundation for MS. Platform
Design, Supply, Installation, Testing , loading and unloading of Construction of Control Tower with ( 5Mtrs x 5Mtrs x 22Mtrs with landing outside for stair case with Ground Floor +TOP Floor with 4 feet walk way out side the room ) Design and claculation to be approved by IIT/NIT/Any IACS member below specification to be followed : Boring, providing and installation bored cast-in-situ reinforced cement concrete piles of grade M-30 of specified diameter and length below the pile cap, to carry a safe working load not less than specified, excluding the cost of steel reinforcement but including the cost of boring with bentonite solution and temporary casing of appropriate length for setting out and removal of same and the length of the pile to be embedded in the pile cap etc. by percussion drilling using Direct mud circulation (DMC) or Bailer and chisel technique by tripod and mechanical Winch Machine all complete, including removal of excavated earth with all its lifts and leads (length of pile for payment shall be measured up to bottom of pile cap). 600 mm dia Note: Truck Mounted rotary/TMR/Tubewell boring machine shall not be used . Vertical load testing of piles in accordance with IS 2911 (Part IV) including installation of loading platform by Kentledge/Anchor piles method and preparation of pile head or construction of test cap and dismantling of test cap after test etc. complete as per specification & the direction of Engineer in-charge. Note: 1. Initial and Routine Load Test shall not be carried out by Dynamic method of testing. Note: 2. Testing agency shall submit the design of loading platform for the approval of Engineer-in-charge. Single pile upto 50 tonne Safe capacity Initial test (Test Load 2.5 times the Safe capacity) Vertical load testing of piles in accordance with IS 2911 (Part IV) including installation of loading platform by Kentledge/Anchor piles method and preparation of pile head or construction of test cap and dismantling of test cap after test etc. complete as per specification & the direction of Engineer in-charge. Routine test ( Test load 1.5 times safe load) Earth work in excavation by mechanical means (Hydraulic excavator)/manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out and disposal of excavated earth lead upto 50 m and lift upto 1.5 m, as directed by Engineer-in-charge. CEMENT CONCRETE (CAST IN SITU) Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level :1:4:8 (1 Cement : 4 coarse sand (zone-III) : 8 graded stone aggregate 40 mm nominal size) DESIGN MIX CONCRETE Providing and laying in position machine batched and machine mixed design mix M-30 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer-in-charge. (Note :- Cement content considered in this item is @ 330 kg/cum. Excess/ less cement used as per design mix is payable/recoverable separately).All works upto plinth level
DESIGN MIX CONCRETE Providing and laying in position machine batched and machine mixed design mix M 30 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer-in-charge. (Note :- Cement content considered in this item is @ 330 kg/cum. Excess/ less cement used as per design mix is payable/recoverable separately).All works above plinth level upto floor V level FORM WORK Centering and shuttering including strutting, propping etc. and removal of form for : Foundations, footings, bases of columns, etc. for mass concrete s FORM WORK 5.9 Centering and shuttering including strutting, propping etc. and removal of form for : Suspended slabs, beams, columns etc STEEL REINFORCEMENT 5.22 Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete. Thermo-Mechanically Treated bars of grade Fe-500D or more Top Floor slab min 2m away from main wall that is (7x7 meter area ) with 3 feet sun shed sloped with concrete work only Designed approved by NIT/IIT/Any IACS Member Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor level in all shapes and sizes in :Cement mortar 1:6 (1 cement : 6 coarse sand) 18 mm cement plaster in two coats under layer 12 mm thick cement plaster 1:5 (1 cement : 5 coarse sand) and a top layer 6 mm thick cement plaster 1:3 (1 cement : 3 coarse sand) finished rough with sponge CEMENT PLASTER (IN FINE SAND) 12 mm cement plaster of mix : 1:6 (1 cement: 6 fine sand) Distempering with oil bound washable distemper of approved brand and manufacture to give an even shade : New work (two or more coats) over and including water thinnable priming coat with cement primer sqm 153.45 13.42 Distempering with 1st quality acrylic distemper inside finishing EXTERIOR FINISHING: Finishing walls with water proofing cement paint of required shade : New work (Two or more coats applied @ 3.84 kg/10 sqm)
Providing and fixing water closet squatting pan (Western pan ) with S trap, 10 litre low level white P.V.C. flushing cistern, including flush pipe, with manually controlled device (handle lever) conforming to IS : 7231, with all fittings and fixtures complete, including cutting and making good the walls and floors wherever required: 17.1.1 White Vitreous china Orissa pattern W.C. pan of size 580x440 mm with integral type foot rests wash room to be furnished by tiles at six feet level
Providing and fixing white vitreous china flat back or wall corner type lipped front urinal basin of 430x260x350 mm and 340x410x265 mm sizes respectively with automatic flushing cistern with standard flush pipe and C.P. brass spreaders with brass unions and G.I clamps complete, including painting of fittings and brackets, cutting and making good the walls and floors wherever required :Range of two urinal basins with 5 litre white P.V.C. automatic flushing cistern
Providing and fixing wash basin with C.I. brackets, 15 mm C.P. brass pillar taps, 32 mm C.P. brass waste of standard pattern, including painting of fittings and brackets, cutting and making good the walls wherever require: White Vitreous China Wash basin size 630x450 mm with a single 15 mm C.P. brass pillar tap Providing and laying integral cement based water proofing treatment including preparation of surface as required for treatment of roofs, balconies, terraces etc consisting of following operations: (a) Applying a slurry coat of neat cement using 2.75 kg/sqm of cement admixed with water proofing compound conforming to IS. 2645 and approved by Engineer-in-charge over the RCC. slab including adjoining walls upto 300 mm height including cleaning the surface before treatment. (b) Laying brick bats with mortar using broken bricks/brick bats 25 mm to 115 mm size with 50% of cement mortar 1:5 (1 cement : 5 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge over 20 mm thick layer of cement mortar of mix 1:5 (1 cement :5 coarse sand ) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge to required slope and treating similarly the adjoining walls upto 300 mm height including rounding of junctions of walls and slabs. (c) After two days of proper curing applying a second coat of cement slurry using 2.75 kg/ sqm of cement admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge. (d) Finishing the surface with 20 mm thick joint less cement mortar of mix 1:4 (1 cement :4 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge including laying glass fibre cloth of approved quality in top layer of plaster and finally finishing the surface with trowel with neat cement slurry and making pattern of 300x300 mm square 3 mm deep. (e) The whole terrace so finished shall be flooded with water for a minimum period of two weeks for curing and for final test. “All above operations to be done in order and as directed and specified by the Engineer-in-Charge :
Steel work welded in built up sections/ framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required. In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works S & F Door suitable to marine environment S & F Window/ aluminium frame with glasses Providing and laying vitrified floor tiles in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS: 15622, of approved make, in all colours and shades, laid on 20mm thick cement mortar 1:4 (1 cement : 4 coarse sand), jointing with grey cement slurry @ 3.3 kg/ sqm including grouting the joints with white cement and matching pigments etc., complete. Size 600 X 600 mm Providing and fixing 1st quality ceramic glazed floor tiles conforming to IS : 15622 (thickness to be specified by the manufacturer ) of approved make in all colours, shades except burgundy, bottle green, black of any size as approved by Engineer-in-Charge in skirting, risers of steps and dados over 12 mm thick bed of cement Mortar 1:3 (1 cement: 3 coarse sand) and jointing with grey cement slurry @ 3.3kg per sqm including pointing in white cement mixed with pigment of matching shade complete. Design & built, providing & fixing of industrial grade capsule lift including all fittings, accessories complete as directed by EIC, Lift liesence certificate from the government body under vendor scope. The vendor have responsible till the complete the all works up to VPT satisfactory and hand cover the lift. Make: RK Elevators / Sunrise Lifts /Schiender Top floor 3 wall mount fans, and one two ton split AC , necessary lighting and socket points. Make: LG/VOLTAS/ for split AC and USHA /CROMPTON for fans
Electrical Audit of the entire berth by a competent person under Petroleum rule 114. and OISD guidelines related to Electrical Installations submit to VPT Project In charge 1. Supply of any material must be as per site conditions and with prior approvals from VPT 2)Transportation for contractor’s staff, tools and tackles and consumables to the site is in the scope of contractor. 3) At present there is no power supply at berth. The power supply is in the scope of contractor. 5) . For fabrication of materials at fabrication yard (on shore )supply shall be provided on chargeable basis 6) . The Vendor must visit the site and understand the site conditions and VPT requirement and accordingly Remote control PLC based panel shall be considered. 7) All line items are billable against actual ITEMS ARE FABRICATED AND ERECTED AT SITE
Supply , Installation , Testing and Commissioning of Fire alarm and Control Panel having the Following features: a) Redundant Central Processing Unit ( CPU) b)16 lines 40 character backlit alphanumeric liquid crystal display (LCD) c) Loop ( signalling line circuit) Control Module with loop capacity of max. 250 devices. ( No. of loops : 3 nos.) d) Redundant Power Supply Unit e) Modbus gateway ( Redundant) f) Network Communication Interface for repeter panel. g) 24 hours backup battery and battery charger j) Stand alone enclosure k) Autodialer ( 5nos. dialing) l) Loop expandable to 5 loops Approvals : UL listed / FM / VDS approved. Make: Honeywell / Edwards / Siemens / Tyco / Bosch / SCHRACK
Supply , Installation , Testing and Commissioning of Repeater panel having the same display size and keypads as the Main Fire alarm Panel with required network communication interface unit. Make: Honeywell / Edwards / Siemens / Tyco / Bosch / SCHRACK
FIELD DEVICES
Supplying, Installation, Testing and Commissioning of Addressable Multi-criteria Detector (Smoke & Heat).The intelligent multi criteria detection device shall include the ability to combine the signal of the thermal sensor with the signal of the photoelectric signal in an effort to react hastily in the event of a fire situation. It shall also include the inherent ability to distinguish between a fire condition and a false alarm condition by examining the characteristics of the thermal and smoke sensing chambers and comparing them to a database of actual fire and deceptive phenomena. The detector shall have twin bi-colour LED for 360 deg viewing. Addressing shall be with user friendly rotary decimal switches. Device shall be with standard base. UL Listed. Make: Honeywell / Edwards / Siemens / Tyco / Bosch / SCHRACK
Supply, Installation, Testing & Commissioning of Flame proof Conventional Manual Call Point for outdoor marine application with Stainless Steel(SS-304) hardware, Material, 2Wire : Aluminium Lm6, IP 65, Anti corrosive epoxy powder coated Finish, Cable Entry : 2 x M25, Neoprene Gasket, 24V DC operating Voltage. The line item should include 1 meter length MS channel painted with Fire red colour to mount the MCP along with canopy and Flame proof double compression cable glands & Flame proof MS platted stoppers to shield against rainy conditions and FLP JB with foundation works and related flexible hard conduits till the Hooter. Make: Flamepack / Baliga / Flexpro / Neptune / Airlight/ FEPL/ EX-Protecta
Addressable Monitor Module for monitoring of FLP Manual call point Make: Honeywell / Edwards / Siemens / Tyco / Bosch / SCHRACK
Supply, Installation, Testing & Commissioning of Flame proof Conventional Hooters For outdoor marine application Hooter, FLP, Type: Conventional Area classification: ZONE 1- Gr. IIA/IIB MOC : Aluminium diecast (LM6) IP rating -IP66 - Input Supply :24V DC; Sound level:106dB at 1 meter distance; Tone type: Single tone; Cable Entries: 2Nos 0.75ET; Finish: Epoxy Light grey shade 631/IS-5. With FLP double compression glants and Plugs. Make: Flamepack / Baliga / Flexpro / Neptune / Airlight/ FEPL/ EX-Protecta
