Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹20.8 LAccepted-Finance MEERUT UTTAR PRADESH 250110 INDIA UDYAM UP 56 0008622 | MEERUT | UTTAR PRADESH | 250110 | ₹20.8 L | 1 | Accepted-Finance O.K. |
| 2 | 2₹24.3 LAccepted-Finance | ₹24.3 L | 2 | Accepted-Finance O.K. |
| 3 | 3₹24.4 LAccepted-Finance | ₹24.4 L | 3 | Accepted-Finance O.K. |
| 4 | 4₹24.5 LAccepted-Finance | ₹24.5 L | 4 | Accepted-Finance O.K. |
Tender Value
Refer Docs
EMD Value
₹25,000
Closing Date
4 Jan 2021, 5:00 pmClosed
S.E., E.T.C., Bareilly
Superintending Engineer Transmission Campus Near L.I.C. Office Rampur Garden, Bareilly
Construction of 132KV Amariya Feeder-I and II Bays by conversion of 132KV T.B.C. Bay into Feeder Bay, Construction of 132KV T.B.C. Bay, strengthening of 132KV Main Bus Bar to Twin ACSR Moose Conductors at 132KV S/S Pooranpur under E.T.D.-II, Bareilly
2020_UPTCL_536206_1
E-Tender No. 39/W/ETC(B)/ 2020-21
Open Tender
Electrical Works
120 days
Bareilly
Please refer Tender documents.
2 documents required · 2 mandatory
₹11,800
A/c No 10897666087 IFSC SBIN0000615 S.B.I. Bly
₹25,000
5 Jan 2021
8 Dec 2020
5 Jan 2021
8 Dec 2020
4 Jan 2021
8 Dec 2020
8 Dec 2020 - 4 Jan 2021
Amount
Construction of 132KV Amariya Feeder - I & II Bays by conversion of existing 132KV T.B.C. Bay into Feeder Bay and Construction of new 132KV T.B.C. Bay at new place including extension & strengthening of 132KV Main Bus Bar of Single ACSR Moose Conductor to Twin ACSR Moose Conductors and Providing of Periphery Lighting arrangement in extended Switchyard alongwith other associated works at 132KV Sub Station Pooranpur, with all Cost of Men, Materials, Misc. Consumables, T&Ps etc. Required for Satisfactory Completion of the Work as per Technical Specifications and Direction of the Supervising Engineer as per Site Requirement and Details below :
(1) Supply of 5 No. U-Bolted type Single Tension Fitting Assembly with Turn Buckle, suitable for Twin ACSR Moose Conductors & 132KV Bus Bar Disc Insulator String comprising of 10 No. 70 KN Disc Insulators, complete with Hardware Fittings, D-Shackle, Socket Eye, Ball Link, Yoke Plate, Tension Clamp etc., as per Technical Specifications & Sample.
(2) Supply of 5 No. U-Bolted type Single Tension Fitting Assembly without Turn Buckle, suitable for Twin ACSR Moose Conductors & 132KV Bus Bar Disc Insulator String comprising of 10 No. 70 KN Disc Insulators, complete with Hardware Fittings, D-Shackle, Socket Eye, Ball Link, Yoke Plate, Tension Clamp etc., as per Technical Specifications & Sample.
(3) Supply of 5 No. U-Bolted type Single Tension Fitting Assembly, suitable for Single ACSR Zebra Conductor & 132KV Bus Bar Disc Insulator String comprising of 10 No. 70 KN Disc Insulators, complete with Hardware Fittings, D-Shackle, Socket Eye, Ball Hook, Tension Clamp etc., as per Sample.
(4) Supply of Spacer, suitable for Bus Bar of Twin ACSR Moose Conductors with 250 mm Spacing and duly made of LM-6 Aluminium Alloy, complete with 12 mm dia. HDG Bolts, Nuts, Spring & Plain Washers, as per Technical Specifications & Sample.
(5) Supply of Spacer, suitable for Jumper of Twin ACSR Zebra Conductors with 100 mm Spacing and duly made of LM-6 Aluminium Alloy, complete with 12 mm dia. HDG Bolts, Nuts, Spring & Plain Washers, as per Technical Specifications & Sample.
(6) Supply of Spacer, suitable for Jumper of Twin ACSR Panther Conductors with 100 mm Spacing and duly made of LM-6 Aluminium Alloy, complete with 12 mm dia. HDG Bolts, Nuts, Spring & Plain Washers, as per Technical Specifications & Sample.
(7) Supply of PG Clamp duly made of LM-6 Aluminium Alloy, suitable for ACSR Moose to ACSR Moose Conductor, complete with 4 No. 16 × 90 mm size G.I. Bolts, Nuts, Spring & Plain Washers, as per Sample.
(8) Supply of PG Clamp duly made of LM-6 Aluminium Alloy, suitable for ACSR Moose to ACSR Zebra Conductor, complete with 4 No. 16 × 90 mm size G.I. Bolts, Nuts, Spring & Plain Washers, as per Sample.
(9) Supply of PG Clamp duly made of LM-6 Aluminium Alloy, suitable for ACSR Moose to ACSR Panther Conductor, complete with 4 No. 16 × 90 mm size G.I. Bolts, Nuts, Spring & Plain Washers, as per Sample.
(10) Supply of PG Clamp duly made of LM-6 Aluminium Alloy, suitable for ACSR Zebra to ACSR Zebra Conductor, complete with 4 No. 16 × 90 mm size G.I. Bolts, Nuts, Spring & Plain Washers, as per Sample.
(11) Supply of PG Clamp duly made of LM-6 Aluminium Alloy, suitable for ACSR Panther to ACSR Panter Conductor, complete with 3 No. 16 × 75 mm size G.I. Bolts, Nuts, Spring & Plain Washers, as per Sample.
(12) Supply of 132KV Isolator Bi-Metallic Terminal Connector duly made of LM-6 Aluminium Alloy, suitable for 132KV Isolator & Twin ACSR Zebra Conductors, complete with 4 No. 12 mm size G.I. Bolts, Nuts, Spring & Plain Washers, as per Technical Specifications & Sample.
(13) Supply of 132KV Isolator Bi-Metallic Terminal Connector duly made of LM-6 Aluminium Alloy, suitable for 132KV Isolator & Twin ACSR Panther Conductors, complete with 4 No. 12 mm size G.I. Bolts, Nuts, Spring & Plain Washers, as per Technical Specifications & Sample.
(14) Supply of 132KV C.B. Terminal Connector duly made of LM-6 Aluminium Alloy, suitable for 132KV C.B. & Twin ACSR Zebra Conductors, complete with 4 No. 12 mm size G.I. Bolts, Nuts, Spring & Plain Washers, as per Technical Specifications & Sample.
(15) Supply of 132KV C.B. Terminal Connector duly made of LM-6 Aluminium Alloy, suitable for 132KV C.B. & Twin ACSR Panther Conductors, complete with 4 No. 12 mm size G.I. Bolts, Nuts, Spring & Plain Washers, as per Technical Specifications & Sample.
(16) Supply of 132KV C.T. Bi-Metallic Terminal Connector duly made of LM-6 Aluminium Alloy alongwith Bi-Metallic Sleeve / Plate, suitable for 132KV C.T. & Twin ACSR Zebra Conductors, complete with 4 No. 12 mm size G.I. Bolts, Nuts & Spring / Plain Washers, as per Technical Specifications & Sample.
(17) Supply of 132KV C.T. Bi-Metallic Terminal Connector duly made of LM-6 Aluminium Alloy alongwith Bi-Metallic Sleeve / Plate, suitable for 132KV C.T. & Twin ACSR Panther Conductors, complete with 4 No. 12 mm size G.I. Bolts, Nuts & Spring / Plain Washers, as per Technical Specifications & Sample.
(18) Supply of 132KV Post Insulator Clamp duly Made of LM-6 Aluminium Alloy, suitable for 132KV Post Insulator & Twin ACSR Zebra Conductor, complete with G.I. Bolts, Nuts, Spring & Plain Washers, as per Sample.
(19) Supply of 132KV Post Insulator Clamp duly Made of LM-6 Aluminium Alloy, suitable for 132KV Post Insulator & Twin ACSR Panter Conductor, complete with G.I. Bolts, Nuts, Spring & Plain Washers, as per Sample.
