| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹34.1 LAccepted-AOC VIKRAM COACHING GALI SUDAMA NAGARI MADI NATH BAREILLY 243001 | BAREILLY | UTTAR PRADESH | 243001 | L1 | Accepted-AOC Accepted | |
| 2 | L2₹37.0 L+₹1.4 L (3.92%)Rejected-Finance | L2 | Rejected-Finance Being L1 | |
| 3 | L3₹39.4 L+₹3.8 L (10.7%)Rejected-Finance | L3 | Rejected-Finance High Bid | |
| 4 | L4₹46.7 L+₹11.1 L (31.3%)Rejected-Finance 303 GHS 888 SECTOR 20 PANCHKULA 134116 HARYANA | PANCHKULA | PANCHKULA | HARYANA | 134116 | L4 | Rejected-Finance High Bid |
Tender Value
₹43.8 L
EMD Value
₹87,560
Closing Date
2 Jul 2024, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
CWE Office BAREILLY
HQ, CWE, MES, Station Road, Bareilly
CA NO.CWE BLY/GE (W) /13 OF 2024- 2025UPGRADATION OF HT INFRA OF FEEDER NO 2 OF EAST AREA UNDER GE (WEST) BAREILLY
2024_MES_657389_1
8100/B/805/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE (West) Bareilly
As per NIT
6 documents required · 6 mandatory
₹500
GE (West) Bareilly
₹87,560
Yes
31 Aug 2024
3 Jun 2024
4 Jul 2024
3 Jun 2024
2 Jul 2024
18 Jun 2024
Amount
Supply, Installation, testing and commisssioning of 11 KV SCADA Compatible of 11 KV 630Amps 21 KA for 3 second of SF 6 insulated ring main unit (RMU) 4 way consist of motorised 3 load break switch and 01 (one) No. VCB suitable size replaceable bushing complete all specified and as directed.
Supply , Installation, testing and commissioning of 11 KV SCADA Compatible of 11 KV 630 Amps 21 KA for 3 second of SF 6 insulated ring main unit (RMU) 3 way consist of motorised 2 load break switch and 01 (One) No. VCB suitable size replaceable bushing complete all specified and as directed. Make-ABB/Seimens/Crompton/Schneider
M&L for dismentling of 4/2 Pole HT Stucture from ground level including opening of existing cable connection from GOD/Jumper opening of insulater, I.A Angle iron fram complete with making good of disturebd surface and connectiong the HT Cable with RMU complete all as specified and as directed.
M&L for foundation for RMU with bricks masonary work including plastering whitel wash of the same upto 0.60 mtr from ground level including provn of a step infront of RMU on openable side with brick masonary, plastering and white wash up to height of RMU botton , width 0.45 Cm and length equal to the RMU width for operating of RMU nad surrounding area fenced with chain link fencing duply supported with MS work i.e angle iron 50x50x6 mm and braced with flate iron 25x25x6mm including provn of opening gate with same material with locking arragement and brick work with flate iron 25x25x6mm including provn of opening gate with same material with locking arragement and brick work with plastering and white wash around the fencing with height 0.30 cm from GL and height of fence should be up to RMU height complete all as specified and as directed.
M&Lfor earhing complete with galvanised or steel plate electrode of size 60cmx60cmx6mm thick burried directly in ground vertically (to a depth not less 2.25mtr deep below morma ground level) with top edge of the plate not less than 1.5 mtr below normal ground level connected to strip 32x6 mm size with nuts , bolts, check nuts, washers, earth plate surrounding by packed layers of charcoal dust and common salt 15cm thick all around top & bottom watering pipe 20mm bore of GI medium grade with funnel and wiremesh all as shown in electrical plate No. 5 of SSR-2010 Part I and connecting to arthing test point main switch board and testing on completion including PCC chamber concrete 1:3:6 type C-2 and RCC Cover 75mm thcik with MS TMT bar 8mm dia @150mm c/c both ways in cement concrete (1:2:4) type B-1 all as shown in electrical plate in No.3 of SSR Part -I 2010 complete all as specified and as directed.
Supply and fixing testing and commissioning of heat shrink end jointing kit suitable for HT Cable of size up to 120 Sqmm, XLPE insulated PVC Sheathed armoured 11000 Volts Grade complete all as specified and as directed.
M/S HINA ELECTRICALS
VINYAK TRADERS
R D Bansal
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .