Loading…
Loading…
Tender Value
₹45 L
EMD Value
₹45,000
Closing Date
13 Jul 2026, 6:00 pm
Similar tender results from the same govt authority in the past 3 years.
DGVCL - Raipipla Division office
Tender for the UG Cable work for Wire Free City and other scheme work of Rajpipla-1 SDN (also in any other sdn of Rajpipla Dn if required) for under Rajpipla Division
316140
E-82/2026-27
Open
Electrical and Maintenance Works
Narmada
2 documents required · 2 mandatory
₹2,360
DGVCL
₹45,000
20 Jun 2026
20 Jun 2026
20 Jun 2026
13 Jul 2026
20 Jun 2026
ARC for Laying,Testing & commissioning of UG Cable work (XLPE Cable to be supplied by DGVCL).
SR NO PARTICUAR WORK QTY UNIT RATE AMOUNT
Labour charge for excavation of cable trench of 400mm width x 1200mm depth, in any type of soil for
1 laying of cable of size up to 240 mm2(For additional cable 200 mm additional width shall be considered i.e. MTR
half trench length is to be considered)
Labour charge for excavation of cable trench of 600mm width x 1200mm depth, in any type of soil for
2 laying of cable of size up to 240 mm2(For additional cable 200 mm additional width shall be considered i.e. MTR
half trench length is to be considered)
Labour charge for excavation of cable trench of 400mm width x 1500mm depth, in any type of soil for
3 laying of cable of size up to 240 mm2()For additional cable 200 mm additional width shall be considered i.e. MTR
half trench length is to be considered)
Labour charge for laying of 11 kV / 22 kV Meter XLPE Cable of size up to 240 mm2 & preparation
of sand layer 100mm thick, in the cable trench & covering the cable with 150 mm dia (Outer), thickness
25 mm, 1.0 meter long RCC half round muffs and providing and fixing of 4inch width yellow colour
polyethylene tape with printing "CAUTION ELECTRIC CABLE BELOW" at 0.75 m depth from ground
surface after laying cable in trench. This will provide indication that electric cable is passing underground
so as to protect cable from mechanical injuries, refilling the same, as per Instruction of Engineer in
Labour charge for horizontal drilling using MeterAuger machine without damage to surface road at
max 2.0 mtrs depth & putting of 6.11 kg/cm2 , class-4,Green color, 110mm O.D. , 8.5mm thickness
H.D.P.E. pipe confirms to IS 4984-1987(3rd revision) and BIS certification and laying of 11KV/22KV XLPE
cable of size up to 240 mm2 in HDPE pipe, as per Site Condition (excluding cost of pipe). The detail map
obtained from HDD machine and excel sheet(hard and soft copy) indicating the respective depth
anddistance from adjacent landmark for each segment for HOD is must require to be submitted. HOD
to be carried out at depth1.5 mtrs to 2.0 mtrs as per site conditionsand as per instruction of EIC
Labour charge for horizontal drilling manually without damage to surface road at max 2.0 mtrs
depth & putting of 6.11 kgjcm2 , class-4,Green color, 110mm 0.0. ,8.Smm thickness H.D.P.E. pipe
confirms to IS 4984-1987(3rd revision) and BIS certification and laying of 11 KV/22KV XLPE cable of
size up to 240 mm2 size, as per Site Condition (excluding cost of pipe). The detail map and excel sheet
(hard and soft copy) indicating the respective depth and distance from adjacent landmark for each
segment of cable to be submitted. Drilling to be carried out at depth Minimum 1.2 mtrs to2.0 mtrs as per
Supply of 6.11kg/cm2 , class-4,Green color,110mm 0.0. , 8.5 mm thickness H.D.P.E. pipe confirms to
7 IS 4984 and SIS certification for laying of underground 11 KV/22KV XLPE cable up to 240 mm2 size MTR
Labour work for RCC concreting on disputedlocation and repairing of damage portion of
road crossing for the work carried out for roads crossing as well as concreting &
muffing of poles including all materials (1:2:4)
Providing & fixing concrete stone routemarker of 300 mm width x 150 mm thick x 650 mm height
embedded in earth at least 300 mm below & 350 mm above ground level respectively at distance
approx. 50 meters along the length of cable. The RCC concreting (1:2:4)(a" necessary materials will be in
bidder's scope) of route marker is to be carried out 300 mm width x 150 mm thick x 300 mm below ground
9 level as per instruction of EIe. The route marker should be with name of company with approved NO
yellow colour-OGVCL. The distance from marker to cable and cable depth with feeder name etc.,
marked with arrow sign is to be painted on it.The route marker is to be fixed at location near to any fixed
permanent location (not necessary to fix exact on top of cable) as per instruction EIC
Erection of D.P. (double pole) structure No using 9 / 11 Mtr. RSJ pole with cable connection
arrangement along with fitting of necessary fabrication for llKV cable including excavation of pit &
10 refilling of earth as per instruction of EIe. (Exclusive of NO
concretinq & muffing of poles)
Erection of Single pole structure using 9 to 11 Mtr RSJ pole with cable connection arrangement along with
11 fitting of fabrication for 11KV/22 KV cable including excavation of pit & refilling of earth as per instruction NO
of EIC (Excusive of concreting and muffing of Pole)
Erection of D.P (Double Pole) structure using 8 mtr PSC Pole with cable connection arrangement along with
12 fitting of necessary fabrication for 11 kv Cable including excavation of pit & refilling of earth as per NO
instruction of EIC
Erection of Single pole structure using 8 Mtr PSC pole with cable connection arrangement along with
13 fitting of fabrication for 11KV/22 KV cable including excavation of pit & refilling of earth as per instruction NO
of EIC (Excusive of concreting and muffing of Pole)
Labour charge for erecting of 11 kV / 22 kV Meter XLPE cable of size up to 240 mm2 on DP Structure
14 with fixing of 02 Nos polymercleats on top and middle part. Polymer cleats,nut bolt etc provided by per job
Providing and fixing of 6.11 kg/cm2 , class-4,Green color, 110mm O.D. , 8.5mm thickness H.D.P.E.
pipe confirms to IS 4984-1987(3rd revision) and BIS certification on the erected DP structure for the
mechanical protection of cable by inserting the cable inside HDPE Pipe.The HDPE Pipe shall be erected in
such a way that 300 mm shall be below ground level and the rest 2700 mm shall be supported on DP
Structure witg 01 nos of polymer cleat.All material including polymer cleat and nut bolt provided by
Providing and fixing of pipe type earthing from 80 mm dia class-B GI pipe with pit to be filled with salt &
coke and construction of chamber as per DGVCL drawing No.DG/100 for DP and cable. Cable. The Earthing
pit should be joined with G.I.strip of size 1 " Widh X 2 mm thick.All material GI Pipe ,Coke ,Salt etc will be
supplied by bidder
Supply & fixing of heat shrink type end terminations (outdoor) for 11kV 3C x 185 mm2 size XLPE cable.
(Using approved make outdoor type cable kit as per DGVCL technical specification)
SR NO PARTICUAR WORK QTY UNIT RATE AMOUNT
Supply & fixing of heat shrink type end terminations (outdoor) for 22 kV 3C x 185 mm2 size XLPE cable.
(Using approved make outdoor type cable kit as per DGVCL technical specification)
Supply & fixing of heat shrink type end terminations (indoor) for 11kV 3C x 185 mm2 size XLPE cable.
(Using approved make outdoor type cable kit as per DGVCL technical specification)
Supply & fixing of heat shrink type end terminations (indoor) for 22 kV 3C x 185 mm2 size XLPE cable.
(Using approved make outdoor type cable kit as per DGVCL technical specification)
Supply & fixing of heat shrinkable straight through jolnt for up to 11kV 3C x 185 mm2
21 size XLPE cables as per DGVCL technical specification. NO
Supply & fixing of heat shrinkable straight through jolnt for up to 22 kV 3C x 185 mm2
22 size XLPE cables as per DGVCL technical specification. NO
Labour charge for excavation of 2100mm long x 1200mm wide x 1200 mm deep jointpits for installation
of 11kV / 22kV Straight through joints as per instruction of engineer-in-charge & covering the cable
with 150 mm dia (Outer), thickness 25 mm,1.0 meter long RCC half round muffs & refilling same as per
instruction of EIC
Providing and fixing of insulating bus bar made from llKV/22KV XLPE cable after removal of semi
conducting layer and applying of PVC heat shrinkable anti- tracking core insulating tubing (1.1KV),
on both end terminal using Aluminium long barrel heavy duty up to 240 sq mm lugs, Aluminium bus
24 connector. Taping with PG- clamp for bus conductor as per drawing and as per instruction of Ere. The NO
Alluminiumlugs and PG clamp shall be covered with 11 KV/22KV HT insulating tapes.(l1KV/22KV XLPE
cable will be in scope of DGVCL while all othes materials will be in bidder's scope
Testing of cable at various points and commissioning the feeder as per instruction
25 of engineer-in-charge.Test result shall be submitted by contractor with bill. NO
Preparation and submission of 6 (six) copies, of complete layout drawings with
GIS mapping as per actual cable routing showing road crossing, HOPEpipe sleeving,
jointing locations, markers etc
Providing and fixing of Sign Board at junction point Made out of 2 mm aluminium sheet size 750x300
mm (2.5 x 1ft) rectangle as per design , pretreated with phosphate process and acid etching coated
with one coat of epoxy primer and two coat best quality paints ,reflectorised with high intensity retro-
27 reflective sheeting as per the latest and frame fabricated from suitable size iron angle .The sign board is to NO
be fixed on the base prepare from channel and bracing angle which is grounted by means of cement
concreting of 1:2:4 for size of 300 mm Dia * 800 mm height (500 mm to be grouted in ground ).The Details
to be displayed on sign board will be given by engineer incharge. (a) Hi intensity prismatic grade
Providing and fixing of Sign Board (Danger Board) on Distribution transformer center made out of
mm alluminium sheet size 300*300 mm(1*1 ft) as per design pretreated with phosphate process and acid
etching coated with one coat of epoxy primer and two coat best quality paints reflectorised with high
intensity retro-reflective sheeting as per the latest and frame fabricated from suitable size iron angle .The
sign board(Danger Board) is to be fixed at the location as per instruction of Engineer in Charge(a) Hi
intensity prismatic grade
Provide and fixing of alluminium tag of size 250mm (L) x75 mm (W) (3mm Al Sheet) along with 1.0mm dia
29 Al binding wire for fixing tag near end terminations joints at DP structure for identifying cable. The feeder NO
name details should be punched on the tag by letter punch (16mm Size) as per EIC
Supply & fixing of heat shrink type end terminations (outdoor) for 11kV 3C x 240 mm2 size XLPE cable.
(Using approved make outdoor type cable kit as per DGVCL technical specification)
Supply & fixing of heat shrink type end terminations (outdoor) for 22 kV 3C x 240 mm2 size XLPE cable.
(Using approved make outdoor type cable kit as per DGVCL technical specification)
Supply & fixing of heat shrink type end terminations (indoor) for 11kV 3C x 240 mm2 size XLPE cable.
(Using approved make outdoor type cable kit as per DGVCL technical specification)
Supply & fixing of heat shrink type end terminations (indoor) for 22 kV 3C x 240 mm2 size XLPE cable.
(Using approved make outdoor type cable kit as per DGVCL technical specification)
Supply & fixing of heat shrinkable straight through joint for up to 11kV 3C x 240 mm2
34 size XLPE cables as per DGVCL technical specification. NO
Supply & fixing of heat shrinkable straight through jolnt for up to 22 kV 3C x 240 mm2
35 size XLPE cables as per DGVCL technical specification. NO
36 Laying of any size of 11/22 KV XLPE Cable in readymade trench or in open space
37 Laying Charge of overhead HT XLPE cable(Including hydra charges) per meter
All the rates are including of P.F & Work Contract Tax and Excluding of GST applicable time to time
NOTE :- Original terms and condition of reference circular bound to agency for all works.
Special Note :- The Bidder must have minimum 2 fault locator machine in order to attend the UG Cable
faults simultaneously at different locations if required so as to minimize interruption period and revenue Executive ENGINEER (O&M)
loss incurred therein.
RAJPIPLA DIVISION OFFICE
REFERENCE CIRCULAR
1) ALL RATES ARE TAKEN FROM COST DATA CIR.NO: DGCS/1197/06/2023 Dt. 26-06-2023 and UG Cable
Revised as per Letter No DGCS/1411/01/2025 Dt: 27-01-2025
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
1. Bid Document.pdf
2 E schedule A.pdf
2.Tender Copy with terms condition tech specifications.pdf
UG New Schedule B.pdf
Download all tender documents and submit your bid