Supply, Installation, Testing & Commissioning of Addressable Safe Area Manual Call point. Make: Honeywell / Edwards / Siemens / Tyco / Bosch / SCHRACK
Addressable Control Relay Module for driving of FLP hooters . Make: Honeywell / Edwards / Siemens / Tyco / Bosch / SCHRACK
Addressable Relay Module for AHU tripping & closing of Fire Dampers. Make: Honeywell / Edwards / Siemens / Tyco / Bosch / SCHRACK
Supplying, Installation, Testing and Commissioning of Isolator Module for Isolating short / dewired / loose circuits with automatic resetting arrangement. Isolator Base can also be proposed, however in that case needs to be considered with each detector & module. The device shall have an LED which shall blink in normal state & get steady on activation to monitor the heath status of the device. Addressing shall be with user friendly rotary decimal switches. Module shall be supplied with mounting plate from OEM for ease of installation & maintenance. FLP JB shall be considered. ( if required by system) Make: Honeywell / Edwards / Siemens / Tyco / Bosch / SCHRACK
Supply installation, Testing & Commissioning of Flame Proof Electrical Siren with Horizontal Single Mounting single Phase 220/250V, 2800 RPM 50Hz, AC RPM 50 C/s 1 km range, 1/2 HP, with required accessories like Flame proof double compression cable glands & Flame proof MS platted stoppers to shield against rainy conditions with required junction box. with required starter control panel to start / stop manually from control room or specified locations. Make: Kheraj / Perfect
FLAME AND GAS LEAK DETECTION SYSTEM
HYDROCARBON GAS DETECTORS ( ZONE -1 - EEx'd) Type : Infrared Point type Accessories to be supplied : Calibration cup, Splash guard/dust guard ( SS material), rain guard , flashback arrestor , collecting cone Detector output: 4-20ma Range : 0-100% LEL With display unit Poison resistant Response time : T90</+ 10 seconds Repeatability : +/- 2% FSD IP rating : IP-65 Detector Housing material : SS 316 Zero drift : 2% FSD per year maximum Certification : FM approved/ UL listed Hazardous certification Approval : PESO/CMIFR Ambient Temperature : 0-50degree C ( Detector will be connected to nearest LCP) Make: Drager / Oldham / Crowcon / Gas sensor/ Det- Tronics
FLAME DETECTOR Type: UV/IR Spectral Response: UV: 0.185-0.260 µm; IR: 2.5-3 µm Detection Range: For Methane 16 Feet Response Time: 5 seconds; High Speed 150 msec response to saturated signal Adjustable time delay up to 30 seconds Sensitivity Range: up to 15 meters Field of view: Horizontal: 100 degrees, Vertical: 95 degrees Should have Automatic and Manual in-built test to ensure continued reliable operation Detector output: 4-20ma Should have Heated window for operation in harsh weather conditions Operating temperature: -40 OC to +70 OC Power supply: 18 to 30 V DC Cable Entry: 2 entries Should be EMI/ RFI protected as per EN61326-3 and EN61000-6-3 Outputs: i) Relays for alarm ii) fault indication iii) 4-20 mA iv) HART protocol v) RS-485 output Should have a special logic circuit to help prevent false alarms caused by solar radiation. Enclosure: Explosion proof Ingress Protection: IP 66 Certification : FM approved/ UL listed Hazardous certification Approval : PESO/CMIFR ( Detector will be connected to nearest LCP) Make: Tyco / Agni Controls/ Spectrex/ Rezontech / Gas sensor
PUBLIC ADDRESS SYSTEM
Supply, Installation, Testing & Commissioning of Flame Proof-Exf T6 IP 65 Speaker with 30W rated and 15W/20W/25W line matching transformer with Cast Aluminium LM 6, ZoneI & II, Gas groups Class-I & IIA, IIB, IIC, Neoprane Gasket, SS, 100V / 70V Line transformer, Sound output 115db, earthing terminals, input terminal blocks, Pilfer proof, FLP JBs with Mounting MS stand corrosion resistance for Hooter and JB with foundation works and related flexible hard conduits till the Hooters. Approval CCE & BIS, IS 2148. Make: Baliga
Supply, Installation, Testing & Commissioning of 6W wall Mount Speaker with line matching transformer and mounting accessories for indoor application.(For office area etc). Make: Honeywell/ Bosch/Aties
Supply, Installation, Testing & Commissioning of 6 Zone PA controller built in amplifier . And shall have pre-recorder massage facility to evacuate in case of emergency conditions, and as per technical specification. Make: Honeywell/ Bosch/Aties
Supply, Installation, Testing & Commissioning of 240 / 480W Power Amplifier. Make: Honeywell/ Bosch/Aties