(20) Opening of existing Jumpers of Single ACSR Panther Conductor between existing 132KV Main Bus Bar to 132KV BI and 132KV BI to other Eqiupments in 5 No. 132KV Bays. (1 Job per Bay)
(21) De-Stringing & Dismantling of existing 132KV Main Bus Bar of Single ACSR Moose Conductor including De-hoisting of Disc Insulator Tension String with Tension Fitting from Gantry alongwith Shifting of the old Conductors, Tension Fittings etc. from Switchyard to Stores at the Sub Station. (1 Job per Phase per Section)
(22) Laying & Re-Stringing of 132KV Main Bus Bar of Twin ACSR Moose Conductors including Hoisting of Disc Insulator Tension String with Tension Fitting alongwith Shifting of the Conductors, Tension Fittings, Spacers etc. from Stores at the Sub Station to Switchyard. (1 Job per Phase per Section)
(23) Fixing of Spacers between Twin ACSR Moose Conductors of above newly Laid 132KV Main Bus Bar.
(24) Dismantling of 132KV B.I. Installed in existing 132KV T.B.C. Bay.
(25) Opening of Control Cables Termination and Taking Out the Control Cables of 132KV B.I. & C.B. of existing TBC Bay.
(26) Dismantling of Following Equipments / Items from old 132KV Pilibhit Feeder Bay after due Opening of Jumpers, Cutting of Earthing, Opening of Cable Terminations etc. including their Shifting from Switchyard to Safe Storage Place at the Sub Station :
(a) 132KV C.T.
(b) 132KV P.T.
(c) 132KV L.A.
(d) 132KV C.T. Junction Box
(e) 132KV P.T. Junction Box
(27) Erection of Following Structures & Equipments including their Shifting from Storage Place at the Sub Station to Erection Site :
(a) Lattice type Main & Aux. Structures
(b) 132KV SF6 C.B.
(c) 132KV C.T.
(d) 132KV P.T.
(e) 132KV L.A.
(f) 132KV Bus Isolator with associated PIs
(g) 132KV Line Isolator with associated Earth Blades & PIs
(h) 132KV Tandem Isolator with associated PIs
(i) 132KV Post Insulator
(j) 132KV C.T. Junction Box
(k) 132KV P.T. Junction Box
(l) 132KV Double Feeder Control Panel
(m) 132KV Distance Protection Panel
(28) Stringing of 132KV Jack Bus Bar of Single ACSR Zebra Conductor to Interconnect the Split 132KV Transfer Bus. (1 Job per Phase per Section)
(29) Jumpering of Equipments of Following 132KV Bays with the help of Twin ACSR Moose / Zebra / Panther Conductors to Connect the Bus Bar Conductors of 132KV Main Bus & 132KV Transfer Bus with Equipments and Equipments to Equipments with the help of suitable Clamps / Connectors including, Cutting, Bending, Shaping etc. of the Conductor as per Site Requirement :
(a) Jumpering of 132KV Amariya - I & II Feeder Bays with Twin ACSR Zebra Conductors. (1 Job per Bay)
(b) Jumpering of 132KV TBC Bay with Twin ACSR Zebra Conductors. (1 Job per Bay)
(c) Jumpering of 132KV side of 40MVA Transformer - I & II Bays, 132KV Pilibhit & Pooran Pur TSS Feeder Bays with Twin ACSR Panther Conductors. (1 Job per Bay)
(30) Laying of Following sizes Control Cables in Cable Trenches from Control & Relay Panels in Control Room to various Equipments, Junctions Boxes etc. in Switchyard as per Cable Schedule including Shifting of Cables in Drums from Storage Place at the Sub Station to Erection Site and Shifting Back the Balance Cables to Stores at the Sub Station :
(a) 2C x 2.5 mm2
(b 4C x 2.5 mm2
(c) 6C x 2.5 mm2
(31) Interconnection & Termination of various sizes above Laid Control Cables between Feeder C&R Panel / DPP to various Equipments & Equipments to Equipments in Following 132KV Bays including Extending D.C. Supply from DCDB and A.C. Supply from ACDB to C&R Panel / DPP and various Equipments including Making necessary Holes in Gland Plates, wherever Required alongwith Providing & Fixing of Appropriate sizes Cable Glands, Providing of Ferrules for each Core of the Cables, then Termination with Crimping type Copper Lugs alongwith Preparation of Inter-Connection Drawing and Commissioning of the Bay in Co-ordination with T&C Wing including Providing of 2 Sets of Hard Copies of as Executed Inter-Connection Drawing. (1 Job per Bay) :
(a) Cable Termination in 132KV Amariya Feeder - I & II Bays
(b) Cable Termination in 132KV T.B.C. Bay
(32) Making of Shielding Mesh for 132KV LAs in 132KV Amariya Feeder - I & II Bays by Fabrication of 3 Meter Long Electrodes with 36 mm dia. M.S. Rod Bar having 150 mm long Conical Shape and then its Piercing Vertically in the Ground with Top 500 mm below Ground Level, Jointing the Electrodes with 75 × 10 mm size M.S. Flat by Welding for making of Mesh, Connecting the Shielding Mesh with Main Earth Mat at 2 Places and finally, Painting of the Shielding Mesh / Earthing Strips with Anti-Corrosive Paint, with due Digging of Earth / Trench & its Back Filling. (1 Job per Bay)
(33) Earthing by Cutting, Straightening & Laying 500 mm below Inside Ground & above Ground of Following sizes M.S. Flat to Provided by the Department for Diagonal / Double Earthing of the Main & Aux. Structures, Equipments and Cable Trenches including Welding with Main Earth Mat and with the Object to be Earthed including Excavation of Trenches & its Back Filling etc. as per Details below :
(a) Earthing of LAs with 75 × 10 mm size M.S. Flat
(b) Earthing of Main & Aux. Structures and Equipments (CBs, Isolators, CTs, PTs, C&R Panel, DPP, Junction Boxes etc. with 50 × 6 mm size M.S. Flat
(c) Earthing of Cable Trench with 25 mm × 6 mm / 25 × 5 mm size M.S. Flat
(34) Painting of M.S. Earthing Strips by Rubbing with Sand Paper & Wire Brush, then Painting with 1 Coat of Red Oxide Primer & 2 Coats (The 2nd Coat of Paint shall be Applied at the Gap of 48 hrs. when 1st Coat of Paint is Done & Checked by concerned J.E. / S.D.O.) of 1st Quality Synthetic Enamel Paint of Asian / Berger / Nerolac make in Bus Green Colour as per Details below :
(a) 75 × 10 mm size M.S. Earthing Strip in Bus Green Colour
(b) 50 × 6 mm size M.S. Earthing Strip in Bus Green Colour
(c) 25 × 6 mm / 25 × 5 mm size M.S. Earthing Strip in Bus Green Colour
(35) Providing of 3 Phase L.T. A.C. Supply Cubicals of size 1200×600×500 mm with Hinged Door and Proper Locking Arrangement duly made of 16 SWG M.S. Sheet and Painted with Grey Colour Synthetic Enamel Paint. The L.T. A.C. Supply Cubical should be Fitted with 3 No. 100 Amp. Aluminum Bus Bar (3 Phase + Neutral), 5 No. 32 Amp. TPN MCB, 6 No. 40 Amp. DP MCB, 40 No. Link type Terminal Bock, Cable Glands etc. with Internal Wiring and then Installation of each L.T. A.C. Cubical on M.S. Angle Frame Structure after due Fabrication with the help of Scrap M.S. Angles to be Provided by the Department Free of Cost and Grouting of Legs of the M.S. Angle Frame Structure in the Ground with C.C. Mixture and Painting of the M.S. Angle Frame Structure with Synthetic Enamel Paint. (1 Job per L.T. A.C. Cubical)
(36) Earthing of L.T. A.C. Supply Cubical with Providing & Fixing of 600 × 800 × 8 mm size G.I. Plate with its Top At Least 3 Meter below the Ground Level with 20 mm dia. G.I. Pipe & Funnel for Watering, 1 No. 8 SWG G.I. Wire Earthing Lead etc. with Alternate Layer of Charcoal / Coke and Salt At Least 150 mm Thick Around it.
(37) Providing, Erection & Grouting of M.S. Round Pole of 9 Meter Long duly made of ‘B’ Class M.S. Pipe (114.3 mm dia. × 4.5 mm × 5.0 Meter + 88.9 mm dia. × 3.65 mm × 2.0 Meter + 76.1 mm dia. × 3.25 mm × 2 Meter) with Base Plate by Concreting in the Ratio of 1:4:8 with Cement, Coarse Sand & 40 mm Brick Ballast Mixture in size of 450 × 450 × 1900 mm and Plastering of 300 mm Length of Concrete above the Ground Level including Excavation, Back Filling, Curing etc. alongwith Earthing of the Pole with M.S. Electrode.
(38) Providing of Junction Box of size 280 × 225 × 150 mm duly made of 16 SWG Sheet and Painted with Smoke Grey Colour Synthetic Enamel Paint and Fitted with 1 No. 6 Amp. SP MCB on Anodized M.S. Channel, 1 No. Bakelite Fuse Fitting with 6 Amp. NS 6 type HRC Fuse, 1 No. Copper Neutral Link, Bakelite Terminal Block of 4 Terminals, Cable Glands suitable for 2C × 2.5 mm2 / 4C × 2.5 mm2 size Incoming / Outgoing Control Cables etc., then Installation of Junction Box on M.S. Round Pole at designated Height with the help of suitable M.S. Clamps alongwith Earthing of the Junction Box with 12 SWG G.I. Wire including Cable Terminations with Satisfactory Testing & Commissioning.
(39) Providing & Grouting of G.I. Pipe duly made of 35 mm dia. 2.5 Meter Long ‘B’ Class Pipe and Bent at One End by Quarter Circle in 0.5 Meter through Concrete Plinth for Safe Entry of Cables in the Junction Box duly installed on M.S. Round Pole.
(40) Providing & Fixing of G.I. S.L. Pole Bracket duly made of 40 mm dia. 1.2 Meter Long ‘B’ Class Pipe and Bent at One End by Quarter Circle in 1.0 Meter at an Angle of 300 for Fixing of 150 Watt LED Street Light Luminaries Fittings on M.S. Round Pole with help of M.S. Clamps.
(41) Providing & Fixing of 150 Watt L.E.D. Street Light Luminaries Fittings of Philips / Compton Greaves / Havells make in Single Piece Die Cast Aluminium Alloy Housing with Pot Optics Reflector & Toughened Clear Glass Cover with Frame for Lamp Compartment inlcuding Cable Terminations.
(42) Painting of M.S. Round Pole with 1 Coat of Red Oxide Primer and 2 Coats of Zinc Rich Aluminium Paint of 1st Quality of Asian / Nerolac / Burger. (1 Job per Pole)
(43) Making of 3 No. Strips of 50 mm width at the Height of 450 mm from the Plinth with P.O. Red Colour in Botton & Top Strips and with White Colour in Middle Strip on each M.S. Round Pole, then Making of 150 mm dia. Circle and Writing the No. of the Pole in the Circle. (1 Job per Pole)
(44) Laying 3½ × 70 / 50 mm2 LT Power Cable, 50 cm below the Ground Level after Excavation of Trench, Laying the 1st Class Brick Lining, Filling of River Sand Along & Over the Cable, then Back Filling & Leveling the Trench after Laying of Cable. The Work also includes Termination of Cable on both sides with Crimping of Lugs.
(45) Laying of 2C × 2.5 mm2 / 4C × 2.5 mm2 size Control Cables from L.T. A.C.D.B. Cubical to various Junction Boxes for Switchyard Lighting through Excavated Trench of size 300 × 600 mm, Covering the Cables with River Sand & Brick Lining Along & Over the Cable, then Back Filling & Leveling of the Trench after Laying of Cables.
(46) Laying of above Control Cables form L.T. Lighting Junction Box to LED Street Light Fittings through inside the M.S. Pole and outside the Pole by Clamping with suitable M.S. Strip Clamp with Proper Dressing etc.
(47) Providing & Fixing of Cable Marker duly made of Cast Iron.
LASHANI ENTERPRISES
M/S JAI SHREE ENTERPRISES
M/s S.S. Refregeration
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Download all tender documents and submit your bid