Supply, Installation, Testing & Commissioning of 6 Zone Call Station with Goose neck Mic. with interconnecting cable. Make: Honeywell/ Bosch/Aties
Supply & Fixing of PA Rack .( Height as per site conditions) with interconnecting cable and cable power manager. Make: Honeywell/ Bosch/Aties
Supply, Installation, Testing & Commissioning of Music DVD Player with interconnecting cable. Make: panasonic / Philips
CLOSED CIRCUIT TELEVISION
Network Video Recorder ( NVR)
The storage solution shall be NVR based with Hot swappable of hard drive and hot spare redundancy (N+1). The actual estimated storage requirement shall be worked out as per the number of cameras at 10 fps, 4CIF resolution for 45 days storage. The contractor shall propose the best cost effective solution for storage with reference to the parameters mentioned in the technical specification. The contractor shall furnish the backup calculation sheet for storage while quoting. Make: Axis/ Bosch/Interlogix/ Pelco
Video Management Software:
The Video Management System shall be a software based solution running on SMS server and communicating over Ethernet network using the TCP/IP network protocol. The proposed solution shall be based on the latest compatible Windows Server Operating System. The NVMS shall sustain full operation using CIF, 2CIF, VGA, 4CIF, 800 x 600 (0.5 m pixel) and Megapixel video resolutions (upto 5 MP ). It shall support all types of cameras and latest compression technology and Onvif compliant. The contractor shall propose his best solution to meet the requirement. The cost shall include the required licenses to meet the requirement. Make: Axis/ Bosch/Interlogix/ Pelco
IP Based Joystick Controller for PTZ Cameras. The same should be FCC & UL listed. Make: Axis/ Bosch/Interlogix/ Pelco
MS poles for outdoor cameras, made out of 5mm thick, 80mm dia pipe with zinc chromite primer & powder coating of suitable shade along with Outdoor IP 65 rated Flameproof Junction box for termination, Power supply & module fixing. Total Pole height including pedestal = 5Mts. Make: Local
F) NETWORKING ACCESSORIES
Supply, Installation , Testing and Commissioning of 24 ports , 10/100/1000Base-T ports + 4 SFP ports Metro Ethernet Switch and shall be rack mountable with SMPS power supply & other termination. The switch shall have 1 Gigabit port to communicate with other switches. Make: Moxa / Dlink/ Net gear / Cisco/ Hearschmann
Supply, Installation , Testing and Commissioning of 8 ports , 10/100/1000Base-T ports + 2 SFP ports Metro Ethernet Switch and shall be rack mountable with SMPS power supply & other termination. The switch shall have 1 Gigabit port to communicate with other switches. Make: Moxa / Dlink/ Net gear / Cisco/ Hearschmann
Supply, Installation , Testing and Commissioning of Wall Mount enclosure (9U x 550 W x 500 D) , Front Glass Door (tinted, Toughened) with Lock & Key, 2 pairs of 19" Mounting Rails with U-Marking Welded Side Walls Standard Accessories: 1U Cable Manager (1), Hardware Packet (1 Pkt) 6 Socket 5 Amp. Power Distribution Unit (1 No) Roof Mounted Fan Unit / 90 CFM /230V AC (1 No). Make: Moxa / Dlink/ Net gear / Cisco/ Hearschmann
Supply, Installation , Testing and Commissioning of LIU 24 PORT Rack Mount - Loaded (SC) SM. Make: Local
Supply, Installation , Testing and Commissioning of Work station: 70 inch Monitor OS comprising Intel Xeon Processor, Quad Core 3.2 GHz. 8 GB ddR3 Ram, 500GB SATA Hdd, USB Ports, Keyboard & Mouse. Make: HP/ DELL
CABLES AND ACCESSORIES
Supply, Installation , Testing and Commissioning of the following size of Armoured Cables and type
1P X 1.5 Sq.mm Fire Survival cable for Manual call point Loop connections. Make: Polycab/Technoflex/KEI
2C X 2.5 Sq.mm FS cable for Hooter Loop connections. Make: Polycab/Technoflex/KEI
1P X 1.5 Sq.mm Fire Survival cable for FLP Speakers connections. Make: Polycab/Technoflex/KEI
Supply, Installation, Testing, and commissioning of GI Conduit applicable for marine applications with required foundation works and fittings. Make: ISI mrked
Cat - E Ar. cable for Camera integration. Make: Dlink / Belden / Radiant
3C X 2.5 Sq.mm FS Power cable for Network Switches. Make: Polycab / Bonton /Deepanja/ Polycab / Radiant
Supply , Installation , Testing and commissioning of 6C single mode Fibre optic FRLS armoured Cable, PVC jacket, Armoured for Interconnection for CCTV & Repeater Panel. Make: Molex/ Lapp/ Finolex/ Reliance
Bridge and Roof Co India Ltd
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid